Home
        MAC VALVES, INC.
         Contents
1.     Use a small anti static screwdriver to set the positions of the 8 bit switch for the unit s rack position and starting  quarter      1  Address  Bits 3 8     The rack address setting establishes the SI Unit s  identity  within the RIO network  The setting range is 00 74  Octal  61 different settings   Refer to the appropriate Allen Bradley manual for the series of PLCs where octal  is used for address identification     Example of octal  binary  decimal conversion for addressing     Address 73Oct  59Dec   32   16   8   2   I Binary Places   Switches 8 7 6 4  and 3 OFF    Address 140ct 12Dec   8 4Binary Places   Switches 6 and 5 OFF     2  Starting Quarter  Bits 1 2     The starting quarter setting establishes the group number for a quarter rack device within a full rack address   There are four possible settings  Note the first starting quarter uses address 00   and the fourth starting quarter  uses address 115i     UI 024  Rev C  Page 9 of 19     3  SM8 Dip Switch    From our example above and referring to Figure 1  the SM8 unit which is to be located in RIO   Rack 3  third Starting Quarter should have the Address and Starting Quarter dip switches set as 0000 1110  The  next unit  RIO Rack 2  first Starting Quarter  should be 0000 1000  The unit located at RIO Rack 1  second  Starting Quarter should be 0000 0101  The last unit located at RIO Rack 0  fourth Starting Quarter should be  0000 0011     4 2 Data Rate  Baud   Clear Hold Mode  Last Rack     DIP SW2   Refer to Fi
2.     VALVES RACK STARTING    QUARTER  DIP SWITCHES                                                                                                                                                                                                                                         UN      EE         pip                  DIPSW24         Tay                          Sp a 0 4  3 2  ATA 57 6  1 1  40 20  10 4   2     DATA RATE H gt     ges Hiei yo  0                       230 4  0  1                         HULD 0  MODE x  2             CLEAR 1  ADDRESS     LAST RACK         ADDRES    YES 0  73 0  0   0  1  0  0  74 Oa  0    Oo 1 0  1 1  Allen Brodley does not warrant or support  FIRST 1 1 this product  Al  warranty and support  xa          services for this product ore the  START ING SECOND 0 l responsibility of ond provided by  QUARTER  THIRD 1 MAC Valves Incorporoted    FOURTH 0 0   This product incorporates a communications link which is licenced under patents CN    ond proprietary technology af Allen Bradley Company  Inc   4                         UI 024  REV C  PAGE 18 OF 19    TERMINAL BLOCK GUIDE  FIGURE 2                            N TOP VIEW      N NOTE  TERMINATION RESISTOR      INSTALLED IN FIELD CONVERTABLE    N CONNECTOR        X   BLUE    N TC fi     NOT USED      MICRO OPTION       CLEAR         SHIELD     N REMOTE    0 CONNECTOR     BLUE  SHIELD    CLEAR             82 OHM  230 4K    N NOTE  A TERMINATION RESISTOR  N MUST BE INSTALLED IF THIS  N UNIT IS THE LAST
3.  RACK           N DC POWER CONNECTOR  MINI OPTION N   SHIELD  ELEC  POWER  24VDC  ELEC  POWER COMMON  VALVE POWER  24VDC  VALVE POWER COMMON            ee   e a     24 VDC ELECT     24 VDC VALVES NOTE    0     DC COMMONS MAY BE TIED   PE TOGETHER FOR SINGLE SUPPLY  OPERATION              INPUT GUIDE REU   PAGE 19 OF 19  FIGURE 3                                                                                           TOP VIEW  BOTTOM VIEW      WY iin     L        PX J  JUMPER POSITION     JUMPER POSITION  FOR FOR  POS  COMMON  PNP  NEG  COMMON  NPN     PIN  3    _       COMMON  WIRING FOR POSITIVE COMMON  MODULE  PNP   PIN  2      ace                                       ote a  INPUT INPUT                         PROXIMITY SWITCH  MECHANICAL     WIRING FOR NEGATIVE COMMON  PIN   3     MODULE  NPN   COMMON N    PIN  1   24VDC    PIN  2  INPUT 1    INPUT          PROXIMITY SWITCH  MECHANICAL      NOTE  FOR ELECTRONIC SWITCHES  CONSULT  THE MANUFACTURER  5 RECOMMENDED WIRING  PROCEDURE     
