1. To slave master An Slave oder Master 9 wired trunking 9 pol Tragschiene Cable Kabel 0 5 1 0 mm Caution Polarity Achtung Polarit t beachten
2. Raum belegt Bewolkt nicht ausreichendes nat rliches Licht I Jo Natural light level gt 02 Sunny sufficient natural light Fi Room unoccupied Nat rliche Lichtintensit t AN Sonnig ausreichendes nat rliches Licht Before T1 no one is in the office so the lights are off At T1 someone enters the office the artificial light will go to 100 and then immediately start DDR Daylight Depending Regulation to regulate according to the amount of natural daylight coming through the windows At T2 the person is leaving the cell office and the hold time starts During the grace time of 10 seconds from T3 to T4 the lights will be dimmed down to their minimum level and at T4 the lights will be switched off At T6 the person comes back into the office but the lights will stay off because the sun is shining and the light level is sufficient This is called a DDO Daylight Depending Override At T7 it becomes cloudy again The natural light level drops so the artificial light turns on automatically to compensate the lack of light At T8 the person is leaving the office again The light level continues to be regulated for another 15 minutes and at T9 it starts fading down again Finally the lights will be switched off at T10 If during the grace time T3 to T4 or T9 to T10 movement is detected the hold time will be extended by 10 minutes This will be done once only Mode 1 is designed for a classic luminaire arrangement The master
3. luminaire is implemented at the window side In Window Corridor configuration the luminaires alongside the windows are connected to the Window connection of the controller and the others are connected to the Corridor side The corridor side will follow the window side with an offset Raum nicht belegt For cell offices designed around the indoor lighting norm EN12464 or when using direct indirect lighting Mode 5 is advised See chapter 4 5 Mode 5 Open plan Task Workspace amp Decorative When in Parallel Linking or BMS configuration all luminaires are to be connected to the Window connection and commissioning of the luminaires is needed as described in chapter 6 10 Grouping of ballasts drivers When using the ActiLume DALI Gen 2 in Parallel Linking or BMS configuration there is also a possibility of having a third group of luminaires intended for decorative lighting Mode 1 Cell office Modus 1 B roeinheit 15 min Auto on Automatik ein on Auto off Automatik aus ActiLume DALI 2 Generation User Manual Anwender Handbuch Following these Link you will find the User Manual for the Philips Sensor DPC ACL and the driver Philips Controler LLC 1663 00 Auf diesem Pfad finden Sie das Anwender Handbuch fur den Philips Sensor DPC ACL und dem Steuergerat Philips Controler LLC 1663 00 http www lighting philips com main products controls philips multione configurator wpd Subject to cha
4. will fade down to 20 during Grace time T3 to T4 This light level background level will be maintained for 120 minutes T4 to T5 before the lights will be turned off If needed the background level can be altered to 1 10 20 30 40 or 50 This is described in chapter 6 3 Setting the background level Mode 2 Modus 2 100 Background level Light level Grundausleuchtung Licht intensitat 10 Po T1 T2 T3 T4 TS 16 T7 gt Time T8 T9 T10 ZH 5 4 Articial light level lt D Overcast insufficient natural light Kiinstliche Lichtintensitat Bewolkt nicht ausreichendes nat rliches Licht Natural light level SQ Sunny sufficient natural light Nat rliche Lichtintensitat A Sonnig ausreichendes nat rliches Licht In Window Corridor configuration the luminaires Mode 2 Open plan office alongside the windows are connected to the Window Modus 2 Gro raumb ro connection of the controller and the others are Fe 3 Auto on Automatik ein connected to the Corridor side The corridor side Auto off Automatik aus will follow the window side with an offset For open gt Fi Fi Room occupied Raum belegt Room unoccupied Raum nicht belegt plan offices designed around the indoor lighting norm EN12464 or when using direct indirect lighting Mode 5 is advised See chapter 4 5 Mode 5 Open plan Task Workspace amp Decorative When in Parallel Linking or BMS configura
