1. Bit Meaning 0 RTC error 1 EEPROM Error 2 Dtaflash Error 3 reserved 4 reserved 5 reserved 6 reserved 7 reserved 8 reserved 9 reserved 10 reserved 11 reserved 12 reserved 13 reserved 14 reserved 15 reserved Tab 8 Status Register 13 3 Load Profile Parameter Acess Level R read only R W read write M write only in manufacturer mode meter cover opened Modbus Register Acess Units LCD Address level displayed 0C00 Load profile interval R W s no 0C01 LP recorded number R no 0C02 Load profile channels config 1 Second Index R s no 0C03 Load profile channels config 2 R W no 0C04 Load profile channels config 3 R W no Tab 9 Load Profile Parameter Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 23 31 User Manual WH4013 0C05 Load profile channels config 4 R W no 0C06 Load profile channels config 5 R W no 0C07 Load profile channels config 6 R W no 0C08 Load profile channels config 7 R W no 0C09 Load profile channels config 8 R W no 13 4 Display Settings Acess Level R read only R W read write M write only in manufacturer mode meter cover opened Modbus Register Acess Units LCD Address level displayed 1000 Auto Mode Scrolling duration R W M no 1002 In the Test Mode R W M
2. Load profile interval is configurable with 1 2 5 10 15 30 60 120 300 600 900 1800 3600 seconds Memory capable 8 channels the first channel should be time with together 43200 entries The load profile data are stored with time stamp Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 20 31 User Manual WH4013 first channel time stamp upto 7 further channel with values selectable according the following list value Active import energy Active import demand Active import power Voltage Current Power factor Frequency 22222 lt lt Note wv means corresponding item with options means corresponding item without options 12 5 5 Second index The second indexis a continously incremented second counter It is used as time stamp for maximum demand measurement all events inside the meter such as time stamp for power outage clock synchronization etc 12 5 6 Security functions The register for energy demand meter parameter and event records will be saved in non volatile memory if the power is off The meter detects and registers current status and events Event logging with date and time power off last 20 events time synchronisation last 20 events time asynchron last 20 entries Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are al
3. instantaneous measurement for voltage current frequency power factor and power RS485 communication anti tamper protection and event record power quality detection load profile pulse output for test self check 2 20 Appropriate Use The electricity meter WH40 and all versions of it are allowed to be used for measuring electrical energy only 2 3 Properties Type Single phase electricity meter direct connection Voltage Nominal voltage U 230 Vac Voltage range 0 8 1 15 U Frequency Nominal frequency f 50 Hz Frequency range 0 98 1 02 f Current Reference current lef Ij 10 I SA Maximum current Imax 65A Minimum current Li 0 25 A Starting current I lt 0 004 I Accuracy Cl B Class B in compliance with DIN EN 50470 1 3 Measuring Active Energy One Energy Direction A reverse locking Meter constant LED Output 1000 Imp kWh Display LCD 6 digit Life cycle gt 12 years RS485 Data Interface Connector RJ10 Socket Parameter 9 600 bps 8E1 setable Communication protocol Modbus RTU Power Consumption Voltage circuit 2W 10 VA atU Current circuit 4 VAat I Temperature Range Typical Operation 25 C to 70 C Storage 40 C to 85 C EMC Properties Isolation 4 kV AC 50 Hz 1 min Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allo
4. no 1010 Auto display item count R W M no 1012 Test display item count R W M no 1100 Auto Mode Display Items 1 32 R W M no 1140 Test Mode Display Items 1 32 R W M no Tab 10 Display Settings 13 5 Energy Register The meter saves up to 20 previous registers The save function is triggered via RS485 data interface Acess Level R read only R W read write M write only in manufacturer mode meter cover opened Modbus Register Acess Units LCD Address level displayed 4000 Current Total Import kWh R kWh yes 4200 PREVI Total Import kWh R kWh no 4400 PREV2 Total Import kWh R kWh no 4600 PREV3 Total Import kWh R kWh no 4800 PREVA Total Import kWh R kWh no 4A00 PREVS5 Total Import kWh R kWh no 4C00 PREV6 Total Import kWh R kWh no 4E00 PREV7 Total Import kWh R kWh no 5000 PREVS Total Import kWh R kWh no 5200 PREV9_Total Import kWh R kWh no 5400 PREVIO Total Import kWh R kWh no 5600 PREVII1 Total Import kWh R kWh no 5800 PREVI2 Total Import kWh R kWh no Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 24 31 User Manual WH4013 5A00 PREVI3 Total Import kWh R kWh no 5C00 PREV14 Total Import kWh R kWh no 5E00 PREVIS Total Import kWh R kWh no 6000 PREVI6 Total Import kWh R kWh no 6200 PREVI7 Total Import kWh R kWh n
