Installation Guide SNMP/Web Adapter

image

Contents

1. 1024748 SitePro SG Series UPS LP33 Series UPS LAN OO Ours o Do eset O Active UTP 10 100 L RS 232 e 1 RJ45 Connector Ethernet connection 10Base T or 100Base TX e 2 LEDs Ref specific section e 3 RS 232 port Local console connection 115200 N 8 1 3 ph SNMP Web plug in adap w MODB RS485 P N 1024921 SitePro SG Series UPS LP33 Series UPS O ssl O Active UTP 10 100 R JL et RS 232 RS 485 e 1 RJ45 Connector Ethernet connection 10Base T or 100Base Tx e 2 LEDs Ref specific section e 3 RS 232 port Local console connection 115200 N 8 1 e 4 RS485 Port MODBUS RS485 Port Front Panel view of 3 ph SNMP Web plug in adap w MODB RS485 P N1024921 RS485 port following are connection details Wire Size 12 24 AWG Tightening Torque 7 0 Ib in Modifications reserved Page 10 25 GE_UPS_ISG_CNT_SNM_ BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy 1 ph SNMP Web plug in adapter P N 1024747 us ir O Front panel User interface view LS UTP 10 100 RS 232 d et Contact Interface e 1 RJ45 Connector Ethernet connection 10Base T or 100Base TX e 2 LEDs Ref specific section e 3 RS 232 port Local console connection 115200 N 8 1 e 4 Reset button HW reset e 5 RJ11 Connector Contact interface open collector output SP SNMP Web plug in adapter P N 1024746 e 1 RJ45 Connector Ethernet connection 10Base T or 100Base TX e 2 LEDs Ref specific sect
2. SNMP adapter to the UPS using the screw included in the SNMP Web adapter kit Install procedure for SitePro S6 Connectivity box PROTECTION PLATE Change the front plate with the smaller one delivered with the Kit Insert the SNMP adapter in the options slot Fix the front plate of the SNMP adapter to the connectivity box using the screw included in the SNMP Web adapter kit Modifications reserved Page 15 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy Install procedure for SG Series Connectivity box P4 Adv SNMP Card Protection Plate Change the front plate with the smaller one delivered with the Kit Insert the SNMP adapter in the options slot Fix the front plate of the SNMP adapter to the connectivity box using the screw included in the SNMP Web adapter kit 3 1 3 Connecting the card Refer to the architecture detailed in Section 2 4 Now the UPS may be switched on or back to normal mode from manual bypass Modifications reserved Page 16 25 GE_UPS_ISG_CNT
3. address to the adapter MAC address in your DHCP server Then reboot the adapter in order to have it retrieve the IP address The adapter is now accessible and configurable over the network 4 2 2 Reboot Every time the network settings are changed these become effective only after a reboot The adapter can be rebooted e Manually pressing the reset button on the front of the adapter e Using the console interface either serial connection or telnet by injecting the reboot command e Using a web browser selecting Reboot in the menu 4 3 Further information For more information and in order to make full use of all advanced functionalities provided by the SNMP Web adapter refer to the User Manual available on the CD ROM Modifications reserved Page 22 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy 5 ACCESS 5 1 WEB INTERFACE After the installation and configuration of the SNMP Web adapter the connection can be tested with a web browser e Launch the browser e Enter the URL of the SNMP Web adapter http lt IP gt e g http 192 168 24 14 e When prompted enter username and password by default these are set to ge and ge e The SNMP Web adapter home page will be shown 9 2 TROUBLESHOOTING If no answer is received from the adapter verify the adapter installation cabling and network configuration Check the Ethernet connection to the adapter by launching a pin
4. e 10 100 Mpbs connection speed e Use of DHCP BOOTP or manual configuration for the TCP IP network settings e SNMP Agent e Web server e Console interface e UPS status alarms readings event logging over different interfaces e Digital outputs open collector outputs for relay drive 1 ph plug in version only e SNMP Traps and E mail notification upon UPS event e Advanced security features 2 4 ARCHITECTURE ARCHITECTURE DIAGRAM Ethernet Local console NOTE only required for configuration L Contact i f 1 ph plug in version only 2 5 ADDITIONAL DOCUMENTS The SNMP Web adapter is provided with a CD ROM containing the following documentation e Installation Guide e User Manual e SNMP Management Information Base MIB e Release notes and other instructions as applicable Modifications reserved Page 13 25 GE_UPS_ISG_CNT_SNM_ BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy A INSTALLATION NOTE Strictly observe the UPS Safety Rules Read carefully the UPS User Manual amp Installation Guide before installing or operating the equipment If any problems are encountered with the installation procedure here described please contact the nearest Service Centre before proceeding 3 1 3 phSNMP WEB plug in adapter P N 1024748 NOTE SitePro customers only SitePro units produced before 2003 require an additional protective grou
