Home
XFP 1 LOOP 16 ZONE ENGINEERING MANAL - C-Tec
Contents
1. LOCATION NUMBERS 0 1 2 3 4 5 6 7 For an explanation of the numbers XX XX XX XX XX XX XX XX displayed refer to the relevant XX XX XX XX XX XX XX XX Apollo device documentation 8 9 10 11 12 13 14 15 SHOW NETWORKED EVENTS This function allows the status of a network event to be displayed which is useful for fault diagnosis purposes When accepted a window similar to the following will appear ei i ib PT fF iF iF FF I T wy le lf T Event True F Event False XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 33 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL MAINTENANCE Periodic system maintenance should be carried out on the system as prescribed in the local design maintenance and installation regulations The Fire Alarm panel s standby batteries should be checked for integrity of the connections deposits indicating venting and a periodic load test with the Mains supply disabled to ensure adequate battery capacity Both batteries should be renewed if there is any doubt about their integrity The memory log should be checked for any faults that have automatically cleared and these dealt with accordingly XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 34 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL STANDBY BATTERY CALCULATION GUIDE The standby time of the fire alarm panel after the Mains has
2. REPEATER REPEATER XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 13 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL CONTROLS AND INDICATORS Front panel layout Fire Alarm Control Panel Instructions To view more events use the scroll dh W buttons To silence the internal sounder press B To silence resound the alarm sounders Fire A more information Fire Zones Turn key to and press OR press and gt Enter code and press To reset the panel Ensure all alarm conditions are silenced and investigations are complete and press To exit access mode Remove key OR press and hold flashing light call engineer LED Indicators Liquid Crystal Display General Fire Fire Zones 1 16 Supply Present Test Accessed General Disablement Phased Evacuation General Fault Power Supply Fault System Fault Sounder Status Delays Running 4 5 escape silence internal sounder menu supply presse general disablement phased test accessed evacuation silence resound control panel reset sounders power system supply fault fault sounder status CENA running general investigate fault Provides detailed information on the status of the system the type of messages displayed and what they mean is covered in greater detail in the
3. DISPLAY ALARM COUNTER N ENTER ACCESS LEVEL3 B Clear to todays date O DISPLAY FIRE EVENTS DISPLAY FAULT EVENTS PRINT OPTION lt PRINT EVENT HISTORY PRINT OPTION DISPLAY DISABLEMENTS DISPLAY EVENT HISTORY IN Ulsan RESET EVENT HISTORY LAMPS TEST DISPLAY ALARM COUNTER ENABLE DISABLE ZONES SET TIME DATE ENABLE DISABLE SOUNDERS 0 SE SET CLEAR DISABLEMENTS B gt SE GRE DE CS LEVEL 2 GODE ENABLE DISABLE FAULT RELAY ENABLE DISABLE OUTPUT DELAYS CODE ENTRY CHANGE ACCESS LEVEL 2 CODE AIRE ENE CHANGE ACCESS LEVEL 3 CODE DISPLAY FAULT EVENTS ST DISABLEMENTS SETUP PASSWORDS SET PANEL NUMBER CONNECT TO PC SET PANEL FITTED NETWORK FUNCTIONS COMMISSIONING FUNCTIONS LOOP LEARN ENGINEER FUNCTIONS p gt FIND NEW DEVICES SHOW FITTED DEVICES ASSIGN ZONE GROUP CALIBRATE DEVICES COMMISSION THE LOOP S SHOW CALIBRATION PROBLEMS SHOW DUPLICATE ADDRESSES SET DAY NIGHT TIMES ENABLE DISABLE DST ADJUSTMENT CONFIGURE SOUNDER DISABLEMENTS MAKE A CLEAN START SET CLEAR DISABLEMENTS B gt ENABLE DISABLE ZONES MONITOR A POINT ENABLE DISABLE SOUNDERS TEST DEVICE OUTPUTS ENABLE DISABLE OUTPUTS TEST OUTPUTS SETS ENABLE DISABLE RELAYS TEST SOUNDER GROUPS ENABLE DISABLE DEVICES TEST PANEL RELAYS ENABLE DISABLE FAULT RELAY WALK TEST ENABLE DISABLE
4. SET DAY NIGHT TIMES This function allows the user to alter the time the panel enters day building occupied and night building unoccupied mode WE RECOMMEND YOU DO NOT USE THIS FUNCTION UNLESS YOU ARE INTIMATELY FAMILIAR WITH THE OPERATION OF THE FIRE ALARM SYSTEM Changes that may take place when the panel is in day night mode include detector sensitivities how quick a detector reacts in the event of a fire cause and effects what happens in the event of a fire and sounder volumes if available These changes can only be made by an authorised engineer using the panel s sophisticated programming tools at access level 3 If in doubt refer to page 20 where any day night changes will be recorded provided it has been completed by the system engineer When the SET DAY NIGHT TIMES prompt appears press the Accept gt button and the following win dow or similar will appear Day Occupied mode begins 06 00 Use the and buttons to set the time in hours that you want the panel to enter day mode the panel has a 24 hour clock so hours 0 to 23 are available When the correct hour is displayed press the Accept gt button to move to the minutes field Use the and buttons to set the time in minutes you want the panel to enter day mode When the desired time is displayed press the Accept button to access the night mode entry field A window similar to the one below will appear Day Occupied mode begins Nig
5. the desired option The window will now move to the next device allowing further enablements or disablements to be made Alternatively to return to the previous menu press the Escape 4 button Please note if all the input devices on a zone are individually disabled the zone they belong to will also be disabled If you try to re enable a zone which has no enabled devices on it using the ENABLE DISABLE ZONES function described on page 25 a prompt appears saying this cannot be done Instead you must first enable at least one device on the zone before re enabling the zone itself ENABLE DISABLE FAULT RELAY This function can be used to suppress the panel s fault relay from activating in a fault condition When selected press the Accept 7 button and the following window will appear Fault relay is Enabled Use the and buttons to toggle between enabled and disabled and press the Accept button to select the desired option Alternatively to return to the previous menu press the Escape 4 button XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 26 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL ENABLE DISABLE OUTPUT DELAYS This function can be used to globally disable or enable any delays to outputs that have been programmed into the panel When selected press the Accept 7 button and the following window will appear Delays to Outputs are Enabled
6. 2323 aves 131 11 11 1 1111 1 1111 18 Fitting the panel s NVM memory unlock link 02202222 18 A detailed description of the functions available at access level 2220 19 33 820 34 Standby battery calculation 2 35 3 3 3 1111 36 Disclaimer No responsibility can be accepted by the manufacturer or distributors of this range of fire panels for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole The manufacturer s policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice E amp OE
7. OUTPUT DELAYS BLINK DETECTORS LEDS INTENSIVE DEVICE MONITOR LOOP TEST DISPLAY DATABASE VERSION NUMBERS SHOW PSU STATS ENABLE DISABLE EARTH FAULT SHOW LOOP CURRENT SHOW DISCOVERY EEPROM SHOW NETWORKED EVENTS XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 17 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL How to enter access level three Access level 3 can be entered in one of two ways 1 By pressing the Menu button on the panel s front scrolling down to ENTER ACCESS LEVEL 3 and pressing the Accept gt button When you have done this the following prompt will appear Enter Access Level 3 code Enter the four digit access level 3 code using the lt 1 2 w 3 4 4 buttons as appropriate The default code is 4 4 4 4 four presses of the 4 button If this does not work the code may have been changed As soon as the code has been entered correctly you will be taken into access level 3 see pages 19 to 33 2 By entering access level 2 as detailed in the panel s separate user manual scrolling down to ENTER ACCESS LEVEL 3 and repeating the process described above In access level 3 the panel s Silence Resound Sounders Control Panel Reset and Investigate buttons become active and you can Scroll through any fire pre alarm or fault conditions which are displayed on the panel s LCD View any disablements or zones that
8. REMOVING THIS CIRCUIT INCORRECT TYPE OF BATTERIES FITTED BOARD EXPOSES HAZARDOUS ELECTRICITY OBSERVE DISPOSE OF USED BATTERIES ACCORDING VOLTAGES PLEASE REFER TO PRECAUTIONS BEFORE TO THE MANUFACTURERS INSTRUCTIONS INSTALLATION INSTRUCTIONS HANDLING CONSULT THE MAINTENANCE Ls ran PSU PCB connector cable connects to rear Of Main Control PCB and PL1 on PSU PCB XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 9 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Conventional sounder circuit wiring Two conventional sounder circuits are provided These can accommodate up to 40 conventional polarised sounders at 20mA or 32 bells at 25mA per system If a full complement of sounders or bells are to be used split them equally across both circuits A 6k8 end of line resistor provided must be connected at the end of each sounder circuit to allow the wiring to be monitored If the sounder circuit is unused you must still connect the 6k8 resistor at the panel Remember to isolate the panel s Mains and battery backup supplies before making any connections Each sounder circuit should be connected to the terminal marked Sounder Circuits on the Main Control PCB as shown in Fig 6 below and its earth screens terminated at the panel s base earth post Fig 6 Typical conventional sounder circuit connection and detail Conventiona
9. This product has been manufactured in conformance with the requirements of all applicable EU Council Directives XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 2 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL IMPORTANT NOTES This equipment must only be installed and maintained by a suitably skilled and technically competent person This equipment is a piece of Class 1 equipment and MUST BE EARTHED ALWAYS isolate the panel s Mains and battery backup supplies before making connections to its PCBs Items supplied with this panel e Engineering manual this manual e User Manual Log Book e Torx key for unfastening securing the panel lid e Electrical accessory pack containing 2 x 6K8 0 25W conventional sounder circuit resistors 1 x 20mm 1ATH 250V HRC ceramic fuse spare primary fuse 1 x set of battery connection leads red wire black wire jumper link and 2 x nylon cable ties System design Fire alarm system design is beyond the scope of this document A basic understanding of general fire alarm system components and their use is assumed Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements We strongly recommend that a suitably qualified and competent person is consulted in connection with the design of the fire alarm system and that the system is commissioned and serviced in accordance with the laid down specificati
10. Yes On board loop isolators with LED indication when active Yes Auto polling from each loop end Yes Max output current per loop 500mA Voltage 25 V minimum 34 V maximum Max number of addressable devices 126 Max number of loop powered sounders per loop 10mA 40 Number of programmable sounder groups 16 Number of programmable output sets 16 CONVENTIONAL SOUNDER CIRCUIT SPECIFICATION Number of programmable circuits 2 End of line resistor value 6800 ohm 5 Tol 0 25 W Line monitored for open and short circuit faults Yes Outputs fused at 400mA Protected by resettable overload circuit Output voltage 19 5 V minimum 28 V maximum Max number of sounders 20mA 40 AUXILIARY OUTPUTS Type Relay voltage free single pole changeover Max switching current 1A Max switching voltage 30 V d c Relay 1 Relay 2 Relay 3 Programmed from cause and effect Fault Active when no faults are present 24V Aux power output 19 5 V minimum 28 V maximum Max current 100mA Protected by resettable overload circuit AUXILIARY INPUTS Input 1 Input 2 Connect to OV to trigger Max input voltage 27V d c non latching Programmed from cause amp effect Connect to OV to trigger Max input voltage 27V d c non latching Programmed from cause amp effect FUSES to IEC EN60127 Pt2 Mains fuse 1A HRC Ceramic 20mm Battery fuse 1 6A F 20mm This limits the current drawn from the battery PANEL INDICATO
