1. The Serial Statistic page is used to monitor the health of the controller network These numbers will help identify when there are issues with wiring duplicate Modbus ID addresses or noise on communication wires on the controller side of the network In this example controller number 11 is experiencing failure in communication quality Timeout Errors increments anytime that a controller does not respond in an appropriate amount of time Retry Errors increments anytime that a controller does not respond after 3 attempts to read information CRC Errors increments anytime that the controller responds with a bad packet Bad Polls increments when there are timeouts and the retries did not successfully retrieve information Good Polls increments on each valid packet received Illness increments anytime that there are 5 CRC or Timeout errors in a row After a count of 5 in the Illness column the controller is flagged as having no communication On the next valid packet received the Illness value is cleared to zero and communications is restored You must refresh the browser to see these numbers update 15 I WATLOW EM Gateway Network Stats This page was loaded Wed Feb 1318 00 28 2002 IP Address Subnet Gateway Mac Address Receives Unicasts Multicasts Broadcasts Rx Errors Rx Missed Rx CRC Errors Rx Drops Transmits Buffer Defers Tx Errors Tx Collisions Tx Coll Overflow Tx FILO Errors Traffic Backoffs Network Rej
2. Product Overview The EM00 GATE 0000 is a gateway bridge that allows up to 32 Watlow controllers to be directly connected to an Ethernet network Using an HTTP Browser such as Microsoft Internet Explorer or Netscape Navigator you may access 16 controllers and view several controllers parameters via an onboard Web HTTP server Ethernet Gateway The Ethernet gateway provides a means for monitoring and configuring runtime parameters of multiple controllers via a web browser The gateway is also a bridge for Modbus messages between the Ethernet bus and EIA 485 or EIA 232 links The Gateway supports full product configuration monitoring and configuration of runtime parameters via MODBUS TCP over TCP IP using a software package such as Watview sold by Watlow Ethernet Gateway Architecture This product has three physical connectivity points to the physical world They are the serial EIA 485 or EIA 232 Ethernet port 10BaseT and the power supply pins The EIA 485 EIA 232 connection supports Modbus RTU protocol and operates as a Master port It will initiate data read write requests to supported standard Watlow controllers There exists a virtual image of the controller s data points in the gateway The polling engine that initiates the Modbus RTU requests is responsible for synchronization of the virtual image and the actual controller Changes to control data occur both at the controller and at the virtual image The 10BaseT connection s
3. 2 register 106 with choice of Ok Alarm High Alarm Low or Alarm Error as read only Alarm Status Output 3 register 110 with choice of Ok Alarm High Alarm Low or Alarm Error as read only Alarm Acknowledge register 106 with choice to clear alarm as write only Note An input error or inputting Set Point values less than 30000 will disable the Auto Set Point Alarms not configured are not displayed Alarms can not be acknowledged while the alarm condition exists Series 988 989 Operation Mode register 10 with choice of Auto or Manual as read only Input Error register 4 with choice of Sensor Error or Ok as read only Process Value Input 1 register 1 as read only Process Value Input 2 register 2 as read only Auto Set Point register 7 as read write Alarm Status Output 2 3 register 3 with choice of Ok Alarm High Alarm Low or Alarm Error as read only Alarm Acknowledge register 3 with choice to clear alarm as write only Note Selecting Manual control using the Operation Mode an input error or inputting Set Point values less than 30000 will disable the Auto Set Point Alarms not configured are not displayed Alarms can not be acknowledged while the alarm condition exists Series 998 999 Operation Mode register 301 with choice of Auto or Manual as read only Input Error register 209 with choice of Sensor Error or Ok as read only Process Value Input 1 register 100 as read only
