G225 Local Exhaust Ventilation in Design & Technology
Contents
1. Some units will collect dust and chips in a clear plastic bag These may be hung below the fan on a floor mounted unit which may also be portable or the unit may be fixed to the wall with the bag hanging below Plastic bags are vulnerable to damage either accidental or deliberate and if punctured must be replaced The bags fitted to wall mounted units may be heavy when full and because of the position of the unit on the wall may be difficult to lift down Some units have a large filter bag which is placed above the fan and which inflates when the unit is started Whilst such designs will normally be adequate blocking the filter can reduce the efficiency of the unit The filter will also need space to expand so this type of unit cannot be placed under a bench A further type of free standing unit is contained within a circular drum with the dust collected in the bottom Again a face mask should be used when emptying 10 2 9 Extraction of solvent fumes The CLEAPSS Model Risk Assessments for Design and Technology discuss various processes involving solvent fumes Most school operations are on a sufficiently small scale to avoid the need for fume extraction but spray painting in some colleges will require proper booths with extraction particularly where isocyanate paints are used 2 10 Extraction of solder fume The fume produced by rosin colophony based flux materials is hazardous Rosin based fluxes are used for electrical work with
2. opening a window will normally provide sufficient ventilation Although the COSHH Regulations apply to non employees only so far as is reasonably practicable the general duty on employers under the HSW Act Section 3 means that it is wise to apply the same limits for others as for staff Risk Assessment The Regulations require the employer to make a suitable and sufficient assessment of the risks created by the work activity to the health of the employees In education this assessment process is often assisted by consulting model risk assessments e g Model Risk Assessments for Design and Technology in Secondary Schools and Colleges However the process is done the outcome should be a series of control measures that are to be adopted to ensure that relevant limits are met In some cases the general ventilation in the workplace should be sufficient to keep down the concentration of hazardous substances but in other cases general ventilation will need to be supplemented by LEV Maintenance COSHH Regulation 9 requires that every employer who provides a control measure shall ensure that it is maintained in an efficient state in efficient working order in good repair and in a clean condition Even if the task of maintaining LEV is delegated to individual schools it is the employer who has the duty to make arrangements for monitoring that it is done In practice this means that someone must make a simple check that the LEV is
3. CLEAPSS advice 8 1 The provision of air flow indicators The HSE web site www hse gov uk lev faqs htm contains very useful information on issues related to LEV and the first question in relation to the fitting of air flow indicator is quoted below Do I have to fit air flow indicators to all the hoods in the LEV system There isn t a specific legal requirement to have air flow indicators or similar fitted to an extraction But as an employer you do by law have to make sure your LEV system keeps working properly One of main reasons why LEV doesn t do what it should is because the airflow falls for some reason e g build up of material damage to ducting etc becomes inadequate and effective control is lost One simple way of checking this is the use of air flow indicators or a static pressure gauge at the hood and this will provide you reassurance that the flow rate is maintained that the protection for employees is there and that you re not wasting money There are other ways of checking air flow such as using anemometer or a dust lamp or smoke tracer with the work process running However an air flow indicator or static pressure gauge is currently the only method that will show the operator or supervisor immediately if there s a problem and the HSE s LEV guidance HSG 258 recommends these are fitted At the time of writing the CLEAPSS view is that in schools and colleges it is not necessary to fit airflow indicators to every extr
4. see section 3 2 The use of lead free solders will reduce the risk of harm from lead but may increase the level of fumes from the flux used It is recommended that casting lead or its alloys is avoided in schools and colleges and that lead free pewter is used instead Colleges teaching building techniques may need to handle lead flashing which can give rise to significant lead contamination of the skin Reference should be made to the Approved Code of Practice See the Management of Health and Safety at Work Regulations or the COSHH Regulations Model Risk Assessments for Design and Technology in Secondary Schools and Colleges see Assessment 1 025 Model Risk Assessments for Design and Technology in Secondary Schools and Colleges see Assessments 1 019 and 1 020 12 Control of Lead at Work Regulations 2002 Approved Code of Practice and Guidance HSE Books 3rd edition 2002 ISBN 0717625656 14 4 Examination methods In this section we consider those examination methods which are theoretically possible Section 6 gives details of the tests that should be used to comply with the requirement to examine the functioning of LEV systems every 14 months or less 4 1 Measurements of air quality The purpose of local exhaust ventilation is to ensure that air that is inhaled will not damage a person s health The contaminant or range of contaminants that might be present in the air must be known if appropriate tests are to be carr
5. The following items need further attention E E ATT ATE T E T E T Maaeermcmrneses REASON ada sy ca see ese ea EEKAN K OEP ceca Lar ETENEE EAKA AONE TEREE EVENE maces cane hcadeaeedeay EEN KATEAN TERESE Sia E cael EE E E ucaeeasttacan Gat Gages ea met lenma tua Set AG Saeuth ae Geel a tat PROGSOM Aenima n a n T tesa Sieh caatdesetde cane a la Eia She eT E a a a A a a E O REASOM porroa sonar a E EE E Dea dace E E sn EA E E Melia eee es a E E A AET AEA TE AEA REASON AEE AA O A AE E IEE EA A S EE APER E we teens E N AANEEN AEE S D Final result Possible outcomes Tick one box The system is performing satisfactorily The system is in need of major maintenance or repair as discussed above The system should be replaced work using it should cease until this is done Signature ofitester missierna a EA a AEA Ea aTa Aa aAA AAA E ERa wales E Subsequent action The following action has been taken E E E E E E E E a tae ae By E EEE EA A A T Date ia cath haha Ze a a a a a e a a a aaa e E E E E AE E EE RENARE B ofari a AE rtm eae tril a a a a a Date arni beter tate es a ED eee Or fee Eee etree Pere Pe Maer rere ner er erat Gee or Peery Peer ee pe ee eer errant er eer teeter ee cera wetter errr errr ee BY Sects ect alae dice a aoa aaa a AAAA A Tee rRe ike Date espi miiosiske 4 A further test has been arranged On esssseseiiessesererirrressserrrrrrrese DE cheek a EE ET alta ieee teduntaanl boace ET pt detiadeatinahtmeed
6. and another for controlling fumes e g from hearth areas A further system for controlling solvent fumes from painting or other operations may also be required Each machine or workplace where significant amounts of dust are produced should have its own test One test may be sufficient for a small system dealing with fumes or solvents In addition to the annual test regular informal checks are also required to ensure that the LEV system continues to work effectively This is a separate process to the annual testing and should be done as required CLEAPSS recommends that these informal checks are done at least weekly Methods of informal testing are described in section 7 3 If a school or college wishes to do its own annual testing the responsible person must have suitable training and should follow the guidance given below Regular thorough examination and test of an LEV system At regular intervals at most 14 months each system needs a thorough examination to comply with COSHH Regulation 9 and prove that the system is still working effectively These examinations will be similar but not necessarily identical to the commissioning tests We have provided below two suggested report forms to meet the needs the commissioning test and regular examination Although the forms are copyright CLEAPSS member establishments may make as many copies of them as necessary for their own internal use or for use by their contractors Contractors may therefo
7. and mops are unlikely to be suitable even if cleaning staff are required to wear appropriate dust masks The only effective method is to use a vacuum cleaner that is designed to collect wood dust a general purpose vacuum cleaner is unlikely to be suitable because it will not trap the fine dust involved Usually an industrial quality vacuum cleaner is required that is fitted with a HEPA High Efficiency Particulate Air filter that will prevent fine dust form being released into the air Since the waste is likely to include small offcuts as well as dust a variety of nozzles will be needed Cleaning staff will need training and supervision to ensure that the specialist vacuum Cleaner is used where it is required and not generally throughout the school and that it is emptied according to the manufacturer s instructions using similar care to that described in section 7 1 There is some risk in pupils brushing dust from workbenches at the end of a lesson CLEAPSS is not aware of any regulations which state that hand brushing should not be used but it is advisable not to allow fine dust to be brushed off a bench 30 Refer to the separate document PS62 LEV in Design amp Technology Suppliers Testers and Monitoring Equipment for details of companies that supply suitable vacuum cleaners for dust collection for example Depureco Dustcontrol UK and Nilfisk PS62 will be regularly updated so readers should check for the latest issue 25 8
8. budget has been delegated to a particular section or person that the employer has discharged its duties under the Act Filter A device to separate the contaminant from the air flow It often consists of sheets of perforated card a fabric bag or both Paper filters are used to catch fine dust and these need regular replacement Large systems may include a cyclone in which the contaminated air is caused to flow in a circular path with the higher density contaminant flung outwards Hood The hood in an LEV system is the entry point to the system It is a device that encourages the contaminant to enter the air flowing into the duct HSE guidance The Health and Safety Executive HSE supplies guidance in several different forms Information Sheets are short single topic documents which are free as single copies More extensive guidance is given as specific publications and official guidance on regulations in Approved Codes of Practice ACoPs All of these are available from HSE Books Free leaflets can be downloaded from the HSE web site www hse gov uk MDF The common abbreviation for medium density fibreboard This is a composite material of wood particles bonded with urea formaldehyde resin The precautions to be taken when using this material are discussed in CLEAPSS publication PS33 MDF Some dust control systems which are adequate for ordinary sawdust may not be able to control the fine dust from MDF However provided that adequate contro
9. enclosing it in a suitable cage and where necessary from damage from passing traffic on internal roadways or in car park areas Being outside will reduce the noise inside the building but may introduce additional costs Collection units may be installed in a plant room or storeroom within the building but again additional costs may be involved Because of the risk of fire units should not be installed in boiler rooms or rooms containing the main electrical switch gear The other significant issue to consider is that if the system fails none of the machines connected to it can be used This could place most of the machines in a department out of use for some time An alternative to one single large system is to have discrete ducted systems for each room Although the issue of noise still has to be considered having several systems means that individual teachers can control the use in their own room and if one system fails others should still be useable Individual LEV units by each machine can overcome some of the problems outlined above The main disadvantage is that additional space is required to accommodate the extraction units although some smaller units can be placed under benching Collection units for circular saws can often be placed below the take off table of the machine Noise may be a problem with individual units 7 Schools often find it most useful to have a large ducted system for the main resistant materials preparation area a
10. for large LEV systems The electrical controls for LEV systems are an important part of the design of the system The best arrangement for any system is for the collection unit to start when any machine is switched on This will ensure that the LEV is always used and for both large systems and individual units some sort of remote control or linked start up is often provided For small LEV systems an acceptable alternative is for the LEV control switch to be located alongside the machine or on the unit itself if this is close by This arrangement is often employed on LEV that extracts from a single machine Where a system is designed to serve all the machines in one room only one control switch may be provided This is not appropriate since there is a risk that users will fail to turn on the extraction unit A large system that will extract from all the machines across several rooms may have one control in each room but this is also not ideal A single start control that is located alongside the extraction unit itself is not acceptable since this may be some distance from the machines that it serves especially when the unit is in a plant room In general each machine should be linked to the LEV start up system Where there is any sort of remote start up control a suitable isolating switch should be installed alongside the extraction unit to allow it to be isolated during maintenance or emptying 2 6 Significance of multiple collection points Syste
