Home
        vacon nx commissioning and maintenance manual
         Contents
1.                         Figure 3 3 6 Example 3    Dew Point chart for ambient temperatures between  10   50   1013 mbar    15  C 20  C 25  C 30  C 35  C 40  C 45  C    Relative humidity       10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54  Primary circuit water temperature    C       Chart 3 3  1 Dew point chart          No condensation is allowed inside the main drive  If condensation occurs the    warranty is no longer valid   WARNING             Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   37       Note that some Vacon liquid cooled drives have a maximum ambient temperature of 40  C that would  make a scenario with an ambient temperature over 40  C impossible  In a case like this it is  recommended to add a water air condenser with built in fan to reduce the temperature inside the  main drive cubicle  If a water air condenser is used to regulate the temperature inside the main  drive cubicle the drive must be made airtight  e g  IP54      A last resort is to install an air conditioner that can regulate both the humidity and the temperature  at the installation  electrical room   This is a safe but usually a very expensive option     If the temperature of the liquid in the secondary circuit is lower than the room temperature  and the  relative humidity is high  condensation might occur on the secondary circuit piping and the plate  heat exchanger inside the HX unit  This is not dangerous  however nor is it desirable  I
2.        When performing a pressure test on the HX unit  generally acknowl edged safety  standards  EU directives and national regulations must also be followed  Use  safety goggles                 DANGER       Unless national regulations say otherwise the pressure during the pressure test should be 1 5 times  the maximum work pressure     The maximum pressures are as follows    Primary circuit AISI 304 piping    6 bar  therefore the test pressure is 9 bar   Secondary circuit AISI 304 piping    10 bar  therefore the maximum test pressure is 15 bar   Option  Secondary circuit AISI 304 piping    16 bar  therefore the maximum test pressure is 24 bar  Primary circuit PVC  C piping    6 bar  therefore the test pressure is 9 bar   Secondary circuit PVC  C piping    10 bar  therefore the maximum test pressure is 15 bar    If the customer only uses a PN6 piping system on the secondary circuit  the pressure test can be  done with pressurized air to 9 bar        If the secondary circuit is pressure tested higher than 10 bar the test must be  done with water  Compressed air should not be used at pressures over 10 bar  due to the risk of high  speed debris at a compressed pipe failure        DANGER          The pressures mentioned here are only valid for the HX unit  The customer  and or end user are responsible for all other piping made to either the primary  or secondary circuit  If the customer and or end  user make any changes to the  WARNING piping on the HX unit they are responsible 
3.   31       To change the parameters of the Unifl ow SW6000  Figure 3 3 1   the device has to  be in setting mode  More information regarding the FTSA11  Uniflow SW6000   flow switch can be found in the Component Specifications and Maintenance  Instructions at the end of the Commissioning and Maintenance folder that is  supplied with the HX unit  Figure 3 3 2 shows the hierarchy of the parameters  found in the FTSA11 flow switch  An example on how to edit the flow switch point    is found in table 3 3  2   high range   HI   low range    switching point  temperature  SPt        Figure 3 3 1           measurement                   actual switching  point              OFF    standard        normally closed   nic         normally open    normall closed       a          normally open   n     standard           hysteresis   HuS        End                   Figure 3 3 2 FTSA11 parameter hierarchy    24 hour support 4358  0 40 837 1150   Email  vacon vacon com          32   vacon COMMI SSI ONI NG       Table 3 3  2 shows an example on how to set the flow switching point to 68     Description   Push buttons   Display    1  Change to setting mode 2x  2 14   gt   A     SO     switching output     4  Display hundred digit    050     hundred digit is  flashing      actual flow     Table 3 3  2 Setting flow switching point       The settings on the FTSA11 should be the following     Measuring range  HI  high range 30 to 300 cm s    Hysteresis  h05  5  hysteresis    Switching order  n c  nor
4.   More  information can be found in chapter 3 3 7  Temperature alarm settings     P2 10 9 is a FTSA11 high temperature  alarm limit  The default setting for this is set at 28  C  More  information can be found in chapter 3 3 7  Temperature alarm settings     P2 10 10 is a FTSA11 high temperature  trip limit  The default setting for this is set at 35  C  This  means that the drive will shut down   cooling OK  signal going to the main drives will be  disconnected  when the temperature is over 35  C  The HXM unit will stay online  pump running    More information can be found in chapter 3 3 7  Temperature alarm settings     P2 10 11 the default setting is 169    hours     If the setting is between 1 168  hour  the system will try  to change the pumps according to the time setting  This is to be used ONLY when operating the HX   series model HXM120  double pumps   If this value is set to Oh  the pump change will occur every 30  seconds  This is useful for testing and commissioning purposes because all shutoffs are also  deactivated during these 30 seconds  The value  169  will deactivate the attempt to change the pump  and should be used when operating the HXL040 or HXL120     P2 10 12 is the parameter that sets the delay time between when the parameters are exceeded and  the activation of a warning shutdown  The value can be varied from 1 to 5 seconds  The default  setting is 5 seconds  During commissioning and maintenance the value is to be set to 5 seconds     P2 11 1 8 are pa
5.  2 2 3   which removes air from the primary circuit  without letting the water out     The centrifugal pumps  PU11 12  red parts in Figure 2 2 3   circulate the primary circuit liquid  The pumps are run in  sequence  never at the same time  The pumps are as default  setup making a sequence switch every 168 hours  The flow can  be adjusted to match the need of the connected drives by  changing the frequency of the pump motor  The main function of  the pump is to deliver enough flow for an optimal liquid to liquid  heat transfer of the Vacon NX Liquid Cooled series  Other  significant parts are the safety valve  V120  orange  and the  instruments  flow switch  FTSA11  light blue   pressure  transmitter  PT11  brown  and the pressure gauge  P111  yellow    The valves used for maintenance such as filling or de airing are described in chapter 3 1 6  Adding  liquid and de airing        Figure 2 2 3    2 2 2 Secondary circuit components and function    The secondary circuit transports the heat load from the  primary circuit to a customer specific object  Through the  plate heat exchanger  the heat load from the drives is  transferred to the secondary circuit  The HX unit does not have  a control supervision system for the secondary circuit  therefore the customer should use a suitable option to  control supervise the secondary circuit s flow and temperature  e g  flow meter and temperature sensor     A 3 way valve V130  black part in Figure 2 2 4  placed in the  secondary circuit co
6.  A change of 1 C   minute  should not be exceeded    Check the temperature by comparing the  FTSA11 temperature with the secondary  circuit temperature indicator TI21  The  temperature of FTSA11 should be higher  than the TI21 temperature  Replace the  FTSA11 if necessary    If a TI21 is not installed then check the  primary circuit temperature  using a  portable measuring device  and compare it  to FTSA11  To get an accurate value the  portable temperature gauge must be  connected close to the FTSA11  Replace  the FTSA11 if necessary        Tel  4358  0 201 2121   Fax 4358  0 201 212 205    TROUBLESHOOTI NG vacon   53       5 1 3 Low pressure alarm    If the low pressure alarm is active  acc  to panel below  the HX  unit is still online and the    Cooling  OK    signal to the main drive is connected  The yellow and green indicator lights on the electrical box  door are also active  Check the following issues to solve why the alarm has been activated     F1  l Oter    82 InletPressLow    A 11397165    Figure 5 1 4  Low pressure alarm on the NXP panel       Malfunction Reasons for malfunction   Correction measures   Leak in the primary   e Loose connection  e Tighten the connection until the leak stops    circuit outside the Add liquid to the primary circuit until the   HX  unit  correct pre pressure is reached  Follow  the instructions in chapter 3 1 6  Adding  liquid and de airing    e Faulty connection  e Replace the broken parts  Then add liquid  to the primary circuit unt
7.  control unit panel will show the text  A83 OverTempA      And both the red and the yellow indicators on the electrical box will be active     Example  over temperature fault  The primary circuit temperature set point is set to 35 degrees  then the over temperature fault  parameter  P2 10 10  should be set to 45 degrees     The HX unit over temperature fault is designed to work as protection in case of a sudden change in  the primary circuit for example if the flow in the secondary circuit for some reason is stopped     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       38   vacon COMMI SSI ONI NG       The low temperature alarm  e Activates a function that will activate the yellow indicator light on the HX unit electrical box   The parameter is set to 3 C lower than the primary circuit temperature set point  The default  setting of the high temperature shutoff is 22 C   e Whenthis alarm is activated the HX  control unit panel will show the text  A86 LowTemp      Example  low temperature alarm  The primary circuit temperature set point is set to 35 degrees  and then the low temperature alarm  should be set to 32 degrees     Example  all temperature values  A primary circuit temperature set point of 35  C has been calculated for a specific installation  The  temperature parameters should be adjusted the following way     e The primary circuit temperature set point  parameter P 3 5  is set to 35  C   e Newover temperature alarm value  parameter 2 10 9    38  C  
8.  e New low temperature alarm value  parameter 2 10 8      32  C   e Newover temperature fault value  parameter 2 10 10   gt  45  C  The parameters are modified by using the HX Control box interface  Vacon NXP frequency converter  panel   Instructions on how to access and modify the parameters can be found in the Vacon NXP  User s Manual that is supplied with the HX unit   3 3 8 Low pressure alarm    The function of the pressure sensor placed on the pump suctions side is to give the user a warning of  low pressure before the FTSA11 flow switch generates a sudden unwanted shutdown  If there is a  leak in the primary circuit  outside of the HX unit  the pressure starts to reduce in the system  The  set point for the pressure sensor is 0 5 bar  so if the pressure on the primary circuit suction side  goes under 0 5 bar the yellow indicator light on the electrical box will activate  The correct system  pre  pressure is found in the chapter 3 1 6  Adding liquid and de airing        If the suction pressure in the primary circuit is reduced due to a leak  the flow in  the circuit will within a short period of time be insufficient and therefore activate  a FTSA11 flow switch shutdown              WARNING       The low  pressure parameter number is P2 10 4  Follow the instructions in the Vacon NXP User s  Manual on how to access and modify the parameters     3 3 9 Leak switch alarm specifications    The leak sensor is a free standing sensor on to the leakage plate in the floor of the HX
9.  follow the instructions in this manual  the reader must have a reasonable knowledge of  mechanics and electrics        Only a qualified and authorized mechanic is allowed to perform commissioning  or maintenance of the HX unit  A qualified and authorized electrician should    accompany the mechanic performing maintenance or commissioning on the  WARNING unit                 This manual is divided into following chapters     Chapter 1 SAFETY explains the symbols used in this manual and contains the general safety  instructions  Read the safety instructions before continuing     Chapter 2 INTRODUCTION explains how the HX unit is built by looking into the unit process and  instrumentation  The idea is to give the reader a basic understanding of the process and control  philosophy  This chapter also includes specifications on correct ambient conditions for the HX  unit     Chapter 3 COMMISSIONING provides information on how to install and how to start up the unit   The chapter explains  among other things  how the unit is to be filled with liquid and how the system  is to be de aired  The chapter also shows the user the correct valve positions for start  up and how to  set up the HX control unit     Chapter 4 UNIT SERMCE explains required maintenance and some repair instructions for the  components inside the cooling unit  More unit maintenance instructions can be found in the  component maintenance handbooks  They are found at the end of the HX unit Commissioning and  Maintenan
10.  follow when installing   commissioning  operating and maintaining the HX unit  Read the safety instructions before you start  to work on the unit    1 1 USE OF SYMBOLS   For your own safety  please pay special attention to the instructions marked with the following                   symbols   Risk of death  Instructions on preventing a possible severe  hazard to persons or equipment   DANGER  MN Risk of damage  Instructions on preventing possible damage  to equipment   WARNING  Hot surface  Instructions on preventing a possible minor  hazard to persons or equipment   HOT SURFACE  AN Notification  NOTE                Tel  4358  0 201 2121   Fax 4358  0 201 212 205       SAFETY vacon    9       1 2 GENERAL WARNINGS AND NOTES WHEN WORKING WITH THE HX UNIT    These safety instructions are intended for all who work on the HX unit  These instructions include  only a part of the complete safety instructions  Read the Vacon NX Liquid Cooled User s Manual  safety instructions as well  Ignoring the instructions can cause physical injury or death  It can also  cause serious malfunctions to the HX unit that is not covered by the warranty  When working on the  HX unit generally acknowledged safety standards  EU directives and national regulations must also  be followed     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       10   vacon SAFETY       1 Only qualified and authorized electricians and mechanics are allowed to  carry out the installation and maintenance work on t
