1.                                                                                        The table at the top of the screen shows the Data Highway Plus  diagnostic counters  The table at the bottom of the screen shows the  active station list     To update the display  click the Refresh Registers button     The Data Highway Plus diagnostic counters are described on page 38     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 36 AN X AB DHRIO  DH   November 2011    Log Files    System Error Log    Ethernet IP Log    System Info Log    View All Logs    Administration Menu       ICAL  SOLUTIONS    AN X maintains various logs to record diagnostic and error messages   Use the Log Files menu in the web interface to view these logs     The System Error log records errors that occur during AN X operation   This log is normally empty     The Ethernet IP log shows messages and errors associated with Data  Highway Plus operation     The System Info Log records informational messages during startup and  normal operation     Use View All Logs to list and view all the AN X logs  To view a log  file  double click on the file name     The Administration Menu is used to view and edit files on AN X  Itis  password protected and is used only for AN X technical support     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       LEDs    Ethernet LEDs    SYS
2.          Files of type   QTS Flash File    Ot    Cancel      J Open as read only    File name     4       There are two ways to update all the firmware in an AN X module     1  The Configuration Firmware Update command starts the firmware  update wizard  which takes you step by step through the firmware  update process     2  The Utilities Update Firmware command updates all the firmware  on an AN X you have selected using the Utilities Select An AN X  command     Firmware files have extension bin     Select the Configuration Firmware Update command to start the  firmware update wizard     Step 1   In step 1  you identify the AN X you are configuring     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 28 AN X AB DHRIO  DH   November 2011    Step 1  AN X Selection x     Select this computer s Ethernet adapter that s on the same Ethernet subnet as the AN x  module you want to configure  you may only have one Ethernet adapter in your computer      Local Area Connection x     Enter the Ethernet MAC Address of the AN   module you want to configure     You can get  this from the label on the AN  lt  module or by selecting Utilities Locate All AN  Modules  if  the module s current IP address is on the same subnet       00 0c 1 a 00 00 09             Enter the IP address on the local subnet that you intend the AN  module to use   192 168  0   9                1  Select the Ethernet adapter that   s connect
3.      ICAL  SOLUTIONS       AN X AB DHRIO  DH   Page 13    In this example  we will assign the computer an IP address of  192 168 0 10    Set the Subnet mask to 255 255 255 0  standard mask for the Class C  network address of 192 168 0 x      Set the Default gateway to 192 168 0 1  this address does not exist on the  Ethernet network but AN X requires a valid default gateway entry      Click OK to accept the settings  Connect the computer to AN X using the crossover cable     If this is the first time you have used the AN X module  it will look for a  DHCP server on the network  It waits about three minutes  then reverts  to a default IP address of 192 168 0 41    Power up the AN X and wait for the search for a DHCP server to time  out  When the search for a DHCP server times out  AN X will flash the  SYS LED red three times followed by a pause repeatedly     Run AnxInit  Select Utilities Locate All AN X Modules and confirm that  the AN X is found       O  x     A  re Area Connection  0x2  00 Oc 1a 00 00 O0a 192 168 0 10   Anxinit  Configuration Utilities Edit Yiew Help          device s   00000009  Ethernet MAC  00 0c la 00 00 09     192 168 00 41  test    For Help  press F1       A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    Page 14 AN X AB DHRIO  DH   November 2011    Select Utilities Select An AN X and enter the MAC Address and IP  address     Set Ethernet  amp  IP Address x     
4.   dissipation    3 6W       Environmental  Conditions     Operational  Temperature    Storage Temperature    0 50   C  32 122 F        40 to 85  C     40 to 185   F        Relative Humidity       5 95  without condensation          A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com          ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 43  Support    How to Contact Us  Sales and Support    Sales and Technical Support for this product are provided by ProSoft  Technology  Contact our worldwide Sales or Technical Support teams  directly by phone or email     Asia Pacific     603 7724 2080  asiapc  prosoft technology com       Europe     Middle East     Africa   33  0  5 34 36 87 20  Europe   prosoft technology com       North America     1 661 716 5100  support   prosoft technology com       Latin America  Sales only      1 281 298 9109  latinam   prosoft technology com        A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 44 AN X AB DHRIO  DH   November 2011       Warranty    Quest Technical Solutions warrants its products to be free from defects  in workmanship or material under normal use and service for three years  after date of shipment  Quest Technical Solutions will repair or replace  without charge any equipment found to be defective during the warranty  period  Final determination of the nature and responsibility for defective  
5.  Ethernet side  the AN X AB DHRIO  DH   looks like a 4 slot  ControlLogix rack with an ENET module in slot 0 and a DH RIO in slot  1     Example  RSLinx    To configure a topic in RSLinx to access data on the AN X AB DHRIO   DH       1  Create a new topic  From the main menu select DDE OPC Topic  Configuration  Click New and give the topic a name     2  For the Data source  browse the path to the AN X module and click  Apply   3  On the Data Collection tab  set the Processor Type to PLC 5  Check    Polled Messages and select an appropriate update rate  Leave  everything else unchecked  Click Apply    4  You do not need to set anything on the Advanced Communication  tab     5  Click Done to complete the topic configuration     You should now be able to access data using any DDE or OPC client  capable of communicating with RSLinx     You can send messages from devices such as a ControlLogix to  destinations on Data Highway Plus using MSG instructions  For  example  you can send messages to read or write data on a PLC 5     You cannot initiate messages from the Data Highway Plus side     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Anxinit Log       AN X AB DHRIO  DH   Page 21    Using AnxInit    AnxInit is a Windows application supplied with AN X to perform the  following functions     e Locate and identify AN X modules on the Ethernet network  e Select a specific AN X for configuration   e Set the IP 