11. may produce fumes and possibly in colleges handling large amounts of flour Flour has a WEL of 10 mg m over an 8 hour period and 30 mg m over a 15 minute reference period Since flour is an asthmagen exposure must be reduced well below the WEL and be kept as low as is reasonably practicable Solvent fumes from paint spraying are 7 For community and voluntary controlled schools the employer is the LEA For foundation schools voluntary aided schools academies city technology colleges and independent schools and for sixth form and further education colleges the employer is the governing body or possibly a trust or the proprietor The health amp safety responsibilities of employers are spelled out in Health amp Safety Responsibilities and Powers DfES 0803 2001 available on www teachernet gov uk wholeschool healthandsafety responsibilities 12 unlikely to be a problem in schools where the scale is usually small In colleges a proper paint spraying booth with extraction may be needed for teaching Art and Design Design and Technology and bodywork repairing in Motor Vehicle workshops There have been instances where fumes from the melting of paraffin wax in electrically heated pots in textiles rooms has caused headaches The WEL for paraffin wax is 2 mg m over an 8 hour period and 6 mg m over a 15 minute reference period These limits may well be exceeded if more than one pot is in use Where paraffin wax fumes are a problem
12. of a school or college system since supplies of the gas and expensive detection equipment are required Nevertheless research being done by the HSE using this technique should enable a simpler testing method to be devised This has not yet been published so most testing companies adopt a rule of thumb minimum duct flow rate of 10 m s The air speed at an inlet will depend on the ratio of the cross sectional areas of the duct and inlet It is the inlet air speed that is easiest to measure However this is not regarded as relevant by the HSE Temporary procedure The only practical way of testing a fume extraction system is to compare the air speed and or pressures at the various inlets with those recorded during a commissioning test after installation However it is important to ensure that the settings of controls fan speed if a regulator is fitted and dampers to control air flow are the same during the retest as they were during the commissioning test It is unusual for wind speed to affect the results unless the workshop is in a very exposed location In such cases it is important to check that the discharge is via a vertical stack 21 7 Maintenance requirements The requirement to control dust concentrations in the air applies just as much to maintaining the LEV system as to the normal uses of the dust producing equipment 7 1 Emptying dust containers Problems Some systems collect dust in drawers at the bottom of the ext
13. paper filters are used in some systems to collect the finest dust These should be changed at the frequency suggested by the supplier If this is not done the performance of the system can fall off significantly such that replacement of the filter produces an obvious improvement in the air flow rate Similarly washable fabric filters or bags should be washed at such intervals that the clean one produces a change in air flow that is only just detectable without instruments Fume filters Systems to control fumes usually exhaust to the open air without a filter An exception is the type used to deal with fumes from soldering with rosin based fluxes in electronics work These use filters that should be changed at intervals as specified by the supplier Extraction systems used with laser cutters will also use filters and it is essential that these are also changed at intervals as specified by the supplier Some filter units will have a display that will show when the filter has to be changed and this should be used 23 7 3 Informal checking The annual thorough examination and test required by the COSHH regulations will ensure that once a year an LEV system is in effective working order However it is possible for the performance of LEV systems to deteriorate over time and it is important that users of LEV systems carry out more frequent informal checks to ensure that the contaminants are adequately controlled This is particularly important for LEV
14. problems for school staff The HSE web site www hse gov uk lev processes contains video clips of flood lamp tests on a number of LEV systems These clips show clearly how fumes and dust are emitted from a range of processes Although measuring the quality of the air is not easy a good indication of the effectiveness of an LEV system used on wood dust can be gained by checking the amount of dust on horizontal surfaces around the machines and observing any dust in the air whilst a machine is in use Whist a dust lamp can be used for this it is often possible to see the dust in the air in sunlight or in normal artificial light If there is dust on horizontal surfaces or it can be seen in the air then the system is unlikely to be working effectively CLEAPSS has come across examples where teachers and technicians have complained of dust in the air and about the room but have been assured by a person testing the system that it meets requirements Where dust exists this is clearly not the case Such reports should not be accepted and air quality testing should be insisted upon 15 The picture is taken from Assessment and Control of Wood Dust Use of the Dust Lamp 1997 HSE Books WIS12 Free publication 16 Assessment and Control of Wood Dust Use of the Dust Lamp 1997 HSE Books WIS12 Free publication 16 4 2 Measurements of air flow Irrespective of the contaminant that the system is designed to remove the performance of LEV could be m
15. systems designed to extract wood dust and shavings because they can become blocked The HSE currently recommends the fitting of air flow indicators so that routine checking is made relatively easy Where such indicators are not fitted there are a number of simple checks that users can carry out without the need for formal training These are described below a Visual inspection e Check closely all parts of the system for damage wear and tear such as splits in flexible ducting holes in collection bags where fitted missing or loose bolts or other fixings missing blast gate sliders e Check ducting for blockage caused by slivers of wood This is important where dust is collected next to saw blades because plastic cowlings may have small exit points that are easily blocked e Check ducting is still connected to the machine and has not worked loose e Check any necessary filter cleaning devices work correctly e Check for overall effectiveness e g look for deposits of dust in and around hoods or other parts of the systems dust on top of machines or horizontal surfaces near to machines excessive vibration or noise e Check and clean inside machines e g band saws and the base of circular saws for a build up of dust This is an indication that the system may not be working It is suggested that visual inspections of the type described above should be done at least weekly during term time and for machines with heavy use daily would b
16. the air flow through part of a ducting system particularly where air flows through several inlet hoods The setting is used to balance the flow so that efficient collection is achieved at all inlets or at the particular hood in use Duct velocity The duct velocity is the average air speed in the duct It should be greater than that required to keep the contaminant flowing in the duct and prevent it from falling out of the flow under the influence of gravity 31 Dust mask A mask designed to reduce the inhalation of dust There are several different types 1 A nuisance dust mask consists of a layer of cotton gauze often held in place by a light weight metal frame It is ineffective against toxic dusts 2 Toxic dust masks may be disposable half or full mask respirators light weight powered visors or helmets They have filters of different types for different dusts See HSE Woodworking Information Sheet No 14 for more details The disposable types likely to be most relevant to education have the filter type EN 149 FFP2 and 3 They must be worn when changing emptying dust collection bags drawers Dust monitor An instrument designed to measure dust concentrations in the air Those types giving immediate readings measure the light scattered from air samples passing through the instrument Duty A duty laid on anyone by the Health and Safety at Work Act cannot be delegated The employer cannot argue that because the health and safety
17. the current edition is dated 2002 The regulations cover substances on the skin and substances taken into the body by the respiratory system as well as by swallowing Substances include carcinogens and biological agents as well as chemicals that act to the detriment of the health of the person exposed Workplace Exposure Limits Information on hazards from substances is provided by a system of Workplace Exposure Limits WELs which refer to concentrations of each hazardous substance in the air These limits are subjected to time weighting i e the actual concentration is the average value over either 8 hours or 15 minutes Although this means that for many activities these limits are unlikely to be exceeded in an educational workshop there are situations where a risk assessment shows that a high level of contaminant could be reached See the CLEAPSS Model Risk Assessments for Design and Technology for details Even if the limit is not likely to be exceeded the employer is still required to keep the levels as low as reasonably practicable It is therefore difficult for an employer to argue that in any secondary school workshop the level of dust is so low that no precautions are necessary In school and college D amp T departments local exhaust ventilation is likely to be necessary to control wood dust which has a WEL of 5 mg m and fumes from hot processes Precautions may also be required for other activities such soldering which
18. verbal communication difficult Where the noise exceeds 80 dB A ear defenders are normally required Can be a problem unless each fan unit is very quiet A serious problem unless each fan unit is very quiet Portable power tools are often noisy anyway and the extra noise associated with the dust collection system may be trivial Only one dust collection point to attend to and one filter to clean or replace The noise is low if the fan is outside the workplace and the duct does not carry sound Units are often compact being designed to fit under the bench or into the pedestal supporting the machine Automatic start ing of the dust control is easy Failure of one unit does not affect use of any other machine An economical solution for a workshop containing several machines with intermittent use Protection for the user This type of system will also protect others nearby Often large plant e g an extra building is needed to contain the fan and filter units High noise levels if the fan etc is in the workplace and or if the ducting transmits sound This may lead to ambient noise problems in rooms where quiet is needed Extra electrical controls may be required to ensure that the system is operating when any one machine is in use Users will need training to operate dampers If the extraction unit fails none of the machines connected to the system can be used Many
19. working every time the system is used e g by holding a strip of paper near the inlet to see if it is deflected by the air flow It would be advisable for further checks to be made once each week for example by removing a side panel from a circular saw to confirm that off cuts falling inside have not restricted the inlet to the dust collection system and checking to see that flexible hoses have not become blocked Collection points from circular saws in particular can easily become blocked especially if the collecting duct is in the form of a cowling around the blade and this should be checked on a weekly basis Clearly this must be done by people who are qualified to remove access panels and replace them correctly under conditions that do not put their health and safety at risk For example it is essential to ensure that a machine is locked off before any such checking procedure is carried out HSG 258 recommends that air flow indicators are fitted at each collection point so that users can check that the system is working Currently September 2009 this is only a recommendation although some companies that design and install LEV may try to insist that it is a legal requirement The HSE recommends that the user should ensure that the extraction system is working and something needs to be in place that will allow this to be done Checks could be done using an anemometer if available in the duct a manometer a smoke pellet or smoke pencil A usefu
20. 4 Duct velocity The duct velocity required to keep the contaminant flowing in the duct also depends on the nature of the contaminant Dusts and particles drop out of the flow unless it is sufficiently fast Gases vapours smoke and fumes require only low velocities while dusts require at least 15 m s with heavy particles requiring at least 25 m s Fora given capture velocity and inlet size the smaller the duct diameter the greater the duct velocity but the resistance to the flow is also increased The small duct diameters 75 to 150 mm usually used in education require relatively powerful fans that may increase the noise generated Flexible ducting is frequently used in LEV systems in educational establishments However it has a relatively high flow resistance because of its corrugations so long lengths and bends should be avoided 2 For details see the entry under model risk assessments in Appendix 1 1 um is one millionth of a metre 3 See Controlling Airborne Contaminates at Work HSG 258 HSE Books 2008 ISBN 978 0 7176 6298 2 3 2 Design of Local Exhaust Ventilation systems Several different kinds of local exhaust ventilation system can be used in education each with advantages and disadvantages Most establishments will end up using more than one system The types are compared in Table 2 overleaf Table 2A covers dust collection systems and Table 2B covers fume extraction 2 1 Guidelines on LEV design and layout f