4. Status always OK as this is the same output as communications Alarm 3 Status registers 33 and 34 of Alarm 3 Ok Alarm 3 Low Alarm or Alarm 3 High Alarm as read only Note Alarms configured are displayed Alarms can not be acknowledged when the alarm condition still exists In addition the Series SD has many other parameters to read or change by clicking on the link SeriesSD Be sure to submit any changes made on these screens using the Submit button at the bottom of the screen The following are screen captures from the Series SD t EM Gateway WATLOW Gateway Setup Software Revision 2 00 043 This page was loaded Tue Feb 24 10 29 36 2004 Device Modbus AM Input Input Process Auto Alarm Alarm Email Address Mode No Error Value Seipoint Status Ack Ack Series SD 1 Auto 1 Ok 0 0 Alarm 1 Ok Alarm 2 Ok Alarm 3 Ok 20 This page was loaded Tue Feb 24 09 30 53 2004 Configure things using the panel to the left to do whatever you want to the control 21 This page was loaded Tue Feb 24 09 34 30 2004 Analog Input Sensor Type Thermocouple Parameters Thermocouple Type RTD Parameters RID Curve Process Parameters High process scale Low process scale High voltage scale Low voltage scale High current scale Low current scale Thermocouple J DIN 0 385 gt fa999 0 1999 to 9999 Process Units F720 1999 to 9999 Process Units 0 0 10 0 Volts 20 0 0 20 0 mA 4 0 0 20 0 mA Temper
5. to Network Setup Email Setup Clock Setup Network Statistics and the Serial Statistics pages i EM Gateway Network Setup WATLOW This page was loaded Thu Feb 4 23 37 30 2002 Device Identification Name JEmoo01 00 Current Settings TP Address 7 3 37 91 Subnet Mask 255 255 224 0 Default Gateway 7 3 63 250 DNS Server 7 3 55 4 IP Address Resolution Method Choose the method for this hosts IP address assignment Try DHCP server then use Auto IP then use fixed IP address C Try DHCP server then use fixed IP address C Try Auto IP then use fixed IP address C Use Fixed IP address Fixed IP Address Fixed IP Address 0 0 0 0 Fixed Subnet Mask 0 0 0 0 Fized Gateway 0 0 0 0 Fixed DNS Server 0 0 0 0 Submit Reset Use this page to change the Gateway identification name or to change the IP Address Resolution Method Contact your IS administrator for questions regarding these settings EM Gateway Email Setup This page was loaded Thu Feb 24 23 37 49 2002 Electronic Notification The SMTP Server Address has priority over the SMTP Server Name To use the SMTP Server Name leave the SMTP Server Address blank The SMTP Server Name requires a DNS look up Alarms that occur before the Server Name is resolved are not sent I Enable Email Notification SMTP Server Name Sti w T T TUTUTUUUUUU CMHT Example smtp company com SMTPServerAddress Example 102 43 23 2 Email Subject D Example EM Gateway Ale
6. 3 register 106 with choice of Ok Alarm High Alarm Low Alarm High Latched Alarm Low Latched Alarm High Silenced Alarm Low Silenced Alarm High Latched Silenced Alarm Low Latched Silenced Waiting for in Range Alarm Alarm Disabled or Alarm Error as read only Alarm Acknowledge register 331 with choice to clear alarm as write only Note Selecting Manual control using the Operation Mode an input error or inputting a Set Point value less than 30000 will disable the Auto Set Point Alarms not configured are not displayed Alarms can not be acknowledged while the alarm condition exists Series 97 Process Value Input 1 register 100 as read only Limit Status register 319 with choice of Ok High Limit Low Limit or Limit Error as read only Alarm Status Output 2 register 106 with choice of Ok Alarm High Alarm Low or Alarm Error as read only Alarm Status Output 3 register 110 with choice of Ok Alarm High Alarm Low or Alarm Error as read only Alarm Acknowledge register 331 with choice to clear alarm as write only Note Alarms configured are displayed Alarms can not be acknowledged while the alarm condition exists Series 981 982 Operation Mode register 200 with choice of Hold Run or Pre run as read only Input Error register 209 with choice of Sensor Error or Ok as read only Process Value Input 1 register 100 as read only Auto Set Point register 300 as read write Alarm Status Output
