Home
        WARNING: WARNING: IMPORTANT
         Contents
1.      wire gauge and wire lengths for typical thermostat  connections are listed in Table 2    e The thermostat should be mounted about 5 feet  above the floor on an inside wall  DO NOT install the  thermostat on an outside wall or any other location  where its operation may be adversely affected by radiant  heat from fireplaces  sunlight  or lighting fixtures  and  convective heat from warm air registers or electrical  appliances  Refer to the thermostat manufacturer   s  instruction sheet for detailed mounting and installation  information     START UP  amp  ADJUSTMENTS   Pre Start Check List     Verify the indoor unit is level and allows proper   condensate drainage   V Verify the outdoor coil and top of the unit are free from  obstructions and debris  and all equipment access   control panels are in place   Verify air filters are cleaned and properly installed   Verify duct work is sealed to prevent air leakage   Verify line voltage power leads are securely connected  and the unit is properly grounded   Verify low voltage wires are securely connected to the  correct leads on the low voltage terminal strip   Verify power supply branch circuit overcurrent protection  is sized properly      Verify the thermostat is wired correctly     L   L Ll L    Start Up Procedures   The thermostat s function mode should be set to OFF and  the fan mode should be set to AUTO  Close all electrical  disconnects to energize the system     Air Circulation   Indoor Blower   1  Set the thermostat
2.    Label all wires prior to disconnection when  servicing the unit  Wiring errors can cause  improper and dangerous operation    e All electrical connections must be in compliance with  all applicable local codes and ordinances  and with  the current revision of the National Electric Code   ANSI NFPA 70         For Canadian installations the electrical connections  and grounding shall comply with the current Canadian  Electrical Code  CSA C22 1 and or local codes      Pre Electrical Checklist      Verify that the voltage  frequency  and phase of the  supply source match the specifications on the unit  rating plate    V Verify that the service provided by the utility is sufficient  to handle the additional load imposed by this equipment   Refer to the unit wiring label for proper voltage wiring    V Verify factory wiringis in accordance with the unit wiring  diagram  Inspect for loose connections     Line Voltage     A wiring diagram is located on the inside cover of the  electrical box of the outdoor unit  The installer should  become familiar with the wiring diagram before making  any electrical connections to the outdoor unit      An electrical disconnect must be located within  sight of and readily accessible to the unit  This  switch shall be capable of electrically de energizing  the outdoor unit    e Line voltage to the unit should be supplied from a  dedicated branch circuit containing the correct fuse  or circuit breaker for the unit  Incoming field wiring  and minimu
3.  interior of the structure  The roof must be structurally  capable of handling the weight of the unit    e Full perimeter support is required under the unit   Support must be made of weather resistant materials  and installed prior to unit installation    e The support must be built to raise the unit 6  above  the roof     6    from Building             24  for  Service Access             OBSTRUCT    TOP OF UNIT 12   or 18     See Note    NOTE  Units require full perimeter clearances   Installer must maintain 18    between two units  or 12    between single unit and structure     V 2  Mounting Pad                      Figure 1  Clearance Requirements    Connecting Refrigerant Tubing Between the Indoor   amp  Outdoor Unit      CAUTION     When servicing  cover or seal openings to  minimize the exposure of the refrigerant system  to air to prevent accumulation of moisture and  other contaminants              After outdoor and indoor unit placement has been  determined  route refrigerant tubing between the  equipmentin accordance with sound installation practices     e When connecting refrigerant linesets together  it is  recommended that dry nitrogen be flowing through the  joints during brazing to prevent internal oxidation and  scaling    Hefrigerant tubing should be routed in a manner that  minimizes the length of tubing and the number of bends  in the tubing  If precise forming of refrigerant lines is  required  a copper tubing bender is recommended   Avoid sharp bends and 