21. March 2010 G225 Local Exhaust Ventilation in Design and Technology G225 Local Exhaust Ventilation in Design and Technology March 2010 Contents 1 Introduction emina a heute dense doen tie dane ee reine A a veered E T A eT Eaa 1 1 1 What is local exhaust ventilation cccccceeeececeeeeceeeeeeeeeeeeeeeeeeeeaeeeeecaeeeesecaeeeesseeeeeeeeeeeeeeneeeess 1 1 2 What contaminants occur in educational D amp T workplaces cc ccccceceeeeeeeeeeeeeeeeeeeteeeeeeeeeeees 3 1 3 Capture VeloGity i ctiss tet elt eit et tel ec A E 3 T4 Ductvelocity nceh a chidhicdie be Ge Lads Lee ed lai dee Bea ds SOL dee deci 3 2 Design of Local Exhaust Ventilation SySteMS cc ccceeceeceeeeeeceeeeeseceeeeeneeeeeecaeeeeecaeeeeeceaeeeeeeneeeeseaees 4 2 1 Guidelines on LEV design and layout for dust extraction cccccccceeeesceceeeeeeeeeeeeeeeeseeeeteeseeeees 4 2 2 Guidance from the HSE cccccecceceeeeeeceeeeeeeceeeeeeaeeeeesaaeeeeeeaeeeeeecaeeeeseaeeeeeeaeeeesseaeeseseneeeessneeeees 4 2 3 Design requirements for dust extraction from woodworking Machines ccceeeceeeeeeteeeeeees 7 2 4 Criteria for an LEV Specification a a a a a iaa 8 2 5 Electrical control for large LEV SySteMs cccecceceeeeceeeeeeceeeeeeeeeeeeeaeeeeeceeeeeeesaeeeesenueeeesenaeeees 9 2 6 Significance of multiple Collection points cececeeceeeecceeeeeeceeeeeeeeeeeeeceeeeeeceeeeeeseeeeeeesenee
22. Qualitative tests for dust In the case of dust or any other particulate contaminant the Tyndall Dust Lamp can provide a qualitative indication of whether or not a problem exists When a strong beam of light is passed through a cloud of dust particles the light is scattered by the particles making them visible The effect is particularly strong for the fine particles that make up respirable dust which is responsible for certain health conditions The referenced document discusses in some detail the principles of using a beam of light to reveal the presence of a cloud of particles It discusses lamps video and still photography and different photographic films There is no doubt that this technique properly used can graphically reveal the extent of a problem but it does not give any quantitative results 13 For details of the equipment and addresses of suppliers refer to PS62 LEV in Design amp Technology Suppliers Testers and Monitoring Equipment This will be regularly updated so readers should check for the latest issue The Dust Lamp a simple tool for observing the presence of airborne particles MDHS82 1997 HSE Books ISBN 0717613623 gives full details of this technique Available via www hse gov uk lev 15 Dust cloud Shield 3 me ae e Z oS 3 Maximum ort A Oe divergence of light beam f Eye or camera Observer or camera viewing towards lamp whilst shielding eyes from direct glare Lamp
23. Ree eas Ath eA AG ON ah ree ee ah eae DERE 4 A further test has been arranged on AUS cect sist nonent By bhatt Actas elt te ed ea a eae cence luteal ore et aoa Ee aaah Suet DANG sche hone ete 37 II Suggested Report on a Regular Thorough Examination and Test of an LEV System A Description of the system Name or eStabliShIment 5s sicsracesencven etna n ted dc ie ii e a awed haat ERMPlOW SR tush EE AEAT A E AT cuties Smutacha ake E T WOrkShOpi cinta a tide tds oven tne hea ape tet dead Sande Ave AEA aed Siete TEENA WANA CINE OF SyS E a a tate atnaiatede cots scape E E Aaa a E a a Ea aaae ei aia Manufacturer s code or reference for the system sessseesseeeerrriettteteeririrtrtisssstitintnnsssntttnnnnnnseeseeet Installer of system if different seccisnciecacd tes dades seceactenag te eakeed ce ts ce da peeec sence ned nwndne yatta wend padseaecceetdeey exe Purpose Tick one box Control of wood dust Control of solvent fumes Control of fumes from hot metal working wmo ee Fixed installation serving all activities simultaneously Fixed installation serving several activities but at a time1 Fixed installation at one work point or machine Portable system serving alternative machines System extracting from one portable power tool 1 Insert only one up to two up to three etc in the space provided B Tests Date esec Name of testing company LEA officer technici
24. action point but staff working in educational establishments do need to ensure that the systems are working correctly CLEAPSS would advise that airflow indicators should be fitted to LEV dust extraction systems in D amp T preparation rooms since these rooms are used by technician and teaching staff who will know how to monitor the airflow Indicators should be fitted to each extraction point or if separate extraction units are used to each unit To spread the cost of this over a reasonable period of time e g 2 years the work could be done according to a written action plan so that the intent to take action is clearly documented CLEAPSS believes it is not appropriate to fit airflow indicators to dust extraction points in workshops used by pupils because the pupils are unlikely to have the necessary expertise and experience to adjust blast gates We advise that D amp T department obtain a suitable hot wire anemometer and use this at intervals to check the air flow in LEV systems in workshops and compare the readings with the data obtained from the annual inspection and test The suggested testing interval is once every four weeks during tem time In further education colleges where wood machining workshops may be present and where students who enter the woodworking industry are trained then it would be sensible to fit an air flow indicator to every extraction point since this would provide a valuable teaching opportunity In general LEV systems used
25. acturers or suppliers Of LEV cc cccceeeeceeeeeeceeeeeeeeeeeeeeaeeeeecaeeeeecaeeeeeecaeeeeeeeaeeeeesaeeeeeeessneeeeeees 19 6 Recommended test Methods eeceescceeee eee eeeeeneeeeeeeeeeeeeeaaeeeeeeeeseeeeeeeaaaaeeeeeeeeeeenaaaeeeeeeeseeeeeaaeeeeeeeees 20 6 1 HSE guidance on thorough testing c ccceeeeeceeeeeeeeeceeeeeeeeeeeeeaeeeeseeeeeeeceeeeeecaeeeeeeseeeeseneeeees 20 6 2 Test methods for systems controlling wood CUSt ccccecceeeceeeeeeeeeeeeeeeeeeeaeeeeeeeeeeeeeseeeeeeenaees 20 6 3 Test methods for systems dealing with fume extraction ccccceeeeececeeeeeeeeeeeeeeeeeeeeeeeeeenaees 21 7 Maintenance requirement cccceeeessseecceeeeteeeesseeeeeeeeeeeesaaeeseeeeeeeeaaeeesaeeeeeeeseeesssaeeseeeeeeseeeaaeeaeeeeeenegs 22 TA Emptying dust Containers aar a a a ge ceet regen ice E E a a a aa Aaa saeusateuieliitegeesatacinapece 22 f 2 Piller maintenance Zes hen ea e a dese ee el deren ee A A eee 23 7 3 Informal checking rcn aae aa e aE a E eE AA aE a aaa 24 7 4 Tips for good housekeeping cceeeeceeeeeeeeeeeeeeeeeeeeeeeeeeeecaeeeesecaeeeeseaeeeeeeaeeseeceeeeseeneeetseseeeess 25 8 CEEAPSS Advice e r a a a e aa ata a ae a a a toe e a a a ca 26 8 1 The provision of air flow indicators cccccceeeeeceeeeeeceeeeeeeeeceeeeeeaeeeeseeaeeeeesaeeeeeeceeeeseneeeeseneetes 26 8 2 What employers representatives should CO ccccccccceeeeceeeeeeeeeeeeeeeeeeeeeee
26. aminant eg bandsaw upper inlet lower inlet It should be noted that there are different types of capture hoods used in LEV systems Receptor or receiving hoods where heat or fumes rise into the hood assisted by an extraction fan In D amp T departments the most common example of this type of hood is extraction from cookers and heat treatment areas in workshops Capture hoods are used where the source and the contaminate cloud are outside of the hood The capture type hood has to generate sufficient air flow at and around the source to draw in the contaminant Capture hoods include the extraction from the tip of a soldering iron and those used on most woodworking machines and for welding fumes The third type of capture hood is the enclosing hood In schools the most common example of this type of hood is a fume cupboard used in science but partially enclosing hoods are found in D amp T including paint spray boots used in graphics and in workshops 1 2 What contaminants occur in educational D amp T workplaces The Health and Safety Executive refers to a whole range of contaminants that may occur in D amp T workplaces but in education the rate of production or the duration of the activity may be too low or too short to require LEV This is a matter for risk assessment and each case is discussed in the CLEAPSS publication Model Risk Assessments for Design and Technology in Secondary Schools and Colleges Table 1 summarises the s
27. aminant level test Most hazardous application in use Machining MDF Casting non ferrous metal Spraying a large item Other specify Conditions of test Insert details below Number of inlets open Machine in use Most hazardous application in use 35 Contaminant level test continued Contaminant tested for Detection method Respirable dust from woodworking Fluorides from casting Solvent fumes from surface treatments Chlorinated hydrocarbons Other specify Result Contaminant level at operator s breathing zone is less than Po Either Air flow measurements for regular thorough examination Anemometer used Make Model For small aperture inlets For large area inlets Machine eee Machine _ Inlet tested Number of system ace rate m s ere eee inlets open Or Pressure measurements instead of air flow rate for regular thorough examination Type of measuring instrument used Make Model The test points should include both sides of any filter and both sides of any anticipated blockage points Where a test point is provided by means of a long tube connected to a nipple in the duct it is important to check that the tube is unblocked before connecting the measuring instrument Test point location Machine Number of system Static pressure kPa running inlets open Close to top inlet hood Close to side inlet hood Cl
28. an cccccceeeeeeeeeeeeereeeeeees Type of test Tick the box Regular thorough examination Previous tests on this system Insert date s Commissioning or initial appraisal Previous regular thorough examination 38 Either Air flow measurements for comparison with previous results Anemometer used For small aperture inlets For large area inlets Machine workplace Machine Area of inlet Number of i Flow rate volume running tested m system inlets open Or Pressure measurements for comparison with previous results Type of measuring instrument used Make Model The test points should include both sides of any filter and both sides of any anticipated blockage points Where a test point is provided by means of a long tube connected to the nipple in the duct it is important to check that the tube is unblocked before connecting the measuring instrument Test point location Machine Number of system Static pressure kPa running inlets open Close to top inlet hood Close to side inlet hood Close to machine casing Inlet side of filter Output side of filter Inlet side of constriction Output side of constriction Tests for air quality Result of air quality test The quality of air around the equipment WAS 060cceee eee cece e cece nent ee ee eee eee ee eee eeeeeeeeeeaeeeeees 39 C Conclusions from examination
29. anufacturers but in practice the need for this will depend on how much the instrument is used If there is any question over the readings produced the anemometer should be recalibrated In many cases however where similar values are obtained when tests are repeated and there is no evidence to suggest that calibration has drifted recalibration can be deferred until it is thought to be necessary 19 This type of anemometer is even less likely to drift than the vane type but the manufacturers still recommend an annual recalibration See the comments in footnote 2 20 A vane anemometer suitable for air flow measurements in large aperture hoods is listed in PS62 21 Vane anemometers used by a science department need to be accurate at an air flow rate of 0 3 ms a much slower air flow than will be required for the inlets and hoods encountered in a design amp technology workshop Therefore if a vane anemometer is borrowed from a science department for measurements of flow rates in large area hoods it is important to check that the instrument is suitable for air flow rate measurements of 2 m s 22 See PS62 for details of a suitable anemometer 17 It is not very helpful to measure flow rates unless the whole system is set up for use because the flow rate will change If a small probe is introduced into a duct it may be possible to make a measurement without changing the duct velocity In many systems it is only practicable to measure the fl
30. any such mixed bag would have to be treated as hazardous waste Some wood waste formed during hand operations will always end up on the floor It should be cleared up using a dustless method i e using an industrial vacuum cleaner or by the use of an appropriate floor sweeping compound to prevent the dust becoming airborne The sweepings can be transferred to a bag correctly labelled and stored safely for eventual disposal or collection In transferring dust and shavings to bags make sure that the operator is not exposed to hazardous levels of dust 7 2 Filter maintenance Dust filters Most dust collection systems incorporate filters which should be shaken periodically to dislodge dust and maintain filter efficiency The largest systems have motor driven shakers that operate automatically More typical systems used in educational establishments have manually operated shakers The supplier normally specifies the intervals at which these should be used These specifications often give a time in hours e g every 8 hours or once a week which would probably be appropriate where the extraction is running throughout the working day In schools and colleges this is rarely true and the interval should be established by experience If a particular system has been in heavy use it might be necessary to shake the filter at the end of the day to prevent its performance deteriorating otherwise once a month could be sufficient Disposable
31. aperture whose plane is parallel to the local flow direction If the measurement is made via an aperture whose plane is perpendicular to the local flow direction the pressure may be above or below the static pressure This reading is called the total pressure The dynamic pressure is the difference between total and static pressures Substances hazardous to health The Control of Substances Hazardous to Health COSHH Regulations define such substances as those which are toxic and very toxic including carcinogenic harmful corrosive or irritant any substance with an occupational exposure limit pathogenic microorganisms dust at a sufficient concentration and any others with a comparable health risk Testing intervals All LEV which is required to meet the COSHH Regulations must be tested at particular intervals Regulation 9 The most common specification is for a 14 month interval i e an annual test with two months grace should the test be unavoidably delayed Time weighting WEL limits are subjected to time weighting i e the actual concentration is the average value over either 8 hours or 15 minutes It is unlikely that the average values of for example wood dust concentrations in an educational workshop exceed the WEL but may approach it In that case the level has not been reduced as low as reasonably practicable Tyndall dust lamp A Tyndall dust lamp is any lamp with a reasonably parallel beam of light that can reveal t
