Refrigerants and the Refrigeration System

image

Contents

1. Figure 25 15 The core depressor on the refrigerant hose pushes in the Schrader valve core when the hose is connected not the same as the cores used in car tires The rubber used in tire valves is not compatible with refrigerants and would dis solve if used on a refrigeration system The stem must be depressed to force the valve seat open against spring pressure Refrigerant hoses with built in core depressors must be used with Schrader valves When a hose with a core depressor is connected to a Schrader valve the valve core is pushed in and the valve opens Figure 25 15 Ideally the seal in the gauge hose will seat just as the depressor is pushed in and very little refrigerant will escape Flow through a Schrader valve is limited be cause the core takes up most of the space in the center of the valve This leaves only a small passage for refrigerant to go through Figure 25 16 If a valve core leaks it can be replaced by using a core removal tool to unscrew it Some tools such as the one in Figure 25 17 allow this to be done while the system is under pressure All Schrader valves should have a leak proof cap on them when not in use The cap can prevent refrigerant loss even if the valve core does leak P Figure 25 16 This cutaway shows how a Schrader valve works b Figure 25 17 This tool can be used to change the core in a Schrader valve without losing the refrigerant in the system REVISED PAGES 4 aptara
2. M25 STANO893 00 SE C25 QXD 9 4 08 9 54 PM Page 7 Figure 25 18 The condensing unit is shipped with the valve closed to hold in the system refrigerant 25 5 SPLIT SYSTEM INSTALLATION VALVES Most new residential split systems come equipped with unit installation valves as shown previously in Figure 25 4 These valves are used to hold the refrigerant charge in the outdoor unit while it is shipped These valves have three ports the port to the unit the line port and the Schrader valve service port Even though they have three ports they do not behave like standard manual service valves No ports are closed in the back seat position the Schrader valve service port is always open to the line port regardless of the position of the valve These valves are used primarily for holding the system charge during shipping The systems are shipped with the valve run all the way down clockwise Figure 25 18 After connecting the refrigerant lines and indoor coil the system is evacuated through the service port The valve is turned counterclockwise to open it and allow the trapped refrigerant to flow through out the system Typically the valve is never used again because it does not control refrigerant flow to the service port SAFETY TIP Be careful when opening split system installation valves The only thing that keeps the plug in the valve is a small lock ring at the top of the valve Stop turning when the valve plug approaches the l
3. With these scales it is not necessary to refer to pressure temperature tables or curves to calculate pressure temperature rela tionships Figure 25 27 shows a compound gauge for an R 410A system Gauge Accuracy Gauges are classified by their percentage accuracy Class 1 gauges are accurate to 1 of the reading throughout their range This means that 100 psig can read anywhere between 99 and 101 Class 1 gauges are the most accurate mechanical p eee S bnili Ti pre alu 5 Pai a ty re A y il Y Th At 1 il EEE f F J i rA a a al amp p A up NA ee se eo ao i amp ub i Pa dul e F ts al i a qA a i i w Dia x ho gt A Lon g 4 XY lt n ty 3 j E a fs g TENE i so i F 1 ts id ee 5 i 3 he SK mf i Figure 25 27 Compound gauge for R 410a Courtesy of Ritchie Engineering Company Inc Yellow Jacket Products REVISED PAGES 4 aptara M25 STANO893 00 SE C25 QXD 9 4 08 9 54 PM Page 11 D UNIT 25 ACCESSING SEALED REFRIGERATION SYSTEMS 11 _ ww ial i a By u F 3 EE A ye in m Ari T d if t P T r ji Kra i mi i Ce mi 1 AITTA il wh hoe 7H TS g ea WT TT a ee gt up k or 4i fi fpr H eee to 5 af w Pra da 49 F Bea A i i 1 s A a yi a gt bP ea 4 luli ae Figure 25 28 Comparison of 21 in 31 in an
4. Operating refrigerant pressures may be observed on the service gauge manifold when hoses are connected to these ports and the valves are cracked open 25 3 MANUAL STEM SERVICE VALVES Manual service valves have three ports and two seats The three ports include a middle port which connects to the com pressor or system a line port which connects to the refriger P UNIT 25 ACCESSING SEALED REFRIGERATION SYSTEMS 3 Figure 25 5 Service valves b Courtesy Rheem Manufacturing ant line and a service port which is used for servicing the sys tem Figure 25 8 The refrigerant has two paths it can take through the valve It can flow between the middle port to the line port the middle port to the service port or between all ports There is not a closed position on these valves because one of the two exit ports will always be open Instead the terms back seated and front seated are used to describe the valve positions The valve is back seated when the stem is turned all the way out counterclockwise This position is called back seated because the valve is seated on the back port of the valve In this position the service port is closed but the middle port is open to the line port Figure 25 9 Service valves should al ways be placed in the back seated position before installing or removing gauges The valve is front seated when the stem is turned all the way in clockwise This position is called front seated because the valve is sea
5. The valves on a gauge manifold are used to control the flow of refrigerant from either side of the manifold to the center Figure 25 29 shows a cutaway view of a gauge manifold It is not necessary to open the valves on the gauge set to read pres sure The parts above and below each valve are intercon nected so the gauges will read pressure at all times when connected to the system The valves open or close the path from each side to the middle port When both valves are closed front seated the center or utility port is isolated Figure 25 30 a Slightly opening a valve is called cracking the valve Cracking open the low side valve connects the low side and center hoses Figure 25 30 b Some refrigerant can now flow from the center hose to the system Fully opening the low side valve opens the low side port to the center port for full flow or refrigerant or for evacuating the system Figure 25 30 c With the low side valve closed cracking open the high side valve will allow some refrigerant to flow from the high side to the center hose Figure 25 30 d Fully opening the high side valve opens the high side port to the center port to remove refrigerant from the system or for system evacuation Figure 25 30 e Opening both the low and high side valves opens both the low and high side ports to the center port This valve po sition is used for system evacuation Figure 25 30 f 25 9 REFRIGERATION HOSES The refrigeration hoses are an im