6.  LED       ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 37    Troubleshooting    The AN X AB DHRIO  DH   has LEDs that indicate the state of the  Ethernet connection  the connection to Data Highway Plus  and the  overall module state     There are two LEDs that indicate the state of the Ethernet connection     The orange LED  labelled 100  is on if the link is running at 100  Mbits second and is off otherwise     The green Link Act LED is off if the link is inactive and is on if the link  is active  If activity is detected  the link blinks at 30 ms intervals and  continues blinking as long as activity is present     The SYS LED is used by the AN X operating system and software to  indicate the state of operations and errors     It should be used in conjunction with the logs to locate the cause of  problems     In the following  red 3 means three red flashes followed by a pause  and  so on                                      SYS LED State Possible cause   Red 2 AN X is in config mode   Red 3 DHCP configuration failed   Red 4 Fatal application error  check logs for cause   Red 5 Application memory access violation  check logs   Red 6 Application failed  illegal instruction  check logs   Red 7 Application crashed  unknown cause  check logs   Fast red flash Reconfiguration  set station number and baud  rate  failed   Single red flash Unscheduled messaging  addressing or  connection problem   Slow red flash script or application problem during startup       At startup  the SYS LED
7.  by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 11    Enter a Host Name for the AN X  This name is used internally by AN X  and may be used to identify the AN X if you have a DNS server on your  network  The name can be from 1 to 31 characters long     To configure the AN X to obtain its IP address from a DHCP server on  the network  select Obtain an IP address automatically  DHCP     To configure the AN X to use a static IP address  select Use the  following Settings and enter     e the desired IP address for the AN X   e the Subnet mask for the AN X  e the default gateway for your network     You must enter a valid default gateway address even if there is no device  at the gateway address on the network     Click OK to complete the configuration     If you Cancel the Configuration AN X IP Settings command  AN X is  left running the boot code  Use the Utilities Restart AN X command to  restart the AN X     Example  Standalone Computer    TIP       A typical example is a laptop computer running programming software  and connecting directly to an AN X to program a PLC     Since you are connecting directly from the computer to AN X  use a  crossover Ethernet cable     The following instructions assume Windows 2000  The procedure for  Windows NT and Windows XP is very similar  They also assume that  an Ethernet network card has been installed in the computer and that  AnxInit has been installed on the computer     The p
8.  command  from another station        Reply could not be sent    AN X increments this counter when it receives a command but  could not deliver the reply        ACK timeout          AN X was expecting an ACK in response to a message but  nothing was received in the timeout period  Sometimes caused  by sending messages to stations that do not exist        Illegal protocol NAKs received    AN X sent a message and got an illegal protocol NAK in  response        No memory NAK received    AN X sent a message and got a no memory NAK in response        Received ACK NAK too long    AN X was expecting an ACK and received a frame that was  longer than 3 characters instead        Token pass retries exhausted          AN X retries the token pass up to 3 times  If it still fails  it  increments this counter  removes the destination from its  active station list  and tries to pass the token to its successor        Token claimed    Not used        Illegal protocol NAKs sent    If AN X receives a message that is shorter than the minimum  length  6 characters   it increments this counter and sends an  illegal protocol NAK to the sender        No memory NAKs sent    IF AN X receives a message and is out of buffer space  it  increments this counter and sends a no memory NAK to the  sender        Received frame too large    AN X received a frame that was larger than the maximum  possible size  308 bytes  including the 2 CRC bytes         Receive frame aborted    AN X increments this counter when
9.  cy  D    Address      http 4 192 168 0 9  i 7   ME inks Norton antivirus E gt     Google    RB Search Web   sechste     g   Eh 104blocked fal Options      Y Automation Network    ECR ORRE EE   AN X DHP Ethernet Gateway Module    onii H                                Introduction     v Log Files    This is the main configuration screen for the AN X DHP Ethernet gateway  Data Highway Plus  product     System Err    or Log  Directions     The main menu  located on the left  provides a list of options that can be configured using this web interface  To see the sub menus for each item  click on the  down arrow icon beside each main option    Menu Details     y Administration    Automation Network   Configure DH  Network    The AN X DHP Eth gateway has a DH  port that support 3 different baud rates and a configurable station address  The DH  network configuration F  menu provides acc  o these configuration options     Monitor DH  Network  The AN X DHP web interface can monitor in real time the X DHP error counters     LogFiles     Contains all the pages that provide access to log files for the AN X device platform     Home Page System Error Log     This sub menu will display the AN X device s error log  If the AN X DHP gateway indicates an error  system LED  then this log file may indicate the exact  error  more specifically    Ethernet IP Error Log     This menu will display the Ethernet IP error log  If the Ethernet IP connection has an error then this log file may indicate the 
10.  documentation    A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    Page 4 AN X AB DHRIO  DH   November 2011    Modes of Operation    ICAL  SOLUTIONS       There are three AN X modes of operation     Boot mode  The AN X is running its low level startup firmware     Configuration mode  This is the mode when you are updating the  firmware in the AN X     Production mode  This is the normal runtime mode of operation     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       AN X AB DHRIO  DH   Page 5    Installation    Prevent Electrostatic Discharge    WARNING     Power    The module is sensitive to electrostatic discharge     Electrostatic discharge can damage integrated circuits or  semiconductors  Follow these guidelines when you handle the module     e Touch a grounded object to discharge static potential    e Do not touch the connector pins    AN X requires DC power input of anywhere from 12 to 24 VDC    1 2 3    na    GND        Left to right the pins on the power connector are chassis ground  negative  voltage and positive voltage     The chassis ground should be connected     Power consumption internally is 300 mA   12VDC or 150 mA    24VDC     The part number for the power connector is Phoenix MSTB  2 5 3 ST 5 08    Data Highway Plus Cabling and Termination       ICAL  SOLUTIONS    Follow Allen Bradley cabling rec
11.  it receives a message that  doesn   t finish  either because the source aborted the message  or because the source went offline        Messages successfully received       AN X increments this cunter when it receives a message          ICAL  SOLUTIONS    A product of Quest Technical Solutions    Sold and Supported by  ProSoft Technology Inc   www prosoft technology com       Page 40 AN X AB DHRIO  DH   November 2011          Counter Description        command or reply   It also increments the commands  successfully received or replies successfully received counter        Replies successfully received AN X increments this counter when it receives a reply to a  command it sent to another station        Replies successfully sent AN X increments this counter when it successfully sends a  reply to another station           Counters roll over when they reach their maximum value     The diagnostic counters are cleared when you reconfigure the Data  Highway Plus network parameters on AN X     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS       AN X AB DHRIO  DH   Page 41    Updating the Firmware    The AN X operating software consists of several parts      boot code  runs at startup   e configuration kernel  runs when you update firmware  e production kernel  runs in normal operation    e application software  for Data Highway Plus communication and  unscheduled messaging    The boot code and
