P90L User`s Manual
Contents
1. P90 BP36 NS NA a OC OO OC CO OD OO 35 t CO D CO D CO is OO I C 0 oxi cs Pad lt gt Xtreme Power Conversion Corporation Page 47 POOL 1500 3000 User s Manual Picture example as below Uninterruptible Power Supply Note The cable connection from the external battery connector to PCB is already present inside the battery box All the other cable connections should be made in accordance with the above wiring diagram P90 BP48 Batt Link PCBA Batt Link PCBA re TT Breaker jo Xtreme Power Conversion Corporation 1st battery bench a BB Is RED BLACK lj fol ig ig a al ja amp RED BLACK 2nd battery bench Page 48 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Picture example as below Note The cable connection from the external battery connector to PCB is already present inside the battery box All
2. ENVIRONMENT Efficiency Up to 98 ECO mode and 92 online mode 90 online mode for P90Lg 3000 Operating temperature 32 104 F 0 40 C Audible noise lt 50dBA Altitude 11 500 ft above sea level OPTIONAL Model number P90 BP36 36E P90 BP48 P90 BP 72 BATTERY PACKS Dimensions W x D xH 17 2 x 18 9 x 3 5 in 17 2 x 18 9 x 3 5 in 17 2 x 23 6 x 3 5 in 17 2 x 24 8 x 3 5 in E BP weight 58 1 Ibs 104 4 Ibs E 74 6 Ibs 104 4 Ibs Battery 6 12V 9AH 36V 8 12V 9AH 48V 12 12V 9AH 72V 12 12V 9AH 36V E AVAILABLE OPTIONS 5 year extended warranty bypass distribution XBDM power distribution XPDU 4 post rail kit 2 post shelf kit Depending on load level P90L capacity derates 20 at 100V output voltage P90Lg 3000 capacity derates 20 at 208VAC output voltage Xtreme Power Conversion Corporation Page 31 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Shipping List UPS 1 ViewPower CD 2 Horizontal brackets front 3 Tower stand brackets 4 Manual 5 4ft USB cable 6 Battery cable for UPS to external battery pack customer supplied Shipping List Battery Pack UPS EBP Anderson cable assembly Manual Tower stand brackets Horizontal brackets pe pP Xtreme Power Conversion Corporation Page 32 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Obtaining Service If the UPS requires Service 1 Use the TROUBLESHOOTING section in this manu
3. e CAUTION Do not open or mutilate the batteries The electrolyte from the batteries is toxic and harmful to the skin and eyes e CAUTION Risk of Electric Shock Hazardous voltage may exist between battery terminals and ground Test before touching with bare hands e CAUTION A battery can present a risk of electrical shock and high short circuit current The following precaution should be observed when working on batteries 1 Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of batteries Disconnect charging source prior to connecting or disconnecting battery terminals Do not plug or unplug the battery connector if UPS works in DC discharging mode VR WN Product Overview and Setup NOTE Before installation please inspect the unit Be sure that nothing inside the package is damaged Please keep the original package in a safe place for future use Xtreme Power Conversion Corporation Page 38 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Rear Panel View 1 DC connector connects to either UPS or 2nd battery box 2 DC breaker Battery over current protection breaker Installation and Setup with UPS Unpacking amp Inspection 1 Remove the battery box from the packing Note The battery box is very heavy be cautious when unpacking and lifting the unit to avoid injury 2 Check the inside pac
4. OR THE CONNECTED EQUIPMENT OR ANY ASSOCIATED EQUIPMENT LOSS OF SOFTWARE COST OF CAPITAL COST OF ANY SUBSTITUTE EQUIPMENT FACILITIES OR SERVICES DOWNTIME THE CLAIMS OF THIRD PARTIES INCLUDING CUSTOMERS AND INJURY TO PROPERTY Submitting a Load Protection Policy Claim 1 Any claim under the Load Protection Policy must be made within 10 days of the date of alleged damage to the Connected Equipment 2 Call the XPC technical support department at 1 800 582 4524 and obtain a Load Protection Policy Returned Material Authorization RMA number Have information on all applicable insurance or other resources of re covery payment that is available to the Purchaser and the name of the power utility supplier for the location of the Connected Equipment XPC will forward to the Purchaser a Load Protection Policy claims form which Xtreme Power Conversion Corporation Page 36 P9OL 1500 3000 User s Manual Uninterruptible Power Supply must be completed and filed with XPC within 30 days Mark the Load Protection Policy RMA number on the Product the Purchaser is returning Pack the Product in its original packaging or similar packing materials if the original packaging has been discarded Enclose the completed Load Protection Policy claim form and a copy of the Purchas er s original sales receipt for the Product in the box Mark the RMA number clearly on the outside of the box Ship the Product one way shipping charges paid by the Purchaser to
5. Reconnect the power cord only after signaling interconnections have been made Servicing of batteries should be performed or supervised by personnel with knowledge of batteries and the re quired precautions Keep unauthorized personnel away from batteries These UPS units are extremely heavy Caution should be taken in moving and positioning equipment The instructions contained within this safety manual are deemed important and should be closely followed at all times during installation and follow up maintenance of the UPS and batteries Xtreme Power Conversion Corporation Page 4 P9OL 1500 3000 User s Manual Uninterruptible Power Supply CAUTION The unit has a dangerous amount of voltage If the UPS indicator is on the unit s outlets may have a dangerous amount of voltage even when not plugged into the wall outlet because the battery may continue to supply power Care should be taken to undertake installation indoors free from electrically conductive particles which are under temperature and humidity control in order to reduce the risk of electric shock It is best to disconnect the device using the power supply cord Ensure that the equipment is placed in a position near the outlet where easily accessible Except for replacing the batteries all servicing on this equipment must be carried out by qualified service personnel Before conducting any maintenance repair or shipment first ensure that everything is turned off complete
6. XPC Corporation 230 Yuma Street Denver CO 80223 Attn LPP RMA 3 XPC will evaluate the Product to determine its level of functionality and will examine the Product for evidence of damage from a Power Disturbance If XPCs evaluation provides no evidence of damage from a Power Disturbance XPC will send to the Purchaser i a report summarizing the tests performed and ii a rejection of claim notice If the Product shows evidence of damage from a Power Disturbance XPC will request that all Con nected Equipment for which a Load Protection Policy claim has been submitted be sent for evaluation to either XPC or an authorized service center If it is determined that the Connected Equipment has been damaged by a Power Disturbance XPC will in its sole discretion issue payment to the Purchaser for either the cost of repair of the Connected Equipment or the Fair Market Value of the damaged Connected Equipment up to the dollar limits stated above XPC reserves the right to require the Purchaser to transfer title and deliver the Connected Equipment to XPC if it chooses to reimburse the Purchaser for the fair market value of the Connected Equipment XPCs maximum liability shall be reduced to reflect all such other payments or sources of recovery whether applied for or not 4 If XPC issues payment to the Purchaser to have the Connected Equipment repaired the repair must be per formed at a service center that is authorized by the manufacturer of