6. gauges made for use on R 134a and R 22 systems What personal protective equipment PPE should be worn when using gauge manifolds What can be done to reduce the risk of exposure to liquid re frigerant spray What is the difference between the two ends of a refrigeration hose What service valves are normally found on a commercial re frigeration system Why do split system heat pumps have three service valves Describe how to remove a gauge manifold set from a system and put most of the trapped refrigerant back into the system Describe how to purge a gauge manifold set using only the high side service valve Describe how to purge a gauge manifold set when connecting to Schrader valves What tool is used to turn the stems on manual stem service valves Describe how split system installation valves are used 29 Why are bolt on piercing valves not supposed to remain on systems permanently What is a process tube REVISED PAGES agg aptara
7. of the refrigerant spray Do not try to replace a hose or valve cap on a valve that has refrigerant escaping Liq uid R 410a is approximately 70 F at atmospheric pres sure It does not take long to get a nasty frostbite burn at that temperature 25 12 CONNECTING A GAUGE MANIFOLD SET TO SCHRADER VALVES Schrader valves automatically open when a hose with a core de pressor is connected to them The service technician normally does not have control over when the valve opens and closes When hoses are connected the valve opens when hoses are re moved the valve closes Frequently the valve will open before the seal is made and release refrigerant If the Schrader valve is on the liquid line the liquid that comes out will be extremely cold as it flashes off at atmospheric pressure Occasionally the hose will seat before the core is depressed and no pressure will be read Some manufacturers hoses have adjustable core de pressors that can help either of these situations Figure 25 34 One way of minimizing the risk to the technician is to in stall the gauges on the Schrader valves with the system off This reduces the pressures available at the high side valve when the hose is connected and reduces the chance of liquid refrigerant escaping Connecting with the system off also makes purging the gauges easier The gauges may be purged by opening the valves one at a time and releasing the air through the center hose Tools are available th
8. tube is pinched off and brazed shut The only way to gain access to these refrigeration sys tems is to use a valve that pierces a hole in the tubing It is bet ter to avoid entering a sealed system unless it is absolutely necessary because poking a hole in a sealed system can create problems The technician could literally be installing a leak Figure 25 40 Process tube on hermetic compressor 7 REVISED PAGES 4 aptara M25 STAN0893_ 00 SE C25 QXD 9 4 08 9 55 PM Page 17 D UNIT 25 ACCESSING SEALED REFRIGERATION SYSTEMS 17 SAFETY TIP You must wear eye protection and gloves any time you ac cess a refrigeration system Liquid refrigerant accidentally released from a pressurized system can be at an extremely low temperature which can cause blindness and skin burns Never position your face or head in a direct line with an access port as you are attaching or removing hoses 25 16 PIERCING VALVES One of the easiest devices available for sealed system access is the saddle piercing valve or tap a line These piercing valves are clamped to the tubing sealed by a bushing gasket and then they pierce the tube with a tapered needle Most contain some sort of shut off control The technician should keep in mind that these valves should be used to gain temporary access to a Figure 25 42 The needle pierces the copper tubing to gain hermetically sealed system for checking system operating pres AOS Ste Bie SEA E sures or for pressurizing
9. used to purge both sides of the manifold on systems whose low side is likely to be in a vacuum To purge from the high side only connect the lines as before but crack only the high side service valve Open the low side and high side manifold valves at the same time and loosen the hose REVISED PAGES 4 aptara M25 STAN0893 00 SE C25 QxXD 9 4 08 9 55 PM Page 14 aby My 14 SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS connection at the low side service valve This will purge every thing but the middle hose It can then be purged separately by loosening the middle hose at the plug connection This proce dure will work on any system with manual service valves but is only necessary when the low side is likely to be in a vacuum Some technicians purge the hoses and gauges from a separate refrigerant tank This has the advantage of not los ing any of the system charge It has the disadvantage of re quiring a drum of refrigerant even if you are just checking the pressures To use this method connect your gauges as before except connect the middle leg to the refrigerant drum Do not open the service valves Crack the tank valve and open both manifold valves Loosen the refrigerant hoses at both the suction and discharge service valves and purge each individually After both hoses are purged close the valve on the refrigerant cylinder and close the manifold valves 25 11 REMOVING A GAUGE MANIFOLD SET FROM MANUAL SERV
