FX3UC-4AD INSTALLATION MANUAL

image

Contents

1. eg 4 8 Mass Weight Approx 130g 0 29lbs 1 Status indicator LED PW Green Lit while 5 V power is normally supplied from PLC 24V Red Lit while 24V power is normally supplied from power supply A D Red Flashes during A D conversion 2 Terminal block European type Wiring of the voltage and current input 3 Connector PLC side Used to fix extension block on right side 4 DIN rail mounting hook 5 Slide lock Used to connect the FX3UC main unit extension block 6 Connector Extension side Used to connect extension block on right side of this special block Remove this cover for connecting 7 Power connector 24V DC The connector for supplying 24V power supply to 4AD 8 Power crossover connector Used to supply power supply to the extension block 4 Installation The 4AD can be installed on a DIN46277 rail 35 mm 1 38 wide INSTALLATION PRECAU TIONS DANGER e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product INSTALLATION PRECAU TIONS CAUTION e Use screwdrivers carefully when performing installation work thus avoiding accident or product damage e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust
2. Associated Manuals Manual name Description FX3U FX3UC Series User s Manual Analog Control Edition FX3U FX3UC Series Programming Manual Basic amp Applied Instruction Edition Describes specifications for analog control and programming method for FX3U FX3UC Series PLC JY997D16701 MODEL CODE 09R619 JY997D16601 Describes PLC programming for basic applied instructions and devices MODEL CODE 09R517 Explains the FX3UC Series PLC specifications for I O wiring installation and maintenance FX3UC Series User s Manual Hardware Edition JY997D28701 MODEL CODE 09R519 How to obtain manuals For product manuals or documents consult with the Mitsubishi Electric dealer from who you purchased your product Certification of UL cUL standards The following product has UL and cUL certification UL cUL File Number E95239 Models MELSEC FX3UC series manufactured FX3UC 4AD Compliance with EC directive CE Marking This note does not guarantee that an entire mechanical module produced in accordance with the contents of this note will comply with the following standards Compliance to EMC directive and LVD directive for the entire mechanical module should be checked by the user manufacturer For more details please contact the local Mitsubishi Electric sales site Requirement for Compliance with EMC directive The following products have shown compliance through direct testing of the identi
3. oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or exposed to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Connect FX3U 4AD securely to their designated connectors Loose connections may cause malfunctions Up to 8 units can be connected to the FX3uc Series PLC 1 Up to 7 units can be connected to the FX3UC 32MT LT PLC 4 1 Connection to the PLC 1 2 3 4 5 4 2 1 2 3 Turn off the power Disconnect all the cables connected to the PLC and demount the PLC from the DIN rail Remove the extension block connector cover on the main unit extension block Slide the special block slide lock of the main unit extension block The 4AD connector PLC side is connected to the main unit extension block connector whose cover was previously removed see the following figure Slide back the slide lock of the main unit extension block to attach the 4AD Main unit Installation In Enclosure Push out all DIN rail mounting hooks Fit the upper edge of the DIN rail mounting groove onto the DIN rail DIN46277 rail 35 mm 1 3
4. For the 4AD the nine kinds of input characteristics are provided for each input Series main unit e Do not drop the product or exert strong impact to it mode Doing so may cause damage For the details of the input character refer to the following FX2NC 100BPCB WIRING PRECAUTIONS CAUTION 1 Connection example with the power supply through crossover wiring to the FX2NC input extension block DISPOSAL CAUTION ae Input mode Analog Digital output Resolu AN input range range tion FX2NC Series PLC FX3UC 4AD PRECAUTIONS Set value e Please contact a certified electronic waste disposal company for the Voltage innutmod 10 to 10V 32000 to 2mV Terminal environmentally safe recycling and disposal of your device 9 PSE PEP 32000 Uem block 1 Voltage input mode 10 to 10V 4000 to 4000 2 50mV TRANSPORT AND STOR AGE PRECAUTIONS NCAUTION Voltage input mode 10000 to 2 Analog value direct 10 to 10V 10000 1 00mV e The product is a precision instrument During transportation avoid any impacts indication Failure to do so may cause failures in the product After transportation verify the operations of the product 3 Current input mode 4 to 20mA 0 to 16000 1 25pA Current input mode 4 to 20mA 0 to 4000 5 00nA Current input mode FX3UC Series PLC Ver 1 30 or later 5 Analog value direct 4000 to 20000 1 25uA From the production manufactured in August 2004 with SER indication No 48 Current input mode Zoto HORN to
