1. PXC24 2 EF32 A PXC Compact 24 point BACnet IP ALN P1 or MS TP FLN Enabled PXC24 2 ERF A PXC Compact 24 point BACnet IP ALN rooftop P1 or MS TP FLN PXC36 E A PXC Compact 36 point BACnet IP or MS TP ALN PXC36 EF A PXC Compact 36 point BACnet IP or MS TP ALN Island Bus P1 or MS TP FLN Optional Licenses Product Number Description LSM FLN License to enable FLN support on PXC 16 or PXC 24 F models LSM FLN36 A License to enable FLN support on models PXC36 E A and PXC36 PE A LSM IB36 A License to enable 4 TX I O modules on the Island Bus on models PXC36 E A and PXC36 PE A LSM 36 A License to enable 4 TX I O modules on the Island Bus and FLN support on models PXC36 E A and PXC36 PE A Siemens Industry Inc Page 11 of 33 Product Number Description LSM FPWEB License to enable BACnet Field Panel Web Server PXC 36 or Web Services PXC 16 24 Option enables HTTP Change of Value needed for field panel hosted graphics LSM SNMP License to enable SNMP Agent License to enable SNMP Agent Accessories Product Number Description PXM10S Controller mounted Operator Display module with point monitor and optional blue backlight PXM10T Controller mounted Operator Display module PXA8 M 8 switch HOA UL864 PXA16 M 16 switch HOA UL864 PXA16 MR 16 switch HOA extended temp UL 916 with HMI cable PXA HMI CABLEP5 Seria
2. SIEMENS www hvacusa com hvac SA com Technical Specification Sheet A MechTronics Controls Company Document No 149 206 July 1 2013 Phone 877 632 4876 PXC Compact Series for BACnet Networks Figure 1 PXC Compact Series Controllers PXC 24 and PXC 36 shown Description The PXC Compact Series Programmable Controller Compact for BACnet networks is a high performance Direct Digital Control DDC supervisory equipment controller which is an integral part of the APOGEE Automation System The controllers are classified as either a BACnet Building Controller B BC with support for BACnet IP or BACnet MS TP protocols The PXC Compact Series offers integrated I O based on state of the art TX I O Technology which provides superior flexibility of point and signal types and makes it an optimal solution for Air Handling Unit AHU control The PXC Compact operates stand Siemens Industry Inc alone or networked to perform complex control monitoring and energy management functions without relying on a higher level processor The PXC Compact Series communicates with other field panels or workstations on a peer to peer Automation Level Network ALN or on the Field Level Network FLN and supports the following communication options e Native BACnet IP communications over 10 100 MB Ethernet networks e Native BACnet MS TP on RS 485 The PXC Compact is available with 16 24 or 36 point termin
3. monitor alarm trend and generate reports on BACnet objects within the controller database including supervised FLN device information schedule BACnet objects within the controller database including supervised FLN devices and remote notification Programmable Control with Application Flexibility The PXC Compact Series of high performance controllers provides complete flexibility which allows the owner to customize each controller with the exact program for the application The control program for each PXC Compact is customized to exactly match the application Proven Powers Process Control Language PPCL a text based programming structure like BASIC provides direct digital control and energy management sequences to precisely control equipment and optimize energy usage Siemens Industry Inc Global Information Access The HMI port supports operator devices such as a local user interface or simple CRT terminal and a phone modem for dial in service capability Devices connected to the operator terminal port gain global information access Multiple Operator Access Multiple operators can access the network simultaneously Multiple operator access ensures that alarms are reported to an alarm printer while an operator accesses information from a local terminal When using the BACnet IP ALN option multiple operators may also access the controller through concurrent Telnet sessions and or local operator termin
4. Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Binary Input Object Type Property Identifier Supported Writable Required Optional Page 21 of 33 Page 22 of 33 Object Identifier Yes R Object Name Yes R Object Type Yes R Present Value Yes Yes R Description Yes Yes O Device_Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes Yes R Polarity Yes R Inactive_Text Yes O Active_Text Yes O Elapsed_Active_Time Yes Yes O Time_Of_Active_Time_Reset Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O Alarm_Value Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Binary Output Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Siemens Industry Inc Siemens Industry Inc Object Name Yes R Object Type Yes R Present Value Yes Yes W Description Yes Yes O Device_Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes R Polarity Yes R Inactive_Text Yes O Active_Text Yes O Elapsed_Active_Time Yes Yes O Time_Of_Active_Time_Reset Yes O Priority_Array Yes R Relinquish_default Yes R Time_Delay Yes Alarm O
5. Creatable Deletable Calendar Command Device Event Enrollment File Multi state Output Multi state Value Notification Class Schedule Trend Log O indicates that the property is optional per the BACnet standard R indicates that the property is required to be present and readable using BACnet services Yes indicates that the property is required to be present readable and writable using BACnet services Analog Input Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Present Value Yes Yes R Description Yes Yes O Device_Type Yes O Siemens Industry Inc Siemens Industry Inc Status Flags Yes R Event State Yes R Reliability Yes O Out_Of_Service Yes Yes R Units Yes Yes R Resolution Yes O COV_lncrement Yes Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O High_Limit Yes Alarm Yes O Low_Limit Yes Alarm Yes O Deadband Yes Alarm O Limit_Enable Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Analog Output Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Object Type
6. Industry Inc Point count includes 3 Universal Input UI 9 Universal I O U 4 Super Universal I O X 3 Analog Output AOV 5 Digital Output DO PXC 36 The PXC 36 provides control of 36 local points including 24 software configurable universal points Point count includes 18 Universal I O U 6 Super Universal I O X 4 Digital Input DI and 8 Digital Output DO The PXC 36 offers the flexibility of expanding the total point count through a self forming Island Bus With the addition of a TX I O Power Supply up to four TX I O modules can be supported For more information see the 7X O Product Range Technical Specification Sheet 149 476 Hardware The PXC Compact Series consists of the following major components e Input Output Points e Power Supply e Controller Processor Input Output Points e The PXC Compact input output points perform A D or D A conversion signal processing point command output and communication with the controller processor The terminal blocks are removable for easy termination of field wiring e The Universal and Super Universal points leverage TX I O Technology from Siemens Building Technologies to configure an extensive variety of point types e Universal Input UI and Universal Input Output U points are software selectable to be 0 10V input Siemens Industry Inc 4 20 mA input Digital Input Pulse Accumulator inputs 41KNi RTD
7. Notification Class Yes Alarm Yes O Feedback_Value Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Binary Value Object Type Property Identifier Supported Writable Required Page 23 of 33 Page 24 of 33 Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Present Value Yes Yes R Description Yes Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes R Inactive_Text Yes O Active_Text Yes O Elapsed_Active_Time Yes Yes O Time_Of_Active_Time_Reset Yes O Priority_Array Yes O Relinquish_default Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O Alarm_Value Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Calendar Object Type Property Identifier Supported Writable Required Optional Siemens Industry Inc Siemens Industry Inc Object Identifier Yes R Object Name Yes R Object Type Yes R Description Yes Yes O Present_Value Yes R Date_List Yes Yes R Command Object Type Property Identifier Supported Writable Required Y Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Descr