5. 06 14 Seite 11 31 User Manual WH4013 5 Assembling and Installation 5 1 Assembling The meter constructed for assembling on DIN rail TH 35 7 5 according to IEC 60715 Abb 1 Housing Nr Element 1 Meter Hook 2 LCD 3 DIN rail space 4 Meter cover 3 Meter case 6 Terminal Block with cover Abb 2 Housing Dimensions Copyright DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 12 31 User Manual WH4013 Abb 3 Terminal Block 5 2 Installation The connection diagramm printed on the housing needs to be considered connecting the meter to the mains power NEN Wechselstromz hler Schaltung Abb 4 Connection diagramm Nr Terminal Term Terminal Terminal screw torque M Nm inal O mm Nr 1 Current In L1 1 6 5 M4 Pozidrive PZ2 M lt 2 7Nm 2 Current Out L1 3 3 Neutral wire 4 4 SO Output pos voltage 20 5 SO Output neg voltage 21 Copyright DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 13 31 User Manual WH4013 Data Interface 8 RS485 A PIN 1 RJ10 female RS485 A PIN 2 RS485 B PIN 3 RS485 B PIN4 Tab 4 Terminal block Warning The requirements of the netprovider need to be fullfil
6. eo ra eoo esee eee ko Pr apre Yet UE aa ee ea tar eR eese Pepe eu 13 Abb 3 Terminal Blo CK S 13 Abb 5 Label Protection Housing s cc ccccccscnssvesctsesssssonssssenvssvocesenessseneetevecsesenssnseedsversovonsseavarsbesseenseevens 14 POEHBuSgBgcee c 15 Abb 7 CD p S 16 Abb 8 Pin Definition RS485 5 2 1 e ereeto ete et terio tes snot eo e eo re eoo eene uice IU Pt HEU re erp es eb ee vs Leer teat eo Ea epe vod 16 ENIPBRTe UTERE 17 Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 5 31 User Manual WH4013 Abbreviations A A dd DIN EN FNN FIFO HH or hh IEC Imp kWh Imp kvarh IR LCD LED MM or mm OBIS P P PTB Q Q RTC R R SS or ss TOU Tx VDE yyyy Copyright DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Import actve energy to customer Expot active energy from customer day German Institut for Standards European Standard Forum Netztechnik Netzbetrieb im VDE First IN First OUT Hour International Electrotechnical Commision quantity of pulses each kWh quantity of pulses each kvarh Infrared Liquid Crystal Display Light Emitting Diode Month or Minutes Object Identification System Import active power Export active power Physikalisch Technische Bundesan
7. operation measurement memory check watchdog events so that billing relevant values may not be used anymore it displays a Fatal Error This status will be indicated with the flashing energy counter value for A 1Hz 12 5 Additional Functions This functions are not approved according MID The values may be used for information and not for billing purposes 12 5 1 Demand channel The demand channel the supports the following demand measurements Active import demand of total energy The meter supports block methods for demand calculation The demand interval is programmable for 60 120 300 600 900 or 1200 seconds The demand can be reset by No Ways of Demand Reset Description 1 Demand reset by software Demand can be reset by software through RS485 interface There is time limit between two demand reset actions for 30minutes When demand reset occurs the current energy and the maximum demand will be automatically saved for the last month The energy of current month will be continuously cumulated and the demand will be reset and restart to record 12 5 2 History data record There are 20 months history energy and demand data All this history data can be read out via Software through RS485 interface 12 5 3 Instantaneous parameter measurements The instantaneous values can be be read out via RS485 interface Voltage and current Power factor Active power Frequency 12 5 4 Load profile
8. the year of production f e 14 2014 7 LED test LED 1000 Imp kWh 8 constant SO pulse output 500 Imp kWh 9 symbols single phase protection class reverse locking 10 firmware version FW 1 05 11 type code 12 number approval document Tab 5 Description Nameplate Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 15 31 User Manual WH4013 8 LCD Display The LCD has the following format LCD size 24 39mm x 9mm Digit size 2 72mm x 6mm CDD D D DI BDOBBOH Abb 7 LCD r E The counter value of energy for A is displayed On the right side the unit kWh is printed on the housing 9 RS485 Interface The interface is provided for meter reading and programming according to Modbus RTU via RS485 The pin definition is as following Pin I A Pin 2 A Pin 3 B 4 l Pin4 B Abb 8 Pin Definition RS485 The Baudrate can be selected with 9600 19200 or 38400 Bd The Modbus RTU protocoll is described in an own document 10 Test LEDs The meter has one pulse LED for active energy with 1000 Imp kWh The ON time of a pulse is 40 ms Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 16 31 User Manual WHA013 11 Components 11 1 Blockdiagramm JOMOd o c 3 2 em 2 a lt 9 E a e w e 3 2 B Abb 9 Blockdiagramm Current