11.  is located in the last two chapters of  this manual  For further information contact your local distributor     24 hour support 4358  0 40 837 1150   Email  vacon vacon com          44   vacon UNI T MAI NTENANCE       4  UNIT MAINTENANCE  4 1 GENERAL MAINTENANCE  4 1 1 Renewing liquid in the primary circuit    The liquid in the primary circuit should be renewed once every 5 years  The liquid in the primary  circuit will be contaminated with particles from the different units and therefore the conductivity of  the liquid will increase  When the conductivity of the liquid increases the risk of electrochemical  reactions between the different alloys in the primary system also increases  Changing the liquid in  the circuit every 5 years will reduce the risk of malfunction due to corrosion     4 1 2 Maintenance schedule    There are a few systematic maintenance tasks that have to be followed to ensure a trouble free  operation of the HX unit  They are presented in the diagram below       Once a month   Once a year   Every 2 years   Every 5 years    Checking   adding the Air    expansion vessel pre pressure waa  f          x O       Changing the primary circuitliquid   Jo         x        Monthly inspection     x  o     Diagram 4 1  1 Maintenance schedule       The monthl y inspection includes the following tasks    e Opening the HX unit cubicle door and checking that no visible leaks can be found  If a leak is  found the unit has to be shut down and the leak repaired    e Checkin
12.  on the Internet at     WWW Vacon com                                                                                                                                                                                              Manual authoring   documentation dvacon com    Vacon Plc  Document ID     Runsorintie 7   65380 Vaasa   Finland   D P D 0O 1 3 08 A    Subject to change without prior notice     2013 Vacon Plc  Rev  A                                        
13.  starts to come out of the drain  hose  connected to the valve V162    During the first minutes you will hear a rattling sound in the pipes  This is the air transported  out of the system by the water  After it rattling sound stops you should open the filling valve  V161 to 100      5  Keepthe water flowing until you can t hear any more rattles  and then close the V161 valve   Also close all the main drive valves  V310  V3xx  both the inlet and the outlet valves     Now it is time to de  air the drives  De  air the main drives one hose pair at a time  for example V310  and V311  See figure 2 2  2      6  Open valve V310 first then valve V311  this means that this path will be the only way for the  water to pass when you continue filling  Then open the filling valve V161  The water will again  come out from the hose connected to the manual de  airing valve V162  Keep the water  running until the rattling sound disappears  that is to say the air has been removed after  which the V161 filling valve is closed again     7  Close the valve V310 first  and then the valve V311  This procedure will leave the specific  drive section filled with water     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       24   vacon COMMI SSI ONI NG          If the external water system used for the filling can produce more than 6 bars  there is a risk of the safety valve  V120  opening  This might cause unnecessary  problems if some particles are left on the sealing surface of the safet
14.  that no particles larger than  0 3 mm can enter the primary circuit     The temperature of the liquid going to the main drives must never be lower than the ambient  temperature in the cabinet at the point of a start up of the main drives  If the system is shut down  during a cold period and the liquid runs a risk of freezing  a maximum of 2096 of glycol can be added  to the primary circuit system  If more glycol than 2096 is needed to keep the liquid from freezing then  contact your local distributor for additional information regarding a load reduction for the main  drive     To prevent corrosion  add the corrosion inhibitor Cortec VpCl  649 to the primary circuit liquid  Use  the additive according to the product specification found in the Component Specifications and  Maintenance Instructions section of the Commissioning and Maintenance folder     Primary circuit liquid quality Unit Value  TI A      NEED  Hardness of liquid    Chlorine  Cl  Iron  Fe  Maximum particle size    Table 2 3  1  Liquid quality       The secondary circuit liquid quality is not expected to be as clean as the primary circuit liquid  bearing in mind that clean liquid will prolong the time between cleaning the plate heat exchanger   HX11   If the customer and or end user are using a natural source of water for the secondary  circuit  one can assume that the water will include some kind of organic sediment  This organic  sediment will attach itself to the plates inside the HX11 and therefore the liqui
15.  the HX unit offline  according to the Vacon NX Liquid  Cooled User s Manual     4  Shut down the power to the HX unit by first turning both the pump control switches to    0      therefore shutting down the pump  then turning the main power switch to position  O   refer  to Figure 2 2  7     5  Check that there is no power coming to the pumps by removing the cover of the pump  electrical connection box and measuring the voltage  No work on the unit is allowed when the  power is connected     6  Disconnect the electrical cables from the pump that is to be changed  Write down the order  of the phases for later use     7  Close the maintenance valves of the pump that is to be maintained  V140  V143   Refer to the  P amp ID in Figure 2 2  2 or the project specific P amp ID if one is available        If the liquid contains corrosion inhibitors or other additives then check national  or local ecological directives for information on how to dispose of the drained  liquid  Information regarding the recommended corrosion inhibitor Cortec is  found in the end of the Commissioning and Maintenance folder that is supplied    NOTE      o with the unit                 24 hour support 4358  0 40 837 1150   Email  vacon vacon com       46   vacon UNI T MAI NTENANCE       8  Remove the bolts and nuts from the pump motor flange   Therefore leaving the pump housing in place  Figure 4 2  1    Note that there is a pre  pressure of 1 5 bars in the system  use  safety goggles     9  Lift out the pu
16.  unit  The  function of the switch is only to alert the user  by switching on the yellow alarm indicator placed on  the control box  The leak sensor generates an alarm if there is liquid on the floor plate inside the  HX unit due to a leak in the unit  If there is condensation inside the HX unit  the leak switch can  generate  false  leak alarms        Note that no condensation is allowed  However  if the relative humidity within the  cubicle is high and the ambient temperature is higher than the secondary circuit  inlet temperature  condensation will occur on the secondary circuit piping                 Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   39       If the secondary circuit inlet liquid temperature is not temperature controlled by the customer  there  is arisk of condensation on the secondary circuit inlet piping     Example  If the secondary circuit liquid inlet is 10  C and the ambient relative humidity inside the HX   unit cubical is 25  with a temperature of 20  C  condensation starts to occur in the secondary circuit  inlet piping  These values can be found on a Mollier diagram that shows the behaviour of moist air in  normal  1 013 bar  pressure     If any condensation occurs  the customer must add insulation on the HX11 heat exchanger and on  the secondary circuit piping  or increase the temperature in the secondary circuit inlet liquid  The  maximum temperature of the secondary circuit inlet liquid is 25  C without having to r
17.  valve  e The 3 way valve V130 is  e Run the actuator calibration  V130is malfunctioning and according to the instructions found  malfunctioning therefore not directing in the HX unit folder that is supplied  enough flow through the with the unit  i e  set the actuator  plate heat exchanger to Dip switch 1 to  On  position  If the  ensure a satisfactory heat actuator is not moving during this  transfer between the procedure it is broken and has to be    primary and secondary replaced    circuit    The FTSA11 setup values Check the project parameters  refer  have been wrongly Table 3 3 1  Parameter list  and  adjusted during compare it with the actual  commissioning  temperature        Table 5 1 2 High temperature fault detection    If the high temperature shutoff is active  same panel layout as high temperature alarm  the HX  unit  is online but the  Cooling OK  signal to the main drive has been disconnected  The yellow and red  indicator lights on the electrical box door are active  The reasons for this shutoff are the same as for  the high temperature alarm     If the low temperature alarm is active  acc  to panel below  the HX unit is still online and the   Cooling OK  signal to the main drive is connected  The yellow and green indicator lights on the  electrical box door are also active  Check the following issues to solve why the alarm has been  activated     F1   86 LowTemp    A  T1 gt  T16 gt     Figure 5 1 3  Low temperature alarm on the NXP panel       Malfunction Re
18. 2 2 3 So Ride A 14   2 2 4 Instruments and their funclon           e eee aea ns 14   2 2 5 Control   supervision parameters                     eeeessssseeeeeeenne nennen nnne nnne 15   2 2 6 alado cea ll  AA 16  INSTALLATION SPECIFICATIONS turis 17   2 3 1 Liquid quilla 17   2 3 2 Required ambient conditions   s ud tt e annene 18   COMMISSIONIN c arar rara pri 19  STEP  F  MECHANICAL PA obo b em 19   3 1 1 General installation INSENUCHONS    cada dad dd 19   3 1 2 Pipe CONReCU DNS cesen ad csi dd de os dls ON 19   3 1 3 lo lo A a o re PI nn AA AA rarer UA AAE AE EEA 20   3 1 4 Pressure testa mem 20   3 1 5 Setting up the primary E O 22   3 1 6 Adding liquid 2273 as    i 3 0 D NR RR 23   3 1 7 Adding corrosion inhibitor when using a fresh water system                         ssssss 25  STEP Z  ELECTRICAL PAMT          eite e e t he e teu a i RR EAR 26   3 2 1 Power supply    eh e ha e a e ase et s 26   3 2 2 Signal cables 4    445 5 a DD ad a e 26  SIEP S CONTROL UNITE SETUP 222032 3000 iind dd do i 8 ask 27   3 3 1 Basic Seton o PP 27   3 3 2 Application parameter loto aee tine euo estet ead un ttd und odas 27   3 3 3 Parameter cescripboris seti essit tiae cipehaotac faepidir eati pai Mira Pp fte 28   3 3 4 General information about alarms and shutoff limits                            sssssss 30   3 3 5 FISATEHONWSWIICh TUTO ba eiie dta eaa as MAL de Do ee 30   3 3 6 Temperature set points vivian salis 32   3 3 7 Temperature alarm settings    e lili 37   3 3 8 Low pressure a
19. 20 360l min    Empty weight of HX  unit   e 240kg  PVC C    Maximum input power   e 36kW    Supply pressure   Supply distance  primary circuit      e 07bar  25 m  25 m straight pipe      24 hour support 4358  0 40 837 1150   Email  vacon vacon com       56   vacon TECHNI CAL SPECI FI CATI ON       Liquid volume  primary side   e 25 5liter    Concentration of gl ycol  e maximum 25     Maximum flow secondary circuit      e 360l min    Pressure drops on customer circuit  secondary circuit   see Appendix 1     Note  Combined nominal flow of frequency converters must not exceed 90  of the maximum rate  of flow       Maximum straight pipe distance between HX unit and drive for achieving maximum fl ow  El bows  and other components will reduce the pipe distance       Pipeline to frequency converter  25 m  and back  25 m   If customer pipelines are long  size of the  pipelines must be DN32 or DN40       The pressure before 3  or 2  way valve must be at least 2 bar to prevent cavitations   See cavitations diagram in Components Specifications and Maintenance Instructions n o 2  TAC  Venta  page 2     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       TECHNI CAL SPECI FI CATI ON    vacon   57       APPENDIX 1    Pressure drops on customer circuit  HX_120       100  FLOW   360 l min                                                                                                       Plate heat Pressure drop   Pressure   exchanger plate heat drop 3 way   route Flow Bypass route   Flow 
20. 3 2 STEP 2   ELECTRICAL PART  turn the main power switch  the red   yellow switch in Figure 2 2  7  to  position  1     It is recommended that the parameter P2 10 1 be changed to 30 Hz at first start up  Later  when the HX unit is completely de  aired the P2 10 1 should be set to the correct value  refer  to chapter 3 4 2  Adjusting the system flow and setting the switch point of the FTSA11     Start up the pump PU11 or PU12 by turning the pump control switch to position  1   the black  and red switch in Figure 2 2  7   The liquid starts to circulate in the primary circuit  Run the  pump for max  30 sec  then do the same to the other pump     Wait for 5 min  and open the manual de airing valve V162 to let out any air that might have  been stuck in the pump housing     Add water to get the pressure back up to 1 5 bars  Then start one of the pumps again and  leave it running     The LED display on the FTSA11 should register that there is flow in the system  If not  stop  the pump and re  check that all valves are open  e g  in the drive section  in the HX unit and if  there is piping valves made by customer in the primary circuit then check them also  The  flow switch is set to 50  as default and has a 5 second delay  the 5 second delay is  programmed into the HX control unit application   What this means is that the flow has to get  over the 50  limit within 5 seconds of starting the pump  or the HX control unit will shut  down the pump     If the pump is shut down and the HX 
21. Cooled drive User s Manual that is  supplied with the main drives        Figure 3 2 4    A 24V auxiliary voltage from the main drive is sent through the cable to the HX unit  If the HX  unit is  working within the preset parameters then the signal is rerouted back to the main drive  When the  signal is active in the main drive basic I O board NXOPTA1  terminal number 14   then the main drive  application will activate a    Cooling OK    function that will allow starting and operating the main drive       Run Enable       When a flow fault or high temperature fault is active in the HX unit  the digital output   cooling OK      contact in the HX control unit will disconnect the 24V signal and the main drives will shut down  The  main drive cannot be brought online before the flow fault or high temperature fault is removed     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   27       3 3 STEP 3  CONTROL UNIT SETUP  3 3 1 Basic setup    The control unit application includes    Flow control    parameters that have to be modified for every  project  Primary circuit inlet temperature and primary circuit flow are two equally important  quantities that have to be monitored at all times  How to calculate the optimum flow is found in  chapter 3 4 2  Adjusting the system flow and setting the switch point of the FTSA11  How to correctly  set up temperature alarms and shutoffs is found in chapter 3 3 6  Temperature set points        If the customer and or end 
