        NJ-series Troubleshooting Manual
         Contents
1.            No    Is power supplied to the Controller  Turn ON the power supply to the Controller        Yes       No Yes       Can the Sysmac Studio    go online with CPU Unit  End    Ge  KN  NO      O  C  2  D  KA  a gt   Q  O  CT       Q  O  wi  m  pe   Q  a gt        pe   Cc  KA  D           Insert the USB cable connectors all the way    Is the USB cable connected properly   ESP at the computer and Controller               Can the Sysmac Studio  go online with CPU Unit           Is the connection method set to a  direct USB connection in the  Communications Setup of the  Sysmac Studio         No Set the connection method to a direct USB connection  in the Communications Setup of the Sysmac Studio           Yes       Can the Sysmac Studio  go online with CPU Unit        Install the USB driver    Refer to the appendices of Sysmac Studio  Is the USB driver installed correctly  Version 1 Operation Manual  Cat  No  W504    for the installation procedure for the USB   driver              Can the Sysmac Studio  go online with CPU Unit        Replace the USB cable     NJ series Troubleshooting Manual  W503  2 15    2 Error Troubleshooting Methods       Remote Connection to Peripheral USB Port    Sysmac Studio cannot  connect to CPU Unit              Is power supplied to the Controller     No  Turn ON the power supply to the Controller     No    Yes            Can the Sysmac Studio  go online with CPU Unit     N  o Insert the cable connectors all the way  at the computer and Contro
2.           00  3 62  CJ series Temperature Control Units                 ccceee 3 59  GJ  seres e ics ae clad ts nt tak eed dt ee ae 3 56  Controller errors      1 6  Controller events E 1 5  elle 1 6  Controller information          cc ccccceccccccecceeeeeseeeeeeeeeeeeeeeeens 1 6  Controller operation             ccccccsseeeeceseeeeeeceeeeeeeeseeeeeeeneees 3 7  CPU Unit operating Status              cc ceeecceeseeeeeeeeeeeeeeeeees 1 3  CPU Unit EE 1 4  2 4  CPU Unit Watchdog Timer Error                   eeceeees 1 4  2 4  E  Error Status variable 0 0    ccecceseeeeeeeeeeeeeesenees 1 13  2 13  Index 2                errors  checking with system defined variables                   2 13  identifying and resetting             cccccseeeeeeees 2 5  2 9  2 11   ESENG eebe 2 12  EtherCAT Master Function Module    3 39  PINGIGAT  SIAVES  Ces 3 42  EtherNet IP Function Module    3 35  event ee TEE 1 10  3 3  3 5  3 6  3 7  3 8   EEN 3 10 3 18  3 35  3 39  3 42   EE 3 43  3 55  3 56 3 58  3 59   EE 3 61  3 62  3 68  3 73  3 90  event codes in sequential Order                ccccseeeeeeees 3 73  E le Le SE 1 5  event NAMES       cceceseceeeeeeeeeeees 3 3  3 5  3 6  3 7  3 8  3 10   ege 3 18  3 35  3 39  3 42  3 43   Seed 3 55  3 56  3 58  3 59  3 61   EE 3 62  3 68  3 73  3 90  EE 1 2  1 5  IS E 1 6  F  fatale dE 1 2  1 4  checking for fatal errors          ccccsseececeeeseeeeeeeeeeeeeeeeees 1 4  TROUDICSMOOUING E 2 4  FINS COMMUNICATIONS      3 8  G  G5 serieS Servo Drives ou    ceccce
3.         trol Instruc  made to change the able that cannot be changed for Motion Con   tion Re  SlaveOffset input re execution was changed  trol Instruc   execution variable when re  tions  Disabled executing a motion Reference   SlaveOffset    control instruction  Manual  Cat    This input variable No  W508  oo  cannot be changed    when re executing    an instruction   S  54640000 hex   Motion Con    An attempt was A parameter for an input vari  Same as g  trol Instruc  made to change the able that cannot be changed for above  4  tion Re  SlaveScaling input re execution was changed     execution variable when re      Disabled executing a motion   SlaveScal  control instruction   ing   This input variable  cannot be changed  when re executing  an instruction   Go  54650000 hex   Motion Con    An attempt was A parameter for an input vari  Same as Ge  trol Instruc  made to change the able that cannot be changed for above m  tion Re  StartPosition input re execution was changed  a  execution variable when re  e  Disabled executing a motion     StartPosi  control instruction  D  tion   This input variable    cannot be changed A  when re executing ra  an instruction   Si  54660000 hex   Instruction High speed hom  High speed homing was exe  Same as si  Execution ing or an interpola  cuted when home was unde  above  a  Error with tion instruction was fined  2  Undefined executed when An interpolation instruction was    Home home was unde  executed for an axes group that    fined  i
4.      Same as  above     Slave Travel  Distance  Specification  Out of Range    548B0000 hex The parameter  specified for the  SlaveDistance input  variable to a motion  control instruction is    out of range     The instruction input parameter  exceeded the range of 40 bit  data when it is converted to  pulses     Phase Shift  Amount Out  of Range    548C0000 hex The absolute value of the  instruction input parameter  exceeded the range of 40 bit  data when it is converted to    pulses     Same as  above     The parameter  specified for the  PhaseShift input  variable to a motion  control instruction is  out of range     548D0000 hex Same as    above     The absolute value of the  instruction input parameter  exceeded the range of 40 bit  data when it is converted to  pulses     Feeding Dis   tance Out of  Range    The parameter  specified for the  FeedDistance input  variable to a motion  control instruction is  out of range        NJ series Troubleshooting Manual  W503  3 31    3 Error Tables    548E0000 hex   Auxiliary and  Slave  Defined as  Same Axis    548F0000 hex   Relative  Position  Selection Out  of Range    54900000 hex   Cam Transi   tion Specifi   cation Out of  Range    54910000 hex   Synchro   nized Con   trol End  Mode Selec   tion Out of  Range    54920000 hex   Enable Exter   nal Latch  Instruction  Execution  Disabled    54930000 hex   Master Axis  Offset Out of  Range    54940000 hex   Slave Axis  Offset Out of  Range    54950000 hex   Command  Current Po
5.     An attempt was  made to change the  parameter for the  Master input vari   able when re exe   cuting a motion  control instruction    This input variable  cannot be changed  when re executing  an instruction      An attempt was  made to change the  parameter for the  MasterOffset input  variable when re   executing a motion  control instruction    This input variable  cannot be changed  when re executing  an instruction      An attempt was  made to change the  parameter for the  MasterScaling input  variable when re   executing a motion  control instruction    This input variable  cannot be changed  when re executing  an instruction         NJ series Troubleshooting Manual  W503     e A parameter for an input vari   able that cannot be changed for  re execution was changed     NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508    e A parameter for an input vari  d Same as  able that cannot be changed for above   re execution was changed    e A parameter for an input vari  d Same as  able that cannot be changed for above   re execution was changed    e A parameter for an input vari  d Same as  able that cannot be changed for above   re execution was changed    e A parameter for an input vari  d Same as  able that cannot be changed for above   re execution was changed     3 25    OO  I      m        O     Vu  o   lt   GU  O  c     O  OD       BINDO  uonouny  O1 UOD uono 3y  Ul SIO E L       3 Error Tables    545C0000 hex    545D0000 hex    545E0
6.     Notice of  Insufficient  Travel Dis   tance to  Achieve  Blending  Transit Veloc     ity    Error Clear  from MC Test  Run Tab  Page    Slave Error  Code Report    The number of  pulses for the actual  position overflowed     The number of  pulses for the actual  position under   flowed     A warning has been  detected for an  EtherCAT slave     You cannot save a  cam table to a file  when non volatile  memory is being  accessed by  another operation     There is not suffi   cient travel distance  to accelerate or  decelerate to the  transit velocity dur   ing blending opera   tion     An error was  cleared from the  MC Test Run Pane  of the Sysmac Stu   dio     The error code was  reported by the  slave when a Slave  Error Detected error  occurred     NJ series Troubleshooting Manual  W503     e In Linear Mode  the command    position when converted to  pulses exceeded the lower limit  of signed 40 bit data     The actual position when con   verted to pulses exceeded the  upper limit of signed 40 bit  data     The actual position when con   verted to pulses exceeded the  lower limit of signed 40 bit data     A warning was detected for the  EtherCAT slave that is allocated  to the axis     An attempt was made to exe   cute the MC_SaveCam Table  instruction when another opera   tion was accessing the non vol   atile memory  e g   transfer or  data trace operation from the  Sysmac Studio      When the Acceleration Decel   eration Over parameter was set  to Use rapid acceler
7.     refers to transferring data from the physical Controller to the Sysmac Studio     For the Sysmac Studio  synchronization is used to both upload and download data  Here     synchronize     means to automatically compare the data for the Sysmac Studio on the computer with the data in the  physical Controller and transfer the data in the direction that is specified by the user     6 NJ series Troubleshooting Manual  W503     Sections in this Manual    Sections in this Manual            Overview of Errors    Error Troubleshooting Methods         Error Tables       NJ series Troubleshooting Manual  W503     Sections in this Manual    8 NJ series Troubleshooting Manual  W503     CONTENTS    CONTENTS           gt  gt  gt   Introdu TION BE 1  Relevant d ET siina aaa 2  Mantial COnfiGuration BE 3  Mana  SU UC CUT E 5  Sections IN this Wa Wal eene deele 7  Read and Understand this Manual                     ccesecsscenseenseensenseeneecnecessonseenseenesenees 11  Safety DE de sorceress a a aa ai 15  Precautions Tol Safe TE 17  Precautions fOr Correct USC uiii eege EE 18  Regulations and Standards s  ssssisscrisisisonaninsai ennei bnina aaan aaan iaa ia 19  UNI VERSIONS serana a aa a aS 21  Related dE Uu UE 24  PROVISION HISIONY EE 26  Section 1 Overview of Errors  1 1 Overview of NJ SerieS Errors              cccesccseeceseceneeeneeceneceneeenseensecesecenseonseonseceaseoasecnseoeneseneeones 1 2  1 1 1 BA  SYS CoG  i col d  6  cee anne eaten ee ee re Cerne cere sine E 1 2  1 1 2 EE
8.    22 NJ series Troubleshooting Manual  W503     Unit Versions    Unit Version Notation    In this manual  unit versions are specified as shown in the following table     Product nameplate Notation in this manual Remarks       Ver 1 0    or later to the right of   Unit version 1 0 or later Unless unit versions are specified  the information in this manual  the lot number applies to all unit versions     NJ series Troubleshooting Manual  W503  23    Related Manuals    Related Manuals       The following manuals are related to the NJ series Controllers  Use these manuals for reference     Manual name    NJ series CPU Unit  Hardware User   s Manual    W500 NJ501 OUUL I  W501 NJ501 OUUL I    W507 NJ501 OUUL I  W502 NJ501 OUUL I    W508 NJ501 UOLUUL I    CJ1W OOLULI    NJ series CPU Unit Soft   ware Users Manual    NJ series CPU Unit  Motion Control Users  Manual    NJ series Instructions  Reference Manual    NJ series Motion Control  Instructions Reference  Manual    CJ series Special Unit  Manuals for NJ series  CPU Unit       24    Model numbers Application    Learning the basic specifi   cations of the NJ series  CPU Units  including intro   ductory information   designing  installation  and  maintenance  Mainly hard   ware information is pro   vided     Learning how to program  and set up an NJ series  CPU Unit  Mainly software  information is provided     Learning about motion  control settings and pro   gramming concepts     Learning about the specifi   cations of the instr
9.    Sysmac Studio   The EC_ConnectSlave instruc   tion was executed   An error reset operation was Same as  performed from the Sysmac above   Studio   The ResetECError instruction  was executed    3 41    OO  I      m        O     Vu  o   lt   GU  O  c     O  OD         JNPON UOIOUNS Joie  Iv ueu OU  U  Sou LE    3 Error Tables    3 1 6 Errors in EtherCAT Slaves    This section provides tables of the events for which OMRON EtherCAT slaves provide notification to the  NJ series CPU Unit     e Block I O  GX series EtherCAT Slave Units   e G5 series Servo Drives with Built in EtherCAT Communications  e MX2 series Inverters with EtherCAT Communications Units    H Block I O  GX series EtherCAT Slave Units   a          14A00000 hex   Non volatile   An error occurredin      Noise GX series  Memory the control parame  EtherCAT  Checksum ters  Slave Units  Error User s Manual   Cat  No   W488   24610000 hex   Switch Set  The setting switch The analog range that is set on Same as  ting Error is set out of range  the switch is outside the setting above   range   64CC0000 hex   I O Discon  An I O signal line is I O signal wiring is discon  Same as  nection disconnected  nected or has a faulty connec  above   Detected tion   An I O signal line is discon   nected   04A10000 hex   Non volatile   An error occurred in Non volatile memory failure Same as  Memory non volatile mem  above     3 42    Hardware  Error    ory        NJ series Troubleshooting Manual  W503     g G5 series Servo Drives 
10.    The synchronized  instruction was not  executed because  an error occurred in  the position of the  master axis of the  synchronized  instruction     The synchronized  instruction was not  executed because  an error occurred in  the position of the  auxiliary axis of the  synchronized  instruction     A communications  error occurred for  the EtherCAT slave  that is allocated to  an axis     The following error  exceeded the Fol   lowing Error Warn   ing Value     The command  velocity exceeded  the velocity warn   ing value     The command  acceleration  exceeded the  acceleration warn   ing value     The command  deceleration  exceeded the  deceleration warn   ing value     The torque com   mand value  exceeded the posi   tive torque warning  value     The torque com   mand value  exceeded the nega   tive torque warning  value     The number of  pulses for the com   mand position over   flowed     munications are not established  for the master axis of the syn   chronized instruction     The slave of the master axis for  the synchronized instruction  was disconnected     An Absolute Encoder Current  Position Calculation Failed error   6458000 hex  was detected for  the master axis of a synchro   nized instruction     EtherCAT process data com   munications are not established  for the auxiliary axis of the syn   chronized instruction     The slave of the auxiliary axis  for the synchronized instruction  was disconnected     An Absolute Encoder Current  Position Calculati
11.    ered or Blending  Buffer Modes  exceeded the buffer  limit     The specified  motion cannot be  executed for the  deceleration rate or  acceleration rate  that was specified  for multi execution  or re execution of a  positioning instruc   tion     There is not suffi   cient travel distance  to accelerate or  decelerate to the  transit velocity     The constant veloc   ity travel distance of  the master axis is  less than zero     For the  MC_GearlnPos   Positioning Gear  Operation  instruc   tion  the target  velocity of the slave  axis is too small to  achieve the  required velocity     executed for an axis for which  the Servo is OFF     Home was preset with the  MC_Home instruction for an  axis for which EtherCAT pro   cess data communications are  not established     A motion instruction was exe   cuted for an axes group while  the MC_Stop instruction was  being executed for a composi   tion axis     An axis instruction was exe   cuted when there was already a  current instruction and a buff   ered instruction for the same  axis     An axes group instruction was  executed when there was  already eight current instruc   tions and buffered instructions  for the same axis     Stopping at the target position  was not possible for the speci   fied acceleration deceleration  rate for multi execution or re   execution of a positioning  instruction when the Accelera   tion Deceleration Over parame   ter was set to generate a minor  fault and stop     There was not sufficient 
12.   34220000 hex TCP IP Basic Setting Error  Local Built in EtherNet IP Port on CPU Unit   W506  Port IP Address    34230000 hex TCP IP Advanced Setting Error  IP Built in EtherNet IP Port on CPU Unit   W506  Router Table     34240000 hex FTP Server Setting Error Built in EtherNet IP Port on CPU Unit   W506  34250000 hex NTP Client Setting Error Built in EtherNet IP Port on CPU Unit   W506  34260000 hex SNMP Setting Error Built in EtherNet IP Port on CPU Unit   W506    NJ series Troubleshooting Manual  W503  3 77    3 Error Tables    3 78    Event code  34270000 hex  34400000 hex    34600000 hex    34610000 hex  34630000 hex  34640000 hex    34800000 hex  34810000 hex    34820000 hex    34830000 hex  34840000 hex    34850000 hex  34860000 hex  34870000 hex  34880000 hex    34890000 hex    348A0000 hex    348C0000 hex    348D0000 hex  34940000 hex  34980000 hex    34A40000 hex    34BC0000 hex  34BD0000 hex  34BE0000 hex  34BF0000 hex  34C00000 hex    34010000 hex    34C20000 hex  34C30000 hex    34E00000 hex    34E10000 hex    ee ee  Tag Name Resolution Error Built in EtherNet IP Port on CPU Unit   W506    Network Configuration Information Built in EtherCAT Master in CPU Unit   W505  Error    Required Process Data Object Not General Motion Control W507  Set    Process Data Object Setting Missing   Motion Control Instructions W508  Axis Slave Disabled General Motion Control W507    Network Configuration Information General Motion Control W507  Missing for Axis Slave    Mean Value
13.   Cfg or    P2_PmrSgwRespTimeout  Cfg device variable is too  short   During Loopback Test  e Loopback test jig failure   e Noise  e The communications circuits  in the Serial Communica   tions Unit are faulty     NJ series Troubleshooting Manual  W503  3 65    OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       SIU  s  n  s f9 Ul S1013 J             3 Error Tables    e A serial gateway cannot inter   rupt processing between proto   col macro steps    If the message frame is cor   rupted due to noise  a response  timeout occurred at the FINS    64A40000 hex    64A50000 hex    64A60000 hex    64A70000 hex    84680000 hex    84690000 hex    3 66    Timeout  Error    Comparison  Error    Reception  Overflow    Command  Format Error    Transmis   sion Error    Overrun  Error    A timeout error  occurred     A comparison error  occurred     More than the spec   ified amount of  receive data was  received in No pro   tocol Mode     An illegal function  code or address  was specified ina  received Modbus   RTU command     A transmission  error occurred     An overrun  occurred     send source if the     P1_TimeoutErr or     P2_TimeoutErr device vari   able is FALSE    A no protocol instruction was  executed when No protocol  Mode was not set        Loopback test jig failure   Noise    The communications circuits in  the Serial Communications Unit  are faulty        One or more bytes of data was  received after the completion  the reception     An illegal function code  
14.   D  m     O     Wa    g Displaying Errors on the Sysmac Studio    H an error occurs while the Sysmac Studio is online with the CPU Unit  the Sysmac Studio notifies the  user of the error in the Controller Status Pane  From there  you can open the Troubleshooting and Event  Logs Window to read detailed error information and troubleshooting methods        Click the Troubleshooting Button in the toolbar  or select Troubleshooting from the Tools Menu     F3  Sysmac Studio             New Project       Configurations and Setup  Ur irF  gt oetungs  The Sysmac Studio automatically collects the Controllers error information  and opens the Trouble   shooting Window       gt   Troubles hooting    Level   Source   Event Name    UO bus End Cover Missing  Partial fault EtherNet IP Communications port IP Address Duplication Error 0x84010000  Minor fault PLC Real Time Clock Stopped 0x00070000  Minor fault EtherNet IP Communications port DNS Server Connection Error 0x84030000    oppe oewWSAS   y  YIM s10113 Bunjesey pue BulAyUap  LES    The End Cover is not connected to right end of the CPU Rack or an Expansion Rack  Cause    1  The End Cover is not connected to right end of the CPU Rack or an Expansion Rack    2  The End Cover is not connected properly        NJ series Troubleshooting Manual  W503  2 5    2 Error Troubleshooting Methods    Checking Current Errors and the Event Logs with the Sysmac  Studio         Checking Current Errors with the Sysmac Studio    You can click the Controlle
15.   Homing  Opposite  Direction  Limit Input  Detected    Homing  Direction  Limit Input  Detected    Homing Limit  Inputs  Detected in  Both Direc   tions    Home Prox   imity Homing  Opposite  Direction  Limit Input  Detected    The main circuit  power of the Servo  Drive turned OFF  while the Servo was  ON     An interrupt input  was not received  during execution of  an MC_MoveFeed   Interrupt Feeding   instruction     The limit signal in  the direction oppo   site to the homing  direction was  detected during a  homing operation     The limit signal in  the homing direc   tion was detected  during a homing  operation     The limit signals in  both directions  were detected dur   ing a homing opera   tion     The home proxim   ity input and the  limit signal in the  direction opposite  to the homing direc   tion were detected  during a homing  operation     NJ series Troubleshooting Manual  W503     e The main circuit power of the    Servo Drive was interrupted  while the Servo was ON     The latch enabled range speci   fication is invalid     There is a problem with the wir   ing of the interrupt signal     The sensor that outputs the  interrupt signal has failed     The Operation Selection at  Negative Limit Input or Opera   tion Selection at Positive Limit  Input parameter is set to No  reverse turn     The location of the homing  input signal sensors  homing  settings  and homing start posi   tion cause a limit input to be  reached     The input signal sensor wiring  is
16.   Same as   Overflow pulses exceeded low the command  above   the setting of the The value of the Following error  Following error win    window  6065 hex  is small   dow  6065 hex   The encoder wiring is incorrect   34E50000 hex   Excessive The difference Motor operation does not fol  Same as  Velocity Error   between the inter  low the command  above   nal position com  The setting of the Excessive  mand velocity and Velocity Error Setting  3602  the actual velocity hex  is too small    i e   the velocity  error  exceeded the  Excessive Velocity  Error Setting  3602  hex     34E60000 hex   Overspeed The Servomotor The velocity command value is Same as  rotation speed too large  above   exceeded the value   e There is overshooting   set on the Over  The wiring is incorrect   speed Detection  Level Setting  3513  hex     383F0000 hex   Excessive During fully closed Connections are not correct  Same as   Hybrid Fol  control  the differ  The settings are not correct  above    lowing Error   ence between the  load position from  the external  encoder and the  Servomotor posi   tion from the  encoder was larger  than the number of  pulses set as the  Hybrid Following  Error Counter Over   flow Level  3328  hex     38400000 hex   Overspeed 2   The Servomotor The velocity command value is Same as  rotation speed too large  above   exceeded the value  e There is overshooting    SE Overspeed The wiring is incorrect   Detection Level  Setting at Immedi   ate Stop  3615  hex    3841000
17.   Same as  above     Same as  above     Same as  above     Synchroniza    A synchronization e Noise d Same as  tion Error error occurred  e Control PCB error above     Sync Man  PDO communica    ager WDT tions were stopped   Error for more than the  specified period of  time     e The EtherCAT communications  cable is disconnected or bro   ken     e There is an error in the host  controller        d Same as  above     ESC Initial  An error occurredin   Control PCB error Same as  ization Error ESC initialization  above     Slave Unit An error occurred in  Verification Slave Unit verifica   Error tion     Communica    There is an error in  tions Setting   the communica   Error tions settings     Synchroniza    A synchronization    tion Interrup   tion Error    interruption error  occurred     NJ series Troubleshooting Manual  W503     e Control PCB error    e An out of range value was set  from the host controller    e A command that changes the  communications state to an  unsupported state was  received     e Control PCB error       Same as  above     Same as  above     Same as  above     3 53    OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       SOAR S LYOJEUIF U  S1013 9           3 Error Tables       weal O     98010000 hex    98020000 hex    08010000 hex    08020000 hex    08030000 hex    08040000 hex    08050000 hex    08060000 hex    08070000 hex    34E00000 hex    383C0000 hex    383D0000 hex    383E0000 hex    3 54    Absolute The multi rotation   Value 
18.   Tr  Receive  Wait Monitor   ing Time   Exceeded    An error occurred in  the protocol macro     The time required  to complete a send  Operation exceeded  the Send Finished  Monitoring Time     The time required  to complete a  reception operation  exceeded the  Receive Finished  Monitoring Time     The receive waiting  time exceeded the  Receive Wait Moni   toring Time     NJ series Troubleshooting Manual  W503     istered number was specified  for SeqNo  communications  sequence number  of the  ExecPMCR instruction  no indi   cators light      Data read write area exceeded  error  The specified area range  was exceeded when data was  written to or read from the CPU  Unit   The ERC indicator and  ERR ALM indicator will flash      Protocol data syntax error   There was a code that cannot  be executed during protocol  execution   The ERC indicator  and ERR ALM indicator will  flash      e The total of the areas speci   fied for link words O1  O2  11   and 12 exceeded 500 words     The same link word is used  by both ports 1 and 2    Writing was specified with a  constant    Interrupt notification was  specified for a Serial Commu   nications Unit     Thirty one or more items  were set for the write attribute  data for one message    A length of 0 bytes was speci   fied for a message that was  sent or received    The length of a message to  be sent or received exceeds  the maximum send receive  bytes    A message is not registered  for matrix reception    The transmission con
19.   W501      The motion control instructions are described   When programming  use this manual together  with the NJ series CPU Unit Hardware User s  Manual  Cat  No  W500   NJ series CPU Unit  Software User   s Manual  Cat  No  W501  and  NJ series CPU Unit Motion Control User s Man   ual  Cat  No  W507      The methods and precautions for using CJ   series Units with an NJ501 CPU Unit are  described  including access methods and pro   gramming interfaces  Manuals are available for  the following Units    Analog I O Units  Insulated type Analog I O  Units  Temperature Control Units  ID Sensor  Units  High speed Counter Units  Serial Com   munications Units  and DeviceNet Units     Use these manuals together with the NJU series  CPU Unit Hardware User s Manual  Cat  No   W500  and NJ series CPU Unit Software User s  Manual  Cat  No  W501      NJ series Troubleshooting Manual  W503     Manual name  NJ series CPU Unit Built   in EtherCAT Port User   s  Manual    W505 NJ501 OULL I    W506 NJ501 UOULL I  W503 NJ501 OULLI    W504 SYSMAC    GEZ II  7 a  8 E    W344    W488    1574  1576    NJ series CPU Unit Built   in EtherNet IP Port  User   s Manual    NJ series Troubleshoot   ing Manual    Sysmac Studio Version 1  Operation Manual    CX Integrator  CS CJ CP NSJ series  Network Configuration  Tool Operation Manual  CX Designer User   s  Manual    CX Protocol Operation  Manual    GxX series EtherCAT  Slave Unit User   s Manual    GX IDUULIL I   GX ODULULL I  GX OCULLL I  GX MDLUIU
20.   somewhere other than the ends  of the trunk line     Noise    The master and slaves have dif   ferent baud rates   Communications cable lengths   trunk line and branch lines  are  unsuitable    A communications cable is dis   connected or loose    The terminating resistance is  somewhere other than the ends  of the trunk line     Noise    The master is not in operation   The master and slaves have dif   ferent baud rates   Communications cable lengths   trunk line and branch lines  are  unsuitable    A communications cable is dis   connected or loose    The terminating resistance is  somewhere other than the ends  of the trunk line     Noise    A COS connection to the mas   ter is not open    A Bus Off state occurred    A network power error  occurred    A send timeout occurred     The available capacity on the  SD Memory Card was insuffi   cient to write a file   Write protection is set on the  SD Memory Card when you  write to a file    Noise   The SD Memory Card is dam   aged    The CPU Unit has failed     The power supply was inter   rupted while writing the mes   sage monitoring timer list to the  non volatile memory     p Level O     a aee een    CJ series  DeviceNet  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W497     Same as  above     Same as    Same as    Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables    3 2 Events in Order of Event Codes    This section provides a table of all events in order of the event codes  Ev
21.   the Controller and see if that resets the error  If the error occurs fre   quently  check the FG and power supply lines to see if noise is enter   ing on them  Implement noise countermeasures as required     CPU Unit failure If the error persists even after you make the above corrections   replace the CPU Unit      Incorrect Power Supply Unit Connected    Cause Correction    A CJ series Power Supply Unit is con  Connect an NJ series Power Supply Unit to the CPU Rack   nected to the CPU Rack       CPU Unit Watchdog Timer Error    Cause Correction  A conductive object has gotten inside  If there is conductive material nearby  blow out the CPU Unit with air   Noise If the error did not result from the above causes  cycle the power to    the Controller and see if that resets the error  If the error occurs fre   quently  check the FG and power supply lines to see if noise is enter   ing on them  Implement noise countermeasures as required    CPU Unit failure If the error persists even after you make the above corrections   replace the CPU Unit     2 4 NJ series Troubleshooting Manual  W503     2 Error Troubleshooting Methods    2 3 Troubleshooting Non fatal Errors    2 3 1 Identifying and Resetting Errors with the Sysmac Studio    Troubleshooting functions are provided by the Sysmac Studio  You can use the troubleshooting func   tions to identify errors that occur in a Controller  and reset the errors     du  Lui  Ka  O  C  GC  D        gt   O                zZ  O     1   Di   F
22.  DeviceNet  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W497     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503        34BD0000 hex   Verification    34BE0000 hex   Structure    Error    34BF0000 hex   Master I O    Refresh Error    34C00000 hex   Master User   set Alloca   tions User    Setting Failed    34C10000 hex   Communica   tions Cycle  Time Setting    Failed    The slave informa   tion registered in  the scan list does  not agree with the  actual slave infor   mation     The scan list is dis   abled and an error  occurred that pre     vented making I O  allocations     The I O memory in  the destination  CPU Unit for I O  refreshing could not  be found when  refreshing the mas   ter function data in  the CPU Unit     An error occurred in  the following opera   tion for user alloca   tion of the master     An error occurred in  one of the following  operations when  setting the commu   nications cycle  time     NJ series Troubleshooting Manual  W503     e A slave that is in the scan list  does not exist     The node address of the local  Unit  which is the master  is reg   istered in the scan list     If the system is set to check the  vendor in the detailed verifica   tion settings  the vendor of the  slave does not match the regis   tration in the scan list     If the connection path is set in  the detailed verification set   tings  then setting the connec   tion