8. power up and power down sequences for the equipment controlled by the I O points even through brownout conditions Controller Processor The PXC Compact Series includes a microprocessor based multi tasking platform for program execution and communications with the I O points and with other PXC Compacts and field panels over the ALN A Human Machine Interface HMI port with a quick connect phone jack RJ 45 uses RS 232 protocol to support operator devices such as a local user interface or simple CRT terminal and a phone modem for dial in service capability A USB Device port supports a generic serial interface for an HMI or Tool connection or used for memory expansion in select models The USB Device port does not support firmware flash upgrades The program and database information stored in the PXC Compact RAM memory is battery backed This eliminates the need for time consuming program and database re entry in the event of an extended power failure Page 4 of 33 The firmware which includes the operating System is stored in non volatile flash ROM memory this enables firmware upgrades in the field Brownout protection and power recovery circuitry protect the controller board from power fluctuations LEDs provide instant visual indication of overall operation network communication and low battery warning Available Options The following options are available to match the application FLN
9. 32 F Siemens Johnson Controls DIN Standard 1K Pt RTD 375 or 385 alpha 32 F 10K NTC Thermistor Type 2 and Type 3 77 F 100K NTC Thermistor Type 2 77 F 0 10V Analog Output Universal Input Output U points only Super Universal X points PXC 24 and PXC 36 only are software selectable to be 0 10V input 4 20 mA input Digital Input Pulse Accumulator inputs 1KNi RTD 32 F Siemens Johnson Controls DIN Standard 1K Pt RTD 375 or 385 alpha 32 F 10K NTC Thermistor Type 2 and Type 3 77 F 100K NTC Thermistor Type 2 77 F 0 10V Analog Output 4 20 mA Analog Output Digital Output using external relay Dedicated Digital Input DI points PXC 16 only are dry contact status sensing Digital Output DO points are 110 220V 4 Amp resistive Form C relays LEDs indicate the status of each point All PXC Compact Series models support 0 10 Vdc Analog Output circuits Page 3 of 33 On PXC 24 and PXC 36 models the Super Universal points may be defined as either 0 10 Vdc or 4 20 mA Analog Output circuits Power Supply The 24 volt DC power supply provides regulated power to the input output points and active sensors The power supply is internal to the PXC Compact housing eliminating the need for external power supply and simplifying installation and troubleshooting The power supply works with the processor to ensure smooth
10. Size 32 Device Address Binding Is Static Device Binding supported Yes Page 32 of 33 Siemens Industry Inc Networking Options Router Clause 6 BACnet IP Annex J to BACnet MS TP Annex H 3 BACnet Tunneling Router over UDP IP BACnet IP Broadcast Management Device BBMD Yes Does the BBMD support registrations by Foreign Devices Character Sets ANSI X3 4 ISO 10646 USC 2 IBM Microsoft DBCS ISO 10646 ICS 4 ISO 8859 1 JIS C 6226 Information in this document is based on specifications believed correct at the time of publication The right is reserved to make changes as design improvements are introduced APOGEE is a registered trademark of Siemens Industry Inc Product or company names mentioned herein may be the trademarks of their respective owners 2013 Siemens Industry Inc Your feedback is important to us If you have Document No 149 206 Siemens Industry Inc comments about this document please send them to Printed in the USA Building Technologies Division SBT _technical editor us sbt siemens com Page 33 of 33 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 USA Tel 1 847 215 1000