11. button to reject it If the Escape 4 button is pressed the panel will continue searching until the next new device is found If the Accept 7 button is pressed you will be given the opportunity to assign the device to a detector zone or a sounder group as appropriate For example Shop floor No name allocated Belongs to Zone 1 Use the and buttons to scroll to the desired zone or group and press the Accept 7 button The device search will now continue until the next new device is found Note that I O units etc can only be assigned to output sets via the panel s programming tools Therefore when accepted the panel will continue its search for new devices straightaway When the new device search is complete a brief summary window will appear similar to the one below 0 changed 0 removed 112 total devices Auto learn completed Press the Escape 4 button to return to the Commissioning Functions submenu SHOW FITTED DEVICES This function will list all of the addressable devices stored in the panel s memory It DOES NOT give a list of what is on the loop at the exact time the function is selected i e unlearnt devices will not show but faulty missing devices will When the SHOW FITTED DEVICES prompt appears press the Accept 7 button and you will be asked to select which loop s devices you want to view On loop 1 Use the and buttons to scroll to the desired loop s and press the Accept
12. button to make these changes When testing is complete press the Escape 4 button to return to the Engineer Functions submenu The device will no longer be live and its output bits will return to their normal settings TEST OUTPUT SETS This function allows you to test one or all of the system s output sets 1 to 16 by altering its their state from Normal to Triggered When the TEST OUTPUT SETS prompt appears press the Accept gt button and the output set selection window will appear Output set 1 Use the and buttons to select the output set you would like to test all or 1 to 16 Press the Accept gt button and the following window will appear Output set 1 is Normal Change the state using the Accept button Press the Accept gt button and the output set you have selected will activate To change the state back to normal press the Accept button again Should you wish to test additional output sets use the a and buttons to change the output set s number accordingly To return to the main Engineer Functions submenu press the Escape 4 button TEST SOUNDER GROUPS This function allows you to test one or all of the system s sounder groups 1 to 16 by altering its their state between Silenced Intermittent and Continuous When the TEST SOUNDER GROUP prompt appears press the Accept button and the sounder group selection window will appear Sounder group 1 Use the and buttons t
13. buttons Press the Accept button and the zone s status Enabled or Disabled will flash Next use the and but Zone 1 Shop Floor tons to toggle between enabled and disabled and press the Enabled Accept gt button to select the desired option The window will now move to the next available zone allowing further enablements or disablements to be made Alternatively to return to the previous menu press the Escape 4 button Please note if all the input devices on a zone have been individually disabled using the ENABLE DISABLE DEVICES function described on page 26 the zone they belong to will also be disabled If you try to re enable a zone which has no enabled devices on it a prompt appears saying this cannot be done Instead you must first enable at least one device on the zone using the ENABLE DISABLE DEVICES function before re enabling the zone itself ENABLE DISABLE SOUNDERS This function allows you to disable one or more sounder groups from sounding in a fire condition When selected press the Accept 7 button and a window similar to the one below will appear Select the sounder group 1 to 16 or ALL to be Sounder Group All disabled enabled using the and buttons When the desired sounder group has been selected press the Accept gt button once and the sounder group s status Enabled or Disabled will flash Next use the and buttons to toggle between enabled and disabled and press the Accept 7 button to
14. loop you wish to monitor and how many times you want the panel to poll each device 1 to 255 Loop 1 Number of polls for each device 25 Use the and Accept gt keys to select the desired loop followed by the number of polls required The test will begin and a test status window will appear showing the address currently being polled together with a running total of the number of good and bad polls Polling takes place on an address by address basis in numerical order and will take several minutes Loop 1 Device 1 Results Good polls 25 Bad Polls 0 When the test is complete the results will appear in a new window similar to the one below Loop 1 Device 1 Results Good Polls 128 Bad Polls 3 Pressing the Escape 4 button will abort the test at the address currently being polled A number of bad polls in a particular section of the system indicates a problem area for investigation e g voltage drop bad connection etc To assert output channels 1 and 3 of the device being viewed press the More Information button You will be presented with a window similar to the one below Loop 1 Device 1 Turn ON output channels 1 amp 3 In the case of detectors and manual call points activating channels 1 and 3 will turn their LEDs on Caution note that channels 1 and 3 on an I O unit may be programmed to trigger say a water extinguishant system so this function must be used with care
15. panel s separate user manual Flashes red when there is a fire condition on any zone and goes steady red when the alarm is silenced Subsequent fire conditions will restart the General Fire indicator flashing until it is silenced again One or more of these indicators will flash red in an alarm condition and will go steady when silenced Normally lit green to show that all of the panel s power supplies are functioning correctly Lit yellow when the panel is in walk test mode This LED does NOT illuminate for any other test condition Lit yellow when the panel is in access levels 2 or 3 Lit yellow when one or more zone sounder output or relay is disabled Flashes yellow when there is a phased evacuation in process Flashes yellow when there is an fault condition on the panel Will always be lit in conjunction with at least one other fault LED Lit yellow when the panel s power supply or Mains has failed or the panel s standby battery is in poor condition Lit amber when a system error such as a microprocessor fault occurs Remains lit even if the panel automatically clears the fault Flashes yellow when a fault is detected on either of the panel s two conventional sounder circuits or if there is a sounder disablement anywhere on the system Lit yellow when one or more output delay has been programmed into the panel Flashes yellow when one or more output delay is running XFP ENGINEERING MANUAL Approved Document No
16. provided Note that the analogue loop and conventional sounder circuit cabling is classed as low voltage and must be segregated away from Mains voltages i Careful planning is needed to ensure this see Fig 2 above for guidance 7 We recommend tails of at least 20 30cm are left inside the panel to ensure straightforward connection of the field wiring to the panel s terminals lt A Drill centre points are provided in the panel base to aid drilling tools Cut out suitable holes in the panel using a hole saw directed by a pilot bit in the centre of the hole saw see right Always ensure that if a hole is cut out it is filled with a good quality cable gland Any unused holes must be securely blanked off Mains wiring The requirement for the Mains supply to the fire panel is fixed wiring using three core cable no less than 1mm and no more than 2 5mm or a suitable three conductor system fed from an isolating switched fused spur fused at 3A This should be secure from unauthorised operation and be marked FIRE ALARM DO NOT SWITCH OFF The Mains supply must be exclusive to the fire panel As an alternative to a switched fused spur a double pole isolating device may be used providing it meets the appropriate national wiring regulations see diagram below 1 0mm lt 2 5mm 3A A MAIN FIRE DISTRIBUTION y PANEL BOARD O XFP ENGINEERING MANUAL Appr
17. required Example 2 The panel has 100 devices each consuming 250pA each 40 sounders at 20mA each connected to the panel sounder circuits the required standby time is 24 Hours and the required alarm time is 0 5 hours Z 100 x 0 00025 0 025A P 0 042A A 40 x 0 02 0 8A H 24 T 0 5 Standby Time in Ah 1 25 x 0 5 x 0 8 24 x 0 025 0 042 2 51Ah Therefore batteries with at least 2 51Ah capacity are required XFP ENGINEERING MANUAL e Approved Document No DFU1200510 Rev 1 Page 35 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL TECHNICAL SPECIFICATION POWER SUPPLY SPECIFICATION Mains supply 230V a c 50 60Hz Max current 350mA Internal Power Suppl 27 V d c Nominal Total output current limited to 1 4A 230 V a c Power rating Imax a 210mA Imin 40 mA Maximum internal battery resistance Ri max 1 10 Supply and battery charger monitored for failure Yes Batteries monitored for disconnection and failure Yes Batteries protected against deep discharge Yes Max battery size and type 3 2Ah VRLA Use 2 x YUASA NP3 2 12 for LPCB approved systems Quiescent current drain 1 loop unloaded lt 50mA Earth fault monitoring Yes any conductor Temperature compensated charging Yes LOOP DRIVER SPECIFICATION Number of loop drivers 1 Line monitored for open and short circuit faults
18. required the panel can be configured to sit on network of up to eight interconnected XFP master panels or it can have up to eight XFP repeaters connected to it If you wish to utilise either of these options the panel will require a separately available Network Communication Card Part No CFP761 XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 4 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL INSTALLATION AND WIRING The fire panel enclosure The panel is supplied with a plastic detachable lid a plastic back box a Main Control PCB and a Power Supply PCB Space is available inside the panel for the rated capacity of VRLA backup batteries and an optional Network Communication Card The panel must be sited indoors in an area that is not subject to conditions that are likely to affect its performance e g damp salt air water ingress extremes of temperature physical abuse near sources of electromagnetic interference such as high current machines welding equipment radio transmitters etc See Page 36 for more details It should be sited at a height where it is easily accessible and in a prominent position within the building Ideally its front panel indicators should be at eye level Typical locations for the panel are in the entrance foyer hallway at ground floor level the first and most obvious point of contact for emergency services or a permanently manned security office It is recom
