Home
WX 16_rev 1.1_EN (77036022-1)
Contents
1. Cannan Satai 04 Cal Resuired 12 Ortion Disabled vrase en 95 Cal Reauired 13 Ortion Disabled a6 Cal Resuired 14 Ortion Disabled Cal Rewiired Option Disabled We Gf Ei FS LE gt og Cal Resuired 16 Ortion Disabled C SSS Figure 2 16 2 4 Authorization Mode A password entered in the AUTHORIZATION menu allows locking all menus Viewing menus is not denied but attempts to edit variables flashes the Locked message on the LCD Authorized individuals locking the system should first enter a name phone or other contact information into the 10 digit field To lock or unlock the system the correct 4 digit authorization number must be entered into the Enter Code field Point to the Unlock System menu entry and press EDIT to complete the unlock procedure WX16 User Manual 29 It is very important to record the 4 digit code However if lost it may be displayed briefly at power up using the following procedure Remove power from the controller Reapply power and as the alarm LED s begin scrolling down hold the following keys simultaneously UP DOWN NEXT amp EDIT Watch closely The 4 digit authorization code appears briefly at bottom left of the screen IMPORTANT DO NOT hold the keys before applying power since this causes a cold boot and returns all settings back to factory defaults ENTER NAME Enter Cade Figure 2 17 2 5 LCD Contrast Adjustment The Setup
2. VVX16 User Manual 47 WX16 User Manual 48 SECTION 5 5 0 ModBus RS 485 Ports The WX16 is equipped with Master COMM 1 and Slave COMM 2 ModBus RTU ports Port configurations are described in sections 2 2 and 2 3 of this manual Section 5 0 defines register locations of data available via the WX16 slave port 5 1 ModBus Slave Register Locations The following tables describe the WX16 s ModBus slave database Any portion of this data may be read by a ModBus master device such as a PC PLC or DCS Since the ModBus port is RS 485 many WX16s may be multi dropped onto the same cable Memory Integer ASCII Notes ASCII may be read 2 characters at a time or in strings using a multiple register read Sixteen character channel tag name Type Channel First Last ReadFC Write FC Notes Channel Tag 1 40401 40408 3 n a 2 characters per register Channel Tag 2 40409 40416 3 n a 2 characters per register Channel Tag 3 40417 40424 3 n a 2 characters per register Channel Tag 4 40425 40432 3 n a 2 characters per register Channel Tag 5 40433 40440 3 n a 2 characters per register Channel Tag 6 40441 40448 3 n a 2 characters per register Channel Tag 7 40449 40456 3 n a 2 characters per register Channel Tag 8 40457 40464 3 n a 2 characters per register Channel Tag 9 40465 40472 3 n a 2 characters per register Channel Tag 10 40473 40480 3 n a 2 characters per register Channel Tag 11 40481 40488 3 n
3. 5 and terminals 3 amp 7 Socketed RS 485 terminating resistors R6 COMM 1 and R12 COMM 2 are located on the MAIN I O board These resistors should be removed if communication wire lengths are very short less than 25 feet or if the port is not at the end of the communication line An optional Auxiliary Relays piggyback PCB part 10 0144 may be added to the I O PCB via ribbon cable J4 These add another form C contact set to the common A1 A2 and HORN alarms Auxiliary Relay contacts are available at the TB1 AUX terminals shown in Figure 3 1 WX16 User Manual 31 TR AUK RELAYS OPTION 8 100144 LALN A ms hornortar wot in JPY for 2 wro R5 485 operation WS 486 lenreratrg reamtors rerreree tor short were palis amp whan ST T1 m not ent of path COMM tambe CONI Gema Main I O PCB WITH COMMON RELAYS 10 0142 Figure 3 1 3 1 Input Output Optional PCB s Telephone style RJ11 connections are used to add optional 8 channel analog and digital I O A screen appears briefly after power up indicating what options are connected and for which channels This information is also available from the Diagnostics Mode described in Section 4 PRESS NEXT KEY TO EXIT Figure 3 2 3 1 1 Optional Analog Input PCB 10 0158 Many transmitters or sensors have analog output signals and the 12 bit Analog Input PCB shown in Figure 3 3 is available to accept these TB1 with 24 positions offers 3 termin
4. Any other key to exit FE REED RR DEZE ZI ele SED DI EZ z Press EDIT to enter diagnostics Any other key to exit Ommon Rela Discrete Relays Plezo Serial Ports Analog Outeuts Anslo Ineuts Alarm LEDs Printer Fort onne d 0 Diagnostics menu Figure 4 1 WX16 User Manual 46 ir fre te chante commen Allows manual actuation of Common Alml Alm2 FAIL and HORN relays Front panel LED ON confirms Press MENT vey 10 eer relay actuation Sat Allows manual actuation of mats BT any connected discrete relays ee without stimulating the inputs Front panel LED ON confirms ves wir way TO ar relay actuation Pulses the controller s local piezo beeper Fw pred ae Provides simple means of Pi testing the controller s 7g serial ports Liman seat es FR ED FOSSES Pan mw EE TO DIT Pal BERN rd ER VEE Allows forcing 4mA 12 mA cram ouet BORED WOT Faua or 20mA to any connected analog output channels Displays A D counts re ceived from connected Sensor or Analog inputs Initiates flashing pattern on 4 all front panel LED s with out affecting alarm relays West DR a ES sree ment Tests printer ports by sending a brief test message to the printer PRESS WERT MEV TO EMT Indicates all connected VO options If not indicated the option is not connected Es or a problem exists Figure 4 2
5. Coils Notes Set this coil to issue an alarm Acknowledge via ModBus see Echo Ack in section 2 3 4 Channel First Last Read FC Write FC Alarm Reset n a 2001 n a n a 5 WX16 User Manual 54 write Oxff to high byte to set Memory Discretes Notes May be read as single discrete or packed with multiple register read Type Channel First Last Read FC Write FC Notes Chnl Alarm 1 1 16 12001 16 n a 2 n a discrete may be packed Type Channel First Last Read FC Write FC Notes Chnl Alarm2 1 16 12017 32 n a 2 n a discrete may be packed Type Channel First Last Read FC Write FC Notes Chnl Alarm3 1 16 12033 48 n a 2 n a discrete may be packed Memory Reals Notes Real value represents float value without the decimal point such as 123 4 is returned as 1234 Decimal devisor is returned as 1 10 100 or 1000 for decimal position of 1 2 3 or 4 where 123 4 would return the value 10 Type Channel First Last Read FC Write FC Notes Zero Real 1 16 41001 16 n a 3 n a zero real w o decimal point Zero DP 1 16 41017 32 n a 3 n a zero real divisor Span Real 1 16 41033 48 n a 3 n a span real w o decimal point Span DP 1 16 41049 64 n a 3 n a span real divisor Alarm 1 Real 1 16 41065 80 n a 3 n a alarm 1 real w o decimal point Alarm 1 DP 1 16 41081 96 n a 3 n a alarm 1 real divisor Alarm 2 Real 1 16 41097 112 n a 3 n a alarm 2 real w o decimal point Alarm 2 DP 1 16 41113 28 n a 3 n a al
6. Each 10 0192 channel is equipped with a bridge amplifier and balance potentiometer and an adjustable switching regulator for setting the correct sensor excitation voltage A 3 position coarse gain jumper allows setting the gain of the bridge amplifier Fault supervision circuitry forces the WX16 into a FAULT condition upon sensor failure or removal This option may also be configured to accept 4 20mA inputs for mixing bridge sensors and current loops into the same board Placing any channel s 2 position LEL 4 20mA WX16 User Manual 36 jumper into 4 20mA position and installing the associated precision 100 ohm socketed resistor allows 4 20mA signals to be applied to its C amp A terminals The 10 0192 sensor modules are not required for channels accepting 4 20mA Channels receiving input data from this board should have the Data From menu set for Sensor as described in section 2 2 4 This activates Cal Mode menus described in section 2 2 7 needed to zero and span sensor readings After performing the one time only Initial Setup as described below all subsequent calibrations are by the WX16 s electronic Cal Mode menus Catalytic sensors connected directly to the WX16 should be limited to ranges of 0 1000ppm 3 1 4 Catalytic Bead Sensor Initial Setup Catalytic bead sensors vary widely in power requirements and sensitivity It is therefore important to configure each channel to match the sensor with which it will operate 1 Prior
7. This third earth path causes damage unless the other two paths provide a better earth connection allowing surge energy to bypass the electronics When an antenna is located outside of a building and outside of an industrial plant environment external coax surge diverters are recommended to further minimize the effect of surge current in the inner conductor of the coax cable WX16 User Manual 69 Coax surge diverters have a gas discharge element which breaks down in the presence of high surge voltage and diverts any current directly to a ground connection A surge diverter is not normally required when the antenna is within a plant or factory environment as the plant steelwork provides multiple parallel ground paths and good earthing will provide adequate protection without a surge diverter 7 6 2 Connections to Other Equipment Surges can enter the wireless unit from connected devices via I O serial or Ethernet connections Other data devices connected to the wireless unit should be well grounded to the same ground point as the wireless unit Special care needs to be taken where the connected data device is remote from the wireless unit requiring a long data cable As the data device and the wireless unit cannot be connected to the same ground point different earth potentials can exist during surge conditions There is also the possibility of surge voltages being induced on long lengths of wire from nearby power cables Surge diver
8. zro 856 sis GE PRINTER INTERFACE OPTION 10 0229 Figure 3 8 3 1 7 1 Clock Printer System Setup Menu Detection of the 10 0229 on the I2C bus causes the Clock Printer System Setup menu item to appear Selecting it and pressing EDIT brings up the menu shown at right in Figure 3 9 Date Time menu entries allow setting of correct local time and date The ALARM PRINT ON OFF entry allows printing to be discontinued if turned to OFF PORT allows selection of RS 232 RS 422 or the parallel port With only one port able to be activated at a time BUFFER DUMP allows immediate printing of all the 30 35 stored events PRINT CONFIG allows immediate printing of all channel variables such as channel ID s Engineering Units etc PRINTER READY ERROR indicates the functional status of the printer WX16 User Manual 43 Alarn 1 Reim Date 86 05 05 Alarm 2 Relay Tine 16142131 Horn Piezo Alarn Print ON odbus Port RS232 8 16 Ch Mode Buffer Dunr Clock Printer Print Confis Printer Ready Entry menu Clock Printer Controls Figure 3 9 3 1 8 Optional 24 VDC 150 Watt Power Supply The WX16 Controller may be powered from 10 30 VDC However many applications require 24 VDC power for the monitors or transmitters providing inputs to the WX16 A 150 watt AC DC power supply may be included for these applications 115 VAC or 230 VAC selected via slide switch When ordered from the factory it is pre wired to provide 24 VDC primary power
9. 3 registers per channel EUNITS 14 40568 40570 3 n a 2 characters per register 3 registers per channel EUNITS 15 40571 40573 3 n a 2 characters per register 3 registers per channel EUNITS 16 40574 40576 3 n a 2 characters per register WX16 User Manual 50 3 registers per channel Six character Value ASCII string Type Channel First Last ReadFC Write FC Notes ASCII Value 1 40577 40579 3 n a 2 characters per register 3 registers per channel ASCII Value 2 40580 40582 3 n a 2 characters per register 3 registers per channel ASCII Value 3 40583 40585 3 n a 2 characters per register 3 registers per channel ASCII Value 4 40586 40588 3 n a 2 characters per register 3 registers per channel ASCII Value 5 40589 40591 3 n a 2 characters per register 3 registers per channel ASCII Value 6 40592 40594 3 n a 2 characters per register 3 registers per channel ASCII Value 7 40595 40597 3 n a 2 characters per register 3 registers per channel ASCII Value 8 40598 40600 3 n a 2 characters per register 3 registers per channel ASCII Value 9 40601 40603 3 n a 2 characters per register 3 registers per channel ASCII Value 10 40604 40606 3 n a 2 characters per register 3 registers per channel ASCII Value 11 40607 40609 3 n a 2 characters per register 3 registers per channel ASCII Value 12 40610 40612 3 n a 2 characters per register 3 registers per channel ASCII Value 13 40613 40615 3 n a 2 characters per register 3