5. loose wires Do not solder plate the electric wire ends 2 Connection example to the external power supply Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed FX3UC Series PLC Main unit Power crossover connector connector Power connector A 6 1 Applicable PLC FX2NC 10BPCB1 FX2NC 100BPCB Power crossover cable Power cable Applicable PLC O O Q o n o w O 5 2 5 Q O FX3UC Series PLC Main unit 5 1 Wire and Terminal Tightening Torque 5 1 1 Cable A D conversion circuit driving 24V DC 10 80mA 9 to E Not used ij Applicable cable power 24V DC power is supplied from the power connector F No channels used Type Wire size Interface driving 5V DC 100mA l l l 5V DC power is supplied from the internal power supply of main Single wire 0 3mm to 0 5mm2 AWG22 to 20 sia power unit it is not necessary to prepare power supply Double wire 0 3mm AWG22 2 6 4 Performance Specifications FX2NC 100BPCB Power cable Specifications 2 Termination Item Strip the coating of strand wire and twist the cable core before connecting it 24V 7 Volt t C ti t or strip the coating of single wire before connecting it An alternative DC h Class D grounding dire ee connection is t
6. rise enter the ventilation slits 3 Realm Failure to do so may cause fire equipment failures or malfunctions te Connect FX3U 4AD securely to their designated connectors Bi Loose connections may cause malfunctions For installation uninstallation Refer to the FX3UC Series User s Manual 4 E Hardware Edition C Up to 8 units can be connected to the FX3uc Series PLC 1 Up to 7 units can be connected to the FX3UC 32MT LT PLC 5 Wiring Power supply and analog input 5 3 Power supply wiring 6 Specifications 1 Change the offset and gain values to change the input characteristics However the resolution doesn t change even when the offset and gain values change In the direct indication mode however the offset gain cannot be adjusted Supply the 24V DC power to 4AD via the power supply connector PRECAUTIONS lt gt DANGER Model e Make sure to cut off all phases of the power supply externally before FX2NC 10BPCB1 attempting installation or wiring work Failure to do so may cause electric shock or damage to the product STARTUP AND MAINTE Application NANCE PRECAUTIONS Z CAUTION Power crossover cable offered as an accessory for the FX3UC 4AD 2 The resolution depend on the input mode e Do not disassemble or modify the PLC Doing so may cause fire equipment failures or malfunctions 6 5 Input characteristics Power cable offered as an accessory for the FX3UC For repair contact your local Mitsubishi Electric distributor
7. 1 25uA 6 2 General Specifications 20mA 16000 The general specifications are equivalent to the PLC main unit 20 to For general specifications refer to the manual of the PLC main unit 7 Current input mode 20mA 4000 to 4000 5 00HA 6 3 Power Supply Specifications Current input mode 20 to 20000 to ne 8 Analog value direct 5g 20000 1 25uA erung Item Specifications indication 5 block e Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due to abnormal data written to the PLC under the influence of noise 1 Do not bundle the main circuit line together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take place As a guideline lay the control line at least 100mm 3 94 or more away from the main circuit or high voltage lines 2 Ground the shield wire or shield of the shielded cable at one point on the PLC However do not use common grounding with heavy electrical systems e Make sure to properly wire to the European terminal board in accordance Black Green Black with the following precautions Failure to do so may cause electric shock a short circuit wire breakage or damage to the product The disposal size of the cable end should be 9mm 0 35 Tightening torque should be between 0 22 and 0 25 Nem 24V Twist the end of strand wire and make sure that there are no
