D400 Substation Data Manager
Contents
1. Setting Description Range Default Quality Whether or not quality information is included With Quality With Quality with this entity Descriptor Descriptor Without Quality Descriptor Per Point Settings Address The address of this entity Read only N A N A IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected DI Assigned point from the Point Picker Read only Identifier Point Name Text description of the point in the Binary Input Up to 128 Assigned IED map Based on selected DI point Read only characters point name Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Polarity Specifies whether or not a negative analog Bipolar Value Bipolar Value Threshold The initial minimum change in the analog input Oto 5 value that is required in order to produce a 1 000 000 000 spontaneous report or event High Limit The initial high limit that is required for an 1 0E 12 to 1 0E 12 analog input value to exceed in order to 1 0E 12 produce an event Low Limit The initial low limit that is required for an analog 1 0E 12 to 1 0E 12 input value to exceed in order to produce an 1 0E 12 event Packed Single Point Table 88 Packed Single Point Mapping Settings Setting Description Range Default Info Object Settings Info O
2. Setting Description Range Default Per Point Settings Address The address of this entry Read only N A N A Control Type The type of control to operate Trip Close Persistent Regulating Persistent Short Pulse The control duration in seconds of the short 1to 1000 Duration pulse output 2147483647 Long Pulse The control duration in seconds of the long 1to 2000 Duration pulse output 2147483647 Transmission The type of transmission either a select and Select and Select and Type execute command sequence or only an execute Execute Execute Source Point First of two digital input source points selected Not editable System One from the Point Picker to comprise the 4 state assigned point being monitored Based on user identifier configured DI point name prefixed with system assigned identifier Source Point Second of two digital input source points List of points N A Two selected to comprise the 4 state point being based on monitored configured Dis Single Point Table 93 Single Point Mapping Settings Setting Description Range Default Info Object Settings Info Object The name of the information object as entered N A N A Name on the New Info Object window Read only Starting The starting address of this entry 1 to 16777215 Address Interrogation The interrogation group used for reporting this Not Used Not Used Group information object Group 1 Group 16 Interrogation Specify whether to include this
3. Setting Description Range Default Primary Port Primary serial port for device 1 to 16 Incremented communications with the D400 from 1 Backup Port Secondary port for device communications 1 to 16 N A if the primary port fails The Backup port automatically takes on the settings of the associated Primary port Baud Rate The speed of information being transmitted 300 600 1200 9600 across the serial connection in bits per 2400 4800 9600 second bps 19200 38400 57600 115200 Parity A bit added to a group of bits to detect the Even None presence of an error None Odd Data Bits Number of bits used for each character 7 8 8 Stop Bits Number of bits used to indicate the end of 1 2 1 each character as it is transmitted 22 SWM0066 2 75 0 General RTS and CTS Values Some protocols may require these parameters to be configured Table 3 RTS Values GE Energy Setting Description Range Default Flow Control Specifies whether or not RTS Flow Controlis Enabled Disabled enabled Disabled Pre Trans Delay Specifies the time in milliseconds that RTS 1 to 65535 15 is asserted before data is transmitted Also known as the RTS preamble Post Trans Specifies the time in milliseconds after data 1 to 65535 15 Delay is transmitted that RTS is held asserted Also known as the RTS postamble Table 4 CTS Values Setting Description Range Default Flow Control Specif
4. Setting Description Range Default Point Number of the point in the device Analog Input 0 to 65535 Incremented Map from 0 Point Name Text description of the point in the Analog Input Up to 128 DI xxx Map characters Multiplier Scale factor of the point m of formula mx b Full range of 1 0 64 bit Float Offset Scale factor of the point b of formula mx b Full range of 0 0 64 bit Float Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 Analog Outputs Settings are available on the Analog Output tab on the Client Map tab The D400 provides the mapping settings for analog outputs as shown in Table 58 Table 58 Analog Output Mapping Settings Setting Description Range Default Point Number of the point in the Analog Output 0 to 65535 Incremented Map from O Point Name A text string that describes this point Up to 128 AO_Xxx characters Multiplier Scale Factor of a point m of formula mx b Full range of 64 1 0 bit Float Offset Scale Factor of a point b of formula mx b Full range of 64 0 0 bit Float Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 AO Variation How the point values should be reported 16 bit 32 bit 16 bit Digital Inputs Settings are available on the Digital Input tab on the Client Map tab The D400 provides the mappin
5. D400 Substation Data Manager Software Configuration Guide 33 GE Energy Setting Description Range Default Control Select Timeout The maximum allowed time in seconds between control select and control execute commands for digital and analog output points from the IEC 60870 5 101 104 master station 0 01 to 60 0 5 0 Double Point Valid Time The minimum time in seconds that both digital input points must be stable before an ON OFF state is reported Note The value of this property only applies when the corresponding parameters of a double point information object are specified as undefined Not used when set to 0 0 to 65535 500 Double Point Suppress Time The minimum time in seconds that both digital input points must be stable before an indeterminate state is reported Note The value of this property only applies when the corresponding parameters of a double point information object are specified as undefined Not used when set to 0 0 to 65535 1000 LRU Event Buffer Size The number of events non time tagged time tagged and hour update objects that are buffered by this LRU 50 to 65535 255 LRU Event Buffer Location The location where unreported events that are collected from event queues are stored RAM NVRAM RAM Event Buffer Overflow Policy Specify whether the newest or oldest events are discarded when the server event
6. Setting Description Range Default X X horizontal pixel position from the top left corner 0 to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 20 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 Font Type The type of font used to display text One of SansSerif SansSerif Serif Monospaced DialogInput Font Size The size of the font used to display text 1 to 100 11 Font Style The font style to apply to the display of text One of normal Normal bold or italic Foreground Color The color to apply to text Any 24 bit RGB Black Color Background Color The color to apply to the background Any 24 bit RGB White Color Caption Text for the object to display Text Label Text Horizontal The horizontal alignment of the text within the One of Left Center Left Alignment object s display
7. Table 72 SEL Binary Device Properties Setting Description Range Default Name Name of the device map file Up to 8 lt File name gt characters No of Targets Number of Target Rows returned by the device 0 to 255 0 in the Fast Meter command No of Breakers Number of Breakers supported by the Fast 1 to 10 0 Operate message No of Remote Number of Remote Bits supported by the Fast Oto 255 0 Bits Operate message Pulse Remote Bits If Pulsing of remote bits is supported by the Yes No Fast Operate message No No of Calculation Number of Calculation blocks returned by the Oto 4 0 Blocks Fast Meter Definition Block 86 SWM0066 2 75 0 General GE Energy Setting Description Range Default Block1 Type of calculations that is defined in Block 1 0 Standard None Calculation Type Power 1 Delta Power 2 Voltages Only 3 Currents Only 4 Single Phase None Block2 Type of calculations that is defined in Block 2 Oto4 None Calculation Type None Block3 Type of calculations that is defined in Block 3 Oto4 None Calculation Type None Block4 Type of calculations that is defined in Block 4 Oto4 None Calculation Type None MODBUS Client The MODBUS Client map defines how the D400 is configured to poll data from MODBUS devices The D400 supports the following configurable MODBUS data types e Read Coil Status status of coils e Read Input
8. GE Energy gt gt gt gt GE Energy can issue a batch license file which contains licenses for multiple D400 units This is useful when licensing features across many D400 units or when licensing several applications on one D400 unit 1 Start a terminal session and log into the D400 2 Connect a USB drive containing the D400 batch license file 3 Atthe prompt enter the following commands cd home D400_APPS swlic batch The tool locates the license file and licenses all applicable features for the current D400 Repeat steps 1 to 3 for each remaining D400 unit To view detailed information on your D400 license 1 Start a terminal session and log into the D400 2 Atthe prompt enter the following commands cd home D400_APPS swlic report The application output shows the D400 ownership information and a list of available features Each item under Application License represents an application or feature that can be licensed They are shown in the format 3 digit application ID number Description of feature License status There are four possible license statuses Unlocked The feature has been licensed and is available for use Trial Disabled A trial license is available for this feature To enable see the instructions below Trial Enabled The feature is available for use under a temporary trial license The Expires YYYY MM DD license will expire on the date shown Disabled A trial licen
9. Open Raise Lower Control Interface User Specified URL in Same Window User Specified URL in New Window URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load for actions of type Any valid URL None User Specified URL in Same Window or User address Specified URL in New Window D400 Substation Data Manager Software Configuration Guide 145 GE Energy Setting Description Range Default Object Identifier f Action Type is Open Analog Set Point Interface Object Identifier None object identifier must belong to an Analog Set Point Object f Action Type is Open Digital Control Interface object identifier must belong to a Digital Control Object f Action Type is Open Raise Lower Control nterface object identifier must belong to a Raise Lower Control Object Otherwise Object Identifier shall be empty Table 132 Capacitor Object Settings Setting Description Range Default x X horizontal pixel position from th
10. Table 70 Peak Demand Analog Outputs Setting Description Range Default Name Text description of the point in the Peak Demand Up to 128 PDA_Xxx Analog Channel Map characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float D400 Substation Data Manager Software Configuration Guide 85 GE Energy Setting Description Range Default Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float SER Digital Channel Settings are available on the SER Digital Channel tab on the Client Map tab The D400 provides the mapping settings for SER digital inputs Function code 5 as shown in Table 71 Table 71 SER Digital Input Settings Setting Description Range Default Point Name A text string that describes this point Up to 128 SER_Xxxx characters Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 OFF State Name_ Text description of the 0 state Up to 32 OFF characters ON State Name _ Text description of the 1 state Up to 32 ON characters Device Properties Settings are available in the Device Properties pane on the Client Map tab Table 72 lists the poll specific settings for the SEL Fast Meter device
11. 5 6 7 8 9 Enter Your Choice Between 1 and 9 i Configure TELNET Service Enable or disable access to the D400 through the TELNET protocol Configure FTP Service Enable to disable access to the D400 through the FTP protocol Note When transferring files to and from the D400 you may receive file permission errors Disable permission change error reporting in your file transfer utility to prevent these messages from appearing Configure SSH Service Enable or disable access to the D400 through the SSH protocol Configure SFTP Service Enable or disable access to the D400 through the Secure FTP protocol Note When transferring files to and from the D400 you may receive file permission errors Disable permission change error reporting in your file transfer utility to prevent these messages from appearing Configure Web Mode Select if users can access the D400 web interface through an HTTP connection or if users should be redirected to an HTTPS connection Configure Emergency Access Ports By default the root user cannot access the D400 remotely Instead this account can only be used to access the D400 locally through one of the configured emergency access ports D400 Substation Data Manager Software Configuration Guide 177 GE Energy Configure Administrator Only Logins Select if access to command line utilities is restricted to Administrator level users or not By default this option is enabled
12. pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 40 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 Rotation Angle of clockwise rotation in degrees to apply to 0 90 180 270 0 the image File Path File path of image to display Any existing server None side image file URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load when a user selects Any valid URL None the object address 154 swm0066 2 75 0 General Table 139 Label Object Settings GE Energy
13. 3 2 Network Cone ctions ceessesssecssscssssssessececceeceeescseesee 47 4 Configuring Devices 56 4 1 Configuration Overview uun eeccssssssseessscccsssssssneeesseeesee 56 wes CIEMEMODS cstv cdl 57 43 IEC 608 70 5 1014104 ninesini 58 AA VEE 608 7025 105 iiinn 68 G5 DNPS CUO iar I A ANEA 74 D400 Substation Data Manager Software Configuration Guide 3 GE Energy 4 SWM0066 2 75 0 General AG NEC61850 CUM enian inmin 80 G7 Hydran Client eseas 80 48 SEL BIOs Seni a EA ER 83 4 9 MODBUS Clie t iaa 87 5 Configuring Masters 93 5 1 Configuration Overview eeeecssccsssssssssseseeeesseesssnsees 94 52 SEnve Mipira ieie Nn 94 5 3 IEC 60870 5 101 104 ona ccssccssccceccsseossonnnnsonsastecseees 95 BAS DNP SEVE teinana 109 9 5 MODBUS SEVEN nesasioeeininniarn nia 116 6 Configuring D400 Automation Applications 123 6 1 6 2 63 gt COICO Ncercsccstscteeecct cemuscstnaecananniec eectibaslentacds 133 6 4 LOgicLinx Optional 134 6 5 D400 Redundancy MANgQel sssssssscsssesssnes 135 7 Creating One Line Diagrams 137 7 1 Drawing OvervieW eeccccssssseeccsssssteesccesssteccecssneeees 137 Te Types OF Objects ii ison cian Menon 139 7 3 Object Configuration Settings 142 8 System Utilities 170 8 1 Utilities Overview ssssssesssssessssssessesssrsstsseeseesessse 170 8 2 Setting up a Terminal Session ss s 11511121 171 8 3 D400 Configuration Utility cscs 171 g4 PPP DAHIN oE 185 8 5 Pass Throu
14. Inter Poll Delay Delay in millisections between polls 0 to 999 100 Reconnect Interval Time in seconds between attempts by the 1 to 3600 10 D400 to bring an offline device online Endian Type Endian data interpretation in the map file Little Big Big Max Block Size The maximum block size in bits of MODBUS 0 to 255 255 requests Request Retry The number of retries for each request 1to 255 10 Count Fast to Slow Poll Number of fast poll cycles before a slow poll 0 to 255 10 Cycle Frequency cycle is initiated Fault Reset Time Time in seconds for which the fault parameter O to 3600 5 pseudo points retain values from the latest fault Restrike Interval Once the first fault has occurred the time to 0 to 3600 30 wait in seconds before updating the Fault Pseudo points with information if subsequent faults occur before this interval has elapsed PRF Processing The PRF processing type to use Pre defined list None Type of types Response Timeout The number of retries attempted before the 100 to 65535 2000 device is assumed to be offline 92 SWM0066 2 75 0 General GE Energy Configuring Masters You can customize the D400 to transmit the necessary data from Intelligent Electronic Devices IEDs to master stations Server applications in the D400 allow the D400 to retrieve selected data from event queues and the real time database and send the data to the master station according to the how the SCADA pr
15. Low Range Color The color to apply to the background but only when Any 24 bit RGB Red the real time value is less than the configured Low Color Range Value Low Range Value The value which when the real time value is lower Any 64 bit floating 0 shall result in the background being displayed with point value the Low Range Color D400 Substation Data Manager Software Configuration Guide 163 GE Energy Setting Description Range Default High Range Value The value which when the real time value is higher Any 64 bit floating 0 shall result in the background being displayed with point value the High Range Color Text Horizontal The horizontal alignment of the value displayed as One of Left Center Left Alignment text within the object s display area or Right Table 145 Reactor Object Settings Setting Description Range Default x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 40 the object height Width Pixel width of the rectangular are
16. Mgetty d400getty none ttyS1 TELNET d400telnet none 23 FTP d400ftp none 21 SSH d400sshd none 22 SFTP d400sshd none 22 Terminal Server d400terminalserver none lt Port Number gt Pass through d400passthrough none lt Port Number gt D400 Substation Data Manager Software Configuration Guide 207 GE Energy Modification Record Version Rev Date Author Change Description 1 00 0 July 31 2007 S Tessari Document created 1 00 1 Nov 14 2007 M Haska Updated Table 62 Bug 3673 added note regarding upgrade availability changed DNP to DNP3 throughout 1 00 2 Dec 4 2007 M Haska Documented new d400cfg options Feb 6 2008 M Haska Added LogicLinx MODBUS Client Hydran Client MODBUS Server pass through connections April 30 2008 M Haska Documented licensing tools rewrote serial connections chapter updated serial and network connections sections 2 00 0 June 5 2008 M Haska Updated configuration parameters for DNP3 protocol throughout June 17 2008 M Haska Revised Calculator section for new GUI 2 20 0 September 16 2008 M Haska Updated Serial DNP Master Stations for multiple LRU 2 50 0 October 21 2008 M Haska Added Redundancy Manager Configuration Manager IP Changer and System Status Manager Updated d400cfg section on network interfaces 2 60 0 Dec 2 2008 M Haska Addition of IEC 60870 5 101 103 client protocols 2 70 0 Jan 26 2009 M Haska Addit
17. Normal bold or italic 0066 2 75 0 Genera GE Energy Setting Description Range Default Foreground Color The color to apply to text Any 24 bit RGB Black color Text Horizontal The horizontal alignment of the text within the One of Left Center Left Alignment object s display area or Right Text Vertical The vertical alignment of the text within the object s One of Bottom or Bottom Alignment display area Top Alarm Behavior Defines blinking display characteristics of the alarm One of Blink Text or Blink Border box Blink Border Normal State Text Defines the text to display in the Alarm Box when its Text None corresponding Alarm is in normal state Alarm State Text Defines the text to display in the Alarm Box when its Text None corresponding Alarm is in alarm state Normal Defines the background color to display in the Alarm Any 24 bit RGB Green Background Color Box when its corresponding Alarm is in normal state color Alarm Background Defines the background color to display in the Alarm Any 24 bit RGB Red Color Box when its corresponding Alarm is in alarm state color Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object color Border Type Defines the type of border to display Oto 255 0 Border Width Defines the pixel width of the border 1to7 4 Ackn
18. Oor1 1 2 True State TT Color The background color to display when the digital Any 24 bit RGB Red input 1 value low bit corresponds to the true state Color and the digital input 2 value high bit corresponds to the true state TF Color The background color to display when the digital Any 24 bit RGB Red input 1 value low bit corresponds to the false state Color and the digital input 2 value high bit corresponds to the true state FT Color The background color to display when the digital Any 24 bit RGB Red input 1 value low bit corresponds to the true state Color and the digital input 2 value high bit corresponds to the false state FF Color The background color to display when the digital Any 24 bit RGB Red input 1 value low bit corresponds to the false state Color and the digital input 2 value high bit corresponds to the false state D400 Substation Data Manager Software Configuration Guide 147 GE Energy Table 134 Digital Control Object Settings Setting Description Range Default Primary Output Point identifier of a digital output point where the Existing digital None Point Identifier identifier consists of the device name and point output point descriptor identifier Function Code The protocol function code to pass as part of the One of Direct None digital control command sent to a device Operate Direct Operate with No Acknowledgement Select Before Operate Sele
19. Orientation Whether to draw the object transformer windings in Horizontal or Horizontal a horizontal or vertical orientation Vertical Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 D400 Substation Data Manager Software Configuration Guide 167 GE Energy Setting Description Range Default Number of Defines the number of transformer windings to 2or3 2 Windings include in the object Winding 1 Line Line width of the first winding in pixels 1 to 100 1 Width Winding 1 Line Line color of the first winding Any 24 bit RGB Black Color Color Winding 2 Line Line width of the second winding in pixels 1 to 100 1 Width Winding 2 Line Line color of the second winding Any 24 bit RGB Black Color Color Winding 3 Line f Number of Windings are Configured as 3 Line 1 to 100 1 Width width of the third winding in pixels Winding 3 Line f Number of Windings are Configured as 3 Line Any 24 bit RGB Black Color color of the third winding Color Load Tap Changer Line width of the load tap changer arrow 1 to 100 1 Line Width Load Tap Changer Line color of the load tap changer arrow Any 24 bit RGB Black Line Color Color Load Tap Changer Defines which winding to draw the load tap chang
20. This can be useful in situations where your remote authentication server is temporarily unavailable You can only create an emergency access code when you are logged in as the root user and you must be connected to the D400 through one of the configured emergency access ports refer to Configure Secure Access on p 176 To generate an emergency access code 1 Start a terminal session through one of the configured emergency access ports 2 Log into the D400 using the root account 3 Atthe prompt enter the following commands cd home D400_APPS emergencyaccess gen An emergency access code is generated and displayed on screen This code remains valid for five minutes after being created or until someone logs in with it The emergency access code can only be used to log into the HMI of your D400 you cannot use it connect to command line services like TELNET or SSH To manually clear an emergency access code that has been generated 1 Start a terminal session through one of the configured emergency access ports 2 Log into the D400 using the root account 3 Atthe prompt enter the following commands cd home D400_APPS emergencyaccess clear D400 Substation Data Manager Software Configuration Guide 191 GE Energy The emergency access code is cleared from the system and the standard HMI login screen is displayed again Note Emergency access codes are automatically cleared by the D400 immediately after being used or fiv
21. To link to another drawing type in the correct file name note that all One Line Designer files are saved with a dot extension of dra which must be typed as part of the filename Likewise to link to a web page type in the full web address such as http www ge coml In this manner you may actually create complex interlinked drawings This enables someone viewing a particular file to go to a different diagram that may provide further detail Should a user want to know more readings associated with a particular device clicking on that device image launches him or her into another diagram that has been created to provide such magnified detail D400 Substation Data Manager Software Configuration Guide 139 GE Energy E i Line Use this tool to create a one dimensional line The properties associated with this object allow you to alter the type of line dotted or bold and whether arrowheads are included at either the start or end of the line but not on both ends Rectangle This tool allows you to create a four sided box of any size You can modify the color of the border and the fill the border type and thickness and the URL Anchor for linking to another drawing Ellipse This tool allows you to create a round object of any dimension You can modify the color of the border and the fill the border type and thickness and the URL Anchor for linking to another drawing Image This tool allows you to place an image on the drawin
22. You can set the password of this account using the D400 configuration utility Password aging requires the following settings e Maximum number of days the password will be valid for e Number of days to warn the user before a password change is required e Date on which accounts except administrator will expire if account expiration is enabled e f account expiration is enabled Set to O to disable Pass through Authentication Allows you to enable or disable pass through authentication When authentication is enabled a valid username and password is required to access client applications through pass through ports Enabled by default Administrator Group Users Allows you to create administrator level users if you are using local authentication mode and to change details associated with existing administrator user accounts Configure Network Settings The Network Settings menu includes optional settings for the D400 network interface Note The D400 must be rebooted to activate changed network settings 174 swm0066 2 75 0 General GE Energy lox l D400 Configuration Utility Menu Network Settings 1 Current Settings 2 Configure DHCP Server 3 Enable Port Forwarding 4 Enable ICMP Echo 5 Configure Machine Host Name 6 Back Enter Your Choice Between 1 and 6 i DHCP Server Allows the D400 to act as a DHCP Server Following settings are available for customization e Ethernet Interface ethO a
23. as compared to the configured bar scaling value If set to left the highlighted area shall rise horizontally to the right being filled from its left edge to the right ending at a vertical line that corresponds to the percentage of the real time value as compared to the configured bar scaling value If set to right the highlighted area shall rise horizontally to the left being filled from its right edge to the left ending at a vertical line that corresponds to the percentage of the real time value as compared to the configured bar scaling value URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load when a user selects Any valid URL None the object address 160 swm0066 2 75 0 General Table 143 Range Aware Line Object Settings GE Energy Setting Description Range Default Object Identifier 1 Object Identifier of one of three Analog Status Existing Analog None objects Status Object Identifier Object Identifier 2 Object Identifier of one of three Anal
24. where each alarm point is uniquely linked with one digital input point for a 2 state alarm or two digital input points for a 4 state alarm in the system point database based on the configured alarm point s alarm type Points selected for an Alarm Four State type can be contiguous or non contiguous points in the same device or across two different devices To configure alarm points e Onthe Alarm Points Configuration tab select and configure points from the Point Picker for each alarm type Absolute Alarms On Update Alarms Four State Alarms Settings are available on the Absolute Alarms On Update Alarms Four State Alarms tabs respectively The D400 provides the alarm configuration settings as listed in Table 115 Table 116 and Table 117 D400 Substation Data Manager Software Configuration Guide 125 GE Energy Note To clearly distinguish alarms on the Active Alarms page it is highly recommended to configure alarms with a unique combination of Line ID Device ID and Alarm name The Automatically create unique alarm point names option on the Global settings tab assists in alarm point naming by prefixing alarm points with a unique identifier See Table 122 Table 115 Absolute Alarms Settings Alarm Name Text description of the alarmable point as it will be Up to 100 DI source displayed in the Active Alarms page It defaults to the alphanumeric Point name name of the source point characters Source Point DI source po
25. 0 0 Remote Hosts connect to the D400 If all are set to 0 0 0 0 all addresses hosts will be able to connect Application Parameters For instance specific DNP3 Server application settings see DNP3 Server Application Parameters in section 3 1 Serial Connections The communication settings in Table 7 and Table 8 are available on every instance of the server application For instance specific Modbus Server application settings see Modbus Server Application Settings in section 3 1 Serial Connections The communication settings in Table 19 are available on every instance of the server application For instance specific IEC 60870 5 101 Server application settings see EC 60870 5 101 Master Station Application Settings in section 3 1 Serial Connections The communication settings in Table 13 are available on every instance of the server application IEC 60870 5 104 IED Block The following settings are used when configuring an IEC 60870 5 104 IED block Table 29 IEC 60870 5 104 IED Block Setting Description Range Default Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots D400 Substation Data Manager Software Configuration Guide 49 GE Energy Setting Description Range Default Application Select the application parameters defining Use
26. 2 75 0 General GE Energy 3 1 Serial Connections You can configure up to 16 serial connections These connections can be one of the following e Point to Point Device e Multi drop Device e Serial Master Station Each serial port can be assigned a single device protocol client application for device communications Serial Connection Redundancy Communications that take place over a serial connection can be configured for redundancy by setting up two Serial ports a primary port and a secondary back up port Communications will normally take place over the primary port In the event of a loss of communication with the device over the primary port the D400 will try to re establish communication over the secondary port Multi Drop Some devices support a daisy chain connection in which multiple devices are wired together from one to the other A multi drop configuration requires additional configuration to set up each individual device on a multi drop connection SCADA Communications The D400 supports serial connections to SCADA masters through up to four serial ports Each serial port can be assigned a single SCADA protocol server application for master station communications The D400 currently supports serial master communications using the DNP3 and Modbus server protocols Other Connections Connections for a serial line printer a terminal server and a LogicLinx device can be configured Adding a Serial Co
27. ASC Device X associated with this serial connection characters Bay ID Text description to identify the bay area 1 to 32 ASC Bay X associated with this serial connection characters IED Address Protocol address of the device i e DNP3 0 to 65519 Xx device address Map File Name of the Client map file to be used with List of user N A the specific device configured client map files Enable on Start Indicates if communication to the device Disabled Disabled Up automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Password For devices that require a password to 1 to 32 ASCII N A access information characters Single SEL Binary The Schweitzer Engineering Laboratories SEL Binary protocol supports exchanging information with SEL Fast Meter metering and relay devices over a serial link It also supports pass through connection to the device SEL Binary Client Application Parameters SEL Binary Client application settings are available under the Application Parameters field Table 25 SEL Binary Client Application Parameters Setting Description Range Default Wait Between Duration in seconds to wait to transmit a 0 to 60 00 0 1 Messages new message after a response to the previous message has been received Wait Between Duration in seconds to wait to begin a new O to 60 00 0 Cycles cycle of collecting data points after the pervious one was complete Respons
28. Analogs registers upon receiving the Preset Single No Register or Preset Multiple Register command with an Exception code 4 in the response If disabled the D400 reports the value of the offline registers as 0 Modbus Multi drop The following settings are used when configuring a Modbus Multi drop connection Table 20 Modbus Multi drop Setting Description Range Default Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Line ID Text description to identify the electrical 1 to 32 ASCII Line X transmission line associated with this serial characters connection Device ID Text description to identify the device 1 to 32 ASCII Device X associated with this serial connection characters Bay ID Text description to identify the bay area 1 to 32 ASCII Bay X associated with this serial connection characters IED Address Protocol address of the device i e DNP3 0 to 65519 X device address Map File Name of the Client map file to be used with List of user N A the specific device configured client map files Enable on Start Indicates if communication to the device Disabled Disabled Up automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Printer Device The following settings are used when connecting a printer device To print
29. Command Setpoint Command Single Command An identifier used within the configuration interface Info Object Name 1 to 128 ASCII characters Address The assigned address for BitString and Packed Single Point types the starting default address for all other types 1to 16777215 62 SWM0066 2 75 0 General GE Energy The table directly below the Info Object type drop down menu shows the configured Info Object Name and either the Address or Starting Address of the selected information object When Bitstring or Packed Single Point types are selected the Address value indicates the actual information object address If any other Info Object type is selected the Starting Address value indicates the default starting address that will be used when a new information object element is added The Info Object Name field in this table cannot be edited Bitstring Table 37 Bitstring Element Settings Setting Description Range Default Bit Position The bit position within the DI point 1 to 32 Incremented from 1 Point Name Text description of the point in the map file Up to 128 lt Info object characters name gt X ON State Text description of the 1 state Up to 32 ON characters OFF State Text description of the O state Up to 32 OFF characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Double
30. D400 units and the RS232 switch panel It also controls synchronization of quality and non pseudo accumulator point data Operational States The D400 Redundancy Manager supervises the operational state and state transitions of the D400 units The following states are possible Table 123 D400 Redundancy Manager Operational States State Description Active The unit is active and performing all the standard functions of a D400 Standby The unit is connected to another D400 unit that is in active mode and is ready to assume active mode in the event of a failure of the other D400 unit or a manual change over request Non redundant The D400 is placed in this mode when redundancy is disabled through the d400cfg utility or when a configuration error is detected In this state the D400 ignores the RS232 switch panel and the other D400 unit All redundancy related system points and functions are disabled Failed The D400 has entered an unrecoverable state and all software functions have been suspended The unit must be serviced or restarted to restore functionality Service During service mode D400 units do not accept change over requests This mode is used to allow time for the D400 to re initialize following a restart or system configuration change System Points When running in active mode the application provides indications through the following digital input system points Table 124 D400 Redundancy
31. Default Use Default Parameters this connection The default parameters can Use Custom be used or a custom configuration can be created Refer to IEC 60870 5 104 IED Block Application Settings Line ID Text description to identify the electrical 1 to 32 ASCII Line X transmission line associated with this serial characters connection Device ID Text description to identify the device 1 to 32 ASCII Device X associated with this serial connection characters Bay ID Text description to identify the bay area 1 to 32 ASCII Bay X associated with this serial connection characters Common The device s common address of ASDU Oto 254 1 Address of ASDU Map File Name of the Client map file to be used with List of user N A the specific device configured client map files IP Address IP address of the device Single IP address 0 0 0 0 Backup IP Redundant backup IP address of the device Single IP address Blank Address Network Port The port number on which the device will 0 to 65535 2404 communicate Transport Layer Whether to use TCP or UDP network Non editable TCP protocol Enable on Start Indicates if communication to the device Enabled Disabled Up automatically starts when the configuration Disabled is changed and reloaded or when the D400 re boots IEC 60870 5 104 IED Block Application Settings IEC 60870 5 104 settings are available under the Application Parameters field Table 30 IEC 60870 5 104 IED Block Application Paramete
32. Device ID Text description to identify the device 1 to 32 ASCII Device X associated with this serial connection characters Bay ID Text description to identify the bay area 1 to 32 ASCII Bay X associated with this serial connection characters Common The device s common address of ASDU 1 to 65534 1 Address of ASDU Link Address The link address of the device 0 to 65535 1 Map File Name of the Client map file to be used with List of user N A the specific device configured client map files Enable on Start Indicates if communication to the device Disabled Disabled Up automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots IEC 60870 5 101 Multi drop Application Settings IEC 60870 5 101 settings are available under the Application Parameters field Table 15 IEC 60870 5 101 Multi drop Application Parameters Setting Description Range Default Application Tab Number of The number of message buffers allocated by 1 to 65535 5 Message Buffers the application used to receive messages and to transmit requests to the remote devices D400 Substation Data Manager Software Configuration Guide 37 GE Energy Setting Description Range Default Restart Delay The delay in seconds between each device 0 0 to 3600 0 0 0 restart sequence at application start up Stagger General Specifies whether or not G
33. Energy Setting Description Range Default Secondary Output Enabled Whether to enable a secondary output point or not When a primary output exists but a secondary is not enabled an on and off control state are both associated with the primary output point Setting a control state to on or off has the result of executing the configured control code on the primary output point When a primary output and a secondary output is enabled then the on control state must be assigned to only one of them and the off control state must be assigned to the other output Setting a control state to on or off in this case has the result of executing the configured control code on either the primary or secondary output point but never both True or False False Secondary Output Point Identifier If Secondary Output Enabled set to True point identifier of a digital output point where the identifier consists of the device name and point descriptor Existing digital output point identifier None Secondary Pulse On Time If Secondary Output Enabled set to True secondary control pulse on time in milliseconds applies only to Control Codes of type Pulse On Pulse Off Trip or Close 0 to 65535 Secondary Pulse Off Time If Secondary Output Enabled set to True secondary control pulse off time in milliseconds applies only to Control Codes of type Pulse On Pulse Off Trip or Close 0 to 65535 Second