23.  During Loopback Test  e Loopback test jig failure   e Noise    e The communications circuits  in the Serial Communica   tions Unit are faulty     OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD    846B0000 hex   Parity Error A parity error In Serial Gateway Mode or Pro  Same as  occurred  tocol Macro Mode  above     e The reception circuits in the  Serial Communications Unit  are faulty     e A transmission error occurred  due to noise or other factors     During Loopback Test  e Loopback test jig failure   e Noise    e The communications circuits  in the Serial Communica   tions Unit are faulty        846C0000 hex   Overrun An overrun error  The communications conditions Same as  Error  Fram  framing error  or and baud rate settings do not above   ing Error  or parity error match the host     Parity Error occurred  Noise or other external interfer    Transmis  ence     SIU s  n  s f9 Ul S1013 J          sion Error     The baud rate is outside the  allowable range or there are bit  errors due to different stop bit  settings or other parameters   The communications cable wir   ing is faulty    Terminating resistance is not  set correctly for the RS   422A 485 ports     Wiring is faulty or terminating  resistance is not set correctly  on an NT AL001 or other  Adapter   846D0000 hex   Transmis  A CRC error Noise Same as    sion Error occurred  CRC calculation method does above    CRC Error  not match the device     NJ series Troubleshooting Manual  W503  3 67    3 Er
24.  Ee 1 3  t2 Fatal KEE EE EE 1 4  1 2 1 TYPES Of Pala de EE 1 4  1 2 2 Checking Tor Fatal e E 1 4  to Nomfatal EOF tege EEN 1 5  1 3 1 Types  Of NOf fatal ETS eege Seege cee Sextet oad EENS 1 5  1 3 2 Checking for Non fatal Errors              cccccsseececceceeeeeceeeeeeecaeeeeceseceeeeeeaeeeeessaseeeessaeeeeeseeasesessaanees 1 11  1 3 3 Resetting  Non fatal EMOS E 1 13  Section 2 Error Troubleshooting Methods  2 1  Troubleshooting FIOWCNANS i eegene 2 2  2 1 1 Checking to See If the CPU Unit Is COpoeratng  ER ceceeeeeeceeeeeeeeeeeeeeeaaaaeeeeeesenaaseeeeenensags 2 2  2 1 2 Troubleshooting Flowchart for Non fatal Errors             ccccccceeeeeeeeeeeeeeeeeeeeaaeeeeeeeesaeaaeeeeeeeesaaaeeeneess 2 3  2 2 Troubleshooting Fatal  EPO gedeien a a aa a a aa a a E 2 4  2 3 Troubleshooting Non fatal EEGENEN 2 5  2 3 1 Identifying and Resetting Errors with the Sysmac Gtudo   2 5  2 3 2 Identifying and Resetting Errors with an NS SerieS Hl  2 9  2 3 3 Identifying and Resetting Errors from the User brogram  2 11  2 3 4 Checking for Errors with System defined Variables              000nnnnennnnnnsnnnnnernnensrrnnnssrrenssrrrensrrenene 2 13  2 4 Troubleshooting When You Cannot Go Online from the Sysmac Studio                   20008 2 14    NJ series Troubleshooting Manual  W503  9    CONTENTS       2 4 1 Causes and Correction When You Cannot Go Online from the Sysmac Studie    2 14  2 4 2 Troubleshooting for Each Cause  2 15  Section 3 Error Tables  sch EMOS DV SOUCO isio a S e a eee eee m
25.  Error than the specified  value when the  power supply was  turned ON     EtherCAT A communications   State state change com    Change Error   mand was received  for which the cur   rent communica   tions state could not  be changed     EtherCAT An undefined com    Illegal State munications state   Change Error   change command  was received     The number of con   tions Syn  secutive errors in  chronization   receiving data dur   Error ing the communica   tion sync time  exceeded the value  specified for the  Communications  Control Setting     Communica     e EtherCAT communications   change from Init to Pre opera   tional state  was established or  an attempt to turn ON the  Servo from the Controller   enable operation  was made  while executing an FFT that  operates with the Servo Drive  trial run     e The rotation of the encoder was  higher than the specified value  when the power supply was  turned ON     e A communications state  change command was received  for which the current communi   cations state could not be  changed     e An undefined communications  state change command was  received     e Power to the host controller was  interrupted during PDO com   munications     e An EtherCAT communications  cable is disconnected  broken   or incorrectly connected     e Noise       3 Error Tables    p Level O     a m Tae GEN    AC Servomo   tors Servo  Drives G5  Series with  Built in Ether   CAT Commu   nications  User s Man   ual  Cat  No   1576     Same as  above   
26.  Errors for Self Diagnosis W500  SD Memory Card Invalid Format Errors for Self Diagnosis W500    SD Memory Card Restored or For  Errors for Self Diagnosis W500  matted    SD Memory Card Data Corrupted Errors for Self Diagnosis W500    SD Memory Card Access Power OFF   Errors for Self Diagnosis W500  Error    Main Memory Check Error Errors for Self Diagnosis W500  Battery backup Memory Check Error   Errors for Self Diagnosis W500    User Program Controller Configura  Errors Related to Controller Opera    W500  W501  tions and Setup Transfer Error tion    Illegal User Program Execution ID Errors Related to Controller Opera    W500  W501    tion   Event Log Restoration Error Errors Related to Controller Opera    W500  W501  tion   Illegal User Program Errors Related to Controller Opera    W500  W501  tion    Illegal User Program Controller Con    Errors Related to Controller Opera    W500  W501    figurations and Setup tion    Trace Setting Transfer Failure Errors Related to Controller Opera    W500  W501  tion    CPU Bus Unit Setup Area Error Errors Related to FINS Communica    W501  tions    vn  W506  W506  W508    Absolute Encoder Home Offset Read   General Motion Control W507  Error  Motion Control Parameter Setting General Motion Control W507  Error    Cam Data Read Error General Motion Control W507  Cam Table Save Error General Motion Control W507    Protocol Data Error CJ series Serial Communications W494  Units    Invalid Message Timer List Error CJ series DeviceNet Unit
27.  EtherCAT Communications    External Encoder Connection Error    G5 series Servo Drives with Built in 1576  EtherCAT Communications    Function Setting Error    Safe Mode Errors Related to Controller Opera  W500  W501  tion    EtherCAT Fault Built in EtherCAT Master in CPU Unit   W505  Motion Control Initialization Error General Motion Control W507    Electronic Gear Ratio Numerator Set    Motion Control Instructions W508  ting Out of Range   Electronic Gear Ratio Denominator Motion Control Instructions W508  Setting Out of Range    E  W508  W508  W508  W508    Master Coefficient Scaling Out of Motion Control Instructions W508  Range  Slave Coefficient Scaling Out of Motion Control Instructions W508  Range  Feeding Velocity Setting Out of Motion Control Instructions W508  Range    Buffer Mode Selection Out of Range   Motion Control Instructions W508    Coordinate System Selection Out of   Motion Control Instructions W508  Range   Circular Interpolation Mode Selection   Motion Control Instructions W508  Out of Range    E  W508  w508  w508    Transition Mode Selection Out of Motion Control Instructions W508  Range   Continue Method Selection Out of Motion Control Instructions W508  Range   Combine Mode Selection Out of Motion Control Instructions W508  Range   Synchronization Start Condition Motion Control Instructions W508  Selection Out of Range   Master and Slave Defined as Same Motion Control Instructions W508  Axis   Master and Auxiliary Defined as Motion Control Instructi
28.  EtherCAT Master Function Mod   ule     Get EtherNet IP Error Status GetEIPError Gets the status and the event code of the error with the  highest level of the Controller errors in the EtherNet IP  Function Module     Refer to the NJU series Instructions Reference Manual  Cat  No  W502  for details on these instructions        NJ series Troubleshooting Manual  W503  2 11    T  Wi  Ca  SG  E  CH  D  N   gt   O          gt          O     T  D  mp     m        SG     a       LUSIDOoL   JOS 24  WO SIO Bulesey pue BulAjnuep      E Z    2 Error Troubleshooting Methods    Example of Error Detection for the EtherCAT Master Function Module  User defined Variables  trigger  BOOL   ec_error  BOOL       Get condition    EtherCAT master error flag    trigger       GetECError GC error    Resetting Controller Errors with Instructions    You can use the instructions that are provided to reset errors in the user program to reset errors that  occur in the Controller  Before you attempt to reset a Controller error  isolate and remove the cause of  the error  Reset the errors with the instruction provided to reset errors for each function module     Instruction name    Instruction   Function    Reset PLC Controller Error ResetPLCError Resets current Controller errors from the PLC Function  Module     Reset I O Bus Controller Error Resets current Controller errors from the I O bus    Reset Motion Control Error Resets current Controller errors from the Motion Control  Function Module    Reset Ethe
29.  Motion Con   trol Function  Module   Communica   tions Control   ler Failure   EtherCAT  Master Func   tion Module     Flashes at 1 s  intervals     Continues  2    Front     green   panel RUN Not lit Lit  indica     green   tors      ERROR Im   red   RUN out    OFF ON  put on  Power  Supply  Unit  User pro    Stops   gram  NJ  execu   series tion sta   CPU   tus a  Unit Outputs   Yes No  opera    turned  tion OFF          Not possible  Depends on  the nature of  the error     Recorded   Event  Some errors  logs are not    recorded      NJ series Troubleshooting Manual  W503        Recorded     These errors  prevent part of  the control  operations in a  certain func   tion module     e Positive Limit  Input  Detected   Motion Con   trol Function  Module     Analog Input  Disconnec   tion Detected   CJ series  Unit    Low Battery  Voltage  PLC  Function  Module     O    it   it  N  O    the error     e Packet Dis   carded Due  to Full  Reception  Buffer  Eth   erNet IP  Function  Module        Depends on  the nature of    D    Controller  information    Major fault Partial fault Minor fault      Observation Information  level level level    These errors  do not affect  system control  operations     These are not  errors  but  appear in the  event log to  notify the user  of specific  information   e Power  Turned ON    e Power Inter   rupted   e Memory All  Cleared    Flashes at 1 s   Not lit Not lit  intervals    TI l    Continues     No    Recorded     1 7    mmh  I  Ai  
30.  Noise is entering on the  encoder line    e The ambient temperature is too Same as  high  above    e Servomotor failed    e The life expectancy of the Same as  capacitor or the fan is shorter above   than the specified value    e There is insufficient power sup  Same as  ply voltage for the external above   encoder    e Noise is entering on the exter   nal encoder connector cable    e The external encoder failed    e There is insufficient power sup  Same as  ply voltage for the external above     encoder     e Noise is entering on the exter   nal encoder connector cable     Data Setting   An object setting is ie An object setting is out of Same as  Warning out of range  range  above     Overload The load ratio is    Warning 85  or more of the    protection level     Excessive The regeneration    Regenera  load ratio is 85  or    tion Warning   more of the level     e Overload Same as  e There is incorrect wiring of the above   motor line or a broken cable        Vibration Vibration was    Detection detected   Warning    e There is excessive regenera  d Same as  tion  above    e This Regeneration Resistor  cannot be used for continuous  regenerative braking    e The gain or inertial ratio setting d Same as  is not suitable  above     NJ series Troubleshooting Manual  W503        3 Error Tables       Lwa O     74800000 hex   Command    A command could e The absolute multi rotation AC Servomo     Warning    not be executed     counter was cleared when the  Servo was not OFF whe
31.  Or  division by an inte   ger of O occurred in division  or remainder calculations     The relationship for the  instruction input parame   ters did not meet required  conditions  Or  a numeric  value during or after  instruction execution did  not meet conditions     Non numeric data was  input for a real number  input variable to an instruc   tion     A value that was not BCD  was input for a BCD input  parameter to an instruction     exceeded the valid range for an input vari   able  Or  division by an integer of O occurred  in division or remainder calculations     The relationship for an input parameter did  not meet required conditions    A value when processing an instruction or in  the result does not meet the conditions     Non numeric data was input for a real num   ber input variable to an instruction     A hexadecimal digit of A  B  C  D  E  or F  was input for a BCD input parameter to an  instruction        e An input parameter for an instruction    NJ series  Instructions  Reference  Manual  Cat   No  W502     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables                16 0404 Signed BCD Error   An illegal value was input e An illegal value was input for the most signif    NJ series  for the most significant digit icant digit for a signed BCD input parameter   Instructions  for a signed BCD input to an instruction  Reference  parameter to an instruction  e The most significant digit was 2 to 
32.  Processing Setting Error   CJ series Analog I O Units W490  Input Value Exceeded Adjustment CJ series Analog I O Units W490  Range in Adjustment Mode   Input Number Specification Error in CJ series Analog I O Units W490  Adjustment Mode    Scaling Data Setting Error CJ series Analog I O Units W490    Input Signal Range Setting Error or CJ series Analog I O Units W490  Error in Number of Inputs Setting  Mean Value Processing Setting Error   CJ series Analog I O Units W490    Error in Setting of Conversion Mode   CJ series Analog I O Units W490  Output Hold Setting Error CJ series Analog I O Units W490    Output Number Specification Error in   CJ series Analog I O Units W490  Adjustment Mode   Conversion Time Resolution Setting   CJ series Analog I O Units W490  Error or Operation Mode Setting Error    Output Signal Range Setting Error or   CJ series Analog I O Units W490  Error In Number of Outputs Used Set   ting    UO Number Specification Error in CJ series Analog I O Units W490  Adjustment Mode    Data Range Error CJ series Process I O Units W498  Setting Error CJ series Temperature Control Units   W491    Results Information  Data Storage CJ series ID Sensor Units Z317  Area Specification Error    System Setup Error CJ series Serial Communications W494  Units    waor  was   was   was     Master User set Allocations User Set    CJ series DeviceNet Units W497   ting Failed   Communications Cycle Time Setting   CJ series DeviceNet Units W497   Failed   Slave I O Refresh Erro
33.  Servo Drive The Servo Drive and Servomo  Same as  conformity and Servomotor tor combination is not correct  above   combination is not  correct     34E10000 hex   Servo Drive The temperature of The ambient temperature of the Same as  Overheat the Servo Drive Servo Drive exceeded the above   radiator or power specified value   elements exceeded Overload  the specified value        34E20000 hex   Overload When the feedback Operation was continued for a Same as  value for torque long time while overloaded  above     command exceeds There is incorrect wiring of the  the overload level motor line or a broken cable   specified in the   Overload Detection   Level Setting  3512    hex   overload pro   tection is per   formed according to  the overload char   acteristics     NJ series Troubleshooting Manual  W503  3 47    3 Error Tables       wea O     34E30000 hex   Regenera  The regenerative e The load inertia is too large  Or  AC Servomo   tion Overload   energy exceeds the the Servomotor rotation speed tors Servo   processing capac  is too high to absorb the regen  Drives G5   ity of the Regenera  erative energy within the speci  Series with   tion Resistor  fied deceleration time  Built in Ether   This Regeneration Resistor CAT Commu   cannot be used for continuous nications  regenerative braking   The User s Man   operating limit of the external ual  Cat  No   resistor is limited to a 10  1576   duty     34E40000 hex   Error Counter   Position error Motor operation does not fol
34.  Troubleshooting Manual  W503     3 Error Tables    Event code Event name Functional classification Reference    900B0000 hex Memory All Cleared Errors Related to Controller Opera  W500  W501  tion    900C0000 hex Event Log Cleared Errors Related to Controller Opera    W500  W501  tion   90110000 hex Power Turned ON Errors Related to Controller Opera  W500  W501  tion   90120000 hex Power Interrupted Errors Related to Controller Opera  W500  W501  tion    90130000 hex Operation Started Errors Related to Controller Opera  W500  W501  tion   90140000 hex Operation Stopped Errors Related to Controller Opera    W500  W501  tion   90150000 hex Reset Executed Errors Related to Controller Opera  W500  W501  tion   90160000 hex User Program Execution ID Write Errors Related to Controller Opera  W500  W501  tion   90180000 hex All Controller Errors Cleared Errors Related to Controller Opera  W500  W501  tion   90190000 hex Forced Refreshing Cleared Errors Related to Controller Opera    W500  W501  tion    940C0000 hex SNMP Started Started Built in   Built in EtherNet IP Port on CPU Unit   Port   Built in EtherNet IP Port on CPU Unit   CPU Unit   W506   94200000 hex Notice C Insufficient Travel Distance   General Motion Control W507  to Achieve Blending Transit Velocity   94210000 hex Error Clear from MC Test Run Tab General Motion Control W507  Page    98010000 hex Absolute Value Cleared G5 series Servo Drives with Built in 1576  EtherCAT Communications    98020000 hex Position Data I
35.  V073  for details on the operation authority        2 3 3 Identifying and Resetting Errors from the User Program  In an NJ series Controller  you can check for errors that have occurred from the user program  This fea   ture allows you to program operations in the user program according to the error status  Special instruc     tions are provided for this purpose  These include instructions to get Controller error information and  instructions to reset Controller errors     Instructions That Get Controller Error Information    Determine the error status with the instruction to get error information that is provided for each function  module  The following table lists the instruction that are used to get error information for each function  module     Instruction name   Instruction     Function    Get PLC Controller Error Status   GetPLCError Gets the status and the event code of the error with the  highest level of the Controller errors in the PLC Function  Module     Get I O Bus Error Status GetCJBError Gets the status and the event code of the error with the  highest level of the Controller errors in the I O bus     Get Motion Control Error Status   GetMCError Gets the status and the event code of the error with the  highest level of the Controller errors in the Motion Control  Function Module     Get EtherCAT Error Status GetECError Gets the status and the event code of the error with the  highest level of the communications port errors and mas   ter errors detected by the
36.  address  or data was specified  in a received Modbus RTU  command     One of the following errors  occurred     e Tfs  Send Finished Monitor   ing Time  Exceeded    Tfr  Receive Finished Moni   toring Time  Exceeded    Tr  Receive Wait Monitoring  Time  Exceeded    FCS Check Error  Command Error  Timeout Error  Overrun Error  Framing Error  Parity Error       In Serial Gateway Mode or Pro    tocol Macro Mode    e The reception circuits in the  Serial Communications Unit  are faulty    e A transmission error occurred  due to noise or other factors    No protocol Mode    e The reception buffer received  more than 259 bytes of data  before the SerialRev instruc   tion was executed    During Loopback Test   e Loopback test jig failure    e Noise   e The communications circuits  in the Serial Communica   tions Unit are faulty       Level O     a aee een    CJ series  Serial Com   munications  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W494     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     846A0000 hex   Framing A frame error e In Serial Gateway Mode or Pro  CJ series  Error occurred  tocol Macro Mode  Serial Com     e The reception circuits in the munications    Serial Communications Unit Units Opera   are faulty  tion Manual for    NJ series  CPU Unit  Cat   No  W494        e A transmission error occurred  due to noise or other factors    
37.  cations between the  external encoder Co  and the Servo Drive im  were stopped more m  frequently than the a  specified value  e  D gt   O080D0000 hex   External There was a com  There is insufficient external Same as m  Encoder munications error in encoder power supply voltage  above  T  Communica    data from the exter    e Noise     tions Data nal encoder   Error 2  O80E0000 hex   External Bit 00 of the exter  Bit OO of the external scale error Same as S  Encoder Sta    nal encoder error code  ALMC  was set to 1  above   tus Error 0 code  ALMC  was  set to 1   O80FO000 hex   External Bit 01 of the exter  Bit 01 of the external encoder Same as  Encoder Sta    nal encoder error error code  ALMC  was set to 1  above   tus Error 1 code  ALMC  was  set to 1   08100000 hex   External Bit 02 of the exter  Bit 02 of the external encoder Same as  Encoder Sta    nal encoder error error code  ALMC  was set to 1  above   tus Error 2 code  ALMC  was  set to 1   08110000 hex   External Bit 03 of the exter  Bit 03 of the external encoder Same as  Encoder Sta    nal encoder error error code  ALMC  was set to 1  above   tus Error 3 code  ALMC  was  set to 1   08120000 hex   External Bit 04 of the exter  Bit 04 of the external encoder Same as  Encoder Sta    nal encoder error error code  ALMC  was set to 1  above   tus Error 4 code  ALMC  was  set to 1   08130000 hex   External Bit 05 of the exter  Bit 05 of the external encoder Same as  Encoder Sta    nal encoder error error code  ALMC  w
38.  composition axis that was not  stopped     When the MC_GroupEnable   Enable Axes Group  instruc   tion was executed  there was a  composition axis for which the  MC_TouchProbe  Enable Exter   nal Latch  instruction was being  executed        3 Error Tables    p Level O     a Tae SS    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     3 21    OO  I      m        O     Vu  o   lt   GU  O  c     O  OD       BINDO  uonouny  O1 UOD uono 3y  Ul SIO E L       3 Error Tables    e An operation instruction was    54410000 hex    54420000 hex    54430000 hex    54440000 hex    54450000 hex    54460000 hex    54470000 hex    3 22    Impossible  Axis Opera   tion Speci   fied when the  Servo is OFF    Composition  Axis Stopped  Error    Motion Con   trol Instruc   tion Multi   execution  Buffer Limit  Exceeded    Insufficient  Travel Dis   tance    Insufficient  Travel Dis   tance to  Achieve  Blending  Transit Veloc   ity   Move Link  Constant  Velocity  Insufficient  Travel Dis   tance    Positioning  Gear Opera   tion Insuffi   cient Target  Velocity    An operation  instruction was exe   cuted for an axis for  which the Servo is  OFF     A motion instruction  was executed for an  axes group while  the MC_Stop  instruction was  being executed for  a composition axis     The number of  motion control  instructions that is  buffered for Buff
39.  events according to the effect that the errors  have on control     No  Classification Level name  High Controller errors Major fault level    Partial fault level  Minor fault level  Observation         Controller informa  Information  tion    Errors with a higher level have a greater impact on the functions that the NJ series Controller pro   vides  and are more difficult to recover from  When an event occurs  the Sysmac Studio or PT will  display the level        Event Levels    e Major Fault Level   These errors prevent control operations for the entire Controller  When the CPU Unit detects a  major fault  it immediately stops the execution of the user program and turns OFF the loads of all  slave  including remote I O  With EtherCAT slaves and some CJ series Special Units  you can set  the slave settings or Unit settings to select whether outputs will go OFF or retain their previous  status  You cannot reset major fault level errors from the user program  the Sysmac Studio or an  NS series PT  To recover from a major fault level error  remove the cause of the error  and either  cycle the power supply to the Controller  or reset the Controller from the Sysmac Studio     e Partial Fault Level  These errors prevent control operations in a certain function module in the Controller  The NJ   series CPU Unit continues to execute the user program even after a partial fault level error occurs   You can include error processing in the user program in order to stop equipment safel
40.  incorrect or the sensor is  faulty     The Operation Selection at  Negative Limit Input or Opera   tion Selection at Positive Limit  Input parameter is set to No  reverse turn     The location of the homing  input signal sensors  homing  settings  and homing start posi   tion cause a limit input to be  reached     The input signal sensor wiring  is incorrect or the sensor is  faulty     The wiring of the limit signal is  incorrect     The limit sensor is installed in  the wrong location     The contact logic of the limit  signal is not correct     The limit sensor failed     The wiring of the home proxim   ity signal or limit signal is incor   rect    The home proximity sensor or  limit sensor is installed in the  wrong location    The contact logic of the home  proximity signal or limit signal is  not correct    The home proximity sensor or  limit sensor failed        NJU series  CPU Unit  Motion Con   trol User   s  Manual  Cat   No  W507     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     3 13    OO  I      m        O     Vu  o   lt   GU  O  c     O  OD       BINDO  uonouny  O1 UOD uono 3y  Ul SIO E L       3 Error Tables    74280000 hex    74290000 hex    742A0000 hex    742B0000 hex    742C0000 hex    742D0000 hex    742F0000 hex    74300000 hex    74330000 hex    3 14    Home Prox   imity Homing  Direction  Limit Input  Detected    Home  Input Hom   ing Opposite  Direction  Limit Input  Detected    Home  Input Hom   ing Di
41.  path that is set in the scan  list failed     The size of the slave I O data  does not match the registration  in the scan list     If the device type is set in the  detailed verification settings   then setting the device type that  is set in the scan list failed     If the product code is set in the  detailed verification settings   then setting the product code  that is set in the scan list failed     The device does not support  the I O service specified in the  scan list     The I O words allocated to  slave overlap     The I O words allocated to the  slave exceed the valid range     The I O size of the slave  exceeds 200 bytes for outputs  or 200 bytes for inputs     I O words are allocated in an  EM bank that does not exist     The master function is not  enabled     There is a mistake in the user  allocations in the master     CPU Unit is not in PROGRAM  mode     More than one software switch  changed to TRUE at the same  time  Or  another software  switch changed to TRUE before  processing was completed for a  previous software switch     There is an error in the set  information     CPU Unit is not in PROGRAM  mode     3 Error Tables    p Level O     a Tae Ga    CJ series  DeviceNet  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W497     d Same as  above    d Same as  above     d Same as  above     d Same as  above     3 69    OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       SIU s  n  s f9 Ul S1013 J          3 Error Tables    The I 
42.  spec   ified for the Reference Type  input variable to the instruction     Something other than a cam  data variable was specified for  the CamTable input variable to  the instruction          Level O     a aTe ee    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     e The MC_CamOut  End Cam    543A0000 hex    543B0000 hex    543C0000 hex    543D0000 hex    543E0000 hex    543F0000 hex    54400000 hex    Synchroniza   tion Stopped    Motion Con   trol Instruc   tion Re   execution  Disabled    Motion Con   trol Instruc   tion Multi   execution  Disabled    Instruction  Not Allowed  for Encoder  Axis Type    Instruction  Cannot Be  Executed  during Multi   axes Coordi   nated Control    Multi axes  Coordinated  Control  Instruction  Executed for  Disabled  Axes Group    Axes Group  Cannot Be  Enabled    A synchronized  control motion con   trol instruction was  executed  but con   ditions required for  execution were not  met     An attempt was  made to re execute  a motion control  instruction that can   not be re executed     Multiple functions  that cannot be exe   cuted simulta   neously were  executed for the  same target  MC  common or axis      An operation  instruction was exe   cuted for an  encoder axis     An operation  instruction was exe   cuted for an axis 
43.  that was in a coordi   nated multi axes  motion     A multi axes coordi   nated control  instruction was exe   cuted for an axes  group that was in  the Axes Group  Disabled state     Execution of the  MC_GroupEnable   Enable Axes  Group  instruction  failed     NJ series Troubleshooting Manual  W503     Operation  instruction was exe   cuted even though the  MC_CamIn  Start Cam Opera   tion  instruction is not being  executed     The MC_GearOut  End Gear  Operation  instruction was exe   cuted even though the  MC_GearlIn  Start Gear Opera   tion  or the MC_GearlnPos   Positioning Gear Operation   instruction is not being exe   cuted     The MC_Phasing  Shift Master  Axis Phase  instruction was  executed even though the  MC_CamIn  Start Cam Opera   tion   MC_GearlIn  Start Gear  Operation   MC_GearInPos   Start Gear Operation   or  MC_MoveLink  Synchronous  Positioning  instruction is not  being executed     A motion control instruction that  cannot be re executed was re   executed     Multiple functions that cannot  be executed simultaneously  were executed for the same tar   get  MC common or axis      An operation instruction was  executed for an encoder axis     An operation instruction was  executed for an axis that was in  a multi axes coordinated  motion     A multi axes coordinated con   trol instruction was executed for  an axes group that was in the  Axes Group Disabled state     When the MC_GroupEnable   Enable Axes Group  instruc   tion was executed  there was a 
44.  to Unit Configuration   W500  24030000 hex End Cover Missing Errors Related to Unit Configuration   W500    24040000 hex Incorrect Unit Expansion Rack Con    Errors Related to Unit Configuration   W500  nection    24610000 hex Switch Setting Error Block I O  GX series EtherCAT Slave   W488  Units    24680000 hex Motor Non conformity G5 series Servo Drives with Built in   1576  EtherCAT Communications   24690000 hex Motor Non conformity G5 series Servo Drives with Built in   1576  EtherCAT Communications   246A0000 hex Motor Non conformity G5 series Servo Drives with Built in   1576  EtherCAT Communications   246B0000 hex Motor Non conformity G5 series Servo Drives with Built in   1576  EtherCAT Communications   246C0000 hex Motor Non conformity G5 series Servo Drives with Built in   1576  EtherCAT Communications    34010000 hex I O Setting Check Error Errors Related to Unit Configuration   W500    Wi  N  m   lt   OD   gt   mr       5  O     Q   OD     O  mb  m   lt        gt   mp  O  O  Q   ui            SOT 1013   t    34100000 hex IP Address Table Setting Error Errors Related to FINS Communica    W501  tions   34110000 hex Unknown Destination Node Errors Related to FINS Communica    W501  tions   34130000 hex FINS TCP Connection Table Setting   Errors Related to FINS Communica    W501  Error tions    34200000 hex Tag Data Link Setting Error Built in EtherNet IP Port on CPU Unit   W506  34210000 hex Basic Ethernet Setting Error Built in EtherNet IP Port on CPU Unit   W506  