11. Support The PXC 16 and PXC 24 F32 models provide support for up to 32 RS 485 P1 or MS TP devices The PXC 16 and PXC 24 F models with the addition of a FLN license support up to 32 RS 485 P1 or MS TP devices The PXC 36 with an FLN license supports up to 96 RS 485 P1 or MS TP devices A Wireless FLN may also be used to replace the traditional P1 FLN cabling with wireless communication links that form a wireless mesh network Additional hardware is required to implement the Wireless FLN For more information about FLN support contact your local Siemens Industry representative Extended Temperature Operation PXC 24 R models support extended temperature operation allowing for rooftop installations Siemens Industry Inc Web Server and Web Services The PXC Compact Series supports Web Server and Web Services functionality The Web Server license provides an HTML Web based user interface for your APOGEE Building Automation System It is an ideal solution for small or remote facilities with field panels on a BACnet IP Automation Level Network ALN The Web Server Web Services is a licensable option on the PXC Compact The Web Services must be used in conjunction with Web Server located on a PXC 36 or PXC Modular and provides Web access to database information in PXC 24 and PXC 16 BACnet IP controllers This solution provides the user the following features Web based graphics and user interface command
12. Yes R Present Value Yes Yes W Description Yes Yes O Page 19 of 33 Page 20 of 33 Device Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes R Units Yes R Min_Pres_Value No O Max_Pres_Value No O Resolution Yes O Priority_Array Yes R Relinquish_default Yes R COV_Increment Yes Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O High_Limit Yes Alarm Yes O Low_Limit Yes Alarm Yes O Deadband Yes Alarm O Limit_Enable Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Analog Value Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Siemens Industry Inc Siemens Industry Inc Object Name Yes R Object Type Yes R Present Value Yes Yes R Description Yes Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes R Units Yes R Priority_Array Yes O Relinquish_default Yes O COV_Increment Yes Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O High_Limit Yes Alarm Yes O Low_Limit Yes Alarm Yes O Deadband Yes Alarm O Limit_Enable Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes
13. al ports plus optional Web interface using the Web or Web Services option Menu Prompted English Language Operator Interface The PXC Compact includes a simple yet powerful menu driven English Language Operator Interface that provides among other things e Point monitoring and display e Point commanding e Historical trend collection and display for multiple points e Event scheduling e Program editing and modification via Powers Process Control Language PPCL e Alarm reporting and acknowledgment e Continual display of dynamic information Page 5 of 33 Built in Direct Digital Control Routines The PXC Compact provides stand alone Direct Digital Control DDC to deliver precise HVAC control and comprehensive information about system operation It receives information from sensors in the building processes the information and directly controls the equipment The following functions are available in the PXC Compact Adaptive Control an auto adjusting closed loop control algorithm which provides more efficient adaptive robust fast and stable control than the traditional PID control algorithm It is superior in terms of response time and holding steady state and at minimizing error oscillations and actuator repositioning Closed Loop Proportional Integral and Derivative PID control Logical sequencing Alarm detection and reporting Reset schedules Page 6 of 33 Built in Energy Manag
14. arm and Event Information A AE INFO B Alarm and Event Information B Trending T VMT A Trending Viewing and Modifying Trends A T VMT I B Trending Viewing and Modifying Trends Internal B T VMT E B Trending Viewing and Modifying Trends External B T ATR B Trending Automated Trend Retrieval B Network Management NM CE A Network Management Connection Establishment A Page 16 of 33 Siemens Industry Inc Device Management DM DDB A Device Management Dynamic Device Binding A DM DDB B Device Management Dynamic Device Binding B DM DOB A Device Management Dynamic Object Binding A DM DOB B Device Management Dynamic Object Binding B DM DDC B Device Management DeviceCommunicationControl B DM PT A Device Management Private Transfer A DM PT B Device Management Private Transfer B DM TM A Device Management Text Message A DM TM B Device Management Text Message B DM TS B Device Management TimeSynchronization B DM RD B Device Management ReinitializeDevice B DM BR B Device Management Backup and Restore B DM LM B Device Management List Manipulation B DM OCD B Device Management Object Creation and Deletion B Standard Object Types Supported Siemens Industry Inc Name Creatable Deletable Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Page 17 of 33 Object Attributes Page 18 of 33 Name