8. 8 wide Lock the DIN rail mounting hooks while pressing the PLC against the DIN rail For installation uninstallation Refer to the FX3UC Series User s Manual Hardware Edition 5 Wiring Power supply and analog input DANGER e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product WIRING PRECAUTIONS WIRING PRECAUTIONS CAUTION e Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due to abnormal data written to the PLC under the influence of noise 1 Do not bundle the main circuit line together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take place As a guideline lay the control line at least 100mm 3 94 or more away from the main circuit or high voltage lines 2 Ground the shield wire or shield of the shielded cable at one point on the PLC However do not use common grounding with heavy electrical systems e Make sure to properly wire to the European terminal board in accordance with the following precautions Failure to do so may cause electric shock a short circuit wire breakage or damage to the product The disposal size of the cable end should be 9mm 0 35 Tightening torque should be between 0 22 and 0 25 N
9. A 0 to 4000 5 00nA Current input mode 5 Analog value direct 4to20mA 4000 to 20000 1 25nA indication 20 to 16000 to Current input mode O 20 to 7 Current input mode 20mA 4000 to 4000 5 00uA Current input mode f 20 to 20000 to 8 Analog value direct 20mA 20000 1 25nA indication 9toE Not used F No channels used This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict
10. C AnD block 1 shield VOi I cho the channel number represents 1 Use the 2 core shielded twisted pair cable for the analog input lines and separate the analog input lines from the other motive power lines or inductive lines 2 To use the current input be sure to short circuit the line between the VO terminal and the IL terminal O channel number 3 The SLD and T terminals are connected to each other inside 4 Do not connect any lines to the e terminal 6 Specifications STARTUP AND MAINTE NANCE PRECAUTIONS CAUTION e Do not disassemble or modify the PLC Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric distributor e Do not drop the product or exert strong impact to it Doing so may cause damage DISPOSAL PRECAUTIONS CAUTION e Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device TRANSPORT AND STOR AGE PRECAUTIONS CAUTION e The product is a precision instrument During transportation avoid any impacts Failure to do so may cause failures in the product After transportation verify the operations of the product 6 1 Applicable PLC FX3UC Series PLC
11. SHI ELECTRIC CORPORATION Occupied points 8 point Count either the input or output points of the PLC HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN Manufacturer
12. Ver 1 30 or later From the production manufactured in August 2004 with SER No 48 Applicable PLC 6 2 General Specifications The general specifications are equivalent to the PLC main unit For general specifications refer to the manual of the PLC main unit 6 3 Power Supply Specifications Item Specifications A D conversion circuit driving power 24V DC 10 80mMA 24V DC power is supplied from the power connector 5V DC 100mA 5V DC power is supplied from the internal power supply of main unit it is not necessary to prepare power supply Interface driving power 6 4 Performance Specifications Specifications Item Voltage input Current input Analog input 10 to 10V DC 20 to 20mA 4 to 20mA DC range Input resistance 200 KQ Input resistance 250 Q Offset 10 to 9V 20 to 17mA BE 10V or less 30mA or less oan Gain Offset gt 1V Gain Offset 3mA Maximum 30mA Digital output Effective numeric value 9 P 15bits Sign bit 0 32mV 20Vx1 64000 2 50mV 20Vx1 8000 Effective numeric value 14bits Sign 41bit 1 25mA 40mAx1 32000 5 00uA 40mAx1 8000 e 0 5 200nA for full scale of 40mA when ambient temperature is 25 C 5 C and a current of 20 mA to 20 mA is input Resolution e 0 3 60mV for full scale of 20V when ambient Same when input is 4mA to temperature is 25 C 5 C 20mA 100mV for full e 1 0 400A for full scale of 40mA when ambi
13. ck connector whose cover was previously removed see the following figure 5 Slide back the slide lock of the main unit extension block to attach the 4AD 4 Remark Compliance with all relevant aspects of the standard EMI e Radiated Emissions e Mains Terminal Voltage Emissions 8 2004 Mitsubishi Electric Corporation EMS Mass Weight Approx 130g 0 29Ibs RF immunity e Fast Transients Safety Precaution Read these precautions before use e ESD This manual classifies the safety precautions into two categories j Bae e 1 Status indicator LED Londucte PW Green Lit while 5 V power is normally supplied from PLC DANGER and A CAUTION e Power magnetic fields 24V Red Lit while 24V power is normally supplied from power supply Main unit A D Red Flashes during A D conversion Indicates that incorrect handling may cause hazardous Caution for EC Directive 2 Terminal block European type 42 Installation In Enclosure lt gt DANGER conditions resulting in death or severe injury The FX3UC 4AD have been found to be compliant to the European standards in Wiring of the voltage and current input 1 Push out all DIN rail mounting hooks the aforesaid manual and directive However for the very best performance 3 Connector PLC side Indicates that incorrect handling may cause hazardous from what are in fact delicate measuring and control