34. Fail Count Number of consecutive failed requests the DNP3 client must see before it attempts to establish communications on the Backup Port 1 to 300 Device Offline Fail Count Number of consecutive failed requests to a device before the RTDB points is marked offline 1 to 300 Enable Concurrent Polling Concurrent polling is currently not supported False False Wait Between Messages Time in seconds to wait between two consecutive messages sent on the serial port 0 to 60 0 0 D400 Substation Data Manager Software Configuration Guide 31 GE Energy Setting Description Range Default Response Timeout Time in seconds to wait for an application layer response before deciding it has failed Set the value higher for a dial up modem connection i e 40 0 to 60 Hydran Multi drop The following settings are used when configuring a Hydran Multi drop connection Table 11 Hydran Multi drop Setting Description Range Default Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Line ID Text description to identify the electrical 1 to 32 ASCII Line X transmission line associated with this serial characters connection Device ID Text description to identify the device 1 to 32 ASCI
35. False False Never send Enable Unsolicited Disable True Send Disable Unsolicited at startup and True False Unsolicited in response to ANY UR False False Never send Disable Unsolicited Feedback Poll AO When the LOCAL IIN bit is asserted in the True False device poll for Analog Outputs False Feedback Poll DO When the LOCAL IIN bit is asserted in the True True device poll for Digital Outputs False Feedback Poll When the LOCAL IIN bit is asserted in the True False Events device poll for Class 1 2 3 data False Override Control When an Override is configured ignore the None None Type Control Type propagated by the system point Direct Operate database Thot is always send the control type configured for this setting Pree O DErOrE No ACK SBO Remote True Send Accumulator commands to the True True Accumulators device False False Perform accumulator operations in the system point database Link Check Enable True Periodically send Link Status messages True True to the device to check connection False D400 Substation Data Manager Software Configuration Guide 77 GE Energy Setting Description Range Default Link Check If Connection Check is enabled send a Link 30 to 36000 3600 Timeout Status message to the device after this time out interval in seconds has elapsed since a message was last received from the device Enable Extended True Send the Extended Digital
36. Guide 109 GE Energy Analog Inputs Settings are available on the Analog Inputs tab The default property values are defined in the lower pane The D400 provides the mapping settings for analog inputs as shown in Table 95 Table 95 Analog Input Mapping Settings Setting Description Range Default Index Point Index 0 Based Each point index number 0 to 65535 Incremented must be unique from 0 IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected Al Assigned point from the Point Picker Read only Identifier Point Name Text description of the point in the Analog Input Up to 128 Assigned IED map Based on selected Al point Read only characters point name Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Dead Band Minimum change in the Al point value that 0 to 65535 User selected constitutes an event A value of 0 disables event Default generation for the point Static Variation How the point values should be reported 32 Bit User selected 16 Bit Default 32 Bit w o flag 16 Bit w o flag 32 Bit Float Event Variation Indicates how an event on this point should be reported 32 Bit with Time 32 Bit without Time 16 Bit with Time 16 Bit without Time 32 Bit Float with Time 32 Bit Float without Time User selec
37. Modbus Master Station Table 18 Modbus Master Station Setting Description Range Default Name Text description to identify the master 1 to 32 ASCII MASTERX station being connected to characters Master Station DNP3 address of the server application 0 to 65519 Xx Address instance Map File Name of the Client map file to be used with List of user N A the specific device configured client map files Application Select the application parameters defining Use Default Use Default Parameters this connection The default parameters can Create New be used or a custom configuration can be created Refer to Modbus Server Application Settings Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots D400 Substation Data Manager Software Configuration Guide 41 GE Energy Modbus Server Application Settings Modbus Server settings are available under the Application Parameters field Table 19 Modbus Server Application Parameters Setting Description Range Default NACK Offline If enabled the D400 will NACK the offline Yes No Digitals coils upon receiving the Force Single Coil or No Force Multiple Coils command with an Exception code 4 in the response If disabled the D400 reports the offline coil with the value OFF NACK Offline If enabled the D400 will NACK the offline Yes No
38. Number of times to consecutively repeat a control 1 to 255 1 code applying the pulse on and pulse off times to each control pulse repetition A value of 1 means to issue the control code once e g no repetition Secondary Output Whether to enable a secondary output point or not True or False False Enabled When a primary output exists but a secondary is not enabled a raise and lower control state are both associated with the primary output point Setting a control state to raise or lower has the result of executing the configured control code on the primary output point When a primary output and a secondary output is enabled then the raise control state must be assigned to only one of them and the lower control state must be assigned to the other output Setting a control state to raise or lower in this case has the result of executing the configured control code on either the primary or secondary output point but never both Secondary Output If Secondary Output Enabled set to True point Existing digital None Point Identifier identifier of a digital output point where the identifier output point consists of the device name and point descriptor identifier Secondary Pulse If Secondary Output Enabled set to True secondary O to 65535 0 On Time control pulse on time in milliseconds Secondary Pulse If Secondary Output Enabled set to True secondary O to 65535 0 Off Time control pulse off time in milliseconds D400 Substation Data M
39. ON State Text description of the 1 state Up to 32 ON characters OFF State Text description of the O state Up to 32 OFF characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Setpoint Command Table 44 Setpoint Command Type 2 Element Settings Setting Description Range Default Address The address of this information object 1 to 16777215 Incremented element by 1 from starting address Point Name Text description of the point in the map file Up to 128 SC X characters Conversion The type of setpoint command There are 3 Normalized Normalized possible types Scaled e Normalized value is between 1 and ShortFP 1 2 15 e Scaled value is scaled using multiplier and offset to 2 15 to 2415 1 e Short Floating Point value is a 32 bit floating point Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 66 SWM0066 2 75 0 General Single Command Table 45 Single Command Element Settings GE Energy Setting Description Range Default Address The address of this information object 1 to 16777215 Incremented element by 1 from starting address Point Na
40. Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 Rotation Angle of clockwise rotation in degrees to apply to 0 90 180 270 0 the image File Path File path of alternate non default image to display Any existing server None side image file URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load when a user selects Any valid URL None the object address D400 Substation Data Manager Software Configuration Guide 153 GE Energy Table 138 Image Object Settings Setting Description Range Default x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical
41. Point group to which the point belongs List of defined Group assigned point groups to ID number 0 Read Holding Register Settings are available on the Read Holding Register tab on the Client Map tab The D400 provides mapping settings for read holding register points as shown in Table 75 Table 75 Read Holding Register Settings Setting Description Range Default Point Number A unique identifying number in the register map O to 65535 x Point Name A text string that describes this point Up to 128 Holding Register characters XXX Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Poll Type The type of poll to be taken of the point See Table 64 Fast Data Type The type of data polled See Table 76 UINT16 ASCII Size ASCII size in bits when a text string is being 0 to 99 0 retrieved from the device If this field is set to 0 the register does not contain ASCII data Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 Table 76 lists the available data types for MODBUS Client points D400 Substation Data Manager Software Configuration Guide 89 GE Energy Table 76 Supported Data Types Data Type Description NT8 8 bit signed i
42. SWM0066 2 75 0 General GE Energy Setting Description Range Default Map File Name of the Client map file to be used with List of user N A the specific device configured client map files Application Select the application parameters defining Use Default Use Default Parameters this connection The default parameters can Create New be used or a custom configuration can be created Refer to DNP3 Server Application Parameters Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Multiple Logical Remote Units LRU You can configure multiple logical remote units on a single or redundant serial connection This allows a remote DNP3 master station to communicate with multiple logical remote units within a physical D400 unit using a single serial link You can use multiple LRU functionality to test a system configuration without needing to connect to multiple physical devices Figure 5 Multiple LRU Overview DNP3 Master Station Multiple Remote Devices DNP3 Master Station D400 with Multiple LRUs D400 To add an LRU to communicate over a serial link with a DNP3 Master Station click the Add button under Configuration Parameters and configure the row In the example below a DN
43. Set on the device Pending 1 DisableDevice This control disables or enables communications Disabled 1 to the IED If disabled the application shall not Enabled 0 have an open association with the device nor Ngo accept user requests for the device Enable Polling of IED This control disables or enables data set retrieval Disabled 0 from the device but leaves the association up Enabled 1 and does not prevent other controls such as nae Retrieve all Data Sets or Force to Alternate Channel The application will also disable all Report Control Blocks when this control is disabled Force IED to Alternate This control forces the device to the alternate Completed 0 Channel communications channel Pending 1 194 swm0066 2 75 0 General Table 154 IEC 61850 Application Per Device Digital Input GE Energy Name Description DI State Set to Primary Channel Health Indicates health of primary communications Failed 0 channel If primary channel is in use Normal health means the association is up If primary Normal 1 channel is not in use Normal health means an association is possible on this channel Failed health means the last association attempt failed Secondary Channel Indicates health of secondary communications Failed 0 Health channel If secondary channel is in use Normal N w health means the association is up If secondary Preg channel is not in
44. Status digital input data e Read Holding Register holding registers of the device e Read Input Register input registers of the device e Write Single Coil set a single output to either ON or OFF in the device e Write Single Register 6A set a single holding register in the device value required e Write Single Register 6B set a single holding register in the device value optional MODBUS Client map settings are available on the Client Map tab when a MODBUS protocol device type is selected D400 Substation Data Manager Software Configuration Guide 87 GE Energy Figure 10 MODBUS Client Map Page D400 Configuration Mozilla Firefox De Eat yew Hgtory e Commit Changes Discard Changes Serial vow Beckmarts Toos Heb Er S25 8 8 212 2 Network Client Map Server Map Alarm Calculator System wide Topan PEIEE Read input Status Read Holding Register Read Inout Register Write Single Coll Write Single Register GA Write Single Register 66 User Management Point Number Please specifiy which Digital Inputs you would like to collect for Function Code 1 tk Point Name OFF State ON State Poll Type Map File s1760 xmi 0 Dt Points Reconnect interval Endan Type Max Block Sze Add Point Group Anter Pow Delay Delay between polls im HMI Access Manager OneLine Designer millneconds NUM Applet GenmiagCont started Read Coil Status Settings
45. The control commands that the IED will accept Latch ON OFF Latch ON OFF Pulse ON OFF TRIP CLOSE Function Code The protocol function code to pass as part of Select Before Select Before the digital control command sent to a device Operate Operate Direct Operate Count Number of times to consecutively repeat a 1 to 255 1 control code applying the pulse on and pulse off times to each control pulse repetition applies only to Control Codes of type Pulse On Pulse Off Trip or Close On Time Duration in milliseconds of an ON pulse 0 to 65535 0 Off Time Duration in milliseconds of an OFF pulse 0 to 65535 0 Property settings are available in the lower pane of the Coils tab The configuration settings defined in Table 107 are used to configure the default values for all coils defined in the MODBUS server map Table 107 Coil Properties Setting Description Range Default Default Control See Table 108 Spec Default If set to Self the values of the DO points are Self Self Feedback Opt returned If set to Digital Inputs the value ofthe pigitalinput Digital Input point is returned Default Invert Select if the value of the mapped points should True or False False be inverted by default Table 108 Default Control Specification Properties Setting Description Range Default Default Control The control commands that the IED will accept Latch ON OFF Latch ON OFF Code by default Pulse ON OFF TRIP CLOSE Default Function Code The default p
46. This setting restricts access to the following services e Login e SSH e SFTP e Telnet e FTP e getty e mgetty Note The root user is not able to access these services at any time unless it is through one of the configured emergency access ports Configure Host Names The Configure Host Names menu allows you to assign a host name to your D400 and to view add and delete entries in the hosts file Note The D400 will only allow you to enter IPV4 addresses of 3 84 167 235 PuTTY i idd a new Host 2 Delete a Host 3 Modify a Host 4 Delete all Hosts 5 View all Hosts 6 Back Enter Your Choice Between 1 and 6 i Add a New Host This option prompts you to add a host name and IP address to the hosts file Delete a Host Provides you with a list of configured hosts Select an item number to delete the associated host entry 178 swm0066 2 75 0 General GE Energy Modify a Host Provides you with a list of configured hosts Select an item number to modify the associated host name and IP address Press Enter to use the previously entered value Delete all Hosts This option will remove all entries from the hosts file View all Hosts Provides you with a list of configured hosts Configure Time Synchronization The Configure Time Synchronization menu allows you set the D400 s internal date and time as well as modify options associated with time synchronization 10x 1 Show Time and Curr
47. Up to 32 OFF characters ON State Name _ Text description of the 1 state Up to 32 ON characters Data Value The value to be written to the point 0000 FFOO FFOO Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 Write Single Register 6B Settings are available on the Write Single Register 6B tab on the Client Map tab The D400 provides mapping settings for write single register 6B points as shown in Table 80 Table 80 Write Single Register 6B Settings Setting Description Range Default Point Number A unique identifying number in the register map 0 to 65535 x Point Name A text string that describes this point Up to 128 Single 6B characters Register xxx Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float D400 Substation Data Manager Software Configuration Guide 91 GE Energy Setting Description Range Default Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 Device Properties The D400 provides mapping settings for the MODBUS Client settings on the right side of the Client Map tab as shown in Table 81 Table 81 MODBUS Device Properties Setting Description Range Default
48. already has an automatic terminal server configured 186 swm0066 2 75 0 General GE Energy gt gt To start d400connect 1 Connect and configure devices in the D400 Configuration Tool 2 Start a terminal session and log into the D400 3 Atthe D400 gt gt enter the following commands cd home D400_APPS d400connect d u lt D400 port number gt For example the command in the format d400connect d u 1 enables communications to a device connected to Serial Port 1 on the D400 The device command prompt is displayed 4 Configure or query the connected device as usual Tip Type d400connect h to view help information about the tool gt gt To exit d400connect e Press CTRL C and press Enter The D400 command prompt appears 8 7 D400 Configuration Manager The D400 Configuration Manager provides two modes of operation In redundant systems the utility synchronizes configurations between the two D400 units to ensure that both are configured identically In non redundant setups you may launch it manually to copy configurations from the current D400 to another D400 connected over a network or to a location in the D400 s file system like a connected USB drive In redundant systems the D400 Configuration Manager can also be activated by operating the SyncConfig digital output point which copies the configuration from the active unit to the standby unit See section 6 5 D400 Redundancy Manager for more inform
49. an event 5 5 MODBUS Server The MODBUS Server application allows a remote master station to retrieve and or modify the information in the database of the D400 using the MODBUS protocol The MODBUS Server map defines how the D400 is configured to present data to MODBUS masters The D400 supports the following configurable MODBUS data types Coils Read Only Registers Read Write Registers Input Status The MODBUS Server map settings are available on the Server Map tab when a MODBUS protocol type is selected 116 swm0066 2 75 0 General Figure 12 MODBUS Server Map Page D400 Configuration Mozilla Firefox File Edit View History Bookmarks Tools Help GE Energy 4 e 36 GE Energy Configuration E Commit Changes Discard Changes supervisor Supervisor New Wopen kasae uilS Read Only Registers Read Write Registers Input Status Serial Network client Map Server Map Alarm calculator System Wide User Management HMI Access Manager OneLine Designer E Devices DTA Please choose which Coils you would like to present to the master Address IED Point Name Type Name Default Control Spec Default Feedback Opt Default Invert Default Control Spec Default Control Spec Write Coil Property Map File Untitled IndexTo Dec Index To Hex Control Spec Feedback Opt Value Latch ON OFF Select Before Operate 1 0 0 Self false Delete Delete All NE Feedback Poin
50. and masters e Configure alarms e Create custom data calculations e Set system preferences e Manage user accounts e Create one line diagrams Although you are configuring the D400 while it is online your configuration changes do not take effect until you commit the changes Once a configuration is committed it is validated and copied to the system disk and the D400 applications are restarted One Line Designer The One Line Designer is a specialized drawing tool for creating substation one line diagrams and forms such as an annunciator panel The One Line Designer is accessed from within the D400 Online Configuration Tool D400 Substation Data Manager Software Configuration Guide 15 GE Energy gt gt To start the online configuration tool e Log into the D400 HMI and click the Configuration button al on the Power bar You must have Supervisor privileges to access the configuration tool Only one Supervisor user at a time can be logged in to perform configuration functions This manual provides detailed information on the configurable settings in the D400 and how to configure the D400 to work with different aspects of the substation system For more information about using the D400 Online Configuration Tool functions and screens refer to the D400 online Help 2 2 IEC 61850 Loader optional The IEC 61850 Loader referred to as the Loader is a PC based software program that is specifically designed to confi
51. any master station communicating with the LRU The D400 can be configured to represent multiple Logical Remote Units LRUs to multiple master stations The data presented to each master station may be identical or unique and can be achieved using multiple protocols simultaneously For example the D400 can maintain a separate event queue for every master station configured in the system If a data point is configured for presentation to eight master stations an event on the point will cause eight events to be reported one event to each master station Communication Statistics Server applications maintain communication statistics and other status information in the real time database as pseudo points 5 3 IEC 60870 5 101 104 The IEC 60870 5 101 and IEC 60870 5 104 Server applications allow remote master stations to retrieve and or modify the information in the database of the D400 using the IEC 60870 5 protocol The IEC 60870 5 101 104 Server map defines how the D400 is configured to present data to IEC 60870 5 masters You can create the following types of information objects e Bitstring e Double Command e Double Point e Integrated Total e Measurand e Packed Single Point e Regulating Command e Root Directory e Setpoint Command e Single Command e Single Point e Step Position D400 Substation Data Manager Software Configuration Guide 95 GE Energy gt gt To create an Information Object 1 Cl
52. are available on the Read Coil Status tab on the Client Map tab The D400 provides mapping settings for read coil status points as shown in Table 73 Table 73 Read Coil Status Settings Setting Description Range Default Point Number A unique identifying number in the register map O to 65535 x Point Name A text string that describes this point Upto 128 Coil xxx characters OFF State Name Text description of the 0 state Up to 32 OFF characters ON State Name Text description of the 1 state Up to 32 ON characters Poll Type The type of poll to be taken of the point See Table 64 Fast Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 88 swMm0066 2 75 0 General Read Status Input Settings are available on the Read Status Input tab on the Client Map tab The D400 provides mapping settings for read status input points as shown in Table 74 Table 74 Read Status Input Settings GE Energy Setting Description Range Default Point Number A unique identifying number in the register map 0 to 65535 x Point Name A text string that describes this point Up to 128 Input xxx characters OFF State Name Text description of the 0 state Up to 32 OFF characters ON State Name _ Text description of the 1 state Up to 32 ON characters Poll Type The type of poll to be taken of the point See Table 64 Fast Point Group
53. area or Right URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load when a user selects Any valid URL None the object address D400 Substation Data Manager Software Configuration Guide 155 GE Energy Table 140 Line Object Settings Setting Description Range Default x1 X horizontal pixel position from the top left corner 0 to the Draw Panel 0 of the screen to the top left corner of the start point width of the line Y1 Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the start point of height the line x2 X horizontal pixel position from the top left corner 0 to the Draw Panel 0 of the screen to the top left corner of the end point width of the line Y2 Y vertical pixel position from the top left corner of O to the Draw Panel O the screen to the top left corner of the end point of height the line Arrow Type Defines the type of arrow head to apply to the line at One of No Arrow No Arrow the
54. at this interval in seconds Setting Description Range Default Frozen Acc Poll The D400 requests frozen counter data at this 0 to 36000 0 sec interval in seconds If set to O the request is never transmitted Frozen Acc The D400 requests frozen counter event data O to 36000 0 If set to O the request is never transmitted 4 6 IEC 61850 Client The D400 supports communications to IEC 61850 compliant devices using the IEC 61850 client application The IEC 61850 Loader was specifically developed to assist in the configuration of the D400 for IEC 61850 server devices For information on how to configure the D400 for IEC 61850 communications refer to the IEC 61850 Loader online help 4 7 Hydran Client The Hydran Client map defines how the D400 is configured to poll data from Hydran devices The D400 supports the following configurable Hydran data types e Read system variable read from a register in a device e Read system Boolean read discrete inputs in a device e System status read discrete inputs such as alarm and alarm acknowledgement information in a device e Device properties device level settings Hydran Client map settings are available on the Client Map tab when a Hydran protocol device type is selected 80 swM0066 2 75 0 General GE Energy Figure 8 Hydran Client Map Page D400 Configuration Mozilla Firefox lj xj De Git yem Hgtory ockmarts Toos Help 4 2 CO
55. available in the lower pane of the Digital Outputs tab The configuration settings defined in Table 102 are used to configure the default values for all digital output points defined in the DNP3 server map Table 102 Digital Output Properties Setting Description Range Default Default The DNP3 server uses this as the default All operations SBO Only Command command to support when the master does SBO Only Supported not request any specific type Accumulators The accumulators are used for reporting running values frozen values and events This means that the same DNP3 point index is used for both the running and frozen value The DNP3 server returns the running value when data points for Static Variation Object 20 is requested by the master station The DNP3 server returns the frozen value when data points for Static Variation Object 21 is requested by the Master station The Threshold configured is used to qualify events for running accumulators only Event Variation Object22 Frozen accumulator events Object 23 are generated whenever a configured accumulator is frozen Settings are available on the Accumulators tab The default property values are defined in the lower pane The D400 provides the mapping settings for accumulators counters as shown in Table 103 Table 103 Accumulator Mapping Settings Setting Description Range Default Index Point Index 0 Based Each point index number 0
56. buffer is filled Discard Newest Discard Oldest Discard Newest Event Buffer Low Threshold A percent value of the total event buffer When the amount of available buffer space drops below this threshold a server event buffer low indication is reported by the application 10 to 100 20 DI Cancels Select Specify whether digital output select requests are automatically cancelled when any digital input changes are detected Enabled Disabled Disabled 34 SWM0066 2 75 0 General GE Energy Setting Description Range Default Buffer Al Specify whether analog input changes spontaneous periodic background scan are buffered for reporting When this is enabled the LRU reports each analog change separately For example if an analog input point exceeds the threshold 3 times before the LRU is polled for data in unbalanced mode the LRU shall report all 3 value changes If this feature is disabled the LRU shall report only the most recent value Enabled Disabled Disabled Zero Threshold Reporting Specify how the LRU should treat a zero value for the Threshold configuration parameter for an analog input If this setting is enabled setting the threshold configuration parameter of an analog input point to zero i e 0 0 spontaneously reports all changes for the point If disabled setting the Threshold configuration parameter of an analog input point to zero
57. by a dot and up to three additional alphanumeric characters Once the filename is entered click on the OK button Note If you want the drawing to be the default diagram the one that is loaded when you use the One Line Viewer then the filename must be main dra Open Use the Open button amp to retrieve and edit any drawing that has been previously saved Select the desired file name from the list and click the OK button Repositioning Repositioning requires no toolbar button Select an item hold down the left mouse button while the cursor is positioned anywhere inside the object and drag it to the desired location Resizing To resize an object select the item with the Select tool Position the mouse cursor on any of the eight mini boxes hold down the left mouse button and drag the object to increase or decrease the size Objects may also be resized together and in relationship to each other After selecting the multiple objects three choices are available on the toolbar to resize the objects so they are the same size on the horizontal plane the vertical plane 0 or both planes simultaneously 3 The last item selected is the controlling element This means all chosen objects are resized to match the last object you have selected while holding down the lt CTRL gt key and clicking the mouse button Alignment Multiple objects may be aligned so that any of their four edges or two axes are in alignment and level along the
58. configuration you must use the IEC 61850 Loader tool and re load the configuration into the D400 Refer to the IEC 61850 Loader online Help for more information Configuring Network Blocks Table 27 Network Block Connection Settings Setting Description Range Default Line ID Text description to identify the electrical 1 to 32 ASCII Line X transmission line associated with this serial characters connection Device ID Text description to identify the device 1 to 32 ASCII Device X associated with this serial connection characters Bay ID Text description to identify the bay area 1 to 32 ASCII Bay X associated with this serial connection characters IED Address Address of the device 0 to 65519 N A Map File Name of the client map file to be used with the List of user N A specific device configured client map files IP Address IP address of the device Single IP 0 0 0 0 address Backup IP Address Redundant backup IP address of the device Single IP 0 0 0 0 address Network Port The port number on which the device will 0 to 65535 20000 communicate Enable on Start Up Indicates if communication to the device Enabled Disabled automatically starts when the configuration is Disabled changed and reloaded or when the D400 re boots For instance specific DNP3 Client application settings see DNP3 Client Application Settings in section 3 1 Serial Connections The communication settings in Table 1
59. configuration tool 3 Set up device serial and network connections including protocol specific settings 4 Program Automation applications 5 Create and or edit Server master station maps 6 Setup master station connections including protocol specific settings 7 Create substation one line diagrams using the One Line Designer 8 Save the configuration file 9 Run the configuration file on the D400 by committing the changes 2 7 Configuration File Format Configuration information for an individual D400 is stored as a set of XML files The configuration files are labeled with the D400 device name and saved to the User CompactFlash disk on the D400 main board The configuration files contain the following information e Device and master point maps e Application settings e HMI settings Configuration information for each application is also contained in the configuration files including the application version configuration settings default settings and saved user settings System configuration information that is modified using the system utilities is stored in separate system configuration files stored on the D400 The system configuration files are updated each time changes are made 18 SWM0066 2 75 0 General GE Energy 2 8 Configuration Management While you are creating and editing the D400 configuration using the D400 configuration tool your settings are saved in a temporary file and location When you ar
60. events the Event Logger must be configured on the System Wide tab of the Configuration Tool 42 SWM0066 2 75 0 General GE Energy Table 21 Printer Device Setting Description Range Default Device Name Text description to identify the printer 1 to 32 ASCII N A connection characters Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Redundancy Dedicated Link The following settings are used when configuring D400 system redundancy A Redundancy Dedicated Link is configured on the port that the D400 ping cable is connected to Table 22 Redundancy Dedicated Link Setting Description Range Default Device Name Text description to identify the redundancy 1 to 32 ASCII RLINKx connection characters Ensure that both D400 units in the redundant setup have connected the ping cable to the same serial port number In a redundant setup the D400 Configuration Manager synchronizes configurations between the D400 units and this setting will be lost if there is a difference between the two Redundancy Switch Panel The following settings are used when configuring D400 system redundancy A Redundancy Switch Panel connection is configured on the port that the RS232 watchdog cable is connected to Table 23 Redundancy Switch Panel Setting Description R
61. for the alarm group e g color and sound settings is applied to every point associated with the alarm group Transient Delay in milliseconds after which if an alarm is stillin O to 65535 Suppression a transient state State 00 or State 11 that an alarm is Delay generated This setting does not apply to alarms on the State 01 and State 10 Alarmable State See Table 118 Text State See Table 119 Table 118 Alarmable State Settings State 00 Type of alarm that is generated when both Alarm Point None None in Transit 1 and Alarm Point 2 are in state 0 typically Normal Absolute Used with Alarmable State 11 to configure an On O Usdate Update alarm representing the transient states of a p dual point State 01 Open Type of alarm that is generated when Alarm Point 1is None None in state 0 and Alarm Point 2 is in state 1 typically Absolute alarmable Typically used to configure an Absolute On Update alarm to record a breaker being open D400 Substation Data Manager Software Configuration Guide 127 GE Energy State 10 Closed Type of alarm that is generated when Alarm Point 1is None None in state 1 and Alarm Point 2 is in state 0 typically Absolute Normal On Update State 11 Invalid Text to display to represent the point state when both None None Alarm Point 1 and Alarm Point 2 are in state 1 typically absolute alarmable Used with Alarmable State 00 to configure On Update an On Update alarm re
62. g color and sound settings is applied to every point associated with the alarm group ACK Method Selected method to acknowledge the alarm manually Manual Manual by the user or automatically by the D400 when Automatic generated and then immediately archived 126 swm0066 2 75 0 General GE Energy Off Text State 0 Text to display to represent the point state when the 1 to 32 associated digital input point value becomes 0 alphanumeric typically the Normal state characters Text State 1 Text to display to represent the point state when the 1 to 32 On associated digital input point value becomes 1 alphanumeric typically the Alarm state characters Table 117 Four State Alarm Settings Alarm Name Text description of the alarmable point as it will be Up to 100 DI source displayed in the Active Alarms page It defaults tothe alphanumeric Point name name of the source point characters Source Point 1 First of two digital input source points selected from Not editable System the Point Picker to comprise the 4 state point being assigned monitored for alarms Based on user configured DI identifier point name prefixed with system assigned identifier Source Point 2 Second of two digital input source points selected to List of points based comprise the 4 state point being monitored for on configured Dls alarms Alarm Group Single alarm group to which the point s alarmis tobe 1to4 associated with All configuration information
63. grid no matter what their size Buttons for each of the four edges and two axes are provided on the upper toolbar mi Align Left mi Align Top ki Align horizontal center al Align Right a Align Bottom Align vertical center Distribution Multiple objects may be distributed horizontally or vertically For horizontal distribution IM the selected objects that are furthest to the left and right remain in place while the remaining selected objects are distributed evenly based on their centers For vertical distribution the top and bottom selected objects remain in place while the remaining selected objects are distributed evenly based on their centers 138 swmM0066 2 75 0 General GE Energy Establishing Order Objects may be placed one on top of another in a layered configuration A rectangle for example can be placed over a line To control the layer order of objects select an object and choose to bring that element to the front or send it to the back Al 7 2 Types of Objects All of the object types you can use to create your diagram are displayed on the drawing toolbar Drawing Toolbar Select As you add individual objects to the canvas they are treated as separate and distinct entities After an object has been created you may wish to return to the object in order to change its size position properties or appearance Clicking the Select tool then clicking the mouse on the object makes that object the activ
64. information Include Include Response object in a general interrogation response Exclude Report Class Specify if spontaneous events for this object are Class 1 Class 1 reported as class 1 or class 2 messages Applies Class 2 to unbalanced mode and spontaneous events only 106 swm0066 2 75 0 General GE Energy Setting Description Range Default Periodic Update The type of periodic updating Not Used Not Used Mode Background Scan Periodic Update The time in seconds between periodic reports 0 to 65535 0 Interval Used only if Periodic Update Mode is not set to Not Used Periodic Report Specify if periodic reporting if enabled should Disabled Disabled On Power Up begin immediately upon startup Enabled Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag Per Point Settings Address The address of the entity IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected DI Assigned point from the Point Picker Read only Identifier Point Name Text description of the point in the Binary Input Up to 128 Assigned IED map Based on selected DI point Read only characters point name Invert Select if the value of the mapped points should True or False False be inverted Step Position Table 94 Step Position Mapping Settings Setting Description Range Default Info Objec
65. into the appropriate corresponding Value offers the floating menu choices Properties for HttpPort CmdHttpPort CmdlEDName and CmdPointName are not being used currently and are reserved for future implementation To assign input points to the CB Box object you would invoke the Tag Picker interface as described below e Double Click on the property area of IEDName1 e Select a device from the Select IED dialog e Double Click on the property area of PointName 1 e Select a BitString point from the Select Point dialog e Repeat Steps above for the IEDNamez and PointName2 The next step is to choose the desired bits out of the BitString you just selected The bit strings are treated as a 0 based array of digital status points The BitPosition1 and BitPostion2 properties accept input in x y format Where x index of the desired status point in the BitString and where y length of the BitString This should always be 1 for the D400 Transformer This object is a basic graphic representation of a transformer and has the same Property Value characteristics as a standard rectangle except for the fill choice including border color and type and rotation The URL Anchor is also available for linking to another drawing Ground This object offers graphical representation of a ground and is limited to the same Property Value characteristics as a standard line including border color and type The URL Anchor is also available for linking
66. maximum of 10 000 alarms all types Note Digital points must already be configured in the D400 before they can be selected as alarmable points 124 swm0066 2 75 0 General D400 Configuration Mozilla Firefox GE Energy Figure 13 Alarm Configuration Page 0 x File Edit View History Bookmarks Tools Help e gt COA a Ge a Bcc Energy Configuration N Commit Changes Discard Changes Serial kasae Reset kin 20Ints Global Settings Network Client Map Server Map Alarm Calculator System Wide User Management HMI Access Manager OneLine Designer Absolute kins On Update Alarms Four State Alarms Devices DTA Please select the points you would like to configure Absolute alarms on a See Alarm Name Source Point Alarm Group Alarmable State Text State 0 Text State 1 ConfigError CALCULATOR ConfigE Group1 CalcStatus CALCULATOR CalcStat Group1 v ON OFF DeviceDisabled CALCULATOR DeviceD Group1 v ON OFF 4 ern 3 Absolute alarms Applet AnnunciatorConf started gt gt To configure the D400 Annunciator 1 On the Configuration page select the Alarm tab 2 Select and configure points for each alarm type Absolute Alarms On Update Alarms Four State Alarms Configure settings for group alarms 4 Configure global settings for alarms Alarm Points Configuration The Annunciator supports the configuration of a maximum of 10 000 alarm points