7. are indicates the wire fastener positions for the correct battery placement Note To install the second string of batteries repeat the same procedure on the right side of battery box Step 7 Connect all batteries following the wiring diagram shown in next chapter Xtreme Power Conversion Corporation Page 42 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Step 8 Put all batteries inside and secure in place with hold down brackets Note To install the second string of batteries repeat the same procedure on the right side of battery box Step 9 Put the metal top cover back on the unit Close the front fixing plate and the two parts of the front panel and secure it with screws Step 10 Connect the battery box to the UPS P90 BP48 Step 1 Open the package and place the battery box on a horizontal plane Step 2 Remove the removable front panel part by pulling it from the lower extremity Step 3 Remove the fixed part of the front panel by removing the 2 screw present Xtreme Power Conversion Corporation Page 43 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Step 4 Remove the metal top cover of the battery box by unscrewing 8 screws present on the two sides 4onthe right side and 4 on the left side 3 screws on the top and 4 screws on the back side oo q Step 5 Once the battery box is opened remove the battery hold down brackets present on the left side of the bat tery box by uns
8. code is shown as 14 and alarm is sounding continuously Xtreme Power Conversion Corporation Check that the input power cord is The AC i ili e AC input power is not con firmly connected to the utility nected well The AC input is connected to the Plug the AC input power cord into UPS output the AC input utility correctly Set the circuit to the closed posi EPO function is enabled tion to disable EPO function Line and neutral conductors of UPS Have a qualified electrician correct input are reversed the input receptacle wiring Check to make sure all batteries are properly connected The internal battery is incorrectly connected Battery voltage is too high or the de Contact vour dealer for support charger is in fault condition y PP Battery voltage is too low or the charger is in fault condition Remove excess loads from PSisi UPS is in overload UPS output UPS is in overload Devices con nected to the UPS are being fed directly from the electrical utility via the Bypass Contact your dealer for support Remove excess loads from UPS output After repetitive overloads the UPS is locked in the Bypass mode Connected devices are being fed directly by the electrical utility Remove excess loads from UPS output then shut down the UPS and restart The UPS shut down automatically because of the overload condition on the UPS output Remove excess loads from the UPS output and r
9. from the customer in a timely manner as agreed to with the customer once the customer has requested and received a Return Material Authorization RMA number DOA equipment is defined as equipment that does not properly function according to user documenta tion when initially received and connected in conjunction with proper procedures as shown in the user documen tation or via support provided by XPC Corporation personnel or authorized agents This warranty shall be void if a the equipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifi cations or c the equipment has been used or stored in a manner contrary to the equipment s operating manual intended use or other written instructions Any technical advice furnished by XPC Corporation or a XPC Corpora tion authorized representative before or after delivery with regard to the use or application of Xtreme Power Con version equipment is furnished on the basis that it represents XPC Corporations best judgment under the situation and circumstances but it is used at the recipient s sole risk EXCEPT AS STATED ABOVE XPC Corporation DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE E
10. in any way What is Not Covered Under the Load Protection Policy The following damage is not covered by this Policy 1 Restoration of lost data and reinstallation of software 2 Damage from a cause other than AC power line transients except for damage due to telephone line Local Area Network or CATV transients which is covered only if the Product offers such protection 3 DAMAGE CAUSED BY FAILURE TO PROVIDE A SUITABLE INSTALLATION ENVIRONMENT FOR THE PRODUCT INCLUDING BUT NOT LIMITED TO LACK OF A PROPER SAFETY GROUND Damage caused by the use of the Product for purposes other than those for which it was designed Damage caused by accidents or natural disasters including but not limited to fire flood and wind Damage caused by abuse misuse alteration modification or negligence Any labor costs or travel room and board expenses associated with the repair and or restoration of lost or damaged hardware software or data ONP S EXCEPT AS EXPRESSLY PROVIDED IN THIS POLICY XPC SHALL NOT BE LIABLE FOR ANY DAMAGES WHATSOEVER INCLUDING BUT NOT LIMITED TO DIRECT INDIRECT SPECIAL INCIDENTAL CONSEQUENTIAL OR MULTIPLE DAMAGES ARISING OUT OF THE USE OF THE PRODUCT OR DAMAGE TO THE CONNECTED EQUIPMENT REGARD LESS OF THE LEGAL THEORY ON WHICH SUCH CLAIM IS BASED EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE SUCH DAMAGES INCLUDE BUT ARE NOT LIMITED TO LOSS OF PROFITS LOSS OF SAVINGS OR REV ENUE LOSS OF USE OF THE PRODUCT
11. of the Product The installation must comply with all applicable electrical and safety codes set forth pursuant to the NEC 4 The Product must have undeniable physical evidence of a Power Disturbance that directly and proximately caused the damage 5 The Connected Equipment must have been damaged by a Power Disturbance on a properly installed grounded and National Electric Code NEC code compliant 120 208 240 Volt AC power line in the United States or Canada by a Power Disturbance on standard telephone land line or PBX telephone equip ment line that is properly installed and connected to an RJ11 port on the Product or by a Power Distur bance on a standard Local Area Network connection that is properly installed and connected to an RJ45 port on the Product and d is directly plugged into and properly connected to the Product in its original condition which was properly operated when a Power Disturbance passed through the Product and i exhausts the protection capacity of the Product or ii damages the Product 6 The Load Protection Policy does not apply if the Product has been operated in a failure mode or not in compliance with XPC operating instructions in the Product user s manual or if the Connected Equipment has not been operated in compliance with the instructions and manuals of its manufacturer vendor 7 This policy is null and void if XPC determines in its sole discretion that the Product has been tampered with or altered
