1. 2 Adjust each foot until the equipment is level and plumb ns2004a NetShelter SV User Manual 7 Joining Cabinets Cabinets can be joined with or without side panels installed to provide for alignment and some stability The cabinets are shipped with pre installed joining brackets for 600 mm centers To join on 24 in centers the cabinet is provided with 24 in joining brackets in the hardware bag A WARNING TIP HAZARD Joining cabinets provides limited stability Ensure the cabinet is secured to the floor before installing equipment Failure to follow these instructions can result in serious injury or equipment damage 1 Remove the front and rear doors 2 The cabinet is preinstalled with 600 mm centers To join with 24 in centers replace the preinstalled joining brackets with 24 in joining brackets provided in the hardware bag 3 Align the cabinets and join them using one M5 x 12 flat head screw provided in the hardware bag per bracket two brackets for the front and two brackets for the rear 4 Reinstall the doors ns2005a 8 NetShelter SV User Manual Secure the Cabinet NOTICE Bolt down brackets secure the cabinet to the pallet during shipment Remove them from the cabinet and pallet and save them to secure the cabinet to the floor during installation A WARNING TIP HAZARD Secure the cabinet to the floor before installing equipm
2. 2 040 in 1 334 498 mm 2 069 in 27 422 mm 42 5 in 27 802 mm 43 1 in 69 4 open area 76 990 78 096 14 0 mm 0 6 in 1000 kg 2 205 Ib 460 kg 1 014 Ib 45 kg 99 Ib To move the cabinet on its casters the equipment load must be evenly distributed and must not exceed 460 kg 1 014 Ib and equipment must not be installed above the 20 U height NOTICE It is prohibited to ship a NetShelter SV cabinet while the unit is loaded with any equipment NetShelter SV User Manual 23 Limited Factory Warranty The limited warranty provided by Schneider Electric in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business Terms of Warranty Schneider Electric warrants its products to be free from defects in materials and workmanship for a period of five years from the date of purchase Its obligation under this warranty is limited to repairing or replacing at its sole discretion any such defective products This warranty does not apply to equipment that has been damaged by accident negligence or misapplication or has been altered or modified in any way Repair or replacement of a defective product or part thereof does not extend the original warranty period Any parts furnished under this warranty may be new or factory remanufactured Non transferable Warranty This warranty applies only to the original
3. 81 0 in Width 600 mm 23 6 in 800 mm 31 5 in Depth 1200 mm 47 2 in 1000 mm 39 4 in Net weight 121 3 kg 267 4 Ib 126 7 kg 279 3 Ib Total open area front door 778 176 mm 1 206 in 1 137 330 mm 1 763 in Total open area rear door 805 637 mm 1 2492 1 171 657 mm 1 816 in Open area per U front door 18 528 mm 28 7 in 27 079 mm 42 0 in Open area per U rear door 19 182 mm 29 7 in 27 897 mm 432 in Perforation pattern 69 4 open area 69 4 open area Perforation pattern front door 69 3 75 8 Perforation pattern rear door 71 7 78 0 Clearance for wiring between front door and 14 0 mm 0 6 in 14 0 mm 0 6 in vertical mounting flange Weight rating static leveling feet load 1000 kg 2 205 Ib 1000 kg 2 205 Ib Weight rating dynamic casters load 460 kg 1 014 Ib 460 kg 1 014 Ib Weight rating cabinet roof cable load 45 kg 99 Ib 45 kg 99 Ib T To move the cabinet on its casters the equipment load must be evenly distributed and must not exceed 460 kg 1 014 Ib and equipment must not be installed above the 20 U height 20 NetShelter SV User Manual 42 U Cabinets continued AR2480 AR2580 Height 2057 mm 81 0 in 2057 mm 81 0 in Width 800 mm 31 5 in 800 mm 31 5 in Depth 1060 mm 41 7 in 1200 mm 47 2 in Net weight 130 5 kg 287 7 Ib 139 5 kg 307 5 Ib Total open area front door Total open area rear door Open area per U front door Open area per U rear door Perforatio
