1. disturbing the critical load bus Module redundancy level shall be a predefined number of modules that are required to supply the full rated load With the number of connected modules equal to this value a malfunction of another module shall cause the load to be transferred automatically and uninterrupted to the bypass line by the use of the static mains bypass switch 2 2 3 System Protection The UPS shall have built in protection against surges sags and over current from the AC rectifier input source over voltage and voltage surges from output terminals of paralleled sources and load switching and circuit breaker operation in the distribution system The UPS rack system shall be protected against sudden changes in output load and short circuits at the output terminals The UPS shall have built in protection against permanent damage to itself and the connected load for all predictable types of malfunctions Fast acting current limiting devices shall be used to protect against cascading failure of solid state devices Internal UPS malfunctions shall cause the module to trip off line with minimum damage to the module and provide maximum information to maintenance personnel regarding the reason for tripping off line The load shall be automatically transferred to the bypass line uninterrupted should the connected critical load exceed the Emerson Network Power 11 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 capacity o
2. BCB open Normal mode SPM Internal Comm Failure SPM Maitainance Bypass Operation invalid BCB closed Battery mode ERN E Output fuse fail Battery float charging Check UPS output SPM Output Breaker Open Control power 2 fail Battery boost charging Generator connected Turn on fail Unit over load Battery discharging BCB open Alarm reset Byp abnormal shutdown Battery period testing BCB closed UPS system testing Inverter over current Batt capacity testing Battery float charging Inverter in setting Batt maint Testing E Inverter ON OFF Each UPS module shall be equipped with an inverter ON OFF buttons which will transfer the load from all UPS modules to the bypass mains supply if it is available The inverter ON OFF control shall be protected under menu confirm protect if the bypass mains is not available 2 3 7 Communication Ports The UPS shall have input and output volta free contactsa to provide the following interfaces EPO Environment parameter input interface User communication interface Intellislot intelligent card interface Temperature detection interface See Section 2 4 for a description of the required optional equipment 2 3 8 Software Compatibility The UPS shall have optional software available for monitoring control and event management The available solutions shall provide users with basic UPS operating status plus automated shutdown of a
3. a battery disconnect and battery system The UPS system shall be modular scalable in design and shall be hot swappable with internal power distribution modules and branch monitoring system 2 2 2 Configurations The UPS rack system shall consist of either a single power module unit or two or more up to a maximum of five units in the same UPS rack enclosure Systems greater than one power module shall operate simultaneously in a parallel configuration with the load shared equally between the connected modules With the exception of a single module configuration the system shall be redundant or non redundant as stated elsewhere in this specification A Non redundant system all the modules making up the UPS system shall supply the full rated load If a module should malfunction and that the remaining modules cannot support the load the load has to be transferred automatically and uninterrupted to the bypass line by the use of the internal static mains bypass switch B Redundant system the UPS system shall have one or more module s than required to supply the full rated load The malfunction of one of the modules shall cause that module to be disconnected from the critical load and the remaining module s shall continue to carry the load Upon repair of the module it shall be reconnected to the critical load to resume redundant operation Any module shall also be capable of being taken off the critical load manually for maintenance without
