K-BUS R Universal Interfaces, 4fold User manual
Contents
1. 6 4 2 Description of setting the system parameter in part of device channel 6 4 2 1 Parameter window General Setting 7 4 2 2 Parameter window Switch X 8 4 2 3 Parameter window Switch dimming X 13 4 2 4 Parameter window Value force output X 16 4 2 5 Parameter window Scene control X 18 4 2 6 Parameter window Switching sequence X 23 4 2 7 Parameter window Counter X 25 4 2 8 Parameter window Multiple operation X 29 4 2 9 Parameter window Shutter control X 32 4 3 Description of setting the system parameter in part of LED channel 35 4 3 1 Parameter window Flashing X 35 4 3 2 Parameter window Switch X
2. 46 5 9 Communication object LED X flashing 47 5 10 Communication object LED X SWITCH 48 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com 1 General The Universal Interfaces can install to be system with EIB KNX bus and other device which are mainly use in building control system The functions are both simple to operate and intuitive users can program it according to the requirement to implement the function systematically This manual provides technical information about the Universal Interfaces in detail for users as well as assembly and programming and explains how to use the Universal Interfaces by the application examples 1 1 Product and functional overview The Universal Interfaces achieve the functional applications via conventional push buttons switches communicate by technical binary which are used to control the devices such as the Dimmer Actuator the Relay Actuator to control domestic appliance indirectly At the same time they also enable the control of LEDs The extremely compact design enables the device to be inserted in a conventional 60 mm wiring box The Universal Interfaces connect to the bus though the EIB connection terminals and have no us
3. This parameter defines the value which is sent on operation The value range is dependent on the selected data type Two values can be set here when there is a distinction between a short and long operation Parameter Long operation after Basex Factor 0 255 This parameter is visible if there is a distinction between a short and long operation The period TL is defined here after which an operation is interpreted as long TL Base x Factor Base options 100s Is lh Factor options 2 255 Parameter Send object value after voltage recovery This parameter defines whether to send object value of Tele Value X on the bus after the voltage recovery This parameter is visible if there is no distinction between a short and long operation If yes is selected the device sends the object Tele Value X on the bus after bus voltage recovery Options Yes No Parameter Debounce time It can set the vibration time to prevent unwanted multiple operation by bouncing of contacts in vibration time which means the effective time of the contact operation Options 10ms 20ms Min operation A minimum operation time can only be set if there is no distinction between a short and long operation The parameter window will be shown in Fig 3 4 2 5 Parameter window Scene control X Parameter window Scene control X will be shown in Fig 8 it will be visible when the function channe
4. 36 4 3 3 Parameter window Control by input X 38 4 3 4 Parameter window Indicate object in X 38 4 3 5 Parameter window Indicate object out X 39 4 3 6 Parameter window Indicate object in and out X 40 5 Description of communication object 22 2220 22022 2220022222222 42 5 1 Communication object swicth 42 5 2 Communication object switch dimming 43 5 3 Communication object value force output 43 5 4 Communication object scene control 44 5 5 Communication object switch sequence 44 5 6 Communication object counter 45 5 7 Communication object multiple operation 46 5 8 Communication object shutter control
5. 65535 32bit 2147483648 2147483647 Parameter Counter starts at The starting value of the absolute counter is defined in this parameter When the bus power on it will calculate the new counter value from this preset starting value Parameter Debounce time It can set the vibration time to prevent unwanted multiple operation by bouncing of contacts in vibration time which means the effective time of the contact operation Options 10ms 20ms Min operation The parameter window Min operation will be shown in Fig 3 Parameter Send object value after voltage recovery This parameter defines whether to send the current value when the bus voltage recovery If the differential counter has been enabled it is also sent on the bus and it is reset to zero If the bus voltage failure the standard counter and the differential counter are reset to the starting value the standard counter will calculate from the 27 em EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com preset starting value Options Yes No Parameter Enable additional options factor divider Cyclical send Additional functions are possible here If this parameter is set to yes the parameter window Fig 13 is displayed Options Yes No 1 1 1 Univerzal Interfaces 4 fold General Setting Counter A Channel
6. EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI RR with an operation step by step Each object corresponding to one switch level Humber Hame Object Function Deser Group Addresses Le C Yo IT U Data Type Pro a0 EPEC iia ii iii iii Fe re ae ae nee E P EE gree om si ccnssssansescnsecnsiananndencseaseee eee a a zssSUllcscthCccereststea Ds aasssnccnmeeassantsicbere a one oa cae simian 7 7 krasane mz Qutput leyvyel 2 A CH A level 2 i bit CE I Low m3 Qutput level 3 A CH A level i bit CE I Low Hija Qutput level 4 A CH A level 4 l bt C T Low gs Qutput level 5 A CH A level 5 i bit CE I Low mis Level increment decrement A CH A Level increment decrement l bit C W Low Fig 5 5 Communication object Switching sequence The number of the communication object maximum 5 which the levels of switch set by parameter No of object The communication object sent on bus is the object which is modified which the value of the communication object had been changed The detail process will be described in the switching sequence parameter chapter A CH X level increment decrement level increment decrement X The communication object level increment decrement X is used to increase decrease the level of the switch It will increase one leve
7. U means that value response telegrams are interpreted as a write command the value of the object is updated When enable the channel function this communication object will be active to disable enable the channel function The communication object will disable this function if receive a telegram with logic value 0 while it will enable the channel function if receive a telegram 1 The control telegram sent by all objects are ineffectiveness when the channel function disable The channel function default to enable when the bus voltage recovery All communication object Disable in channel function operate equally This communication object is visible if the channel function Switch is enable It is visible no matter to distinguish short long operation or not Operate with button input or a short operation the object value to carry out the relevant action such as ON OFF TOGGLE This communication object is visible if parameter Number of objects for short long object operation is 2 objects and it is distinguish with long and short operation Operate with a long operation to input the object value to carry out the relevant action such as ON OFF TOGGLE Form 1 Communication object Switch 42 eee won EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qs
8. E read out the telegram The objects Output Ibit 8bit group A E can be modified via the bus for the duration of the long operation After the end of the long operation the object values can t be modified the object store scene X will send value 0 On the long operation If the object Store scene X receives the value 0 on the bus even the long operation has not finished the current object value also can t be modified Provided that a 1 has not been received at the object Store scene X a long operation is interpreted in the same way as a short operation 21 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SURPOWER z ea GR Control the scene via 8 bit scene On long operation After a long operation the object 8 bit scene sends a save command on the bus and thereby triggers the storing of the current scene in the actuators e g dimming actuator switch actuator If object value 1 If the object Store scene X receives the value 1 the object 8 bit scene sends a save command on the bus and save the current scene On long operation and object value 1 If the object Store scene X receives the value 1 on the bus the next long push button action triggers the sending of a save command
9. Tele Status selected Yes it is used to send the status of LED Sending 1 means LED open and sending 0 means the LED is stop The object LED switch X will send telegram 1 if sending open requirement every time Form 10 Communication object LED X Switch 48 E EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com