12.  kernels are supplied in file with extension qtf and are  updated using the AnxInit utility  Run the command Utilities Update  AN X Flash and select the file you wish to download  Refer to page 26  for details     Firmware files contain the application programs for AN X and have  extension bin  They are downloaded using the command  Configuration Firmware Update or Utilities Update Firmware in  AnxInit  Refer to page 27 for details     Occasionally individual patch files are released  They have extension pch  and are downloaded using the Utilities Patch Firmware command in  AnxInit  Refer to page 31 for details     Reading Version Numbers    To read the version numbers of the various software components        Boot code AnxInit     AN X Info       Configuration kernel AnxInit     AN X Info          Production kernel AnxInit     AN X Info   Firmware AnxInit     AN X Info  version depends on  current mode  boot  configuration or  production        Individual applications       Web interface  System Info Log       Unscheduled messaging   Web interface  Ethernet IP Log          A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    Page 42 AN X AB DHRIO  DH      ICAL  SOLUTIONS          November 2011  Specifications  Parameter Specification  Function Bridge between Ethernet and Data Highway    Plus network       Typical Power  Consumption    300 mA   12 VDC or 150 mA   24 VDC       Maximum Power
13.  on the same Ethernet subnet as the AN  lt   module you want to configure  you may only have one Ethernet adapter in your computer      Local Area Connection             Enter the Ethernet MAC Address of the AN  module you want to configure  You can get  this from the label on the AN  module or by selecting Utilities Locate All AN  Modules  if  the module s current IP address is on the same subnet       0 0 1 a 00 00 09          Enter the IP address on the local subnet that you intend the AN  module to use   192   168  0   9                1  Select the Ethernet adapter that   s connected to the AN X  In most  cases there will be just one Ethernet adapter in the computer  The AN X  must be on the same subnet as the computer     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       AN X AB DHRIO  DH   Page 9       2  Enter the MAC address of the AN X you are configuring  This is  printed on the AN X label  It consists of six pairs of hexadecimal digits   separated by hyphens  In the example above  it   s 00 Oc 1a 00 00 09     If the AN X is already online  you can obtain its MAC address using the  Utilities Locate All AN X Modules command     3  Enter the IP address you intend the AN X to use     Step 2    In step 2  you choose a method of restarting AN X to put it in boot mode     Step 2  Cycle Power or Reboot Command x     In order to configure the IP address or update the module s firmware the module must b
14.  sequence is       boot code starts     fast flashing red    A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 38 AN X AB DHRIO  DH   November 2011    e boot code loads a kernel     solid red    e if the configuration kernel is loaded  2 red flashes followed by a  pause    e if the production kernel loads with no errors  solid green    NET LED     Network Status    The NET LED indicates the status of the Data Highway Plus network  connection              All stations operating correctly Solid green  No other stations Yellow  Network error Flashes red          Data Highway Plus Diagnostic Counters    AN X maintains Data Highway Plus diagnostic counters  Use    Automation Network Monitor DH  Network in the web interface to view  the diagnostic counters     The counters are        Counter    Description       Solicit ACK Bad    Solicit ACK bad  not to AN X  bad ACK value  or source is  not the station AN X solicited        Transmit retries exhausted    AN X retries messages up to 3 times  4 in total   If it still  hasn   t successfully sent the message  it discards the message  and returns an error        Bad LSAP NAKs received    AN X sent a message and got a bad LSAP NAK in response   Usually caused by routing problems        Received ACK NAK too short    AN X was waiting for an ACK and received a frame that was  less than 3 characters long instead        Token pass timeout    AN X passed the token bu
15.  to   e identify a hazard  e avoid the hazard    e recognize the consequences    Identifies information that is especially important for successful  application and understanding of the product     Identifies information that explains the best way to use the AN X AB   DHRIO  DH      Microsoft is a registered trademark of Microsoft Corporation   Windows  Windows XP Windows Vista and Windows 7 are trademarks of Microsoft Corporation     ControlLogix  RSLinx and RSLogix 5000 are trademarks of the Allen Bradley Company  Inc     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       AN X AB DHRIO DATA HIGHWAY PLUS OVERVIEW  Hardware Features  Package Contents    Modes of Operation    INSTALLATION   Prevent Electrostatic Discharge   Power   Data Highway Plus Cabling and Termination  Ethernet Cabling    Software Installation    BASIC CONFIGURATION    Ethernet Configuration  Example  Standalone Computer    Reconfiguring an AN X from an Unknown State    Data Highway Plus Configuration    USING PROGRAMMING SOFTWARE  Configuring the AN X AB DHRIO  DH   in RSLinx  Using the Programming Software    Multiple Programmer Access    USING DDE OPC AND UNSCHEDULED MESSAGES    Sending Messages    USING ANXINIT  Anxinit Log    Locating Available AN X Modules    20    20    21  21    22    Page 4 AN X AB DHRIO  DH      Selecting an AN X   Set AN X IP Configuration   Restart an AN X   AN X Info   Read Kernel Parameters   Run Config M
16. 7 6  Kbaud     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www  prosoft technology com       ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 17  Using Programming Software    Configuring the AN X AB DHRIO  DH   in RSLinx    To use an AN X AB DHRIO  DH   module with Rockwell  programming software such as RSLogix 5  you must first configure a  driver in RSLinx to access the AN X module     The following instructions assume that   e AN X has been configured and is active on the Ethernet network  e AN X has been connected to the Data Highway Plus network    e the AN X Data Highway Plus station number and baud rate have  been assigned and are compatible with the existing network    Use the following steps to configure the AN X AB DHRIO  DH   in  RSLinx     1  Select Communications Configure Drivers       2  From the list of Available Driver Types   select Remote Devices  via Linx Gateway and click Add New       3  Give the driver a name  Add New RSLinx Driver    Choose a name for the new driver    15 characters maximum      AN X       4  For Server   s IP Address or hostname  enter the IP address of the  AN X AB DHRIO  DH   and click OK     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS       Page 18 AN X AB DHRIO  DH   November 2011    Configure Remote Devices via Linx Gateway    Driver Selection   Configure Browser      Device Name   AN    Server s 