7. EM Gateway User s Manual For Watlow part number EM00 GATE 0000 gt ma bie lt es ox aig RSs Mw WATLOW 1241 Bundy Boulevard P O Box 5580 Winona Minnesota USA 55987 5580 Phone 1 507 454 5300 Fax 1 507 452 4507 Internet http www watlow com 0600 0040 0001 Rev D 10 00 February 2004 EM Gateway Table of Contents Chapter 1 Chapter 2 Chapter 3 Chapter 4 Chapter 5 Product Overview Ethernet Gateway Ethernet Gateway Architecture Program Upgrades Installation and Wiring Dimensions Configuration Getting Started Network Services Email Alarm Notification Data Logging Control Monitoring and Configuration HTML Pages EM Gateway EM Gateway Setup EM Gateway Network Setup EM Gateway Email Setup EM Gateway Clock Setup EM Gateway Serial Statistics EM Gateway Network Statistics Controller Parameters and Registers Series 96 non ramping Series 97 Series 981 982 Series 988 989 Series 998 999 Series F4S F4D Series F4P MicroDin Power Series CLS200 Series Series SD non ramping ar RA NO EM Gateway Table of Contents cont Chapter 6 Chapter 7 Reference Documents Reference Documents Serial Numbers Specifications Power Supply Environmental Indication Agency Communications Control Output Signals Enclosure Size User Interface Ordering Information Declaration of Conformity How to Reach Us Chapter One
8. Process Value Input 2 register 104 as read only Auto Set Point 1 register 300 as read write Auto Set Point 2 register 319 as read write Alarm Status Output 3 register 110 with choice of Ok Alarm High Alarm Low or Alarm Error as read only Alarm Acknowledge register 110 with choice to clear alarm as write only Note Selecting Manual contro using the Operation Mode an input error or inputting Set Point values less than 30000 will disable Auto Set Points 1 or 2 Alarms not configured are not displayed Alarms can not be acknowledged while the alarm condition exists Series F4S F4D Operation Mode register 200 with choice of Auto or Manual as read only Input 1 Error register 101 with choice of Sensor Error or Ok as read only Input 2 Error register 105 with choice of Sensor Error or Ok as read only Input 3 Error register 109 with choice of Sensor Error or Ok as read only Process Value Input 1 register 100 as read only Process Value Input 2 register 104 as read only Process Value Input 3 register 108 as read only Auto Set Point 1 register 300 as read write Auto Set Point 2 register 319 as read write Alarm Status Output 2 register 102 with choice of Ok Alarm High Alarm Low Alarm High Latched Alarm Low Latched Alarm High Silenced Alarm Low Silenced Alarm High Latched Silenced Alarm Low Latched Silenced Waiting for in Range Alarm Alarm Disabled or Alarm Error as read
9. RTU specification is located at http Awww modicon com techpubs toc7 html or http Awww modbus org Serial Numbers Gateways are labeled with a unique serial number in numeric and bar code formats The serial number is embedded in the gateway firmware EM Gateway Features and Benefits e Ethernet Internet connectivity Operate amp monitor your process remotely e Browser Graphical User Interface GUI Operate amp monitor your process remotely with standard Web browsers e Dedicated Web page design Easy to understand and operate e Email alarm notification Reduced process monitoring costs 25 Chapter Seven Specifications Power supply e Voltage input 24 V ac dc 10 15 50 60 Hz 5 e Connection through 2 position removable screw style terminal block e 22to12 AWG e Power consumption 10 VA MAX e UL Approved Class 2 power supply required e Real time Clock backed by 3v lithium battery RAYOVAC BR1225 Environmental e Operating temperature range 0 to 60 C e Storage temperature range 40 to 70 C e Operating and storage humidity 0 to 90 non condensing Indication e Green LED for Ethernet connection e Green LED for Ethernet activity e Green LED for EIA 485 or ElA 232 activity Agency e CE Approved see Declaration of Conformity 61326 Industrial Immunity Class B Emissions Communications e MODBUS RTU communications e Both EIA 485 and EIA 232 supported at 9600 and 19200 baud e Connection through 5 posit