9. 0 Tab 16 Quantity of pulses Copyright DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 30 31 User Manual WH4013 14 EG Declaration of Conformity HIN G Ay DZG Metering GmbH Heidelberger Strasse 32 16515 Oranienburg Telefon 45 0 3301 854 O EG Konformit tserkl rung PERS RE EC Declaration of Conformity Mittebrandenburgische Sparkasse Potsdam BLZ 160 500 00 Konto 37 400 300 37 BIC WELA DE D PMB IBAN DEB1 1605 0000 3740 0300 37 nach EMV Richtlinie 2004 108 EG nach Messger te Richtlinie 2004 22 EG MID acc To EMC Directive 2004 108 EC acc to Measuring Instruments Directice 2004 22 EC MID Hersteller manufacturer DZG Metering GmbH Heidelberger Strasse 32 D 16515 Oranienburg Erklart hiermit in eigener Verantwortung dass folgendes Produkt Certifies on its own responsibility that the following product is Produktbezeichnung Elektrizit tsz hler Product Designation Electricity meter Typenbezeichnung WH4013 Type designation den Bedingungen der oben genannten Richtlinien einschlie lich deren zum Zeitpunkt der Erkl rung geltenden nderungen entspricht Conform to above mentioned directives including all amendments valid at the moment of issuing this declaration Die Konformitat des Baumusters Modul B mit den unten angef hrten Normen wurde tellt The conformity of the type Modul B with the listed s
10. 36 Clock synchronous LOG10 R 263C Clock synchronous LOGI1 R 2642 Clock synchronous LOG12 R 2648 Clock synchronous LOG13 R 264E Clock synchronous LOG14 R 2654 Clock synchronous LOGI5 R 265A Clock synchronous LOG16 R 2660 Clock synchronous LOG17 R 2666 Clock synchronous LOG18 R 266C Clock synchronous LOGI9 R 2672 Clock synchronous LOG20 R 2800 Clock asynchronous LOGO1 R 2802 Clock asynchronous LOG02 R 2804 Clock asynchronous LOG03 R 2806 Clock asynchronous LOG04 R 2808 Clock asynchronous LOG05 R 280A Clock asynchronous LOG06 R 280C Clock asynchronous LOG07 R 280E Clock asynchronous LOG08 R 2810 Clock asynchronous LOG09 R 2812 Clock asynchronous LOG10 R 2814 Clock asynchronous LOGI 1 R 2816 Clock asynchronous LOG12 R 2818 Clock asynchronous LOG13 R 281A Clock asynchronous LOG14 R 281C Clock asynchronous LOG15 R 281E Clock asynchronous LOG16 R 2820 Clock asynchronous LOG17 R 2822 Clock asynchronous LOG18 R 2824 Clock asynchronous LOG19 R 2826 Clock asynchronous LOG20 R Tab 15 Logging Clock Synchronisation Copyright DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 29 31 User Manual WH4013 13 8 Accuracy Test The accuracy of the meter is done with the pulse LEDs For testing the following quantity of minimum pulses dependant from the load are recommended Load I Min quantity pulses kele 1 Ir rer 5 gt Lief 1
11. E SV FEN er eure 10 3 6 Serviceand Warranty scssscaiscssrerscssescessssecssosdevenesscsonssnsseedensevenccsessessdecesvoonseceeessecsssanetessenesecess 10 PE boule 11 Assembling and Installation 1 eoo eee eene ri tea ooo oe eon ea seas aee Fee bone PE ones soossscosssseses sensseseosssees 12 HANE C SulnDI 12 5 2 InstallatiOD ESSE AET RE A Up p Ys uinea Ene VE Dp Pss ao eaae eoe PE Pese ae eR AE DR PETERS Ea ae CS Op Pes Ree a EUG 13 5 3 Protection Housing sincsen 14 6 Firmware VerslOD 5 5 e ee vast eo so rev ae asd esto vo se uae vase Un Ue sese ou e vaso on Ut rosa o ve vase on Uo pose siskosta seoste ee 15 FE Pluisgriqe c 15 8 LCD Display c 16 D IRSASS Tite lace ERTE TT T TT A E E 16 10 Test LEDS p 16 IEMEEGDRIOUSILCREORUT UTERE DOLLS CLLLLLDLU LLL 17 11 1 dd IBCIIIEETEEOTEEEEEELT EIOS nennen hessen 17 11 2 Real time Clock RICO m M 17 IUE ISulrtxeiieE E 18 LAB ne OI ZREE 19 12 1 M as reimenit eco e e oe pese eges u aeo Ebo A EP ER Pe Vase EE E unen e Pe Vo T 19 12 2 Firmware Architecture 4 eere eee eese eene eese sette tn sese eee tete en ss asses e tete s