10. Low Battery and Calibration WX16 User Manual 65 e Communications Error Each channel s 30 minute trend screens Figure 7 4 are very useful for diagnosing wireless problems since they indicate amount of time since the most recent transmission was received The down arrow on top of the trend screen resets to far right each time a transmission is received by that channel When not in alarm OLCT 200 s transmit each 5 minutes so the arrow should never progress past the 5 minute interval The WX16 activates the channel s FAULT alarm and indicates ComErr if no transmission has been received in 18 consecutive minutes e Low Battery status indicates the OLCT 200 s integral 3 6V lithium D cell part 10 0293 has dropped to below 3 3V and should be replaced very soon LoBatt is indicated on the WX16 s LCD readout and the Alarm 3 LED flashes Relays are not energized by low battery conditions The actual battery voltage of each OLCT 200 may be seen in the INPUT DATA FROM screen described above in section 7 2 e Calibrations performed at the OLCT 200 force a transmission of 75 counts negative 15 62 which may be indicated on the WX16 s LCD readout by In Cal by using the Marker Menu described in section 2 2 4b Alarms are inhibited while the Marker Value of 15 62 is activated neS thas Wireless RmtCal LoBatt ComErr conditions displayed here 286 COUNTS Observe this arrow to monitor time between RF trans
11. a 2 characters per register Channel Tag 12 40489 40496 3 n a 2 characters per register Channel Tag 13 40497 40504 3 n a 2 characters per register Channel Tag 14 40505 40512 3 n a 2 characters per register Channel Tag 15 40513 40520 3 n a 2 characters per register Channel Tag 16 40521 40528 3 n a 2 characters per register Six character Eunits Tag Type Channel First Last ReadFC Write FC Notes WX16 User Manual 49 EUNITS 1 40529 40531 3 n a 2 characters per register 3 registers per channel EUNITS 2 40532 40534 3 n a 2 characters per register 3 registers per channel EUNITS 3 40535 40537 3 n a 2 characters per register 3 registers per channel EUNITS 4 40538 40540 3 n a 2 characters per register 3 registers per channel EUNITS 5 40541 40543 3 n a 2 characters per register 3 registers per channel EUNITS 6 40544 40546 3 n a 2 characters per register 3 registers per channel EUNITS 7 40547 40549 3 n a 2 characters per register 3 registers per channel EUNITS 8 40550 40552 3 n a 2 characters per register 3 registers per channel EUNITS 9 40553 40555 3 n a 2 characters per register 3 registers per channel EUNITS 10 40556 40558 3 n a 2 characters per register 3 registers per channel EUNITS 11 40559 40561 3 n a 2 characters per register 3 registers per channel EUNITS 12 40562 40564 3 n a 2 characters per register 3 registers per channel EUNITS 13 40565 40567 3 n a 2 characters per register
12. by special order Inputs may also be configured to accept 4 20mA signals allowing mixing RTD sensors and current loops into the same board Two jumpers per channel determine either a RTD or 4 20mA input These dual position jumpers JP1 JP16 must both be placed WX16 User Manual 38 into the UP position for RTD inputs or both in the DOWN position for 4 20mA inputs see Figure 3 6 Channels receiving input data from this board should have the Data From menu set for Sensor as described in section 2 2 4 This activates Cal Mode menus described in section 2 2 9 needed to perform zero and span calibrations of RTD sensor readings Each channel must be calibrated individually by either simulating desired zero and span calibration resistance values or by actually placing the channel s RTD into an actual precision temperature generator Ice water is an acceptable method for generating the 0 C zero temperature value Upscale span values are best simulated with an RTD calibrator Since RTD s are stable and repeatable over long time periods calibrations normally only need to be performed upon initial installation Since the PCB has 8 channels two are required for 16 channel applications JP25 configures inputs for channel groups 1 8 or 9 16 WX16 User Manual 39 ROMA rou PCS sapa m RTDimA mput PCB accepts for CH s 1 8 of 8 16 assembles are required is Boones un un JP JPB work with JPS JP16 ta eg parley Sey a ress
13. example this would cause Oppm to display 0 and 100ppm to display 100 2 2 6 4 Turning Off Unused Channels The Channel On entry determines if this channel is to be utilized Turning it off will cause the controller to never process inputs applied to this channel and no alarms will be tripped or data displayed Inactive channels have a line drawn through them on the Setup screen as indicated by channels 15 amp 16 in Figure 2 0 If less than 9 channels are to be activated the WX16 may be set for 8 channel mode deactivating channels 9 WX16 User Manual 21 16 This is done in the System Setup menu described in section 2 3 The WX16 will only allow 15 channels to be turned off At least one channel must remain on 2 2 6 5 Copy Data To This menu simplifies the Setup procedure by allowing similar channels to be copied from one to another For example if all channels are identical except for the Measurement Name entry channel 1 could be configured and copied to channels 2 16 Only Measurement Name then must be configured on channels 2 16 Use EDIT to increment channel numbers and UP DN to point to Copy Now Press EDIT once more to copy 2 2 7 Cal Mode IMPORTANT Each channel s CALIBRATION menu is inactive unless its Input Data From menu described in section 2 2 4 is set for Analog with Local Calor Sensor Direct WX16 CAL MODE features allow pushbutton calibration of zero and span values This feature should be utilized only w
14. for the WX16 controller as well as any transmitters or monitors that may be connected by the end user are no AOC CS CA 4 Ap Gen Ane located under TOLOS cover To access decommect power a and amavo A some 6 T pisia pe then cicio Corer ief ang SR By 35 0 WARNING For contrusd protection O ge aL a A De SHOCK A RISK OF ELECTRICAL La a as es TURN OFF POVVER i TOROI SST 1 BEFORE SERVICING Els OXORON EQUIPMENT AC RAC TT SELECTOR SWITCH ma 150 Watt 24 VDC Power Supply Option 10 0172 Figure 3 10 WX16 User Manual 44 SECTION 4 4 0 System Diagnostics A System Diagnostic Mode shown in Figures 4 1 and 4 2 may be entered during normal operation from the Setup menu The entry menu indicates firmware revision and offers useful routines for testing front panel LED s relays serial ports and analog I O It is exited manually by pressing NEXT and automatically if no keys are pressed for 5 minutes It is very important to understand that CHANNEL INPUT DATA IS NOT PROCESSED DURING THE DIAGNOSTICS MODE It is possible to miss A important input values while utilizing this mode and appropriate safeguards should be in place However the Diagnostics Mode can prove invaluable when testing I O since relays and analog outputs may be stimulated without driving inputs to precise levels WX16 User Manual 45 wee eURRNINGere suite A aa Re Hei en tents char a Et a ec Nds Zeller Press EDIT to enter A diants tida
15. graph indicates number of minutes samples have been taken After 999 minutes the AVERAGE buffer overflows and the message ERROR appears in the AVERAGE field Exiting this screen resets the buffer and clears the error message WX16 User Manual 9 1 2 Specifications 1 2 1 DC Power Supply Requirements Standard WX16 power requirements are 10 30 VDC 3 watts applied to terminals 9 amp 11 of TB2 on the standard I O PCB see section 3 0 Optional features increase power consumption as described below e Discrete Relay PCB option add 2 watts per PCB assumes all 8 relays are energized e Analog Input PCB option add 1 2 watt e 4 20mA Output PCB option add 1 watt e Catalytic Bead Sensor Input option add 12 watts max assumes maximum sensor power consumption e TB2 terminals 10 amp 12 of the standard I O PCB provide a maximum of 500mA fused output power for powering of auxiliary external devices such as relays lamps or transmitters Power consumed from these terminals should be considered when calculating system power consumption 1 2 1 1 150 Watt AC 24 VDC Power Supply 110 120 VAC 3 2A max 220 240 VAC 1 6A max A slide switch on the front of the power supply selects AC input range The 10 0172 150 watt power supply Figure 3 8 is for powering the WX16 and up to 16 detectors A minimum of 5 watts per channel is available for powering of external transmitters 1 2 2 Relays Common relays are standard and menu
16. menu item identified as CONTRAST allows users to adjust the LCD contrast to a level suitable to the ambient lighting Selecting CONTRAST and pressing EDIT causes the UP DOWN keys to increase and decrease LCD contrast WX16 User Manual 30 SECTION 3 3 0 Main I O Interface PCB 10 0142 The most basic WX16 Controller requires only the I O PCB shown in Figure A 3 1 for interfacing to field wiring The WX16 primary power supply is applied to terminals 9 amp 11 of TB2 This may be from 10 30 VDC WARNING HIGH VOLTAGES SUCH AS 115 VAC APPLIED TO THESE TERMINALS MAY CAUSE SEVERE DAMAGEI DC output terminals 10 amp 12 on TB2 provide up to 500mA of output power for powering remote devices such as lamps transmitters etc This PCB includes both master COMM 1 and slave COMM 2 RS 485 ModBus ports 5 amp form C relays for each common alarm event A1 A2 FAULT A3 amp HORN and power supply I O terminals JP1 allows the RS 485 ports to be configured for 2 or 4 wire operation A 26 pin ribbon cable connects the I O PCB to the WX16 CPU and Display nest assembly Two C bus connectors allow addition of optional functions such as analog I O and discrete alarm relays for each channel Horizontal jumpers installed in JP1 connect the RS 485 port s RX amp TX lines simplifying 2 wire daisy chains by providing additional terminals for incoming and outgoing cables For example installing the 2 COM 1 jumpers connects screw terminals 1 amp
17. mounted with vertical polarity then the Yagi s must also have vertical polarity Care needs to be taken to ensure the Yagi is aligned correctly to achieve optimum performance Two Yagis can be used for a point to point link In this case they can be mounted with the elements horizontally to give horizontal polarity There is a large degree of RF isolation between horizontal and vertical polarity approx 30dB so this installation method is a good idea if there is a large amount of interference from another system close by transmitting vertical polarity An important mounting tip If a Yagi has drainage holes in the dipole element do not mount the antenna with the drainage 7 5 3 Mounting Near Other Antennas Avoid mounting your network s antenna near any other antenna even when the other antenna is transmitting on a different radio band High RF energy of the transmission from a close antenna can deafen a receiver This is a common cause of problems with wireless systems Because antennas are designed to transmit parallel to the ground rather than up or down vertical separation between antennas is a lot more effective than horizontal separation If mounting near another antenna cannot be avoided mounting it beneath or above the other antenna is better than mounting beside it Using different polarity to the other antenna if possible will also help to isolate the RF coupling 7 5 4 Coax Cables If a coax cable connects to the ant
18. positions as standard and 4 more with the 10 0180 expansion plate since in panel rack mount installations 10 0180 s must be mounted in user space behind panels or inside racks multiple 10 0180 s may be incorporated to support the required option positions WX16 User Manual 61 e WX16N4 8 WX16SS NEMA 4X Wall Mount supports 3 option positions as standard and 4 more with the 10 0180 expansion plate If more than 7 option positions are required the 10 0178 NEMA 4X wall mount option enclosure supporting 8 positions may be added e VVX16XP NEMA 7 Wall Mount supports 5 option positions as standard and 3 more with the 10 0181 expansion plate Figure 6 6 provides Main I O and option PCB dimensions 5 125 _ 4 975 125 holes 4 places MAIN I O amp OPTION s PCB FOOTPRINT 15 gg TL T 0 0 16 2 56 2 80 WX16 User Manual 62 SECTION 7 7 0 Adding The Wireless Radio Kit Option WX16 master slave serial ports may be connected to a FHSS Frequency Hopping Spread Spectrum wireless radio modem shown in Figure 7 1 There are two different frequency options offered 900 MHz and 2 4 GHz 900 MHz is available in a single port modem 10 0364 or dual port modem 10 0365 2 4 GHz is also available in a single port 10 0357 or dual port modem 10 0358 The dual port radio modems have two radio modules installed and can be used to receive and transmit data simultaneously The radio kit options allow three