10. aded Thu Feb 14 23 37 08 2002 Display Setup M Enable Home page auto refresh interval 30 Time period of Home page auto refresh 5 9999 seconds Submit Reset Modbus Note Submitting any changes to the Modbus settings below will cause the EM Gateway to rediscover any serial devices Rescan Modbus Network Baud Rate fi 9600 Start Address E 1 247 End Address M 4 247 Maximum Nodes fi 1 16 Submit Reset Ethernet Network Setup Email Setup Clock Setup Network Statistics Serial Statistics Use this page to disable or enable automatic page refreshing or to change the time in between refreshes In addition you can force a rescan of the Modbus Network This will cause the Gateway to detect any new devices added to the serial network Set the baud rate of the network to 9600 or 19200 baud The value selected must match the value in all of the controllers on the serial network Up to 16 controllers may be scanned by the Gateway using the built in HTTP server Set a start address to the lowest address number of the controller on the serial network Set an end address to the highest address number of the controller on the serial network As an example you have your first controller set to address 23 and the last one set to 35 Set Start Address to 23 and End Address to 35 You can limit the number of controllers accessed by the Gateway by setting the Maximum Nodes value to less than 16 Lastly this page provides links
11. ature Process Value Configuration Temperature Process Value Units Input Filtermg Filter Value Filter Effe ctavity InfoSense Data TnfoSense Enabled TnfoSense Point 1 TnfoSense Point 2 TnfoSense Point 3 TnfoSense Point 4 Offsets Single offset value Fahrenheit bp Seconds l 00 0 00 0 00 0 TT F This page was loaded Tue Feb 24 09 44 08 2004 Control Loop Loop Algorithm Input Failure Parameters Failure Latching Output transition from Auto Mode closed loop to Failure Fixed Power Limits Set Point Thermocouple Set Point RTD Set Point Process On Off Parameters Hysteresis Temperature Hysteresis Process PID Parameters Prop Band Temperature Prop Band Process Tntegral Derivative Dead Band Heat Indirect Cool Direct Limit High 1500 0 F B a280 1472 0 oF pao 999 0 a ii Heat Indirect Cool Direct oF T Heat Indirect Cool Direct 5 0 2 sl 5 0 22 oF SE uaii 23 This page was loaded Tue Feb 24 20 26 22 2004 Process Alarm Parameters Alarm Process Low 32 0 oF Alarm Process High fi 500 0 oF Deviation Alarm Parameters Alarm Deviation Low Fa99 0 oF Alarm Deviation High 293 0 oF General Alarm Settings Alarm Hysteresis oF Latching Blocking Message Yes x 24 Chapter Six Reference Documents The MODBUS
12. cate compliance 89 336 EEC Electromagnetic Compatibility Directive EN 61326 1997 With A1 1998 Electrical equipment for measurement control and laboratory use EMC requirements Industrial Immunity Class B Emissions EN 61000 4 2 1996 With A1 1998 Electrostatic Discharge Immunity EN 61000 4 3 1997 Radiated Field Immunity EN 61000 4 4 1995 Electrical Fast Transient Burst Immunity EN 61000 4 5 1995 With A1 1996 Surge Immunity EN 61000 4 6 1996 Conducted Immunity EN 61000 4 11 1994 Voltage Dips Short Interruptions and Voltage Variations Immunity EN 61000 3 2 1995 With A1 3 1999 Harmonic Current Emissions EN 61000 3 3 1995 With A1 1998 Voltage Fluctuations and Flicker Use of an appropriately approved class 2 power source is required for compliance Jim Boigenzahn Winona Minnesota USA Name of Authorized Representative Place of Issue General Manager February 28 2002 Title of Authori Representative Date of Issue Signature of Authorized Representative 27 How to Reach Us Technical Assistance If you encounter a problem with your EM Gateway review all of your wiring and configuration information to verify that your selections are consistent with your application If the problem persists after checking the above you can get technical assistance from your local Watlow representative or by dialing 507 454 5300 An applications engineer will discuss your application with you Warranty This prod
13. ects Address Rejects Protocol Rejects ARP Rejects SMTP Server IP Send Queue Length Send Queue Max Send Queue Min Recv Queue Length Recv Queue Max Recv Queue Min Big Queue Length Big Queue Max Big Queue Min Little Queue Length Little Queue Max Little Queue Min The Network Statistics page monitors the health of the Ethernet network These numbers will help identify settings for the EM Gateway as well as when there are issues with wiring incorrect addresses or noise 7 3 37 91 255 255 224 0 7 3 63 250 00 03 AA 00 00 C1 128349 1207 0 127061 0 2089 28 0 1251 oOO0O00 on communication wires on the Ethernet side of the Gateway Chapter Five Controller Parameters and Registers