4. a total of up to 3 PDU modules with 54 single pole MCBs These shall be orated 10 63A single pole MCBs An internal intelligent branch circuit monitoring system shall also be fitted inside the UPS rack system for continuous monitoring of each output branch distribution 2 4 OPTIONS 2 4 1 Optional Communications A SNMP HTTP Network Interface Card The UPS shall have an optional internally fitted network interface card that will provide real time status information over an 10 100 base T Ethernet to for users The network interface card will support SNMP v1 v2c and be MIB II compatible for integration into an ENP monitoring solution or a Network Management System The card supports SNMP traps for up to 20 destinations and supports LGP and RFC1628 MIB definitions UPS information will also be available over the network via a web browser via an HTTP page The card supports static as well as DHCP and BootP boot modes of operation for plug and play network installations The card is also configurable via the network using the HTTP web page Telnet session or serial interface Configuration properties include device naming and specific service enable disable and control enable disable The card provides configuration and control security through a user name and password The cards firmware can also be update such that future releases can be downloaded to enjoy card enhancements B RS 485 Interface Card The UPS shall have an optional interna
5. increments Default shall be 2 0 Hz Frequency Stability Frequency regulation whilst free running on battery shall be 0 05 Hz If the bypass is available and within limits even if the UPS is on battery operation in this case the output will sync to the bypass Nominal frequency shall be 0 05 in single module mode and 0 25 in parallel mode Frequency Slew Rate For single mode the slew rate shall be adjustable from 0 1Hz s to 3Hz s default setting shall be 0 1 Hz s For parallel mode the slew rate shall be fixed to a suitable value default setting shall be 1 Hz s Efficiency It is defined as output kW input kW e Up to 96 at full rated load nominal input no battery Greater than 95 for loads over 25 e Not less than 98 at full rated load when supplying the load through the static bypass G Phase Unbalance 120 1 el for 100 balanced or unbalanced loads Voltage Transients 5 for 100 output load step up or step down Transient Recovery Time Return to within 5 of steady state output voltage within half a cycle Emerson Network Power 6 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 J Voltage Distortion at 400V 100 rated load with crest factor 3 1 e Less than 1 total harmonic distortion THD for linear loads e 4 THD for 100 balanced non linear loads 3 1 crest factor e 5 THD for 100 unbalanced non linear loads 3 1 crest factor K Module Overload Capability at R
6. me eS eG ele satan tees 9 127 2 Battery Warranty nists step argh Aw E Sia 9 1 8 QUALTY ASSURANCE sot aia a a ata A A 9 1 8 1 Manufacturer Qualifications cccccccssccessceesecseccecssecesccecsaecseceecsaecsscecsueeeeseecaeesseeeceseseeseecseeeeneees 9 1 7 2 Factory Testa iia 9 2 ASFABRICATIION outils edad Da Dt E 10 QA A Materials ita aia iaa RA 10 LULA aie A eet aie va A 10 21 3 Consttuct OM ei li a ds 10 NR COONS sects tl Bei ate E aie a a aie 10 2 2 EQUIPMENT Licor aged ae eee tied eave aired Cai Da Dt ied 11 22 1 UB SYM ties AGRA RY ai lis oe oh aeons ah a aeleG aes 11 2 2 2 Comm guratlOns sd RA iO iia ieee Raves Ei a SE 11 2 2 3 System Protection ui ire aie a ae dasha ea ana ohare se 11 2 3 STANDARD COMPONENTS oerrinne deaa naar n nn nr ran nn ieaie ierdie i a e 12 23 L Reca iio is loo apa id 12 2 3 2 Battery converte anen aii aid ias i des 13 2 3 3 A E NA 13 2 3 4 Static Bypass aio ias oa an 14 2 3 5 Internal Maintenance Bypass ocni iesin lios di iii antiga avin aia die cd 14 2 3 6 Man Machine Interface MMD ccscccsssecssscesscecsecesseecsaecesseecascssseecsaecsecseceeeseaeecsasesesaecesaeessaes 14 2 3 7 Communication POTS cian an tido Bande ii ities ea did 17 2 3 8 Software Compatibility ica dad ia ias dto id 17 2 3 9 LBS Load Bus Synchronizer enorer Eea e Era EE EEEE EE E ERE 18 2 3 10 Internal modular Power Distribution Unit PDU with optional Branch Circuit Monitoring SAKE O ON 18 24 OPTIONS lo ia rE O da tee e
7. minute e 125 of UPS rated output with a resistive load for ten minutes e 110 of UPS rated output with a resistive load for one hour B Output Frequency The inverter shall track the bypass mains supply continuously providing the bypass source remains within the limits for the rated frequency of either 50 or 60Hz The inverter will change its frequency at 0 1Hz per second to maintain synchronous operation with the bypass This shall allow make before break transfers of the load between the inverter and the bypass mains supply If the bypass mains supply frequency falls outside of these limits the inverter shall revert to an internal digital oscillator that maintains the inverter output frequency to within 0 05 of nominal frequency in single module mode and 0 25 in parallel mode C Phase to Phase Balance System logic shall provide individual phase voltage compensation to obtain phase balance of 1 under all conditions including up to 100 unbalanced non linear load D Fault Sensing and Isolation Fault sensing shall be provided to isolate a malfunctioning inverter from the critical load bus to prevent disturbance of the critical load voltage beyond the specified limits The inverter output static switch shall be switched off to isolate a malfunctioning module from the critical load E Battery Protection The inverter shall be provided with monitoring and control circuits to protect the battery system from damage due to excessive discha
