Home
        E7 Metasys® N2
         Contents
1.     1 3  Metasys N2 Set Up            UU T u                1 5    Installation 1 1    This page intentionally left blank     Installation 1 2    Installation Check Sheet    The following is a quick reference guide to the installation and configuration of the E7 drive with the Metasys N2 protocol  Make a copy of  this page and check off each item as it is completed  For detailed information please refer to the detailed sections that follow     1  Unpack the drive and verify that all components are present and undamaged     2  Connect power to the drive and verify that the drive functions  This includes running the drive in    Hand    mode from the  digital operator without the network selected or connected  Refer to the E7 User Manual for more information on  connecting and operating the drive     3  Remove power from the drive and wait for the charge lamp to be completely extinguished  Wait at least five additional  minutes after all indicators are off  Measure the DC bus voltage and verify that it is at a safe level     Connect the drive to the Metasys N2 communication network  Refer to Chapter 2     Network Connection for the Metasys  N2 connection procedure     5  Ifthis drive is either the first or the last device on the network  set the terminating resistor switch  S1 1  to ON  If this  device is not the first or last device on the network  set the terminating resistor switch  S1 1  to OFF  Refer to Chapter 2      Network Connection for details     6  Configure the Meta
2.   the value to the drive  An ENTER or ACCEPT command does not need to be sent for the data to be taken by the drive  The  behavior of the write is the same as with the digital operator  If the drive is running  there are a limited number of drive  parameters that can be written to     Example     Writing a value of 387  183 hex  to AO 31 specifies drive parameter b1 04  Writing a value of 1 to AO 32 enables the drive for  reverse run     Mailbox Function 5 3    This page intentionally left blank     Mailbox Function 5 4    Chapter 6 E7 Bypass Applications    This chapter lists the typical parameters for a bypass engineered drive     Bypass Engineered Drive Parameter Settings                 6 3    E7 Bypass Applications 6 1    This page intentionally left blank     E7 Bypass Applications 6 2    Bypass Engineered Drive Parameter Settings    For many applications  the drive is integrated into a bypass or engineered package  This type of package typically features an enclosure  with contactors that allow the user to run the motor from line power  bypass mode  or from the drive  drive mode   This package also  provides the flexibility for interfacing normally closed safety interlocks  fire status  freeze status  vibration sensors  etc   which stop the  drive if the contacts open        Typical Parameter Settings    A bypass engineered drive is supplied with a list of parameters and their default values  Use the table below to record any parameter  modifications for this particula
3.  Enabled   Enter key Not Required from Keypad        Cumulative Operation Time Select  1     Time    RUN        Keypad COPY Function Select  1     Enabled                                                                       E7 Bypass Applications 6 4    Appendix A Troubleshooting    This appendix describes the steps necessary to troubleshoot the E7 drive  communicating on a Metasys N2 network     Troubleshooting Check List                                                A 3  Installing and Configuring Metasys   2                             A 5  Wiring And Cabling                                                                 7    Drive Faults    Troubleshooting    1    This page intentionally left blank     Troubleshooting    2    Troubleshooting Check List            OOCL LI    1     10     11     12     Connect power to the drive and verify that the drive operates correctly in HAND mode from the digital operator without  being connected to the network  Record the drive model number and    spec    number at this time     Model Number  CIMR E7U  e g  CIMR E7U20P4         SPEC  Number   e g  20P41A        Record the control board part number     ETC      e g         618021 52012             network devices have unique addresses and drives are addressed between 0 255  0 FE hex      Drive address     The Run Stop command source parameter  b1 02 is set correctly     b1 02     The Speed Command source parameter  b1 01  is set correctly     51 01     The correct cable type is use