4.  system mode on OFF and the fan  mode to ON    2  Verify the blower runs continuously  Check the air delivery  at the supply registers and adjust register openings for  balanced air distribution  If insufficient air is detected   examine ductwork for leaks or obstructions    3  Set the thermostat fan mode to AUTO and verify the  blower stops running     System Cooling  1  Set the thermostat   s system mode to COOL and the    fan mode to AUTO  Gradually lower the thermostat  temperature setpoint below room temperature and  verify the outdoor unit and indoor blower energize    2  Verify blower wheel is spinning in direction indicated by  arrow  Feel the air being circulated by the indoor blower  and verify that it is cooler than ambient temperature     Listen for any unusual noises  If unusual sounds occur   determine the source of the noise and correct as  necessary    3  Verify HI and LO refrigerant pressures    4  Allow the system to operate for several minutes and then  set the temperature selector above room temperature   Verify the fan and compressor cycle off with the  thermostat  NOTE  The blower should also stop unless  fan mode is set to the ON position     System Heating  optional   1  Set the thermostat s system mode to HEAT and the  temperature mode above room temperature    2  Verify the optional heating equipment  furnace or  electric heat  and indoor blower energize  Feel the air  being circulated by the indoor blower and verify that  it is warmer than ambient t
5. 24 vac 40ca class 2 circuit  See furnace airhandler installation    IGPTIORALS COMPRESSOR    CONTACTS    CloUTDOOR FAN  MOTOR    HPS T    YELLOW BLACK    24 VOLT FIELD  CONNECTIONS    LEGEND     FIELD WIRING            LOW VOLTAGE  HIGH VOLTAGE sm    CC   Contactor Coil  CCH   Crankcase Heater  HPS   High Pressure Switch    SEE NOTE 6    Single Phase    1  Couper le courant avant de faire letretien   2  Employez uniquement des conducteurs en cuivre   3  Ne convient pas aux installations de plus de 150 volt a la terre          pe BLACK      55 TDOOR  FAN MOTOR  LUE    ORANGE    CAPACITOR      YELLOW  RED OR  HED BLACK    CONTACTOR       RED OR  RED BLACK    BLACK    GROUNDING  SCREW    an      i Es odi i  ee ee         Oo    CRANKCASE  HEATER   OPTIONAL     710388B   Replaces 7103884        Figure 3  Wiring Diagram for 1 5   4 Ton Units   Single Phase Air Conditioner without CoreSense                               WISOWHAHE OL   H2LIMS SHNSS3Hd HOIH  SAH     TOA           HOLIMS                  MOT                  _3 0 110A         VEECLLZ    h H3lyvy3H JSVYOHAN VHI                       ONIHIM            I I 059 HOLOVINOO  30    CIN3931    TVNOLLdO  d                       H21IMS  lt  SNOLLS3NNOO  kunssaud MOT    3Hf18S3Hd          mald ADA Fe        m  i      ud       Aw Ig G    MoMA                            SIONS          21 11               I        6   4                                  Fog                   amp                      E                 b      O78 WNIWHA
6. L grr   ds  j               9 M o doodino GIOWINOO   3  e HOSSdHdWOO            131 E  Oo C i  y Bas      HOLOW         HOLOVINOO IT 1  034 wow G          3 P                    1       MCTISA    AOEC BOC    HOSS3HBdlNco                 daH      HJW E     syy                                             pue                             suomonugsug                                                        aes           2 sse 3 eAQp 2     pz 0                  9   ayejd Burgi yun aas  uonsejoad                                              Joy  G  SOL 163 919      5                        esn sam jueure2ejdaJ Jod  t                Ej E        OGL ep snjd ap                    xne sed juarauo2                                        061 paaaxe jeu  suisjs  s uo ajqejins JON      Ama ua sunajonpuoo sap jusaurenbiun zaAojdwy  z    juo s10723npuoo 1eddo   esn suonoseuuo2 Ajddns 104  z    uaaa                                          Jadnoy                                                e J2 UUIODSIG  L    S3LON    10101 J00pinQ W93 YUM     ZH 09   eseug ajbuls A0  c 80c  uonoes 100pino  1euonipuo       urejs  S Hids                                Figure 4  Wiring Diagram        5 Ton Units   Single Phase Air Conditioner without CoreSense        AIR CONDITIONER MAINTENANCE      WARNING     To prevent electrical shock  personal injury  or  death  disconnect all electrical power to the unit  before performing any maintenance or service   Theunitmay have morethan oneelectrical supply     Prop
