Home

Evolis from 7.2 to 24 kV

image

Contents

1. Description of functions Remote control Function Remote control enables the remote opening and closing of the circuit breaker Composition The remote control mechanism comprises m an electrical motor with gearing m a shunt closing release YF combined with an anti pumping device m an operation counter Electrical motor with gearing The electrical motor carries out the automatic rearming of the stored energy unit as soon as the circuit breaker is closed This allows the instant reclosing of the device after opening The arming lever is only used as a backup operating mechanism in the case of the absence of the auxiliary power supply The M3 contact indicates the end of arming operations Characteristics Power supply See Order form page Threshold V AC V DC 0 85 to 1 1 Un Consumption V AC 380 VA VDC 380 W Shunt closing release YF This release allows the remote closing of the circuit breaker when the operating mechanism is armed Characteristics Power supply See Order form page Threshold V AC 0 85 to 1 1 Un VDC 0 85 to 1 1 Un Consumption V AC 160 VA VDC 50 W The shunt closing release is combined with an anti pumping relay that enables priority to be given to opening in the case of a permanent closing order This thus avoids the device being caught in an uncontrolled opening closing cycle DE56116 DE60087 DE51953 DE60124 Evolis 24 kV withdrawable
2. Releases combinations table Shunt opening YO1 Shunt opening YO2 1 Undervoltage YM 1 1 1 Mitop 1 1 Operation counter already included if remote control supplied LV plug possibility of choosing a 42 pin LV plug instead of a 21 pin LV plug Operating crank Evolis 24 kV Offer structure cont withdrawable frontal version Locking interlocking DE56039 DE56043 DE56855 DE56035 DE56044 DDE51950 DE56045 TPL 160 TPL 190 Open position circuit breaker locking device without lock Ronis lock Profalux lock Operating mechanism auto discharge 230 mm phase distance circuit breaker 250 mm phase distance circuit breaker Circuit breaker earthing sliding device Pilot module with connecting kit Diagnosis by Schneider Electric expert Cradle with 230 mm phase distance Cradle with 250 mm phase distance Racked in out position contacts 4 AC fig 1 6 field deflectors for cradle bushings fig 2 630 1250 A 2500 A LPCT tore sensor 230 mm phase distance cradle TLP 160 with insulating screen 230 mm phase distance cradle TLP 190 Evolis 24 kV Order form withdrawable frontal version the needed value have to be considered between each horizontal line Rated voltage Ur kv 24 Orange box X corresponds to none priced functions Rated short circuit breaking current Isc kA Rated normal current Ir A Phase distance
3. Open closed auxiliary contacts OC These auxiliary contacts indicate the open or closed position of the circuit breaker The number of contacts available depends on the options chosen on the operating mechanism In the basic configuration the circuit breaker operating mechanism comprises a total of m 5 normally closed contacts NC m 6 normally open contacts NO m 1 changeover contact CHG The usage mode for auxiliary contacts is given in the following table Options NC contact NO contact Remote control 1 1 Shunt opening release each one 0 1 Undervoltage release 0 0 Low energy release Mitop 0 0 Trip circuit Supervision 1 0 To know the final number of available contacts you must deduct the total number of contacts included in the circuit breaker 5 NC 6 NO 1 CHG from the number of contacts used indicated in the table below E g a circuit breaker equipped with a remote control and a shunt release has the following contacts available 4NC 4NO 1 CHG With an undervoltage release instead of a shunt release this circuit breaker would have the following available contacts 4NC 5NO 1 CHG Contact characteristics Rated current 10A Breaking capacity AC 220 V cos 0 3 1A DC 110 220 V L R lt 0 02 s 0 3 A Locking of the circuit breaker in the open position This locking system enables the fitting o
4. MN undervoltage release r 24 30 Vdc 24 V 50 60 Hz 33668 48 60 Vdc 48 V 50 60 Hz 33669 100 130 Vac 50 60 Hz 33670 200 250 Vac 50 60 Hz 33671 MCH electrical motor r 24 30 Vdc 47888 g 48 60 Vdc 47889 100 125 Vdc 47890 200 250 Vdc 47891 48 60 Vac 50 60 Hz 47889 100 130 Vac 50 60 Hz 47893 200 240 Vac 50 60 Hz 47894 4 AC 47887 DE56885 3 o 3 clusters 3 fingers 630 1250 A 59369 CB 3 clusters 3 fingers 630 2500 A 59371 o 3 arms 630 1250 A 59396 Fi 3 arms 630 2500 A 59397 inger 2 1 full bushing 630 1250 A 59382 g 1 full bushing 630 2500 A 59383 you need at least 6 bushings per cradle Field deflectors for bushings g om amp D we eS 6 deflectors used to increase dielectric i withstand from 75 to 95 kV 59283 Standard 18 pins 59114 All options 42 pins 59115 LV terminal blocks 1 terminal block 47074 DE56958 LV wiring 21 marked LV wires fitted in socket type pins 59117 DE56951 DE56951 DE56951 DE56898 DE56897 DE56996 DE56997 Evolis 17 5 kV fixed frontal version Offer structure Separated components cont Upstream and downstream fixed connections Ir to be mounted on basic circuit breaker or bushings 56952 a Fig 3 F il pe WEN o z ce A i i Ss alo Fig 2 Fig 1 DE56953 Upstream fixed connections Ir to be mounted on basic circuit breaker or bushings or do
5. Threshold 0 85 to 1 1 Un Consumption VA or W 180 Motor overcurrent 2 to 3 In for 0 1 s Arming time 6 s maximum Operating rate 3 cycles maximum per minute CH contact 10 A 240 V Shunt releases XF and MX They can be permanently or briefly supplied power Shunt closing release XF This release allows remote closing of the circuit breaker when the control mechanism is armed Shunt opening release MX This release allows remote opening of the circuit breaker It locks it in the open position is the order is latched Power supply See Order form page Threshold XF 0 85 to 1 1 Un MX 0 7 to 1 1 Un Consumption VA or W Triggering 200 for 200 ms Latched 4 5 DE56885 DE56886 DE56887 Evolis 17 5 kV fixed frontal version Operation counter CDM Description of functions Indication Open closed auxiliary position contacts OC These auxiliary contacts indicate the open or closed position of the circuit breaker m Rotary type changeover contacts directly controlled by the circuit breaker mechanism m Indicator contacts are proposed O for standard relaying applications O for low level control applications with plc s or electronic circuits This version is compatible with Sepam series 20 40 80 units Standard delivery 4 Maximum quantity 12 Breaking capacity A Standard Min load 100 mA 24 V Cos 9 0 3 V AC 240 380 10 6 AC12 DC12 480 10 6 690 6 V DC 2
6. EVOset 24 kV fixed lateral version MV connection on the right hand side As a specialist in breaking technologies Merlin Gerin took naturally an interest in vacuum breaking techniques A major R amp D investment was made to develop and engineer Evolis providing customers with the very best of vacuum technology Ceramic chamber rt Shield Fixed contact Y y j J f Mobile contact A KS Metal bellows Fig 1 vacuum interrupter components l Current DE60164 Electrode AMF coil Contact disk Arc plasma Axial magnetic field Fig 2 cross section of AMF contact PE60042 Fig 3 diffuse vacuum arc AMF technology Evolis The very best of vacuum technology Make up of a vacuum interrupter Vacuum interrupters basically have two electrical contacts one fixed and the other mobile and a sealed enclosure The latter enables a high level of vacuum to be maintained inside the interrupter less than 10 2 Pa to provide insulation between the open contacts The dielectric strength of the vacuum allows the contact to contact distance to be reduced This short distance together with the low opening speed allow the use of a low energy control mechanism A metal clusters provides the link between the mobile contact and the enclosure In order to keep the vacuum level required for the correct operation of the interrupter for 30 years the enclosure must be perfectly sealed and the vari
7. Energizing this release causes instant opening of the circuit breaker Characteristics Power supply See Order form page Threshold V AC 0 85 to 1 1 Un VDC 0 7 to 1 1 Un Consumption V AC 160 VA VDC 50 W Undervoltage release YM This release unit causes the systematic opening of the circuit breaker when its supply voltage drops below a value less than 35 of the rated voltage even if this drop is slow and gradual It can open the circuit breaker between 35 and 70 of its rated voltage If the release unit is not supplied power manual or electrical closing of the circuit breaker is impossible Closing of the circuit breaker is possible when the supply voltage of the release unit reaches 85 of its rated voltage Characteristics Power supply See Order form page Threshold Opening 0 35 to 0 7 Un Closing 0 85 Un Consumption Triggering V AC 400 VA VDC 100 W Latched V AC 100 VA VDC 10 W Low energy release Mitop This release includes a low consumption unit and is specifically used with the Sepam 100LA self powered relay REFLEX MODULE or the VIP relay Characteristics Power supply Direct current Threshold 0O 6A lt I lt 3A Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact option DE56115 DE60093 DE60151 Evolis 24 kV withdrawable frontal version Shunt closing release 5
8. DE56041 DE56033 DE56042 DE56036 DE56039 Shunt opening release YO1 or YO2 24 Vdc AAA10 115 48 Vdc AAA10 116 110 Vdc AAA10 117 125 127 Vdc AAA10 118 220 Vdc AAA10 119 110 Vac 50 Hz AAA10 120 220 230 Vac 50 Hz AAA10 121 120 Vac 60 Hz AAA10 122 24 Vdc AAA10 106 48 Vdc AAA10 107 110 Vdc AAA10 108 125 127 Vdc AAA10 109 220 Vdc AAA10 110 110 Vac 50 Hz AAA10 111 220 230 Vac 50 Hz AAA10 112 120 Vac 60 Hz AAA10 113 24 Vdc AAA10 124 48 Vdc AAA10 125 110 Vdc AAA10 126 125 127 Vdc AAA10 127 220 Vdc AAA10 128 110 Vac 50 Hz AAA10 129 220 230 Vac 50 Hz AAA10 130 120 Vac 60 Hz AAA10 131 24 32 Vdc AAA10 027 48 60 Vac dc AAA10 028 100 127 Vac dce AAA10 029 220 250 Vac de AAA10 030 Gear reducer AAA10 065 Open position CB locking device without lock AAA10 092 Ronis lock AAA10 058 Profalux lock AAA10 059 Interlocking kit fixed CB AAA10 033 Evolis 24 kV Offer structure fixed frontal version Separated components cont MV connection accessories lt 2 BX g Clusters set including fingers 630 1250 A AAA10 025 i Ge Ch CB 2500 A AAA10 026 D l NUS S Arms set 630 1250 A AAA10 022 Arm e9 Cluster Finger LV connection lt s 21 pin LV plug LV plug support AAA10 035 5 21 pin plug AAA10 031 42 pin LV plug LV plug support AAA10 035 42 pin plug AAA10 032 2 references are necessary 9 Flexible conduct for LV wiring 59099 8 LV connecting
9. Description of functions Racking in MV connection LV connection Opening circuit Remote control Indication Locking interlocking Wiring diagram Safety functions Dimensions Offer structure Order form Separated components Services Evolis 24 kV fixed frontal version Evolis 24 kV withdrawable frontal version Evolis and EVOset 24 kV fixed lateral version Evolis Pilot monitoring device 11 15 34 35 36 37 38 40 41 42 43 44 45 46 48 49 51 53 67 87 109 PE55101 Evolis 17 5 kV withdrawable frontal version Main characteristics Ur 7 2 kV Isc Ir Phase to phase distance mm 145 185 240 Ud 20 kV 50 Hz 1 min 25 kA 630 A E E Up 60 kV peak 1250 A m m 2500 A m 31 5 kA 630 A m 1250 A m 2500 A E 40 kA 630 A E 1250 A E 2500 A m Ur 12 kV Isc Ir Phase to phase distance mm 145 185 240 Ud 28 kV 50 Hz 1 min 25 kA 630 A E E Up 75 kV peak 1250 A E m 2500 A E 31 5 kA 630 A E 1250 A E 2500 A E 40 kA 630 A E 1250 A Ej 2500 A E Ur 17 5 kV Isc Ir Phase to phase distance mm 145 185 240 Ud 38 kV 50 Hz 1 min 25 kA 630 A a Up 95 kV peak 1250 A E 2500 A E 31 5 kA 630 A T 1250 A m 2500 A E 40 kA 630 A E 1250 A E 2500 A E Rated values Voltage Ur kV rms 7 2 12 17 5 Insulation voltage power frequency withstand Ud kV rms 20 28 38 lightning impulse withstand Up kV peak 60 75 95 Frequency fr Hz 50 60 Short time withstand curr
10. Electrical motor gear reducer shunt closing release anti pumping relay operation counter DE56037 DE56033 Releases combinations table Mitop 1 171 Shunt opening YO1 1 Undervoltage YM 1 Indication Operation counter already included if remote control supplied DE56040 Open position circuit breaker locking device without lock Ronis lock Profalux lock Push button disabling DE56039 EVOset 24 kV Order form fixed lateral version the needed value have to be considered between each horizontal line Rated voltage Ur kv 24 Orange box X corresponds to none priced functions Rated short circuit breaking current Isc kA Rated normal current Ir A Phase distance mm 250 300 Colour for push buttons and indicators IEC standard ANSI standard Push buttons open closed red black Indicator open closed black white green red Operating mechanism charged discharged white yellow charge discharge VIP protection relay VIP30 VIP35 Service current 8 80 A 20 200 A VIP300P VIP300LL Service current 10 50 A 40 200 A 63 312 A 250 1250 A VAP6 test unit for VIP relay Opening release see possible choices in combination table below Shunt opening release YO1 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Undervoltage release YM 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 V
11. Extraction Possible status Possible status operation impossible gt lt Impossible status Racking in 1 Cradle Fool proof protection Anti drop No opening shutters Shutters padlocking possible 2 LV plug Disconnected No racking in Connected be No unplugging 3 Circuit breaker Closed a ae N king N king EE T o racking in B o racking out function 3 Open MACL No closing Open position circuit breaker locking available 9 4 Switchboard door Open No racking in eee No door opening 4 ean ning wien pen No earthing switch closing Closed No racking in 1 This protection mechanism ensures that the performance levels of the circuit breaker correspond with those of the cradle 2 Device that prevents the circuit breaker from dropping when extracted from the cradle The device can be either unlocked manually or when the extraction rig is put in position 3 Option 4 Interlocking device to be fitted to the cubicle door If there is no interlocking the circuit breaker device should be inhibited Evolis 24 kV Dimensions withdrawable frontal version Isc Ir 16 kA 630 A 1250A 25 kA 630 A 1250 A Weight 145 125 kg DE56131 DE56132 Weight 206 148 kg DE56133 DE56132 24 kV 2500 A 2000 A 2500 A 630 A 1250 A 2000 A Circuit breaker cradle
12. Important Detailed installation instructions are given in the Evolis Installation Guide Please consult us DE56032 DE56037 DE56040 DE51954 DE56915 Evolis 24 kV withdrawable frontal version Offer structure The basic withdrawable frontal circuit breaker includes m 6 arms with clusters m racking truck with operating crank and screw shaft system m a manual operating mechanism spring type ma 21 pin LV plug m 1 shunt opening release YO1 m 1 block of auxiliary contacts m an interlocking kit between the LV plug and the circuit breaker position O C The circuit breaker can receive options The cradle includes m 6 bushings with fingers m shutters m shutters mechanism The cradle can receive accessories Phase distance mm 230 250 24 kV 125 kV peak 16 kA 630 A E 1250 A m 2000 A E 2500 A 25 kA 630 A m 1250 A m 2000 A 2500 A 31 5 kA 630 A 1250 A 2000 A 2500 A Remote control see possible choices in combination table below DE56033 Indication 2 E X Rack in rack out operation DE56038 1st opening release Possibility of replacing YO1 by undervoltage release YM fig 2 2nd opening release Shunt opening release YO2 fig 1 Undervoltage release YM fig 2 Low energy release Mitop fig 3 Remote control including Electrical motor gear reducer shunt closing release anti pumping relay operation counter
13. XF shunt closing release MX1 shunt opening release MX2 shunt opening release or MN undervoltage release Mitop low energy release SDE electrical fault signal contact Reset remote SDE contact reset PF ready to close contact Evolis 17 5 kV Dimensions fixed frontal version Phase to phase distance 145 mm Ur Isc Ir Weight 7 2 kV 25 kA 630 A 51 kg 1250 A DE56110 12 kV 25 kA 630 A 1250 A Phase to phase distance 185 mm Ur Isc Ir Weight ou 7 2 kV 25 kA 630 A 55 kg i 31 5 KA 1250 A 31 5 kA 630 A 1250 A 17 5 kV 25 kA 630 A 1250 A 31 5 kA 630 A 1250 A Phase to phase distance 240 mm Ur Isc Ir Weight z gt 240 e 240 90 j 7 2 kV 25 kA 2500 A 79 kg i 2500 A 630 A 1250 A 2500 A 12 kV 2500 A 31 5 kA 2500 A 40 kA 630 A 17 5 kV 25 kA 2500 A 40 kA 630 A 1250 A 2500 A Important Detailed installation instructions are given in the Evolis Installation Guide Please consult us DE56111 DE56111 DE56111 DE56940 Evolis 17 5 kV Offer structure fixed frontal version The basic fixed frontal circuit breaker includes m a manual operating mechanism spring type m 1 shunt opening release MX m 1 block of 4 ON OFF indication contacts The circuit breaker can receive options Phase distance mm 145 185 240 7 2 kV 25 kA 630 A E 1250 A m E 2500 A E 31 5 kA 630