14. em Twist the end of strand wire and make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed 5 1 Wire and Terminal Tightening Torque 5 1 1 Cable 1 Applicable cable Type Wire size Single wire 0 3mm to 0 5mm AWG22 to 20 Double wire 0 3mm AWG22 2 2 Termination Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of single wire before connecting it An alternative connection is to use a ferrule with insulating sleeve Al 0 5 8WH e Bar terminal with insulating sleeve Pressure bonding tool CRIMPFOX ZA 3 or CRIMPFOX UD 6 Manufacturer Phoenix Contact e Stranded wire solid wire Insulating sleeve Contact area IN Crimp area 2 6mm 0 11 Termination of cable end dif 9mm 0 36 When using a stick terminal with an insulating sleeve choose a wire with proper cable sheath referring to the above outside dimensions otherwise the wire cannot be inserted easily 5 1 2 Tightening Torque Tightening torque should be between 0 22 and 0 25 Nem 5 2 Tool To tighten terminals use a purchased With small sized screwdriver whose head is straight tip straight and is not widened as shown in the right figure 0 4mm 2 5mm N
15. ent temperature is 25 C 5 C and a current of 20 mA to 20 mA is input Same when input is 4mA to 20mA Total accuracy 0 5 scale of 20V when ambient temperature is 0 C to 55 C 500us x number of selected channels A D conversion If channels use the digital filter s 5ms x number of selected time channels e The photo coupler insulates the analog input area from the Insulati PLC ede e The DC DC converter insulates the analog input area from the power supply unit e Channels are not insulated from each other Occupied points 8 point Count either the input or output points of the PLC Change the offset and gain values to change the input characteristics However the resolution doesn t change even when the offset and gain values change In the direct indication mode however the offset gain cannot be adjusted 2 The resolution depend on the input mode 6 5 Input characteristics For the 4AD the nine kinds of input characteristics are provided for each input mode For the details of the input character refer to the following Input P mode Inputmode Aea e Distal output Rea Set value P g g 32000 to 0 Voltage input mode 10 to 10V 32000 0 32mV 1 Voltage input mode 10 to 10V 4000 to 4000 2 50mV Voltage input mode 2 Analog value direct 10 to 10V tOnOU to 1 00mV eae 10000 indication 3 Current input mode 4 to 20mA 0 to 16000 1 25uA A Current input mode 4 to 20m
16. fied standards below and design analysis through the creation of a technical construction file to the European Directive for Electromagnetic Compatibility 89 336 EEC when used as directed by the appropriate documentation Type Programmable Controller Open Type Equipment Models MELSEC FX3uC series manufactured from October 1st 2007 FX3UC 4AD Standard EN61131 2 2003 Programmable controllers Equipment requirements and tests Remark Compliance with all relevant aspects of the standard EMI e Radiated Emissions e Mains Terminal Voltage Emissions EMS RF immunity e Fast Transients e ESD e Surge e Conducted e Power magnetic fields Caution for EC Directive The FX3UC 4AD have been found to be compliant to the European standards in the aforesaid manual and directive However for the very best performance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered care fully For users of proprietary cables integral with sensors or actuators these users should follow those manufacturers installation requirements Mitsubishi Electric recommend that shielded cables should be used If NO other EMC protection is provided then users may experience temporary loss or accuracy between 10 in very heavy industrial areas However Mitsubishi Electric suggest that