7. SPLIT SYSTEM AIR CONDITIONER 14 SEER  SINGLE PHASE  INSTALLATION INSTRUCTIONS       INSTALLER  Please read all instructions before servicing General Information   this equipment  Pay attention to all safety warnings and Before You Install this Unit   any other special notes highlighted in the manual  Safety Locating the Air Conditioner   markings are used frequently throughout this manual to                     lamaoni   designate a degree or level of seriousness and should ging   not be ignored  dis inei   WARNING indicates a potentially hazardous situation that Connecting Refrigerant Tubing Between the  if not avoided  could result in personal injury or death  indoor  amp  Outdoor Unit    CAUTION indicates a potentially hazardous situation that ELECTRICAL WIRING  if not avoided  may result in minor or moderate injury or Pre Electrical Checklist  property damage  Line Voltage    Grounding  A  WARNING  Thermostat Connections                                 HTC        Shut off all electrical power to the unit before Pre Start Check List  performing any maintenance or service on the Start Up Procedures  system  Failureto comply may result in personal Air Circulation   Indoor Blower    injury or death  System Cooling                                      S System Heating  optional     REFRIGERANT CHARGING  Charging the Unit in AC Mode  AN WARNING  Application Notes for Using the Charging Chart  6  Unless noted otherwise in these instructions  PURE UII OEEO e  only factory authori
8. carrier    V Please consult your dealer for maintenance information  and availability of maintenance contracts  Please read  all instructions before installing the unit     Locating the Air Conditioner   e Survey the job site to determine the best location for  mounting the outdoor unit    e Sufficient clearance for unobstructed airflow through  the outdoor coil must be maintained in order to achieve  rated performance  See Figure 1   page 3  for  minimum clearances to obstructions        Overhead obstructions  Figure 1   poorly ventilated  areas  and areas subject to accumulation of debris  should be avoided        Consideration should be given to availability of electric  power  service access  noise  and shade     Packaging Removal   NOTE  To prevent damage to the tubing connections   carefully remove the carton and user   s manual from the  equipment  Discard the shipping carton     Ground Level   Ground level installations must be located according to   local building codes or ordinances and these requirements    e Clearances must be in accordance with those shown  in Figure 1        A suitable mounting pad  Figure 1  must be provided  and separate from the building foundation  The pad  must be level and strong enough to support the weight  of the unit  The slab height must be a minimum of 2      5 cm  above grade and with adequate drainage     Roof Mount   e The method of mounting should be designed so that it  does not overload roof structures or transmit noise to  the
9. contact of the refrigerant lines  with metal surfaces    Hefrigerant tubing should be supported in a manner  that the tubing will not vibrate or abrade during system  operation    Tubing should be kept clean of foreign debris during  installation    Every effort should be made by the installer to ensure  thatthefield installed refrigerant containing components  of the system have been installed in accordance with  these instructions and sound installation practices to  insure reliable system operation and longevity    The maximum recommended interconnecting  refrigerantline lengths is 75 ft  and the vertical elevation  difference between the indoor and outdoor sections  should not exceed 20 ft    A filter dryer is provided with the unit and must be  installed in the liquid line of the system  If the installation  replaces a system with a filter dryer already present  in the liquid line  the filter dryer must be replaced with  the one supplied with the unit  The filter dryer must be  installed in strict accordance with the manufacturer   s  installation instructions    Optional equipment such as liquid line solenoid valves   low ambient  etc   should be installed in strict accordance  with the manufacturer   s installation instructions     ELECTRICAL WIRING     WARNING     To avoid risk of electrical shock  personal  injury  or death  disconnect all electrical power  to the unit before performing any maintenance  or service  The unit may have more than one  electrical supply  