45.  user actions   e No lit  There are no minor fault level or higher level errors   EtherNet IP EtherNet IP Function Module Status    NET ERR e Lit  Errors for which normal status cannot be recovered through user actions  i e   errors  for which you must replace the CPU Unit or contact your OMRON representative      e Flashing  Errors for which normal status can be recovered through user actions   e No lit  There are no minor fault level or higher level errors     H Checking with the Troubleshooting Function of Sysmac Studio    When an error occurs  you can connect the Sysmac Studio online to the Controller to check current  Controller errors and the log of past Controller errors        Current Errors    Open the Sysmac Studio   s Controller Error Tab Page to check the current error   s level  source   source details  event name  event code  details  attached information 1 to 4  actions  and correc   tions  Errors are not displayed for observations     o Log of Past Errors    Open the Sysmac Studio   s Controller Event Log Tab Page to check the times  levels  sources   source details  event names  event codes  details  attached information 1 to 4  actions  and correc   tions for previous errors     Refer to the NU Series Sysmac Studio Version 1 Operation Manual  Cat  No  W504  for details on  troubleshooting with the Sysmac Studio     i Checking with the Troubleshooter of an NS series PT    When an error occurs  if you can connect communications between an NS series PT and the 
46.  was specified for  the  MC_MoveCircular2  D  Circular 2D  Interpolation   instruction     For the  MC_MoveCircular2  D  Circular 2D  Interpolation   instruction  the  radius of the circle  exceeded the maxi   mum value for the  border point or cen   ter specification  method     The parameter  specified for the Cir   cAxes input variable  to a motion control  instruction is out of  range     The values of the  parameters for the  Auxiliary and Slave  input variables to a  motion control  instruction are not  in ascending order     A phase that was  not in ascending  order was found  during calculating  the number of valid  data  Or  after cal   culations  the num   ber of valid data is  0     The parameter  specified for the  Target input vari   able to a motion  control instruction is  out of range     The parameter  specified for the  MasterDistance  input variable toa  motion control  instruction is out of  range     e For the MC_MoveCircular2D     Circular 2D Interpolation   instruction  it was not possible  to create a circular path for the  specified radius when the  radius method was specified for  circular interpolation     For the MC_MoveCircular2D   Circular 2D Interpolation   instruction  the radius of the cir   cle exceeded 40 bit data when  converted to pulses for the bor   der point or center specifica   tion method     Instruction input parameter  exceeded the valid range of the  input variable     The axes that were specified in  CircAxes are not included in 
47. 0 hex   Command The position com  The change in position com  Same as  Error mand variation after mand is too large  above     3 48    the electronic gear  exceeded the spec   ified value     The backlash compensation  amount is too large        NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O           38420000 hex   Command During position e During position command pro  AC Servomo   Generation command process  cessing  an error such as a cal  tors Servo  Error ing  an error such culation range error occurred  Drives G5  as a calculation Series with  range error Built in Ether   occurred  CAT Commu   nications Ce  User s Man     ual  Cat  No  7  1576  a  38430000 hex   ErrorCounter   The absolute The absolute encoder  absolute Same as 2  Overflow 1 encoder  absolute scale  position in pulses divided above  A  scale  position in by the electronic gear ratio    pulses divided by GEES D  the electronic gear  2 147 483 648    ratio exceeded   231   2 147 483 648    38440000 hex   Error Counter   The position follow  There is insufficient torque  Same as  Overflow 2 ing error in pulses There is insufficient gain  above  T  exceeded  229 The encoder wiring is incorrect  e   536 870 912   Or  m  the position follow  a  ing error in com     mand units m  exceeded  230 D   1 073 741  824       38450000 hex   Interface There is a dupli  There is a duplicate setting in Same as a  Input Dupli  cate setting in the the input signal  IN1  IN2  INS  above  D  cate Alloc
48. 0 hex  54700000 hex    First Position Method Specification  Out of Range    54710000 hex    Motion Control Instruction Re execu   tion Disabled  First Position Method     Unused Axis Specification for Auxil  Motion Control Instructions W508  lary Axis    3 82 NJ series Troubleshooting Manual  W503     54720000 hex    54740000 hex    Event code  54750000 hex  54760000 hex    54770000 hex    54780000 hex  54790000 hex  547A0000 hex    547B0000 hex    547C0000 hex    547D0000 hex    547E0000 hex    547F0000 hex    54800000 hex    54810000 hex  54820000 hex    54830000 hex    54840000 hex    54850000 hex  54860000 hex    54870000 hex    54880000 hex    54890000 hex    548A0000 hex  548B0000 hex    548C0000 hex  548D0000 hex  548E0000 hex    548F0000 hex    54900000 hex    54910000 hex    54920000 hex    3 Error Tables    Event name Functional classification Reference    Position Gear Value Error Motion Control Instructions    Position Gear Master Axis Zero Motion Control Instructions  Velocity   Cam Table Data Error during Cam General Motion Control  Motion    Target Position Setting Out of Range   Motion Control Instructions  Travel Distance Out of Range Motion Control Instructions    Cam Table Start Point Setting Out of   Motion Control Instructions  Range   Cam Master Axis Following First Posi    Motion Control Instructions  tion Setting Out of Range   Circular Interpolation Radius Setting   Motion Control Instructions  Error   Circular Interpolation Radius Over  Motion Contro
49. 000 hex    545F0000 hex    54600000 hex    54610000 hex    54620000 hex    3 26    Motion Con   trol Instruc   tion Re   execution  Disabled   MasterStart   Distance     Motion Con   trol Instruc   tion Re   execution  Disabled   Continuous     Motion Con   trol Instruc   tion Re   execution  Disabled   MoveMode     Illegal Auxil   lary Axis  Specification    Illegal Axis  Specification    Illegal Axes  Group Speci   fication    Illegal Mas   ter Axis  Specification    An attempt was  made to change the  parameter for the  MasterStartDis   tance input variable  when re executing  a motion control  instruction   This  input variable can   not be changed  when re executing  an instruction      An attempt was  made to change the  parameter for the  Continuous input  variable when re   executing a motion  control instruction    This input variable  cannot be changed  when re executing  an instruction      An attempt was  made to change the  parameter for the  MoveMode input  variable when re   executing a motion  control instruction    This input variable  cannot be changed  when re executing  an instruction      The axis specified  for the Auxiliary  input variable toa  motion control  instruction does not  exist     The axis specified  for the Axis input  variable to a motion  control instruction  does not exist     The axes group  specified for the  AxesGroup input  variable to a motion  control instruction  does not exist or is  not a used group     The axis specified  for th
50. 1     34940000 hex   Setting Error   There is an illegal e The set value is incorrect  d Same as  setting  above    64840000 hex   Sensor Error   An error occurredin      Error in input from the Sensor  d Same as  the sensor input  above     64850000 hex   CT Overflow   An overflow e The heater current exceeded d Same as  occurred in the CT 55 0 A  above   input    64860000 hex   Heater Burn    A heater burnout e The power supply to the heater d Same as   out Alarm occurred  is not ON  above   e The heater is burned out or  deteriorated     i CJ series ID Sensor Units    The section provides tables of the events that can occur in the following Units     OO  I      m        O     Vu  o   lt   GU  O  c     O  OD          SIU s  n  s f9 Ul S1013 J          CJ1W V680C 11  CJ1W V680C 12  p Level  ae Cd sn LI ven Jemet  isie ee  046C0000 hex   Unit Status  An error occurred in Ve An error occurred in the power CJ series ID    Antenna the power supply to supply  24 V  to the Antenna  Sensor Units  Power Sup  the Antenna  Operation   ply Error Manual for NJ   series CPU  Unit  Cat  No   Z317     046D0000 hex   Unit Status  An error occurred There is a source of noise Same as  Memory when reading non  nearby  above     Error volatile memory  Non volatile memory failure    046E0000 hex   Results Infor    An error occurred in The Antenna is not connected  Same as  mation  the Antenna  Antenna failure above     Antenna The ID Sensor Unit failed   Error    046F0000 hex   Unit Status  An e
51. 2  D  Circular 2D  Interpolation   instruction  Or  the  start point  end  point  and border  point were the  same when the bor   der point method  was specified     The position speci   fied for the center  point exceeded the  allowed range when  the center method  was specified for  the  MC_MoveCircular2  D  Circular 2D  Interpolation   instruction     The  MC_MoveCircular2  D  Circular 2D  Interpolation   instruction was exe   cuted for an axis for  which the Count  Mode was set to  Rotary Mode     The parameter  specified for the  ParameterNumber  input variable to a  motion control  instruction is out of  range     The parameter  specified for the  StopMode input  variable to a motion  control instruction is  out of range     The parameter  specified for the  TriggerIn   put  LatchI D input  variable to a motion  control instruction is  out of range     The parameter  specified for the  Setting Value input  variable to a motion  control instruction is  out of range     NJ series Troubleshooting Manual  W503     e The start point and end point    were the same when the radius  method was specified for the  MC_MoveCircular2D  Circular  2D Interpolation  instruction     The start point  end point  and  border point were the same  when the border point method  was specified for the  MC_MoveCircular2D  Circular  2D Interpolation  instruction     The difference between the dis   tance from the start point to the  center point and the distance  between the end point to the  cen
52. 3 Error Tables    644F0000 hex Deceleration Warning General Motion Control W507    64580000 hex Absolute Encoder Current Position General Motion Control W507  Calculation Failed   64590000 hex Home Undefined during Coordinated   General Motion Control W507  Motion    648D0000 hex Results Information  Verification Error   CJ series ID Sensor Units Z317    Wi  N  m   lt   OD   gt   mr       5  O     Q   OD     O  mb  m   lt        gt   mp  O  O  Q   ui            SOT 1013   t    648E0000 hex Results Information  ID Tag Commu    CJ series ID Sensor Units Z317  nications Error   648F0000 hex Results Information  ID Tag Missing CJ series ID Sensor Units Z317  Error   64900000 hex Results Information  ID System Error   CJ series ID Sensor Units Z317  1   64910000 hex Results Information  ID System Error   CJ series ID Sensor Units Z317  2   64920000 hex Results Information  ID System Error   CJ series ID Sensor Units Z317  3    64930000 hex Results Information  ID Tag Status CJ series ID Sensor Units Z317  64940000 hex Results Information  Error Correction   CJ series ID Sensor Units Z317    64A00000 hex Tfs  Send Finished Monitoring Time    CJ series Serial Communications W494  Exceeded Units    NJ series Troubleshooting Manual  W503  3 85    3 Error Tables    3 86    Event code  64A10000 hex    64A20000 hex    64A30000 hex    64A40000 hex    64A50000 hex    64A60000 hex    64A70000 hex    64AC0000 hex  64CC0000 hex    64E00000 hex    64E10000 hex    64E20000 hex    68010000 hex  
53. 4630000 hex   Slave Function Enable Disable Failed Function Enable Disable Failed   CJ series DeviceNet Units         CJ series DeviceNet Units       DeviceNet Units W497    74640000 hex Sa Fixed Allocation Area Setting CJ series DeviceNet Units W497  Failed   74800000 hex Command Warning G5 series Servo Drives with Built in   1576  EtherCAT Communications   74810000 hex Command Error G5 series Servo Drives with Built in 1576  EtherCAT Communications   78010000 hex Operation Command Competition G5 series Servo Drives with Built in   1576  EtherCAT Communications   78020000 hex Absolute Encoder Status Error G5 series Servo Drives with Built in 1576  EtherCAT Communications    80010000 hex Illegal Packet Discarded Errors Related to Unit Configuration   W500    80100000 hex Packet Discarded Errors Related to FINS Communica    W501  tions   80110000 hex Packet Discarded Errors Related to FINS Communica    W501  tions   80120000 hex Packet Discarded Errors Related to FINS Communica    W501  tions    84050000 hex Packet Discarded Due to Full Recep    Built in EtherNet IP Port on CPU Unit   W506  tion Buffer    84210000 hex Network Configuration Error Built in EtherCAT Master in CPU Unit   W505    842200000 hex   Network Configuration Verification Built in EtherCAT Master in CPU Unit   W505  Error    84230000 hex Slave Initialization Error Built in EtherCAT Master in CPU Unit   W505  84280000 hex Slave Application Error Built in EtherCAT Master in CPU Unit   W505  84290000 hex Proce
54. 501 1500 SL 31810  Hardware        Production information  SYSTEM   1 00 00 22519  Model information Lot number   BOOT   20110627  TOPFE   B 3 0  Rack  0 Slot  1 Unit  0 C 1W V680C12 Ver 1 2  16  10V TOPAW   0 73  Runtime   155  Rack  0 Slot 1 Unit  O CIIW V680C12 Ver 1 2 167  10V   Unit revision  1   PCE revision  100   Software revision  17 0    Output file       Simple Display Detailed Display  In this example     Ver 1 0    is displayed next to the unit model     The following items are displayed     CPU Unit CJ series Units  Unit model Unit model  Unit version Unit version  Lot number Lot number    Rack number  slot number  and unit number       EtherCAT Slaves    1 Double click EtherCAT under Configurations and Setup in the Multiview Explorer  Or  right   click EtherCAT under Configurations and Setup and select Edit from the menu     The EtherCAT Configuration Tab Page is displayed for the Controller Configurations and Setup  layer     2 Right click the master in the EtherCAT Configurations Editing Pane and select Display Produc   tion Information     The Production Information Dialog Box is displayed      3  Production Information EN    Type information   Serial number      Mode RSSD KNO1L ECT Rev 2 1  OMRON Corporation  Oxo0000000       The following items are displayed   Node address   Type information      Serial number      If the model number cannot be determined  such as when there is no ESI file   the vendor ID  product  code  and revision number are displayed  
55. 74200000 hex  74210000 hex  74220000 hex  74230000 hex    74240000 hex    74250000 hex    74260000 hex    74270000 hex    74280000 hex    74290000 hex    742A0000 hex    742B0000 hex  742C0000 hex  742D0000 hex  742F0000 hex  74300000 hex  74320000 hex  74330000 hex  74340000 hex      Eventname     Functional classification Reference    Tfr  Receive Finished Monitoring CJ series Serial Communications W494  Time  Exceeded Units    Tr  Receive Wait Monitoring Time  CJ series Serial Communications W494  Exceeded Units    FCS Check Error CJ series Serial Communications W494  Units   Timeout Error CJ series Serial Communications W494  Units   Comparison Error CJ series Serial Communications W494  Units   Reception Overflow CJ series Serial Communications W494  Units   Command Format Error CJ series Serial Communications W494  Units    Send Timeout Error CJ series DeviceNet Units W497    UO Disconnection Detected Block I O  GX series EtherCAT Slave   W488  Units    Drive Prohibition Input Error 1 G5 series Servo Drives with Built in   1576  EtherCAT Communications   Drive Prohibition Input Error 2 G5 series Servo Drives with Built in   1576  EtherCAT Communications   Immediate Stop Input Error G5 series Servo Drives with Built in   1576  EtherCAT Communications    ns  W507  W507  wsos    Interrupt Feeding Interrupt Signal General Motion Control W507  Missing   Homing Opposite Direction Limit General Motion Control W507  Input Detected   Homing Direction Limit Input General Motion C
56. 8  w508  w508  w508    Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  SlaveOffset    Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  SlaveScaling    Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  StartPosition    Instruction Execution Error with Motion Control Instructions W508  Undefined Home   Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  Position Type    Unused Axis Specification for Master   Motion Control Instructions W508  Axis    First Position Setting Out of Range Motion Control Instructions W508  Last Position Setting Out of Range Motion Control Instructions W508    54640000 hex    54650000 hex    54660000 hex    54670000 hex    54680000 hex    54690000 hex  546A0000 hex    546B0000 hex Illegal First Last Position Size Rela  Motion Control Instructions W508  tionship  Linear Mode    546C0000 hex Master Sync Start Position Setting Motion Control Instructions W508  Out of Range   546D0000 hex Slave Sync Start Position Setting Out   Motion Control Instructions W508  of Range   546E0000 hex Duplicate Latch ID for Trigger Input Motion Control Instructions W508    Condition    Jerk Override Factor Out of Range Motion Control Instructions W508    Acceleration Deceleration Override Motion Control Instructions W508  Factor Out of Range  Motion Control Instructions W508    Motion Control Instructions W508    546F000
57. AT Commu   Error nication Unit  User s Man   ual  Cat  No   1574     04BA0000 hex   Connection An error occurred in Contact failure between the Same as  Inverter and the EtherCAT above   Communications Unit for the       Error the connection  between between the  Inverter and Inverter and the Inverter     Communica    EtherCAT Commu   tions Unit nications Unit for  the Inverter     Inverter trip was reset     The Inverter was initialized or  the mode was changed     The EtherCAT Communications  Unit for the Inverter failed     04BB0000 hex   Inverter An Inverter warn  e An Inverter warning was d Same as  Warning ing was detected  detected  above     NJ series Troubleshooting Manual  W503  3 55       3 Error Tables       weal O     04BC0000 hex   Inverter Trip   An Inverter trip was     An Inverter trip was detected  MX2 Series       detected  Inverter Ether   CAT Commu   nication Unit  User s Man   ual  Cat  No   1574     34F00000 hex   PDO Setting   There is an illegal e The PDO mapping or Sync  Same as    Error setting value in the Manager settings are incorrect  above   PDO mapping        3 1 7 Errors in CJ series Units    The section provides tables of the events that can occur in the CJ series Units   e Analog I O Units   e Process I O Units   e Temperature Control Units   e ID Sensor Units   e High speed Counter Units   e Serial Communications Units   e DeviceNet Units    CJ series Analog UO Units       The section provides tables of the events that can occur in the fol
58. CJ series DeviceNet Units Operation Manual for NJ series CPU Unit  W505 NJ series CPU Unit Built in EtherCAT Port User   s Manual  W506 NJ series CPU Unit Built in EtherNet IP Port Users Manual  1574 MX2 Series Inverter EtherCAT Communication Unit User s Manual  W507 NJ series CPU Unit Motion Control User   s Manual  W508 NJ series Motion Control Instructions Reference Manual  1576 AC Servomotors Servo Drives G5 Series with Built in EtherCAT Communications User s Manual  Z317 CJ series ID Sensor Units Operation Manual for NJ series CPU Unit    3 2 2 Error Table    NJ series Troubleshooting Manual  W503  3 73    3 Error Tables    3 74    Event code  000D0000 hex  000E0000 hex  000F0000 hex  00100000 hex  04010000 hex  04200000 hex  04400000 hex  04600000 hex    04610000 hex  04620000 hex    04680000 hex  046C0000 hex    046D0000 hex  046E0000 hex  046F0000 hex  04740000 hex    04750000 hex    04760000 hex    04880000 hex  04890000 hex  048A0000 hex  04A10000 hex    04A80000 hex    04A90000 hex    04AA0000 hex    04AB0000 hex    04AC0000 hex    04AD0000 hex    04AE0000 hex    04AF0000 hex    04B00000 hex    04B10000 hex    W500   W506  W506  W500  w500  W506    Communications Controller Failure    Built in EtherCAT Master in CPU Unit   W500    CJ series Analog I O Units and CJ   series Process I O Units    A D Conversion Error    Cold Junction Sensor Error CJ series Process I O Units W498    Non volatile Memory Error CJ series Analog I O Units and CJ    W490  W498  series Proce
59. Con   trol Instruc   tion Re   execution  Disabled   Buffer Mode  Selection     Motion Con   trol Instruc   tion Re   execution  Disabled   Direction  Selection     Motion Con   trol Instruc   tion Re   execution  Disabled   Execution  Mode     The parameter  specified for the  Triggerlnput   Mode  input variable to a  motion control  instruction is out of  range     The parameter  specified for the  Triggerlnput  Input   Drive input variable  to a motion control  instruction is out of  range     An attempt was  made to change the  parameter for the  Axis input variable  when re executing  a motion control  instruction   This  input variable can   not be changed  when re executing  an instruction      An attempt was  made to change the  parameter for the  BufferMode input  variable when re   executing a motion  control instruction    This input variable  cannot be changed  when re executing  an instruction      An attempt was  made to change the  parameter for the  Direction input vari   able when re exe   cuting a motion  control instruction    This input variable  cannot be changed  when re executing  an instruction      An attempt was  made to change the  parameter for the  ExecutionMode  input variable when  re executing a  motion control  instruction   This  input variable can   not be changed  when re executing  an instruction      e Instruction input parameter  exceeded the valid range of the  input variable     e A parameter for an input vari   able that cannot be cha
60. Continuous to  a motion control  instruction  changed     The parameter  specified for the  CombineMode  input variable to a  motion control  instruction is out of  range     The parameter  specified for the  LinkOption input  variable to a motion  control instruction is  out of range     The same axis is  specified for the  Master and Slave  input variables to a  motion control  instruction     The same axis is  specified for the  Master and Auxil   iary input variables  to a motion control  instruction     The axis numbers  specified for the  Master and Slave  input variables to a  motion control  instruction are not  in ascending order     The parameter  specified for the  CamTable input  variable to a motion  control instruction is  out of range     exceeded the valid range of the  input variable     _mcAborting or _mcBuffered    was specified for BufferMode  and    _mcTMCornerSuperimpose    was specified for Transition   Mode     The value of the reserved input  variable Continuous changed     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     The parameter is the same for  the Master and Slave input vari   ables to the instruction     The parameter is the same for  the Master and Auxiliary input  variables to the instruction     The parameters for the Master  and Slave input variables to the  instruction were not in ascend   ing order when  _mcLatestCommand was
61. Control   ler  you can check current Controller errors and the log of past Controller errors      Current Errors    Open the Controller Error Tab Page on the NS series PT   s Troubleshooter to check the current  errors event name  event code  level  source  source details  time  details  and attached information  1 to 4  Observations are not displayed on this tab page        Log of Past Errors    Open the Controller Event Log Tab Page on the NS series PT   s Troubleshooter to check the time   level  source  event name  event code  details  and attached information 1 to 4 for previous errors     Refer to the NS series Programmable Terminals Programming Manual  Cat  No  V073  for details on  the NS series PT   s Troubleshooter     NJ series Troubleshooting Manual  W503     1 Overview of Errors       i Instructions That Read Function Module Error Status  amp   O  You can determine the error status with the instructions that get error status provided for each function A  module from the user program  These instructions get the status and the event code of the error with S  the highest level  m  O  Applicable function module Instruction name Instruction     PLC Function Module Get PLC Controller Error Status GetPLCError  Get I O Bus Error Status GetCJBError  Motion Control Function Module   Get Motion Control Error Status GetMCError  EtherCAT Master Function Mod    Get EtherCAT Error Status GetECError  ule  EtherNet IP Function Module Get EtherNet IP Error Status GetEIPError    Fo
62. Controllers and their features   and gives the NJ series Controller specifications     This section describes the variables and control systems of the CPU Unit and CPU  Unit status     This section describes how to use I O ports  how to create the slave configuration  and unit configuration and how to assign functions     This section describes the initial settings of the function modules     This section describes the task system and types of tasks     This section describes programming  including the programming languages and the  variables and instructions that are used in programming     This section describes simulation of Controller operation and how to use the results  of simulation     This section describes CPU Unit status     This section describes the functionality provided by the CPU Unit     This section describes how to go online with the CPU Unit and how to connect to  other devices     This section describes the procedures that are used to actually operate an NJ series  Controller     This section describes the event codes  error confirmation methods  and corrections  for errors that can occur     The appendices provide the CPU Unit specifications  task execution times  system   defined variable lists  data attribute lists  CU series Unit memory information  CJ   series Unit memory allocation methods  and data type conversion information     Manual Configuration    f NJ series Troubleshooting Manual  Cat  No  W503   This Manual     Section    Section 1  Overvi
63. D e The SD Memory Card has run out of free Same as  Insufficient Capac    Memory Card was insuffi  space  above   ity cient when writing to the   SD Memory Card for an  instruction    16 1403 File Does Not Exist   The file specified for an e The specified file does not exist  Same as  instruction does not exist  above    16 1404 Too Many Files  The maximum number of e The number of files or directories exceeded   Same as   Directories files directories was the maximum number  above   exceeded when creating a  file directory for an instruc   tion    16 1405 File Already in Use   A file specified for an e An instruction attempted to read or write a Same as  instruction cannot be file already being accessed by another above   accessed because it is instruction   already being used    16 1406 Open Mode Mis  A file operation for an e The file open mode specified by the Open Same as   match instruction was inconsistent File instruction does not match the file oper    above   with the open mode of the ation attempted by a subsequent SD Mem   file  ory Card instruction    16 1407 Offset Out of Access to the address is e An attempt was made to access beyond the   Same as  Range not possible for the offset size of the file  above    specified for an instruction   3 92 NJ series Troubleshooting Manual  W503     3 Error Tables       16 1408 Directory Not A directory was not empty e A directory was not empty when the Delete   NJ series  Empty when the Delete Directory Directory instructio
64. EC Directives  To ensure that the machine or device in which   the NJ series Controller is used complies with EC Directives  the Controller must be installed as fol    lows    e The NJ series Controller must be installed within a control panel    e You must use reinforced insulation or double insulation for the DC power supplies connected to  DC Power Supply Units and I O Units    e NJ series Controllers that comply with EC Directives also conform to the Common Emission Stan   dard  EN 61000 6 4   Radiated emission characteristics  10 m regulations  may vary depending  on the configuration of the control panel used  other devices connected to the control panel  wir     ing  and other conditions   You must therefore confirm that the overall machine or equipment complies with EC Directives     NJ series Troubleshooting Manual  W503  19    Regulations and Standards    Conformance to Shipbuilding Standards    The NJ series Controllers comply with the following shipbuilding standards  Applicability to the ship   building standards is based on certain usage conditions  It may not be possible to use the product in  some locations  Contact your OMRON representative before attempting to use a Controller on a  ship     i Usage Conditions for NK and LR Shipbuilding Standards    e The NJ series Controller must be installed within a control panel     e Gaps in the door to the control panel must be completely filled or covered with gaskets or other  material     e The following noise filte
65. ESS sO00000000000        PORT2 Soe ADDRESS  EE         Lot number and serial number MAC address    The following information is provided on the ID information label     Item Description  Unit model Gives the model of the Unit   Unit version Gives the unit version of the Unit   Lot number and Gives the lot number and serial number of the Unit     serial number DDMYY  Lot number  LJ  For use by OMRON  xxxx  Serial number       M    gives the month  1 to 9  January to September  X  October  Y  November  Z  December   MAC address Gives the MAC address of the built in port on the Unit     i Confirming Unit Versions with Sysmac Studio    You can use the Unit Production Information on the Sysmac Studio to check the unit version of the CPU  Unit  CJ series Special I O Units  CJ series CPU Bus Units  and EtherCAT slaves  The unit versions of  CJ series Basic I O Units cannot be checked from the Sysmac Studio        CPU Unit and CJ series Units  1 Double click CPU Expansion Racks under Configurations and Setup in the Multiview    Explorer  Or  right click CPU Expansion Racks under Configurations and Setup and select  Edit from the menu     The Unit Editor is displayed for the Controller Configurations and Setup layer     NJ series Troubleshooting Manual  W503  21    Unit Versions    2 Right click any open space in the Unit Editor and select Production Information     The Production Information Dialog Box is displayed      3  Production information EN    Model information Lot number    
66. F when   Manual  Cat   _BCDO was specified as the BCD format    No  W502   e The most significant digit was A  B  C  D  wo  or E when _BCD2 was specified as the 2  BCD format  D  e The most significant digit was B  C  D  or c  E when _BCD3 was specified as the BCD Ce  format  Se  16 0405 Illegal Bit Position   The bit position specified e The bit position specified for an instruction Same as 3  Specified for an instruction was ille  exceeds the data range  above     gal  3   g   16 0406 Illegal Data Posi  The data position specified      The data position or data size specified for   Same as  tion Specified for an instruction exceeded an instruction exceeded the data area above   the data area range  range   16 0407 Data Range The results of instruction e The results of instruction processing  such Same as  Exceeded processing exceeded the as the number of array elements  exceeded   above   data area range of the out  the data area range of the output parameter  D  put parameter     N  16 0409 No Errors to Clear   An instruction to clear a e An instruction to clear a Controller error was   Same as m  Controller error was exe  executed when there was no error in the above  S  cuted when there was no Controller      error in the Controller  S  16 040B No User Errors to   An instruction to clear user    e An instruction to clear user defined errors Same as  Clear defined errors was exe  was executed when there was no user  above   cuted when there was no defined error   user def