12. the other cable connections should be made in accordance with the above wiring diagram P90 BP72 1st battery bench Batt Link PCBA Batt Link PCBA RED BLACK ee je aje g Breaker a al da al ja BE RED BLACK i jal i fr d w 2nd battery bench Xtreme Power Conversion Corporation Page 49 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Picture example as below Note The cable connection from the external battery connector to PCB is already present inside the battery box All the other cable connections should be made in accordance with the above wiring diagram Storage amp Maintenance The unit contains no user serviceable parts If the battery service life 375 years at 25 C ambient temperature has been exceeded the batteries must be replaced In this case please contact your dealer Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material Storage Before storing charge the unit 4 hours Store the unit covered and upright in a cool dry location Dur
13. up the UPS Parameter 1 for program alternatives there are 9 programs to set up Parameter 2 for setting information display Parameter 1 Interface You may choose the following output voltage BATTERY 110 presents output voltage as 110VAC 115 presents output voltage as 115VAC 120 presents output voltage as 120VAC 127 presents output voltage as 127VAC Xtreme Power Conversion Corporation Page 21 P9OL 1500 3000 User s Manual Uninterruptible Power Supply 02 Frequency Converter enable disable Interface CF ENA converter mode enable CF DIS converter mode disable Interface You may set the initial frequency on battery mode BAT 50 sets output frequency to 50Hz BAT 60 sets output frequency to 60Hz If converter mode is enabled you may choose the fol lowing output frequency CF 50 sets output frequency to 50Hz CF 60 sets output frequency to 60Hz Interface ENA ECO mode enable DIS ECO mode disable Xtreme Power Conversion Corporation Page 22 P9OL 1500 3000 User s Manual Uninterruptible Power Supply 05 AECO enable disable Interface TT a ai i 7 m D d ENA Advanced ECO mode enable myk DIS Advanced ECO mode disable 9 Interface ENA Bypass mode enable DIS Bypass mode disable Interface ENA Programmable outlets enable DIS Programmable outlets disable Xtreme Power Conversion Corporation Page 23 POOL 1500 3000 User s Manual 08 Prog
14. If the problem is not corrected please collect information so that the Technical Support personnel can more effectively assist you IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS CAUTION UPS having Internal Batteries Risk of electrical shock Hazardous live parts inside this unit are ener gized from the battery supply even when the input AC power is disconnected CAUTION No User serviceable Parts Risk of electrical shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not isolated from AC input haz ardous voltage may exist between battery terminals and ground Test before touching WARNING Fuses To reduce the risk of fire replace only with the same type and size of fuse WARNING Unit intended for installation in a controlled environment CAUTION Do not dispose of batteries in a fire the battery may explode CAUTION Do not open or mutilate the battery released electrolyte is harmful to the skin and eyes CAUTION A battery can present a risk of electric shock and high short circuit current The following precaution should be observed when working on batteries e Remove watches rings or other metal objects e Use tools with insulated handles To reduce the risk of electric shock disconnect the UPS from the main supply before installing a computer interface signal cable
15. Local Area Network if appli cable spike or surge 3 Connected Equipment properly connected electronic equipment 4 Fair Market Value of damaged Connected Equipment as determined by XPC shall be the lower of a the average price the same or similar items are being sold for on eBay b the price list of Orion Blue Book or if such price list is no longer published a published or announced price list reasonably selected by XPC c the lowest price the same or similar items can be purchased for in the United States or d the total amount of all payment s you have or are entitled to receive from insurance other warranties extended warranties a legal liability claim or from other sources or persons for the damaged Connected Equipment 5 Purchaser means the person or entity that originally purchased the Product from an authorized reseller or distributor of XPC Products The Purchaser of this Product is protected for the term of the XPC Limited Warranty against certain losses caused by a Power Disturbance for properly connected electronic equipment referred to as the Connected Equipment subject to certain terms and conditions provided below This policy applies only to the original purchaser of the Product If the Product is transferred or sold to another person or entity this policy is void Load Protection Policy Dollar and Period Limits For purchasers that meet the qualifications and conditions set forth in this policy
16. POOL Online UPS P90L 1500 2000 3000 Models User amp Installation Manual www xpcc com O 2015 Xtreme Power Conversion Corporation All rights reserved Rev 12 14 15 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Table of Contents Tyl geo 191 oa 0 ER es 6 Product DSC OOI ee ER Ge eg 6 Double Conversion Online Teen OOO VR EE n oe ee Ee GREG ee oe 6 Dia se oo Eie ie ed ee Go E ee n oi 7 System Con UNA Os ND 7 C mmu unication CONNECTIONS EER ie EG tes ene EE EE a ie EE ee EE Ge tee 9 Emergency Power Off EPO PT vvs 10 Hardware Installation Guide sees sesse ese RENEE RE RE RE RE AE RE RE RE RE RE RE Re 11 UPS WPA SMART RE EI EE OE RE EE OE EE OE ER 12 TENNE 17 NNN 17 8 TETE LA LS 1 iN OE OE EE OG 18 HINN 18 Meal EEE NE EE N ON N 18 PAU EP SE ee DE Ee ee AD NE EN 20 ANNEN 20 PN 21 Operating Mode Ne NA 25 Fault Reference COS an N GER Ge RE ea RE N cause OR 26 VIN NN 27 Troublesnoome en 28 Storage And MaINteNane cccccccscscccccccccccccccecscccccccecccscccccccccccscccecscecees 30 OS EE ER OE EE OE ORR OO OR OE OE 30 WERS NAN OE OE N OE EE OE EN 30 BLUAS A o AO E iden sker RAA RE 30 SPENN 31 Shipping LiSEOUPS a RE GN ee ee Ee Ne ra 32 Shipping List Battery Pack sesse sees ese ss esse ee ee ee ee ee ee ee ee ee ee ee ee ee 32 Xtreme Power Conversion Corporation Page 2 P9OL 1500 3000 User s Manual Uninterruptible Power Supply ObtaininE SEVICE EEE 33 Xtreme Power Conversion Limited
17. RS232 port and the other to the communications port on your PC or server With the monitoring software installed the UPS can be scheduled for shutdown start up and monitoring of the UPS status through the PC or server USB port RS 232 port Intelligent slot RS232 Communications The RS 232 interface uses a 9 pin female D sub connector Information provided includes data about utility load and the UPS The interface port pins and their functions are identified in the following table 900800 Hoa PNE FUNGTIONS SNMP Communications Option The UPS provides an intelligent slot for internal or external network card This special intelligent network card can be compatible with popular software and hardware found on the web and in operating systems It can support op erating systems such as HP Open View IBM Netview SUN Netmanager etc This enables the UPS to provide instant UPS and power information over the network Please contact your reseller for additional details Xtreme Power Conversion Corporation Page 9 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Emergency Power Off EPO Port A customer supplied switch located remotely can be used to close the EPO connection and allows the UPS output receptacles to be switched off Since the EPO shuts down the equipment immediately orderly shutdown proce dures are not followed by any power management software The UPS will have to be manually restarted in order to regain pow
