FX3U-4AD-PNK-ADP USER`S MANUAL
Contents
1. Applicable standards FX3U 4AD PNK ADP units made in December 2007 or later comply with the EC Directive EMC Directive and UL standards UL cUL Further information can be found in the following manual FX3S Series Hardware Manual Manual No JY997D48301 FX3G Series Hardware Manual Manual No JY997D46001 FX3GC Series Hardware Manual Manual No JY997D45201 FX3U Series Hardware Manual Manual No JY997D18801 FX3uc D DS DSS Series Hardware Manual Manual No JY997D28601 FX3UC 32MT LT 2 Hardware Manual Manual No JY997D31601 Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Attention e This product is designed for use in industrial applications Note e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany Caution for EC Directive The FX3U 4AD PNK ADP have been found to be compliant to the European standards in the aforesaid manual and directive However for the very best per formance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered care fully For users of proprietary cables integral with sensors or actuators these users should follow those manufacture
2. 670 Input charac teristics e The photocoupler is adopted to insulate the analog input area lati from the PLC PU AON e The DC DC converter is adopted to insulate the power supply method line from the analog input area e Channels are not insulated from each other Occupied 0 point This number is not related to the maximum number of points input output points of the PLC This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This pr
3. to the PLC FX3U Series PLC is used for the following example For installation method to other PLCs refer to the respective PLC User s manual Hardware Edition Procedure 1 Turn off the power Disconnect all the cables connected to the PLC main unit and special adapter and demount the main unit and special adapter mounted on DIN rail or mounted directly using screws 2 Install an expansion board to the main unit For the expansion board installation procedure refer to the following manual FX3U Series User s Manual Hardware Edition 3 Remove the special adapter connector cover on the expansion board fig A When connecting this product to another special adapter please replace the expansion board in the above description with a special adapter and perform the procedure as indicated 4 Slide the special adapter slide lock fig B of the main unit When connecting this product to another special adapter please replace the main unit in the above description with a special adapter and perform the procedure as indicated Please replace the following procedures similarly Connect the special adapter fig C to the main unit as shown on the right 6 Slide back the special adapter slide lock fig B of the main unit to fix the special adapter fig C 5 Connection precautions Connect all the high speed I O special adapters before connecting other spe cial adapters when they a
4. 500 V DC unit megger 4 3 Power Supply Specifications Insulation resistance Item Specification A D conversion 24 V DC 20 15 50 mA for 24 V DC circuit driving power Connect a 24 V DC power supply to the terminal block 5 V DC 15 mA 5 V DC power is supplied from the internal power supply of main unit Interface driving power 4 4 Performance Specifications Description Item Centigrade C Fahrenheit F Platinum resistance thermometer sensor 2 wire or 3 wire Pt1000 Inp t siqnal JIS C 1604 1997 p g Nickel resistance thermometer sensor 2 wire or 3 wire Ni1000 DIN 43760 1987 Rated Pt1000 50 C to 250 C Pt1000 58 F to 482 F ee range Ni1000 40 C to 110 C Ni1000 40 F to 230 F 580 to 4820 400 to 2300 Pt1000 500 to 2500 Pt1000 Digital output Ni1000 400 to 1100 Ni1000 Pt1000 Pt1000 Resolution 0 1 C 0 2 F Ni1000 Ni1000 Total 0 5 for full scale when ambient temperature is 25 C 5 C 1 0 for full scale ae ambient temperature is in the range of 0 accuracy 6 to 55 C e FX3U FX3UC Series PLC 200 us ee The data will be updated at every scan time of the PLC time e FX3S FX3G FX3GC Series PLC 250 us The data will be updated at every scan time of the PLC Description Item z Centigrade C Fahrenheit F Pt1000 Pt1000 4928 z a 4820 gt i BEL IION 18S m TA T Stat 482 F Zo 4 580 Ho
5. 97D16701 MODEL CODE 09R619 Describes specifications for analog control and programming method for FX3S FX3G FX3GC FX3U FX3UC Series PLC FX3S FX3G FX3GC FX3U FX3UC Series User s Manual Analog Control Edition FX3S FX3G F X3GC FX3U FX3UC Series Programming Manual Basic amp Applied Instruction Edition FX3S Series User s Manual Hardware Edition JY997D16601 MODEL CODE 09R517 Describes PLC programming for basic applied instructions and devices JY997D48601 MODEL CODE 09R535 Explains FX3S Series PLC specifications for I O wiring installation and maintenance FX3G Series User s Manual Hardware Edition JY997D31301 MODEL CODE 09R521 Explains FX3G Series PLC specifications for I O wiring installation and maintenance FX3GC Series User s Manual Hardware Edition JY997D45401 MODEL CODE 09R533 JY997D16501 MODEL CODE 09R516 JY997D28701 MODEL CODE 09R519 Explains FX3GC Series PLC specifications for I O wiring installation and maintenance Explains FX3U Series PLC specifications for I O wiring installation and maintenance FX3U Series User s Manual Hardware Edition FX3UC Series User s Manual Hardware Edition Explains FX3UC Series PLC specifications for I O wiring installation and maintenance How to obtain manuals For product manuals or documents consult with the Mitsubishi Electric dealer from who you purchased your product