19. you want to program an existing system as if it were a new system press the Accept 7 button The following message will appear Are you sure you want to erase the Database Press the Accept 7 button again and the panel will erase its database update its flash memory and start to learn the loop s as appropriate Note that by default the loop learn will assign all detectors manual call points to zone 1 and all sounders bea cons to group 1 This is to ensure that all of the system s sounders will activate in the event of a fire condition anywhere in the building i e one out all out These default settings can be modified as appropriate using the panel s PC programming software tools at a later date Note that no default sets are assigned to the outputs of VO units these must be assigned using the panel s PC programming software tools Option 2 If you DO NOT wish to erase the loop device data press the Escape 4 button and the panel will immediately start to learn the loop without overwriting data such as zone and group allocation detector sensitivities device names etc which will remain as it was before the Loop Learn The only data that will be overwritten is device type and whether or not it is fitted See note above about default loop learn settings Depending on the size of the installation the loop learn process can take several minutes When the auto learn process is complete a brief summary window will appear s
20. 7 button A window similar to the one below will appear L 1D 1 SMCCOOIC I 10 L 1D 11 C TT MMC 20 Devices are displayed in groups of 10 In the example above the top line shows the type of devices fitted at addresses 1 to 10 on loop 1 and the second line shows the type of devices fitted at addresses 11 to 20 The letters displayed will be dependent on the type of device at that address location XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 22 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL C call point ionisation detector M module O optical detector S sounder Z zone monitor H heat detector D multisensor unknown To view the remaining devices on the loop use the and buttons as appropriate Press the Escape 4 button to return to the Commissioning Functions submenu ASSIGN ZONE GROUP This function allows you to assign devices to be members of detector zones or sounder groups as appropriate This would normally be done using the panel s PC programming software tools but is provided at the panel in case you need to add a device at short notice typically when a PC is not avail able It therefore allows you to get a new device working in a basic manner whilst it is waiting to be properly configured at a later date When selected you will be prompted to enter the loop on which the device you want to assign is located followed by the device s address
21. Activating channels 1 and 3 on a sounder beacon will have no effect If you are happy to proceed press the Accept gt button to assert the output channels of the selected device Once activated you will be given the option to switch off output channels 1 and 3 by pressing the Accept 7 button again Press the Escape 4 button as appropriate to return to the previous menus DISPLAY DATABASE This function allows you to view the panel s database of loop devices Available on a loop by loop basis the information displayed includes the device s type address and description zone and device text When the DISPLAY DATABASE prompt is accepted you will be prompted to enter the loop you wish to view the database of Loop 1 XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 31 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Use the and buttons to select the desired loop and press the Accept button You will then be prompted to enter the address of a particular device Loop 1 Device 22 Use the and buttons to select the desired address number and press the Accept gt button The information that is stored on the database that relates to that address will now appear for example Loop 1 Device 22 0 Optical det 0x88 Shop Floor Gents Toilet You can now use the and buttons to scroll through the rest of the database for the selected loop as required
22. DFU1200510 Rev 1 Page 14 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Button controls More Information Scroll Up 1 Scroll Down v 3 Accept gt 2 Escape 4 4 Menu Silence Internal Sounder Control Panel Reset Silence Resound Sounders Investigate Keyswitch control Displays additional information on any fire pre alarm or fault conditions that appear on the panel s display Will also display additional context dependent information where appropriate Dependent on the status of the panel these two buttons scroll vertically through any fire pre alarm or fault conditions that appear on the panel s display e scroll vertically through the panel s user menus manipulate date time and disablement settings etc serve as code input buttons to access levels 2 or 3 Dependent on the status of the panel these two buttons scroll horizontally through the panel s user menus e escape or accept options available in the panel s user menus serve as code input buttons to access levels 2 or 3 Provides access to the panel s menus Silences the panel s internal sounder Resets the panel when the sounders are silenced access levels 2 amp 3 only Silences or resounds the system s sounders access levels 2 amp 3 only Starts the panel s investigate timer function access levels 2 amp 3 only Turning the keyswitch to the armed position I gives the user instant access to
23. Escape 4 button XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 32 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL ENABLE DISABLE EARTH FAULT This function allows the panel s earth fault monitoring circuitry to be temporarily disabled When accepted the following window will appear Earth fault monitoring is Enabled Use the and buttons to toggle between enabled and disabled and press Accept gt button to select the desired option The panel s flash database will update and you will be returned to the Engineering Functions submenu SHOW LOOP CURRENT This function allows you to view the level of current being drawn by the addressable loop s at any given time to help verify the design of a system When accepted a window similar to the following Loop 1 current 3mA Loop 2 current 7mA w xe D o ay The actual current drawn will depend upon the size of the loop and the number of items connected Press the Escape 4 button to return to the Engineering Functions submenu SHOW DISCOVERY EEPROM This function allows the panel to interrogate and view information held by Apollo Discovery devices When accepted enter the loop and address of the Apollo Discovery device example shown below Loop 71 gt Loop 1 Device nn When accepted a list of 16 Extended Command Field Data is shown on the display
24. IRE ALARM PANEL WALK TEST This function allows you to put one or more of the system s detection zones into walk test mode When a zone is in walk test mode any detector manual call point triggered on that zone will turn on all of the sounders that are mapped to that zone for a brief period note that output sets will not operate When the WALK TEST prompt appears press the Accept gt button and the zone selection window will appear Use the and buttons to select the zone you wish to put into walk test mode Press the Accept gt button and the following window will appear Zone 1 Normal operation Use the and buttons to change the zone s state from Normal Operation to Walk Test Mode and press the Accept 7 button You will now be returned to the Engineering Functions submenu and you can proceed to test the zone as appropriate note that you must be in access level 1 if you wish to view the device s being tested Should you wish to put additional zones into test at the same time you can do so by repeating the above process To take zones out of test reverse the procedure Any zones in test will be indicated at all access levels via the DISPLAY ZONES IN TEST menu and the test LED on the front of the panel BLINK DETECTOR LEDS This function allows you to momentarily assert the LED outputs of loop devices such as detectors and manual call points in one continual sweep This is a particularly u
25. P main panels e Allows the interconnection of up to eight XFP main panels any mix of single loop 16 zone XFPs and 1 and 2 loop 32 zone XFPs Up to 1 km of cable may be fitted to an XFP main panel network Each networked XFP main panel can be programmed to Accept Fires from other main panels Accept Faults from other main panels Accept Control actions such as Silence Alarm Sounders and Control Panel Reset from other main panels Accept Disablement commands for zones sounders and output sets from other main panels Each of these four functions may be individually selected via the panel s PC Programming Software Tools e All panels monitor all other panels for network wiring faults Fires on remote panels are displayed on local panels including the point description of the alarm s origin e Faults on remote panels are displayed on local panels including the point description in the case of a detector Cause and effect can be programmed into local panels dependent on which remote panel is in alarm The network supports the programming of site information into remote panels from a PC connected at a local panel Time and date is common to all panels throughout the network Key features of the XFP s network protocol when used for connecting XFP repeaters Allows the connection of up to eight XFP repeaters any mix of single loop 16 zone repeaters and 1 and 2 loop 32 zone repeaters Up to 500m of cabl
26. RS AND CONTROLS Control buttons Menu More Information Silence Internal Sounder Control Panel Reset Investigate Resound Event scrolling and menu access buttons Upa 1 Down 3 Accept gt 2 Escape 4 4 Liquid crystal display Two lines x 40 characters backlit Number of zonal LED indicators 16 Other LED indicators General Fire Supply Present Test Accessed General Disablement Phased Evacuation General Fault Power Supply Fault System Fault Sounder Status Delays Running PHYSICAL DIMENSIONS Approx dimensions of panel W x H x D 380 x 235 x 90mm plastic Approx weight without batteries 1 8kg CABLING REQUIREMENTS Type of cable Fire resistant screened cable minimum size 1mm Max cable length per loop 1KM Connector blocks Plug on type largest acceptable conductor size 1 5mm Max allowable loop impedance each conductor 20 ohm Max cable capacitance 27uF NETWORK SPECIFICATION Connection Via CFP761 network driver fitted at main panel Max no of main panels per network 8 Max no of repeaters per non networked master panel 8 Max cable length per network 1 KM main panel network 500m repeater network PC PRINTER INTERFACE PC connection Via main panel RS232 molex connector lead supplied in XFP507 upload download software kit Printer connection Not applicable OPERATING CONDITIONS The components are selected to operate within their specification
27. To exit the database press the Escape 4 button at any time VERSION NUMBERS This function allows you to view the current version number of the panel s firmware and to ascertain when the site s data was last changed When accepted the following two windows with details specific to the panel will appear in quick succession The version of the The date the panel s panel s firmware firmware was released XFP 8A22 28 06 2005 2 loops fitted Hochiki protocol The number of The protocol of the loops fitted panel s loops The identification number The date the site of the site data was last changed Site data 49191 49191 11 3 2005 Program checksum 16886 16886 The number of Program checksum loops fitted code Matching site data codes i e 49191 49191 and program checksum codes i e 16886 16886 show that the panel is functioning correctly Mis matched numbers i e 49191 40286 indicate that the panel s memory may be corrupt After five seconds the panel will return to the Engineering Functions submenu SHOW PSU STATS This function allows you to view important information regarding the state of the panel s PSU and its standby battery supply When accepted two windows similar to the following will appear in quick succession Batt 24651mV Earth fault OK Mains OK Batt OK Charge OK Batt R OK Mains OK Batt OK Charge OK To return to the Engineering Functions submenu press the