4. e 6 Tools provided 0 cece eee eee eee eee eee eee 6 Tools not provided cece eee eee eee eee eee 6 Cabinet Installation encre rennen Moving the Cabinet 020 x K e 7 Level the Cabinet eee c e e RR ERREUR wate C4448 Cave eh aC 7 Joining Cabinets sss kara E er at ee R UE Ra e Dd PI edd 8 Secure the Cabinet eelleeee enne 9 Ground the Cabinet e e ee 9 Bonding Location on the Cabinet 9 NetShelter SV User Manual Customize the Cabinet ences Reverse the Front Door 000 e eee eee ees 10 Side Panels 225294 Seo NRT ute ux eee RR N ewe ee 12 Remove and install side panels lesse 12 Real DOOS s e Xe 7 0 6 Ue ak C RRR AURORA eens e 12 Removal a a a eeu itu ane aerate te m mime lE RS 12 Installations url ko ace A 7 R ee erroe e pete 13 Equipment Installation Adjust Vertical Mounting Flanges eeseeee 14 Installation 4 Aes 2227 ear R S Ta CESC TR RRR TRT Oa 15 Installing Equipment leeren 17 Vertical Mounting Flange Cutouts sisse 17 Cable Management eeeeeee eren Adjust Vertical 0 U Accessory Mounting Brackets 18 SDecifICatlOlis teo ea ie eco eoe te eco de Go doctae oce 42 0 G biniels 5 0 o
5. granted herein are reserved No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information This publication shall not be for resale in whole or in part Please Note Electrical equipment should be installed operated serviced and maintained only by qualified personnel A qualified person is one who has skills and knowledge related to the construction installation and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved No responsibility is assumed by Schneider Electric for any consequences arising from the use of this material Contents DiSclalifier ovi ra EX aa eee ne RW e waa hac aqux he EN 1 Please N te ie sie Sa RT RENER I ER ERI M Raw RR 9 8 1 General Information eese rennen nnns Introduction unis ue dcn a ori alate aren ace id te a ae ee ee 1 Safety rars esi eae ee en hea da dacs eee hae oan kapoor 2 Important Safety Information x x K K x K K KK 2 Receiving and Unpacking INSPECIION bone zo ELTERN Eee E eRe Ree eee ee eee E kas 3 Please Recycle eseeeeeeeeeee nnn nnne 3 Moving the Equipment eeeeeeeesesessesrse 3 Unpacking cus eis ea we rack a Rr ko ee hao Rx Rn 4 Component Identification Equipment Installation Hardware
6. the instructions are not followed This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death ADANGER Indicates an imminently hazardous situation which if not avoided will result in death or serious injury A WARNING Indicates a potentially hazardous situation which if not avoided can result in death or serious injury A CAUTION Indicates a potentially hazardous situation which if not avoided can result in moderate injury NOTICE Addresses practices not related to physical injury including certain environmental hazards potential damage or loss of data NetShelter SV User Manual Receiving and Unpacking NOTICE Schneider Electric is not responsible for damage sustained during shipment of this product Inspection Upon receipt inspect the package and contents for damage Verify the contents are complete Report missing contents damage or other problems immediately to Schneider Electric or your Schneider Electric reseller Keep all packaging for inspection if damage is found Please Recycle The shipping materials are recyclable Save them for later use or dispose of them fs appropriately Moving the Equipment Recommended tools for moving the equipment while it is still on the pallet Pallet Jack Forklift 3 NetShelter SV User Manual Unpacki
7. 00 mm 23 6 in wide 1200 mm 47 2 in deep cabinet without side panels AR2501 NetShelter SV 42 U 800 mm 31 5 in wide 1000 mm 39 4 in deep cabinet AR2280 NetShelter SV 42 U 800 mm 31 5 in wide 1060 mm 41 7 in deep cabinet AR2480 NetShelter SV 42 U 800 mm 31 5 in wide 1200 mm 47 2 in deep cabinet AR2580 NetShelter SV 48 U 600 mm 23 6 in wide 1060 mm 41 7 in deep cabinet AR2407 NetShelter SV 48 U 600 mm 23 6 in wide 1200 mm 47 2 in deep cabinet AR2507 NetShelter SV 48 U 800 mm 31 5 in wide 1060 mm 41 7 in deep cabinet AR2487 NetShelter SV 48 U 800 mm 31 5 in wide 1200 mm 47 2 in deep cabinet AR2587 NOTICE NetShelter SV cabinets are intended for use with approved equipment If you install other than approved equipment fully evaluate the safety of your configuration Use qualified personnel to install the cabinet NetShelter SV User Manual Safety Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to assemble operate service or maintain it The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if