4.  the baud rate  Use 150 Ohms for 57 6kbaud and  115 2kbaud and 82 Ohms for 230 4kbaud     There is no restriction as to the spacing between each device or Serial Interface Unit  as long as the maximum  cable distance is not exceeded  However  no two devices may connect to the same point on the RIO network     Table 6    Type of Cable Recommended Cable       Shielded  twisted pair  2 core  Allen Bradley no  1771 CD  Blue Hose   Belden Co   type 9463    5 3 DC Power Wiring    All DC power for the valves  and serial interface is connected through the five contact connector on the side of  the SM8  The first thing that must be decided is the number of power supplies which are to be used to operate  the unit  The system is set up so that a separate DC supply can be used for Inputs Serial Interfaceand Outputs so  as to be able to lock out a section  i e  valve power  without turning off the communications section  It is also  possible to operate the entire system from a single DC source  In either case  refer to Figure 2 for terminal  instructions     S 4 Input SI Wiring    The MAC SMS employs the industry standard Eurostyle micro four pin female connector for the modules   There are many companies which have lines of pre assembled wire harnesses which will connect the electronics  to a variety of sensors     Also note the type of switch logic must be know prior to turning the circuit on  The type  NPN or PNP  is  selected by way of a jumper next to the dip switches  Refer to Figur
5.  this document     Along with 16 output channels  the SM8 has the capability to read 16 input channels  These inputs are  interfaced to either up to four inputs on top of the electronics box or up to 16 inputs for the tethered input  module  The inputs which are accepted by our electronics can be either NPN or PNP type  This must be known  prior to powering the unit up  If the inputs are improperly wired  damage can occur to the switches     Each SM8 is mounted directly to the MAC Valve manifold and is connected to the PLC network via the a three  pin phoenix style terminal connector rather than individual wires for each solenoid and each input as would be  the case for discretely wired manifolds  This greatly reduces both the amount of wiring and the time required to  get the product on line compared to conventionally wired system     MAC Valve 5  85 have pre wired solenoid connections  It is only necessary to make the communication and  power connections to the Serial Interface terminals and to set the node address and baud rate dip switches   located on the bottom of the electronics box  at the time of installation  The MAC SMS system comes with a  standard five phoenix style connector for electronics and valve power  Thus  the amount of wiring by way of the  connectors is minimized     UI 024  Rev C  Page 4 of 19    2  SYSTEM STRUCTURE    2 1 Applicable PLCs    Table 1  SLC 500  5 02 w RIO Scanner 1747   SN   PLC 5 11  PLC 5 15  PLC 5 VME  PLC 5 20  PLC 5 25  PLC 5 40  PL
6. C 5 40L  PLC 5 60  PLC 5 60L  PLC 5 250  5250 LP1  5250 LP2   PLC 3 10  1775 LP4  1775 LP8  175   LPA  1775 LPD   PLC 3  1775 L3   PLC 2 20  PLC 2 30       Consult the factory for other applications     UI 024    Rev C  Page 5 of 19    2 2 Applicable MAC Valve Series for the SM8 Unit    The following are the valves which can be used with the SM8     34 44 Series  35 45 Series  37 47 Senes  ISO1 2 3 Series  82 Series   92 Series   6200 Series  6300 Series  6500 Series  6600 Series    Please consult the factory for other series to be made available and additional options     3  SPECIFICATIONS    3 1 General Specifications Table 2    Operating ambient temperature  Operating ambient humidity  Vibrating resistance    Impact resistance 10G    Dielectric strength 500V AC 60 Hz for 1 sec    between external terminal and case   Insulation resistance 10Mohm    UI 024       Rev C  Page 6 of 19    3 2 Performance Specifications Table 3    Transmission Distance 10 000ft  3000m   57 6kbaud  5 000ft  1500m   115 2kbaud  2 500ft  750m   2230  4kbaud    Transmission Path Shielded Twisted Pair Cable  Belden type 9463  Blue Hose   3 3 SMS Unit Specifications Table 4    Power supply voltage For solenoid valves 24VDC    10   For SM8 Unit  internal  24VDC    10     Power consumption For solenoid valves  Max  4 0A  For SI Unit  internal  and Inputs     Max  1A    UI 024  Rev C  Page 7 of 19          4 SWITCH SETTINGS    4 1 Addressing     DIP SWI1   Refer to Fig  1   The Allen Bradley Remote I O sy