The EM Gateway supports the following parameters for each type of controller when using an HTTP browser Series 96 non ramping Operation Mode register 200 with choice of Auto or Manual as read only Input Error register 101 with choice of Sensor Error or Ok as read only Process Value Input 1 register 100 as read only Process Value Input 2 register 105 as read only Auto Set Point 1 register 300 as read write Alarm Status Output 2 register 106 with choice of Ok Alarm High Alarm Low Alarm High Latched Alarm Low Latched Alarm High Silenced Alarm Low Silenced Alarm High Latched Silenced Alarm Low Latched Silenced Waiting for in Range Alarm Alarm Disabled or Alarm Error as read only Alarm Status Output
14. er information This information is automatically refreshed after 10 seconds by default You may change this refresh time using the appropriate page Network Services The EM00 GATE 0000 supports DHCP client autoIP and static IP for address assignment Normally you will not need to make any changes The user is able to configure preferences as to which services are used if available Intelligence is employed within the gateway to revert to backup IP assignment methods if the primary method is unavailable The gateway does support DNS client and Netbios name resolution Configuration information may be entered at the EM Gateway Network Display Setup page Email Alarm Notification The email function allows the user to send emails to four addresses alerting them of alarm conditions that have occurred on the controllers connected to the Gateway A button on the Graphical User Interface GUI allows the user to enable or disable this feature Emails can be generated whenever an alarm condition occurs for each controller An email acknowledge feature requires that the user acknowledge the email message by operating the email acknowledge button before additional email alarm messages can be generated for that controller For multiloop controllers only one email acknowledge feature is supported if more than one loop produces an alarm only the first alarm detected will generate an email until acknowledged You will need to configure your Gateway with y
15. h Latched Alarm Low Latched Alarm High Silenced Alarm Low Silenced Alarm High Latched Silenced Alarm Low Latched Silenced Waiting for in Range Alarm Alarm Disabled or Alarm Error as read only Alarm 1 Acknowledge register 312 with choice to clear alarm as write only Alarm 2 Acknowledge register 331 with choice to clear alarm as write only Note Alarms configured are displayed Alarms can not be acknowledged when the alarm condition still exists MicroDIN Operation Mode register 200 with choice of Auto or Manual as read only Input Error register 101 with choice of Sensor Error or Ok as read only Process Value Input 1 register 100 as read only Auto Set Point register 300 as read write Alarm Status Output 2 register 106 with choice of Ok Alarm High Alarm Low Alarm High Latched Alarm Low Latched Alarm High Silenced Alarm Low Silenced Alarm High Latched Silenced Alarm Low Latched Silenced Waiting for in Range Alarm Alarm Disabled or Alarm Error as read only Alarm Acknowledge register 331 with choice to clear alarm as write only Note Alarms configured are displayed Alarms can not be acknowledged when the alarm condition still exists Power Series Heat Sink Temperature in Degrees C register 1590 as read only Load Current in Amps RMS on Line 1 register 154 as read only Based on configuration Load Current in Amps RMS on Line 2 register 164 as read only Based on configuration Load Cu
16. ion removable screw style terminal block e 221012 AWG e Ethernet communications e Ethernet RJ45 Connector e 10BaseT per IEEE 802 3 Ethernet Standard e HTTP v1 1 e Modbus TCP e DHCP Auto IP Or Fixed IP Address e Email Alarm Notification Supports Windows browsers e Microsoft Internet Explorer 4 0 or newer e Netscape 4 0 or newer Control Output Signals Activity L E D for Ethernet communications per IEEE 802 3 Activity L E D for Serial communications Enclosure Size Dimensional Size L 3 75 in X W 1 in X H 2 5 in with cutouts for L E D s RJ45 port and power jack User Interface 3 L E D s to indicate operation status Ethernet link Ethernet traffic and Modbus traffic Ordering Information Order part number