10. e        DO NOT DESTROY  PLEASE READ CAREFULLY  amp  KEEP IN A SAFE PLACE FOR FUTURE REFERENCE        WARNING     This split system air conditioners is shipped    charged with R410A refrigerant and ready  for installation  If repairs make it necessary  for evacuation and charging  it should only  be attempted by qualified trained personnel  thoroughly familiar with this equipment  Under  no circumstances should the owner attempt to  install and or service this equipment  Failure to  comply with this warning could resultin property  damage  personal injury  or death       CAUTION     This unit uses refrigerant R 410A  DO NOT use  any other refrigerant in this unit  Use of another  refrigerant will damage the unit       WARNING     The information listed below must be followed  during the installation  service  and operation  of this unit  Unqualified individuals should  not attempt to interpret these instructions or  install this equipment  Failure to follow safety  recommendations could result in possible  damage to the equipment  serious personal  injury or death          he installer must comply with all local codes and  regulations which govern the installation of this type  of equipment  Local codes and regulations take  precedence over any recommendations contained in  these instructions  Consult local building codes and  the National Electrical Code  ANSI Cl  for special  installation requirements      All electrical wiring must be completed in accordance  with local  s
11. e present to actuate the  valve        Ahigh pressure switch 15 factory installed and located  in the liquid line internal to the outdoor unit  The switch  is designed to protect the system when very high  pressures occur during abnormal conditions  Under  normal conditions  the switch is closed  If the liquid  pressure rises above 575 psig  then the switch will  open and de energize the outdoor unit  The switch    will close again once the liquid pressure decreases  to 460 psig  Please note that the switch interrupts the  thermostat inputs to the unit  Thus  when the switch  opens and then closes  there may be a 5 minute short  cycling delay before the outdoor unit will energize     Charging the Unit in AC Mode    At outdoor temperatures above 55   F for  optimized sub cooling of 10  F   12   F     1  With the system operating at steady state  measure the    liquid refrigerant pressure  in psig  at the outdoor unit  service valve     2 Measure the liquid refrigerant temperature  in    Fahrenheit  at the service valve     3  Determine the required liquid refrigerant pressure from    the charging chart  Figure 2   page 7      If the pressure measured in Step 1 is greater than  the required liquid refrigerant pressure determined in  otep 3  then there is too much charge in the system   Remove refrigerant and repeat Steps 1 through 3 until  the system is correctly charged    If the pressure measured in Step 1 is less than the  required liquid refrigerant pressure determined in S
12. e shipped from the factory wired  for 230 volt operation  For 208V operation  remove the  lead from the transformer terminal marked 240V and  connect it to the terminal marked 208V    e Optional equipment requiring connection to the power  or control circuits must be wired in strict accordance  of the NEC  ANSI NFPA 70   applicable local codes   and the instructions provided with the equipment     Grounding       WARNING     The unit cabinet must have an uninterrupted or  unbroken electrical ground to minimize personal  injury if an electrical fault should occur  Do not  use gas piping as an electrical ground     This unit must be electrically grounded in accordance  with local codes or  in the absence of local codes  with  the National Electrical Code  ANSI NFPA 70  or the CSA  C22 1 Electrical Code  Use the grounding lug provided in  the control box for grounding the unit     Thermostat Connections   e Thermostat connections should be made in accordance  with the instructions supplied with the thermostat and  the indoor equipment    e The outdoor unit is designed to operate from a 24 VAC  Class 11 control circuit  The control circuit wiring must  comply with the current provisions of the NEC  ANSI   NFPA 70  and with applicable local codes having  jurisdiction    e The low voltage wires must be properly connected to  the units low voltage terminal block  Recommended    THERMOSTAT MAXIMUM RECOMMENDED  WIRE GAUGE THERMOSTAT WIRE LENGTH  FT     Table 2  Thermostat Wire Gauge  