19. registers per channel ASCII Value 14 40616 40618 3 n a 2 characters per register 3 registers per channel ASCII Value 15 40619 40621 3 n a 2 characters per register 3 registers per channel ASCII Value 16 40622 40624 3 n a 2 characters per register WX16 User Manual 51 3 registers per channel Memory Floating Point Notes Returned as 15 bit 2s complement with 5 over under range applied Therefore this must be considered when scaling values to be displayed at the ModBus master The following equation may be used to determine a value for display Display Value MODBUS Value Span Value Zero Value 1 1 zero Value Span Value Zero Value 05 32767 Type Channel First Last Read FC Write FC Notes Channel Value 1 16 33001 16 n a 4 n a 15bit 2s complement w 5 over under range Analog Output Notes 12 bit integer for Channel Reading value 800 counts zero value 4000 counts 100 value Type Channel First Last Read FC Write FC Notes Channel 1 16 31001 31016 4 n a 12bit integer Reading Channel Status words contain configuration and status bits for a channel They are as follows Type Channel First Last Read FC Write FC Notes Channel Status 1 16 31017 31032 4 n a 16bit integer see bit by bit definition below Alarm 1 Trip bitO 1 Low 0 High Alarm 1 Horn Drive bit1 1 On 0 Off Alarm 3 Type bit2 1 Level 0 Fault Alarm 2 Horn Drive bit3 1 On 0 Off Linearize bit4
20. screen indicates channel real time reading in engineering units measurement name range and MIN MAX amp AVERAGE values for the preceding 24 hour period The SI field on the top right indicates number of seconds remaining in the current 6 minute subinterval 1 1 2 Bar Graphs Screen The WX16 Bar Graphs screen shown in Figure 2 0 allows all active channels to be viewed simultaneously Both engineering units values and bar graph values are indicated in real time Lines across the bars indicate the alarm trip points making it easy to identify channels at or near alarm A feature in the Systems menu tree allows new alarms to always force the LCD to the bar graphs screen This is useful for applications requiring channels with alarms to be displayed 1 1 3 Combination Screen The WX16 Combination screen shown in Figure 2 0 offers a view of a single channel but displays the data as a 30 minute trend bar graph and large engineering units It is also useful for testing inputs for stability since MAX MIN amp AVERAGE values refresh each time this screen is selected For example to test stability over a one hour period for an input begin timing as soon as the channel is selected One hour later record the MAX MIN amp AVERAGE values The difference between MAX amp MIN indicates peak to peak excursions over the one hour period and AVERAGE is the average for the hour Longer or shorter tests may also be run The numeric value shown below the bar
21. separate modes of wireless operation These are Wireless Receiver section 7 2 accepting data from OLCT 200 sensor transmitters Wireless ModBus Slave section 7 3 providing data to a ModBus master master side of network requires additional radio and Wireless ModBus Master section 7 4 accepting wireless data from ModBus slaves slaves side of network requires additional radio Wireless Receiver and Wireless ModBus Master modes require the radio be connected to the WX16 s RS 485 master port and Wireless ModBus Slave mode connects it to the RS 485 slave port Figure 3 1 It is important to remember RADIO SETUP functions described in section 7 1 may only be performed with the radio connected to the master port Each transceiver on a wireless network must have its RADIO SETUP menus configured to share the same hopping channel 0 32 and System ID 0 255 to communicate All WX series wireless transceivers utilize a Server Client network where Clients synchronize their hopping to the Server The Server transmits a beacon at the beginning of every hop 50 times per second Client transceivers listen for this beacon and upon hearing it will indicate InRange with the LED on the radio modem board and synchronize their hopping with the Server Each network should consist of only one Server There should never be two servers on the same RF Channel number in the same coverage area as the interference between the two
22. to connecting sensors apply power to the system Note this PCB requires 24 VDC power be connected to its TB2 terminals 1 amp 2 as shown in Figure 3 5 Suitable fused power is available from the Main I O board s TB2 terminal 10 amp 12 see Figure 3 1 Measure the voltage between each channel s A and R terminals and set the Voltage Adjust potentiometers for the correct sensor excitation voltage This may range from 1 5 volts to 7 5 volts depending upon sensor specifications Sensors may be damaged by A accidental over voltage conditions It is recommended the Voltage Adjust potentiometer screws be covered by a dollop of RTV or similar material after completion of this procedure to avoid accidental over voltage conditions 2 Remove system power and connect sensor wires to the R C A terminals Reapply system power and confirm correct voltage across each sensor s A amp R terminals Note If sensor wires are long it may be necessary to measure the excitation voltage at the sensor end to compensate for PR losses in the wiring 3 With the minus voltmeter lead on TB2 2 common connect the plus lead to the channel s test point With zero air on that sensor adjust its Balance potentiometer for 4 volts at the test point 4 Apply 50 LEL combustible span gas to the sensor and allow the test point voltage to stabilize Two volts 100 input to the A D Converter and 4 volts 0 Therefore 1 2 volts 50 Place the 3 position Coars
23. understand contents of this manual prior to operation Failure to do so could result in serious injury or death WX16 User Manual 3 WX16 User Manual 4 Table of Contents SECTION 1 Important Safety Issues 1 0 General Description 1 1 Data Display Screens 1 1 Trend Screen 1 2 Bar Graphs Screen 1 3 Combination Screen Specifications 1 DC Power Supply Requirements 2 Relays 3 Ambient Temperature Range 4 Humidity Range 5 Altitude 6 Housings 1 2 7 Approvals SECTION 2 2 0 Basic Operation 2 1 Setup Menu Configuration 2 1 1 Changing Menu Variables Using the Keypad 2 2 Channel Configuration Menus 2 2 1 Channel Setup Entry Menu 2 2 2 Alarm 1 Alarm 2 Horn Relay Setup Menu 2 2 3 Alarm 3 Fault Alarm Menu 2 2 4 Data From Menu to Set Input Source 2 2 5 Linearization Menu 2 2 6 Configure Menu 2 2 7 Cal Mode 2 3 System Configuration Menus 2 3 1 Common Alarm Relays 1 amp 2 2 3 2 10 0195 Discrete Relay Failsafe Mode 2 3 3 Common Horn Relay amp Local Piezo 2 3 4 Comm Port Menus 2 3 5 Eight Sixteen Channel Modes 2 3 6 Sensor Information 2 4 Authorization Mode 2 5 LCD Contrast Adjustment SECTION 3 3 0 Main I O Interface PCB 10 0142 3 1 Input Output Optional PCB s 3 1 1 Optional Analog Input PCB 10 0158 3 1 2 Optional Discrete Relay PCB 10 0195 3 1 3 Optional Bridge Sensor Input Board 10 0191 WX16 User Manual 5 Catalytic Bead Sensor Initial Setup Optional RTD 4 20mA Analog Input Board
24. 1 On 0 Off Alarm 3 Trip bit5 1 Low 0 High Input Marker bit6 1 Input Marker Detected 0 Normal Mode Channel Disable bit7 1 Disabled 0 Enabled Controller Channel In Cal bit8 1 Local Cal Mode 0 Normal Mode ModBus Data Type bit9 1 4 byte float 0 2 byte integer reserved bit10 reserved reserved reserved bit11 reserved reserved Alarm 1 Latch bit12 1 Latching 0 Non latching Alarm 2 Latch bit13 1 Latching 0 Non latching Alarm 3 Latch bit14 1 Latching 0 Non latching Alarm 2 Trip bit15 1 Low 0 High Alarm status words are bits packed into 16 bit integer where Isb channel 1 alarm status and msb channel 16 alarm status Alarm status bit 1 indicates alarm is active Type Channel First Last Read FC Write FC Notes Alarm 1 Status 1 16 31033 n a 4 n a packed 16bit integer WX16 User Manual 52 Alarm 2 Status 1 16 31034 n a 4 n a packed 16bit integer Alarm 3 Status 1 16 31035 n a 4 n a packed 16bit integer Relay Status n a 31036 n a 4 n a packed 16bit integer Note Common Relay status bits register 31036 are as follows Relay 1 bitO Relay 2 bit1 Fault Relay bit2 Horn Relay bit3 Type Channel First Last Read FC Write FC Notes Cal Status 1 16 31037 n a 4 n a packed 16bit integer Trend Interval 1 16 31038 n a 4 n a 16bit integer Timer Time in Seconds Fault Status 1 16 31039 n a 4 n a packed 16bit integer Alarm LED flashing status bit 1 indicates LED is flashing Acknowledge c
25. 10 0170 Optional 4 20mA Analog Output Board 10 0167 Optional Clock Printer Interface Board 10 0229 Optional 24 VDC 150 Watt Power Supply SECTION 4 4 0 System Diagnostics SECTION 5 5 0 ModBus RS 485 Ports 5 1 ModBus Slave Register Locations SECTION 6 6 0 Panel Rack Mount Enclosure 6 1 NEMA 4X Wall Mount Fiberglass Enclosure 6 2 NEMA 4X Wall Mount 316 Stainless Steel Enclosure 6 3 XP NEMA 7 Explosion Proof Wall Mount Enclosure 6 4 Main I O amp Option PCB Footprint Dimensions SECTION 7 7 0 Adding The Wireless Radio Kit Option 7 1 Radio Setup Menu 7 2 Wireless Receiver Mode 7 2 1 Radio Status Alarms Wireless Receiver Mode 7 3 Wireless ModBus Slave Mode 7 4 Wireless ModBus Master Mode 7 5 Antenna Selection 7 5 1 Dipole And Collinear Antennas 7 5 2 Yagi Antennas 7 5 3 Mounting Near Other Antennas 7 5 4 Coax Cables 7 6 Surge Protection amp Grounding 7 6 1 Antenna Grounding 7 6 2 Connections to Other Equipment ww www ONDUA WX16 User Manual 6 SECTION 1 Important Safety Issues The following terms and symbols are used in this manual to alert the operator of important instrument operating issues A A A This symbol is intended to alert the user to the presence of important operating and maintenance servicing instructions This symbol is intended to alert the user to the presence of dangerous voltage within the instrument enclosure that may be sufficient magnitude to constitute a risk
26. 71 ay Fle O OEE Ret Aj allows timing voltage Bl onTP1 2 048 vos provides mE i 8 Channel 4 20mA Output Option 10 0167 Figure 3 7 WX16 User Manual 41 3 1 7 Optional Clock Printer Interface Board 10 0229 When equipped with the 10 0229 Clock Printer Interface option shown in Figure 3 8 the WX16 Controller is capable of automatically printing time amp date stamped alarm events to a 24 PIN dot matrix printer such as the Panasonic KX P1131 The cable interface between the WX16 and the KX P1131 may be either parallel or serial Parallel interfaces only allow 6 feet of separation while the RS 232 serial interface allows up to 50 feet Distances up to 4000 feet may be obtained using the 10 0229 printer interface option s RS 422 port but require an additional tri port RS 422 RS 232 converter at the printer end of the cable The 10 0229 Printer Interface may also be connected to a PC running HyperTerminal or other communications software as an alternative to hard copy printing of the data Printer PC cable schematics are shown in Figure 3 8 Printer settings for serial interfaces are 9600 baud 8 data bits no parity and one stop bit Communications software settings are 9600 baud 8 data bits no parity one stop bit and FlowControl Hardware Printer diagnostic red LED s indicate printer faults such as out of paper overflowed buffer or loss of communications Green LEDs flicker to confirm good commun
27. Alias register location of the data to be retrieved from the RTU Alias register numbers define the location of the variable representing the input value and must be obtained from the manufacturer of the ModBus RTU device WX16 User Manual 17 e Our 10 0288 Radio Modem may be connected to the ModBus RS 485 master port to enable wireless communication to OLCT 200 wireless sensor transmitters EDIT toggles the Data From entry between Analog Analog with Local Calor Sensor Direct WIRELESS RF900 and ModBus RTU signed unsigned amp floating point Analog should be selected when the channel s input comes from a transmitter or monitoring device with a calibrated output such as 4 20mA Analog with Local Cal is available when the WX16 will be the point of calibration for the analog input Sensor Direct is identical to Analog with Local Cal and both activate the WX16 s Cal Mode features see section 2 2 7 Problems may arise if calibrations are performed in two places upon the same signal so Cal Mode menus are only visible when Sensor Direct or Analog with Local Cal is selected These selections should only be used when the input originates from a non calibrated signal source such as the Bridge Sensor Input option described in section 3 1 3 These applications require the WX16 to be used as the calibration point since the sensors have no zero or span controls 12 86 Analog tapats mmary be dres foen Sersut inguk options ce Vohage Ceremi Inp