67. mkdir lt user name gt chmod 770 lt user name gt cd lt user name gt Enter the following commands to copy the public key from D400 A scp lt admin user name gt lt IP address of D4090 A gt mnt datalog SSHKeys id_rsa pub authorized keys chmod 660 authorized keys Log onto the terminal of D400 A and enter the following command cd mnt datalog SSHKeys Create a directory using the user name configured on D400 B in Redundancy gt User Name of PEER D400 using the following command mkdir lt user name gt chmod 770 lt user name gt cd lt user name gt Enter the following commands to copy the public key from D400 B unit scp lt admin user name gt lt IP address of D4 B gt mnt datalog SSHKeys id rsa pub authorized keys chmod 660 authorized keys 8 8 gt gt Software Licensing Tools The D400 contains a set of utilities to manage software licensing for optional applications and features Licensing is controlled through a single license file stored on your D400 To unlock an application using a license code Start a terminal session and log into the D400 At the prompt enter the following commands cd home D400_APPS swlic unlock l lt 26 digit license code gt Note The parameter l above is a lower case letter L The feature is unlocked and available for use gt gt To update existing D400 licenses using a batch file D400 Substation Data Manager Software Configuration Guide 189
68. not an ACTCON PDU is Yes Yes expected from the remote device after the No application sends an ACT PDU request GE Energy Setting Description Range Default ACTCON Timeout The time in milliseconds after which an 1 to 65535 1000 ACTCON PDU is assumed to come back after sending out a request of ACT PDU only applicable to control requests general interrogation requests and counter interrogation requests ACTTERM Specifies whether or not an ACTTERM PDU is Yes Yes Expected expected to indicate the completion of a No transaction Time Offset The device s time base offset from UTC in 1440 to 1440 0 minutes A positive value means the device s time base is ahead or East of GMT while a negative value means the device s time base is behind or West of GMT Control Override Specifies whether or not the application shall None None override the Control Type sent in an RTDB DirectOperate control request to use in the actual Binary SBO Output request to the remote device Time Sync Interval The time synchronization interval in minutes 0 0 to 1440 0 10 0 A value of 0 0 disables scheduled time synchronization to the remote device Global Counter The Global Counter Interrogation interval in 0 0 to 1440 0 0 0 Interrogation minutes A value of 0 0 disables Global Interval Counter Interrogations to the remote device except on application startup Group X Counter The Group X Counter Inte
69. not support use of a DHCP server to assign dynamic IP addresses If the D400s have a secondary Ethernet interface installed a second set of 3 IP addresses is assigned to that interface using the same rules 200 swm0066 2 75 0 General GE Energy Configuration Synchronization Over Ethernet All data synchronization normally occurs over the dedicated serial link between the two D400 units However if the units can communicate with each other over Ethernet the standby D400 will attempt to use this connection for faster data transfer when synchronizing the configuration Refer to the procedure shown under To Configure Public Key Authentication in section 8 7 D400 Configuration Manager B 4 Error Messages and Troubleshooting Table 157 describes the possible error messages displayed by the D400 Redundancy Manager These messages are entered in the diagnostic log of the D400 Table 157 D400 Redundancy Diagnostic Error Messages Sr No Diagnostic log messages Details 1 b034_active_proc_db_syncl failed with error Initial mSQL database synchronization lt error code gt failed Quality or accumulator records may not have been transferred correctly 2 Active failed to pull switch towards The active unit failed to pull the switch The RS232 switch panel may not be powered correctly or the connection from the switch panel to the D400 may not be correct 3 Active Health CHK failed Terminating Child A so
70. of non 24 to 255 255 Length background messages excluding framing overhead Extra Frame The time in milliseconds that the application 0 to 65535 150 Timeout adds to the frame timeout calculation Single Char Specify if the application should respond to Enabled Disabled Acknowledge the master station with a single character Disabled acknowledgement message Comm Fail The maximum allowed time in seconds for 0 to 86400 30 Timeout when there is no available connection in the STARTDT state that is no communication from the master station before the application assumes communications have failed Not used when set to 0 File Transfer The report class to use when sending file Class 1 Class 2 Report Class transfer related PDU Used in unbalanced Class 2 mode only Balanced Serial Link Tab Max ASDU Frame The maximum length in octets of non 24 to 255 255 Length background messages excluding framing overhead Extra Frame The time in milliseconds that the application 0 to 65535 150 Timeout adds to the frame timeout calculation Single Char Specify if the application should respond to Enabled Disabled Acknowledge the master station with a single character Disabled acknowledgement message Transmit Retries The maximum number of transmission Oto 255 1 retries when no acknowledgement is received from the master station before the application assumes communications has failed Extra Response The time in milliseconds that the a
71. of t0 Send Timeout The maximum time in seconds that the 1 to 255 15 application waits for an acknowledgement after sending a frame value of t1 No Data Timeout The maximum time in seconds that the 1 to 255 10 application waits before sending a supervisory acknowledgement S frame value of t2 Idle Timeout The period during which no messages are 1 to 255 20 received in seconds that the application allows pass before sending a test frame value of t3 D400 Substation Data Manager Software Configuration Guide 61 GE Energy Info Objects An information object consists of a set of data elements You can create the following types of information objects e Input Bitstring Double Point Integrated Total Measurand Packed Single Point Single Point Step Position e Output Double Command Regulating Step Command Setpoint Command Single Command gt gt To create an Information Object 1 Click Add Info Object 2 On the New Info Object window enter values for the fields as described in Table 36 and click OK 3 Enter the number of rows and click Add to create and configure elements within the information object Table 36 Info Object Settings Setting Description Range Info Object Type The type of information object to create Bitstring Double Point Integrated Total Measurand Packed Single Point Single Point Step Position Double Command Regulating Step
72. only Identifier Point Name Text description of the point in the Binary Input Up to 128 Assigned IED map Based on selected DI point Read only characters point name Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Polarity Specifies whether or not a negative analog Bipolar Value Bipolar Value value is valid Unipolar Value Threshold The initial minimum change in the analog input Oto 5 value that is required in order to produce a 100 000 000 spontaneous report or event High Limit The initial high limit that is required for an 1 0E 12 to 1 0E 12 analog input value to exceed in order to 1 0E 12 produce an event Low Limit The initial low limit that is required for an analog 1 0E 12 to 1 0E 12 input value to exceed in order to produce an 1 0E 12 event 108 swmo066 2 75 0 General GE Energy 5 4 DNP3 Server The DNP3 Server application allows a remote master station to retrieve and or modify the information in the database of the D400 using the DNP3 protocol Because the DNP3 server application supports device level addressing it can access the full range of addresses supported by the protocol For example for DNP3 all master station addresses are user configurable per the DNP3 address range of 0 to 65519 The DNP3 Server map defines how the D400 is configured to pres
73. required The D400 stores all the desired information for a master station in a map that lists and describes the selected data points from selected devices The server map file is based on a specific protocol and specifies what information to present to a master The map file contains information on how and when data is transmitted to a particular master station and the selected devices and data points The D400 includes a default DNP3 server map You can use the default server map or customize it for your system requirements Once you create a server map file it becomes available to select on the Configuration page when assigning master connections Creating Server Maps gt gt To create or edit a server map 1 On the Configuration page select the Server Map tab 2 Click New to create a new client map or Open to edit an existing server map 3 Select the SCADA protocol type and then create or select the master map file 4 Edit the data type and protocol settings as desired 5 Click Save and enter a name for your map file 94 SWM0066 2 75 0 General GE Energy Tip To create a custom mapping template create a map file click Save and enter a template name For more information on creating a server map refer to the D400 online Help Logical Remote Units The D400 can be configured to function as several distinct instances Each instance is called a Logical Remote Unit LRU It appears as a single physical server to
74. selects Any valid URL None the object address 146 swm0066 2 75 0 General Table 133 Circuit Breaker Box Object Settings GE Energy Setting Description Range Default Object Identifier Object Identifier of a four state Digital Status Object Existing Digital None or of a Digital Control Object configured with four Status or Digital state feedback status Control Object Identifier x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 40 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 T Border Type Defines the type of border to display Oto 255 0 Digital Input Value Digital input 1 value to associate with a true state Oor1 1 1 True State Digital Input Value Digital input 2 value to associate with a true state
75. starts when the configuration Enabled is changed and reloaded or when the D400 re boots DNP3 Client Application Settings DNP3 client settings are available under the Application Parameters field and apply to all multi dropped devices Table 10 DNP3 Client Application Settings Setting Description Range Default Master Address Address of the DNP3 client application Must be different from all configured devices on this port 0 to 65519 1 As per DNP3 convention IIN React Class1 True Respond to Class 1 IIN in a message by requesting class 1 event data False Ignore Class1 IIN Class 1 Data events are typically very important and should be retrieved from the target device as soon as the indication is received True False True IIN React Class2 True Respond to Class 2 IIN in a message by requesting class 2 event data False Ignore Class2 IIN Class 2 Data events are typically very reasonably important and should be retrieved from target device as soon as the indication is received True False True 30 SWM0066 2 75 0 General GE Energy Setting Description Range Default IIN React Class3 True Respond to Class 3 IIN in a message by requesting class 3 event data False Ignore Class3 IIN Some target devices generate large numbers of insignificant Class 3 events To minimize I O traffic set t
76. the Hydran device Table 67 Hydran Device Properties Setting Description Range Default Poll Interval Time in milliseconds to wait between polls 0 to 65535 10 Time Sync How often in seconds performing time 0 to 86400 60 Frequency synchronization should be performed with the remote device If set to 0 time synchronization is disabled System Status Poll The polling rate of system status information See Table 64 Fast Type Fast to Slow Poll Number of fast poll cycles before a slow poll 1to 255 10 Frequency cycle is initiated Retry Count The number of retries attempted before the 0 to 255 3 device is assumed to be offline Degraded Time Time in seconds between attempts by the O to 86400 30 D400 to bring an offline device online 4 8 SEL Binary The SEL Binary Client map defines how the D400 is configured to poll data from SEL Fast Meter devices The SEL client application uses ASCII messages to extract Protective Relay Fault PRF information from the SEL device The D400 supports the following configurable SEL Binary data types e Fast Meter analog channel e Demand analog channel e Peak demand analog channel D400 Substation Data Manager Software Configuration Guide 83 GE Energy e SER digital channel e Device properties The SEL Binary Client map settings are available on the Client Map tab when a SEL Binary protocol device type is selected Note Additional SEL Binary configur
77. the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 80 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 Font Type The type of font used to display the scaling value as One of SansSerif SansSerif text Serif Monospaced DialogInput Font Size The size of the font used to display the scaling value 1 to 100 11 as text Font Style The font style to apply to the display of the scaling One of normal Normal value as text bold or italic Foreground Color The color to apply to scaling value displayed as text Any 24 bit RGB Black Color Background Color The color to apply to the background non Any 24 bit RGB Red highlighted area of the bar chart Color High Range Color The color to apply to the highlighted area but only Any 24 bit RGB Red when the real time value exceeds the configured Color High Range Value Low Range Color The color to apply to the highlighted area but only Any 2
78. time and administrator passwords The utilities are intended for use by service personnel and application engineers responsible for setting up and maintaining the D400 Because of the advanced functionality it is helpful to have basic knowledge of Telnet ftp and Linux commands in order to execute the commands for your specific system setup This chapter covers how to use the various system utilities 8 1 Utilities Overview The D400 includes the following utility programs e D400 Configuration e D400 Connect e 1 0 Traffic Display e Printer e Email Transfer e Software licensing tools e Emergency Access Code These advanced D400 configuration and system administration functions are available at the D400 command line interface 170 swm0066 2 75 0 General GE Energy 8 2 Setting up a Terminal Session You can access these system utilities directly at the D400 command prompt through the local maintenance port or remotely through the Utilities Power bar button in the D400 HMI The Utilities page provides a TELNET or a Secure Shell SSH login to establish a remote terminal session with the D400 Access to the command line interface requires an Administrator or root log in Note When accessing the D400 with an Administrator level user account you may not have sufficient security privileges to execute the commands listed in this manual If this occurs type sudo in front of each command Refer to the D400 Subst
79. to another drawing Switch This object represents a switch in the substation configuration As such it has Property Values that can be drawn from existing equipment assuming that there is a device polling this information You must assign the appropriate IEDname and the PointName for the switch You also need to identify the correct Property Value for when the switch is closed 0 or 1 and apply the opposite value for the open position note that the graphic configuration changes its appearance relative to the switch s condition Properties for HttpPort CmdHttpPort CndlIEDName and CmdPointName are not being used currently and are reserved for future implementation The basic graphic Property Values seen in other objects including line width and color border color and type and background color can also be assigned in the appropriate Values boxes D400 Substation Data Manager Software Configuration Guide 141 GE Energy 7 3 142 sw Object Configuration Settings Property Panel The Property Panel displays the properties associated with the currently selected object Based on the type of object selected the properties window will show different options Table 126 Accumulator Status Object Settings Setting Description Range Default Point Identifier A point identifier for a single accumulator point Existing None where the identifier consists of the dev
80. which the point belongs List of defined Group assigned point groups to ID number 0 Write Single Coil Settings are available on the Write Single Coil tab on the Client Map tab The D400 provides mapping settings for write single coil points as shown in Table 78 90 swM0066 2 75 0 General Table 78 Write Single Coil Settings GE Energy Setting Description Range Default Point Number A unique identifying number in the register map 0 to 65535 x Point Name A text string that describes this point Up to 128 Single Coil xxx characters OFF State Name Text description of the O state Up to 32 OFF characters ON State Name Text description of the 1 state Up to 32 ON characters Data Value The value to be written to the point 0000 FFOO FFOO Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 Write Single Register 6A Settings are available on the Write Single Register 6A tab on the Client Map tab The D400 provides mapping settings for write single register 6A points as shown in Table 79 Table 79 Write Single Register 6A Settings Setting Description Range Default Point Number A unique identifying number in the register map 0 to 65535 x Point Name A text string that describes this point Up to 128 Single 6A characters Register xxx OFF State Name Text description of the 0 state
81. 0 are available on every instance of the client application Configuring Network Master Stations Each row under the Network Master Stations item represents one master connection through an Ethernet port on the D400 You can configure a maximum of 8 ports on the Master Block A server map file must be available in the D400 before a master type is available for selection on the Master Connection page The D400 includes a default server map If 48 SWM0066 2 75 0 General GE Energy you require a custom map create it first before setting up the network connection See section 5 2 Server Maps Table 28 DNP3 Master Network Connection Settings Setting Description Range Default Remote Text description to identify the master station 1 to 32 ASCII N A Connection associated with this serial connection characters Name Map File Name of the Server map file to be used with List of user N A the specific master configured client map files Auto Start Indicates if the client application automatically Automatic N A starts when the configuration is changed and_ Disabled reloaded or when the D400 re boots D400 Address DNP3 address of the server application 0 to 65519 0 instance Transport Layer Whether to use TCP or UDP network protocol TCP TCP UDP Network Port The D400 port number on which the master 0 to 65535 20001 station will communicate Permitted IP addresses of master stations permitted to Up to 8 IP 0 0
82. 1 that both digital input points must be stable before an indeterminate state is reported 1 disables this setting Per Point Settings Address The address of the entry Read only N A N A Source Point First of two digital input source points selected Not editable System One from the Point Picker to comprise the 4 state assigned point being monitored Based on user identifier configured DI point name prefixed with system assigned identifier Source Point Second of two digital input source points List of points N A Two selected to comprise the 4 state point being based on monitored configured Dis Invert Select if the value of the mapped points should True or False False be inverted Integrated Total Table 86 Integrated Total Mapping Settings Setting Description Range Default Info Object Settings Info Object The name of the information object as entered N A N A Name on the New Info Object window Read only Starting The starting address of this entry 1 to 16777215 Address D400 Substation Data Manager Software Configuration Guide 99 GE Energy Setting Description Range Default Interrogation The interrogation group used for reporting this Not Used Not Used Group information object Group 1 Group 16 Report Class Specify if spontaneous events for this object are Class 1 Class 1 reported as class 1 or class 2 messages Applies Class 2 to unbalanced mode and spontaneous events
83. 1 Switch State If the Digital Status Object is a 4 State Digital The One of Open None switch state to display when the digital input 1 value Closed In Transit low bit corresponds to the 1 state and the digital or Invalid input 2 value high bit corresponds to the O state 10 Switch State If the Digital Status Object is a 4 State Digital The One of Open None switch state to display when the digital input 1 value Closed In Transit low bit corresponds to the O state and the digital or Invalid input 2 value high bit corresponds to the 1 state 11 Switch State If the Digital Status Object is a 4 State Digital The One of Open None switch state to display when the digital input 1 value Closed In Transit low bit corresponds to the 1 state and the digital or Invalid input 2 value high bit corresponds to the 1 state O Switch State If the Digital Status Object is a 2 State Digital The One of Open or None switch state to display when the digital input value corresponds to the O state Closed 166 swm0066 2 75 0 General GE Energy Setting Description Range Default 1 Switch State If the Digital Status Object is a 2 State Digital The One of Open or None switch state to display when the digital input value Closed corresponds to the 1 state URL Action Specifies whether to load the URL Address into the Same or New Same same wind
84. 4 bit RGB Red when the real time value is less than or equal to the Color configured High Range Value High Range Value The value which when exceeded by the real time Any 24 bit RGB Red value shall result in the highlighted area of the bar Color chart being displayed in the High Range Color and which when the real time value is less than or equal to shall result in the highlighted area of the bar chart being displayed in the Low Range Color D400 Substation Data Manager Software Configuration Guide 159 GE Energy Setting Description Range Default Bar Scaling Value The value by which the real time values are divided Any 64 bit floating 1 to calculate a full scale percentage that determines point value the height of the bar during run time The Bar Scaling Value determines the maximum run time value that can be displayed in the bar chart Fill Direction Fill direction defines the manner in which the One of Top Bottom highlighted area shall be drawn Bottom Left or If set to bottom the highlighted area shall rise Right vertically upwards being filled from its bottom edge upwards ending at a horizontal line that corresponds to the percentage of the real time value as compared to the configured bar scaling value If set to top the highlighted area shall rise vertically downwards being filled from its top edge downwards ending at a horizontal line that corresponds to the percentage of the real time value
85. 400AActive and D400BActive remain fixed at 0 or 1 regardless of the position of the A B switch on the RS232 panel ensure that the RS232 adapter cards containing the redundancy control ports are set to the DTE position Refer to Switch SW1 SWe Configuration and Switch SW3 SW4 Configuration in the D400 Substation Data Manager Hardware User s Manual 994 0089 for more information 5 Select the Digital Output tab and verify that all points are online and have a value of zero B 2 Data Synchronization The following data is automatically synchronized from the active to the standby D400 e Accumulator running values e Local commands that have been applied to individual system points control inhibit scan inhibit local force etc Data is synchronized between the units through the dedicated serial link Initial states are synchronized when the active unit first begins to communicate with the standby unit Once this initial synchronization is complete individual events are transferred from the active unit to the standby unit as they occur in real time The data to be synchronized is stored in the user CompactFlash card of the D400 so that it is not lost in the event that power is interrupted to both units The active unit will indicate if the configuration on the standby unit does not match itself via the Standby Config Out of Sync digital input Note Disabling a device from being scanned using the DisableDevice digital output or b
86. 64 0 0 bit Float Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Packed Single Point Table 42 Packed Single Point Element Settings Setting Description Range Default Bit Position The bit position within the DI point 1 to 32 Incremented from 1 Point Name Text description of the point in the map file Up to 128 lt object characters name gt X ON State Text description of the 1 state Up to 32 ON characters OFF State Text description of the 0 state Up to 32 OFF characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Regulating Step Command Table 43 Regulating Step Command Element Settings Setting Description Range Default Address The address of this information object 1 to 16777215 Incremented element by 1 from starting address Point Name Text description of the point in the map file Up to 128 RC X characters D400 Substation Data Manager Software Configuration Guide 65 GE Energy Setting Description Range Default Regulating The relative position that the step controller is Lower Lower Command State commanded to move to Higher Command An attribute that specifies in greater detail the No Additional Persistent Qualifier type of control action requested Definition Short Pulse Duration Long Pulse Duration Persistent
87. Analog True True Feedback Polling Feedback poll to the device when a False Digital Analog control is sent to the device Feedback Poll Interval to wait in seconds after the control is 1 to 3600 1 Delay requested before issuing the Feedback Poll Counter Feedback Interval to wait in seconds after the counter 1 to 3600 1 Poll Delay command is requested before issuing the counter poll IED Persists True Device persists counters across restarts True True Counters False Device clears counters on startup False This setting affects accumulator processing Freeze Command Freeze command used by the application Running Running Type Freeze and Clear Running Counters or Freeze Counters Counters and Clear Frozen Counters Frozen Counters Time Offset Time offset in minutes from UTC For 1440 to 1440 0 example for Eastern Standard Time specify 300 which means UTC minus 5 hours Specify only if the device does not use UTC within DNP3 messages DNP3 requires the time base to be UTC but non compliant devices may use local time Integrity Poll min The D400 requests integrity poll data at this 1 to 6000 5 interval in minutes If set to O the request is never transmitted Class1 Poll sec The D400 requests class 1 data at this interval 0 to 36000 5 in seconds If set to O the request is never transmitted Class2 Poll sec The D400 requests class 2 data at this interval 0 to 36000 5 in seconds If set to O the reques
88. Capacity Max Length buffered This can either be Up to Capacity or a Number If a Number is entered the sum Max Lengths for all Class Queues cannot exceed the nternal Event Buffer Capacity 4096 8192 16384 Up to Capacity DNP3 Multi drop The following settings are used when configuring a DNP3 Multi drop connection If a Modem connection is used refer to the additional settings defined in Table 5 D400 Substation Data Manager Software Configuration Guide 29 GE Energy Table 9 DNP3 Multi drop Setting Description Range Default Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Line ID Text description to identify the electrical 1 to 32 ASCII Line X transmission line associated with this serial characters connection Device ID Text description to identify the device 1 to 32 ASCII Device X associated with this serial connection characters Bay ID Text description to identify the bay area 1 to 32 ASCII Bay X associated with this serial connection characters IED Address Protocol address of the device i e DNP3 0 to 65519 X device address Map File Name of the Client map file to be used with List of user N A the specific device configured client map files Enable on Start Indicates if communication to the device Disabled Disabled Up automatically
89. Command Table 38 Double Command Element Settings Setting Description Range Default Address The address of this information object 1 to 16777215 Incremented element by 1 from starting address Point Name Text description of the point in the map file Up to 128 DC X characters Command An attribute that specifies in greater detail the No Additional Persistent Qualifier type of control action requested Definition Short Pulse Duration Long Pulse Duration Persistent ON State Text description of the 1 state Up to 32 ON characters OFF State Text description of the O state Up to 32 OFF characters D400 Substation Data Manager Software Configuration Guide 63 GE Energy Setting Description Range Default Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Double Point Table 39 Double Point Element Settings Setting Description Range Default Address The address of this information object 1 to 16777215 Incremented element by 1 from starting address P1 Name Text description of the first point in the map Up to 128 DP XA file for this double point object characters P1 ON State Text description of the 1 state for the first Up to 32 ON point characters P1 OFF State Text description of the O state for the first Up to 32 OFF point characters P1 Group Point group to which the first point
90. Error Codes Err No Cause 1 The two D400 units are not already in sync 0 Success 1 Md5sum txt tar zipped file missing in local tar modes 2 Command line arguments are not proper 3 IP Address or target unit not provided in correct format 4 Validation of transferred configuration files failed 5 Authentication is not set or remote D400 is not accessible 6 Insufficient permissions to read from file 8 Copying of new configuration to mnt usr has failed 20 Configuration is already in sync D400 Substation Data Manager Software Configuration Guide 205 GE Energy Remote Authentication C 1 Cisco TACACS Use the following settings to configure your TACACS server for use with your D400 Table 160 User Account Privilege Levels D400 Permission Level TACACS Privilege Level Root n a see note Administrator 0 3 Supervisor 4 7 Operator 8 11 Observer 12 15 Note Only one root account exists on the D400 and it is stored locally While it cannot be deleted from the system you can change the password using the D400 Configuration Utility Table 161 TACACS Service Parameters TACACS Parameters D400 Service Service Protocol Port Login d400local none console HMI Access Manager d400httpd none web Getty d400getty none ttySO 206 SwM0066 2 75 0 General GE Energy TACACS Parameters D400 Service Service Protocol Port
91. GE Energy D400 Substation Data Manager Software Configuration Guide SWMO0066 Version 2 75 Revision O imagination at work Genera GE Energy Copyright Notice 2007 2009 General Electric Company All rights reserved The information contained in this online publication is the exclusive property of General Electric Company except as otherwise indicated You may view copy and print documents and graphics incorporated in this online publication the Documents subject to the following 1 the Documents may be used solely for personal informational non commercial purposes 2 the Documents may not be modified or altered in any way and 3 General Electric Company withholds permission for making the Documents or any portion thereof accessible via the internet Except as expressly provided herein you may not use copy print display reproduce publish license post transmit or distribute the Documents in whole or in part without the prior written permission of General Electric Company The information contained in this online publication is proprietary and subject to change without notice The software described in this online publication is supplied under license and may be used or copied only in accordance with the terms of such license Trademark Notices GE and are trademarks and service marks of General Electric Company Trademarks of General Electric Company Cisco is a registered trademark of C
92. I Device X associated with this serial connection characters Bay ID Text description to identify the bay area 1 to 32 ASCII Bay X associated with this serial connection characters IED Address Protocol address of the device i e DNP3 O to 65519 X device address Map File Name of the Client map file to be used with List of user N A the specific device configured client map files Enable on Start Indicates if communication to the device Disabled Disabled Up automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots IEC 60870 5 101 Master Station The following settings are used when configuring an IEC 60870 5 101 Master Station connection Table 12 IEC 60870 5 101 Master Station Setting Description Range Default Transmission The link transmission mode used by the Balanced Unbalanced Mode application Unbalanced Link Address The number of octets used for the link lor2 1 Size address of the LRU LRU Name The name of the LRU master station 1 to 32 ASCII MASTERX connection characters 32 SWM0066 2 75 0 General GE Energy Setting Description Range Default Common The number of octets used for the common lor 2 1 Address of ASDU address of ASDU for the LRU Size Common The Common Address of ASDU for the LRU 1 to 254 1 octet 1 Address of ASDU size 1 to 65534 2 octet size Link Address The link address of the LRU 0 to 65535 1 Map File Name of th
93. I polls performed Enabled Disabled Interrogation by the application are staggered Disabled GI Qualifier The Qualifier to use for the General Global Group 1 Global Interrogation poll through Group 16 GI Stagger The staggered GI poll interval in minutes 0 0 to 1440 0 30 0 Interval Backoff Time The time in seconds to wait before the 0 to 65535 30 application tries to re contact a device after a communication failure Min Inter Poll The minimum time delay in minutes 0 0 to 1440 0 0 0 Delay between any two consecutive application level polls Max ADSU Frame The maximum value for the length in octets 24 to 255 255 Length of non background messages excluding framing overhead Extra Frame The time in milliseconds that the application 0 to 65535 150 Timeout adds to the frame timeout calculation Max Confirm Idle The maximum communication idle time in 1 to 65535 100 Time milliseconds before the application must receive a confirm message Max Respond Idle The maximum communication idle time in 1 to 65535 100 Time milliseconds before the application must receive a respond message Max Transmit The maximum number of transmission 1to 255 1 Retries retries before declaring that communication with a remote device has failed Wait Between The minimum time in seconds to wait 0 0 to 60 0 0 0 Messages between polls measured from receiving the response of one poll to the beginning of the next poll Link Transmission The link tran
94. ICT BOTH D400s are ACTIVE Check the wiring of the D400 units to the Restarting this D400 switch panel 16 STATE CONFLICT BOTH D400s are STANDBY Check the wiring of the D400 units to the Restarting this D400 switch panel There could also be loss of power to the switch panel as a powered down switch panel reads as standby to the D400 17 Configuration read failed Entering into Active Redundancy serial ports are not configured Non Redundant mode in the connection configuration of the D400 18 Redundancy is DISABLED Entering into Active Diagnostic message only Redundancy is Non Redundant mode disabled in the configuration 19 Failed to open switch panel port Entering into This message indicates a software failure Active Non Redundant mode of the D400 Either the configuration files of the D400 have been corrupted or the D400 has not started properly 202 SWM0066 2 75 0 General GE Energy Sr No Diagnostic log messages Details 20 Failed to open heartbeat port Entering into This message indicates a software failure Active Non Redundant mode of the D400 Either the configuration files of the D400 have been corrupted or the D400 has not started properly 21 Error in reading switch panel Entering into This message indicates a software failure Active Non Redundant mode of the D400 Either the configuration files of the D400 have been corrupted or the D400 has not started properly 22 Failed to rec
95. L TE A d GS 23 17 61 S Commit Changes Discard Changes Serial Network Client Map Server Map Alarm Calculator System Wide User Management HMI Access Manager Oneline Designer Bnew Gopan hefse EIR AESI Read System Boolean System Status Neme faa Poll interval 10 Please specify which Analog Inputs you would like to collect for Function 1 15 aaa rane See Fragen N System Status Pol Type Fast Point Number Point Name Wultiplier Ofset Poll Type Point Group Fastto Slow Po Cycle Fre 10 C6_000 10 0 0 Once Pval a Retry Count 3 10 0 0 Once Pval Degraded Time 30 1 0 0 0 Once Pval 1 0 0 0 Once Pval 1 0 O 0Fast Pval 1 0 0 0 Fast Pval 10 OOFast Pval 10 OOFast Pval 10 00Fast pva 10 00Fast Pval 10 00Fast Pval 10 OOFast Pval 1 0 OOF ast Pval 1 0 0 0Fast Pval 1 0 00Fast PVal 1 0 0 0Fast Pval 10 0 0Fast Pval 10 00 Siow Pval 1 0 0 0 Siow Pval 1 0 0 0Fast Pval 1 0 O OFast Pval 10 OOFast Pval 1 0 O OFast Pval 10 OOF ast Pval 10 00Fast Pval 10 OOFast Pval 30 FC6_030 10 00Fast Pval Pom interval were an 1a AAE Cr T Element mhich Specifies the defosit poll interval Map File 201 Tiumi 87 Al Points NUM Done Read System Variable Settings are available on the Read System Variable tab on the Client Map tab The D400 provides mapping settings for read system variables as shown in Table 63 Table 63 Read System Variable Mapping Settings Setting Description Range Default Point Number of the point in the
96. Low Range Value Low Range Line The color to apply to the line but only when the Any 24 bit RGB Black Color summation of the three Analog Status values Color exceeds the configured Very Low Range Value and is less than the Low Range Value Normal Range Line The color to apply to the line but only when the Any 24 bit RGB Black Color summation of the three Analog Status values is Color greater than or equal to the configured Low Range Value and is less than or equal to the High Range Value High Range Line The color to apply to the line but only when the Any 24 bit RGB Black Color summation of the three Analog Status values Color exceeds the configured High Range Value and is less than or equal to the Very High Range Value Very High Range The color to apply to the line but only when the Any 24 bit RGB Black Line Color summation of the three Analog Status values Color exceeds the configured Very High Range Value 162 swm0066 2 75 0 General Table 144 Range Aware Value Box Object Settings GE Energy Setting Description Range Default Object Identifier Object Identifier of an Analog Status or Accumulator Existing Analog None Status object Status or Accumulator Status Object Identifier X X horizontal pixel position from the top left corner 0 to the Draw Panel 0 of the screen to the top left corner of the area used width less the to di
97. Manager Digital Input Points Point Name Description SystemRedundant TRUE if the D400 is configured to be redundant FALSE if the D400 is not redundant StandbyD400Comm Fail TRUE if communications with the redundant D400 unit have failed FALSE if not OFFLINE if the D400 is in non redundant mode StandbyD400inServiceMode TRUE if the standby D400 is in service mode FALSE if not OFFLINE if the D400 is in non redundant mode StandbyD400NotAvailable TRUE if the standby D400 is in failed mode False if not OFFLINE if the D400 is in non redundant mode D400 Substation Data Manager Software Configuration Guide 135 GE Energy Point Name Description D400AActive TRUE if the D400 has been designated as unit A See note OFFLINE if the D400 is in non redundant mode D400BActive TRUE if the D400 has been designated as unit B OFFLINE if the D400 is in non redundant mode Config Sync in Progress TRUE if configuration synchronization is currently in progress FALSE if not OFFLINE if the D400 is in non redundant mode Standby Config Out of Sync TRUE if the configurations on the active and standby D400s do not match FALSE if they do match OFFLINE if the D400 is in non redundant mode Note The D400 is designated as unit A or B depending on the input block it is wired to on the RS232 switch panel You may issue Local Force or Alarm Inhibit commands on these points A
