Home

62-0396 H20 Series (Class 200) MeterKWH & KWH

image

Contents

1. O N Or 62 0396 02 2 H20 SERIES CLASS 200 METER 1 0 PRE INSTALLATION INFORMATION The Honeywell H20 Series kWh Demand meter is a 3 element meter used to monitor electric power usage of individual loads after the utility meter Installation must only be performed by qualified personnel and in accordance with these instructions and all applicable local and national electrical codes Honeywell nor its representatives assume no responsibility for damages or injury resulting from the improper installation of this meter Meters are supplied in a UL Type 1 steel enclosure appropriate for indoor installation where it will not be affected by the elements such as moisture and extreme temperatures Units designated by the R suffix on the model number have an extended environmental operating range and are enclosed in a UL Type 4X equivalent to NEMA 4X enclosure to accommodate outdoor environments Verify the input voltage rating and configuration on the meter label to ensure it is suitable for the intended electrical services H20 Series meters labeled for 120 208V service MUST NOT be installed on service feeds of 277 480V and vice versa Verify the current sensors are sized suitably for the load to be monitored Compare the color of the arrows on the current sensors to the chart below to confirm the correct Current sensor is being used Sensor Arrow Color Code Sensor Rating 100 Amp Yellow 400 Amp 1600 Amp Whi
2. 5 x 2 10 kWh actual usage NOTE One set of current sensors equates to three sensors one per phase The multiplier only applies when extra sets of current sensors are installed on one meter Therefore if you are using only one set of three sensors one per phase the multiplier is not required 62 0396 02 18 H20 SERIES CLASS 200 METER LINE VOLTAGE CURRENT SENSORS QA OAOB OC PE WB WB WB N LOAD SOURCE LOAD B M33187 Fig 14 Multiple Loads with one Meter 19 62 0396 02 H20 SERIES CLASS 200 METER 6 0 KWH METER FEATURES amp FUNCTIONS 6 1 KWh Meter Display Features kHH 1 2 Fig 15 Normal Mode kWh Reading The H20 Series kWh meter display requires no multiplier and shows kilowatt hours consumed See section 6 2 for information on calculating cost based on kWh usage LOAD 2 5 Fig 16 KW Load Mode Current Load in kW The H20 Series kWh meter LOAD display shows the present circuit load in kilowatts CL 28080 1 8 8 E MON D MON Shey 100A Fig 17 Start Up Mode When initially powered on the H20 Series meter will display the startup screens This screen indicates the meter voltage amps and service configuration It will remain on for approximately five seconds before switching to the version screen after which the meter enters the normal operating mode 62 0396 02 20 H20 SERIES CLASS 200 METER 6 2 How to Read the kWh Meter a a
3. frayed or are shorting to adjacent terminal block positions H20 SERIES CLASS 200 METER 5 External Switch Mechanism In Line Fuse Installation a To ensure a Safe installation the H20 Series meter requires an external switch mechanism such as a circuit breaker be installed on the H20 Series MAINS input wiring The switch mechanism must be installed in close prox imity to the meter and easily reachable for the operator This device must also be marked as the disconnecting device for the H20 Series meter b Install 1 10 Amp Slow Activation in line fuses with the suitable voltage rating for each conductor phase at the MAINS input to the meter The fuses must be labeled to indicate voltage and current rating as well as element charac teristics The fuse element must be slow activating type 6 Once the MAINS wiring is complete replace the clear Lexan protective shield over terminal block TB1 and close the enclosure front panel Secure the enclo sure cover using the locking mechanism Activate the external circuit breaker or equivalent switch to apply AC MAINS power to the unit 7 The H20 Series meter display should turn on and indicate total kWh accumula tion reading NOTE On demand meters the unit display clock and other critical configuration parameters will be reset once the unit installation and wiring is complete Using an AC Voltmeter verify the input voltage readings are within the limits specified below Meter Input Volta
4. 1 PTr 35 Wraps Passes 5 35 x 80 5 35 x 16 560 EE METER MULTIPLIER PTr x CTr Wraps 37 62 0396 02 H20 SERIES CLASS 200 METER 12 0 FREQUENTLY ASKED QUESTIONS Q When providing line voltage to the meter can tap off of the same breaker am monitoring A Yes the voltage can be pulled from the same breaker being monitored Q Can the meter s line voltage wires be run in the same conduit as the sensor leads A Yes there will be no effect on the meter if the sensor leads and line voltage wires are run in the same conduit Q Can the meter communication wires and line voltage wires be run in the same conduit A It is NOT recommended to run these wires together due to noise concerns and their effects on the communications signal integrity Communication wires can be routed separately using the 1 2 conduit port Q How do find the cost for kWh and kW to bill my tenants A Your local utility bill should list the cost per kWh and kW If not simply call your utility and ask them to provide you with the cost per KWh and kW Q What size wire do use for the line voltage leads A These wires are normally 14 AWG but be sure to consult your local electrical codes for proper sizing requirements Q What size wire should use to extend the current sensor leads A These wires are normally sized at 14 22 AWG twisted pair arrangement Consult your local electrical codes for proper sizing re