10. 3 in the dotted outline This movement will pull on the link which will turn Figure 25 20 Digital manifold gauge set Courtesy of Ritchie Engineering Company Inc Yellow Jacket Products The most advanced gauge manifolds use digital gauges rather than analog bourdon tube gauges Figure 25 20 These provide more accurate pressure measurement built in satu ration temperature charts for several refrigerants and system analysis All gauge manifold sets are test instruments and should be handled carefully Never drop or abuse the gauge manifold Keep ports or charging lines capped when not in use Never use any fluid other than clean oil and refrigerant SAFETY TIP There are two major groupings of gauge manifold sets One group is designed to be used with R 12 R 22 R 134A R 408 R 407 and R 404 The other groups of gauge manifold sets are designed to be used with R 410A only Do not use gauges designed for the lower pressured refrigerants on the very high pressure R 410A system Figure 25 21 Example of a bellows style refrigeration gauge Courtesy of REFCO Manufacturing Ltd 7 REVISED PAGES 4 aptara M25 STAN0893 00 SE C25 QXD 9 4 08 9 54 PM Page 9 D UNIT 25 ACCESSING SEALED REFRIGERATION SYSTEMS 9 Figure 25 24 High side pressure gauge for most common refrigerants except R 410a Courtesy of Yellow Jacket Division Ritchie Engineering Company the gear sector counterclockwise The pointe
11. 3_ 00 SE C25 QXD 9 4 08 9 55 PM Page 18 D 18 SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS Figure 25 44 Steps in installing a braze on piercing valve Braze on piercing valves can be used as both a means of gaining access to a sealed system as well as a permanent valve Braze on piercing valves are available such as the one in Figure 25 44 They function like a Schrader valve after the tubing is pierced Braze on piercing valves can be used for initial access and left on the system One safety concern with braze on piercing valves is that they are brazed on while the system is still under pressure Brazing on a system with pres sure still in it is generally considered unsafe If the tubing is overheated it can rupture allowing refrigerant and oil under pressure to blast out unexpectedly The oil spray can ignite and create a flame thrower effect Another tool for accessing sealed systems is a set of pierc ing pliers Figure 25 45 These can pierce the tubing and allow temporary access for system diagnosis and refrigerant recovery Since the pliers obviously must be removed they can only be used if the technician plans to recover the system refrigerant After piercing the system and recovering the refrigerant a Schrader valve can be installed Schrader valves are avail able for field installation in a variety of forms as seen in Figure 25 43 The core should be removed from the valve be fore brazing to avoid melting t
12. ICE VALVES The simplest way to remove the gauge set is to back seat both the service valves This should prevent any further escape of refrigerant into the gauges There is still a considerable amount of refrigerant in the gauges and hoses that needs to be carefully released Generally it is easier to release the refriger ant through the middle leg Disconnect the middle hose at the plug connection and direct it into an empty can or other safe area Slowly open each manifold valve one at a time until all the refrigerant has been released from the gauges There is a way to remove the gauges and avoid losing quite as much refrigerant Leave the unit running Instead of back seating both service valves back seat only the discharge service valve Crack open both manifold valves This will al low the high pressure gas in the discharge side of the mani fold to pass into the low side of the refrigeration system The pressure on the gauges will then be equal to the low side op erating pressure This is the lowest pressure any part of the system will ever have on it After the pressures in the gauge manifold have come down to the operating low side pressure back seat the suction service valve The pressure trapped in the gauges can now be bled off through the middle hose ex cept now the trapped pressure is significantly lower SAFETY TIP If an error or equipment failure Causes an unexpected release of refrigerant keep your hands and body out
13. M25 STAN0893 00 SE C25 QXD 9 4 08 9 54 PM Page 1 abs LY SECTION FOUR Refrigerants and the Refrigeration System UNIT 25 Accessing Sealed Refrigeration Systems OBJECTIVES After completing this unit you will be able to describe the different types of refrigeration service valves explain the operation of gauge manifold valves explain how to properly install and remove a gauge manifold set on manual service valves explain the operation of split system installation valves explain how to properly install and remove a gauge manifold set on Schrader valves describe how to gain access to systems without service valves 25 1 INTRODUCTION One of the last things a service technician should do when troubleshooting a system is attach a set of gauges to the sys tem Each time a sealed system is accessed there is a chance that some contaminants can be introduced to the system or refrigerant can be lost However there are times when a re frigeration system s operating conditions cannot be accurately assessed without accessing the system s refrigerant piping to determine the pressures Knowing the temperature differ ence across the coils the amperage and the airflow all give the technician vital information but sometimes without the system operating pressures a final determination of a prob lem cannot be accurately made It is important to attach and remove a gauge manifold set pro
14. XD 9 4 08 9 54 PM Page 5 BACK SEAT STEM ALL THE WAY OUT Figure 25 9 Two way service valve in the back seated position REFRIGERANT FLOW STEM IS ALL THE WAY IN Figure 25 10 Two way service valve in the front seated position BACKSEAT CRACKED Figure 25 11 When a two way service valve is cracked the valve is just off of the seat creating a small opening or crack AN a UNIT 25 ACCESSING SEALED REFRIGERATION SYSTEMS D Figure 25 12 Square stem service valve and valve wrench Figure 25 13 This valve stem has been ruined by a careless technician using the wrong tool of the valve stems round off easily when they are turned with adjustable wrenches or pliers Once a stem is rounded it cannot be turned with the correct wrench Figure 25 13 The cap for the valve stem and the cap for the service port should always be replaced after using manual service valves 25 4 SCHRADER VALVES Schrader valves provide a convenient method of checking system pressures or servicing the system where it is not eco nomical or convenient to use manual stem service valves The Schrader valve core shown in Figure 25 14 is a spring loaded device for positive seating The valve is like those used on au tomobile tires but the cores used in refrigeration valves are E REVISED PAGES 4 aptara M25 STANO0893 00 SE C25 QXD 9 4 08 9 54 PM Page 6 6 SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS a aE