22. S11   All  alarm and shutoff limits have a default value  These default values should  if needed  be modified at  the commissioning phase        Refer to the Vacon NX USER S MANUAL to change the parameters  Only  authorized personnel are allowed to make modifications to the parameters              NOTE       The parameters and their settings can be found in chapter 3 3 2  Application parameter list  When  you change the default settings during commissioning  you should write down the new setting  including the date and your name to keep track of changes  Write down the new parameters to the  custom setting column of the flow control parameter table 3 3  1     3 3 5 FTSA11 flow switch function    The flow switch is set to shut down the HX unit if the flow does not meet the requirements  refer to  chapter 3 4 2  Adjusting the system flow and setting the switch point of the FTSA11  The unit settings  should be modified  during commissioning  through the switch interface panel  The default setting  for the switch is 50   050      Adjusting the FTSA11 flow switch     1  Turn the pump power switch  the black and red switch in Figure 2 2  7  to the position  1  to  connect the power to the HX unit  This will activate the FTSA11     2  When the power is connected  the display flashes for approximately 30 seconds with  888   for initialization  When the flashing stops  the device is ready for programming     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon 
23. VACON   NX    AC DRIVES    HXM 120 COOLING UNIT  SS PIPING  AND PVC C PIPING VERSION 3 0    COMMISSIONING AND  MAINTENANCE MANUAL       VACON    DRIVEN BY DRIVES    vacon   3       QUICK START UP GUIDE    THE FOLLOWING STEPS OF THE QUICK START  UP GUIDE MUST BE PERFORMED DURING THE  INSTALLATION AND COMMISSIONING     If any problems occur  contact your local distributor     10     11     Check that the delivery corresponds to your order   Before starting commissioning  read carefully the safety instructions in Chapter 1 SAFETY     Check that the specified installation location and ambient conditions comply with the  specification  Refer to Chapter 2 3 2 Required ambient conditions     Any customer made piping must be thoroughly flushed before connecting to the HX unit   Check that the liquid quality is approved  Refer to Chapter 2 3 1  Liquid quality     Connect the mechanical and electrical couplings  Refer to Chapter 3 1 2  Pipe connections  and 3 2 STEP 2  ELECTRICAL PART     Adjust the HX control unit parameters to match the specific project requirements  Refer to  Chapter 3 3 2  Application parameter list     Perform a pressure test to the primary circuit and secondary circuit connections  Refer to  Chapter 3 1 4  Pressure test     Add coolant to the circuits and de air them according to the instructions in 3 1 6  Adding  liquid and de airing    Adjust the primary circuit flow and temperature to match the project requirements  Refer to  Chapter 3 4 2  Adjusting the syste
24. al ve  V162 that is positioned on top of the HX11  plate heat exchanger  The other end of this hose should be pointed into a drain or into a tank  depending on which system is used for the filling procedure  The system used for filling should be  able to produce at least 2 bar and delivery at least 15 l min     There are many ways of adding water to a piping system like the primary circuit  The two most  common ways of filling are presented next  Which of these are used depend on if the site has a fresh  water system or if the water has to be filled from a tank     Figure 3 1 9 shows how to connect the hoses to the HX unit if there is no pressurized fresh  water  system at hand  cas fh   e Connect a suction pump outlet to the Ts    filling valve V161  Secure the  connections with a hose clamp    e Connect the drain hose to the manual  de airing valve V162 and put the other  end of the hose in the barrel  Secure the  connection with a hose clamp    e Secure the drain hose to the barrel so it  won t jump out during the filling and de   airing    e  f corrosion inhibitors are used they can  be mixed  in the right amount  with the  water in the barrel    e Depending on the system size there has  to be 20  200 litres of liquid in the barrel        Figure 3 1 9    Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   23       Figure 3 1  10 shows how to connect the hoses to the HX unit if there is a pressurized fresh  water  system at hand    e Connect the 
25. an be found in the Vacon NXP User s Manual that is supplied with d    the cooling unit  Sy e    The frequency converter includes a Fieldbus link card  By connecting to this card   the customer can view eight different values  parameters   e g  primary circuit  temperatures  pressures  warnings and shutoffs  This is very useful if the HX unit  is not monitored locally  Information regarding the connection type is found in the  Vacon NXP User s Manual that is supplied with the HX  unit              Figure 2 2 5    2 2 4 Instruments and their function    The flow switch FTSA11  Figure 2 2 6  measures the speed of the flow inside the pipe  This flow  speed is shown as    100  of the measuring range of the instrument  The FTSA11 has two different  flow measuring ranges to choose from  15 150 cm s or 30 300 cm s of which the higher range is  used in the HX  units  The unit also sends the primary circuit temperature as a 4   20mA signal to the  FV11 3  way valve actuator  Both the analogue temperature signal and the    on off    switch signal are  sent to the HX control unit  The analogue signal is used to control the temperature in the primary  circuit and also to generate temperature alarms and shutoffs  The PNP switch  output that monitors the flow is used to generate a shutdown command     The flow speed shown in 96 on the FTSA11 can easily be modified to flow  l min   by using the diagram in chapter 3 4 2  Adjusting the system flow and setting the  switch point of the FTSA11  N
26. asons for malfunction   Correction measures  The regulating valve  e The 3 way valve V130  e Run the actuator calibration according to  V130  refer to the is malfunctioning and the instructions found in the HX unit  P amp ID  is therefore directing too manual that is supplied with the unit  i e   malfunctioning much flow through the set the actuator Dip switch 1 to  On   plate heat exchanger  position  If the actuator is not moving  during this procedure it is broken and has  to be replaced        24 hour support 4358  0 40 837 1150   Email  vacon vacon com       52   vacon    TROUBLESHOOTI NG       The FTSA11  refer to  the P amp ID  flow  sensor with the  analogical  temperature outlet  is malfunctioning     The inlet temperature  on the secondary    circuit is decreasing  too fast  and the 3  way  valve is not able to  adjust the flow in the  secondary circuit fast  enough    The FTSA11 flow  sensor with the  analogical  temperature outlet is  broken     Table 5 1 3  Low temperature fault detection       Wait for two minutes and see if the alarm  is reset automatically  If the alarm is active  longer than two minutes  check the 3  way  valve s function  If the 3  way valve or the  valve actuator is malfunctioning it must be  replaced  If the temperature in the primary  circuit is too low it will result in  condensation in the main drive section  No  condensation is allowed    The temperature in the secondary circuit  should not be allowed to decrease or  increase too fast 
27. at exchanger cleaning instructions found in the end of the  Commissioning and Maintenance folder that is supplied with the HX unit     If the liquid used in the secondary circuit contains biological or chemical residue  it is recommended  that a spare heat exchanger be stored locally  When the flow in the secondary circuit is too low  the  HX unit should be shut down and the heat exchanger replaced  The dirty heat exchanger should be  cleaned according to manufacturer s instructions and placed in storage for the next time HX11  needs to be changed     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       UNI T MAI NTENANCE vacon   47       The HX11 can  if needed  be removed without removing the HX  unit from the cubicle     l  Drain both the primary circuit and the secondary circuit  The secondary circuit is drained  through the V163 valve  marked yellow in Figure 4 2 2   The primary circuit is drained  through the valves V301 and V302  refer to the P amp ID in Figure 2 2  2      HXM 120 AISI     Disconnect the primary and secondary circuit connections  marked violet in Figure 4 2  2   from the unit  The connections can be opened with a box wrench     HXM120 PVC C     The connections can be opened by hand  or if needed use oil filter  remover  used to remove the oil filter from cars   Be careful not to  damage the connections              2  Remove the one M8 nut from underneath the heat exchanger   marked violet in Figure 4 2  3                  3  Carefully pull   lift   t
28. at show    how the primary circuit temperature is calculated depending on which of the three above  mentioned  factors is the deciding one     Tel  4358  0 201 2121   Fax 4358  0 201 212 205    COMMI SSI ONI NG vacon   33       Example 1  high ambient temperature   If the customer and or end user have a high ambient temperature  35 C  at the main drive that  would require the primary circuit temperature to be equal or higher than 35  C  This would normally  require a load reduction of the main drive  If the maximum relative humidity at the main drive is  known  the dew point chart  Chart 3 3  1  can be used to determine a more optimized temperature  for the primary circuit     Ambient temperature  35  C  Maximum relative humidity  60   Acc  to chart 3 3  1 gt  Dew point is  26  C    It is recommended to use a 2  C safety margin  Therefore the primary circuit temperature should in  this case be set to 28  C  26  C  2  C   In this case no reduction of load in the main drive is needed   even if the ambient temperature is high  due to a rather low maximum relative humidity     Maximum ambient temperature  35   C  Maximum ambient relative humidity 60        02 03 04 05 M  VACON LIQUID COOLED NX DRIVE HXM120      can Ss    Secondary circuit    E    maximum  23  C   28  C 5  C                                                                                                                                               ej                                        A i a    Primary circuit 
29. ay up with  water  When no more water will go into the  HX11 then close the manual de airing valve  V162 and remove the hose           6  Now open the filling valve V161 and increase the  pressure back to 1 5 bar  The corrosion inhibitor  will get mixed when the pump is rotated for a while     Figure 3 1  11    24 hour support 4358  0 40 837 1150   Email  vacon vacon com       26   vacon COMMI SSI ONI NG       3 2 STEP 2  ELECTRICAL PART       Only qualified and authorized electricians are allowed to perform electrical work  on the HX unit   WARNING                3 2 1 Power supply    The HX unit uses 3   400VAC  50Hz  or 3   440VAC   60Hz   16 A power supply  There are two alternatives  to bring the supply cables to HX unit  from under or  from above  Figure 3 2  1  Figure 3 2  2                        Figure 3 2 1 Figure 3 2 2    Connect the power supply to the motor protection relay  marked green in  Figure 3 2  3  in the HX  unit electrical box     Figure 3 2 3    3 2 2 Signal cables    A signal cable must be connected between the main drive and the HX unit  electrical box  It should be connected from the main drive basic I O board  NXOPTA1  terminal number 6 or 12  24V out  to the HX unit X1 terminal block   marked green in Figure 3 2 4  terminal number 16  cooling OK in   and back  from X1  terminal number 17  cooling OK out  to the main drive  terminal  number 14  DI 4   For more information refer to the project specific electrical  diagram and to the Vacon NX Liquid 
30. ce folder that is supplied with the unit     Chapter 5 TROUBLESHOOTING includes fault tracing to help the user identify and solve a problem  when the HX control unit  air  cooled Vacon N XP 0009  has an active alarm or fault     Chapter 6 TECHNICAL SPECIFICATION    24 hour support 4358  0 40 837 1150   Email  vacon vacon com       12   vacon   NTRODUCTI ON       2 2 PROCESS AND INSTRUMENTATION    The HX unit s principle of operation is based on liquid to liquid transfer of heat  The primary circuit  transports the heat load from the frequency converter to the plate heat exchanger  The secondary  circuit liquid flowing through the plate heat exchanger then collects the heat load and transports it  to an external condenser  This external condenser  which does not appear  on the diagram  is part of the customer and or end user s existing cooling  system  Another way to dispose of the heat load is to use existing natural  resources e g  a lake or river  The use and choice of a system for disposing  of the heat load is the customer s and or end user s responsibility     e Primary circuit  HXM120  PSO1  green colour in the Figure 2 2  1   e Secondary circuit  HXM120  PSO2  red colour in the Figure 2 2 1     The FTSA11 flow switch  which monitors the flow in the primary circuit  also  includes a temperature sensor  This temperature sensor controls the  primary circuit temperature  This sensor sends out an analogue signal to  the HX control unit  The control unit application adjusts 
31. control unit display is registering a flow fault  reset the  fault from the Vacon NXP control panel  turn the pump control switch back to position  O   and try again  refer to the NXP    All in one    manual on how to work the panel   If the pump  does not stay online after three  3  attempts  de  airing has not been done correctly or some  of the valves mentioned in step 1 and 2 are still closed  De air the system again  refer to  Chapter 3 1 6 Adding liquid and de airing     Check that all valves except V161  V163 and V301  V302 are open  If the pump does not stay  online after a new de airing  try to temporarily lower the flow switching point for the FTSA11  to 1096  5096 as default   Information on how to modify the FTSA11 switching point is found in  chapter 3 3 5  FTSA11 flow switch function     Tel  4358  0 201 2121   Fax 4358  0 201 212 205    COMMI SSI ONI NG vacon   41       14  If the pump stays online  run it for 15 minutes and then change the flow switch point back to  the project specific setup value  The flow switch point can be changed during operation     During the first days of operation  the pre  pressure decreases because some air might be left in the  system after de  airing     To adjust the pressure     1  Connect a filling hose to valve V161  De air the filling hose before adding liquid to avoid air  getting into the primary circuit     2  Addliquid to increase the pressure back to 1 5 bar on the PI11 pressure gauge   Close valve V161 and remove the h