5. This secondary is connected to the Honeywell meter voltage inputs as shown in the wiring diagram High voltage CTs reduce the primary current amps to a directly proportional 0 5 amp output As an example a 0 400 amp primary becomes a 0 5 amp proportional signal from the secondary output This allows much smaller wiring to be utilized in the meter hookup The high voltage CT secondary is installed as a continuous loop with a single lead connected to both secondary terminals Honeywell meters accept a 0 2 volt signal from their Current Sensors To convert the 0 5 amp signal the Current Sensors are installed on the CT secondary lead A set of 25 amp sensors is used in this application These sensors have the high voltage CT secondary lead passed through them five 5 times by looping the wire as shown in the drawing This allows a direct conversion of the CTs primary current to a directly proportional 0 2 volt signal which is used by the meter Since there is a signal ratio introduced by the high voltage CTs and PTs it will be necessary to multiply the number on the meter s display for a correct reading The meter multiplier is calculated by using the CT ratio and the PT Ratio PTr x CTr Number of Secondary Lead Passes Through Sensor The Honeywell 25 amp HV kWh meter with 5 wraps of the high voltage CT secondary will have its multiplier calculated by the formula shown below EXAMPLE 400 5 80 1 CTr 80 PT 4200 120 35
6. detailed troubleshooting of the meter installation and will assist you in getting the unit operating correctly 62 0396 02 32 H20 SERIES CLASS 200 METER 10 1 Line Voltage Diagnostics Honeywell meters detect the direction of rotation of three phase power The proper phase sequence must be A B C The AC power input must be in proper phase sequence A B C If incorrect the display will read Check Install See figure below Fig 27 Check Install Error STEP 1 VERIFY amp RESOLVE A PHASE SEQUENCE ERROR 1 Have the electrician unplug or disconnect all three current sensors at the current sensor input 2 If the meter display Check Install Error without any sensors connected the utility power supply connection is out of expected sequence 3 Disconnect the power to the meter line voltage inputs Swap A amp C line inputs Swap A amp C line inputs Power up the meter and verify there is not a Check Install error on the LCD NOTE If line voltage phase sequence was corrected sensors must be adjusted accordingly 33 62 0396 02 H20 SERIES CLASS 200 METER 10 2 Current Sensor Diagnostics NOTE Light Load or No Load May Cause Check Install Error to be Displayed The meter must have at least 1 load for each current sensor For example model number H20 208200KIT is 200 amp rated each current sensor must have at least two amps flowing though it to verify installation If the error goes away w
7. 1 3 Fig 23 KW Demand Reading The kW Demand reading is the peak usage over a specified time period 15 minute standard 30 minute optional While kWh costs are interpreted as cents Kilowatt costs are usually represented in dollars and interpretation of demand costs are based on your utility s tariff and rate structures You will need to contact your utility to see how your utility structures their kilowatt demand charges to ensure proper allocation of costs utilizing data from the Honeywell meter NOTE THE FOLLOWING ONLY APPLIES TO METERS USING MORE THAN ONE SET OF CURRENT SENSORS For meters using parallel current sensors you must multiply the kWh display reading by the number of sets of current sensors installed With Demand meters the PEAK Demand is also multiplied by the number of sets of current sensors installed Example 17 meter display reading x 2 sets of sensors in parallel 34 kWh 34 kWh x 0 121 utility cost per kWh 4 12 25 62 0396 02 H20 SERIES CLASS 200 METER 7 3 Demand Display Set Up OUO DOWN M33207 The demand meter display is set up using the four buttons located on the meter display board which is mounted on the door inside the meter enclosure STEP 2 Press the DOWN button to enter the setup screen SETUP DRTE 4112711711 STEP 3 Press the ENTER button to enter the DATE screen SETUP DRTE 11 1111 STEP 4 Press the Enter button to cycle between the day mo
8. 5 VDC Logic Levels Rating 100mA Time delay 600VAC Cartridge Fuse Battery Cell Description Non rechargeable Cell Used For Memory Retention 62 0396 02 42 H20 SERIES CLASS 200 METER 14 0 METER LIMITED WARRANTY Subject to the exclusions listed below Honeywell will either repair or replace at its option any product that it manufactures and which contains a defect in material or workmanship The following exclusions apply 1 This Limited Warranty is only effective for a period of 5 five years following the date of manufacture when installed in accordance with manufacturer s instruc tions by qualified personnel 2 Honeywell must be notified of the defect within ninety 90 days after the defect becomes apparent or known 3 Buyer s remedies shall be limited to repair or replacement of the product or com ponent which failed to conform to Honeywell s express warranty set forth above 4 Buyer shall be responsible for all freight costs and shall bear all risk of loss or damage to returned goods while in transit 5 This Limited Warranty does not cover installation removal reinstallation or labor costs and excludes normal wear and tear Buyer shall provide labor for the removal of the defective component or item and installation of its replacement at no charge to Honeywell 6 This Limited Warranty does not cover any product if i a product is altered or modified from its original manufactured condition ii
9. Honeywell H20 Series Class 200 Meter KWH amp KWH DEMAND METER INSTALLATION INSTRUCTIONS Honeywell E e 62 0396 02 H20 SERIES CLASS 200 METER TABLE OF CONTENTS x Section 4 4 MAINS Line Voltage amp Current Sensor Wiring Diagrams Section 4 5 Line Voltage Current Sensor Diagnostics Section 4 6 Final Main Board Checks Monitoring Multiple Loads with One Meter Section 6 0 KWh Meter Features amp Functions Section 6 1 KWh Meter Display Features 1 Section 6 2 How to Read the kWh Meter Section 6 3 KWh Meter Hardware Functions Section 6 4 H2O Pulse Output Removable Two Screw 18 Terminal Plug Section 7 0 KWh Demand Meter Features amp Functions Section 7 1 KWh Demand Meter Display Functions Section 7 2 How to Read the kwh Demand Meter Section 7 3 Demand Display Set Up Section 7 4 Demand Reset Section 8 0 Preventative Scheduled Maintenance Section 9 0 Lithium Battery Replacement Instructions Section 10 0 Troubleshooting Guide Section 10 1 Line Voltage Diagnostics Section 10 2 Current Sensor Diagnostics Section 11 0 High Voltage Metering Section 12 0 Frequently Asked Questions Section 13 0 Meter Technical Specifications Section 14 0 Meter Limited Warranty Applies to meters equipped with the Demand option CD WM CD D S OD O D ct ets O O O gt zu 2 C1 O e O O O i t cee ON OI