7. MAC VALVES  INC     DOCUMENT NUMBER  PAGE 1 OF 19 UI 024    TITLE  User   s Manual for MAC Valves RIO  SM8 Manifold    LEVEL RELEASED NUMBER   APPROVAL   APPROVAL  A   114599  ENGINEERING RELEASE TRJ  12 13 99   DIP SWITCH SETTINGS CHANGED    4 6 00 FIGURE 2 UPDATED TO INCLUDE MINI POWER 16523  ee AND MICRO BUS CONNECTOR       UI 024  Rev C  Page 2 of 19    User s Manual  for  MAC Valves  Allen Bradley RIO    SMS Serial Manifold  12 13 99    1  SYSTEM OVERVIEW  1 1 Remote I O    The Remote I O System is an Allen Bradley proprietary control system which supports high speed transfer of  control information  A typical network consists of one master PLC and multiple slave devices  Allen Bradley  does not warrant or support this product  All warranty and support services for this product are the  responsibility of and provide by MAC Valves Inc     The master  PLC with its network scanner  and slave devices are connected via a standard Belden cable which  provides communications to the product     The scanner communicates with each slave device on the network in an exchange referred to as data exchange   Data transferred on the network is organized by node addresses  These addresses are grouped by rack number  and starting quarter  There can be up to 16 slaves on the primary racks  numbers 0 3   Each slave device is  assigned a node number  or address  so it can communicate with the network     The introduction of a new product on the network varies slightly from master to master b
8. alve Solenoid 16 1000 0000 0000 0000       7 Input Programming Bit Map    Like the outputs  the inputs to the SM8 are mapped according to the node address  The SM8 will produce two  consecutive bytes  16 bits  which are assigned for use by the input section of the unit to the PLC memory for  programming  Refer to Table 9 for a memory map for the input channels using Class 8 and Attribute 3     In the table below  Top refers to input connectors on top of the electronics  Tether refers to input connectors on  the tethered module  to be released later   LMS is the logic monitor for a PPC  and Water is a watersaver valve  channel     UI 019  Rev C  Page 14 of 19    Table 9    Input Binary Word    Top 1 or Tether 1 0000 0000 0000 0001    The location of the Input Connectors can be see in Figure 3  Notice each connector has assignments for one  input channel as noted in the above table     1         242    p     ec c n  E       A                                                 fa  es a  PG       There are two basic types of inputs based on the direction of current flow  We call the two types Positive  Common and Negative Common  The Inputs are factory set by way of a jumper to either of these type  One  word of caution  by setting the jumper for the mode of operation for the module  the whole module is that type   Positive Common  PNP or Negative Common  NPN   There is no option for connector by connector setting of  type  If the tethered input module option is used  then each row 
9. e 3 for wiring and jumper information     5 5 PPC  Proportional Pressure Controllers     The SMS  using special MODs  can operate up to two PPCSCs  This is performed by using 4 outputs and 1  input channel per PPC for pressure control  This is then divided so that you can have 16 steps  for 4 bits  of  pressure from lowest to highest and a pressure achieved input  LMS  to control the PPC  Note  because these  pressure controllers consume inputs and outputs  the channels that are used for PPCs can not be used for other  valve control on the stack     When programming for a PPC  consult the output and input memory mapping table later in this document   UI 024  Rev C  Page 12 of 19    5 6 Fusing Circuit Protection    The SMS uses a multi tiered approach to isolation and protection of the electronics and bus systems  The first  line of defense are the two fuses location on the bottom of the unit  One of these fuses is for the valve power  circuit  the other is used to protect the electronics and inputs circuit  Inside this circuit is a blocking diode to  prevent any damage from reverse power wiring  Next in line is the opto isolation imployed for the separation of  any electronic interference which might be created by either the valves or input and the communications bus   Along the valve circuits  we have both blocking and spike separation diodes to significantly reduce the valve s  de energized spike from reaching the electronics  As a farther step  we place on each valve chann