32. corner of the HX unit electrical box  door  Try to wipe off the sensor and the  leakage plate with a dry cloth  If the yellow  light is still on then the sensor is most  likely broken and will need to be replaced        Tel  4358  0 201 2121   Fax 4358  0 201 212 205    TECHNI CAL SPECI FI CATI ON vacon   55       6  TECHNICAL SPECIFICATION    Physical size  without cubicle    Dept   e Width  705mm  982mm   e Height  1885mm AISI304  1872 PVC C  e Depth  540mm  603mm                                         Liquid connections   e Primary circuit  Rp 2     ISO 7 1  or DN50 DIN 2642  e Secondary circuit  Rp 2     ISO 7 1  or DN50 DIN 2642   PN10   DIN 2633  PN16     Height    Electrical supply   e 3   400VAC  50Hz  or 3   440VAC  60Hz   16 A  e 3   400   500VAC  50 60Hz    16A  when sinifilter              Depth  Width     Other electrical connection   e 24V auxiliary voltage  between HX  unit and main drive   e Option  Fieldbus  Profibus  connection from the HX  control unit to customer monitoring  system    Ambient conditions   e 45 450 C  e RH5  96   no condensation allowed    Pressure ratings   e Primary circuit  PN6  e Secondary circuit  customer piping   PN10  Option  PN16 for AISI 304 piping     Temperature ratings   e Primary circuit  45  4509C  e Secondary circuit  45    502C    Storage temperature rating   e  40  4609C  e All liquid must be removed from the unit during storage if the temperature is below O9C     Cooling capacity   e 120kW    Rate of flow range       e 1
33. ction  The modes are either normal control  OP      off     or calibration  ADJ      on    In mode calibration  ADJ   the actuator runs a sequence  reads end positions and adjusts  itself to the valve it is mounted on  The value of the end positions are stored in a non  volatile  memory i e  the positions are not lost when power supply is lost  When the calibration  sequence is finished the actuator halts until the switch is reset to OFF position  OP   OP is the  position of the switch at normal control     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       40   vacon COMMI SSI ONI NG       3 4 STEP 4  ADJ USTING THE FLOW    3 4 1    Starting the pump    Note that de  airing of the unit has to be done before the HX  pump can be started  To start the pumps  for the first time           WARNING    The pumps must not be run dry under any circumstances  Running the pump dry  even for a short period of time might cause the shaft seal in the pump to start  leaking              AM BF WN    10     11     12     13        Open the maintenance valves for the main drives  V310 to V31x  that are to be used    Check that the valves V140    V143 are open and that V160 has the lever turned downwards   Check that the valve V161 and V162 is closed  And that the pre  pressure is at 1 5 bar    If the customer has added some valves these must also be in checked    Check that there are no visible leaks     If the electrical cables have been connected and checked  refer to chapter 
34. d to liquid heat  transfer between the primary circuit and the secondary circuit will  over time  be less efficient   Another problem with this organic sediment is that the pressure loss over the HX11 will also  increase and therefore the flow will decrease  which will also lead to poor liquid to liquid heat  transfer between the primary and secondary circuit     Because of possible organic sediment in the liquid circulation  it is strongl y recommended that flow  measuring equipment or a pressure difference measurement be installed on the secondary circuit   This equipment should generate an alarm if the flow is below requirements  When there is a need to  clean the heat exchanger  refer to the Alfa Laval  AlfaCaus  Heat Exchanger Cleaning material found  in the Component Specifications and Maintenance Instructions section of the Commissioning and  Maintenance folder     In the secondary circuit  the liquid should not contain particles larger that 2 mm  If there are larger  particles in the liquid circulation  the 3  way valve or the heat exchanger might clog within a short  period of time  Therefore it is strongly recommended that a filter  MF21  be installed at the  secondary circuit inlet  which will filter out particles larger than 2mm  For more information  regarding this filter unit please contact our local distributor     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       18   vacon   NTRODUCTI ON       The secondary circuit liquid should not include a
35. ded  The HX control unit will generate a    Low  pressure    alarm if the pre  pressure  is below 0 5 bar     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   25       3 1 7 Adding corrosion inhibitor when using a fresh water system    If you are using a fresh water system to add water it is more difficult to add the corrosion inhibitor   The corrosion inhibitor can be added through the manual de  airing valve V162  To do this the water  level has to be lowered in the HX11 and a funnel has to be used  Figure 3 1  11      1  The corrosion inhibitor should be added after all the main drives have been de  aired  Check  that all the main drive valves  V310   V3xx  are closed     2  Lower the liquid level in the plate heat exchanger HX11 by opening the valve V301 and letting  out 2 litres of water  This will lower the level inside the HX11 and make the necessary space  for the corrosion inhibitor     3  Remove the hose from the valve V162 and replace it with a one  1  meter long hose  Connect  afunnel to the loose end of the hose     4  Keep the funnel higher up than the heat exchanger HX11  and pour the corrosion inhibitor  into the HX11 using a jug  Refer to the Cortec  VpCl  649 product description for calculating the  right amount of corrosion inhibitor  refer to the  technical specifications for Cortec found in the  Commissioning and Maintenance folder      5  After all the corrosion inhibitor is added use the  same jug to fill the HX11 all the w
36. educe the load  in the main drive  More information regarding the secondary circuit temperature is found in chapter  3 3 6  Temperature set points     3 3 10 Three way valve   two way valve actuator settings    Please check the DIP switch positions in the valve actuator  There are five switches and their  positions are as follows    N o 1   gt 0n   N o 2   gt on   N 0 3 off   N 0 4   gt off   N o 5     To be run once at    on    so that the valve actuator finds min and max movement values  then     off        Detailed description about DIP  switch positions     N o 1 Selection of control signal type Y  The control signal might either be a voltage level  V    off    or a current level  mA    on      N o 2  Input control signal operating range  The input signal can either start at O V mA i e  no offset    off   or at 2 V 4mA with offset   on    A new setting will be recognized after a new calibration  run  ADJ      N o 3  Operating direction of actuator  The actuator can either give a movement downwards at  increasing control signal  096 at opening in upper position    off   or increasing control signal  giving a movement upwards  096 opening in lower position    on    A new setting will be  recognized after a new calibration run  AD       N o 4  Running time selection  The running time can be set to either 120 seconds   off   or 240  seconds     on     for a 20mm stroke  A new setting will be recognized after a power off followed  by a reference run    N o 5  Working mode sele
37. erature  It is  recommended that the primary circuit temperature is higher than the ambient temperature but in  Some cases this will cause an unnecessary reduction of load in the main drive  If this is the case the  maximum relative humidity  RH  at the installation must be specified  When the maximum RH and  the maximum ambient temperature have been determined  the Dew Point Chart found in chapter  3 3 6  Temperature set points can be used to define the minimum primary circuit temperature     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   19       3  COMMISSIONING  3 1 STEP 1  MECHANICAL PART       Only qualified and authorized mechanics are allowed to perform mechanical  work on the HX unit   WARNING                3 1 1 General installation instructions    The HX unit is delivered with a self supporting frame as shown  in Figure 3 1  1  Therefore the customer can place the HX unit in  the cubicle of their choice  The unit is designed to fit inside a  VEDA or Rittal 800x600x2000mm  W x D x H  cubicle  If the  customer and or end user are using another kind of cubicle it is  their responsibility to ensure that the HX unit fits inside the  cubicle of choice  The unit can be delivered pre fitted to a VEDA  or Rittal cubicle on request  For more information regarding this  option contact your local distributor     If the customer positions the HX unit in their own cubicle  it is  the customer s and or end user s responsibility to make sure  that 
38. exchanger valve Total pressure drop  100  360 l min   0  0 0 5 bar 1 83 bar 2 33 bar   75  270 l min   25  90 l min   0 25 bar 1 83 bar 2 08 bar   50  180 l min   50  180 l min   0 116 bar 1 83 bar 1 95 bar   25  90 l min   75  270 l min   0 03 bar 1 83 bar 1 86 bar   0  0 100  360 l min     1 83 bar 1 83 bar     gt  Pressure drop varies between 1 83 bar   2 33 bar   75  FLOW   270 l min   Plate heat Pressure drop Pressure   exchanger plate heat drop 3 way   route Flow Bypass route   Flow exchanger valve Total pressure drop  75  270 l min   0  0 0 25 bar 1 03 bar 1 28 bar   5096 180 l min   25  90 l min   0 116 bar 1 03 bar 1 146 bar   2596 90 l min   50  180 l min   0 03 bar 1 03 bar 1 06 bar   096 0 7596 270 l min     1 03 bar 1 03 bar     gt  Pressure drop varies between 1 03 bar   1 28 bar   50  FLOW   180 l min   Plate heat Pressure drop   Pressure   exchanger plate heat drop 3 way   route Flow Bypass route   Flow exchanger valve Total pressure drop  5096 180 l min   096 0 0 116 bar 0 46 bar 0 58 bar   2596 90 l min   2596 90 l min   0 03 bar 0 46 bar 0 49 bar   096 0 5096 180 l min     0 46 bar 0 46bar                           gt  Pressure drop varies between 0 46 bar   0 58 bar    24 hour support 4358  0 40 837 1150   Email  vacon vacon com             58   vacon       NOTES                                                                       Tel  4358  0 201 2121   Fax 4358  0 201 212 205                   VACON    DRIVEN BY DRIVES    Find your nearest Vacon office 
39. f there  appears condensation inside the HX unit it might trigger the leak sensor  LS11  on the HX unit floor  and therefore giving some    false  leak alarms  In a case like this it is recommended that the  customer insulate the secondary circuit piping and the plate heat exchanger inside the HX unit to  stop the condensation and therefore avoid any more  false  alarms     On request the HX unit secondary circuit and the plate heat exchanger can be insulated before  delivery     3 3 7 Temperature alarm settings    The temperature alarm levels depend on the primary circuit temperature set point  Refer to chapter  3 3 6  Temperature set points     The over temperature alarm  e Activates a function that will activate the yellow indicator light on the HX unit electrical box   The value is set to 3 C higher than the primary circuit temperature set point  The default  setting of the high temperature shutoff is 28  C   e When this alarm is activated the HX  control unit panel will show the text    A83 OverTempA      Example  over temperature alarm  The primary circuit temperature set point is set to 35 degrees  then the over temperature alarm  parameter  P2 10 9  should be set to 38 degrees     The over temperature fault  e Activates a function that will shut down the drives but will keep the HX  unit running  is set to  10  C higher than the primary circuit temperature set point  The default setting of the high   temperature shutoff is 40  C   e When this alarm is activated the HX
40. for them                 The pressure in the primary circuit can be monitored from the pressure indicator PI11 during the  pressure test  If the pressure remains constant for 15 minutes  the system is airtight  If the pressure  is decreasing  look for the leak by soaking the pipe connections with soap liquid  When the leak is  located tighten the connection and redo the pressure test     If the pressure test is done with water the leaks can be located visually  therefore no soap  water is  necessary     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       22   vacon COMMI SSI ONI NG       3 1 5 Setting up the primary circuit    Before filling the system with liquid  check that all pipes and hoses are  connected  The maintenance valves V160  V162 are plugged so that no  accidents can occur during operation  During maintenance these plugs  must be replaced with hose nipples or similar parts so that a hose can  be connected to the val ve     The valve handle positions before pre filling the system are as  following        e Valves V161   V162 X open  violet colour in Figure 3 1 8    e Valve V160 lever down  brown colour in Figure 3 1  8   e Valves V140   V141 closed  yellow colour in Figure 3 1 8    e Valves V142  V143 open  orange colour in Figure 3 1 8    e Valves V301   V302 closed  see P amp ID  Figure 2 2 2    e Valves V310   V31x open  see P amp ID  Figure 2 2 2                                Figure 3 1 8    A hose must be connected to the manual de  airing v
41. g might in some cases help to prevent an unexpected shutdown of the drive     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       16   vacon   NTRODUCTI ON       2 2 6 HX unit electrical box    The electrical box inside the HX unit consists of a motor protection relay  circuit breakers   contactors  400 24 V DC power supply and a terminal     There are four switches attached to the electrical box door  main power switch  two pump power  switches and leak sensor reset switch     e Main power switch  red yellow in Figure 2 2  7  is connected  to the motor protection relay  Positions  O   zero  and  1    The contact breaker controls the main power to the HX unit   including the HX control unit     e Pump power switch  black and red in Figure 2 2  7   positions     0     zero  and    1     The contact breaker controls the power to  the HX unit pumps  PU11 and PU12  The pump can be  started by turning the switch to position  1   and stopped by  turning it back to position  O   If both switches are in position     1    then the pumps are automatically working in sequence   changing every 168 hours  or acc  to project specific value      e LS11 leak sensor reset switch  white in Figure 2 2 7  resets  the leak alarm  To reset the alarm  the liquid must first be  removed from the sensor on the HX unit leakage plate        Figure 2 2  7    There are also five indication lights on the electrical box door  The colours indicate the following     e Red indicates that the HX 