10. PURPOSE PRODUCTS OR COMPONENTS DISTRIB UTED BUT NOT MANUFACTURED BY HONEYWELL ARE NOT WARRANTED BY HONEYWELL AND BUYER MUST INSTEAD RELY ON THE REPRESENTATIONS AND WARRANTIES IF ANY PROVIDED DIRECTLY TO THE BUYER BY THE MANUFACTURER OF SUCH PRODUCT OR COMPONENT 43 62 0396 02 H20 SERIES CLASS 200 METER Automation and Control Solutions Honeywell International Inc Honeywell 1985 Douglas Drive North U S Registered Trademark Golden Valley MN 95422 2013 Honeywell International Inc customer honeywell com 62 0396 02 JPG Rev 03 13 Printed in United States
11. R STEP 2 Use the UP and DOWN buttons to access the CHECKOUT screen CL 2888 T4 CHECKOUT STEP 3 Press the ENTER button to access the kw RESET screen CHECKOUT kH RESET YES STEP 4 Press ENTER to access the RESET select screen Use the UP and DOWN buttons to select yes or no Press ENTER to save the selection Change stored will be displayed after pressing ENTER LL 20808 MENU STEP 5 Press the HOME button to return to the menu screens Use UP and Down to select the MENU screen iz HH 7 STEP 6 Press ENTER to return to the normal display 8 0 PREVENTATIVE SCHEDULED MAINTENANCE The H2O kWh Demand meter is shipped in a calibrated tested and fully functional condition No field adjustments are required No preventative or scheduled maintenance is required No cleaning or decontamination procedures are required for this instrument 29 62 0396 02 H20 SERIES CLASS 200 METER 9 0 LITHIUM BATTERY REPLACEMENT INSTRUCTIONS The H2O kWh Demand meter has a Lithium Battery Cell which is used to retain the contents of SRAM and the RTC during power outages The battery has a life expectancy of greater than 5 years M33208 Fig 24 Battery Location Nominal Working Voltage 3 Vdc Output Nominal Current Capacity 225 mAHr Cell Chemical Manganese Dioxide Lithium Operating Temperature Range 30 to 60 Degrees Celsius Manufacturer s Part Number CR2032 Fig 25 Battery Specifi
12. R Temperature Range 20 C 70 C UL Type 4X equivalent to NEMA 4X Relative Humidity 0 95 Non condensing Range Altitude 200 Meters Maximum Voltage Overload 25 Continuously 100 For 20 Cycles Current Sensor 100 For 1 Minute Without Damaging Meter Overload Pollution Degree Degree 2 In Accordance With IEC 664 Installation Category 111 Overvoltage Category Measurement Category 111 Category Enclosure Material Indoor Housing Rating Standard Type 1 Outdoor Housing Rating Optional UL Type 4X equivalent to NEMA 4X Display Readout KWh Accumulated Standard Ranges 4 Wire Wye 120 208 VAC 100 200 400 800 1600 3200 Amp 2 Phase 120 240 VAC 100 200 400 800 1600 3200 Amp 4 Wire Wye 277 480 VAC 100 200 400 800 1600 3200 Amp 3 Wire Delta 220 240 VAC 100 200 400 800 1600 3200 Amp 3 Wire Delta 480 VAC 100 200 400 800 1600 3200 Amp Modem Interface UL listed Telephone Cord 6 cond 300 VAC Stranded Cond 22 26 AWG Cable Connector RJ 45 male IDC Input Output Voltage 5 VDC 18 VAC Ckt Input Isolation 5 3K VAC for 1 Minute Baud Rate 9600 41 62 0396 02 H20 SERIES CLASS 200 METER IDR Interface Port Cable UL listed rated Telephone Cord 4 cond Input output Voltage Ground isolated 5 4VDC Cable Connector RF 45 Male IDC Or Screw Terminal Termination 5 3kVAC Circuit output Isolation 21 5kVAC Isolated Pulse Alarm Outputs TB5 TB6 Output Voltage Potential 0 VDC to
13. TER SINGLE PHASE 3 WIRE CONNECTION 120 208 240 VOLT SINGLE PHASE NOTES LINE VOLTAGE CURRENT SENSORS A B LINE VOLTAGE CONNECTION 14 AWG OA B OC N PE SENSOR CONNECTION BLACK W WHITE IMPORTANT LINE VOLTAGE MUST BE PRESENT AT THE A AND B PHASE VOLTAGE TERMINALS SHORTING LINK MUST BE INSTALLED ON C PHASE CURRENT SENSOR TERMINALS N 1 10 AMP INLINE FUSES RECOMMENDED SOURCE M34223 Fig 9 Single Phase 3 Wire Installation Diagram 4 5 nstallation Overview CURRENT SENSOR AND VOLTAGE CONNECTIONS M34224 Fig 10 Install Overview 15 62 0396 02 H20 SERIES CLASS 200 METER 4 6 Check Polarity of the Current Sensor Verify all phases are loaded by at least 1 of meter rated load and check the polarity of the sensors Test the sensors wires one pair at a time verifying polarity phase rotation and correspondence to line input Safety guards must be in place CAUTION High voltage extra care must be taken Fig 11 Sensor Polarity When current sensor is installed properly error LED is off If the Error LED is illuminated then disconnect the gray plug and reverse the input lead If it clears the Sensor Error then mark appropriately Repeat for all sensors Fig 12 Error LED 62 0396 02 16 H20 SERIES CLASS 200 METER Repeat the process for the C sensor gray plug With only the C sensor plug connected if the sensor error remains clear then the C sensor input and
14. andard split core units however the conductors that they are monitoring must first be disconnected NOTE Under circumstances is this operation to take place without shutting off the power to the conductor s being monitored With the power off disconnect the conductor from its breaker or terminal Slide the solid core current sensor over the conductor making sure that the indicator on the sensor is pointing in the direction of the load After this is done reconnect the conductor and verify that it is properly installed Run the black and white wires from the solid core current sensors and install them according to the standard installation diagram When this is completed the power to the monitored conductor can be turned back on Fig 6 Solid core Current Sensor 62 0396 02 12 H20 SERIES CLASS 200 METER 4 3 2 Current Sensor Wiring Once all the current sensors are installed on their appropriate phase conductors you can begin terminating the current sensors on to the H20 Series main power board The current sensor leads can be extended up to 2 000 feet using 14 22 AWG wire for remote monitoring applications Consult your local electrical codes for proper wire sizing 22 AWG twisted pair wire with a black and white conductor rated for 600 VAC recommended The current sensor connection points are located on the bottom right of the main power board Three removable plugs exist one for each current sensor phase inp