12. Jun 14 User Manual WH4013 Date Last changes Single Phase Electronic Electricity Meter for DIN Rail Assembling 11 06 2014 17 03 2015 DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg User Manual WH4013 The contents of this user manual are copyright reserved Translations prints and copies are only allowed authorized by DZG All mentioned brand names and product names are ownership of DZG Metering GmbH Contents may be completed changed or deleted without prior announcements The descriptions of this user manual are not integral part of contracts DZG Metering GmbH All rights reserved DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copyright DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 2 31 User Manual WH4013 Notice This manual dscribes electricity meters of the type DVH4013 It includes all necessarry informations for assembling setting into operation and use of the meter Used Symbols Danger through Electric Voltages The symbol indicates warnings which may lead to personal injuries or death if it is ignored Take all necessarry precautions to avoid danger Warning The symbol indicates warnings to a possible dangerous situation which may lead to personal injuries or damage to properties Avoid dangerous situations Attention Attention indicates warnings which may lea
13. Maximum Demand Registers Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 26 31 User Manual WH4013 C 13 7 Logging Registers The logging register are not displayed on the LCD 13 7 1 Logging Demand Resets Acess Level R read only R W read write W M write only in manufacturer mode meter cover opened Modbus Register Acess Units Address level 2000 Demand reset record01 R S 2002 Demand reset record02 R S 2004 Demand reset record03 R S 2006 Demand reset record04 R S 2008 Demand reset record05 R S 200A Demand reset record06 R S 200C Demand reset record07 R S 200E Demand reset record08 R S 2010 Demand reset record09 R S 2012 Demand reset record10 R S 2014 Demand reset record11 R S 2016 Demand reset record12 R S 2018 Demand reset record13 R S 201A Demand reset record14 R S 201C Demand reset record15 R S 201E Demand reset record16 R S 2020 Demand reset record17 R S 2022 Demand reset record18 R S 2024 Demand reset record19 R S Tab 13 Logging Demand Registers Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 27 31 User Manual WH4013 13 7 2 Logging Power Outages Acess Level R read only R W read w
14. and Import kW Second Index R S 9200 PREV9 Maximum demand Import kW R kW D200 PREV9 Maximum demand Import kW Second Index R S 9400 PREVIO Maximum demand Import kW R kW D400 PREVIO Maximum demand Import kW Second Index R S 9600 PREV11 Maximum demand Import kW R kW D600 PREV11 Maximum demand Import kW Second Index R S 9800 PREVI2 Maximum demand Import kW R kW D800 PREVI2 Maximum demand Import kW Second Index R S 9A00 PREV13 Maximum demand Import kW R kW DA00 PREVI3 Maximum demand Import kW Second Index R S 9C00 PREV14 Maximum demand Import kW R kW Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 25 31 User Manual WH4013 DC00 PREV14 Maximum demand Import kW Second Index R S 9E00 PREV15_ Maximum demand Import kW R kW DE00 PREVI5 Maximum demand Import kW Second Index R S A000 PREV16 Maximum demand Import kW R kW E000 PREV16 Maximum demand Import kW Second Index R S A200 PREV17 Maximum demand Import kW R kW E200 PREV17 Maximum demand Import kW Second Index R S A400 PREV18 Maximum demand Import kW R kW E400 PREV18 Maximum demand Import kW Second Index R S A600 PREV19 Maximum demand Import kW R kW E600 PREVI9 Maximum demand Import kW Second Index R S A800 PREV20 Maximum demand Import kW R kW E800 PREV20 Maximum demand Import kW Second Index R S Tab 12
15. d to damage of properties if not observed Notice Noice indicates important information in the manual Bedienungs anleitung The symbol is printed on the nameplate an references to further informations in a instruction manual prepared for the customer Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 3 31 User Manual WH4013 Content 1 Eurther BTE 7 PME d CU T2 E E E E T A 8 DMs amp 0 1 1 1 Li 1 EEEE A E E E E E E eddeoesesuss voceassees 8 2 2 Appropriate US sssssssssisissessssssssssssssoossssssseesisssossssssroossscisseosoisoesssssos soss ivsos ssor meer 8 PM MM uu P 8 2 3 1 Technical Standards eee teen Ceo eei beer tese E uere vere PUE Eve it 9 RER I CATEEE 10 3 1 nl R rase 10 3 2 Common safety instrcutions ee eeee ee ee eese ee eee eee te seen aset tasse to setae stans eee en sese sa setas e seen a ee 10 3 3 Service and warranty instructions eee ee ecce esee eee eee en eee to soto testen aset ense eese seta asse eaae 10 3 4 Disposal product end of life information 1 eese eee ee eee e ee eene eene etes en senate tona 10 34 5 Environment ssssessississinss csceesseinsunesessrensssinsunnsnsnnenneesnsnnnsuenrene sehen es O