67. Gear Ratio  Denominator  Setting Out of  Range    Target Veloc   ity Setting  Out of Range    Acceleration  Setting Out of  Range    Deceleration  Setting Out of  Range    Jerk Setting  Out of Range    Torque Ramp  Setting Out of  Range    The PDO mapping  is not correct     The parameter  specified for the  RatioNumerator  input variable to a  motion control  instruction is out of  range     The parameter  specified for the  RatioDenominator  input variable toa  motion control  instruction is out of  range     The parameter  specified for the  Velocity input vari   able to a motion  control instruction is  out of range     The parameter  specified for the  Acceleration input  variable to a motion  control instruction is  out of range     The parameter  specified for the  Deceleration input  variable to a motion  control instruction is  out of range     The parameter  specified for the  Jerk input variable  to a motion control  instruction is out of  range     The parameter  specified for the  TorqueRamp input  variable to a motion  control instruction is  out of range     the motion control instruction  are not mapped     A motion control instruction that  specifies phase Z   _mcEncoderMark  as the trig   ger conditions was executed for  an axis that is mapped to an  OMRON Gs ECO IL  Ether   CAT Encoder slave     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Th
68. IPM Error    Regenera   tion Tr Error    Encoder  Phase Z  Error    Encoder CTS  Signal Error    Node  Address Set   ting Error    Encoder   Communica   tions Discon   nection Error    Encoder  Communica   tions Error    The current flowing    through the con     verter exceeded the    specified value     The current flowing    through the con     verter exceeded the    specified value     The Servo Drive    regeneration drive    Tr is faulty     A missing serial  incremental    encoder phase Z  pulse was detected     A missing serial  incremental  encoder CTS signal  logic error was  detected     The node address  that was read from  the rotary switches  was not between 00    and 99     A disconnection  was detected    because communi   cations between the    encoder and the    Servo Drive were  stopped more fre     quently than the  specified value     There is a commu   nications error for    the encoder        e A short circuit  line to ground    fault  contact failure  or insula   tion failure occurred on the U  V   or W motor line    The Servo Drive failed    The relay for the dynamic brake  has been welded due to fre   quent Servo ON OFF opera   tions    Motor windings are burned out   The Servomotor is not suitable  for the Servo Drive    The command input timing is  the same as or earlier than the  Servo ON timing     A short circuit  line to ground  fault  contact failure  or insula   tion failure occurred on the U  V   or W motor line    The Servo Drive failed    T
69. Instructions W508  tion Disabled  Direction Selection     54560000 hex Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  Execution Mode     Wi  N  m   lt   OD   gt   mr       5  O     Q   OD     O  mb  m   lt        gt   mp  O  O  Q   ui               SOT 1013   t    NJ series Troubleshooting Manual  W503  3 81    3 Error Tables    Event code    54570000 hex    54580000 hex    54590000 hex    545A0000 hex    545B0000 hex    545C0000 hex    545D0000 hex    545E0000 hex         Eventname     Functional classification Reference    Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  Axes Group Specifica    tion    Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  Jerk Setting    Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  Master Axis    Motion Control Instruction Re execu    Motion Control Instructions W508    tion Disabled  MasterOffset     Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  MasterScaling    Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  MasterStartDistance    Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  Continuous    Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  MoveMode     545F0000 hex  54600000 hex  54610000 hex  54620000 hex  54630000 hex    w50
70. LILI  GDS AID IT     DS DA III  DS ECO III  XWT IDLIL  XWT ODLIL     3G3AX MX2 ECT       MX2 Series Inverter  EtherCAT Communica   tion Unit User   s Manual    R88D KNLI ECT  R88M KLI    G5 series AC Servomo   tors Servo Drives with  Built in EtherCAT Com   munications Users Man   ual    NJ series Troubleshooting Manual  W503     Model numbers Application    Using the built in EtherCAT  port on an NJ series CPU  Unit     Using the built in Ether   Net IP port on an NJ series  CPU Unit     Learning about the errors  that may be detected in an  NJ series Controller     Learning about the operat   ing procedures and func     tions of the Sysmac Studio     Learning how to configure  networks  data links  rout   ing tables  Communica   tions Unit settings  etc       Learning to create screen  data for NS series Pro   grammable Terminals     Creating data transfer pro   tocols for general purpose  devices connected to CJ   series Serial Communica   tions Units    Leaning how to connect  GX series EtherCAT Slave  Units        Leaning how to connect a  3G3AX MX2 ECT Ether   CAT Communications Unit  for MX2 series Inverters        Leaning how to connect  G5 series AC Servomo     tors Servo Drives with  EtherCAT Communica   tions        Related Manuals    Description    Information on the built in EtherCAT port is pro   vided  This manual provides an introduction and  provides information on the configuration  fea   tures  and setup    Use this manual together with the NJ series  CPU U
71. MC_MoveFeed the range of signed 40 bit data S   Interrupt Feeding  when converted to pulses  S  instruction over   0  flowed or under     flowed  S  74390000 hex   Error in Changing the Con  When the Same as    Changing trol Mode was not MC_SyncMoveVelocity instruc  above  2  Servo Drive completed within tion was stopped  the actual    Control Mode   the specified time  current velocity was not  reduced to 10  or less of the  maximum velocity within 10  seconds for three consecutive  periods after a command veloc   ity of O was output   For an OMRON G5 series  Servo Drive  the actual current  velocity was not reduced to  10  or less of the maximum  velocity within 10 seconds for  three consecutive periods when  the MC_TorqueControl instruc   tion was stopped   Changing the Control Mode of  the Servo Drive between CSP   CSV  and CST was not com   pleted within one second after  the command was executed   NJ series Troubleshooting Manual  W503  3 15    3 Error Tables    e EtherCAT process data com     743A0000 hex    743B0000 hex    84400000 hex    644C0000 hex    644D0000 hex    644E0000 hex    644F0000 hex    64500000 hex    64510000 hex    64520000 hex    3 16    Master Axis  Position  Read Error    Auxiliary Axis  Position  Read Error    EtherCAT  Slave Com   munications  Error    Following  Error Warn     ing    Velocity  Warning    Acceleration  Warning    Deceleration  Warning    Positive  Torque Warn     ing    Negative  Torque Warn   ing    Command  Position  Overflow 
72. Manual  NJ series CPU Unit   Software User   s Manual  NJ series Instructions  Reference Manual   NJ series CPU Unit Motion  Control User   s Manual  NJ series CPU Unit Built in  EtherCAT Port User   s Manual  NJ series Motion Control  Instructions Reference Manual  NJ series CPU Unit Built in  EtherNet IP Port User   s Manual  NJ series Troubleshooting Manual  CJ series Special Unit Operation  Manuals for NJ series CPU Unit    VM    Programming    Testing operation and debugging    Using motion control    Using EtherCAT  Using EtherNet IP    JT E    11 T ii Naa  2 E8 e    v          oO  l    Use the  Troubleshooting and managing relevant    errors in an NJ series Controller manuals for  references  according to  any error that    Maintenance    Using EtherCAT  Using EtherNet IP  Using CJ series Units      gt        2 NJ series Troubleshooting Manual  W503        Manual Configuration    Manual Configuration    NJ series CPU Unit Hardware User   s Manual  Cat  No  W500     I Nu series CPU Unit Hardware User s Manual  Cat  No  W500     Section    Section 1  Introduction    Section 2  System Configuration    Section 3  Configuration Units    Section 4  Installation and Wiring    Section 5  Troubleshooting    Section 6  Inspection and Maintenance    Appendices    Description    This section provides an introduction to the NJ series Controllers and their features   and gives the NJ series Controller specifications     This section describes the system configuration used for NJ ser
73. NMP Set   ting Error    34260000 hex    34270000 hex   Tag Name  Resolution    Error    DNS Server  Connection  Error    84030000 hex    NTP Server  Connection  Error    84040000 hex    84070000 hex   Tag Data Link    Connection    Failed    3 36    An error was  detected in the  communications  settings for tag data  links     An error was  detected in the  hosts in the IP  router table     An error was  detected in the FTP  server settings     An error was  detected in the NTP  client settings     An error was  detected in the  SNMP agent trap    settings     Resolution of a tag  used in a tag data  link failed     Connection with the  DNS server failed     Connection with the  NTP server failed     Establishing a tag  data link connection  failed     e Power was interrupted when a  download was in progress for  the data link settings     Memory error    Power was interrupted when a  download was in progress for  the TCP IP advanced settings     Memory error    There is a mistake in the IP  router table settings or hosts  settings     Power was interrupted when a  download was in progress for  the FTP server settings     Memory error    Power was interrupted when a  download was in progress for  the NTP client settings     Memory error    Power was interrupted when a  download was in progress for  the SNMP agent trap settings     Memory error    The size of the network pub   lished variable is different from  the tag settings    The I O direction set for a tag  data link an
74. NT  MERCHANTABILITY  OR FITNESS FOR PARTICULAR PURPOSE OF THE  PRODUCTS  ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR  INTENDED USE  OMRON DISCLAIMS ALL OTHER WARRANTIES  EXPRESS OR IMPLIED     LIMITATIONS OF LIABILITY    OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL  INDIRECT  OR CONSEQUENTIAL DAMAGES   LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS   WHETHER SUCH CLAIM IS BASED ON CONTRACT  WARRANTY  NEGLIGENCE  OR STRICT  LIABILITY     In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which  liability is asserted     INNO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY  REPAIR  OR OTHER CLAIMS  REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS  WERE PROPERLY HANDLED  STORED  INSTALLED  AND MAINTAINED AND NOT SUBJECT TO  CONTAMINATION  ABUSE  MISUSE  OR INAPPROPRIATE MODIFICATION OR REPAIR        NJ series Troubleshooting Manual  W503  11    Read and Understand this Manual    Application Considerations    SUITABILITY FOR USE    OMRON shall not be responsible for conformity with any standards  codes  or regulations that apply to the  combination of products in the customer s application or use of the products     At the customer s request  OMRON will provide applicable third party certification documents identifying  ratings and limitations of use that apply to the products  This info
75. O memory in  the destination  CPU Unit for I O  refreshing could not  be found when  refreshing the slave    34C20000 hex   Slave I O    Refresh Error    34C30000 hex   Slave User  Allocation  Area Setting    Failed    64ACO0000 hex   Send Time   out Error    74600000 hex   Master Func   tion  Enable Dis   able Failed    74610000 hex   Master Fixed  Allocation  Area Setting    Failed    3 70    function data in the  CPU Unit     An error occurred in  the following opera   tion for user alloca   tion of the slave     A send timeout  occurred     An operating error  occurred when  enabling or dis   abling the master  function     An error occurred in  one of the following  operations for fixed  allocation of the  master     e UO words are allocated in an  EM bank that does not exist     The slave function is not dis   abled     There is a mistake in the user  allocations to a slave     CPU Unit is not in PROGRAM  mode     More than one software switch  changed to TRUE at the same  time  Or  another software  switch changed to TRUE before  processing was completed for a  previous software switch        There is no slave or other  device on the network     The same baud rate is not set  for all nodes     Communications cable lengths   trunk line and branch lines  are  unsuitable    A communications cable is dis   connected or loose    The terminating resistance is  somewhere other than the ends  of the trunk line    Noise   There is an error in the CAN  controller     An attempt 
76. OFF     Observation    e Axis operation  continues     e The motion con   trol instruction is  not executed  for  instructions not  related to axis  operation      EtherCAT commu   nications continue     EtherNet IP com   munications con   tinue     Unit or slave operation  Depends on the slave set     e All inputs are turned OFF     Depends on the Unit operat     ing specifications   ERH indi   cator lit    All axes stop immediately        Stops updating the command val   ues     Servo Drives      Settings and setting methods depend on the slave  Refer to the manual for the slave  For a Servo  Drive  operation depends on the setting of object 605E hex  Fault Reaction Option Code      NJ series Troubleshooting Manual  W503  1 9       h  I  Ai  Z  O   gt   A  D  mp  CH  m        O               S101143 ISISLUON Jo s  d  L  1          1 Overview of Errors    e The following table gives the operation for all other errors     Unit CPU Unit operation Unit or slave operation    EtherCAT slaves The slave operates in Safe Opera  Depends on the slave set   tional state  tings        CJ series Basic I O Units e All outputs are turned OFF  e All outputs are turned OFF     e Input refreshing continues  e External inputs are  refreshed     CJ series Special Units Refreshing continues  Depends on the Unit operat   ing specifications   Servo Drives Stops updating the command val  All axes stop immediately   ues       Settings and setting methods depend on the slave  Refer to the manual for 
77. OMRON    Machine Automation Controller  NJ series       Troubleshooting Manual    NJ501 1300  NJ501 1400  NJ501 1500    always in control          OMRON  2011    All rights reserved  No part of this publication may be reproduced  stored in a retrieval system  or transmitted  in any form  or    by any means  mechanical  electronic  photocopying  recording  or otherwise  without the prior written permission of  OMRON     No patent liability is assumed with respect to the use of the information contained herein  Moreover  because OMRON is  constantly striving to improve its high quality products  the information contained in this manual is subject to change without  notice  Every precaution has been taken in the preparation of this manual  Nevertheless  OMRON assumes no responsibility  for errors or omissions  Neither is any liability assumed for damages resulting from the use of the information contained in  this publication     Introduction    Introduction       Thank you for purchasing an NJ series CPU Unit    This manual contains information that is necessary to use the NJ series CPU Unit  Please read this  manual and make sure you understand the functionality and performance of the NJ series CPU Unit  before you attempt to use it in a control system    Keep this manual in a safe place where it will be available for reference during operation     Intended Audience    This manual is intended for the following personnel  who must also have knowledge of electrical sys   tems  a
78. PU Unit is not in PROGRAM  Failed allocation of the mode     slave  More than one software switch    changed to TRUE at the same  time  Or  another software  switch changed to TRUE before  processing was completed for a  previous software switch        NJ series Troubleshooting Manual  W503  3 71    3 Error Tables             Bus Off  Detected    84740000 hex    Remote UC  Communica   tions Error    84750000 hex    Remote UO  Communica   tions Error   during Slave  Operation     84760000 hex    Slave COS  Send Failed    84770000 hex    048A0000 hex   File  Read Write    Error    148C0000 hex   Invalid Mes   sage Timer    List Error    3 72    A Bus Off error  occurred  i e   com   munications  stopped because  there were too  many communica   tions errors      A timeout occurred  in remote I O com   munications     An error occurred in  remote I O commu   nications     An attempt was  made to send COS  data to the master  using the Slave  COS Send Switch   software switch 2   device variable     Sw2SlavCOSSen  dCmad   but the  send failed     An error occurred  when user setup  data was read from  an SD Memory  Card in the CPU  Unit or when data  was written as a file  to an SD Memory  Card     The data in the  message monitor   ing timer list is not  correct     e The master and slave have dif   ferent baud rates   Communications cable lengths   trunk line and branch lines  are  unsuitable    A communications cable is dis   connected or loose    The terminating resistance is
79. S  Setup Trans    rectly  transfer of the user program or W500  o  fer Error the Controller Configurations Nu series g  and Setup  CPU Unit Soft  9  The program is illegal because ware User s 5  the power supply to the Control  Manual  Cat  D  ler was interrupted or communi  No  W501   cations with the Sysmac Studio  were disconnected during  online editing   10210000 hex   Illegal User The user program The user program execution Same as  Program execution IDs set in IDs set in the user program and above  CG  Execution ID   the user program in the CPU Unit do not match  N  and in the CPU Unit   e A user program execution ID is m  do not match  set in the CPU Unit but not in S  the user program  2  10240000 hex   Illegal User The user program There are more than 8 nesting Same as S  Program is not correct  levels for functions or function above  U  blocks  O  10250000 hex   Illegal User The user program Power was interrupted while Same as 3  Pro  or Controller Con  writing the user program or above  2  gram Con  figurations and Controller Configurations and S  troller Setup is corrupted  Setup to non volatile memory     Configura  Non volatile memory is deterio  a  tions and rating or has failed  i  Setup  40160000 hex   Safe Mode The Controller The power supply was turned Same as  started in Safe ON to the Controller when Safe above   Mode  Mode was set on the DIP switch  on the CPU Unit   10230000 hex   Event Log Restoring the event A low battery voltage prevented Same as  R
80. Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     18210000 hex   Encoder Ini    An encoder initial  e Servomotor failed  AC Servomo    tialization ization error was tors Servo   Error detected  Drives G5  Series with  Built in Ether   CAT Commu   nications  User s Man   ual  Cat  No   1576     18220000 hex   Absolute The encoder Servomotor failed  d Same as  Encoder detected a one  above   One rotation   rotation counter  Counter Error   error   18230000 hex   Absolute The encoder Servomotor failed  d Same as  Encoder detected a multi  above   Multi rotation   rotation counter  Counter Error   error   24680000 hex   Motor Non  The Servo Drive The Servo Drive and Servomo  Same as  conformity and Servomotor tor combination is not correct  above   combination is not  correct     24690000 hex   Motor Non  The Servo Drive The Servo Drive and Servomo  Same as  conformity and Servomotor tor combination is not correct  above   combination is not  correct        OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       246A0000 hex   Motor Non  The Servo Drive The Servo Drive and Servomo  Same as  conformity and Servomotor tor combination is not correct  above   combination is not  correct     SOAR S LYOJOUIF U  S1013 9           246B0000 hex   Motor Non  The Servo Drive The Servo Drive and Servomo  Same as  conformity and Servomotor tor combination is not correct  above   combination is not    correct     246C0000 hex   Motor Non  The
81. Sysmac Studio  go online with CPU Unit         Change the Ethernet interface card  specification on the Sysmac Studio or  connect the Ethernet cable to the specified  interface card  Refer to the appendices of  Sysmac Studio Version 1 Operation Manual   Cat  No  W504  for the procedure to specify  the Ethernet interface card         Is the Ethernet cable  connected to the Ethernet  interface card that is specified  to use to connect to the  Controller in the Sysmac            Yes       Can the Sysmac Studio  go online with CPU Unit        Replace the Ethernet cable     NJ series Troubleshooting Manual  W503  2 17    2 Error Troubleshooting Methods         Ethernet Hub Connection    Sysmac Studio cannot  connect to CPU Unit        No    Is power supplied to the Controller  Turn ON the power supply to the Controller        Yes       No        Can the Sysmac Studio  go online with CPU Unit          Insert the cable connectors at the personal  computer  Ethernet switches  and the  Controller until they lock into place  Verify that  the link indicator is lit at the computer and  Ethernet switches  and the LINK ACT  indicator is lit at the Controller        Is the Ethernet cable  connected properly           Yes       Can the Sysmac Studio  go online with CPU Unit        Is the connection method Set the connection method to an Ethernet hub  set to an Ethernet hub connection in the Communications Setup of the  connection in the Sysmac Studio  Set the destination IP address  Communic
82. Velocity    54460000 hex Move Link Constant Velocity Insuffi    Motion Control Instructions W508  cient Travel Distance    54470000 hex Positioning Gear Operation Insuffi  Motion Control Instructions W508  cient Target Velocity   54480000 hex Same Start Point and End Point for Motion Control Instructions W508  Circular Interpolation   54490000 hex Circular Interpolation Center Specifi    Motion Control Instructions W508  cation Position Out of Range    544A0000 hex Circular Interpolation Cannot Be Exe    Motion Control Instructions W508  cuted with Rotary  Infinite  Axis    544C0000 hex Parameter Selection Out of Range Motion Control Instructions W508  544D0000 hex Stop Method Selection Out of Range   Motion Control Instructions W508    544E0000 hex Latch ID Selection Out of Range for   Motion Control Instructions W508  Trigger Input Condition   544F0000 hex Setting Out of Range for Writing MC   Motion Control Instructions W508  Seiting   54500000 hex Trigger Input Condition Mode Selec    Motion Control Instructions W508  tion Out of Range   54510000 hex Drive Trigger Signal Selection Out of   Motion Control Instructions W508  Range for Trigger Input Condition    54530000 hex Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  Axis Specification     54540000 hex Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled  Buffer Mode Selection     54550000 hex Motion Control Instruction Re execu    Motion Control 
83. W503     3 Error Tables       Lwa O           74340000 hex   Latch Posi  An overflow e An overflow occurred for the NJ series  tion Overflow   occurred for the latched position for the CPU Unit  latched position for MC_TouchProbe  Enable Exter  Motion Con   the nal Latch  instruction  trol User   s  MC_TouchProbe Manual  Cat    Enable External No  W507   Latch  instruction  Ce  74350000 hex   Latch Posi  An underflow An underflow occurred for the Same as m  tion Under  occurred for the latched position for the above  3  flow latched position for MC_TouchProbe  Enable Exter  o  the nal Latch  instruction  g  MC_TouchProbe 4   Enable External S  Latch  instruction      74360000 hex   Master Sync   The master axis The master axis continued to Same as  Direction continued to move move in the direction opposite above   Error in the direction to the sync direction of the mas   opposite to the sync ter and slave axes  resulting in  direction  an overflow   74370000 hex   Slave Dis  An EtherCAT slave An EtherCAT slave that is allo  Same as S  connection that is allocated to cated to an axis was discon  above  Ge  during Servo   an axis was discon  nected or replaced while the H  ON nected while the Servo was ON  S  servo was ON     74380000 hex   Feed Dis  The target position The target position after the Same as    tance Over  after the interrupt interrupt input was received for above     flow input was received the MC_MoveFeed  Interrupt    for the Feeding  instruction exceeded 5  
84. Z  O   gt   A  D  mp     m        O               S101143 ISISLUON Jo s  d  L  1          1 Overview of Errors    1 8       4   2    Controller    Controller errors   i  Event level information    item Major fault Partial fault Minor fault EE EE  level level level    Refer to LC e Errors in According to According to According to  Operation for EtherCAT user program    user program    user program   Major Fault Master Func    Level Control  tion Module    ler Errors on Depends on   page 1 9  settings in    Outputs from  EtherCAT slaves  and Basic Output  Units    the slave     Errors in   other func    tion modules    According to   user pro    gram   Error messages are automatically displayed in the   These errors and events are not  Sysmac Studio dis    Controller Status Pane  shown on the display of Control     play  when online    The user can display detailed information in the ler errors         Troubleshooting Dialog Box   If multiple Controller errors have occurred  the indicators show the error with the highest event level     Operation stops in the function module  Motion Control Function Module  EtherCAT Master Function Module   or EtherNet IP Function Module  in which the error occurred     NJ series Troubleshooting Manual  W503     1 Overview of Errors    Operation in the Function Module Where an Error Event Occurred    Event level    Major fault level    Function module    PLC Function Mod    Operation stops  w    ule    Operation stops     Motion Control  Functi
85. a  input signal  IN1  and IN4  function allocations  2  tion Error 1 IN2  IN3  and IN4   function allocations   38460000 hex   Interface There is a dupli  There is a duplicate setting in Same as  Input Dupli  cate setting in the the input signal  IN5  IN6  IN7  above   cate Alloca  input signal  IN5  and IN8  function allocations   tion Error 2 IN6  IN7  and IN8   function allocations   38470000 hex   Interface There is an unde  There is an undefined number Same as  Input Func  fined number speci  specification in the input signal above   tion Number   fication in the input  IN1  IN2  IN3  and IN4  func   Error 1 signal  IN1  IN2  tion allocations   IN3  and IN4  func    e Different logic is set for the  tion allocations  Or    same function in the function  a logic setting error   assignments of the input sig   was detected  nals  IN1  IN2  IN3  and IN4    38480000 hex   Interface There is an unde  There is an undefined number Same as  Input Func  fined number speci  specification in the input signal above   tion Number   fication in the input  NS IN6  IN7  and IN8  func   Error 2 signal  IN5  IN6  tion allocations   IN7  and IN8  func    e Different logic is set for the  tion allocations  Or    same function in the function  a logic setting error   assignments of the input sig   was detected  nals  IN5  IN6  IN7  and IN8    38490000 hex   Interface Out    There is an unde  There is an undefined number Same as  put Function   fined number speci  specification in the output s
86. able for which CJ series Unit memory   above   Address which CJ series Unit mem  must be specified   ory must be specified   16 0414 Stack Underflow There is no data in a stack   e An attempt was made to read data from a Same as  stack that contains no data  above   16 0416 Illegal Number of The valid range was e The valid range was exceeded for the num    Same as  Array Elements or   exceeded for the number of ber of array elements or dimensions in an above   Dimensions array elements or dimen  array I O parameter for an instruction   sions in an array I O param   eter for an instruction   16 0417 Specified Task The task specified for the e The specified task does not exist  Same as  Does Not Exist instruction does not exist  above   NJ series Troubleshooting Manual  W503  3 91    3 Error Tables             Event code   Eventname   Meaning   Assumed cause   Reference   16 0418 Unallowed Task An unallowed task was e The local task  the primary periodic task  or   NJ series   Specification specified for an instruction  a periodic task was specified  Instructions  Reference  Manual  Cat   No  W502   16 0419 Incorrect Data A data type that cannot be   e A data type that cannot be used for an Same as  Type used for an instruction is instruction is specified for an input or in out   above   specified for an input or in  variable   out variable   16 041A Multi execution of   Multi execution was speci  je Execution of an instruction that does not Same as  Instructions fied for an in
87. ables    p Level O   EE GE EE    Axis Slave The slave to which  e The slave to which the axis is NJ series  Disabled the axis is assigned assigned is disabled  CPU Unit  is disabled  Motion Con   trol User s  Manual  Cat   No  W507   Network The network config    e The EtherCAT network configu  Same as  Configura  uration information ration information is not regis  above   tion Informa    is not registered for tered for the slave to which the  tion Missing   the slave to which axis is assigned   for Axis Slave   the axis is  assigned   Motion Con    A fatal error e Hardware has failed  Same as  trol Initializa    occurred in the sys  above   tion Error tem and prevented  initialization of the  Motion Control  Function Module   Motion Con    Processing forthe e The processing load in the pri  Same as  trol Period primary periodic mary periodic task is too heavy  above     Exceeded task was not fin   ished within two  control periods     Cam Table Saving a cam table  e Saving a cam table to a file d Same as  Save Error to a file failed  failed  above     Cam Table The phases are not  e Data containing cam table d Same as  Data Error in ascending order phases that are not in ascend  above   during Cam in the cam table  ing order was detected during  Motion cam motion    The phase and displacement of   the start point in the cam table   were not 0 during cam opera    tion    The phase of the end point in   the cam table when converted   to pulses was not 1 pulse or   greater dur
88. above  as  ler Failure hardware test at    startup  j  14400000 hex   MAC The MAC address The CPU Unit has failed  Same as    Address is incorrect  above  2  Error    44010000 hex   EtherCAT A fatal error was Software is corrupted  Same as  Fault detected in the above   EtherCAT Master  Function Module   24200000 hex   Slave Node The same slave The same node address is set Same as  Address address is used for for more than one slave  above   Duplicated two nodes   34400000 hex   Network There is an error in The power supply to the Con  Same as  Configura  the network config  troller was interrupted or com  above   tion Informa    uration information  munications with the Sysmac  tion Error Studio were disconnected while  downloading the network con   figuration information   84200000 hex   Link OFF A Link OFF state The Ethernet cable is broken Same as  Error occurred  between the master and slaves  above   The Ethernet cable connector is  disconnected   The Ethernet cable is not con   nected   NJ series Troubleshooting Manual  W503  3 39    3 Error Tables    84210000 hex    842200000  hex    84230000 hex    84280000 hex    84290000 hex    842B0000 hex    842C0000 hex    64200000 hex    842D0000 hex    3 40    Network  Configura   tion Error    Network  Configura   tion Verifica   tion Error    Slave Initial   ization Error    Slave Appli   cation Error    Process Data  Transmis   sion Error    Process Data  Reception  Timeout    Process Data  Communica   tions Error    Emerge