5. not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures e Reorient or relocate the receiving antenna e Increase the separation between the equipment and receiver e Connect the equipment into an outlet on a circuit different from that to which the receiver is connected e Consult the dealer or an experienced radio TV technician for help 3 ph SNMP Web plug in adapter P N 1024748 3 ph SNMP Web plug in adap w MODB RS485 P N 1024921 SP SNMP Web plug in adapter P N 1024746 These devices have been tested for compliance with the following standards e EN 61000 6 2 e EN 61000 6 4 WARNING This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to rad
6. GE Digital Energy Installation Guide Uninterruptible Power Supply SNMP WEB ADAPTER P N 1024748 3 ph SNMP Web plug in adapter P N 1024921 3 ph SNMP Web plug in adap w MODB RS485 P N 1024747 1 ph SNMP Web plug in adapter P N 1024746 SP SNMP Web plug in adapter GE Consumer amp Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41 0 91 850 52 52 www gepowerquality com CE imagination at work Cored Quality System ISO 9001 Digital Energy 3 ph SNMP Web plug in adapter 3 ph SNMP Web plug in adap w MODB RS485 EES 1 ph SNMP Web plug in adapter SP SNMP Web plug in adapter Date of issue 10 10 2012 File name GE_UPS_ISG_CNT_SNM_BAS_ CRD_1GB_V020 Revision 2 0 P N 1024748 Identification No P N 1024921 P N 1024747 P N 1024746 2 0 New SNMP Web Adapter 10 10 2012 COPYRIGHT 2012 by GE Consumer amp Industrial SA All rights reserved The information contained in this publication is intended solely for the purposes indicated The present publication and any other documentation supplied with the UPS system is not to be reproduced either in part or in its entirety without the prior written consent of GE Digital Energy The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail The content of this publication may be subject to modification without pr
7. MP 115200 HyperTerminal Active IP 3 168 196 2011 Mask 255 255 254 0 Gateway 3 18 196 1 boot method DHCP IP Address 192 168 1 89 Subnet Mask 255 255 255 0 Gateway 192 168 1 254 Save settings Reboot Help Quit_ 1 2 3 4 5 R H Q Modifications reserved Page 20 25 GE _UPS_ISG_CNT_SNM_BAS_CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy NOTE Although the console interface provides a full set of commands access using the serial connection is only needed for initial configuration when no DHCP server is available or the IP address is unknown The quick network configuration menu provides a simple interface for basic network configuration For all other settings the user friendly web interface is recommended NOTE Save the settings Apart from some network parameters most setting are immediately active However the adapter will revert to the last saved settings at reboot Therefore in order to permanently modify the SNMP Web adapter setting remember to save the configuration after every change This can be done e Pressing S on the quick configuration menu e Entering nvsave at the command interface prompt 4 1 2 Configuration via the network TELNET e Launch a telnet client e g on a PC running Windows select Run from the Start menu and type telnet lt IP gt e The default username login and password are ge and ge e Acommand line configuration int
8. P N IO320208l 14 e Pe eier elee E e a a s c ee en er ene eT evn nN enn ore rere weve On ey eT ASEE AEA TAEAE 14 3 1 2 Installing the SNMP Card in option sot 15 Be CASSIUS COG EE 16 3 2 1 PHSNMP WEB PLUG IN ADAPTER P N 1024747 viucccccecccsssssscssssesscssssescsssssessssssessssssseecssssssssssssescssssusessssseesssssetesssneeessasees 17 SS SP SNMP WEB PLUG IN ADAPTER P N LO24 222 EE 17 A SB E E er er nee ene eee eee ee 18 341 UTP 10 100 RJ4S e 18 Ae Pe AA GE 18 3 4 3 Contact interface RJ11 port 1 ph plug in version only 18 aA PODEU EU a a EE E EE OO R 19 JA ER H 19 E CONFIGURATION E 20 AL UR ARME TE 1 pass scsccnsceucaseceesycesca ies loases scssonscacuceusecscoscoces eds csses leo ozccs ces seusaveascusecscs eased es ed 0s losseusescuseaseazeoseovesieaieeweasooied 20 4AL1 ge ut Lelleg Tee serdi Connectors a a 20 ME e S SaR Sa a e 21 ae NEOR EE 0 cee eee OOOO OONA 22 42 1 Default configurator EE 22 E ee 22 a E be e e EE RA acta secesazasanensensennennsnsesessseaseaeassaseaseaseaseasensennsnsssessssseaseassassassazsansaseaseavennsssssessssssaatantassazsansaseaneavennensssesisisteniestia 22 T ee EE 23 EES EA E AEAEE AEAEE EAEE AAAA E E EEA AE AN AE 23 E IE EE POA TEN E 23 e Hr UUW FEET EI VE FUN I West snsnvs testa ssaadecaeeseansansannassaenssonsnnesventeateasaasastassansassansannaveaseaseasessesssaseataasisiaseassaseassaseaneaseaseaseaveanatetentiate 23 CUSTOMER SUPPORT viscerececcecscsteccersccsctccssice