5. EDER NORDEUNE Daylight Presence Control Tageslicht Pr senzregelung Philips ActiLume Installation Instructions Montageanleitung Notice de montage indicaciones de montaje Istruzioni per l installazione Installatie instructies Trunking Tragschiene Electrical unit with sensor Lichttr ger mit Sensor L mm Electrical unit Lichttr ger per trunking je Tragschiene 281 562 1 124 1 686 Drawing shows version 281 mm Zeichnung stellt Version 281mm dar Nordeon GmbH Rathenaustra e 2 6 D 31832 Springe Germany Phone 49 0 5041 750 www nordeon com 060 0906 362 00 12 14 Daylight sensor Tageslichtsensor LED indicator Kontroll LED Anzeige Infra Red sensor Infra Rot Sensor Movement sensor Bewegungssensor Detection pattern diagram Erfassungsbereich a a 30 30 30 30 30 30 27 27 X 27 x no detection keine Erkennung Mode 1 Modus 1 For cell Office applications ActiLume DALI Gen 2 has 3 dedicated Modes From these Modes Mode 1 is the basic and most applied mode Mode 1 is the default mode in which the ActiLume DALI Gen 2 is supplied The functioning of Mode 1 is described in the graph below Mode 1 Modus 1 100 Light level Licht intensitat 10 1273 17 Time 18 T9 Articial light level K nstliche Lichtintensitat cD Overcast insufficient natural light R Room occupied
6. d trunking plus 7 pol Tragschiene plus zusatzliche requested muss mindestens 9 pol sein extra wires by client 2 polige Kommunikationsleitung look page 7 siehe Seite 7 look page 7 siehe Seite 7 Mode 1 Occupancy sharing simple Mode 1 Occupancy sharing simple Mode 1 Occupancy sharing simple max 30 light units Lichttrager Slave Master z B 100 For change in mode Fur Wechsel des Modus Mode Steuerung ber den PC Software MultiOne 2 Controls Occupied Hierf r wird das Set ben tigt Bewegung LCN860 00 MultiOne Interface Be 7 USB2DALI L He Not occupied pA inactiv Handsender IRT9090 00 A l Keine Bewegung E D inaktiv for f r Vers 2 BALDUR Daylight Presence Control Tageslicht Prasenzregelung Master pres sensor slave Optional To slave master An Slave oder Master To slave master An Slave oder Master 9 wired trunking 9 pol Tragschiene Cable Kabel 0 5 1 0 mm Caution Polarity Achtung Polarit t beachten Mode 2 Modus 2 Mode 2 functions in principle in the same way as Mode 1 but with the difference that in Mode 2 the lights do not turn off after the hold time 15 minutes but are set to a background light level This is to avoid that in parts of an open plan office where no one is present people are not looking into a completely dark area Background level 15 minutes after the last movement has been detected T3 the lights
7. nge without notice Technische Anderungen vorbehalten ActiLume has 15 pre programmed application Modes in which a group of luminaires can be controlled according to the Table below Mode 1 Cell Office Window Corridor amp Decorative Mode 3 School Classroom amp Decorative Mode 5 Open plan Task Workspace amp Decorative Mode 7 Pilet Mode 9 Open plan Task middle Workspace amp mains switching Mode 11 Adjacent Cell Office Window Corridor amp Decorative Mode 13 Free for OEM copy of Mode 8 Mode 15 Free for OEM copy of Mode 11 Table 2 This chapter explains for which application which Mode is best suited or which lighting design requires which Mode Vers 1 BALDUR Daylight Presence Control Tageslicht Prasenzregelung Stand alone Mode Modus 1 Mode Modus 1 Mode Modus 1 max 30 light units Lichttrager max 30 light units Lichttrager max 30 light units Lichttrager ed I je u _ O Of For change in mode Fiir Wechsel des Modus Mode Steuerung ber den PC Software MultiOne 2 Controls Occupied Bewegung Hierf r wird das Set ben tigt LCN860 00 MultiOne Interface USB2DALI z K Not occupied Handsender IRT9090 00 EE Keine Bewegung AB Vers 2 BALDUR Daylight Presence Control Tageslicht Prasenzregelung Master pres sensor slave Option D Option a 9 wired trunking Ab Werk vorverdrahtet Tragschiene 7 wire
8. tion all luminaires are to be connected to the Window connection and commissioning of the luminaires is needed as described in chapter 6 10 Grouping of ballasts drivers When using the ActiLume DALI Gen 2 in Parallel Linking or BMS configuration there is also a possibility of having a third group of luminaires intended for a middle row row between window and corridor row lighting Vers 3 BALDUR Daylight Presence Control Tageslicht Prasenzregelung Multimaster Option D Option a 9 wired trunking Ab Werk vorverdrahtet Tragschiene 7 wired trunking plus 7 pol Tragschiene plus zusatzliche requested muss mindestens 9 pol sein extra wires by client 2 polige Kommunikationsleitung look page 10 siehe Seite 10 look page 10 siehe Seite 10 Mode 2 Occupancy sharing mode based Mode 2 Occupancy sharing mode based Mode 2 Occupancy sharing mode based max 30 light units Lichttrager max 30 light units Lichttr ger max 30 light units Lichttrager p For change in mode F r Wechsel des Modus Mode Steuerung ber den PC Software MultiOne 2 Controls Occupied Hierf r wird das Set ben tigt Bewegung LCN860 00 MultiOne Interface Pr Sy USB2DALI LE WE A Not occupied Handsender IRT9090 00 5 Keine Bewegung for f r Vers 3 BALDUR Daylight Presence Control Tageslicht Pr senzregelung Multimaster Optional LeU tan or oder To slave master An Slave oder Master