15. ations Selected models in the Compact Series provide the following options e Supervision for FLN devices e An extended temperature range for the control of rooftop devices e Support for Island Bus which uses TX I O modules to expand the number of point terminations for high speed loop control Page 1 of 33 Features e BACnet Testing Laboratories BTL certified Classified as BACnet Building Controllers B BC using the BACnet IP protocol and or BACnet MS TP DIN rail mounted device with removable terminal blocks simplifies installation and servicing e Proven program sequences to match equipment control applications e Built in energy management applications and DDC programs for complete facility management e Comprehensive alarm management historical data trend collection operator control and monitoring functions e Sophisticated Adaptive Control a closed loop control algorithm that auto adjusts to compensate for load seasonal changes e Message control for terminals printers pagers and workstations e Highly configurable I O using Siemens state of the art TX I O Technology e HMI RS 232 port which provides laptop connectivity for local operation and engineering e Extended battery backup of Real Time Clock Persistent database backup and restore within the controller e Optional HOA Hand Off Auto module for swappable and configurable HOA capability Optional extended t
16. ature Models 18 months Coin cell BR2032 3 Volt lithium Communication A D Resolution analog in D A Resolution analog out BACnet IP Automation Level Network Siemens Industry Inc 16 bits 10 bits 10Base T or 100Base TX compliant Page 7 of 33 ALN BACnet MS TP Automation Level Network ALN BACnet MS TP Field Level Network FLN on selected models license required RS 485 P1 Field Level Network FLN on selected models license required Human Machine Interface HMI USB Device port for non smoke control applications only USB Host port on selected models for ancillary smoke control applications only RS 485 9600 bps to 115 2 Kbps RS 485 9600 bps to 76 8 Kbps 4800 bps to 38 4 Kbps RS 232 compliant 1200 bps to 115 2 Kbps Standard 1 1 and 2 0 USB device port Type B female connector Standard 1 1 and 2 0 USB host port Type A female connector Electrical Power Requirements Power Consumption Maximum AC Power and Digital Outputs Communication and all other I O Digital Input Digital Output Analog Output Universal Input UI and Universal Input Output U Page 8 of 33 24 Vac 20 input 50 60 Hz PXC 16 18 VA 24 Vac PXC 24 20 VA 24 Vac PXC 36 35 VA 24 Vac NEC Class 1 Power Limited NEC Class 2 Contact Closure Sensing Dry Contact Potential Free inputs only Does not support counter inputs Class 1 Rel
17. ay 0 to 10 Vdc Analog Input Voltage 0 10 Vdc Siemens Industry Inc Electrical Current 4 20 mA 1K Ni RTD 32 F 1K Pt RTD 375 or 385 alpha 32 F 10K NTC Type 2 or Type 3 Thermistor 77 F 100K NTC Type 2 Thermistor 77 F Digital Input Pulse Accumulator Contact Closure Sensing Dry Contact Potential Free inputs only Supports counter inputs up to 20 Hz Analog Output Universal Input Output U points only Voltage 0 10 Vdc Super Universal X Analog Input Voltage 0 10 Vdc Current 4 20 mA 1K Ni RTD 32 F 1K Pt RTD 375 or 385 alpha 32 F 10K NTC Type 2 or Type 3 Thermistor 77 F 100K NTC Type 2 Thermistor 77 F Digital Input Pulse Accumulator Contact Closure Sensing Dry Contact Potential Free inputs only Supports counter inputs up to 20 Hz Analog Output Voltage 0 10 Vdc Current 4 20 mA Digital Output requires an external relay 0 to 24 Vdc 22 mA max Siemens Industry Inc Page 9 of 33 Operating Environment Ambient operating temperature 32 F to 122 F 0 C to 50 C Ambient operating temperature with 40 F to 158 F 40 C to 70 C rooftop extended temperature option Relative Humidity PXC 76 and PXC 24 5 to 95 non condensing PXC 36 5 to 95 non condensing Mounting Surface PXC 76 and PXC 24 Direct equipment mount building wall or structural member PXC 36 Building wall or a secure structure Agency Listin