17. AN X AB DHRIO    Data Highway Plus User Manual    Communication       A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       SOLUTIONS       Page 2 AN X AB DHRIO  DH   November 2011       WARNING     IMPORTANT     TIP       ICAL  SOLUTIONS    Because of the variety of uses for the products described in this  publication  those responsible for the application and use of these  products must satisfy themselves that all necessary steps have been taken  to assure that each application and use meets all performance and safety  requirements  including any applicable laws  regulations  codes and  standards  In no event will Quest Technical Solutions be responsible or  liable for indirect or consequential damage resulting from the use or  application of these products     Any illustrations  charts  sample programs  and layout examples shown  in this publication are intended solely for purposes of example  Since  there are many variables and requirements associated with any particular  installation  Quest Technical Solutions does not assume responsibility or  liability  to include intellectual property liability  for actual use based  upon the examples shown in this publication     Throughout this manual we use notes to make you aware of safety  considerations     Identifies information about practices or circumstances that can lead to  personal injury or death  property damage  or economic loss     These warnings help
18. Adapter    Local Area Connection     Ethernet MAC Address    00 0c 1 a 00 00 09    IP   ddress   192   168  0   4       Click OK to accept the setting   Select Utilities AN X IP Configuration     AN X TCP IP Configuration x     Enter the IP configuration you want the previously selected AN  module to use   You MUST enter a valid Default gateway IP address that is on the same subnet as the  AN    module  but you don t need to have a device at that address     Host Name   test       Obtain an IP address automatically  DHCP     Use the following Settings     IP Address   E   168      Subnet mask         Default gateway   192 168  0   1   192 168  0  WS   168         Cancel         Enter an IP Address  In this case we chose 192 168 0 20    Enter the same Subnet mask and Default gateway that you entered for the  computer  The default gateway address does not exist on the network  but AN X requires that the field have a valid entry     Click Finish to accept the settings   Select Utilities Restart AN X to restart AN X with the new parameters     When the AN X has restarted  SYS LED is solid green   select  Utilities Locate All AN X Modules and confirm that the AN X is found  with the new parameters     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 15          A EE Area Connection  0x2  00 0c 1a 00 00 09 192 168 0 20   Anxinit  Configuration Utilities Edit Yiew Hel
19. IP Address or hostname  fi 92 168 0 10 Browse       Server Name     Remote driver name       Cancel Apply   Help      5  Check that the driver has status Running       Configure Drivers         Available Driver Types      Remote Devices via Linx Gateway               Configured Drivers     Name and Description Status    AN to on 192 168 0 10 RUNNING Running  TCP 1 to on 192 168 0 65 RUNNING Running                   6  Click Close    A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 19    Using the Programming Software    To go online with programming software such as RSLogix 5  browse the  network and go online     Multiple Programmer Access       ICAL  SOLUTIONS    Multiple computers can connect to a Data Highway Plus network  through a single AN X AB DHRIO  DH       Multiple applications on a computer can connect to a Data Highway Plus  network through the same AN X AB DHRIO  DH       A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 20 AN X AB DHRIO  DH   November 2011    Using DDE OPC and Unscheduled Messages    Sending Messages       ICAL  SOLUTIONS    You can use a DDE or OPC server  such as RSLinx  to access data using  the AN X AB DHRIO  DH       Configure the AN X module as you would a ControlLogix 1756 ENET  Ethernet module and 1756 DHRIO Data Highway Plus module     From the
20. O  BootRev Boot code version   ConfigRev Configuration kernel version   ProdRev Production kernel version   HwRev Hardware version   FirmwRev Firmware release version  depends on current    operating mode                    Status see below   Vendorld Vendor ID   ProdId Product ID   IpAddrStr IP address assigned using Utilities AN X IP  Configuration   HostName name assigned using Utilities AN X IP  Configuration          In boot mode  FirmwRev  Vendor ID and Product ID and not valid  and  IpAddrStr and HostName are not shown     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 26 AN X AB DHRIO  DH   November 2011       Possible status values are        Value Meaning                1 Boot mode  2 Configuration mode  4 Production mode       Read Kernel Parameters    The Utilities Read Kernel Parameters command displays various  communications parameters for the currently selected AN X    This command resets the AN X  You will be warned and given the  opportunity to cancel the command        AEEA Area Connection  0x2  00 0c 1a 00 00 0a 192 168 0 10   AnxInit a    Oj x   Configuration Utilities Edit Yiew Help  X     AnxInit Ready A  AN X now in BOOT mode            AN X Kernel Parameters   console ttyS0 115200 ip 192  168 0 10 192  168 0 105 192  168 0 1 255 255 255 0 ANX00000a eth0O none       lu We    For Help  press F1 La a any z    The Utilities Read Kernel Parameters command leaves the AN X  runni
21. address and other network parameters for an AN X  e Restart an AN X   e Display information about the selected AN X   e Read the kernel parameters for the selected AN X   e Update the flash  low level firmware  on the selected AN X   e Update the firmware on the selected AN X   e Patch the firmware on the selected AN X    In addition  it can be used to   e clear the AnxInit log      copy the contents of the log to the clipboard for use by another  application  This is often useful for technical support    AnxInit logs messages in its main window  These messages are often  useful for determining the cause of errors or for technical support     To clear the log  select Edit ClearLog     To copy the contents of the Log to the Windows clipboard so that they  can be pasted into another application  select Edit Copy     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 22 AN X AB DHRIO  DH   November 2011    A EE Area Connection  0x2  00 0c 1a 00 00 09 192 168 0 9   AnxInit       Configuration Utilities Edit view Help       aK        AnxInit Ready    BAN X Info  00 0c la 00 00 08    SerNum  DaughterID  BootRev  ConfigRev  ProdRev  HwRev  FirmwRev    IpAddrstr  HostName    For Help  press F1    00000008  9006   1 02  O001  1 00 0000  1 00 0000  1 01 0001  L 02 000I  ox00000004  OTSTIHNG   AN X DHP Ethernet Gateway  SZ Les   oo  DHP       AN X Log    Locating Available AN X Modules       ICAL  SOLUTIONS    T
22. arameters in this example will work when you set up any  standalone computer to work with AN X     First configure the computer to use a static IP address  From the Start  menu  select Start Settings Network and Dialup Connections  Double  click on Local Area Connection     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 12 AN X AB DHRIO  DH   November 2011             Local 4rea Connection Status  gt  2  x  General        Connection  Status  Connected  Duration  01 57 12  Speed  100 0 Mbps  Activity  Ha P  Sent        i     Received  L th  Packets  956   885               Disable         Click the Properties button   Double click on Internet Protocol  TCP IP      Internet Protocol  TCP IP  Properties       General       You can get IP settings assigned automatically if your network supports  this capability  Otherwise  you need to ask your network administrator for  the appropriate IP settings        Obtain an IP address automatically                        Use the following IP address   IP address  192 168  0   10  Subnet mask    255  255 255  0  Default gateway  192 168  O   1          Obtain DNS server address automatically        Use the following DNS server addresses     Preferred DNS server           Alternate DNS server                         Advanced         Cancel         A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com  