16. ese se see e tete te sese eee 19 12 3 Energy Checksum Mechanism eee eese ee ee ee ete seen aset aa sesto setae s eaae seen s tese se tpa ee saaa 19 12 4 Fatal Error siccssccccsiissssssovsccscessasscoscescccccssesscescoseccecoveavsssdessscocssesscecceseecesessessccseseesssssadesecsesecees 20 12 5 Additional DLL RTI ESSERE G 20 12 5 1 Demand chammel ccccccccssssessscccccecccssssscoccccccccvnccesccccecccncessscecccsecscssessscceeceeeenevees 20 12 5 2 History data TeCOrd 9 ue teen areas ats einge 20 12 5 3 Instantaneous parameter measurements ucessersnersnessnnesnnesnnesnnesnnnsnnnnnnnnnsnensnnnnn essen 20 254 Load prole ansehen 20 12 5 5 Second index csesessscecccccccsssessscccccecsccsvsececcessccussssssccessceccssvescecsssscesssescsecessccasesvees 21 12 5 6 Security functions 2 022 cseceseeceeeiteossasensesecesstecseveseeduceduoensosnusedssesedecssieuesdussduencusseussdanners 21 MMENuD Q CP Neos 22 EM MEM HICIPHIBHUIICRIELC REESE 22 ISI ET TEL menden essen seen 22 13 221 Status Reglster z e neret sesta een roi o PER Do EE ede PO Regna 23 13 3 Load Profile Parameter ssscesicsacccssecscvesicencsesccsascessesocsenseseecesscvocseseasesvessevocssseesssvessceocseeeassees 23 13 4 Display Settings 24 13 5 Energy REGIStCr sisisssssssvoscs
17. lation power line state Main Loop Second index LED pulse Save data EEPROM Communication interface RS485 RX TX interface handler error detection 12 3 Energy Checksum Mechanism The energy register is stored once in the internal RAM of the MCU and once in the external EEPROM In each memory two backups are available The contents original and backup are stored together with a checksum Before the current energy concumption A E is accumulated to the energy registersin the RAM or EEPROM the energy registers are red out and the checksum is controlled If the check sum is not correct the backup registers are used The current A E is accumulated to the energy register and the check sum is calculated new This informations are stored to the memories Finally a new back up of the energy registers and the checksum is created Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 19 31 User Manual WH4013 12 4 Fatal Error The meter has an internal software watch dog If the firmware is running abnormally without feeding the watch dog periodically the watch dog will reset the main CPU Watchdog events lead to fatal error if the events occur more times within a defined time slot The meter has implemented a self monitoring system If the meter recognizes no proper
18. led Selective hedges has to be used according requirements of the netproviders Attention Damage of the terminals due to high torque The specified maximum torques must not be exceeded Ensure that the connected lines are fixed with the needed torque compliant to EN 60999 for a safe connection The needed torque depends on the type of used lines and the maximum current 5 3 Protection Housing The assembled meter base and meter cover will be protected against unauthorized opening with a manufacturer label format 18x26 mm corner radius 0 5 mm on the side of the housing Abb 5 Label Protection Housing Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 14 31 User Manual WH4013 6 Firmware Version SS The firmware of the meter has the version number FW1 05 with the checksum 3B0987 Hex The firmware version is printed to the nameplate 7 Nameplate 12 11 10 21 C N YS DE MTP 14 B 003 MI 003 WH4013 230v 0 25 5 65 A KILS FW1 05 SOHz 25 C 70 C J Emm L 5 UN O 1000imp Wh RA 500Imp kWh Abb 6 Nameplate Nr Element Function 1 RJ10 female RS485 interface 2 sealing terminal cover 3 year of certification 4 electrical characteristics 5 LCD 6 digits without decimal 6 serial number number and barcode 128 The first 2 charakter are used for
19. lowed authorized by DZG 11 06 14 Seite 21 31 User Manual WH4013 13 Registers 13 1 Instantanous data Acess Level R read only R W read write W M write only in manufacturer mode meter cover opened Modbus Register Access Units LCD Address level displayed 0000 Total active import power R W no 0004 voltage R V no 000A current R A no 0010 Power factor R no 0012 Frequency R Hz no 0014 The total Import demand R W no Tab 6 Instantanous Data 13 2 Basic Parameter Acess Level R read only R W read write M write only in manufacturer mode meter cover opened Modbus Register Acess Units LCD Address level displayed 0400 Second Index R W M s no 0402 Meter ID R W M no 0405 SoftWare Date R W M no 0407 SoftWare time R W M no 0409 Clock Asynchronous Period R W S no 040B Communication baud R W bps no 040C Rated voltage R V no 040D Rated current R A no 040E Frequency R Hz no 040F Maximum current R A no 0410 Active constant R imp kWh no 0411 Active remote constant R W M imp kWh no 0412 Demand reset number R no 0413 Status Register R W M no 0800 Demand interval R W s no Tab 7 Basic Parameter Copyright DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 22 31 User Manual WH4013 13 2 1 Status Register