98. P3 Master Station is configured on serial port 1 of the D400 Under Configuration Parameters four rows are added and configured as follows Name D400 Address Map File Application Auto Start Up Parameters LRU A 1 LRUA xml Use Default v LRU B 2 LRUB xml Use Default v LRU C 3 LRUC xml Use Default v LRU D 4 LRUD xml Use Default v D400 Substation Data Manager Software Configuration Guide 25 GE Energy Figure 6 Example Remote LRU Configuration D400 Substation Data Manager System Database Serial Connection to DNP3 Master Station External Device DNP3 Master Station In this example the DNP3 master station can connect to each of the four LRUs through the serial connection COM1 Each LRU has a unique DNP address so that they can be communicated with independently Each LRU can reference the same or different server map file If the same server map file is referenced by multiple LRUs each of these LRUs will serve the same data to the remote DNP3 master station DNP3 Server Application Parameters Regular and advanced DNP3 server settings are available under the Application Parameters field See Table 7 and Table 8 Table 7 DNP3 Server Communication Settings Regular remote station to confirm an application message before re sending it Set the value much higher for a dial up modem connection i e 60000 Setting Description Range Default Application Retry Nu
99. The starting address of this entry 1 to 16777215 Address Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag D400 Substation Data Manager Software Configuration Guide 97 GE Energy Setting Description Range Default Per Point Settings Address The address of this entry Read only N A N A Control Type The type of control to operate Trip Close Persistent Regulating Persistent Short Pulse The control duration in seconds of the short 1to 1000 Duration pulse output 2147483647 Long Pulse The control duration in seconds of the long 1to 2000 Duration pulse output 2147483647 Transmission The type of transmission used for control Select and Select and Type command execution either a select and Execute Execute execute command sequence or direct execute Direct Execute command sequence Source Point First of two digital input source points selected Not editable System One from the Point Picker to comprise the 4 state assigned point being monitored Based on user identifier configured DI point name prefixed with system assigned identifier Source Point Second of two digital input source points List of points N A Two selected to comprise the 4 state point being based on monitored configured Dis Double Point Table 85 Double Point Mapping Settings Setting Description Range Default Info Object Settings Info Object The name of th
100. Ticket with Session Ticket Access Manager 10 swmoo66 2 75 0 General GE Energy 1 3 Types of Applications The D400 makes use of three types of embedded software applications to collect present and manipulate data These are called client server and automation applications respectively The input and output data of these applications is stored in a real time database commonly referred to as the System Point Database Client Application This type of application typically interfaces with a substation device over a communications channel and collects data points from it The client application writes input point values to the real time database and may process control requests Known previously within GE embedded devices as a Data Collection Application DCA Server Application This type of application typically allows a GE Energy gateway device to communicate with a master station or host computer over a communications channel The server application reads input point values from the real time database and sends control requests to it Known previously within GE embedded devices as a Data Presentation Application DPA Automation Application This type of application manipulates data within the real time database The automation application has the ability to examine the status of defined input points in the real time database and accept control requests from server applications or other automation applications The autom
101. Use Frozen Value Date and Time Freeze Date and Time Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Property settings are available in the lower pane of the Read Only Registers tab The configuration settings defined in D400 Substation Data Manager Software Configuration Guide 119 GE Energy Table 110 are used to configure the default values for all read only registers defined in the MODBUS server map 120 swm0066 2 75 0 General Table 110 Read Only Register Properties GE Energy Setting Description Range Default Default Point The attribute of the point that should be polled Value Value Value To Use by default Frozen Value Date and Time Freeze Date and Time Default Default scale factor of the point m of formula Full range of 64 1 0 Multiplier mx b bit Float Default Offset Default scale factor of the point b of formula Full range of 64 0 0 mx b bit Float Read Write Registers Mapping settings are available on the upper pane of the Read Write Registers tab as shown in Table 111 Table 111 Read Write Register Mapping Settings Setting Description Range Default Address The MODBUS address assigned to the point 0 to 65535 Xx IED System Point Identifier Consists of Home N A Sy
102. X1 Y2 position start of line and or the X2 Y2 Start Arrow End position end of line Arrow or Both Start and End Arrows Line Type Defines the type of line to draw One of Solid Solid Dotted or Dashed Line Color Defines the color to apply to the line Any 24 bit RGB Black color Line Width Defines the pixel width of the line 1 to 100 1 156 swm0066 2 75 0 General Table 141 Raise Lower Control Object Settings GE Energy Setting Description Range Default Primary Output Point identifier of a digital output point where the Existing digital None Point Identifier identifier consists of the device name and point output point descriptor identifier Function Code The protocol function code to pass as part of the One of Direct None digital control command sent to a device Operate Direct Operate with No Acknowledgement Select Before Operate Select Operate Primary Pulse On Primary control pulse on time in milliseconds 0 to 65535 0 Time Primary Pulse Off Primary control pulse off time in milliseconds 0 to 65535 0 Time Raise State Control Protocol control code to send as part of the control One of Pulse On None Code command when the user requests to send a Raise Pulse Off Trip or Close Lower State Protocol control code to send as part of the control One of Pulse On None Control Code command when the user requests to send a Lower Pulse Off Trip or Close Repeat Count
103. a used to display 1 to the Draw Panel 40 the object width Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 Rotation Angle of clockwise rotation in degrees to apply to 0 90 180 270 0 the image File Path File path of alternate non default image to display Any existing server None side image file URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load when a user selects Any valid URL None the object address 164 swm0066 2 75 0 General Table 146 Rectangle Object Settings GE Energy Setting Description Range Default x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 t
104. adjusts the mix of Red Green and Blue values RGB Red Green Blue Adjust Green and Blue values on the scale to a maximum of 255 each Global Settings To configure global settings e Onthe Alarm Configuration tab select Global Configuration and configure the settings Settings are available on the Alarm Configuration tab The D400 provides the global settings as listed in Table 122 D400 Substation Data Manager Software Configuration Guide 131 GE Energy Table 122 Alarm Global Settings Setting Description Range Default Maximum Maximum number of alarms both active and 1 to 25000 10000 Number of historical that can be present on the Active Alarms Alarms and Historical Alarms pages Buffer Overflow Whether to delete oldest alarms or reject incoming Overwrite oldest Overwrite Deletion Method alarms when the maximum number of alarms is reached alarms Reject new alarms oldest alarms User Email Time to wait in seconds to buffer alarm email 0 to 3600 30 Notification messages before sending all of them as a single email Delay to all configured email users A setting of zero disables this feature it does not result in instantaneous sending Buffer Flush Inactivity period in 1 second increments after which 10 to 100 30 Rate the latest alarm updates to the database are written to the CompactFlash disk Saves on CPU usage by buffering the latest alarm updates internally a
105. anager Software Configuration Guide 157 GE Energy Setting Description Range Default Secondary Control State If Secondary Output Enabled set to True whether to associate the secondary output point with the Raise State or Lower State The primary outpoint point will be associated with whichever state the secondary is not associated with On or Off Off Feedback Enabled Whether or not to enable feedback status Note In a distributed system the only reliable way to determine the success of a control operation is through a hardwired digital input or analog input point providing the feedback of the process state being controlled True or False False Analog Feedback Point If Feedback Enabled set to True point identifier for a single analog input point where the identifier consists of the device name and point descriptor Existing analog input point identifier None 158 swm0066 2 75 0 General Table 142 Range Aware Bar Chart Object Settings GE Energy Setting Description Range Default Object Identifier Object Identifier of an Analog Status or Accumulator Existing Analog None Status object Status or Accumulator Status Object Identifier x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display
106. and utilities that are provided with the D400 Table 1 List of D400 Applications IEC 61850 optional Hydran SEL Binary MODBUS Client Server Automation Tools Utilities DNP3 IEC 60870 5 101 104 Alarm Runtime HMI IEC 60870 5 101 DNP3 Calculator Configuration Tool IEC 60870 5 103 MODBUS LogicLinx optional System Utilities System Point Database HMI Access Manager User Management One Line Designer amp Viewer optional IEC 61850 Loader optional 12 SWM0066 2 75 0 General GE Energy 1 5 About the DNP3 Software The DNP3 Distributed Network Protocol software in the D400 is layered to be consistent with the International Electrotechnical Commission IEC Enhanced Protocol Architecture EPA The protocol software comprises a Physical Layer Data Link Layer and Application Layer Both the DNP3 client and server applications implement the Application Layer and Data Link Layer and support the serial Physical Layers The Ethernet layer is implemented using separate software the DNP3 Transport Layer application Figure 3 EPA Layers for the DNP3 Software D400 System Point Database DNP3 client and server DNP3 client and server DNP3 Transport applications client and server D400 Substation Data Manager Software Configuration Guide 13 GE Energy Configuration Overview To get the D400 up and running in your substation automation system you need to configure it fo
107. ange Default Device Name Text description to identify the redundancy 1 to 32 ASCII RSWITCHx connection characters Ensure that both D400 units in the redundant setup have connected the watchdog cable to the same serial port number In a redundant setup the D400 Configuration Manager synchronizes configurations between the D400 units and this setting will be lost if there is a difference between the two Single Generic ASCII The Generic ASCII application is designed to extract data from devices using an ASCII based communications protocol over a serial port The information collected from these devices is stored in the internal system database of the D400 Fault and Event Information is collected from connected devices as well as Protective Relay Fault Information to facilitate user notification of faults D400 Substation Data Manager Software Configuration Guide 43 GE Energy The following settings are used when configuring a Single Generic ASCII connection Table 24 Single Generic ASCII Setting Description Range Default Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Line ID Text description to identify the electrical 1 to 32 ASC Line X transmission line associated with this serial characters connection Device ID Text description to identify the device 1 to 32
108. anged file to the user CompactFlash disk gt gt To set up a PPP interface 1 Start a terminal session and log into the D400 2 At the D400 gt gt prompt type vi etc ppp options ttyS1 and press Enter The default D400 IP address and host IP address are displayed in the format D400 IP address host IP address as follows 192 168 169 2 192 168 169 1 3 If desired modify the host IP address the second IP address displayed To save your changes and exit the command type wq and press Enter The D400 command prompt appears 5 Atthe D400 gt gt prompt enter the following commands mkdir p home D400_SysConfig etc ppp cp etc ppp options ttyS1 home D400_SysConfig etc ppp The configuration is saved to the User CompactFlash 6 Ifyou haven t already done so set up the host computer for a basic dial up connection and use the D400 administrator user name and password The D400 is now set up to transfer data through a dial in connection D400 Substation Data Manager Software Configuration Guide 185 GE Energy 8 5 Pass Through Connections For client applications that support pass through connections these connections are accessible through a TCP port on the D400 You can connect to the device through the D400 using PC based configuration tools and if necessary COM port redirection software gt gt To enable client pass through connections 1 On the System Wide tab of the D400 Online Configuration Tool click Sec
109. appens at the data link layer Wait Between The minimum time in seconds to wait 0 0 to 60 0 0 0 Messages between polls measured from receiving the response of one poll to the beginning of the next poll 40 swmM0066 2 75 0 General GE Energy Setting Description Range Default Quick Check Specifies whether or not quick check is Enabled Enabled performed between standard polling for Disabled class data Reply Poll Count The Maximum number of times to poll a Oto 255 10 device for Class 2 and 1 data subsequent to receiving a positive acknowledgement at the link layer CONFIRM ACK in response to a SEND CONF user data request at the link layer that was sent due to an application level request Max Poll Count The maximum number of times to poll a 1to 255 3 device for Class 1 data before changing to poll the next device while performing background autonomous polling Reset Link The function code for the reset link request RESET_CU RESET_FCB Function Code RESET FCB LogicLinx Device A LogicLinx Device connection is used to define a communications link between the LogicLinx application running on the D400 and a PC running the LogicLinx Editor This connection type can only be created using the LogicLinx Wizard in ConfigPro CCE Once assigned the connection is displayed to provide you with port details Modbus Master Stations The following settings are used when configuring a
110. applications varies depending on the application The D400 currently supports the following automation applications e Alarm Annunciator e Calculator e LogicLinx optional 6 1 Configuration Overview Configuring automation applications for use on the D400 typically includes the following steps 1 Select data points 2 Define application points 3 Setup the point manipulations and associated settings 4 Save and run the configuration file by committing the changes D400 Substation Data Manager Software Configuration Guide 123 GE Energy 6 2 Alarm In the substation monitoring environment alarms are used to indicate the occurrence of an event that requires attention for example the opening of a breaker due to an over current condition The D400 Annunciator monitors a given set of digital input points for alarm conditions Each configured alarm has three points associated with it in the D400 system two digital input points and one analog input point Upon detecting an alarm condition on a source point or a group of points the Annunciator creates a record in the D400 database and presents the alarm to the operator on the D400 Active Alarms page for further action Once an alarm is acknowledged it is archived by moving it from the Active Alarms page to the Historical Alarms page Alarm Types The following alarms types are configurable for the D400 Annunciator e Absolute 2 state Generates an active alar
111. arm groups e Onthe Alarm Configuration tab select a group under Alarm Groups and configure the attributes including the alarm information columns to display on the Active Alarms page Settings are available on the Alarm Configuration tab The D400 provides the alarm group settings as listed in Table 120 128 swm0066 2 75 0 General GE Energy Figure 14 Alarm Group Configuration Page D400 Configuration Mozilla Firefox loj x File Edit View History Bookmarks Tools Help P COA amaie J GE Energy comowaton Sled Q 7 03 E99 al NO Sl spent pp Commit Changes Discard Changes Serial l Network Il Client Map Server Map Alarm Calculator System Wide User Management HMI Access Manager OneLine Designer kasae Reset Alarm Points Global Settiniys Global Configuration Name Value Alarm Group Configuration Alarmable Foreground Color g Alarmable Background Color roup2 croup3 Alarmable Blink Rate 5 Groups Normal Foreground Color System5 Normal Background Color Normal Blink Rate 0 Acknowledge Foreground Color Acknowledge Background Color Acknowledge Blink Rate 0 Alarmable Foreground Color Select the foreground color of the text that displays when a point belonging to the group is in an active alarm condition Color choices available in Color palette window Global Settings NUM Applet AnnunciatorConf started Table 120 Alarm Group Settings Group Name Def
112. ary Control State If Secondary Output Enabled set to True whether to associate the secondary output point with the On State or Off State The primary outpoint point will be associated with whichever state the secondary is not associated with On or Off Off Feedback Enabled Whether or not to enable feedback status Note In a distributed system the only reliable way to determine the success of a control operation is through a hardwired digital input or analog input point providing the feedback of the process state being controlled True or False False Feedback Size If Feedback Enabled set to True whether to utilize 2 state feedback or 4 state feedback 2 State or 4 State None Primary Feedback Point Identifier If Feedback Enabled set to True point identifier for a single two state feedback point consisting of a single digital input point or of the first of two digital input points required to represent four state status where the identifier consists of the device name and point descriptor Existing digital input point identifier None D400 Substation Data Manager Software Configuration Guide 149 GE Energy Setting Description Range Default Secondary If Feedback Enabled set to True and Feedback Size Existing digital None Feedback Point set to 4 State point identifier for the second of two input point Identifier digital input poi
113. ased on the device s capabilities frequency of polling selected data points etc The D400 includes the following default client maps e DNP3 e Hydran e SEL Binary e MODBUS You can use these default client maps or customize them for your system requirements Once you create a client map file it becomes available to select on the Configuration page when assigning device connections Note If you are running a LogicLinx program on your D400 and you change the point mapping you must synchronize the configuration within ConfigPro CCE to ensure that your LogicLinx mappings are still valid Creating Client Maps gt gt To create or edit a client map 1 On the Configuration page select the Client Map tab 2 Click New to create a new client map or Open to edit an existing client map 3 Select the device protocol type and then create or select the device map file 4 Edit the data type and device protocol settings as desired 5 Click Save and enter a name for your map file D400 Substation Data Manager Software Configuration Guide 57 GE Energy Tip Keep the default map files as basic templates To create custom templates modify the default map files click Save and then enter a new template name For more information on creating a client map refer to the D400 online Help 4 3 58 SWM0066 2 75 0 General IEC 60870 5 101 104 The IEC 60870 5 101 104 Client map defines how the D400 is configured to poll data fr
114. at the 1 to 255 10 application waits before sending a supervisory acknowledgement S frame value of t2 54 SWM0066 2 75 0 General GE Energy Setting Description Range Default Idle Timeout The period during which no messages are 1 to 255 20 received in seconds that the application allows pass before sending a test frame value of t3 Max APDU Frame The maximum length in octets of APDU 253 Not editable Length frames D400 Substation Data Manager Software Configuration Guide 55 GE Energy Configuring Devices You can customize the D400 to poll receive and store the necessary data from connected Intelligent Electronic Devices IEDs Client applications in the D400 allow the D400 to collect event and or static data from devices through different communication protocols and store the data in the system point database The D400 configuration tool supports configuration of protocol specific object references scaling factors and user defined names for various objects configured for collection Where applicable you can also configure additional device level settings for the same protocol at the same time This chapter gives detailed information for configuring specific types of devices For step by step information on using the configuration tool refer to the D400 online Help 4 1 Configuration Overview Configuring the D400 to communicate with devices typically includes the fo
115. ation Note The D400 Configuration Manager does not synchronize the configuration parameters defined in the d400cfg utility You must apply these settings manually gt gt To use the D400 Configuration Manager 1 Start a terminal session and log into the D400 2 Atthe prompt enter the following command configmgr pl lt command line parameters gt When executing the application the following command line parameters are accepted Parameter Description Arguments m Mode network local or tar D400 Substation Data Manager Software Configuration Guide 187 GE Energy Parameter Description Arguments IP Address network mode only The IP address of the remote D400 device Lower case L Local Path local and tar modes only The local path to transfer the configuration to In local mode the entire directory structure containing the configuration files is copied to a specified location for example the path to a USB drive may be dev sda1 In tar mode the configuration files are stored in a single compressed archive file When specifying the path include a filename ending in tar gz Username network mode only Username that is used to access the remote D400 unit Password Prompt network mode only yes no If a password is required to access the network D400 device entering yes for this parameter will prompt you for a password during the connectio
116. ation Data Manager User s Manual 994 0089 for instructions on how to access the D400 s command line interface 8 3 D400 Configuration Utility The D400 Configuration Utility is used to configure operating system Linux specific settings on the D400 Using the D400 Configuration Utility you can perform the following actions e Control user authentication mode e Configure network and network interface settings e Configure secure access e Configure host names e Configure time synchronization e Reset system logs e Reset mSQL database tables e Reset NVRAM e Configure KVM monitor settings The D400 Configuration Utility differs from the D400 Configuration Tool in the D400 HMI in that it directly modifies Linux system configuration files rather than generating XML configuration files D400 Substation Data Manager Software Configuration Guide 171 GE Energy gt gt To start the D400 configuration utility e Atthe D400 gt gt command prompt type d400cfg and press Enter The D400 Configuration Utility menu appears 3 84 165 242 PuTTY D400 Configuration Utility Menu Configure Authentication Configure Network Settings Configure Network Interfaces Configure Secure Access Configure Host Names Configure Time Sync Reset System Logs Reset mSQL Database Tables Reset NVRAM 10 Local HMI 11 Redundancy 12 Quit orn wnb Wh to Enter Your Choice Between 1 and 12 To select a function t
117. ation application is able to process this data and then update the values of the digital inputs and analog inputs owned by the automation application or output points belonging to another application Known previously within GE embedded devices as a Data Translation Application DTA System Point Database Information collected by the D400 is stored in a central database on the D400 called the System Point Database The database is a SQL Server database and includes all types of system information including communication statistics present values peak values and event records The real time database is dynamically updated for all the D400 system inputs outputs as substation events take place and information is exchanged between applications Figure 2 illustrates a simplified relationship between the three application types and the system point database within the D400 D400 Substation Data Manager Software Configuration Guide 11 GE Energy Master Station Server Application DPA System Point Database Automation Application DTA Figure 2 Data Applications Within the D400 Client Application DCA D400 Substation Data Manager Device s 1 4 D400 Applications Table 1 lists the configurable applications that are available for the D400 The applications available to you depend on your D400 purchase and configuration You set up and run the applications using a variety of tools
118. ation settings are available for device communications when configuring SEL serial connections on the Serial tab Figure 9 SEL Binary Client Map Page D400 Configuration Mozilla Firefox Ble Gat yew Higtory Bookmarks Tools Hel a gt COR gt ice AMORE Pelee Pa fe PE Commit Changes Discard Changes Serial Network Client Map Server Map Alarm Calculator System wide User Management HMI Access Manager OneLine Designer Bnew Wopen Hs SPLATT SIL Demand Analog input Peak Demand Analog Input SER Digital input Name Value Number of Targets 1 Please specify which Analog Inputs you would like to collect for Function 1 ee e Number of Remote as 4 Point Name Multiplier Offset Point Group Pulse Remote Bas No IAV Present Values 10 00 Pval Number of Cakulation Bio IDW Prasant Values 1 0 0 0 Pval Block 1 Calculaton Type 3 Currents Only ICW1 Present Values 10 00 Pval Biock 2 Caicutason Type 3 Currents Only 10 00 Pval Block 3 Calculaton Type 0 Standard 2 10 00 Pval Block 4 Calculaton Type 0 Standard ICW2 Present Values 1 0 0 0 Pval Mumber of Targets The number of Target Rows retemed by the device in the Fast Meter command Map File SEL 587 xmi 6 Al Points NUM nais Monday February 11 2008 Fast Meter Analog Channel Settings available on the Fast Meter Analog Channel tab on the Client Map tab The D400 provides the mapping settings for fast meter analog outputs Function code 1 as shown in Tab
119. ault group name of the selected alarm group Not editable As selected Alarmable Foreground color Red Green Blue to be displayed in See Table 121 for Foreground alarm text when an alarm from a point belonging to options Color this group becomes active Alarmable Background color Red Green Blue to be displayed in See Table 121 for Background alarm text when an alarm belonging to this group options Color becomes active Alarmable Blink Rate in one tenths of a second at which the active 0 to 100 Rate alarm text blinks Value Rate Second Blinking does not occur 1 10th or 10 times per second 2 10th or 5 times per second 20 10th or 1 per 2 seconds Normal Foreground color Red Green Blue to be displayed in See Table 121 for Foreground alarm text when an alarm belonging to this group options Color becomes normal Normal Background color Red Green Blue to be displayed in See Table 121 for Background alarm text when an alarm belonging to this group options Color becomes normal D400 Substation Data Manager Software Configuration Guide 129 GE Energy Setting Normal Blink Rate Value Acknowledge Foreground Color Acknowledge Background Color Acknowledge Blink Rate Rate in one tenths of a second at which the normal alarm text of alarms belonging to this group blinks Rate Second Blinking does not occur 1 10th or 10 times per second 2 10th or 5 times per second 20 10th or 1 per 2 seconds Foregroun
120. ault transmission delay in 0 to 60000 0 milliseconds that is used by the application to perform a Clock Sync of the remote device when the TX Delay Acquisition is disabled 60 swM0066 2 75 0 General IEC 60870 5 104 Settings are available in the IEC 60870 5 104 pane Table 35 lists the device specific protocol settings Table 35 IEC 60870 5 104 Properties GE Energy Setting Description Range Default Information The number of octets used in the information Not editable 3 Object Address object address field Length Cause of The number of octets used in the Cause of Not editable 2 Transmission Transmission field Length Default TX Delay The transmission delay in milliseconds that is O to 60000 0 used by the application to perform a Clock Sync of the remote device Controls with Time Specify if the application is to include a time Enabled Disabled Tag tag with control requests Disabled Max TX Frames The maximum number of information frames 1 to 32 767 8 Before Ack that the application transmits before it must receive an acknowledgement message value of w Max RX Frames The maximum number of information frames 1 to 32 767 12 Before Ack that the application receives before it must send an acknowledgement message value of k Connect Timeout The maximum time in seconds that the 1 to 255 30 application waits for the TCP transport layer to establish a connection value
121. belongs List of defined Group point groups assigned to ID number 0 P2 Name Text description of the second point in the Up to 128 DP XB map file for this double point object characters P2 ON State Text description of the 1 state for the second Up to 32 ON point characters P2 OFF State Text description of the O state for the second Up to 32 OFF point characters P2 Group Point group to which the second point List of defined Group belongs point groups assigned to ID number 0 Integrated Total Table 40 Integrated Total Element Settings Setting Description Range Default Address The address of this information object 1 to 16777215 Incremented element by 1 from starting address Point Name Text description of the point in the map file Up to 128 IT X characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 64 SWwM0066 2 75 0 General GE Energy Measurand Table 41 Measurand Element Settings Setting Description Range Default Address The address of this information object 1 to 16777215 Incremented element by 1 from starting address Point Name Text description of the point in the map file Up to 128 MX characters Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of
122. bject The name of the information object as entered N A N A Name on the New Info Object window Read only Address The address of this entry N A N A Interrogation The interrogation group used for reporting this Not Used Not Used Group information object Group 1 Group 16 Interrogation Specify whether to include this information Include Include Response object in a general interrogation response Exclude 102 swmo066 2 75 0 General GE Energy Setting Description Range Default Report Class Specify if spontaneous events for this object are Class 1 Class 1 reported as class 1 or class 2 messages Applies Class 2 to unbalanced mode and spontaneous events only Periodic Update The type of periodic updating Not Used Not Used Mode Background Scan Periodic Update The time in seconds between periodic reports 0 to 65535 0 Interval Used only if Periodic Update Mode is not set to Not Used Periodic Report Specify if periodic reporting if enabled should Disabled Disabled On Power Up begin immediately upon startup Enabled Per Point Settings Bit Position Specifies the bit position within the information 1 to 32 Incremented object element from 1 IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected DI Assigned point from the Point Picker Read only Identifier Point Name Text description of the
123. ble system event messages displayed by the D400 Redundancy Manager These messages are entered in the system event log of the D400 These are notifications of significant events not necessarily errors If it indicates an error or failure consult the diagnostic log for details GE Energy Table 158 D400 Redundancy System Log Messages Sr No System Event log messages Details 1 Redundancy Manager Started in Active Mode 2 Switching to standby mode 3 Sent message to Software Watchdog to RESTART AIl applications 4 Sent message to Software Watchdog to STOP All The D400 is being placed in applications failed mode 5 Heartbeat s received from Standby system A lost connection with the Declaring peer D400 back in Standby State standby has been restored 6 Redundancy Manager Child Started 7 Redundancy Manager Application Started 8 Redundancy Manager Started in Active Non Redundant Mode 9 Heartbeat s missed from Standby system The standby D400 has Declaring peer D400 as Failed stopped responding to communications 10 Heartbeat s missed from Active system The active D400 has stopped Declaring peer D400 as Failed responding to communications 11 Redundancy Manager Started in Standby Mode 12 Switching from Standby to Active mode Table 159 describes the error codes that may be returned by the D400 Configuration Manager Table 159 Configuration Manager
124. ces to produce additional local pseudo data points The real data collected from devices and the calculated data are stored D400 Substation Data Manager Software Configuration Guide 9 GE Energy in a database in the D400 and are available to pass on to SCADA master stations and or HMI Human Machine Interface applications The D400 is able to accomplish these tasks through the use of embedded software applications running on the Linux operating system You configure these software applications to set up the D400 to operate as your system requires Figure 1 D400 HMI Overview Newly generated active alarms active alarm resets and alarm archive indications Annunciator Alarm Acknowledgement Configuration Information Ponit Mappings and One Line drawing Home Page Configuration Email Configuration Login Request with Configuration and Point Group details credentials Telnet Server Files Login Request with eaenia SSH Server RTDB Point data Digital Control 1 0 Traffic Status Tagging Inhibit Status Force D400 Repository Value Status Statistics HMI eN S Operator Notes and SOEs PRFs Historical Alarm data And initial set of Active Alarms System Logs System Event Log Diagnostic Log Command monL Log HMi Event Log Firmware and application Login Credentials Linux version list Authorization File Login Request with System Status Authorization Session Ticket Response with Logout Request Session
125. ct Existing Digital None Status Object Identifier x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 40 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Orientation Whether to draw the switch state representations in Horizontal or Horizontal a horizontal or vertical orientation Vertical Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 Line Color Defines the color with which to draw the lines that Any 24 bit RGB Black comprise the switch display Color Line Width Line width in pixels 1 to 100 1 00 Switch State f the Digital Status Object is a 4 State Digital The One of Open None switch state to display when the digital input 1 value Closed In Transit low bit corresponds to the O state and the digital or Invalid input 2 value high bit corresponds to the O state 0
126. ct Operate Primary Pulse On Primary control pulse on time in milliseconds applies 0 to 65535 0 Time only to Control Codes of type Pulse On Pulse Off Trip or Close Primary Pulse Off Primary control pulse off time in milliseconds 0 to 65535 0 Time applies only to Control Codes of type Pulse On Pulse Off Trip or Close On State Control Protocol control code to send as part of the digital One of Latch On None Code control command when the user requests to send Latch Off Pulse On an On state Pulse Off Trip or Close Off State Control Protocol control code to send as part of the digital One of Latch On None Code control command when the user requests to send Latch Off Pulse On an Off state Pulse Off Trip or Close On State Control The user defined text used to describe the operation Any text Textual Text to turn the digital control to on representation of the configured control code Off State Control The user defined text used to describe the operation Any text Textual Text to turn the digital control to off representation of the configured control code Repeat Count Number of times to consecutively repeat a control 1 to 255 code applying the pulse on and pulse off times to each control pulse repetition applies only to Control Codes of type Pulse On Pulse Off Trip or Close A value of 1 means to issue the control code once e g no repetition 148 swm0066 2 75 0 General GE
127. ct width Background Color The background color with which to fill the object Any 24 bit RGB Red Color Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load when a user selects Any valid URL None the object address 152 swmM0066 2 75 0 General Table 137 Ground Object Settings GE Energy Setting Description Range Default x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 40 the object height Width
128. d System Boolean Mapping Settings Setting Description Range Default Point Number of the point in the device Analog Input 0 to 65535 Incremented Map from 0 Point Name Text description of the point in the Analog Input Up to 128 RSB xxx Map characters ON State Text description of the 1 state Up to 32 ON characters OFF State Text description of the 0 state Up to 32 OFF characters Poll Type The type of poll to be taken of the point See Table 64 Fast Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 System Status Settings are available on the System Status tab on the Client Map tab The D400 provides mapping settings for system status points as shown in Table 66 82 SWM0066 2 75 0 General Table 66 System Status Mapping Settings GE Energy Setting Description Range Default System Status Text description of the point in the Analog Input Up to 128 SS Xxx Name Map characters Word Position Specifies the word index that contains the Oto 3 0 system status Bit Position Specifies which resulting integer is used to 0 to 23 0 determine the state of the DI Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 Device Properties Settings are available in the Device Properties pane on the right of the Client Map tab Table 67 lists device specific settings for
129. d color Red Green Blue to be displayed in alarm text when an alarm belonging to this group becomes acknowledged Background color Red Green Blue to be displayed in alarm text when an alarm belonging to this group becomes acknowledged Rate in one tenths of a second at which the alarm text of alarms belonging to this group blink when acknowledged Value Rate Second Blinking does not occur 1 10th or 10 times per second 2 10th or 5 times per second 20 10th or 1 per 2 seconds Default a See Table 121 for Black options B See Table 121 for options All foreground and background colors are in 24 bit RGB format and can be selected and modified using the Swatches HSB or RGB color palettes see Figure 15 Table 121 lists the available color palettes for each Foreground Color and Background Color setting for each alarm groups on the Alarm Configuration page 130 swm0066 2 75 0 General GE Energy Figure 15 Color Palette Window x Swatches HSB RGB mm pE E ae Cs IE BE T m mj Cea V E a a eae are Se Preview oO Cl Sample Text Sample Text Sample Text Sample Text w E O Sample Text Sample Text ok Cancel Reset Table 121 Alarm Color Palettes Color Palette Description Swatches Select individual colors from a default RGB palette HSB Hue Saturation Brightness Adjust H Hue S Saturation and B Brightness levels Hue
130. dback state required to occur in response to If 2 State one of0 None Feedback State an On State sent to a control in order for the control or 1 to be considered successful f 4 State one of 00 01 10 or 11 Off Control State The feedback state required to occur in response to If 2 State oneofO None Feedback State an On State sent to a control in order for the control or 1 to be considered successful f 4 State one of 00 01 10 or 11 Confirmation Defines whether the GUI is to display a confirmation True or False True Required dialog immediately prior to executing a control 150 swm0066 2 75 0 General Table 135 Digital Status Object Settings GE Energy Setting Description Range Default Size Whether to utilize 2 state status or 4 state status 2 State or 4 State 2 State Primary Point A point identifier for a single two state status point Existing digital None Identifier consisting of a single digital input point or of the first input point of two digital input points required to represent four identifier state status where the identifier consists of the device name and point descriptor Secondary Point If Size set to 4 State point identifier for the second of Existing digital None Identifier two digital input points required to represent four input point state status where the identifier consists of the identifier device name and point descriptor State 0 Text f Si