10. el  an  electronic resettable fuse  PTC  to protect the valve driver circuits  In the event of a valve short  these  components will automatically disconnect the channel at fault  They will then reset themselves when the fault is  cleared     The first of these protective systems is the fusing across all of the incoming power  Please refer to Figure 1 for  fuse identification and Table 7 for size and replacement guide     Table 7  Fuse Size Replacement    Fuse Value Protects Connector Ref  Replace P N  Designation                                 3405000125  PIN 3  Neg  3405 0921 25        T   miaa 1             PIN 1  Neg  3405 0924 25    6 Output Programming Bit Map       The outputs to the SM8 unit are mapped according to the node address inside the Remote I O scanner  Due to  the large variety of scanners  please refer to their User s Manual for complete programming instructions     The MAC Valves SM8 will consume two consecutive bytes  16 bits  which are assigned for use by the output  section of the SM8 unit to the PLC memory for programming     Table 8 is a mapping to the word inside the scanner    UI 024  Rev C  Page 13 of 19    Table 8    Binary Output Word    Valve Solenoid 1 0000 0000 0000 0001       2 Valve Solenoid2   0000 0000 0000 0010      Valve Solenoid 7 or PPC2 0000 0000 01000 0000  B ee a  Valve Solenoid 8 or PPC2 0000 0000 1000 0000  21 7   Bit 3              MSB Bit 4  LSB Bit 1     Bit 2     Bit 3  i  MSB Bit 4    Valve Solenoid 15 0100 0000 0000 0000  V
11. g  2   These three functions are set by way of the four bit switch located directly to the right of the eight bit switch   It is important to note that all of the units on a particular network must operate at the same baud rate  Thus  the  speed which is set into the Scanner Card must be duplicated by all of the nodes on the net or a bus error will    occur     With the power supply OFF  use a small anti static screwdriver to set the positions of the four bit switch located  on the bottom plate of the unit to set the data rate  mode  and last rack indications      1  Data Baud Rate  Bits 3 4     Table 5    Switch Position Data Rate Max  I O Transmission Distance    11 57 6kbps 10 000ft  3000m     10 115 2kps 5 000ft  1500m   01 230 4kps 2 500ft  750m   00 not used        2  Clear Hold Mode  Bit 2     UI 024  Rev C  Page 10 of 19    Switch Position Mode of Operation       Clear  With the switch in this position  if a  communication error occurs  the Remote  I O unit clears the current outputs state  and stops operation temporarily  When  the signal becomes normal  the Remote  I O unit automatically returns to normal  operation   0  Hold  With the switch in this position  if a  communication error occurs  the Remote  I O unit holds the last normal signal of the  output and stops operation  When the  signal becomes normal  the Remote I O  unit must be power cycled due to the  hazards associated with potentially  energized valves        5 Wiring Installation    All Wiring and ins
12. lace  if blown      Verify communications cable    properly connected      Verify correct address and    baud rate is set on the dip  switches    Check Output fuse F2  Check wiring for power    UI 024  Rev C  Page 16 of 19    Under no circumstances are MAC Valves to be used in any application or system where failure of the valves or  related components to operate as intended could result in injury to the operator or any other person     Do not operate outside of prescribed pressure or temperature ranges    Air supply must be clean  Contamination of valve can affect proper operation    Before attempting to perform any service on valve  consult catalog  P  amp  O sheet  or factory for proper  maintenance procedures  Never attempt service with air pressure to