89. ails   Event Name   Event Code         YObus Mater End Cover Missing    x24030000    Partial fault EtherNet IP Communications port IP Address Duplication Error 0x84010000       Minor fault PLC Real Time Clock Stopped 0x00070000  Minor fault EtherNet IP Communications port DNS Server Connection Error 0x84030000  After Source heading is clicked   Troubleshooting E3     Controller Errors Controller Event Log    Level   Source   Source Details   Event Name   Event Code    Minor fault EtherCATM Node No  1 Network Configuration Verific 0x84220000    User defined Errors User defined Event Log       Minor fault EtherNet IP Communications port DNS Server Connection Error 0x84030000  Partial fault EtherNet IP Communications port IP Address Duplication Error 0x84010000       YObus Mater End Cover Missing 24030000    Minor fault PLC Real Time Clock Stopped 0x00070000       2 6 NJ series Troubleshooting Manual  W503     2 Error Troubleshooting Methods       Displaying Event Logs with the Sysmac Studio    With Sysmac Studio  you can check a log of the Controller events that previously occurred on the  Controller Event Log Tab Page     You can select the event logs and levels to display in the Display Settings Area  Information on the  events that you specify are displayed in the detailed information area     5 Troubleshooting Seles    Controller Errors iser defined Errors User defined E    Time   Level   Source Source Details   Event Name   Event Code    1 1 1970 9 00 38 AM Minor fault Eth
90. al Packet  Discarded    An error occurred in  data exchange  between the CPU  Unit and a Special  Unit     An illegal packet  was received during  message communi   cations  The illegal  packet was dis   carded     e An error occurred in the Special  Unit     The Unit connection is faulty   Noise  A Unit has failed        Reference    NJ series  CPU Unit  Hardware  User   s Manual   Cat  No   W500     Same as  above     i Errors Related to Tasks  Event code Assumed cause  een Jeer    60020000 hex    60030000 hex    60040000 hex    60010000 hex    60050000 hex    3 6    Task Execu   tion Timeout    I O Refresh   ing Timeout  Error    Insufficient  System Ser   vice Time  Error    Task Period    Exceeded    Task Period  Exceeded    Task execution  exceeded the time   out detection time     Two consecutive  I O refresh failures  occurred during the  primary periodic  task or periodic task  period     The specified sys   tem service execu   tion time could not  be obtained     Task execution was  not completed dur   ing the set task  period for the pri   mary periodic task  or a periodic task     Task execution was  not completed dur   ing the set task  period for the pri   mary periodic task  or fixed periodic  task        p Level    e The timeout detection time set   ting is too short     The task period setting is too  short     A user program is too large     The number of times that pro   cessing is repeated is larger  than expected     The priority of the periodic task  is 
91. all events  This allows you to see what errors have occurred and find corrections for them with  the same methods for the entire range of errors that is managed  i e   CPU Unit  EtherCAT slaves   and  CJ series Units       The EtherCAT slaves must support NJ series error management     Host computer NS series PT          EtherNet IP    Troubleshooter    wt            Built in EtherNet IP  NJ series port    CPU Unit CJU series Units  Troubleshooting functions    pu  L                   Sysmac Studio                Je e        4  A    Built in EtherCAT port                                           EtherCAT  slaves T gi gi  General purpose slaves  tE Ee    Error management range for S      ervo Drives  NJ series Controller    You can use the troubleshooting functions of the Sysmac Studio or the Troubleshooter on an NS series  PT to quickly check for errors that have occurred and find corrections for them     1 1 1 Types of Errors    There are two main types of errors  events  depending on whether the NJ series Controller can man   age them or not       Fatal Errors    These errors are not detected by the event management function of the NJ series Controller  because the CPU Unit stops operation  You cannot identify or reset these errors with the Sysmac  Studio or an NS series PT     Refer to 1 2 Fatal Errors for error types and confirmation methods for fatal errors        Non fatal Errors    These errors are detected and managed with the event management function of the NJ seri
92. anual  W501     18 NJ series Troubleshooting Manual  W503     Regulations and Standards    Regulations and Standards       Conformance to EC Directives    Applicable Directives    e EMC Directives  e Low Voltage Directive    H Concepts       EMC Directive    OMRON devices that comply with EC Directives also conform to the related EMC standards so that  they can be more easily built into other devices or the overall machine  The actual products have  been checked for conformity to EMC standards    Whether the products conform to the standards in the system used by the customer  however  must  be checked by the customer  EMC related performance of the OMRON devices that comply with EC  Directives will vary depending on the configuration  wiring  and other conditions of the equipment or  control panel on which the OMRON devices are installed  The customer must  therefore  perform the  final check to confirm that devices and the overall machine conform to EMC standards     Applicable EMC  Electromagnetic Compatibility  standards are as follows   EMS  Electromagnetic Susceptibility   EN 61131 2 and EN 61000 6 2  EMI  Electromagnetic Interference   EN 61131 2 and EN 61000 6 4  Radiated emission  10 m regulations        Low Voltage Directive    Always ensure that devices operating at voltages of 50 to 1 000 VAC and 75 to 1 500 VDC meet the  required safety standards  The applicable directive is EN 61131 2        Conformance to EC Directives    The NuJ series Controllers comply with 
93. as lit    The power supply to the Con   troller was interrupted momen   tarily while the SD BUSY  indicator was lit        NJ series Troubleshooting Manual  W503     3 Error Tables    j Errors Related to Unit Configuration  vent coae ssumed cause ereren  ae       04010000 hex   I O Bus An error occurred in      The I O Connecting Cable is NJ series  Check Error   a bus line transmis  disconnected or wires inside it CPU Unit  sion between the are broken  Hardware W  CPU Unit and the Conductive material has gotten User   s Manual    Units in the rack inside   Cat  No     slots  Or  detection The connector contact is faulty W500   of all Special I O due to foreign material in the    Units and CPU Bus te op  Units was not com  2  pleted when the NOISE O  power supply to the      A Unit has failed  S  Controller was  turned ON   24010000 hex   Unsupported   An unsupported An unsupported CJ series Unit Same as  Unit Detected   CJ series Unit or or Power Supply Unit was above   Power Supply Unit detected    s  is mounted  rm  24020000 hex   Too Many I O   The total number of The total number of I O points Same as m  Points I O points in the in the connected CJ series above  g  connected CJ  Basic I O Units exceeds 2 560  e  series Units    exceeds the maxi  D  mum specified d  value of the CPU d  Unit  3  24030000 hex   End Cover The End Cover is The End Cover is not con  Same as     Missing not connected to nected to right end of the CPU above     right end of the Rack or an Expans
94. as set to 1  above   tus Error 5 code  ALMC  was  set to 1   08140000 hex   Phase A An error such as An error such as broken wiring Same as  Connection broken wiring was was detected in the external above   Error detected in the encoder phase A connection   external encoder  phase A connec   tion   NJ series Troubleshooting Manual  W503  3 45    3 Error Tables       weal O     08150000 hex    08160000 hex    08170000 hex    08180000 hex    14A80000 hex    14A90000 hex    14AA0000 hex    14AB0000 hex    14AC0000 hex    14AD0000 hex    18200000 hex    3 46    Phase B  Connection  Error    Phase Z  Connection  Error    Encoder  Data Resto   ration Error    External  Encoder  Data Resto   ration Error    Object Error    Object Error    Object Error    Object Cor   rupted    Object Cor   rupted    Object Cor   rupted    Absolute  Encoder    Overspeed  Error    An error such as  broken wiring was  detected in the  external encoder  phase B connec   tion     An error such as  broken wiring was  detected in the  external encoder  phase Z connec   tion     Initialization of  internal position  data was not pro   cessed correctly in  Semi closed Con   trol Mode and  Absolute Value  Mode     Initialization of  internal position  data was not pro   cessed correctly in  Fully closed Control  Mode and Absolute  Value Mode     The object area  data in non volatile  memory is cor   rupted     The object area  data in non volatile  memory is cor   rupted     The object area  data in non volat
95. ation decel   eration  Blending is changed to  Buffered   the results of profile  creation caused the accelera   tion deceleration rate to be  exceeded when blending was  specified  so buffered was  used     Blending was specified  but the  target position was already  reached  so it was changed to  Buffered because the profile  could not be created     Blending was specified for an  interpolation instruction  but  based on the results of profile  creation  this was changed to  Buffered because the execution  time of the instruction before  the transition was four control  periods or less     An error was cleared from the  MC Test Run Pane of the Sys   mac Studio     The error code was reported by  the slave when a Slave Error  Detected error  742F0000 hex   occurred        3 Error Tables      Level O     a Tae Ges    NJU series  CPU Unit  Motion Con   trol User   s  Manual  Cat   No  W507     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     3 17    OO  I      m        O     Vu  o   lt   GU  O  c     O  OD         jNpoN uonouny  O4 UOD uono 3y  Ul SIO E L       3 Error Tables    H Motion Control Instructions    e The PDOs that are required for    34610000 hex    54200000 hex    54210000 hex    54220000 hex    54230000 hex    54240000 hex    54250000 hex    54270000 hex    3 18    Process Data  Object Set   ting Missing    Electronic  Gear Ratio  Numerator  Setting Out of  Range    Electronic  
96. ations Setup of for a remote USB connection or Ethernet hub  the Sysmac Studio  connection in the Communications Setup              Can the Sysmac Studio  go online with CPU Unit              Is the destination  IP address for a remote USB  connection or Ethernet hub   connection set correctly in the  Communications Setup of the  Sysmac Studio     Correct the destination IP address for a remote  USB connection or Ethernet hub connection in  the Communications Setup of the Sysmac Studio            No        Can the Sysmac Studio  go online with CPU Unit        2 18 NJ series Troubleshooting Manual  W503     2 Error Troubleshooting Methods    Set the IP address for the personal computer   Use the default IP address for the Controller or  connect the Sysmac Studio to the Controller  with a USB cable and set the required IP  address         Is the same IP address set for  more than one node  computer  or Controller  in the same  domain           o5 JOUURD DO uayM Bunooys  ajqnolL p Z    oppe dewWsAS   y  UO sUl UO       Can the Sysmac Studio go  online with CPU Unit          Change the Ethernet interface card          Is the Ethernet cable connected specification on the Sysmac Studio or  to the Ethernet interface card connect the Ethernet cable to the specified  that is specified to use to interface card  Refer to the appendices of  connect to the Controller in the Sysmac Studio Version 1 Operation Manual  Sysmac Studio   Cat  No  W504  for the procedure to specify        the Eth
97. ay 3 2  3 1 1 Interpreting Error Descriptions                cccccccsseeeeeeseeeceeeeceseeeeeaeeeensueeeneaesessuseessaeensansessanseesseeeseass 3 2  3 1 2 Errors nthe PEC Function ModE a hae ciel ie dete ay A A Sexe haunted earned 3 2  3 1 3 Errors in the Motion Control Function Module  3 10  3 1 4 Errors in the EtherNet IP Function Module  3 35  3 1 5 Errors in the EtherCAT Master Function Module  3 39  3 1 6 Errors In EtherGAl EE 3 42  3 1 7 Errors initGJ SenesS UNIS EE 3 56  3 2 Events in Order of Event Codes ke K NNN ENNEN EN ENEE ENKEN ENNEN EN EN EN ENEE ENNEN ENNEN EN EN E 3 73  3 2 1 Interpreting Error Descriptions NENNEN EEN 3 73  3 2 2 Emor E EE 3 73  3 3 Instruction Error Table siccosicc ii dicaicascaesdanasvesseasins ccdacciadscdascasdodanseasiewvetaccdaadeaauscuadeestsesiatessvabsias 3 90  3 3 1 interpreting Error DESCIIDUONS E 3 90  3 3 2  treie   3      ER 3 90    Index       10 NJ series Troubleshooting Manual  W503     Read and Understand this Manual    Read and Understand this Manual       Please read and understand this manual before using the product  Please consult your OMRON representative  if you have any questions or comments     Warranty and Limitations of Liability  WARRANTY    OMRON s exclusive warranty is that the products are free from defects in materials and workmanship for a  period of one year  or other period if specified  from date of sale by OMRON     OMRON MAKES NO WARRANTY OR REPRESENTATION  EXPRESS OR IMPLIED  REGARDING NON   INFRINGEME
98. ck of the Units as shown below until they click into place     Move the sliders toward the back  until they lock into place     sjuasuodwog 49   o4JU0D HuljoeuUu0D LE b    Dy Precautions for Correct Use  EES   The sliders on the tops and bottoms of the Power Supply Unit  CPU Unit  I O Units  Special UO    z Units  and CPU Bus Units must be completely locked  until they click into place  after connecting  Icons indicate the adjacent Unit connectors   precautions  additional  information  or reference    information     Special information    E        M a n u al n am e NJ series CPU Unit Hardware User   s Manual  W500        This illustration is provided only as a sample  It may not literally appear in this manual     Special Information    Special information in this manual is classified as follows          Y Precautions for Safe Use  Precautions on what to do and what not to do to ensure safe usage of the product     L   Precautions for Correct Use  Precautions on what to do and what not to do to ensure proper operation and performance     EN Additional Information    Additional information to read as required   This information is provided to increase understanding or make operation easier     Note References are provided to more detailed or related information     NJ series Troubleshooting Manual  W503     Manual Structure    Precaution on Terminology  In this manual     download    refers to transferring data from the Sysmac Studio to the physical Controller  and    upload
99. coder or  because the power the battery power supply was  supply to the down   encoder or the bat   tery power supply  was down   384E0000 hex   Absolute The multi rotation The set value for switching Same as  Encoder counter of the operation with the absolute above   Counter encoder exceeded encoder is too large   Overflow the specified value  The traveling distance from  Error home of the machine exceeded  32 767 revolutions   384F0000 hex   Object Set  The electronic gear The electronic gear ratio Same as  ting Error 1 ratio exceeded the exceeded the allowable range  above   allowable range   38500000 hex   Object Set  External encoder External encoder ratio Same as  ting Error 2 ratio exceeded the exceeded the allowable range  above   allowable range   38510000 hex   External The set value of the The set value of the External Same as  Encoder External Feedback Feedback Pulse Type Selec  above     3 50    Connection  Error    Pulse Type Selec   tion  3323 hex  dif   fers from the  external encoder  type that is con   nected for serial  communications     tion  3323 hex  differs from the  external encoder type that is  connected for serial communi   cations        NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     38520000 hex   Function Set    The function that The electronic gear object ratio AC Servomo   ting Error was set does not was not 1 1 when the communi  tors Servo  support the com  cations period was set to 250 or Drives G5  munications per
100. com  the ID Tag is used  above     Correction mand performeda  e ID Tag error   1 bit error correc   tion        H CJ series High speed Counter Units    The section provides tables of the events that can occur in the following Units   CJ1W CT021    p Level O   Event code Assumed cause a Tae Reference  68010000 hex   Unit Error An error occurred in      There is an error in the Special CJ series  the High speed Unit Setup  High speed  Counter Unit  e An overflow or underflow error Counter Units  occurred  Operation  e An illegal preset value was Manual for NJ   ised series CPU  l   Unit  Cat  No   e A CPU Unit monitor error or bus W492   error occurred     NJ series Troubleshooting Manual  W503  3 61       OO  I      m        O     Vu  o   lt   GU  O  c     O  OD       SIU s  n  s f9 Ul S1013 J          3 Error Tables    i CJ series Serial Communications Units    The section provides tables of the events that can occur in the following Units   CJ1W SCU22  CJ1W SCU32  CJ1W SCU42    p Level    04740000 hex   Error Log An error occurredin      There is a source of noise CJ series  Data Error the error log data  nearby  Serial Com   Non volatile memory failure munications  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W494   14800000 hex   Protocol Data   A protocol data The communications connec  Same as  Error checksum error has tor with the CX Protocol was above   occurred  disconnected or the power sup   ply to the Controller was inter   rupted during transfer 
101. control  instruction is out of  range     The parameter  specified for the  PermittedDeviation  input variable to a       NJ series  exceeded the valid range of the Motion Con   input variable  trol Instruc    tions   Reference   Manual  Cat    No  W508     Instruction input parameter  exceeded the valid range of the    input variable     Instruction input parameter  exceeded the valid range of the    input variable     Instruction input parameter  exceeded the valid range of the    input variable     Same as  above     Same as  above     Same as  above     OO  I      m        O     Vu  o   lt   GU  O  c     O  OD       motion control  instruction is out of  range     54890000 hex Same as    above     The value of AutPoint exceeded  signed 40 bit data when con   verted to pulses for the border  point or center specification  method     For a radius specifications  the  absolute value of AuxPoint 0O   exceeded 40 bit data when  converted to pulses     Border The parameter  Point Center   specified for the  Posi  AuxPoint input vari   tion Radius able to a motion  Specification   control instruction is  Out of Range   out of range     BINDO  UONOUN J  O4 UOD uono 3y  Ul SIO E L       548A0000 hex   End Point  Specification    Out of Range    Same as  above     The parameter  specified for the  EndPoint input vari   able to a motion  control instruction is  out of range     The instruction input parameter  exceeded the range of signed  40 bit data when it is converted  to pulses
102. counter for the   Cleared absolute encoder  was cleared during  USB communica   tions by the CX   Drive     Position Data   A Config operation   Initialized was performed or  the multi rotation  counter was  cleared for the  absolute encoder  during EtherCAT  communications        Fan Warning   The fan stop state       continued for 1 sec     ond     Encoder Encoder communi    Communica    cations errors   tions Warn  occurred in series   ing more frequently  than the specified  value     Encoder The encoder tem   Overheating   perature exceeded    Warning the specified value     Life Expect    The remaining life  ancy Warn  of the capacitor or  ing the fan is shorter    than the specified  value     External The external    Encoder encoder detected a    Error Warn  warning   ing    External The external  Encoder encoder had more  Communica    communications  K   Warn  errors than the  specified value     e The multi rotation counter for AC Servomo   the absolute encoder was tors Servo  cleared during USB communi  Drives G5  cations by the CX Drive  Series with   Built in Ether   CAT Commu   nications  User s Man   ual  Cat  No   1576    e A Config operation was per  Same as  formed or the multi rotation above   counter was cleared for the  absolute encoder during Ether    CAT communications   Same as  above    e There is foreign matter in the Same as  fan  above    e The Servo Drive failed    e There is insufficient power sup  Same as  ply voltage for the encoder  above    e
103. cted the Detail View for the error  the display shows the errors cause and corrections     After you confirm the cause of the displayed error and the conditions in which it occurred  perform the  steps in the displayed correction     eea P Address Duplication Error    F 344 10H late 2911 06 20   19 45 45    The same IP address is used more than once     Cause    The IP address of the built in EtherNet IP port is also  used as the IP address of another node     Attached information 1     Duplicated IP address  example  MxCMASFAM1   address 19     168  250  1        aT teaminele  CAASFAML Atch  infos  tch  into          Panel capture    RUN   192  168  25   1   Controller    After you complete all of the correction steps for the current errors  click the Reset error Button to reset  all of the current errors  If the cause of the error is not removed  or if the power supply is not cycled or  the Controller is not reset as required after resetting the error  the error will occur again     NJ series Troubleshooting Manual  W503     2 Error Troubleshooting Methods    NJ series Troubleshooter      IP Address Duplication Error  a   l  sst bam  ONS Server Correction Error  D   II  GT II      Pane  capture     Reset error    RUN   192  168  254  1   Controller    In order to reset the Controller errors  it is necessary to confirm your rights according to the operation  authority settings for the Troubleshooter  Refer to the NS series Programmable Terminals Programming  Manual  Cat  No 
104. d the I O direction of  the Controller variable do not  match    There are no network published  variables for the Controller tag  settings    A variable in the Controller that  is set for a tag data link has the  Network Publish attribute set to  Input but also has the Constant  attribute     Parameter error   Server is down    An error occurred in the com   munications path    Parameter error   Server is down     An error occurred in the com   munications path        The tag data link connection  information is not the same for  the originator and target     Insufficient connections         Level O     a aTe ee    NJ series  CPU Unit    Built in Ether   Net IP Port  User   s Manual     Cat  No     W506     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     84080000 hex   Tag Data Link   A timeout occurred      The power supply to the target NJ series          Timeout in a tag data link  node is OFF  CPU Unit  Communications with the target Built in Ether   node stop  Net IP Port  The Ethernet cable for Ether  ects  Manual  Net IP is disconnected   Cat  No   W506  W  The Ethernet cable for Ether  4  Net IP is broken  D  Noise S  54E00000 hex   Variable Accessing a tag An out of range value was writ  Same as KC  Access Error   variable that is used ten by an EtherNet IP tag data above  N  in a tag data l
105. e      When bit 09  Remote  of the  Statusword  6041 hex  was set  to 0  local   a command was  received during FFT or test run  status that changes the ESM  state from Operational  Safe   operational  or Pre operational  state to Init state     An unsupported number was  set for 6060 hex  Operation  Mode      During Fully closed Control  Mode  csv or cst was set for  6060 hex  Operation Mode      The setting of 6060 hex  Opera   tion Mode  was changed at an  interval of less than 2 ms     Homing was started when 6098  hex  Homing Method  was set  to a value other than 8  12  19   20  33  34 or 35     Data setting warnings  BO hex   occurred continuously for the  number of data setting warn   ings that is set in 3781 hex   Data Setting Warning Detec   tion Count            Reference    AC Servomo   tors Servo  Drives G5  Series with  Built in Ether   CAT Commu   nications  User s Man   ual  Cat  No   1576     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     Operation  Command  Competition    78010000 hex    78020000 hex    84B10000 hex    84B20000 hex    84B30000 hex    84B40000 hex    84B50000 hex    84B60000 hex    84B70000 hex    84B80000 hex    84B90000 hex    An attempt was  made to establish  EtherCAT commu   nications or to turn  ON the Servo from  the Controller   enable operation   while executing an  FFT that operates  with the Servo  Drive alone ora  trial run     Absolute The rotation of the   Encoder Sta    encoder was higher   tus
106. e    Exceeded the SD Memory  Card was  exceeded  Or  the  number of bad  blocks exceeded  the specified value    10030000 hex   SD Memory   The file format of The file format of the SD Mem  Same as   Card Invalid   the SD Memory ory Card inserted in the CPU above    Format Card is not FAT16 Unit is not FAT16 or FAT32   or FAT32    10040000 hex   SD Memory   An error was The Controller power supply Same as   Card detected during the was turned OFF while the SD above    Restored or   file system check BUSY indicator was lit    Formatted and the file system The power supply to the Con   was restored  Files troller was interrupted momen   may have been tarily while the SD BUSY  deleted  indicator was lit    The SD Memory Card was  removed while the SD PWR  indicator was lit   The SD Memory Card is dam   aged   10060000 hex   SD Memory   A file that must be The Controller power supply Same as   Card Data in the SD Memory was turned OFF while the SD above    Corrupted Card is missing or BUSY indicator was lit   corrupted  The power supply to the Con    troller was interrupted momen   tarily while the SD BUSY  indicator was lit   The SD Memory Card was  removed while the SD PWR  indicator was lit   The SD Memory Card is dam   aged   10070000 hex   SD Memory   The power supply The Controller power supply Same as  Card Access   to the Controller was turned OFF while the SD above     3 4    Power OFF  Error    was interrupted   during access to  the SD Memory  Card     BUSY indicator w
107. e  Servo Drive was OFF          Level O     NJ series Troubleshooting Manual  W503     Reference    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     3 Error Tables    3 1 4 Errors in the EtherNet IP Function Module    i Built in EtherNet IP Port on CPU Unit  a aee          OO  10200000 hex   User Pro  The user program e The program is illegal because NJ series m  gram Con  or Controller Con  the power supply to the Control  CPU Unit o  troller figurations and ler was interrupted or communi  Built in Ether     Configura  Setup were not cations with the Sysmac Studio Net IP Port D  tions and transferred cor  were disconnected during a User   s Manual Q  Setup Trans    rectly  transfer of the user program or  Cat  No  E  fer Error the Controller Configurations W506  Ve  and Setup   The program is illegal because  the power supply to the Control   ler was interrupted or communi   cations with the Sysmac Studio  were disconnected during T  online editing  E  04200000 hex   Communica    A hardware error Communications Controller Same as u  tions Control    was detected in the hardware error above  S  ler Failure communications  i  controller of the    built in EtherNet IP om  port     14200000 hex   MAC The MAC address Non volatile memory failure Same as  lt   Address in non volatile above     Error memory was not nm  read correctly  z  14220000 hex   EtherNet IP A fatal e
108. e Master input  variable to a motion  control instruction  does not exist or is  not a sync master  axis     e A parameter for an input vari   able that cannot be changed for  re execution was changed     e A parameter for an input vari   able that cannot be changed for  re execution was changed     e A parameter for an input vari   able that cannot be changed for  re execution was changed        An axis does not exist for the  variable specified for the Auxil   lary input variable to the  instruction     An axis does not exist for the  variable specified for the Axis  input variable to the instruction     An axes group does not exist  for the variable specified for the  AxesGroup input variable to the  instruction     The axes group specified for  the AxesGroup input variable to  the instruction is not specified  as a used group     An axis does not exist for the  variable specified for the Master  input variable to the instruction     The axis that was specified for  the Master input variable to the  MC_Phasing  Shift Master Axis  Phase  instruction is not the  master axis for syncing       Level O        NJ series Troubleshooting Manual  W503     Reference    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     3 Error Tables       Level O     54630000 hex   Motion Con    An attempt was e A parameter for an input vari  NJ series  
109. e Target Velocity  input vari   able Velocity  is still at the  default  0      Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable        Level    Reference    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     e Instruction input parameter    54280000 hex    54290000 hex    542A0000 hex    542B0000 hex    542C0000 hex    542D0000 hex    542E0000 hex    542F0000 hex    54300000 hex    54310000 hex    Master Coef   ficient Scal   ing Out of  Range    Slave Coeffi   cient Scaling  Out of Range    Feeding  Velocity Set   ting Out of  Range    Buffer Mode  Selection Out  of Range    Coordinate  System  Selection Out  of Range    Circular Inter   polation  Mode Selec   tion Out of  Range    Direction  Selection Out  of Range    Path Selec   tion Out of  Range    Position Type  Selection Out  of Range    Travel Mode  Selection Out  of Range    The parameter  specified for the  MasterScaling input  variable to a motion  control instruction is  out of range     The parameter  specified for the  SlaveScaling input  
110. e as  Started started by Network Network Configurator or manip  above   Configurator or ulation of a system defined  manipulation of a variable   system defined  variable  Or  the  data link table was  downloaded from  the Network Config   urator again   NJ series Troubleshooting Manual  W503  3 37    3 Error Tables       wea O     94050000 hex   Link Establishment of an e Establishment of an Ethernet NJ series  Detected Ethernet link was link was detected  CPU Unit       detected  Built in Ether   Net IP Port  Users Manual   Cat  No   W506   94060000 hex   Restarting The built in Ether  The built in EtherNet IP port Same as  Ethernet Port   Net IP port was was restarted  above   restarted   94070000 hex   Tag Data Link   Tag data link con  Tag data link connections to all Same as  All Run nections to all target nodes have been estab  above   nodes have been lished   established   94080000 hex   IP Address The correct IP The correct IP address has Same as  Fixed address has been been determined and Ethernet above   determined and communications can start   Ethernet communi   cations can start   94090000 hex   BOOTP Cli  The BOOTP client The BOOTP client started Same as  ent Started started requesting requesting an IP address  above     an IP address     940A0000 hex   FTP Server The FTP agent e The FTP agent started nor  y Same as  Started started normally  mally  above     940B0000 hex   NTP Client The NTP client e The NTP client started normally d Same as  Started started n
111. e axis   velocity of the slave axis would  not exceed the axis maximum   velocity for the specified travel   distance     Performance of slave axis posi   tioning operation is poor and  the actual motion is slower than  the command     The Servo was turned OFF for  an axis due to an axes group  error     The ring counter setting in the  Controller or the ring counter  setting in the Servo Drive set   tings was changed     The position to restore when  converted to pulses exceeded  the range of signed 40 bit data     The command position or  actual position overflowed or  underflowed for a logical axis in  an axes group motion or a logi   cal axis that was decelerating to  a stop and the home definition  was lost     A slave communications error  occurred for a logical axis and  home became undefined during  axes group motion or while  decelerating to a stop     A slave for a logical axis left the  network and home became  undefined during axes group  motion or while decelerating to  a stop          Level O     a aee ee    NJ series  CPU Unit  Motion Con   trol User   s  Manual  Cat   No  W507     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     74210000 hex    74230000 hex    74240000 hex    74250000 hex    74260000 hex    74270000 hex    Servo Main  Circuit Power  OFF    Interrupt  Feeding  Interrupt Sig   nal Missing  