9. _SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy 3 2 1 phSNMP WEB plug in adapter P N 1024747 e Switch off the UPS and wait approx 2 minutes or switch the UPS to the manual bypass In the latter case please ensure that the mains input is reliable during this period e Install the SNMP WEB Interface card in the RS232 option slot For more details about the slot please read the UPS User Manual e Switch on the UPS or go back to normal mode from bypass 3 3 SPSNMP WEB plug in adapter P N 1024747 e Switch off the UPS and wait approx 2 minutes or switch the UPS to the manual bypass In the latter case please ensure that the mains input is reliable during this period e Install the SNMP WEB Interface card in the RS232 option slot For more details about the slot please read the UPS User Manual e Switch on the UPS or go back to normal mode from bypass Modifications reserved Page 17 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy 3 4 INTERFACES 3 4 1 UTP 10 100 RJ45 port Connection to Ethernet 10 100 Mbits s networks using a UTP cable 3 4 2 RS 232 RJ45 port Serial communication connection to a local console Use the serial cable provided with snmp web adapter RJ45 to DB9 fo
10. cescasssgscstacedenssscnpessteaceeeseansgeastcceeecsasasgensnocsesosasacaeesecesteniasareeseers 24 E AR FERDE OPP E 24 e NEERA RE 24 S WWW SERVER soisissa iini aia 24 C APPEND EE 25 Modifications reserved Page 4 25 Installation Guide SNMP Web Adapter Digital Energy 1 SAFETY RULES With this document GE Digital Energy gives to the user all the necessary information about the correct installation of the SNMP Web Adapter Please read carefully this Installation Guide before installing or operating the adapters We recommend that this manual be kept next to the UPS for future references If any problems are encountered with the procedures contained in this manual please contact the nearest Service Centre before you proceed For more information on the UPS system please refer to the applicable Installation Guide and User Manual All maintenance and service work should be performed by qualified service personnel only The KNOWLEDGE of and FULL compliance to the safety instructions and the warning contained in this manual are THE ONLY CONDITION to avoid any dangerous situations during installation operation maintenance work and to preserve the maximum reliability of the UPS system NOTE While every care has been taken to ensure the completeness and accuracy of this manual GE Digital Energy assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this docum
11. ctions Follow the below instructions to activate and make Modbus RTU RS232 operational e After entering the required license key the Modbus RS485 protocol is activated Please refer to the user manual for necessary commands to activate the Modbus RS485 protocol e Perform the connections as per the below details m Pin1 D m Pin3 GND Wire Size 12 24 AWG Tightening Torque 7 0 Ib in e The Modbus RS485 protocol is available now and can be accessed through the above mentioned connections and can be accessed as per the user criteria Modifications reserved Page 19 25 GE_UPS_ISG_CNT_SNM_ BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter GE Digital Energy 4 CONFIGURATION 4 1 CONFIGURATION METHODS The SNMP Web plug in adapters can be configured using different interfaces 4 1 1 Configuration via serial connection e Connect the SNMP adapter to a computer using the RJ45 DB9 serial cable provided with the kit e Runaterminal simulator e g HyperTerminal on a PC running Windows e Configure the terminal simulator as follows 115 200bps 8 data bits 1 stop bit parity none flow control none Terminal emulation VT 100 COM1 Properties SNMP 115200 Properties e Establish the connection and press lt enter gt e The default username login and password are ge and ge e A command line configuration interface is entered Type menu to enter the quick network configuration menu SN