18. bject Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Description Yes Yes O Log_Enable Yes Yes W Start_Time Yes Yes O Stop_Time Yes Yes O Log_DeviceObjectProperty Yes O Log Interval Yes O Client COV Interval Yes O Stop_When_Full Yes Yes R Buffer_Size Yes R Log_Buffer Yes R Record_Count Yes Yes W Total_Record_Count Yes R Notification_Threshold Yes Alarm Yes O Records_Since_Notification Yes Alarm O Last_Notify_Record Yes Alarm O Event_State Yes Alarm R Page 31 of 33 Notification Class Yes Alarm Yes O Event_Enable Yes Alarm O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Event_Time_Stamps Yes Alarm O Data Link Layer Options BACnet IP Annex J BACnet IP Annex J Foreign Device ISO 8802 3 Ethernet Clause 7 ANSI ATA 878 1 2 5 Mb ARCNET Clause 8 ANSI ATA 878 1 RS 485 ARCNET Clause 8 baud rate s MS TP master Clause 9 baud rate s 9600 bps 19200 bps 38400 bps 76800 bps MS TP slave Clause 9 baud rate s Point To Point EIA 232 Clause 10 baud rate s Point To Point modem Clause 10 baud rate s LonTalk Clause 11 medium Other Segmentation Capability Able to transmit segmented messages Yes Window Size 32 Able to receive segmented messages Yes Window
19. ct Type Yes R Present Value Yes Yes R Description Yes Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes Yes R Number_Of_States Yes R State_Text Yes O Priority_Array Yes O Relinquish_default Yes O Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O Alarm_Values Yes Alarm O Fault_Values Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Notify_Type Yes Alarm O Page 29 of 33 Page 30 of 33 Event Time Stamps Yes Alarm O Notification Class Object Type Property Identifier Supported Writable Required Y Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Description Yes Yes O Notification Class Yes R Priority Yes Yes R Ack Required Yes Yes R Recipient List Yes Yes R Schedule Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Present Value Yes Yes R Description Yes Yes O Effective Period Yes Yes R Weekly Schedule Yes Yes O Exception_Schedule Yes Yes O Schedule_Default Yes Yes R List Of Object Property References Yes Yes R Priority For Writing Yes Yes R Siemens Industry Inc Siemens Industry Inc Status Flags Yes R Reliability Yes R Out Of Service Yes Yes R Trend Log O
20. ement Applications The following applications are programmed in the PXC Compact Series and require simple parameter input for implementation Automatic Daylight Saving Time switchover Calendar based scheduling Duty cycling Economizer control Equipment scheduling optimization and sequencing Event scheduling Holiday scheduling Night setback control Peak Demand Limiting PDL Temperature compensated duty cycling Temporary schedule override Siemens Industry Inc BACnet Compact Series Specifications Dimensions L x W x D PXC 16 and PXC 24 PXC 36 10 7 x 5 9 x 2 45 272 mm x 150 mm x 62 mm 11 5 x 5 9 x 3 0 293 mm x 150 mm x 77 mm Processor Battery and Memory Processor and Clock Speed Memory Battery backup of Synchronous Dynamic SD RAM field replaceable Battery backup of Real Time Clock PXC 16 and PXC 24 Freescale MPC852T 100 MHz PXC 36 Freescale MPC885 133 MHz PXC 16 and PXC 24 24 MB 16 MB SDRAM 8 MB Flash ROM PXC 36 80 MB 64 MB SDRAM 16 MB Flash ROM PXC 16 and PXC 24 Non rooftop Models 60 days accumulated AA LR6 1 5 Volt Alkaline non rechargeable PXC 36 28 days accumulated AA LR6 1 5 Volt Alkaline non rechargeable Rooftop Extended Temperature Models 90 days accumulated AA LR6 3 6 Volt Lithium non rechargeable Non rooftop Models 10 years Coin cell BR2032 3 Volt lithium Rooftop Extended Temper