112. e axis specified for the Auxil  Same as g   Specification   for the Auxiliary iary input variable to the above  4   for Auxiliary input variable toa instruction is an unused axis      Axis motion control     instruction is an  unused axis    54750000 hex   Position Gear   Synchronized The specified synchronized Same as   Value Error motion is not possi  motion cannot be performed at above   ble for the velocity  the velocity  acceleration rate   acceleration rate  or deceleration rate that is input oi  and deceleration to the instruction  3  rate that were input m  to a motion control a  instruction  a   5  54760000 hex   Position Gear   The velocity of the The velocity of the master axis Same as     Master Axis master axis was was 0 when the instruction was above  2   Zero Velocity   zero when a motion started  ei  control instruction O  was started  Q   54780000 hex   Target Posi    The parameter Instruction input parameter Same as S  tion Setting specified for the exceeded the valid range of the above  es   Out of Range   Position input vari  input variable     able to a motion The target position of a Rotary S  controlinstructionis   Mode axis is not within the ring    out of range  setting range  S   54790000 hex   Travel Dis  The parameter that The absolute value of the Same as    tance Out of   was specified for instruction input parameter above    Range the Distance input exceeded the range of 40 bit  variable to a motion data when it is converted to  control instruct
113. e posi   tive software limit     The first position is beyond the  positive software limit and an  instruction that specifies motion  in the opposite direction of the  software limit was executed     The parameter that was speci   fied for the AuxPoint input vari   able to a border point  MC_MoveCircular2D  Circular  2D Interpolation  instruction is  beyond the positive software  limit       3 Error Tables      Level O     Reference    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     3 33    OO  I      m        O     Vu  o   lt   GU  O  c     O  OD         jNpoN uonouny  O4 UOD uono 3y  Ul SIO E L       3 Error Tables    e The parameter specified for the    64410000 hex    64420000 hex    64430000 hex    64440000 hex    74220000 hex    3 34    Target Posi   tion Negative  Software  Limit  Exceeded    Command  Position  Over   flow Under   flow    Positive Limit  Input    Negative  Limit Input    Servo Main  Circuits OFF    The specified posi   tion exceeds the  negative software  limit     Positioning  an  instruction in the  underflow overflow  direction  or an  instruction for which  the direction is not  specified was exe   cuted when there  was an under   flow overflow in the  command position     An instruction was  executed for a  motion in the posi   tive direction when  the positive limit  input was ON     An instruction 
114. ececce esse eseeeseeeeeeeueeeeeees 3 43  GX series EtherCAT Slave Units ccce 3 42  I  Incorrect Power Supply Unit Connected                   1 4  2 4  te Wie Le TEE 1 3  1 11  information level oo    ccc eecc eee eeseceeeeseeeaesueeeueeeeeeueeeaes 1 7  instructions  GeEICI TEEN 1 13  2 11   CTE G d EE 1 13  2 11  ET   gol d C  ae Oe a 1 13  2 11  Lee a a es 1 13  2 11  GetPLGCEMO xc ences otter ede neste 1 13  2 11  getting error information E 2 11  reading function module error status                 006 1 13  ResetCJBETTOTF        c  cccccccccecceccseseesseeseeseneeeessneneeeens 2 12  FRESCTEG EE 2 12  RRESEIM CEM OF WEE 2 12  SE Bd EE 2 12  M  Major EI EE 1 6  1 9  vleit HUE 1 6    NJ series Troubleshooting Manual  W503     motion control                         general kee 3 10  Ittre EE 3 18  Motion Control Function Module               ccc ssseeeesseeeees 3 10  MX2 SerieS Inverters             cccccceeeceseeeeeeeeseeensseeensaeeeess 3 55  N  non fatal errors oo    ceeecceseceeeeeeeeeeeeeeeeeeeeeeeaes 1 2  1 5  1 11  DEEL eet 1 13  MOUDISSMOOUNG   EE 2 5  O  observation level    2  set d ugikieeg  eeg reegen d eg eE   ec 1 6  online  troubleshooting problems going online           aa0snn  2 14  P  partial ET OI E 1 6  POWESUDDIV e EE 1 4  2 4  R  Ke Bel 2 12  resetting non fatal errors ENEE 1 13  S  Sale MOE EE 2 19  leren le 3 3  SOUICS EE E EEN 1 6  starting  sale e EE 2 19  system defined variables            ccccssseceeecesseeeeseeeeeeeeaees 1 13  checking for error
115. ed    All memory was  cleared           weal O     Event Log The event log was je The event log was cleared by d  Cleared cleared  the user    Power The power supply e The power supply was turned d  Turned ON was turned ON  ON    Power Inter    The power supply e The power supply was inter  d  rupted was interrupted  rupted    Operation Operation was es A command to start operation d  Started started  was received    Operation Operation was e A command to stop operation d  Stopped stopped  was received    Reset Exe  A reset was exe  e A reset command was   cuted cuted  received     User Pro   gram Execu   tion ID Write    All Controller  Errors  Cleared    Forced  Refreshing  Cleared    The user program  execution ID was  set or changed in  the CPU Unit     All current errors  were cleared     Clearing a forced  refreshing value  was specified     e A user with Administrator rights    changed the user program exe   cution ID that is set in the CPU  Unit     e All current errors were changed    by the user     e Clearing a forced refreshing  value was specified by the user     ff Errors Related to FINS Communications    e The power supply to the Con     14010000 hex    34100000 hex    34110000 hex    34130000 hex    3 8    CPU Bus  Unit Setup  Area Error    IP Address  Table Setting  Error    Unknown  Destination  Node    FINS TCP  Connection  Table Setting  Error    An error was  detected in the  memory check of  the Setup Area for  CPU Bus Units     The IP address  table set
116. either the   Forward Drive Pro    hibition Input  POT    or the Reverse   Drive Prohibition   Input  NOT  turned   ON     NJ series Troubleshooting Manual  W503  3 51    OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       SOAR S LYOJOUIF U  S1013 9              3 Error Tables       weal O     GEES Eventname   Meaning SE a aee    64E10000 hex    64E20000 hex    74810000 hex    3 52    Drive Prohibi   tion Input  Error 2    Immediate  Stop Input  Error    Command  Error    An operation com   mand  such as a  trial run of FFT   was received from  the CX Drive when  the Drive Prohibi   tion Input Selection   3504 hex  was set  to 0  EtherCAT  communications  was interrupted   and either POT or  NOT was ON  Or   POT or NOT turned  ON while operation  was being per   formed for a CX   Drive operation  command     An Immediate Stop   STOP  signal was  input     A mistake was  made in using a  command     e A problem occurred with the    switches  wires  and power sup   plies that are connected to the   Forward Drive Prohibition input  or the Reverse Drive Prohibition    input     An Immediate Stop  STOP  sig   nal was input     Incorrect wiring of the immedi   ate stop input  STOP      When bit 09  Remote  of the  Statusword  6041 hex  was set  to 1  remote   and the Servo  Drive was in operation enabled  state  Servo ON   a command  was received that changes the  communications state from  Operational to another state   Init  Pre operational  or Safe   operational stat
117. entification and troubleshooting flowcharts  Use them when an error  occurs in the NJ series Controller     2 1 1 Checking to See If the CPU Unit Ils Operating    When an error occurs in the NJ series Controller  use the following flowchart to determine whether the  error is a fatal error or a non fatal error     Whenever possible  set the Sysmac Studio   s software connection method in the flowchart to a direct  USB connection  If you use Ethernet  there are many reasons that prevent a software connection from  the Sysmac Studio  so time is required to determine if a fatal or non fatal error has occurred  If you can   not go online from the Sysmac Studio  perform 2 4 Troubleshooting When You Cannot Go Online from  the Sysmac Studio before you assume that the error is a fatal error     A fatal error occurred  Refer to 2 2    Troubleshooting Fatal Errors           PWR indicator Not lit     Power Supply Error   green      Lit             Not   possible   Going online from the CPU Unit Reset  Sysmac Studio            Not lit             ERROR indicator   red      Possible     Flashing        RUN indicator  green   Incorrect Power Supply Unit Connected    Not lit         Not possible         Going online from the    Sysmac Studio  CPU Unit Watchdog Timer Error        Possible     A non fatal error occurred  Refer to 2 1 2  Troubleshooting Flowchart for Non fatal    Errors        2 2 NJ series Troubleshooting Manual  W503     2 Error Troubleshooting Methods    2 1 2 Troubleshootin
118. ents that are not errors are also  given in the tables     3 2 1 Interpreting Error Descriptions    The contents of the error table is described below     p  N  m   lt   OD   gt   mp       5  O     Q   OD     O  GN  m   lt   OD   gt   mp  O  O  Q   D  Vu       Item Description  Event code The event code of the error in the NJ series Controller is given  The codes  are given in eight hexadecimal digits   Event name The name of the event is given  Functional classification A functional classification of the source is given   Reference The catalog number of the manual that provides details on the event are  given     Refer to information for the specified functional classification of the error in the error descriptions in the  manual given in the Reference column in the tables for detailed information on an error     The manual names are given below for the catalog numbers     suoldiuoseg 10113 Bunsidusluy L Z        Cat  No  Manual name  W500 NJ series CPU Unit Hardware User   s Manual  W501 NJ series CPU Unit Software User   s Manual  W490 CJ series Analog I O Units Operation Manual for NJ series CPU Unit  W491 CJ series Temperature Control Units Operation Manual for NJ series CPU Unit  W492 CJ series High speed Counter Units Operation Manual for NJ series CPU Unit  W498 CJ series Analog I O Units Operation Manual for NJ series CPU Unit  W488 GxX series EtherCAT Slave Units User s Manual  W494 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit  W497 
119. er of Inputs   inputs setting  2  Setting S   34850000 hex   Mean Value   There is a mistake  e There is a mistake in the setting Same as S  Processing in the setting of the of the number of samplings for above    Setting Error   number of sam  mean value processing   plings for mean  value processing    34860000 hex   Error in Set    There is a mistake     The specification of the Cyclic Same as Ge  ting of Con  is the Conversion Conversion Mode or Direct above   version Mode   Mode setting  Conversion Mode is not correct    34870000 hex   Output Hold   There is a mistake  e The setting for output status Same as    Setting Error   in the output hold when conversion stops is incor  above  o   setting  rect  z   34890000 hex   Conversion There is a mistake  e There is a mistake in the con  Same as T  Time Resolu    in the conversion version time resolution or oper  above  D  tion or Oper    time resolution or ation mode setting  p  ation Mode operation mode set  c  Setting Error   ting  a   348A0000 hex   Output Signal   There is a mistake      There is a mistake in the output Same as  Range Set  in the output signal signal range setting or in the above   ting Error or   range setting or in number of outputs setting    Error In Num    the number of out   ber of Out  puts setting    puts Used   Setting   38010000 hex   Scaling Data   There is anerrorin le The upper or lower limit data for Same as  Setting the scaling data scaling is outside the setting above    Error Ratio sett
120. erCAT Master Node No  1 Network Configuration Verification Error 0Ox84220000  1 1 1970 9 00 07 AM Minor fault EtherNet IP Communications port DNS Server Connection Error  1 1 1970 9 00 06 AM EtherNet IP Communications port IP Address Duplication Error  1 1 1970 9 00 05 AM   Major fault 1 O bus Master End Cover Missing  1 1 1970 9 00 03 AM Minor fault PLC Real Time Clock Stopped    du  Lui  Ka  O  C  GC  D        gt   O                zZ  O     1   Di   F  D  m     O     Wa         Display Settings    Displayed Information    ba System Event Log ba Access Event Log    Level       Major fault  amp  Partial fault E Minor fault    Observation If Information    Details The same IP address is used more than once    Cause     The IP address of the built in EtherNet IP port is also used as the IP address of another node    Attached information 1   Me zess ell M addennn farna MT NAOTANI     adden 1979 100  HEED 1    Attached information 1 OxCOA8FA0A   Attached information 2   Attached information 3   Attached information 4    Display Switch Update Print  12 events Last data logged at 6 23 2011 11 59 20 PM    i Resetting Errors with the Sysmac Studio    You can use the Sysmac Studio to reset errors that occur in a Controller  Before you attempt to reset a  Controller error  isolate and remove the cause of the error        oppe oewsAs   y  LU s10113 Bunjesey pue DuuInuept  E Z    The Troubleshooting Dialog Box displays the cause  source  and corrections for the error  You can  select an
121. erator   Motion Control Instructions W508  Out of Range   Auxiliary Axis Gear Ratio Denomina    Motion Control Instructions W508  tor Out of Range   Master Axis Position Type Selection Motion Control Instructions W508  Out of Range   Auxiliary Axis Position Type Selection   Motion Control Instructions W508  Out of Range   Target Position Ring Counter Out of   Motion Control Instructions W508  Range   Results Information  ID Tag Address   CJ series ID Sensor Units Z317  Error   Results Information  Write Protection   CJ series ID Sensor Units Z317  Error    Results Information  Command Error   CJ series ID Sensor Units Z317    Command Error CJ series Serial Communications W494  Units   Sequence Abort Completed CJ series Serial Communications W494  Units    Protocol Macro Error CJ series Serial Communications W494  Units    Variable Access Error    Built in EtherNet IP Port on CPU Unit   W506    Error    Task Period Exceeded Errors Related to Tasks W501  Impossible to Access Special Unit Errors Related to Unit Configuration   W500  Emergency Message Detected Built in EtherCAT Master in CPU Unit   W505    Target Position Positive Software General Motion Control W508  Limit Exceeded    Target Position Negative Software General Motion Control W508  Limit Exceeded    Command Position Overflow Under  General Motion Control W508  flow    Positive Limit Input General Motion Control W508  Negative Limit Input General Motion Control W508       NJ series Troubleshooting Manual  W503     
122. eries DeviceNet Units W497    EtherCAT Communications Warning   G5 series Servo Drives with Built in   1576  EtherCAT Communications   EtherCAT State Change Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   EtherCAT Illegal State Change Error   G5 series Servo Drives with Built in   1576  EtherCAT Communications   Communications Synchronization G5 series Servo Drives with Built in   1576   Error EtherCAT Communications   Synchronization Error G5 series Servo Drives with Built in   1576  EtherCAT Communications    Sync Manager WDT Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   ESC Initialization Error G5 series Servo Drives with Built in 1576  EtherCAT Communications   Slave Unit Verification Error G5 series Servo Drives with Built in 1576  EtherCAT Communications    Communications Setting Error G5 series Servo Drives with Built in   1576  EtherCAT Communications    Synchronization Interruption Error G5 series Servo Drives with Built in   1576  EtherCAT Communications    Clock Changed Errors Related to Controller Opera    W500  W501  tion    Time Zone Changed Errors Related to Controller Opera    W500  W501  tion    Variable Changed to TRUE with Errors Related to Controller Opera    W500  W501   Forced Refreshing tion   Variable Changed to FALSE with Errors Related to Controller Opera    W500  W501   Forced Refreshing tion   All Forced Refreshing Cleared Errors Related to Controller Opera    W500  W501  tion    NJ series
123. ernet interface card        Can the Sysmac Studio go  online with CPU Unit        OT UG Jo  Dunoousaignoi  orc    Ethernet switch   i Troubleshooting a High System Service Load    If a high system service load is the problem  you will be able to go online with the CPU Unit from the  Sysmac Studio if you start in Safe Mode  Use the following procedure     1 Set on the DIP switch on the CPU Unit as shown below and then cycle the power supply to the  Controller     The CPU Unit will start in Safe Mode     Turn OFF     Turn ON        2 Go online with the CPU Unit from the Sysmac Studio and perform the required operation     Ensure that there is sufficient system service time to enable the Sysmac Studio to go online with  the CPU Unit  To do so  either increase the period of the primary periodic task or decrease the  sizes of the programs in the primary periodic task  Refer to NJ series CPU Unit Software User   s  Manual  Cat  No  W501  for information on setting the primary periodic task     3 Turn OFF all DIP switch pins and then cycle the power supply to the Controller to restore normal  CPU Unit operation     NJ series Troubleshooting Manual  W503  2 19    2 Error Troubleshooting Methods      Safe Mode Operation  In Safe Mode  the CPU Unit does not execute the user program even in RUN mode  This increases  the ratio of system service processing that is performed by the CPU Unit  which makes it easier for  the Sysmac Studio to go online with the CPU Unit  A major fault level Co
124. error   it   The CPU Unit has failed   00070000 hex   Real Time The oscillation of The battery voltage is low  Same as  Clock the real time clock The battery connector has above   Stopped stopped  The real  come loose   Ime clock IS SEUI The Battery is missing   an illegal time   00080000 hex   Real Time The real time clock The CPU Unit clock has failed  Same as  Clock Failed   in the CPU Unit above   failed   000B0000 hex   Low Battery   The voltage of the The battery voltage is low  Same as  Voltage Battery has The battery connector has above   dropped  come loose   The Battery is missing   10090000 hex   Battery  An error was The battery voltage is low  Same as  backup Mem    detected in the The battery connector has above     ory Check  Error    memory check of  the battery backup  memory in the CPU  Unit     NJ series Troubleshooting Manual  W503     come loose   The Battery is missing        3 3    3 Error Tables       weal O     000C0000 hex   CPU Unit The temperature e The ambient operating temper  NJ series    Overheat inside the CPU Unit ature is too high  CPU Unit  exceeded the spec  Hardware  ified value  User s Manual    Cat  No   W500   000F0000 hex   SD Memory   The current SD An SD Memory Card that is not Same as   Card Invalid   Memory Card is not supported was inserted into the above    Type supported  CPU Unit    00100000 hex   SD Memory   The specified num  The service life of the SD Mem  Same as   Card Life ber of deletions for ory Card was exceeded  abov
125. es Con   troller  You can confirm these errors with the Sysmac Studio or an NS series PT     1 2 NJ series Troubleshooting Manual  W503     1 Overview of Errors    Refer to 1 3 Non fatal Errors for error types and confirmation methods for non fatal errors     1 1 2 CPU Unit Status    You can check the operating status of the CPU Unit with the PWR  RUN  and ERROR indicators on the  front panels of the Power Supply Unit and CPU Unit     Power Supply Unit CPU Unit       ei             RUN     OMRON    RUN indicator                       __       PWR indicator geg     mH 801 1500  ERROR indicator Sie           PA3001                      SD PWR CH    SD BUSY CC                            EI  AC100 240V  INPUT   L2 N    The following table shows the status of the front panel indicators  the status of user program execution   and the ability to make a software connection to the Sysmac Studio or an NS series PT during startup   during normal operation  and when there are errors in the Controller                 CPU Unit User pro  Software connec   gram execu    tion to Sysmac Stu     PWR RUN ERROR tion status   dio or NS series PT  Lit Flashing Not lit Stops  Not possible   During startup  1 s inter   vals   a    During normal   RUN mode Nat Possible  operation PROGRAM mode Not lit Not lit    Power Supply Error     Not lit Not lit Not lit Not possible   CPU Unit Reset     Not lit Not lit    Incorrect Power Sup  a C Lit Stops   vals     CPU Unit Watchdog Lit Not lit Lit Stops    Time
126. estoration log failed  retention of memory during a above   Error power interruption   10260000 hex   Trace Setting   The power supply The power supply was inter  Same as  Transfer Fail    was interrupted rupted while transferring the above   ure while transferring trace settings   the trace settings   90010000 hex   Clock The clock time was Te The clock time was changed  d Same as  Changed changed  above   90020000 hex   Time Zone The time zone was _  e The time zone was changed  d Same as  Changed changed  above   90080000 hex   Variable Changing a variable   e Changing a variable to TRUE d Same as  Changed to to TRUE with forced with forced refreshing was above   TRUE with refreshing was specified by the user   Forced specified   Refreshing  90090000 hex   Variable Changing a variable   e Changing a variable to FALSE d Same as  Changed to to FALSE with with forced refreshing was above   FALSE with forced refreshing specified by the user   Forced was specified   Refreshing  900A0000 hex   All Forced Clearing all forced e Clearing all forced refreshing d Same as  Refreshing refreshing values values was specified by the above     Cleared    was specified     NJ series Troubleshooting Manual  W503        user     3 7    3 Error Tables    e A user with Administrator rights  cleared all of the memory     900B0000 hex    900C0000 hex    90110000 hex    90120000 hex    90130000 hex    90140000 hex    90150000 hex    90160000 hex    90180000 hex    90190000 hex    Memory All  Clear
127. et Value Error CJ series Analog I O Units W490    Overload Warning G5 series Servo Drives with Built in   1576  EtherCAT Communications   Excessive Regeneration Warning G5 series Servo Drives with Built in   1576  EtherCAT Communications   Vibration Detection Warning G5 series Servo Drives with Built in   1576  EtherCAT Communications   Excessive Hybrid Following Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   Overspeed 2 G5 series Servo Drives with Built in   1576  EtherCAT Communications   Command Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   G5 series Servo Drives with Built in   1576   EtherCAT Communications   G5 series Servo Drives with Built in   1576   EtherCAT Communications    Command Generation Error    Error Counter Overflow 1    G5 series Servo Drives with Built in 1576  EtherCAT Communications    Error Counter Overflow 2    Interface Input Duplicate Allocation G5 series Servo Drives with Built in   1576    Error 1 EtherCAT Communications  Interface Input Duplicate Allocation G5 series Servo Drives with Built in   1576  Error 2 EtherCAT Communications  Interface Input Function Number G5 series Servo Drives with Built in   1576  Error 1 EtherCAT Communications  Interface Input Function Number G5 series Servo Drives with Built in   1576  Error 2 EtherCAT Communications  Interface Output Function Number G5 series Servo Drives with Built in   1576  Error 1 EtherCAT Communications  Interface Output Function N
128. ew of Errors    Section 2  Error Troubleshooting Methods    Section 3  Error Tables    Description    This section describes the errors that can occur on an NJ series Controller  the oper   ation that occurs for errors  and methods to confirm errors     This section describes how to handle errors     This section lists all of the error events that can occur on NJ series Controllers     i Sysmac Studio Version 1 Operation Manual  Cat  No  W504     Section    Section 1  Introduction    Section 2  Installation and Uninstallation    Section 3  System Design    Section 4  Programming    Section 5  Online Connections to a Controller    Section 6  Debugging  Section 7   Other Functions    Section 8  Reusing Programming    Section 9  Support Software Provided with the  Sysmac Studio    Section 10  Troubleshooting    Appendices    Description    This section provides an overview and lists the specifications of the Sysmac Studio  and describes its features and components     This section describes how to install and uninstall the Sysmac Studio     This section describes the basic concepts for designing an NJ series System with the  Sysmac Studio and the basic operating procedures     This section describes how to create programs with the Sysmac Studio     This section describes how to go online with a Controller     This section describes how to debug the programs online on the Controller or debug  it offline with the Simulator     This section describes Sysmac Studio functions other t
129. f the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     _mclmmediateStop was speci   fied for the StopMode input  variable when the  MC_TouchProbe  Enable Exter   nal Latch  instruction was exe   cuted in Drive Mode  but the  Control Mode was not CSP  Mode or the Servo was OFF     The instruction input parameter  exceeded the range of signed  40 bit data when it is converted  to pulses     The instruction input parameter  exceeded the range of signed  40 bit data when it is converted  to pulses     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable       Level O     a aee ee    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     e Instruction input parameter    54970000 hex    54980000 hex    54990000 hex    549A0000 hex    549B0000 hex    549C0000 hex    64400000 hex    Master Axis  Gear Ratio  Denominator  Out of Range    Auxiliary Axis  Gear Ratio  Numerator  Out of Range    Auxiliary Axis  Gear Ratio   Denominator  Out of Range    Master Axis  Position Type  Selection Out  of Range    Auxiliary Axis  Position Type  Selection Out  of Range    Target Posi   tion Ring  Counter Out  of Range    Tar
130. for a  motion in the nega   tive direction was  executed when the  negative limit input  was ON     An attempt was  made to turn ON  the Servo when the  main circuit power  supply to the Servo  Drive was OFF     Position input variable to the  instruction is beyond the nega   tive software limit     The first position is beyond the  negative software limit and an  instruction that specifies motion  in the opposite direction of the  software limit was executed    The parameter that was speci   fied for the AuxPoint input vari   able to a border point  MC_MoveCircular2D  Circular  2D Interpolation  instruction is  beyond the negative software  limit   One of the following was exe   cuted when there was a com   mand position  overflow underflow     e A positioning instruction   e A continuous control instruc   tion in the underflow overflow  direction    e An instruction for which the  direction is not specified   syncing or torque control     An instruction for a motion in  the positive direction was exe   cuted when the positive limit  input was ON  or an instruction  for a motion with no direction  specification was executed  when the positive limit input  was ON     An instruction for a motion in  the negative direction was exe   cuted when the negative limit  input was ON  or an instruction  for a motion with no direction  specification was executed  when the negative limit input  was ON     An attempt was made to turn  ON the Servo when the main  circuit power supply to th
131. for a particular axes  group    e For the I O bus  you can reset all errors or  just the errors for a particular Unit     Use a CIP message from a host computer  to reset errors     After the causes of the Controller errors are  removed  all Controller errors in all function  modules are reset as a result     NJ series Troubleshooting Manual  W503        Error Troubleshooting Methods    This section describes troubleshooting methods for specific errors        2 1    2 2  2 3    2 4    Troubleshooting Flowcharts           000 cee eee es 2 2  2 1 1 Checking to See If the CPU Unit Is Operating                     0005  2 2  2 1 2 Troubleshooting Flowchart for Non fatal Errors    2 3  Troubleshooting Fatal Errors          0 0  cee es 2 4  Troubleshooting Non fatal Errors              0000 eee ee 2 5  2 3 1 Identifying and Resetting Errors with the Sysmac Studio                  2 5  2 3 2 Identifying and Resetting Errors with an NS series PT                    2 9  2 3 3 Identifying and Resetting Errors from the User Program                  2 11  2 3 4 Checking for Errors with System defined Variables                      2 13    Troubleshooting When You Cannot Go Online from the Sysmac Studio 2 14    2 4 1 Causes and Correction When You Cannot Go Online from the  Set ele EE 2 14  2 4 2 Troubleshooting for Each Cause  2 15    NJ series Troubleshooting Manual  W503  2 1       2 Error Troubleshooting Methods    2 1 Troubleshooting Flowcharts    This section provides basic error id
132. g  Hardware W  User   s Manual     Cat  No  u  W500  S  000D0000 hex   Internal NJ  A fatal error was Conductive material has gotten Same as g  series Bus detected on the inside  above  2  Check Error   internal bus  Noise S  O  The CPU Unit has failed  Ve  000E0000 hex   Non volatile   The specified num  Non volatile memory life Same as  Memory Life   ber of deletions for expired  above   Exceeded non volatile mem   ory was exceeded   Or  the number of D  bad blocks in mem  L  ory exceeded the N  specified value  u   O  10010000 hex   Non volatile An error was The Controller power supply Same as o  Memory detected in the non  was turned OFF while the above  5  Restored or   volatile memory BUSY indicator was lit  Se  Formatted check and file SyS  The power supply to the Con  d  tem recovery or for    troller was interrupted momen  O  matting was tarily while the BUSY indicator 3  executed  Previous was lit      files may have been O  deleted     O  10020000 hex   Non volatile   A file that must be The Controller power supply Same as a  Memory Data   in non volatile was turned OFF while the above  p  Corrupted memory is missing BUSY indicator was lit   or corrupted  The power supply to the Con   troller was interrupted momen   tarily while the BUSY indicator  was lit   The CPU Unit has failed   10080000 hex   Main Memory   An error was Conductive material has gotten Same as  Check Error   detected in the inside  above   memory check of Noise  SE Gg Ge D n There is a software 
133. g Flowchart for Non fatal Errors    For a non fatal error  use the Sysmac Studio or an NS series PT to troubleshoot the error with the fol   lowing flowchart  You can use the indicators to check the following     e Level  e Whether the error is in the EtherNet IP Function Module or the EtherCAT Master Function Module    e  f the sources of the error is the EtherNet IP Function Module or the EtherCAT Master Function Mod   ule  whether you can restore normal status yourself    N  I         oO  z  z      G   gt   O  O   i  5       1  O     O   gt   D  ch  a    Non fatal error  To immediately check the  specific error    To check error status with the indicators       Lit  Flashing     ERROR indicator  red      Not lit  Partial fault level or  minor fault level    Check all of the following branches that correspond to the  status of the EtherNet IP NET ERR and EtherCAT NET  ERR indicators        EtherNet IP NET ERR indicator is lit or flashing  Both indicators are not lit         EtherCAT NET ERR indicator is  lit or flashing                  EtherCAT NET ERR Flashing     indicator  red      EtherNet IP NET ERR  indicator  red          S101143 IEISL UON 10  WeUOMO 4 BuNoousejqnol  Z L Z        l Error in the Error in the  Major fault Observa  Error in the Error in the EtherCAT Master EtherCAT Master Error in PLC    level tion    EtherNet IP Function EtherNet IP Function Function Module for Function Module for Function Module or    MC Function    Module for which you Module for wh