12. efer to the user manual for necessary commands to activate the Modbus Protocol e After the license is activated Plug out the SNMP card from UPS e Based on SNMP Web Adapter model select the jumpers as per the table below for Modbus RTUS RS232 to operate Product Part Desription Jumper Position 1024746 SP SNMP Web Adapter J3 2 3 J4 2 3 1024747 1 Ph SNMP Web Adapter J4 2 3 J5 2 3 1024748 3 ph SNMP Web Adapter J3 2 3 J4 2 3 1024921 3 ph SNMP w MODB RS485 J3 2 3 J4 2 3 e Plug in the card back into the UPS e Connect the RJ45 DB9 cable RJ45 end to the RJ45 RS232 port of SNMP card connect the DB9 end of this cable to the PC running the modbus master program e Start the Modbus master programifor eg Modbus tool and start the communication with the respective settings done for SNMP card e Please note console interface and is disabled when Modbus RS232 is active and functioning to reactivate the console connection restore the jumpers to the standard position and console will be operational 3 4 5 MODBUS RTU RS485 Modbus RTU RS485 is available with part number 1024921 Modbus RS485 is available at the RS 485 port Front Panel view of 3 ph SNMP Web plug in adap w MODB RS485 P N1024921 e RS485 port following are connection details o Pin1 D o Pin2 D o Pin3 GND e Wire Size 12 24 AWG e Tightening Torque 7 0 Ib in A three pin phoenix connector is provided for Modbus RS485 conne
13. ent GE Digital Energy refuses any responsibility in case of non observance unauthorised alterations or improper use of the delivered equipment Modifications reserved Page 5 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy 1 1 WARNINGS AND CAUTIONS GENERAL e Always strictly observe the UPS Safety Rules e Check carefully the integrity of the equipment In case you note some visible damage do not install the equipment but contact the nearest Service Centre e WARNING RISK OF ELECTRICAL SHOCK Do not remove any UPS covers there are no user serviceable parts inside e After switching off it takes up to 5 minutes for the DC capacitors to discharge because a lethally high voltage remains at the terminals of the electrolytic capacitors e All maintenance and service work should be performed by qualified service personnel e The outlet bars may be electrically live even when the UPS is disconnected from the mains STORAGE e Store the SNMP Web adapters in a dry location storage temperature must be within 25 C to 55 C 13 F to 131 F HANDLING e The SNMP Web adapters are ESD sensitive devices When handling the adapters only touch the front panel external cover and use suitable ESD protection e g wrist straps e TheSNMP Web adapters contain a removable lithium coin cell battery Perchlorate Material special handling may apply See www dtsc ca gov hazard
14. erface is entered WEB BROWSER e Launch a web browser e Enter the URL of the SNMP Web adapter http lt IP gt e The default username and password are ge and ge e Navigate the pages using the menu bar NOTE Save the settings Apart from some network parameters most setting are immediately active However the adapter will revert to the last saved settings at reboot Therefore in order to permanently modify the SNMP Web adapter setting remember to save the configuration after every change Modifications reserved Page 21 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy 4 2 NETWORK PARAMETERS The SNMP Web adapter connects to the network using the following parameters e P address identifies the adapter on the network e Subnet mask defines a range of addresses within the organisation e Gateway the node used for connection to addresses outside the subnet The adapter can be configured to obtain these settings automatically using DHCP or BOOTP protocols or to use static addresses manual configuration 4 2 1 Default configuration The SNMP Web adapter comes with a pre configured MAC address with the following format 00 12 93 Fx xx xx 00 12 93 identifies the manufacturer X XX XX IS a unique code for every adapter The MAC address is written on a label sticker on the SNMP Web adapter The factory default configuration for the SNMP Web adapter is using DHCP Assign the IP
15. g command from a workstation in the same subnet E g in a Windows system e Select Run from the Start menu e Enter ping lt IP gt e g ping 192 168 24 14 e Verify that the SNMP Card adapter is correctly replying 9 5 FURTHER INFORMATION For more information and in order to make full use of all advanced functionalities provided by the SNMP Web adapter refer to the User Manual available on the CD ROM Modifications reserved Page 23 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter E Digital Energy 6 CUSTOMER SUPPORT 6 1 FIRST LINE SUPPORT Please contact your local GE distributor for problems with the installation of the product or its use 6 2 INTERNET On line support available on request Internet access required 6 5 WWW SERVER We have a WWW server running at www gedigitalenergy com With your favourite web browser you can access the latest information from GE and download updates and manuals for this product Modifications reserved Page 24 25 GE_UPS_ISG_CNT_SNM_ BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter iE Digital Energy 7 APPENDIX A SitePro EARTH CONNECTION In order to guarantee correct functional behaviour the SNMP Web plug in adapter must be connected to protective earth UPS chassis On SitePro UPSs manufactured before 2003 the square plates delivered with the 3 ph adapter kit must be mounted refer to the pictures below for the installation detail