6. JY997D29201F MITSUBISHI ELECTRIC PROGRAMMABLE CONTROLLERS MELSEC F FX3U 4AD PNK ADP USER S MANUAL Manual Number JY997D29201 F X 3U This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective April 2015 Specifications are subject to change without notice 2007 Mitsubishi Electric Corporation Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories and A CAUTION Indicates that incorrect handling may cause hazardous Z WARNING conditions resulting in death or severe injury Indicates that incorrect handling may cause hazardous conditions resulting in medium or slight personal injury or physical damage Depending on the circumstances procedures indicated by A CAUTION may also cause severe injury It is important to follow all precautions for personal safety Associated Manuals Manual name Description JY9
7. dapters to the left side of the PNK ADP 4 T 5 6 7 8 2 Installation For installation uninstallation details refer to the respective PLC User s manual Hardware Edition INSTALLATION PRECAUTIONS WARNING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product INSTALLATION PRECAUTIONS CAUTION e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur INSTALLATION PRECAUTIONS CAUTION When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not touch the conductive parts of the product directly Doing so may cause device failures or malfunctions Connect special adapter securely to their designated connectors Loose connections may cause malfunctions 2 1 Connection to the PLC This section describes the connection method
8. einafter called PNK ADP is an analog special adapter for measuring temperature via four channels 2 wire or 3 wire sensors of a connected Pt1000 Ni1000 resistance thermometer 1 1 Incorporated Items Verify that the following product and items are included in the package FX3U 4AD PNK ADP Pt1000 Ni1000 temperature sensor input Product special adapter Accessories User s manual This manual 1 2 External Dimensions Part Names and Terminal Layout 10 98 3 86 mounting hole pitch Special adapter connector cover is removed Weight Approx 0 1 kg 0 22 Ibs 1 DIN rail mounting groove DIN rail DIN46277 2 Name plate 3 Special adapter slide lock Used to connect additional special adapters onto the left side of this special adapter Special adapter connector cover Remove this cover to connect additional special adapters to the left side Direct mounting hole 2 holes of 64 5 0 18 mounting screw M4 screw Not used when connecting to FX3GC FX3UC Series PLC POWER LED green Lit while 24 V DC power is supplied properly to terminals 24 and 24 Terminal block European type Connect Pt1000 sensor Ni1000 sensor and 24 V DC power supply Special adapter connector Used to connect this special adapter to PLC main unit or special adapter 9 DIN rail mounting hook 10 Special adapter fixing hook 11 Special adapter connector Used to connect communication or analog special a
9. ingle wire before connecting it An alternative connection is to use a ferrule with insulating sleeve lt Reference gt Phoenix Contact Co Ltd Al 0 5 8WH Old model name CRIMPFOX ZA 3 2 Old model name CRIMPFOX UD 6 Strand wire single wire 0 35 Caulking tool CRIMPFOX 6 or CRIMPFOX 6T F 2 Stick terminal with insulating sleeve Insulation sleeve Contact area Crimp area 8mm 2 6mm 0 1 When using a stick terminal with insulating sleeve choose a wire with proper cable sheath referring to the above outside dimensions or otherwise the wire cannot be inserted easily The tightening torque must be 0 22 to 0 25 Nem Do not tighten terminal screws exceeding the specified torque Failure to do so may cause equipment failures or malfunctions 3 2 Power Supply Wiring For the power supply wiring refer to the following manual FX3S FX3G FX3GC FX3U FX3UC Series User s Manual Analog Control Edition 3 3 Selection of resistance thermometer sensors For the terminal layout refer to Section 1 2 Precautions on resistance thermometer wiring e When using a 2 wire temperature sensor type short circuit the L terminal and the I terminal For the lead wire use a 10 Q resistance or less per line e Separate the cable of the resistance thermometer sensors from the other power cables or areas easily affected by inductive noise of the commercial power etc Example of resistance thermome