8. start up date or 15 months after ship date whichever comes first 1 7 2 Battery Warranty The battery manufacturer s standard warranty shall be passed through to the end user 1 8 QUALITY ASSURANCE 1 8 1 Manufacturer Qualifications A minimum of twenty years experience in the design manufacture and testing of solid state UPS systems is required The manufacturer shall be certified to ISO 9001 1 7 2 Factory Testing Before shipment the system shall be fully and completely tested to ensure compliance with the specification Emerson Network Power 9 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 PRODUCT 2 1 FABRICATION 2 1 1 Materials All materials of the UPS Rack System shall be new of current manufacture high grade and shall not have been in prior service except as required during factory testing All active electronic devices shall be solid state Control logic and fuses shall be physically isolated from power train components to ensure operator safety and protection from heat All electronic components shall be accessible from the front 2 1 2 Wiring Wiring practices materials and coding shall be in accordance with the requirements of IEC All electrical power connections shall be torqued to the required value and marked with a visual indicator English tag Provision shall be made in the cabinets to permit installation of input output and external control cabling Provision shall be made for b
9. AC source shall be initiated if an overload or short circuit condition is sustained for a period in excess of the inverter output capability or due to a malfunction that would affect the output voltage Transfers caused by overloads shall initiate an automatic retransfer of the load back to the inverter only after the load has returned to a level within the rating of the inverter source C Back feed Protection Using another optional customer supplied contactor located upstream of the UPS Bypass input and whose trip coil control voltage comes from the input bypass line voltage the UPS shall provide a normally closed contact to be used for isolating the bypass source to protect the operator against back feed of energy resulting from a short circuit of the bypass line SCRs That is in the event that the UPS works on Battery mode and no main input Rectifier and Bypass is available the contactor cannot be closed So if the bypass line SCRs are short circuited the UPS will be still disconnected from the Bypass supply 2 3 5 Internal Maintenance Bypass A fully rated bypass circuit shall be fitted on all single module UPS systems to provide an alternative path for power flow from the alternate AC supply to the critical load for the purpose of maintaining the UPS when it is completely powered down A Maintenance Bypass protection shall be provided it will be activated when the Maintenance Bypass Switch is closed before the inverter shutdown 2 3 6
10. EMERSON Liebert APM UPS GUIDE SPECIFICATIONS For a 30 to 150 kVA kW 50 or 60Hz Modular Digital Uninterruptible Power Supply UPS System Emerson Network Power ma Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 Contents TAL SUMMARY ns AIAR A A AR E atin A AARE atten AA asters 3 Te STANDARDS cai TRE Aa E Sates TEE darth EI Aa E E A RA 3 Ta SYSTEM DESCRIPTION isre aaaea SAna a caren ea A E aR ET A ETARE ie ARRS Aa ae ARREN 4 1 3 1 Design Requirements srta tir 4 1 3 2 Modes Of Operation rta A A ii a 4 1 3 3 Scalability amp Modulo 0d tt 5 1 33 1UPS Module AC Input uta ada cs 6 1 33 2 UPS Modul AC OUP siria ett pit rita 6 1 3 3 3 Bypass Static S with 2 eegee er eerie E e e aE EA e e RNS E Eea s 7 TRS PE Farthing APESE OS 7 1 4 ENVIRONMENTAL CONDITIONS gt rosia amaa naai nn nr nnnn nn ar nnn rra rnnnnn rar nnnn rara 8 1 4 1 Operating Ambient Temperatures s 2 sec ccscdeecescsecsanesdbdstasecepsocdesenssbesetevetsdpspasontsescecdosvbneboasaviessaaes 8 1 4 2 Storage Transport Ambient Temperature 0 cc eecesescssecscesecseeseeseceeesecseeecsaceeesaecaeesesneseeenaesetees 8 1 4 3 Relative H midity ia idad 8 VA A Alida did ida 8 Operating To 1000 m above sea level without de TatiO8 0 0 cece eeeeceseeeeseceeeecneeeecsaeeeessecneeseenerseeerens 8 AS O O OS 8 to UPS DIMENSION 5 O ee aera 8 1 6 UPS DELIVERY SUBMITTAL S Gta ad 9 17 WARRANTS A add teed epee ere et eta 9 17 AUBS Waman ld ese E deed