15. any repairs alterations or other work has been performed by Buyer or others on such item other than work performed with Honeywell s authorization and according to its approved proce dures iii the alleged defect is a result of abuse misuse improper maintenance improper installation accident or the negligence of any party iv damaged as a result of events beyond Honeywell s control or other force majeure events or v used in conjunction with equipment components accessories parts or materi als not supplied or approved by Honeywell 7 This Limited Warranty is limited to the obligation to repair or replace the manu factured product This is the sole and exclusive remedy for any breach of war ranty INNO EVENT SHALL HONEYWELL BE LIABLE FOR ANY INDIRECT INCIDENTAL SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES INCLUD ING ANY DAMAGE FOR LOST PROFITS ARISING OUT OF OR IN CONNECTION WITH THE FURNISHING OF PRODUCTS PARTS OR SERVICES OR THE PER FORMANCE USE OF OR INABILITY TO USE ANY PRODUCTS PARTS OR SER VICES SALE OF OR OTHERWISE WHETHER BASED IN CONTRACT WARRANTY TORT INCLUDING WITHOUT LIMITATION NEGLIGENCE OR ANY OTHER LEGAL OR EQUITABLE THEORY 8 EXCEPT AS EXPRESSLY PROVIDED HEREIN HONEYWELL MAKES NO WAR RANTY OF ANY KIND EXPRESS OR IMPLIED WITH RESPECT TO ANY PROD UCTS PARTS OR SERVICES PROVIDED BY HONEYWELL INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FIT NESS FOR A PARTICULAR
16. cations at 25 Degrees Celsius 62 0396 02 30 H20 SERIES CLASS 200 METER A WARNING Only replace battery with Panasonic part number CR2032 only Use of another battery may present a risk or explosion See owners manual for safety instructions Internal circuit card components are extremely sensitive to electrostatic discharge Be careful not to touch internal circuitry prior to discharging any static buildup on your person To discharge yourself touch a grounded metal object such as conduit or a metal enclosure exterior The battery cell is mounted in a coin cell on the upper right side of the main power board Replace the battery if the low battery warning is on display k HH 8808881 7 LOM BATTERY gt Fig 26 Low Battery Display Use the following procedure to replace the battery cell STEP 1 Disconnect power from the meter at the unit external circuit breaker STEP 2 Remove the battery from its holder and place on a non conductive surface STEP 3 Install new battery into the battery holder NOTE Care should be taken to insure that the replacement battery is installed the same polarity as the battery that was removed No damage to unit or battery will occur if battery is inadvertently installed in the wrong direction STEP 4 Dispose of the used battery in accordance with the manufacturers Panasonic instructions 31 62 0396 02 H20 SERIES CLASS 200 METER 10 0 TROUBLESHOOTING GUIDE The H20 Series kWh Demand met
17. ed below KWh display shows the amount of energy 1 consumed in kilowatt hours kWh Reading is E in whole numbers there are no decimals and the meter requires no multipliers IZ A LOAD KH LOAD display shows the present circuit load in kilowatts KW display shows the electrical PERK 11 3 kH cad Demand in kilowatts KW Demand interval is either 15 minutes or 30 minutes Default is 15 minutes PR TIME Bi dcBHHM Time display shows the time of the day that the demand peak occurred Date display shows the date of the demand DATE aGi gi ii Y KW peak Fig 21 KWh Demand Meter Display Functions 62 0396 02 24 H20 SERIES CLASS 200 METER 7 2 How to Read the kWh Demand Meter k HH 1 Fig 22 KWh Reading The H20 Series kWh meter displays readings in whole numbers there are no decimals To find the dollar cost for the power used by the load s being monitored you must first find out what the cost per kWh is in your area this cost can be found on your utility electric bill or call your local utility and ask for their cost per kilowatt hour Simply multiply the cost per kWh by the kWh reading from the Honeywell meter The resultant figure is the dollar cost for power used by the load s being monitored by this meter Example 8 digit display reading 00000017 Cost per kWh from utility 0 12100 17 x 0 121 2 06 1
18. er is calibrated and tested at the factory before being packaged and shipped If installed properly and in accordance with these installation instructions your H20 Series meter should provide years of trouble free service If the meter should not function the following guide will assist in troubleshooting the installation 1 Display window is blank 2 Display shows incomplete figures or Press RESET button located on door numbers other than zeros when power is meter enclosure 5 sec turned on 3 Display reading all zeros 00000000 Determine if load is sufficient to update the display Check RESET button to ensure there are no wires or other objects pressing against it when the door is closed Check the current sensors for installation and polarity Be sure the current and voltage inputs have the proper phase relationship Check wiring to voltage terminals Check circuit breaker or fuses Test source for correct voltage 4 Display reads only a fraction of Check the supply voltage to be sure that it consumption is on continuously 24 hrs day Check the current sensors for installation and polarity Check sensor wiring to the terminal strip in meter color coding B amp W NOTE f you still need assistance after performing the above troubleshooting proce dures do not remove the unit Before removing the unit contact Honeywell s technical support department and our support experts will assist you in