14. frontal version kit to lock the circuit breaker in the open position 8 Description of functions Indication and locking interlocking Operation counter The operation counter is visible on the front panel It displays the number of switching cycles CO that the device has carried out Open closed auxiliary contacts OC These auxiliary contacts indicate the open or closed position of the circuit breaker The number of contacts available depends on the options chosen on the operating mechanism m Inthe basic configuration the circuit breaker operating mechanism comprises a total of O 5 normally closed contacts NC O 6 normally open contacts NO o 1 changeover contact CHG The usage mode for auxiliary contacts is given in the following table Options NC contact NO contact Remote control 1 1 Shunt opening release each one 0 1 Undervoltage release 0 0 Low energy release Mitop 0 0 Trip circuit Supervision 1 0 To know the final number of available contacts you must deduct the total number of contacts included in the circuit breaker 5 NC 6 NO 1 CHG from the number of contacts used indicated in the table below E g a circuit breaker equipped with a remote control and a shunt release has the following contacts available 4NC 4NO 1 CHG With an undervoltage release instead of a shunt release this circuit breaker w
15. 100 127 Vac dc AAA10 029 220 250 Vac dc AAA10 030 Gear reducer AAA10 065 Open position circuit breaker locking device without lock AAA10 092 Ronis lock AAA10 058 Profalux lock AAA10 059 Push button disabling 48536 Pilot module consult us Evolis and EVOset 24 kV Services fixed lateral version The following components can only be adapted or replaced on site by staff trained by Schneider Electric m the Pilot monitoring device except on EVOset m remote control mechanism comprising electrical motor gearing shunt closing release anti pumping relay operation counter m operation counter m low energy release Mitop m circuit breaker front cover Evolis Evolis Pilot monitoring device Panorama Evolis 17 5 kV fixed frontal version Evolis 17 5 kV withdrawable frontal version Evolis 24 kV fixed frontal version Evolis 24 kV withdrawable frontal version Evolis and EVOset 24 kV fixed lateral version Description of functions 11 15 33 53 67 87 110 PE55697 DE56049EN DE56050 Evolis Pilot monitoring device Fitted on the circuit breaker the Pilot monitors its operating conditions YM YL Energy supply IL Aux voltage 8 C 45C e A 50 C 40 C 455 C N gt 20000 I gt 360j Communication Description of functions The Pilot circuit breaker monitoring device has two specific features Monitoring operating c
16. Shunt opening MX Undervoltage MN Mitop Evolis 17 5 kV Offer structure withdrawable Separated components frontal version The following components can be ordered separately and can be adapted or replaced by the customer MX1 MX2 XF shunt opening closing release a 24 30 Vdc 24 V 50 60 Hz 59141 8 48 60 Vdc 48 V 50 60 Hz 59142 100 130 Vac 50 60 Hz 59143 200 250 Vac 50 60 Hz 59144 MN undervoltage release 24 30 Vdc 24 V 50 60 Hz 33668 48 60 Vdc 48 V 50 60 Hz 33669 100 130 Vac 50 60 Hz 200 250 Vac 50 60 Hz 33670 33671 DE56879 MCH electrical motor 24 30 Vdc 47888 S 48 60 Vdc 47889 100 125 Vdc 47890 200 250 Vdc 47891 48 60 Vac 50 60 Hz 47889 100 130 Vac 50 60 Hz 47893 200 240 Vac 50 60 Hz 47894 4 AC 47887 DE56885 g 3 clusters 3 fingers 630 1250 A 59369 8 CB 3 clusters 3 fingers 630 2500 A 59371 3 arms 630 1250 A 59396 peer 3 arms 630 2500 A 59397 5 Standard 18 pins 59114 i All options 42 pins 59115 LV terminal blocks 1 terminal block 47074 DE56958 LV wiring 21 marked LV wires fitted in socket type pins 59117 Upstream and downstream fixed connections Ir to be mounted on basic circuit breaker or bushings E y F 9 3 fixed distance H or V fig 1 630 1250 A 59400 S E EA S S eke i 3 variable distance H fig 3 630 1250 A 59401 Fig 1 Fig 2 Aa Fig 3 3 variable d
17. Shunt opening release MX 24 Vac 24 30 Vdc 100 130 Vdc ac 48 Vac 48 60 Vdc 200 250 Vdc ac Undervoltage release MN 24 Vac 24 30 Vdc 100 130 Vdc ac 48 Vac 48 60 Vdc 200 250 Vdc ac Time delay unit for MN 48 60 Vdc ac 100 130 Vdc ac 200 250 Vdc ca Low energy release Mitop 1 AC fault signalling SDE and reset 200 250 Vac are included Remote control operation counter already included Electrical motor MCH 24 30 Vdc 100 125 Vdc 200 250 Vdc 48 60 Vdc ac 100 130 Vac 200 240 Vac Shunt closing release XF 24 Vac 24 30 Vdc 100 130 Vdc ac 48 Vac 48 60 Vdc 200 250 Vdc ac Operation counter CDM already included if remote control supplied E Additional auxiliary contacts OF 4 AC 1 2 Ready to close contact PF 1 AC ie LV plug 18 pins LV plug 42 pins LV plug _ LV terminal blocks _ Locking of the circuit breaker in the open position By padlock or by locks and keys Profalux If locks 1 lock 2 identical locks Disabling of O C circuit breaker push buttons 2 different locks Evolis 17 5 kV Offer structure fixed frontal version separated components The following components can be ordered separately and can be adapted or replaced by the customer MX1 MX2 XF shunt opening closing release 24 30 Vdc 24 V 50 60 Hz 59141 48 60 Vdc 48 V 50 60 Hz 59142 DE56879 100 130 Vac 50 60 Hz 59143 200 250 Vac 50 60 Hz 59144
18. connector Protection and control E UMI Metering m VPIS m PM500 Panorama Fixed frontal version Withdrawable frontal version Operating mechanism Operating mechanism on the front on the front on the front The Pilot option monitors correct circuit breaker operation Renek en WEB enabled Rated voltage Ur kV 50 60 Hz Short circuit rated breaking capacity Isc from 25 to 40 kA from 25 to 40 kA from 16 to 31 5 kA Rated current Ir from 630 to 2500 A from 630 to 2500 A from 630 to 2500 A Fixed frontal version Operating mechanism Withdrawable frontal version Operating mechanism on the front The Pilot option monitors correct circuit breaker operation Renek en WEB enabled from 16 to 31 5 KA from 630 to 2500 A Panorama Fixed lateral version Operating mechanism on the side Integrated protection system Fixed lateral version Operating mechanism on the side The Pilot option monitors correct circuit breaker operation Ready WEB enabled Rated voltage Ur kV 50 60 Hz Short circuit rated breaking capacity Isc from 12 5 to 25 kA from 12 5 to 20 kA Rated current Ir from 630 to 1250 A from 630 to 1250 A VIP30 for phase protection VIP35 for phase and earthing protection VIP300P for phase protection VIP3OOLL for phase and earthing protection Sepam series 20 for normal ap
19. mm 230 250 Colour for push buttons and indicators IEC standard ANSI standard Push buttons open closed red black Indicator open closed black white green red Operating mechanism charged discharged white yellow charge discharge 1st opening release see possible choices in combination table below Shunt opening release YO1 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Undervoltage release YM 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz 2nd opening release see possible choices in combination table below Shunt opening release YO2 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Undervoltage release YM 24 Vdc 110 Vdc 48 Vdc 125 127 Vdc 220 Vdc 110 Vac 50 Hz 220 230 Vac 50 Hz 120 Vac 60 Hz Low energy release Mitop Remote control operation counter already included Electrical motor 24 32 Vdc 48 60 Vdc ac LT im CLL 100 127 Vdc ac 220 250 Vdc ac Shunt closing release YF 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Operation counter already included if remote control supplied LV plug 42 pin instead of 21 Operating crank Open position CB locking device without lock Lock Ronis Profalux Auto discharge device Earthing sliding contact Pilot module with conne
20. 16 kA 630 A 1250 A 20 kA 630 A 250 A _ DE52024 DE51975 MV connection on the right hand side Phase to phase distance E 250 mm L 1095 Isc 12 5 kA 16 kA 630 A 1250 A 630 A DE51972 DE51973 1250A 630 A 1250A Phase to phase distance E 300 mm L 1195 Ur Isc Weight Ir 24 kV 12 5 kA 630 A 120 kg 1250A 16 kA 630 A 1250 A 20 kA 630 A 1250 A Important Detailed installation instructions are given in the Evolis Installation Guide Please consult us Evolis 24 kV Offer structure fixed lateral version The basic fixed lateral circuit breaker includes m a manual operating mechanism spring type m 1 shunt opening release YO1 m 1 block of auxiliary contacts The circuit breaker can receive options Phase distance mm 250 300 Right Left Right Left co 24 kV 125 kV peak 12 5 kA 630 A 16 kA 630 A x u E 1250 A E 1250A e n u u 25 kA 630 A E Remote control see possible choices in combination table below S 1st opening release Possibility of replacing YO1 by undervoltage release YM fig 2 2nd opening release Shunt opening release YO2 fig 1 Undervoltage release YM fig 2 Low energy release Mitop fig 3 Remote control including Electrical motor gear reducer shunt closing release anti pumping relay operation counter DE56037 DE56033 DE56038 Rele
21. A m 1250 A m 2500 A E 40 kA 630 A E 1250 A E 2500 A E 12 kV 25 kA 630 A E E 1250 A m E 2500 A E 31 5 kA 630 A E 1250 A E 2500 A E 40 kA 630 A E 1250 A E 2500 A E 17 5 kV 25 kA 630 A E 1250 A m 2500 A E 31 5 kA 630 A a 1250 A E 2500 A E 40 kA 630 A E 1250 A m 2500 A E Evolis 17 5 kV Offer structure cont fixed frontal version Remote control see possible choices in combination table below 1st opening release Possibility of replacing MX by undervoltage release MN fig 3 Possibility of replacing MX by low energy release Mitop fig 2 2nd opening release Shunt opening release MX circuit breaker opening fig 3 DE56933 DE56879 DE56881 Fig 3 DE56887 Undervoltage release MN circuit breaker opening fig 3 Time delay unit for MN setting 0 5 0 9 1 5 3 s fig 4 Low energy release Mitop fig 2 1 AC fault signalling SDE and reset 200 250 Vac are included Remote control including Electrical motor MCH and shunt closing release XF and operation counter CDM fig 1 3 amp 5 Releases combinations table MX 1 2111 1 2 1 MN 1 1 1 1 Mitop 1 17171471 Indication Operation counter CDM fig 1 Additional auxiliary contacts OF 4 AC fig 2 Ready to close contact PF 1 AC fig 3 DE56887 DE56885 DE56886 Fig 1 LV wiring connection Standard plug 18 pins fig 1 DE51943 DE51944 DE56889 All options plug 42 pins fig 2 L
22. DE56866 DE56867 DE56868 An adjustable connector enables the vertical distance to be increased to enable rotation of 90 Adjustable gap connectors Extendable connectors Extendable connectors horizontal H vertical V DE56869 DE56870 K OA L QD i is 19 V7 An adjustable connector enables the connection distance to be increased from 0 to 25 mm 3 connector sets Mixed solution Example DE56871 Comment The insulation withstand values given in the performance table do not take account of the connectors With these connectors it is possible to use unplated or tin plated copper conductors or tin plated aluminium conductors without any specific precautions being required The shape and dimensions of these conductors must be determined by the panel builder according to the dielectric withstand and temperature rise characteristics of the whole connection system Typical examples are provided in the Installation Guide DE56872 DE51945 DE56874 Evolis 17 5 kV fixed frontal version N i Vi gt AIT LY P 60 SIS Arms clusters fingers and bushings busbars and field deflectors Description of functions MV connection cont Composition Panels builders can transform a fixed device into a withdrawable device by adding the following assemblies m arms m clusters
23. Guide DE51951 DE51952 Fvolis 24 kV fixed frontal version LV connection with plug Description of functions LV connection Two connection solutions Directly on the LV terminal block The circuit breaker s LV wiring can be directly connected to the LV terminal block of the operating mechanism through a cable protection duct With LV plug m The fixed part male mounted on the circuit breaker and fully connected to the operating mechanism m The mobile part female compatible with the male part Two versions of the LV plug are available An 21 pin version enabling connection of m a shunt opening release YO1 m an electrical remote control mechanism electrical motor shunt closing release XF anti pumping relay m the Pilot monitoring device m a maximum number of auxiliary contacts 3 NC 3 NO 1 changeover contact see indication and locking interlocking page Open closed position auxiliary contacts chapter Note see the table of the releases combinations Order form page An 42 pin version enabling connection of m an opening release shunt type YO1 or undervoltage type YM m a second opening release shunt type YO2 or undervoltage type YM or Mitop low energy release m an electrical remote control mechanism electrical motor shunt closing release YF anti pumping relay m the Pilot monitoring device m a maximum number of auxiliary contacts 5 NC
24. circuit breaker into which is integrated a protection chain comprising m a set of current sensors installed on the lower current terminals of the circuit breaker tyoe CEc CEa or CEb m aVIP protection relay mounted on the control unit of type VIP30 VIP35 VIP300P or VIPS00LL m a Mitop low energy release installed on the circuit breaker operating mechanism The unit is fully independent and functions without an auxiliary power supply PE55932 DE56137 Evolis EVOset with a VIP protection unit installed on the front panel PE55933 EVOset schematic diagram Independent protection chain operating principle The protection chain is supplied with power by sensors which supply m the current information processed by the VIP protection unit m the electrical power required for the whole protection chain to operate VIP relay and Mitop release All settings are visible and accessible from the front of the device To achieve the indicated performance levels the VIP relay must be used with the specified sensors The combination of the unit sensor is essential in order to comply with the indicated characteristics and in particular with m operation throughout the whole range m trip times m precision m short circuit thermal withstand The sensors on each of the phases must be of the same type VIP300LL protection unit Hardware description for the VIP relay The VIP relay is mounted in an injected
25. control Function Remote control enables the remote opening and closing of the circuit breaker The opening order always takes priority over the closing order In the event of simultaneous opening and closing orders the mechanism discharges under no load without moving the main contacts The circuit breaker remains in the open position In the event of latched opening and closing orders the mechanism carries out anti pumping function as standard by blocking the circuit breaker in the open position Anti pumping function after opening on a fault or deliberate opening via the manual or electrical mechanism the closing order must be interrupted then reactivated to enable reclosing of the circuit breaker Composition The remote control comprises m an electrical motor MCH equipped with a spring armed CH limit switch m a shunt closing release XF m a shunt opening release MX m an operation counter It can be added with m a ready to close contact PF m a second block of 4 contacts OC for O C position indication for the circuit breaker m a third block of 4 contacts OC for O C position indication for the circuit breaker Electrical motor MCH The electrical motor carries out the automatic rearming of the storage energy springs as soon as the circuit breaker closes This allows instant reclosing of the device after opening The arming lever is only used as a backup control in the case of the
26. curve EIl curve PE55935 PE55774 EVOset 24 kV fixed lateral version VAP6 test unit Protection monitoring and control Current sensors and test unit for VIP relays Current sensors for VIP relays In order to achieve the specified performance levels the VIP protection relays must be used with the specified sensors The relay sensor pairing is indissociable in order to comply with characteristics and in particular m operation throughout the whole range m response time m precision m short circuit thermal withstand Sensor type Relay Service current Is CEc VIP30 VIP35 8 Ato 200A CEa VIP300P VIP300LL 10 Ato 200A CEb VIP300P VIP300LL 63 A to 1250 A VAP6 test unit for VIP relays VIP type protection units have a test socket to connect a VAP6 test unit This portable unit with its own power supply enables the correct functioning of the protection relay to be checked Evolis and EVOset 24kV Dimensions fixed lateral version MV connection on the right hand side Phase to phase distance E 250 mm L 1095 630 A Isc 12 5 kA 16 kA 630 A DE51971 DE52023 20 kA 630 A 1250A 630 A 1250A Phase to phase distance E 300 mm L 1195 Ur Isc Ir Weight 24 kV 12 5 kA 630 A 90 kg 16 kA 630 A 1250 A 20 kA 630 A 1250 A 25 kA 630 A 250 A MV connection on the left hand side Phase to phase distance E 250 mm L 1095 Ur Isc Weight 12 5 kA 630 A 1250 A