8. 00 mm cabinet 800 mm cabinet ns2014a A CAUTION STABILITY HAZARD When adjusting vertical mounting flanges ensure that no equipment is installed on the vertical mounting flanges Failure to follow these instructions can result in injury or equipment damage NOTICE Vertical mounting flange attachment positions are in 10 mm 0 4 in increments If the vertical mounting flanges are adjusted from their factory mounting position more than 60 mm 2 4 in the vertical mounting flanges attach to the cabinet side brace using cage nuts and fasteners T T IE3 E3 OO O OO O P OL hoQ T T ep peed QG O G C U ns2030a hw i NetShelter SV User Manual 15 16 2 Move the mounting flange to the desired location and reinstall the T30 fastener at the top middle and bottom to secure the vertical mounting flange poo oO Ire e N E c Qo G GG G f v XL U Ae X IE3 O OO O OO O OO O OO O 4 3 Perform the vertical mounting flange adjustment to the opposite side of the cabinet Ensure that the same mounting position is used at the top middle and bottom Torque to 28 30 in lb 3 2 3 4 N m j l U E i Im c gt NOTICE Verify that all Vertical Mo
9. 057 mm 81 0 in Width 600 mm 23 6 in 600 mm 23 6 in 600 mm 23 6 in Depth 1000 mm 39 4 in 1060 mm 41 7 in 1060 mm 41 7 in Net weight 108 8 kg 239 9 1b 112 2 kg 247 4 1b 85 0 kg 187 4 Ib Total open area front door 778 176 mm 778 176 mm 778 176 mm 1 206 in 1 206 in 1 206 in Total open area rear door 805 637 mm 805 637 mm 805 637 mm 1 249 in 1 249 in 1 249 in Open area per U front door 18 528 mm 28 7 in 18528 mm 287 i 18528 mm 28 7 in Open area per U rear door 19 182 mm 29 7 in 19 182 mm 29 7 in 19182 mm 29 7 in Perforation pattern 69 4 open area 69 4 open area 69 4 open area Perforation pattern front door 69 3 69 3 69 3 Perforation pattern rear door 71 7 96 71 7 96 71 7 96 Clearance for wiring between 14 0 mm 0 6 in 14 0 mm 0 6 in 14 0 mm 0 6 in front door and vertical mounting flange Weight rating static leveling 1000 kg 2 205 Ib 1000 kg 2 205 Ib 1000 kg 2 205 Ib feet load Weight rating dynamic casters 460 kg 1 014 Ib 460 kg 1 014 Ib 460 kg 1 014 Ib load Weight rating cabinet roof cable 45 kg 99 Ib 45 kg 99 Ib 45 kg 99 Ib load To move the cabinet on its casters the equipment load must be evenly distributed must not exceed 460 kg 1 014 Ib and the equipment must not be installed above the 20 U height NetShelter SV User Manual 19 42 U Cabinets continued AR2280 Height 2057 mm 81 0 in 2057 mm
10. 70 3 70 3 Perforation pattern rear door 71 6 71 6 Clearance for wiring between front door and 14 0 mm 0 6 in 14 0 mm 0 6 in vertical mounting flange Weight rating static leveling feet load 1000 kg 2 205 Ib 1000 kg 2 205 Ib Weight rating dynamic casters load 460 kg 1 014 Ib 460 kg 1 014 Ib Weight rating cabinet roof cable load 45 kg 99 Ib 45 kg 99 Ib To move the cabinet on its casters the equipment load must be evenly distributed and must not exceed 460 kg 1 014 Ib and equipment must not be installed above the 20 U height 22 NetShelter SV User Manual 48 U Cabinets continued Height Width Depth Net weight Total open area front door Total open area rear door Open area per U front door Open area per U rear door Perforation pattern Perforation pattern front door Perforation pattern rear door Clearance for wiring between front door and vertical mounting flange Weight rating static leveling feet load Weight rating dynamic casters load Weight rating cabinet roof cable load AR2487 2324 mm 91 5 in 800 mm 31 5 in 1060 mm 41 7 in 143 8 kg 317 0 Ib 1 316 270 mm 2 040 in 1 334 498 mm 2 069 in 27 422 mm 42 5 in 27 802 mm 43 1 in 69 4 open area 76 9 78 0 14 0 mm 0 6 in 1000 kg 2 205 1b 460 kg 1 014 1b 45 kg 99 1b AR2587 2324 mm 91 5 in 800 mm 31 5 in 1200 mm 47 2 in 152 8 kg 336 9 1b 1316 270 mm