4.  FUNCTION INPUT 4  H1 04        MULTI FUNCTION INPUT 5  H1 05                              PANEL LOCK          LOCAL REMOTE AND  STOP RESET KEYS  ENABLED    LOCAL REMOTE AND STOP RESET  KEYS DISABLED          COMMUNICATION FAULT ENABLE                 NOT ACTIVATED IF  CABLE LOSS OCCURS    Cable Loss Behavor 4 5              ACTIVATED IF CABLE LOSS  OCCURS       This page intentionally left blank     Cable Loss Behavior 4 6    Chapter 5 Mailbox Function    This chapter defines the Metasys N2 points that read and write E7 drive  parameters     Mailbox Function Points                                                     5 3    Mailbox Function 5 1    This page intentionally left blank     Mailbox Function 5 2    Mailbox Function Points        Reading a Drive Parameter    Two points are defined for reading any drive parameter     AO30  Specifies the parameter to be read from the E7 drive   AI38 Reports the value of the parameter specified in AO 30   When this point is read  it retrieves data from the parameter and sends it to the controller  Example     Writing a value of 387  183 hex  to AO 30 specifies drive parameter b1 04  Reading AI 38 returns the current setting of  parameter b1 04 to the controller        Writing to a Drive Parameter    Two points are defined for writing to any drive parameter     AO31  Specifies the parameter to be written to    AO32 Entry location of the value to be written to the parameter specified in AO 31  When this point is written to  it will write
5.  changed blinks     ATA  NTE     DRIVE      Main Menu     Select the Drive Mode     DRIVE  Rdy  Frequency Ref  0 00Hz  Enter the Drive Mode  0 00Hz  0 004       Installation 1 7    This page intentionally left blank     Installation 1 8    Chapter 2 Network Connection    This chapter discusses how to connect the E7 drive to a Metasys N2 network     Physical Connection                                                            2 3    Network Connection 2 1    This page intentionally left blank     Network Connection 2 2    Physical Connection    Communication on the network is half duplex  two wire RS 485  with communication parameters fixed at 9600 baud  eight data bits  no  parity and one stop bit  The network cable is a shielded two conductor cable         Network Connection    W Connect a jumper between R  and S  and R  and S      ENISCISPTATTAZI                RR      5 82 53 5 55 55 8                        5  5      Figure 2 1       7 Terminal Block Jumper Connections       W Connect the positive     cable lead to 5   Connect the negative     cable lead to S                                               RI M  Ei  15152 59154155 158 5                                         Figure 2 2     Metasys   2 Network Cable Connections    Network Connection 2 3        Network Termination    A bus terminating resistor of 1100 is available on each drive terminal board and can be applied to the Metasys N2 communication bus  by setting switch S1 1 to the ON position  In a multi node s
6.  result in damaging the drive or  building equipment         Programming the E7 Drive for Metasys N2    The procedure for programming the E7 drive for communication on a Metasys N2 network is shown in the table below     Table 1 2   Drive Programming Procedure for Metasys N2    Key Operation Digital Operator Display     DRIVE   Frequency Ref  Apply Power E     ADV      Main Menu       Select the Programming Menu    Programming     ADV   Initialization  Enter the Programming Menu    Select Language       Installation 1 5    Table 1 2   Drive Programming Procedure for Metasys N2    Key Operation Digital Operator Display     ADV   Reference Source  Select the Reference Source  for Serial Communication 952  Serial Com    1       gt      5   gt               Run Source    m  z            2     Select the Run Source for  Serial Communication      Serial Com               gt     ESC  X    m              ADV   Protocol Select  Select the N2  Metasys N2   Communication Protocol    N2  Metasys      o        gt     5   gt     m     4        2    5         gt     m  z  4        D       Installation 1 6    Table 1 2   Drive Programming Procedure for Metasys N2    Key Operation Digital Operator Display     ADV     Select the Serial Communication Serial Comm Adr    Address Between 0 and FE Hex   Each Device On The  Metasys N2 Network Must  Have A Unique Address      ADV   Serial Baud Rate    Select the Serial Baud Change value by pressing     Rate of 9600 Baud                The digit to be
7.  to a Metasys N2 network and facilitates the exchange of data                  This document pertains to the Yaskawa E7 drive  Additionally  in this document  the word    inverter        ac drive  and    drive    may be used  interchangeably     To ensure proper operation of this product  read and understand this manual  For details on installation and operation of the E7 drive or  details on specific E7 parameters  refer to the E7 User Manual  document reference TM E7 01  For details on E7 MODBUS  communications  refer to      E7 MODBUS  Technical Manual  document reference        7 11       technical manuals and support files  are on the CD that was supplied with the drive and available for download at www drives com     For more information on the Metasys N2 protocol  please visit www jci com     GPD is a trademark of Yaskawa  Inc   MODBUS   is a registered trademark of Schneider Automation  Inc     Metasys   N2 is a trademark of Johnson Controls  Inc     Table of Contents    Chapter 1                              1 1  Installation Check                                       1 3                Set  Ups               tire                     erent ets Reames Mouton diede 1 5   Chapter 2 Network Connection                                                            2 1  Physical Connection                         EAE                   2 3   Chapter 3      Drive Functions                                         J                    3 1                         3 3  Cable Loss C