19. exception This exception is that the conduit and fittings for outdoor installa tions require an outdoor material rating and approval for 4X applications 4 Unit MAINS Wiring Voltage Wiring Connections a NOTE 62 0396 02 Remove the shield located over the phase A B and C screw terminals on the main power board This shield can be removed by pulling back on the latch on the right side of the shield and lifting up on the front Wire each connec tion to the terminal block with stranded wire 14 12 AWG rated at 600 VAC Strip back all wire insulation to expose between 1 4 and 3 8 of the copper conductors Gently twist each wire to prevent fraying Insert the conductors into their respective terminal block position and tighten down the terminal block screw to securely fasten the conductor The terminal block is clearly labeled PHASE A PHASE B PHASE C and NEUTRAL Connect the NEUTRAL wire to the appropriate terminal block position For Delta MAINS input wiring DO NOT connect the NEUTRAL wire Remove the terminal block screw for this position Connect the AC mains power wires Phase A Phase B and Phase C to their respective positions as labeled on terminal block Tighten the screws to 7 in lb of torque After all conductors are connected to their respective terminal block positions and tightened down verify that each terminal block screw is securely fas tened by gently tugging on each conductor Verify no conductor wires are
20. ge Configuration Nominal Voltage Limits 1096 120 208V 3 Ph 4 Wire 120 VAC L N 108 to 132 VAC 277 480V 3 Ph 4 Wire 277 VAC L N 249 to 305 VAC 240V 3 Ph 3 Wire 240 VAC L L 216 to 264 VAC L L 480V 3 Ph 3 Wire 480 VAC 432 to 528 VAC 347 600V 3 Ph 4 Wire 347 VAC L N 540 to 660 VAC 8 Remove power from the unit by de energizing the external switch NOTE For 3 Wire systems the voltages are measured Phase to Phase On 4 Wire systems the voltages are measured Phase to Neutral 9 62 0396 02 H20 SERIES CLASS 200 METER 4 3 Current Sensor Installation amp Wiring Once the AC voltages have been confirmed to be within acceptable limits you are ready to install the current sensors The MAIN power board contains three header connectors located at the bottom right of the board The connectors are labeled A B and C along with conductor color indication This format must be followed in order for the meter to function correctly The H20 Series meter will be used with Split Core Current Sensors The sensor opens so that it can be attached around the circuit conductor being monitored without interrupting power Unless otherwise specified all H20 Series meters are supplied with this sensor type The sensor outputs a 0 2 VAC signal proportional to the current being measured The current sensors must be matched with the voltage phases The A phase sensor must be monitoring the same phase as the A phase voltage B amp C p
21. hase Meter Pulse LED Blinks to show the meter load Blink rate increases with load Power On LED When lit indicates power to meter is on Pulse Output Optically isolated output pulse for connection to BAS or peripheral equipment 6 4 H20 Pulse Output Removable Two Screw Terminal Plug PULSE VALUE GUIDE FOR H20 KWH amp OR KW DEMAND METER Color Code Key of Sensor Arrow Must Match the Amperage of Meter Purple White Brown Red Yellow Black Blue Two Blue Watt Hours per Pulse Pulse output signal is a 50 50 duty cycle There is no voltage present at the pulse output connection It is a solid state relay and there is no polarity associated with the relay The interface range is from 4 5 to 28 VDC with a maximum of 50 mA 62 0396 02 22 MAIN POWER TERMINAL BLOCK H20 SERIES CLASS 200 METER PULSE OUTPUT CALIBRATION IDR JACK JACK DESCRIPTION ABOVE POWER ON LED METER PULSE LED ERROR LED HEADER CONNECTOR CURRENT SENSORS M33212 Fig 19 Hardware Functions MENU UP DOWN SELECT M33183 Fig 20 Hardware Functions 23 62 0396 02 H20 SERIES CLASS 200 METER 7 0 KWH DEMAND METER FEATURES amp FUNCTIONS Applies to meters equipped with the Demand Option 7 1 KWh Demand Meter Display Functions The H20 Series kWh Demand meter has a single display window that cycles through the energy data screens The meter will cycle through four 4 separate screens The screens are describ
22. hase sensors must also monitor the same phase as their respective voltage inputs 4 3 1 Installing the Split Core Current Sensor Assembly Each phase being monitored will require one two piece current sensor assembly Therefore a three phase meter will require three 3 assemblies Open the two piece current sensor assembly by releasing the nylon clamp using a flat head screwdriver Fig 4 Split Core Current Sensor Assembly 1 Reassemble the current sensor assembly around the conductor s to be moni tored Ensure the current sensor halves marked Load are both facing the load side of the conductor The colored arrow will be on the source side of the con 62 0396 02 10 H20 SERIES CLASS 200 METER ductor being monitored and MUST be pointed in a clockwise direction around the conductor being monitored Tighten the nylon clamp to complete the assembly SOURCE M33213 Fig 5 Arrow On The Current Sensor Assembly IMPORTANT When looking trom the source side of the conductor s being monitored you should see the arrow on the current sensor assembly The arrow should be pointing in a clockwise direction around the conductor s being monitored the arrow is not positioned on the source side inaccurate readings will result 11 62 0396 02 H20 SERIES CLASS 200 METER 4 3 2 Installing the Solid Core Current Sensor Assembly The optional solid core current sensors can be installed in the same applications as the st
23. indoor or outdoor applications within the defined specifica tions Refer to Section 12 0 for a definition of suitable environmental condi tions for indoor and outdoor units 62 0396 02 4 H20 SERIES CLASS 200 METER 1 1 1 Main Power Board Connections to this board include the MAINS Input Voltage Current Sensors external IDR interface and Isolated Pulse Output The MAINS input terminals are covered with a protective shield for safety purposes The current sensor assemblies interface to three header connectors labeled A B and C along with conductor color indication Each header connector input corresponds to an input voltage phase so care must be taken to ensure each current sensor is connected to the correct input header TB1 TB2 TB3 TB4 M33178 Fig 2 Standard Configuration 1 1 2 Display Board The display connects to the main power board via a flex ribbon cable and is mounted on the inside of the enclosure door The LCD readout indicates the cumulative kWh and instantaneous kW value on kWh meters The LCD readout indicates cumulative kWh peak demand and instantaneous kW values on kWh Demand meters 2 0 SAFETY LABEL DEFINITIONS AND INFORMATION The H2O meter may contain one or more of the following labels Operator s should familiarize themselves with the meaning of each label to minimize risk The presence of this label is a cautionary indicator identifying a danger risk The manual should be consulted prior to p