11. Man Machine Interface MMI A UPS Display and Control Panel Each UPS module shall be equipped with a 320 x 240 dot graphic LCD display Dimension L x H 160x109 mm This shall Emerson Network Power 14 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 automatically provide all information relating to the current status of the UPS as well as being capable of displaying metered values The display shall be menu driven permitting the user to easily navigate through operator screens The LCD shall be able to store 512 historical event records that can be retrieved and reference and diagnosis Metered Values An MCU or DSP shall control the display functions of the monitoring system All three phase parameters shall be displayed simultaneously All voltage and current parameters shall be monitored using true RMS measurements for accurate 1 representation of non sinusoidal waveforms typical of computers and other sensitive loads The following parameters shall be displayed e Main input e Three phase main input line to neutral voltage e Three phase main input line to line voltage e Three phase main input current e Main input frequency e Three phase input power factor e Bypass e Each phase bypass input line to neutral voltage e Bypass input line to line voltage Bypass input frequency e UPS output e Each phase output voltage of UPS e Each phase output current of UPS e Output line to line voltage of UPS e Power factor
12. S The UPS and all associated equipment and components shall be manufactured in accordance with the following applicable standards e Safety Requirements IEC 62040 1 1 EN 50091 1 1 EMC IEC 62040 2 Class A EN 50091 2 Class A Performance IEC 62040 3 VFI SS 111 EN50091 3 The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN standards for safety 60950 electromagnetic emission and immunity 61000 series and construction 60146 series and 60529 For more details see below IEC 61000 3 4 IEC 61000 4 2 4 5 6 8 11 EN60950 EN60529 IEC 60146 1 1 The UPS is CE marked in accordance with EEC directives 73 23 low voltage and 89 336 electromagnetic compatibility The Quality System for the engineering and manufacturing facility certificated to conform to Quality System Standard ISO 9001 for the design and manufacture of power protection systems for computers and other sensitive electronics Emerson Network Power Riis Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 1 3 SYSTEM DESCRIPTION 1 3 1 Design Requirements A For non redundant operation applicable not applicable the UPS system shall be sized to provide a minimum of kVA kW output B For redundant operation applicable not applicable the UPS system shall be sized to provide a minimum of kVA kW output with ___ module s out of service Load voltage and b
13. ansferred to bypass the internal maintenance bypass or external maintenance bypass can be turned on and the UPS can be shut down and the battery can be disconnected for maintenance purposes F Module Paralleling For higher capacity or higher reliability power modules can be paralleled inside the UPS rack parallel power modules automatically share the load The largest parallel capacity is up to five times the nominal load of each power module composing the system Each power module shall have its own intelligent control logic to avoid single point of failure There should not be any common controller that controls all power modules in parallel G Regen Mode The UPS rack system shall have the ability to perform self test for full rated capacity without using any external load banks In this mode UPS rectifier inverter and static bypass shall be tested up to full load capacity without any failure Power consumption in this mode shall only be full load losses of UPS H Source Share mode A part of the critical AC load is supplied by the mains AC input and the remainder of the critical AC load is supplied by battery The ratio of the input and the remainder of the critical AC load is supplied by battery The ratio of the power This mode is mostly used in generator mode when a smaller generator than needed is employed 1 3 3 Scalability amp Modularity The UPS rack system shall consist of hot swappable power modules with each modules rate