8. 7  YASKAWA    E7                       Technical Manual    Models  CIMR E7U  Document Number  TM E7 22       This page intentionally left blank    This page intentionally left blank    Warnings and Cautions    This Section provides warnings and cautions pertinent to this product that if not  heeded  may result in personal injury  fatality or equipment damage  Yaskawa is  not responsible for consequences of ignoring these instructions         WARNING    YASKAWA manufactures component parts that can be used in a wide variety of industrial applications  The selection and application of  YASKAWA products remain the responsibility of the equipment designer or end user  YASKAWA accepts no responsibility for the way its  products are incorporated into the final system design  Under no circumstances should any YASKAWA product be incorporated into any  product or design as the exclusive or sole safety control  Without exception  all controls should be designed to detect faults dynamically  and to fail safely under all circumstances  All products designed to incorporate a component part manufactured by YASKAWA must be  supplied to the end user with appropriate warnings and instructions as to that part s safe use and operation  Any warnings provided by  YASKAWA must be promptly provided to the end user  YASKAWA offers an express warranty only as to the quality of its products in  conforming to standards and specifications published in the YASKAWA manual  NO OTHER WARRANTY  EXPRESS OR IM
9. 7  Yongchang North Street  Beijing Economic  amp  Technological Development Area   Beijing 100076 China  Phone  86 10 6788 0551 Fax  86 10 6788 2878   YEA  TAICHUNG OFFICE IN TAIWAIN   B1  6F  No 51  Section 2  Kung Yi Road  Taichung City  Taiwan  R O C   Phone  886 4 2320 2227        886 4 2320 2239    Version  3010       Data subject to change without notice  Yaskawa Electric America  Inc     
10. BOTEC GmbH  Kammerfeldstrabe 1  85391 Allershausen  Germany  Phone  49 8166 900 Fax  49 8166 9039    YASKAWA ELECTRIC UK LTD     1 Hunt Hill Orchardton Woods Cumbernauld  G68 9LF  Scotland  United Kingdom  Phone  44 12 3673 5000 Fax  44 12 3645 8182    YEA Document Number  TM E7 22    8 1 2002    Y  YASKAWA    YASKAWA ELECTRIC KOREA CORPORATION  Paik Nam Bldg  901 188 3  1 Ga Euljiro  Joong Gu  Seoul  Korea  Phone  82 2 776 7844 Fax  82 2 753 2639       YASKAWA ELECTRIC  SINGAPORE  PTE  LTD   Head Office  151 Lorong Chuan   04 01  New Tech Park Singapore 556741  Singapore  Phone  65 282 3003 Fax  65 289 3003    TAIPEI OFFICE  AND YATEC ENGINEERING CORPORATION   10F 146 Sung Chiang Road  Taipei  Taiwan  Phone  886 2 2563 0010 Fax  886 2 2567 4677    YASKAWA JASON  HK  COMPANY LIMITED  Rm  2909 10  Hong Kong Plaza  186 191 Connaught Road West  Hong Kong  Phone  852 2803 2385 Fax  852 2547 5773    BEIJING OFFICE   Room No  301 Office Building of Beijing International Club   21 Jianguomanwai Avenue  Beijing 100020  China   Phone  86 10 6532 1850 Fax  86 10 6532 1851    SHANGHAI OFFICE  27 Hui He Road Shanghai 200437 China  Phone  86 21 6553 6600 Fax  86 21 6531 4242    SHANGHAI YASKAWA TONJI M  amp  E CO   LTD   27 Hui He Road Shanghai 200437 China  Phone  86 21 6533 2828 Fax  86 21 6553 6677    BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO   LTD   30 Xue Yuan Road  Haidian  Beijing 100083 China  Phone  86 10 6232 9943 Fax  86 10 6234 5002    SHOUGANG MOTOMAN ROBOT CO   LTD    
11. EVERSE MONITOR  BI 2  shows the current direction         CAUTION    Improper drive direction may damage HVAC equipment if parameter B1 04  Reverse Enable  is  improperly set  B1 04   0      Lock the E7 panel    Locking the panel prevents the user from using the HAND and OFF keys locally at the drive panel  PANEL LOCK  BO 10  can  be commanded to lock and unlock the panel     Digital Inputs    MULTI FUNCTION INPUT 1  BO 5  through MULTI FUNCTION INPUT 5  BO 9  are physical digital inputs on the drive   They can be set either by external devices  such as limit or pressure switches  or by the network  Their function depends on how  the drive has been programmed  Refer to the E7 User s Manual section on Multi Function Inputs  H1 01 through H1 05  for  detailed information on the use and programming of the multi function inputs  The multi function input status can be monitored  through MULTI FUNCTION INPUT 1 MONITOR  BI 14  through MULTI FUNCTION INPUT 5 MONITOR  BI 19   The  MULTI FUNCTION INPUT   MONITOR state is the logical OR of the serial command value  BO 5 through BO 9  and the state  of the external connection         CAUTION    Because the multi function inputs can be set by both external devices or over the network  care must  be taken when connecting the multi function inputs to external devices to ensure correct system  operation     Digital Outputs    MULTI FUNCTION OUPUT 1  BI 10  through MULTI FUNCTION OUPUT 3  BI 12  are physical digital outputs on the drive   The