valve    If air line lubrication is used  consult catalog  P  amp  O sheet  or factory for recommended lubricants    Before interfacing the product to any bus or serial system  consult the controller and bus manuals for proper  usage           UI 024    ADDRESS DIP SWITCH GUIDE P  PAGE 17 OF 19  FIGURE 1                                                                                                                                         O  COM 18 14 12 10    6  SA           5    2  2626960504 9     Bites TI T FWR   d     ac                                2 Ne  INPUT 1       TOP VIEW  BOTTOM VIEW     M   522      ON    TIS s  070 IMS WE v n     TIS 4 4      OFF     LOGIC 0  FUSE F1 _     ELECTRONICS   PUn RAIL eu  FUSE F2  
13. of four inputs can be selected either Postive or  Negative Common     Refer to Figure 3 in selecting the desired mode of operation for the inputs  The terms  sinking  and  sourcing   are not used due to the possibility of confusion  In our terminology  Positive Common is used when the load is  connected between the signal pins 2 and the positive voltage terminal pin 1  typical for PNP logic switches    Negative Common is used when the load is connected between the signal pins 2 and the negative voltage  terminal pin 3  typical for NPN logic switches      UI 024  Rev C  Page 15 of 19    8 Troubleshooting Guide    In the event of difficulties in either operation or installation of the SM8 Manifold  your local MAC Valves  Distributor and the factory are ready and able to assist you in solving any problems which might be encountered     Below is a table of some typical problems  symptoms  and their solutions  All troubleshooting LEDs are  visible on the top of the electronics module  They consist of the Comm LED  Fault LED  and PWR LED  for    Valve Power      Table 10    Does not operate Valve Power LED off  Fault LED off  Comm LED off  No Output LEDs on  No Valve operation  Does not operate Valve Power LED on  Fault LED on  Comm LED off  No Output LEDs on  No Valve Operation    RIO is active does not drive Valve Power LED off  valves Fault LED off  Comm LED on  No Output LEDs on  No Valve Operation       Warning     1  Verify primary 24VDC supply  2    Check fuse F1 and F2  rep
14. s means for RIO Rack 3 we want an SM8 in Starting Group  4  Starting Group 4 controls output words O x 28 and O x 29 along with input words I x 28 and I x 29  In order  to complete the addressing of this SM8 unit  we must set word G2 bit 14  least significant bit is far right   most  significant bit is left  to 1 so that the left nibble is 0100  This is translated to mean we are starting on Group 4  and the third 1 4 rack in size     The next SMS uses the third nibble in both      and G2  This time we want to operate output words O x 16 and  O x 17 along with input words I x 16 and I x 17  In order for us to do this  we assign the second nibble of G1 to  read RIO Rack 2  Starting Group 0 or 0001 and assign the third nibble of G2 to read first Starting Quarter or  0001     UI 024    Rev C  Page 8 of 19    The third SM8 uses output words O x 10 and O x 11 and input words I x 10 and I x 11  Our assignment for G1  is 0010  which means RIO Rack 1  Starting Group 2  Our G2  second nibble  would be 0010 or second Starting  Quarter     The last SM8 unit will control words O x 6  O x 7  I x 6  and I x 7  In order to get this combination  we set the  first nibble of G1 to 1000 or as it reads  RIO Rack 0  Starting Group 6  G2 becomes 1000 or the fourth Starting  Quarter     The next step in addressing is to set the Starting Quarter and Rack Address dip switches on each SM8 unit   With the power supply OFF  remove the head from the valve stack  On the bottom  find the 8 bit dip switches 