27. in the table below E g a circuit breaker equipped with a remote control and a shunt release has the following contacts available 4NC 4NO 1 CHG With an undervoltage release instead of a shunt release this circuit breaker would have the following available contacts 4NC 5NO 1 CHG m Using a 21 pin LV plug for withdrawable applications the maximum number of available contacts is o 3 NC o 3 NO O 1 changeover Instead of 5 NC 6 NO 1 CHG with a 42 pin socket Contact characteristics Rated current 10A Breaking capacity AC 220 V cos 0 3 1A DC 110 220 V L R lt 0 02 s 0 3 A Locking of the circuit breaker in the open position This locking system enables the fitting of a Profalux or Ronis captive key type keylock right turn type keylock The keylock is not part of the kit but can be supplied as an option DE56117EN Evolis 24 kV fixed frontal version Oe g Motor o 9 lose CB Description of functions Wiring diagram Wiring diagram principle anti pumping Mitop _ S mam Shunt closing Control Shunt Under Low energy Changeover NO NC release mechanism opening voltage release contact contacts contacts anti pumping armed release release Mitop system indicator contact e Remote control Evolis 24 kV Dimensions fixed frontal v
28. is closed for the withdrawable version with a cradle au B S T ii AAN AN S AN i Cubicle door interlocking mechanism Evolis 17 5 kV Description of functions withdrawable Wiring diagram frontal version Wiring diagram principle z Circuit breaker open Operating mechanism loaded l l A A Ready F EN l l close l l l DE56135E MX2 er Remote control Auxiliary contacts MCH electrical motor XF shunt closing release MX1 shunt opening release MX2 shunt opening release or MN undervoltage release Mitop low energy release SDE electrical fault signal contact Reset remote SDE contact reset PF ready to close contact Evolis 17 5 kV Description of functions withdrawable Safety functions frontal version This table describes the safety functions available on the withdrawable version of the Evolis 17 5 kV circuit breaker How to use the table Each of the boxes describes the functional status of each circuit breaker position and the associated parts Possible status Possible status operation impossible gt lt Impossible status Insertion Racking in C OO O O O j EEEE NENE E 1 Cradle Fool proof protection Anti drop No opening shutters Shutters padlocking possible 2 LV plug Disconnected No racking in gt a Connected No unplugging 3 Circuit breaker Closed No racking in A No racking out Ope
29. m fingers m bushings m field deflectors Cluster and finger m The tulip type cluster has a shape which provides maximum contact surface whilst optimising heat dissipation Moreover in the case of short circuit it offers good compensation characteristics for electrodynamic forces m The finger is a component designed specifically for the cluster regarding its shape tolerances and materials Contact between the finger and the cluster is guaranteed by type testing 1000 racking in out operations Arm and bushing m The arms cylindrical shape optimizes dielectric strength and avoids the need for any additional insulation m The bushing s cylindrical shape gives it outstanding dielectric strength m The previously described connectors can be mounted on bushing connection terminals Comment Performance levels of the whole assembled unit must be tested by the panel builder Installation conditions for the two units presented above are described in the Installation Guide For the 17 5 kV withdrawable circuit breaker phase to phase distance 185 mm field deflectors must be added to the bushings Field deflectors For circuit breakers with a rated voltage of Ur 17 5 kV with a phase to phase distance of 185 mm field deflectors are used to increase the dielectric strength by 75 kV to 95 kV DE56889 DE51943 DE51944 Evolis 17 5 kV fixed frontal version 42 pin version LV plug Description of functions LV connectio
30. or electronic circuits This version is compatible with Sepam series 20 40 80 units Standard delivery 4 Maximum quantity 11 Breaking capacity A Standard Min load 100 mA 24 V Cos 9 0 3 V AC 240 380 10 6 AC12 DC12 480 10 6 690 6 V DC 24 48 10 6 125 10 6 250 3 Low level Min load 2 mA 15 V DC VAC 24 48 6 240 6 380 3 VDC 24 48 6 125 6 250 3 Standard contacts 10 A optional contacts 6 A temperature derating Ready to close PF contact The circuit breaker is ready to close when shown by a mechanical indicator and a PF contact This information simultaneously indicates that m the circuit breaker is open m the storage energy springs are armed m there is no permanent closing order m there is no permanent opening order caused by o a safety opening order 2nd MX or MN o keylocking of the device in the open position Standard delivery 0 Maximum quantity 1 Breaking capacity A Standard Min load 100 mA 24 V Cos 9 0 3 V AC 240 380 5 AC12 DC12 480 5 690 3 V DC 24 48 3 125 0 3 250 0 15 Low level Min load 2 mA 15 V DC VAC 24 48 3 240 3 380 3 VDC 24 48 3 125 0 3 250 0 15 Operation counter CDM The operation counter is visible on the front panel It totalizes the number of switching cycles CO that the device has carried out Evolis 17 5 kV Description of functions withdrawable Locking interlocking frontal version DE56891 DE56892 DE56893 DE51947 Locking
31. polycarbonate casing which protects it against run off water and dusty atmospheres The front face is protected by a transparent cover with a seal This cover can be sealed to prohibit access to settings Settings are made with rotary switches The phase service current and the earthing current limit are set directly in Amps Therefore the graduation on the front face must be adapted to the rating used on the sensor this is achieved by a graduation plate must be positioned on the relay when fitted Connection is carried out at the rear of the relay using fast on clips EVOset 24 kV Protection monitoring and control fixed lateral version VIP30 and VIP35 protection units Use Independent protection units VIP30 and VIP35 are intended for use on distribution networks mainly in MV LV substations where they provide upstream protection of the transformer These are independent relays that do not require any auxiliary power supply they are powered by the current sensors The relays directly actuate the Mitop release DE56138 Simplified connection arrangement The associated current sensors of type CEc give a setting range of Is 8 Ato 200A for the service current VIP30 relay This provides protection against phase to phase faults The protection curve is similar to a fuse curve Phase protection is achieved using an inverse definite time threshold from 1 2 times the service current Is VIP35 relay T
32. priority to be given to opening in the case of a permanent closing order This thus avoids the device being caught in an uncontrolled opening closing cycle DE56116 DE60087 DE51953 DE60124 Evolis 24 kV fixed frontal version kit to lock the circuit breaker in the open position 8 Description of functions Indication and locking interlocking Operation counter The operation counter is visible on the front panel It displays the number of switching cycles CO that the device has carried out Open closed auxiliary contacts OC These auxiliary contacts indicate the open or closed position of the circuit breaker The number of contacts available depends on the options chosen on the operating mechanism m In the basic configuration the circuit breaker operating mechanism comprises a total of O 5 normally closed contacts NC O 6 normally open contacts NO O 1 changeover contact CHG The usage mode for auxiliary contacts is given in the following table Options NC contact NO contact Remote control 1 1 Shunt opening release each one 0 1 Undervoltage release 0 0 Low energy release Mitop 0 0 Trip circuit Supervision 1 0 To know the final number of available contacts you must deduct the total number of contacts included in the circuit breaker 5 NC 6 NO 1 CHG from the number of contacts used indicated
33. to each sensor LPCT for cubicle CLP type Electrical characteristics m conformity with IEC standard 60044 8 which defines LPCT s with an output voltage m usable for nominal currents of 25 A to 2500 A m class 0 5 throughout the range m current sensors give a voltage output at a ratio of 100 A 22 5 mV Rated primary current 100A Rated secondary output at 100 A 22 5 mV Accuracy class for measuring 0 5 Accuracy class for protection 5P Burden gt 2 kQ Frequency 50 60 Hz Assembly In the cubicle In the cubicle On the bushings On the bushings DE60097 DE60098 DE60099 DE60100 Rated extended primary current 1250 A 2500 A 1250 A 2500 A Accuracy limit factor 250 315 250 315 Rated short time thermal current 25 kA 3 s 31 5 kA 3 s 25 kA 3 s 31 5 kA 3 s Rated voltage 24 kV 24 kV 24 kV 1 24 kV 1 Rated power frequency withstand voltage 50 kV 50 kV 50 kV 50 kV Rated lightning impulse withstand voltage 125 kV 125 kV 125 kV 125 kV Internal diameter 160 mm 190 mm 1 Voltage applied to the cradle equipped with sensors DE60158 Evolis 24 kV withdrawable frontal version DE56026 Description of functions MV connection Connection The customer connection is carried out easily from outside the cradle on copper vertical connection terminals integrated in the bushings Field deflectors The aim of field deflectors is to improve the dielectric strength at the
34. values Voltage Ur kV rms 24 Insulation voltage power frequency withstand Ud kV rms 50 lightning impulse withstand 1 2 50 us Up kV peak 125 Frequency fr Hz 50 60 Short time withstand current Ik tk kA Isc 3 s Peak withstand current Ip kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Short circuit making capacity kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Other characteristics Operating sequence O 0 3 s CO 15 s CO O 0 3 s CO 3 min CO O 3 min CO 3 min CO Operating times Opening ms lt 50 Breaking ms lt 65 Closing ms lt 70 Mechanical endurance Class M2 Number of switching 10000 30000 on request operations Electrical endurance Class E2 Number of switching operations 16 kA 100 at full Isc value 25 kA 100 31 5 kA 100 Capacitive current breaking capacity Class C1 C2 for certain applications Operating conditions 25 C to 40 C Average relative humidity Over 24 h lt 95 Over 1 month lt 90 Evolis 24 kV fixed frontal version Description of functions MV connection Composition The basic circuit breaker is equipped with nickel plated aluminium connector terminals with drilled holes Connection The customer connection is carried out easily from outside the circuit breaker on these vertical connection terminals DE56011 Connection configurations that have undergone type testing are shown in the Installation
35. 122 24 Vdc AAA10 106 48 Vdc AAA10 107 110 Vdc AAA10 108 125 127 Vdc AAA10 109 220 Vdc AAA10 110 110 Vac 50 Hz AAA10 111 220 230 Vac 50 Hz AAA10 112 120 Vac 60 Hz AAA10 113 24 Vdc AAA10 124 48 Vdc AAA10 125 110 Vdc AAA10 126 125 127 Vdc AAA10 127 220 Vdc AAA10 128 110 Vac 50 Hz AAA10 129 220 230 Vac 50 Hz AAA10 130 120 Vac 60 Hz AAA10 131 24 32 Vdc AAA10 027 48 60 Vac dc AAA10 028 100 127 Vac de AAA10 029 220 250 Vac de AAA10 030 Gear reducer AAA10 065 Open position circuit breaker locking device without lock AAA10 092 Ronis lock AAA10 058 Profalux lock AAA10 059 Push button disabling 48536 Pilot module consult us EVOset 24 kV Offer structure fixed lateral version The basic fixed lateral circuit breaker includes m a manual operating mechanism spring type m low energy release Mitop m 1 block of auxiliary contacts m phase protection relay VIP 30 and associated sensors The circuit breaker can receive options Phase distance mm 300 gt 24 kV 125 kV peak 12 5 KA 630 A E D 16 kA 630 A u 1250 A E 250A mi Remote control see possible choices in combination table below Protection relay Possibility of replacing VIP30 by VIP35 phase protection earth VIP300P phase protection VIP300LL phase protection earth VAP6 test unit for VIP relay Opening release Shunt opening release YO1 fig 1 Undervoltage release YM fig 2 Remote control including
36. 1250 A E 2500 A E 31 5 kA 630 A T 1250 A E 2500 A E 40 kA 630 A E 1250 A E 2500 A E Rated values Voltage Ur kV rms 7 2 12 17 5 Insulation voltage power frequency withstand Ud kV rms 20 28 38 lightning impulse withstand Up kV peak 60 75 95 Frequency fr Hz 50 60 Short time withstand current Ik tk kA Isc 3 s Peak withstand current Ip kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Short circuit making capacity kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Other characteristics Operating sequence O 0 3 s CO 15 s CO O 0 3 s CO 3 min CO O 3 min CO 3 min CO Operating times Opening lt 50 ms Breaking lt 60 ms Closing lt 65 ms Mechanical endurance Class M2 Number of switching 10000 operations Electrical endurance Class E2 Number of switching operations 25 kA 100 at full Isc value 31 5kA 50 40 kA 30 Capacitive current breaking capacity Class C1 Operating conditions 25 C to 40 C Average relative humidity Over 24 h lt 95 Over 1 month lt 90 DE56864 DE56865 Evolis 17 5 kV Description of functions fixed frontal version MV connection Composition The basic circuit breaker is equipped with drilled copper connection terminals at the top and bottom of the breaking units The connectors are fitted to the terminals using the corresponding bolts Several variants are possible Fixed connectors Horizontal connectors H Vertical connectors V Mixed connectors
37. 4 48 10 6 125 10 6 250 3 Low level Min load 2 mA 15 V DC VAC 24 48 6 240 6 380 3 VDC 24 48 6 125 6 250 3 Standard contacts 10 A optional contacts 6 A temperature derating Ready to close PF contact The circuit breaker is ready to close when shown by a mechanical indicator and a PF changeover contact This information simultaneously indicates that m the circuit breaker is open m the storage energy springs are armed m there is no permanent closing order m there is no permanent opening order caused by o a safety opening order 2nd MX or MN o keylocking of the device in the open position Standard delivery 0 Maximum quantity 1 Breaking capacity A Standard Min load 100 mA 24 V Cos 9 0 3 V AC 240 380 5 AC12 DC12 480 5 690 3 V DC 24 48 3 125 0 3 250 0 15 Low level Min load 2 mA 15 V DC VAC 24 48 3 240 3 380 3 VDC 24 48 3 125 0 3 250 0 15 Operation counter CDM The operation counter is visible on the front panel It totalizes the number of switching cycles CO that the device has carried out DE56891 DE56892 DE56893 Evolis 17 5 kV Description of functions fixed frontal version Locking interlocking DE56894 Locking the circuit breaker in the open position Opening button Closing button Control mechanism status charged or discharged Push button locking Circuit breaker position indicator Operation counter Push button locking This tran
38. 5 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Undervoltage release YM 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz 2nd opening release see possible choices in combination table below Shunt opening release YO2 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Undervoltage release YM 24 Vdc 48 Vdc 110 Vdc 125 127 Vdc 220 Vdc 110 Vac 50 Hz 220 230 Vac 50 Hz 120 Vac 60 Hz Low energy release Mitop Remote control operation counter already included Electrical motor 24 32 Vdc 48 60 Vdc ac IT LLU 100 127 Vdc ac 220 250 Vdc ac Shunt closing release YF 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Operation counter already included if remote control supplied fl LV plug 21 pins LV plug 42 pins LV plug Open position CB locking without lock Lock Ronis Profalux Pilot module with connecting kit E Without LV plug Diagnosis by Schneider Electric expert separated order E No LV plug or 21 pin 42 pin LV plug LV plug Shunt opening YO1 1 1 111 1 Shunt opening YO2 1 Undervoltage YM 1 1 1 Mitop 1 1 Fvolis 24 kV fixed frontal version Offer structure Separated components The following components can be ordered separately and can be adapted or replaced by the customer DE56037
39. 6 NO 1 changeover contact see indication and locking interlocking page Open closed position auxiliary contacts chapter Note see the table of the releases combinations Order form page LV wiring kit A wiring kit with 21 or 42 wires 2 meters long equipped with pins that can be adapted to the LV plug can be supplied for connected in to the cubicle s LV compartment Flexible ducting This 525 mm long duct with a hinged LV plug enables protection of the LV wiring that connects the circuit breaker to the cubicle s LV compartment Interlocking kit For circuit breakers intended for withdrawable applications an interlocking kit can be adapted The kit enables the mechanical position status to be given connected disconnected of the LV plug By adding a link between this mechanical data by the customer and the open closed position of the circuit breaker interlocking can be achieved between the LV plug and the open closed position of the circuit breaker required by IEC standard 62271 200 A detailed explanation of operation is given in the Installation Guide DE56114EN DE60094 DE60089 DE60091 Evolis 24 kV fixed frontal version al z Low energy release 3 Description of functions Opening circuit Composition The opening circuit is produced using the following components m shunt open