32. arse dust such separation is not perfect Animal litter should be dust free and not contaminated with chemicals used to preserve wood or potentially harmful hardwood particles It is impracticable for workshops to meet these conditions and litter for keeping animals should be obtained from a supplier who can guarantee they are met Solutions It is therefore important that all of the following control measures are adopted when emptying dust containers Anyone not involved in the emptying process should be kept well away from the area 1 The person handling loose collected dust is provided with a toxic dust mask also referred to as a disposable respirator Type FFP2 is suitable for ordinary sawdust but type FFP3 should be used if there is a lot of fine dust present e g from MDF29 2 The procedure used minimises the dispersion of the dust e g the drawer can be placed in a large plastic bag before inversion to empty it 3 The wood dust is sealed in plastic bags for waste collection 29 Suitable masks respirators are available from many manufacturers and even more suppliers examples include 3M part number 9320 and 9332 It is not possible to give guidance on the time for which one mask can be used If the use is intermittent care must be taken to avoid dust contamination of the inside between sessions Note that there may be problems in providing adequate protection if the masks are worn over beards Nuisance dust m
33. asks must never be used as they provide no protection at all 22 Disposal of dust The CLEAPSS document PS 31 Disposal of waste in Design and Technology gives full details of the correct disposal of waste produced in design and technology It should be noted that some types of wood waste may be considers as hazardous The relevant section from PS 31 is given below Waste from the machining of new untreated timber would be classified under the List of Wastes Regulations 2005 as 03 01 05 sawdust shavings cuttings wood particle board and veneer other than those mentioned in 03 01 04 The entry 03 01 04 is sawdust shavings cuttings wood particle board and veneer containing dangerous substances The asterisk denotes that this is hazardous waste The term dangerous substances is interpreted to mean hazardous chemicals used to treat or cover the wood such as preservatives but not necessarily thin layers of paint unless it is very old paint containing lead based pigments Wood dust which comprises only materials in 03 01 05 will not be hazardous and can therefore be disposed of in the normal refuse Dusts and shavings in category 03 01 04 will be hazardous and will need to be disposed of by a registered waste contractor For a bag of dusts and shavings which contains a mix of both types of waste it will be practically impossible for a department to determine whether the threshold of dangerous substances has been exceeded It follows that
34. be used as a stand for machines such as sanding machines that would otherwise need to be fixed to a bench An essential feature of any LEV system is that is should correctly control the contaminant It should be recognised that a standard off the shelf unit such as are available from a number of manufacturers may not provide adequate control Schools contemplating buying such units must ensure that it they will do the job Guidance in HSG 258 states that it is the responsibility of the supplier to ensure that they system supplied will provide adequate control and to provide a commissioning certificate to show the performance on installation By their nature off the shelf units will not be supplied with commissioning reports It will therefore be necessary to arrange for a commissioning test and report An important feature of individual units is the size and type of the container that stores the dust Most free standing individual units are unlikely to have a container of sufficient size to cope with the volume of chips and dust produced by a wood planing machine for example unless only very small quantities are produced They may however be sufficient for a small band saw bench mounted jigsaw or a sanding machine Some dust extraction units are contained within rectangular steel casings and these will usually collect the dust in a tray or drawer that needs to be emptied by hand The person emptying the tray should wear a face mask see section 7 1
35. dentified Please contact CLEAPSS or check on the D amp T resource part of its web site www cleapss org uk for the most recent version of PS62 which can be downloaded For password details look in the spring term Bulletin contact the science department or e mail CLEAPSS at password cleapss org uk 30 Appendix 1 Glossary of terms Anemometer An instrument that measures air speeds Two different principles are used the cooling effect of the air flow on a heated component which might be a hot wire filament or a semiconductor and the mechanical effect of the air flow on a light vane which can rotate or be deflected Approved code of practice An Approved Code of Practice ACOP for a set of regulations made under the Health and Safety at Work Act includes the regulations themselves interpretation of those regulations marked ACOP in the margin and often further comment from the HSE Sections marked ACOP have a special legal status In a prosecution for breach of health amp safety law where it is proved that the Code has not been followed the court will find the defendant guilty unless the defence can show that the law has been met in some other way Blast gate Another name for a damper when used as an on off control in an LEV system Capture velocity The capture velocity for each contaminant is the air speed necessary to draw the contaminant into the inlet of the LEV system Carcinogen A carcinogen is a substance that has been ident
36. dust collection bags and or filters to attend to Many fans can generate much noise The relatively small filter area and size of unit can result in the filter becoming clogged and hence a lack of efficiency These units are unlikely to cope with large volumes of waste such as those produced by wood planing machines General purpose units are not always efficient and may not adequately control contaminates Difficult to make system and machine electrically interlocked It is then debatable whether or not the system fulfils legal requirements There is a high risk that LEV may not be used because of the fuss of connecting up The dust collection system may make the tool difficult to control If a small dust bag is fitted it can be filled after only a few minutes work and must be changed or emptied frequently Table 2 Different types of LEV 2B Fume extraction systems Characteristics Noise e Advantages Disadvantages Fume Hearths forges welding A combined LEV is run only The dampers should be set extraction benches and crucible system with a when it is on installation to balance from hot furnaces fitted with single fan is less needed and may the flows so that all units metal areas either noisy than be interlocked have adequate fume a individual fume separate fans for with the system extraction and should not extraction or each unit when used to heat the then be moved In practice b acomb
37. e breathing zone of an operator have ever been measured and which processes were being performed during the measurements If no records of tests exist arrange for concentrations of dust amp or fumes to be measured by a contractor or a trained employee Decide whether it is necessary to repeat these tests annually or whether annual tests of air flow rates and or pressure changes are sufficient Make arrangements for the annual tests either by contractors or trained employees Follow up the test results with any necessary remedial measures and retest if appropriate Such measures could involve retraining staff to use correctly the LEV systems provided and documenting how the systems work for the benefit of future staff repairing hoods ducting and filter housings maintaining dampers blast gates and fans replacing filters or control systems fitting explosion relief panels on dust collectors a panel which acts as a safety valve in the dust collection unit It is designed to blow out under excess pressure Ensure that workshop cleaning staff are provided with appropriate types of vacuum cleaners and are trained to use them correctly 31 For community and voluntary controlled schools the employer is the local authority For foundation schools academies city technology colleges voluntary aided and independent schools and for sixth form and further education colleges the employer is the governing body or possibly a trus
38. e more appropriate The chosen interval should be recorded in the log book b Other checks e A good test that dust extraction working effectively is to hold some sawdust in the palm of one hand and see if the collection hose or extraction point will collect it Repeating the test and moving the hand further away from the collection point will give an indication of effectiveness Obviously care should be taken not to do this near to rotating blades or cutters If the dust is not collected effectively then it is an indication that the system is not working as intended and further investigation should be carried out A similar check can be done using a strip of plastic cut from a plastic carrier bag These tests will only give a qualitative indication of effectiveness e If any faults are suspected test the flow rate using either a vane anemometer or a hot wire type as described in section 4 2 e Alternatively a dust lamp test as described in section 4 1 could be used 24 7 4 Tips for good housekeeping It is important to realise that dust can deposit within inlet hoods inside band or circular saws or on bends in ducting especially flexible ones and seriously affect the performance of the system In extreme cases it has been known for dust to accumulate to such an extent that the duct or hose can be totally blocked If the problem points can be identified regular brushing can eliminate the problem if there is an access port If access po
39. eeeeceaseeeeseeeeeteeeeees 27 8 3 Whata head of department should dO cccceeeccceeeeeeeeeeeceeeeeeeceeeseaeeeeecaeeeeeceeeeseseeeeeeteneeess 28 8 4 What all staff should dO eee eececeecccceceeeeeeeeeceeeeeeeeeeeteaaeeeeecaeeeeeeaeeeeseaaeeeeesaaeeeeeceeeeseseeeeseneeees 29 9 Suppliers AddreSSES sisinio eii aiei aaien iai eiaeia iie aiats 30 N EA Glossary of E ek eee ce A E 31 Appendix 2 Testing of LEV Systems A Er a r aea e a E 34 CLEAPSS 2009 Strictly Confidential Circulate to members and associates only As with all CLEAPSS materials members and associates are free to copy all or part of this guide for use in their own establishments CLEAPSS Brunel Science Park Kingston Lane Uxbridge UB8 3PQ Tel 01895 251496 Fax 01895 814372 E mail science cleapss org uk Web Site www cleapss org uk L225 Local Exhaust Ventilation in Design and Technology 1 Introduction Local exhaust ventilation is used to remove or reduce the level of contamination in workplace atmospheres and thus reduce the risk of ill health in staff students and visitors It is essential that LEV is provided where the risk assessment shows it is required that it is used and that it is maintained in good working order It is also essential that the correct type of LEV is installed so that contaminants are removed from the air The purpose of this guide is to help those employers responsible for Design amp Technology D amp T departments in seco
40. eeseees 9 2 f WFIOXIDIC CUCUING s aiccsuateveetn stat tobstatuccaatecdsavece Uacdtatandsisetetincduatanasanees A E 10 2 8c Individual extractioniunits 0nc het saat ea eee ie ae ee Ae teeth 10 2 9 Extraction of Solvent fUMES ccccccceeeeeceeeeeeeeeeeeeeeeeeeeeeeeeeeeaeeeeeeaaeeeeecaeeeeseeeeeeeeeeaeeeeeeneeeesenaees 11 2 10 Extraction of Solder fUMC cccccccceeeeceeeeeeeeeeeeeeeeeceeeeecaeeeeceaaeeseecaeeeeeeeaeeeeseeaeeeeseneeeessneeeeeeeaees 11 2 11 Dust masks an alternative to ventilation cccccccceeeccceeeeeeeeeeeeeceeeeeeeeeeeseeaeeeeseeaeeeeseneeeeeseaees 11 2 12 Minimising the explosion risk with mixed particulates eee ceeeeeeeeeeeeneeeeeeeeeeeeeeeeeeeeeeeeeeeeaaeeees 11 3 Legal requirements 25 re r r ee inland ee ee ee ee eee eee 12 3 1 Health and Safety at Work etc Act 1974 0 cccccessseceeeeescssseeeeeeceessseeaseeeeesesseeensaeesaaeeeeeeeees 12 3 2 COSHH Regulations ccccccceccecccceeeeeeeeeeeeeeeeeeeaeeeeeeeaeeeeseaeeeeeeeaeeeessaeeseeeaaeeeeseeeeeesceeeeeeseeeess 12 3 3 Other regulations 2 22 0 c teccceccecceceniectedeceeececeetedenedvbesctcevbedauedvbesahieshedotsevaecctsevhedetedveeeetaeeeedarest 14 4 Examination methods AREE fetes Aas eat ete tesa trad a E 15 4 1 Measurements of air g a E a a ea a ar 15 4 2 Measurements of air flow ccccccccceeeeeceeeeeeceeeeeeeeeeeeceeeaeeeseeaeeeesecaeeeeseaeeeeseaeeeeeseeeeeeseeeeesnaees 17 5 Manuf
41. either traversed by hand to illuminate dust source or mounted on a stand The lamp does not have to be a special one if it produces a confined beam of strong light A stage spotlight or slide projector may be suitable If photography is being used to record the result the beam should be photographically white but for visual observation the colour is not important The required arrangement is illustrated above In use the lamp is usually set up to produce a beam in front of the face of the user of a machine or process The observer stands facing the lamp but with a screen to protect the eyes from the direct beam It is often useful to reduce other lighting in the area and then the dust cloud if there is one will become visible The presence of a visible cloud means that the dust control system is not adequate to protect the user HSE Woodworking Information Sheet 1216 gives enough information for any school wishing to try the procedure Attempts to use this technique have shown that in practice in many school workshops space is so tight that a dust lamp is very difficult to use Machines are often so close to walls that it is impossible for either the lamp or the observer to be positioned to achieve the required angles A further problem arises because many educational workshops have good natural lighting and no blinds The most practicable way of doing the test is to wait until the winter and use the lamp at dusk which may present