12. P MONITOR    Default          Off  0  State  STOPPED    On  1  State  RUNNING       FORWARD   REVERSE MONITOR    FORWARD    REVERSE       DRIVE READY MONITOR    NOT READY    READY       FAULT MONITOR    NOT FAULTED    FAULTED       ZERO SPEED    NOT ZERO SPEED    ZERO SPEED       SPEED AGREE    NOT SPEED AGREE    SPEED AGREE       MINOR FAULT    NO MINOR FAULT    MINOR FAULT       MAJOR FAULT    NO MAJOR FAULT    MAJOR FAULT       DRIVE COMMUNICATION  ERROR MONITOR    NO ERROR    ERROR       MULTI FUNCTION OUTPUT 1  H2 01        MULTI FUNCTION OUTPUT 2  H2 02        MULTI FUNCTION OUTPUT 3  H2 03        SAFETY INTERLOCK MONITOR    SAFETY CLEAR  TERMINAL 3 CLOSED    SAFETY SET  TERMINAL 3 OPEN       HAND   AUTO REFERENCE MONITOR    REMOTE    LOCAL       MULTI FUNCTION INPUT 1 MONITOR    OFF    ON       MULTI FUNCTION INPUT 2 MONITOR    0  0  0  0  0  0  0  0  0  0  0  0  0  0  0    OFF    ON       MULTI FUNCTION INPUT 3 MONITOR    c                                MULTI FUNCTION          4 MONITOR                BI 19 MULTI FUNCTION INPUT 5 MONITOR                Metasys   2 Binary Output  BO  Summary    Object ID    Object Name  RUN FORWARD COMMAND    Default          Off  0  State  STOP    On  1  State  FORWARD       RUN REVERSE COMMAND    STOP    REVERSE       SERIAL FAULT  EF0  COMMAND    NO FAULT    FAULT       FAULT RESET COMMAND    NO RESET    RESET       MULTI FUNCTION INPUT 1    1 01        MULTI FUNCTION INPUT 2  H1 02        MULTI FUNCTION INPUT 3  H1 03        MULTI
13. PLIED  IS  OFFERED  YASKAWA assumes no liability for any personal injury  property damage  losses  or claims arising from misapplication of its  products         WARNING       Read and understand this manual before installing  operating  or servicing this drive  All warnings  cautions  and instructions must be  followed  Qualified personnel must perform all activity  The drive must be installed according to this manual and local codes       Do not connect or disconnect wiring while the power is on  Do not remove covers or touch circuit boards while the power is on  Do  not remove or insert the digital operator while power is on        Before servicing  disconnect all power to the equipment  The internal capacitor remains charged even after the power supply is turned  off  Status indicator LEDs and Digital Operator display will be extinguished when the DC bus voltage is below 50 VDC  To prevent  electric shock  wait at least 5 minutes after all indicators are OFF and measure DC bus voltage and verify that it is at a safe level       Do not perform a withstand voltage test on any part of the unit  This equipment uses sensitive devices and may be damaged by high  voltage        The drive is not suitable for circuits capable of delivering more than the specified RMS symmetrical amperes  Install adequate branch  short circuit protection per applicable codes  Refer to the specification  Failure to do so may result in equipment damage and or  personal injury       Do not connect una
14. d  Mfg  P N                cable connections are correct per device schematic and are secure         cables have been checked for continuity  There are no breaks or shorts    The network is correctly terminated    The shield is continuous throughout the network and is properly grounded on each end   The network cable is routed away from any high voltage cable s  or source s           network devices have been tested for conformance with the Metasys N2 specification     Troubleshooting A 3    This page intentionally left blank     Troubleshoating    4    Installing and Configuring Metasys N2    The following is a short guide to troubleshooting the Metasys N2 installation and configuration  It highlights some of the most common  issues faced when diagnosing and correcting issues associated with the startup and operation of an E7 drive with Metasys N2 building  automation network  While most of the information is centered on the application of the drive  the guidelines presented are applicable in  most Metasys N2 networks     Diagnosis of network fault issues will typically fall into three categories  1  Installation set up of Metasys N2  2  wiring and cabling issues   and 3  network configuration diagnostics  Each of these areas will be discussed after to help resolve common problems associated in  Metasys N2 network troubleshooting         Drive Operates Correctly Without Network Enabled    Before programming the drive for Metasys N2 communication  verify that the drive functi