42. g that the primary circuit pressure at the PI11 is between 1 0 and 1 5 bar  If the  pressure is too low it must be rectified    e Check that the FTSA11 flow switch LED display is reading the same value as lasting the  previous month  If the flow switch is showing  lt 5  reduction of the installed value  at  commissioning  then refer to chapter 5 1 1  Flow fault for advice    e Check the temperature of the primary circuit by pressing the button on the FTSA11 marked  once  Check the temperature value with the value set at commissioning  Press it once more  to go back to reading the flow percentage     The indicator lights on the HX electrical box should be monitored at all time  If the HX unit is placed  at a position were it isn t possible to monitor the indicators continuously  the Fieldbus interface of  the HX control box can used to re route the alarms to a place were they are monitored at all times  If  it isn t possible to use the Fieldbus interface then the indicators on the HX electrical box must be  moved to a position were they can be monitored at all times     4 2 MAINTENANCE BY COMPONENT  4 2 1 Pump    The pumps PU11 12  refer to the P amp ID  do not require regular service  During the life cycle of the  HX unit  it is likely that the shaft seal will have to be changed at some point  The shaft seal between  the pump housing and the motor is the most probable cause for leak on the centrifugal pump  When  changing the shaft seal  follow the pump maintenance rules in t
43. garding the  load reduction of the drives refer to the Vacon NX Liquid Cooled User s Manual that is supplied with  the main drive     Maximum ambient temperature  40  C  Maximum ambient relative humidity 8096       02 03 04 05    VACON LIQUID COOLED NX DRIVE HXM120   R  cun cau ca Secondary circuit    maximum  33   C   38  C 5   C                                                                                                                                         o e    E                                                              loe  P TT M euius    Primary circuit minimum  38  C  36  C 2  C                                                                          Figure 3 3 4 Example 2    The secondary circuit maximum temperature should always be 5  C lower that the primary circuit  temperature to ensure a good thermal load transfer between the two circuits  In example 2 this  means that the secondary circuit should be between  5   433  C during operation  The 3  way valve in  the secondary circuit will then keep the primary circuit temperature at 38  C regardless of the main  drive load     Example 2b  reducing the ambient relative humidity   If the load reduction isn t acceptable for the specified drive it is recommended that a humidity  remover be installed that can reduce the maximum RH to an acceptable level  In example 2  a  reduction of the maximum RH from 80  to 50  will allow the primary circuit temperature to be 30  C  and therefore give the possibility to run t
44. he HX unit   Do not open the drive section doors while the drives are online  If you    suspect a coolant leak in the drive section  shut down the drives and  disconnect the power to them before opening the drive section cubicle    AN When working with the HX unit together with the frequency converter   also follow the Vacon NX Liquid Cooled Drive User s Manual safety  DANGER instructions to prevent any accidents   Any installation work on the HX unit must be done with power off  The  power must not be reconnected before the installation work is  complete      N El The primary cooling circuit can contain hot coolant  over 450 C  during    WARNING normal operation  Serious burns are possible  Before performing  maintenance  switch off the unit and allow it to cool down   The primary cooling circuit can contain high  pressure coolant  6 bar   during operation  Release the pressure in the HX unit before     A performing maintenance  Use safety goggles    HOT SURFACE    7 The HX unit must be positioned in a non  hazardous area where it can t  pose a threat to any main systems or persons     The coolant consists  depending on the project  of plain drinking water  or of a mix of water  propylene glycol and corrosion inhibitors  Glycol  and corrosion inhibitors are dangerous to health  If you get coolant  mixed with glycol or corrosion inhibitors in your eyes  on your skin  or in  your mouth  seek medical advice    It is the customer s and or end user s responsibility to provide flo
45. he main drive at full load     Ambient temperature  40  C  Maximum relative humidity  80  50   Acc  to chart 3 3  1 gt  Dew point is  28  C    When adding the safety margin of 2  C the primary circuit temperature can be set to 30  C  In this  case a reduction of the maximum RH from 8096 to 5096  by using a humidity remover  will allow the  primary circuit temperature to be set to 30  C therefore allowing the main drives to be run at full  load     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   35       Maximum ambient temperature  40  C  Maximum ambient relative humidity 5096       02 03 04 05    VACON LIQUID COOLED NX DRIVE HXM120      Ca    Ca Secondary circuit    maximum  25  C   30  C 5  C                                                                                                                                               E o e                                  PF din ee  Primary circuit minimum  30  C  28  C 2  C                                                                          Figure 3 3 5 Example 2b    The secondary circuit maximum temperature should always be 5  C lower than the primary circuit  temperature to ensure a good thermal load transfer between the two circuits  In example 2b this  means that the secondary circuit should be between 45   425 C during operation  The 3  way valve in  the secondary circuit will then keep the primary circuit temperature at 30  C regardless of the main  drive load     Example 3  high sec
46. he pump service instructions found  in the Commissioning and Maintenance folder that is supplied with the HX  unit     It is recommended that a reserve pump be stored locally in order to restore the operation quickly    when a pump needs to be maintained  There should also be a shaft seal in storage to facilitate  changing a broken or leaking shaft seal at site     Tel  4358  0 201 2121   Fax 4358  0 201 212 205    UNI T MAI NTENANCE vacon   45       When the pump is leaking  remove the broken pump and replace it with a reserve pump  The broken  pump should be fixed immediately and stored for later use in case a similar pump failure occurs   Purchase a new shaft seal from the unit manufacturer  and keep this in storage as well        High pressure hot coolant  6 bar  460 C  may be present in the primary  WARNING cooling circuit  The coolant consists of liquid  propylene glycol and corrosion  inhibitors  depending on the project  Glycol and corrosion inhibitors are  damaging for the eyes  If you get coolant in your eyes  on your skin  or in your  mouth  seek medical advice  Use safety goggles              HOT SURFACE       To change a pump     1  Check that it is safe to turn off the drives connected to the HX unit  and that there is enough  time reserved for the maintenance     N    Prepare the HX unit for liquid filling by connecting a hose to the filling valve  V161   Read  Chapter 3 1 6  Adding liquid and de airing before continuing     3  Take the main drives connected to
47. hose from the faucet to the filling  valve V161  Secure the connections with a  hose clamp    e Connect the drain hose to the manual de   airing valve V162 and put the other end of the  hose into a drain  Secure the connection with  a hose clamp    e Secure the drain hose to the drain so it won t  jump out during the filling and de airing    e For adding corrosion inhibitor read chapter  ALI       Figure 3 1  10    If a local sink or floor drain is used and corrosion inhibitors are added to the liquid in the primary  circuit then it is the customer and or end user s responsibility to check that the coolant mix can be  disposed of through the local sewer system     3 1 6 Adding liquid and de airing    Follow the instructions for the pre filling process before starting the pump at commissioning or  after maintenance     How to fill the primary circuit HXM120  PSO1  See P amp ID in figure 2 2 2      l  Prepare the unit according to the recommendations in chapter 3 1 5 Setting up the primary  circuit  Use valve V161 to regulate the flow during the filling and de airing of the unit     2  It is recommended that the flow  from the external pump or water supply system  is low in  the beginning of the filling process  This ensures that a minimum amount of air pockets is  left in the piping     3  Close valve V161  Open the faucet or start the external pump depending on which filling  System you are using  Slowly open valve V161 to a 30 50  of maximum     4  After a short while liquid
48. il the correct pre   pressure is reached  Follow the  instructions in chapter 3 1 6  Adding liquid  and de airing    e Hose failure in the  e Replace the hose  Refer to the NX Liquid   main drive section  Cooled User s Manual  Then add liquid to  the primary circuit until the correct pre   pressure is reached  Follow the  instructions in chapter 3 1 6  Adding liquid  and de airing   Pressure vessel e The gas  air or e Check and refill the  pre pressure  EV11  refer to the nitrogen  has escaped according to the instructions in chapter  P amp ID  is without through the butyl 4 2 3 Pressure vessel   pre  pressure  rubber membrane into  the primary circuit    e The EV11 filling valve  e Replace the valve and refill the pre  is broken and pressure according to the instructions in  therefore letting out chapter 4 2 3 Pressure vessel   gas     e The butyl membrane   e Replace the expansion vessel and refill the  inside the expansion pre  pressure according to the instructions  vessel is broken  in chapter 4 2 3 Pressure vessel     Other reason  e Faulty pressure sensor  e Compare the value from the pressure  gauge  PI11  with the value from the  pressure transmitter PT11  If the pressure  transmitter is broken it has to be replaced        Table 5 1 4  Pressure fault detection    24 hour support 4358  0 40 837 1150   Email  vacon vacon com       54   vacon    TROUBLESHOOTI NG       5 1 4 Leak alarms    If the leak alarm is active  acc  to panel below  the HX unit is still online and 
49. l ARNG eed ed aa LL d ase 38   3 3 9 Leak switch alarm specifications 3 35  4 sd addidi dido odd e 38   3 3 10 Three way valve   two way valve actuator settings                          see 39  STEP 24 ADI USTING THE FLOW  ooo 40   3 4 1 A eG e cette tie er LI ISI bd ae 40   3 4 2 Adjusting the system flow and setting the switch point of the FTSAT1                        41   3 4 3 Checklist before starting main NX drives                            eeeeeeeeeeeee 42   UNIT MAINTENANCE 5 ssupaiavins Ria ese QA has ventana Fee pibe a 44  GENERAL  MAINTENANCE o caen tcs tl dt He C eeepc e 44   4 1 1 Renewing liquid in the primary circuit                       eeeeeeeenemeeeeenene 44    Tel  4358  0 201 2121   Fax 4358  0 201 212 205    vacon   7       4 1 2 Maintenance schedule e oos o 44   4 2 MAINTENANCE BY COMPONENT    tot htt tt e i ea n EE I ai  44  4 2 1 ung o eR 44   4 2 2 Heat exchanger i544  000 od oo coda ob adobes 46   4 2 3 Pressure A dE 48   5  TROUBLESHOOTIN cemere riada et 49  LTEM en 49  5 1 1 Lear lA PR  o MIU QUID IO UU P a 49   5 1 2 Temperature alarms and Shutoffs          iet eite tei rarae teen su ta eee acto iei  50   5 1 3 Mode posce Eoi RO 53   5 1 4 Leak al aL IIIS usto ocius ia A CR AA EE D ERU T SEDE 54   6  TECHNICAL SPECIFICATION arman oa 55  APPENDIX Diana AAA AA ARA AAA AAN 57    24 hour support 4358  0 40 837 1150   Email  vacon vacon com       8   vacon SAFETY       1  SAFETY   This chapter contains the general safety instructions  which you must
50. lug on valve V160 and replace it with a hose connector     Place an eight  8  litre jar under the valve  if the expansion vessel air nozzle or membrane is  broken there might be up to 8 litres in the vessel      Turn the lever  marked violet in Figure 4 2 5  on valve V160 90   so that it poi  you  points towards the back wall   This will close off the     au      primary circuit and therefore only the liquid in the NO  expansion vessel will come out   There is line mark in the  end of the stem  where you can also ensure the right  position of the 3  way valve  This mark shows the open flow  direction      nts  M        away from  3        When the pressure vessel is drained check the pre   pressure with a portable pressure gauge  The air nozzle  can be found under the black rubber top on the vessel  The  portable pressure gauge should have a similar interface to  that used to fill a car tyre    Figure 4 2 5    The pressure can be added with a nitrogen tank  pressure over 2 bar  or if air is used then a  compressed air system or even a hand pump can be used     Refill pressure if necessary  The pressure should be 100 kPa  1 bar   Use nitrogen if possible   otherwise air can also be used     Reconnect the plug to valve V160  change the plug O ring if necessary     8  Turn back the lever on valve V160 90  so that it points down     10        The pressure in the primary circuit will decrease due to the water that is removed during this  process  Therefore water must be added thro
51. m flow and setting the switch point of the FTSA11     Do not energize the main drives before the HX unit has been running for 30 min without any  alarms  Refer to the Chapter 3 4 3  Checklist before starting main NX drives     Vacon Plc is not responsible for the use of its products contrary to these instructions     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       4   vacon       ABOUT THE VACON HX UNIT MANUAL    The Commissioning and Maintenance Manual provides you with the necessary information about the  maintenance and commissioning of a Vacon HX unit  We recommend that you carefully study these  instructions before powering up a Vacon liquid  cooled drive and HX unit for the first time     This manual is available both in paper and electronic editions  We recommend you use the electronic  version if possible  If you usethe electronic version  you benefit from the following features     e The manual contains several links and cross references  which make it easier for the reader  to move around in the manual  to check and find things faster     e The manual contains hyperlinks to web pages  To visit these web pages through the links   you must have access to the Internet and have an Internet browser installed in your  computer     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       vacon   5       VOCABULARY       Primary circuit     A closed circuit filled with coolant that connects the drive to the HX                 HXM120 PSO1 unit    Secondary ci