40. A 630 A 1250 A 2000 A 2500 A Rated values Voltage Ur kV rms 24 Insulation voltage power frequency withstand Ud kV rms 50 lightning impulse withstand 1 2 50 us Up kV peak 125 Frequency fr Hz 50 60 Short time withstand current Ik tk kA Isc 3 s Peak withstand current Ip kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Short circuit making capacity kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Other characteristics Operating sequence O 0 3 s CO 15 s CO O 0 3 s CO 3 min CO O 3 min CO 3 min CO Operating times Opening ms lt 50 Breaking ms lt 65 Closing ms lt 70 Mechanical endurance Class M2 Number of switching 10000 30000 on request operations Electrical endurance Class E2 Number of switching operations 16 kA 100 at full Isc value 25 kA 100 31 5 kA 100 Capacitive current breaking capacity Class C1 C2 for certain applications Operating conditions 25 C to 40 C Average relative humidity Over 24 h lt 95 Over 1 month lt 90 m Merlin Gerin Evolis 24 kV Description of functions withdrawable Racking in frontal version TI Composition The racking in function is carried out by m the racking carriage holding the circuit breaker mobile part m the cradle with bushings fixed part m LV plug DE51984 Operating position i Operation The circuit breaker can be placed in 3 stable positions m service position circuit breaker racked i
41. A E E 630 A E E 1250 A E E 630 A E E 1250 A E E Rated values Voltage Ur kV rms 24 Insulation voltage power frequency withstand Ud kV rms 50 lightning impulse withstand 1 2 50 us Up kV peak 125 Frequency fr Hz 50 60 Short time withstand current Ik tk kA Isc 3 s Peak withstand current Ip kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Short circuit making capacity kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Other characteristics Operating sequence O 0 3 s CO 15 s CO O 0 3 s CO 3 min CO O 3 min CO 3 min CO Operating times Opening ms lt 50 Breaking ms lt 60 Closing ms lt 65 Mechanical endurance Class M2 Number of switching 10000 operations Electrical endurance Class E2 Number of switching operations 12 5 kA 100 at full Isc value 16 kA 100 20 kA 100 Capacitive current breaking capacity Class C1 C2 for certain applications Operating conditions 25 to 40 C Average relative humidity Over 24h lt 95 Over 1 month lt 90 Evolis and EVOset 24kV Description of functions fixed lateral version MV and LV connections MV connection The base circuit breaker is equipped with copper connection terminals with drilled holes The customer connection is carried out easily from outside the circuit breaker on these connection terminals ZN AKENT IEN N j Le N amp y Ve i mW Qe Ss a tO DE51979 Y Connection configuration
42. Vacuum circuit breakers Evolis from 7 2 to 24 kV Catalogue a brand of Schneider Electric The Guiding System the new way to create your electrical installations A comprehensive offer of products with consistent design The Guiding System is first and foremost a Merlin Gerin product offer covering all electrical distribution needs However what makes all the difference is that these products have been designed to operate togheter mechanical and electrical compatibility interoperability modularity communication Thus the electrical installation is both optimised and more efficient better continuity of supply enhanced safety for people and equipment guaranteed upgradeability effective monitoring and control Tools to simplify design and implementation With the Guiding System you have a comprehensive range of tools the Guiding Tools that will help you increase your product knowledge and product utilisation Of course this is in compliance with current standards and procedures These tools include technical booklets and guides design aid software training courses etc and are regularly updated The Guiding System combined with the know how and Creativity allows optimised reliable open ended and standard compliant installations For a genuine partnership with you Because each electrical installation is unique there is no standard solution With the Guiding System the variety of combinations allow
43. Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz 2nd opening release see possible choices in combination table below Shunt opening release YO2 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Undervoltage release YM 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Low energy release Mitop Remote control operation counter already included Electrical motor 24 32 Vdc 48 60 Vdc ac im LET 100 127 Vdc ac 220 250 Vdc ac Shunt closing release YF 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Operation counter already included if remote control supplied Open position CB locking device without lock Lock Ronis _____Profalux Push button disabling Pilot module with connecting kit without LV plug Diagnosis by Schneider Electric expert separated order DE56037 DE56041 DE56033 DE56042 DE56036 DE56039 DE56035 Fvolis 24 kV fixed lateral version The following components can be ordered separately and can be adapted or replaced by the customer Shunt opening release YO1 or YO2 Offer structure separated components 24 Vdc AAA10 115 48 Vdc AAA10 116 110 Vdc AAA10 117 125 127 Vdc AAA10 118 220 Vdc AAA10 119 110 Vac 50 Hz AAA10 120 220 230 Vac 50 Hz AAA10 121 120 Vac 60 Hz AAA10
44. absence of the auxiliary power supply An electrical motor MCH equipped with a spring armed CH limit switch This contact indicates the armed position of the mechanism springs armed Power supply See Order form page Threshold 0 85 to 1 1 Un Consumption VA or W 180 Motor overcurrent 2 to 3 In for 0 1 s Arming time 6 s maximum Operating rate 3 cycles maximum per minute CH contact 10 A 240 V Shunt releases XF and MX They can be permanently or briefly supplied power Shunt closing release XF This release allows remote closing of the circuit breaker when the control mechanism is armed Shunt opening release MX This release allows remote opening of the circuit breaker It locks it in the open position if the order is latched Power supply See Order form page Threshold XF 0 85 to 1 1 Un MX 0 7 to 1 1 Un Consumption VA or W Triggering 200 for 200 ms Latched 4 5 DE56885 DE56886 DE56887 Evolis 17 5 kV withdrawable frontal version Operation counter CDM Description of functions Indication Open closed auxiliary position contacts OC These auxiliary contacts indicate the open or closed position of the circuit breaker m Rotary type changeover contacts directly controlled by the circuit breaker mechanism m Indicator contacts are proposed O for standard relaying applications O for low level control applications with plc s
45. adle m on vertical copper terminals integrated in the bushing m by aconnector set also used on the base circuit breaker Note The dielectric strength values given in the performance table do not take these connectors into account The panel builder must check the whole cubicle connection configuration For circuit breakers with a rated voltage of Ur 17 5 kV with a phase to phase distance of 185 mm field deflectors are used to increase the dielectric strength by 75 kV to 95 kV DE51943 DE51944 Evolis 17 5 kV withdrawable frontal version 42 pin version LV plug Description of functions LV connection Main functions With the base circuit breaker the LV wiring uses a LV plug which comprises m the fixed part male mounted on the circuit breaker and fully connected to the control mechanism m the mobile part female compatible with the male part Two versions of the LV plug are available An 18 pin version enabling connection of m a shunt opening release MX1 m aremote control mechanism electrical motor shunt closing release XF m a ready to close contact PF m a maximum number of auxiliary contacts 1 NC 1 NO 2 changeover contacts see indication page Open closed position auxiliary contacts chapter An 42 pin version enabling connection of a shunt opening release MX1 a second opening release shunt type MX2 or undervoltage type MN a low energy release Mitop a fault t
46. age release MN m time delayed undervoltage release MNR MN time delay The time delay placed outside the circuit breaker can be disabled by an emergency stop button to give instant circuit breaker opening m low energy release Mitop Note see the table of the releases combinations Order form page Shunt opening release MX1 and MX2 Energizing this release causes instant opening of the circuit breaker Permanent power supply to the MX unit locks the circuit breaker in the open position Power supply See Order form page Threshold 0 7 to 1 1 Un Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Evolis 17 5 kV withdrawable frontal version t Undervoltage release MN DE56879 DE56881 DE56882 Low energy release Mitop Description of functions Opening circuit cont Undervoltage release MN This release unit causes the systematic opening of the circuit breaker when its supply voltage drops below a value less than 35 of the rated voltage even if this drop is slow and gradual It can open the circuit breaker between 35 and 70 of its rated voltage If the release unit is not supplied power manual or electrical closing of the circuit breaker is impossible Closing of the circuit breaker is possible when the supply voltage of the release unit reaches 85 of its rated voltage Power supply See Order form page Threshold Opening 0 35 to 0 7 Un C
47. ases combinations table Shunt opening YO1 1 1 111 Shunt opening YO2 1 Undervoltage YM 1 1 1 Mitop 1 1 Indication Operation counter already included if remote control supplied DE56040 Open position circuit breaker locking device without lock Ronis lock Profalux lock Push button disabling DE56039 Pilot module with connecting kit without LV plug Diagnosis by Schneider Electric expert DE56035 Evolis 24 kV fixed lateral version Only one of the boxes ticked or filled e by the needed value have to be considered between each horizontal line Orange box x corresponds to none priced functions Releases combinations table Shunt opening YO1 1 1 1 1 Shunt opening YO2 1 Undervoltage YM 1 1 1 Mitop 1 1 Order form Rated voltage Ur kV 24 Rated short circuit breaking current Isc kA Rated normal current Ir A MV connection On the left On the right Phase distance mm 250 300 Colour for push buttons and indicators IEC standard ANSI standard Push buttons open closed red black Indicator open closed black white green red Operating mechanism charged discharged white yellow charge discharge 1st opening release see possible choices in combination table below Shunt opening release YO1 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Undervoltage release YM 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127
48. between operations A circuit breaker expert can analyse the stored data in order to check the correct mechanical functioning of the circuit breaker 1000 events are stored in the module Servicing note pad The device incorporates this useful feature to record any information related to servicing the circuit breaker 250x250 character note pad PE60037 DE56051EN DE56030 Evolis Pilot monitoring device Description of functions cont Local or remote data collection Local use Alarms are displayed on the device itself A dry contact relay collates the faults and can be wired to the low voltage compartment A laptop user machine Interface can be used to set parameters and to display and upload data Remote use The monitoring device can be connected to a supervisor or concentrator for connection to the Web via a local RS485 Modbus network The supervisor can display process and acknowledge alarms Data is then either processed in the supervision system or in the remote web enabled system Easy to install module The module is mounted on all Evolis 24 kV circuit breakers apart from EVOset It is inserted in a special slot on the front face of the circuit breaker This module may be added at any time during the circuit breaker s service life The module may be factory mounted within the circuit breaker connection and parameter setting are done by Schneider Electric The module may be ad
49. ce busbar sections etc Evolis a fixed frontal or lateral version Here the circuit breaker is in its simplest version In this case it can be combined with additional accessories to meet various requirements For the fixed lateral version the MV connection can be on the right or on the left depending on the type of circuit breaker Ay e gt ab PE55692 PE55931 Evolis 24 kV fixed lateral version Evolis 24 kV fixed lateral version MV connection on the left hand side MV connection on the right hand side m Merlin Gerin Evolis Circuit breakers adapted to your needs cont Evolis a withdrawable frontal version In this version the circuit breaker is equipped with arms clusters and a rack and cradle The cradle and the circuit breaker can be ordered and delivered separately PE55101 PE55693 Evolis 17 5 kV withdrawable frontal version Evolis 24 kV withdrawable frontal version EVOset a fixed lateral version equipped with an integrated protection chain The EVOset is provided with a fully autonomous integrated protection chain with a VIP type control unit operating without an auxiliary power source The protection unit exists in 4 models VIP30 VIP35 VIPSOOP and VIPSOOLL VIP protection units are associated with functional current sensors The circuit breaker is delivered with its factory tested protection chain It therefore simplifies the panel builder s installation work PE55932
50. charges under no load without moving the main contacts The circuit breaker remains in the open position In the event of latched opening and closing orders the mechanism carries out anti pumping function as standard by blocking the circuit breaker in the open position Anti pumping function after opening on a fault or deliberate opening via the manual or electrical mechanism the closing order must be interrupted then reactivated to enable reclosing of the circuit breaker Composition The remote control comprises m an electrical motor MCH equipped with a spring armed limit switch m a shunt closing release XF m a shunt opening release MX m an operation counter It can be added with m a ready to close contact PF m a second block of 4 contacts OC for O C position indication for the circuit breaker m a third block of 4 contacts OC for O C position indication for the circuit breaker Electrical motor MCH The electrical motor carries out the automatic rearming of the storage energy springs as soon as the circuit breaker closes This allows instant reclosing of the device after opening The arming lever is only used as a backup control in the case of the absence of the auxiliary power supply An electrical motor MCH equipped with a spring armed limit switch This contact indicates the armed position of the mechanism springs armed Power supply See Order form page
51. cting kit and LV plug Diagnosis by Schneider Electric expert Separated order Rated current Up to 1250 A and 25 kA Above 1250 A or 25 kA Cradle accessories Rack in rack out position contact 4 AC LPCT TLP Up to 1250 A and 25 kA Above 1250 A or 25 kA Releases combinations table 6 field deflectors Shunt opening YO1 1 111 1 1 Shunt opening YO2 1 Undervoltage YM 1 1 1 Mitop 1 1 DE56037 DE56041 DE56033 DE56042 DE56036 DE56039 Evolis 24 kV withdrawable frontal version The following components can be ordered separately and can be adapted or replaced by the customer Shunt opening release YO1 or YO2 Offer structure Separated components 24 Vdc AAA10 115 48 Vdc AAA10 116 110 Vdc AAA10 117 125 127 Vdc AAA10 118 220 Vdc AAA10 119 110 Vac 50 Hz AAA10 120 220 230 Vac 50 Hz AAA10 121 120 Vac 60 Hz AAA10 122 24 Vdc AAA10 106 48 Vdc AAA10 107 110 Vdc AAA10 108 125 127 Vdc AAA10 109 220 Vdc AAA10 110 110 Vac 50 Hz AAA10 111 220 230 Vac 50 Hz AAA10 112 120 Vac 60 Hz AAA10 113 24 Vdc AAA10 124 48 Vdc AAA10 125 110 Vdc AAA10 126 125 127 Vdc AAA10 127 220 Vdc AAA10 128 110 Vac 50 Hz AAA10 129 220 230 Vac 50 Hz AAA10 130 120 Vac 60 Hz AAA10 131 24 32 Vdc AAA10 027 48 60 Vac dc AAA10 028 100 127 Vac de AAA10 029 220 250 Vac dc AAA10 030 Gear reducer AAA10 065 Open position CB locking device without lock AAA10 092 Ronis lock AAA10 058 Pr
52. d line feeders ww Fig 4 17 5 kV external coil type interrupter DE60162 Fig 5 24 kV internal coil type interrupter Evolis The very best of vacuum technology cont Systematic advanced control The main components of the circuit breaker such as vacuum interrupter and operating mechanism are produced by Schneider Electric The vacuum interrupters are manufactured in an ultra modern production unit in France During manufacture each circuit breaker is subjected to systematic advanced testing Vacuum interrupter testing The level of vacuum in each interrupter is tested using the magnetron discharge method Using this sophisticated procedure measurement is very precise and does not require access to the inside of the interrupter thus not affecting the airtight seal Circuit breaker testing Vacuum interrupter A rigorous set of tests and measurements is carried out on each circuit breaker The results are reported and signed off by the quality control department on each device s test certificate to ensure product traceability PE55694 PE55695 Compliance with standards m Evolis complies with IEC 62271 100 m Design and production are certified to ISO 9001 2000 m Production sites are certified to ISO 14001 environmental standard DE55745 DE55746 Q ISO 14001 VERSION 2000 Industrial process expertise Certification The certificate of conformity provides guarantees t