24. ith 1 or more load then there is no issue with installation The error was due a light load this is normal and may go back on during light load conditions STEP 1 LINE VOLTAGE PHASE ROTATION MUST BE CORRECTED PRIOR TO CURRENT SENSOR DIAGNOSTICS SEE SECTION 10 1 Is the Current Sensor s clamped on backwards Assemble the current sensor halves around the conductor s to be monitored Ensure the current sensor halves marked Load Load Side shown with two arrows Figure 24 below are both facing the load side of the conductor The load is the side of the conductor where the equipment you are monitoring is located WARNING If removal of the split core Current Sensor is necessary DO NOT Cut the Tie Wrap The head of the cable tie has a release tab Push down on the tab to release How do I know line from load Generally speaking line is the power coming in or upstream to a circuit breaker fuse disconnect etc Load is the power going out downstream of the device that interrupts power Fig 28 Load Side 62 0396 02 34 H20 SERIES CLASS 200 METER 11 0 HIGH VOLTAGE METERING kWh Meter Installation Instructions for Use with Honeywell Meters in High Voltage Applications The Honeywell model 12025HV kWh meter is designed to be used for monitoring high voltage 2400 4160 13200 etc circuits either stand alone or in an AMR application This meter is intended to be used with the appropria
25. moving the unit contact Honeywell s technical support department and our experts will assist you in detailed troubleshooting of the meter installation and assist you in getting the meter functional without having to remove and return the unit 39 62 0396 02 H20 SERIES CLASS 200 METER 13 0 METER TECHNICAL SPECIFICATIONS Ordering Information Define brand class input voltage current sensor amperage enclosure type and sensor type in the format A B CCC DDD E FFF where A Brand H for Honeywell B 20 for H20 Series CCC Input Voltage 208 480 or 600 DDD Amperage 100 200 400 800 1600 3200 E Enclosure Type J standard metal R outdoor UL Type 4X equivalent to NEMA 4X FFF Current Sensors included KIT 3 sensors included Blank None supplied H 20 208 200 J KIT HONEYWELL CLASS 200 METER INPUT VOLTAGE 208V AMPERAGE ENCLOSURE TYPE STANDARD METAL 3 SENSORS INCLUDED SPLIT CORE M33215 Input Voltage 3 wire Delta Or 4 wire Wye Configuration Mains Voltage Input Up To 480 VAC RMS Available Input Power 6 VA Maximum Rating Current Sensor Up To 3200 Amps RMS AC Available Rating 0 5 Leading Or Lagging Line Frequency 50 60 Hz Metering Accuracy Certified To ANSI C12 16 From 1 100 Of Rated Load Voltage Operating 10 Of Rated Load Range Temperature Range 20 C To 50 C Standard indoor enclosure 62 0396 02 40 H20 SERIES CLASS 200 METE
26. nang Fig 18 Readings are displayed in whole numbers The H20 Series kWh meter displays readings in whole numbers there are no decimals To find the dollar cost for the power used by the load s being monitored you must first find out what the cost per kWh is in your area this cost can be found on your utility electric bill or call your local utility and ask for their cost per kilowatt hour Simply multiply the cost per kWh by the kWh reading from the H20 Series meter The resultant figure is the dollar cost for power used by the load s being monitored by this meter Example 8 digit display reading 00000017 Cost per kWh from utility 0 12100 17 x 0 121 2 06 NOTE THE FOLLOWING ONLY APPLIES TO METERS USING MORE THAN ONE SET OF CURRENT SENSORS For meters using parallel current sensors you must multiply the kWh display reading by the number of sets of current sensors installed Example 250 meter display reading x 2 sets of sensors in parallel 500 kWh 500 kWh x 0 121 utility cost per kWh 60 50 21 62 0396 02 H20 SERIES CLASS 200 METER 6 3 KWh Meter Hardware Functions IDR Jack 8 pin RJ 45 used to connect kWh meter to the Honeywell Energy automatic meter reading system Calibration Jack Connector J11 is for factory calibration only and is not a user accessible port Silicon plug is not to be removed Error LED When lit indicates that the current sensor is backwards or on the incorrect p
27. nth and year Press the UP and DOWN buttons to change their respective numbers CHANGE STORED STEP 5 When the numbers have been changed press ENTER again to save the changes 62 0396 02 26 H20 SERIES CLASS 200 METER STEP 6 Press the DOWN button to access the TIME screen SETUP T4 TIME Fr 83 18 PM STEP 7 Press ENTER to cycle between the hour minutes and day of week selection Use the UP and DOWN buttons to change the selection CHRHGE STORED STEP 8 When the changes are completed press the ENTER button to save the changes DEMAND INT 15min STEP 9 Press ENTER to enter the DEMAND INTERVAL screen DEMAND INT 15min STEP 10 Press ENTER again to access the interval selection screen Use the UP and DOWN buttons to select the appropriate interval time default is 15 min i i ul AGE STORED mt S STEP 11 When the appropriate demand interval has been chosen press ENTER to save the changes 27 62 0396 02 H20 SERIES CLASS 200 METER T SETUP STEP 12 Press the HOME button to return to the setup screen cLeaga 4 MENU STEP 13 Press the UP arrow to display the STATUS screen k HH Bal 1 7 STEP 14 Press the ENTER button to enter the normal display screen 7 4 Demand RESET LL 280808 MENLI STEP 1 Press the HOME button to access the Series H2O MENU screen CL 28008 CHECKOUT 62 0396 02 28 H20 SERIES CLASS 200 METE