10. Transmission cycle time Basex Factor Base options 1s 10s lh Factor options 1 255 Parameter Enable different counter This parameter defines whether to enable the differential counter function if Yes is selected it will enable Options Yes No Parameter Over under run of differential at This parameter is visible if the parameter Enable differential counter is set to yes It can be set in this parameter which value generates an overflow of the differential counter The overflow object will send an overflow value 1 on the bus when in the event of an overflow Note Counting rule take 16bit 32768 32767 for example the standard counter starts at 2500 When the factor is negative then counting in reverse the count direction for the standard counter is from 2500 to 32768 the count direction for the differential counter is from 0 to 32768 when the factor is positive counting forward the count direction for the standard counter is from 2500 to 32767 the count direction for the differential counter is from 0 to 32767 The counting rule is similar between the differential counter and the standard counter The difference is that the differential counter can set the overflow value When the differential counter overflow occurs then the current count value the count value the overflow value 4 2 8 Parameter window Multiple operation X The parameter window Mu
11. CH X Upper limit Upper limit position X position It is used to limit the upper moving It is limit the upper moving if the object receive a logic value 1 and negate it if receive 0 CH X Lower limit Lower limit position X position It is used to limit the lower moving It is limit the lower moving if the object receive a logic value 1 and negate it if receive 0 Form 8 Communication object Shutter control 5 9 Communication object LED X flashing The communication object LED X Flashing will be shown in Fig 5 9 Humber Hame Object Function Deser group Addresses Le C R W T Uj Data Type Fr zs LED flashing A LED A Flashing li bit C E Low mies LED permanent on A LED A Permanent on i bit C HH Low qjao Send its status A LED A Send its status Lit C TPT Low Fig 5 9 Communication object LED X Flashing It is used to control the LED flashing It will start flashing if receive 1 or 0 telegram defines by LED flashing if the flashing time set by parameter And it will stop LED if receive 0 or 1 It is used to open LED for a long period and its priority is higher than the communication object LED Flashing X It will open LED if receive telegram 1 negate priority and the LED resume the foregoing operation if receive 0 It is visible if Send status by object Tele Status selected Yes i
12. Channel D 1 255 LED 4 LED E LED C LED D Info Fig 3 Parameter window X Mini Time Parameter Minimum operation time Base x Factor The effective time of the contact operation is Base x Factor Base options 100ms Imin Factor options 1 255 Note The parameter window and the explanation of parameter Min operation in the Debounce time in the below chapters are the same with here 11 a EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe Ea GR 1 1 1 Universal Interfaces 4 fold General Setting Channel Channel B Channel C Function of the channel Channel D Distinction between long and LED 4 short operation LED B LED C Connect contact type normally oper LED D Reaction on short operation OFF Reaction on long operation no action Long operation after Base lt co ire 4 Factor 255 Number of objects for short long object operation Tabject LED function set LED amp accord to switch value Debounce time Rims Fig 4 Parameter window Switch X distinguish between a short and long operation Parameter Connect contact type This parameter is visible when there is a distinction between a short and long operation it is used to define whether the contact is a normally open contact or
13. Control by input X will be shown in Fig 18 the LED is used to indicate the button input 1 1 1 Universal Interfaces 4 fold General Setting Channel 4 Channel E IF LED function i enable in input Channel C this must chose Control by put lt NOTE Information Channel D LED A Function of the LED Channel LED B LED C LED D Default Info Fig 18 Parameter window Control by input X 4 3 4 Parameter window Indicate object in X The parameter window Indicate object in X will be shown in Fig 19 the LED is used to indicate the input of the communication object 38 s U EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com 1 1 1 Universal Interfaces 4 fold General Setting Channel A plone LED function ig enable in input Channel C this must chose Control by rout lt NOTE Information Channel D LED 4 Function of the LED Channel Indicate Object In LED B LEDC LED on time LED D Info Fig 19 Parameter window Indicate object X Parameter LED on time This parameter defines the indicative time of LED when there is input of communication object which means the switch on time Options 100ms 200ms 4 3 5 Parameter window Indicate object out X The parameter window Indicate object out X will be shown in Fig 20 the LED is used to indicate
14. Interfaces General Setting Channel 4 Channel B Channel C Channel D LED 4 LED B LED C LED D 4 fold Function of the channel Connect contact type Mo of objects Type of swiching sequence Function on operation Sequence i 000 001 011 111 Debounce timetlin Time Fig 11 Parameter window switching sequence X Parameter Connect contact type Sequentially on otfseveral push buttons w Switch upwards NOTE Information Pms This parameter defines whether the contact at the input is a normally open contact or a normally closed contact Options Normally open Normally closed The parameter introduced in this chapter is use Normally open as the example the normally close is just opposite Parameter No of objects This parameter defines the number of objects which is the number of levels it is identical to the number of communication objects Options 2level 3level 4level Slevel For example parameter 3level means there are 3 communication objects level 1 level 2 level 3 The first operation modified the value of level 1 the second operation modified the value of level 2 the third operation modified the value of level 3 the fourth from modified the value of level 3 the switch sequence is 000 001 011 111 011 saan The data send on the bus is the value of the communication object that after modif
15. Preset value actuator group C 0 0 FF 0N Control of actuator group D by 1 bit object Preset value actuator group O 0 0 Fe 0N o lt Control of actuator group E by bit object Preset value actuator group E 0 0 FF 0N Fig 10 Parameter window Scene X Parameter window Scene X The parameter window Scene X will be shown in Fig 10 it is visible if the control of the light scenes is carried out via 5 separate objects Parameter Control of actuator group A E It can be set for each actuator group whether the control is carried out via a 1 bit object or an 8 bit object Options 1 bit object 8 bit object Parameter Preset value actuator group A E This parameter set the preset value of the actuator group This value can be modified via the bus when save the scene If the bus voltage recovery this value will be modified as preset value 4 2 6 Parameter window Switching sequence X The parameter window Switching sequence will be shown in Fig 11 It is visible if the input is operated with the function Switching sequence A switching sequence enables the stepwise modification of several values via a single operation 23 E EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER 1 1 1 Universal
16. down set by parameter 2 push button stepping Operation Stop Adjust upward or Stop Adjust downward set by parameter keep pressing the button can send cyclic 2 switch operation moving shutter Operation start Move up or Move down set by parameter Operation end Stop Adjust upward or Stop Adjust downward the sending value is identical to the value that the operation starting 33 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe Ea GR Parameter Tele STOP adjust adj Cyclical send It is visible if the shutter control type is l push button short moving long stepping and 2 push button stepping It is able to set the interval time of sending the object stop adjust adj cyclical Options 0 3s 0 5s 10s Parameter Reaction on short operation It is visible if the shutter control type is 2 push button standard This parameter defines the operation with short operation Options Stop adjust up Stop adjust down Parameter Reaction on long operation It is visible if the shutter control type is 2 push button standard This parameter defines the operation with long operation Options Move up Move down Parameter Reaction on operation It is visible if the shutt
17. ea GR 5 2 Communication object switch dimming Humber Hame Object Function Descr Group Addresses Le B Y T WU Data Type Fr iia TERPIN Mii E E EA perua ee eT pias ee E re a A So E E EE E ET o A E cit S ee E Se i o aoe ae TEET SEENI seo 3 S G2 Dimming A CH A Dimming 4t bit C I Low Fig 5 2 Communication object Switch dimming It is visible if parameter Dimming functionality selected Dimming and switching Operate with a short operation to input the object value to carry out the relevant action such as ON OFF TOGGLE This communication object input by a long operation to send the command to dim up or dim down It can control the dimming device on bus to carry out relative dimming It will send a stop command to stop dimming when the long operation is end Form 2 Communication object Switch dimming 5 3 Communication object value force output There are many data types and communication objects it will not list in Fig 5 3 This different data types communication object have the same operation that are transmit the input object value which the range of transmit object value are different It is possible to distinguish a long short operation or not the two objects enable when distinguished Humber Hame Object Function Descr Group Addresses Le C Y T U Data Type Pr of TETEE neh gaat a a allan E E EEE ae ae i E EE aa P AEE AAE ET A TEE N NEE EEE ee een A en i ae ee ae seam