21. emperature range for rooftop installation Optional support for RS 485 P1 or MS TP devices e Optional P1 Wireless FLN support Page 2 of 33 Auto Save and persistent database backup and restore within the controller e PXM10T and PXM10S support Optional LCD Local user interface with HOA Hand off auto capability and point commanding and monitoring features e MS TP Point Pickup Module PPM support Universal Inputs can be configured for analog or digital input Input Output type is configured by writing to BACnet object properties e BACnet Field Panel Web Server support Web based Graphical User Interface GUI compatible with BACnet networks Ideal for small or remote facilities to monitor and control the Building Automation System e The Simple Network Management Protocol SNMP Agent allows points in the field panel to communicate with an SNMP manager over Ethernet The Compact Series In addition to building and system management functions the Compact Series includes several styles of controllers that flexibly meet application needs PXC 16 The PXC 16 provides control of 16 points including 8 Software configurable universal points Point count includes 3 Universal Input UI 5 Universal I O U 2 Digital Input DI 3 Analog Output AOV and 3 Digital Output DO PXC 24 The PXC 24 provides control of 24 points including 16 software configurable universal points Siemens
22. ent_Parameters Yes Yes R Object_Property_Ref Yes R Event_State Yes R Event_Enable Yes Yes R Acked_Transitions Yes R Notification Class Yes Yes R Event_Time_Stamps Yes R File Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Description Yes O File_Type Yes R File_Size Yes Yes R Page 27 of 33 Page 28 of 33 Modification Date Yes R Archive Yes Yes Ww Read only Yes R File Access Method Yes R Multi state Output Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Present Value Yes Yes W Description Yes Yes O Device_Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes Yes R Number_Of_States Yes R State_Text Yes O Priority_Array Yes R Relinquish_default Yes R Time_Delay Yes Alarm O Notification Class Yes Alarm Yes O Feedback_Value Yes Alarm O Event_Enable Yes Alarm Yes O Acked_Transitions Yes Alarm O Siemens Industry Inc Siemens Industry Inc Notify Type Yes Alarm O Event_Time_Stamps Yes Alarm O Multi state Value Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Obje
23. gs UL UL864 UUKL Smoke Control Equipment except rooftop models UL864 UUKL7 Smoke Control Equipment except rooftop models CAN ULC S527 M8 except rooftop models UL916 PAZX all models UL916 PAZX7 all models CSA CSA 22 2 No 205 M1983 SIGNAL EQUIPMENT Agency Compliance FCC Compliance CFR47 Part 15 Subpart B Class B Australian EMC Framework European EMC Directive CE European Low Voltage Directive LVD BTL BACnet Testing Laboratories BTL Certified Firmware Revision 3 0 and later OSHPD Seismic Certification Product meets OSHPD Special Seismic Preapproval certification OSH 0217 10 under California Building Code 2010 CBC2010 and International Building Code 2009 IBC2009 when installed within the following Siemens enclosure part numbers PXA ENC18 PXA ENC19 or PXA ENC34 Page 10 of 33 Siemens Industry Inc Ordering Information PXC Compact Series Part Number Description PXC16 2 E A PXC Compact 16 point BACnet IP ALN PXC16 2 M A PXC Compact 16 point MS TP ALN PXC16 2 EF A PXC Compact 16 point BACnet IP ALN P1 or MS TP FLN PXC16 2 EF32 A PXC Compact 16 point BACnet IP ALN P1 or MS TP FLN Enabled PXC24 2 E A PXC Compact 24 point BACnet IP ALN PXC24 2 M A PXC Compact 24 point MS TP ALN PXC24 2 ER A PXC Compact 24 point BACnet IP ALN rooftop PXC24 2 MR A PXC Compact 24 point MS TP ALN rooftop PXC24 2 EF A PXC Compact 24 point BACnet IP ALN P1 or MS TP FLN
24. iption Yes Yes O Present_Value Yes Yes W In_Process Yes R All Writes Successful Yes R Action Yes Yes R Action Text Yes Yes O Device Object Type Property Identifier Supported Writable Required Optional Object Identifier Yes R Object Name Yes R Object Type Yes R System Status Yes R Vendor Name Yes R Page 25 of 33 Page 26 of 33 Vendor Identifier Yes R Model Name Yes R Firmware Revision Yes R Application Software Version Yes R Location Yes O Description Yes O Protocol_Version Yes R Protocol_Revision Yes R Protocol_Services_Supported Yes R Protocol_Object_Types_Supported Yes R Object_List Yes R Max_APDU_Lenght_Accepted Yes R Segmentation Supported Yes R Max Segments Supported Yes O Local_Time Yes O Local_Date Yes O Daylight_Savings_Status Yes O APDU_Segment_Timeout Yes O APDU_Timeout Yes R Number Of APDU Retries Yes R Device Address Binding Yes R Database Revision Yes R Configuration Files Yes O Last_Restore_Time Yes O Backup_Failure_Timeout Yes Yes O Siemens Industry Inc Siemens Industry Inc Active COV Subscriptions Yes O Event Enrollment Object Type Property Identifier Supported Writable Required Y Optional Object Identifier Yes R Object Name Yes R Object Type Yes R Description Yes Yes O Event_Type Yes R Notify_Type Yes Yes R Ev