15. a system under pressure Gauge manifolds are used to read system pres sure They consist of a compound gauge to read low side pressures a high pressure gauge to read high side pressure a manifold and valves to control re frigerant flow through the gauges and hoses to connect to the system Gauges are available in a high pressure range suitable for R 410a and in a lower pressure range suitable for everything else Positive shut off hoses or adapters help technicians control the flow of refrigerant in and out of the gauges especially when using Schrader valves The saturation temperature of common refrigerants can be read on the gauges by looking at the colored scales WORK ORDERS Service Ticket 2501 Customer Complaint Air Conditioner Freezes Up Equipment Packaged Terminal Air Conditioner PTAC Using R 22 Refrigerant A service technician for the Rest Easy Motel chain is asked to look at a PTAC in one of the rooms because it cools poorly and freezes over Like most PTACs this one has no service valves of any kind The technician knows that the two most common causes of air conditioning evapora aby My UNIT 25 ACCESSING SEALED REFRIGERATION SYSTEMS 19 tors freezing over are poor airflow and refrigerant under charge The technician decides to check the airflow first The air filter is missing and the evaporator is very dirty This is most likely causing reduced airflow over the evap orator After cleaning the coil
16. at give the technician more control over the valve With control over when the valves open and gt gt NNN M x N uty gt gt pe j Cw yj 7 NIN ENUN YY daddadddddad ie Figure 25 34 Adjustable core depressor Courtesy of Ritchie Engineering Company Inc Yellow Jacket Products a I7 REVISED PAGES agg aptara M25 STAN0893 00 SE C25 QXD 9 4 08 9 55 PM Page 15 D UNIT 25 ACCESSING SEALED REFRIGERATION SYSTEMS 15 Figure 25 35 Thumbscrew core depressor valve Courtesy of Ritchie Engineering Company Inc Yellow Jacket Products Figure 25 36 Positive shut off adapters make connecting to Schrader valves easier close gauges may be safely connected to Schrader valves with the unit in operation A valve core removal tool like the one shown in Figure 25 17 allows gauges to be connected before opening the valve Then the tool is used to remove the core opening the system to the gauges This also has the advantage of improving flow through the valve This type of core re moval tool can be used to change a Schrader valve core with out recovering the system refrigerant A simpler tool the thumbscrew core depressor also al lows the connection of gauges before the valve is opened Figure 25 35 Turning in the thumbscrew depresses the valve core and opens the valve This process is revers
17. ated on the compressor where the suction line attaches Check to make sure the service valve stem is back seated This will ensure that no pressure is currently applied to the gauge port of the serv ice valve Remove the gauge port flare cap and attach the hose connected to the compound side of your gauges to the gauge port Locate the discharge service valve It is also located on the compressor but it is the valve connected to the smaller discharge line leaving the compressor Check to be sure the valve stem is back seated Remove the gauge port cap and at tach the hose connected to the high side of the manifold to the gauge access port on the discharge service valve The gauge manifolds and connecting lines should be purged to avoid system contamination from air and mois ture To purge a unit that does not operate in a vacuum crack both the suction and discharge service valves Open the gauge manifold valves one at a time and bleed refrigerant out the middle line until all the air is out This usually just takes a few seconds This will purge the gauge manifold and the con necting lines Many technicians simply loosen the hoses at the manifold connections and purge each hose However this does not purge the manifold or middle line SAFETY TIP Contact with the gases being purged should be avoided Oil and liquid refrigerant will sometimes escape during the purging process Liquid refrigerant can cause frostbite The high side is
18. d 4 in mechanical gauges Courtesy of Ritchie Engineering Company Inc Yellow Jacket Products gauges used in refrigeration Class 1 6 and class 2 gauges are accurate to 1 6 and 2 respectively Class 2 3 2 gauges are accurate to 2 for the first third of their scale 3 for the middle third and 2 for the final third of their scale Class 3 2 3 gauges are the least accurate gauges used in refrigeration Gauge Size Gauges are available in different sizes The most common sizes are 214 3 4 and 4 in diameter Figure 25 28 shows all three common sizes of gauges Larger gauges are easier to read than smaller gauges Their larger circumference allows for more ac curate increments making them more accurate as well This is especially important for gauges that are used over a wider range of pressure like gauges designed for use with R 410a SERVICE TIP Refrigeration gauges have a small adjustment screw that allows the gauge to be zeroed The gauge is ad justed to zero with the hoses open to atmospheric pres sure However it is possible for a gauge to zero out but not read other pressures accurately From time to time the technician should attach the gauges to a new cylin der of refrigerant at a Known temperature and compare the pressure reading to the temperature pressure chart so that the gauge can be checked for accuracy Gauges that are zeroed and are still inaccurate should be replaced 25 8 GAUGE MANIFOLD VALVES
19. e the Schrader valve in them reads line pressure regardless of the valve position SAFETY TIP A few residential split systems use manual stem valves as shown in Figure 25 3 a The gauge connec tion on these valves is not a Schrader valve These valves must be opened to read pressure More impor tantly they must be closed before removing the gauges Figure 25 1 Manual two way service valve dh L7 REVISED PAGES 4 aptara M25 STANO893 00 SE C25 QXD 9 4 08 9 54 PM Page 3 oe TI a a x n F j i n a Vie I 4 eS i 4 di a J Hihii A i R410A REFRIGERANT j WITH POE 3MA OIL EQUIPMENT COMPATIBLE WITH E Figure 25 4 Residential split system installation valves On heat pump systems both lines are on the high side during the heating cycle To allow technicians to read low side pressures in heat heat pump systems use a third valve which is always connected to the low side of the system regardless of the cycle Figure 25 6 Residential packaged units typically have a low side and high side Schrader valve mounted on the outside of the equipment Figure 25 7 Commercial refrigeration systems typically have three manual stem service valves A suction service valve and a dis charge service valve are located on the compressor A service valve called the king valve is mounted on the outlet of the re ceiver These service valves are equipped with a gauge service port