18. Step 6 IQHH gnda Lng ga Hob Po Eole ob oS BI a Page 15 Xtreme Power Conversion Corporation P9OL 1500 3000 User s Manual Uninterruptible Power Supply Tower Installation Step 1 Inter connect the tower brackets that shipped in the box with the UPS Step 2 Carefully lower the UPS into the brackets as shown Your UPS is now mounted as shown in the tower position Xtreme Power Conversion Corporation Page 16 P9OL 1500 3000 User s Manual Uninterruptible Power Supply UPS Input Connection Connect the UPS to an approved electrical input source consistent with the input power cord connection provided with the UPS Do not replace the power cord or use a substitute Avoid using extension cords when connecting AC input to any UPS UPS Output There are two types of output on the P90L 1500 P90L 2000 and P90L 3000 models programmable outlets and general outlets Please connect non critical devices to the programmable outlets and critical devices to the general outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices Programmable outlets can also be used to re cycle the power to remote devices if required to re start a server due to lock up issues Starting the UPS Press the ON MUTE button on the front panel of the UPS for two seconds to power on the UPS Note the battery charges during the first five hours of normal operation Do n
19. Warranty screens 34 Xtreme Power Conversion Load Protection Policy ss 35 Appendix A P90 BP36 P90 BP48 amp P90 BP72 User Guide ccscscscscsees 38 Important Safety Instructions 38 Product Overview and Setup c cccccscscsssssssssscsssscssscscsesssscssscsvscescssscsssesssscssssseeeescssssseseeeesssssseeseess 38 Type of Battery REQUIFed c ccccccscsccssscsessssssessscsssscscscscscescscssscscssescssscscssseasasscessessticssscseesescacaeavees 40 Battery Replace Ment csccccscsessssssescsesscscscscseesescscscssscscscscscsvesescsescsessescscssssseeesscssssaesseecisasseeeeseess 40 Wiring Diagram iii 47 Storage amp Maintenance ee ee ee ee ee ee ee ee ee ee ee ee ee Ge ek ee ee ee ee ee ee ee ee ee ee 50 Xtreme Power Conversion Corporation Page 3 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Thank you for selecting this uninterruptible power supply UPS It provides you with protection for connected equipment Please read this manual before installing the P9OL Series UPS models P90L 1500 P90L 2000 and P9OL 3000 as it provides important information that should be followed during installation and maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performance Included is information on customer support and service if it is required If you experience a problem with the UPS please refer to the Troubleshooting section in this manual to correct the problem
20. XCEPT AS STATED ABOVE IN NO EVENT WILL XPC Corporation BE LIABLE FOR DIRECT INDIRECT SPECIAL INCI DENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF Xtreme Power Conversion EQUIPMENT including but not limited to any costs lost profits or revenue loss of equipment loss of use of equipment loss of software loss of data cost of substitutes or claims by third parties Purchaser s sole and exclusive remedy for breach of any warranty expressed or implied concerning Xtreme Power Conversion equipment and the only obligation of XPC Corporation under this warranty shall be the repair or replacement of defective equipment components or parts or at XPC Corporations sole discretion refund of the purchase price or substitution of an equivalent replacement product Xtreme Power Conversion Corporation Page 34 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Xtreme Power Conversion Load Protection Policy THIS POLICY IS NOT A WARRANTY REFER TO THE XPC CORPORATION INC LIMITED WARRANTY FOR INFORMATION CONCERNING THE WARRANTY FOR YOUR XPC PRODUCT THE LIMITATIONS AND CONDITIONS CONTAINED IN THIS POLICY DO NOT AFFECT THE TERMS OF THE XPC LIMITED WARRANTY Definitions 1 Product means a Standard 120 208 or 240 Volt power protection device that is used in the United States and Canada This policy does not include custom manufactured products 2 Power Disturbance means an AC power line transient telephone line or
21. XPC will provide reimbursement cost of repair or fair market value as determined by XPC during the period limits and up to the dollar limits stated as follows ao _ sxe Hesse This Load Protection Policy is not deemed first dollar coverage XPC s obligation is reduced by any amounts that the Purchaser is entitled to recover from other sources regarding the Connected Equipment including but not limited to insurance other warranty extended warranty or legal liability regardless of whether or not the Pur chaser makes a claim for recovery Eligibility for Coverage Under the Load Protection Policy 1 The Product must be registered on the XPC website www xpcc com within 10 days of purchase All re quired information must be provided and Purchaser should retain a copy for Purchaser s records When registering on the website Purchaser must list all connected equipment that is directly connected to the Xtreme Power Conversion Corporation Page 35 P9OL 1500 3000 User s Manual Uninterruptible Power Supply product Only those devices registered in that manner will be covered 2 All Connected Equipment must be UL or CSA approved 3 The Product must be plugged into a properly wired and grounded outlet Use of input surge devices ex tension cords adapters ground wires or electrical connections not manufactured by XPC voids the XPC Load Protection Policy No other surge protection device may be connected to the output sockets
22. al to eliminate obvious causes 2 Verify there are no circuit breakers tripped 3 Callyourdealerforassistance lfyoucannotreachyourdealer oriftheycannotresolvethe problem call Xtreme Power Conversion Corp Technical Support at 800 582 4524 Technical support inquiries can also be made at support xpcc com Please have the following information available BEFORE calling the Technical Support Department e Your name and address e The serial number of the unit e Where and when the unit was purchased e All of the model information about your UPS e Any information on the failure including LED s that may or may not be illuminated e Adescription of the protected equipment including model numbers if possible e A technician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer available ask the Technical Sup port Technician about obtaining a replacement set of packaging material It is important to pack the UPS properly in order to avoid damage in transit Never use Styrofoam beads for a packing material 2 Include a letter with your name address daytime phone number RMA number a copy of your origi
23. atteries for their maximum potential In the event that the power failure lasts longer than the UPS backup time the UPS will shut down avoiding battery damage When the input AC voltage returns the UPS will automatically return online to recharge the batteries As shown in block diagram e An input filter reduces transients on the incoming utility e To maintain full battery charge the AC input power is rectified and regulated in the rectifier feeding power to the battery converter and inverter e DC power is converted to AC in the inverter passing it on to the load e Power is maintained from the battery during a power failure e The converter increases voltage appropriately for the inverter p M By pass Monitoring panel Control Bu Chargerk Monitoring battery switch Xtreme Power Conversion Corporation Page 6 R5232 slot P9OL 1500 3000 User s Manual Uninterruptible Power Supply Diagnostic Tests When the UPS is started a diagnostic test is automatically executed checking the electronics and batteries report ing any problems on the LCD display System Configuration The UPS device and the internal batteries make up the system Depending on the site and load require ments of the installation certain additional options are available for the solution Planning a UPS system the following should be taken into consideration e The total demand of the protected system shall dictate the output power rating VA Al
