Home
Ponto Series CPUs PO3x42
Contents
1. 5 fa 1 g a ji O I A I I O i g a 4 z 4 I I I Re rT f SF T gt TA F othe d O 3 b 3 NR i es r EEEE U mo g 3 a Ei N m h 99 0 L 101 8 J Manuals For correct application and utilization the User s Manual CPU Ponto Series must be consulted For further technical details configuration installation and programming of products from Ponto Series please consult following documents Document Code CT109000 Characteristics and Configuration from Ponto Series MU209000 User s Manual Ponto Series IP20 mu299025 Users Manual Mastertooi mtaro ba oe Technical Characteristics CEs from Ponto Series Modules Altus S A 10
2. are referred to the most completed model the PO3342 Available on firmware version 2 00 or greater or product revision AS or greater Ordering Information Included Items The product packing comes with e CPU PO3042 or PO3142 or PO3242 or PO3342 e Installation Guide Product Code Use the following codes when ordering the product Code Description S PO3042 CPU 128K Flash 16 I O Modules 2 Serial MODBUS PO3142 CPU 256K Flash 30 I O Modules 3 Serial MODBUS CPU 256K Flash 30 I O Modules 2 Serial MODBUS PROFIBUS Ethernet CPU 256K Flash 30 I O Modules 2 Serial MODBUS PROFIBUS WebServer Altus S A 1 Ponto Series CPUs PO3x42 Cod Doc CE109104 Revis o J Related Products Depending on your system requirements the following products might be ordered along with the CPU 3 i i PO6302 Base to CPUs PO3042 PO3142 PO3242 and PO3342 AL 1715 Cable assembled with one RJ45 connector and one RS 232 9 pin male sub D connector IBM PC standard It is used on COM1 and COMS to connect the following equipment MMI which uses IBM PC standard connector for local supervision IBM PC standard microcomputer with supervision software IBM PC standard microcomputer to UCP programming through MasterTool Software AL 1718 Cable assembled with one RJ45 connector and one RS 232 9 pin male sub D connector Altus standard It is used on COM1 and COM3 to connect the following equipment AL 1413 module RS
3. connector e Serial Port RS 485 isolated COM 2 Connection with equipment that use MODBUS protocol The port is isolated adequate to network implementation e Serial Port RS 232 COM 3 Connection to local MMI via RJ45 connector The COM 1 and COM 3 ports can use modems or radio modems Some options of connection with these ports are FOTON 1 FOTON 3 FOTON 5 and FOTON 10 Supervision software any that understand ALNET I v2 0 protocol COM 2 RS 485 o MODBUS COM 1 RS 232 Altus S A 7 Ponto Series CPUs PO3x42 Cod Doc CE109104 Revisao J Local Bus I O Capacity The CPU has the following limits for local I O PO3142 10 gt e Maximum number of modules 30 e Maximum number of segments 4 e Maximum number of module by segment 10 e The maximum number of points depends of the each type The limit for digital points is 960 The limit for analog points is 240 a A Baj m E coon a a a a a a eM TASSR m For further details see User s Manual Ponto Series SS Se af mH eT SS SS SI Local bus scan time The communication between the CPU or head is based on a high speed bus which is implemented with a unique chip achieving in this way unsurpassed acquisition and parameterization speed The main features of this bus are e 12Mbaud serial bus 0 5 ms scan time for 480 digital points e Automatic addressing and module identification KEEK 12 M
4. 232 RS 485 Converter AL 1719 Cable assembled with one RJ45 connector and one RS 232 9 pin male sub D connector Altus standard It is used on COM1 and COM3 to connect the following equipment Foton 5 or Foton 10 MMI AL 1720 Cable assembled with one RJ45 connector and one RS 232 RS 485 9 pin male sub D connector Altus standard It is used on COM1 and COMS to connect the following equipment Foton 1 or Foton 3 MMI AL 1731 Cable assembled with one RJ45 connector and one RS 485 9 pin male sub D connector Altus standard It is used on COM2 to connect the PO8525 module AL 2301 Shielded cable with two pairs no connectors It is used on RS 485 network Connecting an RS 485 network between two or more AL 2600 or PO8525 maximum length of 1000 meters Altus S A 2 Ponto Series CPUs PO3x42 Sng te pO pn UNOS we Cod Doc CE109104 Revis o J AL 2306 Shielded cable with two pairs no connectors It is used on RS 485 network e Connecting an RS 485 network between two or more AL 2600 or PO8525 maximum length of 500 meters AL 2600 This module helps to connect a RS 485 network AL 2301 cable to the AL 2305 cable PO8525 This module can be use to connect the CPU to a RS 485 network It has two terminals to network derivation termination resistors and one RJ45 connector The serial port COM2 is connected to this module through the AL 1731 cable MT6000 MasterTool ProPonto The ProPonto allows the definition of modules to b