14. arm and status conditions shall be reported at a single module UPS system or at a paralleled module UPS or both The display and control panel shall report the alarms and status information listed below Each alarm shall be visually displayed in text form and an audible alarm will sound for each alarm displayed see the following table Emerson Network Power 16 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 Control power 1 fail Inv turned OFF manually SPM Board Not Ready Input contactor fault Mains phase reversed EPO SPM CRC Check Error Contactor P S 1 fault Rectifier overcurrent Transfer confirm SPM Branch Curr Over LL Contactor P S 2 fault Soft start fail Transfer cancel SPM Branch Curr Over HL DSP firmware error Bypass unable to trace Fault reset SPM Branch Over Current SPM Board Not Ready Bypass abnormal Alarm silence SPM Branch 1 Inrush OC SPM CRC Check Error Inverter asynchronous Bypass mode SPM Branch Breaker Fail SPM Branch Curr Over LL Inverter fault Normal mode SPM Internal Comm Failure SPM Branch Curr Over HL Inverter overtemp Battery mode SPM Maitainance Bypass Breaker Close SPM Branch Over Current Fan fault Check UPS output SPM Output Breaker Open SPM Branch 1 Inrush OC Main STS fail Generator connected Bypass mode SPM Branch Breaker Fail Bypass STS fail
15. ated Output Voltage e 150 of UPS rated output with a resistive load for one minute e 125 of UPS rated output with a resistive load for ten minutes The UPS will achieve the overload mentioned above lt 30 C operating temperature nominal input voltage and when the battery is in a full charged condition e 110 of UPS rated output with a resistive load for one hour The UPS will achieve the overload mentioned above with 380 400 415V nominal input and output voltage and when the battery is fully charged L Module Current Limit a is equal to 3 4xIn for up to 200ms 1 3 3 3 Bypass Static Switch A Voltage Range Upper limit 10 15 or 20 default shall be 15 Lower limit 10 20 30 or 40 default shall be 20 B Frequency Range 2 5 5 10 20 Field Selectable C Overload Capability specified without fuses For 100 to 135 rated output current long term operation no time limitation From greater than 135 to 170 rated output current 10 minutes For 1000 of full UPS rated output current 100 milliseconds D Neutral Conductor Sizing 1 7 times rated current 1 3 3 4 Earthing The AC output neutral shall be electrically isolated from the UPS chassis The UPS chassis shall have an equipment earth terminal Provisions for local bonding are to be provided Emerson Network Power Fs Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 1 4 ENVIRONMENTAL CONDITIONS 1 4 1 Operati
16. computers Operating System in the event of an extended power outage cost efficient centralized monitoring and event management of UPS Environmental and Power systems that can utilize an existing network infrastructure Emerson Network Power 30 150kVA kW Modular UPS System 17 Guide Specifications Version 1 0 2 3 9 LBS Load Bus Synchronizer The objective of the Load Bus Synchronizer LBS is to keep the output of two independent UPS systems either two independent single units OR two independent parallel systems each with and without Main Static Switch in synchronization even when the two systems are operating on different modes bypass inverter or on batteries It is usually used with Static Transfer Switches to achieve Dual Bus Power Supply configuration LBS shall be able to synchronize systems of same type and brand each system composed of same type and brand paralleled UPS s with TWO completely different sources of incoming power to UPS systems With optional LBS adapter it shall be possible to synchronize systems of different type and brand each system composed of same type and brand paralleled UPS s with TWO completely different sources of incoming power to UPS systems 2 3 10 Internal modular Power Distribution Unit PDU with optional Branch Circuit Monitoring System The UPS rack system shall be equipped with an internal output distribution that can offer up to 18 single pole MCBs per PDU module and
17. d for 30kVA kW and scalable up to 150kVA kW Modularity design of the UPS system shall enable ease of service and upgradability or downgrade ability of the UPS rack system without interruption to the whole system Emerson Network Power ayia Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 1 3 3 Performance Requirements The UPS is VFI classified according to IEC 62040 3 producing an output waveform that is independent of both the input supply frequency and voltage 1 3 3 1 UPS Module AC Input A B C Voltage Range 305 to 477V Frequency Range 40 70Hz Power Walk In maximum 30 seconds to full rated input current Field selectable from 5 to 30 seconds adjustable with 5 second increments D Power Factor Shall be gt 0 99 without any option at full rated UPS output load Generator Adaptability UPS input current limit can be adjusted to suit the generator power rating Wide input frequency range is permissible Current Distortion Less than 3 at full rated UPS output load and 100 balanced non linear load with input voltage THD lt 2 1 3 3 2 UPS Module AC Output Three phase 4 wire plus ground Load Rating UPS shall be able to support Unity power factor load rating at indicated ambient temperature for any combination of linear and non linear loads Voltage Stability 1 steady state for balanced loads 2 for 100 unbalanced loads Bypass Line Sync Range Field selectable 0 5 to 3 0 Hz at 1 0 Hz