53. dc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Remote control operation counter already included Electrical motor 24 32 Vdc 100 127 Vdc ac 48 60 Vdc ac 220 250 Vdc ac Shunt closing release YF 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 125 127 Vdc 220 230 Vac 50 Hz 220 Vdc 120 Vac 60 Hz Operation counter already included if remote control supplied Open position CB locking device without lock Lock Ronis Push button disabling Releases combinations table Mitop Shunt opening YO1 Undervoltage YM DE56037 DE56041 DE56033 DE56042 DE56036 DE56039 DE56035 EVOset 24 kV fixed lateral version The following components can be ordered separately and can be adapted or replaced by the customer Shunt opening release YO1 or YO2 Electrical motor Offer structure separated components 24 Vdc AAA10 115 48 Vdc AAA10 116 110 Vdc AAA10 117 125 127 Vdc AAA10 118 220 Vdc AAA10 119 110 Vac 50 Hz AAA10 120 220 230 Vac 50 Hz AAA10 121 120 Vac 60 Hz AAA10 122 24 Vdc AAA10 106 48 Vdc AAA10 107 110 Vdc AAA10 108 125 127 Vdc AAA10 109 220 Vdc AAA10 110 110 Vac 50 Hz AAA10 111 220 230 Vac 50 Hz AAA10 112 120 Vac 60 Hz AAA10 113 24 Vdc AAA10 124 48 Vdc AAA10 125 110 Vdc AAA10 126 125 127 Vdc AAA10 127 220 Vdc AAA10 128 110 Vac 50 Hz AAA10 129 220 230 Vac 50 Hz AAA10 130 120 Vac 60 Hz AAA10 131 24 32 Vdc AAA10 027 48 60 Vac dc AAA10 028
54. ded after circuit breaker commissioning connection parameter setting and testing are done by a specialized service provider Schneider Electric or other The customer is provided with the product manual and the CD Rom containing the computerized manual and UMI PC software Connection to a withdrawable circuit breaker is carried out with a connection kit with a LV plug For a fixed circuit breaker two types of connection are possible according to whether or not the circuit breaker has a LV plug m a connection kit with LV plug m a connection kit without LV plug Operation and service The Pilot monitoring device can be used on two levels m information on operating conditions m diagnosis of mechanical circuit breaker conditions performed by a circuit breaker expert from Schneider Electric by analyzing the recorded data Notes Schneider Electric Industries SAS 89 boulevard Franklin Roosevelt F 92500 Rueil Malmaison France Tel 33 0 1 41 29 85 00 http www schneider electric com http www merlin gerin com AMTED305018EN As standards specifications and designs change from time to time please ask for confirmation of the information given in this publication ky This document has been amp printed on ecological paper Production Schneider Electric Graph me Photos Schneider Electric Printing Imprimerie du Pont de Claix JPF 06 2005 ART807087 2005 Schneider Electric All rights re
55. dicates that the C B is locked in place in the cradle DE56938 2 rails 59299 Drawings and casters DE56996 User manual 59069 DE56997 Evolis 17 5 kV Services withdrawable frontal version The following components can only be adapted or replaced on site by staff trained by Schneider Electric m remote control mechanism comprising electrical motor shunt closing release operation counter m operation counter m low energy release Mitop m interlocking between the open circuit breaker position and the LV plug m racking truck m circuit breaker front cover Evolis Evolis 24 kV fixed frontal version Panorama 11 Evolis 17 5 kV fixed frontal version 15 Evolis 17 5 kV withdrawable frontal version 33 Main characteristics 54 Description of functions 55 MV connection 55 LV connection 56 Opening circuit 57 Remote control 58 Indication and locking interlocking 59 Wiring diagram 60 Dimensions 61 Offer structure 62 Order form 63 Separated components 64 Services 66 Evolis 24 kV withdrawable frontal version 67 Evolis and EVOset 24 kV fixed lateral version 87 Evolis Pilot monitoring device 109 PE55692 Fvolis 24 kV fixed frontal version Main characteristics Ur 24 kV Isc Ir Phase to phase distance mm 230 250 Ud 50 kV 50 Hz 1 min 16 kA 630 A E Up 125 kV peak 1250 A E 2000 A 2500 A 25 kA 630 A E 1250 A a 2000 A 2500 A 31 5 kA 630 A 1250 A 2000 A 2500 A Rated
56. ease MX1 and MX2 Circuit breaker equipped with Energizing this release causes instant opening of the circuit breaker a shunt opening release MX Permanent power supply to the MX unit locks the circuit breaker in the open position Characteristics a Power supply See Order form page 3 Threshold 0 7 to 1 1 Un E Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Shunt opening release MX1 and MX2 Evolis 17 5 kV fixed frontal version t Undervoltage release MN DE56879 DE56881 DE56882 Low energy release Mitop Description of functions Opening circuit cont Undervoltage release MN This release unit causes the systematic opening of the circuit breaker when its supply voltage drops below a value less than 35 of the rated voltage even if this drop is slow and gradual It can open the circuit breaker between 35 and 70 of its rated voltage If the release unit is not supplied power manual or electrical closing of the circuit breaker is impossible Closing of the circuit breaker is possible when the supply voltage of the release unit reaches 85 of its rated voltage Power supply See Order form page Threshold Opening 0 35 to 0 7 Un Closing 0 85 Un Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Time delay for MN To eliminate spurious tripping of the circuit breaker when there are brief voltage drops the MN action is controlled with a time d
57. elay This function is achieved by adding a time delay unit outside of the undervoltage release MN circuit adjustable time delay This unit is placed outside the circuit breaker and can be inhibited by an emergency stop button to obtain instant circuit breaker opening Power supply See Order form page Threshold Opening 0 35 to 0 7 Un Closing 0 85 Un Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Time delay 0 5s 0 9s 1 5s 35 Low energy release Mitop This release includes a low consumption unit and is specifically used with the Sepam 100LA self powered unit REFLEX MODULE or the VIP relay Power supply Direct current Threshold 06A lt I lt 3A Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact This release also includes a coil reset enabling remote SDE contact reset Comment Use of the Mitop low energy release requires adjustment of the protection relay time delay in order to ensure that the circuit breaker trips between 45 50 ms DE56883 DE56884 DE56879 Evolis 17 5 kV fixed frontal version Electrical motor MCH t Shunt release XF MX Description of functions Remote control Function Remote control enables the remote opening and closing of the circuit breaker The opening order always takes priority over the closing order In the event of simultaneous opening and closing orders the mechanism dis
58. end of the cradle bushings They are necessary in the case of installation in a NEX 24 kV type cubicle For any other installation the dielectric strength is the responsibility of the installation designer DE51958 Evolis 24 kV withdrawable frontal version Description of functions LV connection Main functions With the base circuit breaker the LV wiring uses a LV plug unit which comprises m the fixed part male mounted on the circuit breaker and fully connected to the control mechanism m the mobile part female compatible with the male part Two versions of the LV plug are available An 21 pin version enabling connection of m a shunt opening release YO1 m an electrical remote control mechanism electrical motor shunt closing release YF anti pumping relay m the Pilot monitoring device m a maximum number of auxiliary contacts 3 NC 3 NO 1 changeover contact see indication and locking interlocking page Open closed position auxiliary contacts chapter Note see the table of the releases combinations Order form page An 42 pin version enabling connection of m an opening release shunt type YO1 or undervoltage type YM m a second opening release shunt type YO2 or undervoltage type YM or Mitop low energy release m an electrical remote control mechanism electrical motor shunt closing release YF anti pumping relay m the Pilot monitoring device m a maximu
59. ent Ik tk kA Isc 3 s Peak withstand current Ip kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Short circuit making capacity kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Other characteristics Operating sequence O 0 3 s CO 15 s CO O 0 3 s CO 3 min CO O 3 min CO 3 min CO Operating times Opening lt 50 ms Breaking lt 60 ms Closing lt 65ms Mechanical endurance Class M2 Number of switching 10000 operations Electrical endurance Class E2 Number of switching operations 25 kA 100 at full Isc value 31 5kA 50 40 kA 30 Capacitive current breaking capacity Class C1 Operating conditions 25 C to 40 C Average relative humidity Over 24 h lt 95 Over 1 month lt 90 Evolis 17 5 kV Description of functions withdrawable Racking in frontal version Composition The racking in function is carried out by m the racking truck supporting the circuit breaker mobile part m the cradle with bushings fixed part m LV plug DE51956 Operation The circuit breaker can be placed in 3 stable positions m service position circuit breaker racked in and locked in position LV plugs connected m test position circuit breaker racked out and locked in position LV plug connected m disconnected position the circuit breaker can be unlocked and extracted from the cubicle 3 stable states for operating DE56851 DE56856 DE56857 DE56858 Service position Test position Disconnected po
60. ersion Phase to phase distance 230 mm 230 4 230 Ur Isc Ir Weight g 4 N 24 kV 16 kA 630A 97kg ap 25 kA 630 A y ee y y 645 Phase to phase distance 250 mm 250 250 Isc Ir g N 16 kA 630 A af i i 25 KA 1250 A E E Fu Y 7 645 P 730 Ur Isc Ir Weight g 2 24 kV 16 kA 2000A 135kg 3 n O 25 kA 2000 A PA faw 315 A 1250 A 2000 A E 730 Important Detailed installation instructions are given in the Evolis Installation Guide Please consult us Evolis 24 kV Offer structure fixed frontal version The basic fixed frontal circuit breaker includes m a manual operating mechanism spring type m 1 shunt opening release YO1 m 1 block of auxiliary contacts The circuit breaker can receive options Phase distance mm 230 250 24 kV 125 kV peak 16 kA 630 A E 1250 A a 2000 A 2500 A 25 kA 630 A 1250A 2000 A 2500 A 31 5 kA 630 A 1250A 2000 A 2500 A DE56031 Remote control see possible choices in combination table below 1st opening release Possibility of replacing YO1 by undervoltage release YM fig 2 2nd opening releasee Shunt opening release YO2 fig 1 Undervoltage release YM fig 2 Low energy release Mitop fig 3 Remote control
61. es 2 meters long equipped with pins that can be adapted to the LV plug can be supplied for connected in to the cubicle s LV compartment Flexible ducting This 525 mm long duct with a hinged LV plug enables protection of the LV wiring that connects the circuit breaker to the cubicle s LV compartment Interlocking kit For circuit breakers intended for withdrawable applications an interlocking kit can be adapted The kit enables the mechanical position status to be given connected disconnected of the LV plug By adding a link between this mechanical data by the customer and the open closed position of the circuit breaker interlocking can be achieved between the LV plug and the open closed position of the circuit breaker required by IEC standard 62271 200 A detailed explanation of operation is given in the Installation Guide Evolis 17 5 kV Description of functions fixed frontal version Opening circuit Composition The opening circuit is produced using the following components m a shunt opening release MX1 m a second shunt opening release MX2 m an undervoltage release MN m time delayed undervoltage release MNR MN time delay The time delay placed outside the circuit breaker can be disabled by an emergency stop button to give instant circuit breaker opening m low energy release Mitop Note see the table of the releases combinations Order form page DE56877 Shunt opening rel
62. f a Profalux or Ronis captive key type keylock right turn type keylock The keylock is not part of the kit but can be supplied as an option Push button locking This transparent screen blocks access to the opening and closing push buttons on the circuit breaker The device enables the opening or closing push button to be locked independently It is often associated with an electrical motor Locking is achieved either m by 2 screws m by 3 padlocks not supplied m by a lead seal kit to lock the circuit breaker in the open position 8 DE56895 DE56896 O P 7 D z Padlocking Lead sealing DE56117EN Evolis and EVOset 24kV Description of functions fixed lateral version Wiring diagram Wiring diagram principle Close CBE E Open CB H 4 l YF Mitop Motor Shunt closing Control Shunt Under Low energy Changeover NO NC release mechanism opening voltage release contact contacts contacts anti pumping armed release release Mitop system indicator contact e Remote control EVOset 24 kV Protection monitoring and control fixed lateral version EVOset integrated protection chain by a VIP relay The EVOset circuit breaker has an independent protection chain The EVOset circuit breaker comprises an Evolis
63. gn of LV installations to give but a few examples Evolis a range of circuit breakers that takes account of your electrical installations requirements today and in the future Evolis is an integral part of the Merlin Gerin Guiding System PE40002 PE55930 Evolis Circuit breakers adapted to your needs Description Evolis a range of vacuum type circuit breakers from 7 2 kV to 24 kV combining easy selection and a comprehensive offer m a fixed frontal or lateral version m a withdrawable frontal version with a circuit breaker and cradle m a fixed lateral version equipped with an integrated protection chain m separately delivered accessories The Evolis circuit breaker is operated via a spring mechanism that gives an operating speed that is independent of the operator and that does not require an auxiliary power supply When the operating mechanism is motorized the circuit breaker can include telecontrol functions and carry out rapid reclosing cycles The various circuit breaker versions are easy to integrate in a cubicle environment An Installation Guide details the required procedure Applications Evolis is intended for use in medium voltage network applications in new installations or renovation for utilities companies infrastructures the process industry and the tertiary sector It provides protection for all types of applications cables overhead lines motors capacitors transformers sour
64. h gearing m a shunt closing release YF combined with an anti pumping device m an operation counter Electrical motor with gearing The electrical motor carries out the automatic rearming of the stored energy unit as soon as the circuit breaker is closed This allows the instant reclosing of the device after opening The arming lever is only used as a backup operating mechanism in the case of the absence of the auxiliary power supply The M3 contact indicates the end of arming operations Characteristics Power supply See Order form page Threshold V AC V DC 0 85 to 1 1 Un Consumption V AC 380 VA VDC 380 W Shunt closing release YF This release allows the remote closing of the circuit breaker when the operating mechanism is armed Characteristics Power supply See Order form page Threshold V AC 0 85 to 1 1 Un VDC 0 85 to 1 1 Un Consumption V AC 160 VA VDC 50 W The shunt closing release is combined with an anti pumping relay that enables priority to be given to opening in the case of a permanent closing order This thus avoids the device being caught in an uncontrolled opening closing cycle DE56116 DE60087 DE51953 DE60124 Evolis and EVOset 24kV Description of functions fixed lateral version Indication and locking interlocking Operation counter The operation counter is visible on the front panel It displays the number of switching cycles CO that the device has carried out