28. Use the andw buttons to toggle between enabled and disabled and press the Accept button to select the desired option Alternatively to return to the previous menu press the Escape 4 button MONITOR A POINT This function allows you to view the current analogue status of any point any addressable device on the system When selected you will be prompted to enter the loop on which the device you want to monitor is located and the device s address Loop 1 Device 1 Use the and Accept buttons to select the desired loop and address The panel will tem porarily disable the point in question and return back its analogue values for example The loop the point being The point s The point s The point s normal monitored is located on address current analogue value analogue value L 1 D 7 AV 63 ZP 62 FP 192 ATL 148 F 0 C 0 T 0x88 The maximum value The point s alarm The code The points The the point will return when threshold level _ for any fault current stage point s type in a fire condition the level at which it will 6 condition that of calibration lag an alarm condition point may be in To return to the Engineer Functions submenu press the Escape 4 button TEST DEVICE OUTPUTS This function allows you to assert the output s of any addressable device to check it is working cor rectly It can be used for example to assert a detector s internal or remote LED if connected or to check tha
29. XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL Single Loop 16 Zone Version engineering manual Approved Document No DFU1200510 Rev 1 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL CONTENTS 5 3 Key feature 3 7 7 11111 0 4 Installation and WIFING dni 5 Thefire parniel ot 5 Removing the lid and base 7 111 50 0737 1 5 Mounting the base to the 233 13 11 111 1 1 1 111 1 6 Planning the cable layout in the 1 0 508 0 6 ME PB PS 2 5 3 NO 6 Connecting Mains to the Power Supply PCB assises isanne iaaa iaaiiai i aa Analogue addressable loop wiring Connecting the analogue l
30. access level 2 authorised user level XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 15 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL COMMISSIONING AND PROGRAMMING Overview Commissioning is the setting to work of the equipment The efficiency with which this is done depends upon e The accuracy of information received regarding the wiring and devices fitted The freedom of the installation from faults and errors The completeness of the information received from the client specifier as regards the zoning naming and functioning of the system The final quality of the installation ALWAYS depends upon the quality of these three factors Recommended commissioning procedure Re fit the panel s PCBs and all connection leads by reversing the removal procedure detailed on page 5 Ensure all PCB retaining screws are firmly fastened down and that the PSU earth strap is connected to the base earth post If a network communication card is required this should be fitted as shown on page 12 Check the continuity of the loop the resistance of the conventional sounder circuits if applicable and all other field wiring as appropriate to ensure they are free from faults DO NOT MEGGER Remove all electronic devices if 500V testing is demanded If okay connect all field wiring to the main control PCB as detailed on pages 8 to 11 Connect the Mains supply to the L N and terminals on th
31. alue L 1 D 7 AV 63 ZP 62 FP 192 ATL 148 F 0 6 0 T 0x88 The maximum value The point s alarm The code The points The the point will return when threshold level for any fault current stage point s type in fire condition the level at which it will condition that of calibration lag an alarm condition point may be in As the device is intensively polled some of its analogue values may change helping to assist you in the fault finding process To view a running total of the number of good and bad polls between the panel and the device at any time press the More Information button and a window similar to the one below will appear Good polls 592 Bad polls 3 To return to the analogue value window press the More Information button again To exit the INTENSIVE DEVICE MONITOR function press the Escape 4 button XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 30 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL LOOP TEST This function helps pinpoint loop wiring communication faults by continually polling all loop addresses for a specified number of times and reporting back how many good and bad polls there have been on an address by address basis In order to do this the panel suspends all other system activity when this test is taking place fires etc will not be flagged so please use this function with care When selected you will be prompted to enter the
32. anges include detector sensitivity high low and zone dependency settings An investigation delay period function programmable for length of time which zone s it applies to and whether or not it operates in day night mode which works as follows When there is an alarm in a zone programmed to operate in investigate mode the full alarm condition will occur after a delay It is possible to manually impose a further delay to allow the source of the alarm to be investigated If the second delay expires or there is another alarm in the same zone then a full alarm condition is established During either delay period the panel may be reset in the case of a false alarm Individual sensitivity settings for each device EN54 2 Clause 7 11 Delays to outputs and a phased evacuation facility An EN54 2 Clause 7 13 alarm counter to record the number of times the panel has been in an alarm state A powerful short circuit protected loop driver capable of supporting a total of 126 addressable devices An integral 1 4A EN54 4 switch mode PSU rated 185 260V a c 50 60Hz Earth fault monitoring Keypad access code to access levels 2 amp 3 Keyswitch entry to access level 2 40 characters of custom text per device 500 event monitoring Comprehensive EN54 2 Clause 10 test with maintenance and commissioning functions An intuitive Windows based upload download PC program Part No XFP507 that MUST be used to configure the system Networking If
33. appear Panel Relay 1 Select the relay 1 2 or 3 to be disabled enabled using the and buttons When the desired relay has been selected press the Accept 7 button and the relay s status Enabled or Disabled will flash Next use the and buttons to toggle between enabled and disabled and press the Accept 7 button to select the desired option The window will now move to the next relay allowing further enablements or disablements to be made Alternatively to return to the previous menu press the Escape 4 button ENABLE DISABLE DEVICES This function allows loop devices to be disabled from reporting faults fires pre alarms etc and is normally used to temporarily disable detectors call points that are nuisance tripping When selected press the Accept 7 button and a window similar to the one below will appear Select Zones 1 Shop Floor Use the and buttons to select the zone where the device you wish to disable enable is located When selected press the Accept gt button and a list of all devices that can be disabled or enabled in that zone will appear for example Shop Floor 1 Gent Loop 1 Device 3 Enabled Use the and buttons to scroll through the available devices When the desired device appears press the Accept gt button and the device s status Enabled or Disabled will flash Next use the a andy buttons to toggle between enabled and disabled and press the Accept 7 button to select
34. are in test if applicable e Change the entry codes to access levels 2 and 3 from their factory default settings Connect the panel to a compatible PC for system programming e Set the panel up to belong to a network of eight XFP main panels or allow it to have up to eight XFP repeaters connected to it Gain access to a wide range of commissioning functions including auto loop learn device calibration and group zone assignment Gain access to a wide range of engineering test and fault finding functions Ascertain software revision numbers loop current and PSU statistics e Enable disable earth faults e Set the time the panel enters and exits day building occupied and night building unoccupied mode Access all of the panel s access level 2 menu options as described in the panel s separate user manual This section of the engineering manual explains in detail the various functions available via the access level 3 menu options Note that information on how fire pre alarm and fault conditions are reported and how the panel s control buttons operate can be found in the separate user manual log book AN Fitting the panel s NVM memory unlock link GENERAL FIRE ZONE1 ZONE2 ZONI O To allow site specific changes to be made to the panel s NVM memory non volatile memory the NVM memory unlock link must unlock link be fitted to the Main Control PCB as shown right It is recommended that
35. arth post as shown on page 9 Fig 4 A typical analogue addressable loop cE 6 j eo a SHY I Zone Monitor with Isolator e NRARA eo m n m Ll x Conventional detectors and manual call points j Sounder control L unit with Isolator Local 24V G7 PSU 7 Fire 0 14 Externally powered conventional Fault Input SY Input Output Unit with Isolator aS Important Isolators should be installed at koc intervals not exceeding 20 devices and at the m building s structural fire barriers zonal boundaries Detector c w Mounting Base Detector c w Isolating Base r Ancillary function E Manual Call Point EL F p I i T EE Ss E E Sy Loop Powered Switch Monitor Sounder with Isolator Loop Powered Relay output 1 Programmable input 1 Beacon Relay output 2 Programmable input 2 Relay output 3 a Fault output E ee Conventional Sounder Circuit 1 Stand Alone 24V output tL ih Conventional Sounder Circuit 2 Isolator XFP SINGLE LOOP gi 16 ZONE MAIN PANEL Design issues reducing faults and their consequences To ensure a reliable system it should be designed and maintained to local design and installation regulations The XFP has loop isolators included in the panel and loop isolators should be included in the loop wiring A singl
36. ce manufacturers protocol coupled with the cable s characteristics The panel s loop driver is easily capable of driving lightly loaded loops up to 4 km long without a problem However devices connected at the end of 4 km may not be able to read the data once corrupted by the cable Always refer to the instructions supplied with each device prior to installation XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 8 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Connecting the analogue loop to the Main Control PCB The analogue loop should be connected to the Main Control PCB as illustrated in Fig 5 below Remember to isolate the panel s Mains and battery backup supplies before making any connections The loop s earth screens should be adequately insulated and connected between the nut and washers on the base earth post using eyed crimp connectors Do not disturb the lower nut this must be secure to ensure earth continuity earthing point The installer must review the external earth bonding if required with respect The base earth post is provided for terminating earth screens or drains and is NOT the main to the national wiring rules If the installation requires protective earth bonding then this must be applied externally and in conjunction with the type of earthing system employed on site Note that the Main Control PCB connects to the Power Supply PCB via an 8 way te