23. bled     Step 3  Wait for Boot Mode x     If you selected the  Cycle Power  option  power ON the AN  lt  module now   If you selected the  Reset Command  option  a reset command has been sent to the  AN  module     This program is now sending messages to the AN X module using the MAC address and  IP address you entered previously  These messages tell the AN  module to remain in its   Boot  state in preparation for configuring the IP settings    If the AN  module enters  Boot  mode successfully the  Next  button below will be  enabled so you can move on to the next step    If the AN  module has been powered ON for more than 10 seconds and the Next button  is still disabled press the Back  button  confirm the MAC and IP addresses and check  the Ethernet cabling        If the AN X does not enter boot mode within about 10 seconds  return to  the previous screens and check the entries     The AN X TCP IP Configuration dialog appears     AN X TCP IP Configuration x        Enter the IP configuration you want the previously selected AN  module to use   You MUST enter a valid Default gateway IP address that is on the same subnet as the  AN X module  but you don t need to have a device at that address     Host Name   RR          Obtain an IP address automatically  DHCP     Use the following Settings     IP Address   E   168      Subnet mask         Default gateway   192   168  0  1   192 168  0  1 92   168        Cancel         A product of Quest Technical Solutions  Sold and Supported
24. ch File    pch  x  Cancel      J Open as read only       4    This command resets the AN X  You will receive a warning and be  given the opportunity to Cancel the command     You do not have to reconfigure the AN X after applying a patch  All  configuration information will be left intact     When the patch has been applied  AnxInit restarts the AN X in  production mode     If you cancel at the filename dialog  the AN X has already been reset and  is in configuration mode  Use the Utilities Restart AN X command to  restart it in production mode     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       AN X AB DHRIO  DH   Page 33       Using the Web Interface    The AN X module contains a webserver capable of communicating with  standard web browsers such as Internet Explorer     Use the web interface to    e set the Data Highway Plus station number and baud rate  e monitor Data Highway Plus diagnostic counters   e view AN X logs    To use the web interface  you need to know the IP address of the AN X   Use the Utilities Locate All AN X Modules command in AnxInit to find  all AN X modules on the Ethernet network     To access the web interface  start your web browser and type the AN X  IP address where you normally enter web addresses in the browser         QTS AN X DHP web interface  v1 1 2    Microsoft Internet Explorer BE  Ele Edit View Favorites Tools Help     EE  gt     a  x  a EA JO search eo lil   B    
25. e  be set to a specific mode  There are two ways to do this       1  Cycle power on the AN X Module   This is the preferred method  but the AN  module must be nearby   If you choose this option  POWER OFF the 4N X module and click on the Next button     C 2 Send a command on Ethernet that restarts the AN X module   This method is more convenient if the module is not nearby     If you choose this option  make sure the AN  module is powered ON and fully up and  running  then click on the Next button      lt  lt  Back            The preferred method is to cycle power on the AN X  Select the first  option on the screen and click the Next  gt  gt  button     The second method  useful if the AN X in not easily accessible  is to  send it a command over Ethernet  The AN X must be powered on and  completely running for this method to work  For example  if this is the  first time you are configuring a new AN X  allow sufficient time for it to  acquire an IP address from a DHCP server or to time out and use its  default IP address  about 3 minutes   Select the second option on the  screen and click the Next  gt  gt  button     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS       Page 10 AN X AB DHRIO  DH   November 2011    Step 3     Wait for AN X to enter boot mode  While AnxInit is waiting  the  Next gt  gt  button will be disabled  When AN X is in boot mode  the  Next gt  gt  button will be ena
26. e PLC 5 or  ControlLogix over Data Highway Plus  Refer to page 17 for details     You can use a DDE or OPC server such as RSLinx to access Data  Highway Plus using the AN X AB DHRIO  DH    Refer to page 20 for  details     The AN X AB DHRIO  DH   module has a web interface for  configuration of Data Highway Plus station number and baud rate and  for monitoring diagnostic counters and the active station list  You can  communicate with the module using any standard web browser such as  Internet Explorer     AN X AB DHRIO  DH   Page 3    A watchdog timer is implemented in the module   s hardware  If the  firmware does not kick the watchdog within the timeout period the  watchdog times out and places the module into a safe fatal failure state     A jabber inhibit timer is implemented in the module   s hardware  If the  network transmitter is on longer than 150  of the longest network frame  time  the transmitter is forced off and the module is placed into a safe  fatal failure state     The module firmware can be updated over Ethernet using the Windows  utility supplied  Refer to page 41 for details     Hardware Features       The module has     e LEDs to indicate the status of the connection to the Ethernet  its  own internal state  and the connection to the Data Highway Plus  network      an Ethernet connector  e a Phoenix connector to connect to the Data Highway Plus network    bd a power connector    Package Contents    AN X AB DHRIO  DH   module    CD containing software and
27. ed to the AN X  In most  cases there will be just one Ethernet adapter in the computer  The AN X  must be on the same subnet as the computer     2  Enter the MAC address of the AN X you are updating  This is printed  on the AN X label  It consists of six pairs of hexadecimal digits   separated by hyphens  In the example above  it   s 00 Oc 1a 00 00 09     If the AN X is already online  you can obtain its MAC address using the  Utilities Locate All AN X Modules command     3  Enter the IP address of the AN X you want to update    Step 2    In step 2  you choose a method of restarting AN X to put it in config  mode     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 29       Step 2  Cycle Power or Reboot Command x     In order to configure the IP address or update the module s firmware the module must be  be set to a specific mode  There are two ways to do this       1  Cycle power on the AN Module   This is the preferred method  but the AN  module must be nearby   IF you choose this option  POWER OFF the 4N   module and click on the Next button     C 2  Send a command on Ethernet that restarts the AN X module   This method is more convenient if the module is not nearby   If you choose this option  make sure the AN X module is powered ON and fully up and  running  then click on the Next button      lt  lt  Back            The preferred method is to cycle power o