18. de Specifications 30 150kVA kW Modular UPS System Version 1 0 2 3 2 Battery converter Batteries can be VRLA Maintenance Free Ni Cd or Wet Cell type Constant current boost charging constant voltage boost charging float charging float charging compensation and EOD protection are available for different kinds of batteries A Charging In addition to supplying power to the load the battery converter shall be capable of producing a battery charging current sufficient to replace 95 of the battery discharge power within ten 10 times the discharge time Ripple voltage at the battery terminal RMS should be less than 1 and ripple current must not exceed 5 of C 10 Ah rating nominal discharging current Number of battery is 30 40 blocks nominal voltage is 12V per block B Discharging The battery converter will supply power to the inverter when the rectifier is shut down or in joint mode and also the rectifier is current limiting 2 3 3 Inverter The term inverter shall denote the equipment and controls to convert DC from the rectifier or battery converter to provide AC power to the load The inverter shall be solid state capable of providing the rated output power The inverter shall be of Vector Controlled design and utilize insulated gate bipolar transistors IGBTs switching at high frequency in order to minimize output voltage distortion A Overload Capability e 150 of UPS rated output with a resistive load for one
19. ery or Frequency Converter When the battery system is taken out of service for maintenance or the UPS is used as a frequency converter it is disconnected from the battery converter and inverter by means of an external disconnect breaker s The UPS shall continue to function and meet all of the specified steady state performance criteria except for the power outage back up time capability D Bypass If the inverter fails or the inverter overload capacity is exceeded or the inverter is manually turned off by user and at this time the inverter is synchronous with the bypass the static transfer switch shall perform a transfer of the load from the inverter to the bypass source with no interruption in power to the critical AC load If the inverter is asynchronous with the bypass the static switch will perform a transfer of the load from the inverter to the bypass with interruption in power to critical AC load Emerson Network Power 4 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 This interruption must be less than 15ms in 50Hz or less than 13 33ms in 60HZ The static bypass shall be able to support continuously 135 of rated UPS capacity E Maintenance Each UPS has an internal maintenance bypass external maintenance bypass is an external maintenance bypass which can be installed in the Maintenance Bypass Cabinet MCB If the UPS needs to be maintained or repaired after the inverter is turned off and the load is tr
20. f the available on line modules The status of protective devices shall be indicated on a graphic display screen on the front of the unit 2 3 STANDARD COMPONENTS 2 3 1 Rectifier The term rectifier shall denote the solid state equipment and controls necessary to convert AC to regulated DC for input to the inverter The rectifier shall be of DSP Digital Signal Processor controlled design and utilize insulated gate bipolar transistors IGBTs A Input Current Total Harmonic Distortion Less than 3 at full rated UPS output load and 100 balance non linear load with input voltage THD lt 2 Power factor correction The rectifier also performs a PFC function input power factor shall be a minimum 0 99 AC Input Current Limiting The maximum Input current limit can be reduced at 100 for generator operation Input Power Walk in The rectifier charger shall provide a feature that limits the total initial power requirements the power of rectifier will increase gradually and power walk in time can be set from 5 seconds to 30 seconds default shall be 10 seconds Mains AC Input phase sequence reverse protection Before soft starting of the rectifier if the phase sequence of the main AC input is reversed the rectifier will not start and an alarm displayed on the LCD Input Over Current Protection Each AC phase is individually fused so that loss of any semiconductor shall not cause cascading failures Emerson Network Power 12 Gui