131. ddress of this entry Read only N A N A IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected DI Assigned point from the Point Picker Read only Identifier Point Name Text description of the point in the Binary Input Up to 128 Assigned IED map Based on selected DI point Read only characters point name Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Polarity Specifies whether or not a negative analog Bipolar Value Bipolar Value Transmission The type of transmission used for control Select and Select and Type command execution either a select and Execute Execute execute command sequence or only an execute Direct Execute command sequence Send Ackterm Specifies whether the application sends an No No ACTTERM response to the master station when yes a C_SE setpoint command completes Single Command Table 92 Single Command Mapping Settings Setting Description Range Default Info Object Settings Info Object The name of the information object as entered N A N A Name on the New Info Object window Read only Starting The starting address of this entry 1 to 16777215 Address Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag D400 Substation Data Manager Software Configuration Guide 105 GE Energy
132. ddresses include e Maintenance Also referred to as the static address this is the primary IP address and subnet mask for use by this D400 e Active Used for D400 system redundancy Whichever redundant D400 is active at the time will assume this IP address the standby unit reverts to its own maintenance IP address The active address settings should be the same on both redundant units e Alias An alternate address that can be configured to allow a secondary communications link with the D400 This is typically used for redundant LAN D25s When used within a redundant D400 system setup the alias address settings should be the same on both redundant units If your D400 contains a second Ethernet card you can configure secondary maintenance active and alias IP addresses Dynamic Address Configure the D400 to use network parameters that are provided by a DHCP server Note Dynamic addressing is not compatible with D400 system redundancy or redundant LAN D25s as the active and alias addresses are not provided by DHCP Configure Secure Access The Configure Secure Access menu allows you to configure the modes through which users can access the D400 176 SwM0066 2 75 0 General GE Energy Ee lolx al Current Configuration Configure Telnet Service Configure FTP Service Configure SSH Service Configure SFTP Service Configure Web Mode Configure Emergency Access Ports Configure Administrator Only Logins Back 1 2 3 4
133. device Analog Input O to 65535 Incremented Map from 0 Point Name Text description of the point in the Analog Input Up to 128 RSV xxx Map characters Multiplier Scale factor of the point m of formula mx b Full range of 1 0 64 bit Float Offset Scale factor of the point b of formula mx b Fullrangeof 0 0 64 bit Float Poll Type The type of poll to be taken of the point See Table 64 Fast Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 D400 Substation Data Manager Software Configuration Guide 81 GE Energy Table 64 lists the available Poll Types Table 64 Supported Poll Types Poll Type Description Fast The application schedules requests to retrieve the values of Registers Coils as quickly as possible subject to the configured Inter Poll Delay Slow The application schedules requests to retrieve the values of Registers Coils at a slower rate requests occur once a Fast Poll Cycle Count cycle has been completed Once The application schedules requests to retrieve the values of Registers Coils once upon startup and subsequently whenever the device returns to an online state after communications failure Read System Boolean Settings are available on the Read System Boolean tab on the Client Map tab The D400 provides mapping settings for read system Boolean points as shown in Table 65 Table 65 Rea
134. e Class 1 unsolicited message support for class 1 False events Unsolicited Mode Flag that enables or disables DNP3 Server True False Class 2 unsolicited message support for class 2 False events Unsolicited Mode Flag that enables or disables DNP3 Server True False Class 3 unsolicited message support for class 3 False events Unsolicited Poll Frequency in milliseconds at which the DNP3 1 to 120000 5000 Frequency Server checks for unreported data Select Timeout Time in seconds the DNP3 Server waits for an 0 1 65535 5 89 operate request before canceling the select D400 Substation Data Manager Software Configuration Guide 27 GE Energy Setting Description Range Default RTS Flow Control Flag that enables the RTS flow control signal True False Enabled It is only used when communication is over False Serial and is ignored for TCP or UDP network communications RTS Preamble RTS preamble time in milliseconds Used only 1 to 120000 20 when RTS Flow Control Enabled is set to True in Serial communication RTS Postamble RTS postamble time in milliseconds Used 1 to 120000 20 only when RTS Flow Control Enabled is set to True in Serial communication Time Offset Time offset in minutes from UTC For 1440 to 1440 0 example for Eastern Standard Time specify 300 which means UTC minus 5 hours Specify only if the Master does not use UTC within DNP3 messages DNP3 requires the time base to be UTC b
135. e D400 requests analog output status data at this interval in seconds If set to 0 the request is never transmitted 0 to 36000 Float AO Poll sec This request is never transmitted 0 tod 16 Bit AO Poll sec The D400 requests 16 bit analog output status data at this interval in seconds If set to O the request is never transmitted 0 to 36000 32 Bit AO Poll sec The D400 requests 32 bit analog output status data at this interval in seconds If set to O the request is never transmitted 0 to 36000 DI Poll sec The D400 requests digital input data at this interval in seconds If set to O the request is never transmitted 0 to 36000 DI Change Poll sec The D400 requests digital input event data at this interval in seconds If set to O the request is never transmitted 0 to 36000 DO Poll sec The D400 requests digital output data at this interval in seconds If set to 0 the request is never transmitted 0 to 36000 Acc Poll sec The D400 requests static counter data at this interval in seconds If set to O the request is never transmitted 0 to 36000 Acc Change Poll sec The D400 requests counter event data at this interval in seconds If set to 0 the request is never transmitted 0 to 36000 D400 Substation Data Manager Software Configuration Guide 79 GE Energy Change Poll sec
136. e Maximum duration in seconds to wait fora 0 100 to 300 00 1 Timeout response from the device 44 SWM0066 2 75 0 General GE Energy Setting Description Range Default Communication Number of retries on the communications O to 100 2 Retries channel before the device is determined offline Pass Through Duration in seconds for which the device 1 00 to 300 00 5 Wait Interval waits on the Serial Interface to obtain a response to a communication message received on the Pass Through socket Demand Data How many times the Fast Meter Data must O to 36000 600 Poll Cycle be retrieved before Demand Data can be polled 0 disables Demand Data polling Peak Demand How many times the Fast Meter Data must O to 36000 600 Data Poll Cycle be retrieved before Peak Demand Data can be polled 0 disables Peak Demand Data polling History Poll How many times the Fast Meter Data must O to 36000 3600 Cycle be retrieved before the History command can be sent to the SEL device 0 disables the History command Fault Reset Time Time in seconds for which the fault 0 to 3600 5 parameter pseudo points retain values from the latest fault Restrike Interval Once the first fault has occurred the time to O to 3600 30 wait in seconds before updating the Fault Pseudo points with information if subsequent faults occur before this interval has elapsed The following settings are used when configurin
137. e Value Low Range Value The value which when the real time value is lower Any 64 bit floating 0 but higher than or equal to the Very Low Range point value Value shall result in the line being drawn with the Low Range Line Color Note that Very Low Range Value lt Low Range Value lt High Range Value lt Very High Range Value D400 Substation Data Manager Software Configuration Guide 161 GE Energy Setting Description Range Default High Range Value The value which when the real time value is the Any 64 bit floating 0 same or lower but higher than or equal to the Low point value Range Value shall result in the line being drawn with the Normal Line Color Also the value which when the real time value is higher but less than or equal to the Very High Range Value shall result in the line being drawn with the High Line Color Note that Very Low Range Value lt Low Range Value lt High Range Value lt Very High Range Value Very High Range The value which when the real time value is the Any 64 bit floating 0 Value higher shall result in the line being drawn with the point value Very High Line Color Note that Very Low Range Value lt Low Range Value lt High Range Value lt Very High Range Value Very Low Range The color to apply to the line but only when the Any 24 bit RGB Black Line Color summation of the three Analog Status values is less Color than or equal to the Very
138. e are described in Table 55 below For all other info object types values entered for Function Type and Info Number are used for all information object elements that are created General Command Table 50 General Command Element Settings Setting Description Range Default Function Type The IEC 60870 5 103 function type O to 255 0 corresponding to this information object type reported by the remote device Info Number Address for this object 0 to 255 Incremented by 1 from starting address Point Name Text description of the point in the map file Up to 128 lt Info object characters name gt X Y ON State Text description of the 1 state Up to 32 ON characters 70 SWM0066 2 75 0 General GE Energy Setting Description Range Default OFF State Text description of the O state Up to 32 OFF characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Measurand Time Tag Relative Time Table 51 Measurand Time Tag Relative Time Element Settings Setting Description Range Default Point Name Text description of the point in the map file Up to 128 lt Info object characters name gt X Multiplier Scale factor of the point m of formula mx b Full range of 64 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 bit Float Point Group Point
139. e following modes are available e Stand by Monitor blanks but power supply remains on screen restores in approximately one second when reactivated by keyboard or mouse input by user e Suspend Monitor power supply shuts off screen restores in approximately 2 3 seconds e Turned off Monitor is fully powered down except for an auxiliary circuit to detect a wake up signal screen restores in approximately 8 10 seconds D400 Substation Data Manager Software Configuration Guide 183 GE Energy Note Refer to the manual that came with your monitor for more information on how it receives and responds to DPMS signals Screen Resolution Select one of three output resolutions e 1280x1024 e 1024 x 786 e 800 x 600 CAUTION Never exceed the maximum resolution of your monitor as damage may occur Refer to the manual that came with your monitor for more information Redundancy If you are configuring your D400 for use within a redundant setup you can configure redundancy application settings through the Redundancy menu The secondary standby IP configuration option is only available if a second Ethernet interface is installed and configured within the D400 ET lolx al D400 Configuration Utility Menu Redundancy 1 Enable Redundancy 2 Configure HeartBeat Timeout 3 Configure HeartBeat Retries 4 Configure IP Address of PEER D400 5 UserName of PEER D400 6 Back Enter Your Choice Between 1 and 6 il Enable Redundanc
140. e information object as entered N A N A Name on the New Info Object window Read only Starting The starting address of this entry 1 to 16777215 Address Interrogation The interrogation group used for reporting this Not Used Not Used Group information object Group 1 Group 16 Interrogation Specify whether to include this information Include Include Response object in a general interrogation response Exclude Report Class Specify if spontaneous events for this object are Class 1 Class 1 reported as class 1 or class 2 messages Applies Class 2 to unbalanced mode and spontaneous events only 98 SWM0066 2 75 0 General GE Energy Setting Description Range Default Periodic Update The type of periodic updating Not Used Not Used Mode Background Scan Periodic Update The time in seconds between periodic reports 0 to 65535 0 Interval Used only if Periodic Update Mode is not set to Not Used Periodic Report Specify if periodic reporting if enabled should Disabled Disabled On Power Up begin immediately upon startup Enabled Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag Valid Time The minimum amount of time in milliseconds 1 to 65535 1 that both digital input points must be stable before an ON or OFF state is reported 1 disables this setting Suppress Time The minimum amount of time in milliseconds 1 to 65535
141. e minutes after being generated whichever comes first 192 swm0066 2 75 0 General GE Energy Application Pseudo Points Applications may provide status information and allow functions or operations to be initiated through system and or device level pseudo points These points can be accessed through the Point Summary page of the Online HMI gt gt To access pseudo points 1 Log into the online HMI of the D400 unit 2 Click the t Point Summary button on the toolbar 3 Under the Application tab click the Details button for the selected application 4 Select the appropriate point type tab to view all points belonging to the group 5 To send a control request right click the point and select Forcing IEC 61850 Application Table 151 IEC 61850 Application Global Digital Output Point Name Description DO State Set to Retrieve All Data Sets This control queues an integrity request for every Completed 0 from All IEDs data set on every device Pending 1 Global DisableDevice This control disables communications to all Disabled 1 devices belonging to the application If disabled Enabled 0 the application does not have an open association with any of its devices or send user requests to any device When it is set to Enabled the application sets the device state to its previous state D400 Substation Data Manager Software Configuration Guide 193 GE Energy Poi
142. e object able to be manipulated or altered by the user A user may confirm that the object is selected by observing a series of eight 8 boxes located one to each corner and one to the middle of each edge a standard Windows symbols to highlight selected objects Note Even in the case of rounded objects such as circles the highlight boxes are in a square configuration Since a line is one dimensional there is space only for two highlight boxes one on each end of the chosen line Text Box The Text Box tool allows you to create a box designed specifically to insert text In the One Line Designer the user first creates the box text is added or altered by using the Properties display located on the right side of the screen Clicking into the Values entry labeled Caption allows the user to enter the desired text Other properties that may be changed include the alignment of the text inside the box limited to left aligned or centered the color of the text ForeColor the box s background color BackColor and the box s border color Double clicking in the Font value offers the user a separate dialog box that includes the ability to change both the font type and size The Text Box tool as well as other tools described below also contains the capability to link to another drawing created by the One Line Designer and stored on the D400 In the Properties Values box click the mouse into the value column associated with the URL Anchor choice
143. e ready to run the new configuration in the D400 you commit the changes The configuration tool validates your changes against the XML schema and reports any errors Once a configuration is validated and committed the previous configuration file is archived the new file is copied to the system disk and the D400 applications are restarted The following chapters describe how to configure the D400 for various substation applications D400 Substation Data Manager Software Configuration Guide 19 GE Energy Setting Up Communications The D400 supports communication connections for devices and master stations on two types of interfaces e Serial e Network The number of serial ports and Ethernet cards available for configuration depends on the hardware configuration of the D400 Refer to the D400 Substation Data Manager User s Manual The D400 supports up to 128 connected devices in total Communication Statistics The D400 maintains communication statistics and other status information for connected devices and master stations in the system point database as pseudo points This chapter describes how to set up serial and network connections for devices and master stations Settings for the communication connections are available on the Connection tab of the Configuration page in the D400 configuration tool Both devices and master station connections are set up on the same tab for the desired type of connection 20 SWM0066
144. e server map file to be used with List of user N A the specific LRU configured server map files Application Select the application parameters defining Use Default Use Default Parameters this connection The default parameters can List of user be used or a custom configuration can be customized created Refer to IEC 60870 5 101 Master application Station Application Settings configuration files Auto Start Up Indicates if the server application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots IEC 60870 5 101 Master Station Application Settings IEC 60870 5 101 settings are available under the Application Parameters field for Master Stations Table 13 IEC 60870 5 101 Master Station Application Parameters Setting Description Range Default Application Tab Info Object The number of octets used by the LRU for 1 2 0r3 2 Address Length information object addresses Time Mode Specifies if the master station is allowed to Set main use main Set main use set or use the main D400 and or local LRU time main time time Set local use local time Set local use main time Time Sync The maximum allowed time in seconds 0 to 86400 900 Timeout between time synchronization attempts from the IEC 60870 5 101 104 master station or other time source before time tagged data is reported as invalid by the LRU Not used when set to 0
145. e top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 40 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 Rotation Angle of clockwise rotation in degrees to apply to 0 90 180 270 0 the image File Path File path of alternate non default image to display Any existing server None side image file URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load when a user
146. ed when set to 0 Time to Live The time period in seconds a queued control 0 0 to 60 0 0 0 command is to be treated as active in the system If the configured value is 0 the RTBD setting is used Holding Time The maximum delay in milliseconds of 0 1 to 500000 0 0 2 reporting spontaneous data changes to the master station after the data is available for transmission Control Time The time range in seconds used to qualify a 0 001 to 86400 0 1 Window time tagged request Network Tab Comm Fail The maximum allowed time in seconds for O to 86400 30 Timeout when there is no available connection in the STARTDT state that is no communication from the master station before the application assumes communications have failed Not used when set to 0 Max TX Frames The maximum number of information frames 1 to 32 767 8 Before Ack that the application transmits before it must receive an acknowledgement message Value of w Max RX Frames The maximum number of information frames 1 to 32 767 12 Before Ack that the application receives before it must send an acknowledgement message value of k Connect Timeout The maximum time in seconds that the 1 to 255 30 application waits for the TCP transport layer to establish a connection value of t0 Send Timeout The maximum time in seconds that the 1 to 255 15 application waits for an acknowledgement after sending a frame value of t1 No Data Timeout The maximum time in seconds th
147. eive initial HB from peer D400 The active D400 never sent a heartbeat Entering into Active mode message to the standby causing the standby unit to become active Check that the active unit is functional and that the serial link between the two units is properly installed 23 STATE CONFLICT This D400 ACITVE and A Check the wiring of the D400 units to the PEER D400 ACTIVE and A switch panel Failing this D400 24 STATE CONFLICT This D400 ACITVE and A Check the wiring of the D400 units to the Peer D400 ACTIVE and B switch panel Peer D400 should fail 25 STATE CONFLICT This D400 ACITVE and B Check the wiring of the D400 units to the Peer D400 ACTIVE switch panel Failing this B D400 26 STATE CONFLICT This D400 STANDBY andA Check the wiring of the D400 units to the Peer D400 STANDBY and A switch panel Failing this B D400 27 STATE CONFLICT This D400 STANDBY and B Check the wiring of the D400 units to the Peer D400 STANDBY switch panel This could also be loss of Failing this B D400 power to the switch panel as a powered down switch panel reads as standby and B to the D400 28 STANDBY Failed to pull the switch Rejecting The D400 could not pull the switch Check Change Over request the wiring of the D400 units to the switch panel This could also be loss of power to the switch panel 29 STANDBY Config Sync failed in network The standby D400 unit failed to commi
148. eneral GE Energy Setting Description Range Default Report Class Specify if spontaneous events for this object are Class 1 Class 1 reported as class 1 or class 2 messages Applies Class 2 to unbalanced mode and spontaneous events only Periodic Update The type of periodic updating Not Used Not Used Mode Background Scan Periodic Update The time in seconds between periodic reports 0 to 65535 0 Interval Used only if Periodic Update Mode is not set to Not Used Periodic Report Specify if periodic reporting if enabled should Disabled Disabled On Power Up begin immediately upon startup Enabled Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag Per Point Settings Bit Position 1 to 32 Incremented from 1 IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected DI Assigned point from the Point Picker Read only Identifier Point Name Text description of the point in the Binary Input Up to 128 Assigned IED map Based on selected DI point Read only characters point name Invert Select if the value of the mapped points should True or False False be inverted Double Command Table 84 Double Command Mapping Settings Setting Description Range Default Info Object Settings Info Object The name of the information object as entered N A N A Name on the New Info Object window Read only Starting
149. ent Settings 2 Set System Clock 3 Set System Time Zone 4 Time Syne Input 5 Time Syne Output 6 Back Enter Your Choice Between 1 and 6 i Set System Clock Enter the current calendar date and time of day The value entered will be recorded in the D400 Set Time Zone Enter the time zone of the D400 Note The D400 uses the IEEE POSIX standard for time zone naming POSIX uses the time zone offset to get GMT from the local time that is GMT local time instead of the more common format local time GMT For example Eastern Standard Time in North America which is 5 hours behind GMT is listed as GMT 5 and not GMT 5 Time Sync Input Configures the D400 to use either IRIG B or NTP SNTP to calibrate the system clock D400 Substation Data Manager Software Configuration Guide 179 GE Energy e IRIG B Enter the IRIG B format options are TTL pulse width code Sine wave amplitude modulated and Manchester Ensure SW2 of the IRIG B Input Adapter is configured for the proper input type Fiber Optic or TTL for TTL and Manchester BNC for Sine wave e NTP Enter the IP address of the NTP server The D400 will verify if the source is accessible by pinging the address Time Sync Output The D400 can be configured to operate as an NTP time server Reset System Logs You can use the Reset System Logs menu to clear various system logs that are stored in the D400 lox 1 Check Size of Archived Logs 2 Chec
150. ent data to DNP3 masters The D400 supports the following configurable DNP3 data types e Analog inputs measured or computed values by the device e Digital inputs states of physical or logical Boolean devices e Analog outputs physical or computed analog quantities e Digital outputs physical or logical ON OFF raise lower and trip close points e Accumulators counter values e Device properties device level settings The DNP3 Server map settings are available on the Server Map tab when a DNP3 SCADA protocol type is selected Figure 11 DNP3 Server Map Page D400 Configuration Mozilla Firefox 15 x Eile Edit View History Bookmarks Tools Help gt COR HA core B ce Energy conmouaton Chex ata QI 27 2 2 95 2 S Ses Commit Changes Discard Changes h Serial Network Client Map Server Map Alarm Calculator System Wide User Management HMI Access Manager OneLine Designer Bnew open fsave GOJ Digital Input Analog Output Digital Output Accumulator Devices A at dik S E DTA Please choose which Analog Inputs you would like to IndexTo Dec IndexToHex Delete Delete All NE present to the master Index IED Point Name Multiplier Offset Dead Band Static Variation Event Variation Class Name Value Default Class Specifies a default Class for change events on the point Map File Untitled NUM Done D400 Substation Data Manager Software Configuration
151. er 0 1 2 or 3 0 Winding arrow over top of with 0 indicating to not draw a load tap changer arrow URL Address Defines the web page to load when a user selects Any valid URL None the transformer address URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page 168 swm0066 2 75 0 General Table 150 Value Box Object Settings GE Energy Setting Description Range Default Object Identifier Object Identifier of an Analog Set Point Analog Existing Analog Set None Status Accumulator Status Digital Status or Text Point Analog object Status Accumulator Status or Digital Status Object Identifier x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used t
152. for change events on the point None 3 2 1 User selected Default Settings available in the lower pane on the Accumulators tab The configuration settings defined in Table 104 are used to configure the default values for all accumulator points defined in the DNP3 server Table 104 Accumulator Properties Setting Description Range Default Default Class All ACC Events belong to this class by default None 3 Assignment 3 2 1 Default Static Type to report when the master does not 32 Bit 32 Bit Variation request any specific type 16 Bit Object 20 and 21 Default Event Variation Object 22 and 23 Type to report when the master does not request any specific type 32 Bit with Time 32 Bit without Time 16 Bit with Time 16 Bit without Time 32 Bit with Time D400 Substation Data Manager Software Configuration Guide 115 GE Energy Setting Description Range Default Frozen Static Variation Type to report when the master does not request any specific type 32 Bit with Time 32 Bit without Time 16 Bit with Time 16 Bit without Time 32 Bit with Time Frozen Event Type to report when the master does not 32 Bit with Time 32 Bit with Time Variation request any specific type 32 Bit without Time 16 Bit with Time 16 Bit without Time Default Minimum change in the ACC point value that 0 to 5000 0 Threshold constitutes
153. ftware error in the D400 Redundancy Manager has occurred 4 ACTIVE Rejecting command lt command type The user issued a command that is not gt because other D400 is in Service Mode valid when the standby is in Service Mode 5 ACTIVE Rejecting command lt command type The user issued a command that was gt because activity lt activity type gt is in rejected because another activity was progress already in progress 6 ACTIVE Rejecting command lt command The user issued a command that was type gt because other D400 is not available rejected since the active cannot communicate with the other D400 The other D400 may have failed or the serial link between the two may be disconnected 7 ACTIVE CONFIG SYNC activity response Configuration synchronization failed timeout waiting for response from standby because the standby unit failed to respond to the active The standby unit may have failed or the serial link between the two may be disconnected 8 ACTIVE Standby D400 rejected the Config Configuration synchronization failed Sync request with reason lt reason code gt because the standby unit issued an error D400 Substation Data Manager Software Configuration Guide 201 GE Energy Sr No Diagnostic log messages Details 9 ACTIVE Standby D400 failed in Config Sync Configuration synchronization in network using network mode Ethernet mode has failed The net
154. g a Single SEL Binary connection Table 26 Single SEL Binary Setting Description Range Default Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Line ID Text description to identify the electrical 1 to 32 ASCII Line X transmission line associated with this serial characters connection Device ID Text description to identify the device 1 to 32 ASCII Device X associated with this serial connection characters Bay ID Text description to identify the bay area 1 to 32 ASCII Bay X associated with this serial connection characters IED Address Protocol address of the device i e DNP3 O to 65519 X device address D400 Substation Data Manager Software Configuration Guide 45 GE Energy Setting Description Range Default Map File Name of the Client map file to be used with List of user N A the specific device configured client map files Enable on Start Indicates if communication to the device Disabled Disabled Up automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Password For devices that require a password to 1 to 32 ASCII N A access information characters Terminal Server The D400 can be configured to provide transparent access also Known as pass through to connected devices using vendor su
155. g area such as a scanned image of a piece of equipment or another specialized element not provided for in the default object types When an image object is initially added the image field is empty To assign an image double click the value box for the property labeled Image File A list of all images contained in the D400 s conf htdocs images directory is presented Select the desired Image File and click OK As with the rectangle and ellipse object types the border color and type may be changed as well as the URL Anchor for linking to another drawing Additionally the image may be rotated 90 or 180 degrees Value Box This is a central element in the development of dynamic diagrams The Value Box can contain any device value that is being polled by the D400 After creating the Value Box enter the device name into the Properties Values text box You can do this by double clicking into the appropriate value column This action reveals a floating menu listing all available devices You may also choose to manually type this information into the box in which case the format for this entry must include the port number preceded by the letter P and the unit ID number with a zero 0 separating the two numbers The format is PnOxx where n is the port number and xx is the Unit ID number Likewise the specific PointName is entered in the appropriate Properties Values column double clicking in the Values column offers a similar floating menu f
156. g settings for digital inputs as shown in Table 59 D400 Substation Data Manager Software Configuration Guide 75 GE Energy Table 59 Digital Input Mapping Settings Setting Description Range Default Point The DNP3 Point Index of this point as 0 to 65535 Incremented reported from the device from O Point Name A text string that describes this point Up to 128 DI xxx characters OFF State Name Text description of the O state Up to 32 OFF characters ON State Name Text description of the 1 state Up to 32 ON characters Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 Digital Outputs Settings are available on the Digital Output tab on the Client Map tab The D400 provides the mapping settings for digital outputs as shown in Table 60 Table 60 Digital Output Mapping Settings Setting Description Range Default Point Number of the point in the Digital Output 0 to 65535 Incremented Map Point Name A text string that describes this point Up to 128 DO xxx characters ON State Name Text description of the 1 state Up to 32 OFF characters OFF State Name Text description of the 0 state Up to 32 ON characters Point Group Point group to which the point belongs List of defined Group assigned point groups to ID number 0 Accumulators Settings are available on the Accumulators tab on the Client Ma
157. gh Connections sssssessccsssssssneees 186 8 6 Direc Cannet Toae a O satan Saanich 186 8 7 D400 Configuration MANAGE 187 8 8 Software Licensing TOooOlS ss s911551155115511501151 189 8 9 Emergency Access Code wocecccssssssseeesssecssesssnnneeees 191 A Application Pseudo Points 193 B System Redundancy 198 B 1 Validating the Redundant Connections 198 B 2 Data Synchronization B 3 Ethernet Connections B 4 Error Messages and Troubleshooting 201 C Remote Authentication 206 Gl GisGosTACAGS Erreinuan 206 GE Energy About this Document Purpose This manual provides detailed information on how to configure the D400 software Although this document describes all the configurable software applications in the D400 only the applications you purchased for your D400 will be available to you Intended Audience This document is a helpful resource for utility personnel and system engineers who are implementing the D400 in an overall substation automation system and protection engineers who are controlling network devices It is intended for readers who have knowledge of substation automation equipment and applications Additional Documentation For further information about the D400 refer to the following documents e D400 Substation Data Manager User s Manual 994 0089 e D400 online Help includes D400 configuration tool online Help e IEC 61850 Loader online Help How to Use this Guide This gu
158. group to which the point belongs List of defined Group point groups assigned to ID number 0 Measurand Type 1 Table 52 Measurand Type 1 Element Settings Setting Description Range Default Point Name Text description of the point in the map file Up to 128 lt Info object characters name gt X Multiplier Scale factor of the point m of formula mx b Full range of 64 bit 1 0 Float Offset Scale factor of the point b of formula mx b Full range of 64 bit 0 0 Float Element Name Specifies the name of each element current L2 or I N current L2 or voltage L1 L2 or LN V EN active power P reactive power Q Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 D400 Substation Data Manager Software Configuration Guide 71 GE Energy Measurand Type 2 Table 53 Measurand Type 2 Element Settings Setting Description Range Default Point Name Text description of the point in the map file Up to 128 lt Info object characters name gt X Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Element Name Specifies the name of each element current L1 current L1 current L2 current L3 voltage L1 E voltage L2 E voltage L3 E active power P reactive power Q frequency f Poi
159. guration Guide 195 GE Energy Name Description DI State Set to Configuration Comparison Status Indicates whether the most recent configuration Failed 0 comparison for this device failed The application The DCA compares the composition of the device s Data Sets with what it has configured locally logged the discrepancies it detected OK 1 There were no discrepancies in the most recent comparison Device Online Indicates whether communications with the ON 1 device is Active Online or Inactive Offline OFF 0 Table 155 IEC 61850 Application Per Device Analog Input Name Description Value of the Al point AddCause for This point is created for each field DO and AO point The name of the pseudo point includes the point name of the associated DO or AO field point See note below Note The value of this field indicates the result of the last AO or DO operation on an IEC 61850 enhanced security control see the following table For IEC 61850 normal security controls the values are 0 for commands that are successfully sent and 255 for commands that fail to send For enhanced security controls a non zero value indicates failure a zero value indicates success A positive value indicates one of the IEC 61850 Additional Causes was reported by the device A negative value larger than 255 indicates a low level MMS error was re
160. gure the D400 to communicate to IEC 61850 compliant server devices using the D400 s IEC 61850 client application The Loader makes use of the self description capabilities of the IEC 61850 protocol and device information files provided by most devices to simplify and speed up configuration of the IEC 61850 client application Using the Loader you create the client configuration that identifies the devices points and polling information required to set up communications between IEC 61850 devices and the D400 Once you are finished configuring the IEC 61850 client using the Loader you download it to the D400 directly from the Loader For more information on using the IEC 61850 Loader see the Loader online Help 2 3 LogicLinx optional LogicLinx is a tool that enables you to create automation applications that have traditionally been too costly or difficult to implement all without hard wiring Using any or all of the IEC 61131 3 programming languages you can create automation routines that run on your D400 LogicLinx automation routines are created using the LogicLinx editor The LogicLinx Wizard within ConfigPro CCE is then used to configure and upload the LogicLinx application to your D400 For more information on using LogicLinx refer to the LogicLinx on D400 Quickstart Guide SWMO0069 16 SWM0066 2 75 0 General GE Energy 2 4 D400 System Redundancy The D400 redundancy solution provides warm standby functiona
161. he screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 20 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Background Color The background color with which to fill the object Any 24 bit RGB Red Color Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 URL Action Specifies whether to load the URL Address into the Same or New Same same window or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load when a user selects Any valid URL None the object address D400 Substation Data Manager Software Configuration Guide 165 GE Energy Table 147 Switch Object Settings Setting Description Range Default Object Identifier Object Identifier of a four state Digital Status Obje
162. he time in seconds after which a General Interrogation is assumed to have completed if no Termination of General Interrogation message has been received from the remote device 0 01 to 3600 0 30 0 Command Timeout The time in seconds after which a General Command is assumed to have completed if the appropriate ASDU Type 6 COT ACK or NACK message has not been received from the remote device 0 01 to 3600 0 Auto Time Sync Specifies whether or not the application performs a time sync to the remote device when the application detects a change in the local system time and at application startup Enabled Disabled Enabled Time Sync Interval The time synchronization interval in minutes A value of 0 0 disables scheduled Time Synchronizations to the remote device 0 0 to 1440 0 Time Sync Timeout The time in seconds after which a time sync shall be assumed to have completed if the appropriate ASDU Type 6 COT Time Sync message has not been received from the remote device 0 01 to 3600 0 5 0 Info Objects An information object consists of a set of data elements You can create the following types of information objects e Input Measurand Time Tag Relative Measurand Type 1 Measurand Type 2 Measurand User Defined Time Tagged Message e Output General Command gt gt To create an Information Object 1 Click Add Info Object 2 On the New I
163. ice name and accumulator point point descriptor identifier Accumulator Type Whether to monitor status on frozen or running One of Frozen or None value Running Table 127 Alarm Object Settings Setting Description Range Default Point Identifier A point identifier for a single alarm indicator point Existing alarm None where the identifier consists of the alarm indicator indicator point point descriptor identifier Table 128 Alarm Box Object Settings Setting Description Range Default Alarm Object Unique identifier for an Alarm Object that provides Existing Alarm None Identifier the data source required for the Alarm Box Object identifier x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 40 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Font Type The type of font used to display text One of SansSerif SansSerif Serif Monospaced DialogInput Font Size The size of the font used to display text 1 to 100 11 Font Style The font style to apply to the display of text One of normal