5. Ponto Series CPUs PO3x42 Cod Doc CE109104 Revis o J Product Description The Ponto Series CPUs present an extended integration of functions on line programming high memory capacity and integrated serial ports The PO3142 model has three serial interfaces to programming local supervision and MODBUS network The CPUs communicate through the GBL bus creating a compact control and supervision system With the use of network interfaces the CPUs can control up to 4 096 I O points Main features e Direct access to 30 I O modules through Ponto Series bus e Capacity up to 4 096 I O points e High speed processing adequacy to complex and extensive systems e Communication to PROFIBUS networks e 2 RS 232 serial ports with configurable and programmable protocols including MODBUS master or slave e 1 Isolated RS 485 serial port with configurable and programmable protocols including MODBUS master or slave e Great Flash memory capacity up to 512 Kbytes for application program e It allows PROFIBUS DP Master Interface e Connectivity to Ethernet network e WebServer characteristics e Diagnostic and status operation via LEDs indicators on front panel e Diagnostic information via operands e Floating point operand F e 24 Vdc internal power supply with capacity of 12 modules along two segments e Floating Point operand F e Unsigned integer 32 bits operand l e Identification label These characteristics
6. The CPUs PO3x42 includes an internal power supply which is feed with 24 Vdc The power supply supports up to 12 I O modules distributed on two segments If it is necessary the use of more I O modules the PO8085 power supply must be installed in the beginning of the segment MODBUS Protocol The MODBUS protocol is available on PO3042 CPU from firmware version 2 00 or greater MasterTool Programming to use MODBUS protocol in PO3042 CPU or l operand it is necessary MasterTool Programming version 3 90 or greater Altus S A 4 Ponto Series CPUs PO3x42 Cod Doc CE109104 Revis o J General Characteristics Module type analog points demands 11 PROFIBUS analog remotes Local bus rate Retentive memory P es Real Time Clock es es Watchdog Battery for retentive operands Inside the base hot swap Connector configuration 1 RJ45 connector RJ45 COM 1 PO6302 Base 1 DB9 connector DB9 COM 2 1 RJ45 connector RJ45 COM 3 Status indication LEDs EX PG ER WD TX RX Diagnostic indication LED DG multifunctional Isolation 1500 Vac 1 minut ac 1 minute RS 485 Serial port RS 485 External power supply 19 a 30 Vdc including ripple maximum consumption 620 mA 24 Vdc fifteen I O modules Dimensions W x H x D mm Bases Serial Ports The Ponto Series CPUs have an optimal communication capability which provides a wide range of communication features They have up to 3 serial ports with the followin
7. baud gt 22 e Hot swap for any I O module Power Supply The CPUs have an internal power supply that can supply energy for up to 12 I O modules This power supply is fed by 24 Vdc power supply connected on the base terminals Using the software MasterTool ProPonto is possible to configure a CPU PO3x42 I O Modules greater number of modules because it is considered the individual current of each module Otherwise it is possible to have interface modules with greater consumption so the number of modules will decrease Base PO6302 Altus S A 8 Ponto Series CPUs PO3x42 Cod Doc CE109104 Revis o J Software Characteristics PO3042 PO3142 PO3242 PO3342 modules with functions and sub routines Input E and output S operands Auxiliary operands bits Memory operands M word 16bits Decimal operands D 32 bits BCD form signal Floating point operand F 32 bits IEEE 754 Memory table operand TM word 16bits Floating point table operand TF 32 bits IEEE Up to 255 tables with 255 positions each 754 Decimal table operand TD 32 bits BCD format Up to 255 tables with 255 positions each signal Memory constant KM 16 bits Stored in the application program Decimal constant KD 32 bits BCD form Stored in the application program signal Floating point constant 32 bits IEEE 754 Stored in the application program Typical memory occupation by contact 7 bytes instruction Memory