18. objects 20 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe Ea KR Parameter value Behaviour On long operation As soon as a long operation is detected the object Store scene X sends the value 1 on the bus and the object Output I bit 8bit group A E send read out telegram The objects Output Ilbit 8bit group A E can be modified via the bus for the duration of the long operation Once the long operation has finished the objectStore scene X sends the value 0 on the bus and the current object values can t be modified On the long operation If the object Store scene X receives the value 0 on the bus even the long operation has not finished the current object value also can t be modified If object value 1 If the object Store scene X receives the value 1 the object values Output 1bit 8bit group A E are read out via the bus While the object value is 1 the objects Output lbit 8bit group A E can be modified via the bus On receipt of the object value 0 the current object values can t be modified On long operation and object value 1 If the object Store scene X receives the value 1 on the bus on the next long operation the object Output 1bit 8bit group A
19. via the object 8 bit scene the current scene will be saved When the object store scene X receives the value 0 end up the saving the value of current scene Provided that a 1 has not been received at the object Store scene since the last save a long Operation is interpreted in the same way as a short operation Parameter Long operation after This parameter is visible when the parameter Store scene 1s On long operation or On long operation and object value 1 it is defines the period here after which an operation is interpreted as long Options 0 3s 0 5s Parameter Debounce time It can set the vibration time to prevent unwanted multiple operation by bouncing of contacts in vibration time that means the effective time of the contact operation Options 10ms 20ms 22 eon EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI GR 1 1 1 Universal Interfaces 4 fold General Setting Channel Channel B Control of actuator group 4 by 1 bit object Channel C Preset value actuator group 4 Channel D o 0 FF 0N LED 4 FOR Control of actuator group B by bit object pines Preset value actuator group B LED D 0 0FF oll UN a o Control of actuator group C by bit object
20. 4 Counter Divider number of input pulse for Channel B one counter stepli 3276r Channel C Factorone counter step changes Channel D counter value by 32768 32767 LED 4 LEC E Send counter value cyclically LED C LEDD Base Factor 1 255 Enable differential counter Fig 13 Parameter window Counter X Parameter Divider number of input pulse for one counter step 1 32767 It can be set via this parameter how many pulses are necessary to generate a counting pulse The range of pulse importability 1 32767 Parameter Factor one counter step changes counter value by 32768 32767 This parameter defines how much the counter and differential counter should be increased by in the event of a counting pulse Range 32768 32767 Parameter Send counter value cyclically This parameter defines whether to send the current value cyclically If this parameter has the value yes the values of the counter and the differential counter are sent cyclically on the bus Options Yes 28 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com POWER S m Parameter Base Factor 1 255 It is visible if the parameter Send counter value cyclically is Yes This parameter is used to set the interval time between two telegrams that are sent cyclically
21. EUROPOWER Ge EIJ KNX K BUS Universal Interfaces 4fold User manual Ver 1 KI U 0401 1 KNX EIB Intelligent Installation Systems K BUS 1 KI U 0401 1 C IIR 4 ti DE Ys 7 o ooo iY J 3 3 i K BUS i 1 1 KI U 0401 1 _Un 20V 0 EIJ KN CE EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI GR Contents 1 General 2 222 222 2200 2 20002 nn nee nn nnn ne nnn enna nen n nn enn ne een nn cnn ne eeneeecesee 3 1 1 Product and functional overview 3 2 Technical data 00 22000220002 nn nnn nn nnn en nen en nee nnneeenneeceneeenneeee 4 3 Dimension and Connection diagram 222 002 0222 2 eee e nnn n nee ee nee eee 5 3 1 Dimension drawing 5 3 2 Connection diagram 5 4 Project design and programming 22220 20022 2 220 ee nnn e eee eee e eee 6 4 1 Overview of the functions
22. RPOWER z ma GR following table 1 push button short stepping long moving Short operation Alternate implement Stop Adjust upward or Stop Adjust downward operation alternate send the value of the object 0 and 1 Long operation Alternate implement Move up or Move down operation alternate send the value of the object 0 and 1 l push button short moving long stepping Short operation Alternate implement Move up or Move down operation alternate send the value of the object 0 and 1 Long operation Alternate implement Stop Adjust upward or Stop Adjust downward operation alternate send the value of the object 0 and 1 1 push button operation moving Operation When operation send the command in sequence gt Move up gt Stop Adjust upward gt Move down gt Stop Adjust downward gt 1 switch operation moving Operation start Alternate implement Move up or Move down operation press the button alternate send the value of the object 0 and 1 Operation end Stop Adjust Release the button 2 push button standard Short operation Stop Adjust upward or Stop Adjust downward set by parameter Long operation Move up or Move down set by parameter 2 push button moving shutter Operation When operation send the command in sequence Move up
23. Switch downwards The implement direction of the parameter Switch upwards is 0O00 001 011 111 the implement direction of the parameter Switch downwards is 111 011 001 000 After the bus voltage recovery the current value is 000 if the parameter Switch downwards is selected the effect will be invisible when operation then it is possible to operation after switch up a few levels by the object level increment decrement X Parameter Sequence is This parameter indicate the manage process when there are different type of switching sequence Parameter Debounce time Min Time It can set the vibration time to prevent unwanted multiple operation by bouncing of contacts in vibration time which means the effective time of the contact operation Options 10ms 20ms Min operation The parameter window Min operation will be shown in Fig 3 4 2 7 Parameter window Counter X The parameter window Counter X will be shown in Fig 12 It is visible when the input is operated with 25 E EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EIT KAR the function Counter Using the Counter function the device is able to count the number of pulse edges at the input A differential counter 1s therefore available if required in a
24. a normally close contact in general Options Normally open Normally close The parameter introduced in this chapter is use Normally open as the example the normally close is just opposite Parameter Reaction on short operation or Reaction on long operation This parameter is visible when there is a distinction between a short and long operation It is able to set the operation when preset a short and long operation When the button operation is confirm to a short or a long operation the object value will be update immediately Options No action Off On Toggle Parameter Long operation after Basex Factor This parameter is visible if there is a distinction between a short and long operation The period TL is defined here after which an operation is interpreted as long TL Basex Factor Base options 100s Is 12 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com lh Factor options 2 255 Parameter Number of objects for short long object operation This parameter is visible if there is a distinction between a short and long operation It is able to set one or two communication objects when one communication object is set long and short operation share one communication object when two communication objects are set long and short operation use one communication object sepa
25. apter 1s use Normally open as the example the normally close is just opposite Parameter Max number of operations Num of objects This parameter specifies the maximum permitted number of operations This number is identical to the number of communication objects Output X fold Options Single operation 2 fold operation 3 fold operation 4 fold operation Parameter Value send object Tele Operation fold It can be set here which object value should be sent Options On Off Toggle 30 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SURPOWER z on GR The current object value is inverted in the Toggle setting Parameter Value on every operation send This parameter defines whether to send the operation value Options Yes No If yes is entered in this parameter the associated object value is updated and sent after each operation in the case of multiple push button actions Example For three fold operations the objects output 1 fold after the first operation output 2 fold after the second operation and output 3 fold after the third operation are sent If No is selected the current value will be send on the bus until the last operation delay the delay time is the interval time between two operations Parameter Max t