164. ick Add Info Object 2 On the New Info Object window enter values for the fields as described in Table 82 and click OK 3 Configure each info object and add points to present to the master station Table 82 Info Object Settings Setting Description Range Info Object Type The type of information object to create Bitstring Double Command Double Point Integrated Total Measurand Packed Single Point Regulating Command Root Directory Setpoint Command Single Command Single Point Step Position Info Object Name interface An identifier used within the configuration 1 to 128 ASCII characters Starting Info Object Address Starting address for this object 1to 16777215 The table directly below the Info Object type drop down menu shows the configured values for the selected Info Object Info Object Name cannot be edited in this table Bitstring Table 83 Bitstring Mapping Settings Setting Description Range Default Info Object Settings Info Object The name of the information object as entered N A N A Name on the New Info Object window Read only Address The address of this entry 1 to 16777215 Interrogation The interrogation group used for reporting this Not Used Not Used Group information object Group 1 Group 16 Interrogation Specify whether to include this information Include Include Response object in a general interrogation response Exclude 96 SWM0066 2 75 0 G
165. ide describes how to configure the D400 software The D400 employs sophisticated applications that contain many advanced features and capabilities To successfully configure and operate the D400 for your substation environment it is highly recommended that you work through this manual as follows 1 Read chapter 1 About the D400 to familiarize yourself with the D400 and software 2 Read chapter 2 Configuration Overview to understand the approach to configuring the D400 including the tools and configuration procedure D400 Substation Data Manager Software Configuration Guide 5 GE Energy 3 Read chapter 3 Setting Up Communications for information on configuring the serial and network connections to devices and master stations 4 Refer to chapter 4 Configuring Devices for detailed information on how to configure the D400 to communicate with devices 5 Refer to chapter 5 Configuring Masters for detailed information on how to configure the D400 to communicate with master stations 6 Refer to chapter 6 Configuring D400 Automation Applications for detailed information on to configure specialty applications on the D400 7 Refer to chapter 7 Creating One Line Diagrams for a description of the drawing tools and configurable objects available in the One Line Designer 8 Refer to chapter 8 System Utilities for information on accessing and using the D400 command line functions to configure the D400 9 The appendices of this docu
166. ied and unusable 34 Response timeout in DB SYNC Activity The standby unit failed to send a response while synchronizing quality or accumulator data The data on the standby unit may not be up to date The standby unit may be experiencing problems or the communication link between the two units may be disconnected 35 ACTIVE Config check completed Configuration is same The configuration is the same on both active and standby units 36 STANDBY Response timeout for activity lt activity type gt subactivity lt sbuactivity type gt The standby unit failed to send a response to the active unit The numeric codes define the activity that timed out This is a diagnostic message that only needs to be considered if there are messages indicating that something has failed 37 ACTIVE Switch pulled away Peer D400 is failed Failing this D400 Switch pulled manually when the standby unit is not available The standby unit may have failed or the communication link between the two units may be disconnected 38 ACTIVE Switch pulled away Rejecting CHANGE OVER since Other D400 is in Service Mode Switch pulled manually when the standby unit is in service mode The active unit rejects the command to switch over 39 ACTIVE RACE Condition for switch Failing this B D400 Switch was pulled in the last 1000 ms 204 SWM0066 2 75 0 General Table 158 describes the possi
167. ier single analog input point on which to receive the input point feedback value in response to a set point command identifier where the identifier consists of the device name and point descriptor Timeout If Enable Feedback is True the timeout period in 0 to 65535 10 seconds during which the feedback point value must change to correspond to the set point value to indicate successful completion of the set point command A value of 0 shall indicate there is no timeout Deadband If Enable Feedback is True the feedback value 0 to 100 5 Threshold maximum percentage variation from the set point Percentage value by which the feedback value shall still be considered to be equal to the set point value Confirmation Defines whether the GUI is to display a confirmation True or False True Required dialog immediately prior to executing a set point Table 130 Analog Status Object Settings Setting Description Range Default Point Identifier A point identifier for a single analog input where the Existing analog None identifier consists of the device name and analog input point input point descriptor identifier Deadband The percentage variation from the last value that 0 to 100 5 Threshold exceeded deadband which once exceeded Percentage becomes reported and becomes the new last value for future reporting Table 131 Button Object Settings Setting Description Range Default X X horizontal pixel position from the top left corner 0 to the Draw Panel 0
168. ies whether or not CTS Flow Control is Enabled Disabled enabled Disabled Dial up Modem Settings The following settings are required when configuring a Dial up Modem link Table 5 Modem Settings Setting Description Range Default Init String The data string sent to the modem when 1 to 64 ASCII ATZ the application starts characters no spaces Attention String The data string sent to the modem to place 1 to 32 ASCII it into command mode characters no spaces Hang Up String The data string sent to the modem to cause 1 to 32 ASCII ATH it to hang up the phone connection characters no spaces Retry Count How many times to retry a failed connection O to 30 3 before giving up Increase the value for unreliable connections Retry Delay sec The amount of time to wait in seconds O to 3600 3 Client between retry attempts 30 Server Idle Wait Time The amount of time in seconds that must O to 3600 10 Client sec elapse without data transmission before the 15 Server connection is terminated D400 Substation Data Manager Software Configuration Guide 23 GE Energy Setting Description Range Default Auto Answer Enable the modem to automatically answer Enabled Enabled incoming calls Disabled Protocols Serial connections can be configured using the following protocols e DNP3 Master Stations p 24 e DNP3 Multi drop p 29 e Hydra
169. ined Not used when set to 0 52 SWM0066 2 75 0 General GE Energy Setting Description Range Default LRU Event Buffer The number of events non time tagged 50 to 65535 255 Size time tagged and hour update objects that are buffered by this LRU LRU Event Buffer The location where unreported events that RAM RAM Location are collected from event queues are stored NVRAM Event Buffer Overflow Policy Specify whether the newest or oldest events are discarded when the server event buffer is filled Discard Newest Discard Oldest Discard Newest Event Buffer Low Threshold A percent value of the total event buffer When the amount of available buffer space drops below this threshold a server event buffer low indication is reported by the application 10 to 100 20 DI Cancels Select Specify whether digital output select requests are automatically cancelled when any digital input changes are detected Enabled Disabled Disabled Buffer Al Specify whether analog input changes spontaneous periodic background scan are buffered for reporting When this is enabled the LRU reports each analog change separately For example if an analog input point exceeds the threshold 3 times before the LRU is polled for data in unbalanced mode the LRU shall report all 3 value changes If this feature is disabled the LRU shall report only the most recent value Enabled Di
170. int selected from the Point Picker Based Not editable System on user configured DI point name prefixed with system assigned assigned identifier identifier Alarm Group Single alarm group to which the point s alarmis tobe 1to4 N A associated with All configuration information for the alarm group e g color and sound settings is applied to every point associated with the alarm group Alarmable State Indicates when the point value is considered to bein True T the alarmable state Off False or On True False rue Text State 0 Text to display to represent the point state when the 1 to 32 Off associated digital input point value becomes 0 alphanumeric typically the Normal state characters Text State 1 Text to display to represent the point state when the 1 to 32 associated digital input point value becomes 1 alphanumeric typically the Alarm state characters Table 116 On Update Alarm Settings Alarm Name Text description of the alarmable point as it will be Up to 100 DI source displayed in the Active Alarms page It defaults to the alphanumeric Point name name of the source point characters Source Point DI source point selected from the Point Picker Based Not editable System on user configured DI point name prefixed with system assigned assigned identifier identifier Alarm Group Single alarm group to which the point s alarmis tobe 1to4 N A associated with All configuration information for the alarm group e
171. ion by trip 17 Additional Cause Object not selected 18 GE Energy D400 Substation Data Manager Software Configuration Guide 197 GE Energy System Redundancy This chapter provides additional information on redundant D400 setups Refer to 2 4 D400 System Redundancy for an overview of configuring redundancy B 1 Validating the Redundant Connections Once you have configured your redundant setup you should test the system to ensure that redundancy has been properly configured gt gt To validate a redundant system 1 Log into the online HMI of the active D400 unit 2 Click the t Point Summary button on the toolbar 3 Under the Application tab click the Details button for RedunMgr 4 Select the Digital Input tab and verify that the points are in the following states Point Name Quality Value SystemRedundant Online 1 StandbyD400Comm Fail Online 0 StandbyD400inService Mode Online 0 StandbyD400NotAvailable Online 0 D400AActive Online 1if you are connected to D400 A 0 if you are connected to D400 B See note D400BActive Online 1 if you are connected to D400 A 0 if you are connected to D400 B See note 198 swmo0066 2 75 0 General GE Energy Point Name Quality Value Config Sync in Progress Online 0 Standby Config Out of Sync Online O if both D400s have the same configuration 1 if both D400s have a different configuration Note If D
172. ion of IEC 60870 5 101 104 server protocols Enhancements to security features amp remote authentication 2 70 1 Jan 27 2009 M Haska Minor corrections to Table 161 2 70 2 Feb 24 2009 M Haska Minor corrections to Table 10 Table 155 note Added troubleshooting note to section B 1 Added note regarding feedback points to Table 129 Table 134 Table 141 2 75 0 July 22 2009 M Haska Minor corrections to Table 155 note Added new buttons for One Line Designer tool Added IEC 60870 5 104 Client D400 Substation Data Manager Software Configuration Guide 208
173. ions Type Conversions Averages rExpression sample Digital input Basic Addition foai E Reference Points a Oai 1ai Analog Input Oai 0000003 Al 0 0 1ai 0000003 Al 1 2ai 0000003 AI 2 3ai 0000003 AI 3 Clear Validate O 4ai 0000003 AI 4 7 a T 5ai 0000003 als m AE O 6ai 0000003 Al 6 m Fe L 7ai 0000003 AI 7 0 8ai 0000003 AI 8 ee i L 9ai 0000003 AI 9 E log Calculator Expressions The Calculator creates and updates new data points in the D400 based on user configured expressions You construct expressions by combining operands and operators to produce a resulting point Operands can include constants system data points and Quality attributes Operators include mathematical logical and bit wise operators The expressions also define the Point Names and Data Types that are used to represent the resulting evaluation 6 4 LogicLinx optional The D400 supports soft logic automation using LogicLinx The ConfigPro CCE LogicLinx Wizard was specifically developed to assist in the configuration of LogicLinx on the D400 For information on how to configure LogicLinx on the D400 refer the LogicLinx on D400 Quick Start Guide SWM0069 134 swmo066 2 75 0 General GE Energy D400 Redundancy Manager The D400 Redundancy Manager is responsible for managing communications between the two
174. is class by default None 1 Assignment 3 2 1 Default Static Type to report when the master does not With Status With Status Variation request any specific type Without Status Default Event Type to report when the master does not With Time With Time Variation request any specific type Without Time Analog Outputs Settings are available on the Analog Outputs tab The default property values are defined in the lower pane The D400 provides the mapping settings for analog outputs as shown in Table 99 112 swm0066 2 75 0 General Table 99 Analog Output Mapping Settings GE Energy Setting Description Range Default Index Point Index 0 Based Each point index number 0 to 65535 Incremented must be unique from 0 IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected Assigned AO point from the Point Picker Read only Identifier Point Name Text description of the point in the Analog Up to 128 Assigned IED Output map Based on selected AO point Ready characters point name only Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Static Variation How the point values should be reported 32 Bit User selected 16 Bit Default 32 Bit w o flag 16 Bit w o flag 32 Bit Float Settings are available in the lower pane of
175. isco Corporation Hyperterminal is a registered trademark of Hilgraeve Incorporated IEC is a registered trademark of Commission Electrotechnique Internationale IEEE and POSIX are registered trademarks of the Institute of Electrical and Electronics Engineers Inc Internet Explorer Microsoft and Windows are registered trademarks of Microsoft Corporation JAVA is a registered trademark of Sun Microsystems Inc MODBUS is a registered trademark of Schneider Automation Inc Netscape is a registered trademark of Netscape Communications Corporation SEL is a registered trademark of Schweitzer Engineering Laboratories Inc Other company or product names mentioned in this document may be trademarks or registered trademarks of their respective companies GE Energy Contents About this Document 5 Product Support 7 1 About the D400 9 1 1 OVEPVICW Lo cscs 1 2 How the D400 Works 1 3 Types of Applications 1 4 D400 Applications 1 5 About the DNP3 Software 2 Configuration Overview 14 2 1 D400 Online Configuration TOO ccc 15 2 2 IEC 61850 Loader Optional esses 16 2 3 LOGICLINX OPTION eseeeeesssssssesssseseseseecceeseeeeeees 16 2 4 D400 System Redundan y weeccccccccssssseneeecscseessseeee 17 2 5 D400 System Utilities 26 Configurdton Steps serere nnen 2 7 Configuration File Format ssssss1ss1911151110111011121 2 8 Configuration Management 3 Setting Up Communications 20 Sil Seridl COMNMSCHONS 4 senenneaean 21
176. k size of current Application Logs 3 Delete Archived Logs 4 Delete current Logs 5 Back Enter Your Choice Between 1 and 5 i Check Size of Archived Logs Active system logs are automatically archived when they reach a size of 256 KB Up to 10 archives are kept within the D400 with newer logs overwriting older stored logs Check Size of Archived Logs lets you view the amount of disk space occupied by these archived log files The value is shown in KB Check Size of Current Application Logs View the amount of disk space occupied by the current application logs The value is shown in KB Delete Archived Logs Permanently delete archived logs from the D400 Delete Current Logs Permanently delete current application logs from the D400 180 swmo066 2 75 0 General GE Energy Reset mSQL Database Tables You can modify tables in the mSQL database through the Reset mSQL Database Tables menu of 3 84 167 235 PuTTY 1 Delete SOE records 2 Delete Quality records 3 Delete PRF Event records 4 Delete Active Alarm records 5 Delete Historical Alarm records 6 Delete Operator Note records 7 Enter Your Choice Between 1 and 7 i To delete records from the D400 select a line item from the list During the deletion the mSQL database will be locked for reading or writing Important Once you have finished deleting records from the mSQL database exit the D400 Configuration Utility and reboot the D400 by en
177. l users can be created using the D400 configuration utility see Administrator Group Users on p 174 Tip If you enable local authentication mode be sure to create at least one administrator level user before exiting from the D400 configuration utility If you log out of the system without creating any new administrator users you will not be able to log into the D400 remotely D400 Substation Data Manager Software Configuration Guide 173 GE Energy Remote Authentication Mode The D400 supports two remote authentication modes e RADIUS e Cisco TACACS RADIUS remote authentication mode requires the following settings e RADIUS server address valid IPV4 address e Shared secret as provided by the RADIUS administrator 6 or more characters Cisco TACACS remote authentication mode requires the following settings e TACACS server address valid IPV4 address e Encryption select whether to enable or disable encryption for the connection between the D400 and the TACACS server Refer to Cisco TACACS on p 206 for information on configuring your TACACS server Root Administrator Settings Allows you to change the password associated with the system root user account HMI Supervisor Settings HMI supervisors are allowed full privileges to access to all configuration runtime operation and system administration screens in the D400 HMI One default supervisor account with the username supervisor is always available on the D400
178. ld for Master Stations Table 32 IEC 60870 5 104 Master Station Application Parameters Setting Description Range Default Application Tab Time Mode Specifies if the master station is allowed to Set main use main Set main use set or use the main D400 and or local LRU time main time time Set local use local time Set local use main time Time Sync The maximum allowed time in seconds 0 to 86400 900 Timeout between time synchronization attempts from the IEC 60870 5 101 104 master station or other time source before time tagged data is reported as invalid by the LRU Not used when set to 0 Control Select The maximum allowed time in seconds 0 01 to 60 0 5 0 Timeout between control select and control execute commands for digital and analog output points from the IEC 60870 5 101 104 master station Double Point The minimum time in seconds that both 0 to 65535 500 Valid Time digital input points must be stable before an ON OFF state is reported Note The value of this property only applies when the corresponding parameters of a double point information object are specified as undefined Not used when set to 0 Double Point The minimum time in seconds that both 0 to 65535 1000 Suppress Time digital input points must be stable before an indeterminate state is reported Note The value of this property only applies when the corresponding parameters of a double point information object are specified as undef
179. le 68 84 swmMo066 2 75 0 General Table 68 Fast Meter Analog Outputs GE Energy Setting Description Range Default Name Text description of the point in the Fast Meter Up to 128 FMA_xxx Analog Channel Map characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Demand Analog Channel Settings available on the Demand Analog Channel tab on the Client Map tab The D400 provides the mapping settings for demand analog outputs Function code 2 as shown in Table 69 Table 69 Demand Analog Outputs Setting Description Range Default Name Text description of the point in the Demand Analog Up to 128 DAC_Xxx Channel Map characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Peak Demand Analog Channel Settings available on the Peak Demand Analog Channel tab on the Client Map tab The D400 provides the mapping settings for peak demand analog outputs Function code 3 as shown in Table 70
180. lity using two D400s connected through a serial link one in active mode and one in standby mode If the active unit fails the standby unit becomes active and takes over system operation D400 system redundancy is configured and enabled through several software applications that run on each redundant D400 unit Hardware configuration is required as well refer to the D400 Substation Data Manager User s Manual and appendix B System Redundancy for more information D400 Redundancy Manager The D400 Redundancy Manager is responsible for managing communications between the two D400 units and the RS232 switch panel It also controls data synchronization and state changes For more information see section 6 5 D400 Redundancy Manager Redundancy Serial Port Settings Two serial ports on each D400 are dedicated to redundancy related communications e Redundancy Dedicated Link Links the two D400 units together through the ping cable See Redundancy Dedicated Link in section 3 1 Serial Connections e Redundancy Switch Panel Connects each D400 unit to the RS232 switch panel through the watchdog cable See Redundancy Switch Panel in section 3 1 Serial Connections D400 Configuration Manager The D400 Configuration Manager allows you to synchronize configurations between two D400 units The D400 redundancy application uses this tool to manage the synchronization of configuration files between the active and standby units to ensure both unit
181. ll other commands will be rejected In addition to these indications the following control points are available as digital outputs Table 125 D400 Redundancy Manager Digital Output Points Point Name Description StartChangeOver Triggers a change over the active D400 moves to standby mode while the standby D400 takes over the active mode If you are logged into the online GUI of the active D400 when a changeover occurs the browser window closes and you are required to log in again OFFLINE if the D400 is in non redundant mode RestartActive Requests a restart of all software on the active D400 RestartStandby Requests a restart of all software on the standby D400 OFFLINE if the D400 is in non redundant mode RebootActive Requests a reboot of the active D400 RebootStandby Requests a reboot of the standby D400 OFFLINE if the D400 is in non redundant mode SyncConfig Requests that the configuration of the standby D400 be synchronized with that of the active unit OFFLINE if the D400 is in non redundant mode You may issue any control operation on these points to initiate the request associated with the point Upon receiving a control operation the Redundancy Manager will momentarily pulse the state of the digital output to ON then OFF All local commands other than Control Inhibit will be rejected 136 SwmM0066 2 75 0 General GE Energy Creating One Line Diagrams The One Line Designe
182. llowing steps 1 Create D400 client map file for each device and protocol type 2 Define the data points list and set point properties 3 Set protocol specific properties 4 Set up serial and network device connections 5 Configure protocol specific settings for each device connection 6 Save the configuration file 7 Run the configuration file in the D400 by committing the changes 56 SWM0066 2 75 0 General GE Energy 4 2 Client Maps The D400 communicates with devices connected to your power network These devices monitor and record several types of information The information can be generally classified in the following point groups defined by default in the D400 e Present values PVal that reflect the current state of the power system at an instance in time e Peak demand that reflects the minimum and maximum power flow conditions encountered e Demand Point groups can be modified on the System Wide tab in the D400 Online Configuration Tool The devices store all the information in a map Refer to the device manufacturer s manual for a list and description of all the data points available from a particular device The D400 polls for and retrieves information from a device according to a client map file The client map file is based on a specific protocol and specifies what information to gather from a device The map file contains information on how polling is scheduled for a particular type of device b
183. ls on why the synchronization did not complete Caution It is extremely important that you do not change the configuration of the active D400 while configuration synchronization is in progress B 3 Ethernet Connections When you configure a pair of D400s for redundancy you need a total of 3 IP addresses for the two D400s e One unique IP address for each D400 e One active IP address to be used by the active D400 The same active IP address is configured in both D400s When a D400 is in active mode it will use the configured active IP address In any other state it will use its own unique IP address This allows external devices and master stations to use only one IP address to access the pair of D400s Table 156 describes the possible combinations Table 156 IP Address Combinations D400 A D400 B State IP Address State IP Address E Active C Unique D400 B L Unique D400 A HM Active C Unique D400 A L Unique D400 B Active See note B Active See note Hi denotes active state _ denotes standby state Note Having both D400s active at the same time can only be achieved if the two units have not been connected to either the switch or to each other In any other scenario the two units will successfully arbitrate so that only one D400 claims the active IP address This scheme requires static IP address configuration The D400 Redundancy solution does
184. ltiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 4 4 IEC 60870 5 103 The IEC 60870 5 103 Client map defines how the D400 is configured to poll data from IEC 60870 5 103 compliant devices Map settings are available on the Client Map tab when an IEC 60870 5 103 protocol type is selected Device Properties Settings are available in the Device Properties pane Table 48 lists the device specific protocol settings Table 48 IEC 60870 5 103 Device Properties Setting Description Range Default Time Offset The device s time base offset from UTC in 1440 to 1440 0 minutes A positive value means the device s time base is ahead or East of GMT while a negative value means the device s time base is behind or West of GMT Data Link Confirm Specifies whether or not the application will Enabled Enabled request data link confirmation when Disabled transmitting data General The General Interrogation interval in minutes 0 0 to 1440 0 30 0 Interrogation A value of 0 0 disables General Interrogations Interval to the remote device except on application 68 SWM0066 2 75 0 General startup GE Energy Setting Description Range Default General Interrogation Timeout T
185. m when the point state changes from normal to alarmable and archives the alarm only when the point state returns to normal and the alarm is acknowledged e On Update 2 state Generates an active alarm when the alarm state changes from one state to another and archives the alarm when the alarm is acknowledged In effect two alarms are created the first alarm is generated when the source point changes from ON to OFF and a second alarm is generated when the source point changes from OFF to ON e Four State Generates an active On Update alarm when the point values change to a state configured as an On Update alarm and generates an active Absolute alarm when the point values change to a state configured as an Absolute alarm The On Update alarm is archived when it is acknowledged The four state Absolute alarm is archived once it is acknowledged and the pair of source points have moved into a non alarmable state for example a change to a state that has an On Update alarm will not reset the alarm Four state alarms must have at least one non alarmable state Setting Up Alarms You set up alarm points for the D400 on the Alarm tab on the Configuration page Alarms must be configured to activate the Active Alarms page in the D400 HMI The Point Picker lists the digital inputs currently configured in the system that are available for selection as alarm points The selected points appear on the alarm type tab for configuration You can configure a
186. mber of times the DNP3 resends an 0 to 300 2 unconfirmed application message before taking a degraded timeout Application Timeout Time in milliseconds the DNP3 waits for the 1 to 120000 6000 26 SWM0066 2 75 0 General GE Energy Setting Description Range Default Data Link Confirm Defines when the DNP3 requests remote Never Never station confirmation of a data link message Multi fragment only Event only Event or Multi fragment IIN only IIN or Multi fragment Event or IIN Event IIN or Multi fragment Always Data Link Retry Number of times the DNP3 Server resendsan 0 to 300 2 unconfirmed data link message before taking a degraded timeout Data Link Timeout Time in milliseconds the DNP3 Server waits 1 to 120000 1000 for remote station confirmation of a data link message before re sending it Set the value higher for a dial up modem connection i e 60000 Initial Master DNP3 Server master address 0 to 65519 100 Address Degraded Timeout Time in milliseconds the DNP3 Server delays 1 to 7200000 5000 between retry cycles when seeking confirmation of an application message Transmission Maximum size in bytes of an unsolicited 249 to 2048 2048 Fragment Size application message or response message fragment minimum is 249 bytes Accept Time Enable Time synchronization from Master True True Synchronization False Unsolicited Mode Flag that enables or disables DNP3 Server True Fals
187. me Text description of the point in the map file Up to 128 SC X characters Command An attribute that specifies in greater detail the No Additional Persistent Qualifier type of control action requested Definition Short Pulse Duration Long Pulse Duration Persistent ON State Text description of the 1 state Up to 32 ON characters OFF State Text description of the 0 state Up to 32 OFF characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Single Point Table 46 Single Point Element Settings Setting Description Range Default Address The address of this information object 1 to 16777215 Incremented element by 1 from starting address Point Name Text description of the point in the map file Up to 128 SP X characters ON State Text description of the 1 state Up to 32 ON characters OFF State Text description of the 0 state Up to 32 OFF characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 D400 Substation Data Manager Software Configuration Guide 67 GE Energy Step Position Table 47 Step Position Element Settings Setting Description Range Default Address The address of this information object 1 to 16777215 Incremented element by 1 from starting address Point Name Text description of the point in the map file Up to 128 SP X characters Mu
188. ment provide additional information on configuring advanced features of your D400 for example remote authentication and system redundancy If you need assistance contact GE Energy Customer Service See Product Support for contact details In configuration tables N A in the Default column indicates there is no default setting provided and X indicates the number is automatically incremented Document Conventions This manual uses the Systeme International SI and the Microsoft Manual of Style as a basis for styles and conventions The following typographic conventions are used throughout this manual Bold face is used for e Names of software program menus editors and dialog boxes also for the names of menu commands keyboard keys icons and desktop shortcuts and buttons and fields in editors and dialog boxes e Names of hardware components e User input that must be typed exactly Italic face is used for e Emphasis e Cross references to sections figures and tables within this manual and for titles of other documents e File and directory names examples of directory paths are generally given in the Windows form e Placeholders for user input that is specific to the user May also include angle brackets around the placeholder if the placeholder is already in italic text For example c lt product gt product def e References to a setting or field value shown The software related procedures in this g
189. n If no is entered SSH key authentication must be enabled to allow communication between the D400 devices See To Configure Public Key Authentication below If the p parameter is not specified the default action is yes f Reset Flag yes no Entering yes will trigger a restart of all applications running on the remote D400 device once the configuration has been synchronized If no is entered the applications will not be restarted If the f parameter is not specified the default action is no For example to trigger a network synchronization followed by a restart of the applications running on the remote unit you would enter the command configmgr pl m network i lt IP address of remote computer gt u lt username of remote D400 unit gt p yes f yes If the transfer of the configuration is successful a confirmation notice is displayed If any errors occur a description of the failure is shown gt gt To Configure Public Key Authentication When redundancy mode is enabled in d400cfg public and private SSH keys are automatically created for you Follow these steps to enable authentication between both redundant D400 units 1 Log onto the terminal of D400 B and enter the following command cd mnt datalog SSHKeys 188 swmoo66 2 75 0 General GE Energy Create a directory using the user name configured on D400 A in Redundancy gt User Name of PEER D400 using the following command
190. n Multi drop p 32 e IEC 60870 5 101 Master Station p 32 e IEC 60870 5 101 Multi drop p 37 e IEC 60870 5 103 Multidrop p 39 e LogicLinx Device p 41 e Modbus Master Stations p 41 e Modbus Multi drop p 42 e Printer Device p 42 e Redundancy Dedicated Link p 43 e Redundancy Switch Panel p 43 e Single Generic ASCII p 43 e Single SEL Binary p 44 e Terminal Server p 46 DNP3 Master Stations The Distributed Network Protocol DNP3 supports communication with one or more devices over dedicated serial links as well as over Ethernet The D400 supports communications to DNP3 devices using the DNP3 client application It collects the point values from the devices based on the protocol and device settings and stores them in the system point database The DNP3 protocol is highly configurable You have the option of configuring the way the DNP3 client application on the D400 behaves by modifying the DNP3 protocol settings or use the default configuration settings The following settings are used when configuring a DNP3 Master Station If a Modem connection is used refer to the additional settings defined in Table 5 Table 6 DNP3 Master Stations Setting Description Range Default Name Text description to identify the master 1 to 32 ASCII MASTERX station being connected to characters Master Station Unique DNP3 address of the server O to 65519 x Address application instance 24
191. nd eth1 e P Address and Subnet Mask for use by the D400 Server e Gateway address by default no gateway configured e Start and End addresses to be used by the dynamic assignment Port Forwarding Allows a device on the D400 first network interface to communicate with devices coming in on a second network interface or a dial up connection This requires configuration only if the D400 has two Ethernet interfaces and or will use PPP dial in and require access to network devices external to the D400 ICMP Echo ICMP echo is a feature to help with securing the D400 By default the D400 cannot be pinged on any interface but it can be enabled if required by the administrator Host Name Used to assign a host name to the D400 unit The name must be unique to this D400 and only contain alphanumeric characters hyphen is supported Configure Network Interfaces The Configure Network Interfaces menu includes settings for the D400 s network connections D400 Substation Data Manager Software Configuration Guide 175 GE Energy Note The D400 must be rebooted to activate changed network settings 2101 si D400 Configuration Utility Menu Network Interface Netl 1 Current Configuration 2 Static IP Address 3 Dynamic Address 4 Back Enter Your Choice Between 1 and 4 i Static IP Address Configures the D400 to use manually defined network parameters All addresses must be on different subnet masks Configurable a
192. nd then flushing them when the buffer reaches the flush now level or the flush time period expires Alarm Sound File Sound file to play when an alarm belonging to this None None group becomes active on the Active Alarms page List of available Supported formats are AIFF AU or WAV sound files Alarm Blinking The rate in one tenths of a second at which the alarm 0 to 65535 5 Rate text blinks at Enter O to disable blinking Alarmable Image to display on the Active Alarms button when None None Image active alarms are present List of available image files Acknowledge Image to display on the Active Alarms button when None None Image acknowledged alarms are present List of available image files 132 SWM0066 2 75 0 General GE Energy 6 3 Calculator The Calculator application is typically used in the D400 to carry out the following functions e Provide the digital output point for the Global Controls Disable functionality e Perform Mathematical Logical or Timer based operations on selected system data points e Automatically operate one or more digital or analog outputs when certain conditions are met The Calculator creates new points in the D400 system point database based on the results of configured expressions All Calculator owned points are referred to in the expressions by a configurable alias name The values of the data points generated by the Calculator are evaluated each time a change eve
193. nergy Note The format for the default value is X Y Z where X is the function type Y is the info number and Z is either Point 1 or Point 2 4 5 DNP3 Client The DNP3 Client map defines how the D400 is configured to poll data from DNP3 devices The D400 supports the following configurable DNP3 data types e Analog inputs measured or computed values by the device e Analog outputs physical or computed analog quantities e Digital inputs states of physical or logical Boolean devices e Digital outputs physical or logical ON OFF raise lower and trip close points e Accumulators counter values e Device properties device level settings The DNP3 Client map settings are available on the Client Map tab when a DNP3 protocol device type is selected Note Additional DNP3 client configuration settings are available for device communications when configuring DNP3 serial connections on the Serial tab Figure 7 DNP3 Client Map Page D400 Configuration Mozilla Firefox Be Edt Yew Higtory Bookmarks Tools Help e gt EOR e conc Commit Changes Discard Changes Serial I Network if Client Map I Server Map Alarm I Calculator I System Wide I User Management HMI Access Manager I Oneline Designer Enew Coven hesr POETEI Ansiog Output Digita input Digital Output Accumutator Name value Request Data Link Confirm false Please specty which Analog Inputs you would bke to collect 1S Ae Da
194. nfo Object window enter values for the fields as described in Table 49 and click OK 3 Enter the number of rows and click Add to create and configure elements within the information object D400 Substation Data Manager Software Configuration Guide 69 GE Energy Table 49 Info Object Settings Setting Description Range Info Object Type The type of information object to create General Command Measurand Time Tag Relative Measurand Type 1 Measurand Type 2 Measurand User Defined Time Tagged Message Info Object Name An identifier used within the configuration 1 to 128 ASCII characters interface Function Type The IEC 60870 5 103 function type 0 to 255 corresponding to this information object type reported by the remote device Info Number Starting address for this object Oto 255 The table directly below the Info Object type drop down menu shows the configured Info Object Name and either the Function Type and Info Number or the Default Function Type and Initial Info Number of the selected information object When General Command or Time Tagged Message types are selected the Default Function Type value indicates the default function type that will be used when a new information object element is added The Initial Info Number value is incremented for each new information object element that is added Note Additional info object level settings are available for Time Tagged Message objects Thes