37. device number Loop 1 Device 1 Use the and Accept buttons to select the desired loop and address device You will then be presented with the zone group assignment window for example Shop floor No name allocated Belongs to Zone 1 Use the amp buttons to scroll to the desired zone or group and press the Accept gt button The assignment will be made and you will be prompted to select another loop device to assign using the same procedure Alternatively to return to the Commissioning Functions submenu press the Escape 4 button Important although I O units etc can be assigned to be members of zones using this menu this will only apply to their input functions The panel s PC programming software tools must be used to assign them to output sets CALIBRATE DEVICES Daily calibration of the system s smoke and heat detectors to take into account environmental changes drift compensation factors etc takes place automatically at 0400 hours or at an alternative time as pro grammed by the engineer The CALIBRATE DEVICES function allows you to carry out an additional manual calibration of the system s devices at any time When selected you will be asked if you wish to proceed Continue to Calibrate Devices Press the Accept gt button and calibration will start Depending on the size of the system this may take some time When calibration is complete the system will return to the Co
38. e may be fitted to an XFP repeater network Each XFP repeater offers all the functions and controls of XFP main panel Any XFP main panel connected to the network requires the installation of a Network Communication Card Part No CFP761 as shown in Fig 11 below Repeaters come with a Network Communication Card already fitted Typical network wiring details are shown in Fig 12 Fig 11 Installing the network communication card Important Before installing the network communication card isolate the Mains supply and disconnect the panel s battery back up supply With reference to the diagram below e Secure the card inside the panel using the two retaining screws provided See Fig 12 for typical Connect the two way polarised power supply loom network wiring details supplied with the card between PL1 on the card s and PL2 on the Power Supply PCB NETWORK Connect the 8 way telecoms style connector cable CARD Rs also supplied with the card between PL2 on the card and the socket on the reverse of the Main Control PCB socket SK2 which is located alongside the PCB s microprocessor The DIP switch SW1 on the network communi cation card has no function when used with the B XFP However all networked XFP main panels a require a unique ID number 1 8 so they can be To SK1 on recognised by other pa
39. e power supply PCB and the standby battery supply to its BAT1 terminals Upon powering up the panel s LCD will display a number of start up messages detailing the protocol of the panel etc Investigate any faults reported on the panel s display and take the necessary steps to correct them When all faults have been corrected carry out a loop learn as detailed on page 21 Rectify any problems resulting from loop learn e g double addresses missing devices incomplete loops etc Note that a wide range of test and fault finding functions are available in access level 3 When all faults have been cleared proceed to program the panel as appropriate When you are satisfied the panel has been programmed and is working correctly secure the panel lid and instruct the client customer in the operation of the system Complete and handover all necessary manuals and other documentation prior to leaving site System operation terms of reference Input devices such as detectors manual call points and the input channels of I O units are programmed to be members of a Zone Output devices such as loop powered sounders sounder control units and the panel s conventional sounder circuits are programmed to be members of a Group The output channels of I O units and the panel s relays are programmed to be members of a Set Zones are programmed via the panel s software to activate Groups and or Sets as appropriate The method of activation of Group
40. e short circuit fault will now only disable devices in the section of wiring between isolators Local design and installation regulations will dictate how many devices or zones may be lost in the case of this type of fault In the case of a single open circuit no devices will lost since communication is from both ends of the loop but a loop integrity fault will be shown Note that a critical design issue with any analogue fire system is the combined effect of loop resistance loop capacitance and the current demand of items connected to the loop Factors that influence this include loop length cable diameter cable type the number of isolators used and the number and type of devices between isolators There are no hard and fast rules regarding these factors as every situation is unique However if the following conservative advice is followed the loop WILL almost certainly work Absolute maximum loop length 1km with either 1mm or 1 5mm cables e No more than 20 addressable devices between loop isolators of which no more than 6 are loop sounders If loop sounders are used use 1 5mm cable and do not fit more that 32 loop sounders per loop in total If more than 10 loop sounders are used per loop then the maximum loop length per loop should be no greater than 750m The above SHOULD NOT be considered the maximum operating conditions for the panel as many other permutations are possible Any limitations are a consequence of devi
41. ead supplied with the soft ware tools should be connected lt a Plug the lead s D type connector to the panel and the PC as into the appropriate serial socket shown in Fig 9 right com1 com2 etc on the PC Aux 24V output One fused 24V d c output rated at 100mA is provided and can be used for supplying power to ancillary fire alarm equipment This input should not be used to power electromagnetic door retainers Installing the standby battery supply Two new good quality and fully charged 12V valve regulated lead acid batteries are required as the emergency stand by power supply for the panel The batteries should be connected in series and located in the panel s enclosure as shown in Fig 10 below The battery leads link wire and nylon cable ties are provided in the panel s accessory pack Run the battery leads through the slits in the panel s lower plastic ribs and secure the batteries into position using the nylon cable ties as shown The panel s sophisticated battery monitoring unit protects the batteries against deep discharge by activating a cut off circuit when the stand by supply voltage reaches 21V approx If batteries are not fitted are discharged or in poor condition a PSU fault will show at the panel The capacity of the batteries used will depend upon the required stand by time To calculate the batteries required for any given stand by period refer to the battery ca
42. ections are correct the following message will appear PC connected Press ESC to disconnect from PC If there is a problem with the panel to PC connection this will be flagged at the PC when you try to upload or download any site specific data Network functions Selecting this menu option takes you to the network functions submenu where you can configure the panel to be part of a network of up to eight XFP master panels or allow it to have up to eight XFP repeaters connected to it This option is only available if you have a network communication card fitted at the panel see pages 12 amp 13 for a detailed overview of master panel networking and repeater panel connection The network functions submenu has three options SET COMMS FUNCTION SET PANEL NUMBER and SET PANEL FITTED Other options such as what events and what level of control is allowed between networked panels is implemented using the panel s PC programming software tools SET COMMS FUNCTION This function allows you to set the panel s RS485 comms to operate in Network or Repeater mode When selected press the Accept button and a message similar to the one below will appear COMMS IS SET FOR REPEATER Use the and buttons to scroll between Repeater and Network and press the Accept gt button as appropriate The panel s flash database will update and you will be returned to the Network Functions submenu SET PANEL NUMBER If networking XFP main pane
43. ery leads supplied in the panel s accessory pack For battery connection details refer to page 11 PRIMARY FUSE Ft 1A DO NOT ADJUST BATTERY FUSE 1 6AF ra 250V HRC The incoming Mains earth wire MUST be connected to the terminal marked and NOT to the base earth post The PSU earth strap connects the PCB to the base earth post A WHEN CONNECTED THE PCB STORES VOLTAGES AT UP TO 400Vd c AND MAY BE LETHAL IF TOUCHED DO NOT TOUCH THE PCB WHILST THE RED HAZARDOUS VOLTAGES PRESENT LED IS LIT Main Control PCB connector cable socket connect other end of lead to the rear of Main Control PCB XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 7 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Analogue addressable loop wiring Fig 4 below shows a typical analogue addressable loop complete with loop isolators detectors loop powered sounders modules and monitors The descriptions and availability of the devices shown may not be applicable to all manufacturers protocols check with your supplier for further details Also this example arrangement of devices may not be permitted by design and installation regulations in certain countries The loop should be connected to the relevant 5mm connector block on the panel s Main Control PCB and its screens terminated at the panel s base e
44. failed depends on the quiescent loading of the panel the alarm load of the panel and the capacity of the batteries To determine the capacity of batteries required for any given stand by period the following formula should be used Standby Time in Ah 1 25 x TxA H x P Z The multiplier 1 25 is present to account for lost capacity over the life of the batteries H Number of hours standby required P The quiescent current of the panel 0 042A This value is with the Mains failed beeper silenced and the Supply Present and General Fault indicators lit If there are other quiescent drains on the Panel then these must be added in Z The total quiescent current of all zone devices As a guideline the average quiescent current addressable devices is typically 0 00025A 250A To obtain accurate figures consult the device manufacturers own specifications A The total alarm current of the panel sounders plus any other devices connected to other alarm outputs T The amount of time in hours required for the alarm most commonly being half an hour Example 1 The panel has 50 devices each consuming 250pA each 15 sounders at 8mA each the required standby time is 24 hours and the required alarm time is 0 5 hours Z 50 x 0 00025 0 0125A P 0 042A A 15 x 0 008 0 12A H 24 T 0 5 Standby Time in Ah 1 25 x 0 5 x 0 12 24 x 0 0125 0 042 1 71Ah Therefore batteries with at least 1 71Ah capacity are
45. ht Un Occupied mode begins 18 00 Use the scroll 4 w and Accept buttons to set the time in hours and minutes that you want the panel to enter night mode When the desired time is displayed press the Accept 7 button again and you will be returned to the commissioning functions submenu XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 24 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL ENABLE DISABLE DST DAYLIGHT SAVING TIME ADJUSTMENT This function when enabled allows you to programme the panel s time so it automatically goes forward one hour on the last Sunday in March and goes back one hour on the first Sunday in October Auto DST Time Adjustment is Press the and buttons to scroll between enabled Enabled and disabled and Accept gt to select the desired option CONFIGURE SOUNDER DISABLEMENTS This function configures the Sounder Groups 1 to 16 to be Globally or Individually disabled enabled When accepted two windows are available Sounder Groups can be Disabled Enabled Sounder Groups can be Disabled Enabled Globally Individually Press the and buttons to scroll between Globally and Individually and Accept gt to select the desired option MAKE A CLEAN START This function allows you to clear the panel s memory back to its factory default settings When selected you will be asked to input the five digit clean start confirmatio