28. ES forces the LCD to display the Bar Graphs screen upon any new alarm This feature is offered to satisfy applications requiring channels in alarm to be displayed automatically all channels are displayed on the Bar Graphs screen 2 3 4 Comm Port Menus The system Comm Port menu allows setting RTU Slave ID address Slave Baud rate Parity and UART Timer for the comm2 slave ModBus serial port comm1 master port ID settings are per channel as described in section 2 2 4 This slave port may be used to transfer WX16 data to a host device such as a PC PLC DCS or even another WX16 The slave port is addressable allowing many WX16 controllers to be connected to a single RS 485 cable The UART Timer setting is disabled with 00 seconds entered Entering a value causes the comm2 slave ModBus serial port to reinitialize if no ModBus query is processed within this time period This ensures against serial port lockup Section 5 of this manual provides important information describing how to interface to the WX16 s ModBus slave port WX16 User Manual 27 The Mastr TO master time out and Mastr PR master poll rate menu items affect the VVX16 s master ModBus port Time out sets length of time in milliseconds before a communications error Three consecutive timeout errors must occur before a communication error is indicated This item is useful for optimizing throughput to the WX16 from other slave RTU s Poll Rate sets frequency of data requests to the RT
29. Enable Y Harker 15 62 Mark Rs IN CAL Sensor life Reset Sen Life Alara i Alarn 2 Alarn 3 Data Fron Linear ize Conf igure Analog Inrut Min Rau 00880 Max Rau 84008 Marker Meru Entry Menu Input From menu Marker menu Figure 2 5 2 2 4 3 Sensor Life Detection Sensor Life should only be activated when the Marker event is Calibration and when a sensor life value is transmitted after each calibration This feature is provided primarily for use when interfacing the WX16 to Oldham s OLCT 200 Transmitters which may be configured to transmit sensor life values after each calibration see Figure 2 6 For Sensor Life to record properly the monitor must perform as follows After the Calibration Marker interval 4 0mA transmits for 10 seconds to indicate its calibration mode is complete The monitor then transmits between 4 0mA and 5 0mA for five seconds depending on remaining sensor life where 4 0mA 0 and 5 0mA 100 remaining sensor life The WX16 reads this value and records it as the channel s Sensor Life Sensor Life is stored in the WX16 ModBus database and displayed as a WX16 User Manual 19 bar graph in the Sensor Info screen see section 2 3 6 It is a useful tool for planning sensor replacement schedules 5mA for 5 seconds hen 4 X Monitoring 4mA for 10 seconds after Cal Exit Monitoring Mark As 6 digit field indicated Cal Marker detected _ on readouts Ca
30. G Ready n a 12066 n a 2 n a 0 data ready 1 update in progress MAX Ready n a 12067 n a 2 n a 0 data ready 1 update in progress Trend database registers Type Channel First Last Read FC Write FC Notes 24 hr Trend 1 16 33017 36857 5 n a Transfers 24 hour trend WX16 User Manual 56 for MAX MIN or AVG SECTION 6 6 0 Panel Rack Mount Enclosure The WX16 shown in Figure 6 1 is a half width 19 rack enclosure It is supplied with hardware that allows mounting in either a full width 19 rack style cabinet or it may be panel mounted in a rectangular cutout Only two 8 channel I O option PCB s such as analog input or discrete relays may be mounted directly to the back of the enclosure Additional 8 channel I O option PCB s must be located external from the assembly on another mounting plate A 3 foot length of FC cable is also supplied for this purpose Weight is approximately 7 pounds Properly ground the enclosure and follow national and local electrical codes le 1080 hi 910 e 280 el rn 8 SIDE VIEW 8 8 5 22 IO FRONT VIEW e If EIE 1 Le a u Note Panel cut out 5 25 X 820 RACK PANEL MOUNT 19 RACK SPREADER PLATES 8 PANEL MOUNT BEZAL NOT SHOWN Figure 6 1 WX16 User Manual 57 6 1 NEMA 4X Wall Mount Fiberglass Enclosure The WX16 shown in Figure 6 2 is a fiberglass NEMA 4X wall mount enclosure Seven 8 channel I O option PCB s such as analog input or discr
31. L combustible sensor is to be spanned with 50 LEL span gas the span set point must be 50 If 45 LEL is to be used later the span set point must be changed to 45 to match the span calibration gas If the reading is only 40 LEL with the 50 gas applied a span calibration is needed Move the pointer to the Set Span entry and press EDIT twice Unity Gain may be used at any time to cancel incorrect calibrations and start again WX16 User Manual 22 Alarn 1 Alarn 2 Set Span Alarh 3 Cal ZERO Data Fron Cal SPAN 50 80 Linearize Unity Gain Conf igure ad Per tar OFF Calibrate Seer tes OFF Entry Menu If input with Local Cal Figure 2 9 WX16 User Manual 23 2 3 System Configuration Menus Some items needing configuration are not specific to a channel but affect the entire WX16 system These are located in the system entry menu shown on the left side of Figure 2 10 System menus are accessed by pointing to the desired item and pressing EDIT SYSTEM CONFIGURATION MENUS Votes entry determines the number channels needed to set Relay 1 or Relay 2 Acknowledge is disabled when no A2 Votes are entered lass SRi Failsafe MO R2 Failsafe HO RS Failsafe VES Discrete Relay Common Relay 1 Piezo Alarn OFF Connon Relay 2 d Rlarm I BEEP Disc Relay Rlarn 2 on Horn Piezo Failsafe ore Horn Grour t i Reknowledee VES Diarlav Gin HO Comm Parts 8 16 Ch Node Piezo Horn Rel
32. T key moves the cursor to the next position within a field When the field is complete EDIT clears the cursor and loads it into non volatile memory where it is retained indefinitely With no cursor present NEXT closes open menus in reverse order and returns the LCD to the most recent data display WX16 User Manual 14 2 2 Channel Configuration Menus Figure 2 1 illustrates the menu tree for configuring Channel variables These items affect only the specific channel selected System specific variables are in the menu tree shown in section 2 3 CHANNEL MENUS TREE Setroint Latcning No Teie On a On Deles wo Off Delay Dim Mora Drive Ves Alarm oc 2 menu Setroint 040 Latehine o Tre on nin Tu LeveL Setscint me ewe FAMAT r Alarm 3 Fault mems If for A3 level mob Bir Hin Rau 008 Ne Rau mama Rerote ID et Alias 33081 Hirter Menu If input ts Modhus input From menu Ness sr enert Eunite sit Decimal Pow Channel Oa Vee Cow To XX If input with Local Cal Figure 2 1 WX16 User Manual 15 2 2 1 Channel Setup Entry Menu The entry menu shown on the left side of Figure 2 1 allows access to all configuration variables for the selected channel These are Alarm 1 Alarm 2 Alarm 3 Data From Linearize Configure and Calibrate 2 2 2 Alarm 1 Alarm 2 Horn Relay Setup Menu Alarms 1 and 2 are identical except A1 may not be
33. U s in milliseconds This is useful when an RTU is limited in how fast it may respond to consecutive data requests The Echo ACK echo acknowledge menu allows alarm reset alarm acknowledge functions be sent from the ModBus master port to connected ModBus slave devices having ModBus coil 2001 assigned as the reset acknowledge coil This menu may be set to OFF LCL local or MB LCL ModBus local Off disables the feature and 2001 coils of slave devices are unaffected LCL only writes to the 2001 coils of connected RTU s when the local Reset pushbutton is pressed MB LCL writes these coils if this WX16 s 2001 coil has been reset via mobus AND when the local pushbutton is pressed The MB LCL option is useful if WX16s are being cascaded from an HMI or other ModBus master A short time delay between reset of remote RTU s and the primary WX16 may occur since remote resets are processed first IMPORTANT ALL MODBUS 2001 COILS ARE WRITTEN BY THIS IN FEATURE DO NOT CONNECT DEVICES WITH 2001 COILS CONTROLLING OTHER CRITICAL EVENTS 2 3 4 1 Master Port Radio Setup Menu The radio kit option may be connected to the comm1 master port and receive A vvireless data transmissions from up to sixteen of Oldham s OLCT 200 wireless sensor transmitters It is not possible to also use the comm1 master port to communicate to wired ModBus transmitters and if any channels are set for ModBus they will report comm error See Section 7 for a det
34. UIPMENT 316 STAINLESS STEEL NEMA 4X WALL MOUNT Figure 6 4 WX16 User Manual 60 6 3 XP NEMA 7 Explosion Proof Wall Mount Enclosure The WX16XP shown in Figure 6 5 is an aluminum NEMA 4X 7 wall mount enclosure designed for mounting into DIV 1 amp 2 Groups B C D potentially hazardous areas Eleven 8 channel I O option PCB s such as analog inputs or discrete relays may be mounted inside this enclosure It is suitable for mounting outdoors but an above mounted weather deflector shield is recommended Weight is approximately 110 pounds Properly ground the enclosure and follow national and local electrical codes T we gt x 2 o l e 24 vs o FRONT VAW BOTTOM VEW 238 SSS i 2 N we Llo le ma ee e an 7 dm a4 ur CONDUIT ENTRY ha Ae YP 4 PLACES _ svie u J Ar 1 Pe Vi oo pi u I ie to MOUNTING FOOT L rec T F CONDUIT ENTRY MOUNTING MOLE DNENSON HOL POSITION HORIZONTAL POSITION 15W 12 MTH VERTICAL POSTION Twat ST 71XP NEMA 7 EXPLOSION PROOF Figure 6 5 6 4 Main I O amp Option PCB Footprint Dimensions WX16 controllers have virtually unlimited possibilities for configuration of options such as analog I O discrete relays printer interface and others All WX16 enclosure styles require the Main I O PCB Figure 3 1 but also support the mounting of additional option PCB s as described below e WX16PM Panel Rack Mount supports 2 option
35. USER MANUAL WX 16 Sixteen Channel Controller u nn ee OLDHAM Revision 01 1 Reference Firmware 6 09 rev 4 7 The Fixed Gas Detection Experts WX16 User Manual 2 THE INFORMATION CONTAINED IN THIS MANUAL IS ACCURATE TO OUR KNOWLEDGE As a result of continuous research and development the specifications of this product may be modified at any time without prior notice IMPORTANT INFORMATION The modification of the material and the use of parts of an unspecified origin shall entail the cancellation of any form of warranty The use of the unit has been projected for applications specified in the technical characteristics Exceeding the values cannot in any case be authorized LIABILITY Neither Oldham nor any other associated company can be held liable for any damages including without limitations damages for the loss or interruption of manufacture loss of information defect of the WX4 unit injuries loss of time financial or material loss or any direct or indirect consequence of loss occurring in the context of the use or impossibility of use of the product even in the event that Oldham has been informed of such damage SAFETY INSTRUCTIONS Labels intended to remind you of the principal precautions of use have been placed on the unit in the form of pictograms These labels are considered an integral part of the unit If a label falls off or becomes illegible see to it that it is replaced Warning Read amp
36. a password character or network number and makes network eavesdropping more difficult A transceiver will not go in range of or communicate with a transceiver operating on a different System ID Mode may be set for CLIENT or SERVER For a single WX16 communicating to up to sixteen battery powered OLCT 200 transceivers Mode must Server To prolong battery life OLCT 200 s sleep most of the time and therefore may not be Servers If an application calls for multiple WX16 locations only one may be set for Server and all others must be Clients This single Server transmits a beacon that all of the network s Clients synchronize to ONLY ONE SERVER PER NETWORK WX16 User Manual 64 RADIO COMPIG 900 MHZ Conmon Relay 1 Slave ID 81 HOP Channel xx Conmon Relay 2 Slave Baud 9688 Systen ID Kx Disc Relays Parity NONE Node CLIENT Horn Piezo UART Timer 68S Conm Ports ra Mastr TO 85GOnS 8 16 Ch Mode NEXT Mastr PR 035m5 Radio Setur Entry menu Serial Ports Radio Config Figure 7 2 7 2 Wireless Receiver Mode Wireless Receiver mode is exclusively for wireless communication to Oldham s OLCT 200 wireless sensor transmitters See www oldhamgas com for more details In Receiver mode the radio connects to the WX16 s master port and receives input data from up to sixteen OLCT 200 sensor transmitters Wired and wireless inputs may be mixed between the VVX16 s sixteen channels so it is possible to also accept wired signals from analog i