52. mally closed    Temperature switch  OFF  no temperature switch point used    Flow switch point  according to calculations in chapter 3 4 2  Adjusting the system flow and  setting the switch point of the FTSA11     3 3 6 Temperature set points    If the primary circuit temperature isn t set correctly the main drive might malfunction because of  condensation  The default setting of the parameter P3 5 in the HX control unit application is 25 C   This means that the 3  way valve adjusts the flow in the secondary circuit to keep the primary circuit  liquid temperature at 25  C  measured by the FTSA11 before the drives      There are three factors that will affect the nominal temperature of the primary circuit   e Ambient maximum temperature at the main drive installation  e Ambient maximum relative humidity at the main drive installation  e Secondary circuit maximum temperature    All of these factors have to be taken into consideration when calculating the primary circuit  temperature set point   e If the humidity is high  condensation will occur in the piping inside the main drives and  therefore cause a malfunction   e If the ambient temperature is too high the load of the drive must be reduced   e And if the customer and or end user have an existing cooling system  which is going to be  connected to the secondary circuit  the temperature of this circuit might be the deciding  factor     The primary circuit temperature is individual for every project  Here are three examples th
53. minimum  28  C  26  C 2  C                                                                       Figure 3 3 3 Example 1    The secondary circuit maximum temperature should always be 5  C lower that the primary circuit  temperature to ensure a good thermal load transfer between the two circuits  In example 1 this  means that the secondary circuit should be between  5   423  C during operation  The 3  way valve in  the secondary circuit will then keep the primary circuit temperature at 28  C regardless of the main  drive load     Example 2  high ambient relative humidity   If the customer and or end user have a high ambient temperature  40  C  at the main drives that  would require the primary circuit temperature to be equal or higher than 40  C  This would normally  require a significant load reduction of the main drive  If the maximum relative humidity at the main  drive is known  the dew  point chart can be used to determine a more optimized temperature for the  primary circuit     Ambient temperature  40  C    Maximum relative humidity  80   Acc  to chart 3 3  1 gt  Dew point is  36  C    24 hour support 4358  0 40 837 1150   Email  vacon vacon com       34   vacon COMMI SSI ONI NG       It is recommended to use a 2  C safety margin  Therefore the primary circuit temperature should in  this case be set to 38  C  36  C  2 C   Using a 38  C temperature  instead of 40  C  on the primary  circuit will reduce the required load reduction of the main drive  For more information re
54. mp from the HX unit  Note the pump weight is  about 50kg  It is recommended that there are two persons  present when the pump is removed           10  Perform the necessary maintenance on the pump and  reconnect the pump to the pump housing  Or simply replace  the pump if a spare pump is available     11  Connect the electrical cables to the  new  pump motor   12  Open the maintenance valves V140 V143     13  Refill and de air the pipes according to the instructions in chapter 3 1 5 and 3 1 6   Figure 4 2 1       There are replacement parts available if there is a leak  e g  shaft seal   or if the pumps are not able  to keep sufficient pressure  Refer to the technical specifications of the pump for the replacement  parts  The specifications can be found in the end of the Commissioning and Maintenance folder that  is supplied with the HX unit     4 2 2 Heat exchanger    The heat exchanger does not need regular service  If the primary circuit temperature is too high   high temperature alarm is active  and the 3  way valve directs all the liquid through HX11  by  pass  line closed   the flow is too low in one of the circuits or the temperature in the secondary circuit inlet  is outside the defined parameter values  If the flow in the secondary circuit is too low  there may be  some biological residue clogging the heat exchanger     Because the primary circuit is filled with clean liquid  it is unlikely that the primary circuit s side of  the heat exchanger clogs  Refer to the he
55. n     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       28   vacon COMMI SSI ONI NG       3 3 3 Parameter description    The table 3 3  1 includes parameters made to monitor and control the HX unit  This chapter includes  short explanations on what the different parameters are used for     P2 10 1 is the actual frequency that the pump motor will run at when producing the required flow in  the system  The speed of the pump frequency should be optimized according to the required flow   see Chapter 3 4 2  Adjusting the system flow and setting the switch point of the FTSA11   This will  reduce the wear of the cooling system and therefore extend the MTBF  mean time before failure  of  the HXM unit and the main drives     Changes   Customer     Parameter Parameter description Default Custom   code setting settings  P2 10 1   Frequency to PU11 when PID 50Hz  enabled  pressure setting  scaling  P2 10 3 PT11 pressure transmitter 10 bar  high pressure setting  scaling  pressure alarm  P2 10 5 Inlet pressure supervision  P2 10 6 FTSA11 temperature  transmitter low temperature  setting  scaling  P2 10 7 FTSA11 temperature 100   C  transmitter high temperature  setting  scaling    low temperature alarm   high temperature alarm   high temperature shutoff   sequence time  P2 10 12  ZE  P2112  P2 11 3  P2 11 4  P2115  P2 11 6  P2 11 7    P2 11 8 Fieldbus outlet 7  P3 5   FV11 reference temperature 5    Table 3 5 1  Parameter list       N ul Hie N  RP U Oje  Y Ald Uli o  M O 
56. nit  If the pipes have been welded with a TIG it is  sufficient to clean the pipes by blowing pressurized air through them  If the welding has been done  by other means the pipes have to be thoroughly flushed with water at a minimum of 3 m s for 5  minutes     3 1 4 Pressure test    A pressure test has already been performed on the HX  unit before delivery but because some of the  connections are made on site  additional pressure testing is required  The pressure test performed  on site should be done according to EU directives or national regulations  whichever has priority on  site     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   21          The safety valve V120  marked orange in Figure 2 2  3  in the primary circuit is  set to 6 bar and has to be removed during the pressure test  The V120 valve  connection must be plugged during this pressure test    During the pressure test the de airing valve AD11  Figure 3 1 7  has to be  closed  The threaded top plug must be replaced with tight plug or add an extra  seal under the top plug  After the test change back the originally plug  tighten to  end and then open 360 degrees     NOTE                To ensure that every site connection is sufficiently tightened  it is recommended that a  pressure test be performed for the primary circuit using pressurized air  The  pressurized air can be added through the liquid filling point of the unit  e g  at valve V161  in the primary circuit     Figure 3 1  7
57. ntrols the temperature of the primary  circuit  The valve is regulated by an analogue temperature  signal delivered by the flow switch FTSA11  The main function  of the valve is to adjust the flow through the plate heat  exchanger  HX11  in the secondary circuit  and thereby control  the temperature in the primary circuit  By reducing the flow  through the heat exchanger  the primary circuit s temperature increases  and vice versa        The default valve regulation set point is 430 C  If the temperature drops below the set point  the 3   way valve starts to reduce the flow through the plate heat exchanger and directs more liquid through  the bypass  Keeping the temperature as high as possible in the primary circuit  with regards to the  type and load of the main drive  lowers the risk of condensation inside the drive cubicle    Figure 2 2 4    24 hour support 4358  0 40 837 1150   Email  vacon vacon com       14   vacon   NTRODUCTI ON       22 3 Control unit    The frequency converter  Vacon NXP series  Figure 2 2 5   works as a control supervision unit for  the primary circuit s temperature and flow  and adjusts the frequency of the cooling pump motor   PU11 12   The frequency converter is programmed to read the I O signals from the flow switch   FTSA11   pressure sensor  PT11  and leak switch  LS11      Information on the alarms and how to calculate their limits is found in chapter 3 3  STEP 3  CONTROL UNIT SETUP  Information on how to modify the control unit  parameters c
58. ny chemical residue that might be harmful for the  material used in the HX unit e g  high amounts of chloride  chlorine  oil etc  The HX unit with the  PVC C pipes uses EPDM rubber seals that will deteriorate if they come in contact with oil     2 3 2 Required ambient conditions    The HX  unit is designed to work within ambient temperatures between 45   450 C  It is the customer  and or end user s responsibility to ensure that the temperature remains within this limit during  operation  The HX unit is not built to withstand rain  sand  or snowstorms  If the HX unit is  positioned outside it must be placed inside a cubicle that is equipped with temperature and humidity  control     There is no condensation allowed in the main drive  As the primary circuit piping is located inside the  same cubicle as the main drive it is vital that the primary circuit water temperature doesn t go below  the dew point temperature  The primary circuit temperature is set accordingly to ambient  temperature and relative humidity  The most secure way of preventing condensation inside the main  drives is to keep the water temperature in the primary circuit higher than the ambient temperature     If the temperature in the drive room is higher than the temperature of the liquid in the primary  circuit piping it can  depending on the relative humidity of the air  cause condensation on the piping  as well as inside the drive     A dew point chart can be used to optimize the primary circuit minimum temp
59. o o O   E  rm    P2 10 2 is the min  value of the range of the pressure transmitter PT11  It is used to scale the  pressure transmitter  PT11  low pressure point  The PT11 has a min measure point at O bar     Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   29       P2 10 3 is the max  value of the range of the pressure transmitter PT11  It is used to scale the  pressure transmitter  PT11  high pressure point  The PT11 has a max measure point at 10 bar     P2 10 4 is a PT11low temperature  alarm limit  The default setting for this is set at 0 5 bar  More  information can be found in chapter 3 3 8  Low  pressure alarm     P2 10 5 is a selection parameter that should be set to 1  If the PT11 pressure transmitter  malfunctions the parameter can be set to O therefore overriding the pump suction side pressure  supervision  The pressure transmitter MUST BE REPLACED as soon as possible  the warranty is not  valid if this parameter is set to    0        P2 10 6 is the min  value of the range of the temperature transmitter FTSA11  It is used to scale the  temperature transmitter  FTSA11  low temperature point  The FTSA11 has a min measure point at  0  C     P2 10 7 is the max  value of the range of the temperature transmitter FTSA11  It is used to scale the  temperature transmitter  FTSA11  high temperature point  The FTSA11 has a max measure point at 100  C     P2 10 8 is a FTSA11 low temperature  alarm limit  The default setting for this is set at 22  C
60. ominal required flow   10   The nominal  flow for a Ch74 is 315 l min  therefore the switch point should be set to 283 l min  315 x 0 9    From the Diagram 3 4 1 we can establish that 283 l min corresponds to 70  on the FTSA11   Information on how to modify the switch point of the FTSA11 is found in chapter 3 3 5  FTSA11  flow switch function    e Ifthe actual flow goes under 65   set point 70    5  hysteresis   the FTSA11 flow switch will  open the switch  when the FTSA11 is set to    normally closed     N C   If the alarm disappears  within 5 seconds  the control unit application filters out the alarm  If the alarm is still active  after 5 seconds  the  cooling OK  signal to the drives is disconnected  and both the HX unit  pump and the drives shut down     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       42   vacon COMMI SSI ONI NG                               D   o  o   gt   S  o  um   o     T   lt   o  LE  LL                      200    Flow  l min       Diagram 3 4  1 Converting table for the FTSA11 flow switch  PVC  C     Converting formula for the FTSA11 flow switch     HXM  120 AISI  x 5  y  147   where y  FTSA11 display      x  flow l min  HXM  120 PVC C  x  5  y  60   where y  FTSA11 display        x  flow l min    3 4 3 Checklist before starting main NX drives    After the de airing  when the control unit setup and the flow adjustment are performed and the HX   unit has been running for 30 minutes without any alarms  the main drive can be brough
61. ondary circuit temperature   If the customer has an existing cooling system that delivers liquid at a temperature of 40  C then the  primary circuit temperature has to be 5  C warmer to maintain a sufficient heat transfer between the  primary and secondary circuit  This means that the primary circuit temperature cannot be colder  than 45  C  This results in a significant reduction of the main drive load  In this case the only way of  increasing the load of the main drive is to lower the temperature in the secondary circuit by  installing additional coolers or a new cooling system with a lower water temperature  Next the dew  point must be checked     Secondary circuit maximum temperature  40  C   Primary circuit maximum temperature  40  C  40  C 5  C   Ambient temperature  30  C   Maximum relative humidity  95     Because the ambient temperature is beneath the primary circuit temperature there is no risk of  condensation in the main drive     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       36   vacon COMMI SSI ONI NG       Maximum ambient temperature  30  C  Maximum ambient relative humidity 9596       02 03 04 05 T  VACON LIQUID COOLED NX DRIVE HXM120     mum  o     o                                                                      m Secondary circuit  E o Q    hb maximum  40  C    g                                                                                              Primary circuit minimum  45   C  40  C 5  C                                   