42. est issue Specialist companies offering a full service should be asked to provide e a commissioning test with air sampling to demonstrate the effectiveness of their equipment whether designed to cope with fumes or dust e a manual covering the equipment s maintenance and use including a maintenance log and or e training in the equipment s use As with any other contractor the client should attempt to determine the competence of the company to be contracted to do the work The HSE has provided a list of suggested questions but the most significant ones to ask here are given below e What experience does the company have in the type of work required e What qualifications and skills does its employees have e Does the company have any independent assessment of its competence e ls the company a member of a relevant trade or professional body Care should be taken in the purchase of off the peg units to see that they will properly control the contaminate There are instances of schools wasting money on the purchase of inappropriate equipment that fails to provide adequate control A better course of action would be to approach a specialist company who can provide the appropriate level of expertise and to check that that any specification produced by a company meets the criteria given in section 2 4 27 Use of Contractors a joint responsibility HSE 2002 HSE Books ISBN 0717625664 19 6 Recommended test methods It
43. for fume extraction from hot metal areas do not have such heavy use as those used for dust extraction and we feel that airflow indicators are not needed for these systems in schools In further education colleges where such systems may have more extensive use and in welding workshops in such colleges the CLEAPSS advice is that air flow indicators should be fitted 26 8 2 What employers representatives should do Confirm that dust and fume control systems are provided in the workshops If not draw up a specification for the LEV needed for each situation ensuring that it meets the criteria listed in section 2 3 1 and that the recommended maximum noise level 65 dB A for a teaching workshop is not exceeded bearing in mind the most hazardous operation carried out at each location obtain several quotations from different suppliers ensure that each quote includes provision for a commissioning test using a dust or fume monitor and measurements of flow rate or pressure and the resulting noise level during the operation specified ensure that following installation training will be provided on how the system should be used and maintained and reject any quotes which do not include hoods specific to the machines involved Where dust and fume control systems have been installed determine whether records exist of tests performed on this equipment Check to see whether these records show that dust or fume concentrations in th
44. g the efficiency of which they are capable 1 1 What is local exhaust ventilation General ventilation of the workplace dilutes any contamination of the air but does not give a control at the source Local exhaust ventilation is designed to intercept a contaminant as close to the source as possible and carry it away through a duct often to a filter unit before passing the air to the atmosphere outside or possibly back into the workplace A typical LEV system comprises the following components in order See list and diagram overleaf 1 See Controlling airborne contaminants at work HSG 258 HSE Books 2008 ISBN 978 0 7176 6298 2 1 1 A hood enclosure or other inlet device that will collect the contaminant at its source 2 A duct through which air flows to carry the contaminant away from the source 3 Where necessary a filter bag or other air cleaning device to remove sufficient of the contaminant to allow the air to be passed to the outside or returned to the workplace 4 Anair mover usually a fan to produce a difference in air pressure so that the air flows as required The inlet device duct and filter then contain air at a pressure below atmospheric 5 Further ductwork to carry the cleaned air to the outside or back into the workplace This ductwork contains air at a pressure above atmospheric main duct ie oy oH rat stack branch duct ro rama angled junction short flexible duct machine producing cont
45. gn must be re evaluated and the necessary modifications made so that the system is proved to be effective Measurements of pressure in ducts The measurement of the static pressure in ducts can locate a restriction to air flow and indicate the nature of any problem The instrument used to measure the pressure should be calibrated in pascal and a range of 0 to 5000 Pa may be required with the ability to discriminate changes of 5 Pa between 500 Pa and 5000 Pa Test points could be provided close to each inlet either side of any dust collector or filter unit and before and after the fan If the pressures are recorded when the system is performing satisfactorily changes will indicate blockages or faulty fans Problems with this method arise when the ducting etc is in an inaccessible location However test points can be permanently attached by the use of inexpensive plastic tubing to provide connections at more accessible positions for regular monitoring Pressure measurements can also be used to determine the air velocity in ducts if a pitot static tube can be introduced without disturbing the air flow significantly This however requires a sensitive and expensive manometer and some specialist skill in operating it It is rarely used and would normally be inappropriate for use by school staff 23 See Controlling airborne contaminants at work 2008 HSG 258 2008 HSE Books ISBN 97807176162982 24 The static pressure is the actua
46. hand held soldering irons and plumbing or other pipe fitting work The HSE has advised educational establishments to avoid the use of rosin based fluxes by using rosin free types It is hoped that this will avoid the need for LEV on soldering benches where there is good general ventilation but the advice may change as experience grows with alternative fluxes Extraction may be needed if a large amount of soldering is done as may be the case in systems and control courses at examination level and where soldering is done in rooms with fairly low ceilings It may also be needed by teachers and technicians using a soldering iron for long periods of time perhaps in a small room Pupils with respiratory problems may also need to use fume extraction 2 11 Dust masks an alternative to ventilation It is neither acceptable nor practicable for everyone in an educational workshop to wear a dust mask capable of containing toxic dusts see section 7 1 Nuisance dust masks as sold by some d i y shops do not give significant protection A toxic dust mask may however be needed by the person who is emptying dust containers or carrying out other maintenance when the collection system is necessarily switched off see section 7 1 2 12 Minimising the explosion risk with mixed particulates Wood or plastics dust suspended in the air can form an explosive mixture that may be ignited by a spark It is for this reason that ferrous metals should not be gro
47. have found that it is very easy for the extraction point from such cowlings to become blocked by slivers of wood that then allow the dust to clog the pipe We have several examples where the extraction point is totally blocked to the extent that no dust is being collected from the machine It is essential that the collection point on any machine is checked to see that it is of sufficient size 65mm diameter should be considered the minimum size for effective use A large system with ducting to each machine can be noisy and in the vicinity of the collection unit the noise can exceed 80dB Where the noise is above this level ear protection would normally be required In addition the ducting will often transmit ambient noise throughout the building and this can disrupt teaching especially when the teacher needs to talk to the whole class In a large system serving several rooms and a resistant materials preparation room it is likely that at least one machine that requires LEV will be in use at any one time This means the unit may well be in operation for most of the day producing a constant background noise If the collection unit is located in the preparation area this constant noise may become intolerable for a technician spending much of their working day in the room Some collection units are designed so that they can be placed outside the building This can be very effective but the unit will need to be protected from potential vandalism damage by
48. he flow rate Again the instrument is calibrated to give a direct reading of the flow rate In this case an accurate reading can be obtained for the air flowing through a narrow slot provided the calibration is checked periodically 9 Again if this instrument is used to measure the flow rate into a large aperture hood an average rate should be worked out by taking several readings at different places Hoods vary enormously from the very small aperture of a pipe attached to an individual soldering iron to the mesh wall of a spray booth Vane anemometers will only give accurate mean flow rates for large apertures e g fume cupboards in a science department Their use is not appropriate for very small apertures i e those for which the inlet area of the hood is much smaller than the area of the vane It is however possible to obtain small vane anemoneters that will measure the air flow in the ducting typically found in school and college systems and these can be effective although an instrument with a small probe is therefore required for many flow rate measurements in design amp technology 2 17 See PS62 for suppliers of smoke pencils NB The smoke is often highly corrosive and the smoke generator must be resealed after use Choose types based on acetic acid if possible 18 A vane anemometer is an electromechanical device and its accuracy depends on the friction in the pivots remaining unchanged Annual recalibration is recommended by the m
49. he presence of fine dust by the forward scattering process first identified by Professor Tyndall Workplace Exposure Limit WEL A WEL is the maximum concentration to which employees may be exposed by inhalation averaged over a certain time span The value is not a distinction between levels that are unsafe or safe and exposure should be well below any relevant WEL value If the substance is a class 1 or 2 carcinogen or a sensitiser the level of exposure should be reduced to as low a level as reasonably practicable The values of WELs for different substances are published by HSE in document EH40 2005 Workplace Exposure Limits 33 Appendix 2 Testing of LEV systems Commissioning test of an LEV system Any new LEV system should have a commissioning test carried out after installation to ensure that it is performing as required This also applies to any off the shelf system that a school or college may purchase and install itself or which is supplied and fitted by a contractor during a refurbishment programme Thereafter the COSHH regulations require that every LEV system has a thorough examination and test annually although a two month slippage period is permitted HSG 258 contains guidance on what should be included in this An LEV system should also be recommissioned after any modification or change in the way it is used Most educational workshops will contain at least two systems one for controlling dust e g from woodworking machines
50. ied out Quantitative and semi quantitative tests For some substances there are instruments which draw in samples of the inhaled air automatically measure the concentration of the particular substance and show the result as figures on some kind of display Such figures may look very impressive but the user must be aware of the limitations of the instrument some results could be inaccurate because of the presence of another contaminant others could need a calibration correction etc These tests are particularly useful for measuring the concentration of fine dusts that are invisible under normal lighting Instruments that are suitable are listed in the accompanying document PS62 In other tests samples of the air are drawn through a tube containing chemicals and an indicator changes colour according to the concentration of the substance being tested for These systems are often referred to as semi quantitative because the precise extent of the colour change in the tube may be difficult to determine the volume of air drawn in may be uncertain etc Nevertheless these uncertainties are often no greater than those introduced by the choice of sampling position or test conditions Such measurements may be as accurate as those from a much more sophisticated instrument They are useful for example for monitoring levels of solvent vapours Suitable detection kits are available from Anachem Ltd for Gastec products or Draeger Ltd see PS62
51. ified as being capable of giving rise to some form of cancer in humans There are three categories of carcinogen 1 substances known to cause cancer on the basis of human experience 2 substances which it is assumed can cause cancer on the basis of reliable animal evidence 3 substances where there is only evidence in animals which is of doubtful relevance to human health i e the evidence is not good enough for Category 1 or 2 Category 1 and 2 carcinogens carry the risk phrases R45 May cause cancer or R49 May cause cancer by inhalation Category 3 carcinogens carry the risk phrase R40 Limited evidence of a carcinogenic effect Further discussion on these is contained in Section 7 8 of the CLEAPSS Laboratory Handbook held by science departments Chemical sampling tube Used to measure the concentration of a chemical pollutant that is drawn through the tube by a pump hand operated or powered The concentration is shown by means of a colour change of an indicating material in the tube Colophony A commonly used flux for soft soldering which has been identified as the cause of health problems in some users It is also known as rosin Contaminant Contaminants are the substances hazardous to health that the LEV system is required to remove or control In a typical workshop these include particles of wood or metal dust mist smoke fume vapour and gas See Table 1 Damper A shutter which can be used to regulate