EM00 GATE 0000 26 Declaration of Conformity Gateway Products C Watlow Winona Inc 1241 Bundy Blvd Winona MN 55987 USA Declares that the following product Model Numbers EM00 GATE 0000 NGW0 0000 2400 and NGW0 0000 0000 Classification Communications interface card Installation Category Pollution degree Il Rated Voltage 24V acordc or5V dc Rated Frequency 50 60 Hz or dc Rated Power 10VA maximum NGW0 0000 0000 Requires use of a Ferrico NF130 Clamp on ferrite on all lines to pass Class B emissions Depending on end use setup this bead may or may not be necessary Meets the essential requirements of the following European Union Directives by using the relevant standards show below to indi
17. ntroller if you will be using only one controller provided that the controller has an EIA 232 port 3 Wire a 24 volt AC or DC power supply to the gateway terminals This is not polarity sensitive 4 Configure each controller to the same baud rate 9600 or 19200 from the front panel of the controller Set each controller s Modbus address to a unique number As an example set the first controller to address 1 the second to address 2 and so on 5 Power up the gateway controllers and PC 6 Start your Internet browser Enter the TCP IP address of the gateway into the browsers address field Two different addresses may be used to access the gateway Either EMxxxxxx where xxxxxx is the first six digits of the serial number or WATxxxxxx where xxxxxx is the last six digits of the gateways MAC address The MAC address is printed on a decal in the form xx xx XX XX XX XX 7 Select the Gateway Setup Page Enter User name new and Password user by default The Password can be changed on the Security Configuration screen 8 Configure the Baud Rate and range of controllers addresses to match those you configured in step four 9 Click on Rescan Modbus Network 10 Click on the back button of the browser to return to the previous page 11 Click on the refresh button of the browser and your controllers information should now be visible Note You must click on the refresh button within the browser to capture the latest controll
18. odbus Network to update the detection of controllers on the bus The Modbus network is automatically scanned every two minutes for new devices Chapter Four HTML Pages The section describes the pages available from the EM Gateway s Web server When the web page is first accessed you are prompted for a User name and Password The default User name is new The default Password is user These are case sensitive The user name and password may be changed on the security configuration page Connect to em000261 GatewaySetup htm User name E new m Password eooo IV Remember my password user cme l EM Gateway WATLOW Gateway Setup Software Revision 0 05 009 This page was loaded Thu Feb 24 23 36 43 2002 Device Modbus AM Input Input Process Auto Alarm Alarm Email Address Mode No Error Value Setpoint Status Ack Ack F4 1 Auto 1 Ok 100 120 Alarm 1 Ok 2 Ok 135 136 Series 982 2 Hold 1 Ok 78 78 Alarm 2 Ok 2 Ok Alarm 3 Ok This is the main page for monitoring the controllers on the Gateway You can click on values that are located within a box Entering in a new value may change these values In addition use Alarm Ack to clear alarms when a process value has returned within a safe operating range Use the Email Ack to reactivate future emails for this controller See the controller s user s manuals for details of Modes Errors and Alarm operation 10 EM Gateway Setup This page was lo
19. only Alarm Status Output 3 register 106 with choice of Ok Alarm High Alarm Low Alarm High Latched Alarm Low Latched Alarm High Silenced Alarm Low Silenced Alarm High Latched Silenced Alarm Low Latched Silenced Waiting for in Range Alarm Alarm Disabled or Alarm Error as read only Alarm 1 Acknowledge register 312 with choice to clear alarm as write only Alarm 2 Acknowledge register 331 with choice to clear alarm as write only Note Alarms configured are displayed Alarms can not be acknowledged when the alarm condition still exists Series F4P Operation Mode register 200 with choice of Auto or Manual as read only Input 1 Error register 101 with choice of Sensor Error or Ok as read only Input 2 Error register 105 with choice of Sensor Error or Ok as read only Input 3 Error register 109 with choice of Sensor Error or Ok as read only Process Value Input 1 register 100 as read only Process Value Input 2 register 104 as read only Process Value Input 3 register 108 as read only Auto Set Point register 300 as read write Alarm Status Output 2 register 102 with choice of Ok Alarm High Alarm Low Alarm High Latched Alarm Low Latched Alarm High Silenced Alarm Low Silenced Alarm High Latched Silenced Alarm Low Latched Silenced Waiting for in Range Alarm Alarm Disabled or Alarm Error as read only Alarm Status Output 3 register 106 with choice of Ok Alarm High Alarm Low Alarm Hig
