Home
ArmorStart LT Distributed Motor Control - Full Voltage
Contents
1. 3 1 02 REFERENGES eileen ie in eke eh a eos 3 1 03 ENVIRONMENTAL REQUIREMENTS 2 1 6 6 4 1 44 PRE MANUFACTURE 5 0 66 4 1 05 FINAL 5 00 00 0 2 a 4 5 2 01 DESGRIP TION 55 5 2 02 RATING S ee eal Be ke td ds ek aA tA ee aN 5 2 03 55 4 6 2 04 COMMUNICATIONS 7 2 05 7 2 06 FUNCTIONS 8 2 07 DETAILED SPECIA CAT O N r 9 2 08 DIMENSIONS AND 10 2 52 10 3 01 DELIVERY STORAGE AND 2 1 0 00 10 3 02 INSTALLATION T NE ANE TO TS 10 3 03 SPARE MATERIALS a 11 3 04
2. 25 11 Rockwell Automation Bulletin 290 291 ArmorStart LT DMC 2 290 SR001A EN P PROJECT NUMBER PROJECT NAME DATE PROJECT LOCATION SECTION XX XX XX DISTRIBUTED MOTOR CONTROL WITH FULL VOLTAGE FULL VOLTAGE REVERSING MOTOR STARTING PART 1 GENERAL 1 01 QUALIFICATIONS A Manufacturer 1 The manufacturer shall have a minimum of 25 years of experience in the manufacture of distributed motor control 2 The approved manufacturers are a Rockwell Automation Allen Bradley b Substitutions None permitted B Support 1 The manufacturer shall maintain factory trained and authorized service facilities within 100 miles of the project and shall have a demonstrated record of service for at least the previous ten years 2 Support personnel are to be direct employees of the manufacturer and be available 24 hours per day through a toll free number 3 The manufacturer shall provide all required start up and training services 4 The approved manufacturers are a Rockwell Automation Customer Support amp Maintenance b Substitutions None permitted C Certification 1 To ensure all quality and corrective action procedures are documented and implemented all manufacturing locations shall be certified to the ISO 9001 Series of Quality Standards 2 Third party manufacturers and brand labeling shall not be allowed 1 02 R
3. 6 10 Class 1 Connection API 2 to 3200 ms 11 Class 3 Connection API 100 to 10 000 ms 12 Request Packet Interval RPI 20 ms default 2 ms minimum Bulletin 290 291 ArmorStart LT DMC Rockwell Automation 290 SR001A EN P 9 PROJECT NUMBER PROJECT NAME DATE PROJECT LOCATION C DeviceNet versions DeviceNet Supply Voltage Rating Range 11 to 25 VDC 24 VDC nominal DeviceNet Input Current 50 mA 24 VDC DeviceNet Input Current Surge 500 mA peak inrush Baud Rates 125 250 500 kbps Distance Maximum a 500 1630 ft 125 kbps b 200 m 656 ft 250 kbps c 100 m 328 ft 500 kbps 6 Auto Baud Rate Identification Yes 7 Group 2 Slave Only Device Type Yes 8 Polled I O Messaging Yes 9 Change of State Messaging Yes 10 Cyclic Messaging Yes 11 Explicit Messaging Yes 12 Full Parameter Object Support Yes 13 Group 4 Off Line Node Recovery Messaging Yes 14 Configuring Consistency Value Yes 15 Unconnected Messaging Manager UCMN Yes 2 08 DIMENSIONS AND WEIGHT A The dimensions of the distributed motor control DMC shall not exceed 217 8 mm B 8 6 in height x 260 mm 10 2 in width x 166 5 mm 6 6 in depth The approximate weight of the DMC shall be 4 6 kg 10 Ib PART 3 EXECUTION 3 01 DELIVERY STORAGE AND HANDLING A B The supplier shall coordinate the shipping of equipment The supplier shall store the equipment in a clean and dry spa
4. PROJECT NUMBER PROJECT NAME DATE PROJECT LOCATION ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION Bulletin 290 291 ArmorStart LT Distributed Motor Control with Full Voltage Full Voltage Reversing Motor Starting NOTICE The specification guidelines in this document are intended to aid in the specification of products Specific installations have specific requirements and Rockwell Automation does not recommend or intend any specific application based solely upon the guidelines provided here Because of the variety of uses for this information the user of and those responsible for applying this information are responsible for ensuring the acceptability of each application and appropriate use of the guidelines In no event will Rockwell Automation be liable for misuse misapplication or reliance on these guidelines in connection with any specific application Rockwell Automation also disclaims indirect or consequential damages resulting from the use or application of this information Note To download or view a doc file version of this procurement specification please visit www rockwellautomation com industries procurement specifications Bulletin 290 291 ArmorStart LT DMC Rockwell Automation 290 SR001A EN P 1 PROJECT NUMBER PROJECT NAME DATE PROJECT LOCATION TABLE OF CONTENTS PART JH GENERAU 5255553 e 3 1201 QUALIPIGATIONS