11. L ioco oc Def x ot ce DR e e Ro A D ae 19 42 U Cabinets continued Llu ll lullulsess s 20 42 U Cabinets continued Llusll lll luleusss 21 48 U Cabinets uu Poo era are e M RA SD CE s A ER RR e d 22 48 U Cabinets continued Llllleusss 23 Limited Factory Warranty Terms of Warranty lessen nnn 24 Non transferable Warranty x x x e x K x x e eee eee 24 Exclusions ee ee eee eee eve ee ee eee RRR R RR ee eee eae 24 Warranty Claims ee III 25 ii NetShelter SV User Manual General Information Introduction The NetShelter SVcabinet is for storage of industry standard EIA ECA 310 19 inch rack mount hardware which includes servers and voice data networking internetworking and Schneider Electric power protection equipment This manual provides installation and customization instructions for the following NetShelter SV 42 U 600 mm 23 6 in wide 1000 mm 39 4 in deep cabinet AR2200 NetShelter SV 42 U 600 mm 23 6 in wide 1000 mm 39 4 in deep cabinet without side panels AR2201 NetShelter SV 42 U 600 mm 23 6 in wide 1060 mm 41 7 in deep cabinet AR2400 NetShelter SV 42 U 600 mm 23 6 in wide 1060 mm 41 7 in deep cabinet without side panels AR2401 NetShelter SV 42 U 600 mm 23 6 in wide 1200 mm 47 2 in deep cabinet AR2500 NetShelter SV 42 U 6
12. NG OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES THE WARRANTIES SET FORTH ABOVE CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASER S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES 24 NetShelter SV User Manual IN NO EVENT SHALL SCHNEIDER ELECTRIC ITS OFFICERS DIRECTORS AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES ARISING OUT OF THE USE SERVICE OR INSTALLATION OF THE PRODUCTS WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT IRRESPECTIVE OF FAULT NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC HAS BEEN ADVISED IN ADVANCE OF THE POSSIBLY OF SUCH DAMAGES SPECIFICALLY SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY COSTS SUCH AS LOST PROFITS OR REVENUE LOSS OF EQUIPMENT LOSS OF USE OF EQUIPMENT LOSS OF SOFTWARE LOSS OF DATA COSTS OF SUBSTITUANTS CLAIMS BY THIRD PARTIES OR OTHERWISE NO SALESMAN EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY WARRANTY TERMS MAY BE MODIFIED IF AT ALL ONLY IN WRITING SIGNED BY A SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT Warranty Claims Customers with warranty claims issues may access the Schneider Electric worldwide customer support network b
13. Side Panels 2 Fa Door and Side Panel Keys Horizontal Side Braces 6 Door Handles Accessory Mounting Brackets 4 e Front Door Base 1 W Roof Base Access Panels 2 NetShelter SV User Manual Equipment Installation Hardware yy Plastic cup M6 x 16 Phillips Cage nuts 30 Joining Brackets for M5 x 12 screws 4 washers 30 head screws 30 24 in centers 4 for joining cabinets Tools provided Koc e c Torx T30 2 Phillips wrench Cage nut tool Tools not provided Sp e Torque wrench Open end wrench 6 NetShelter SV User Manual Cabinet Installation Moving the Cabinet A WARNING TIP HAZARD This cabinet is easily tipped Use extreme caution when unpacking or moving Use at least two people to unpack and move the cabinet Before moving the cabinet on its casters load 158 kg 350 Ib of equipment into the bottom equipment mounting space of the cabinet for extra stability When moving on its casters make sure the leveling feet are up and push the cabinet from the front or rear Failure to follow these instructions can result in death serious injury or equipment damage MAX 460 kg GW 1 014 1b MAX 20 U AP Ww NOTICE o X The leveling feet provide a stable base if the floor is uneven but cannot compensate for a steeply sloped surface um ns2130a Level the Cabinet 1 Using a 13 mm wrench lower each leveling foot until in makes contact with the floor
14. User Manual Racks and Accessories NetShelter SV AR2200 AR2201 AR2280 AR2400 AR2400FP1 AR2401 AR2407 AR2480 AR2487 AR2500 AR2501 AR2507 AR2580 AR2587 990 4823A 001 Publication Date 2013 Schneider Electric ZW N RRE AMA EZA This manual is available in English on the APC Web site www apc com Dieses Handbuch ist in Deutsch auf der APC Webseite www apc com verf gbar Este manual est disponible en espafiol en la p gina web de APC www apc com Ce manuel est disponible en fran ais sur le site internet d APC www apc com Questo manuale disponibile in italiano sul sito web di APC www apc com RV a T RR DRE TE S gt It APC 72TH L wwwape com DDZ G D HG X E EE Instrukcja obslugi w jezyku polskim jest dostepna na stronie internetowej APC www apc com lanHoe PyKOBOACTBO H PYCCKOM A3bIKe nocrynHo Ha canre APC www apc com Bu kullanim klavuzunun T rk esi APC web sayfasinda www apc com mevcuttur Ze APC ZH Ed E www ape com AFA HOCH e Este manual est dispon vel em portugu s no site da APC www apc com Disclaimer The information presented in this manual is not warranted by Schneider Electric to be authoritative error free or complete This publication is not meant to be a substitute for a detailed operational and site specific development plan Therefore Schneider Electric assumes no liability for damages violations of codes impr