46. imilar to the one below 0 changed 0 removed 112 total devices Auto learn completed Press the Escape 4 button to return to the Commissioning Functions submenu XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 21 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL FIND NEW DEVICES This function allows you to check if any new devices have been connected to the panel since the last loop learn It works in a similar way to the loop learn function except whilst learning the loop the panel asks if you want to accept any of the new devices it has found and allows you to assign them to a detector zone or sounder group as appropriate To start the search process when the FIND NEW DEVICES prompt appears press the Accept button The following window will appear Continue to find new devices Press the Accept 7 button again to confirm you wish to continue and you will be asked to select which loop s you want the panel to search for new devices on 1 2 or ALL as applicable On loop 1 Use the and buttons to scroll to the desired loop s and press the Accept 7 button The search will now begin When a new device is found the panel will tell you its type its address Dev and the loop it is fitted on for example Loop 2 Dev 48 Optical det 0x88 Accept device To accept the new device press the Accept 7 button Alternatively press the Escape 4
47. l sounder circuit Conventional sounder circuit detail POLARISED POLARISED POLARISED SOUNDER SOUNDER SOUNDER Fy END OF LINE 6k8 Ohm DO NOT SPUR wiring not monitored Earth strap from power supply PCB For more precise earth screen termination details refer to the typical analogue loop wiring diagram on page 9 Relay 3 NO NC C NO NC C NO Addressabl leLoop ha A B ha Auxiliary input wiring Two programmable auxiliary input connections are fig 7 Typical auxiliary input wiring connection provided These can be programmed using the panel s PC programming software tools to operate as required The wiring for each input should be connected to the terminal block marked Auxiliary on the Main Control PCB as shown in Fig 7 right Remember to isolate the panel s Mains and battery backup supplies before making any connections If applicable i e in electrically noisy environments input wiring screens should be terminated at the panel s base earth post in the same way as the ana logue loop earth screens as detailed on page 9 Relay 1 NC C NO Relay output wiring Four volt free relay output connections are provided a failsafe fault output which switches for any fault condition and three programmable auxiliary relay outputs All four relays are capable of switching 1A 30Vdc They should NOT be used for switching Mains voltages The three auxiliar
48. lators containing devices 15 20 When the BLINK DETECTOR LEDs prompt appears the following window will appear Which loop 1 Select the loop you wish to carry out the test on using the and buttons and press the Accept gt button You will then be prompted to select from which end of the loop you wish to run the test Which loop 1 End A Use the and buttons to select End A End B or Both Ends as appropriate and press the Accept gt button The LEDs of all detectors on the loop will now start blinking accordingly Note that addresses do not have to be in sequential order for this facility to work To end the test press the Escape 4 button at any time XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 29 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL INTENSIVE DEVICE MONITOR This function allows you to monitor a specific addressable point to see how it responds to intensive repeated polls from the panel In order to do this the panel suspends all other system activity when this test is taking place fires etc will not be flagged so please use this function with care By reporting back how many good and bad polls are made between the panel and the monitored device this function can help pinpoint loop wiring communication faults and or faulty devices When selected you will be prompted to enter the loop on which the device you want to monitor is loca
49. lculation guide on page 35 Always dispose of used batteries according to the battery manufacturer s instructions Fig 10 Battery location and connection details Link wire Take care to arrange batteries so terminals do not touch AJ Nylon tie wraps i Run the battery leads supplied through slits in the plastic ribs O 2 l DL Location of small Location of medium Location of large Connection of leads sized batteries sized batteries sized batteries to Power Supply PCB typically 1 2 Ah typically 2 1 Ah typically 3 0 Ah XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 11 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Network repeater wiring optional The XFP s network protocol allows the interconnection of up to eight XFP main panels any mix of single loop 16 zone XFPs and or 1 to 2 loop 32 zone XFPs over a two wire RS485 network Alternatively the network can be used to connect up to eight XFP repeaters to one XFP main panel It is not possible to mix XFP main panels and repeaters on the same network Key features of the XFP s network protocol when used for interconnecting XF
50. lecoms style connector cable the socket for which is located on the PCB s reverse This cable must be connected before the Main Control PCB is secured in the panel Ensure all six PCB retaining screws amp are properly tightened before operation as they play an important part in the electrical safety and EMC immunity of the panel Fig 5 Typical analogue addressable loop connection Analogue loop crimped spring connections nut washer plain washers screens Do not untighten lower nut BE Sl Earth strap from power supply PCB Auxilliary he Relay 1 Relay 2 Relay 3 Fault A Sounder Circuits Earth Fault Detect t Addi issaflle i a lo te 00 000 24V IIP1 52 Ov NC C NO NC C NO NC C NO NC C NO A Short B Short GENERAL i z FIRE ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6 This LED will O O be lit amber if there is a short circuit on the loop s O O O A A leg ra ZONE9 ZONE 10 ZONE 11 ZONE12 ZONE 13 ZONE 1 This LED will be lit amber if there is a short circuit on the loop s B B leg O Mite Op4s Beeper SUPPLY GENERAL PHASED PRESENT TEST ACCESSED DISABLEMENT EVACUATION O O O Q O O GENERAL PSU SYSTEM SOUNDER DELAYS FAULT FAULT FAULT STATUS RUNNING CAUTION RISK OF EXPLOSION IF
51. ls this function allows you to give the panel a unique ID number 1 8 so it can be recognised by other panels on the network Note that Repeaters do not need to be assigned an ID number When selected press the Accept gt button and a message similar to the one below will appear SET PANEL NUMBER 1 Use the and buttons to scroll to the desired number and press the Accept gt button to select it The panel s flash database will update and you will be returned to the Network Functions submenu SET PANEL FITTED This function allows you to turn off the fault monitoring of other networked XFP main panels It is typically used if maintenance work is to be carried out at a networked panel to temporarily prevent integrity faults being flagged When selected press the Accept button and a message similar to the one below will appear NETWORK PANEL 1 Use the and buttons to scroll to the desired networked panel and press the Accept gt button to accept it The panel s flash database will update and you will be returned to the Network Functions submenu Remember to reverse the function when maintenance work is complete XFP ENGINEERING MANUAL e Approved Document No DFU1200510 Rev 1 Page 20 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Commissioning functions Selecting this menu option takes you to the commissioning functions submenu where you can carry out a loop learn find new de
52. mended that you remove the panel s lid and base PCBs prior to first fix installation to protect the electronics from damage Removing the lid and base PCBs Fig 1 Location of the panel s base PCBs and removal details PL1 lt push tab and gently lift cable POWER SUPPLY PCB g Leave this end of the connector cable connected to SK2 on the reverse of the Main Control PCB 1 Take the panel out of its box and undo the two lid screws using the Torx key provided Remove the lid to expose the Main Control PCB the Power Supply PCB is located underneath 2 Carefully remove the five retaining screws on the Main Control PCB and slide the PCB up and over the mounting pillars taking care not to damage any of the components 3 Disconnect the telecoms style connecting cable at PL1 on the Power Supply PCB making sure that the cable remains connected to the reverse of the Main Control PCB to prevent it being misplaced 4 Pull the Power Supply s earth strap off the spade connector at the base earth point 5 Carefully remove the three retaining screws on the Power Supply PCB and slide the PCB up and over the mounting pillars again taking care not to damage any of the components 6 Store the PCBs in a clean dry place which is free from vibration dust and excessive heat Retaining the PCBs in a s
53. mmissioning Functions submenu COMMISSION THE LOOP S This function refreshes the characteristics calibration levels contamination values etc and checks the type codes of all devices connected to the loop s When selected you will be asked if you wish to proceed This may take several minutes OK to proceed Press the Accept 7 button and the commissioning function will start When completed the system will return to the Commissioning Functions submenu SHOW CALIBRATION PROBLEMS This function allows you to view any detector s with calibration issues In addition to listing detectors that have definitely failed to calibrate correctly and will no longer function reliably it also lists those that are in the process of being checked and MAY fail to operate correctly When the SHOW CALIBRATION PROBLEMS prompt is accepted details of the first detector with a cal ibration problem will appear For example Loop 1 Device 23 Calibration issue Turn ON output channels 1 amp 3 XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 23 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL If there are multiple addresses with calibration issues press the button to scroll to the next affected address Press the Accept 7 button and output channels 1 and 3 of the detector being viewed will be asserted Once activated you will be given the option to switch off output channels 1 and 3 by pressi
54. n code Enter confirmation code The button sequence for this is 1 gt 2 3 4 4 Silence Internal Sounder button Engineer functions Selecting this menu option takes you to the engineer functions submenu where you can set or clear disablements access the panel s comprehensive test functions and display important system status information All of the panel s engineering submenu functions are described in detail below SET CLEAR DISABLEMENTS Selecting this menu option takes you to the disablements sub menu which allows you to enable or disable zones sounders outputs relays individual devices and or the panel s fault relay Any disablement s will be indicated at all access levels via the DISPLAY DISABLEMENTS menu and the General Disablement LED on the front of the panel We strongly recommend all disablements are regularly reviewed and immediately enabled when no longer necessary as they can have a major effect on how the system works The following options are available ENABLE DISABLE ZONES This function allows you to disable zones from reporting faults fires pre alarms etc and is normally used to tem porarily disable a zone of detectors call points in areas such as loading bays that are prone to nuisance triggering from vehicle fumes When selected press the Accept button and window similar to below will appear Select the zone to be disabled enabled using the and