15. stem of addressing uses    logical racks  and    starting quarter  as a bases for  the node address  The basic system uses four racks with four quarters in these racks for a maximum of sixteen  node addresses possible  Since each SM8 must have a unique address  with the basic system  there are sixteen  available addresses for the SM8 unit  There are methods to increase the number of logical racks inside the  system  Please consult Allen Bradley for the methods which are applicable for each specific PLC     Inside each controller is a file called a  G  file  It contains three words of 16 bits each which set the address   and   ultimately  which output and input words are allocated to which SM8  For example  the G file words  for the  basic system  for a particular system could look something like this     RIO RIO RIO RIO  Rack 3 Rack 2 Rack 1 Rack 0  Start Gr  Start Gr  Start Gr  Start Gr   6420 6420 6420 6420  GO 0010 0001 0000 1100  Gl 0100 0001 0010 1000  G2 0100 0001 0010 1000    In this example  we have four SM8 units addressed  Note the user only sets words G1 and G2  The word  labeled    GO    is assigned by the computer and should not be modified     The first word the user has to set to address the SM8 is G1  This is called the Device Address  For our  example  we have four devices assigned  The other word is called the Device Size  Since all of the SM8 units  occupy 1   4 of a rack  they all need one bit of G2     In our example the left four bits of G1 are 0100  Thi
16. tallation steps should be performed with the system power supply off   5 1 Terminal Blocks  Refer to Figure 2 for terminal identification during installation     There are two sets of terminal blocks visible on the sides of the unit  The three contact terminal block  located  on the far right is for the communications cable  The five contact terminal block for DC power     5 2 Wiring of Twisted Pair Cable    The connection of the cable should be as shown in Figure 2  Refer also to the appropriate Allen Bradley  manual     Remove the female portion of the three contact terminal block its mate  Cut back the insulation exposing the  wires from the    Blue Hose cable  There will be a clear inner wire  blue wire  and overall shield  Place the clear  wire with the appropriate resistor  based on the operating baud rate  on the left terminal of the connector and  secure with the screw on the top of the block  Next place the shield in the center conductor and tighten the set  screw  Lastly  place the blue colored wire and the other end of the terminating resistor on the right contact and  tighten the set screw for that terminal  Ensure the wires are fully engaged and not shorting to each other or the  printed circuit board  It is advisable to insulate the shield to prevent shorting     UI 024  Rev C  Page 11 of 19    Connect terminating resistors at the end of each link  Termination kits are normally included with your Allen   Bradley Scanner  The type of resistor used is dependent on
17. ut in general  the  process is as follows     1  Set the address dip switches on the slave to correspond to the required node number  This includes the rack  number and starting quarter    Set the baud rate dip switches to correspond to network baud rate    Wire the communications bus on the new product    Place power on the new node  product     Initialize the master    Ensure the          file in the master is set for the new node number    Program the master for the required work    Go online     CO OO         tS    UI 024  Rev C  Page 3 of 19    1 2 MAC Valves SMS Serial Manifold    The MAC Serial Manifold  5  8  is a slave device within the Allen Bradley Remote I O network  Thus  it will  respond to all of the commands associated with the network like any other node of its type  The PLC  programmer will not have to make any special allowances with this product     Since the MAC SMS Unit is nothing more than a node on the Remote I O network  it can also be used in  conjunction with our Serial Input Manifold  SIM   SLIM  or any other RIO compatible device     Each SM8 occupies a single node in the network  The output and input portion occupy 1 4 rack  Thus  16  output bits are controlled and 16 input bits are monitored  We can thus control up to 16 MAC solenoid valves  and read  with the tethered input module  up to 16 user supplied sensors  We will discuss the inputs later in this  document  The memory location and addressing of these bytes also will be discussed later in
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
User's Guide to AMSFonts Version 2.2d January 2002 Standard    Copyright © All rights reserved. 
   Failed to retrieve file