15. eout interval  the drive s speed  command  AO 1  is set to 0  The stopping method is determined by the setting of H5 04  An EF0 drive fault will be set           5 04   0 selects Ramp to Stop  The deceleration time or the slope of the ramp is determined by the setting of drive  parameter C1 02   H5 04   1 selects Coast to Stop  The drive does not attempt to control the rate of deceleration     H5 04   2 selects Emergency or Fast Stop  The deceleration time is determined by the setting of drive parameter   1 09         CAUTION    The behavior of the drive at cable loss is controlled by parameter H5 04  This drive parameter works  with the points as described in the table above to determine how the drive will respond to a cable  loss  If the cable loss fault is disabled  the drive will continue in its last state  if running the drive  will continue to run at the last commanded frequency       Fault  EFO     In this mode  Cable Loss Timeout  AO 21  is set to the desired interval and Communication Fault Enable  BO 11  is set to    On     If  the time between messages exceeds the timeout interval  an            fault is declared and the drive stops  The stopping method is  controlled by the setting of H5 04 and is described above  Cable Loss Speed  AO 22  is ignored     Network Connection 3 5    E7 Drive Fault Numbers      06             GromdFadt GE      8       ppDCBsOvevk OV       9  Ovehet OH          Network Connection 3 6    Chapter 4 Metasys N2 Point  Database    This chapt
16. er shows the Metasys N2 point database  This database features 100  logical points  38 Analog Inputs  Al   32 Analog Outputs  AO   19 Binary Inputs                 11 Binary Outputs  BO   These points configure  control or monitor the  operation of the drive     Metasys     Analog Input  AI                                            4 3  Metasys     Analog Output  AO  Summary                        4 4  Metasys   2 Binary Input        Summary                             4 5  Metasys     Binary Output  BO  Summary                         4 5    Cable Loss                4 1    This page intentionally left blank     Cable Loss Behavior 4 2    Metasys N2 Analog Input  AI  Summary      x4          sxwuromwemg       OSOSOSCSCSSCSCSCSCSC            C  C      Y                  arse  READ Paramererpata ____   LLL                     Cable Loss Behavor 4 3    Metasys N2 Analog Output  AO                                   4  ___                                        20                  REFERENCE OPERATION MODE SELECT            m          _RUNOPERATION Mopesetecr       r            0m                       o                  FREQUENCY COMMAND LOWERLIMIT              o   on    om                                 _           o          05                    o  t oss    PI FEEDBACK REFERENCE  PI FEEDBACK REFERENCE  PI FEEDBACK REFERENCE       MISSING DETECTION TIME                      Cable Loss Behavior 4 4    Metasys   2 Binary Input  BI  Summary    Object ID    Object Name  RUN   STO
17. ions  CE Memobus Communication Error MS B 4 5    stopped communicating Verify all Metasys N2 software configurations        E7 Drive Faults       Table A 7       7 Drive Faults     _____6 Ground Fat GR     8 DC Bus Overvolt       S    o Overheat OM        Troubleshooting    8    E7                         YASKAWA ELECTRIC AMERICA  INC    Drives Division   16555 W  Ryerson Rd   New Berlin  WI 53151  U S A    Phone   800  YASKAWA  800 927 5292  Fax   262  782 3418  Internet  http   www drives com    YASKAWA ELECTRIC AMERICA  INC    Chicago Corporate Headquarters   2121 Norman Drive South  Waukegan  IL 60085  U S A   Phone   800  YASKAWA  800 927 5292  Fax   847  887 7310  Internet  http   www yaskawa com    MOTOMAN INC    805 Liberty Lane  West Carrollton  OH 45449  U S A   Phone   937  847 6200 Fax   937  847 6277  Internet  http   www motoman com    YASKAWA ELECTRIC CORPORATION   New Pier Takeshiba South Tower  1 16 1  Kaigan  Minatoku  Tokyo  105 0022  Japan  Phone  81 3 5402 4511 Fax  81 3 5402 4580   Internet  http   www yaskawa co jp    YASKAWA ELETRICO DO BRASIL COMERCIO LTDA    Avenida Fagundes Filho  620 Bairro Saude Sao Paolo SP  Brasil CEP  04304 000  Phone  55 11 5071 2552 Fax  55 11 5581 8795   Internet  http   www yaskawa com br          YASKAWA ELECTRIC EUROPE GmbH  Am Kronberger Hang 2  65824 Schwalbach  Germany  Phone  49 6196 569 300 Fax  49 6196 888 301    MOTOMAN ROBOTICS AB  Box 504 538525  Torsas  Sweden  Phone  46 486 48800 Fax  46 486 41410    MOTOMAN RO
18. ir function depends on how the drive has been programmed  Refer to the E7 User s Manual section on Multi Function  Outputs  H2 01 through H2 03  for detailed information on the use and programming of the multi function outputs     Loop gain    PI PROPORTIONAL GAIN       4  and PI INTEGRAL TIME  AO 5  are the gain and integral time parameters used by the E7   The E7 PI loop is structured differently than the Metasys loop  Refer to the E7 User s Manual section on PID for information on  how the E7 PI loop functions     Reading and resetting faults    FAULT MONITOR  BI 4  and DRIVE READY MONITOR  BI 3  show the current status of the drive  FAULT CODE  AI 10   contains the code for the most current fault  LST FLT CODE  AI 19  contains the code for the previous fault  See table below for  descriptions of the fault codes  The drive fault can be reset through FAULT RESET COMMAND  BO 4   The FAULT RESET  COMMAND is only available when the RUN FORWARD COMMAND and the RUN REVERSE COMMAND are both OFF     Network Connection 3 3    Cable Loss Configuration and Behavior    This section describes the configurable cable loss feature of the drive  This feature offers a user maximum flexibility in determining the  drive s response to a loss of communication         Drive Behavior At Loss of Communication    After some interval without receipt of a message  the drive can be configured to respond in one of the following manners   Continue at last speed  Continue at last speed with Alarm  Contin