24. carried out only by qualified mainte nance personnel N Even after the unit is disconnected from the mains components inside the UPS system are still connected to the battery packs which are potentially dangerous _ Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS Capacitors Only person who are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept away from the batteries pair In this product the battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Verify that no voltage between the battery terminals and the ground is present before maintenance or re Batteries may cause electric shock and have a high short circuit current Please remove all watches rings VAN and other metal personal objects before maintenance or repair and only use tools with insulated grips and handles for maintaining or repairing VAN When replacing the batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion The batteries must be properly disposed of according to local regulation Please replace the fuse only with the same typ
25. cates the backup time in numbers H hours M minutes Warning amp Fault information Indicates the warning fault codes and the codes are listed in details in this manual Setting Operation Indicates the setting operation Input Output amp Battery information H EAr BU TPLF HE w Indicates the output input voltage output input frequency or battery volt age V output voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuited Indicates that programmable management outlets are working Indicates the UPS is working in online mode Indicates the UPS is working in converter mode Indicates the UPS is working in bypass mode Indicates the UPS is powering the output directly from utility Indicates that the UPS alarm is disabled ETS Indicates the battery charger is working Xtreme Power Conversion Corporation Page 19 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Battery information Indicates low battery Indicates there is something wrong with the battery Audible Alarms Abbreviations in LCD Display Xtreme Power Conversion Corporation Page 20 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Freguency Unstable in Bypass Mode Input Voltage is Out of Bypass Range Parameter 2 There are two parameters to set
26. crewing the 2 screws on each bracket Note To install the second string of batteries repeat the same procedure on the battery hold down brackets on the right side of the battery box Step 6 Now it is possible to put all batteries inside the unit by following the below picture the following drawing are indicates the wire fastener positions for the correct battery placement Note To install the second string of batteries repeat the same procedure on the right side of battery box Step 7 Connect all batteries following the wiring diagram shown in next chapter Xtreme Power Conversion Corporation Page 44 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Step 8 Put all batteries inside and secure in place with hold down brackets Note To install the second string of batteries repeat the same procedure on the right side of battery box Step 9 Put the metal top cover back on the unit Close the front fixing plate and the two parts of the front panel and secure it with screws Step 10 Connect the battery box to the UPS P90 BP72 Step 1 Open the package and place the battery box on a horizontal plane Step 2 Remove the removable front panel part by pulling it from the lower extremity Step 3 Remove the fixed part of the front panel by removing 2 screw present Xtreme Power Conversion Corporation Page 45 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Step 4 Remove the metal to
27. e UPS Press and hold the button more than 2 seconds to turn off the UPS The UPS will be in standby mode under normal power or transfer OFF ENTER Button to bypass mode if the Bypass enable setting is set by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Switch LCD message Press this button to change the LCD message for in put voltage input frequency battery voltage output voltage and output frequency SELECT Button Setting mode Press and hold this button for 5 seconds to enter the UPS setting mode when UPS is off Down key Press this button to display the next selection in UPS setting mode Switch to Bypass mode When the utility power is normal press ON MUTE and SELECT buttons simultaneously for 5 seconds The UPS will then enter Bypass mode The Bypass mode will be disabled when the input voltage is out of acceptable range ON Mute Select Button LCD Panel Rack Display Tower Display Load info Battery info Input output and Battery info Battery info Warning amp Fault info Input outpul _ Warning Setting operation Er amp Fault info and Battery 3 setting dis i a operation UPS status H al tL Backup UPS status info Backup time info Xtreme Power Conversion Corporation Page 18 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Display Backup time information Indicates the backup time in pie chart Indi
28. e and amperage in order to avoid fire hazards Do not disassemble the UPS system The UPS contains no user serviceable parts VAN Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Batteries The life of batteries used in these UPS products is estimated at 3 6 years depending on level of usage Once the battery is no longer useful and must be replaced please contact service personnel for assistance Xtreme Power Conversion Corporation Page 30 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Specifications MODEL NUMBER P9OL 1500 P9OL 2000 P9OL 3000 P9OLg 3000 CAPACITY AC output 1250VA 1125W 1700VA 1530W 2500VA 2250W 3000VA 2400W DC charging 246W 328W 493W 656W INPUT Voltage range 50 150VAC 110 300VAC Frequency 50 60Hz auto sensing OUTPUT Voltage 120VAC nominal 100 110 115VAC selectable 208 220 230 240VAC Frequency 50 60Hz 0 5Hz THD full load lt 2 Overload capacity 125 2 min 150 10 sec gt 150 1 sec Crest factor 5 1 BATTERY Charger amps CHARGER Nominal float voltage 36 41VDC 48 55VDC 72 82VDC PHYSICAL Dimensions W x D x H 17 2 x 18 9 x 3 5 in 17 2 x 18 9 x 3 5 in 17 2 x 25 8 x 3 5 in UPS weight 33 Ibs 35 Ibs 47 lbs Input connection 6 ft 5 15P 6 ft 5 20P 6 ft L5 30P 8 ft C19 to L6 20P Output connection 8 NEMA 5 15R 8 NEMA 5 15 20R 1 NEMA L5 30R 1 IEC C19 4 NEMA 5 15 20R 6 IEC C13
29. eces of 12V 9Ah batteries per string Battery Replacement If your battery box is not installed with batteries please follow proper procedure to put batteries inside of unit NOTE MAKE SURE THAT THE BATTERY BOX IS DISCONNECTED FROM THE UPS BEFORE PERFORMING THE FOLLOW ING SEQUENCE OF OPERATIONS P90 BP36 Step 1 Open the package and place the battery box on a horizontal plane Xtreme Power Conversion Corporation Page 40 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Step 2 Remove the removable front panel part by pulling it from the lower extremity Step 3 Remove the fixed part of the front panel by removing the 2 screw present Step 4 Remove the metal top cover of the battery box by unscrewing 6 screws present on the two sides 3 on the right side and 3 on the left side 3 screws on the top and 4 screws on the back side mm au ma Xtreme Power Conversion Corporation Page 41 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Step 5 Once the battery box is opened remove the battery hold down brackets present on the left side of the bat tery box by unscrewing the 2 screws on each bracket Note To install the second string of batteries repeat the same procedure on the battery hold down brackets on the right side of the battery box Step 6 Now it is possible to put all batteries inside the unit by following the below picture the following drawing