26. ble if parameter Additional object for long operation selected yes Once detected a long operation the object will send telegram on bus the telegram is set by parameter value send object Tele Long operation Form 7 Communication object Multiple operation 5 8 Communication object shutter control The communication object Shutter Control will be shown in Fig 5 8 Humber Name Object Function Descr Group Addresses Le C R W T WV Data Type PEN Ejo Disable A CH A Disable l bit C Low CHP Output shutter UP DOWN A CH A shutter UP DOWN 1 bit G T Low E2 Output Stop lamella adj A CH A Stop lamella adj Ibit G T Low a3 Upper limit position A CH A Upper limit position i bit C W Low Eja Lower limit position A CH A Lower limit position Chit C p Low Fig 5 8 Communication object Shutter control 46 C EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SURPOWER z ea GR This communication object move up down the shutter by sending command by bus It will move down if the communication object send a 1 telegram it will move up if sending a 0 It will stop adjust the shutter by sending command by bus It will stop adjust down if sending a 1 telegram and it will stop adjust up if sending 0
27. ch Dimming Value Forced output Scene control Switching sequence Counter Multiple operations Shutter Control Parameter Distinction between long and short operation This parameter sets whether the input distinguishes between a short and long operation If yes is selected there is a waiting period after the opening closing of the contact to determine whether the operation is long or short Only then is a possible reaction triggered The following drawing clarifies the function 8 C EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER s ea KR Without With distinction between distinction between Input signal Possible reaction Possible reaction to the input signal to the input signal Options Yes No Note The long operation in the below chapters are the same with here Parameter Cyclic send Tele Tele Switch This parameter is visible if there is no distinction between a short and long operation It is able to set whether to send the current value of object Tele Switch X cyclically on the bus Options No Always If switch off If switch on If the parameter value always is selected the object sends cyclically on the bus regardless of its value is O or 1 If the parameter value if switch off or if switch on is set only the corresponding obj
28. ddition to the standard counter Both counters are triggered by counting pulses but otherwise operate independently of each other The counter always has the same data width as the differential counter The function is similar with the differential counter and the standard counter The difference is the differential counter can reset the counter value count from 0 and overflow by the bus counter report Attention When disable the function both key scanning and object in out are disabled Any key status change will be ignored 1 1 1 Universal Interfaces 4 fold General Setting Channel A Channel 4 Counter Channel B Function of the channel Channel C 7 Channel O Pulse detection on Closing contact nising edge we LED 4 LED E LED status on pulse detection LED 4 ON LED C LED D Data width of counter 16 bit 32768 32767 Counter starts at 32 768 32767 Debounce tine Min Time Send object value atter voltage recover Enable additional options Factor divider cyclical send Fig 12 Parameter window Counter X Parameter Pulse detection on The type of input signal is defined in this parameter It can be set whether the contact is a normally open contact pulse trailing edge or a normally closed contact pulse rising edge Options Closing contact rising edge Opening contact falling edge The parameter introduced in this chapter is use Closing contact rising edge as the example the operati
29. e for additional supply voltage It is available to assign the physical address and set the parameters by Engineering design tools ETS with VD2 VD3 higher than edition ETS2v1 3 It is able to install VD3 file if use ETS3 software The Universal Interfaces have many functions that can be used in a wide variety of application areas The following list provides an overview Switching and dimming function Control of blinds and shutters Sending of values e g temperature values water line Invocate and storing of scenes Trigger an LED for reporting an operation Operation of various loads by multiple push button actions Operation of several loads in a fixed switching sequence Standard counting and differential counting Each channel of a device can adopt any of the functions described above 3 eee oon EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com 2 Technical data Power supply Bus voltage 21 30V DC via the EIB bus Input output 4 channels Can be individually parameterized as inputs or outputs Bus length lt 10M Input Scanning voltage 20 V DC Input current 5 mA Output Output voltage SV DC Output current max 2 5mA limited via series resistor of 2 KQ Safety Short circuit proof overload protection reverse voltage protection Operating and Red LED and push for assigning the phys
30. ect value is sent cyclically Parameter Reaction on closing the contact rising edge Reaction on opening the contact fall edge This parameter is visible if there is no distinction between a short and long operation It can be set the operation to open and close the contact Options No action Off On Toggle Stop cyclic transmission If the parameter Toggle is selected negate the operation that means negate the current value For example if On is selected when negate it will carry out Off operation If the parameter Stop cyclic transmission is selected it will stop the cyclical sending telegram till there is a new object value to be sent If the parameter No action is selected it will not implement any operation Parameter Interval of Tele Cyclic send Basex Factor This parameter is used to set the interval time between two telegrams that are sent cyclically it is visible if cyclical sending has been set Transmission cycle time Basex Factor Base options 1s 9 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI GR Os lh Factor options 1 255 Parameter Send object value after voltage recovery if yes not equal toggle It can be set whether to send the value of the object Tele Switch X on the bus after vo
31. en 7 n ieee Ge Qutput lbit long A CH A Value 1bit long l bit C I Low Fig 5 3 Communication object Value Forced output CH X Value Ibit Output 1bit X 1bit 2bit 4byte 1bit 2bit 4byte C1 bit 2bit Abyte This communication object is used to transmit the input value It is only transmit the object value in short operation if distinguish a long and short operation The value range is depend on the data type if the data type of the communication object is different the importability range of the object value is different The data type depend on parameter Reaction on short operation CH X Value Ibit long Output 1bit long X bit C1 bit 2bit 4byte C1 bit 2bit 4byte C1 bit 2bit Abyte This communication object is visible if there is a distinction between long and short operation it is used to transmit the object input value in long operation The value range is depending on the data type if the data type of the communication object is different the importability range of the object value is different The data type depends on parameter Reaction on long operation Form 3 Communication object Value Forced output 43 eee amon EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com Svs EII KRR EUROPOWER 5 4 Communication object scene control The com
32. en short long operation and cyclical sending of the contact state are possible Switch dimming sensor For switching dimming the lighting There are start stop dimming and stepwise dimming as well as dimming via a single push button are possible Value Forced operation For sending the valued of different data types e g temperature values It is possible to send different values or data types for short long operation possible to activate deactivate the forced operation of actuators Control scene For recalling and storing the states of several actuator groups The actuator groups can either be controlled via max 5 individual objects or via an 8 bit scene object Switching sequence For the operation of several actuator groups in a preselected sequence e g the latching relay Counter For counting input pulses Various data types of the counter can be set It is able to set the counting rate whether to sending the current counting values cyclically and the differential counter when enables an additional counter The differential counter can be reset and run out in report thereby it is convenient to count the daily consumption Push button with multiple operations For triggering various functions depending on the frequency of the operation A long operation can also be detected and a function can be triggered Shutter sensor For movement and adjustment of a shutter or blind Eight present operation modes are possible in total Contro