13. ect a systems operation using quality  instruments  match the measured liquid temperature  to the units table  The measured liquid pressure  reading should be within 396 of the table value for most  installations    For systems that are operating with more than a 5   deviation  inspect the unit for the proper voltage and  phase balance and the refrigeration system for leaks   Units that are operating    less then 95  of the nominal  voltage or with a 296 phase imbalance may see a more  significant deviation than the amount stated above   DO NOT usethe charts in systems thathave afan cycling  under low ambient control  Refer to the low ambient  kit instructions for more information   If applicable     Charging Chart    me  o  V   Q            Som     o  o      Sem       oS              Add a eter erant if  m g      below the curve   oo           Do not add or remove refrigerant if  pressure reading is between unit  g curves and saturation curve     95 100 105 110 115 120 125 130 135  Liquid Temperature  F        Figure 2  Charging Chart for 2   5 Ton Units   TXV Matches     WIRING DIAGRAMS    WIRING DIAGRAM    Split System Air Conditioner  Outdoor Section     NOTES     1  Disconnect all power before servicing    2  For supply connections use copper conductors only    3  Not suitable on systems that exceed 150 volts to ground    4  For replacement wires use conductors suitable for 105 deg C    5  For ampacities and overcurrent protection  see unit rating plate    6  Connect to 
14. emperature  Listen for any  unusual noises  If unusual sounds occur  determine the  source of the noise and correct as necessary     REFRIGERANT CHARGING    WARNING     This split system air conditioners is shipped  charged with R410A refrigerant and ready  for installation  If repairs make it necessary  for evacuation and charging  it should only  be attempted by qualified trained personnel  thoroughly familiar with this equipment  Under  no circumstances should the owner attempt to  install and or service this equipment  Failure to  comply with this warning could resultin property  damage  personal injury  or death     After refrigerant line connections are completed  it is  required that you leak check and evacuate the indoor  section and all line connections  using proper methods   before finalizing the full system refrigerant charge         Refrigerant charging charts are applicable only to  matched assemblies of this equipment and listed  airflows for the indoor coil  Refer to Figure 2   page  7  for correct system charging    e Outdoor units with non AHRI listed indoor coils         not recommended  Deviations from rated airflows or  non listed combinations may require modification to the  expansion device and refrigerant charging procedures  for proper and efficient system operation    e The refrigerant charge can be checked and adjusted  through the service ports provided external to the  outdoor unit  Use only gage line sets which have a   Schrader  depression devic
15. er maintenance is important to achieve optimum  performancefrom the air conditioner  The ability to properly  perform maintenance on this equipment requires certain  mechanical skills and tools  If you do not possess these  skills  contact your dealer for maintenance  Consult your  local dealer aboutthe availability of maintenance contracts   Routine maintenance should include the following    e Inspect and clean or replace air filters at the beginning  of each heating and cooling season  or more frequently  if required    e  nspect the condensate drain and outdoor coil at the  beginning of each cooling season  Remove any debris   Clean the outdoor coiland louvers as necessary using a  mild detergent and water  Rinse thoroughly with water    e Inspect the electrical connections for tightness at the  beginning of each heating and cooling season  Service  as necessary       CAUTION     The unit should never be operated without a  filter in the return air system  Replace disposable  filters with the same type and size         Donotattemptto add additional oilto motors unequipped    with oil tubes  The compressor is hermetically sealed  at the factory and does not require lubrication     10    REPLACEMENT PARTS  Replacement parts are available through all Nordyne  distributors  Please have the complete model and serial  number of the unit when ordering replacement parts     Electrical        Capacitors     Temperature Limit Switches      Compressors     Thermostats       Contacto