25. l cable required for HOA or PXM10T S connection to non rooftop variants of the 16 point and 24 point Compact Series pack of 5 TXA1 LLT P100 Labels for HOA and TX I O Modules pack of 100 letter format Service Boxes and Enclosures Product Number Description PXA SB115V192VA PX Series Service Box 115V 24 Vac 50 60 Hz 192 VA PXA SB115V384VA PX Series Service Box 115V 24 Vac 50 60 Hz 384 VA PXA SB230V192VA PX Series Service Box 230V 24 Vac 50 60 Hz 192 VA PXA SB230V384VA PX Series Service Box 230V 24 Vac 50 60 Hz 384 VA PXA ENC 18 18 Enclosure Utility Cabinet UL Listed NEMA Type 1 Enclosure PXA ENC19 19 Enclosure UL Listed NEMA Type 1 Enclosure PXA ENC34 34 Enclosure UL Listed NEMA Type 1 Enclosure Page 12 of 33 Siemens Industry Inc Documentation Product Number Description 553 104 PXC Compact Series Owner s Manual 125 1896 APOGEE Powers Process Control Language PPCL User s Manual Information in this document is based on specifications believed correct at the time of publication The right is reserved to make changes as design improvements are introduced APOGEE and Insight are registered trademarks of Siemens Industry Inc Other product or company names mentioned herein may be the trademarks of their respective owners 2013 Siemens Industry Inc Siemens Industry Inc Your feedback is important to
26. pported Device Profile BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC BACnet Smart Actuator B SA BACnet Smart Sensor B SS Supported BACnet Interoperability Building Block BIBBs BIBB Name Initiate Execute Data Sharing DS RP A Data Sharing ReadProperty A DS RP B Data Sharing ReadProperty B DS RPM A Data Sharing ReadPropertyMultiple A DS RPM B Data Sharing ReadPropertyMultiple B DS WP A Data Sharing WriteProperty A DS WP B Data Sharing WriteProperty B DS WPM B Data Sharing WritePropertyMultiple B DS COV A Data Sharing COV A DS COV B Data Sharing COV B DS COVU A Data Sharing COV Unsolicited A DS COVU B Data Sharing COV Unsolicited B Siemens Industry Inc Page 15 of 33 Scheduling SCHED I B Scheduling Internal B SCHED E B Scheduling External B Alarm and Event Management AE N A Alarm and Event Notification A AE N I B Alarm and Event Notification Internal B AE N E B Alarm and Event Notification External B AE ACK A Alarm and Event ACK A AE ACK B Alarm and Event ACK B AE ASUM B Alarm and Event Alarm Summary B AE ESUM A Alarm and Event Enrollment Summary A AE ESUM B Alarm and Event Enrollment Summary B AE INFO A Al
27. us If you have Document No 149 206 Building Technologies Division comments about this document please send them Printed in the USA 1000 Deerfield Parkway to SBT_technical editor us sbt siemens com Page 13 of 33 Buffalo Grove IL 60089 4513 U S A Compact Series BACnet Protocol Implementation Conformance Statement Products Product Model Number Protocol Revision Software Revision Firmware Revision PXC16 2 E A PXC16 2 EF A PXC16 2 M A PXC16 2 EF32 A PXC24 2 E A PXC24 2 ER A PXC24 2 EF A PXC24 2 ERF A PXC24 2 M A PXC24 2 MR A PXC24 2 EF32 A PXC36 E A PXC36 EF A BACnet PXC 135 2008 N A 3 2 5 Compact Series Vendor Information Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 www buildingtechnologies siemens com bt us Product Description An integral member of the APOGEE product family the PXC Compact for BACnet Networks is a high performance modular Direct Digital Control DDC supervisory equipment and primary building controller The PXC Compact operates stand alone or networked to perform complex control monitoring and energy management functions without relying on a higher level processor The PXC Compact communicates on a 10 100 MB Ethernet BACnet IP or BACnet MS TP network and optionally supervises BACnet MS TP devices Page 14 of 33 Siemens Industry Inc BACnet Standardized Device Profile Annex L Su