17. from the other motive power lines or inductive 20mA industries and has not been designed or manufactured to be incorporated in Note 0 02 0 7 lines a device or system used in purposes related to human life l If the diameter of screwdriver grip is too Se gt ler 2 To use the current input be sure to short circuit the line between the VO AID conversion 500us x number of selected channels e Before using the product for special purposes such as nuclear power electric small tightening torque will not be able terminal and the IO terminal O channel number time If channels use the digital filter s 5ms x number of selected power aerospace medicine or passenger movement vehicles consult with to be achieved Use the following recommended screwdriver or an appropriate channels Mitsubishi Electric l l replacement grip diameter approximately 25mm 3 The SLD and terminals are connected to each other inside e The photo coupler insulates the analog input area from the e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the 4 Do not connect any lines to the e terminal insulation PEG product fails install appropriate backup or failsafe functions in the system e The DC DC converter insulates the analog input area from the method Phoenix Contact SZS 0 4X2 5 power supply unit e Channels are not insulated from each other A MITSUBI
18. g of the identified September 2007 standards below and design analysis through the creation of a technical construction file to the European Directive for Electromagnetic Compatibility 89 336 EEC when This manual describes the part names dimensions mounting and used as directed by the appropriate documentation specifications of the product Before use read this manual and the manuals of Type Programmable Controller Open Type Equipment all relevant products fully to acquire proficiency in handling and operating the Models MELSEC FX3UC series manufactured product Make sure to learn all the product information safety information and from October 1st 2007 FX3UC 4AD precautions Store this manual in a safe place so that it can be taken out and read whenever Standard necessary Always forward it to the end user Registration EN61131 2 2003 The company and product names described in this manual are registered Programmable controllers trademarks or the trademarks of their respective companies Equipment requirements and Effective September 2007 tests Specifications are subject to change without notice 2 Remove the extension block connector cover on the main unit extension block KCYCYKSCVKHSGNg 90 3 55 CYCVPGSC VSS NV Ns 3 Slide the special block slide lock of the main unit extension block 4 The 4AD connector PLC side is connected to the main unit extension blo
19. if adequate EMC precautions are fol lowed for the users complete control system users should expect accuracy as specified in this manual e Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling Where possible users should run analog cables separately e Good cable shielding should be used Ground the shield of the twisted shielded cable at one point on the PLC side e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the special function block for analog input or through a users program in the FX3UC Series PLC main unit e Please use FX3UC 4AD while installed in a shielded enclosure For the details refer to the following manual Refer to the FX3Uc Series User s Manual Hardware Edition 1 Outline The FX3UC 4AD special function block for analog input converts four analog input values voltage current to digital values and transfers those digital values to the PLC main unit For the purpose of this manual the FX3UC 4AD will from here be referred to as the 4AD 2 Incorporated Items Verify that the following product and items are included in the package FX2NC 10BPCB1 Power crossover cable Product Manual Special unit block No label i ed H This 4 manual 3 External Dimensions Part Names and Terminal Layout 15 2 0 6 5 74 2 92
20. in the same trunking or cable f 5 conduit as high voltage cabling Where possible users should run analog 4 Installation 2 PI mhe APPa eee ore DN FX3U FX3UC Series Describes specifications for cables separately eons rail mounting groove onto the i JY997D16701 The 4AD can be installed on a DIN46277 rail 35 mm 1 38 wide DIN rail User s Manual MODEL CODE nalog control and e Good cable shielding should be used Ground the shield of the twisted DIN46277 rail 35 mm 1 38 Analog Control 09R619 programming method for FX3U shielded cable at one point on the PLC side INSTALLATION PRECAU i Edition FX3UC Series PLC DANGER wide e When reading analog values EMC accuracy can be improved out by TIONS FX3U FX3UC Series ioorpanees averaging the readings This can be achieved either through functions on the Programming Manual Describes PLC programming special function block for analog input or through a users program in the e Make sure to cut off all phases of the power supply externally before attempting i 8 MODEL CODE for basic applied instructions FX3UC Series PLC main unit llati n k Basic amp Applied 09R517 and devic s installation or wiring work Instruction Edition e Please use FX3uc 4AD while installed in a shielded enclosure For the Failure to do so may cause electric shock or damage to the product TE mex a details refer to the following manual xplains the 3UC Series P i fees ee Ko a PLC specifications for I O Refer