15. ent Failure to follow these instructions can result in serious injury or equipment damage To secure the cabinet to the floor use fastener locations on the outside or inside of the cabinet and the bolt down brackets provided ns2011a Ground the Cabinet Each cabinet should be bonded directly to a common ground using the designated grounding location two M6 threaded inserts at the bottom rear of the cabinet Use a Common Bonding Network Jumper kit not provided For example Listed KDER Panduit RGCBNJ660PY or equivalent Use paint piercing washers between ground terminal and cabinet frame or remove paint on frame under ground terminals per NEC NFPA 70 Article 250 12 Torque screws to 60 in Ib 6 8 N m Bonding Location on the Cabinet NetShelter SV User Manual Customize the Cabinet Reverse the Front Door You can reverse the front door so that the door is hinged on the opposite side 1 Remove the handle using the Torx T30 2 Phillips wrench provided ns2006a 2 Unfasten the ground wire from the cabinet and door then remove the door ns2007a 3 Rotate and reinstall the door to the opposite side Remove any plastic hole plugs and reinstall the ground wi
16. n pattern 1 137 330 mm 1 763 in 1 171 657 mm 1 816 in 27 079 mm 42 0 in 27 897 mm 432 i 69 4 open area 1 137 330 mm 1 763 in 1171 657 mm 1 816 in 27 079 mm 42 0 in 27 897 mm 43 2 in 69 4 open area Perforation pattern front door 75 8 75 8 Perforation pattern rear door 78 0 78 0 Clearance for wiring between front door and 14 0 mm 0 6 in 14 0 mm 0 6 in vertical mounting flange Weight rating static leveling feet load 1000 kg 2 205 Ib 1000 kg 2 205 Ib Weight rating dynamic casters load 460 kg 1 014 Ib 460 kg 1 014 Ib Weight rating cabinet roof cable load 45 kg 99 Ib 45 kg 99 Ib To move the cabinet on its casters the equipment load must be evenly distributed and must not exceed 460 kg 1 014 Ib and equipment must not be installed above the 20 U height NetShelter SV User Manual 48 U Cabinets AR2507 Height 2324 mm 91 5 in 2324 mm 91 5 in Width 600 mm 23 6 in 600 mm 23 6 in Depth 1060 mm 41 7 in 1200 mm 47 2 in Net weight 123 5 kg 272 3 Ib 131 2 kg 289 2 Ib Total open area front door 900 609 mm 1 396 in 900 609 mm 1 396 in Total open area rear door 917 858 mm 1 423 in 917 858 mm 1 423 in Open area per U front door 187 63 mm 29 1 in 187 63 mm 29 1 in Open area per U rear door 19 122 mm 29 6 in 19 122 mm 29 6 in Perforation pattern 69 4 open area 69 4 open area Perforation pattern front door
17. ng A WARNING TIP HAZARD This cabinet is easily tipped Use extreme caution when unpacking or moving Use at least two people to unpack and move the cabinet Before moving the cabinet on its casters load 158 kg 350 Ibs of equipment into the bottom of the cabinet for extra stability When moving on its casters make sure the leveling feet are up and push the cabinet from the front or rear Failure to follow these instructions can result in death serious injury or equipment damage 1 Move the shipping pallet to a firm level surface 2 Inspect for visible signs of shipping damage If damage has been detected contact Schneider Electric Customer Support using the contact information on the back cover of this manual 3 Remove the plastic stretch wrap cardboard corners and polyethylene bag surrounding the equipment 4 Use the Torx T30 2 Phillips wrench provided and 13 mm wrench not provided to remove the four pallet mounting brackets Save these mounting brackets if you plan to bolt the cabinet to the floor 5 Carefully roll the equipment off the pallet and onto the floor 4 NetShelter SV User Manual Component Identification l po ns2118a Description Qty Item Description Roof 1 Leveling Feet Rear Frame 1 W Casters Rear Split Doors 2 Vertical Mounting Flanges