30. er to the outlets on the UPS Keep Pin 1 and Pin 2 closed for UPS normal operation To activate EPO function open the wire between Pin 1 and Pin 2 It s in closed status for UPS B normal operation Xtreme Power Conversion Corporation Page 10 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Hardware Installation Guide Inspect the UPS upon receipt The packaging is recyclable keep it for reuse or dispose of properly Safety Information Information presented here is vital to all personnel Please read all Safety information Storage and Transportation Please handle the UPS and associated equipment with extreme caution since a high amount of energy is contained in the batteries Always keep the unit in an upright position as marked on the packaging and never drop the unit Please adhere to the following instructions if the UPS is not installed immediately e Store the equipment as is in its original packing and shipping carton e Do not store in temperatures outside the range of 15 C to 25 C e Ensure that the equipment is fully protected from wet or damp areas and from moist air In order to maintain the batteries the UPS should be recharged every 6 months for at least 8 hours If flammable substances such as gases or fumes are present or if the room is airtight a hazardous situation may exist in which no electrical equipment should be operated The instructions in this manual explain how to install the UPS safel
31. estart the UPS The UPS shut down automatically because short circuit condition oc curred on the UPS output Disconnect loads and check to see if output wiring or connected devic es are in short circuit status Page 28 P9OL 1500 3000 User s Manual Uninterruptible Power Supply A UPS internal fault has occurred There are two possible results 1 The load is still supplied but directly by AC utility via bypass Contact your dealer for support The load is no longer supplied with power Fault code is shown as 01 02 03 04 11 12 13 and 41 on LCD dis play and alarm is sounding continu ously Charge the batteries for at least 5 hours and then re check capacity Batteries are not fully charged Battery backup time is shorter than If the problem still exists contact expected your dealer for support Contact your dealer for batter Batteries are defective y y replacement Xtreme Power Conversion Corporation Page 29 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Storage And Maintenance Storage Before storing charge the UPS at least 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C Every 3 months 1 2 hours 40 C 45 C Every 2 months Maintenance The UPS system operates with hazardous voltages Repairs may be
32. ing storage recharge the battery in accordance with the following table Storage Temperature Recharge Freduency Charging Duration 25 C 40 C Every 3 months 1 2 hours 40 C 45 C Every 2 months Xtreme Power Conversion Corporation Page 50
33. kage Battery box unit Manual Battery connection cable x 1 Far x 2 amp screw x 8 Extended stand Selecting Installation Position It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the battery box and extend the life of the batteries Please follow the instructions below 1 2 3 4 5 Keep at least 20cm 8 inches clearance from the rear panel of the unit from the wall or other obstructions Do not block the air flow to the ventilation openings of the unit Please ensure the installation site environmental conditions are in accordance with the unit s working specifications to avoid overheat and excessive moisture Do not place the unit in a dusty or corrosive environment or near any flammable objects This unit is not designed for outdoor use This unit can either be rack mounted or placed vertically on the desk Rack Installation Xtreme Power Conversion Corporation Page 39 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Tower Installation 220 m Connecting with UPS and Other Battery Box Follow below installation chart to connect with UPS and other battery box with included cable Type of Battery Required This battery box has been designed to operate with the following types of batteries 36V 9Ah Version 3 pieces of 12V 9Ah batteries per string 48V 9Ah Version 4 pieces of 12V 9Ah batteries per string 72V 9Ah Version 6 pi
34. lectrical installation must also carefully follow local legislation and regulations Only qualified personnel should conduct these installations as failure to acknowledge electrical hazards could prove to be fatal Product Description Many different kinds of sensitive electrical equipment can be protected by an Uninterruptible Power Supply UPS including computers workstations process control systems telecommunications systems sales terminals other critical instrumentation etc The purpose of the UPS is to protect these systems from poor quality utility power complete loss of power or other associated problems Electrical interference exists in many forms causing problems in AC power from lightning power company ac cidents and radio transmission motors air conditioners and vending machines Protection of sensitive electrical equipment is vital to protect against power outages low or high voltage conditions slow voltage fluctuations frequency variations differential and common mode noise transients etc To prevent power line problems from reaching critical systems causing damage to software hardware and equip ment malfunctions the UPS maintains constant voltage isolating critical load output and cleaning the utility AC power Double Conversion Online Technology A double conversion on line technology UPS provides completely isolated clean uninterrupted single phase pow er to your critical systems while maintaining the b
35. ll be void e To eliminate any overheating of the battery box keep all ventilation openings free from obstruction and do not place any foreign objects on top of the battery bank Keep the battery box 20cm away from the wall e Make sure the battery box is installed within the proper environment as specified 0 40 C and 30 90 non condensing humidity e Do not install the battery box under direct sunlight Your warranty will be void if the batteries fail due to overheating e This battery box is not designed for use in dusty corrosive and salty environment e The warranty for this battery bank will be void if water or other liquid is spilled or poured directly onto the battery box Similarly we do not warrant any damage to the battery box if foreign objects are deliberately or accidentally inserted into the battery box enclosure e The battery will discharge naturally if the system is unused for a period of time e It should be recharged every 2 3 months if unused If this is not done then the warranty will be null and void During normal operation the batteries will automatically remain in charged condition e Servicing of batteries should be performed or supervised by trained personnel with knowledge of batter ies and the required precautions e When replacing batteries it is necessary to replace ALL batteries with the same quantity type amp capacity e CAUTION Do not dispose of battery or batteries in a fire The battery may explode