20. ed to remove the gauges The thumbscrew is turned out allowing the valve to close After the valve is closed the gauges are removed 25 13 REMOVING A GAUGE Figure 25 37 The hoses at the top of the picture have a standard MANIFOLD SET FROM Schrader core depressors The hoses on the bottom of the SCHRADER VALVES picture have automatic check valves built in that keep the refrigerant in the hose from coming back out when the hose is When a hose is disconnected from a Schrader valve the re removed frigerant that is trapped in the hose and gauges comes back out This can be a surprising amount of refrigerant when the high side is connected to the liquid line Positive shut off fold valves to allow the trapped high pressure refrigerant into hoses can drastically reduce the amount of refrigerant re the low side Last disconnect the low side with the unit still op leased when the gauges are disconnected Positive shut off erating The remaining amount of refrigerant in the hoses can devices include check valves on the end of refrigerant hoses be safely and legally vented Note that the gauges must be manually operated ball valves on the ends of hoses and purged when they are connected or part of what is going back adapters that can be used with standard hoses Available into the system will be air and contaminants adapters include check valves mechanisms like the quick Three simple steps will reduce your exposure to refriger couplings u
21. for leak testing The piercing valve shown in Figure 25 41 allows quick access to system pressures is to install the piercing valve on a process tube After the refrig to immediately start diagnosing the refrigeration problem erant is recovered the process tube can be cut and a permanent valve brazed onto the process tube Figure 25 43 shows Schrader valves made for field application SAFETY TIP Before brazing a Schrader valve onto a existing refrigerant line all of the refrigerant in the system must be recovered Any refrigerant that is allowed to enter the torch flame will produce a noxious gas Breathing this gas can be dangerous and could even cause lung damage Remove the Schrader core before brazing to keep it from becoming damaged Bolt on piercing valves are bolted on the line then the pierc ing needle is run down to pierce the copper tubing Figure 25 42 Refrigerant flows through the hole pierced by the needle to the service port on the valve Bolt on piercing valves should be removed once the source of the sealed system malfunction has been located The only way to do this is to recover the refrigerant from the system through the piecing valve After the refrigerant has been recov ered a permanent valve may be brazed on One way to do this SSS 60 Figure 25 43 a Pigtail type Schrader valve b Schrader valve Figure 25 41 Bolt on piercing valve replacement cores 7 REVISED PAGES 4 aptara M25 STAN089
22. he plastic seals Figure 25 45 These piercing pliers can be used to gain access to sealed systems REVISED PAGES agg aptara M25 STANO893 00 SE C25 QXD 9 4 08 9 55 PM Page 19 UNIT 25 SUMMARY Service valves are used to gain access to the refrig eration system Type II and Type III systems all have service valves installed at the factory Type I systems have process tubes Commercial refrigeration sys tems typically use manual stem service valves on the suction and discharge sides of the compressor and on the liquid receiver The normal operating position of a manual stem service valve is back seated In the back seated position the service port is closed System pressures can be read in the back seat cracked position In the back seat cracked position the valve is turned one half turn off of the back seated position Schrader valves are similar to the valves on car tires They are found on most residen tial air conditioning systems Schrader valves auto matically open when a hose with a core depressor is connected and close when the close is removed Type I systems must be accessed using piercing valves Bolt on piercing valves should be used for system diagnosis and refrigerant recovery but should not be left on the system Braze on piercing valves can be used for access and may be left on the system Care should be taken when installing a braze on piercing valve because of the inherent dan ger of brazing on
23. icket 2504 Job Check Oil for Acidity on Semi Hermetic Com pressor Equipment Commercial Refrigeration System with Semi Hermetic Compressor A 1 Refrigeration changed the compressor is a commer cial refrigeration system last week A technician is sent to collect a small oil sample and perform an oil acid test on the oil to see if the oil is contaminated The technician does not want to recover all the system refrigerant but knows that the refrigerant pressure must be taken off of the compressor before opening the oil plug so the tech nician decides to isolate the compressor using the suction and discharge service valves First the system is operated long enough to warm up the crankcase and boil out any residual refrigerant from the oil The system is turned off and locked out Then gauges are installed on the com pressor and both the service valves are front seated The compressor is now isolated from the rest of the system A recovery system is used to recover the small amount of refrigerant in the compressor The crankcase plug is re moved a small oil sample taken the plug replaced and the oil is tested The oil is clean so the technician pulls a 500 micron vacuum on the compressor through the suc tion and discharge service valves The service valves are back seated and the system is put back in operation UNIT 25 REVIEW QUESTIONS 1 What do technicians use the gauge manifold for 2 What are the colors used on a gauge ma