195. ng Points Fleeting fleeting points Not Fleeting Points Points Fleeting Points Specifies how fleeting point values are sent to Two Events Two Events Reporting the database Applicable only for fleeting Send Always point objects Table 56 Time Tagged Message Element Settings Setting Description Range Default Function Type The IEC 60870 5 103 function type O to 255 0 corresponding to this information object type reported by the remote device Info Number Starting address for this object O to 255 Incremented by 1 from starting address P1 Name Text description of the first point in the map Up to 128 See note file for this double point object characters P1 Group Point group to which the first point belongs List of defined Group point groups assigned to ID number 0 P1 ON State Text description of the 1 state for the first Up to 32 ON point characters P1 OFF State Text description of the O state for the first Up to 32 OFF point characters P2 Name Text description of the second point in the Up to 128 See note map file for this double point object characters P2 Group Point group to which the second point List of defined Group belongs point groups assigned to ID number 0 P2 ON State Text description of the 1 state for the second Up to 32 ON point characters P2 OFF State Text description of the O state for the second Up to 32 OFF point characters D400 Substation Data Manager Software Configuration Guide 73 GE E
196. nnection You manage the serial connections on the D400 on the Connection tab on the Configuration page A client map file must be available in the D400 before a protocol type is available for configuration The D400 includes several default client maps If you require a custom map create it first before setting up the serial connection See section 4 2 Client Maps D400 Substation Data Manager Software Configuration Guide 21 GE Energy gt gt To add a serial connection e On the Configuration page click the Connection tab then click Add Connection and configure a connection for each serial port Each row under the Serial heading of the Connections pane represents one connection through an RS 232 or RS 485 serial port on the D400 The port numbers correspond to the port numbers on the rear of the D400 unit See the D400 Substation Data Manager User s Manual You can configure a maximum of 16 ports Each serial connection can be configured for device client or master station server communications using a selected protocol The type of connection and the protocol you select determine the client or server application and related settings that will be used for the communications on that serial port See Table 2 Port Settings The following settings are required for each connection they define how the D400 communicates over the serial link Some settings may not be available for all connection types Table 2 Port Settings
197. nt Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 Measurand User Defined Table 54 Measurand User Defined Element Settings Setting Description Range Default Measurand You can define up to 255 elements within the 1to 255 Incremented Position Measurand User Defined info object type The from 1 Measurand Position setting specifies the element position that this value is assigned to Point Name Text description of the point in the map file Up to 128 lt Info object characters name gt X Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 72 SWM0066 2 75 0 General GE Energy Time Tagged Message Table 55 Time Tagged Message Info Object Settings Setting Description Range Default Relative Time Specifies whether the time tagged message is Yes No returned using relative times No In General Specifies whether the points in this object are n General In General Interrogation returned in response to a General nterrogation Interrogation Interrogation Not In General nterrogation Fleeting Points Specifies whether the points in this object are Fleeti
198. nt Name Description DO State Set to Enable Polling of All This control disables or enables data set retrieval Disabled 0 IEDs from all devices belonging to the application but Enabled 1 leaves the associations up and does not prevent other controls such as Retrieve All Data Sets from IED or Force to Alternate Channel The application stops polling all devices and disable all Report Control Blocks Force All IEDs Off Primary Channel This control clears all devices off the requested channel Clear Primary Channel 1 Clear Secondary Channel 0 Table 152 IEC 61850 Application Global Digital Input Name Description DI State Set to Global DeviceDisable Communications is disabled to all devices owned Disabled 1 by the application Reflects the status of the uy SRO Enabled 0 Global DisableDevice Digital Output pseudo point Enable Polling of All Automatic data retrieval from devices is globally Disabled 0 IEDs Status disabled Reflects the status of the Enable Polling Enabled 1 of All IEDs Digital Output pseudo point nge DCA Status Indicates if the application is running Enabled 1 Disabled 0 Table 153 IEC 61850 Application Per Device Digital Outpu Name Description DO Status Set to Retrieve all Data Sets This control queues a poll request for every locally Completed 0 configured Data
199. nt is received on one of the data points referenced in a defined expression The following data types are supported for use in expressions e Analog Input Al e Digital binary Input DI e Analog Output AO e Digital binary Output DO e Accumulators e Text The Calculator supports the following types of point calculations e Quality conversion e Type conversion e Evaluation timer expressions e Assignment expressions One you have defined calculated points they are available for selection when creating client and server maps and configuring alarms During runtime calculated point values are presented to the operator on the Automation tab on the Point Details page Creating Calculated Points You create calculated points on the Calculator tab on the Configuration page Refer to the Online Help for additional information D400 Substation Data Manager Software Configuration Guide 133 GE Energy Figure 16 Calculator Page E D400 Configuration Microsoft Internet Explorer Fle Edt View Favorites Tools Help Address Eco Osak O a D DP seach Fao B O a O CE cE Energy coman PAYPEN TEAC edie Palle RPS EQ ees Commit Changes Discard Changes ts ppReset Reference Points E Pr3351913 Expressions x BATTERIER Evaluations Output Point Type Output Point Name Output Alias 0 Sample Basic Addition Timers Analog Assignments Description Digital Assignments Quality Convers
200. nteger Range 128 to 127 UINT8 8 bit unsigned integer Range 0 to 255 NT16 16 bit signed integer Range 32768 to 32767 UINT16 16 bit unsigned integer Range 0 to 65535 NT32 32 bit signed integer Range 2147483648 to 2147483647 UINT32 32 bit unsigned integer Range 0 to 4294967295 FLOAT32 IEEE single precision floating point value DATE Date in the format of DD MMM YYYY TIME 24 hour time in the format of HH MM SS ASCII A string of ASCII data Range as specified in ASCII Size Read Input Register Settings are available on the Read Input Register tab on the Client Map tab The D400 provides mapping settings for read holding register points as shown in Table 77 Table 77 Read Input Register Settings Setting Description Range Default Point Number A unique identifying number in the register map 0 to 65535 x Point Name A text string that describes this point Up to 128 Input Register characters XXX Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Poll Type The type of poll to be taken of the point See Table 64 Fast Data Type The type of data polled See Table 76 UINT16 ASCII Size ASCII size in bits when a text string is being 0 to 99 0 retrieved from the device If this field is set to 0 the register does not contain ASCII data Point Group Point group to
201. nts required to represent four state identifier status where the identifier consists of the device name and point descriptor Timeout If Feedback Enabled set to True The timeout period O to 65535 10 after which a digital control is executed that the feedback state must change to correspond to the digital control state If the digital control state does not correspond within the timeout period the control shall be aborted A value of 0 indicates no timeout State 0 Text If Feedback Enabled set to True and Feedback Size Any text Empty set to 2 the user defined text used to represent a 2 state feedback value of 0 State 1 Text If Feedback Enabled set to True and Feedback Size Any text Empty set to 2 the user defined text used to represent a 2 state feedback value of 0 State 00 Text If Feedback Enabled set to True and Feedback Size Any text Empty set to 4 the user defined text used to represent a 4 state feedback value of 00 State 01 Text If Feedback Enabled set to True and Feedback Size Any text Empty set to 4 the user defined text used to represent a 4 state feedback value of 01 State 10 Text If Feedback Enabled set to True and Feedback Size Any text Empty set to 4 the user defined text used to represent a 4 state feedback value of 10 State 11 Text If Feedback Enabled set to True and Feedback Size Any text Empty set to 4 the user defined text used to represent a 4 state feedback value of 11 On Control State The fee
202. o False True False False IIN React Time Sync True Respond to Need Time Sync IIN in a message by sending a Time Sync message False Ignore Need Time Sync message If a target device asks for a time sync it should be given one unless the target device has access to another clock than the D400 True False True Integrity Time Sync True Send out a Time Sync message to a target device each time an Integrity Poll message is sent to that device False Do not send out a Time Sync message to a target device each time an Integrity Poll message is sent to that device In general if a target device needs a time sync it will ask for one This setting should be used only if there is a known problem with the target device s clock True False False Stagger Integrity Enable Specifies whether Staggered Integrity polling is enabled or not True The DNP3 client ignores the Integrity Poll Interval configured for the devices and utilizes an internal scheduling mechanism to determine when the next integrity poll should be transmitted False Do not enable staggered integrity polling Use the configured settings True False False Stagger Integrity Interval If Staggered Integrity polling is enabled the DNP3 client shall schedule Integrity polls to devices based on the interval in seconds specified here 30 to 36000 600 Channel Switch
203. o display 1 to the Draw Panel 20 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 Font Type The type of font used to display value as text One of SansSerif SansSerif Serif Monospaced DialogInput Font Size The size of the font used to display value as text 1 to 100 11 Font Style The font style to apply to the display of the value as One of normal Normal text bold or italic Foreground Color The color to apply to the value displayed as text Any 24 bit RGB Black Color Background Color The color to apply to the background Any 24 bit RGB Red Color Text Horizontal The horizontal alignment of the value displayed as One of Left Center Left Alignment text within the object s display area or Right D400 Substation Data Manager Software Configuration Guide 169 GE Energy System Utilities Configuration information related to the D400 system is changed using utility programs that are installed on the D400 platform The D400 system utilities are typically used during the initial setup of the D400 and for changing the basic configuration of the system including the network connections system date and
204. of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height 144 swm0066 2 75 0 General GE Energy Setting Description Range Default Height Pixel height of the rectangular area used to display 1 to the Draw Panel 20 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Font Type The type of font used to display text One of SansSerif SansSerif Serif Monospaced DialogInput Font Size The size of the font used to display text 1 to 100 11 Font Style The font style to apply to the display of text One of normal Normal bold or italic Foreground Color The color to apply to text Any 24 bit RGB Black Color Background Color The color to apply to the background Any 24 bit RGB Grey Color Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Caption Text for the object to display Text Button Action Type Defines the action to occur when the user selects One of Open None the button Analog Set Point Interface Open Digital Control Interface
205. og Status Existing Analog None objects Status Object Identifier Object Identifier 3 Object Identifier of one of three Analog Status Existing Analog None objects Status Object Identifier X1 X horizontal pixel position from the top left corner 0 to the Draw Panel 0 of the screen to the top left corner of the start point width of the line Y1 Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the start point of height the line x2 X horizontal pixel position from the top left corner 0 to the Draw Panel 0 of the screen to the top left corner of the end point width of the line Y2 Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the end point of height the line Arrow Type Defines the type of arrow head to apply to the line at One of No Arrow No Arrow the X1 Y2 position start of line and or the X2 Y2 Start Arrow End position end of line Arrow or Both Start and End Arrows Line Type Defines the type of line to draw One of Solid Solid Dotted or Dashed Line Width Defines the pixel width of the line 1 to 100 1 Very Low Range The value which when the real time value is lower Any 64 bit floating 0 Value shall result in the line being drawn with the Very Low point value Range Line Color Note that Very Low Range Value lt Low Range Value lt High Range Value lt Very High Rang
206. om IEC 60870 5 101 104 compliant devices Map settings are available on the Client Map tab when an IEC 60870 5 101 104 protocol type is selected Common Properties Settings are available in the Device Properties pane Table 33 lists the device specific protocol settings Table 33 Common Properties Setting Description Range Default Buffer Overflow DI The information object address of the DI point O to 16777215 0 where the ON 1 state indicates that the event buffer on the device has overflowed A value of 0 disables this feature Command The time in seconds after which a Command 0 01 to 3600 0 10 0 Timeout is assumed to have completed if the Termination message has not been received from the remote device General The time in seconds after which a General 0 01 to 3600 0 30 0 Interrogation Interrogation is assumed to have completed if Timeout no Termination of General Interrogation message has been received from the remote device Counter The time in seconds after which a Counter 0 01 to 3600 0 30 0 Interrogation Interrogation is assumed to have completed if Timeout no Termination of Counter Interrogation message has been received from the remote device Time Sync The time in seconds after which a Delay 0 01 to 3600 0 5 0 Timeout Acquisition Request or a Time Sync request is assumed to have completed if the ACTCON PDU has not been received from the remote device ACTCON Expected Specifies whether or
207. on Range Default Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Application Select the application parameters defining Use Default Use Default Parameters this connection The default parameters can Yse Custom be used or a custom configuration can be created Refer to IEC 60870 5 103 Multi drop Application Settings Line ID Text description to identify the electrical 1 to 32 ASCII Line X transmission line associated with this serial characters connection Device ID Text description to identify the device 1 to 32 ASCII Device X associated with this serial connection characters Bay ID Text description to identify the bay area 1 to 32 ASCII Bay X associated with this serial connection characters Common The device s common address of ASDU 0 to 254 1 Address of ASDU D400 Substation Data Manager Software Configuration Guide 39 GE Energy Setting Description Range Default Link Address The link address of the device 0 to 254 1 Map File Name of the Client map file to be used with List of user N A the specific device configured client map files Enable on Start Indicates if communication to the device Disabled Disabled Up automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots IEC 60870 5 103 Multi drop Application Set
208. one or more data collection blocks and polled according to the instance specific protocol settings Network Master Stations The D400 can support communications to multiple up to eight master stations The data presented to each master station may be identical or unique as defined by a server map Although the D400 accepts data requests from only one master station at a time it can support requests from any master station Adding a Network Connection You manage the network connections on the D400 on the Connection tab on the Configuration page A map file must be available in the D400 before a protocol type can be added The D400 includes several default maps If you require a custom map create it first before setting up the network connection See section 4 2 Client Maps or section 5 2 Server Maps gt gt To add a network connection e On the Configuration page click the Connection tab then click Add Connection and configure each network connection Network devices are added to and configured in the defined network blocks Each item under the Network heading of the Connections pane represents one device D400 Substation Data Manager Software Configuration Guide 47 GE Energy connection through an Ethernet port on the D400 Up to 64 devices can be configured on each data collection block Note IEC 61850 device connections are available for viewing only and cannot be edited on the Network page To change the IEC 61850 client
209. only Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag Per Point Settings Address Read only N A N A IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected DI Assigned point from the Point Picker Read only Identifier Point Name Text description of the point in the Binary Input Up to 128 Assigned IED map Based on selected DI point Read only characters point name Accumulator Specifies whether every change transition or Pulse Pulse Type every pair of changes pulse in the monitored Transition accumulator point value increments the reported count Accumulator Specifies whether the running or frozen Running Running Return Type accumulator value is reported Frozen Accumulator Specifies whether or not the master station is Enabled Disabled Freeze allowed to freeze the monitored accumulator Disabled point Accumulator Specifies whether or not the master station is Enabled Disabled Clear allowed to clear the monitored accumulator Disabled point Threshold Specifies the minimum change in accumulator 0 to 1000000 1 value required to produce a spontaneous report or event Only used when the Accumulator Return Type is Running 100 swmoo66 2 75 0 General GE Energy Measurand Table 87 Measurand Mapping Settings Setting Description Range Default Info Object Settings Info Object The name of the informa
210. ored Based on user identifier configured DI point name prefixed with system assigned identifier Source Point Second of two digital input source points List of points N A Two selected to comprise the 4 state point being based on monitored configured Dis Root Directory Info Object Settings Table 90 Root Directory Mapping Settings Info Object The name of the information object as entered Name on the New Info Object window Read only Address The address of this entry address of this The address of this entry Setpoint Command Table 91 Setpoint Command Mapping Settings Setting Description Range Default Info Object Settings Info Object The name of the information object as entered N A N A Name on the New Info Object window Read only Starting The starting address of this entry 1 to 16777215 Address Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag 104 swmo066 2 75 0 General GE Energy Setting Description Range Default Conversion The type of setpoint command There are 3 Normalized Normalized possible types Scaled e Normalized value is between 1 and ShortFP 1 24 15 e Scaled value is scaled using multiplier and offset to 2 15 to 2 15 1 e Short Floating Point value is a 32 bit floating point Per Point Settings Address The a
211. otocol is defined The D400 configuration tool supports configuration of protocol specific object references scaling factors and user defined names for various objects configured for transmission Where applicable you can also configure additional device level settings for the same protocol at the same time This chapter gives detailed information for configuring a DNP3 SCADA master For step by step information on using the configuration tool refer to the D400 online Help D400 Substation Data Manager Software Configuration Guide 93 GE Energy 5 1 Configuration Overview Configuring server applications for use on the D400 typically includes the following activities 1 Create D400 server map file for each master station and protocol type Select data points and assign point indices Configure protocol specific settings Configure scaling and enable reverse scaling reverse effect of scaling applied by a client application Set up serial and network master connections Configure protocol specific settings for each master connection Save the configuration file Run the configuration file in the D400 by committing the changes FW Nh fo NTN 5 2 Server Maps SCADA master stations monitor many remote terminal units and gateway devices for certain critical information The D400 forms an integral part of a SCADA system by collecting data from devices and then transmitting selected information to the master station as
212. ow or a new window An action to open a link in a different window shall require that the configured URL does not address a Main page or Power Bar Enabled page An action to open a link in the same window shall require that the configured URL addresses a Power Bar Enabled page when the current page is also a Power Bar Enabled page URL Address Defines the web page to load when a user selects Any valid URL None the object address Table 148 Digital Status Object Settings Setting Description Range Default Point Identifier A point identifier for a single RTDB text point where Existing text point None the identifier consists of the device name and point identifier descriptor Table 149 Transformer Object Settings Setting Description Range Default Object Identifier Optional Object Identifier of a Raise Lower Control Existing None Object Raise Lower Control Object Identifier x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 60 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 60 the object width
213. owledgement Defines the user mouse action required to One of Single Left Double Left Action acknowledge an alarm box Click Double Left Click Click or No Mouse Click Table 129 Analog Set Point Object Settings Setting Description Range Default Point Identifier A point identifier for a single analog output point on Existing analog None which to operate a set point command where the output point identifier consists of the device name and point identifier descriptor Minimum Value Minimum permitted set point value Any 64 bit floating 0 point value Maximum Value Maximum permitted set point value Any 64 bit floating 0 point value Function Code The type of protocol request to send as part of the One of Direct Direct Operate set point command Operate or Direct Operate with No Acknowledgement D400 Substation Data Manager Software Configuration Guide 143 GE Energy Setting Description Range Default Enable Feedback Whether or not to enable a feedback analog input True or False False point to receive status on a set point command Note In a distributed system the only reliable way to determine the success of a control operation is through a hardwired digital input or analog input point providing the feedback of the process state being controlled Feedback Point If Enable Feedback is True a point identifier for a Existing analog None Identif
214. p tab The D400 provides the mapping settings for accumulators as shown in Table 61 Table 61 Accumulator Mapping Settings Setting Description Range Default Point Number of the point in the Accumulator Map 0 to 65535 Incremented from O Point Name A text string that describes this point Up to 128 ACC_Xxx characters Point Group Point group to which the point belongs List of defined Group point groups assigned to ID number 0 76 SWM0066 2 75 0 General Device Properties Settings are available in the Device Properties pane on the Client Map tab Table 62 lists the poll specific settings for the DNP3 device Table 62 DNP3 Device Properties GE Energy Setting Description Range Default Name Name of the device map file Up to 8 N A characters Request Data Link Enables request Data Link Confirmations from True True Confirm the device False Data Link Retry How many times to retry a failed data link O to 300 a layer message before giving up Increase the value for unreliable connections noisy environment modem communication etc Data Link Timeout Time in milliseconds to wait for a data link 1 to 3600000 1000 i e 1 layer response before deciding it has failed second Set the value much higher for a modem connection i e 600000 Enable Unsolicited True Send Enable Unsolicited at startup and True False in response to a NULL UR
215. point in the Binary Input Up to 128 Assigned IED map Based on selected DI point Read only characters point name Invert Select if the value of the mapped points should True or False False be inverted Regulating Command Table 89 Regulating Command Mapping Settings Setting Description Range Default Info Object Settings Info Object The name of the information object as entered N A N A Name on the New Info Object window Read only Starting The starting address of this entry 1 to 16777215 Address Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag Per Point Settings Address The address of this entry Read only N A N A Control Type The type of control to operate Trip Close Persistent Regulating Persistent D400 Substation Data Manager Software Configuration Guide 103 GE Energy Setting Description Range Default Short Pulse The control duration in seconds of the short 1to 1000 Duration pulse output 2147483647 Long Pulse The control duration in seconds of the long 1to 2000 Duration pulse output 2147483647 Transmission The type of transmission used for command Select and Select and Type control execution either a select and execute Execute Execute command sequence or direct execute Direct Execute command sequence Source Point First of two digital input source points selected Not editable System One from the Point Picker to comprise the 4 state assigned point being monit
216. ported by the device A value of 255 indicates another error condition not specifically listed has occurred Error Class Error Description Value of Al Unknown Error Unknown error 255 DataAccessError object non existent 10 DataAccessError object access unsupported 9 DataAccessError object attribute inconsistent 8 DataAccessError type inconsistent 7 DataAccessError type unsupported 6 DataAccessError invalid address 5 DataAccessError object undefined 4 DataAccessError object access denied 3 DataAccessError temporarly unavailable 2 196 swmoo66 2 75 0 General Error Class Error Description Value of Al DataAccessError hardware fault 1 Success Success 0 Additional Cause Blocked by switching hierarchy 2 Additional Cause Select failed 3 Additional Cause Invalid position 4 Additional Cause Position reached 5 Additional Cause Parameter change in execution 6 Additional Cause Step limit 7 Additional Cause Blocked by Mode 8 Additional Cause Blocked by process 9 Additional Cause Blocked by interlocking 10 Additional Cause Blocked by synchrocheck 11 Additional Cause Command already in execution 12 Additional Cause Blocked by health 13 Additional Cause 1 of n control 14 Additional Cause Abortion by cancel 15 Additional Cause Time limit over 16 Additional Cause Abort
217. pplication 0 to 65535 200 Timeout adds to the frame timeout calculation Inter Frame Gap The minimum idle time in milliseconds 0 to 1000 0 between frames transmitted by the application Holding Time The maximum delay in milliseconds of 0 1 to 500000 0 0 2 reporting spontaneous data changes to the master station after the data is available for transmission Retry Time The interval in seconds between LRU 0 1 to 86400 0 5 0 attempts to resend messages held in its buffer after previous failed transmissions 36 SWM0066 2 75 0 General IEC 60870 5 101 Multi drop The following settings are used when configuring an IEC 60870 5 101 Multi drop GE Energy connection Table 14 IEC 60870 5 101 Multi drop Setting Description Range Default Link Address The number of octets used for the link lore 1 Size address of the device Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots Application Select the application parameters defining Use Default Use Default Parameters this connection The default parameters can Yse Custom be used or a custom configuration can be created Refer to IEC 60870 5 101 Multi drop Application Settings Line ID Text description to identify the electrical 1 to 32 ASCII Line X transmission line associated with this serial characters connection
218. pplied PC programs This is done by configuring the port the device is connected to as a Terminal Server Refer to section 8 5 Pass Through Connections for more information The following settings are used when configuring a Terminal Server Setting Description Range Default Device Name Text description to identify the terminal 1 to 32 ASCII N A server characters Auto Start Up Indicates if the client application Disabled Disabled automatically starts when the configuration Enabled is changed and reloaded or when the D400 re boots 46 SWM0066 2 75 0 General GE Energy 3 2 Network Connections You can configure up to eight Ethernet ports for network communications using TCP IP or UDP IP to master stations and networked devices The D400 supports network connections as follows e Upto four instances of each client application e Up to 64 devices per client instance e Upto 8 master stations The D400 currently supports network communications using the DNP3 protocol Network Blocks To improve the efficiency of communications the D400 supports network capable device and master connections using blocks that can process communications concurrently Each network block is an instance of a designated protocol client or server application Connections to devices are grouped on up to four data collection blocks per protocol Network Devices Network capable devices can be connected to
219. presenting the transient states p of a dual point Table 119 Text State Settings Text State 00 Text to display to represent the point state when both 1 to 32 Alarm Point 1 and Alarm Point 2 are in state 0 typically alphanumeric the Normal state Typically set to InTransit characters Text State 01 Text to display to represent the point state when Alarm 1 to 32 Point 1 is in state 0 and Alarm Point 2 is in state 1 alphanumeric typically the Alarm state Typically set to Open characters Text State 10 Text to display to represent the point state when Alarm 1 to 32 10 Point 1 is in state 1 and Alarm Point 2 is in state O alphanumeric typically the Normal state Typically set to Closed characters Text State 11 Text to display to represent the point state when both 1 to 32 11 Alarm Point 1 and Alarm Point 2 are in state 1 typically alphanumeric the Alarm state Typically set to Invalid characters Alarm Group Configuration The Annunciator supports the configuration of five alarm groups Group1 Groupe Group3 Group4 and System5 When you configure an alarm you select to which group the alarm belongs The System alarm comprises the Buffer Overflow alarm which is raised when the alarm buffer has reached its configured maximum size and started either deleting old records or rejecting new ones based on the configured behavior See Maximum Number of Alarms in Table 122 To configure al
220. r device communications SCADA master communications and substation monitoring and control functions In particular you may want to customize the following aspects of the D400 Communication connections Device data collection Master Station data presentation Alarm annunciation Data calculation Data logging Operational one line diagrams optional User management HMI preferences E mail notification The D400 includes a variety of tools to help you set up the D400 to operate in your substation automation system including D400 Online Configuration Tool One Line Designer IEC 61850 Loader and LogicLinx optional D400 System Utilities This chapter gives an overview of each tool and the basic steps to configuring the D400 14 SWM0066 2 75 0 General GE Energy 2 1 D400 Online Configuration Tool The D400 Online Configuration Tool is used to create edit and update the software configuration of the D400 while it is in operation The Online Configuration Tool is a component of the D400 HMI Figure 4 D400 Configuration Tool Interface HMI Power Bar Invoke Configuration Tool we N Configuration Tool GUI e Configuration Data k y Configuration XML Files Configuration Data You use the D400 Online Configuration Tool to e Set up D400 communications to devices and masters serial or network connections e Select and or create point maps for devices
221. r is a tool that enables you to create specialized diagrams and forms customized to your substation environment and viewable via the One Line Viewer In addition to creating a diagram or schematic of your network you can display real time readouts of the values of selected ports and points 7 1 Drawing Overview Standard Toolbar The standard toolbar provides tools to save and open diagrams modify the placement of objects and change the way the Drawing Area is shown gt gt 2 gt gt z g 2 2 jo E E jo as S 6 o 2 x E 5 2 8 3 5 8 e S 2 BF BEF 5 2 Ss 2 B 3B 3B 5b Eg Bg gt 2V gt g So e 8 e e 8 e B gt a BD amp 3 5 8 8 Fe Fe F amp F FS BH R A S S z 0 FA GO GO DY te tof a Aa D a GB a Ad e i im gan oe Dice Ga RL GS ole aT ett MERWE Ae If you forget a button s meaning hover the mouse pointer over the button and a short description of the button s function is provided in the upper right of the display A shortcut key combination is also shown that you can use to invoke the command D400 Substation Data Manager Software Configuration Guide 137 GE Energy Save As with any application it is imperative that you save your data in a regular and ongoing fashion Click the Save button and enter a file name Please note that the filename must be limited to a maximum of eight alphanumeric characters followed
222. rmula Full range of 64 0 0 mx b bit Float Input Status Mapping settings are available on the upper pane of the Input Status tab as shown in Table 113 Table 113 Input Status Mapping Settings Setting Description Range Default Address The MODBUS address assigned to the point 0 to 65535 Xx IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected Assigned DO point from the Point Picker Read only Identifier Point Name Text description of the point in the Digital Output Up to 128 Assigned IED map Based on selected DO point Read only characters point name Type The point type Read only DI Al AO ACC Assigned type Invert Select if the value of the mapped points should True or False False be inverted Property settings are available in the lower pane of the Input Status Mapping tab The configuration settings defined in Table 114 are used to configure the default values for all read write registers defined in the MODBUS server map Table 114 Input Status Properties Setting Description Range Default Default Invert Select if the value of the mapped points should True or False False be inverted by default 122 swm0066 2 75 0 General GE Energy Configuring D400 Automation Applications The D400 Automation applications retrieve data from the real time database manipulate the data and store the results in the real time database The type of data supported by the automation
223. rom which the PointName may be selected In the One Line Designer the combined device name and PointName are shown However when this diagram is viewed with the One Line Viewer the actual value targeted by this designator is what appears in the Value Box Font elements and color choices are available for customization The HttpPort value is presently reserved for future implementation CB Box The CBBox object is designed to schematically represent a power system circuit breaker The CBBox object accepts status inputs from 2 digital points BitStrings You can program the fill colors of the breaker object by setting colors to the following properties e FT_Color e FF_Color e TT_Color e TF_Color Based on the logic levels of the Digital Points selected the fill color of the CBBox will change appropriately in the Run_Mode 140 swm0066 2 75 0 General o GE Energy In the design mode you can set the properties of Value1 and Value2 to 0 or 1 and verify that the fill color settings are satisfactory Additionally several values unique to Circuit Breaker Box operation are required You can designate the color values for the object dependent on what the Target Value is and whether or not it is returned Two appropriate points should be identified These two Points may come from two different devices or can come from same device and are entered into the appropriate Property Value lines for EDname and the PointName Again double clicking
224. rotocol function code to pass as part of the digital control command sent to a device Select Before Operate Direct Operate Select Before Operate 118 swm0066 2 75 0 General GE Energy Setting Description Range Default Default Count Number of times to consecutively repeat a 1 to 255 uh control code applying the pulse on and pulse off times to each control pulse repetition applies only to Control Codes of type Pulse On Pulse Off Trip or Close Default On Time Default duration in milliseconds of an ON pulse O to 65535 0 Default Off Time Default duration in milliseconds of an OFF 0 to 65535 0 pulse Read Only Registers Mapping settings are available on the Read Only Registers tab as shown in Table 109 Table 109 Read Only Register Mapping Settings Setting Description Range Default Address The MODBUS address assigned to the point 0 to 65535 Xx IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected Assigned DO point from the Point Picker Read only Identifier Point Name Text description of the point in the Digital Output Up to 128 Assigned IED map Based on selected DO point Read only characters point name Type The point type Read only DI Al AO ACC Assigned type Data Format The type of data polled See Table 76 INT16 Point Value to The attribute of the point to be polled Value Value
225. rrogation interval in 0 0 to 1440 0 0 0 Interrogation minutes A value of 0 0 disables Group x Interval Counter Interrogations to the remote device except on application startup Global The Global General Interrogation Interval in 0 0 to 1440 0 30 0 Interrogation minutes A value of 0 0 disables Global Interval General Interrogations to the device except on application startup Group X The Group X General Interrogation Interval in 0 0 to 1440 0 0 0 Interrogation minutes A value of 0 0 disables Group X Interval General Interrogations to the device except on application startup D400 Substation Data Manager Software Configuration Guide 59 GE Energy IEC 60870 5 101 Settings are available in the IEC 60870 5 101 pane Table 34 lists the device specific protocol settings Table 34 IEC 60870 5 101 Properties Setting Description Range Default Information The number of octets used in the information 1to3 1 Object Address object address field Length Cause of The number of octets used in the Cause of 1to2 1 Transmission Transmission field Length Data Link Confirm Specifies whether or not the application Enabled Enabled requests data link confirmation when Disabled transmitting data TX Delay Specifies whether or not the application Enabled Enabled Acquisition performs a TX Delay Acquisition command to Disabled the device prior to performing the Clock Synchronization Default TX Delay The def
226. rs Setting Description Range Default Application Tab Number of The number of message buffers allocated by 1 to 65535 5 Message Buffers the application used to receive messages and to transmit requests to the remote devices Device Restart The delay in seconds between each device 0 0 to 3600 0 0 0 Delay restart sequence at application start up Stagger General Specifies whether or not GI polls performed Enabled Disabled Interrogation by the application are staggered Disabled 50 SWM0066 2 75 0 General GE Energy Setting Description Range Default GI Qualifier The Qualifier to use for the General Not editable Blank Interrogation poll GI Stagger The staggered GI poll interval in minutes Not editable Blank Interval Backoff Time The time in seconds to wait before the 0 to 65535 30 application tries to re contact a device after a communication failure Min Inter Poll The minimum time delay in minutes 0 0 to 1440 0 0 0 Delay between any two consecutive application level polls Network Tab Max Length The maximum length in octets of APDU 253 Not editable APDU Frame frames IEC 60870 5 104 Master Station The following settings are used when configuring an IEC 60870 5 104 Master Station connection Table 31 IEC 60870 5 104 Master Station Setting Description Range Default Remote Text description to identify the mas