18. oper installation or any other problems that could arise based on the use of this publication The information contained in this publication is provided as is and has been prepared solely for the purpose of evaluating data center design and construction This publication has been compiled in good faith by Schneider Electric However no representation is made or warranty given either express or implied as to the completeness or accuracy of the information this publication contains IN NO EVENT SHALL SCHNEIDER ELECTRIC OR ANY AFFILIATE OR SUBSIDIARY COMPANY OF SCHNEIDER ELECTRIC OR THEIR RESPECTIVE OFFICERS DIRECTORS OR EMPLOYEES BE LIABLE FOR ANY DIRECT INDIRECT CONSEQUENTIAL PUNITIVE SPECIAL OR INCIDENTAL DAMAGES INCLUDING WITHOUT LIMITATION DAMAGES FOR LOSS OF BUSINESS CONTRACT REVENUE DATA INFORMATION OR BUSINESS INTERRUPTION RESULTING FROM ARISING OUT OF OR IN CONNECTION WITH THE USE OF OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT EVEN IF SCHNEIDER ELECTRIC HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES SCHNEIDER ELECTRIC RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME WITHOUT NOTICE Copyright intellectual and all other proprietary rights in the content including but not limited to software audio video text and photographs rests with Schneider Electric or its licensors All rights in the content not expressly
19. purchaser who must have properly registered the product Product may be registered at http www warranty apc com Exclusions Schneider Electric shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user s or any third person s misuse negligence improper installation or testing Further Schneider Electric shall not be liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical voltage or connection inappropriate on site operation conditions corrosive atmosphere repair installation start up by non Schneider Electric designated personnel a change in location or operating use exposure to the elements Acts of God fire theft or installation contrary to Schneider Electric recommendations or specifications or in any event if the Schneider Electric serial number has been altered defaced or removed or any other cause beyond the range of the intended use THERE ARE NO WARRANTIES EXPRESS OR IMPLIED BY OPERATION OF LAW OR OTHERWISE OF PRODUCTS SOLD SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH SCHNEIDER ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE SCHNEIDER ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED DIMINISHED OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF SCHNEIDER ELECTRIC RENDERI
20. re to the door and cabinet 10 NetShelter SV User Manual 4 Remove and reinstall the latch and washer oriented as shown using a Torx T30 2 Phillips wrench The washer is rotated 90 degrees from its original orientation and the latch is rotated 180 degrees ns1766b 5 NetShelter SV User Manual 11 Side Panels Remove and install side panels ns2060a Rear Doors Removal 1 Disconnect the grounding wires attached to the rear doors at the connector 2 Remove the left and right rear doors by pulling the top hinge pin down to release the pin from the hole securing it to the frame 3 Lift the door to remove the bottom hinge pin from the hole in the cabinet base 12 NetShelter SV User Manual Installation 1 Install the left and right rear doors by aligning the bottom hinge pin e to the hole in the cabinet base 2 Pull the top hinge pin down align with the hole in the roof then release 3 Connect the grounding wires NetShelter SV User Manual ns2064a ns2065b 13 Equipment Installation NOTICE NetShelter SV cabinets are intended for use with Listed equipment If you install