24. m and from 0 to 120 psig 7 REVISED PAGES 4 aptara M25 STANO893 00 SE _C25 QXD 9 4 08 9 54 PM Page 10 10 Figure 25 25 High side pressure gauge for R 410a Courtesy of Ritchie Engineering Company Inc Yellow Jacket Products pressure On a typical compound gauge each mark on the vacuum scale represents 2 in Hg vacuum and each mark on the pressure scale represents 1 psig pressure It is common for the standing pressure on the low side of a system to exceed the normal range of the compound gauge Figure 25 26 Compound gauge for most common refrigerants except R 410a Courtesy of Yellow Jacket Division Ritchie Engineering Company P SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS The retard range protects the gauges from damage when a pressure above their normal range of operation is connected to them Gauges for R 134a and R 22 typically have a retard range of up to 350 psig Compound gauges made for R 410a have a higher pressure range because of the higher operating pressures of R 410a systems R 410a gauges can typically read pressures up to 350 psig and have a retard range up to 500 psig On an R 410a compound gauge each mark on the pressure scale represents 5 psig pressure Each mark on the vacuum scale represents 5 in Hg vacuum Like the high pressure gauge the compound gauge also has scales calibrated to read saturation temperatures of vari ous refrigerants such as R 134a R 22 and R 410A
25. mes only hold a few ounces and putting gauges on them can remove enough refrigerant to make the system undercharged It is definitely not a good idea to install zane 25 14 READING REFRIGERANT piercing valves on small sealed systems just to perform a rou SATURATION TEMPERATURES tine check However when the refrigeration system must be accessed a piercing valve or piercing pliers are required Refrigeration gauges not only read system pressure they also show the refrigerant saturation temperature of common refrig erants The saturation temperature of a refrigerant may be de termined by observing the colored scale for that particular refrigerant The gauge in Figure 25 38 is showing 150 psig for an R 410A system The needle also points toward its corresponding saturation temperature 45 F The high pressure gauge shown in Figure 25 39 indicates a pressure of 365 psig and a correspon ding temperature for R 410A of 110 F 25 15 ACCESSING SEALED SYSTEMS Most small appliances like refrigerators or window units do not have any valves installed at the factory Instead the systems are evacuated and charged at the factory through process tubes A process tube or process stub is a copper tube connected to the system for the sole purpose of evacuating and charging the unit at the factory The process tubes can be on the compressor or on one of the system lines Figure 25 40 After the system is evacu ated and charged at the factory the process
26. ngs to seal the system Be sure these O rings are in place be fore installing the cap to ensure a proper seal Caps that have a metal to metal seal must be tightened one eighth turn with a wrench after they have been finger tightened mee EE PU aL Factory installed service valves may be a manually oper ated stem shut off valve as in Figure 25 1 or a Schrader type valve Schrader valves are spring loaded valves similar to the valves used on car tires They have a core that threads down into them Figure 25 2 Refrigerant is allowed to flow into and out of the valve when the core is depressed To prevent leaks Schrader valves should always have their valve caps on when not in use Figure 25 3 Residential split system equipment service valves are usually located on the suction line and liquid line Figure 25 4 The valve on the suction line is used to read the low side sys tem pressure and the valve on the liquid line is used to read Figure 25 3 Shrader valves should always have their cap on the high side system pressure Most air conditioning systems when not in use use front seating split system shut off valves as shown in Figure 25 5 b These valves are used to hold the system re frigerant in during shipping The gauges connect to the Schrader valve that is built into them These valves are nor mally opened when the unit is installed and then seldom used after that It is not necessary to turn them to read pres sure becaus
27. nifold set and what do they indicate 3 What is the term for slightly opening a valve 4 List three cautions when handling a gauge manifold set 5 Why is the low side gauge called a compound gauge aby My SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS 6 How does a Bourdon tube work in a gauge 7 What must always be put on a Schrader valve port when not in 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 30 db I7 use Why is it not always a good idea to install a gauge set and check system pressure What type of units are required to have service valves 10 11 What type of units are only required to have process stubs Explain the difference between the back seated position and the front seated position on manual stem service valves When using manual stem service valves describe how to posi tion both the service valves and the gauge manifold valves when reading system pressures Why are positive shut off hoses helpful when using Schrader valves What is the purpose of the saddle or piercing valve How can refrigeration gauges show the saturation temperature of the refrigerant in the system What is the retard range on compound gauges for What is the normal pressure range for the compound and high pressure gauges made for use on R 410a systems What is the normal pressure range for the compound and high pressure
28. ock ring The valve does not need to be tightened in the counterclockwise or up position Overtightening the valve can cause the lock ring to pop out and the plug will fly out under sys tem pressure with all the system refrigerant behind it 25 6 GAUGE MANIFOLD SET Technicians use the gauge manifold to diagnose trouble in re frigeration systems Gauges allow the operator to watch both gauges simultaneously during evacuation or charging opera co UNIT 25 ACCESSING SEALED REFRIGERATION SYSTEMS 7 tions and save time on almost any work that must be done on the system The most common gauge manifold test sets contains two shut off valves three external connections and two pressure gauges The gauges and the flexible hoses that connect to the manifold to connect it to the system are color coded blue is the low side of the system red is the high side The left hand gauge is called a compound or suction pressure gauge The right hand gauge is called the high pres sure or discharge pressure gauge The hoses have inside diameter and are designed to seal on a inch male flare end Typically one end is straight and connects to the manifold and the other end is angled to allow easier connection to service valves More advanced gauge manifolds are available that have four hose connections and four shut off valves Figure 25 19 Besides the low side and high side connections there are two center connections each with its own shut off