19. onfiguration and                                                                                 3 4  E7 Drive Fault              S u I U            O          Er Oleg el          3 6   Chapter 4 Metasys N2 Point                                                                 4 1  Metasys N2 Analog Input  Al                                   4 3  Metasys N2 Analog Output  AO                                                                         4 4  Metasys N2 Binary Input                                       4 5  Metasys   2 Binary Output  BO                                                                         4 5   Chapter 5 Mailbox                                                 nnna 5 1  Mailbox Function Points                       eet rer ibt eti ra e be        DM RO PER eek sere 5 3   Chapter 6 E7 Bypass                                                                               6 1  Bypass Engineered Drive Parameter Settings                                                     6 3   Appendix A Troubleshooting                                                                   1  Troubleshooting Check                                3  Installing and Configuring Metasys   2                        4   2   5  WINGA ni   mm 7  bags mm 8    This page intentionally left blank     Chapter 1 Installation    This chapter covers the initial set up procedure for the E7 drive on a Metasys N2  network     Installation Check Sheet                                                 
20. ons properly  Refer to the E7 User Manual   TM E7 01  for information on the drive s installation and operation         Network Cable Is Connected Correctly And Securely      Connect a jumper between R  and S  as well as R  and S   Connect network cable to terminals S  and S                  SN SC SP  A1  A2   VAC   V    54  55156  57              5152       Shield       Figure A 1     E7 Metasys N2 Network Connections        Run Stop Operation Parameter Is Set Correctly    The run stop operation parameter needs to be set for    Serial Com      Table A 1   Run Stop Operation Parameter  Parameter Number Setting Choices Setting Descriptions             Serial Com  Metasys NZ        Troubleshooting    5        Speed Command Operation Parameter Is Set Correctly    The speed command operation parameter needs to be set for  Serial Com      Table A 2   Speed Command Operation Parameter  Parameter Number Setting Choices Setting Descriptions          Serial Com  Metas ND            Correct and Unique Network Address    Each device on a Metasys N2 network requires its own unique address  The drive also needs to be programmed to accept the Metasys N2    protocol     Table A 3   Serial Communication Device Address Parameter  Parameter Number Setting Range Setting Description    H5 01 0 to 20 hex Serial communication device address  us o       mow       Troubleshooting A 6    Wiring And Cabling        The network cable is the correct type           Cable Lengths Are Within Specified Limit
21. pproved LC or RC interference suppression filters  capacitors  or over voltage protection devices to the output of  the drive  Capacitors may generate peak currents that exceed drive specifications        To avoid unnecessary fault displays  caused by contactors or output switches placed between drive and motor  auxiliary contacts must  be properly integrated into the control logic circuit     W  YASKAWA is not responsible for any modification of the product made by the user  doing so will void the warranty  This product  must not be modified     Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power   To meet CE directives  proper line filters and proper installation are required     Some drawings in this manual may be shown with protective covers or shields removed  to describe details  These must be replaced  before operation     Observe Electrostatic Discharge Procedures when handling the drive and drive components to prevent ESD damage     The attached equipment may start unexpectedly upon application of power to the drive  Clear all personnel from the drive  motor and  machine area prior to applying power  Secure covers  couplings  shaft keys  machine beds and all safety equipment before energizing  the drive     Introduction    This manual explains the specifications and handling of the Metasys N2 protocol for the Yaskawa model E7 drive  The E7 drive with the  Metasys N2 protocol selected  connects the E7 drive