20. our SMTP server name or address A DNS server address must also be configured if using a SMTP name Contact your system administrator if you don t know the SMTP name or address Data Logging The gateway provides no explicit means of data logging Data can be polled via Modbus TCP by an external PC program Consider WatView from Watlow for your setup data logging and graphing needs Control Monitoring and Configuration The gateway provides a means of monitoring the current process value for analog inputs of each controller using a built in HTTP server It also provides a means of monitoring the present alarm status of each controller Additionally you may monitor and change control set points for control loops of each controller The gateway is capable of supporting Watlow Series 96 non ramping 97 981 982 988 989 998 999 F4S F4D F4P MicroDin Power Series CLS200and SD non ramping controllers with up to 16 controllers in any combination The gateway is capable of automatically determining when a controller is connected to the serial bus It will identify the model and address of each controller Controllers with duplicate Modbus addresses will be ignored by the gateway You can configure the baud rate of the EIA 485 or EIA 232 bus You may also specify which controller addresses are scanned under the EM Gateway Setup page The gateway supports from 1 to 16 controllers in any combination of supported model numbers Select Rescan M
21. rrent in Amps RMS on Line 3 register 174 as read only Based on configuration Note Display of current on lines 1 2 and 3 depends on the number of zones the installed options and the load type CLS200 Series Loop 1 to 16 if available Operation Mode register 264 to 279 with choice of Auto or Manual as read only Input Error registers 660 to 675 with choice of Ok TC Reversed TC Short TC Open RTD Open or RTD Short as read only Process Value registers 363 to 378 as read only Auto Set Point registers 330 to 345 as read write Alarm Status registers 660 to 675 with choice of Ok Low Deviation High Deviation Low Process or High Process as read only Alarm Acknowledge registers 8311 to 8326 with choice to clear alarm as write only Note Alarms configured are displayed Alarms can not be acknowledged when the alarm condition still exists Note The Communication Specifications manual list absolute registers which are the relative register with 40001 added to them As an example relative register 264 is absolute register 40265 Series SD non ramping Operation Mode register 25 with choice of Auto or Manual as read only Input Error registers 24 with choice of Ok or Error as read only Process Value registers 20 21 as read only Auto Set Point registers 27 28 as read write Alarm 1 Status registers 29 and 30 of Alarm 1 Ok Alarm 1 Low Alarm or Alarm 1 High Alarm as read only Alarm 2
22. rt Source Email Address Coo it Example joe_service company com Email Recipient 1 Eo y Example 3125554444 pager com Email Recipient 2 O E Example anyone yahoo com Email Recipient 3 Leave blank if unused Email Recipient 4 O Leave blank if unused Location Info Appended to Email Submit Reset Use this page to enable notification and configure the addresses for email recipients These recipients will receive an email when an alarm occurs on any controller Contact your IS administrator for questions regarding these settings 13 Now EM Gateway Clock Setup This page was loaded Thu Feb 24 23 38 06 2002 Current EM Gateway Time 14 Feb 2002 13 35 42 Year 2002 Month Feb Date faa Hour EE Minute EJ Second a2 Submit Reset Use this page to update the time and date stored in the Gateway This information is used to identify the time and date of alarms when emails are sent EM Gateway Serial Stats This page was loaded Thu Feb 24 23 38 53 2002 Device Timeout Retry CRC Bad Good Address Errors Errors Errors Polls Polls Eus 1174 1174 1174 1174 1174 1174 1174 1174 1174 1174 1167 1174 1174 1174 1174 1174 o ON OOA OMN ak ok o ke A O N O r o O oomlmcODUUCUCcUlUCCUrlLUCOOUCCOTOCCOT OCT CTC TI i H 9 DC O oO O G DUOGO OGOGOQOOGOO GOG OGOGO OG G O O O O O O O OGD O O OO O OG oo O O O O O aO O COT O O CO O OG D O G O O O OG O OOl OOHO I k e gt