28. perate the H20 Series meter without a protective earth ground connection securely installed 3 Wire Entry a Two openings exist on the unit enclosure one for 1 2 conduit and one for 3 4 conduit The 3 4 conduit opening located on the bottom of the enclosure is used to bring in MAINS Power voltage lines to power meter and current sensor wiring The 1 2 conduit opening located on the top of the enclosure is used to interface low voltage signals such as the IDR interface and iso lated pulse output Outdoor enclosures equipped with one 3 4 conduit opening on bottom of enclosure only Route the appropriate cabling to and through the respective enclosure open ing The conduit and fittings interfacing the enclosure entrances must be UL listed and properly sized to the enclosure port diameter The interfacing fit ting must use a gasket seal ring to interface between the conduit fitting and the enclosure entry point After installing the conduit fitting and conduit verify that the conduit fittings are aligned properly to their respective enclosure entrance ports and tightened securely to prevent moisture entry VERIFY that each conduit slip nut is securely tightened to its respective conduit fit ting Outdoor applications require the use of the optional 4X enclosure The same principles outlined for indoor meter installations as defined in the aforemen tioned paragraph carry over and apply to outdoor installations with one
29. quirements 62 0396 02 38 H20 SERIES CLASS 200 METER Q The load need to monitor has parallel feeds How do install the current sensors for this application A There are two ways you can monitor parallel feeds One method is to clamp the sensors around all feed wires for each phase no additional reading multiplier required The second way to monitor parallel feeds is to clamp the sensor around one of the feed wires for each phase and when you read the kWh meter the final reading must be multiplied by the number of feed wires for each phase Q have two subpanels would like to monitor with one meter These subpanels are fed by different transformers in the building Can parallel sensors and monitor both panels with one meter A No These panels cannot be monitored by one meter because they are different power sources When you parallel current sensors all loads must be from the same voltage source Q have 5 breakers in one subpanel would like to monitor with one meter Can this be done without having to parallel current sensors A Yes Simply run all the breaker wires through one set of current sensors Make sure all A phase circuits are run through the A phase sensor and the same for B amp C phases The meter should be sized by the highest amount of current being monitored by one sensor Q I ve gone through the troubleshooting guides and still can t get my meter to work What should do A Before re
30. roceeding The presence of this label indicates an electrical shock hazard exists in the location or area where the label is placed Prior to proceeding the MAINS power must be disconnected and the manual consulted for safety information 5 62 0396 02 H20 SERIES CLASS 200 METER 3 0 PRECAUTIONARY AND SAFETY INFORMATION N CAUTION Internal circuit card components are extremely sensitive to electrostatic discharge Be careful not to touch internal circuitry prior to discharging any static buildup on your person To discharge yourself touch a grounded metal object such as conduit or an earth grounded metal enclosure WARNING High voltages present on main PCB terminal block TB1 screw terminals Risk of serious injury and or electrical shock exists Prior to performing any wiring operations review all contents of the user manual and de energize the MAINS power switch Only qualified personnel should perform installation wiring Installation wiring must comply with all local and national electrical codes WARNING Failure to ground the enclosure creates a possible shock hazard Do not operate the H20 Series meter without a protective earth wire attached securely to the PE terminal screw After installing protective earth wiring secure the screw tightly 7in Ib torque WARNING NEVER open front panel of unit while unit has MAINS power applied Failure to comply can increase the risk of serious injury and or elec
31. te Black 3200 Amp 3 62 0396 02 H20 SERIES CLASS 200 METER N CAUTION Internal circuit card components are extremely sensitive to electrostatic discharge Prior to handling or touching internal circuitry discharge any static buildup on your person To discharge yourself touch a grounded metal object such as conduit or an earth grounded metal enclosure WARNING Use of this instrument in a manner inconsistent with this manual or not specified by the manufacturer in writing can cause permanent damage to the unit and or serious injury to the operator The protection and safety features provided by this equipment may become impaired or otherwise compromised NOTE If any trouble arises during installation or functional verification operations do not immediately remove unit Before removing the unit contact Honeywell s technical support department The technical department will assist you in detailed troubleshooting of the H20 Series installation 1 1 Internal Electronic Assemblies The unit is comprised of a Main Power Board Display Board and Keyboard All circuit cards are mounted inside a UL Type 1 standard or UL Type 4X optional enclosure MAIN POWER DISPLAY AND BOARD KEYBOARD M33177 Fig 1 Power Supply Board and Display Board NOTE Units are supplied in a UL Type 1 metal enclosure suitable for indoor applica tions only Units supplied in the optional UL Type 4X fiberglass enclosure are suitable for either
32. te high voltage Potential Transformers PTs and Current Transformers CTs supplied by others The meter application is centered around a 120 VAC secondary output from the high voltage PTs and a 5 amp secondary output from the high voltage CTs Items addressed by this document include the installation of the 12025HV meter on high voltage circuits as well as the calculations to provide the correct meter multiplier based on the PT and CT sizes used on the high voltage conductors Installation should be performed by qualified personnel and only according to all applicable electrical codes High Voltage CTs supplied by others reduce the primary current amps to a directly proportional 0 5 amp secondary output As an example a 0 400 amp primary becomes a 0 5 amp proportional signal from the secondary output In our application the high voltage CT secondary is installed as a continuous loop with a single conductor connected to both secondary terminals To convert the 0 5 amp signal to a 0 2 volt signal Honeywell s Current Sensors are installed on the CT secondary conductor A set of 25 amp sensors is used in this application These sensors have the high voltage CT secondary conductor passed through them five 5 times see below by looping the secondary conductor as shown in the drawing The reason for this is so that the 5 amp secondary now appears to the current sensor as a 0 25 amp signal This creates a conversion of the CT s primary c