62. ose     3 4 2 Adjusting the system flow and setting the switch point of the FTSA11    The pump flow should be adjusted according to the required flow of the connected drives  Before  adjusting the flow  the primary circuit has to be correctly filled and de aired  The target flow can be  calculated by adding up the nominal flow for the main drives connected to the HX unit  For  information on how to calculate the optimum system flow see the example below  To adjust the  system flow     1  Start up the pump and run it at 50 Hz  which is the default value in the HX control unit  application     2  Check the actual flow speed in percent from the flow switch FTSA11 and convert it into l min  by using the flow speed diagram 3 4  1 or by using the converting formula     3  Adjust the frequency of the pump to match the required total nominal flow   10   see  example      Example  If you are using 3 x Ch74 drive  the nominal flow according to the NX Liquid drive manual  is 315 I min  The flow should then be set to    nominal flow    x 10     e Adjust the flow to 346 l min  315 x 1 1  that is 80  according to Diagram 3 4 1  by changing  the frequency parameter P 2 10 1 in the    Flow control    part of the control unit application  The  default value of the parameter is 50Hz  Reduce the frequency by 2 Hz at a time until the  FTSA11 display shows the value  80   The value shown on the FTSA11 is somewhat  irregular in the beginning    e The setting point for FTSA11 should be set at the n
63. ote that this diagram is correct only when using the  FTSA11 high measuring range  30 300 cm s  and the original pipe inner  diameter        This flow meter is suitable for concentration of maximum 25  glycol  75  water      Figure 2 2 6    The other instruments found on the HX unit are a pressure transmitter  PT11  and a pressure gauge   PI11   The pressure transmitter sends a 4   20mA signal to the HX control unit  The control unit  application then converts this signal into pressure  bar   This pressure input is then used to  monitoring the pump inlet pressure  The idea is to give the user an early warning in case there is a  leak in the primary circuit somewhere outside of the HX unit  The pressure gauge is used when  filling the primary circuit with liquid or when performing a pressure test on the unit  It can also be  used to get a pressure reference value if the pressure transmitter is thought to be malfunctioning     Tel  4358  0 201 2121   Fax 4358  0 201 212 205         NTRODUCTI ON vacon   15       2 2 5 Control   supervision parameters    When the HX unit is working within the pre set limits  it sends a  cooling OK  signal to the main  drives  The HX unit supervision system is programmed to generate alarms to alert the user to a  malfunction in the unit  If the malfunction is more severe  the control unit removes the  cooling OK   signal to the main drive and takes them offline    The project  specific minimum flow speed is to be set as switching point for the flo
64. penetration is made according to IP54  requirements        Figure 3 1 4 Figure 3 1 5    If the HX unit isn t placed in the same line up as the drives  therefore creating piping between the  HX unit and the main drives  the pressure loss of the piping between the HX unit and the drive must  not exceed 0 7 bar  If the calculated pressure loss is higher than 0 7 bar then the HX unit will not be  able to produce the maximum flow of 360 l min that is specified for the HXM120  If the 360 l min is  required for the installed main drives  e g  one Vacon 3xCh74  but the HX  unit has to be placed at a  point were the calculated pressure loss  for the added piping  is more than 0 7 bar it is  recommended that two units is used instead       or 1 I i   I 93     va    15 l                            HXN  AZG                can can        a a  L HH Secondary circuit  E olo E ojo l M inlet outlet  S  0                          Additional piping between  HX unit and the main drives                                                                                                    Figure 3 1 6    If the HX unit is delivered as a part of NX Liquid Cooled switchgear  therefore being in the same line   up  then the connections between the HX unit and the drive are ready and the customer only needs  to connect the secondary circuit piping     3 1 3 Pipe flushing    All piping in the primary or secondary system made by the customer and or end user must be  flushed before being connected to the HX u
65. rameters for the Fieldbus  Profibus  output  The customer and or end user can  choose any 8 of the NXP 0009 parameters to be sent out to a higher control system for external  monitoring  The default values are as follows     P2 11 1  Primary side temperature from FTSA11    C   P2 11 2  HX pump motor speed  rpm    P2 11 3  HX pump motor current  A    P2 11 4  Primary side pump inlet pressure  bar   P2 11 5  Output frequency to HX pump motor  Hz   P2 11 6  Motor torque as 96   1000 equals 410090   P2 11 7  Motor shaft power in 96  1000 equals 100    P2 11 8  Fault  trip  history    24 hour support 4358  0 40 837 1150   Email  vacon vacon com       30   vacon COMMI SSI ONI NG       P3 5 is the FV11 actuator reference temperature  Default value is 25   C  This value is the liquid inlet  temperature value to the main drives  More information can be found in chapter 3 3 6 Temperature  set points        Only an authorized person is allowed to make changes to the parameter  settings  If the drive or HXM unit is malfunctioning or if they break due to a  customer and or end user parameter setup error the warranty is not valid              NOTE       3 3 4 General information about alarms and shutoff limits    Apart from the standard NXP frequency converter alarms  found in the Vacon NXP User s Manual   the HX unit application can generate alarms or shut  offs from one flow switch  FTSA11  with a built  in analogue temperature transmitter  a pressure sensor  PT11  and one leak sensor  L
66. rcuit  A circuit filled with coolant that connects the HX unit to the   HXM120 PS02 customer piping    HX unit HXM120 cooling unit  see the front picture of the manual   The  ordering code for the unit on the front page is HXM  M  120  N  S  but  itis referred to as HXM120 or just plain HX unit for short    Drive Liquid cooled frequency converters or inverters that are connected  to the HX unit    Main drive A term used in some contexts for the Vacon NX liquid Cooled    converters so that they are more easily separated from the air   cooled Vacon NXP 0009 used in the HX unit  The main drive concept  might also include other liquid cooled electrical equipment        HX control unit          The air  cooled NXP 0009 drive that is placed inside the HX unit for  the purpose of controlling and monitoring the primary circuit pump  and instruments        24 hour support 4358  0 40 837 1150   Email  vacon vacon com          6   vacon       2 3    3 1    3 2    3 3    3 4    4 1       SAFETY qme                                               P 8  USE OF SYMBOLS O p d cay 8  GENERAL WARNINGS AND NOTES WHEN WORKING WITH THE HX UNIT nsee 9   INTRODUCTION       cecindeexxr us c eorr ee AA e e c 11  ABOUT THIS  MAN UAL aes wa ca c ito ot EUER eL te ene oU eec AAA oe LO don eee  Qe etus 11  PROCESS ANDINSTR  NMEN EATION   1  itas a dtt ttt tte tutatus 12   2 2 1 Primary circuit components and TUPGBOD s soot 13   2 2 2 Secondary circuit components and function                        sse 13   
67. re  pressure and leak supervision  The HX control unit  application monitors these quantities  The application generates alarms or shut offs from the  instrument s I O  input output  signals depending on the parameter settings  The HX control unit  interface panel allows the user to access these settings  The settings are found as editable  parameters in the HX control unit application  Apart from the leak sensor  LS11  which is placed on  the HX unit floor  all instruments are placed in the primary circuit  Therefore the temperature and  flow monitoring in the secondary circuit is the responsibility of the customer and or end user     Tel  4358  0 201 2121   Fax 4358  0 201 212 205         NTRODUCTI ON vacon   13       2 2 1 Primary circuit components and function    The primary circuit is a closed circuit with an expansion vessel  EV11  blue part in Figure 2 2  3  that  compensates for temperature changes  The primary circuit flow and temperature must match the  requirements of the drives that they are connected to  These requirements can be calculated by  following the instructions in the Vacon NX Liquid Cooled Drive User s Manual     As mentioned earlier  the system includes a plate heat exchanger  HX11  copper grey colour in  Figure 2 2 3   This unit separates the primary circuit from the secondary circuit so therefore it is  actually a part of both the primary and the secondary circuits  On  top of the HX11 is the automatic de  airing valve  AD11  violet part  in Figure
68. rimary  bar  circuit by adding liquid through valve  V161   e Thereis aleak in the e Check the primary circuit for leaks  If a  primary circuit  leak is found the unit must be drained  and the leak fixed before the unit is  restarted   The pump isn t e A valve in the primary  e Check if any of the following valves in  delivering enough circuit is closed  the primary circuit is closed  refer to  pressure i e  the flow the P amp ID    is too low  V140  143  V310    3xx  Any valves in the primary  circuit added by the  customer    The FTSA11 is set e The flow requirement  e Check the current flow requirements   incorrectly  this is a has changed after the they might have changed if e g  a  fault that is most commissioning stage  converter is taken offline  and its  likely to appear during valves closed  because of  maintenance or at the maintenance        24 hour support 4358  0 40 837 1150   Email  vacon vacon com       50   vacon TROUBLESHOOTI NG       commissioning stage      e Check the required flow values for the  converters and readjust the alarm set  point on the FTSA11  refer to chapter  3 4 2 Adjusting the system flow and    setting the switch point of the FTSA11      The FTSA11 setup  values have been poorly  adjusted during  commissioning        Table 5 1  1  Flow fault detection    5 1 2    If the high temperature alarm is active  acc  to panel below  the HX unit is still online and the   Cooling OK  signal to the main drive is connected  The yellow and green indica
69. signal to the drive is disconnected  The default setting for this  parameter is 45 C     The leak switch s sensor  LS11  is located on the leakage plate at the bottom of the HX unit  The  function of the switch is to give a signal to the HX control unit  in case there is liquid on the leakage  plate  The liquid can be from a leak in one of the circuits  or from condensation on colder pipe  surfaces due to high relative humidity of the air        The HX unit provides no control of the temperature or flow in the secondary  circuit  It is strongly recommended that the customer and or end user add a  temperature and flow control on the secondary circuit piping outside the HX   NOTE unit                 Depending on the quality of the secondary circuit liquid  the plate heat exchanger might clog and  affect the efficiency and flow of the unit  Because the primary circuit is a closed circuit  it contains  only a small amount of liquid  This means that it will react fast to changes in temperature or flow in  the secondary piping        If the flow for some reason is shut down in the secondary circuit  the HX unit will  disconnect the  cooling OK  signal to the drive within seconds  depending on the  main drive load  due to a high temperature shutoff              NOTE       If there is no monitoring equipment in the secondary circuit  it is harder to determine the reason for  a possible alarm from the HX unit  Secondary circuit flow  or pressure difference  and temperature  monitorin
70. t online  If  there is more than one converter  it is recommended that they be started up one by one to avoid any  sudden changes in the temperature  The load of the drives should also be increased step by step   otherwise the temperature might change too fast and cause an alarm  or in the worst case  a drive  malfunction     Before starting the drives     1  Check that the HX unit flow and temperature are within the given parameter values  no  alarms      Tel  4358  0 201 2121   Fax 4358  0 201 212 205       COMMI SSI ONI NG vacon   43       2  Check that there is no air left in the plate heat exchanger by carefully opening the manual  de airing valve V162 and letting out a small amount  about 1 centilitre  of water     3  Checkthat the PI11 pressure gauge is at about 1 5 bar   Check that the maintenance valves to the converters  in use  V310   V31x are open     5  Check that the flow  refer to FTSA11 converting table above  is according to the connected  converter requirements     Check that the primary circuit temperature is according to the setup value     Check that there is no condensation in the main drive cubical  If there is condensation inside  the drive cubicles  the drives must be dried out before start  up     After successfully performing the different steps of commissioning presented in chapter 3  the HX   unit and the connected drives are ready to be moved from the commissioning stage to operation  mode  Troubleshooting information and unit service information
71. the  Cooling OK  signal  to the main drive is connected  The yellow and green indicator lights on the electrical box door are  also active  Check the following issues to solve why the alarm has been activated     F1     51 External Fault  F  F1 gt  F125    Figure 5 1 5  Leak alarm on the NXP panel       Malfunction Reasons for malfunction   Correction measures    Leak e Loose connection  e    e Faulty connection     Condensation e The secondary circuit  liquid temperature is  too low in regard to the  ambient temperature  and relative humidity     Other reason No condensation or  leak is found but the  alarmis still active     Figure 5 1 5  Leak fault detection       Tighten the connection until the leak stops   Add liquid to the primary circuit until the  correct pre pressure is reached  Follow  the instructions in chapter 3 1 6  Adding  liquid and de airing    Replace the broken parts  Then add liquid  to the primary circuit until the correct pre   pressure is reached  Follow the  instructions in chapter 3 1 6  Adding liquid  and de airing    If the cooling process allows it then  increase the secondary circuit inlet liquid  temperature until the condensation stops   Decrease the humidity or the temperature  in the cubicle until the condensation stops   If there is condensation on the secondary  circuit piping  insulate the secondary  circuit pipes and the plate heat exchanger   HX11    Try resetting the alarm on the reset  switch  It is the push button in the lower  right 