5. local distributor for the spare parts ONL PART 2 PRODUCTS 2 01 DESCRIPTION A Allen Bradley Bulletin 290 291 ArmorStart LT Distributed Motor Control with Full Voltage Full Voltage Reversing Motor Starting No substitutions 2 02 RATINGS A The distributed motor control DMC shall support a three phase induction motor DMC power circuit ratings 1 Horsepower range of 0 5 to 2 HP or 3 to 5 HP 2 Operating voltage of 400Y 230 to 480Y 277 VAC 15 10 3 Operating frequency of 50 60 Hz 10 The DMC shall accept 24 VDC control power externally or through an internal power supply and have an operating range of 20 4 to 26 4 VDC The DMC shall have a minimum SCCR of 10 kA 480Y 277 VAC The DMC shall be equipped with a Short Circuit Protection Device SCPD The DMC shall be UL Listed for Group Motor Applications sized per NFPA 70 NEC or NFPA 79 The DMC s environmental ratings include O O W m Enclosure rating of Type 4 or Type 4 12 and IP66 Operating temperature range of 20 to 50 C 4 to 122 F Relative humidity range of 0 to 95 non condensing Operating shock resistance to 30 G exceeds IEC 60947 1 Operating vibration resistance to 2 5 G MIL STD 810G exceeds IEC 60947 1 Ability to operate without de rating to an elevation of 2000 m Application in Pollution Degree 3 environments O O A OI N Bulletin 290 291 ArmorStart LT DMC Rockwell Automation 290 SR001A EN P 5 PROJECT NUMBE
6. 0 100mb s embedded Ethernet switch that supports linear star or device level ring DLR topology 3 EtherNet IP addressing shall be by N a Auto addressing via DHCP utility b Local node switch c Static IP address The EtherNet IP DMC shall support the IEEE 1588 transparent clock The EtherNet IP DMC shall support DeviceLogix which allows local control using simple embedded logic Fis B DeviceNet versions 1 DeviceNet versions of the distributed motor control DMC shall allow efficient data handling on the device level DeviceNet network 2 DeviceNet addressing shall be by a Hard set node address switches b Software node addressing 3 The DeviceNet DMC shall support DeviceLogix which allows local control using simple embedded logic 4 The DeviceNet DMC shall provide peer to peer zone interlocking parameters ZIP to allow direct communication with up to 4 other DeviceNet nodes 2 05 CONFIGURATION distributed motor control DMC shall have the capability to be programmed by 1 Add On Profile AOP for CompactLogix and ControlLogix Controllers The AOP is used for the Logix Designer programming tool in Studio 5000 software which is a single control platform The AOP simplifies setup and commissioning via predefined tags and commissioning wizards and allows automatic tag generation and copy and paste functionality for quick setup and configuration of multiple DMCs The Logix Designer programming
7. EFERENCES A distributed motor control shall be designed to meet or exceed the applicable requirements to comply with the standards 1 UL CSA a UL 508 Industrial Control Equipment Suitable for Group Installation CSA C22 2 14 Bulletin 290 291 ArmorStart LT DMC Rockwell Automation 290 SR001A EN P 3 PROJECT NUMBER PROJECT NAME DATE B PROJECT LOCATION 2 EN IEC a EN 60947 4 1 Low Voltage Switchgear b CE Marked per Low Voltage Directive 2006 95 EC and EMC Directive 2004 108 EC 3 CCC 4 KCC 5 6 ODVA for EtherNet IP and DeviceNet The distributed motor control shall be certified cULus File No E3125 Guide NLDX NLDX7 1 03 ENVIRONMENTAL REQUIREMENTS A B The supplier shall confirm specified service conditions during and after installation of products The supplier shall maintain the area free of dirt and dust during and after installation of products 1 04 PRE MANUFACTURE SUBMITTALS A B Refer to Section for submittal procedures Product Data 1 Publications on distributed motor control 2 Data sheets on all furnished options Specification Response 1 Detailed response to this specification showing where in the literature each requirement is satisfied 2 Clearly identified clarifications and exceptions Installation Instructions 1 A copy of the manufacturer s installation instructions including receiving handling and storage instructio