22. r application     Table 7 1   Typical Bypass Engineered Drive Parameters    Parameter Bypass Settings  Number Default User    Description    Input Voltage  VAC       default dependent on drive model        Maximum Output voltage  VAC       default dependent on drive mode l       Motor Rated Current  FLA            default dependent on drive model        Motor Rated Power  kW       default dependent on motor        Motor Rated Current  FLA   A       default dependent on motor        Parameter Access Level  2     Advanced        Frequency Reference Source  dependent on bypass options specified        Command Source  dependent on bypass options specified        Stopping Method  0     Ramp to Stop   ramp slope set by C1 02        Reverse Operation  1     Disabled        Local Remote RUN Selection  1     Accept External RUN        RUN Command During Programming  1     Enabled        HAND Mode Frequency Reference Selection  Operator Keypad        DC Injection Braking Current  5096        DC Injection Braking Current   Start  5 0sec        Motor Preheat Current       1 Speed Search Select  1     Enabled  Speed Estimated         1 Energy Conservation Control Select  1     Enabled        60 0 sec Acceleration Time       60 0 sec Deceleration Time       10 0 hz Frequency Reference 1  HAND Mode   see H1 03        20 0 hz Frequency Reference 2  HAND Mode   see H1 03        Input Voltage   default dependent on drive model               Pattern Select       Output Voltage  Parameter defaul
23. ration of the communications timeout interval  the FAULT LED lights and remains lit until communication is restored          Continue at Last Speed    In this mode  Cable Loss Timeout  AO 21  is set to 0  disabling the cable loss feature  The other two settings Cable Loss Speed   AO 22  and Communication Fault Enable  BO 11  are ignored  If communication is lost  the drive simply maintains its last  commanded state  The drive will not display an alarm or fault to indicate it has lost communication  This behavior can also be  achieved by setting parameter H5 04 to    3     The drive will display an alarm and continue running  For this specific condition   the Communication Fault Enable  BO 11  must be enabled and Cable Loss Timeout  AO 21  should be set to something other  than 0       Continue at Preset Speed    In this mode  Cable Loss Timeout  AO 21  is set to the desired interval  Cable Loss Speed  AO 22  is set to the desired preset  speed and H5 04 is set to    4     If the time between messages exceeds the timeout interval  the drive s speed command  AO 1  is  set to the Cable Loss Speed  AO 22  and the drive continues running at this new speed  Communication Fault Enable  BO 11   must be set to             Network Connection 3 4       Stop    Communication Fault Enable       11  must be set to    On     In this mode  Cable Loss Timeout  AO 21  is set to the desired interval  and parameter H5 04 is set to a value of 0 1 or 2  If the time between messages exceeds the tim
24. s    Cable lengths cannot exceed 500 feet at 9600 baud         The Network is Terminated Correctly    A bus terminating resistor of 1100 is available on each drive terminal board and can be applied to the Metasys N2 communication bus by  setting switch S1 1 to the ON position     In a multi node system  only those nodes at the end of a bus segment should have terminating resistors  Before applying a terminating  resistor as described above  care should be taken to understand the physical layout of the network and where other resistors might already  be applied  An overloaded or improperly terminated bus may not function properly        Figure A 2     Termination Resistor Setting    Table A 5   Terminating Resistor Switch Setting    Switch Location Function Setting Choices    OFF  No terminating resistance  ON  Terminating resistance of 1100          SI 1 RS 422 and RS 485 Terminating Resistance              Shield Is Continuous And Both Ends Of The Shield Are Grounded    As each drive is daisy chained to the next  twist together the shields of the adjoining cables  Do not connect the shield at each drive   The continuous shield should then be single point grounded at the field panel       Cable Is Routed Correctly    Route the cable away from all power and high frequency lines  Routing within a separate conduit is preferred     Troubleshooting    7    Drive Faults      Communications Fault    Table A 6   Drive Faults    joo Connection is broken or master has Check all connect
25. sys N2 network for the drive  Refer to the documentation included with the Metasys N2 configuration  software     7  Set parameters B1 01  B1 02  H5 01  H5 02 and H5 08 to their appropriate values  Refer to Table 1 1   Drive  Communication Parameter Settings on page 1 5      D LIL LI LL    Installation 1 3    This page intentionally left blank     Installation 1 4    Metasys N2 Set Up    A Yaskawa Electric America  Inc   YEA  representative is responsible for proper configuration of the drive for its primary application   while a Johnson Controls  Inc  representative is responsible for field panel programming to make use of the drive s functionality in the  building automation system  As such  there must be coordination between the Yaskawa Electric America and Johnson Controls  representatives to ensure that the programming of the drive is consistent with the particular application requirements  After verifying that  the drive installation and wiring are correct  apply power to the drive  Table 1 1 below lists the parameters and their values required for  proper Metasys N2 communication and control         E7 Drive Parameter Settings for Metasys N2 Communications    Table 1 1   Drive Communication Parameter Settings  Parameter Number Digital Operator Display Settings for Metasys N2 Communication           CAUTION    A YEA representative should set the drive parameters to their appropriate values  Changes made to  the parameters other than what is listed in the table above can