20. measuring Voltage measuring A D MCU RTC Communication interface Data storage Display LED Pulse output Pulse Output Display RS485 Interface DATA FLASH manganin shunt resistor devider analog to digital converter for the sampled voltage and current Micro Controller Unit real Time Clock RS485 Interface RJ10 female nonvolatile storage for energy register A and meter parameter in EEPROM and Dataflash memory LCD with 6 digits active energy A 1000 Imp kWh SO Pulse Output for active energy A 500 Imp kWh 11 2 Real time clock RTC AC power and super capacitor are powering the internal clock Built in 32 768kHz quartz oscillator frequency adjusted for high precision 5x10 at ambient temperature 25 C Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 17 31 User Manual WH4013 accuracy x 0 5 sec day at 23 C The variation of the time keeping accuracy with temperature is less than 0 1s C day The RTC usesGregorian calendar 100years calendar including leap year The time and date can be set through the RS485 interface by software 11 3 S0 Pulse Output The meter provides on terminal 20 positiv voltage and 21 negative voltage a puls output for active energy A according IEC 62053 31 Maximum voltage 80 Vpc standard is 27 V Maximum current 60 mA standard 27 mA Pulse co
21. nstant 500 Imp kWh Pulse duration 80 ms Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 18 31 User Manual WH4013 QE 12 Functionality 12 1 Measurement The meter measures one phase active energy A with accuracy class B The line current is measured with a shunt resistor The line voltage is divided with resistors to a voltage level which can be measured by the A D converter unit The voltages of the shunt resistor and voltage divider are measured with an A D unit which supports the MCU with the realtime digital values for voltage and current The MCU calculates in realtime active power energy and demand based on the converted analog signals for voltage and current The energy for A is counted in an register wich is stored in a non volatile memory This value is diaplayed on the LCD The measured energy is indicated on an LED with 1000 Imp kWh used for testing the accuracy of the meter Additionally the energy is put to a SO puls output with 500 Imp kWh used for external registration devices 12 2 Firmware Architecture The functionality of the meter is periodically processed in the main loop of the application layer The main loop is interupted by interrupt service routines based on timer events and asynchron events Interrupt Service Routines Basic timer 250us 1ms initialize board power off detected NO SO Pulse Energy accumu
22. o 6400 PREVIS Total Import kWh R kWh no 6600 PREVI9 Total Import kWh R kWh no 6800 PREV20 Total Import kWh R kWh no Tab 11 Energy Registers 13 6 Maximum Demand Register The meter saves up to 20 Maximum Demand register The demand interval is defined in regsiter 0800 The Damand register are not displayed on the LCD Acess Level R read only R W read write W M write only in manufacturer mode meter cover opened Modbus Register Acess Units Address level 8000 Current Maximum demand Import kW R kW C000 Current Maximum demand Import kW Second Index R s 8200 PREV1 Maximum demand Import kW R kW C200 PREVI Maximum demand Import kW Second Index R S 8400 PREV2 Maximum demand Import kW R kW C400 PREV2 Maximum demand Import kW Second Index R s 8600 PREV3 Maximum demand Import kW R kW C600 PREV3 Maximum demand Import kW Second Index R S 8800 PREV4 Maximum demand Import kW R kW C800 PREV4 Maximum demand Import kW Second Index R S 8A00 PREV5 Maximum demand Import kW R kW CA00 PREV5 Maximum demand Import kW Second Index R S 8C00 PREV6_Maximum demand Import kW R kW CC00 PREV6 Maximum demand Import kW Second Index R S 8E00 PREV7 Maximum demand Import kW R kW CE00 PREV7 Maximum demand Import kW Second Index R S 9000 PREV8 Maximum demand Import kW R kW D000 PREV8 Maximum dem
23. opies only are allowed authorized by DZG 11 06 14 Seite 9 31 User Manual WH4013 3 Safety 3 1 Responsibility The owner or provider is responsible for the proper use of the device The installation putting into operation and reinstallation of the meter is only allowed to be done by electrically skilled persons which got knowledge about the contents of this user manual 3 2 Common safety instrcutions For installation setting into operation and deinstallation of the device the local requirements for safety requirements has to be observed Danger Inappropriate use of parts under high voltage may lead to grave injuries and accidents which may be fatal even with 230V The conductors which are connected to the device must be disconnected to the mains during assembling and installation It must be used a prevention for being switched on accidentally The device is not allowed to be used out of specifications 3 3 Service and warranty instructions Damaged devices can t be repaired by yourself The warranty and liablity will be terminated with opening the device The same applies to damages caused by external influences For the device no servicing is required 3 4 Disposal product end of life information I e This meter was designed and built by DZG to provide many years of service and is backed by our commitment to provide high quality support When it eventually reaches the end of its