21. led output device Mitsubishi Used to fix extension block on right side Z CAUTION conditions resulting in medium or slight personal injury Electric would like to make the following points 4 DIN rail mounting hook or physical damage As analog devices are sensitive by nature their use should be considered care 5 Slide lock fully For users of proprietary cables integral with sensors or actuators these Used to connect the FX3UC main unit extension block Depending on the circumstances procedures indicated by CAUTION may users should follow those manufacturers installation requirements 6 Connector Extension side also cause severe injury Acaurion Mitsubishi Electric recommend that shielded cables should be used If NO other Used to connect extension block on right side of this special block It is important to follow all precautions for personal safety EMC protection is provided then users may experience temporary loss or Remove this cover for connecting accuracy between 10 in very heavy industrial areas 7 Power connector 24V DC However Mitsubishi Electric suggest that if adequate EMC precautions are fol The connector for supplying 24V power supply to 4AD A iated M lowed for the users complete control system users should expect accuracy as 8 Power crossover connector ssociate anuals specified in this manual Used to supply power supply to the extension block Manual name Description e Sensitive analog cable should not be laid
22. o use a ferrule with insulating sleeve i Analog input 10 to 10V DC 20 to 20mA 4 to 20mA DC n e Ground the terminal to the Class D grounding line 100 Q or less together range Input resistance 200 kQ Input resistance 250 Q Manufacturer Model Pressure bonding tool with the ground terminal of the main unit 7 CRIMPFOX ZA 3 e Remove the resin cover from the power crossover connector and perform crossover Offset 10 to 9V 20 to 17mA Phoenix Contact Al 0 5 8WH or CRIMPFOX UD 6 wiring to connect the power line from 4AD to a succeeding extension block P 10V or less 30mMA or less Gain 5 4 Wiring of Analog Input Gain Offset 1V Gain Offset 3mA e Stranded wire solid wire e Bar terminal with insulating sleeve g g np For the terminal layout refer to Chapter 3 Maximum Termination of Insulating sleeve Contact area absolute input 30MA cable end Crimp area FX3UC 4AD selected I Digital output Effective numeric value Effective numeric value Imm a 1 shield h 15bits Sign bit 14bits Sign 1bit 0 36 COCO 7 0 32mV 20Vx1 64000 1 25mA 40mAx1 32000 This manual confers no industrial property rights or any rights of any other kind Resolution 2 50mV 20Vx1 8000 5 00uA 40mAx1 8000 nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be 2 6mm held responsible for any problem
23. ote If the diameter of screwdriver grip is too 0 02 te aj ew small tightening torque will not be able to be achieved Use the following recommended screwdriver or an appropriate replacement grip diameter approximately 25mm Manufacturer Phoenix Contact SZS 0 4X2 5 5 3 Power supply wiring Supply the 24V DC power to 4AD via the power supply connector Model Application Power crossover cable offered as an accessory for the FX2NC 10BPCB1 FX3UC 4AD Power cable offered as an accessory for the FX3UC FX2NC 100BPCB f f Series main unit 1 Connection example with the power supply through crossover wiring to the FX2NC input extension block FX3UC Series PLC Main unit FX3Uc 4AD FX2NC Series PLC Terminal block Power crossover connector connector Power connector FX2NC 10BPCB1 Power crossover cable FX2NC 100BPCB Power cable FX3UC Series PLC Main unit Terminal block FX2NC 100BPCB Power cable DC h Class D grounding e Ground the teder terminal to the Class D grounding line 100 Q or less together with the ground terminal of the main unit e Remove the resin cover from the power crossover connector and perform crossover wiring to connect the power line from 4AD to a succeeding extension block 5 4 Wiring of Analog Input For the terminal layout refer to Chapter 3 If current input is selected gt Terminal RAS
24. quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system a MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN side JY997D14901C A B K E JAPANESE B ENGLISH Changes for the Beiter Certification of UL cUL standards 3 External Dimensions Part Names and Terminal Layout 4 1 Connection to the PLC g The following product has UL and cUL certification 20 2 15 1 Turn off the power MITSUBISHI UL cUL File Number E95239 0 8 2 0 6 74 2 92 5 Disconnect all the cables connected to the PLC and demount the PLC from Models MELSEC FX3UC series manufactured the DIN rail PROGRAMMABLE CONTROLLERS FX3UC 4AD MELSTEG IF WS FX3UC 4AD Compliance with EC directive CE Marking This note does not guarantee that an entire mechanical module produced in N STAL LAT O N MAN UAL accordance with the contents of this note will comply with the following standards Compliance to EMC directive and LVD directive for the entire mechanical module should be checked by the user manufacturer For more details please contact the Manual Number JY997D14901 local Mitsubishi Electric sales site 3 Requirement for Compliance with EMC directive 3UC The following products have shown compliance through direct testin
25. s involving industrial property rights which may 0 11 EAN e 0 5 200uA for full scale occur as a result of using the contents noted in this manual of 40mA when ambient When using a stick terminal with an insulating sleeve choose a wire with temperature is 25 C 5 C Warranty proper cable sheath referring to the above outside dimensions otherwise the gt and a current of 20 mA to Mitsubishi will not be held liable for damage caused by factors found not to be wire cannot be inserted easily e 0 3 60mV for full scale 20 mA is input the cause of Mitsubishi opportunity loss or lost profits caused by faults in the 5 1 2 Tightening Torque gt ae Sai ae TAA when input is 4mA to le A a ela a orien wera ees vase E i emperature is 25 C 5 m caused by special factors unpredictable by Mitsubishi damages to products Teena i a ane ee Ne Total aceuiacy 40 5 4100mV for full 1 0 400pA for full scale other than Mitsubishi products and to other duties 5 2 Tool ae icho E represents scale of 20V anen ambient of 40mA when ambient small sized screwdriver whose head is straight tip 20 mA is input straight and is not widened as shown in 1 Use the 2 core shielded twisted pair cable for the analog input lines and Same when input is 4mA to This product has been manufactured as a general purpose part for general the right figure ja 5 separate the analog input lines
26. side JY997D14901C B Side JAPANESE ENGLISH Changes for the Better sa MITSUBISHI PROGRAMMABLE CONTROLLERS MELSEG F FX3UC 4AD INSTALLATION MANUAL SUC i star This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective September 2007 Specifications are subject to change without notice 2004 Mitsubishi Electric Corporation Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories RODANGER and CAUTION Indicates that incorrect handling may cause hazardous lt gt DANGER conditions resulting in death or severe injury Indicates that incorrect handling may cause hazardous Z CAUTION conditions resulting in medium or slight personal injury or physical damage Depending on the circumstances procedures indicated by A CAUTION may also cause severe injury It is important to follow all precautions for personal safety
27. to the FX3UC Series User s Manual Hardware Edition INSTALLATION PRECAU AUTEN a i wiring installation and A F Hardware Edition 09R519 ATA A 1 Outline TIONS 3 Lock the DIN rail mounting hooks while pressing the PLC against the DIN The FX3UC 4AD special function block for analog input converts four analog input e Use screwdrivers carefully when performing installation work thus avoiding accident Fall values voltage current to digital values and transfers those digital values to the PLC or product damage How to obtain manuals main unit For the purpose of this manual the FX3UC 4AD will from here be referred to e Use the product within the generic environment specifications described in PLC main For product manuals or documents consult with the Mitsubishi Electric dealer as the 4AD unit manual Hardware Edition from who you purchased your product Never use the product in areas with excessive dust oily smoke conductive dusts 2 Incorporated Items corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts Verify that the following product and items are included in the package or exposed to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions Product Manual Special unit block FX2NC 10BPCB1 deterioration or damage may occur No label Power crossover cable When drilling screw holes or wiring make sure cutting or wire debris does not