37. acknowledged and front panel LED indicators are yellow while A2 s are red Since their configuration menus are the same only one is shown in Figure 2 2 for clarity Channel X Channel 5 Measurement Name ALARM 172 Setur Alarm 1 Setroint 20 00 Alarm 2 Latching NO Alarm 3 Trier On HIGH Data From On Delav 00s Linearize Off Delay 88m Configure NEXT Hern Drive Yes Entry Menu Alarm or 2 menu Figure 2 2 The first entry determines the Setpoint value where the alarm trips It is entered in engineering units For example if a channel monitors 0 50 ppmH2S and the alarm must trip at 10 ppm the correct entry is 10 00 e Latching determines either manual or automatic alarm reset operation YES requires a manual Alarm Reset to unlatch the alarm even though an alarm condition no longer exists YES also causes this alarm group s common relay front panel LED and optional discrete relay to latch NO allows all outputs for this alarm to automatically reset as soon as the alarm condition clears e TRIP ON is set to HIGH for increasing alarms or LOW for decreasing alarms to determine if the alarm activates upon exceeding or falling below the setpoint e The ON DELAY OFF DELAY entries allow ON and OFF time delays affecting how long the setpoint must be surpassed before an alarm event transition occurs ON delays are limited to 10 seconds while OFF delays may be as long as 120 minutes Delays are useful in many applications to prevent nuis
38. ailed discussion of WX16 wireless operation System Setur RADIO CONFIG Serial Ports 968 MHZ Common Relay Slave ID ei Mb HOP Channel xx Common Relay Slave Baud 9688 Sustem ID xx Disc Relays Parity a Mode CLIENT Horn P Comm Ports RT Teams 8 16 Ch Mode j Mastr PR 350nS KNEXT Echo ACKkormerc Radio Setur Entry menu Serial Ports Radio Config Figure 2 14 2 3 5 Eight Sixteen Channel Modes The system menu allows setting the WX16 controller to accept either 8 or 16 channels If 8 channels are selected by this menu they are channels 1 8 and 9 16 are disabled WX16 User Manual 28 EDIT Common Relay 1 gt Channels 16 Common Relay 2 Disc Relays Horne Rieza 8716 Ch Mode NEXT Entry menu 8 16 Channel Config Figure 2 15 2 3 6 Sensor Information Sensor Info is available when at least one channel has Sensor Life activated in the Marker menu see section 2 2 4b The Sensor Info screen displays each channel s sensor status as illustrated in Figure 2 16 Channels with Sensor Life disabled indicate Option Disabled above the corresponding empty bar graph If Sensor Life is enabled the channel will have its Measurement Name above the bar or an empty bar with a Cal Required label Cal Required indicates no Calibration Marker value has been received by the WX16 SENSOR LIFE Measurement Name Option Disabled 81 89 vn Cal Rewuired Option Disabled 93 Cal Resuired 11 Ortion Disabled
39. als per channel for distributing power and receiving analog inputs These are WX16 User Manual 32 EXC and HI LO inputs TB2 with only two positions is for connecting the power supply for powering external transmitters Precision 100 ohm resistors R1 R8 between each channel s IN LO and IN HI terminals are socketed termination resistors for 4 20mA inputs These may be removed if voltage inputs are to be applied EXC and IN LO terminals are bussed together internally EXC terminals are tied directly to TB2 1 and IN LO terminals are tied to TB2 2 Bussing allows transmitter power to be brought into the system at a single point TB2 and distributed back out at each channel s EXC IN LO terminals to simplify field wiring Figure 3 3 includes typical wiring to 2 amp 3 wire 4 20mA transmitters JP1 determines if the 8 analog inputs are applied to channels 1 8 or channels 9 16 Connecting more than 8 analog inputs requires 2 PCB s with one JP1 set for channels 1 8 and the other set for channels 9 16 WX16 User Manual 33 2 EES k En E T JP determines ths B channel u i j L il Per er AT ETC gp for CHs 1 8 0r 916 2 PCB 4 asante are rocpired for 16 SO amem used to Canes J ir sodssesas C II resistors RHG LE F a are 100 dm terrinetions for 4 20mA us 02 VIC Ps may 8 m m pM excepted by resso oca IBook morari baye ar aa gp ABBA 4 pews a vr dymom EXC DE HM D PC HM w
40. ance alarms and unwanted cycling into and out of alarm conditions e The HORN ON entry allows linking this alarm to the common horn relay NO causes the alarm to have no effect upon the horn relay Entering YES causes this alarm to turn the horn relay on steady or to pulse it depending upon horn configuration in they system menu see section 2 3 1 Discrete LED indicators on the front panel indicate the status of each alarm and relay Any new alarm event causes the associated LED to flash until Alarm Reset occurs causing an acknowledged steady on condition Operators should recognize new alarms by a flashing LED Alarm Reset also acknowleages or deactivates the horn relay until another new alarm occurs WX16 User Manual 16 IMPORTANT Appropriate diode DC loads or MOV AC loads snubber devices must be installed with inductive loads to prevent RFI noise spikes Relay wiring should be kept separate from low level signal wiring 2 2 3 Alarm 3 Fault Alarm Menu The discrete channel alarms identified as Alarm 3 Fault may be configured either as a 3 level alarm or as a Fault alarm indicating the input is out of range in the negative direction When used as a level alarm features such as on off delays latching and trip direction are also available It is important to understand that though discrete channel alarms LED s amp optional discrete relays may be set as Alarm 3 level alarms the common relay for this group is always a Fa
41. annel and system ID settings The difference is each Channel s INPUT DATA FROM menu must be configured with the correct MODBUS values to match the slave device instead of Wireless RF900 Wired and wireless inputs may be mixed between the WX16 s sixteen channels so it is also possible to accept wired signals from analog input option PCB s described in section 3 1 This is a popular application when the ModBus slave is another remote WX16 or Oldham s WX4 controller available with built in radio modem compatible with the WX16 Radio Kit Other ModBus slave devices may also be converted to wireless by addition of another Radio Kit at the slave s location 7 5 Antenna Selection 7 5 1 Dipole And Collinear Antennas These antennas are connected to the radio via a length of coax cable If the cable is larger than 6mm diameter 1 4 inch do not connect the cable directly to the radio connection on the WX16 enclosure Thick cables have large bending radii and sideways force on the connector can cause a poor connection Use a short flexible pigtail such as our 1000 2308 between the thick cable and the radio The polarity of these antennas is the same as the main axis and they are normally installed vertically They can be mounted horizontally horizontal polarity however the antenna at the other end of the wireless link would need to be mounted perfectly parallel for optimum performance This is very difficult to achieve over distance If the
42. antenna is mounted vertically it is only necessary to mount the other antennas vertically for optimum coupling this is easy to achieve Dipole and collinear antennas provide best performance when installed with at least 1 to 2 wavelengths clearance of walls or steelwork The wavelength is based on the frequency Wavelength in meters 300 frequency in MHz Wavelength in feet 1000 frequency in MHz Therefore 900 MHz antennas require at least 2 3 meter 2 feet and 2 4GHz 15 cm 6 inches Antennas may be mounted with less clearance but radiation will be reduced WX16 User Manual 67 If the radio path is short this won t matter It is important the antenna mounting bracket be well connected to earth or ground for good lightning surge protection 7 5 2 Yagi Antennas Yagi antennas are directional along the central beam of the antenna The folded element is toward the back and the antenna should be pointed in the direction of the transmission Yagis should also be mounted with at least 1 to 2 wavelengths of clearance from other objects The polarity of the antenna is the same as the direction of the orthogonal elements For example if the elements are vertical the Yagi transmits with vertical polarity In networks spread over wide areas it is common for a central unit to have an omni directional antenna and the remote units to have Yagi antennas In this case as the omni directional antenna will be
43. arm 2 real divisor Alarm 3 Real 1 16 41129 44 n a 3 n a alarm 3 real w o decimal point Alarm 3 DP 1 16 41145 60 n a 3 n a alarm 3 real divisor Fault Real 1 16 41161 76 n a 3 n a alarm 3 real w o decimal point Fault DP 1 16 41177 92 n a 3 n a alarm 3 real divisor WX16 User Manual 55 24 Hour Trend Database The 24 hour MAX MIN and AVERAGE trend data may be retrieved over the ModBus serial interface Each channel consists of 240 MAX MIN and AVERAGE values or one value for every 1 10 hour 6 minutes Since there are 16 channels this database equals 3 840 registers in addresses 33017 36857 Due to the large size MAX MIN or AVERAGE values may only be retrieved one at a time To improve bandwidth the master may retrieve the database in blocks of 120 registers at a time one half of a channel s data The C1 only updates these 3 840 registers upon receiving an update command from the ModBus master Type Channel First Last Read FC Write FC Notes Update MIN n a 2065 n a n a 5 Moves 24 hour MIN data trend to trend data base Update AVG n a 2066 n a n a 5 Moves 24 hour MIN data trend to trend data base Update MAX n a 2067 n a n a 5 Moves 24 hour AVG data trend to trend data base This update requires several seconds Therefore a data ready register is available to notify the master upon completion Type Channel First Last Read FC Write FC Notes MIN Ready n a 12065 n a 2 n a 0 data ready 1 update in progress AV
44. ay Slave ID et Slave Baud 9608 Parity MONE 4 ae HER HB asaans Meatr PR G 25805 Echo CK orem Radio Setur 8 16 Channel Config Figure 2 10 WX16 User Manual 24 2 3 1 Common Alarm Relays 1 amp 2 READ THIS SECTION CAREFULLY AND TEST ALL SETTINGS BY A SIMULATING WX16 INPUT CONDITIONS THAT SHOULD ACTIVATE THESE ALARM RELAYS Common Relay 1 amp Common Relay 2 menus are identical and therefore discussed only once It is very important to fully understand these menus since they determine the functions of each common relay Votes entry determines the number channels needed to set Relay 1 or Relay 2 Comnon Relay 1 Grour 1 16 Common Relaw 2 Failsafe OFF Disc Relays a Vokas amp Acknowledge is disabled when Conn Porte BR fhe no A2 Votes are entered 8716 Ch Mode Entry menu R1 R2 Relay menus are identical Figure 2 11 e The Group menu entry offers additional flexibility by controlling which channels trip this menu s common alarm relay The 3 choices are 1 16 1 8 or 9 16 Some applications have different types of sensors or sensors in different areas connected to the same WX16 Controller In these cases it may be undesirable for a sensor on channel 9 to trip the same relay as a sensor on channel 2 The Group menus may restrict this For example channels 1 8 might be set to trip common relay 1 while channels 9 16 trip common relay 2 Another possibility is channels 1 8 be set to trip common
45. ches 0 PCTLEL Bar Graphs Trend FS Chia Measurenent Hane MAR SETUP MENU MIN Y AUG Systen Channel 81 Channel 83 SPAN 100 Contrast Chanel 82 Channel 1 emit r gt Author ize Channel 9S Channel 1 aii COUNTS PCTLEL ZERO 8 Dissmostics Chanmei 04 Channel 12 3 u 1 UNLOCKED Channel 05 Channel 13 Charrel 86 Channel 14 Channel 07 Chanmnel 15 TS rara o a e Channel 8S Channel 16 ase 30 MINUTES Combination Setup Figure 2 0 WX16 User Manual 13 2 1 Setup Menu Configuration Variables inside system and channel menu trees allow optimum WX16 configuration for a wide range of demanding multi point monitoring applications Access to menus is via the Setup mode by pressing EDIT and activating the Setup screen shown in Figure 2 0 Menu trees are provided for each of the 16 channels and another for system variables Select the desired menu by scrolling with UP DOWN and EDIT to enter the menus 2 1 1 Changing Menu Variables Using the Keypad Upon entering a menu a pointer controlled by the UP DOWN keys indicates the selected variable Some are simple YES NO or ON OFF entries toggled by pressing the EDIT key Others such as Measurement Name and Eunits fields may have many ASCII character possibilities Allowed ASCII characters are as follows ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijkImnopgrstuvwxyz blank space l 8 0123456789 lt gt EDIT places a cursor over the item and UP DOWN scrolls through each allowed entry The NEX