36. low a margin for future expansion or calculation inaccuracies from measured power requirements e Backup time required will indicate the battery size needed If the load is less than the UPS nominal power rating then actual backup time is longer e The following options are available o Connectivity Options Web SNMP Card Relay Card Modbus Card o Extended Battery Packs minimum 1 required rail kits bypass switches See the Specification section of this manual for additional model information CT PEPE Power Conversion POOL front view EN DL Yok apel ai P90L 2000 rear view N Xtreme Power Conversion Corporation Page POOL 1500 3000 User s Manual Uninterruptible Power Supply P9OL 3000 rear view Front panel Enmore ff secect forrenter ff me aa I Load info Input outpu and Battery info UPS status Xtreme Power Conversion Corporation BET Selector buttons RATT OUTPUT Rack display Battery info Warning amp Fault info Setting operation Backup time info Page 8 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Battery info ER ey EDE Input output ri gt and Battery info Warning amp Fault info Setting operation UPS status Load info Backup time info Tower display Communication Connections To allow for unattended UPS shutdown start up and status monitoring connect one end of the communication cable to the USB
37. ly and disconnected For additional safety instructions please use the Safety Manual as a reference Special Symbols The following symbols used on the UPS warn you of precautions N RISK OF ELECTRIC SHOCK Please observe the warning that a risk of electric shock is present CAUTION REFER TO OPERATOR S MANUAL Refer to the operator s manual for additional information such as important operating and maintenance instructions SAFE GROUNDING TERMINAL Indicates primary safe ground LOAD ON OFF Pressing the button turns on off the output receptacles and the indicator light RJ45 RECEPTACLE The receptacle provides network interface connections and telephone or telecommu nications equipment should not be plugged into it AE OP Please do not discard the UPS or the UPS batteries as the UPS may have valve regulated lead acid batter ies Please recycle batteries appropriately Xtreme Power Conversion Corporation Page 5 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Introduction The information provided in this manual covers single phase 1250VA 1700VA 2500VA and 3000VA uninterrupt ible power systems their basic functions operating procedures options available and emergency situations It also includes information on how to ship store handle and install the equipment Only detailed requirements of the UPS units are described herein and installation must be carried out in accordance with this manual E
38. mizer bypass switch for energy sav ing PFC and INVERTER are off in this mode When input frequency is within 40Hz to 70 Hz the UPS can be set at a constant Frequency Converter output frequency 50 Hz Mode Rack or 60 Hz The UPS will still charge battery in this mode Static bypass When the input voltage is be yond the acceptable range or there is a power failure and alarm is sounding every 4 seconds the UPS will provide Battery Mode backup power from battery Xtreme Power Conversion Corporation Page 25 P9OL 1500 3000 User s Manual Uninterruptible Power Supply When input voltage is within acceptable range but UPS is overloaded the UPS will Bypass Mode enter bypass mode or bypass mode can be set by the front panel Alarm is sounding every 10 seconds UPS is powered off without Standby Mode output power but the bat tery is still being charged The UPS is in fault mode when no output power is supplied from the UPS and Fault Mode the fault icon flashes on the LCD display although the in formation from the UPS can be displayed on the screen Fault Reference Codes Fault event Fault code Fault event Faultcode icon Bus start failure Inverter output short SHORT rein hen Ed Bus under Battery voltage too low p i Bus unbalanced Over temperature EE Inverter soft start fail High inverter voltage Low inverter voltage Xtreme Power Conversio
39. n Corporation Page 26 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Warning Indicators Icon flashing Overload OVER LOAD HE Sounds twice every second Hl Battery not connected Sounds every second Site wiring fault Sounds every second EPO enable L Sounds every second Battery fault p A Sounds every second Bypass out of range ar N Sounds every second Bypass frequency unstable ard N Sounds every second Xtreme Power Conversion Corporation Page 27 POOL 1500 3000 User s Manual Troubleshooting Uninterruptible Power Supply If the UPS does not operate correctly please use the table below to troubleshoot the problems symptom No indication and alarm even though the utility is normal The icon and the warning code EP are flashing on LCD display and alarm is sounding every second The icon and SF are flashing on LCD display and alarm is sounding every second The icon and are flashing on LCD display and alarm is sounding every second Fault code is shown as 27 and the icon is showing on LCD display and alarm is continuously sound ing Fault code is shown as 28 and the icon is showing on LCD display and alarm is continuously sound ing The icon and de are flashing on LCD display and alarm is sounding twice every second Fault code is shown as 43 and the icon is showing on LCD display and alarm is sounding con tinuously Fault
40. nal sales receipt and a brief description of the problem 3 Mark the RMA number on the outside of all packages Xtreme Power cannot accept any package without the RMA number marked on the outside of the boxes 4 Return the UPS by insured prepaid carrier to the address provided by the Technician 5 Refer to the Warranty statements in this manual for additional details on what is covered Xtreme Power Conversion Corporation Page 33 P90L 1500 3000 User s Manual Uninterruptible Power Supply Xtreme Power Conversion Limited Warranty Xtreme Power Conversion XPC Corporation warrants Xtreme Power Conversion equipment when properly ap plied and operated within specified conditions against faulty materials or workmanship for a period of three years for P9OL Series products from the date of purchase XPC Corporation warrants P90L Series battery packs for a period of three years from the date of purchase For equipment sites within the United States and Canada this warranty covers repair or replacement at the sole discretion of XPC Corporation The customer is responsible for the costs of shipping the defective product to XPC Corporation XPC Corporation will pay for ground shipment of the repaired or replacement product This warranty applies only to the original purchaser If equipment provided by XPC Corporation is found to be Dead on Arrival DOA XPC Corporation will be respon sible for the costs of shipping product to and returning equipment