52. ined system more than one is metals the crucible furnace may with a damper fitted in use The flexible arm produce such a lot of fumes above each inlet to ducting can be e g during degassing that Solder fume where rosin cored flux is not replaced by rosin free type Solvent vapour control Fumes from laser cutters Extraction from CNC machines such as milling machines and routers control the air flow into the duct flexible ducting that can positioned where needed Systems either use inlets on each soldering iron or air currents that are drawn across the work away from the user In both cases the air is filtered and returned to the workplace Spray booths for painting small components are available commercially or improvised using sheets of hardboard or even cardboard and sit ona bench An exhaust fan takes the air from the booth straight through a wall or window to the outside Alternatively a filter is provided to catch the paint aerosol and or solvent before the air is returned to the workplace Usually a filter system housed in a cabinet alongside the machine is needed In some systems there may also be a flue that will take fumes to outside the building Some of these machines are totally enclosed within a cabinet fitted with electrical interlocks In these cases it may be better to remove dust after the machine has finished its cycle rather than trying to extract it N
53. ints are not provided then parts of the extraction dusting may have to be dismantled This should not be a problem since blockages are most common where there are bends in flexible ducting which are usually secured by large hose clips If this releases dust into the workshop the person doing the brushing must use a vacuum cleaner suitable for the collection of dusts or wear a toxic dust mask as discussed in 7 1 with nobody else nearby Where systems incorporate dampers to maximise the air flow at the inlet in use it is essential that the user appreciates how the controls must be used This implies a need for training in the use of the system together with a guidance sheet or users manual and reminder notices near machines Cleaning Even with an excellent dust collection system at each machine there will still be dust produced for example by hand sanding or dust which escapes at each machine Cleaning in a workshop is not a trivial activity because wood dust has been given a WEL and the employer is required to keep its concentration as low as reasonably practicable to protect the health of cleaning staff as well as of D amp T staff and pupils Some establishments do not include wood preparation and storage areas in cleaning schedules If regular cleaning staff do not service these areas other arrangements must be made to ensure that the health of the person doing the cleaning is safeguarded Traditional cleaning methods using brushes
54. is not sufficient just to test a dust collection system with measurements of pressure or air flow rate measurements of dust concentration must be made under standard conditions of use Once the system has been shown to be controlling the dust adequately air flow measurements can be used to confirm that it is still doing so provided the materials used and the process have not changed substantially Therefore the test results should be compared to the original commissioning test to see that the standard of extraction is being maintained It is important for schools to keep copies of all test reports whoever has done the tests for at least 5 years The D amp T department should always be given a copy of the test report Someone in the D amp T department must know where they are filed an inspector from the HSE could ask to see them 6 1 HSE guidance on thorough examination and test Guidance for the 2002 COSHH Regulations does not require that a dust monitor see section 4 1 be used in the commissioning test of a new dust control system to confirm that under the most severe conditions of use the system is keeping the airborne dust concentration below the WEL Nevertheless it is difficult to see how the system can be proved effective without doing so The commissioning test should be repeated if the conditions of use or the work being done change e g the introduction of MDF where natural softwood had been used before However other simpler tes
55. ituation and gives specific references to the Model Risk Assessments MRAs Table 1 Air contaminants and their control Contaminant Size range Examples LEV required Air filter pms references to CLEAPSS MRAs in education Baa DAR Grinding dust metal 1 034 Possibly Not needed Wood a 1 E Probably B ide 1 100 Wood dust 1 071 Yes Fabric or paper Textile dust aie Unlikely Flour 3 029 Unlikely Spray from etching tanks Not if a lid is used Not needed 1 014 amp 1 015 Smoke 0 01 1 0 Casting in oil bonded sand 1 020 Yes Not needed Tests on burning textiles 2 010 No Fume 0 001 1 0 Solder fume 1 025 Possibly Combination Welding fume 1 028 1 030 Yes Casting fume 1 020 Yes Vapour 0 005 Solvent vapours 1 068 1 069 Possibly Activated carbon Gas 0 0005 Forge gases 1 022 Yes Vent to atmosphere Vehicle exhaust 1 050 Yes Note Fumes from forging are only usually a problem if coke fired forges are used 1 3 Capture velocity The capture velocity is the air velocity necessary to draw the contaminant into the inlet of the LEV system The HSE recommends different capture velocities for different situations and different contaminants These range from 0 25 m s for the solvent vapours released by paint drying up to 10 m s for dust released from fast machines with small collection inlets However the capture velocity required also depends greatly on the design of the hood forming the inlet aperture 1
56. l air pressure i e not increased by the motion of the air It is measured via an aperture parallel to the air flow If the aperture is at right angles to the flow measurements of the total pressure are possible the sensor for measuring this is called a Pitot tube The difference between these two pressures is the dynamic pressure due to the motion of the air from which the flow velocity can be calculated 25 See PS62 for details of a suitable digital micromanometer 26 A Pitot static tube allows the measurement of the total and static pressure at the same position The dynamic pressure is the difference between the two It is normally used with a manometer which indicates the difference between these two pressures and therefore gives the extra pressure due to the air flow 18 5 Manufacturers or suppliers of LEV Dust and fume control equipment is available through different routes general suppliers of equipment for D amp T or specialist manufacturers and installers While general suppliers may offer components at keen prices they are unlikely to be able to design or recommend the best system for a customer s needs and provide a proper commissioning test after installation Specialists who are likely to provide a full service are listed in the separate CLEAPSS document PS62 LEV in Design amp Technology Suppliers Testers and Monitoring Equipment This is likely to be regularly updated so readers should check for the lat
57. l measures are in place there is no reason why MDF cannot be used in educational establishments Model risk assessments MRAs A collection of generic risk assessments for a group of activities or typical activities that can be used with minor adjustments to form risk assessments for the actual activities See the publication Model Risk Assessments for Design and Technology in Secondary Schools and Colleges 2009 only available to subscribers published by CLEAPSS The latest version of the Model Risk Assessments was published on the CLEAPSS web site in September 2009 Occupational Exposure Limit OELs have now been replaced by WELs See below Personal Protective Equipment Personal Protective Equipment PPE consists of items such as protective aprons boots gloves goggles and masks These should be used as last resort protection if other precautions fail or are impossible to use 32 Pitot static tube A Pitot static tube measures both static and total pressures in a duct see below and allows the difference to be measured as the dynamic pressure that then allows the airspeed to be calculated Rosin A commonly used flux for soft soldering which has been identified as the cause of health problems in some users It is also Known as colophony Static pressure and dynamic pressure The static pressure of the air in a duct is the average pressure of the air without allowing for any change due to its motion It is measured via an
58. l quick visual check is to see if dust is collecting on top of a band saw for example or in the base of a band saw or circular saw or if dust collects on horizontal surfaces around rooms where machines are located Dust in these places 8 If the CLEAPSS models are not appropriate the assessor should bear in mind the hierarchy for controlling risks described in Five Steps to Risk Assessment HSE available from www hse gov uk 13 indicates that the system is probably not working effectively The HSE web site www hse gov uk lev faqs htm provides some very helpful information on what is and is not required in LEV systems Testing intervals When the risk assessment shows that LEV is required for adequate health and safety COSHH Regulation 9 requires in general that it is examined and tested at least once every 14 months in practice an annual test This applies to all methods of collecting wood dust including simple systems where a vacuum cleaner may be used and fume extraction from heat treatment equipment In the case of a system used to control fumes from non ferrous metal casting the interval is reduced to 6 months However in many educational establishments non ferrous metal casting is done during a period of a few weeks and not repeated until the following year In such cases an annual test of the LEV allowing sufficient time before use to correct any defects would provide testing at intervals of less than 6 months of use and
59. ly be significant on large machines that may not be fully enclosed 2 3 Design requirements for dust extraction from woodworking machines For collecting wood dust LEV systems will normally be one of three types a multi branched ducted system serving all rooms and leading to a large collection unit which may be outside the building a discrete ducted system for each room individual extraction units for each machine The advantages and disadvantages of these are given in table 2A but some important design criteria are outlined below The most important function of an LEV system is that it should control the contaminant The flow rate needed to collect and remove the contaminant the type and design of hood the capture velocity and the filter media if any are all important Teachers and technicians are not expected to have this specialist knowledge but those involved in the specification for LEV systems should ensure that a suitably qualified person who does is involved in the design Because of this purchasing off the shelf units and having it installed by a technician is not recommended There is an important design consideration in the extraction of dust from circular saws sometimes called table saws Some circular saws have a cowling fitted round the lower part of the saw blade below the saw table These cowlings are fitted with an extraction point that is usually connected via a flexible pipe to the main extraction system CLEAPSS staff
60. m provided if the risk assessment requires it or not to wear a mask provided for use when emptying dust containers Once each day or every time a machine is operated a simple check should be used to confirm that the LEV is working e g by holding a strip of paper or flexible plastic where the air flow should produce a deflection Under COSHH Regulation 8 2 staff are required to report defects in safety systems hopefully before such defects give rise to significant hazards The reporting system should be such that dated copies of reports are retained at least until the fault is dealt with Staff are also expected to report any health problems which might be related to conditions at work for example blocked sinuses excessive eye watering or other hay fever like symptoms Staff are expected to ask for instruction or training if it becomes necessary e g when new processes or materials are introduced or when new staff are appointed 32 There is a serious shortage of training facilities and services for D amp T nationally The Design amp Technology Association DATA is trying to rectify the situation 29 9 Suppliers addresses This guide L225 is accompanied by the publication PS62 LEV in Design and Technology Suppliers Testers and Monitoring Equipment which contains the contact details for LEV contractors and other companies mentioned in this guide PS62 will be updated as details change or new suppliers are i
61. ms are often designed to allow more than one collection inlet If the air flow is appropriately balanced all collection points can be made to work adequately and simultaneously However in some systems perhaps because a small less noisy fan has been fitted not all of the collection points can be used simultaneously A system of dampers or blast gates is then required to close off those parts which are not in use in order to achieve an adequate air flow at the points that are being used Unfortunately operators may fail to close unused inlets or fail to open those that are needed Frequent instruction and written reminders perhaps adjacent to each inlet will be required to overcome this problem particularly in schools with a high staff turnover There is an additional problem in school workshops where it may be unreasonable to expect pupils to operate damper controls because they will not understand how to set them effectively HSE recommends that air flow indicators are provided to allow the operator of any machine to ensure that the flow of air in a system is sufficient to control the dust or fumes One way of doing this is to install a manometer near to each collection point Although this is essential in an industrial context and may be useful in a preparation room such an arrangement may not be appropriate in a workshop used by pupils since they may lack the understanding to control the blast gate settings However it is important that LEV s