55. nels on the network and aa f control PCB this is assigned using the network functions menu options at access level 3 XFP repeaters do not require an ID number XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 12 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Fig 12 Typical network wiring The network wiring should be installed to meet BS 5839 Part 1 and BS7671 Wiring Regulations and or other national standards of installation where pertinent see cable types amp limitations page 3 Connect A to A B to B and terminate incoming and outgoing earth screens to terminal C Note that earth screens should also be terminated at the base earth post of ONE master panel ONLY as illustrated below TO NEXT TO NEXT NETWORKED NETWORKED PANEL IF PANEL IF REQUIRED REQUIRED NETWORK COMMUNICATION COMMUNICATION CARD CARD 2 POWER SUPPLY PCB NETWORK crimped COMMUNICATION connection CARD nut J washers Do not untighten lower nut A typical XFP main panel network PANEL 2 ty PANEL 1 p PANEL 5 p PANEL 3 PANEL 4 SPUR WIRING SPUR WIRING NOT ALLOWED NOT ALLOWED A typical XFP repeater network XFP XFP XFP XFP XFP MAIN REPEATER REPEATER x x SPUR WIRING SPUR WIRING NOT ALLOWED NOT ALLOWED
56. ng the Accept button again Press the Escape 4 button as appropriate to return to the previous menus or to select another device with calibration issues SHOW DUPLICATE ADDRESSES This function helps you to locate devices with duplicate addresses by asserting their output channels 1 amp 3 In the case of detectors and manual call points activating these channels will turn their LEDs on Caution Note that channels 1 amp 3 on an I O unit may be programmed to trigger say a water extinguishant system so this function must be used with care Activating channels 1 and 3 ona sounder beacon will have no effect When the SHOW DUPLICATE DEVICES prompt is accepted details of the first double address will appear For example Loop 1 Device 23 Duplicate Address If there are multiple duplicate addresses press the button to scroll to the next affected address Press the More Information button at any time and a window similar to the one below will appear Loop 1 Device 23 Duplicate Address Turn ON output channels 1 amp 3 If you are happy to proceed press the Accept 7 button and output channels 1 and 3 of all devices with the duplicate address being viewed will be asserted Once activated you will be given the option to switch off output channels 1 and 3 by pressing the Accept button again Press the Escape 4 button as appropriate to return to the previous menus or to select another duplicate address to check
57. o select the sounder group you would like to test all or 1 to 16 Press the Accept gt button and the following window will appear Output 1 is Silenced Change the state using the Accept button Press the Accept 7 button to change the state of the selected sounder group between Silenced Intermittent and Continuous Should you wish to test additional sounder groups use the andv keys to change the sounder group s number accordingly To return to the main Engineer Functions submenu press the Escape 4 button TEST PANEL RELAYS This function allows you to test the panel s three volt free relays When the TEST PANEL RELAYS prompt appears press the Accept gt button and the panel relay selection window will appear Panel relay 1 Use the and buttons to select the output set you would like to test all or 1 to 16 Press the Accept gt button and the following window will appear Panel relay 1 is Normal Change the state using the Accept button Press the Accept 7 button and the panel relay you have selected will trigger To change the state back again press the Accept 7 button again Should you wish to test additional panel relays use the a and buttons to change the panel relay s number accordingly To return to the main Engineer Functions submenu press the Escape 4 button XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 28 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE F
58. on and national standards If in doubt please consult your supplier We recommend you read BS 5839 Part 1 Fire Detection and Alarm Systems for Buildings Code of Practice for System Design Installation Commissioning and Maintenance available at your local reference library or from the BSI Other national standards of installation should be referenced where applicable Cable types and limitations All system wiring should be installed to meet current national standards in the United Kingdom these are BS 5839 Part 1 and BS7671 Wiring Regulations Fire resistant screened cable should be used throughout the installation This not only shields the data moving up and down the cables from outside interference but is essential to ensure compliance with EMC regulations Cables such as FP 200 Firetuff Firecel and MICC may be acceptable provided they are properly terminated at the fire panel and meet national standards the system specification as applicable Consult Clause 26 of BS 5839 Part 1 for more detailed information on cables wiring and other interconnections Equipment guarantee This equipment is not guaranteed unless the complete installation is installed and commissioned in accordance with the laid down national standards in the UK BS 5839 Part 1 by an approved and competent person or organisation Anti static handling guidelines Always observe appropriate electro static handling precautions prior to handling the panel
59. oop to the Main Control PCB Conventional sounder circuit wiring Auxiliary input wiring 2 3 80 REMOTES PC 2 2 3 11 1 11 3 3 23 3 ee eel 050 11 Installing the standby 9 1 1 1 111 11 1 91 1 313 1 1 12 Controls 1 1 ini 14 Commissioning and 2 16 Recommended commissioning 6 2200 16 System operation terms of referen 7 1 1 1 16 33111111159 17 1 2
60. oved Document No DFU1200510 Rev 1 Page 6 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Connecting Mains to the Power Supply PCB The panel s PSU is a 185 265Va c 50 60Hz off line switched mode power supply that combines the functions of a power supply unit battery charging unit battery monitoring unit and earth fault monitoring unit It should be positioned in the panel s enclosure as shown in Fig 3 below DO NOT operate the panel without the Power Supply PCB correctly mounted in the enclosure with its three PCB retaining screws amp securely tightened DO NOT connect Mains to the Power Supply PCB until the installation is complete and ALL relevant PCBs are correctly attached within the panel Fig 3 Power Supply PCB layout and Mains connection details Incoming Mains cable must be segregated from other cables and should only enter the panel through these cut outs Good quality cable glands must always be fitted The PSU earth strap MUST be connected to the spade on the base earth post before operation The spade is compressed against a shoulder on the post via the lowest nut The earth post may appear loose this is intended by design Primary fuse F1 20mm 1ATH 250V HRC ceramic fuse to IEC 127 EN60127 2 Battery fuse F2 20mm x 1 6AF glass fuse to IEC 127 EN60127 2 Do not use any other types or sizes of fuse in these positions Batt
61. s PCBs or any other static sensitive components XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 3 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL KEY FEATURES This single loop 16 zone analogue addressable fire alarm panel offers the following features Full compliance with EN54 parts 2 and 4 including EN54 2 Clauses 7 8 Output to fire alarm devices 8 3 Fault Signals from points and 9 5 Disablement of addressable points Full compatibility with Hochiki s ESP and Apollo s XP95 Discovery and Xplorer protocols dependent on the model purchased Two independently programmable conventional sounder circuits Two programmable inputs A fault output relay and three programmable relay outputs with volt free changeover contacts A selection of zone dependency functions EN54 2 Clause 7 12 type A B or C as detailed below Type A If there is an alarm from a detector the panel will look for a confirmatory alarm from the same or another detector in the same zone before a full alarm is established If there is no confirmatory alarm the first alarm will automatically reset Type B As type A except the confirmatory signal must be from another detector in the same zone Type C As type A except the confirmatory signal may also be from another zone and the first alarm will not automatically reset A day night building occupied unoccupied function engineer programmable day night ch
62. s can be continuous or pulsed with or without a delay as required Note that the panel s two auxiliary inputs can be programmed to function in multitude of ways using the special cause and effects options available in the XFP programming software XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 16 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL ACCESS LEVELS MENU TREE Three access levels are available at the panel access level 1 general user access level 2 authorised user and access level 3 engineer The diagram below shows the menu options available at each level all of which can be navigated using the panel s scroll a w Accept 7 and Escape 4 buttons Note The menu options shown in bold will only be available if relevant to the panel s status This manual focusses on the functions available at access level 3 only access levels 1 and 2 are covered in the panel s separate user manual Details of how to gain entry to access level 3 and an explanation of the various functions available can be found on the following pages Menu button on front of panel ENTER ACCESS LEVEL 2 DISPLAY FIRE EVENTS DISPLAY FAULT EVENTS DISPLAY DISABLEMENTS DISPLAY ZONES IN TEST ENTER ACCESS LEVEL 3 LAMPS TEST DISPLAY ALARM COUNTER AL1
63. scroll to the desired option the option in block capitals is the selected option and press the Accept gt button The following message will appear if the CHANGE ACCESS LEVEL 2 CODE prompt is accepted Enter NEW Access Level 2 code Using the 1 gt 2 3 4 4 buttons enter the new four digit access level 2 code After the fourth digit has been entered the panel will request you confirm the new code by re entering it XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 19 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Enter NEW Access Level 2 code Confirm New Access Level 2 code Enter the code again by pressing the lt 1 gt 2 w 3 4 4 buttons in same sequence If the two codes match the new code will be accepted and you will be taken back into Access Level 3 If you type an incorrect confirmation code you will be prompted to start the code entry sequence again The same process can be used to change the access level 3 code BE SURE TO KEEP A RECORD OF ANY CHANGED CODES FOR FUTURE USE Connect to PC This function allows you to activate the panel s PC connection for system programming purposes ALL of the panel s cause and effect programming device and zone naming zone dependency functions etc must be carried out using our separately PC programming software tools XFP507 When the CONNECT TO PC prompt appears press the Accept button If all conn
64. seful function for helping to locate any open or short circuit faults on the loop wiring LEDs are asserted on all learnt loop devices on a step by step basis each step takes approximately one second Therefore on a system with say 80 loop devices each device will blink once every 80 seconds You can select the test to be carried out from either end of the loop or from both ends at the same time An example illustration of how this test may be carried out is shown below For a fault between points 17 and 18 on the example loop left OPEN CIRCUIT FAULT If Direction A End A is selected all devices 1 17 will periodically illuminate with devices 18 23 not illuminated If Direction B End B is selected all devices 18 23 will periodically illuminate with devices 1 17 not illuminated This would therefore identify an open circuit fault between devices 17 amp 18 SHORT CIRCUIT FAULT If Direction A End A is selected then all devices 1 14 will periodically illuminate END END The short circuit isolator between devices 14 amp 15 will have been activated and A B all other devices 15 23 will not be lit If Direction B End B is selected then devices 21 23 will periodically illuminate 61 The short circuit isolator between devices 20 and 21 will have been activated and all other devices 1 20 will not be lit 0 Loop Devices This would therefore identify a short circuit fault somewhere between the two iso