227. s are configured identically For more information see section 8 7 D400 Configuration Manager D400 Configuration Utility Redundancy The D400 Configuration Utility is a tool accessed through the command line of the D400 The Redundancy section of this utility is used to configure the parameters of the redundancy application For more information see Redundancy in section 8 3 D400 Configuration Utility 2 5 D400 System Utilities Configuration information related to the D400 system is changed using utility programs that are installed on the D400 platform You can access these system D400 Substation Data Manager Software Configuration Guide 17 GE Energy utilities directly at the D400 command prompt through the local maintenance port or remotely through the Utilities Power bar button in the D400 HMI The D400 system utilities are typically used during the initial setup of the D400 and for changing the basic configuration of the system including the network connections system date and time and administrator passwords For more information on using the D400 System Utilities see chapter 8 System Utilities and also the D400 Substation Data Manager User s Manual 2 6 Configuration Steps The typical sequence of steps to configure the D400 to operate in a substation automation system is as follows 1 Set up network and system settings using the D400 System Utilities 2 Create and or edit Client device maps using the
228. sabled Disabled Zero Threshold Reporting Specify how the LRU should treat a zero value for the Threshold configuration parameter for an analog input If this setting is enabled setting the threshold configuration parameter of an analog input point to zero i e 0 0 spontaneously reports all changes for the point If disabled setting the Threshold configuration parameter of an analog input point to zero shall disable spontaneous reporting for the point Enabled Disabled Disabled Time Tagging When to report time tag data If configured as Not on Interrogations the LRU reports a time tag only for spontaneous periodic cyclic or background scan causes of transmission that is the LRU suppresses time tag for interrogated data If configured as Always the LRU reports time tag for all causes of transmission Not on Interrogations Always Not on Interrogations Clear Statistics Specify if the application should reset all LRU statistics to zero at startup Enabled Disabled Disabled D400 Substation Data Manager Software Configuration Guide 53 GE Energy Setting Description Range Default Comm Log Mode The logging mode for all I O communications Disabled Hex traffic with the LRU ASCII Hex ASCII and Hex Number of Files The number of information object addresses 0 to 128 0 Supported reserved for file transfer Not us
229. se was used and the feature has now been disabled This feature cannot be re activated unless a license is purchased To enable a trial license for an application or feature A 30 day trial license can be obtained for any application listed as Trial Disabled in the Application License report 1 Start a terminal session and log into the D400 2 Atthe prompt enter the following commands cd home D400_APPS swlic trial id lt 3 digit application ID number gt Note The 3 digit application ID number can be obtained using the swlic report utility The 30 day trial license is enabled for the feature Once the 30 days has elapsed the feature will be disabled A trial license can only be enabled once for each feature 190 swm0066 2 75 0 General GE Energy gt gt To obtain information about your D400 Some older D400 units may not contain a license file In this case Customer Service can generate a replacement license file for you To do this you must provide unique identifying information about your D400 1 Start a terminal session and log into the D400 2 Atthe prompt enter the following commands cd home D400_APPS swlic info Provide the information shown to Customer Service 8 9 Emergency Access Code gt gt gt gt In the event that you cannot log into your D400 you can generate an emergency access code that will bypass user authentication and give you access to the local or remote HMI
230. shall disable spontaneous reporting for the point Enabled Disabled Disabled Time Tagging When to report time tag data If configured as Not on Interrogations the LRU reports a time tag only for spontaneous periodic cyclic or background scan causes of transmission that is the LRU suppresses time tag for interrogated data If configured as Always the LRU reports time tag for all causes of transmission Not on Interrogations Always Not on Interrogations Clear Statistics Specify if the application should reset all LRU statistics to zero at startup Enabled Disabled Disabled Comm Log Mode The logging mode for all I O communications traffic with the LRU Disabled ASCII Hex ASCII and Hex Hex Number of Files Supported The number of information object addresses reserved for file transfer Not used when set to 0 Oto 128 Time to Live The time period in seconds a queued control command is to be treated as active in the system If the configured value is 0 the RTBD setting is used 0 0 to 60 0 0 0 Cause of TX Length The number of octets used for the Cause of Transmission field lor2 D400 Substation Data Manager Software Configuration Guide 35 GE Energy Setting Description Range Default Unbalanced Serial Link Tab Max ASDU Frame The maximum length in octets
231. smission mode used by the Unbalanced Unbalanced Mode application Balanced Unbalanced Serial Link Tab Background The interval in seconds of background 0 0 to 86400 0 3 0 Polling Interval autonomous polling that happens at the data link layer 38 SWM0066 2 75 0 General GE Energy Setting Description Range Default Reply Poll Count The Maximum number of times to poll a Oto 255 10 device for Class 2 and 1 data subsequent to receiving a positive acknowledgement at the link layer CONFIRM ACK in response to a SEND CONF user data request at the link layer that was sent due to an application level request Max Poll Count The maximum number of times to poll a 1 to 255 3 device for Class 1 data before changing to poll the next device while performing background autonomous polling Balanced Serial Link Tab Extra Response The time in milliseconds to add to the frame 0 to 65535 200 Timeout timeout calculation Inter Frame Gap The minimum idle time in milliseconds 0 to 1000 0 between frames transmitted by the application Single Char Specifies if the application replies to the Enabled Disabled Acknowledgeme_ remote device with a single character Disabled nt acknowledgement IEC 60870 5 103 Multidrop The following settings are used when configuring an IEC 60870 5 103 Multi drop connection Table 16 IEC 60870 5 103 Multi drop Setting Descripti
232. splay the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 20 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the object width Border Color Defines the color to apply to the border around the Any 24 bit RGB Black perimeter of the display area of the object Color Border Width Defines the pixel width of the border 1to7 1 Border Type Defines the type of border to display Oto 255 0 Font Type The type of font used to display value as text One of SansSerif SansSerif Serif Monospaced Dialoginput Font Size The size of the font used to display value as text 1 to 100 11 Font Style The font style to apply to the display of the value as One of normal Normal text bold or italic Foreground Color The color to apply to the value displayed as text Any 24 bit RGB Black Color High Range Color The color to apply to the background but only when Any 24 bit RGB Red the real time value exceeds the configured High Color Range Value Mid Range Color The color to apply to the background but only when Any 24 bit RGB Red the real time value is greater than or equal to the Color configured Low Range Value and is less than or equal to the configured High Range Value
233. stem Directory and Point Name Based on selected Assigned DO point from the Point Picker Read only Identifier Point Name Text description of the point in the Digital Output Up to 128 Assigned IED map Based on selected DO point Read only characters point name Type The point type Read only DI Al AO ACC Assigned type Data Format The type of data polled See Table 76 INT16 Point Value to The attribute of the point to be polled Value Value Use Frozen Value Date and Time Freeze Date and Time Multiplier Scale factor of the point m of formula mx b Full range of 64 1 0 bit Float Offset Scale factor of the point b of formula mx b Full range of 64 0 0 bit Float Property settings are available in the lower pane of the Read Write Registers tab The configuration settings defined in Table 111 are used to configure the default values for all read write registers defined in the MODBUS server map D400 Substation Data Manager Software Configuration Guide 121 GE Energy Table 112 Read Write Register Properties Setting Description Range Default Default Point The attribute of the point that should be polled Value Value Value To Use by default Frozen Value Date and Time Freeze Date and Time Default Default scale factor of the point m of formula Full range of 64 1 0 Multiplier mx b bit Float Default Offset Default scale factor of the point b of fo
234. t Invert Done Coils Mapping settings are available in the upper pane of the Coils tab as shown in Table 105 Table 105 Coil Mapping Settings Setting Description Range Default Address The MODBUS address assigned to the point 0 to 65535 X IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected Assigned DO point from the Point Picker Read only Identifier Point Name Text description of the point in the Digital Output Up to 128 Assigned IED map Based on selected DO point Read only characters point name Type The point type Read only DI DO Assigned type Control Spec See Table 106 Only enabled for DO type points Feedback Opt If set to Self the values of the DO points are Self Self returned If set to Digital Inputs the value of the Digitallnput Digital Input point is returned Only enabled for DO type points Feedback Point If Feedback Opt is set to Digital Input the point List of points N A selected will be returned based on configured Dls D400 Substation Data Manager Software Configuration Guide 117 GE Energy Setting Description Range Default Invert Select if the value of the mapped points should True or False False be inverted Only enabled for DI points Table 106 Control Specification Properties Setting Description Range Default Control Code
235. t Settings Info Object The name of the information object as entered N A N A Name on the New Info Object window Read only Starting The starting address of this entry Address Interrogation The interrogation group used for reporting this Not Used Not Used Group information object Group 1 Group 16 Interrogation Specify whether to include this information Include Include Response object in a general interrogation response Exclude Report Class Specify if spontaneous events for this object are Class 1 Class 1 reported as class 1 or class 2 messages Applies Class 2 to unbalanced mode and spontaneous events only D400 Substation Data Manager Software Configuration Guide 107 GE Energy Setting Description Range Default Periodic Update The type of periodic updating Not Used Not Used Mode Background Scan Periodic Update The time in seconds between periodic reports 1 to 255 60 Interval Used only if Periodic Update Mode is not set to Not Used Periodic Report Specify if periodic reporting if enabled should Disabled Disabled On Power Up begin immediately upon startup Enabled Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag Per Point Settings Address The address of the entity IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected DI Assigned point from the Point Picker Read
236. t is never transmitted Class3 Poll sec The D400 requests class 3 data at this interval 0 to 36000 5 in seconds If set to 0 the request is never transmitted Al Poll sec The D400 requests analog input data at this 0 to 36000 0 interval in seconds If set to 0 the request is never transmitted Frozen Al Poll sec The D400 requests frozen analog input data 0 to 36000 0 at this interval in seconds If set to O the request is never transmitted 78 SWM0066 2 75 0 General GE Energy Setting Description Range Default Al Change Poll sec The D400 requests analog input event data at this interval in seconds If set to 0 the request is never transmitted 0 to 36000 Frozen Al Change Poll sec The D400 requests frozen analog input event data at this interval in seconds If set to O the request is never transmitted 0 to 36000 Float Al Poll sec The D400 requests single precision analog input with flag at this interval in seconds If set to 0 the request is never transmitted 0 to 36000 16 Bit Al Poll sec The D400 requests 16 bit analog input with flag data at this interval in seconds If set to O the request is never transmitted 0 to 36000 32 Bit Al Poll sec The D400 requests 32 bit analog input with flag data at this interval in seconds If set to O the request is never transmitted 0 to 36000 AO Poll sec Th
237. t its mode while copying configuration to transferred configuration into the flash mnt usr card The flash card may be full or someone may have changed the write permissions on the card The standby configuration may be partially copied and unusable 30 STANDBY Config Sync failed in local mode Configuration synchronization failed while due to tool task failure transferring configuration data The standby unit uses its original configuration D400 Substation Data Manager Software Configuration Guide 203 GE Energy Sr No Diagnostic log messages Details 31 STANDBY Config Sync failed in local mode while copying configuration to mnt usr The standby D400 unit failed to commit its transferred configuration into the flash card The flash card may be full or someone may have changed the write permissions on the card The standby configuration may be partially copied and unusable 32 STANDBY CONFIG SYNC Activity Tool task timeout in mode lt tool task mode gt Configuration synchronization failed while transferring configuration data The standby unit uses its original configuration 33 STANDBY CONFIG SYNC Activity Response timeout The active unit failed to send a response during configuration sync activity The active unit may be experiencing problems or the communication link between the two units may be disconnected The standby configuration may be partially cop
238. taLinkRety Data Link Timeout 1 000 Point Number Point Name Muttiplier onset Point Group Enable Unsolicned taise DAL_000 10 0 0 Val a Disable Unsolicited false 1 A001 10 0 0 Pval Feedback Poll AO taise 2A_002 10 0 0 Pval Feedback Poll DO vue 3A_003 10 0 0 Pvat Feeaback Poll events raise 4A_004 10 0 0 Pval Override Control Type None S A_005 10 00 Pval A_006 10 00Pvat 71007 10 00 Pvat A008 10 oo Pvai Enable Exense Feedba wue SA _009 10 o0 Pval Feedback Poll Delay 1 10AL_010 10 00 PVal Counter Feedback Poll D 1 mAN 10 OO Pval IED Persists Counters wue 12A_012 10 o0 Pvai Frasze Commana Runnngcounters 13A_013 10 0 0 Pval Integrity Pon 2 14A_014 10 00 Pval Class 1 Pou 1 15A_015 10 0 0Pval Class 2 Pon 1 16A_016 10 0 0Pval Class 3 Poll 1 174017 10 o0 Pvai DI Poll 0 18A_018 10 ooPva DI Change Polt 0 1941019 10 00 Pval DO Pon o 2041020 10 00 Pval A Pon 0 R 10 00 Pval AI Change Poll 0 22A_022 10 0 0 Pval Frozen A Pol o 23A_023 10 00 Pval Frozen Al Change Poll o 24024 10 0 0 Pvai B 16 A Pon o 25025 10 0 0 Pval Seis Link Roby 26A_026 10 00Pvai Number af tas ts ray a failed data link layer mamape botera 27 a 77 a anovu T giving sp Map Fie analogam amp 4 A Points NUM Done 74 SWM0066 2 75 0 General GE Energy Analog Inputs Settings are available on the Analog Input tab on the Client Map tab The D400 provides the mapping settings for analog inputs as shown in Table 57 Table 57 Analog Input Mapping Settings
239. ted Default Class Default Class for change events on the point None 3 2 1 User selected Default 110 swm0066 2 75 0 General GE Energy Settings are available in the lower pane of the Analog Inputs tab The configuration settings defined in Table 96 are used to configure the default values for all analog input points defined in the DNP3 server map Table 96 Analog Input Properties Setting Description Range Default Default Class All Al events belong to this class by default None 2 Assignment 3 2 1 Default Static Type to report when the master does not 32 Bit 32 Bit Variation request any specific type 16 Bit 32 Bit w o flag 16 Bit w o flag 32 Bit Float Default Event Type to report when the master does not 32 Bit with Time 32 Bit with Time Variation request any specific type 32 Bit without Time 16 Bit with Time 16 Bit without Time 32 Bit Float with Time 32 Bit Float without Time Default Dead Minimum change in the Al point value that 0 65535 5 Band constitutes an event A value of 0 disables event generation for the point Digital Inputs Settings are available on the Digital Inputs tab The default property values are defined in the lower pane The D400 provides the mapping settings for digital inputs as shown in Table 97 Table 97 Digital Input Mapping Settings Setting Description Range Default Index Point Inde
240. ter station 1 to 32 ASCII N A Connection associated with this serial connection characters Name Map File Name of the Server map file to be used with List of user N A the specific master configured client map files Auto Start Indicates if the client application automatically Automatic Disabled starts when the configuration is changed and_ Disabled reloaded or when the D400 re boots Common Address The device s common address of ASDU 1 to 65534 1 of ASDU Transport Layer Whether to use TCP or UDP network protocol Non editable TCP Network Port The D400 port number on which the master 0 to 65535 2404 station will communicate Application Select the application parameters defining this Use Default Use Default Parameters connection The default parameters can be Use Custom used or a custom configuration can be created Refer to IEC 60870 5 104 Master Station Application Settings Accept All Hosts If enabled all remote hosts are able to Enabled Disabled connect Disabled D400 Substation Data Manager Software Configuration Guide 51 GE Energy Setting Description Range Default Permitted IP addresses of master stations permitted to Up to 8 IP 0 0 0 0 Remote Hosts connect to the D400 If Accept All Hosts is addresses enabled these fields are disabled and ignored IEC 60870 5 104 Master Station Application Settings IEC 60870 5 104 settings are available under the Application Parameters fie
241. tering shutdown r now D400 Substation Data Manager Software Configuration Guide 181 GE Energy Reset NVRAM You can reset the data being held in NVRAM through the Reset NVRAM menu of 3 84 167 216 PuTTY 1 Reset NVRAM 2 Back Enter Your Choice Between 1 and 2 i Reset NVRAM Permanently delete data stored in the NVRAM of the D400 Note After you have reset the NVRAM you must restart the processes running on the D400 To do this exit the D400 Configuration Utility type go at the command line and press enter 182 swmo066 2 75 0 General GE Energy Local HMI You can configure the settings of the local KVM monitor output through the Local HMI menu lo x 1 Current Settings 2 Desktop Mode 3 Monitor 4 DPMS 5 screen Resolution 6 Back Enter Your Choice Between 1 and 6 I Desktop Mode Enoble or disable kiosk mode Kiosk mode will display the local HMI full screen rather than windowed Monitor Enter the horizontal and vertical refresh rates in hertz CAUTION Never exceed the maximum refresh rates of your monitor as damage may occur Refer to the manual that came with your monitor for more information DPMS Enoble or disable Display Power Management Signaling These settings determine how much time must pass without user interaction before your monitor is put into a reduced power mode A setting of 00 will prevent the D400 from triggering the power mode Th
242. the Analog Outputs tab The configuration settings defined in Table 100 are used to configure the default values for all analog output points defined in the DNP3 server map Table 100 Analog Output Properties Setting Description Range Default Default Static Type to report when the master does not 32 Bit 32 Bit Variation request any specific type 16 Bit Digital Outputs Settings are available on the Digital Outputs tab The default property values are defined in the lower pane The D400 provides the mapping settings for digital outputs as shown in Table 101 Table 101 Digital Output Mapping Settings Setting Description Range Default Index Point Index 0 Based Each point index number 0 to 65535 Incremented must be unique from 0 IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected Assigned DO point from the Point Picker Read only Identifier Point Name Text description of the point in the Digital Output Up to 128 Assigned IED map Based on selected DO point Read only characters point name D400 Substation Data Manager Software Configuration Guide 113 GE Energy Setting Description Range Default Supported Command the DNP3 server should expect If the All operations User selected Command DNP3 server receives a command that is not Default configured it will reject the command SBO Only Settings are
243. the DNP3 Server sends to the Events and Events and Data remote station in unsolicited messages indications indications Indications only Unsolicited Defines what data the DNP3 Server sends in the Events and Indications only Startup initial unsolicited startup message indications Indications only Buffer Indicates whether the DNP3 Server discards Discard Newest Discard Oldest Overflow Policy newest or oldest event when a class event queue Discard Oldest overflow occurs Internal Buffer Specifies how to store the unreported events RAM RAM Location collected from Event Queues NVRAM Internal Event Number of events that can be contained in the 512 1024 2048 2048 Buffer Capacity Internal buffer of the DNP3 Server 4096 8192 16384 Class 1 Queue Maximum number of Class 1 Events that can be 512 1024 2048 Up to Capacity Max Length buffered This can either be Up to Capacity or a 4096 8192 Number If a Number is entered the sum Max 16384 Up to Lengths for all Class Queues cannot exceed the Capacity nternal Event Buffer Capacity Class 2 Queue Maximum number of Class 2 Events that can be 512 1024 2048 Up to Capacity Max Length buffered This can either be Up to Capacity or a 4096 8192 Number If a Number is entered the sum Max 16384 Up to Lengths for all Class Queues cannot exceed the Capacity nternal Event Buffer Capacity Class 3 Queue Maximum number of Class 3 Events that can be 512 1024 2048 Up to
244. the latest functionality and improvements Visit the Customer Support website to download the upgrade software and instruction guide 8 SWM0066 2 75 0 General GE Energy About the D400 1 1 Overview The D400 is a SCADA gateway device that encompasses the functionality of several typical substation devices in one It can carry out a variety of functions including e Data concentration collect data from intelligent electronic devices IEDs installed in the substation e Data presentation present collected data to a Supervisory Control and Data Acquisition SCADA system e Annunciator monitor devices for alarm conditions and issue alarms to the operator for action e Substation HMI visually present the substation in one line diagrams and display communications data to a system operator to monitor control and operate the substation locally or remotely over a network e Terminal server provide transparent access also known as pass through to connected devices using vendor supplied PC programs 1 2 How the D400 Works The primary function of the D400 is to concentrate substation data by polling and receiving information from connected IEDs Intelligent Electronic Devices Each device communicates data to the D400 through a serial or Ethernet network connection using a selected protocol The D400 retrieves point information from and sends control requests to each communicating device The D400 can manipulate the data from devi
245. tings IEC 60870 5 103 settings are available under the Application Parameters field Table 17 IEC 60870 5 103 Application Parameters Setting Description Range Default Number of The number of message buffers allocated by 1 to 65535 5 Message Buffers the application used to receive messages and to transmit requests to the remote devices TCP Pass The TCP port number used by the application 0 to 65535 0 Through Port to listen for a pass through service connection from an IED vendor PC program A port number of 0 disables the Pass Through connection service Pass Through The duration in seconds of silence on the 1 00 to 300 00 120 0 Wait Interval serial interface before the application closes the pass through connection Max Confirm Idle The maximum communication idle time in 1 to 65535 100 Time milliseconds before the application must receive a confirm message Max Respond Idle The maximum communication idle time in 1 to 65535 100 Time milliseconds before the application must receive a respond message Max Transmit The maximum number of transmission 1to 255 1 Retries retries before declaring that communication with a remote device has failed Backoff Time The time in seconds to wait before the 0 to 65535 30 application tries to re contact a device after a communication failure Background The interval in seconds of background 0 0 to 86400 0 3 0 Polling Interval autonomous polling that h
246. tion object as entered N A N A Name on the New Info Object window Read only Starting The starting address of this entry 1 to 16777215 Address Interrogation The interrogation group used for reporting this Not Used Not Used Group information object Group 1 Group 16 Interrogation Specify whether to include this information Include Include Response object in a general interrogation response Exclude Report Class Specify if spontaneous events for this object are Class 1 Class 1 reported as class 1 or class 2 messages Applies Class 2 to unbalanced mode and spontaneous events only Periodic Update The type of periodic updating Not Used Not Used Mode Background Scan Periodic Cyclic Periodic Update The time in seconds between periodic reports 0 to 65535 0 Interval Used only if Periodic Update Mode is not set to Not Used Periodic Report Specify if periodic reporting if enabled should Disabled Disabled On Power Up begin immediately upon startup Enabled Time Tag The type of time tag to use None None With Time Tag With CP56 Time Tag Conversion The type of setpoint command There are 3 Normalized Normalized possible types Scaled e Normalized value is between 1 and ShortFP 1 2 15 e Scaled value is scaled using multiplier and offset to 2 15 to 2 15 1 e Short Floating Point value is a 32 bit floating point D400 Substation Data Manager Software Configuration Guide 101 GE Energy
247. to 65535 Incremented must be unique from 0 IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected Assigned ACC point from the Point Picker Read only Identifier Point Name Text description of the point in the Accumulator Up to 128 Assigned IED map Based on selected ACC point Read only characters point name Threshold Minimum change required in the Running 0 to 5000 User selected Accumulator count to cause an event to be Default generated 0 will disable generation of Running Accumulator Events Static Variation How the point values should be reported 32 Bit User selected Applies to Running value 16 Bit Default 114 swm0066 2 75 0 General GE Energy Setting Description Range Default Event Variation Indicates how an event on this point should be reported Applies to Running value 32 Bit with Time 32 Bit without Time 16 Bit with Time 16 Bit without Time User selected Default Frozen Static Variation How the point values should be reported Applies to Frozen value 32 Bit with Time 32 Bit without Time 16 Bit with Time 16 Bit without Time User selected Default Frozen Event Variation Indicates how an event on this point should be reported Applies to Frozen value 32 Bit with Time 32 Bit without Time 16 Bit with Time 16 Bit without Time User selected Default Class Default Class
248. uide are based on using a computer running Windows XP Some steps and dialog boxes may vary slightly if you are using another version of Windows 6 SWM0066 2 75 0 General GE Energy Product Support If you need help with any aspect of your GE Energy product you have a few options Search Technical Support The GE Energy Web site provides fast access to technical information such as manuals release notes and knowledge base topics Visit us on the Web at http www gepower com prod_serv products substation_automation en tech_supp ort_login htm Contact Customer Support The GE Energy Customer Service Center is open 24 hours a day seven days a week for you to talk directly to a GE representative In the U S and Canada call toll free 1 800 361 3652 International customers please call 1 403 214 4600 Or e mail to ge4service ge com Have the following information ready to give to Customer Service e Ship to address the address that the product is to be returned to e Bill to address the address that the invoice is to be sent to e Contact name e Contact phone number e Contact fax number e Contact e mail address e Product number serial number e Description of problem The Customer Service centre will provide you with a case number for your reference D400 Substation Data Manager Software Configuration Guide 7 GE Energy Upgrade Your D400 Firmware The firmware of your D400 can be upgraded to provide
249. urity in the left hand menu 2 For Pass Through and Terminal Server Access select Allow Network Connections The port number is automatically assigned as 8000 plus the serial port number the client is using For example if the client is configured to use serial port 1 the pass through connection port is 8001 To enable pass through connections on a serial port without enabling a client application the port must be configured as an automatic terminal server gt gt To enable pass through connections without a client application 1 On the Connection tab of the D400 Online Configuration Tool configure the port as Terminal Server 2 Set the Startup parameter to Automatic 3 On the System Wide tab of the D400 Online Configuration Tool click Security in the left hand menu 4 For Pass Through and Terminal Server Access select Allow Network Connections The port number is automatically assigned as 8000 plus the serial port number For example if the terminal server is assigned to serial port 2 the pass through connection port is 8002 8 6 Direct Connect Using the D400connect utility you can communicate directly with devices via the D400 The d400connect utility establishes a terminal session with a device connected to one of the D400 serial ports and transfers binary data without modification The direct connect utility is set up at the D400 command prompt Note You cannot launch the d400connect utility on a serial port that
250. use Normal health means an association is possible on this channel Failed health means the last association attempt failed Primary Channel Status Indicates if primary channel is In Use or Not In Not In Use 0 use In use status means this channel is the active channel and the association is up on this n Use 1 channel Secondary Channel Indicates if secondary channel is In Use or NotIn Not In Use 0 Status Use In use status means this channel is the active channel and the association is up on this n Use 1 channel Overflow 1 Report Buffer Overflow Indicates if the device has reported a buffer overflow condition in one of its buffered report No Overflow 0 control blocks Ovemiow 1 Retrieve All Data Sets Operation to retrieve All Data Sets from device Completed 0 from IED Status that was triggered by either the Retrieve All Pending 1 Data Sets from All IEDs or the Retrieve All Data Engng Sets from IED pseudo Digital Output is either completed or under way DeviceDisable Device is enabled or disabled as controlled by Disabled 1 the DisableDevice Digital Output or the Global Enabled 0 DisableDevice Digital Output Nage Polling of IED Status Polling is enabled or disabled as controlled by the Disabled 0 Enable Polling to IED Digital Output or the Enabled 1 Enable Polling of All IEDs to IED Digital Output D400 Substation Data Manager Software Confi
251. ut non compliant Masters may use local time The advanced settings listed in Table 8 are for adjustment by experienced system engineering personnel and project engineers deploying the product in a specified configuration Typically these settings should not require modification Table 8 DNP3 Server Communication Settings Advanced Setting Description Range Default Application Confirm Defines when the DNP3 Server requests remote station confirmation of an application message Never Multi fragment only Event only Event or Multi fragment IIN only IIN or Multi fragment Event or IIN Event IIN or Multi fragment Always Event IIN or Multi fragment Internal Indication Confirm Indicates whether local station indications require confirmation on change in status Buffer Overflow None Buffer Overflow Reboot On Cold Start Reboot D400 on receiving cold restart from Master True False True Response Fragment Size Maximum size of a solicited application message fragment minimum is 249 bytes 249 to 2048 2048 28 SWM0066 2 75 0 General GE Energy Setting Description Range Default Report Comm Determines if a D400 Data Point must be reported True True Failed As as Offline to the Master Station when the D400 False Offline COMM FAILED quality attribute is set Unsolicited What information
252. work connection between the D400s may be disconnected or the public private authentication keys may not be correctly configured 10 ACTIVE Tool task failed with error lt error Configuration synchronization failed code gt because the standby unit issued an error Review the lt error code gt in the table of Configuration Manager error codes 11 ACTIVE CONFIG SYNC failed due to tool task Configuration synchronization failed timeout because the Configuration Manager software failed to respond 12 ACTIVE Standby D400 rejected the DB Sync The standby rejected a request to start request with reason lt reason code gt synchronize either quality or accumulator data The lt reason code gt is a technical number with more detail The most common cause is that the standby unit is in service mode or has failed 13 ACTIVE Standby D400 failed in DB sync in Synchronization of either quality or network mode accumulator tables failed to complete The most common cause is that either communications with the standby unit have been interrupted or the standby is in service mode or has failed 14 ACTIVE Response timeout for activity The standby unit failed to send a response lt activity type gt subactivity lt subactivity type gt to the active unit The numeric codes define the activity that timed out This is a diagnostic message that only needs to be considered if there are messages indicating that something has failed 15 STATE CONFL
253. x 0 Based Each point index number 0 to 65535 Incremented must be unique from 0 IED System Point Identifier Consists of Home N A System Directory and Point Name Based on selected DI Assigned point from the Point Picker Read only Identifier Point Name Text description of the point in the Binary Input Up to 128 Assigned IED map Based on selected DI point Read only characters point name Invert Select if the value of the mapped points should True or False False be inverted D400 Substation Data Manager Software Configuration Guide 111 GE Energy Setting Description Range Default Static Variation How the point values should be reported 32 Bit User selected 16 Bit Default 32 Bit w o flag 16 Bit w o flag 32 Bit Float Event Variation Indicates how an event on this point should be reported 32 Bit with Time 32 Bit without Time 16 Bit with Time 16 Bit without Time 32 Bit Float with Time 32 Bit Float without Time User selected Default Class Default Class for change events on the point None 3 2 1 User selected Default Settings are available in the lower pane of the Digital Inputs tab The configuration settings defined in Table 98 are used to configure the default values for all digital input points defined in the DNP3 server map Table 98 Digital Input Properties Setting Description Range Default Default Class All DI events belong to th
254. y Enable or disable redundancy functionality within the D400 Configure Heartbeat Timeout The interval within which the D400 must receive at least one message or heartbeat from the other D400 Valid ranger is 100 to 1000 ms default is 300 ms Configure Heartbeat Retries The number of times the D400 re transmits a heartbeat message before assuming that the other D400 has failed Valid range is 1 to 300 default is 3 184 swmo066 2 75 0 General GE Energy Configure IP Address of Peer D400 Set the unique IP address of the other D400 device configured within the redundant system If the peer D400 has a second Ethernet interface you can configure it as well Username of Peer D400 Enter the username of the root level user account on the peer D400 unit This username must be administrator when using remote authentication mode Generally this setting is the same on both D400 units This setting is used in conjunction with the authentication mechanism defined in appendix B 3 Ethernet Connections 8 4 PPP Dial In The D400 supports a PPP dial in connection from a host computer using a Telnet or Secure Shell terminal session To establish a PPP connection the D400 must have a COM2 adapter card installed and configured for DTE communications The PPP Dial In connection is configured at the D400 command prompt Note This configuration command involves first editing the configuration file in the D400 RAM disk and then copying the ch
255. y using the Enable Disable IED button in the IED Communication Summary of the D400 HMI is not synchronized Both application configurations for example DNP server mappings LogicLinx programs etc and system configurations for example time sync inputs user logins and passwords etc are synchronized The only parameters that are not synchronized are IP addresses as they must be independently configured for each unit see B 3 Ethernet Connections No other data is synchronized between the two D400s including system point values software licenses or firmware images While configuration transfer is in process the standby unit will not accept any commands from the active unit The active unit will indicate via the Config Sync in Progress digital input when configuration synchronization is occurring When synchronization is complete the software on the standby unit will reset in order to D400 Substation Data Manager Software Configuration Guide 199 GE Energy implement all the changes this is only a software restart not a reboot of the entire device During the reset the active unit may briefly indicate that the standby unit has failed If the standby unit remains in failed mode or if the Standby Config Out of Sync digital input does not turn off after the standby unit completes the restart then the configuration synchronization has likely failed Check the system and diagnostic logs in both the active and standby units for detai
256. ype the number and press Enter 172 SWM0066 2 75 0 General GE Energy Configure Authentication From the Authentication menu you can select the authentication mode and change the system access settings Ee lolx al Current AuthMode Status CSACS TACACS Local Authentication mode Remote Authentication mode Root Administrator Settings HMI Supervisor Settings Pass Through Authentication Adminstrator Group Users Back JANB WN be Enter Your Choice Between 1 and 7 Local Authentication Mode Local authentication makes use of files stored locally to control user authentication as opposed to connecting to a remote server to obtain user name and password information The D400 has two types of administrative users e Root Full privileges to view and modify all system settings in the D400 and run commands through the local D400 command line interface The root user cannot log into remote command line services or the D400 HMI Default user name is root and the default password is geroot Only the password can be modified see Root Administrator Settings on p 174 e Administrator Supervisor level access to all configuration runtime operation and system administration screens in the Online D400 HMI as well as full access to run commands at the D400 command line interface when the sudo command is used see section 8 2 Setting up a Terminal Session If you are using local authentication Administrator leve
257. ze set to 2 the user defined text used to Any text Empty represent a 2 state feedback value of 0 State 1 Text f Size set to 2 the user defined text used to Any text Empty represent a 2 state feedback value of 0 State 00 Text f Size set to 4 the user defined text used to Any text Empty represent a 4 state feedback value of 00 State 01 Text f Size set to 4 the user defined text used to Any text Empty represent a 4 state feedback value of 01 State 10 Text f Size set to 4 the user defined text used to Any text Empty represent a 4 state feedback value of 10 State 11 Text f Size set to 4 the user defined text used to Any text Empty represent a 4 state feedback value of 11 D400 Substation Data Manager Software Configuration Guide 151 GE Energy Table 136 Ellipse Object Settings Setting Description Range Default x X horizontal pixel position from the top left corner O to the Draw Panel 0 of the screen to the top left corner of the area used width less the to display the object object width Y Y vertical pixel position from the top left corner of O to the Draw Panel 0 the screen to the top left corner of the area used to height less the display the object object height Height Pixel height of the rectangular area used to display 1 to the Draw Panel 40 the object height Width Pixel width of the rectangular area used to display 1 to the Draw Panel 40 the obje