23. s of updating the program memory of controller devices such as flashing new information into the Series F4 Chapter Two Installation amp Wiring EIA 485 Wiring EMO00 GATE 0000 Ethemet Gateway Sari umbar 1OODOCKY WW Browse at hiip Ev000000 MAC Airne OOOO T R T R 24 VAC or DC Com Ethernet RJ45 EIA 232 Wiring EIA TIA 232 DB 9 Pinout 2 receive 3 transmit 24 VAC or DC 5 common Ethernet RJ45 UL Approved Class 2 power supply required EIA TIA 232 DB 25 Pinout 2 transmit 3 receive 7 common 24 VAC or DC Ethernet 10 11 12 13 2 23 24 25 EM00 GATE 0000 Ethemet Gat leway Modbus Data Protocol Serial Number Pin 1 THR Ethernet 24 Volt Input RJ45 Power 2 T IR Ethernet Fihemet 3 Com in 4mo LED 5 RXD Dimensions are in inches Chapter Three Configuration Getting Started Perform these steps 1 Connect the EM00 GATE 0000 gateway to your computer s Ethernet port using a cross wired RJ45 cable or connect the EM00 GATE 0000 to a hub or network using a straight wired RJ45 Category 5 cable The EM00 GATE 0000 is limited to a 10BaseT connection and will not work on an Ethernet port set for 100BaseT only Use of a 10 100 hub will overcome this issue if your PC has only a 100BaseT port 2 Wire the temperature controllers to the gateway s EIA 485 port You may connect the gateway s EIA 232 port to a co
24. uct is warranted free from defects in material and workmanship for 36 months after delivery to the first purchaser for use providing that the units have not been misapplied Since Watlow has no control over their use and sometimes misuse we cannot guarantee against failure Watlow s obligations hereunder at Watlow s option are limited to replacement repair or refund of purchase price and parts that upon examination prove to be defective within the warranty period specified This warranty does not apply to damage resulting from transportation alteration misuse or abuse Returns e Call or fax Customer Service for a Return Material Authorization RMA number before returning any product Put the RMA number on the shipping label and provide a written description of the problem e Arestocking charge of 20 of the net price is charged for all standard units returned to stock Your Feedback Your comments or suggestions on this manual are welcome please send them to Technical Writer Watlow Winona 1241 Bundy Blvd P O Box 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507 Watlow Winona Inc copyrights the EM User s Manual February 2002 with all rights reserved 2206 28
25. upports the TCP IP stack At the application layer it has an HTTP web and Modbus server The HTTP server will provide current controller status from the virtual image via HTML The HTTP server provides a means of changing some runtime parameters via HTML The TCP IP stack supports DHCP client AutolP static IP DNS client and Netbios name resolution The 10BaseT connector is an RJ45 per the IEEE 802 3 specification The EM00 GATE 0000 can be used as a bridge for Modbus RTU messages This is concurrent with all other communicating functions In this scenario the gateway simply passes the request that comes in on the Ethernet connection through to the EIA 485 or EIA 232 connection When the response is returned from the controller it is sent back on the Ethernet connection No processing of the packet contents is necessary to bridge the two physical layers Block Diagram of Gateway PowerSource Modbus D gt Modbus TCP IP RU lt b m g gt q S Q TFTP GATEWAY D Client ka vu WEB Poll Server Engine Program Upgrades The gateway has a TFTP server for the purposes of reprogramming the program memory A program update will be initiated when a TFTP client residing on a PC begins to write a new program file to the gateway TFTP server When reprogramming the program memory all other gateway services are unavailable The gateway provides no mean