65. select the desired option The window will now move to the next sounder group allowing further enablements or disablements to be made Alternatively to return to the previous menu press the Escape 4 button XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 25 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL ENABLE DISABLE OUTPUTS This function allows you to disable one or more output sets from sounding in a fire condition It is typically used to disable for example auto diallers from activating during routine maintenance When selected press the Accept 7 button and a window similar to the one below will appear Output Set All Select the output set 1 to 16 or ALL to be disabled enabled using the and buttons When the desired output set has been selected press the Accept gt button and the output set s status Enabled or Disabled will flash Next use the and buttons to toggle between enabled and disabled and press the Accept 7 button to select the desired option The window will now move to the next output set allowing further enablements or disablements to be made Alternatively to return to the previous menu press the Escape 4 button ENABLE DISABLE RELAYS This function allows the disablement of one or more of the panel s 3 auxiliary relays from activating as pro grammed When selected press the Accept gt button and a window similar to the one below will
66. t an I O unit is functioning correctly Addressable devices typically have three output chan nels 1 2 and 3 the functions of which depend upon its type please refer to the device manufac turers technical data for further information When selected you will be prompted to enter the loop on which the device you want to test is located the device s address and the relevant output bit code 0 to 7 as explained in the table below Loop 1 Device 1 Output bits 0 Use the and Accept gt buttons to select the desired loop address device and output bit code OUTPUT BIT CODES AND WHICH OUTPUT CHANNELS THEY ASSERT CODE OUTPUT CHANNELS ASSERTED No output channel asserted Output channel 1 asserted Output channel 2 asserted Output channels 1 and 2 asserted Output channel 3 asserted Output channels 3 and 1 asserted Output channels 2 and 3 asserted OI A wl All output channels asserted XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 27 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL When you have accepted the required output bit option the panel will confirm your selection and the device s output channels will be asserted as programmed If desired you can now select alternative sequences using the and buttons note that as the device is now live you will not have to press the Accept 7
67. ted the device s address and its output bit sequence Loop 1 Device 1 Output bits 0 Use the and Accept gt buttons to select the desired loop address device and output bit sequence The output bit option allows you to monitor a device whilst it is in a particular state for example if an I O unit is reporting back faults only when it has triggered say a rollershutter door e g when its output channel 1 is asserted you can set the device up so it is in this state whilst being monitored See the table below for the output bit options available OUTPUT BIT CODES AND WHICH OUTPUT CHANNELS THEY ASSERT CODE OUTPUT CHANNELS ASSERTED No output channel asserted Output channel 1 asserted Output channel 2 asserted Output channels 1 and 2 asserted Output channel 3 asserted Output channels 3 and 1 asserted Output channels 2 and 3 asserted O A Ww All output channels asserted Caution Note that certain channels on an I O unit may be programmed to trigger say a water extinguishant system so this function must be used with care When you have accepted the device s output bits sequence by pressing the Accept gt button the test will begin and the panel will display the device s current analogue values for example The loop the point being The point s The point s The point s normal monitored is located on address current analogue value analogue v
68. uitable cardboard box will also guard them against mechanical damage XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 5 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Mounting the base to the wall The panel can be surface or semi flush mounted using the five mounting holes provided see Fig 2 below To expose the mounting holes you must first remove the panel s lid and base PCBs as described on page 5 The mounting holes are suitable for use with No 8 10 or 4 5mm countersunk screws Always assess the condition and construction of the wall and use a suitable screw fixing Any dust or swarf created during the fixing process must be kept out of the base Note that the central mounting hole can be used to temporarily hang the back box so it can be levelled and its remaining fixing points marked for drilling Fig 2 Location of mounting holes and drill points side view of panel for flush mounting fs TT T T N These four drill centre 75 SS points are reserved includes dimples 8 0 0 for incoming Mains Fixing centres cable only 4 339mm 4 2 e olo c 6 N O hep SN Fixing centres 170mm Planning the cable layout in the panel All cables should be brought into the panel via the drill outs
69. vices view fitted devices assign detectors call points to zones and sounders beacons to groups manually calibrate devices and or return the panel to its default factory settings All of these functions are described in detail below Note that the vast majority of system commissioning cause and effect programming device and zone naming etc must be carried out using our separately available PC programming software tools Part No XFP507 LOOP LEARN This function activates the panel s automatic loop learn facility During a loop learn the panel inter rogates every address location on the loop to see if an addressable unit is present and if so finds out what type of device it is When the LOOP LEARN prompt appears press the Accept gt button and you will be asked to confirm that you wish to continue Continue with Loop Learn Press the Accept 7 button again to continue and you will be asked to select which loop s you want the panel to learn 1 2 or ALL as applicable Learn Loop All Use the and buttons to scroll to the desired loop s and press the Accept 7 button As the panel may already have loop device data stored in its memory from a previous loop learn or PC upload you will be asked if you want to erase this information before the loop learn begins Erase ALL loop device data first You now have two options as detailed below Option 1 If the panel has not previously been programmed or if
70. viewed by pressing the panel s More Information button To return to the main access level 3 menu press the Escape 4 button Display Disablements This function is only available when there are active disablements on the system If available press the Accept button and a window similar to the one overleaf will appear 1st Zone 1 Shop floor On This Panel Is Disabled Pressing the and buttons will scroll the display through all active disablements More detailed information if applicable can be viewed by pressing the panel s More Information button To return to the main access level 3 menu press the Escape 4 button Display Zones In Test This function is only available if one or more zones are being tested If available press the Accept button and a window similar to the one below will appear Zone 1 North Stairs Is On Test Pressing the and buttons will scroll the display through all zones currently in test More detailed information if applicable can be viewed by pressing the panel s More Information button To return to the main access level 3 menu press the Escape 4 button Setup Passwords This function allows you to change the four digit access codes required to activate the panel s access level 2 or 3 menu options When selected press the Accept 7 button and the following window will appear CHANGE ACCESS LEVEL 2 CODE Change Access Level 3 code Use the and buttons to
71. when the environmental conditions outside the enclosure comply with class 3k5 of IEC 721 3 3 1978 Temperature range 5 to 40 C Maximum relative humidity 95 XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 36 of 36
72. y outputs Relays 1 2 and 3 can be programmed using the panel s PC programming software tools to operate as required but their default operations are XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 10 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Relay 1 Switches when any zone goes into fire switches back when the panel is silenced Relay 2 Switches when any zone goes into fire switches back when the panel is reset Relay 3 Has no default operation The wiring for each output should be connected to Fig 8 Relay output detail the relevant connector block on the Main Control PCB remember to isolate the panel s Mains and battery NOG NO ONO NOG WO no cino backup supplies before making any connections v ee v 00199090 Fig 8 right explains how the outputs work Remote PC connection Fig 9 Connecting a PC to the panel s RS232 connector A four way RS232 molex connec tor is provided on the Main Control PCB for the connection 20K 9 10 zoen 2 12 e E of a Windows based PC for pro m 7 a s NVM memory unlock link must be fitted when gramming purposes The ONLY way to program this fire panel is uploading or downloading using a PC loaded with the information from to the PC panel s sophisticated program FE ee SS ming tools Part No XFP507 2 The l
73. you fit this link as a matter of course whenever you are in access level 3 Q O ZDNE9 ZONE 10 ZONE Remember to re lock the memory remove the link when Ops programming is complete to guard against data corruption If you do not re lock the memory a reminder message will appear when you leave access level 3 A detailed description of the functions available at access level 3 can be found overleaf XFP ENGINEERING MANUAL Approved Document No DFU1200510 Rev 1 Page 18 of 36 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL Display Fire Events This function is only available if there are active fire conditions on the system If available press the Accept 7 button and a window similar to the one below will appear Last Zone 1 North Stairs Fire 1 Zone Pressing the and buttons will scroll the display through all active fire conditions More detailed information if applicable can be viewed by pressing the panel s More Information button To return to the main access level 3 menu press the Escape 4 button Display Fault Events This function is only available if there are active faults on the system If available press the Accept gt button and a window similar to the one below will appear Zone 1 Ground Floor There are faults on this zone Pressing the and buttons will scroll the display through all active faults More detailed information if applicable can be
Download Pdf Manuals
Related Search
Related Contents
ficha técnica producto: plastico famaelastic esp.revestimiento 基礎知識 Weider WEEVSY8721 User's Manual OWNER`S MANUAL T。SH ー BA 保管用 HS40 tuning manual John Deere OMGX10742 J9 User's Manual Notice - Jardiland Formation mesures d`urgence lors d`intoxication aux cyanures Jensen XA2150 Car Amplifier User Manual Copyright © All rights reserved.
Failed to retrieve file