16. m size of electrical conductors and circuit  protection mustbe in compliance with information listed  onthe outdoorunit data label  Any other wiring methods  must be acceptable to authority having jurisdiction    e  heoutdoorunit requires both power and control circuit  electrical connections  Refer to the wiring diagram    schematic for identification and location of outdoor unit  field wiring interfaces  See Figure 3   page 8   amp   Figure 4   page 9   Make all electrical connections  in accordance with all applicable codes and ordinances        Overcurrent protection must be provided at the branch  circuit distribution panel and sized as shown on the unit  rating label and according to applicable local codes   See the unit rating plate for minimum circuit ampacity  and maximum overcurrent protection limits      Provide power supply forthe unitin accordance with the  unit wiring diagram  and the unit rating plate  Connect       COPPER WIRE SIZE     AWG   1  Voltage Drop     Supply Wire Length Feet    Supply Circuit  Ampacity    Wire Size based on N E C  for 60   type copper conductors   Table 1  Copper Wire Size    the line voltage leads to the terminals on the contactor  inside the control compartment    e Use only copper wire for the line voltage power supply  to this unit as listed in Table 1  Use proper code agency  listed conduit and a conduit connector for connecting  the supply wires to the unit  Use of rain tight conduit  is recommended        208 230 Volt units ar
17. nd dependable  comfort  providing it is properly installed and maintained   Abuse  improper use  and or improper maintenance can  shorten the life of the appliance and create unsafe hazards     To achieve optimum performance and minimize equipment  failure  it is recommended that periodic maintenance be  performed on this unit  The ability to properly perform  maintenance on this equipment requires certain  mechanical skills and tools     Before You Install this Unit      The cooling load of the area to be conditioned must be  calculated and a system of the proper capacity selected   It is recommended that the area to be conditioned be  completely insulated and vapor sealed    V Check the electrical supply and verify the power supply  is adequateforunit operation  The system mustbe wired  and provided with circuit protection in accordance with  local building codes  If there is any question concerning  the power supply  contact the local power company    V        indoor section  air handler  furnace  etc  should be  installed before routing the refrigerant tubing  Refer to  the indoor unit s installation instructions for installation  details    V Allunits are securely packed atthe time of shipment and  upon arrival should be carefully inspected for damage  prior to installing the equipment at the job site  Verify  coil fins are straight  If necessary  comb fins to remove  flattened or bent fins  Claims for damage  apparent or  concealed  should be filed immediately with the 
18. rs     Time Delay Relays    Pressure Switches     Transformers       Relays   Motors        Blower Motor       Fan Motor   Components        Blower Assembly     Fan Grille        Cabinet Panels Filter Driers        Expansion Valves    11    INSTALLATION   PERFORMANCE CHECKLIST    INSTALLATION ADDRESS  ELECTRICAL SYSTEM  Electrical connections tight     Line voltage polarity correct     Rated Voltage     L1 L2 Volts     INSTALLER NAME   L1 L3 Volts     CITY    NEN L2 L3 Volts   Unit Installed Minimum clearances  YES  shown on page 3   Has the owner s information been Gee Avg  Volts   reviewed with the customer  Max  deviation of voltage  Has the Literature Package been left from avg  volts       YES NO  with the unit     96 Volt imbalance   REFRIGERATION SYSTEM    Was unit given 24 hr warm up period Blower Motor HP  _      Sheave Setting   Turns  YES NO  for crankcase heaters   Has the thermostat been calibrated        Stage 1 Liquid Pressure  high side  Is the thermostat level        Is the heat anticipator setting correct   Stage 1 Suction Pressure  low side   If Applicable   We Encourage  PROPOSITION 65 WARNING    Perm  WARNING   This productcontainschemicals known C US O   LISTED    to the state of California to cause cancer  gor o           oil    Through Technician    WARNING Thisproductcontainschemicalsknown Intertek Certification by NATE  to the state of California to cause birth defects or  other reproductive harm        Att CERTIFIED      www ahridirectory org    Uni
19. tary Small AC  AHRI Standard 210 240    Certification applies only when the complete system is listed with AHRI           AITONS          11 Nicholas Beaver Rd RR 3  Guelph  Ontario N1H 6H9 Fake  888 744 2911     info aitons com     www aitons com    Specifications  amp  illustrations subject to change  without notice or incurring obligations   09 13 709607A  Replaces 7096070   Rev  July 2014    