24. ous Data ge 22 Tab 7 Basic Parameter isvcesccsssscxcbecsvesecssassvetsctedsoesseesveosseossacesuvsvesssued e ada ri esaad iis israe 22 Tab Status Register ee T 23 Tab 9 Load Profile Parameter 5 ccscio sssssasssesssons sosssoasseosseosceossenssesssoescoassossvasssesseoosesssesosssosesscesesersone 23 Tab 10 Display Settings RRRR 24 Tab 11 Energy Cun m 25 Tab 12 Maximum Demand Registers Leere eerte ee esee ee eren seen sten seta seta setas etna ta aseo s etas e sese aue 26 Tab 13 Logging Demand Registers 00 200000000s0000220000200000000s02000202000000s000000020220000000000002000H20000000 27 Tab 14 Logging Power Outages anssonssonnssnnsonnssnnesnnesnnesnnnennnennnennnssnnssnnssunsssnnssnnssnnesnnesnnesnnesnssennne 28 Tab 15 Logging Clock Synchronisation eee ee eee ee eren eee ee ee eee seen aestas etate setae seta aee 29 Tab 16 Quantity of pulses crsnnssossonsonesnssonsnnssnnsnnsnnssnnnnnssnnsnnsnnnsnnsnnsnnsnnnsnnssnnsnnsnnnsnnssnssnnsnnsnnnsannn 30 Pictures EMEN Gu M 12 Abb 2 Housing DimensiODsS 2 eio ee eere et tore eoe edente eor eo c eS bee e tete eee ei or e e BEER eS ese Ese reve istos epi sU 12 Abb 4 Connection diagram esses seosscedssssscesssssezssossseessvcsecesse
25. rite W M write only in manufacturer mode meter cover opened Modbus Register Acess Address level 2400 Power Outages LOGO1 R 2404 Power Outages LOGO2 R 2408 Power Outages LOG03 R 240C Power Outages LOG04 R 2410 Power Outages LOG05 R 2414 Power Outages LOG06 R 2418 Power Outages LOGO7 R 241C Power Outages LOG08 R 2420 Power Outages LOGO9 R 2424 Power Outages LOGIO R 2428 Power Outages LOGI 1 R 242C Power Outages LOGI2 R 2430 Power Outages LOG13 R 2434 Power Outages LOG14 R 2438 Power Outages LOG15 R 243C Power Outages LOGI6 R 2440 Power Outages LOG17 R 2444 Power Outages LOG18 R 2448 Power Outages LOG19 R 244C Power Outages LOG20 R Tab 14 Logging Power Outages Copyright DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 28 31 User Manual WHA013 13 7 3 Logging Clock Synchronisation Acess Level R read only R W read write W M write only in manufacturer mode meter cover opened Modbus Register Acess Address level 2600 Clock synchronous LOGO1 R 2606 Clock synchronous LOG02 R 260C Clock synchronous LOG03 R 2612 Clock synchronous LOG04 R 2618 Clock synchronous LOGO05 R 261E Clock synchronous LOG06 R 2624 Clock synchronous LOG07 R 262A Clock synchronous LOGO08 R 2630 Clock synchronous LOG09 R 26
26. serviceable life it should be disposed of in accordance with local or national legislation 3 5 Environment This meter is designed for indoor use or in a cabinet environment only avoiding extreme weather conditions in accordance with IEC 62052 11 and IEC 62053 21 with the terminal cover fitted 3 6 Service and Warranty This meter product is warranted against defects in material and workmanship for a period of one year from date of shipment During the warranty period DZG will at its option either repair or replace products which prove to be defective For warranty service or repair this product must be returned to a service facility designated by DZG DZG does not warrant that the operation of the meter or firmware will be uninterrupted or error free Damaged devices can t be repaired by yourself The warranty and liablity will be terminated with opening the device The same applies to damages caused by external influences For the device no servicing is required Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 10 31 User Manual WH4013 4 Typecode direct connection two wire single phase meter H40 Static meter 13 range Imax Iref 2130096 Tab 3 Typecode Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11