28. ep    If the AN  module has been powered ON for more than 60 seconds and the Next button  is still disabled press the  Back  button  confirm the MAC and IP addresses and check  the Ethernet cabling        Next  gt  gt          If the AN X does not enter config mode within about 60 seconds  return  to the previous screens and check the entries     Click the Next gt  gt  button  and select the firmware file you want to  download and click Open     Open le  Look in   a anxdesnet    e   ex E                aa  anxamxdcs   1 4 3 bin       anxamxdes v1 4 4 bin       File name  anxamedes  v1 4 4  bin  Files of type  Jars Firmware File    bin  7  Cancel       7 Open as read only        Anxlnit transfers the firmware file and restarts the AN X     After you run update the firmware  you must reconfigure the AN X and  restore the Data Highway Plus station number and baud rate    A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS       AN X AB DHRIO  DH   Page 31    Update Firmware Command    Patch Firmware       ICAL  SOLUTIONS    The Utilities  Update Firmware command updates all the firmware on an  AN X you have previously selected using the Utilities Select An AN X  command     This command resets the AN X  You will receive a warning and be  given the opportunity to Cancel the command     If you cancel at the filename dialog  the AN X has already been reset and  is in configuration mode  Use the Ut
29. exact error  more  y    P z aK aa m                         The left pane contains commands  Click on the arrows at the left of the  main headings to expand or contract the sections     The contents of the right pane depend on the current command being  executed     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc   www prosoft technology com       Page 34 AN X AB DHRIO  DH   November 2011    Data Highway Plus Configuration    Select Automation Network Configure DH  Network to set the station  number and baud rate       QTS AN X DHP web interface  v1 1 2    Microsoft Internet Explorer  File Edit View Favorites Tools Help ay    Ow  O  DAD Awe sero See O AD VA      Address      http  192 168 0 9  v  Eco  Links  gt  Norton Antivirus B     Google   v   esearchweb     searchste ee  g   E 104 blocked fea  Options                         Automation Networ    AN X DHP Network  Configuration    v Log Files    Tm 20 KGE      Administration          Select the baud rate     Enter the station number in the Station field  It can range from 0 to 77  octal  0 is not recommended as a Data Highway Plus station number     The default AN X configuration is station 20 octal  baud rate 57 6  Kbaud     Click the SUBMIT button to send the values to AN X     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www  prosoft technology com       ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 35       Monitor Diagnostic Counters    T
30. ilities Restart AN X command to  restart it in production mode     Click the Next gt  gt  button  and select the firmware file you want to  download and click Open          Look in  E anxdesnet  gt     ae         a  anxamxdes  v1 4 3  bin   a  anxamxdes   1 4 4  bin       File name  anxamxdes  v1 4 4  bin  Files of type  fats Firmware File    bin  7  Cancel      J Open as read only  4a    AnxInit transfers the firmware file and restarts the AN X     After you run update the firmware  you must reconfigure the AN X and  restore the Data Highway Plus station number and baud rate     The Utilities Patch Firmware command applies small patches to the  firmware running on the AN X     These patch files files have extension pch     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 32 AN X AB DHRIO  DH   November 2011       ICAL  SOLUTIONS             Look in   a downloads x  e    FE    a  anxdes   1 00 0002 pch a  anxdes v1 01 0006 pch a  4nxDcsEnetIp_      anxdes v1 00 0004 pch  a  anxdcs webupdate pch a  AnxDcsEnetIp_    a  anxdcs v1 00 0006 pch      AnxDcsEnetIp_1 1 18 pch    4nxDcsEnetIp_        anxdcs v1 00 0007 pch      AnxDcsEnetIp_1 1 19 pch  a  4nxDesEnetIp_        anxdes v1 00 0008 pch a  4nxDcsEnetIp_1 1 20 pch      4nxDcsEnetIp_    a  anxdcs v1 00 0009 pch        nxDcsEnetIp_1 1 21 pch  a  4nxDcsEnetIp_                         File name  AneDcsEnetlp 1 1 48 pch    Files of type  Jars Firmware Pat
31. in about three minutes of  starting up  it reverts to a temporary static IP address of 192 168 0 41 If  AN X is using this temporary IP address  it repeatedly flashes the SYS  LED three times followed by a pause     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 8 AN X AB DHRIO  DH   November 2011    IMPORTANT     IMPORTANT     IMPORTANT        ICAL  SOLUTIONS    Use this temporary IP address only for initial setup of AN X  AN X will  not function for its intended purpose at the temporary IP address     If you are using multiple AN X modules  configure one at a time   especially if there is no DHCP server on the network  since they will all  revert to the same temporary IP address when they fail to find a DHCP  server     If you are connecting AN X to an existing Ethernet network  consult the  network administrator to obtain information about how you should  configure AN X and to obtain a static IP address for AN X     The AN X must be on the local Ethernet  same subnet  when you set its  IP address     You configure the Ethernet properties using the Windows utility AnxInit  supplied with AN X     Use the Configuration AN X IP Settings command to start the AN X IP  configuration wizard  which takes you step by step through the IP  configuration process     Step 1  In step 1  you identify the AN X you are configuring     Step 1  AN X Selection x        Select this computer s Ethernet adapter that s
32. n the AN X  Select the first  option on the screen and click the Next  gt  gt  button     The second method  useful if the AN X in not easily accessible  is to  send it a command over Ethernet  The AN X must be powered on and  completely running for this method to work  For example  if this is the  first time you are configuring a new AN X  allow sufficient time for it to  acquire an IP address from a DHCP server or to time out and use its  default IP address  about 3 minutes   Select the second option on the  screen and click the Next  gt  gt  button     Step 3     Wait for AN X to enter config mode  While AnxInit is waiting  the  Next gt  gt  button will be disabled  When AN X is in boot mode  the  Next gt  gt  button will be enabled     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    Page 30 AN X AB DHRIO  DH   November 2011    Step 3  Wait for Config Mode x     If you selected the  Cycle Power  option  power ON the AN  lt  module now   If you selected the  Reset Command    option  a reset command has been sent to the  AN  module     This program is now sending messages to the AN  module using the MAC address and  IP address you entered previously  These messages tell the AN  module to enter into   Config  state in preparation for updating the firmware     If the AN  module enters Config    mode successfully the  Next  button below will be  enabled so you can move on to the next st