16. io communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Modifications reserved Page 8 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter GE Digital Energy 2 INTRODUCTION 2 1 CHECKING PACKAGE CONTENTS The SNMP Web adapters are delivered in different kits according to the model 3 ph SNMP Web plug in adapter P N 1024748 3 ph SNMP Web plug in adap w MODB RS485 P N 1024921 e 3 ph SNMP Web plug in adapter with pre installed standard front panel e A front panel designed for LP33 Series UPSs e Square plates for older SitePro UPSs e Mounting screws e Installation Guide e Third Party License ReadMe e CD ROM e RJ45 DB9 connectivity console cable Plates for old SitePro UPS ref Appendix A Front Plate LP33 Series UPS 1 ph SNMP Web plug in adapter P N 1024747 e 1 ph SNMP Web plug in adapter e Installation Guide e Third Party License ReadMe e CD ROM e RJ45 DBI connectivity console cable SP SNMP Web plug in adapter P N 1024746 e SPSNMP Web plug in adapter e Installation Guide e Third Party License ReadMe e CD ROM e RJ45 DB9 connectivity console cable Modifications reserved Page 9 25 GE_UPS_ISG_CNT_SNM_BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter GE Digital Energy 2 2 OVERVIEW 3 ph SNMP Web plug in adapter P N
17. ion e 3 RJ45 Connector RS 232 Local console connections 115200 N 8 1 e 4 Reset button HW reset Modifications reserved Page 11 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy LEDs The various front panel LEDs have the following meaning e LAN Netlink No LAN connection detected LAN connection established no communication LAN connection established receive or transmit active e UPS Fail OK No Fault No UPS Connection e Active Fault of device Device OK No fault Jumper Selection Following are the factory default jumper selection for SNMP Web Adapters To activate Modbus RTU RS232 protocol a change in the default selection is required Please refer the Modbus RTU RS232 section for jumper selection details Product Part Desription Jumper Position 1024746 SP SNMP Web Adapter J3 1 2 J4 1 2 1024747 1 Ph SNMP Web Adapter J4 1 2 J5 1 2 1024748 3 ph SNMP Web Adapter J3 1 2 J4 1 2 1024921 3 ph SNMP w MODB RS485 J3 1 2 J4 1 2 Factory default jumper configuration is necessary for SNMP Web Adapter installation and commissioning please ensure the default configuration as per the above table and it is advised not to change the jumper selection Modifications reserved Page 12 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter GE Digital Energy 2 5 FEATURES Each SNMP Web adapter provides the following features
18. ior notice Modifications reserved Page 2 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy Dear Customer We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE Digital Energy We trust that the use of the SNMP Web Adapters for our Uninterruptible Power Supply systems developed and produced to the highest standards of quality will give you complete satisfaction Please read carefully the Installation Guide which contains all the necessary information about the installation of the SVMP Web adapters Thank you for choosing GE Digital Energy Distributed by Your service contact GE Digital Energy General Electric Company CH 6595 Riazzino Locarno Switzerland Modifications reserved Page 3 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy Table of contents GE_UPS_ISG_CNT_SNM_BAS_CRD_1GB_V020 docx Page E SNPE HIR ssa ca ccc ec acto caces EE iuscsedevoeesuesseuseucas esau encsaeesecscecssevseeeass 5 BE EK EE IER EU E 6 ee e EHNEN 8 E Ch OU COIN WEE 9 MT ER D E IK EE 9 GC E s E A AA 10 GE a E E S chs A O OO eee veers ea 13 GE HK RT EN 13 2 5 ADDITIONAL DOCUMENTS ccessesssssessesssssssssussessssessessesssssssssssssusssssussussussucsucsucsecssssscsesssssssussusaussucaucaucaussessecseesecseeseeseeseenes 13 KW Lag Bue D 14 3 1 3 PHSNMP WEB PLUG IN ADAPTER
19. isk of electrical shock CAUTION The SNMP Web adapter contains a lithium coin cell battery RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS Perchlorate Material special handling may apply See www dtsc ca gov hazardouswaste perchlorate CAUTION The voltages on SNMP Web Adapter are SELV rated Connection of high voltages to snmp web adapter terminals will results in total damage of snmp web adapter Avoid connection of high voltage to terminals WARNING To prevent the risk of electric shock do not connect SELV circuits to high voltage circuits Modifications reserved Page 7 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy 1 2 EMC COMPATIBILITY 1 ph SNMP Web plug in adapter P N 1024747 This device has been tested for compliance with the following standards e EN 61000 6 2 e EN 61000 6 4 NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will