26. ts dependent on drive model       Operation After Communication Loss  3     Alarm Only        Terminal S3 Function  Bypass Drv Enbl        Terminal S4 Function  Local  Remote Select        Terminal S5 Function  Frequency Reference 2  N O          Terminal S6 Function  External Fault  N O                   E7 Bypass Applications 6 3    Table 7 1   Typical Bypass Engineered Drive Parameters    Parameter Bypass Settings  Number Default User    Description    Terminal S7 Function  External Base Block  N O          Terminal M3 M4  Command Source   Serial        Terminal A2  0 10              Terminal A2  Auxiliary Frequency Reference        Analog Input Filter Time       Master Frequency Reference Terminal Select  0     Terminal A1        Momentary Power Loss Detection Select  2     CPU power active   UV fault not detected        1 Frequency Reference Loss Detection Select  1     RUN   80  of frequency prior to loss        10 Number of Re Start Attempts       600 0 sec Maximum Restart Time After Fault       6 Torque Detection Select  6   No Load Detect and Alarm        1596 Torque Detection Level  96 of drive rated current        10 0 sec Torque Detection Time       4 Overheat Pre Alarm Operation Select  4     Alarm and Reduce        300 sec Heatsink cooling Fan Operation Delay Time       2096 Overheat Frequency Reference Reduction Level       0 Local Remote Key Function  0   Disabled        0 OFF Key Function  0     Disabled        Frequency Reference Setting Method select  1    
27. ue at preset speed  Ramp to Stop with        fault  Coast to Stop with EFO fault    Emergency Stop with EFO fault        Metasys N2 1 0   Three Metasys N2 outputs are used to select the desired behavior   W  AO21  Cable Loss Timeout          22     Cable Loss Speed  W BO 11  Communication Fault Enable    Table 5 1   Cable Loss Behavior Summary    Behavior H5 04 Cable Loss Timeout   Cable Loss Speed   Communication Fault Enable   AO 121  AO 22   BO 11     Decelerate to stop  stop time in C1 02  EF0 Fault Timeout Interval       Coast to stop EF0 Fault Timeout Interval       Continue at last speed 0 X    Continue at last speed with Alarm Timeout Interval    X  X  Emergency stop  stop time in C1 09         Fault Timeout Interval X  X  X                   Continue at preset speed with Alarm Timeout Interval Preset Speed       Notes    1l  Communication must first be established and then lost for these features to function as described  If a drive is powered up without a cable  connected or with the master controller offline  a communications timeout does not occur    2  For modes which describe the drive running after a communications timeout  a run command must have been issued  BO 1      On              2              prior to loss of communications  For safety purposes  the drive will not automatically restart from a stopped condition  If a user requires  the drive to restart automatically  additional external wiring is required to accomplish this  consult factory     Upon expi
28. ystem  only those nodes at the end of a bus segment should have  terminating resistors  Before applying a terminating resistor as described above  care should be taken to understand the physical  layout of the network and where other resistors might already be applied  An overloaded or improperly terminated bus may not  function properly     fa rr mn Ferre    W XUL UAE OE DL       Figure 2 3     Network Termination Resistor Setting    Table 2 1   Terminating Resistor Switch Setting    Switch Location Function Setting Choices       eee   OFF  No terminating resistance  RS 422 and RS 485 Terminating Resistance ON  Terminating resistance of 1100    Network Connection 24    Chapter 3   7 Drive Functions    This chapter discusses the E7 arive functions and cable loss behavior     E7 Drive Functions                                                              3 3  Cable Loss Behavior                                                          3 4  E7 Drive Fault                                                           45         3 6    Network Connection 3 1    This page intentionally left blank     Network Connection 3 2    E7 Drive Functions    Each of the following functions must be enabled during start up of the Drive     Start and stop the drive    Set the RUN FORWARD COMMAND  BO 1  to run the drive in the forward direction  Set the RUN REVERSE COMMAND   BO 2  to run the drive in the reverse direction  RUN STOP MONITOR  BI 1  shows the current run status of the drive   FORWARD R
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
OptiChamber Advantage    LevelOne IEC-1420    Copyright © All rights reserved. 
   Failed to retrieve file