33. nc    www prosoft technology com       AN X AB DHRIO  DH   Page 7    Basic Configuration  The AN X AB DHRIO  DH   module connects a computer or other  device on Ethernet to a Data Highway Plus network     Before you can use the AN X AB DHRIO  DH    you must configure  its network properties  first on Ethernet and then on Data Highway Plus     Ethernet Configuration    AN X can be configured to use a static  unchanging  IP address or it can  be configured to obtain its IP address from a DHCP server     Unless you have control of the DHCP server  in most applications you  will want to configure AN X to use a static IP address  Otherwise the  DHCP server may assign a different IP address each time AN X powers  up  and any software that accesses the AN X module would have to be  reconfigured     AN X is shipped with DHCP enabled  If it finds a DHCP server on the  network  the DHCP server assigns it an IP address  You can use the  utility AnxInit to find the IP address that the DHCP server has assigned   Select Utilities Locate All AN X Modules and AnxInit will locate the  AN X and display its IP address        A EE Area Connection  0x2  00 0c 1a 00 00 0a 192 168 0 10   An      0  x   Configuration Utilities Edit view Help       Ba x   NP     For Help  press F1       ICAL  SOLUTIONS    device s     00000009  Ethernet MAC  00 0c la 00 00 09   192  168 60 41  test    O0000000a  Ethernet MAC  00 0c 1a 00 00 0a   192 168  0 16  ANXOOO00Aa       If AN X does not find a DHCP server with
34. ng the boot code  Use the Utilities Restart AN X command to  restart the AN X in production mode     Run Config Mode    The Utilities Run Config Mode command is used to restart the currently  selected AN X in configuration mode  normally used internally for  updating firmware      This command is not used in normal operation but may be required for  technical support     The AN X is in configuration mode when the SYS LED flashes red  twice  followed by a pause     To exit configuration mode  use the Utilities Restart AN X command to  restart AN X in production mode     Update AN X Flash    The Utilities Update AN X Flash command updates the low level  firmware  boot code  configuration kernel  production kernel      Files have extension qtf     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS       Update Firmware    Firmware Update Wizard       ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 27    This command resets the AN X  You will receive a warning and be  given the opportunity to Cancel the command     If you cancel at the filename dialog  the AN X has already been reset and  is in boot mode  Use the Utilities Restart AN X command to restart it in  production mode     open 8X  Look in   a downloads    e naa     a  ANXBOOT QTF   a  AnxBoot_1_2_1 qtf        zImage cfg v1 00 0001  qtf       zImage cfg v1 00 0002 qtf  a  zImage cfg v1 00 0003  gtf   a  zImage cfg v1 00 0005 qtf            
35. o identify the AN X if you have a DNS server on your  network  The name can be from 1 to 31 characters long     To configure the AN X to obtain its IP address from a DHCP server on  the network  select Obtain an IP address automatically  DHCP     To configure the AN X to use a static IP address  select Use the  following Settings and enter the following     e the desired IP address for the AN X   e the Subnet mask for the AN X  e the default gateway for your network     You must enter a valid default gateway address even if there is no device  at the gateway address on the network     Click OK to complete the configuration     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    Restart an AN X    AN X Info       ICAL  SOLUTIONS    AN X AB DHRIO  DH   Page 25    Utilities AN X IP Configuration resets the selected AN X  Use the  Utilities Restart AN X to restart the AN X in production mode     If you Cancel the Utilities AN X IP Configuration command  AN X is  left running the boot code  Use the Utilities Restart AN X command to  restart the AN X     Use the Utilities Restart AN X command to restart the currently selected  AN X     The Utilities AN X Info command provides information about the  currently selected AN X in the log window     The information shown                             AN X Info Ethernet MAC address   SerNum Serial number   DaughterID Daughterboard ID  3 for AN X AB DHRI
36. o locate all accessible AN X modules on the Ethernet network  select  Utilities Locate All AN X Modules     AnxInit displays a list of the AN X modules it finds  showing their MAC  IDs  IP addresses and host names     This command is useful for determining IP addresses when they have  been set by a DHCP server or for confirming that an AN X is accessible     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       AN X AB DHRIO  DH   Page 23             device s     00000009  Ethernet MAC  60 0c 1a 00 00 08   IpAddrstr   192 168  6 41    test  O000000aR  Ethernet MAC  00 0c 1a 00 00 0a     IpAddrstr   192  168 0 10    ANXOO0000a    For Help  press F1    Selecting an AN X    Before you can perform an operation on an AN X  you must select it   Choose Utilities Select An AN X to select a specific AN X     Set Ethernet  amp  IP Address E xj    Adapter    Local Area Connection      Ethernet MAC Address    00 001 a 00 00 0a    IPAddress   192   168  0   10    Cancel      From the Adapter list  select the network adapter that connects to the  Ethernet network that contains the AN X     In the Ethernet MAC Address field  enter the MAC Address of the AN X  you wish to select  It can be found on the AN X label or using the  Locate All AN X Modules command  The format is as shown above  six  pairs of hexadecimal digits separated by hyphens     In the IP Address field  enter the Ethernet IP address of the AN X you  wish to 
37. o use the web interface to view the Data Highway Plus diagnostic  counters and active station list on AN X  select Automation  Network Monitor DH  Network     E QTS AN X DHP web interface  v1 1 2    Microsoft Internet Explorer E  Ex   File Edit View Favorites Tools Help              QO ex X   gt    x  a    PO search koc C    A  s w  mm  ol          Address      http   192 168 0 97 M  Eco Lnks Norton antivirus f      Google      RB Search Web   sechste   g   Fr 171 blocked    Ea Options      TE AN X DHP DH  Monitor    Monitor DH  Network DH  Interface Error Counters          Configure DH  Network       v  Log Files Refresh Displa        v Administration Counter faa  SOLICIT ACK BAD l   L   EE E 3 ILLEGAL PROTOCOL NAKS RECEIVED        BADISAP NAKS RECEIVED   NOMEMORYNAKRECV       RECEIVED ACK NAK TOO SHORT   RECEIVED ACK NAK TOOLONG    TOKEN PASS RETRIES EXHAUSTED                                 TOKEN CLAIMED         BADCRCONRECEIVED FRAME 000   ILLEGALPROTOCOLNAKS SENT   o0     BADISAPNAKSSENT 000   NOMEMORYNAKSSENT   o0     RECEIVED FRAME TOO SMALL 000 RECEIVED FRAMETOOLARGE    RETRY OF AFRAME RECEIVED 000   RECEIVE FRAME ABORTED  MESSAGES SUCCESSFULLY SENT 17759  MESSAGES SUCCESSFULLY RECEIVED      COMMANDS SUCCESSFULLY SENT 04455 REPLIES SUCCESSFULLY RECEIVED     COMMANDS SUCCESSFULLY RECEIVED 00036   REPLIES SUCCESSFULLY SENT    REPLY COULD NOT BE SENT ooo    Station List                                                                                                       
38. ode   Update AN X Flash   Update Firmware  Firmware Update Wizard    Update Firmware Command    Patch Firmware    USING THE WEB INTERFACE  Data Highway Plus Configuration  Monitor Diagnostic Counters  Log Files   System Error Log   Ethernet IP Log   System Info Log   View All Logs    Administration Menu    TROUBLESHOOTING  LEDs   Ethernet LEDs   SYS LED   NET LED     Network Status    Data Highway Plus Diagnostic Counters    UPDATING THE FIRMWARE    Reading Version Numbers    SPECIFICATIONS    A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       November 2011    23  24  25  25  26  26  26  27  27  31    31    33    34    37    37  37  37    38    41    41    42       SUPPORT    WARRANTY    43    44    AN X AB DHRIO Data Highway Plus Overview                _                 a  WS  er  ee    Programmer  HMI    Ethernet                Programmer Programmer    AN X       Data Highway Plus    The AN X AB DHRIO module running Data Highway Plus  DH    firmware connects a computer or other device to an Allen Bradley Data  Highway Plus network  using Ethernet     The AN X AB DHRIO  DH   module       can act as any valid Data Highway Plus station number  from 0 to 77  octal    e supports all Data Highway Plus baud rates  57 6  115 2 and 230 4  Kbaud      maintains Data Highway Plus diagnostic counters    You can use the AN X AB DHRIO  DH   module with Rockwell  programming software to communicate with PLCs such as th