65. hat the circuit breaker m has been subject to type tests according to EN 45001 standards procedures in accredited laboratories by independent organizations m is in conformity with recognized international standards Evolis is currently being certified by external EN 45011 accredited organizations members of the STL Short circuit Testing Liaison m EN 45001 general requirements for the competence of testing and calibration laboratories m EN 45011 general requirements for bodies of operating product certification systems Environmental care Product design takes account of the environmental constraints described in a Product Environment Profile dossier PEP An end of service life manual details procedures for dismantling and processing components General contents Panorama 11 Evolis 17 5 RV fixed frontal version 15 Evolts 17 5 RV withdrawable frontal version 33 Evolis 24 RV fixed frontal version 53 Evolis 24 RV withdrawable frontal version 67 Evolis and EVOset 24 kV fixed lateral version 87 Evolis Pilot monitoring device 109 PE55691 Panorama Circuit breaker E pilot cradle Instrument transformer MV cubicle components capacitor insulator E earthing switch m heating resistor E voltage presence indicator E crank extraction table Extended products offer LV cubicle components m Mcb m protection relay E amp E push button terminal blocks
66. he two contacts fig 2 which allows a diffuse arc to be maintained fig 3 even at high current values The arc energy is spread over the whole contact surface area therefore causing very low levels of erosion m Merlin Gerin has chosen this last technique for the Evolis range Evolis The very best of vacuum technology cont Merlin Gerin s choices for Evolis combined AMF technology with its industrial expertise provides Evolis circuit breakers use AMF type vacuum interrupters customer with a highly reliable range Sa to e and economic optimization considerations the axial magnetic a ield is generated of circuit breakers These products are E oher by a coil outside of the interrupter fig 4 for rated voltages up to 17 5 kV suitable for the most demanding conditions m or by a coil integrated in the interrupter contact structure fig 5 for the 24 kV with the guarantee of full compliance with voltage level international standards In both cases the AMF vacuum interrupters feature low arc voltages Uarc of around 50 V and maximum usage of the contact surface for very low contact erosion 200110 The advantages provided The above choices provide customers with the following advantages in MV circuit breaker applications m simple and compact vacuum interrupters m high electrical endurance meaning that there is no need for contact wear inspection in normal network protection applications including highly disturbed overhea
67. his provides protection against phase to phase faults and against earthing faults m the phase protection is identical to the VIP30 m the earthing fault protection functions with the measurement of residual current calculated from the sum of the sensor secondary currents This measurement is made by a CSH30 core balance CT mounted at the back of the VIP casing Earthing protection is definite time its threshold and time delay can be adjusted Trip curves DE56139 to gt lo gt VIP30 VIP35 phase protection curve VIP35 earth protection curve EVOset 24 kV Protection monitoring and control fixed lateral version VIP30 and VIP35 protection units cont Phase protection trip curve VIP30 and VIP35 T s 100 10 1 W WA 0 1 NS NN N N ete OTe max Peere i typ IIs 0 01 min 0 5 10 15 20 25 30 35 EVOset 24 kV Protection monitoring and control fixed lateral version VIPSOOP protection relay and VIPSOOLL Use Independent protection units VIP300P and 300LL are intended for use on distribution networks They can be used to protect MV LV transformers to protect the head of the industrial installation but also to protect branches These are independent relays that d
68. hts phase and earth show that the lower threshold has been exceeded and that the time delay has been started EVOset 24 kV Protection monitoring and control fixed lateral version VIP300P protection relay and VIPSOOLL cont Trip curves DE55727 t gt t gt gt Is 1 2 Is 10 Is gt gt Is Is gt gt With a definite time lower threshold With an inverse definite time lower threshold Definite time trip curves t s t s S 100 10 6 4 3 2 1 5 1 1 0 6 oe 3 2 0 15 0 1 0 1 0 07 0 05 I Is 0 01 1 10 100 1 1 2 Is 10 100 RI curve SIl curve t S t s 1000 l oO O O DE55729 0 1 0 1 0 01 0 01 1 1 21s 10 100 1 1 2ls 10 100 VI
69. including Electrical motor gear reducer shunt closing release anti pumping relay operation counter DE56037 DE56033 DE56038 Releases combinations table No LV plug or 21 pin 42 pin LV plug LV plug Shunt opening YO1 Shunt opening YO2 1 Undervoltage release YM 1 1 1 Mitop 1 1 Indication Operation counter already included if remote control supplied DE56040 21 pin LV plug 42 pin LV plug DE51954 Open position circuit breaker locking without lock Ronis lock Profalux lock DE56039 Pilot module with connecting kit Diagnosis by Schneider Electric expert DE56035 Evolis 24 kV fixed frontal version Only one of the boxes ticked or filled Order form J Basic fixed frontal circuit breaker Ovary the needed value have to be considered between each horizontal line Orange box x corresponds to none priced functions Releases combinations table Rated voltage Ur kV 24 Rated short circuit breaking current Isc kA Rated normal current Ir A Phase distance mm 230 250 Colour for push buttons and indicators IEC standard ANSI standard Push buttons open closed red black Indicator open closed black white green red Operating mechanism charged discharged 1st opening release see possible choices in combination table below Shunt opening release YO1 white yellow charge discharge 24 Vdc 110 Vdc 110 Vac 50 Hz 48 Vdc 12
70. ing release Y01 m second shunt opening release YO2 m undervoltage release YM m low energy release Mitop Note see the table of the releases combinations Order form page Shunt opening release YO1 and YO2 Energizing this release causes instant opening of the circuit breaker Characteristics Power supply See Order form page Threshold V AC 0 85 to 1 1 Un VDC 0 7 to 1 1 Un Consumption V AC 160 VA VDC 50 W Undervoltage release YM This release unit causes the systematic opening of the circuit breaker when its supply voltage drops below a value less than 35 of the rated voltage even if this drop is slow and gradual It can open the circuit breaker between 35 and 70 of its rated voltage If the release unit is not supplied power manual or electrical closing of the circuit breaker is impossible Closing of the circuit breaker is possible when the supply voltage of the release unit reaches 85 of its rated voltage Characteristics Power supply See Order form page Threshold Opening 0 35 to 0 7 Un Closing 0 85 Un Consumption Triggering V AC 400 VA VDC 100 W Latched V AC 100 VA V DC 10 W Low energy release Mitop This release includes a low consumption unit and is specifically used with the Sepam 100LA self powered relay REFLEX MODULE or the VIP relay Characteristics Power supply Direct current Threshold 0O 6A lt I1 lt 3A Any tripping due to the Mitop relea
71. istance V fig 2 630 1250 A 59402 Upstream fixed connections Ir to be mounted on basic circuit breaker or bushings or downstream fixed connections Ir to be mounted on bushings only z E y Ma 3 fixed distance H or V fig 1 630 2500 A 59403 eL i qi ac ae iB P A of lee o ea 3 variable distance H fig 3 630 2500 A 59404 op E i ae Fig 1 a Fig 2 Fig 3 3 variable distance V fig 2 630 2500 A 59405 Downstream fixed connections Ir to be mounted on basic circuit breaker only a o M Aa 3 fixed distance H or V fig 1 630 2500 A 59409 a p 9 fl l aa d dsta iB E gt S gt i 10 iB 3 variable distance H fig 3 630 2500 A 59410 Fig 1 X Fig 2 Fig 3 3 variable distance V fig 2 630 2500 A 59411 Evolis 17 5 kV Offer structure withdrawable Separated components cont frontal version Earthing sliding contact on C B 59456 DE56855 Circuit breaker specific labels green red etc DE56898 Adaptation kit needed for circuit breaker opening for retrofit 59093 DE56897 Phase distance 145 mm 59316 Phase distance 185 mm 59317 Phase distance 240 mm DE56994 1 full bushing 630 1250 A 1 full bushing 630 2500 A you need at least 6 bushings per cradle DE56995 6 deflectors used to increase dielectric withstand from 75 to 95 kV 59283 DE56939 4 AC 59173 DE51950 C B ready to be operated PAF 1 AC in
72. kit 24 wires 59117 gt LV connecting kit 42 wires AAA10 087 Pilot module consult us DE56035 Evolis 24 kV Services fixed frontal version The following components can only be adapted or replaced on site by staff trained by Schneider Electric m the Pilot monitoring device m remote control mechanism comprising electrical motor gearing shunt closing release anti pumping relay operation counter m operation counter m low energy release Mitop m circuit breaker front cover Evolis Evolis 24 kV withdrawable frontal version Panorama Evolis 17 5 kV fixed frontal version Evolis 17 5 kV withdrawable frontal version Evolis 24 kV fixed frontal version Main characteristics Description of functions Racking in LPCT sensors MV connection LV connection Opening circuit Remote control Indication and locking interlocking Wiring diagram Safety functions Dimensions Offer structure Order form Separated components Services Evolis and EVOset 24 kV fixed lateral version Evolis Pilot monitoring device 11 15 33 68 69 69 71 72 73 74 19 76 T 78 79 80 82 83 85 87 109 PE55693 Evolis 24 kV withdrawable frontal version Main characteristics Ur 24 kV Isc Phase to phase distance mm Ud 50 kV 50 Hz 1 min 16 kA Up 125 kV peak Ir 630 A 230 250 a 1250 A 2000 A 2500 A 25 kA 630 A 1250 A 2000 A 2500 A 31 5 k
73. lectrical installations For example the LV protection co ordination guide discrimination and cascading optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations MV LV dry cast resin transformer from 160 to 5000 kVA Evolis MV vacuum switchgear and components from 1 to 24 KV CAD software and tools The CAD software and tools enhance productivity and safety They help you create your installations by simplifying product choice through easy browsing in the Guiding System offers Last but not least they optimise use of our products while also complying with standards and proper procedures Compact Multi 9 Prisma Plus Protection switchgear system Modular protection switchgear Functional system for electrical from 100 to 630 A system up to 125A distribution switchboards up to 3200 A Pragma Canalis Enclosures for Prefabricated Busbar distribution Trunking switchboards from 25 to 4000 A up to 160 A PowerLogic Power management Training Training allows you to acquire the Merlin Gerin expertise installation design work with power on etc for increased efficiency and a guarantee of improved customer service The training catalogue includes beginner s courses in electrical distribution knowledge of MV and LV switchgear operation and maintenance of installations desi
74. losing 0 85 Un Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Time delay for MN To eliminate spurious tripping of the circuit breaker when there are brief voltage drops the MN action is controlled with a time delay This function is achieved by adding a time delay unit outside of the undervoltage release MN circuit adjustable time delay This unit is placed outside the circuit breaker and can be inhibited by an emergency stop button to obtain instant circuit breaker opening Power supply See Order form page Threshold Opening 0 35 to 0 7 Un Closing 0 85 Un Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Time delay 0 5s 0 9s 1 5s 35 Low energy release Mitop This release includes a low consumption unit and is specifically used with the Sepam 100LA self powered unit REFLEX MODULE or the VIP relay Power supply Direct current Threshold 06A lt I lt 3A Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact This release also includes a coil reset enabling remote SDE contact reset Comment Use of the Mitop low energy release requires adjustment of the protection relay time delay in order to ensure that the circuit breaker trips between 45 50 ms DE56883 DE56884 DE56879 Evolis 17 5 kV withdrawable frontal version Electrical motor MCH t Shunt release XF MX Description of functions Remote
75. m H E Rated values Evolis 24 kV fixed lateral version Voltage Ur kV rms 24 MV connection on the right hand side PE55930 Evolis 24 kV fixed lateral version MV connection on the left hand side Insulation voltage power frequency withstand Ud kV rms 50 lightning impulse withstand 1 2 50 us Up kV peak 125 Frequency fr Hz 50 60 Short time withstand current Ik tk kA Isc 3 s Peak withstand current Ip kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Short circuit making capacity kA peak 2 5 Isc 50 Hz 2 6 Isc 60 Hz Other characteristics Operating sequence O 0 3 s CO 15 s CO O 0 3 s CO 3 min CO O 3 min CO 3 min CO Operating times Opening ms lt 50 Breaking ms lt 60 Closing ms lt 65 Mechanical endurance Class M2 Number of switching 10000 operations Electrical endurance Class E2 Number of switching operations 12 5 kA 100 at full Isc value 16kA 100 20 kA 100 25 kA 100 Capacitive current breaking capacity Class C1 C2 for certain applications Operating conditions 25 C to 40 C Average relative humidity Over 24 h lt 95 Over 1 month lt 90 m Merlin Gerin PE55932 EVOset 24 kV fixed lateral version EVOset 24 kV fixed lateral version MV connection on the right hand side Main characteristics Ur 24 kV Isc Phase to phase distance mm MV connection on the Ud 50 kV 50 Hz 1 min 12 5 kA Up 125 kV peak 16 kA 20 kA Ir 250 300 right left right left 630 A a E 1250
76. m number of auxiliary contacts 5 NC 6 NO 1 changeover contact see indication and locking interlocking page Open closed position auxiliary contacts chapter Note see the table of the releases combinations Order form page Interlocking function In conformity with IEC standard 62271 200 an interlocking function prohibits m racking in when the LV plug is not connected m disconnection of the LV plug if the circuit breaker is in the racked in position LV wiring kit A wiring kit with 21 or 42 wires 2 meters long equipped with pins that can be adapted to the LV plug can be supplied for connected in to the cubicle s LV compartment Flexible ducting This 525 mm long duct with a hinged LV plug enables protection of the LV wiring that connects the circuit breaker to the cubicle s LV compartment DE56114EN DE60094 DE60089 DE60091 Evolis 24 kV withdrawable frontal version Low energy release 3 Description of functions Opening circuit Composition In its basic version the circuit breaker includes a shunt opening release YO1 The opening circuit can be produced using the following components m second shunt opening release on energizing YO2 m undervoltage release YM m low energy release Mitop Note see the table of the releases combinations Order form page Shunt opening release YO1 and YO2
77. n No closing Open position circuit breaker locking available 4 Switchboard door Open No racking in a eed No door opening P BAANG SWIGN SpPEN No earthing switch closing Closed No racking in 1 This protection mechanism ensures that the performance levels of the circuit breaker correspond with those of the cradle 2 Device that prevents the circuit breaker from dropping when extracted from the cradle The device can be either unlocked manually or when the extraction rig is put in position 3 Interlocking device to be fitted to the cubicle door If there is no interlocking the circuit breaker device should be inhibited Evolis 17 5 kV Dimensions withdrawable frontal version Phase to phase distance 145 mm gt 145 145 4 Ur Isc Ir Weight 3 tt 7 2 kV 25 kA 630 A 165 kg i 1250 A 12 kV 25 kA 630 A 1250 A Phase to phase distance 185 mm Ur 7 2 kV Weight 174 kg DE56122 DE56121 1250 A 630 A 630 A 1250 A 630 A 630 A 17 5 kV Phase to phase distance 240 mm Weight 272 kg DE56123 DE56124 Important Detailed installation instructions are given in the Evolis Installation Guide Please consult us DE56931 Evolis 17 5 kV Offer structure withdrawable frontal version The basic withdrawable frontal circuit breaker includes m 6 arms
78. n Two connection solutions Directly on the LV terminal block The circuit breaker s LV wiring can be directly connected to the LV terminal block of the operating mechanism through a cable protection duct With LV plug m The fixed part male mounted on the circuit breaker and fully connected to the operating mechanism m The mobile part female compatible with the male part Two versions of the LV plug are available An 18 pin version enabling connection of m a shunt opening release MX1 m aremote control mechanism electrical motor shunt closing release XF anti pumping relay m a ready to close contact PF m a maximum number of auxiliary contacts 1 NC 1 NO 2 changeover contacts see indication page Open closed position auxiliary contacts chapter A 42 pin version enabling connection of m an opening release shunt type MX1 or undervoltage type MN a second opening release shunt type MX2 or undervoltage type MN a low energy release Mitop a fault trip indicator contact SDE a remote contact reset system SDE a remote control mechanism electrical motor shunt closing release XF a ready to close contact PF a maximum number of auxiliary contacts 4 NC 5 NO 2 changeover contacts see indication page Open closed position auxiliary contacts chapter Note see the table of the releases combinations Order form page LV wiring kit A wiring kit with 21 or 42 wir