29. perly Understanding how to properly manipulate sys tem access valves and install gauge manifolds is vital to the personal safety of the service technician Improper technique can damage the system or injure the technician Proper tech niques should always be practiced so that they become a habit performed the same way each time SAFETY TIP The proper personal protective equipment PPE for in Stalling refrigeration gauges and manipulating valves includes safety glasses and gloves When liquid refrig erant escapes into the atmosphere it boils at ex tremely cold temperatures Liquid refrigerant sprayed in the eyes can cause blindness sprayed on the skin can cause frostbite a I7 REVISED PAGES ag aptara M25 STAN0893 00 SE C25 QXD 9 4 08 9 54 PM Page 2 aby My 2 SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS 25 2 FACTORY INSTALLED SERVICE VALVES With the implementation of the Clean Air Act all manufac turers are required to install factory installed service valves on Type II and Type III equipment Type I equipment is only required to have a process stub Commercial refrigeration and air conditioning systems have had factory installed serv ice valves for years SERVICE TIP You must put service valve caps back on all access ports This is an EPA refrigerant management require ment Failure to do so is a violation of EPA rules and reg ulations Many service access valve caps have O ri
30. portant part of a gauge manifold set They are what actually connects the gauges to the system Charging and vacuum hoses are available in sizes REVISED PAGES ag aptara 9 4 08 9 54 PM Page 12 My aby M25 STANO893 00 SE C25 QXD SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS 12 Figure 25 29 Cutaway of a pase HIGH SIDE gauge manifold L GAUGE LOW SIDE ALNE VALVE HANDLE VALVE HIGH SIDE m _ e T Le A Yl f 2A gy amp HOSE CONNECTED HOSE CONNECTED TAEUN RIDE B TO HIGH SIDE gt of 1 h 1h and inside diameter The most common size is Refrigeration hoses are available in many colors Figure 25 31 Many gauge sets use hoses that are color coded to the gauges red for the high side blue for the low side and Figure 25 30 Gauge manifold valve positions gt HOSE CONNECTED TO REFRIGERANT CYLINDER VACUUM PUMP OR RECOVERY MACHINE yellow for the center hose Many four port gauge manifolds have a 7 port for vacuum and come equipped with a 7 hose Typical charging hoses have a straight end that connects to the manifold and an angled end that connects to the agg aptara REVISED PAGES a I7 M25 STAN0893 00 SE C25 QXD 9 4 08 9 55 PM Page 13 D UNIT 25 ACCESSING SEALED REFRIGERATION SYSTEMS 13 E Pe lh a k Figure 25 31 Refrigeration hoses are available in many colors Courtes
31. r shaft will move Figure 25 22 Bourdon tube clockwise to move the needle On a decrease in pressure the Bourdon tube moves clockwise toward its original position and the pointer moves counterclockwise to indicate a de crease in pressure Pressure Gauges The high pressure gauge has a single continuous scale Gauge sets made for refrigerants such as R 134a and R 22 are usually calibrated marked off to read O to 500 psi Figure 25 24 shows a high pressure gauge The scale is usu ally marked in 5 lb increments The black scale is the pres sure scale and the colored scales indicate the saturation temperature of different refrigerants at the indicated pres sure For example if the gauge pointer indicated 200 psi pressure for R 22 the saturation temperature of the refrig erant would be approximately 101 F Pressure gauges made for R 410a have a higher pressure range because of the higher pressures of R 410 systems R 410a pressure gauges can typically read pressures up to 800 psig On an R 410a pressure gauge each mark on the pressure scale represents 10 psig pressure Figure 25 25 shows a high pressure gauge for R410a systems Compound Gauges The low side gauge is a compound gauge that measures both pressure and vacuum Figure 25 26 Gauge sets made for re Figure 25 23 The dashed line shows how the Bourdon tube frigerants such as R 134a and R 22 are usually calibrated responds to a pressure increase from 0 to 30 in of mercury vacuu
32. re brazed in a new compressor and liquid line filter are in stalled the system is evacuated to 500 microns and a charge is weighed in Service Ticket 2503 Customer Complaint Unit Does Not Cool Ade quately Equipment Commercial Refrigeration Unit on Walk in Cooler with R 134a A technician is called to look at a walk in cooler whose capacity has noticeably declined A check of the system pressures at the suction and discharge service valves re veals that the suction pressure is very low and the high side pressure is just slightly low Both the system super heat and subcooling are high The technician looks for system restrictions and finds a sweating liquid line filter drier The technician determines that the filter drier is re stricted and decides to change the filter drier but does not want to recover all of the refrigerant Instead the king valve is front seated and the system is operated until the a I7 REVISED PAGES 4 aptara M25 STANO893 00 SE C25 QXD 9 4 08 9 55 PM Page 20 20 filter drier no longer sweats and the pressure on the line leaving the king valve is O psig The technician turns off the unit and waits to make sure the pressure does not go above 0 psig The old filter drier is replaced with a new fil ter drier the system is evacuated from the suction serv ice and king valves to 500 microns the king valve is back seated and the system is returned to service Service T