27. ssscsssestesocessncsessesesenecssevssssesosensvsssessesesssesees rennen esse Teer 24 13 6 Maximum Demand Register 00 0000s000s0s00ns200000000s00000s2000202000000000n0000210000n00000 00000020 00200000 25 13 7 Logging Registers i sesssessscssansssnnessnssnsssnsssnnesssnstensensrennnesnsnhsenssenheneensrns sn EVE eO pe SR PE Pe SE FE espe eet 27 Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 4 31 User Manual WH4013 13 7 1 Logging Demand Resets 5 1 ee Ie ret re innen 27 13 7 2 Logging Power Oultages tei een eire ede e nin Re Pri Pre dete d eee Ot 28 13 7 3 Logging Clock Synchronisation eese nennen 29 WSS Nuiuicadic M 30 14 EG Declaration of Conformity ssssuscosseonseonnennnssonssonssonsssnnsnnnsnnuennunsnnssnnnennnsnnnsnnnssonssannsannse 31 Tables Tab 1 F rther Dokuments 4 000800 esse een nenn n 7 Tab 2 Technical Properties 1 eeee essei eee esee ee seen eene en senten tasse neta stesso s ense ta sesso seta sese netu sena 9 Tab 3 Typecode M 11 Tab puwilirldgudcu c Fee 14 Tab 5 Description Nameplate iecur erue er oa eonim ouai ora orate arie oe eaa oan van on eR aepo a TOS epa aor Ea orae rra uS 15 Tab 6 Instantan
28. stalt Import reactive Power Export reactive Power Real Time Clock Import reactive energy inductive Export reactive energy kapacitive Seconds Time Of Use Tariff z B T1 Tariffl T2 Tariff2 Association of Electrotechnic Elektronic Informationtechnic e V Year Copies only are allowed authorized by DZG 11 06 14 Seite 6 31 User Manual WH4013 1 Further Documents dB Document Nr Document Version from Content D1 User Manual WH40 Appendix A V1 0 11 06 2014 Communication Interface and Implemented Communication Prtocol D3 Product Drawings WH40 V1 0 11 062014 CADs BOM Schematics Tab 1 Further Dokuments Copyright DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 7 31 User Manual WH4013 2 Properties 2 1 Common Welcome to use single phase Din Rail meter Let s introduction it s functions and operations of this product This meter is 1phase 2wire direct connected electricity meter It adopts the advanced technology of LSI Large Scale Integrated circuit and digital signal processing The craftworks of our product are exquisite and the functions provided are comprehensive and client oriented The energy meter is an intelligent instrument equipped with leading technology The functionality of the single phase Din Rail energy meter includes active energy and demand measurement
29. tandards was ascertained Benannte Stelle Name Nummer CSA Group Bayern GmbH 1948 Notified Body name number Baumusterpr fbescheinigungs Nr DE MTP 14 B 003 MI 003 Type examination certificate number Das Ger t erf llt folgende harmonisierte Normen The device meets the requirements of the following harmonized standards EMV Richtlinie 2004 108 EG MID 2004 22 EG EMC Directive 2004 108 EC MID 2004 22 EC EN 55022 2006 EN50470 1 2006 EN 62052 11 2003 EN50470 3 2006 EN 62053 21 2003 Die Konformit tsbewertung wurde nach Modul D durch den Hersteller vorgenommen The conformity assessment was performed by the manufacturer acc Modul D Benannte Stelle Name Nummer CSA Group Bayern GmbH 1948 Notified Body name number Zertifikats Nummer DE MTP 12 D 001 MI 003 Certificate number Ort place Datum date Oranienburg 11 06 2014 L 1 Unf a Digi Inform Ulrich Feldm ller Dipi ing FH Peter Zine Grec haftet ance Geecnanstunrer DOZO Metering OmbH DZO Metering GmbH Sez der Gesellschaft Oranlanburg Neuruppin HRS 7193 NP Gesch fsf hrer Ulrich Felerm ler Peter Zra Ust 4dert Nr DE 81535 540 Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg Copies only are allowed authorized by DZG 11 06 14 Seite 31 31
30. wed authorized by DZG 11 06 14 Seite 8 31 User Manual WH4013 High Voltage 10 kV Impuls 1 2 50 us Housing Dimension DIN Rail 86x35x62 mm Material fiber glass reinforced Polycarbonat flame resistant EN 62053 21 recyclable Class of protection II Degree of protection IP 51 Weight Weight appr 0 25 kg Tab 2 Technical Properties 2 3 1 Technical Standards IEC 62053 21 Static meters for active energy classes 1 and 2 IEC 62052 11 Electricity metering equipment AC General requirements tests and test conditions part 11 metering equipment IEC 62053 31 Electricity metering equipment AC Particular requirements part 31 Pulse output devices for electromechanical and electronic meters two wires only EN 50022 Low voltage switchgear and controlgear for industrial use mounting rails top hat rails 35 mm wide for snap on mounting of equipment 1 PTB Requirements 1 1 Anforderungen an elektronische und software gesteuerte Messger te und Zusatzeinrichtungenf r Elektrizit t Gas Wasser und W rme PTB A 50 7 2002 1 2 Messger te f r Elektrizit t Elektrizit tsz hler und deren Zusatzeinrichtungen PTB A 20 1 Dezember 2003 2 Legal Directives Legal Metrology Guide general rules published in Federal Journal Nr 108a on June 15 2002 3 WELMEC Guide 7 2 software guide Copyright O DZG Metering GmbH Heidelberger Str 32 D 16515 Oranienburg C