20. tate and national codes and regulations  and with the National Electric Code  ANSI NFPA 70   or in Canada the Canadian Electric Code Part 1 CSA  C 22 1    e Thisequipment contains liquid and gaseous refrigerant  underhigh pressure  DONOT USE ANY PORTION OF  THE CHARGE FOR PURGING OR LEAK TESTING   Installation or servicing should only be performed by  qualified trained personnel thoroughly familiar with this  type equipment        Fully annealed  refrigerant grade copper tubing should  beused wheninstallingthe system  Refrigerant suction  line tubing should be fully insulated    e Installation of equipment may require brazing  operations  Installer must comply with safety codes  and wear appropriate safety equipment  safety glasses   work gloves  fire extinguisher  etc   when performing  brazing operations         Follow all precautions in the literature  on tags  and  on labels provided with the equipment  Read and  thoroughly understand the instructions provided with  the equipment prior to performing the installation and  operational checkout of the equipment        Refrigerant and electrical      should be routed through  suitably waterproofed openings to prevent water from  leaking into the structure     AIR CONDITIONER INSTALLATION    General Information   This air conditioner is designed only for outdoor rooftop  or ground level installations  This unit has been tested for  capacity and efficiency in accordance with AHRI Standards  and will provide many years of safe a
21. tep  3  there is too little charge in the system  Add refrigerant  and repeat Steps 1 through 3 until the system is correctly  charged     Application Notes for Using the Charging Chart    This equipment s cooling system contains  refrigerant under high pressure  Always use  safe and environmentally sound methods when  handling refrigerant handling or servicing  the unit  Review the factory literature and  safety warnings prior to servicing     e When repairing system leaks  always use a nitrogen     inert  gasto protectthe refrigerant system and pressure  check the repair before re charging  Always replace  the filter dryers when performing any repair to the  refrigeration system with one capable of acid removal   After completing the repairs  evacuate the system to  350   500 microns and weigh in the refrigerant to the  amount specified on the unit rating label    The refrigerant charging chart is valid for a variety of  indoor  return air conditions and are most influenced by  the outdoor ambienttemperature  outdoor fan operation  and the unit operating voltage  Before using this chart   make sure the unit is in a stable operating mode    As shown in Figure 4  the ideal system sub cooling  can vary over the range of operation  Reference the  charts to determine the ideal amount of sub cooling for  a given liquid pressure  Units charged to other values  will not perform at the rated unit efficiency  EER  or  rated Coefficient of Performance  COP  in heating  mode    To insp
22. zed parts or accessory WIRING DIAGRAMS    kits may be used with this product  Improper Figure 3  Wiring Diagram for 1 5   4 Ton Units    8  installation  service  adjustment  or maintenance Figure 4  Wiring Diagram for 5 Ton Units    may cause explosion  fire  electrical shock or   AIR CONDITIONER MAINTENANCE  other hazardous conditions which may result        REPLACEMENT PARTS    personal injury or property damage INSTALLATION   PERFORMANCE CHECKLIST 12       IMPORTANT  ATTENTION INSTALLERS     It is your responsibility to know this product better than your customer  This includes being able to install  the product according to strict safety guidelines and instructing the customer on how to operate and  maintain the equipment for the life of the product  Safety should always be the deciding factor when  installing this product and using common sense plays an important role as well  Pay attention to all safety    warnings and any other special notes highlighted in the manual  Improper installation of the furnace or  failure to follow safety warnings could result in serious injury  death  or property damage     These instructions are primarily intended to assist qualified individuals experienced in the proper installation of  this appliance  Some local codes require licensed installation service personnel for this type of equipment  Please  read all instructions carefully before starting the installation  Return these instructions to the customer s package  for future referenc
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Vogel's PFW 950  DSS2 - TML  OpenStage 60_80 Manager, User Guide, Issue 15  Samsung Monitor FHD da 24" S24D390HL User Manual  Samsung YP-R2AS User Manual  Onguard Inspection Lamp Manual  Samsung MM-B9 manual de utilizador  Manual de instalacion ADempiere 3.6.0 LTS  INSTRUCTIONS  Guide d`installation pour le professionnel    Copyright © All rights reserved. 
   Failed to retrieve file