21. the sides When removed side airflow is increased Other airflow and cable management options exist Please visit the website www apc com for other options and more information ns2017a NetShelter SV User Manual 17 Cable Management Route secure and organize cables using the multiple cable access openings on the cabinet roof sides and bottom the accessory mounting brackets included with the cabinet plus the variety of cable management accessories available Adjust Vertical 0 U Accessory Mounting Brackets The vertical 0 U accessory mounting brackets four included provide toolless mounting capabilities for Schneider Electric Rack Power Distribution Units PDUs and cable management They also provide tie off locations for cables The factory default position for the vertical 0 U accessory brackets is in the rear of the cabinet The brackets are positioned for full height vertical Rack PDUs The bracket can be moved up or down to accommodate different accessories Additional brackets are available for purchase as requirements change 1 Use the Torx T30 2 Phillips wrench provided to remove the two T30 screws 2 Move to the desired position and reinstall the brackets i j ns2018a o AUNA eF 18 NetShelter SV User Manual Specifications 42 U Cabinets li T AR2400 AR2401 Height 2057 mm 81 0 in 2057 mm 81 0 in 2
22. un Listed equipment you should evaluate the safety of your configuration Adjust Vertical Mounting Flanges Vertical mounting flanges come factory installed in the proper location for use with rack mountable equipment The mounting flanges are adjustable towards the front or the rear of the cabinet to fit different rails or equipment with other depths to accommodate a wide variety of networking and telecommunications equipment ns2013a Adjustable Vertical Mounting Flange Cabinet Depth Factory Installed Minimum Depth Maximum Depth 1000 mm 678 mm 26 7 in 168 mm 6 6 in 718 mm 28 3 in 1060 mm 738 mm 29 1 in 168 mm 6 6 in 778 mm 30 6 in 1200 mm 738 mm 29 1 in 258 mm 10 2 in 918 mm 36 1 in NOTICE If the vertical mounting flanges are adjusted from their factory mounting position more than 60 mm 2 4 in the vertical mounting flanges attach to the cabinet side brace using cage nuts and fasteners Refer to the instructions on page 15 14 NetShelter SV User Manual Installation 1 Use the Torx T30 2 Phillips wrench provided to adjust a vertical mounting flange Remove the T30 screws at the top X D middle and bottom of the vertical mounting flange Save a the screws for adjustment and reinstallation in the new position e ib goorn eur SO my o Pw DOODO DHOO DEJES E EJE3 E31 L 13 La p a a rla a 6
23. unting Flanges are properly aligned before installing equipment in place NetShelter SV User Manual Installing Equipment A WARNING TIP HAZARD This cabinet is easily tipped Follow the precautions below during and after equipment installation Make sure you have secured the cabinet to the floor before installing equipment Install the heaviest equipment first toward the bottom of the cabinet to prevent the cabinet from becoming top heavy Do not extend equipment on sliding rails until you have installed 158 kg 350 Ibs of equipment into the bottom of the cabinet for stability or until you have installed the bolt down brackets Do not extend more than one piece of equipment on sliding rails at a time Failure to follow these instructions can result in death serious injury or equipment damage To install rack mount equipment in the cabinet 1 Review the equipment manufacturer s installation instructions 2 Locate the top and bottom U space on the vertical mounting rails Every third hole on the mounting rail is numbered to indicate the LJ O L middle of a U space 1U e Ll LI SL 3 Install the cage nuts on the interior of the vertical mounting rail then install the equipment To remove a cage nut squeeze the sides to release it from the square hole ns0014a Vertical Mounting Flange Cutouts NetShelter SV 800 mm 31 5 in wide cabinets have removable vertical mounting flange cutouts along
24. y visiting http www apc com support Select your country from the country selection pull down menu Open the Support tab at the top of the web page to obtain contact information for customer support in your region NetShelter SV User Manual 25 Worldwide Customer Support Customer support is available at no charge via e mail or telephone Contact information is available at www apc com support contact 2013 Schneider Electric APC and the APC logo are owned by Schneider Electric Industries S A S or its affiliated companies All other trademarks are property of their respective owners 990 4823A 001 10 2013 Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery amp Lifecycle Information Schneider Electric AR2401