41. ot expect full battery run time during the initial charge period af onmure secect forventer m Ed Software Installation For optimal system protection install UPS monitoring software to fully configure UPS shutdown Please follow steps below to download and install monitoring software or simply install via the included CD 1 Got to the website http www power software download com 2 Click ViewPower software icon and then choose your required Operating System to download the soft ware Follow the on screen instructions to install the software 4 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock ad Xtreme Power Conversion Corporation Page 17 POOL 1500 3000 User s Manual Uninterruptible Power Supply Operations Button Operation ON MUTE ON MUTE SELECT Morrenrerl oe ee O MW ND EE Button Function S Turn on the UPS Press and hold the button more than 2 seconds to turn on the UPS Mute the alarm After the UPS is turned on in battery mode press and hold this button for at least 5 seconds to disable or enable the alarm system ON MUTE Button This feature will not work when warnings or errors occur Up key Press this button to display the previous selection in UPS setting mode Switch to UPS self test mode Press and hold ON MUTE button for 5 sec onds to enter UPS self testing while in AC mode Turn off th
42. p cover of the battery box by unscrewing 8 screws present on the two sides 4onthe right side and 4 on the left side 3 screws on the top and 4 screws on the back side Q N N lt Q Step 5 Once battery box is opened remove the battery hold down brackets present on the left side of the battery box by unscrewing the 2 screws on each bracket Note To install the second branch of batteries repeat the same procedure on the battery fixing plate on the right side of battery box Step 6 Now it is possible to put the batteries inside following below picture in the following drawing are indicated the fasten positions for the correct batteries placing Note To install the second string of batteries repeat the same procedure on the right side of battery box Step 7 Connect all batteries following the wiring diagram shown in next chapter Xtreme Power Conversion Corporation Page 46 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Step 8 Put all batteries inside and secure in place with the hold down brackets Note To install the second string of batteries repeat the same procedure on the right side of battery box Step 9 Put the metal top cover back on the unit Close the front fixing plate and the two parts of the front panel and secure it with screws Step 10 Connect the battery box to the UPS Wiring Diagram
43. rammable Outlets Setting Interface Interface HAT DET U LIE 00 Exit Setting Xtreme Power Conversion Corporation Uninterruptible Power Supply 0 999 setting the backup time limits in minutes from 0 999 for programmable outlets connected to non crit ical devices when operating in battery mode RAC the LCD display is horizontal TOE the LCD display is vertical Choose the following Acceptable input voltage range 55 150 alternating flashing acceptable input voltage range is from 55V to 150V 80 130 alternating flashing acceptable input voltage range is from 80V to 130V 85 135 alternating flashing acceptable input voltage range is from 85V to 135V Page 24 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Operating Mode Description ae LCD Display Operating Mode Description Rack Display Tower Display When the input voltage is within acceptable range the UPS will provide pure and Online Mode stable AC power to the out put The UPS will also charge the battery during Online Mode When the input voltage is within setting range 3 Vo max UPS will provide voltage to output via static bypass switch for energy sav ing PFC and INVERTER are still active in this mode ECO Mode Efficiency Corrective Optimizer When the input voltage is within setting range 3 AECO Mode Advanced Vo max UPS will provide Efficiency Corrective voltage to output via static Opti
44. the Connected Equipment XPC reserves the right to contact the authorized service center directly to discuss repair costs and damage to the Connected Equipment to determine if it was caused by a Power Disturbance and the right to request that the service center forward the Connected Equipment or components of the Connected Equipment to XPC for inspection 5 Unless modified in writing signed by an officer of XPC and the Purchaser the terms of this policy are the com plete and exclusive agreement between the parties superseding all prior agreements oral or written and all other communications between the parties relating to the subject matter of this agreement No employee of XPC or any other party is authorized to make any representations beyond those made in this agreement con cerning the Load Protection Policy XPC Corporation 230 Yuma Street Denver CO 80223 1 800 582 4524 Xtreme Power Conversion Corporation Page 37 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Appendix A P90 BP36 P90 BP48 amp P90 BP72 User Guide Important Safety Instructions Please comply with all warnings and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety information and operating instructions carefully e Do not try to repair the unit yourself contact your local supplier or your warranty wi
45. ty considerations the UPS is shipped from the factory with battery wires Connecting Battery Packs Connect external battery pack s in accordance with the diagrams below Xtreme Power Conversion Corporation Page 12 P9OL 1500 3000 User s Manual Uninterruptible Power Supply Rack mount Installation using front brackets Step 1 Attach brackets to the front corners of the UPS Step 2 Slide the UPS into the rack and secure using hardware provided Apna Rack mount Installation using 4 post rail kit Package contents e Right and left rail sliders 1 each e 2 M6 nuts e 12 M6 screws Xtreme Power Conversion Corporation Page 13 Uninterruptible Power Supply Use 4 screws to mount right and left rail sliders in front of rack POOL 1500 3000 User s Manual Step 1 Page 14 Screw driver nuts 1 i i 1 i I i i i I tj i i j Le 1 i I F i li O00000 0 00 0 aeania a Place the nuts in the proper location in the rack based upon height of UPS Use 4 screws to mount right and left rail sliders in back of rack Xtreme Power Conversion Corporation Step 2 Step 3 Uninterruptible Power Supply POOL 1500 3000 User s Manual Carefully place the UPS on the rail support Step 4 Ld i oe Gero ET nl Ole taa P CA ele DO sr ee III III Fix the UPS in position with screws Step 5 fi Tete ees Rail kit installation is now complete
46. y Not acknowledging such electrical hazards may be fatal keep this manual for future reference It is strongly recommended that the UPS cabinet not be opened as components have very high voltage and touching those components may be fatal Only a qualified technician or authorized agent may service the unit The UPS unit s output receptacles carry live voltage even when not connected to an input volt age source The UPS has its own internal energy source Environment Ensure that all environmental concerns and requirements are met according to specifications listed in this docu ment otherwise the safety of installation personnel cannot be guaranteed and the unit may malfunction Ensure that you remember the following when locating the UPS system and battery options e Avoid extremes of temperature and humidity Maximum battery life can be attained with a recommended temperature range of 15 C to 25 C e Provide protection for the equipment from moisture e Space and ventilation requirements must be met Ensure there is 100mm behind and 50mm on the sides of the UPS for proper ventilation e Ensure that the front of the UPS remains clear for user operation Xtreme Power Conversion Corporation Page 11 P9OL 1500 3000 User s Manual Uninterruptible Power Supply UPS Installation Installation and wiring must be performed in accordance with the local electrical laws and regulations and per formed by appropriate personnel For safe