46. e LEL Gain jumper into the position which reads between 8 volts and 1 2 volts on the test point with 50 LEL gas on the sensor Gain settings for each jumper position are as follows no jumper 1 LOW 7 MED 21 Hl 41 Multiple jumpers have an additive affect upon gain so the LOW and MED jumpers together provide a gain of 28 WX16 User Manual 37 Initial setup is now complete and normally only requires repeating if a sensor is replaced Final calibration of this channel may now be performed using the WX16 s electronic Cal Mode feature described in section 2 2 1 ZPD RR RSS Hor Gans __ 10 0191 JF sets dor Ois 0916 ws ed A MIC TP rel ami one Juan Daonet power Of 24440 usa te before O rig ades oe lan wax antes Oi A SENSAT Sj ALS Os TARTAN Gah CHA DNE Fen Soe 10 0192 DO B iT 6 a a i Dus Cherves OATBEAT Men pg rtp schen em a due DOE AAEE eae aS K a a woes a me i R 385 Ben grana dd ap m Oe pt Aena een AE pl ee OEM 8 Channel CATBEAD Sensor Option 10 0191 10 0192 Figure 3 5 3 1 5 Optional RTD 4 20mA Analog Input Board 10 0170 An optional 12 bit RTD Sensor Input board shown in Figure 3 6 allows these popular temperature sensors to be connected directly to the WX16 without additional signal conditioning or transmitters A 3 position range jumper allows setting the gain of the input bridge amplifier for the three popular ranges of 0 100 C 0 200 C or 0 400 C Other ranges are available
47. eans a large capacity conductor not a small wire with no coils or sharp bends All other devices connected to the WX16 need to be grounded to the same ground point There can be significant resistance between different ground points leading to very large voltage differences during lightning activity As many wireless units are damaged by earth potential surges due to incorrect grounding as are damaged bydirect surge voltage It is very difficult to protect against direct lightning strikes but the probability of a direct strike at any one location is very small Unfortunately power line surges and electromagnetic energy in the air can induce high voltage surges from lightning activity several miles away 7 6 1 Antenna Grounding Electromagnetic energy in the air will be drained to ground via any and every earth path An earth path exists between the antenna and the WX16 and to protect against damage this earth path current must be kept as small as possible This is achieved by providing better alternate earth paths It is important to ground the antenna to the same ground point as the WX16 Antennas are normally mounted to a metal bracket that should be grounded to the WX16 earth connection Surge energy induced into the antenna will be drained first by the mount s ground connection second by the outside shield of the coax cable to the ground connection on the radio and third by the internal conductor of the coax cable via the radio electronics
48. enna via connectors it is very important to weatherproof the connection using our 1000 2314 or equivalent sealing tape Moisture ingress into a coax cable connection is the most common cause of problems with antenna installations A three layer sealing process is recommended an initial layer of electrical PVC tape followed by a second layer of self vulcanizing weatherproofing tape 1000 2314 with a final layer of electrical PVC tape WX16 User Manual 68 Allowing a drip U loop of cable before the connection is also a good idea The loop allows water to drip off the bottom of the U instead of into the connection reduces installation strain and provides spare cable length in case later the original connectors need to be removed the cable cut back and new connectors fitted Avoid installing coax cables together in long parallel paths Leakage from one cable to another has a similar effect as mounting an antenna near another antenna 7 6 Surge Protection amp Grounding Voltage surges can enter the WX16 via the antenna connection power supply connection connections to other equipment and even the earth or ground connection Surges are electrical energy following a path to earth and the best protection is achieved by draining the surge energy to earth via an alternate path Wireless devices need to have a solid connection to earth via a ground stake or ground grid if the soil has poor conductivity Solid connection m
49. er Manual 11 WX16 User Manual 12 SECTION 2 2 0 Basic Operation The WX16 offers 3 graphic screens for viewing monitored data and a Setup menu screen for operator interface to configuration menus They are shown below in Figure 2 0 The Bar Graphs screen allows viewing of all active channels simultaneously The Trend screen displays a 24 hour trend one channel at a time The Combination screen displays a bar graph large engineering units and a 30 minute trend one channel at a time Input channels may be displayed in sequence with the UP DOWN keys The NEXT key switches between the 3 graphic data screens When WX16 power is applied the graphic LCD returns to the screen active when power was last removed Setup menus are entered by pressing EDIT from any data screen and scrolling to the desired menu using the UP DOWN keys Pressing EDIT again enters the selected menu s tree of variables This Setup mode may be exited manually by pressing NEXT or automatically when no keys are pressed for 5 minutes Alarm relays and front panel alarm LED indicators remain active during the Setup mode An AUTHORIZE menu offers a password feature to prevent tampering with WX16 parameters F chet 0 PCTLEL BS t 58 PCTLEL I rg Le a EC gt lonez 19 Pena Sale osata Gnin oa hae M koa ches PCTLEL iCh84 58 FCTLEL ches 8 PCTLEL f ches a egy en here oe ace B ll LU chev PCTLEL Ras 12 34 5 6 7 Si
50. et options 5 mont ranger types remain and Serena MODELS Le BIT indicate 16 tet bs unse kan bel abo supperts E 10 12 Sul Borna by eding Mia Mar Ryw maran ko custan the corrent comnts rames The WERELESS RIOT INPUT option J with cer proprictary wre Madden Figure 2 4 2 2 4 1 Min Max Raw Counts Menus The Min Raw and Max Raw counts entries included in Input Data From menus define the range of input counts that provide Measurement Range read out values described in section 2 2 6b This menu entry is determined by the A D converter resolution of the channel s input For example if the input is a 10 bit ModBus device with zero at 200 counts and 100 at 1000 counts then this menu s MIN should be set at 200 and MAX at 1000 If communicating with the WX16 s optional 12 bit Analog Input PCB the MIN should be 800 and the MAX 4000 If the input device s resolution is unknown the live counts variable on the bottom of the screen displays actual raw A D counts currently being read by this channel This reading may be used to test the input device for what A D counts are provided for zero and 100 ifthese values are unknown Forcing the input device to read zero should provide the A D counts value needed to make this channel s display also read zero Likewise forcing the input device to read 100 should provide the A D counts value needed to make the WX16 channel s display also read 100 WX16 User Manual 18 If ModBu
51. ete relays may be mounted inside this enclosure It is suitable for mounting outdoors but an above mounted weather deflector shield is recommended Weight is approximately 17 pounds Figure 6 3 provides important warning information concerning correct grounding procedures for non metallic enclosures Conduit entries are not provided so installers may place entries as needed Bottom or lower side areas are recommended Care must be taken to avoid drilling into circuit boards mounted inside the enclosure Properly ground the enclosure and follow national and local electrical codes 13 16 10 00 8 50 1 15 12 16 00 Note 4 mounting holes are 31 diameter ds El SHOCR HAZARD ADD LOCXING DEVICE TO CLASP ON BOTTOM RIGHT SIDE TO PREVENT CONTACT WITH DANGEROUS VOLTAGES REMOVE AC POWER BEFORE SERVICING EQUIPMENT NEMA 4X WALL MOUNT Figure 6 2 WX16 User Manual 58 GROUNDING OF EQUIPMENT AND CONDUIT Ground in accordance with the requirements of the National Electrical Code Conduit hubs for metallic conduit must have a grounding bush ing attached to the hub on the inside of the enclosure Ground ing bushings have provisions for connection of a grounding wire Non metallic condut and hubs require the use of a grounding A wire in the conduit Grounding bushings are not required To avoid electric shock System grounding is provided by connection wires from all con grounding must be duit entries to the s
52. evice is being driven by the relay All relays are rated at 5 Amp for 28 VDC and 250 VAC RESISTIVE loads IMPORTANT Appropriate diode DC loads or MOV AC loads snubber devices must be installed with inductive loads to prevent RFI noise spikes Relay wiring should be kept separate from low level signal wiring 2 3 2 10 0195 Discrete Relay Failsafe Mode 10 0195 Discrete relay options may also be configured to function in a Failsafe mode using the System Setup menu shown in Figure 2 12 Entering YES causes these discrete relays to have energized coils when no alarm condition exists for the associated channel and de energized coils when the alarm occurs Failsafe is useful for indicating failed relay coils and loss of power conditions Important 10 0195 zoning jumpers see Figure 3 4 should not be used when Discrete Relays menus are set for failsafe Zoning jumpers cause ANY relay in the zone to energize ALL other relays in the same zone Zoning of failsafe relays may be accomplished with wiring at the relay contact terminals Sustem Setur 4 83 Common Relay 1 NO annon Relm 2 A2 Failsafe NO Mb Disc Relaus A3 Failsafe VES Horn Piezo Comm Ports 8716 Ch Mode Entry menu Discrete Relay Configure Figure 2 12 2 3 3 Common Horn Relay amp Local Piezo The WX16 is equipped with a low decibel audible piezo that chirps when keys are pressed and may be configured to audibly indicate alarm conditions The common horn relay
53. hen there are no other zero span controls within the monitoring system since it is inappropriate to calibrate a signal at more than one point Therefore if calibration is to be performed at another transmitter or monitoring device the WX16 CAL MODE feature should not be used The CALIBRATION MENU allows entering the correct Cal ZERO amp Cal SPAN set point values needed to calibrate the sensor These are entered in the same engineering units as input range Set Zero amp Set Span controls in this menu allow pushbutton calibration by moving the pointer to each and pressing the EDIT key A live reading of the channel s value allows calibration checks to see if an adjustment is needed Unintentional calibrations are reset by the Unity Gain menu item Unity Gain resets zero offset to 0 and span gain to 1 It is useful for returning the calibration to a known starting place Sensor aging may be monitored by recording zero and span readings at Unity Gain when it is new and again at later dates when degradation may have occurred To check zero calibration apply the ZERO calibration value to the sensor and observe the live reading If the zero reading differs from the zero setpoint a calibration is needed To calibrate zero move the pointer to Set Zero and press EDIT A warning message explains that pressing EDIT again will change the zero calibration and any other key will exit The procedure for span calibration is identical For example if an LE
54. i Marker event expires Figure 2 6 2 2 5 Linearization Menu The linearization menu allows each channel to have its own linearization curve stored in the controller s non volatile memory Input versus output points must be entered in percent of full scale values This means if the range is 0 200 ppmH2S then 100 ppm is 50 of full scale Zero input will provide a zero output and 100 input a 100 output Nine intermediate points may be entered to define the curve Minput NOut pur 10 00 10 00 20 00 20 00 Alarm 1 Alarm 2 10 00 30 00 40 00 Alarm 3 0 00 Data From Diinrarise 50 00 50 00 9 Configure I 60 00 69 00 70 00 70 00 40 00 50 00 90 00 Entry menu Linearization menu Figure 2 7 2 2 6 Configure Menu From the entry level setup menu in Figure 2 8 the CONFIGURE menu may be entered for setting variables defining how the controller presents monitored data to the various graphic displays VVX16 User Manual 20 Entry menu Input Copy To menu Figure 2 8 2 2 6 1 Eunits Measurement Name ASCII Data Fields The first two items in this menu are for entering the 6 character engineering unit and 16 character Measurement Name ASCII fields Eunits should define the units of measure for what this channel is to display Measurement Name should describe the source of this data in the user s terminology Section 2 1 1 of this manual describes how to use