8. e installed in every bus thus facilitating the system design Main functions are e Graphical design of ProPonto ALTUS Exemplo1 GBL buses e Bus validation It checks items like power SSS consumption compatible a aay i iai ower Supply bases and design limits EE P08085 Power Supply E Segment e Tags definition It generates labels for module identification e List of materials e Label impression with identification tags The software runs in Windows 32 bits P04056 AS Interface PO7091 Ethernet Interface 0 Module l n PO1000 16 DI24Vde PO1001 16 DI 110 Vac PO1003 16 DI 48 Ydc gt PO1010 32 DI 24 Vdc P01112 8Al 1 V TCRDT F PO4051 Ethernet Interface n PO2022 16 DO Relay PO2132 4A0 1V Bus Verification Messages PO 079 Fast Counter X Expansion cable not found at segment s 0 end Base 1 Base without module at position 08 Base without module at position 09 Altus S A 3 Ponto Series CPUs PO3x42 Cod Doc CE109104 Revis o J Characteristics posoa2 Postaz Poszaz Possa2 Description CPU 128K Flash CPU 256K Flash CPU 256K Flash CPU 256K Flash 16 I O Modules 2 30 I O Modules 3 30 I O Modules 30 I O Modules Serial Interfaces Serial Interfaces PROFIBUS PROFIBUS Ethernet WebServer Application program memory 128K 256K 256K 256K Flash type Application program memory 256K 256K 256K 256K RAM type Maximum Modules ee ae a Max
9. g communication rates e Communication Rate bps COM1 9600 4800 2400 1200 600 300 COM2 38400 19200 9600 4800 2400 1200 600 300 COM3 38400 19200 9600 4800 2400 1200 600 300 The next table shows the protocols allowed by each port It is important to note that some protocols can be used simultaneity Altus S A 5 Ponto Series CPUs Cod Doc CE109104 Alnet slave Included on all CPUs complete ALNET I master functions Product AL 2702 only M tables writing and reading Communication Functions F Module Product AL 2703 It allows the programming of any serial protocol asynchronous MODBUS master Included on PO3142 PO3242 and PO3342 Not available on PO3042 model MODBUS slave Included on PO3142 PO3242 and PO3342 Not available on UCP PO3042 Line communication function Product It allows the communication via modem line Only with Digitel DT22B modems For further details see User s Manual and Technical Characteristics CEs of the listed protocols The following table presents some examples of combination COM1 COM 2 COM 3 MODBUS MODBUS MODBUS Example 02 Alnet slave MODBUS slave Altus S A PO3x42 Revis o J Ponto Series CPUs PO3x42 F Cod Doc CE109104 Revis o J The 3 serial ports can be used like the following way e Serial Port RS 232 COM 1 Connection to computer with the programming software MasterTool or local MMI via RJ45
10. imum number of Segments a ee ee PEET eee eee eee Maximum local I O points 256 using modules 480 using modules 480 using modules 480 using modules with 16 points with 16 points with 16 points with 16 points 512 using modules 960 using modules 960 using modules 960 using modules with 32 points with 32 points with 32 points with 32 points Maximum local analog I O points 128 using modules 240 using modules 240 using modules 240 using modules with 8 i with 8 ie with 8 points with 8 points Maximum I O points through 4096 4096 networks Network interface support PO4053 module Ethernet TCP IP interface support PO7091 module Ethernet TCP IP interface support with WebServer PO7091 module Serial interfaces 1 x RS 232 2 x RS 232 1 x RS 232 1 x RS 232 see Serial Ports item 1 x RS 485 1 x RS 485 1 x RS 485 1 x RS 485 COM1 e COM2 COM 1 COM2 e COM 1 COM2 COM 1 COM2 COM3 Serial port RS 232 COM1 Rts cts _ ATS CTS RTS CTS DSR Floating point operand F p _Yes_ ves MODBUS Protocol master re Power Power supply Embedded Embedded Embedded Embedded MasterTool Programming 3 40 or greater version 3 62 or greater version Software MT4100 or MT4000 ProPonto Configuration Software 1 35 or greater version 1 40 or greater version MT6000 Serial Interfaces The RS 232 ports use RJ45 connector with grounded shielding The RS 485 port uses DB 9 connector Power supply
11. retention Configurable for operands S A M D F Always active for TM TD e TF Permits the storage of great amounts of data in blocks with up to 32 Kbytes 2 5ms 3 125ms 5ms 10ms 25ms 50ms Programmable time for module E018 e The total number of 4096 digital I O points include inputs and outputs from local and remote buses The sum of E with S operands must be less or equal than the limit e All numeric operands KM KD KF KI M D F TM TD TF and TI allow arithmetic signal in the representation values The number of simple operands and tables M D F TM TD TF is configured by each program and is limited by the available memory capacity of operands 48 Kbytes e The feature of memory retention can be attributed to the operands S A M D F e through the programmer The retentive operands have their values preserved during power outage whereas the non retentive operands have their values zeroed The table operands are always retentive e l operand is available from firmware version 2 00 or greater or product revision AS or greater It is necessary MasterTool version 3 90 or greater to use it Altus S A 9 Ponto Series CPUs PO3x42 Cod Doc CE109104 Revis o J Installation The CPUs installation is described on the User s Manual Ponto Series CPUs Physical Dimensions mm dimensions