72. the secondary  circuit flow through the plate heat exchanger  HX11  by adjusting the 3  way  valve actuator  FV11  to match the temperature setup value for the primary  circuit  This temperature setup value is project specific and is adjusted at  commissioning  The temperature setup value is dependent on the ambient  temperature in the drive cubicle and on the maximum temperature of the  customer inlet liquid  The calculation of this value is explained in chapter  3 3 6  Temperature set points                 Figure 2 2 1    HXM120  COOLING UNIT FREQUENCY  CONVERTERS                          pice cnc eH   exis rir ae po l   EE EDD M ECCE Cic S a vc AES E                 l                                                                                             f      l l       ga amp  l A    MEE       CUSTOMER               PSOB 1  Secondary circuit    NET DSS H 2 HX_120 PS01 2  Primar Evi   M AS EC PNE        E OPTION  AIR COOLER        amp  l      Vi6e HXAM ll   n AI E l     ata puie   E qu     I i   iee Vial VI  I Vi43 n      OPTION  SHUTOFF VALVE QO I   L4     4 FILLINGS   AH 3 E T   CUSTOMER    V205   MA   Viab ido SN vite osos CSS             mecoc0k     Ji  BUTLET          e PULL DRAIN        E a HXM120 PSOI 1   i           PS02 2 IDRAIN       i i i          Figure 2 2 2 Piping and instrumentation diagram  P amp ID     A larger P amp ID is found in the Commissioning and Maintenance folder that is supplied with the unit     The HX unit is equipped with flow  temperatu
73. the unit is fixed according to requirements  The HX unit  should be fixed to the cubicle frame with suitable and robust  supports to prevent the unit from moving or being damaged by  vibrations        The HX unit can be fixed to a floor or a wall by itself  The frame  that the unit is built on is self  supporting  If the unit is installed  without an additional cubicle  e g  VEDA or Rittal  it must be  positioned in a non hazardous area where it can t pose a threat  to any main systems or persons  If required  e g  by national  regulations or generally acknowledged safety standards  additional protection must be added to the  unit  e g  warning signs or additional protective gear        Figure 3 1 1    3 1 2 Pipe connections    Standard connections are DN50 flanges according to  DIN2642  Flange adapters are delivered in a separate box   When placing the HX unit inside a cubicle it might be  necessary to remove also the 2  connector parts that are  screwed on to the pipes on the primary and secondary  connections  This is because the total width is about  716mm when the connectors are on  and the width  door opening  on e g   Rittals    800mm cubicle is 712mm   Figure 3 1 2 Figure 3 1 3       24 hour support 4358  0 40 837 1150   Email  vacon vacon com       20   vacon COMMI SSI ONI NG       The material of the primary circuit and secondary  circuit flanges is AISI 316  It is also possible to get  PN16flanges according to DIN 2633  AISI 304  to  secondary circuit     The wall 
74. tor lights on the  electrical box door are also active  Check the following issues to solve why the alarm has been    Temperature alarms and shutoffs    activated     F1   83 OverTempA    A 17137165    Figure 5 1 2  High temperature alarm on the NXP panel         Reasons for malfunction   The   customer filter   outside the HX unit  MF21   refer to the P amp ID  is  clogged    The plate heat exchanger  HX11  refer to the P amp ID  is  clogged on the secondary  side     Malfunction   The flow in the  secondary circuit is  too low     The customer pump in the  secondary circuit is  malfunctioning and  therefore not able to  produce enough flow   Maintaining the HXunit  cannot solve the reason for  this malfunction     The temperature of  the secondary circuit  liquid is too high          Correction measures  Clean the filter     Clean the heat exchanger  Refer to  the cleaning instructions found in  the HX unit folder that is supplied  with the unit  Instructions on how to  remove the plate heat exchanger  are found in chapter 4 2 2  Heat  exchanger    Maintain or replace the customer  circuit pump     The temperature of the liquid in the  secondary circuit inlet has to be 5  degrees lower than the primary  circuit temperature set point  e g  if  the primary circuit temperature set  point is set to 35  C then the  secondary circuit inlet temperature  must be 30  C or lower        Tel  4358  0 201 2121   Fax 4358  0 201 212 205    TROUBLESHOOTI NG vacon   51       The regulating
75. ugh the filling valve V161 until the pressure on  the pressure gauge  PI11  is back at 1 5 bar  Remember to de  air the filling hose before you  connect it to valve V161  otherwise the air in the filling hose will enter the unit during filling     Due to the small amount of liquid removed during this process it is not necessary to add any  corrosion inhibitor     Tel  4358  0 201 2121   Fax 4358  0 201 212 205    TROUBLESHOOTI NG vacon   49       5  TROUBLESHOOTING  5 1 Alarms and shutoffs    This chapter provides help in case the HX control unit activates an alarm or fault  An alarm or fault  is activated  because the HX unit is working outside the parameter settings in the HX control unit   The pre set parameters for the HX unit are shown in chapter 3 3 2  Application parameter list     5 1 1 Flow fault    If the flow fault shutoff is active  acc  to panel below  the HX unit pump has stopped and the     Cooling OK    signal to the main drive has been disconnected  The red indicator light on the electrical  box door is also active  Check the following issues to solve why the alarm has been activated     F1     87 FlowFault  F __F1 gt F1l gt     Figure 5 1 1  Flow fault on the NXP panel       Malfunction   Reasons for malfunction   Correction measures  The pre pressure is  e The pre pressure in the   e Check the EV11 pre  pressure and add  too low in the primary expansion vessel EV11 pressure if necessary   circuit  i e  below 0 5 has been reduced  e Add pre pressure to the p
76. unit is not working within correct parameter values  Either the  temperature has reached the high temperature shutoff limit or the flow is too low in the  primary circuit  This light also indicates that the    cooling OK    signal to the main drives is  disconnected  therefore the main drives are offline     e Yellow indicates that there is an active alarm in the HX unit  meaning that the HX unit is  working outside the optimal temperature and or pressure range or that there is a leak inside  the unit     e Green indicates that the    cooling OK    signal to the main drives is connected   e White indicators show which of the HX  pumps are activated during operation     The troubleshooting guide is found in chapter 5 TROUBLESHOOTING  If the yellow or red indicator is  active then you can find more information by accessing the HX control box interface panel   Information on how work the panel is found in the Vacon NXP User s Manual that is supplied with the  unit     Tel  4358  0 201 2121   Fax 4358  0 201 212 205         NTRODUCTI ON vacon   17       2 3 INSTALLATION SPECIFICATIONS  2 3 1 Liquid quality    In the primary circuit  the quality of the liquid has to be as presented in Table 2 3  1  Liquid quality   The liquid should not contain organic sediment or chemically active qualities  The liquid can be  treated with corrosion inhibitors suitable for AISI pipes  PTFE and Tesnit BA S seals  When adding  liquid to the primary circuit it is recommended that a filter be used so
77. urn out the HX11  Figure 4 2  4                  Figure 4 2 4    4  Replace the unit with a clean one  or clean the unit according to the manufacturer s  instructions found in the end of the Commissioning and Maintenance folder that is supplied  with the HX unit     5  Connect the clean unit in reverse order using the instructions above  Add liquid and de air  theunit according to the instructions in chapter 3 1 5 and 3 1 6     The manufacturer provides cleaning chemicals that improve the cleaning result  If the secondary  liquid quality is bad  itis recommended that these chemicals  and a reserve plate heat exchanger  be  kept in storage     24 hour support 4358  0 40 837 1150   Email  vacon vacon com       48   vacon UNI T MAI NTENANCE       4 2 3    Pressure vessel    If the vessel is pre  pressured with nitrogen  the vessel pre  pressure needs to be checked every  other year  If air is used as the pre  pressuring gas  it has to be checked once a year  In time  the gas  escapes through the butyl rubber membrane into the liquid circuit  and gas or air must be added   The pre  pressure can be checked without draining the primary circuit     It is recommended that this procedure be done during a yearly maintenance           DANGER    When performing maintenance work on a pressurized system generally  acknowledged safety standards  EU directives and national regulations must  also be followed  Use safety goggles              To check the pre  pressure     L  2     Remove the p
78. user cause a malfunction in the HX unit or the main  drive by neglecting the parameter setup instructions in this manual  the  warranty is no longer valid              WARNING       To modify the  Flow control  parameters one has to be able to use the NXP control panel   Information on how to operate the NXP control panel is found in the Vacon NX Liquid Cooled User s  Manual that is supplied with the HX unit     The control unit also includes a Fieldbus uplink card  Profibus   The customer can use this uplink to  get any of the Vacon NXP parameter values linked to a    higher    control system  By using this uplink  the customer can monitor the HX unit from an external interface at a chosen location  More  information regarding this uplink interface is found in the Vacon NX Liquid Cooled User s Manual  that is supplied with the HX unit     3 3 2 Application parameter list    The application parameters and their default values are shown in table 3 3  1  The project specific  parameters are calculated using the rules found in chapters 3 3 6 to 3 3 7  The values that are used  when setting up the HX unit during commissioning should be written down in the  Custom  settings   column  If the values must be changed at a later time the new value should be written in the last  column  Changes  customer   The parameters that must be edited at commissioning are marked  with a    in the table 3 3  1  More information about these parameters is found in chapter 3 3 3   Parameter descriptio
79. w and  temperature control to the secondary circuit  If the project specified  flow and temperature for the secondary circuit is not met the warranty  is not valid     Retain these operating instructions during the entire life cycle of the  HX unit     The HX unit should always be transported empty  that is  without  coolant  to prevent damage caused by low and high ambient  temperatures   Do not allow any force or vibrations to enter the unit through the  secondary circuit pipe connections or through the fixing points of the  HX unit  This will shorten the MTBF  mean time between failure  of the  HX unit   El If the HX  unit is purchased without a cubicle  place it inside a cubicle of  choice and fix the HX unit frame to the cubicle frame  If the HX unit is to  be without a cubicle  it should be fixed to a floor or wall   Always install a filter before the HX unit if the secondary circuit cooling  liquid contains particles larger than 2 mm  If the secondary circuit liquid  contains chemical or biological residue the MTTM  Mean time to  Maintenance  is significantly reduced due to clogging in the plate heat  exchanger inside the HX unit        Tel  4358  0 201 2121   Fax 4358  0 201 212 205         NTRODUCTI ON vacon   11       2    INTRODUCTION  2 1 ABOUT THIS MANUAL    This manual provides information on commissioning and maintenance issues of the HXM120 cooling  unit  The manual is intended to be used by Vacon s own personnel as well as the customer and or  end user     To
80. w switch FTSA11   The flow switch sends a digital signal to the HX control unit  if the flow speed drops under the preset  parameter values  If the signal is active longer than 5 seconds  the HX control unit disconnects the   cooling OK  signal to the drives  This fault  fault number F87  also stops the HX  unit pumps     The flow switch FTSA11 also sends out a temperature signal that controls the 3 way valve in the  secondary circuit  The FTSA11 sends out a 4   20mA signal  which is then sent to the actuator  FV11   on valve V130     The temperature parameters are adjusted at commissioning  depending on the maximum  temperature of the inlet secondary circuit liquid and the ambient temperature in the main drive  area  If the temperature drops below the set point in the primary circuit  the valve on the secondary  circuit decreases the amount of liquid going through the plate heat exchanger  HX11  in order to  increase the temperature in the primary circuit     The temperature signal from FTSA11 also generates low  and high temperature alarms and high   temperature shutoff  The high temperature alarm and shutoff functions protect the main drives  from overheating  and the low temperature alarm protects the main drives from condensation     If the temperature goes above the high temperature shutoff limit  the    cooling OK  signal to the drive  is disconnected  In this case  the HX unit cooling pump continues running  but the main drive is shut  down  that is  the  cooling OK  
81. y val ve and    WARNING therefore causing a leak  If this happens the safety valve must be cleaned                 8  Repeat this procedure until every frequency converter inverter is de aired  that is  open the  valve V312 and V313 next and so on     9  After all the main drive hoses have been de aired and closed  open valve V140   V141 and  then open the filling valve V161  After no more rattling can be heard due to air in the system   close valve V162  the manual de airing valve     10  When valve V162 is closed the pressure  see at the PI11  pressure indicator  will start to rise  in the primary system  When the pressure in the primary system has raised to two  2  bar  close the V161 filling valve  If you are using an external pump for adding the water it can now  be turned off     11  Keep the two  2  bar pressure for about 10 minutes  letting the air bubbles in the system rise  up to the HX11 heat exchanger  Then open the manual de airing valve V162 to let the  pressure back down to 1 5 bar  Close valve V162     12  Now the system is almost completely de aired  After this the pumps must be run for short  periods to get the rest of the air out from the HX unit  Refer to chapter 3 4 1 Starting the  pump for more the rest of the de airing instructions     The pre  pressure in the primary circuit should be set to 1 5 bar  During operation the pre  pressure  should be between 1 0 to 1 5 bar  If the pre  pressure is reduced to below 1 0 bar during operation  liquid must be ad
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Advantech IDK-2117 User Manual  ICY BOX IB-330STU3-B storage enclosure  Getac V100 User Guide Manual Operating Instructions  1768-PA3, 1768-PB3 Fontes de alimentação CompactLogix 1768  Velodyne Acoustics CHT-10R Speaker User Manual    Copyright © All rights reserved. 
   Failed to retrieve file