134. get Posi   tion Positive  Software  Limit  Exceeded    The parameter  specified for the  RatioDenominator   Master input vari   able to a motion  control instruction is  out of range     The parameter  specified for the  RatioNumera   torAuxiliary input  variable to a motion  control instruction is  out of range     The parameter  specified for the  RatioDenomina   torAuxiliary input  variable to a motion  control instruction is  out of range     The parameter  specified for the  Reference Type   Master input vari   able to a motion  control instruction is  out of range     The parameter  specified for the  Reference lypeAux   iliary input variable  to a motion control  instruction is out of  range     Operation is not  possible because  the target position  is out of range for  the ring counter of  the executed  instruction     The specified posi   tion exceeds the  positive software  limit     NJ series Troubleshooting Manual  W503     exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     High speed homing was exe   cuted when 0 was not included  in the ring counter     The parameter specified for the  Position input variable to the  instruction is beyond th
135. h system service   The system service Start in Safe Mode  Refer to Troubleshooting a High System Ser   load load on the CPU Unit   vice Load on page 2 19    is too high and time   cannot be obtained to   connect with the Sys    mac Studio           Note If the EtherNet IP NET ERR indicator on the CPU Unit is lit or flashing  it is possible that you cannot go online  through an EtherNet IP route because of an error in the EtherNet IP Function Module  See if you can go  online with a direct USB connection     You can use the status of the RUN indicator on the CPU Unit to isolate the cause  Implement the trou   bleshooting for the applicable cause     Causes    RUN indicator Incorrect settings or    rane Fatal error in the CPU High system service  faulty communications    Unit load    path    Flashing at 3 s intervals  Cause  Incorrect Power      Supply Unit connected         2 14 NJ series Troubleshooting Manual  W503     2 Error Troubleshooting Methods    2 4 2 Troubleshooting for Each Cause    This section provides troubleshooting methods for incorrect settings  fault communications paths  and  high system service loads     Troubleshooting Incorrect Settings and Faulty Communications  Path       OF JOUURD nog uayM BulooyusealqnolL v z    Olpnis dewsAS   y  UO sUl UO    If the Sysmac Studio cannot go online with the CPU Unit  troubleshoot the problem with the following  flowchart        Direct Connection to Peripheral USB Port    Sysmac Studio cannot  connect to CPU Unit      
136. han system design functions     This section describes how to reuse the programs that you create with the Sysmac  Studio     This section describes the Support Software that is provided with the Sysmac Studio     This section describes the error messages that are displayed when you check a pro   gram on the Sysmac Studio and how to correct those errors     The appendices describe the following    Driver Installation for Direct USB Cable Connection  Specifying One of Multiple Ethernet Interface Cards  Online Help   Simulation Instructions    NJ series Troubleshooting Manual  W503     Manual Structure    Manual Structure       Page Structure    The following page structure is used in this manual     4 Installation and Wiring Level 1 heading  Level 2 heading  Level 2 heading 4 3 Mounting Units Level 3 heading  Gives the current  Level 3 heading 4 3 1 Connecting Controller Components headings     The Units that make up an NJ series Controller can be connected simply by pressing the Units together  and locking the sliders by moving them toward the back of the Units  The End Cover is connected in the  same way to the Unit on the far right side of the Controller     A step In a procedu re 1 Join the Units so that the connectors fit exactly   Indicates a procedure  T    cones  holes    nt   l          Page tab    Gives the number  of the main section     syun Dupunou Et    2 The yellow sliders at the top and bottom of each Unit lock the Units together  Move the sliders  toward the ba
137. he relay for the dynamic brake  has been welded due to fre   quent Servo ON OFF opera   tions    Motor windings are burned out   The Servomotor is not suitable  for the Servo Drive    The pulse input timing is the  same as or earlier than the  Servo ON timing     The Servo Drive regeneration  drive Tr is faulty     The encoder is faulty     The encoder is faulty     The Servo Drive failed     The encoder is not wired cor   rectly     The power supply voltage of the  encoder is low     e Noise       p Level O     Reference    AC Servomo   tors Servo  Drives G5  Series with  Built in Ether   CAT Commu   nications  User s Man   ual  Cat  No   1576     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O           080A0000 hex   Encoder There is an error in        The power supply voltage of the AC Servomo   Communica    the communica  encoder is low  tors Servo  tions Data tions data of the Noise Drives G5  Error encoder  Series with  Built in Ether   CAT Commu   nications Ce  User s Man     ual  Cat  No  u  1576  S  080B0000 hex   Safety Input   At least one of the The cable is disconnected or Same as    Error input photocou  broken  above  oS  plers for safety    inputs 1 and 2     turned OFF   080C0000 hex   External A disconnection The wiring is incorrect  Same as  Encoder was detected above   Connection because communi   Error
138. herCAT Master Function Module    _EC_PortErr Error status variable for communications ports    SOIOGUGA P9UlJep W9a SAS YUM S101414 10  Buiyoauy ebe    EC Meirtrr Error status variable for master    _EC_SlavErr Summary error status variable for all slaves    _EC_SlaveErrTbl Error status variable for slaves    _EIP_ErrSta Error status variable for EtherNet IP Function Module    _EIP_PortErr Error status variable for communications ports    _EIP_CipErr Error status variable for CIP communications    Error status variable of the TCP application function    _EIP_TcpAppErr    NJ series Troubleshooting Manual  W503  2 13    2 Error Troubleshooting Methods    2 4 Troubleshooting When You Cannot  Go Online from the Sysmac Studio    The section describes the procedure to troubleshoot when you cannot go online with the CPU Unit from  the Sysmac Studio     2 4 1 Causes and Correction When You Cannot Go Online from the  Sysmac Studio    The following table lists the possible causes when you cannot go online with the NJ series CPU Unit  from the Sysmac Studio     Incorrect settings or   There is a mistake in   Refer to Troubleshooting Incorrect Settings and Faulty Communi   faulty communica  the settings that the   cations Path on page 2 15   tions path Sysmac Studio uses   to go online with the    CPU Unit  Or  the  communications path  is faulty     Fatal error inthe CPU   A fatal error occurred   Refer to 2 1 1 Checking to See If the CPU Unit Is Operating   Unit in the CPU Unit     Hig
139. ich you which you cannot which you can  Module    ee SE can sie deen restore normal restore normal  status by yourself  status by yourself  status by yourself  status by yourself        Troubleshoot the error with the Sysmac Studio or NS series PT     Refer to 2 3 Troubleshooting Non fatal Errors        NJ series Troubleshooting Manual  W503  2 3    2 Error Troubleshooting Methods    2 2 Troubleshooting Fatal Errors    SSS  The section describes the procedure to troubleshoot fatal errors        Power Supply Error    Cause Correction  Power is not being input  Turn ON the power   The voltage is outside of the allowable Check the Controllers power supply system  and correct it so that the  range for the power supply  voltage is within the allowable range   Power supply system error caused by Remove the Units from the CPU Rack one by one  If the error is elim   mounted Unit inated  replace that Unit   Power Supply Unit failure If the error persists even after you make the above corrections     replace the Power Supply Unit        CPU Unit Reset    Cause Correction  A conductive object has gotten inside  If there is conductive material nearby  blow out the CPU Unit with air   The power supply to an Expansion Rack   Supply the correct voltage to the Power Supply Unit on the Expansion  is OFF  Rack   The I O Connecting Cable is incorrectly   Correct the connection of the I O Connecting Cable   installed   Noise If the error did not result from the above causes  cycle the power to  
140. ies Controllers     This section describes the parts and functions of the configuration devices in the NJ   series Controller configuration  including the CPU Unit and Configuration Units     This section describes where and how to install the CPU Unit and Configuration Units  and how to wire them     This section describes the event codes  error confirmation methods  and corrections  for errors that can occur     This section describes the contents of periodic inspections  the service life of the Bat   tery and Power Supply Units  and replacement methods for the Battery and Power  Supply Units     The appendices provide the specifications of the Basic I O Units  Unit dimensions   load short circuit protection detection  line disconnection detection  and measures for  EMC Directives     H NJ series CPU Unit Software User   s Manual  Cat  No  W501     Section    Section 1  Introduction    Section 2  CPU Unit Operation    Section 3  UO Ports  Slave Configuration  and  Unit Configuration    Section 4  Controller Setup    Section 5  Designing Tasks    Section 6  Programming    Section 7   Simulation  Transferring Projects to  the Physical CPU Unit  and Opera   tion   Section 8   CPU Unit Status    Section 9  CPU Unit Functions    Section 10  Communications Setup    Section 11  Example of Actual Application Pro   cedures    Section 12  Troubleshooting    Appendices    NJ series Troubleshooting Manual  W503     Description    This section provides an introduction to the NJU series 
141. ig  above   Number Error   fication in the nal  OUTM1  function alloca   1 output signal tion    OUTM1  function  allocation   NJ series Troubleshooting Manual  W503  3 49    3 Error Tables       weal O     384A0000 hex   Interface Out    There is an unde  e There is an undefined number AC Servomo   put Function   fined number speci  specification in the output sig  tors Servo  Number Error   fication in the nal  OUTM2  function alloca  Drives G5  2 output signal tion  Series with   OUTM2  function Built in Ether   allocation  CAT Commu   nications  User s Man   ual  Cat  No   1576   384B0000 hex   External There is an error in The latch input was allocated to Same as  Latch Input the latch input func  an input signal other than IN5  above   Allocation tion allocation  IN6  or IN7   Error A latch input is assigned to an  NC signal   The same latch input is not  assigned to the same pin in all  Control Modes   384C0000 hex   Overrun Limit   The Servomotor The gain or inertial ratio is not Same as  Error exceeded the allow  suitable  above   able operating The set value of the Overrun  range set in the Limit Setting  3514 hex  is too  Overrun Limit Set  small   ting  3514 hex  with  respect to the posi   tion command input  range   384D0000 hex   Absolute The voltage of the The voltage of the built in Same as  Encoder Sys    built in capacitor capacitor dropped below the above   tem Down dropped below the specified value because the  Error specified value power supply to the en
142. ile  memory is cor   rupted     The checksum data  in non volatile  memory is cor   rupted     The checksum data  in non volatile  memory is cor   rupted     The checksum data  in non volatile  memory is cor   rupted     The Servomotor  rotation speed  exceeded the spec   ified value when  only the battery  power supply was  used during a  power interruption     e An error such as broken wiring    was detected in the external  encoder phase B connection     An error such as broken wiring  was detected in the external  encoder phase Z connection     There is insufficient power sup   ply voltage for the encoder     Noise is entering on the  encoder line     There is insufficient power sup   ply voltage for the external  encoder     Noise is entering on the exter   nal encoder line        Noise  Non volatile memory failure    Noise  Non volatile memory failure    Noise  Non volatile memory failure    Non volatile memory failure    Non volatile memory failure    Non volatile memory failure    There is insufficient power sup   ply voltage for the encoder   The wiring of the CN2 connec   tor is wrong    An external force is rotating the  motor when the Servo is OFF     AC Servomo   tors Servo  Drives G5  Series with  Built in Ether   CAT Commu   nications  User s Man   ual  Cat  No   1576     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     II  II  II  d Same as  above   II    aa  II    above     Same as  above     Same as  above     d 
143. in the Action and Correction list  either the Jump to Error or  Error Help Button is enabled  depending on the contents  In some cases  neither button will operate   Click the enabled button  and proceed with the displayed troubleshooting steps     After you complete all of the troubleshooting steps for the current errors  click the Reset All Button to  reset all of the current errors  If the cause of the error is not removed  or if the power supply is not  cycled or the Controller is not reset as required after resetting the error  the error will occur again     Display Switch    Reset All       Button Description   Jump to Error This button is enabled when the error correction involves a change in the Sysmac Studio  settings  When you click the button  the Sysmac Studio will automatically switch to the  Editing Pane    Error Help The correction methods or the attached information is displayed if it is not possible to jump  to the settings display    Reset All This button resets all of the current errors  and reads errors again     It is necessary to synchronize the data between the Sysmac Studio and the connected CPU Unit before  you use the Jump to Error Button     For details on synchronization  refer to the Sysmac Studio Version 1 Operation Manual  Cat  No  W504     If you have enabled the verification of operation authority  it is necessary to confirm your authority  before you can reset Controller errors  The Maintainer and Administrator have the authority to reset  er
144. incorrect     The task period setting is too  short     The priority of the periodic task  is incorrect     There are too many Units and  slaves that perform I O refresh  in the task period     There is no unused time avail   able for task execution     The system service execution  interval is too short or the sys   tem service execution time ratio  is too long in the system ser   vice execution time settings     The task period setting is too  short   A user program is too large     The number of times that pro   cessing is repeated is larger  than expected     The priority of the periodic task  is incorrect     The task period setting is too  short     A user program is too large   The number of times that pro   cessing is repeated is larger  than expected    The priority of the periodic task  is incorrect     Reference    NJ series  CPU Unit Soft   ware User   s  Manual  Cat   No  W501     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables      Errors Related to Controller Operation  p Level O   sw  eure  en En  Jas a 7    10200000 hex   User Pro  The user program e The program is illegal because NJ series          gram Con  or Controller Con  the power supply to the Control  CPU Unit  troller figurations and ler was interrupted or communi  Hardware P  Configura  Setup were not cations with the Sysmac Studio User   s Manual m  tions and transferred cor  were disconnected during a  Cat  No  
145. ined error   16 040C Limit Exceeded for   An attempt was made to e An attempt was made to use the Create Same as  User defined use the Create User  User defined Error instruction to create above   Errors defined Error instruction to more than the maximum number of user   create more than the maxi  defined errors   mum number of user   defined errors   16 040D Illegal Unit Speci    The Unit specified for an e A Unit that does not exist in the Unit configu    Same as  fied instruction does not exist  ration information was specified  above   e A Unit that is in the Unit configuration infor   mation was specified  but the Units does not  actually exist in the Controller   16 040F Unit Restart Failed   Restarting a Special I O e The Special I O Unit or CPU Bus Unit is pro    Same as  Unit or CPU Bus Unit failed  cessing data  above   16 0410 Text String Format   The text string input to an e The text string that is input to the instruction   Same as  Error instruction is not correct  for conversion to a number does not repre    above   sent a number or it does not represent a  positive number   e The input text string does not end in NULL   16 0411 Illegal Program The program specified for e The program specified by the function does   Same as  Specified an instruction does not not exist  eg  it was deleted   above   exist   16 0413 Undefined CJ  The required specification e The required AT specification is missing for   Same as  series Memory is missing for a variable for a vari
146. ing cam operation     Immediate An Immediate Stop An Immediate Stop instruction d Same as  Stop Instruc     MC_ImmediateSto was executed  above   tion Executed   p  instruction was   executed   Axes Group   An Axes Group A Group Immediate Stop d Same as  Immediate Immediate Stop instruction was executed  above   Stop Instruc     MC_GroupImmedi  tion Executed   ateStop  instruc    tion was executed   Positive Soft    The position The position exceeded the posi  d Same as  ware Limit exceeded the posi  tive software limit  above   Exceeded tive software limit   while the axis is in   motion   Negative The position The position exceeded the neg  d Same as  Software exceeded the nega  ative software limit  above   Limit tive software limit  Exceeded while the axis is in   motion   In position The in position Time is required to complete d Same as  Check Time   check was not com  positioning  above   Exceeded pleted within the   monitoring time           NJ series Troubleshooting Manual  W503  3 11    OO  I      m        O     Vu  o   lt   GU  O  c     O  OD         jNpoN uonouny  O4 UOD uono 3y  Ul SIO E L       3 Error Tables    e The positioning operation has    64480000 hex    64490000 hex    644A0000 hex    644B0000 hex    64560000 hex    64570000 hex    64580000 hex    64590000 hex    3 12    Following  Error Limit  Exceeded    Immediate  Stop Input    Positive Limit  Input  Detected    Negative  Limit Input  Detected    Illegal Follow   ing Error    Servo OFF  Error    Abso
147. ing or ratio con  range  Or  the maximum value  Conversion version use setting  and minimum value are not 0  Use Setting and they are the same   Error e The I O number for ratio con   version is set to Not used in the  I O specifications    38020000 hex   Ratio Set There is a mistake  e A value other than 16 0000 to Same as  Value Error is the ratio setting 16 9999  0 00 to 99 99  was above    for ratio conversion  specified for the ratio conver   sion A constant for ratio conver   sion    64780000 hex   Input Discon    The input is discon       Input wiring is broken  Same as   nection nected  e Input wiring disconnection above        Detected    64790000 hex   Output Set The output setting      An output set value setting is d Same as  Value Error is out of range  out of range  above   34810000 hex   Input Value In Adjustment e In Adjustment Mode  the input d Same as  Exceeded Mode  the input value exceeded the range for above   Adjustment value exceeded the which adjustment is possible   Range in range for which so the offset and gain cannot  Adjustment adjustment is possi  be adjusted   Mode ble     NJ series Troubleshooting Manual  W503  3 57       3 Error Tables       wea O     EE Eventname   Meaning EE a aee    34820000 hex    34880000 hex    348C0000 hex    Input Number  Specification  Error in  Adjustment  Mode    Output Num   ber Specifi   cation Error  in Adjustment  Mode    I O Number  Specification  Error in  Adjustment  Mode    The input number  specified in Adj
148. ink link for a variable that specifies    failed  SUBRANGE  NW  84050000 hex   Packet Dis  A packet was dis  A network convergence Same as  carded Due carded  occurred  above   to Full  Reception  Buffer  84060000 hex   Link OFF The Ethernet link An Ethernet cable is broken  Same as T  Detected status turned OFF  disconnected  or loose  above  D  The switching hub power sup  m  ply is turned OFF  S  Baud rate mismatch  5  Noise Sp  One of the following operations Y  was performed  D  e The Identify object was reset  a  e Settings were downloaded  0  from the Network Configura  au  tor and EtherNet IP was 5  restarted  O  Settings for EtherNet IP were    downloaded from the Sysmac E  Studio or the Memory All oJ  Clear operation was per   formed   94010000 hex   Tag Data Link   Changing the tag Changing the tag data link set  Same as  Download data link settings tings started  above   Started started   94020000 hex   Tag Data Link   Changing the tag Changing the tag data link set  Same as  Download data link settings tings finished  above   Finished finished   94030000 hex   Tag Data Link   Tag data links were Tag data links were stopped by Same as  Stopped stopped by Network Network Configurator or manip  above   Configurator or ulation of a system defined  manipulation of a variable   system defined  variable  Or  the  data link table was  downloaded from  the Network Config   urator again   94040000 hex   Tag Data Link   Tag data links were Tag data links were started by Sam
149. iod  500 us  Series with  Fully closed Control Mode was Built in Ether   selected for a communications CAT Commu   period setting of 250 us  EE  Modes of operation  6060 hex  User s Man   was set to pp or hm when the ual  Cat  No   communications period was set 1576   to 250 or 500 us   More than 20 bytes were  mapped for RXxPDO when the  communications period was set  to 250 us   More than 12 bytes were  mapped for RxPDO in Fully   closed Control Mode   Modes of operation  6060 hex   was set to pp or hm in Fully   closed Control Mode when the  communications period was set  to 1 ms and the electronic gear  parameter ratio was not set to  1 1   No bytes  i e   no objects  were  mapped for RxPDO   More than 10 objects were  mapped for RxPDO   More than 11 objects were  mapped for TxPDO   CSP Switching Reference Posi   tion  4020 hex  was mapped for  TxPDO when the communica   tions period was set to 250 or  500 us or when the electronic  gear object ratio was not set to  1 1     64E00000 hex   Drive Prohibi    When the Drive A problem occurred with the d Same as   tion Input Prohibition Input switches  wires  and power sup  above   Error 1 Selection  3504 plies that are connected to the   hex  was set to O  Forward Drive Prohibition input   both the Forward or the Reverse Drive Prohibition   Drive Prohibition input    Input  POT  and the   Reverse Drive Pro    hibition Input  NOT    turned ON  Or    when the Drive Pro    hibition Input Selec    tion  3504 hex  was   set to 2  
150. ion Rack  S  CPU Rack or an The End Cover is not con     Expansion Rack  nected properly   24040000 hex   Incorrect The number of More than 10 Units are con  Same as  Unit Expan  Units or Expansion nected to one Rack  above   sion Rack Racks exceeds the More than three Expansion  Connection maximum value Racks are connected   specified for the More than two Interrupt Input  CPU Unit  Or  an   Units are mounted   Interrupt Input Unit    WaS Mounedo A An Interrupt Input Unit was  unsupported slot or mounted to a unsupported slot  to an Expansion or to an Expansion Rack   Rack   24050000 hex   Duplicate The same unit num  The same unit number is set for Same as  Unit Number   ber is set for more more than one Special I O Unit above     than one Special or more than one CPU Bus   I O Unit or more Unit    than one CPU Bus The same unit number is   Unit  assigned to a Special UO Unit  that uses more than one unit  number and another Special  I O Unit     34010000 hex   I O Setting There is an incon  A Unit model in the Unit Config    V Same as  Check Error   sistency between a uration in the CPU Unit is differ  above   Unit model in the ent from the Unit model that is  Unit Configuration mounted in the Controller   in the CPU Unit and  the Unit model that  is mounted in the  Controller     NJ series Troubleshooting Manual  W503  3 5       3 Error Tables       weal O     GE Eventname   Meaning EE a aee    64010000 hex    80010000 hex    Impossible to  Access Spe   cial Unit    Illeg
151. ion is pulses   out of range or the For a Linear Mode axis  the tar   target position with get position with the travel dis   the value of Dis  tance added exceeded signed  tance added is out 40 bit data when the absolute  of range  value is converted to pulses    547A0000 hex   Cam Table The parameter Instruction input parameter Same as   Start Point specified for the exceeded the valid range of the above    Setting Out of   StartPosition input input variable    Range variable to a motion  control instruction is  out of range    547B0000 hex   Cam Master   The parameter Instruction input parameter Same as   Axis Follow    specified for the exceeded the valid range of the above    ing First Posi    MasterStartDis  input variable    tion Setting tance input variable   Out of Range   to a motion control  instruction is out of  range    NJ series Troubleshooting Manual  W503  3 29    3 Error Tables    Circular Inter   polation  Radius Set   ting Error    547C0000 hex    547D0000 hex    547E0000 hex    547F0000 hex    54800000 hex    54810000 hex    54820000 hex    3 30    Circular Inter   polation  Radius Over   flow    Circular Inter   polation Set   ting Out of  Range    Auxil   iary Slave  Axis Num   bers Not in  Ascending  Order    Cam Table  Property  Ascending  Data Error at  Update    MC_Write  Target Out of  Range    Master Travel  Distance  Specification  Out of Range    It was not possible  to create a circular  path for the speci   fied radius when  the radius method 
152. ion was disabled     A switch that can be used  only when the scan list is dis   abled was used when the  scan list was enabled     A switch that can be used  only when the scan list is  enables was used when the  scan list was disabled     A software switch operation  for the slave function was  executed when the slave  function was disabled     A configuration error has  occurred     There is an error in the parame   ters specified in the user set   tings  and the requested setting  could not be made     OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       SIU  s  n  s f9 Ul S1013 J          More than one software switch  changed to TRUE at the same  time  Or  another software  switch changed to TRUE before  processing was completed for a  previous software switch     74630000 hex   Slave Func    Anerror occurred in An attempt was made to enable Same as  tion one of the following the slave function when it was above   Enable Dis  operations in the already enabled     able Failed slave function  An attempt was made to dis   able the slave function when it  was already disabled     CPU Unit is not in PROGRAM  mode     More than one software switch  changed to TRUE at the same  time  Or  another software  switch changed to TRUE before  processing was completed for a  previous software switch     74640000 hex   Slave Fixed An error occurred in The slave function is not dis  Same as  Allocation one of the following abled  above   Area Setting   operations for fixed C
153. ircle and explained in text   This example indicates prohibiting disassembly     The triangle symbol indicates precautions  including warnings    The specific operation is shown in the triangle and explained in text   This example indicates a precaution for electric shock     The triangle symbol indicates precautions  including warnings    The specific operation is shown in the triangle and explained in text   This example indicates a general precaution     The filled circle symbol indicates operations that you must do   The specific operation is shown in the circle and explained in text   This example shows a general precaution for something that you must do     NJ series Troubleshooting Manual  W503     Precautions for Safe Use    Precautions for Safe Use       Refer to the following manuals for precautions for the safe use of the NJ series Controller   Installation precautions are also provided for the NJ series CPU Unit and the NJ series Controller sys     tem   e NJ series CPU Unit Hardware User   s Manual  W500   e NJ series CPU Unit Software Users Manual  W501     NJ series Troubleshooting Manual  W503  17    Precautions for Correct Use    Precautions for Correct Use       Refer to the following manuals for precautions for the correct use of the NJ series Controller   Installation precautions are also provided for the NJ series CPU Unit and the NJ series Controller sys     tem   e NJ series CPU Unit Hardware User   s Manual  W500   e NJ series CPU Unit Software Users M
154. is  One or more pack  An attempt was made to senda Same as  carded ets were discarded  FINS response with over 2002 above   bytes     An attempt was made to route a  FINS response with over 2002  bytes     Packet was received with a No  Such Unit routing error     Packet was received with a  Routing Error routing error     Packet was received with a No  Routing Table routing error   Packet was received with a No  Routing Table routing error   Packet was received with an  Event Area Size Over Limit  routing error    There is insufficient space in  the internal buffer     OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       FINS message routing failed  because the communications  load is too high     80120000 hex   Packet Dis  One or more pack  A FINS response was received Same as  carded ets were discarded  in which DNA was the local net  above   work but DA1 was not the local  node     A FINS command or response  was received in which the hub  network address specification  DNA was greater than or equal  to 80 hex    There is insufficient space in  the internal buffer    A FINS command that does not  have the minimum command  length was received    A FINS command that  exceeded the maximum com   mand length was received   Sending packets failed    FINS message routing failed  because the communications  load was too high       JNPON UOOUNY O 1d OU  U  SION Z L           NJ series Troubleshooting Manual  W503  3 9    3 Error Tables    3 1 3 Errors in the Motion Con
155. is broken  Same as 5  Access Failed failed  e The SD Memory Card slot is broken  above     16 1800 EtherCAT Commu    Accessing the EtherCAT e The EtherCAT network is not in a usable Same as  nications Error network failed when an status  above   instruction was executed     16 1801 EtherCAT Slave Accessing the target slave  e The target slave does not exist  Same as  Does Not Respond failed when an instruction e The target slave is notin an operating condi  above   was executed  tion     16 1802 EtherCAT Timeout   A timeout occurred while e Communications with the target slave timed   Same as  trying to access an Ether  out  above   CAT slave when an instruc   tion was executed     16 1803 Reception Buffer The receive data from an e The receive data from the slave overflowed   Same as  Overflow EtherCAT slave overflowed the receive buffer  above   the receive buffer when an  instruction was executed     16 1804 SDO Abort Error An SDO abort error was e Depends on the specifications of the slave    Same as  received from an EtherCAT above   slave when an instruction  was executed     16 1805 Saving Packet An instruction for packet e An instruction for packet monitoring was Same as  Monitor File monitoring was executed executed while saving an EtherCAT packet   above   while saving an EtherCAT monitor file   packet monitor file     16 1806 Packet Monitoring   A Stop EtherCAT Packet e A Stop EtherCAT Packet Monitor instruction   Same as  Function Not Monitor instruction was was e