20. nd connection refer to APPENDIX A 3 1 1 Setting the logical address The logical address Is configured through dip switch SW1 in the following way YL gawes men om 1 Default setup SD w mm didosii did d d ddd d d i d i d l l t 5 ji d e Kr K zy Oo Ei j ei fo Tew he H vm WEI sm Z va f d i fu erh ru hy A GEHT N Li D GEI D II N 3 i f a s r f N CR gh AM s i i H V mu H gn H zt dg m wl DI cae Ae H Dip Switch SW1 NOTE The logical address is a critical setting when more than one SNMP Card is installed in the same UPS system Modifications reserved Page 14 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy 3 1 2 Installing the SNMP Card in option slot IMPORTANT Switch off the UPS and wait approx 2 minutes or switch the UPS to the manual bypass In the latter case please ensure that the mains input Is reliable during this period All cables must be disconnected from the card during the installation Install procedure for LANPRO 33 LP33 Series Option slot see description below for procedure Customer interface Remove the plate that covers the Option slot by cutting the edges which are holding the plate Take care the plate does not fall inside the UPS Slide carefully the SNMP adapter into the Options slot Fix the front plate of the
21. ouswaste perchlorate INSTALLATION e Switching OFF the unit does not isolate the UPS from the mains e Do not install the equipment in an excessively humid environment or near water e Avoid spilling liquids on or dropping any foreign object onto the equipment e The equipment should be placed in a sufficiently ventilated area the ambient temperature should not exceed 40 C 104 F BATTERY e The SNMP Web adapters contain a removable lithium coin cell battery The battery has been selected in order to power to the relevant devices for over 10 years therefore battery replacement should not be necessary and it is not recommended In any case replace only with batteries of the same type and properly dispose or recycle used batteries e Never dispose of battery in a fire they may explode e Donottry to open or mutilate battery their contents may be toxic e Never short circuit the battery Modifications reserved Page 6 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter Digital Energy ENVIRONMENT e Please take care of packaging material either save it for later use or recycle dispose in compliance with local and other applicable regulations e TheSNMP Web adapters contain a removable Lithium coin cell battery Dispose of used batteries in compliance with local and other applicable regulations WARNING The UPS contains hazardous voltages Observe carefully the safety instructions to prevent r
22. r connection to a PC Connector pin out as follows Pin Function 5 TD Transmit Data 6 RD Receive Data 4 GND 3 4 3 Contact interface RJ11 port 1 ph plug in version only Plug in contact interface port Connector pin out as follows Pin Function 1 Mains failure 4 On bypass AVR 3 2 General alarm 5 N C 8 6 3 Battery low 6 GND Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than already indicated by pin 1 3 4 AVR Automatic Voltage Regulation function on line interactive UPS only e g Match Series Contact interface outputs are specified for the following ratings e c max closed 30MA e Vcemax closed 0 4V 1mA e Ver max open 48V CAUTION The RJ45 and RJ11 port share the same GND signal Exercise caution when both interfaces are used at the same time particularly when connecting these interfaces to non floating ground systems Modifications reserved Page 18 25 GE_UPS_ISG_CNT_SNM BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter iE Digital Energy 53 4 4 MODBUS RTU RS232 Modbus RTU RS232 protocol is available with console connection RJ45 port The RJ45 to DBY cable shall connect the Modbus RTU slave of SNMP Web adapter to the PC running the Modbus Master program Follow the below instructions to activate and make Modbus RTU RS232 operational e After entering the required license key the Modbus Protocol is activated Please r
23. s Note Should the UPS be already equipped with the plates please ignore this step Square plates D II DT 8 8 ee tel Square plates mounting position Square plate mounting detail Plug in adapter earth connection Modifications reserved Page 25 25 GE_UPS_ISG_CNT_SNM_ BAS CRD_1GB_V020 docx Installation Guide SNMP Web Adapter