33. er control type is 2 push button moving shutter 2 switch operation moving shutter and 2 push button stepping It is defines the action when operation Different control type makes different operate action The former two control type is move up and down the last control type is stop reaction Options Move up Move down Options Stop adjust up Stop adjust down Parameter Long operation after This parameter is visible if long operation activate The period is defined here after which an operation is interpreted as long Options 0 3s 0 5s 10s Parameter Debounce time It can set the vibration time to prevent unwanted multiple operation by bouncing of contacts in vibration time which means the effective time of the contact operation Options 10ms 20ms 34 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com 150ms 4 3 Description of setting the system parameter in part of LED channel The LED priority in the channel LED part is lower than the LED in device channel When enable the LED setting in device channel the LED in LED channel will not action 4 3 1 Parameter window Flashing X The parameter window will be shown in Fig 16 It is able to set the LED flash function and turn on the LED for long time simultaneously 1 1 1 Universal Interface
34. ferential Counter X Counter It is visible if enable the parameter Enable differential counter It is used to reset the counting value of the differential counter which counting from 0 It will reset the counting value if receive a logic value 1 telegram and it will no reaction if receive a 0 Form 6 Communication object Counter 5 7 Communication object multiple operation The communication object Multiple Operation will be shown in Fig 5 7 The value of the designate operation object will be modify if detect multiple operation in period Humber Hame Object Function Descr Group Addresses Le C E T U Data Type Pra Ejo Disable CH Disable l bit C W Low Eji Qutput i fold A CH i fold l bit C T Low Eiz Output 2 fold A CH 2 fold l bit C T Low Bng Qutput 3 fold A CH A 3 fold Ibit T Low Eja Output 4 fold A CH 4 fold Lhit G T Low Gas Qutput Long fold A CH A Long fold i bit CE I Low Fig 5 7 Communication object Multiple operation The number of the communication object maximum 4 is set by parameter Max number of operations Num of objects If there are multiple operation multiple objects will send the relevant telegram on bus which the telegram set by parameter value send object Tele Operation fold The detail operation process will be describe in the multiple operation parameter chapter It is visi
35. fo Fig 21 Parameter window Indicate object in and out X Parameter LED on time This parameter defines the indicative time of LED when there is input or output of communication object which means the switch on time Options 100ms 200ms 41 C EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SURPOWER z on GR 5 Description of communication object The communication object is the medium to communicate other device on the bus which means only the communication object can communicate with bus The communication object and the object in each channel are the same then use channel A as the example to introduce the function of each communication object 5 1 Communication object switch Humber Hame Object Function Deser Group Addresses Le C Yo T U Data Type Fr afi ERRER ee i ili ee ia AEE ee es AEE E aru ee nee ee ee eee ee en ee eee aaa eRe oe nes semen ss iene Ge Switch long A CH A switch long i bit C I Low Fig 5 1 Communication object Switch Note C in Flag column in the below table means that the object has a normal link to the bus W means the object value can be modified via the bus R means the value of the object can be read via the bus T means that a telegram is transmitted when the object value has been modified
36. g 6 and Fig 7 in Fig 6 there is a distinction between a short and long operation while in Fig 7 is just opposite 1 1 1 Universal Interfaces 4 fold General Setting Channel A Channel 4 Channel B l Channel C Function of the channel Value Forced output Channel D LED A Connect contact type normally oper LED B Distinction between long and LED C short operation LED lt a ws Reaction on short operation Tbyte value 0 255 im Output value 0 255 4 Reaction on long operation Tbyte value 0 255 Output value 0 255 12 a gt Long operation after base 4 Factor 2 255 a gt Debounce time Fig 6 Parameter window Value force output X distinguish with a short and long operation 16 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com 1 1 1 Universal Interfaces 4 fold General Setting Channel A Channel 4 Channel B Channel C Function of the channel Value Forced output Channel D LED A Connect contact type normally oper LED B Distinction between long and LED C short operation LED D Reaction on operation Tbyte value 0 255 Outout value 0 255 1 Send object value after Mo volage recover Debounce timetlin Time Irto Fig 7 Parameter window Value force output X do not distinguish with a s
37. hort and long operation Parameter Connect contact type This parameter defines whether the contact at the input is a normally open contact or a normally closed contact Options Normally open Normally closed The parameter introduced in this chapter is use Normally open as the example the normally close is just opposite Parameter Distinction between long and short operation This parameter sets whether the input distinguishes between a short and long operation If yes is selected there is a waiting period after the opening closing of the contact to determine whether the operation is long or short Options Yes No Parameter Reaction on operation This parameter is visible if there is no distinction between a short and a long operation It defines the data type that is sent when the contact is pressed Options No reaction 1 bit value 0 1 4 byte value 0 4294967295 17 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI GR Parameter Reaction on short operation Reaction on long operation This parameter is visible if there is no distinction between a short and long operation It defines the data type that is sent after a short or long operation Options 1 bit value 0 1 4 byte value 0 4294967295 Parameter Output value
38. ical address display elements button Green LED flashing Indicate the application layer works normally Connections Input output 2 5 pin cables approx 30 cm long can be extended to max 10 m EIB bus via bus connecting terminal Ambient Operation S C 45 C temperature Storage oC Os range Transport 25C 70C Miscellaneous CE norm in accordance with the EMC guideline and the low voltage guideline Certification EIB certified Mounting in switch box 60 mm Dimensions 46x46x11 7mm Weight 0 05 KG 4 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com 3 Dimension and Connection diagram 3 1 Dimension drawing 11 7 mm lt 4 gt lt 46 0 mm gt A E o v 3 2 Connection diagram 20VDC KIZU 0401 1 _Un 20VD EIJ KNR CE 5 a EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SURPOWER z ona GR 4 Project design and programming 4 1 Overview of the functions Number of Max number of Max number of Application program communication objects group address associations The following functions can be set separately for each input Switch sensor For switching the lighting or scanning a floating contact Distinction betwe
39. ied which is the alterative data The communication object level increment decrement X is used to 24 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SURPOWER Ge or GR increase or decrease the switch level 1 means increase 1 level and O means decrease Different options have different communication objects and different switch levels but their management are similar in the case of the same switch sequence type Parameter Type of switching sequence The switching sequence can be selected here Each sequence has other object values for each switching level Options Sequentially on off one push button Sequentially on off several push buttons All combinations Take 3level as the example to explain the difference between them send the modified data on the bus data OFF 1 ON Type of switching sequence Sequentially on off one push button 000 001 011 111 011 001 Sequentially on off several push buttons 000 001 011 111or 111 011 001 000 All combinations 000 001 011 010 110 111 101 100 Gray code Parameter Function on operation Only visible in the switching sequence Sequentially on off several push buttons It can be set whether an operation of the push button switches up or down a level Options Switch upwards
40. ime between two operation This parameter sets the interval between two operations If there are no further operations within this period the object output 1 fold is sent again Options 0 3s 0 5s 10s Parameter Additional object for long operation This parameter defines whether to activate the long operation If a long operation is carried out after one or several short operations within the maximum period the short operations are ignored Options Yes No Parameter Long operation after This parameter is visible if long operation activate The period is defined here after which an operation is interpreted as long Options 0 3s 0 5s 10s Parameter Value send object Tele Long Operation This parameter is visible if long operation activate This parameter defines the value sent by the object output long fold on the bus when it is set long operation Options On Off Toggle The current object value is inverted in the Toggle setting Parameter Debounce time It can set the vibration time to prevent unwanted multiple operation by bouncing of contacts in vibration time 31 eo EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI GR which means the effective time of the contact operation Options 10ms 20ms 4 2 9 Para