79. n and locked in position i LV plug connected pS m test position circuit breaker racked out and locked in position LV plug connected m disconnected position the circuit breaker can be unlocked and extracted from the cubicle without interlocking DE51977 DE51978 Safety functions A drive system using a threaded shaft gives easier racking and unracking Interlocking mechanisms In conformity with IEC standards 62271 100 and 62271 200 the following interlocks are available m impossibility of racking in or out is the circuit breaker is not in the open position m impossible to rack in the circuit breaker when the LV plug is not connected m impossible to disconnect the LV plug if the circuit breaker is not racked out Cubicle door interlocking mechanism The carriage is equipped with a device that enables interlocking between the racking out of the circuit breaker and the cubicle door the door must be specifically designed m possible to rack in the circuit breaker only if the door is closed m possible to open the door only if the circuit breaker is racked out This device must be disabled if the interlocking function is not present Earthing is achieved throughout the operation via the racking carriage casters An addition earthing system can be supplied as an option Protective shutters placed on the cradle stops access to the racking fingers when the device is e
80. nter CDM fig 1 Additional auxiliary contacts OF 4 AC fig 2 Ready to close contact PF 1 AC fig 3 DE56887 DE56885 DE56886 Fig 1 LV wiring connection 42 pin LV plug instead of 18 pins DE51944 Rack in rack out operation Operating crank DE56915 Locking interlocking Locking of the circuit breaker in the open position by padlock padlock supplied by customer fig 1 Locking of the circuit breaker in the 1 lock open position by key locks fig 2 2 locks DE56936 DE56891 Disabling of O C circuit breaker buttons padlock supplied by customer fig 3 Cradle with 145 mm phase distance Cradle with 185 mm phase distance Cradle with 240 mm phase distance DE56937 Racked in out position contacts 4 AC fig 1 C B ready to be operated PAF 1 AC fig 2 indicates that the C B is locked in place in the cradle 6 field deflectors for bushings mandatory if Ur 17 5 kV 95 kVpeak with phase distance 185 mm Evolis 17 5 kV Order form withdrawable frontal version the needed value have to be considered between each horizontal line Rated voltage Ur kV Orange box x corresponds to none priced functions Rated short circuit breaking current Isc kA Rated normal current Ir A Phase distance mm 145 185 240 Colour for push buttons and indicators IEC standard ANSI standard 1st opening release see possible choices in combination table belo
81. o not require any auxiliary power supply they are powered by the current sensors The relays directly actuate the Mitop release DE55725 DE55726 VIP300 One ee t gt t gt gt 1 2ls 10ls I gt gt Simplified connection arrangement Phase and earthing protection curve The associated current sensors of type CEa and CEb give a setting range for the service current Is of 10 A to 1250 A VIP300P relay This provides protection against phase to phase faults Phase protection has two independently adjustable thresholds m the lower threshold can be chosen to be either definite time or inverse definite time It can be executed according to the RI curve m the upper threshold is inverse definite time The definite time curves are in conformity with standard IEC 60255 3 They are either of type inverse SI very inverse VI and extremely inverse El VIPSOOLL relay This provides protection against phase to phase faults and against earthing faults m the phase protection is identical to the VIP300P m earthing fault protection functions with the measurement of residual current this is carried out based on the sum of secondary currents in the sensors As for phase protection earthing protection has two independently adjustable thresholds Indication Two indicators show the origin of tripping phase or earth They stay in position after breaking the relay power supply Two LED indicator lig
82. ofalux lock AAA10 059 DE51941 DE51954 PE55698 DE56855 DE56035 DE56048 DE56995 DE56045 Evolis 24 kV Offer structure withdrawable separated components cont frontal version MV connection accessories g Clusters set including fingers 630 1250 A AAA10 025 8 gt 2500 A AAA10 026 7 Arms set 630 1250 A AAA10 022 Finger 21 pin LV plug LV plug support AAA10 035 21 pin plug AAA10 031 42 pin LV plug LV plug support AAA10 035 42 pin plug AAA10 032 2 references are necessary Flexible conduct for LV wiring 59099 LV connecting kit 21 wires 59117 LV connecting kit 42 wires AAA10 087 Pilot module consult us Cradle with 230 mm phase distance AAA10 015 Cradle with 250 mm phase distance AAA10 017 N 7 Bushing kit for cradle fig 1 630 1250 A AAA10 016 a 2500 A AAA10 018 6 A 6 field deflectors 630 1250 A AAA10 020 for cradle bushings fig 2 2500 A AAA10 021 4 racked in out position contacts fig 3 59173 to be installed in the cradle o LPCT toroidal sensor TLP 160 up to 1250 A AAA10 094 z TLP 190 above AAA10 095 TPL 160 TPL 190 m Merlin Gerin Evolis 24 kV Services withdrawable frontal version The following components can only be adapted or replaced on site by staff trained by Schneider Electric m the Pilot monitoring device m remote control mechanism comprising electrical motor gearing shunt closing
83. onditions The device monitors external conditions and provides alarms if they are out of the specified range Recording circuit breaker operating data Similarly to an aircraft black box the monitor device logs the circuit breaker s key data over time allowing a diagnosis on its mechanical conditions Pilot main characteristics Characteristics Power supply V AC 50 60 Hz 100 250 15 to 10 VDC 24 250 30 to 10 Service temperature C 25 to 70 C Consumption VA or W lt 3 Measurement inputs V AC 50 60 Hz 100 250 15 to 10 VDC 24 250 30 to 10 Events recording capacity 1000 Conditions record capability 1000 Maintenance notes record capacity 256 x 256 characters Detailed features Monitoring operating conditions m the module continuously monitors O opening auxiliary voltage O circuit breaker ambient temperature O number of operations O time between operations and sends alarms if the set points are exceeded m alarms are visible on the front of the device and can also be transferred to the LV compartment or supervision system m Operating conditions are recorded minimum and maximum values of auxiliary voltage and ambient temperature are time tagged and stored every 24 h Recording circuit breaker data All circuit breaker events are time tagged and stored opening closing motor charging energizing voltage set point temperature set point number of operations time
84. opening of the circuit breaker when its supply voltage drops below a value less than 35 of the rated voltage even if this drop is slow and gradual It can open the circuit breaker between 35 and 70 of its rated voltage If the release unit is not supplied power manual or electrical closing of the circuit breaker is impossible Closing of the circuit breaker is possible when the supply voltage of the release unit reaches 85 of its rated voltage DE60089 Characteristics Power supply See Order form page Threshold Opening 0 35 to 0 7 Un z Closing 0 85 Un A Consumption Triggering V AC 400 VA V DC 100 W Latched V AC 100 VA VDC 10 W Low energy release 3 Low energy release Mitop This release includes a low consumption unit and is specifically used with the Sepam 100LA self powered relay REFLEX MODULE or the VIP relay Characteristics Power supply Direct current Threshold 0 6A lt I lt 3A Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact option DE56115 DE60093 DE60151 Evolis and EVOset 24 kV fixed lateral version Shunt closing release 5 Description of functions Remote control Function Remote control enables the remote opening and closing of the circuit breaker Composition The remote control mechanism comprises m an electrical motor wit
85. ould have the following available contacts 4 NC 5 NO 1 CHG m Using a 21 pin LV plug for withdrawable applications the maximum number of available contacts is o 3 NC o 3 NO O 1 changeover Instead of 5 NC 6 NO 1 CHG with a 42 pin socket Contact characteristics Rated current 10A Breaking capacity AC 220 V cos 0 3 1A DC 110 220 V L R lt 0 02 s 0 3 A Locking of the circuit breaker in the open position This locking system enables the fitting of a Profalux or Ronis captive key type keylock right turn type keylock The keylock is not part of the kit but can be supplied as an option DE56117EN Evolis 24 kV withdrawable frontal version Motor Glose CBE l Open CB F aoe l Description of functions Wiring diagram Wiring diagram principle YF Mitop i m r CAD Shunt closing Control Shunt Under Low energy Changeover NO NC release mechanism opening voltage release contact contacts contacts anti pumping armed release release Mitop system indicator contact Remote control Evolis 24 kV withdrawable frontal version Description of functions Safety functions This table describes the safety functions available on the withdrawable version of the Evolis 24 How to use the kV circuit breaker table Each of the boxes describes the functional status of each circuit breaker position and the associated parts Insertion
86. ous components have to be fully degased This is achieved by m choosing materials that are specifically selected for this application metals and ceramics m choosing an appropriate assembly process vacuum high temperature brazing m the use of a getter material to absorb the residual gas Current breaking in a vacuum interrupter In vacuum breaking the electrical arc generated on separation of the contacts is made up of a plasma of metal vapors produced by the vaporization of the contact material At low values of current these vapors very quickly condense on the shield and contacts when the arc disappears thus allowing m the vacuum to be re established m acontact to contact dielectric strength to be restored that is greater than the recovery voltage breaking is then complete At high currents the electrical arc in the vacuum switches to a concentrated mode which causes high localized temperature rises on the contacts The existence of these hot spots is detrimental to the quick restoring of the dielectric strength Two techniques can be used in order to avoid this stagnation of the static concentrated arc m the so called RMF Radial Magnetic Field technique involves rotating the arc thanks to an electromagnetic effect generated by a radial magnetic field this therefore limits contact erosion m amore recent technique called AMF Axial Magnetic Field involves applying an axial magnetic field parallel to the axis of t
87. ow voltage terminal blocks fig 3 42 pins or terminal blocks are mandatory if more than one opening coil is needed Fig 1 Fig 2 Locking of the circuit breaker in the open position by padlock padlock supplied by customer fig 1 DE56891 Locking of the circuit breaker in the 1 lock open position by key locks fig 2 2 locks Disabling of O C circuit breaker buttons padlock supplied by customer fig 3 Evolis 17 5 kV fixed frontal version Only one of the boxes ticked or filled e by the needed value have to be considered between each horizontal line Orange box X corresponds to none priced functions Releases combinations table Shunt opening MX Undervoltage MN Mitop Order form Rated voltage Ur kV Rated short circuit breaking current Isc kA Rated normal current Ir A Phase distance mm 145 185 240 Colour for push buttons and indicators IEC standard ANSI standard 1st opening release see possible choices in combination table below Shunt opening release MX 24 Vac 24 30 Vdc 100 130 Vdc ac 48 Vac 48 60 Vdc 200 250 Vdc ac Undervoltage release MN 24 Vac 24 30 Vdc 100 130 Vdc ac 48 Vac 48 60 Vdc 200 250 Vdc ac Time delay unit for MN 48 60 Vdc ac 100 130 Vdc ac 200 250 Vdc ca Low energy release Mitop 1 AC fault signalling SDE and reset 200 250 Vac are included 2nd opening release a low voltage plug and socket 42 pins is mandatory
88. plications Sepam series 40 for demanding applications Sepam series 80 for full applications Separate catalogue PM500 PM700 for basic metering PM800 for advanced metering CM3000 CM4000 for full metering and power quality Evolis Evolis 17 5 kV fixed frontal version Panorama Main characteristics Description of functions MV connection LV connection Opening circuit Remote control Indication Locking interlocking Wiring diagram Dimensions Offer structure Order form Separated components Services Evolis 17 5 kV withdrawable frontal version Evolis 24 kV fixed frontal version Evolis 24 kV withdrawable frontal version Evolis and EVOset 24 kV fixed lateral version Evolis Pilot monitoring device 11 16 17 17 19 20 22 23 24 25 26 27 29 30 32 33 53 67 109 PE40002 Evolis 17 5 kV fixed frontal version Main characteristics Ur 7 2 kV Isc Ir Phase to phase distance mm 145 185 240 Ud 20 kV 50 Hz 1 min 25 kA 630 A a a Up 60 kV peak 1250 A m m 2500 A m 31 5 kA 630 A m 1250 A m 2500 A E 40 kA 630 A E 1250 A E 2500 A m Ur 12 kV Isc Ir Phase to phase distance mm 145 185 240 Ud 28 kV 50 Hz 1 min 25 kA 630 A E E Up 75 kV peak 1250 A E m 2500 A E 31 5 kA 630 A E 1250 A E 2500 A E 40 kA 630 A E 1250 A Ej 2500 A E Ur 17 5 kV Isc Ir Phase to phase distance mm 145 185 240 Ud 38 kV 50 Hz 1 min 25 kA 630 A a Up 95 kV peak
89. reaker is extracted from the cubicle This function avoids all risks of spurious closing of the circuit breaker m Test position contact This contact is activated when the circuit breaker is in the test or service position m Access ramp for the circuit breaker in the cradle DE51950 DE56855 DE56025 Auto discharge function DE60099 DE60097 Evolis 24 kV Description of functions withdrawable LPCT sensors frontal version LPCT sensors are the best way to increase Function the effectiveness of the protection chain LPCT type sensors Low Power Current Transducers provide accurate and simplify the selection measurement for protection functions when an Evolis circuit breaker is combined f with a Sepam range relay They comply with IEC 60044 8 standard Composition Two types of LPCT are available m LPCT s for bushings with LV insulation for cradle installation TLP type m LPCT with MV insulation for cubicle installation CLP type The sensor is supplied with 5 m of cable and connectors that allows direct connection to the Sepam unit Mechanical characteristics LPCT for bushings TLP type Mounted directly on the Evolis withdrawable circuit breaker cradle The sensors are simply located on the bushings and fixed using three screws Each sensor covers the full operating range of the corresponding circuit breaker Connection to the Sepam is achieved using a shielded cable which is attached
90. release anti pumping relay operation counter operation counter low energy release Mitop interlocking between the open circuit breaker position and the LV plug racking truck auto discharge device circuit breaker front cover Evolis Evolis and EVOset 24 kV fixed lateral version Panorama 11 Evolis 17 5 kV fixed frontal version 15 Evolis 17 5 kV withdrawable frontal version 33 Evolis 24 kV fixed frontal version 53 Evolis 24 kV withdrawable frontal version 67 Main characteristics 88 Evolis 24 kV 88 EVOset 24 kV 89 Description of functions 90 MV and LV connections 90 Opening circuit 91 Remote control 92 Indication and locking interlocking 93 Wiring diagram 94 Protection monitoring and control 95 EVOset integrated protection chain 95 VIP30 et VIP35 protection units 96 VIP300P et VIP300LL protection units 98 Current sensors and test unit for VIP relays 100 Dimensions 101 Offer structure Evolis 24 kV 102 EVOset 24 kV 105 Order form Evolis 24 kV 103 EVOset 24 kV 106 Separated components Evolis 24 kV 104 EVOset 24 kV 107 Services 108 Evolis Pilot monitoring device 109 PE55931 Fvolis 24 kV fixed lateral version Main characteristics Ur 24 kV Isc Ir Phase to phase distance mm 250 300 MV connection on the right left right left Ud 50 kV 50 Hz 1 min 12 5 kA 630 A E E E Up 125 kV peak 1250 A E m 16 kA 630 A E E E E 1250 A E E E 20 kA 630 A E E E 1250 A E m 25 kA 630 A a E E 1250 A