62. nd smaller systems or individual units in other teaching rooms Portable power tools used on wood and even sanding by hand can produce considerable amounts of dust As is noted in table 2 extraction from portable power tools is not easy One solution is to use a down draft table sometimes called an air table These are in effect a perforated work top on a stand that has a built in extraction system although some larger types can be connected to a fixed LEV system Provided that they control the amount of dust produced these can be effective and are suitable for use with portable power tools and for hand sanding These tables are not common in schools probably because the space needed is equal to that of a standard workbench Down draft tables should be subject to an annual COSHH check 2 4 Criteria for an LEV specification HSG 258 lists the following criteria that should be included in the quotation from a supplier for any new LEV system The potential supplier should e Provide a technical drawing of the system e State the type of hood for each source of contaminant its location or position in the system the face velocity at the hood and the static pressure e Include information on any constraints on the way in which the system is used e g on the number of extraction points that may be used at any one time e Describe the ducts material used dimensions transport velocity where appropriate and volume flow rates e Incl
63. ndary schools and colleges to meet their legal responsibilities to preserve the health of their employees by the use of local exhaust ventilation LEV systems It is not easy to establish just what standards these systems should meet and how their performance can be checked economically A subsidiary purpose is therefore also to help clarify the daily checks undertaken by the LEV users and the measurements made during the thorough examination and test The guidance presented is based on published advice from the Health and Safety Executive HSE visits to school and college workshops where measurements were made with a dust monitor and photographs taken using a dust lamp and discussions with experienced health and safety advisers The visits showed that e some LEV systems are not well designed e some LEV systems are not supplied with performance data on installation This is necessary so that subsequent testing can be compared with the performance on installation e tests are not being carried out within the statutory 14 month period see section 2 2 e there is considerable uncertainty over which tests are really adequate when contractors use different performance criteria e there is little recognition of the significance of the Workplace Exposure Limits WEL for wood dust see section 3 2 and the consequent requirement to keep levels as low as reasonably practicable e inadequate maintenance often prevents systems from achievin
64. oise is not usually a problem with these small systems Noise is not usually a problem with these small systems Noise is not usually a problem with these systems Noise is not usually a problem with these systems effective provided that it is positioned correctly in relation to the source of fumes The systems remove the fumes produced by rosin cored flux Venting to the atmosphere avoids the need for filters Venting to the atmosphere avoids the need for filters the system will only collect them if all other dampers are closed manually It is then unlikely that the users will return the dampers to their previous settings The filters need regular testing for saturation and changing when necessary The inlet tubes used for tip extraction get blocked and require frequent maintenance Where the system exhausts to the outside air it is necessary to ensure that the outlet is well away from any area where vapour could be inhaled by anyone If filters are used they must be tested regularly for saturation and changed when necessary The air flow rate may not be sufficient to control the contaminant Filters need to be changed regularly according to the manufacturer s instructions In some systems residual fumes can cause discomfort The smell from cutting can be unpleasant even where LEV is used The volume of dust produced can be an issue and will certain
65. onitored by measurements of the flow of air through the system It may be necessary to confirm the direction of flow since the measuring instruments are often insensitive to it by the use of a smoke pencil which will also help to indicate the presence of eddies or other turbulence Measurements of flow rate There are two types of anemometer that are used for measuring air speeds A vane anemometer has a very lightweight vane which looks like a fan This is held perpendicular to the flow so that the air pushes the vane around at a rate dependent on the speed of the air The instrument is calibrated to give a direct reading of the air speed In order to give an accurate reading the flowing air column must be of a diameter arger than that of the vane If measurements are made of the speed of the air flowing into a large aperture hood several readings must be taken at different places so that an average speed can be calculated The calibration of the anemometer should also be checked periodically The volume flow rate can be calculated by multiplying the speed by the area of the aperture or duct A hot wire anemometer has a small probe a few millimetres across containing an electrical component perhaps a wire filament which is heated by an electric current flowing through it If this is placed in an air current the component is cooled by the air flow its electrical resistance changes and the voltage across the component then depends on t
66. or dust extraction It is important that those involved in making decisions about what type of LEV system to install consider the needs of the department the way in which the system is used and the impact that usage will have on teaching and use of machines The main problems are to do with collection of dust and wood shavings from woodworking machines The Health and Safety Executive have published a very detailed guide to the design and operation of LEV systems and some important points from this document are given below 2 2 Guidance from the HSE The HSE has issued several helpful guidance publications Controlling Airborne Contaminates at Work is the most relevant and is discussed below Controlling Airborne Contaminates at Work HSG 258 This book is intended to provide guidance to suppliers of LEV equipment employers and to trade union and employee safety representatives It covers the roles and responsibilities of those involved in the design supply installation and commissioning of LEV equipment and the responsibilities of the employer and the employee who used LEV equipment There are helpful sections on the maintenance and repair of LEV equipment and in the statutory annual examination and test The publication is primarily set in an industrial context and it therefore its application to schools is limited It does however represent best practice A school that is considering the purchase of new LEV equipment should check that the
67. ose to machine casing Inlet side of filter Output side of filter Inlet side of constriction Output side of constriction 36 C Conclusions from examination The following items need further attention E E ATT ATE T E T E T Maaeermcmrneses REASON ada sy ca see ese ea EEKAN K OEP ceca Lar ETENEE EAKA AONE TEREE EVENE maces cane hcadeaeedeay EEN KATEAN TERESE Sia E cael EE E E ucaeeasttacan Gat Gages ea met lenma tua Set AG Saeuth ae Geel a tat PROGSOM Aenima n a n T tesa Sieh caatdesetde cane a la Eia She eT E a a a A a a E O REASOM porroa sonar a E EE E Dea dace E E sn EA E E Melia eee es a E E A AET AEA TE AEA REASON EE AEA OE A IEE EE AER EEA T A AER EE ONE OEE A EAEE AAEE D Final result Possible outcomes The system is performing satisfactorily The system is not performing satisfactorily as detailed above The system should be redesigned as it is unsuitable for the task Work using the system should cease until a satisfactory replacement is installed Signat re of testeta iinn a e i A EE ier A a E a iE aaaeei E Subsequent action The following action has been taken e A E E A A EA BY o eeo ude een E A ARE A tar E a OE e a Ona DECE A tha Pe Als ace sant cates eesyaat ete aceta detent steee anaes asememtcres eben iateees BY e cha ieeuntenueneeneccsseeaketociehaanesta heeds dab ubeouudnmersanennanets Date ere in Sotto ee era nae a ee E aaa E AE E EEEE BY sates Se evade teat eA
68. ow rate with an anemometer at either inlet hoods or outlets although some systems will have small removal plastic plugs in the ducting that can be used to insert a probe Since outlets are usually at or above roof level measurements at these points require safe access to heights As a regular procedure therefore flow rates can often only be measured at the inlets A relatively low air speed e g 2 m s is sufficient to capture most contaminants and sweep them into the duct but a higher speed e g 20 m s is required to keep a solid contaminant suspended in the air flowing along a duct23 This is normally achieved by having a hood with a larger area of cross section than that of the duct with a tapered section to join the hood to the duct To achieve a ten fold increase in linear velocity the area of cross section of the duct must be one tenth of that of the aperture of the inlet hood If the flow rate is measured at the inlet the flow rate in the duct can be estimated by multiplying the measurement by the ratio of the areas In practice once the system has been installed it should be given a commissioning test by the installer see section 6 1 using a dust monitor or other contaminant test as appropriate to show its effectiveness The values of the input flow rates should be recorded In any future tests a 10 change from these initial readings would indicate a problem in the system If the system fails the commissioning test its desi
69. raction unit When the drawer is opened the dust can easily be disturbed by air currents and carried up towards the breathing zone of the person emptying it In other systems the dust is collected in plastic bags so that when they are sufficiently full the top of the bag can be released and sealed with minimum risk of disturbance to the collected dust Clearly this is much safer than handling a drawer containing dust Further potential problems occur once the bag or drawer has been removed The practice of emptying the drawer into a dustbin or into a wheelbarrow which is then taken outside the workplace and tipped into an open skip is unacceptable for three reasons 1 There is a high risk of releasing the dust back into the workplace 2 There is a high risk of the person carrying out the task inhaling the dust 3 Dust blowing out of the open skip presents a hazard to passers by or to neighbours Where plastic bags are used they should be heavy duty to minimise the risk of tearing and releasing dust However these are relatively expensive and to save money D amp T staff have been known to take full bags outside and empty them into skips or other containers so that the bags can be reused This is unacceptable for reasons 2 and 3 above Some educational establishments have offered collected dust to those keeping small mammals as litter for their cages Although some dust collection systems claim to separate fine dust from shavings and co
70. re need to see parts of this guide if they are to make sense of the report forms 34 I Suggested Report on a Commissioning Test of an LEV System A Description of the system Name OF SStADIISMIMGMG sirere Teee ead aaia aiai tiga decet ce nec cre an aa n TEE EMPIOyer arse cise Aachen recs io Ne a cao Ree Base te Dae nee Rove da en een om eatin ane Partie dec bees WORKSHOP EEEE TETEE T hd sais E TTE EAE teeth teat ans he ntestsn sateen tease T T MarnlitaClurer of system irisaren eana a wcatnaresl laaa Ea EA EE EAE nme na dl gown abet calm ia Manufacturer s code or reference for the system usssesseeeerrritttteeeerirrirttrssssitinttnssssttntnnnnnssnseeet Installer of system if different 2iccs 3 ct hati etana aeae A ankaa ra a aa ANARA aana aaa Diagram of the system to be attached Purpose Tick one box Control of wood dust Control of solvent fumes Control of fumes from hot metal working wmo O y o Fixed installation serving all activities simultaneously Fixed installation serving several activities but at a time1 Fixed installation at one work point or machine Portable system serving alternative machines System extracting from one portable power tool 1 Insert only one up to two up to three etc in the space provided B Tests Date l a Name of testing company LEA officer technician eeen Commissioning test Recommissioning test specify reason Cont
71. s Health and safety in the UK is controlled by the Health and Safety at Work etc Act 1974 HSW Act and regulations made under it These are discussed below 3 1 Health and Safety at Work etc Act 1974 Section 2 of the Act places on employers the general duty to ensure the health safety and welfare of all their employees at work so far as is reasonably practicable Section 3 of the Act extends this duty to non employees i e visitors students and pupils School and college staff may be so concerned about these others that the duty to employees takes second place Statistics show that staff of all kinds have more accidents than expected and a number of health problems There are for example instances of teachers and technicians suffering permanent damage to their health as a result of failure to control wood dust However for students and pupils health problems are virtually unknown and serious accidents are rare as a proportion of the number of individuals present Generally the low rate of health problems for pupils is ascribed to the fact that they are exposed to dusts and fumes for only a few hours each week while staff are often in the workshops nearly all day 3 2 COSHH Regulations The Control of Substances Hazardous to Health Regulations are intended to protect the health of persons at work from the substances to which they might be exposed The Regulations have been revised several times since they were introduced in 1988