41. is chapter is use Normally open as the example the normally close is just opposite Parameter Control the scene by It is possible to select whether the scene control is carried out via 5 separate objects or whether values that are stored in the actuators are recalled and saved via an 8 bit scene Options 5 separate objects 8 bit scene If the parameter Sseparate objects is selected it will activate the control of the groups of the actuator these 5 objects parameter window will be shown in Fig 10 If the parameter 8 bit scene is selected it can control the scene such as the scene function in dimming actuator switch actuator the parameter window will be shown in Fig 9 Parameter No of scene 0 63 This parameter will be visible when the scene control is 8 bit scene it can be set the No of scene The No range is 0 63 Parameter Reaction on short operation This parameter defines whether a short operation of the input causes a light scene to be recalled or no reaction takes place Options No reaction Recall scene Parameter Store scene This parameter defines how the saving of the current scene Options No On long operation With object value 1 On long operation and object value 1 Different type of scene control makes the saving of the current scene different The following table provides an Overview Control the scene via 5 separate
42. it Output Ibit 8bit Group A E X 1bit lbyte It is visible if parameter Control the scene selected 5 separate It is used to control the actuator group it can control by a 1 bit or 8 bit data set by parameter When saving the scene the value of object output 1bit 8bit group A E will be read and storage by bus When the bus voltage recovery the value of the object resume to the default value and the new storage value will be lost This communication object is visible if parameter Control the scene selected 8bit scene it is used to control the scene It is possible to invocate or save the scene by a 8 bit command sent by this object The definition of the 8 bit command will be described below This object is only to communicate C and transmit T do not have the function modify W and update U Assuming an 8 bit command binary coding as FXNNNNNN F invocate the scene with 0 save the scene with 1 X 0 NNNNNN scene number 0 63 This parameter trigger the scene storage or indicate the accomplish of the scene by bus decided by the mode of the scene storage The detail storage process will be described in the scene storage parameter chapter Form 4 Communication object Scene control 5 5 Communication object switch sequence The communication object Switching sequence will be shown in Fig 5 5 It can modify the object value 44 a
43. just dim darker first and the latter operation negate Note The long and short operation is individual they are not operation on one object Parameter Long operation after This parameter is visible if the value Dimming and switching has been set in the parameter Dimming functionality The period TL is defined here after which an operation is interpreted as long Options 0 3s 0 5s Parameter Reaction on operation This parameter is visible if the value Only dimming has been set in the parameter Dimming functionality 14 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com There is no distinction between a short and long operation The operation and the option of the parameter Reaction on long operation are the same It is able to set a dim brighter or a dim darker after a long operation Options Dimming brighter Dimming darker Dim brighter darker with start brighter Dim brighter darker with start darker Parameter Dimming mode This parameter defines the dimming mode is start stop dimming or steps dimming Options Start stop dimming Steps dimming If Start stop dimming is selected the dimming mode is start stop dimming it begins the dimming process with a dim darker or brighter telegram and ends the dimming process with a stop telegram Cyclical sending
44. l Scene control is selected This function enables the states of several actuator groups to be recalled and stored 18 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER 1 1 1 Universal Interfaces General Setting Channel 4 Scene A Channel 6 Channel C Channel D LED A LED B LED C LED D 1 1 1 Universal Interfaces General Setting Channel 4 Channel B Channel C Channel D LED 4 LED B LED C LED D 4 fold Function of the channel Connect contact type Control the scene by Reaction on short operation Store Scene long operation alter Debounce time Defaut in Fig 8 Parameter window Scene control X 4 fold Channel 4 Function of the channel Connect contact type Control the scene by Mo of ecene 0 63 Reaction on short operation Store Scene Debounce time Fig 9 Parameter window 8 bit scene EUROPOWER ELECTRICAL LIMITED 19 Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe sa GR Parameter Connect contact type This parameter defines whether the contact at the input is a normally open contact or a normally closed contact Options Normally open Normally closed The parameter introduced in th
45. l LED For controlling a light emitting diode switching and flashing As the switch it is with time limit that turns off automatically after a preset time as the flash it is able to set the flashing rates 4 2 Description of setting the system parameter in part of device channel Parameters and objects in the device application are outlined in this section Parameters and objects which are assigned to each channel are equivalent and described in the following sections using output A as an example 6 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com 4 2 1 Parameter window General Setting Parameters for the functions which affect the complete device can be set via the Fig 1 1 1 1 Universal Interfaces 4 fold General Setting General Setting Channel Channel B o Channel Limit number of Tele Channel D LED A Period LED E Max Number Tele within a period LEDC 1 255 LED D Fig 1 parameter window General Setting Parameter Limit number of Tele It is use to limit the number of sending telegrams to decrease the burthen of bus It is possible to set how many telegrams can be sent within an adjustment period Options Yes No Parameter Period It is able to set the limit time of sending telegrams Options 100ms 500ms Is 10min Parameter Max Number Tele Wi
46. l when sending 1 and decrease a level when sending 0 The detail process will be describe in the switching sequence parameter chapter Form 5 Communication object Switching sequence 5 6 Communication object counter The communication object Counter will be shown in Fig 5 6 Including standard counter and differential counter communication object both these communication objects are initiated counter by one operation and the counter range are the same but the counting are independent of each other Humber Hame Object Function Descr Group Addresses Le C R W T U Data Type lear jo Disable A CH A Disable l bit C T Low map Output counter value lbyte A CH A Counter value 1 Byte C W T Low G2 Differential Count lbyte A CH A Differential Counter 1 Byte L T ITI Low G3 Request counter value A CH A Request counter value i bit G gt Low Eja Differential counter overflo CH A Differential overflow ibit C T Low as Reset differential counter A CH A Rst differential counter Lbhit C T Low Fig 5 6 Communication object Counter Output counter value 1byte X 1Byte CH X Counter value C W T lbyte 2byte 4byte lbyte 2byte 4byte This communication object is used to transmit the current counting value of the standard counter and it can modify the counting value simultaneously Different data type makes the different counting range it is defines by parame
47. limit of LED control Time limit base Time limit factor 255 Send status by object Tele Status State of LED on bus voltage recovery Fig 17 Parameter window Switch X Parameter LED is switch ON if This parameter defines the mode to switch on the LED Options Object Tele Switch 0 Object Tele Switch 1 Parameter Time limit of LED control This parameter defines whether to enable the function to restrict the time to switch on the LED Options Yes No Parameter Time limit Basex Factor This parameter is visible if the time limit is active It is defines the time of LED flashing Basex Factor After this period the LED switches off automatically Base options 1s 10s lh Factor options 1 255 Parameter Send status by object Tele Status This parameter defines whether to send the LED status report on the bus Options Yes No 37 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com If Yes is selected the object Send its status X will send value 1 when LED switch on it will send value 0 when LED switch off Parameter State of LED on bus voltage recovery It is defines the state of LED when the bus voltage recovery Options On Off 4 3 3 Parameter window Control by input X The parameter window