91. rip indicator contact SDE a remote contact reset system SDE a remote control mechanism electrical motor shunt closing release XF a ready to close contact PF a maximum number of auxiliary contacts 4 NC 5 NO 2 changeover contacts see indication page Open closed position auxiliary contacts chapter Note see the table of the releases combinations Order form page Interlocking function In conformity with IEC standard 62271 200 an interlocking function prohibits m racking in when the LV plug is not connected m disconnection of the LV plug if the circuit breaker is in the racked in position LV wiring kit A wiring kit with 21 or 42 wires 2 meters long equipped with pins that can be adapted to the LV plug can be supplied for connected in to the cubicle s LV compartment Flexible ducting This 525 mm long duct with a hinged LV plug enables protection of the LV wiring that connects the circuit breaker to the cubicle s LV compartment Evolis 17 5 kV withdrawable frontal version DE56877 Circuit breaker equipped with a shunt opening release MX i e2 N oe oO 1O W Q Shunt opening release MX1 and MX2 Description of functions Opening circuit Composition In its basic version the circuit breaker includes a shunt opening release MX1 The opening circuit can also be produced using the following components m a second shunt opening release MX2 m undervolt
92. s for genuine customisation solutions You can create and implement electrical installations to meet your creative requirements and design knowledge You and Merlin Gerin s Guiding System form a genuine partnership For more details on the Guiding System consult www merlin gerin com A consistent design of offers from Medium Voltage to Ultra terminal Discrimination guarantees co ordination between the operating characteristics of serial connected circuit breakers Should a fault occurs downstream only the circuit breaker placed immediately upstream from the fault will trip Prefabricated and tested solutions upstream and downstream from the device complying with the IEC 60439 1 switchboard standard Thanks to the use of standard Web technologies you can offer your customers intelligent Merlin Gerin switchboards allowing easy access to information follow up of currents voltages powers consumption history etc Guiding Tools for more efficient design and implementation of your installations All Merlin Gerin offers are designed according to electrical mechanical and communication consistency rules The products express this consistency by their overall design and shared ergonomics Electrical consistency Each product complies with or enhances system performance at co ordination level breaking capacity Isc temperature rise etc for more safety continuity of supply discrimination or economic optimisa
93. s that have undergone type testing are shown in the Installation Guide LV connection The circuit breaker s LV wiring must be directly connected to the terminal on the control mechanism via a protection sheath DE51980 Evolis and EVOset 24kV Description of functions fixed lateral version Opening circuit Composition Evolis circuit breaker In its basic version the circuit breaker includes a shunt opening release YO1 The opening circuit can be produced using the following components m second shunt opening release on energizing YO2 m undervoltage release YM m low energy release Mitop EVOset circuit breaker In its basic version the circuit breaker includes a low energy release Mitop DE56114EN In addition the opening circuit can be produced using the following components m shunt opening release YO1 m undervoltage release YM An external power supply is necessary in this case Note see the table of the releases combinations Order form page Shunt opening release YO1 and YO2 Energizing this release causes instant opening of the circuit breaker Characteristics Power supply See Order form page W Threshold VAC 0 85 to 1 1 Un A oe VDC 0 7 to 1 1 Un al Consumption VAC 160 VA VDC 50 W Undervoltage release YM This release unit causes the systematic
94. se unit is momentarily indicated by an SDE type changeover contact option DE56115 DE60093 DE60151 Fvolis 24 kV fixed frontal version Shunt closing release 5 Description of functions Remote control Function Remote control enables the remote opening and closing of the circuit breaker Composition The remote control mechanism comprises m an electrical motor with gearing m a shunt closing release YF combined with an anti pumping device m an operation counter Electrical motor with gearing The electrical motor carries out the automatic rearming of the stored energy unit as soon as the circuit breaker is closed This allows the instant reclosing of the device after opening The arming lever is only used as a backup operating mechanism in the case of the absence of the auxiliary power supply The M3 contact indicates the end of arming operations Characteristics Power supply See Order form page Threshold V AC V DC 0 85 to 1 1 Un Consumption V AC 380 VA VDC 380 W Shunt closing release YF This release allows the remote closing of the circuit breaker when the operating mechanism is armed Characteristics Power supply See Order form page Threshold V AC 0 85 to 1 1 Un VDC 0 85 to 1 1 Un Consumption V AC 160 VA VDC 50 W The shunt closing release is combined with an anti pumping relay that enables
95. served
96. sition Note the arrows show the locked positions for the circuit breaker and the LV plug Functions m A drive system combined with a threaded shaft gives easier racking in and out The racking in mechanism can be operated with the door closed An interlock stops the user from inserting the lever as long as the racking truck has not been put in the racked in out position m An interlock between the circuit breaker status and the truck gives secure operation racking in or out is only possible if the circuit breaker is open m An interlock also exists between the LV connector and the truck It is only possible to rack in if the LV connector is connected The cradle floor has all the fixing holes needed to correctly position the earthing switch control mechanism and power circuit This makes earthing switch operation reliable and gives interlocking between the circuit breaker and the earthing switch m Earthing is automatic when the truck is fully racked in m Protective shutters stop fingers from touching the racking clusters when the device is extracted protection index IP2X m For maintenance operations it is possible to O padlock the shutters in the closed position y O unlock the shutter mechanism to access the racking clusters Circuit breaker Racked in out Earthing sliding device A foolproof device enables correct matching of the cradle and circuit breaker rating DE56852 Shutters DE51946 po
97. sition contacts This system is mounted on the cradle base Part of the system must be assembled contact locked by the panel builder on the cubicle floor DE51947 Accessories m One set of auxiliary contacts O 4 circuit breaker racked in out position contacts O 1 contact showing that the circuit breaker is locked in place on the cradle m Cradle earthing is provided by a sliding copper contact m A key locking system Ronis or Profalux for the circuit breaker in the racked out position enables increased safety downstream of it during work This system is associated with an earthing switch m Locking of the circuit breaker compartment door This device enables the circuit breaker full version to only be operated when the door is closed Door locking mechanism DE51942 DE56847 DE56849 Evolis 17 5 kV withdrawable frontal version a Power circuit 3 connector sets Field deflectors Description of functions MV connection Composition The power circuit comprises m mobile contacts with disconnectable clusters and arms mounted on the circuit breaker m fingers attached to the cradle and insulated by bushings and metal shutters This assembly provides perfect control of the dielectric strength mechanic the short time withstand current and the temperature rise All of these characteristics have been validated in tests Connection Connection is easily done from outside the cr
98. sparent screen blocks access to the opening and closing push buttons on the circuit breaker The device enables the opening or closing push button to be locked independently It is often associated with an electrical motor MCH Locking is achieved either m by 2 screws m by 3 padlocks not supplied m by a lead seal DE56895 DE56896 Lead sealing Locking of the circuit breaker in the open position The circuit breaker is locked in the open position by blocking the opening push button in the engaged position m by a padlock 1 to 3 padlocks not supplied m by a keylocks 1 or 2 different keylocks not supplied The keylocks are of captive key type with the key free after locking either Profalux or Ronis right turn and are proposed according to the options either with m 1 single keylock m 1 single keylock mounted on the circuit breaker 1 identical delivered separately Keylocking of the circuit breaker in the open position for interlocking with another device m 2 different keylocks for double locking Profalux and Ronis keylocks are inter compatible Evolis 17 5 kV Description of functions fixed frontal version Wiring diagram Wiring diagram principle z Circuit breaker open Operating mechanism loaded l DE56125E l l l l l Di oe 4 Fault Ready to close ON l MX2 ES _ EEE Remote control Auxiliary contacts MCH electrical motor
99. the circuit breaker in the open position DE56894 Opening button Closing button Control mechanism status charged or discharged Push button locking Circuit breaker position indicator Operation counter Push button locking This transparent screen blocks access to the opening and closing push buttons on the circuit breaker The device enables the opening or closing push button to be locked independently It is often associated with an electrical motor MCH Locking is achieved either m by 2 screws m by 3 padlocks not supplied m by a lead seal DE56895 DE56896 Padlocking Lead sealing Locking of the circuit breaker in the open position The circuit breaker is locked in the open position by blocking the opening push button in the engaged position m by a padlock 1 to 3 padlocks not supplied m by a keylocks 1 or 2 different keylocks not supplied The keylocks are of captive key type with the key free after locking either Profalux or Ronis right turn and are proposed according to the options either with m 1 single keylock m 1 single keylock mounted on the circuit breaker 1 identical delivered separately for interlocking with another device m 2 different keylocks for double locking Profalux and Ronis keylocks are inter compatible Cubicle door interlocking mechanism This device enables the circuit breaker to only be operated when the door
100. tion cascading The leading edge technologies employed in Merlin Gerin s Guiding System ensure high performance levels in discrimination and cascading of protection devices electrodynamic withstand of switches and current distributors heat loss of devices distribution blocks and enclosures Likewise inter product ElectroMagnetic Compatibilty EMC is guaranteed Mechanical consistency Each product adopts dimensional standards simplifying and optimising its use within the system It shares the same accessories and auxiliaries and complies with global ergonomic choices utilisation mode operating mode setting and configuration devices tools etc making its installation and operation within the system a simpler process Communication consistency Each product complies with global choices in terms of communication protocols Modbus Ethernet etc for simplified integration in the management supervision and monitoring systems SM6 Medium voltage switchboard system from 1 to 36 kV Sepam Protection relays Masterpact Protection switchgear from 100 to 6300 A Trihal The Technical guide These technical guides help you comply with installation standards and rules i e The electrical installation guide the protection guide the switchboard implementation guide the technical booklets and the co ordination tables all form genuine reference tools for the design of high performance e
101. w Shunt opening release MX 24 Vac 24 30 Vdc 100 130 Vdc ac 48 Vac 48 60 Vdc 200 250 Vdc ac 2nd opening release a 42 pin LV plug is mandatory Shunt opening release MX 24 Vac 24 30 Vdc 100 130 Vdc ac 48 Vac 48 60 Vdc 200 250 Vdc ac Undervoltage release MN 24 Vac 24 30 Vdc 100 130 Vdc ac 48 Vac 48 60 Vdc 200 250 Vdc ac Time delay unit for MN 48 60 Vdc ac 100 130 Vdc ac 200 250 Vdc ca Low energy release Mitop 1 AC fault signalling SDE and reset 200 250 Vac are included Remote control operation counter already included Electrical motor MCH 24 30 Vdc 100 125 Vdc 200 250 Vdc 48 60 Vdc ac 100 130 Vac 200 240 Vac Shunt closing release XF 24 Vac 24 30 Vdc 100 130 Vdc ac 48 Vac 48 60 Vdc 200 250 Vdc ac Operation counter CDM already included if remote control supplied E Additional auxiliary contacts OF 4 AC 1 2 Ready to close contact PF 1 AC LV plug 42 pin LV plug instead of 18 Operating crank Quantity one mini per switchboard Locking of the circuit breaker in the open position By padlock or by locks and keys Profalux Ronis flocks Hlock identical locks 2 different locks Disabling of O C circuit breaker push buttons iz Phase distance mm 145 185 240 Cradle accessories Racked in out C B position signalling 4 AC C B ready to be operated PAF 1 AC Field deflectors for bushings Releases combinations table
102. with clusters m racking truck with operating crank and screw shaft system m a manual operating mechanism spring type m LV plug 18 pins m 1 shunt opening release MX m 1 block of 4 ON OFF indication contacts The circuit breaker can receive options The cradle includes m 6 bushings with fingers m shutters m shutters mechanism The cradle can receive accessories Phase distance mm 145 185 240 7 2 kV 25 kA 630 A E E 1250 A a 2500 A m 31 5 kA 630 A E 1250 A E 2500 A E 40 kA 630 A m 1250 A E 2500 A E 12 kV 25 kA 630 A E E 1250 A E E 2500 A E 31 5 kA 630 A E 1250 A m 2500 A E 40 kA 630 A E 1250 A E 2500 A E 17 5 kV 25 kA 630 A m 1250 A a 2500 A a 31 5 kA 630 A m 1250 A E 2500 A m 40 kA 630 A m 1250 A m 2500 A m Evolis 17 5 kV Offer structure cont withdrawable frontal version Remote control see possible choices in combination table below 2nd opening release Shunt opening release MX fig 3 Undervoltage release MN fig 3 Time delay unit for MN setting 0 5 0 9 1 5 3 s fig 4 Low energy release Mitop fig 2 1 AC fault signalling SDE and reset 200 250 Vac are included Remote control including Electrical motor MCH and shunt closing release XF and operation counter CDM fig 1 3 amp 5 DE56933 DE56934 DE56879 DE56881 Fig 3 DE56887 Releases combinations table MX MN Mitop Indication Operation cou
103. wnstream fixed connections Ir to be mounted on bushings only 56952 E T g Der Jl i eS Fig 3 Downstream fixed connections Ir to be mounted on basic circuit breaker only a yr cD lt a ee ae Fig 1 UY fig 2 Se Fig 3 Labels kit for push button and indicator O C Circuit breaker support frame 3 fixed distance H or V fig 1 630 1250 A 59400 3 variable distance H fig 3 630 1250 A 59401 3 variable distance V fig 2 630 1250 A 59402 3 fixed distance H or V fig 1 630 2500 A 59403 3 variable distance H fig 3 630 2500 A 59404 3 variable distance V fig 2 630 2500 A 59405 3 fixed distance H or V fig 1 630 2500 A 59409 3 variable distance H fig 3 630 2500 A 59410 3 variable distance V fig 2 630 2500 A 59411 Circuit breaker specific labels green red etc 59100 Adaptation kit needed for circuit breaker opening for retrofit 59093 Drawings and casters User manual 59050 59069 Evolis 17 5 kV Services fixed frontal version The following components can only be adapted or replaced on site by staff trained by Schneider Electric m remote control mechanism comprising electrical motor shunt closing release operation counter m operation counter m low energy release Mitop m circuit breaker front cover Evolis Evolis 17 5 kV withdrawable frontal version Panorama Evolis 17 5 kV fixed frontal version Main characteristics
104. xtracted protection index IP2X For maintenance purpose it is possible to m padlock the shutters in the closed position m unlock the fixed contact access mechanism and insert a screen to insulate the energized contact set A drawing is available on request to produce this protective screen see Installation Guide A foolproof device enables the cradle to be fitted perfectly to the circuit breaker relative to the cradle caliber Interlocking door cubicle This system is mounted on the cradle side The combination corresponding to the right circuit breaker rating must be produced by the panel builder Anti drop function This function provides operator safety when extracting the circuit breaker DE51961 Earthing switch It can be fitted under the cradle to give the appropriate interlocking between the circuit breaker and the earthing switch see detailed description in the Earthing switch and cubicle components catalogue Evolis 24 kV Description of functions withdrawable Racking In cont frontal version Optional accessories m 4 racked in out position contacts m Additional earthing device copper sliding device m LPCT tore type sensors mounted directly on the cradle bushings m Auto discharge function Racked in out position Earthing sliding device the circuit breaker operating mechanism springs are automatically discharged when the circuit b