8. R PROJECT NAME DATE PROJECT LOCATION 2 03 CONSTRUCTION A The distributed motor control DMC shall have a compact footprint single box construction and offer direct on line DOL or direct on line reversing DOLR control of a three phase AC squirrel cage induction motor B The DMC shall be designed for EtherNet IP or DeviceNet network support C The DMC shall provide a local lockable disconnect that supports a Lockout Tagout LOTO provision D All connections shall be made from the bottom of the unit 1 3 power control power and motor connections shall be made via a gland plate a Conduit cord ready power options with 3 4 and 1 in conduit holes i Trunk and drop ii Daisy chain b ArmorConnect media option The media shall be i produced by the DMC manufacturer or ii UL 2237 and approved for use by the DMC manufacturer 2 The DMC shall support two 10 AWG conductors for power and control stranded and solid copper 3 DMC shall provide fixed pipe or cord power connectivity or quick disconnect power features meeting UL 2238 for incoming control power 4 The DMC shall provide fixed pipe or cord power connectivity or quick disconnect power features meeting UL 2237 for AC motor connection 5 The DMC shall have quick connection for the network 6 The DMC shall have 12 mm 5 pin micro quick connection for inputs and outputs 7 The DMC shall have internal and external protective earth co
9. ce C The supplier shall protect the units from dirt water construction debris and traffic 3 02 INSTALLATION A The supplier shall verify all distributed motor control components have been installed not exceeding the specifications or with proper derating prior to energizing B The supplier shall follow local code and regulations with regard to electrical installation C The supplier shall provide reasonable protection against accidental damage to component and associated cables D The supplier shall ensure accessibility to diagnostic lights communication ports and connection These components shall be free from obstruction at all times E The supplier shall verify all distributed motor control settings have been properly adjusted prior to energizing Rockwell Automation Bulletin 290 291 ArmorStart LT DMC 10 290 SR001A EN P PROJECT NUMBER PROJECT NAME DATE PROJECT LOCATION 3 03 SPARE MATERIALS A The supplier shall provide one 1 spare distributed motor control of each size utilized including options 3 04 WARRANTY A The manufacturer shall provide their standard parts warranty for eighteen 18 months from the date of shipment or twelve 12 months from the date of being energized whichever occurs first B The manufacturer shall confirm this warranty as part of the submittal END OF SECTION Rockwell Automation Rockwell Software Allen Bradley ArmorConnect ArmorStart DeviceLogix RSNetWorx and St
10. nnections E An internal power supply IPS shall eliminate the need for separate control power and I O power option F The electronic control module ECM shall include externally accessible node address switches a local fault reset button and status and diagnostic LEDs that include the following Power status Network status Run Fault status I O status Module status EtherNet IP versions Link status EtherNet IP versions DARON G The DMC shall have local control option with field disable capability except OFF 1 HAND OFF AUTO keypad DOL 2 FORWARD REVERSE OFF AUTO keypad DOLR Rockwell Automation Bulletin 290 291 ArmorStart LT DMC 6 290 SR001A EN P PROJECT NUMBER PROJECT NAME DATE PROJECT LOCATION H The DMC shall offer 6 user configurable I O points to be used with sensors actuators 1 24 VDC nominal 0 5 A outputs per point max 1 5 total outputs 2 24 VDC nominal 50 mA input per point 300 mA total inputs 3 Outputs shall satisfy DC1 and DC13 utilization category 4 The DMC shall have integrated suppression to protect output from switching loads 2 04 COMMUNICATIONS OPTIONS A EtherNet IP versions 1 EtherNet IP versions of the distributed motor control DMC shall allow the integration of I O control device configuration and data collection across multiple networks enabling internet connectivity The EtherNet IP DMC shall include a dual port 1