39. ology Inc    www prosoft technology com       ICAL  SOLUTIONS    
40. ommendations for Data Highway Plus   Refer to Approved Vendor List for DH  DH   DH 485  and Remote I O  Cables  publication ICCG 2 2  February 1996     The network cable must be terminated with terminating loads attached to  the physical ends of the network  usually 82 ohm  but refer to  Allen Bradley documentation since some devices require 150 ohm  terminators  There should be two and only two terminators on the Data  Highway Plus network     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       Page 6 AN X AB DHRIO  DH   November 2011    Ethernet Cabling    Software Installation       ICAL  SOLUTIONS    From left to right on the AN X module  the Data Highway Plus  connections should be line 1  shield  line 2     1 2 3    alala  M    The part number for the connector is Phoenix MSTB 2 5 3 ST 5 08    AN X has a standard RJ 45 connector for connecting to Ethernet     If you are connecting AN X to an existing network through a router or  switch  use a standard Ethernet cable     If you are connecting directly between a computer and AN X  use a  crossover cable     You must uninstall any previous version of the software before you can  install a new version  Use the Windows Control Panel Add and Remove  Programs to remove the old version     Insert the CD supplied with the AN X module and run the program  setup exe on the CD     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology I
41. or damaged equipment will be made by Quest Technical Solutions  personnel     All warranties hereunder are contingent upon proper use in the  application for which the product was intended and do not cover  products which have been modified or repaired without Quest Technical  Solutions approval or which have been subjected to accident  improper  maintenance  installation or application  or on which original  identification marks have been removed or altered  This Limited  Warranty also will not apply to interconnecting cables or wires   consumables nor to any damage resulting from battery leakage     In all cases Quest Technical Solutions    responsibility and liability under  this warranty shall be limited to the cost of the equipment  The purchaser  must obtain shipping instructions for the prepaid return of any item under  this Warranty provision and compliance with such instruction shall be a  condition of this warranty     Except for the express warranty stated above Quest Technical Solutions  disclaims all warranties with regard to the products sold hereunder  including all implied warranties of merchantability and fitness and the  express warranties stated herein are in lieu of all obligations or liabilities  on the part of Quest Technical Solutions for damages including  but not  limited to  consequential damages arising out of or in connection with  the use or performance of the Product     A product of Quest Technical Solutions  Sold and Supported by  ProSoft Techn
42. p    aK     Found 1 AN X device s      l0  x        SerNum 00000009  Ethernet MAC  00 0c 1a 900 00 08   IpAddrstr 192  168  0 296  HostName test    For Help  press F1       Reconfiguring an AN X from an Unknown State    It sometimes happens that an AN X has been previously configured with  an IP address that causes it to be inaccessible on the current Ethernet  network  To reconfigure it to a known state  run the command  Configuration AN X IP Settings to start the AN X IP Configuration  Wizard and reconfigure AN X     A product of Quest Technical Solutions    Sold and Supported by  ProSoft Technology Inc     www prosoft technology com       ICAL  SOLUTIONS       Page 16 AN X AB DHRIO  DH   November 2011    Data Highway Plus Configuration    You set the AN X station number and baud rate using the web interface     Start your web browser and enter the AN X IP address as the web  address     Enter the Data Highway Plus station number  in octal   Select the baud rate     A QTS AN X DHP web interface  v1 1 2    Microsoft Internet Explorer  File Edit View Favorites Tools Help    Qu  O  HED Yawn foros Que O 2 2 a Wa  Address    http   192 168 0 9  v  Eo   Links     Norton Antivirus Jl        Google   v  BPSearch Web     sechste We go Eh 104blocked fa Options A  A    AN X DHP Network  Configuration                7 Automation Network    y Administration          Click the SUBMIT button to send the values to AN X     AN X defaults to a station address of 20 octal and a baud rate of 5
43. select  It can be found using the Locate All AN X Modules  command  The format is as shown above  four decimal numbers each in  the range 0 to 255     Both MAC address and IP address must match the settings on the AN X  in order for communication to occur           A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       ICAL  SOLUTIONS    Page 24 AN X AB DHRIO  DH   November 2011    Click OK to select the AN X     The title bar of AnxInit shows the MAC Address and IP Address of the  currently selected AN X     Set AN X IP Configuration    Utilities AN X IP Configuration sets the AN X IP address and hostname   The AN X must be on the local Ethernet to set its IP address     First select the AN X using the Utilities Select An AN X command     Next select Utilities AN X IP Configuration  The AN X TCP IP  Configuration dialog appears     AN X TCP IP Configuration x        Enter the IP configuration you want the previously selected AN  module to use   You MUST enter a valid Default gateway IP address that is on the same subnet as the  AN  module  but you don t need to have a device at that address     Host Name   JERR          Obtain an IP address automatically  DHCP     Use the following Settings     IP Address     192 168  0   10  Subnet mask     255   255   255  0    Default gateway    192 168 0   1                Cancel       Enter a Host Name for the AN X  This name is used internally by AN X  and may be used t
44. t there was no response from the  destination in the timeout period  AN X retries the token pass  up to 3 times        Token claim sequence entered    AN X increments this counter when there is no network  activity  no token passing  etc    It then starts soliciting for  stations to pass the token to        Bad CRC on received frame    AN X received a frame with a bad CRC  Usually caused by  cabling and termination        Bad LSAP NAKs sent       AN X uses this counter as a noise counter  If it detects a  carrier on the network and then the carrier disapperas before a          ICAL  SOLUTIONS    A product of Quest Technical Solutions  Sold and Supported by  ProSoft Technology Inc    www prosoft technology com       AN X AB DHRIO  DH   Page 39          Counter    Description       frame starts  it increments this counter        Received frame too small    AN X recievied a frame smaller that the minimum possible  size        Retry of a frame received    AN X received a frame with the same transaction number as a  previous frame  It discards the duplicate frame        Messages successfully sent    AN X increments this counter when it sends a message    command or reply  successfully  It also increments the  commands successfully sent or replies successfully sent  counter        Commands successfully sent    AN X increments this counter when it successfully sends a  command to another station        Commands successfully received    AN X increments this counter when it receives a
    