48. ltage recovery this parameter is visible if there is no distinction between a short and long operation Options Yes No If the parameter Yes is selected it will send the current value of the object Tele Switch X on the bus Only when the value Toggle has not been set in either of the two parameters Reaction on opening closing the contact the value of the object Tele Switch X can be send on the bus If one of the two parameters has the value TOGGLE no values are sent in general on the bus after bus voltage recovery If No reaction or Stop cyclic transmission is selected there is no values are sent on the bus either Parameter LED function set This parameter set the LED direction to indicate the status according to the object Tele Switch X There are A B C D 4 LEDs to choose each LED has 2 options If the parameter LED X accord to switch value is selected LED indicate status is the same with the current value of the object Tele Switch X 1f the parameter LED X toggle by switch value is selected LED indicate status 1s negate to the current value of the object Tele Switch X Options No action LED A accord to switch value LED A toggle by switch value LED D accord to switch value LED D toggle by switch value Note If the four channels invocate the same option the priority of channel A is the highest it will indicate the status according to the
49. ltiple operation X will be shown in Fig 14 It is visible if the input is operated with the function Multiple operation Enable the function if the input is operated several times within a certain period a specified object value can be modified depending on the number of operations This enables e g different light scenes to be implemented with multiple push button actions 29 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com 1 1 1 Universal Interfaces 4 fold General Setting Channel A Channel 4 Channel B Channel C Function of the channel Multiple operation Channel D LED A Connect contact type normally oper LED E Mas number of operations LEDC Nurn of objects LED D fold operation Value send object tele operation fold a lt 4 lt lt mm lt Value on every operation send Mas time between two operation Additional object for long operation lt Long operation after Value send object Tele long operation TOGGLE Debounce time Pms info Fig 14 Parameter window Multiple operation Parameter Connect contact type This parameter defines whether the contact at the input is a normally open contact or a normally closed contact Options Normally open Normally closed The parameter introduced in this ch
50. meter window Shutter control X The parameter window Shutter control X will be shown in Fig 15 It is visible if the channel function Shutter control is selected When enable this function it is possible to control the shutter by one button switch or two button switch operation 1 1 1 Universal Interfaces 4 fold General Setting Channel A Channel 4 Channel B Channel C Function of the channel Skutter Control Channel D LED A Connect contact type normally oper LED B LEDC Operation functionality type LED D ShortStop lamella UPYMOVE Note about fuctionality Long Move UP MOVE Reaction on short operation STOPylamella UF Reaction on long operation MOVE UP Long operation after As Debounce tine Fig 15 Parameter window Shutter control X Parameter Connect contact type This parameter defines whether the contact at the input is a normally open contact or a normally closed contact Options Normally open Normally closed The parameter introduced in this chapter is use Normally open as the example the normally close is just opposite Parameter Operation functionality type This parameter defines the types of the shutters operation detailed description of the type and function as the 32 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SU
51. munication object Scene control will be shown in Fig 5 4 it is including the actuator group and the communication object in the scene control mode The control mode of actuator group control by 5 independent communication object it is control by 1bit and 8bit data The scene control mode control by a 8 bit data Humber Hame Object Function Deser Group Addresses ie oe C R WwW T U Data Type PP Ejo Disable A CH A Disable l bit C ff Low mli Qutput ibit Group A A CH A 1bit Group A i bit C T U Low Ge Output ibit Group B A CH A 1lbit Group B i bit C T U Low Gas Qutput ibit Group C A CH A lbit Group C i bit C T U Low Eja Output ibit Group D A CH A 11bit Group D i bit C T U Low Gas Output ibit Group E A CH h lbit Group E i bit C T U Low Eje Store scene CH A Store scene l bit C TIT Low Humber Hame Object Function Descr Group Addresses Eer C E Y T U Data Type EEE Eo Disable A CH A Disable l bit C amp Low m Qutput bit Group A A CH A Shit Group A i Byte C E T U Low Ez utput Sbit Group B A CH A Sbit Group B i Byte C E T U Low G3 Output Gbit Group A CH A Sbit Group C 1 Byte C WF I U Low Eja Qutput Sbit Group D A CH A Sbit Group D i Byte C E T U Low ms Qutput Sbit Group E A CH A bit Group E i Byte C E T U Low i Qutput Shit scene A CHA Sbit Scene 1 Byte C E T U Low Fig 5 4 Communication object Scene control So fe o o O oae 1bit 8b
52. of the dimming telegram is not required in this case If Step dimming is selected the dimming mode is step dimming the dimming telegram is sent cyclically during a long operation Once the operation has finished a stop telegram ends the dimming process Parameter Brightness change on every sent This parameter is only visible for Dimming steps It can be set which change in brightness percentage value causes a dimming telegram to be sent cyclically Options 100 50 Parameter Interval of Tele Cyclic send This parameter is only visible for Dimming steps It is able to set the interval of telegram cyclic sending after a long operation Options 0 3s 0 5s Parameter Debounce time It can set the vibration time to prevent unwanted multiple operation by bouncing of contacts in vibration time that means the effective time of the contact operation Options 10ms 20ms Min operation A minimum operation time can only be set if the value Only dimming has been set in the parameter Dimming functionality The parameter window will be shown in Fig 3 15 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SURPOWER z ons GR 4 2 4 Parameter window Value force output X Parameter window Value force output X will be shown in Fi
53. on of opening contact is just opposite Parameter LED status on pulse detection This parameter defines the indication of LED whether to be on off or no action when detect there is pulse 26 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI GR input Options LED A ON LED A OFF DED D OFF No action Note If the four channels invocate the same option the priority of channel A is the highest it will carry out the preset operation when detected pulse input Then the priority of channel B is higher then it s C the last is D The priority of LED X in function channel in the device is higher than the LED X channel the LED X can not be implement any operation in channel LED X which is used in the function channel in the device If the parameter LED status on pulse detection is set LED A ON or LED A OFF options the operation had been set in LED A can not be carry out Parameter Date width of counter The data type of the counter absolute counter and differential counter is defined in this parameter The data type specifies the counting range for the counter The type of the objects Output counter value and Differential counter is adapted to the data type of the parameter setting Options 8bit 0 255 16bit 32768 32767 16bit 0
54. r This parameter is visible if the time limit is active It is defines the time of LED flashing Basex Factor Base options 1s 10s lh Factor options 1 255 Parameter Send status by object Tele Status This parameter defines whether to send the LED status report on the bus Options Yes No If Yes is selected the object Send its status X will send value 1 when LED flashing it will send value 0 when LED stop flashing Parameter State of LED on bus voltage recovery It is defines the state of LED when the bus voltage recovery Options On Off Parameter LED is switched ON OFF for It is defines the time of the LED switched on off when LED flashing Options 600ms 800ms 4 3 2 Parameter window Switch X The parameter window Switch X will be shown in Fig 17 to defines the switch function of LED The LED will switch off automatic and it can keep switching on after the LED is switch on for a while 36 ee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe Ea KR 1 1 1 Universal Interfaces 4 fold General Setting Channel Channel E FLED function is enable in input Channel C this must chose Control by input Channel D LED A Function of the LED Channel LED E LED C LED is Switch ON it LED D Time