21. lly fitted RS 485 interface card that will provide real time status information over a 2 or 4 wire RS 485 connection The RS 485 Interface Card will support ModBus RTU and JBus Emerson Network Power 18 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 2 4 2 Battery Start The UPS shall be able to start up and run on battery without any incoming mains available The above functionality shall be achieved also when more UPSs are connected in parallel either for redundancy or for capacity 2 4 4 Battery Cabinet Batteries shall be housed in a suitable rack sized cabinet matching in appearance height and depth of the UPS rack This matching battery cabinet shall contain the batteries and the battery circuit breaker for taking out the batteries for maintenance 2 4 5 External battery temperature sensor To ensure temperature compensated charging to protect battery life a battery temperature monitoring probe is necessary to monitor the battery enclosure temperature rise caused by the AC mains power loss and of the battery s internal resistance when operating The probe system includes one battery temperature sensor and one temperature transport Emerson Network Power 19 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0
22. ng Ambient Temperature UPS 0 C to 40 C Battery 25 C 5 C for optimum battery performance 1 4 2 Storage Transport Ambient Temperature UPS 20 C to 70 C Battery 20 C to 30 C 20 C for optimum battery storage 1 4 3 Relative Humidity 0 to 95 non condensing 1 4 4 Altitude Operating To 1000 m above sea level without de rating 1 4 5 Immunity A Conduction IEC 62040 2 class A B Radiation IEC 62040 2 class A C Harmonic IEC 61000 3 4 D Immunity EN 61000 4 2 3 4 6 8 9 11 Level Ill EN 61000 4 5 Level IV 1 5 UPS DIMENSION The UPS dimension shall be housed in 600mm x 1100mm x 2000mm w x h x d free standing rack enclosure for the UPS range of 30kVA 150kVA Emerson Network Power 8 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 1 6 UPS DELIVERY SUBMITTALS The specified UPS shall be supplied with one 1 user manual to include details of A Functional description of the equipment with block diagrams B Detailed installation drawings including all terminal locations for power and control connections for both the UPS and battery system C Safety precautions D Step by step operating procedures E General maintenance guidelines The UPS shall be supplied with a record of pre shipment final factory test report 1 7 WARRANTY 1 7 1 UPS Warranty The UPS manufacturer shall warrant the unit against defects in workmanship and materials for 12 months after initial
23. of each phase UPS output frequency e Local load e Load of each phase of total load e Active power apparent and reactive power of each phase output e Load crest factor e Battery e Battery bus voltage e Battery current e Forecasted Battery backup time remaining time e Battery temperature in degree centigrade Parallel load Apparent power of each output phase for parallel operation system e Active power of each output phase for parallel operation system Emerson Network Power 15 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 e Inactive power Reactive power of each output phase for parallel operation system Input Output transformer when installed e Phase to Neutral L N voltage V e Phase to Phase L L voltage V e SPM Branch Metering e Active power out kW e Apparent power out kVA e Phase to Phase current A e Phase to Neutral A e Load percentage e Power factor e Electric energy kWh e MCB state e Current Ripple Coefficient C Power Flow Mimic Each UPS module shall be equipped with a mimic to indicate power flow to the critical load along with an indication of the availability of the rectifier charger battery automatic bypass inverter load The mimic shall provide a quick and easy indication of the load level displayed on LCD including for overload conditions displayed on LCD This power flow is also shown in the LCD menu D Alarms and Status Information Al
24. ottom access allowing for adequate cable bend radius to the input and output connections 2 1 3 Construction The UPS shall be housed in an IP20 enclosure designed for floor mounting The UPS rack shall be structurally adequate and have provisions for forklift handling Maximum cabinet height shall be 2 meters for all UPS range 2 1 4 Cooling Adequate ventilation shall be provided to ensure that all components are operated well within temperature ratings Temperature sensors shall be provided to monitor UPS internal temperature Upon detection of temperatures in excess of manufacturer s recommendations the sensors shall cause audible and visual alarms to be sounded at the UPS control panel A separate room ambient temperature sensor shall be provided to allow control of the battery charging voltage with change of temperature The air should flow into the cabinet from the front and ventilate from the rear No clearance is required at the rear of the UPS for the purpose of ventilation or maintenance Emerson Network Power 10 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 2 2 EQUIPMENT 2 2 1 UPS System The UPS system shall consist of an appropriate number of power module units to meet capacity and redundancy requirements Each UPS System shall consist of standard rack enclosure three phase power module s mains bypass static protective devices and accessories as specified Each UPS system shall also include