33. the polarity is correct Fig 13 Error LED 17 62 0396 02 H20 SERIES CLASS 200 METER 5 0 MONITORING MULTIPLE LOADS WITH ONE METER The H20 Series meter provides extreme flexibility by allowing additional sets of current sensors to be used in parallel so that multiple load locations can be monitored by one meter This feature allows a totalized display readout from two or more load circuits You may use parallel sensors to monitor specific breakers from one panel specific breakers from more than one panel two or more complete panels etc When paralleling current sensors the following rules must be followed for accurate readings Rule 1 Current sensors must be installed in complete sets of three with a maximum of three sensors installed in parallel per phase Rule 2 All sensors used in parallel must be of the same amperage rating i e 100 amp 200 amp etc The rating is determined by the current rating amperage of the H20 Series meter For example a 200 amp meter must use extra sets of 200 amp current sensors Rule 3 All locations being monitored must have the same power source A 480 volt meter cannot monitor a 208 volt load nor can a meter monitor two 480 or 208 volt loads if they are from different originating power sources or from different transformers Rule 4 The display readings must be multiplied by the number of sets of current sensors installed E g meter reading of 5 kWh with 2 sets of current sensors
34. trical shock 62 0396 02 6 H20 SERIES CLASS 200 METER 4 0 METER INSTALLATION 4 1 Mounting the Meter Using the appropriate sized mounting hardware fasten the H20 Series meter enclosure to the selected mounting surface The four mounting holes are centered 6 75 H x 4 W The mounting hole spacing is identical for either the UL Type 1 or UL Type 4X enclosure NOTE Only the UL Type 4X enclosed unit is suitable for outdoor environmental con ditions Units housed in UL Type 1 enclosures must only be installed in indoor environments where it will not be affected by the elements such as moisture and extreme temperatures M33627 Fig 3 Enclosure Dimensions 4 2 Main Power Board Connections 1 Install a temporary ground for ESD Electrostatic Discharge protection With all circuits de energized connect a temporary protective earth ground connection for ESD protection Prior to performing any unit wiring be sure to discharge any static on your person 2 Install the H20 Series Protective Earth Ground Connect an earth ground wire to the H20 Series protective earth ground terminal screw located on the right side of the line voltage terminal block After installing the protective earth ground wire securely fasten the protective earth ground screw 7 62 0396 02 H20 SERIES CLASS 200 METER A WARNING Failure to attach the protective earth ground wire securely to the enclosure creates a potential shock hazard Do not o
35. urrent to a directly proportional O 2 volt signal which is utilized by the Honeywell meter The example from the first paragraph has now become a 400 amp to 2 volt device by this technique 35 62 0396 02 H20 SERIES CLASS 200 METER PASS 1 PASS 2 PASS 5 M34227 Fig 29 High Voltage CTs oJ T HIGH B VOLTAGE Cc P High Volt CT with 4 QOOOOOOOOUO High PT with Secondary 120V Sensors secondary M34228 Fig 30 Wiring Diagram For 3 wire High Voltage Circuits 62 0396 02 36 H20 SERIES CLASS 200 METER This special high voltage meter installation shows the correct wiring procedure for 3 wire high voltage circuits In this application the 2 element meter connection is used on the secondary circuits of the user supplied high voltage PTs and CTs The Honeywell meter used in this application is the model 12025 HV Installation of these meters requires the use of two 2 current sensors mounted on the secondaries of the high voltage Current Transformers See the drawing above for proper wiring For correct operation the meter must be installed correctly This special high voltage meter installation utilizes high voltage PTs Potential Transformers and CTs Current Transformers supplied by others The Honeywell meter is installed using the secondary outputs of these devices High voltage PTs reduce the primary voltage 4160v 13200v etc to a Secondary output of 120v
36. ut The header portions of the connectors are labeled A B and C Text on the plastic cover of each of the connectors instruct you which terminal of the plug is for the white conductor and which terminal is wired to the black conductor Once each current sensor is wired to its respective plug insert each plug into the appropriate header 13 62 0396 02 H20 SERIES CLASS 200 METER 4 4 MAINS Line Voltage amp Current Sensor Wiring Diagrams LINE VOLTAGE A iu pM 3 PHASE 4 WIRE INSTALLATION DIAGRAM gc N PE s ooo l CT Lg LINE VOLTAGE CONNECTIONS 14 12 AWG SENSOR CONNECTIONS BLACK LEAD W WHITE LEAD NEUTRAL NOT USED IN DELTA SYSTEM REMOVE NEUTRAL TERMINAL BLOCK SCREW FOR DELTA SYSTEMS V XOX OA CAO N AN N 1 10A 600 VAC INLINE FUSE PER CONDUCTOR LITTLEFUSE PART e NUMBER KLDR 100 SOURCE M33185 Fig 7 3 Phase 4 Wire Installation Diagram LINE VOLTAGE CURRENT SENSORS OA 3 PHASE 3 WIRE INSTALLATION DIAGRAM N PE WB NOTES LINE VOLTAGE CONNECTIONS 14 12 AWG SENSOR CONNECTIONS B BLACK LEAD W WHITE LEAD NEUTRAL NOT USED IN DELTA SYSTEM REMOVE NEUTRAL TERMINAL BLOCK SCREW FOR DELTA SYSTEMS WY V AAA AA AWS AAS WW SAS AK ANAS NN 1 10A 600 VAC INLINE FUSE PER CONDUCTOR LITTLEFUSE PART NUMBER KLDR 100 Wy TE SOURCE M33186 Fig 8 3 Phase 3 Wire Installation Diagram 62 0396 02 14 H20 SERIES CLASS 200 ME

Download Pdf Manuals

image

Related Search

Related Contents

  Toro TVAN Nozzles Sell Sheet  HP EliteBook 820 G2  Viewsonic TD2740    Elektromobil Sunrise Medical Sterling S400  

Copyright © All rights reserved.
Failed to retrieve file