55. ications between the WX16 and printer during print attempts Examples of printed alarm events are shown below The format of each event from left to right is DATE TIME 16 character ASCII channel ID from the WX16 WX16 channel alarm IN or OUT status A buffer in the WX16 retains the most recent 30 35 printed events It is possible to dump the entire buffer to the printer from the menu shown in Figure 3 9 This is useful if printer problems have occurred causing missed printouts 05 22 03 08 21 00 Storage Tank 103 Chnl 1 Alarm 2 IN 05 22 03 08 21 01 Storage Tank 103 Chnl 1 Alarm 2 OUT 05 22 03 09 12 01 Storage Tank 103 Chnl 13 Alarm 1 IN 05 22 03 09 13 00 Fuel A Flow Chnl 9 Alarm 1 IN 05 22 03 09 13 05 Storage Tank 103 Chnl 1 FAULT IN 05 22 03 09 13 05 Fuel Dock Chnl 2 FAULT IN 05 22 03 09 40 10 Storage Tank 103 Chnl 13 Alarm 2 IN 05 22 03 09 40 14 Fuel Dock Chnl 2 FAULT OUT 05 22 03 09 40 14 Trans Pump 103 Chnl 3 FAULT OUT 05 22 03 09 40 14 Storage Tank 103 Chnl 1 FAULT OUT 05 20 03 11 53 37 Fuel A Flow Chnl 9 Alarm 1 OUT VVX16 User Manual 42 12C irtertace to Controller PRINTER INTERFACE 82 RSZ32 SERIAL CABLE DIAGRAM 59 MAX 10 0229 END 089 F PRINTER END 0825 N amp DSR 20 07R te 27X0 3TXD i saxo 556 186 ce 38 F 3 ii F ik O Umu Oh 3 PC INTERFACE 2 R5722 SERIAL CABLE DIAGRAM 50 MAX 10 0229 END 089 F PO END 089 F km EDSR 40Te 2K 110 NSONQOOSOS 31x0
56. iive npu or a JP17 Sed ec of Seren tr resistive inputs only Ri Ba Les Bas zj J1 amp J2 are r erchergadie 12C g Connectors used to add option 3 PCB assemblies 1o the T 71 a al ur er al 1d s A 38 8 Channel Resistive 4 20mA Input Option 10 0170 Figure 3 6 VVX16 User Manual 40 3 1 6 Optional 4 20mA Analog Output Board 10 0167 An optional 10 bit 4 20mA analog output board shown in Figure 3 7 may be connected to the I C bus Each channel s output will transmit 4mA for 0 readings and 20mA for 100 readings Loop drive capability depends upon the level of the WX16 s primary DC power supply With at least 20 volts DC primary power they are capable of driving 20mA through a 750 ohm load Outputs are self powered and DC power should not be provided by the receiving device Note This PCB requires nominal 24 VDC power be connected to TB2 terminals 1 amp 2 as shown in Figure 3 7 Suitable power is available from the WX16 Main I O board s TB2 terminal 10 amp 12 see Figure 3 1 Since the PCB has 8 channels two are required for 16 channel applications JP1 configures the outputs for channels groups 1 8 or 9 16 ek JP1 determines if this 8 channel CJL Analog Output PCB provides apts for CHis 1 8 of 9 16 tail 2 PCB asserrblies are required for 16 channels I 318 2 we r urchengubie DC i Li are option PCB asserbles to the ST
57. is similar to the common A1 amp A2 common relays WX16 User Manual 26 System Setur System Setur Horn Relay Common Relay Piezo Alarm OFF Common Relay Mb Alarn 1 BEEP Disc Relays Alarm 2 ON Horn Piezo Failsafe OFF Comm Ports i Horn Groue 1 16 8716 Ch Mod Do Acknowledge YES Display Alm NO Entry menu Piezo Horn Relay Figure 2 13 e Turning Piezo Alarm ON causes the audible piezo to duplicate the action of the horn relay This feature may be used to provide a low decibel indication of the status of the system s horn e Alarm 1 amp Alarm 2 menus control how this alarm level from each channel will affect the common horn relay Choices are OFF ON or BEEP one Hz Pulsating As an example A2 conditions might pulse the horn BEEP and A1 conditions to cause a steady horn ON Any other combination of these 3 choices is possible for A1 and A2 levels affecting the horn relay This feature is very useful since it allows the horn relay to serve as another level A1 level A2 or both for channels 1 16 1 8 or 9 16 Individual channel alarms may also be configured to not affect the Horn relay on a channel by channel basis see section 2 2 2 e Failsafe amp Horn Group menu entries are identical to the descriptions for menus Common Relay 1 amp Common Relay 2 in section 2 3 1 e Turning Acknowledge OFF allows the common Horn relay to drive devices other than horns or sirens such as a light or a fan e Display Alm Y
58. lears all to 0 Type Channel First Last Read FC Write FC Notes Alarm 1 Status 1 16 31049 n a 4 n a packed 16bit integer Alarm 2 Status 1 16 31050 n a 4 n a packed 16bit integer Alarm 3 Status 1 16 31051 n a 4 n a packed 16bit integer Common 1 16 31052 n a 4 n a packed 16bit integer LED Status LCD Display Screen Displayed Integer Type Channel First Last LCD Screen n a 31053 n a VVX16 User Manual 53 Read FC Write FC 4 n a Notes 8bit integer Sensor Life Type Channel First Last Read FC Write FC Notes Sensor Life 1 31065 n a 4 n a Signed 16bit integer Sensor Life 2 31066 n a 4 n a Signed 16bit integer Sensor Life 3 31067 n a 4 n a Signed 16bit integer Sensor Life 4 31068 n a 4 n a Signed 16bit integer Sensor Life 5 31069 n a 4 n a Signed 16bit integer Sensor Life 6 31070 n a 4 n a Signed 16bit integer Sensor Life 7 31071 n a 4 n a Signed 16bit integer Sensor Life 8 31072 n a 4 n a Signed 16bit integer Sensor Life 9 31073 n a 4 n a Signed 16bit integer Sensor Life 10 31074 n a 4 n a Signed 16bit integer Sensor Life 11 31075 n a 4 n a Signed 16bit integer Sensor Life 12 31076 n a 4 n a Signed 16bit integer Sensor Life 13 31077 n a 4 n a Signed 16bit integer Sensor Life 14 31078 n a 4 n a Signed 16bit integer Sensor Life 15 31079 n a 4 n a Signed 16bit integer Sensor Life 16 31080 n a 4 n a Signed 16bit integer Note 2 Disabled 1 CAL Required 0 100 Sensor Life
59. missions Arrow resets to right of screen after each transmission typically 5 minutes with Comm Error after 18 minutes Figure 7 4 7 3 Wireless ModBus Slave Mode Wireless MODBUS allows one or many WX16s to function as wireless ModBus slaves by connecting their RS 485 ModBus slave ports to a radio modem These wireless networks require a ModBus master such as a DCS HMI or another WX16 Sixteen Channel Controller also equipped with a radio modem As in all WX series wireless networks one transceiver must be designated as Server and all others as Clients No special configuration is required by the master or slave since this is a standard ModBus network However radios must have the same Hop Channel and System ID settings to communicate Radio modules may only be configured when connected to the WX16 s master port If it is necessary to modify Hop Channel and System ID settings the radio module may be temporarily connected to the WX16 s master port for configuration then moved back to the slave port for operation WX16 User Manual 66 The entire WX16 ModBus database including registers and supported Function Codes is documented in section 5 1 7 4 Wireless ModBus Master Mode WX16 applications as a Wireless ModBus master are similar to the Wireless Receiver mode described in section 7 2 and wiring to the radio modem is identical The radio setup menus described in section 7 1 may also be used for configuring hop ch
60. n Figure 2 0 PCTLEL PCTLEL PCTLEL PCTLEL PCTLEL PCTLEL 8 PCTLEL 0 PCTLE mem Us Figure 1 0 WX16 User Manual 8 1 1 Data Display Screens The WX16 Controller offers three distinct graphic displays for depicting the monitored data These are Bar Graphs 24 Hour Trend and Combination Each is shown in Figure 2 0 1 1 1 Trend Screen The WX16 Trend screen shown in Figure 2 0 displays a 24 hour trend of input data for the channel selected Horizontal tic marks are each hour and vertical tick marks are each 10 of full scale Dashed lines indicate alarm levels The graphic LCD is 240 pixels wide so each pixel represents 1 10 hour or 6 minutes worth of data The trend is 100 pixels high so each represents 1 of full scale in amplitude Since each data point must be collected for 6 minutes before it may be displayed it is likely input values will fluctuate during this interval Therefore MAX MIN and AVERAGE values are stored in RAM memory for each 6 minute subinterval To accurately portray the trend a vertical line is drawn between MIN amp MAX values for each 6 minute subinterval The AVERAGE value pixel is then left blank leaving a gap in the vertical line This is demonstrated in the noisy area of the 24 hour trend in Figure 2 0 If the MAX amp MIN values are within 2 of each other there is no need for the vertical line and only the AVERAGE value pixel is darkened as in the quiet areas The top portion of each trend
61. nput option PCB s described in section 3 1 Use the WIRELESS RF900 setting shown at center of Figure 7 3 ONLY FOR COMMUNICATION TO OLCT 200 WIRELESS TRANSCEIVERS See section 7 4 for setting up wireless networks with other ModBus slave devices OLCT 200 s transmit 200 counts for 0 and 1000 counts for 100 full scale readings so Input Min Max menu values should be 200 amp 1000 The Remote ID menu entry must match the Remote ID address setting in the OLCT 200 providing data to this WX16 channel Input Req is typically set to VALUE but also allows a BATT entry into this field Entering BATT causes the channel to display and alarm from battery voltage levels at this OLCT 200 Voltage level of the 3 6 volt lithium battery in this OLCT 200 is also displayed on this screen Channel INPUT DATA FRON Channel XX J Channel XX Measurement Name INPUT MARKER Alarm 1 WIRELESS RF 309 Marker Enable Y Alarn 2 Min Raw 80200 Marker 15 62 Alara 3 Max au 1096 Mark As IN CAL Data Fron Remote ID 1 255 Sensor life N Linearize Marker Menu Configure Ineut Res VALUE Battery 3 574 Entry Menu Wireless Monitor Marker menu Figure 7 3 7 2 1 Radio Status Alarms Wireless Receiver Mode When an WX16 channel s INPUT DATA FROM menu is set for WIRELESS RF900 in addition to processing the OLCT 200 s 10 bit counts value it also receives status bits indicating Communications Error
62. o Se nits D cc a BCs and EXC om om 0000000000 IEC H iO PO H 10 EC HM 10 va a 3 Pi oou oew 8 Channel Analog Input Option 10 0158 Figure 3 3 3 1 2 Optional Discrete Relay PCB 10 0195 An optional Discrete Relay PCB shown in Figure 3 4 adds eight 5 amp resistive form C relays per sixteen channel alarm group 2 PCB s required when utilizing more than 8 channels Each PCB may be configured via rotary switch S1 to function for ALARM 1 ALARM 2 or ALARM 3 FAULT for channels 1 8 or 9 16 A 1 minute time delay after power is provided to inhibit relay actuation until the system has had time stabilize Alarm groups or zones may be created by connecting adjacent channels together using JP4 as shown This creates a wire OR function with selected channels causing any alarm included within the zone to actuate ALL zone relays Failsafe operation of 10 0195 discrete relays may be programmed in the system menu as described in WX16 User Manual 34 section 2 3 2 Many WX16 applications utilize the common alarm relays see section 3 0 and do not require discrete relays for each of the 48 alarm events 16 A1 s 16 A2 s amp 16 A3 s If discrete relays are needed for all 48 alarms then six PCB s are required 5 VDC power to the discrete relay option PCB s is normally supplied from the WX16 Controller via the slender I C cables connected to J2 and J3 However I C cables are limited in ability to carry this power further than a few feet with
63. of electric shock VVARNINGS Shock Hazard Disconnect or turn off power before servicing this instrument NEMA 4X wall mount models should be fitted with a locking mechanism after installation to prevent access to high voltages by unauthorized personnel see Figure 6 2 Only the combustible monitor portions of this instrument have been assessed by CSA for C22 2 No 152 performance requirements This equipment is suitable for use in Class Division 2 Groups A B C and D or non hazardous locations only WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 WARNING EXPLOSION HAZARD DO NOT REPLACE FUSE UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS Use a properly rated CERTIFIED AC power mains cable installed as per local or national codes A certified AC power mains disconnect or circuit breaker should be mounted near the controller and installed following applicable local and national codes If a switch is used instead of a circuit breaker a properly rate CERTIFIED fuse or current limiter is required to installed as per local or national codes WX16 User Manual 7 Markings for positions of the switch or breaker should state I for on and O for off e Clean only with a damp cloth without solvents e Equipment n
64. ot used as prescribed within this manual may impair overall safety 1 0 General Description The Oldham WX16 Sixteen Channel Controller is designed to display and control alarm event switching for up to sixteen sensor data points It may also be set as an eight channel controller for applications needing fewer inputs Alarm features such as ON and OFF delays Alarm Acknowledge and a dedicated horn relay make the WX16 well suited for many multi point monitoring applications Data may be input to the WX16 by optional analog inputs or the standard ModBus RTU master RS 485 port A ModBus RTU slave RS 485 port is also standard for sending data to PC s PLC s DCS s or even other WX16 Controllers Options such as analog I O and discrete relays for each alarm are easily added to the addressable PC bus Option boards have 8 channels and therefore require 2 boards for 16 channel applications In addition to traditional analog and serial methods of providing monitored values the WX16 is also capable of sending and receiving wireless data as described in section 7 of this manual A 240 x 128 pixel graphic LCD readout displays monitored data as bar graphs trends and engineering units System configuration is through user friendly menus and all configuration data is retained in non volatile memory during power interruptions The WX16 front panel is shown below in Figure 1 0 displaying the 8 channel bar graph screen Additional data screens are shown i