11. ns Testing and Test Reports 1 Testing per manufacturer s standard 2 A copy of the test reports if available shall be provided as part of the final documentation 1 05 FINAL SUBMITTALS A Refer to Section for procedure on submittal of final documentation B Supplier Certification 1 supplier shall provide certification that the distributed motor control has been installed in accordance with the manufacturer s instructions Rockwell Automation Bulletin 290 291 ArmorStart LT DMC 4 290 SR001A EN P PROJECT NUMBER PROJECT NAME DATE PROJECT LOCATION 2 The supplier shall provide certification that the distributed motor control settings have been properly adjusted C Final Drawings 1 manufacturer shall provide final drawings reflecting the state of the installed equipment 2 Manufacturer drawings shall be provided in DWG format 3 Manufacturer drawings do not need to be stamped if a drawing schedule is provided that lists the drawing numbers revision levels and status of drawings Preliminary Approval Final etc 4 supplier shall be responsible for making any changes to the As Shipped drawings from the manufacturer to reflect any field modifications D Maintenance Data Distributed motor control installation instructions and User Manual Parameter listing with final settings Field service report from start up service Name and phone number for a
12. rt LT DMC 8 290 SR001A EN P PROJECT NUMBER PROJECT NAME DATE PROJECT LOCATION D Device status parameters shall include CONDOaARWNM Phase L1 Current Phase L2 Current Phase L3 Current Average Current Percent Thermal Utilized Starter Status Starter Command Auxiliary I O Status Network Status Trip Status Warning Status Trip Log 0 4 Diagnostic Snap Shot L1 L2 L3 Amps and percent thermal E Basic configuration parameters shall include 1 2 3 FLA Setting OL Reset Level Overload Class 2 07 DETAILED SPECIFICATION A All versions Oe ONS Rated Impulsed Voltage 4 kV Dielectric Withstand UL 1960 VAC IEC 2500 VAC Reset Mode Automatic or manual Overload Reset Level 1 to 100 TCU Overvoltage Category III EtherNet IP versions 1 EtherNet IP ODVA Conformance Testing EtherNet IP Interoperability Performance Per 9 PF 2 1 2 Ethernet Communication Rate 10 100 Mbps auto negotiate half and full duplex 3 Ethernet Ports 2 embedded switch 4 Device Level Ring Support Beacon Performance IEEE 1588 Transparent Clock 5 Data Transported over both TCP and UDP 6 Packet Rate pps a 500 packets per second 2000 us Tx b 500 packets per second 2000 us Rx 7 Message Support Unicast or Multicast 8 Address Conflict Detection ACD IP v4 Address Conflict Detection for EtherNet IP devices 9 Maximum Concurrent Explicit Messages CIP Class 3
13. tool is also used by the DMC s DeviceLogix program to perform configuration locally Bulletin 290 291 ArmorStart LT DMC Rockwell Automation 290 SR001A EN P 7 PROJECT NUMBER PROJECT NAME DATE PROJECT LOCATION 2 RSNetWorx For the DeviceNet version the device configuration tool RSNetWorx can configure the DMC using the embedded electronic data sheet EDS 3 Internal Webpage For the EtherNet IP version the DMC s web interface can be used to configure the DMC when the AOP is not available B The DMC s embedded web server shall be able to be configured for Login and password protection Sending an e mail when a fault or warning occurs E mail supports Simple Mail Transfer Protocol SMTP 3 Uploading EDS files 4 Status and diagnostics read write 5 Administrative tasks N 2 06 FUNCTIONS A Motor control shall be 1 0 5 2 HP AC squirrel cage induction motor 2 3 5 HP AC squirrel cage induction motor Electronic motor overload protection shall be accomplished with an 121 algorithm 1 Solid state overload a 2 current setting of 0 24 A to 3 5 b 5HP current setting of 1 1 A to 7 6 A 2 Selectable trip class of 10 15 or 20 C Fault diagnostics shall include Overload Phase Loss Under Power Sensor Short Phase Imbalance NonVolatile Memory Jam Stall Underload 0 Output Short DONO Rockwell Automation Bulletin 290 291 ArmorSta
14. udio 5000 are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Bulletin 290 291 ArmorStart LT DMC Rockwell Automation 290 SR001A EN P 11