10. lfunctions For repair contact your local Mitsubishi Electric representative Do not drop the product or exert strong impact to it Doing so may cause damage DISPOSAL PRECAUTIONS CAUTION e Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device TRANSPORTATION AND STORAGE PRECAUTIONS CAUTION e The product is a precision instrument During transportation avoid any impacts Failure to do so may cause failures in the product After transportation verify the operations of the product 4 1 Applicable PLC Model name FX3S Series PLC FX3G Series PLC FX3GC Series PLC FX3U Series PLC Applicability Ver 1 00 or later from first production Ver 1 00 or later from first production Ver 1 40 or later from first production Ver 2 20 or later from first production Ver 1 30 or later from the production manufactured in FXSUC Series PLC August 2004 with SER No 48 The version number can be checked by monitoring D8001 D8101 as the last three digits indicate it 4 2 General Specifications Items other than the following are equivalent to the those of the PLC main unit For general specifications refer to the respective PLC User s manual Hardware Edition Item Dielectric withstand Specification voltage Between all terminals and 500 V AC for one minute ground terminal of PLC main 5 MQ or more by
11. oduct has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN
12. re used in combination Do not connect a high speed I O special adapter on the left side of an special adapters other than other high speed I O special adapters 3 Wiring WIRING PRECAUTIONS WARNING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product WIRING PRECAUTIONS CAUTION e When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions WIRING PRECAUTIONS CAUTION e Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due to abnormal data written to the PLC under the influence of noise 1 Do not bundle the power line or shield of the analog input output cable together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take place As a guideline lay the control line at least 100mm 3 94 or more away from the main circuit high voltage line or load line 2 Ground the shield of the analog input output cable at one point on the signal receiving side However do not use common grounding with heavy electrical systems Make sure to properly wire to the terminal block European type in accordance with the following precaution
13. rs installation requirements Mitsubishi Electric recommend that shielded cables should be used If NO other EMC protection is provided then users may experience temporary loss or accuracy between 10 in very heavy industrial areas However Mitsubishi Electric suggest that if adequate EMC precautions are fol lowed for the users complete control system users should expect accuracy as specified in this manual e Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling Where possible users should run analog cables separately e Good cable shielding should be used When terminating the shield at Earth ensure that no earth loops are accidentally created e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the analog special adapters or through a users program e Attach the ferrite core input cable of each channel about FX3U 4AD PNk ADP as follows For the 3 wire sensor Temperature Ferrite core PNK ADP sensor Shield wire For the 2 wire sensor Temperature Ferrite core PNK ADP sensor Shield wire 1 Use the ferrite core which has the impedance characteristic of 150 Q or more in 100 MHz to 500 MHz range 2 Wrap the cable by 2 turns 3 Attach the ferrite core in approximately 200 mm 0 78 or less from terminal block on the PNK ADP side 1 Outline FX3U 4AD PNK ADP her
14. s Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the end of strand wire and make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed Make sure to properly wire the terminal block in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual of the PLC main unit Tightening torque should follow the specifications in the manual of the PLC main unit 3 1 Applicable cable and terminal tightening torque 3 1 1 Terminal block European type 1 Wire size The power supply wire should use 22 20 AWG wire 2 Applicable cable Type Wire size Single wire 0 3 mm to 0 5 mm2 AWG22 to 20 2 wire 2 pieces of 0 3 mm2 AWG22 3 Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of s
15. ter wiring Resistance thermometer PNK ADP wiring gt 45V 3 wire sensors Terminal 47kQ l l 47kQ type Shield wire block 1MQ ch to S IMQ 5V AAR 47kQ 47kQ type ch is Aa 24V DC Class D grounding LO LO IL ch represents the channel number 24 V DC service power supply of the FX3S FX3G FX3U Series PLC can also be used 2 When using a 2 wire temperature sensor type short circuit the LO terminal and the IL terminal 3 4 Grounding Grounding should be performed as stated below e The grounding resistance should be 100 Q or less e Independent grounding should be performed for best results When independent grounding is not performed perform shared grounding of the following figure For details refer to the respective PLC User s manual Hardware Edition Other Other Other oe equipment equipment equipment Shared grounding Common grounding Good condition Not allowed Independent grounding Best condition e The grounding wire size should be AWG 22 20 0 3 0 5 mm_ e The grounding point should be close to the PLC and all grounding wire should be as short as possible 4 Specifications STARTUP AND MAINTENANCE PRECAUTIONS CAUTION Do not disassemble or modify the PLC Doing so may cause fire equipment failures or ma