33. sed on air hoses and ball valves Figure 25 36 ant spray if positive shut off hoses or adapters are not used The check valves built into the end of a hose keep refrig First wear gloves and safety glasses It is always a good idea to erant from flowing backward out of the hose Figure 25 37 wear gloves and safety glasses when handling refrigerant but Refrigerant will be trapped in the hoses after the gauges have it is especially important when using Schrader valves been disconnected using a positive shut off valve Most of the Disconnect the low side with the system operating because trapped refrigerant can be put back in the system if the the low side pressure is lower with the unit on Turn the sys proper removal procedure is followed tem off and let the system sit for several minutes before dis Using a positive shut off hose disconnect the high side connecting the high side because the high side pressure is with the unit still operating Now crack both the gauge mani lower with the unit off 7 REVISED PAGES 4 aptara M25 STAN0893 00 SE _C25 QXD 9 4 08 9 55 PM Page 16 AN a 16 SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS Flutter lt s 70 uo Fluttei R41 lt 0 J 7 FA Li a F mis Figure 25 39 This gauge is reading 365 psig with a saturation temperature of 110 F for R 410a Figure 25 38 This gauge is reading 150 psig with a saturation temperature of 45 F for R 410a Small systems someti
34. ted on the front port of the valve In this position the line port is closed but the middle port is open to the service port Figure 25 10 The front seat position can be used to isolate refrigeration system com ponents REVISED PAGES 4 aptara M25 STAN0893 00 SE C25 QXD 9 4 08 9 54 PM Page 4 D 4 SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS Figure 25 6 The arrow points to the port that is always on the low side of the system regardless of the operating cycle Figure 25 7 High side and low side Schrader valves on a packaged unit If the stem is positioned anywhere in between the back SAFETY TIP seat and front seat positions all three ports will be open l l l Turning the valve one half turn off of a fully seated posi Be sure that internal pressure in the compressor is re tion is called cracking the valve When checking pressures doven Dy MOGaveny ane VEON OOE DANO ai the valves are usually in the back seat cracked position tempting to remove an isolated compressor from the Figure 25 11 system Pressure remains in the compressor even after The stems on manual service valves should only be the service valves are front seated i turned with a valve stem wrench Figure 25 12 The corners Figure 25 8 Two way system GASKET SERVICE PORT service valve E SQUARE HEAD PACKING REFRIGERANT LINE P CONNECTION 7 REVISED PAGES 4 aptara M25 STAN0893 00 SE _C25 Q
35. the unit airflow is notice ably improved and the evaporator no longer freezes The technician elects not to install a piercing valve and keep the system sealed Instead the system operation is checked by checking the system amp draw airflow and temperature drop across the evaporator coil Service Ticket 2502 Customer Complaint Unit Operates But Does Not Cool Equipment Packaged Terminal Air Conditioner PTAC Using R 22 Refrigerant A service technician for the Rest Easy Motel chain is asked to look a PTAC in one of the rooms because it operates but does not cool Like most PTACs this one has no service valves of any kind The system operation is checked by checking the system amp draw airflow and temperature drop across the evaporator coil The amp draw of the compressor is less than half of the normal RLA rating The coil appears clean the airflow is normal but the supply air is the same temperature as the return air no cooling is taking place The technician decides to install a bolt on piercing valve on the low side process tube The reading on the low side with the compressor operating is 150 psig The technician believes the compressor is bad but de cides to install a piercing valve on the high side process tube to be certain The pressure on the high side with the compressor operating is also 150 psig The compressor is condemned the system refrigerant is recovered the bolt on piercing valves are removed Schrader valves a
36. valve Typically one of the middle connections allows the use of a 74 inch hose for faster evacuation Figure 25 19 Four valve manifold gauge set Courtesy Imperial REVISED PAGES agg aptara M25 STAN0893 00 SE C25 QXD 9 4 08 9 54 PM Page 8 D 8 SECTION 4 RESIDENTIAL AND LIGHT COMMERCIAL SYSTEMS 25 7 REFRIGERATION GAUGES Mechanical gauges require a physical device to translate pressure changes into movement that can be used to move a dial Three types of devices are used in mechanical gauges diaphragm bellows and Bourdon tube Diaphragm gauges are generally used for lower pressures within a lim ited range and are usually not used in refrigeration Bellows gauges are used in refrigeration gauges but they are not sel as common as Bourdon tube gauges The bellows expand with an increase in pressure and contract with a decrease in pressure Figure 25 21 shows a bellows gauge used in refrigeration Most refrigeration gauges use a Bourdon tube as the op erating element The Bourdon tube is a flattened metal tube which is sealed at one end curved and soldered to the gauge fitting at the other end Figure 25 22 Figure 25 23 illustrates how a Bourdon tube operates The blue shaded section shows the tube at rest at atmospheric pressure A rise in pressure in side the tube tends to make the Bourdon tube mechanism straighten The position the Bourdon tube will move to when pressure is applied is shown in Figure 25 2
37. y of Ritchie Engineering Company Inc Yellow Jacket Products Figure 25 32 The angled end contains a core depressor for Schrader valves system The angled end contains the core depressor for Schrader valves Figure 25 32 Refrigeration hoses are not simply a single tube they are built in layers Figure 25 33 illustrates the construction of a refrigeration hose The rubber seen on the outside simply provides physical protection for the inner layers The woven fabric layer just under the outer rubber layer provides strength Some refrigeration hoses have two more inner layers while others have only a single inner layer The innermost layer actually contains the refriger ant Hoses with two inner layers have extra permeation protection Hoses designed for use with refrigerants which operate at lower pressures than R 410a typically have a working pressure of 500 psig and a minimum burst pressure of 2 500 psig Hoses designed for use with R 410a typically have a working pressure of 800 psig and a minimum burst pressure of 4 000 psig COVER FOR PROTECTION BRAID FOR RUBBER FOR STRENGTH PERMEATION Pa PROTECTION NYLON D PERMEATION AND MOISTURE J BARRIER UL RECOGNIZED ASSEMBLY Figure 25 33 Diagram of refrigeration hose construction Courtesy of Ritchie Engineering Company Inc Yellow Jacket Products 25 10 CONNECTING A GAUGE MANIFOLD SET ON MANUAL SERVICE VALVES Locate the suction service valve It is usually loc