65. out a significant voltage drop Some WX16 applications with relays for all 48 alarms may require up to 6 boards TB2 allows a heavier 5 VDC power cable to be connected from terminals on the back of the WX16 front panel assembly bypassing the I C cable A 20AWG pair connected to only one of the several TB2 s is sufficient when these boards are in close proximity to each other All relays are rated at 5 Amp for 28 VDC and 250 VAC RESISTIVE loads IMPORTANT Appropriate diode DC loads or MOV AC loads snubber devices must be installed with inductive loads to prevent RFI noise spikes Relay wiring should be kept separate from low level signal wiring WX16 User Manual 35 TEZ is used to supply edema St cots if dsowte are ripped by SVOC power to Aarm boards At AZ or Ad alas kr Os 1 8 oF 9 96 when they se mourted gt 5 See Chart aes ac RC si Area CO BO DGORETE RLY PRE cables provide but losses View BCI t ocar wath longer cable lengths DENS Biases Enara Si geciei A w IAAL Ah Sache A3 AJ FW See dats IS1 50ch1 8 at Kr xB 8 Channel Discrete Relay Option 10 0195 Figure 3 4 3 1 3 Optional Bridge Sensor Input Board 10 0191 An optional 8 channel 12 bit Bridge Sensor Input board allows these popular gas detectors to be connected directly to the WX16 without additional signal conditioning or transmitters Up to four dual channel 10 0192 modules may be installed in each 8 channel 10 0191
66. relay 1 while channels 9 16 trip relays on an optional discrete relay PCB configured for Alarm 1 see section 3 2 e Failsafe controls relay activation for this common relay Failsafe ON causes the relay to de energize during alarm conditions and energize when there is no alarm Thereby a power failure forces the relay contact to the alarm position Note the common Fault relay is always failsafe and may be monitored separately to indicate loss of power conditions in many applications e A1 and A2 Votes allows creation of logical AND function equations that control common relay 1 amp common relay 2 Default settings for common relay 1 are A1 Votes 01 and A2 Votes 00 which cause relay 1 to trip if any channel has an A1 level alarm active Default settings for common relay 2 are A1 Votes 00 and A2 Votes 01 which cause relay 2 to trip if any channel has an A2 level alarm active Example If either default setting is modified such that A1 Votes 02 and A2 Votes 01 then any two channels must have an A1 level alarm active and any one channel must have an A2 level alarm active to trip that relay REMEMBER One of the A1 s and the A2 could be on the same channel These level alarms must come from a channel included in the Group entry described above WX16 User Manual 25 e Turning Acknowledge ON not available on Alarm 1 allows the common relay to be deactivated during alarm conditions by an Alarm Reset This is useful if an audible d
67. s 32 BIT is selected a Byte Order entry appears at the bottom of the menu This determines WORD and BYTE alignment of data atthe remote ModBus transmitter when sending its 4 byte IEEE Floating Point values With the pointer on this entry the EDIT key toggles between the 4 possible modes Min Max Raw values are not used in this mode Note Each Data From item has a matching default Min Max counts value of 20 to 100 with 5 over under range applied If the default value is incorrect for the input device it should be edited 2 2 4 2 Marker Menus Some transmitters or monitoring devices providing WX16 inputs also indicate special modes of operation such as Calibration Maintenance or Fault by transmitting a special lt 4mA or negative Marker value The WX16 offers channel Marker menus for detecting and indicating such events see Figure 2 5 While active the WX16 displays a 6 digit ASCII message to indicate the special event and if equipped with 10 0167 4 20mA output option the WX16 also transmits the same lt 4mA value e Marker Enabled turns the marker feature ON and OFF e The negative Marker value is entered into the Marker field as a negative percent of full scale For example 15 62 of full scale detects a marker value of 1 5mA 1 5mA is 15 62 of full scale when 4 20mA is the range e The Mark As menu allows user entry of the 6 digit ASCII message to be displayed when the marker is detected harker
68. s provide voting logic for A ALARM 1 ALARM 2 FAULT and HORN Discrete relays are optional All relays are rated at 5 Amp for 28 VDC and 250 VAC RESISTIVE loads IMPORTANT Appropriate diode DC loads or MOV AC loads snubber devices must be installed with inductive loads to prevent RFI noise spikes Relay wiring should be kept separate from low level signal wiring 1 2 3 Ambient Temperature Range 25 to 50 degrees C 1 2 4 Humidity Range 0 to 90 R H Non Condensing 1 2 5 Altitude Recommended up to 2000 meters 1 2 6 Housings General purpose panel mount weighing 7 Ibs and including hardware for 19 rack mounting Figure 6 1 NEMA 4X wall mount in fiberglass enclosure weighing 17 lbs Figure 6 2 WX16 User Manual 10 NEMA 7 wall mount suitable for DIV 1 amp 2 Groups B C D weighing 110 Ibs Figure 6 4 Includes non intrusive magnetic keypad 1 2 6 1 Non Intrusive Magnetic Keypad The WX16 operator interface includes five front panel touch keys A magnetic keypad option offers these five keys with adjacent magnetic keys This option is included as a standard feature It is useful in applications where it may be inconvenient to open the enclosure s door to access the touch keypad 1 2 7 Approvals CSA C22 2 No 1010 1 and ISA S82 02 CSA C22 2 No 152 for combustibles UL 1604 C22 2 No 213 Div 2 Groups A B C D EN55011 amp EN61000 CE Mark CSA File 252022 and may be seen at CSA International org WX16 Us
69. servers will severely hinder RF communications The Server must be in a powered location as opposed to a battery powered OLCT 200 utilizing a sleep mode and Servers typically should be centrally located since all Clients must receive the beacon in order to communicate VVX16 User Manual 63 o Big Pes G Tacu 16 o 7 f 1 24 ie a eA 4 El 4 A 8 LI ie Ll 18 LL 19 p en RATIO a wu 10 24 zn xd GAL Di Ira i aw and n NS g bd e a j ER sen LIT mal PARA j I 0 4 Pal s j8x I 4 w ta 2 p a u i he El i oe h B e ISSQOSe 20002 220082 4 L L APTA ASAE A J R348 5407 o 308 s 2 4 GHz Radio Modem 900 MHz Radio Modem Note Note 10 0357 Has One Radio Module Installed 10 0364 Has One Radio Module Installed 10 0358 Has Two Radio Modules Installed 10 0365 Has Two Radio Modules Installed Figure 7 1 7 1 Radio Setup Menu Radio modules must be connected to the WX16 s master port for RADIO SETUP Pressing the EDIT key with the arrow pointing to the Radio Setup menu brings the RADIO CONFIG menus to the screen right side of Figure 7 2 Hop Channel may be set from 1 32 using the WX16 keypad and assigns the pseudo random radio frequency hopping pattern A transceiver will not go InRange of or communicate with a transceiver operating on a different Hop Channel System ID may be set from 1 255 using the WX16 keypad and is similar to
70. ters can be fitted to the data cable to protect against surges entering the wireless unit The same principle applies when the I O device is not close to the wireless unit thus the risk of surge increases Surge diverters for I O wiring are available to protect the wireless unit WX16 User Manual 70 WX16 User Manual 71 P Sa OLDHAM The Fixed Gas Detection Experts EUROPEAN PLANT AND OFFICES ZA Est rue Orfila CS 20417 62027 Arras Cedex FRANCE Tel 33 0 3 21 60 80 80 Fax 33 0 3 21 60 80 00 Website http www oldhamgas com AMERICAS ASIA PACIFIC EUROPE Tel 1 713 559 9280 Tel 86 21 3127 6373 Tel 33 321 608 080 Fax 1 281 292 2860 Fax 86 21 3127 6365 Fax 33 321 608 000 americas oldhamgas com sales oldhamgas com info oldhamgas com
71. the front keypad to modify these fields 2 2 6 2 Input Measurement Range The ZERO SPAN entries allow configuration of the measurement range displayed by this channel Measurement Range works along with A D Counts menus described in section 2 2 4a to define the range of the input signal s engineering units For example if a channel s input is 4 20mA from a transmitter monitoring O to 10ppm chlorine then the Zero value should equal 0 000 and the Span value equal 10 00 The six ASCII engineering units previously entered are automatically displayed at the top of each menu as a reminder Four digits must appear in this entry so trailing 0 s may appear here that are not displayed on other data screens 2 2 6 3 Decimal Point Resolution Resolution of displayed channel values is configured in this menu by setting the number digits trailing the decimal point Values are limited to a maximum of four digits and a polarity sign An auto ranging feature displays the highest resolution allowed by this menu s decimal point entry For example if three decimal points are entered and the range is 0 to 100ppm the reading will be 0 000 at Oppm and 100 0 at 100ppm However this may be undesirable due to the high resolution at zero unless the sensors output is extremely stable If decimal points are limited to one the Oppm reading becomes 0 0 and the 100ppm reading remains 100 0 Resolution may be limited further by setting decimal points to 0 In the above
72. ubpanel or to other suitable point which pro installed by the customer vides continuity Any device having a metal portion or portions as part of the installation i Aqui ES laba ont extending out of the enclosure must also be properly grounded do not provide grounding between conduit connections TYPICAL GROUNDING ILLUSTRATIONS METALLIC CONDUIT NON METALLIC CONDUIT CONNECTOR LOCKNUT GHOUNDING BUSHING GROUNDING WIRE GROUNDING CONNECTION Figure 6 3 VVX16 User Manual 59 6 2 NEMA 4X Wall Mount 316 Stainless Steel Enclosure The WX16 shown in Figure 6 4 is a 316 stainless steel NEMA 4X wall mount enclosure Seven 8 channel I O option PCB s such as analog input or discrete relays may be mounted inside this enclosure It is suitable for mounting outdoors but an above mounted weather deflector shield is recommended Weight is approximately 30 pounds Conduit entries are not provided so installers may place entries as needed Bottom or lower side areas are recommended Care must be taken to avoid drilling into circuit boards mounted inside the enclosure Properly ground the enclosure and follow national and local electrical codes i i d ls Ll Ll Ll 21 00 ODOR OPEN CLEARANCE SHOCK HAZARD ADD LOCKING DEVICE TO CLASP ON MIDDLE RIGHT SIDE TO PREVENT CONTACT WITH DANGEROUS VOLTAGES REMOVE AC POWER BEFORE SERVICING EQ
73. ult alarm The fault out of range threshold for the channel is the most recent Fault trip point entered prior to changing the menu to Alarm 3 The following example describes how to configure both the Fault out of range and Alarm 3 evel trip points for a channel Example If the common Fault relay must trip as the input falls below negative 10 of full scale and the discrete alarms trip as the input exceeds a level then the 10 Fault setpoint must be entered first Toggle the TYPE menu entry to FAULT and enter 10 00 into the setpoint entry Next toggle the menu back to LEVEL and enter the desired Alarm 3 level setpoint The 10 Fault value is retained in memory even though it no longer appears on the menu All relays are rated at 5 Amp for 28 VDC and 250 VAC RESISTIVE loads Channel Channel XX Channel Measurement Nane ALARM 3 Setur ALARM J Setur Alarm 1 Setroint 5 009 Setroint 68 00 Alarm 2 Ture Fault Latching NO Al m 3 Trir On HIGH Data From Tyre LEVEL Linear ize Configure Entry Menu Alarm 3 Fault menu If for A3 Level Figure 2 3 2 2 4 Data From Menu to Set Input Source Channels may be independently configured to accept input data from the following sources also see Figure 2 4 e An analog input PCB attached to the I C bus e A sensor input PCB attached to the I C bus e The ModBus RS 485 master port connected to ModBus slave devices Note Each ModBus menu selection also requests the RTU and the
Download Pdf Manuals
Related Search
Related Contents
Philips LED monitor 227E3LSU FR - MOB-5045 - Manual Android 4.2 Sony VPL-CS21 User's Manual Biblio Clin d `œil Severin WK 3374 electrical kettle MARINE RADAR/ARPA FAR-2827W/2837SW カップシーラー NHJ2 PDF View - Onset CHARGEUSES 724K/744K/824K/844K-II Copyright © All rights reserved.
Failed to retrieve file