55. rately Options object 2 objects 4 2 3 Parameter window Switch dimming X Parameter window Switch dimming X will be shown in Fig 5 it is visible when Function of the channel Switch Dimming is selected The function enables the operation of dimmable lighting 1 button operation is also possible 1 1 1 Universal Interfaces 4 fold General Setting Channel A Channel A Channel B Channel C Function of the channel Channel D LED A Connect contact type normally oper LED E LEDC Dimming functionality Dimming and switching LED D Reaction on short operation aa Reaction on long operation Dim BRIGHTERAOAREER with start BRIGHTE 5 T G lt Long operation after Dimming mode Sheps dimming Brightness change on every sent 1 564 Interval of Tele cyclic send Debounce time Fig 5 Parameter window Switch Dimming Parameter Connect contact type This parameter defines whether the contact at the input is a normally open contact or a normally closed contact Options Normally open 13 eee oo EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SURPOWER z on GR Normally open The parameter introduced in this chapter is use Normally open as the example the normally close is just opposite Parameter Dimming functionality Thi
56. s 4 fold General Setting Channel A omnes if LED function i enable in input NOTE Informat Channel C this must chose Control by input PARR Channel D l LED A Function of the LED Channel LED B LEDE LED flashing Object LED flashing 1 LED D Time limit of LED control lt Time limit base Time limit Factor 255 a Send statue by object Tele Status o 4 State of LED on bus voltage recovery LED ts switched ON for LED ts switched OFF for 4 Fig 16 Parameter window Flashing X Parameter Function of the LED channel This parameter defines the function of the LED channel The default parameter is Flashing function If No action is selected it means this channel disable Options No action Flashing Switch Control by input Indicate object in Indicate object out Indicate object in and out 35 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI GR Parameter LED Flashing if This parameter defines the mode of opening the LED flashing Options Object LED flashing 0 Object LED flashing 1 Parameter Time limit of LED control This parameter defines whether to enable the function to restrict the flashing of the LED Options Yes No Parameter Time limit Basex Facto
57. s parameter determines whether the lighting is only dimmed or whether it should also be switched Options Dimming and switching Only dimming If the parameter Only dimming is selected there is no distinction between a short and long operation The dimming command is therefore carried out immediately after the push button action there is no delay to determine whether the operation is long or short If the parameter Dimming and switching is selected the push button action need to delay to determine whether the operation is long or short In this case the lighting is dimmed via a long operation and switched via a short operation Parameter Reaction on short operation This parameter is visible if the value Dimming and switching has been set in the parameter Dimming functionality It is able to set the operation after triggered the object Switch X that s a short operation Options No action Off On Toggle Parameter Reaction on long operation This parameter is visible if the value Dimming and switching has been set in the parameter Dimming functionality It is able to set a dim brighter or a dim darker after a long operation Options Dimming brighter Dimming darker Dim brighter darker with start brighter Dim brighter darker with start darker The parameter Dim brighter darker with start darker is selected it can be dim brighter or dim darker after a long operation it is
58. t is used to send the status of LED Sending 1 means LED open or flashing and sending 0 means the LED is stop The object LED Flashing X will send telegram 1 if sending open flashing requirement every time Form 9 Communication object LED X Flashing 47 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI RR 5 10 Communication object LED X SWITCH The communication object LED X Switch will be shown in Fig 5 10 Humber Hame Object Function Descr Group Addresses Le C oR Y T W Data Type Fro Fjzs LED switch A LED A Switch l bit C RF Low Tzs LED permanent on A LED A Permanent on l bit C 4 Low 130 Send its status A LED A Send its status l bit f T Low Fig 5 10 Communication object LED X Switch This communication object is used to open LED It will open LED if the object receive a 1 or 0 telegram defines by LED is Switch ON if the open time can be set by parameter it will stop LED if receive 0 or 1 It is used to open LED for a long period and its priority is higher than the communication object LED switch X It will open LED if receive telegram 1 negate priority and the LED resume the foregoing operation if receive 0 It is visible if Send status by object
59. ter Date width of counter Differential Counter I byte X 1Byte CH X Differential Counter 1lbyte 2byte 4byte 1lbyte 2byte 4byte It is visible if enable the parameter Enable differential counter This communication object is used to transmit the current counting value of the differential counter and it can modify the counting value simultaneously Different data type makes the different counting range it is defines by parameter Date width of counter CH X Request Counter Request Counter value X value EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com SURPOWER z ma GR This communication object is used to ask for the current counting value of the standard counter and the differential counter The communication object CH X Counter value and CH X Differential Counter will transmit the current counting value if receive a logic value 1 it will no reaction if receive a logic value 0 telegram CH X Differential overflow Differential counter overflow X It is visible if enable the parameter Enable differential counter Once the counting of the differential counter exceed the overflow value preset by parameter Over under run of differential at 0 255 it will send telegram 1 on bus to report the overflow CH X Rst Differential Reset Dif
60. the output of the communication object 39 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com 1 1 1 Universal Interfaces 4 fold General Setting Channel A plone LED function is enable in input Channel C thi must chose Control by rout lt NOTE Information Channel D LED A Function of the LED Channel Indicate Object Out LED B LEDC LED on time LED D Info Fig 20 Parameter window Indicate object out X Parameter LED on time This parameter defines the indicative time of LED when there is output of communication object which means the switch on time Options 100ms 200ms 4 3 6 Parameter window Indicate object in and out X The parameter window Indicate object in and out X will be shown in Fig 21 the LED is used to indicate the input and output of the communication object 40 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EI GR 1 1 1 Universal Interfaces General Setting Channel 4 Channel E it LED function is enable in input lt NOTE Inf t Channel C this must chose Control by input SV Channel D l LED Function of the LED Channel Indicate Object In and Out LED B LED C LED on time LED D In
61. thin a period 1 255 It is able to set the Max number of sending telegrams within a setting period Options 1 255 7 EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EaI GR 4 2 2 Parameter window Switch X Parameter window Switch X can be shown in Fig 2 and Fig 4 Fig 2 do not distinguish between long and short operation while Fig 4 opposite 1 1 1 Universal Interfaces 4 fold General Setting Channel A Channel 4 n Channel B Channel C Function of the channel Channel D Distinction between long and LED A short operation LED B IEDC Cyclic send Tele Tele switch always LED D Oo lt Reaction on closing the contact OFF Rising edge Reaction on opening the contact Falling edge no action Interval of Tele cyclic send Base Factor 1 255 Send object value atter voltage recovery it YES not equal TOGGLE LED function set LED 4 accord to switch value Debounce timetlin Time Rims Fig 2 Parameter window Switch X do not distinguish between long and short operation Parameter function of the channel The parameter determines the function option in the channel the current option is switch If No function is selected it means the channel is disabled Options No function Switch Swit
62. value of the object Tele Switch X in channel A Then the priority of channel B is higher then it s C the last is D The priority of LED X in function channel in the device is higher than the LED X channel the LED X can not be implement any operation in channel LED X which is used in the function channel in the device If the parameter LED function is set LED A accord to switch value or LED A toggle by switch value options the operation had been set in LED A can not be carry out Parameter Debounce time It can set the vibration time to prevent unwanted multiple operation by bouncing of contacts in vibration time which means the effective time of the contact operation Options 10ms 20ms 10 eee EUROPOWER ELECTRICAL LIMITED Unit 7 The Sandon Estate Sandon Way Liverpool L5 9YN Tel 0151 207 5409 e mail europower europower electrical com www europower electrical com EUROPOWER Qe EI GR Min operation The minimum operation time can only be set when there is no distinction between a short and a long operation This parameter is different from others the effective time of the contact operation is not only means the effective time when contact close but also the contact open The parameter window can be shown in Fig 3 1 1 1 Universal Interfaces 4 fold General Setting A MiniT ime Channel 4 4 MiniT ime T E Channel p Minimum operation time base Channel C Minimum operation tine Factor