72. ssure measurements to be made the head of department must know what is expected and be able to confirm that the tests have been done Ensure that all staff know how to use the dust and fume control equipment correctly providing instruction where necessary and documenting this for the benefit of future staff Arrange for frequent e g weekly visual checks of machines systems with LEV to ensure that off cuts chippings or other deposits have not choked the inlet and prevented extraction from working normally On some systems these checks will require the removal of inspection panels and an appropriate dust mask might have to be worn see section 7 1 This should include completion of the record book supplied with the equipment Report to the employer s representative any defects that become evident between tests or any changes in machinery or procedures which may require different collection hoods or even different filtration equipment to be installed Report any symptoms shown by staff or others which might indicate inadequate control of dusts or fumes e g respiratory or skin irritation problems Liase with cleaning staff to ensure that vacuum cleaners can be used effectively e g by reducing clutter and report any defects in cleaning to the person in charge 28 8 4 What all staff should do All staff must cooperate with the employer E g under COSHH Regulation 8 2 it is a criminal offence to omit to use the LEV syste
73. supplier is aware of the requirements in the document and should be able to confirm that any system to be supplied meets those requirements This applies to any LEV system including small portable units as well as large systems with fixed ducting Appendix 2 gives a summary of the requirements Table 2 Fixed installations for whole area serving several machines Independent installations at each machine Portable systems Extraction from portable power tools Different types of LEV 2A Dust collection systems Characteristics Noise o Advantages Disadvantages Inlets at each machine or source possibly with dampers that can be closed when the inlet is not in use Fixed ducting A fixed filter or dust collection system A fan An outlet that might return air to the workplace or vent it to the outside Fan unit is close to the machine producing the dust Fan and machine are often electrically linked so that the fan is powered whenever the machine is running For dust control the filter dust collection system is normally mounted in the same unit as the fan A mobile duct filter dust sack and fan unit which can be moved between machines The inlet may be general purpose or part of each machine A very flexible duct connected to a stand alone dust collector or a small dust bag connected to the tool Depends on design Sound levels greater than 80 dB A make
74. t or the proprietor For local authority schools the employer s representative may be a health amp safety officer D amp T adviser or other official In other establishments it may be the bursar or other person given the duties of overseeing general health amp safety matters 27 10 11 8 3 10 Ensure that arrangements are made for disposal of dust in accordance with the regulations on waste disposal see CLEAPSS publication PS31 Disposal of Waste in Technology Ensure that all records of tests and action taken are filed in a readily accessible place at the school or college with copies filed centrally for LEA establishments Ensure that arrangements are in place to discharge the employer s duty to monitor that dust and fume control systems continue to work correctly What a head of department should do Determine whether the establishment holds records of tests of individual dust and fume control equipment Report to the employer s representative that tests will be due before the date 14 months after the last test Consider the processes involved which produces the most fine dust probably sanding MDF and which produces the greatest amount of fume probably adding degassing tablets to a crucible of molten aluminium Draw to the attention of the employer s representative the need to have tests on LEV systems when the processes identified in 3 are in progress If the employer arranges for flow rate or pre
75. the dust concentration in the breathing zone of the operator will give the most confidence that the dust levels are well below the WEL If this is done at 14 month intervals as required by the COSHH Regulations while the most dusty process is being carried out the employer can demonstrate that the requirement is being met to keep the dust levels as far below the WEL as is reasonably practicable This test method will ensure that the control is maintained even if the process or materials change Records of the air flow rates at inlets and in the 28 Visit the web site www ukas com for further information about the work of this organisation 20 ducts by calculation and static pressures before and after filters will be useful in future tests to identify faults or blockages However the instruments used to perform these tests are expensive to buy and when necessary to maintain Trained personnel are needed and the tests take a long time Consequently measuring dust levels will be expensive It is impracticable for most individual establishments to reduce costs by doing dust level tests themselves but some local authorities operate such a system Second choice procedure Flow rate pressure measurements If a dust control system is given a thorough test as above once either on installation as soon as it has been brought into full use or on introduction of a proper testing regime the commissioning test the records of the air flo
76. tmateaesteae Date 22 se Anak lott taco amare 40
77. ts e g of air flow rates and or measurements of static pressures are likely to be sufficient to show that the system is still performing satisfactorily where there is no change of use Companies offering a testing service have been able to apply for some time to the United Kingdom Accreditation Service for accreditation under UKAS RG4 to show that they supply a quality service The British Occupational Hygiene Society offer two relevant training courses P601 amp P602 Any company offering a testing service should meet the standards of competence of RG4 even if it is not formally accredited In any case it is wise for those using a company offering a testing service to assess the competence of the contractors by asking them to answer certain questions see sections 5 and 8 HSG 258 Controlling Airborne Contaminants at Work contains a section on what should be tested and the types of test to be applied There is also a sample test form This information is included in Appendix 2 When new systems are installed a commissioning test should be carried out and the system checked to see that it conforms to the design specification A copy of the commissioning test should be included in the user manual and this should be used as the reference point for the subsequent annual COSHH test 6 2 Test methods for systems controlling wood dust First choice procedure Dust level measurements An aerosol dust monitor used by a trained operator to measure
78. ude details of how the air flow in different branches of the LEV will be balanced e Describe any air cleaner fitted to the system e g volume flow rate and static pressure ranges at inlet outlet and across the cleaner e Describe the fan or other air mover e g volume flow rate and static pressure at inlet and direction of rotation of fan e For systems that return air to the workplace provide information on air cleaner efficiency and sensors that monitor cleanliness of the air e Describe the indicators and alarms that are to be provided to show that the system is working correctly and which will give an indication of a failure of the system e Describe the commissioning tests to be carried out e Provide adequate training in using checking and maintaining the system e Provide a user manual and a logbook When schools and colleges are buying a new LEV system or when employers are providing a new system care should be taken that all these criteria are applied to the specification Similarly if new buildings are being provided by the employer or under a Private Finance Initiative scheme heads of D amp T should ensure that any LEV system conforms to these criteria Any school that is considering the purchase of off the shelf units should also ensure that the system meets these criteria otherwise there is a risk that contaminants will not be effectively controlled and the health of employees will be put at risk 2 5 Electrical control
79. und sawn or sanded on a machine which has just been used to abrade wood or plastic There are instances of dust in ducting being ignited as a result of ferrous metals being cut or sanded on machines normally used for shaping wood It has also been know for some workers to sharpen wood working tools such as chisels and plane blades on sanding machines which will cause the same problem In any case this is poor practice and should not be done The same LEV system should not be used to handle both flammable dusts and metal particles If plastics are cut the filters should be cleaned and dust collection bags should be changed between the different uses of the machine It is simpler and safer to have separate machines with their own extraction systems or separate workshops There is a theoretical risk of igniting wood dusts if plastics are cut without first emptying the system of wood dust but extensive research by CLEAPSS has yet to find any examples of where this has happened Model Risk Assessments for Design and Technology in Secondary Schools and Colleges e g see Assessments 1 007 and 1 085 5 Solder Fume and You 2002 HSE Books INDG 248 rev Free publication Those with just a layer of gauze held in place with a thin aluminium support are considered to give no protection against toxic wood dust Better d i y shops sell dust masks meeting EU standards that will offer suitable protection see section 7 1 for details 11 3 Legal requirement
80. w rates and or static pressures can be used in future tests As long as the processes and materials used remain the same future tests of the flow rates and or pressures will indicate whether or not the system is still behaving in the same way Such tests could be carried out by trained school staff supplied with appropriate equipment 6 3 Test methods for systems dealing with fume extraction As with dust control ideally the system should be shown to deal with the fumes by testing the concentration of the contaminant in the air being breathed In many situations the major contaminant is carbon dioxide which has a relatively high WEL value i e the concentration can be allowed to rise considerably before it becomes hazardous If all the carbon dioxide is not being collected by the fume extraction system the general ventilation of the workplace will dilute it and help to sweep it away Measuring the carbon dioxide level is therefore not a very effective test of the collection system A smoke pencil provides a reasonably effective check of these systems The other contaminants are released either at low concentrations e g carbon monoxide or in short bursts from the degassing tablets used when melting aluminium Consequently tests of the effectiveness of fume control systems have usually been done using special tracer gases such as sulfur hexafluoride which can be detected at low concentrations However this is inappropriate as a regular test
81. would meet the spirit of the regulation It is the employer s responsibility to ensure that these tests take place at the required intervals and according to an agreed procedure However arrangements for the tests to be carried out could be delegated to the school or college Any such delegation should be in writing and explicit and the employer must monitor that delegated tasks are actually performed When such tests are carried out a copy of the test report should be provided for the school and a copy of this should be held by any department that has LEV equipment in use See also Section 6 for discussion of thorough testing to meet the 14 month requirement It is a general principle that personal protective equipment should only be used as a last resort when other control measures such as LEV are impracticable So a dust mask may be required while emptying dust containers or carrying out maintenance checks but should not be needed during machine operations except in special circumstances see section 7 1 for further information on dust masks 3 3 Other regulations The Control of Lead at Work Regulations apply to certain processes in school and college workshops such as casting lead and its alloys Soldering with small irons and temperature controlled systems does not give rise to significant levels of lead vapour which would be covered by these Regulations but does produce fumes from fluxes which is a matter for the COSHH Regulations
82. ystems in schools are checked regularly by a teacher or technician to ensure that they are functioning correctly and some method of measuring or checking air flow should be available Methods of doing this are discussed in section 4 2 It is important that when an LEV system is tested the person doing the testing understands how the ventilation system is used in practice if tests of its operation are to be realistic If tests are carried out when the regular staff operators are not present it is essential that the tester is given written information on the mode of use of the ventilation system 2 7 Flexible ducting In order to reduce costs flexible ducting is used extensively in educational LEV systems Unfortunately because of its corrugations it presents a greater resistance to the flow of air than smooth pipes To achieve a given performance a more powerful fan is required to make the air flow through long lengths of flexible ducting Flexible ducting is also more easily damaged than rigid ducting A well designed system therefore uses only short lengths of flexible ducting which are as straight as possible with bends being formed out of rigid pipes 2 8 Individual extraction units Individual dust extraction units may be used in some situations where the cost of a ducted system cannot be justified These vary in quality and may range from a simple vacuum cleaner to a high quality unit enclosed within a steel casing Some of these units can