25. rge Shutdown of the inverter shall be initiated when the battery has reached the end of discharge EOD voltage The battery EOD voltage shall be calculated and Emerson Network Power 13 Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 automatically adjusted increased for reduced load conditions to allow for extended autonomy periods without damage to the battery 2 3 4 Static Bypass For time when maintenance is required or when the inverter cannot maintain voltage to the load due to sustained overload current limiting or malfunction a bypass circuit shall be provided for each single module that forms part of the UPS system The modular bypass circuit s shall provide for isolation of the inverter s and provide a path for power directly from an alternate AC bypass source The UPS control shall constantly monitor the availability of the inverter bypass circuit to perform a transfer The inverter bypass of each module shall consist of a static transfer switch operating in conjunction with the inverter output static switch The static switches shall denote the solid state devices that operating simultaneously can instantaneously connect the load to the alternate AC source A Manual Load Transfers A manual load transfer between the inverter output and the alternate AC source shall be initiated from the control panel B Automatic Load Transfers An automatic load transfer between the inverter output and the alternate
26. s 18 2 4 1 Optional Communications ia a oli 18 2 4 2 Battery talladas oia 19 2 4 4 Battery Cabe mini Aa 19 2 4 5 External battery temperature Sensor ienn piren iskier eip cone sri reco kiek Es 19 Emerson Network Power De Guide Specifications 30 150kVA kW Modular UPS System Version 1 0 GENERAL 1 1 SUMMARY These specifications describe requirements for a Modular amp Scalable Digital Uninterruptible Power System UPS consisting of one or more single power module units connected in parallel inside a standard 600mm x 1100mm x 2000mm rack without the need for either an additional system controller or an external centralized main bypass static switch The UPS system shall have provision for internal Modular Power Distribution Unit or PDU with optional branch circuit monitoring The UPS shall automatically maintain AC power within specified tolerances to the critical load without interruption for specified duration as per battery run time during failure or deterioration of the mains power supply The UPS shall be expandable by paralleling additional modules of the same rating to provide for module redundancy or load growth requirements The manufacturer shall design and furnish all materials and equipment to be fully compatible with electrical environmental and space conditions at the site It shall include all equipment to properly interface the AC power source to the intended load and be designed for unattended operation 1 2 STANDARD
27. ypass line voltage will be _ VAC three phase and neutral Input voltage willbe ___ VAC three phase The battery system shall have a capacity of___ kW for at least____ minutes at 25 C The battery will be installed On open racks On cladded racks In battery cabinets 1 3 2 Modes of Operation The UPS shall be designed to operate as an on line double conversion reverse transfer system in the following modes A Normal UPS inverters continuously powers the critical AC load The rectifier chargers derives power from the mains AC power supply source converting this to DC power to supply the inverters while simultaneously float boost charging the battery system Power supplied by the UPS inverters is to within specified tolerances at rated voltage and frequency B Battery Upon failure of the mains AC power supply source the critical AC load is powered by the inverter which gets without interruption power from the battery system There shall be no interruption in power to the critical load upon failure or restoration of the mains AC power supply source Upon restoration of the mains AC power supply source power to the rectifier initially is restricted by a gradual power walk in Following the short power walk in period the rectifier powers the inverter and simultaneously recharges the battery through the battery converter This shall be an automatic function and shall cause no interruption to the critical load C Off Batt