156. justment  Period Notice    An error occurred in  A D conversion     An error occurred in  the cold junction  sensor     An error occurred in  een mem     An input error  occurred     The zero span  adjustment period  expired     The zero span  adjustment period  is close to expiring     e There is a source of noise  nearby     e A D converter failed     e Faulty connection to the cold  junction sensor for the CJU1W   PH41U     e The cold junction sensor failed     e There is a source of noise  nearby     e Non volatile memory failed        range    Input wiring is broken    Input wiring disconnection or  loose terminal    The zero span adjustment  period expired     The notification period for the  expiration of zero span adjust   ment occurred     Reference    CJ series  Analog I O  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W498     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables    i CJ series Temperature Control Units    The section provides tables of the events that can occur in the following Units   CJ1W TC003  CJ1W TC004  CJ1W TC103  CJ1W TC104    p Level    04680000 hex   ColdJunction   An error occurred in le Faulty connection to the cold CJ series  Sensor Error   the cold junction junction sensor  Temperature  sensor  e The cold junction sensor failed  Control Units   Operation  Manual for NJ   series CPU  Unit  Cat  No   W49
157. l Instructions  flow   Circular Interpolation Setting Out of Motion Control Instructions  Range   Auxiliary Slave Axis Numbers Notin   Motion Control Instructions  Ascending Order   Cam Table Property Ascending Data   Motion Control Instructions  Error at Update    MC_Write Target Out of Range Motion Control Instructions    Master Travel Distance Specification   Motion Control Instructions  Out of Range   Master Distance in Acceleration Motion Control Instructions  Specification Out of Range   Master Distance in Deceleration Motion Control Instructions  Specification Out of Range    Immediate Stop Instruction Executed   General Motion Control    Axes Group Immediate Stop Instruc    General Motion Control  tion Executed    Permitted Following Error Out of Motion Control Instructions  Range    Execution Mode Selection Out of Motion Control Instructions   Range   Border Point Center Position Radius   Motion Control Instructions  Specification Out of Range    End Point Specification Out of Range   Motion Control Instructions    Slave Travel Distance Specification Motion Control Instructions  Out of Range    Phase Shift Amount Out of Range Motion Control Instructions    Feeding Distance Out of Range Motion Control Instructions  Auxiliary and Slave Defined as Game   Motion Control Instructions  Axis    Relative Position Selection Out of Motion Control Instructions    Range    Cam Transition Specification Out of Motion Control Instructions    Range    Synchronized Control End Mode M
158. ller     No    Are the USB cable and  Ethernet cables  connected properly     Yes    Yes               Can the Sysmac Studio  go online with CPU Unit     Set the connection method to a remote USB  connection in the Communications Setup of  Is the connection method set the Sysmac Studio  Set the destination IP  to a remote USB connection address for a remote USB connection or   in the Communications Setup Ethernet hub connection in the Communica   of the Sysmac Studio  tions Setup of the Sysmac Studio             Can the Sysmac Studio  go online with CPU Unit                  Is the destination a  iP address for a remote USB Correct the destination IP address fora    connection or Ethernet hub connection remote USB connection or Ethernet hub  in the Communications Setup of the connection in the Communications Setup of  Sysmac Studio set correctly and is the the Sysmac Studio  Correct the IP address  IP address set correctly in the setting in the destination Controller     destination Controller         Can the Sysmac Studio  go online with CPU Unit     Install the USB driver  Refer to the  Dee appendices of Sysmac Studio Version 1  Is the USB driver installed Operation Manual  Cat  No  W504  for the  correctly  installation procedure for the USB driver        No Yes              Can the Sysmac Studio  go online with CPU Unit        Replace the USB cable  or the Ethernet cables  and Ethernet switches between the computer  and the Controller     2 16 NJ series Troubleshooting Ma
159. lowing Units   CJ1W AD041 V1 AD081 V1  CJ1W AD042  CJ1W DA021 DA041  CJ1W DA08V DA08C  CJ1W DA042V  CJ1W MAD42    p Level    04600000 hex   A D Conver    Anerroroccurredin      There is a source of noise CJ series  sion Error A D conversion  nearby  Analog I O  A D converter failed  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W490     04620000 hex   Non volatile An error occurred in There is a source of noise y Same as  Memory non volatile mem  nearby  above   Error ory  Non volatile memory failed     34800000 hex   Mean Value   There is a mistake There is a mistake in the setting d Same as  Processing in the setting of the of the number of samplings for above   Setting Error   number of sam  mean value processing   plings for mean  value processing     3 56       NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O        34830000 hex   Scaling Data   There is a mistake     The upper or lower limit data for CJ series  Setting Error   in the scaling data scaling is outside the setting Analog UC  settings  range  Or  the maximum value Units Opera   and minimum value are not 0 tion Manual for  and they are the same  NJ series  CPU Unit  Cat   No  W490  Ce   34840000 hex   Input Signal   There is a mistake  e The settings of the input signal Same as m  Range Set  in the input signal range or the setting of the num  above  S  ting Emor or   range setting or in ber of analog inputs that are o  Error in Num    the number of used is incorrect  g  b
160. lute  Encoder Cur   rent Position  Calculation  Failed    Home Unde   fined during   Coordinated  Motion    The error between  the command cur   rent position and  actual current value  exceeded the Fol   lowing Error Over  Limit Value     The immediate stop  input turned ON     The positive limit  input turned ON     The negative limit  input turned ON     The difference  between the com   mand position and  the actual current  position exceeds  the range of 30 bit  data when con   verted to pulses     The Servo was  turned OFF for an  axis due to an axes  group error     It was not possible  to correctly restore  the current position  from the absolute  encoder information  that was saved  when power was  interrupted     Home of the logical  axis became unde   fined during axes  group motion or  while decelerating  to a stop     poor following performance and  the actual motion is slower than  the command     An immediate stop input signal  was detected     The immediate stop input signal  is not connected correctly or  the logic setting for the immedi   ate stop input is wrong     A positive limit input signal was  detected    The positive limit input signal is  not connected correctly or the  logic setting for the positive limit  input is wrong     A negative limit input signal was  detected    The negative limit input signal is  not connected correctly or the  logic setting for the negative  limit input is wrong     The command current position  was restricted so that th
161. n     An instruction was exe   cuted when there was a  setting error in the local IP  address     The UDP or TCP port was  already in use when the  instruction was executed     Address resolution failed  for a remote node with the  domain name that was  specified in the instruction     More than 32 EtherCAT communications  instructions were executed at the same  time  The EtherCAT communications  instructions are listed below     e EC_CoESDOWrite instruction  EC_CoESDORead instruction  EC_ConnectSlave instruction  EC_DisconnectSlave instruction  EC_StartMon instruction  EC_SaveMon instruction  EC_StopMon instruction  EC_CopyMon instruction    Depends on the nature of the error     The format of the route path that is specified  for a CIP communications instruction is not  correct     The handle that is specified for the CIP com   munications instruction is not correct     More than 32 CIP communications instruc   tions were executed at the same time     An attempt was made to use more than 32  handles at the same time     A device does not exist for the specified IP  address     The CIP connection for the specified handle  timed out and was closed     Power to the remote device is OFF     Communications are stopped at the remote  device     The Ethernet cable connector for Ether   Net IP is disconnected     The Ethernet cable for EtherNet IP is dis   connected     Noise    An instruction was executed when there  was a setting error in the local IP address     The UDP or TCP p
162. n electrical engineer or the equivalent      e Personnel in charge of introducing FA systems    e Personnel in charge of designing FA systems    e Personnel in charge of installing and maintaining FA systems   e Personnel in charge of managing FA systems and facilities     For programming  this manual is intended for personnel who understand the programming language  specifications in international standard IEC 61131 3 or Japanese standard JIS B3503     Applicable Products    This manual covers the following products   e NJ series CPU Units   e NJ501 1300   e NJ501 1400   e NJ501 1500    NJ series Troubleshooting Manual  W503  1    Relevant Manuals    Relevant Manuals       There are three manuals that provide basic information on the NJ series CPU Units  the NU series CPU  Unit Hardware User s Manual  the NJ series CPU Unit Software User   s Manual  this manual   and the  NJ series Instructions Reference Manual    Most operations are performed from the Sysmac Studio Automation Software  Refer to the Sysmac Stu   dio Version 1 Operation Manual  Cat  No  W504  for information on the Sysmac Studio    Other manuals are necessary for specific system configurations and applications    Read all of the manuals that are relevant to your system configuration and application to make the most  of the NJ series CPU Unit     NJ series User   s Manuals  Basic information    EE  fo   Setting devices and hardware    Software settings  Using EtherCAT    NJ series CPU Unit   Hardware User   s 
163. n using  an absolute encoder for semi   closed control     A forced brake operation  request was sent while the  Servo was ON     A Switch ON command was    tors Servo  Drives G5  Series with  Built in Ether   CAT Commu   nications  User s Man   ual  Cat  No     sent when the main power was 1576     OFF   When 3508 hex   0     An Enable Operation com   mand was sent to request turn   ing ON the Servo when the  Servomotor was operating at  30 r min or higher     A latch operation was started  under the following conditions     eAn absolute external encoder  was used and phase Z was  selected as the trigger for  fully closed control     eThe absolute multi rotation  data was being cleared or the  Config operation was being  performed     eThe Statusword  6041 hex  bit  09  remote  was 0  local      An operation command is given  in the prohibited direction after  the motor made an immediate  stop due to a drive prohibition  input     OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       SOAR S LYOJOUIF U  S1013 9           84B00000 hex   EtherCAT An EtherCAT com  The EtherCAT communications Same as  Communica    munications error cable is disconnected or bro  above   tions Warn  occurred one or ken   ing more times  e Noise    j MX2 series Inverters with EtherCAT Communications Units  vent coqe ssumed cause ren  a Tae    04A10000 hex   Non volatile   Anerroroccurredin Te Non volatile memory failure MX2 Series  Memory non volatile mem  Inverter Ether   Hardware ory  C
164. n was executed  Instructions  instruction was executed or   e A directory contained another directory Reference  when an attempt was made   when an attempt was made to change the   Manual  Cat   to change the directory directory name  No  W502   name  W  16 1409 That File Name An instruction could not be   e A file already exists with the same name as   Same as 2  Already Exists executed because the file the name specified for the instruction to cre    above  D  name specified for the ate  c  instruction already exists     16 140A Write Access An attempt was made to e The file or directory specified for the instruc    Same as Se  Denied write to a write protected tion to write is write protected  above  3  file or directory when an 2  instruction was executed     16 140B Too Many Files The maximum number of e The maximum number of open files was Same as j  Open open files was exceeded exceeded when opening a file for an instruc    above   when opening a file for an tion   instruction   16 140C Directory Does Not   The directory specified for      The directory specified for an instruction Same as  Exist an instruction does not does not exist  above  Ge  exist  e  16 140D File or Directory The file name or directory e The file name or directory name that was Same as 7  Name Is Too Long   name that was specified for specified for the instruction to create is too   above  a  an instruction is too long  long  E  16 140E SD Memory Card   SD Memory Card access e The SD Memory Card 
165. na that is  connected     The V680 HO01 or V680 H01 V2  was connected to the CJU1W   V680C 12     The user program specifies  addresses in the DM  CIO  AR   EM  or other areas that exceed  the ranges defined for the data  storage area specifications     The address of an ID Tag spec   ified in a command is incorrect     The specified address or num   ber of bytes is incorrect     Write protection is enabled for  the area you attempted to write  to in the ID Tag     The contents of the following  external device variables is not  data that can be specified   where   is the channel num   ber       Ch _CmdSet     Ch _ProcAdr     Ch _ProcByte     Ch _CmdOption        in the variable name is the  Antenna  Head  number     A processing error occurred     The travel speed of the ID Tag  is outside the specified range     The distance between the  Antenna and ID Tag is outside  the specified range     Noise    The travel speed of the ID Tag  is outside the specified range     The distance between the  Antenna and ID Tag is outside  the specified range     Noise    The communications specifica   tion is set to trigger  and the ID  Tag is not in the communica   tions area when the trigger  occurs    The communications specifica   tion is set to single auto or  repeat auto  and the wait time  reached the Auto Wait Time   An Amplifier is connected  but  an Antenna is not connected     System error 1 occurred        p Level O     a aee ee    CJ series ID  Sensor Units  Operation  Manual f
166. ncludes an axis with no defined 2  home  D  54670000 hex   Motion Con    An attempt was A parameter for an input vari  Same as  trol Instruc  made to change the able that cannot be changed for above   tion Re  Reference Type re execution was changed   execution input variable when  Disabled re executing a   Position motion control  Type  instruction   This  input variable can   not be changed  when re executing  an instruction    54680000 hex   Unused Axis   The master axis The master axis specified for a Same as  Specification   specified for a motion control instruction is an above   for Master motion control unused axis   Axis instruction is an  unused axis   54690000 hex   First Position   The parameter Instruction input parameter Same as  Setting Out of   specified for the exceeded the valid range of the above   Range FirstPosition input input variable   variable to a motion  control instruction is  out of range   546A0000 hex   Last Position   The parameter Instruction input parameter Same as  Setting Out of   specified for the exceeded the valid range of the above   Range LastPosition input input variable   variable to a motion  control instruction is  out of range   NJ series Troubleshooting Manual  W503  3 27    3 Error Tables    546B0000 hex   Illegal  First Last  Position Size  Relationship   Linear  Mode     546C0000 hex   Master Sync  Start Posi   tion Setting  Out of Range    546D0000 hex   Slave Sync  Start Posi   tion Setting  Out of Range    546E0000 hex   Du
167. ncy  Message  Detected    EtherCAT  Message  Error    The EtherCAT net   work configuration  is incorrect     A slave that is in the  network configura   tion information is  not connected  Or   a Slave that is not in  the network config   uration information  is connected     Slave initialization  failed     An error occurred in  the slave applica   tion     Sending process  data failed     Process data  reception timed out     An error occurred in  process data com   munications     An emergency  message was  detected     An error occurred in  a message commu   nications with the  slave     e Slave output ports are con   nected to each other     The master and slave are con   nected with the slave output  port     The number of connected  slaves exceeded the maximum  number of slaves  192 nodes   for the EtherCAT master     A slave that is in the network  configuration information is not  connected    There is a node address mis   match    A different slave from the one  that is specified in the network  configuration information is  connected    A slave that is not in the net   work configuration information  is connected    The Ethernet physical layer is  broken between two slaves     An error occurred in EtherCAT  master processing    An initialization error occurred  in the EtherCAT slave     An error was detected in the  slave   s application layer status  register     It was not possible to send the  EtherCAT frame during the  EtherCAT communications  period     The f
168. nderstand this Manual    Disclaimers    CHANGE IN SPECIFICATIONS    Product specifications and accessories may be changed at any time based on improvements and other  reasons     It is our practice to change model numbers when published ratings or features are changed  or when  significant construction changes are made  However  some specifications of the products may be changed  without any notice  When in doubt  special model numbers may be assigned to fix or establish key  specifications for your application on your request  Please consult with your OMRON representative at any  time to confirm actual specifications of purchased products     DIMENSIONS AND WEIGHTS  Dimensions and weights are nominal and are not to be used for manufacturing purposes  even when  tolerances are shown     PERFORMANCE DATA    Performance data given in this manual is provided as a guide for the user in determining suitability and does  not constitute a warranty  It may represent the result of OMRON s test conditions  and the users must  correlate it to actual application requirements  Actual performance is subject to the OMRON Warranty and  Limitations of Liability     ERRORS AND OMISSIONS    The information in this manual has been carefully checked and is believed to be accurate  however  no  responsibility is assumed for clerical  typographical  or proofreading errors  or omissions        NJ series Troubleshooting Manual  W503  13    Read and Understand this Manual    14    NJ series Troublesho
169. ng closed     e Aconnection is already established for  this instruction for the same IP address  and TCP port     SktTCPConnect Instruction    e The TCP port that is specified with the  SrcTcpPort input variable is already open     e The remote node that is specified with  DstAdr input variable does not exist     e The remote node that is specified with  DstAdr and DstTcpPort input variables is  not waiting for a connection     SktTCPRcv Instruction   e The specified socket is receiving data   e The specified socket is not connected   SktTCPSend Instruction   e The specified socket is sending data   e The specified socket is not connected     Same as  above     There is a BOOTP server setting error   The BOOTP server does not exist    The local IP address is not set because  operation just started     Same as  above     SktTCPAccept instruction  There was no  request for a connection from the remote  node during the user set timeout time   SktTCPRcev or SktUDPRcv instruction  Data  was not received from the remote node dur   ing the user set timeout time     Same as  above     The handle that is specified for the socket  service instruction is not correct     Same as  above     More than 32 socket service communica   tions instructions were executed at the  same time     An attempt was made to use more than 16  socket handles at the same time     3 95    KN  oo      m  mp     c  O     O  5  m        O     D   o  D       SOT 1013 GE    3 Error Tables    3 96 NJ series Trouble
170. nged for  re execution was changed     e A parameter for an input vari   able that cannot be changed for  re execution was changed     e An input variable that cannot be  changed for re execution was    changed     e A parameter for an input vari   able that cannot be changed for  re execution was changed          Level O     NJ series Troubleshooting Manual  W503     Reference    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     3 Error Tables       Level O     54570000 hex    54580000 hex    54590000 hex    545A0000 hex    545B0000 hex    Motion Con   trol Instruc   tion Re   execution  Disabled   Axes Group  Specification     Motion Con   trol Instruc   tion Re   execution  Disabled   Jerk Setting     Motion Con   trol Instruc   tion Re   execution  Disabled   Master Axis     Motion Con   trol Instruc   tion Re   execution  Disabled   MasterOff   set     Motion Con   trol Instruc   tion Re   execution  Disabled   MasterScal     ing     An attempt was  made to change the  parameter for the  AxesGroup input  variable when re   executing a motion  control instruction    This input variable  cannot be changed  when re executing  an instruction      An attempt was  made to change the  parameter for the  Jerk input variable  when re executing  a motion control  instruction   This  input variable can   not be changed  when re executing  an instruction  
171. nit Hardware User s Manual  Cat  No   W500  and NJ series CPU Unit Software User s  Manual  Cat  No  W501      Information on the built in EtherNet IP port is  provided  Information is provided on the basic  setup  tag data links  and other features    Use this manual together with the NJU series  CPU Unit Hardware User s Manual  Cat  No   W500  and NJ series CPU Unit Software User s  Manual  Cat  No  W501      Concepts on managing errors that may be  detected in an NJ series Controller and informa   tion on individual errors are described    Use this manual together with the NJ series  CPU Unit Hardware User s Manual  Cat  No   W500  and NJ series CPU Unit Software User s  Manual  Cat  No  W501      Describes the operating procedures of the Sys   mac Studio     Describes operating procedures for the CX Inte   grator     Describes operating procedures for the CX   Designer     Describes operating procedures for the CX Pro   tocol     Provides the specifications of and describes  application methods for GX series EtherCAT  Slave Units     Describes the following information for the  3G3AX MX2 ECT EtherCAT Communications  Unit for an MX2 series Inverters  installation   parameter settings required for operation  trou   bleshooting  and inspection methods     Describes the following information for the G5   series AC Servomotors Servo Drives with Ether   CAT Communications  installation  wiring meth   ods  parameter settings required for operation   troubleshooting  and inspecti
172. nitialized G5 series Servo Drives with Built in 1576  EtherCAT Communications    Wi  N  m   lt   OD   gt   mr       5  O     Q   OD     O  mb  m   lt        gt   mp  O  O  Q   ui            SOT 1013   t    NJ series Troubleshooting Manual  W503  3 89    3 Error Tables    3 3    3 3 1    Instruction Error Table    This section provides a table of errors that occur for instructions  Notification is not provided for errors  that occur for instructions other than motion control instructions     Notification is provided for errors that occur in motion control instructions  Refer to 3 1 3 Errors in the  Motion Control Function Module     Interpreting Error Descriptions    The contents of the error tables are described below     Hem    Error code    Name  Meaning  Cause  Reference    Description    The code of the error that occurs for the instruction is given  The codes are given in    four hexadecimal digits     The name of the error is given     A short description of the error code is given     The assumed cause of the error is given    The name and catalog number of the manual that provides details on the error are    given     Refer to the manual given in the Reference column in the table for detailed information on an error     3 3 2 Error Table    Event code  16 0400 Input Value Out of  Range  16 0401 Input Mismatch  16 0402 Floating point Dec   imal Error  16 0403 BCD Error    3 90    An input parameter for an  instruction exceeded the  valid range for an input vari   able 
173. ns  Events that are not errors are also given in the tables     Interpreting Error Descriptions    The contents of the error tables are described below     Item Description  Event code The event code of the error in the NJU series Controller is given  The codes are  given in eight hexadecimal digits   Event name The name of the error is given  Meaning A short description of the error is given   Assumed cause The assumed cause of the error is given  Level The level of influence on control is given  The following abbreviations are used    and the applicable level is indicated in the tables   Maj  Major fault level   Prt  Partial fault level   Min  Minor fault level   Obs  Observation   Info  Information    Reference The name and catalog number of the manual that provides details on the event  are given     Refer to the manual given in the Reference column in the tables for detailed information on an error     3 1 2 Errors in the PLC Function Module    The section provides tables of the events that can occur in the PLC Function Module  They are divided  into the following functional classifications     e Self diagnosis   e Unit configuration   e Tasks   e Controller operation  e FINS communications    NJ series Troubleshooting Manual  W503     3 Error Tables    j Errors for Self Diagnosis  sos  eon  ote  meee Ceara  om       00090000 hex   DIP Switch An error was e There is an error in the DIP NJ series  Setting Error   detected in the DIP switch setting  CPU Unit  switch settin
174. ntroller error will occur and  a    Safe Mode    event is recorded in the event log  Refer to 1 3 7 Types of Non fatal Errors for infor   mation on operation for a major fault level Controller error     2 20 NJ series Troubleshooting Manual  W503        Error Tables  E    This section lists all of the errors  events  that can occur on NJ series Controllers        3 1    Errors DY SOUC Ge ve Ad wh oes we eae Saree hee a 3 2  3 1 1 Interpreting Error Descriptions           0 0    ee 3 2  3 1 2 Errors in the PLC Function Module             0 0    00  cee eee 3 2  3 1 3 Errors in the Motion Control Function Module                  0 0006  3 10  3 1 4 Errors in the EtherNet IP Function Module    3 35  3 1 5 Errors in the EtherCAT Master Function Module                        3 39  3 1 6 Errors in EtherCAl Slaves EE 3 42  3 1 7 Errors in CJ series UNS  seus se nce eee ge ee ee wes Ss ea ee 3 56   3 2 Events in Order of Event Codes            00  cee ees 3 73  3 2 1 Interpreting Error Descriptions          0   0    ccc eee ee ee 3 73  3 2 2 ee 3 73   3 3 Instruction Error Table ses  aid edhe teat ae ea E ee ee ae 3 90  3 3 1 Interpreting Error Descriptions 3004 vs cn devon dee exe eer eyewear aes 3 90  3 3 2 ORO  Ae os dn te Gace al hee GS ee ee 3 90    NJ series Troubleshooting Manual  W503     3 1       3 Error Tables    3 1    Errors by Source    3 1 1    This section provides tables of errors  events  by source  Within each source  errors are given by func   tional classificatio
175. nual  W503     2 Error Troubleshooting Methods       Direct Connection with EtherNet IP Port    Sysmac Studio cannot  connect to CPU Unit           Is power supplied to the Controller        No  Turn ON the power supply to the Controller     No       Yes    OF JOUURD nog uayM BulooyusealqnolL v z    oppe dewWsAS   y  UO sUl UO       Can the Sysmac Studio  go online with CPU Unit        Insert the cable connectors at the personal   No computer  Ethernet switches  and the  Controller until they lock into place  Verify  that the link indicator is lit at the computer  and Ethernet switches  and the LINK ACT  indicator is lit at the Controller        Is the Ethernet cable  connected properly        Yes       No Yes        Can the Sysmac Studio  go online with CPU Unit          Is the connection method set to Set the connection method to a direct   a direct Ethernet connection in Ethernet connection in the Communications  the Communications Setup of Setup of the Sysmac Studio    the Sysmac Studio            Ge  KN  NO      O  C  2  D  KA  a gt   Q  O  CT       Q  si     m  pe   Q  a gt        pe   Cc  KA   O        Can the Sysmac Studio  go online with CPU Unit          Set the IP address for the personal  Is the same IP address set computer  Use the default IP address for  for more than one node the Controller or connect the Sysmac   computer or Controller  in Studio to the Controller with a USB cable  the same domain  and set the required IP address             Yes       Can the 
176. of the  protocol data from the CX Pro   tocol   The Serial Communications  Unit failed   34A40000 hex   System There is an error in There is an error in the system Same as  Setup Error the system settings settings for the Serial Commu  above   for the Serial Com  nications Unit   munications Unit   04750000 hex   DTR Check An error was found Loopback test jig failure  Same as  Error during the DTR Noise above   check  The communications circuits in  the Serial Communications Unit  are faulty   04760000 hex   CTS Check An error was found Loopback test jig failure  Same as  Error during the CTS Noise above   check  The communications circuits in  the Serial Communications Unit  are faulty   54A80000 hex   Command A command error The constant in the expected Same as  Error occurred  receive message that is set in above   the protocol macro is different  from the constant in the mes   sage that was received   54A90000 hex   Sequence The sequence was The protocol macro data is not Same as  Abort Com  ended by an Abort set correctly  above     3 62    pleted    setting for the next  processing or error  processing     The baud rate  frame format  or  other system setting does not  agree with the remote node        NJ series Troubleshooting Manual  W503     e Sequence No  Error  An unreg     54AA0000 hex    64A00000 hex    64A10000 hex    64A20000 hex    Protocol  Macro Error    Tfs  Send  Finished  Monitoring  Time   Exceeded    Tfr  Receive  Finished  Monitoring  Time   Exceeded  
177. oller  errors    Resetting Controller  errors with CIP mes   sages    Resetting all errors  for all function mod   ules    Resetting all errors  for a specific func   tion module    Resetting all errors  for all function mod   ules    Resetting errors for  individual function  modules    Resetting all errors  for all function mod   ules    Resets all errors        Reset the Controller errors from the Sys   mac Studio   s Troubleshooting Dialog Box     After the causes of the Controller errors are  removed  all Controller errors in the relevant  function module are reset as a result  Errors  are not reset when you download the Con   troller Configurations and Setup     After the causes of the Controller errors are  removed  all Controller errors in all function  modules are reset as a result     After the causes of the Controller errors are  removed  all Controller errors in all function  modules are reset as a result     Reset Controller errors from the Trouble   shooter of an NS series PT that is compati   ble with NJ series Controllers     You can reset errors from a PT that is not  directly compatible with the NJ series Con   troller or another company   s HMI if you use  the PT HMI in combination with the reset  error instruction for the function module in  the user program     Execute the reset error instruction for the  function module in the user program     e For the Motion Control Function Module   you can reset all errors  errors for a par   ticular axis  or errors 
178. oller error status for each function mod    ables ule     This section describes the above checking methods     H Checking the Indicators       Checking the Level of a Controller Error    You can use the PWR indicator on the Power Supply Unit and the RUN and ERROR indicators on  the CPU Unit to determine the level of an error  The following table shows the relationship between  the Controllers indicators and the event level     Indicators    PWR  green  RUN  green  ERROR  red   Lit Major fault level    Lit Lit Flashing Partial fault level   1 s intervals   Minor fault level    E Observation    Event level    NJ series Troubleshooting Manual  W503  1 11       h  I  Ai  Z  O   gt   A  D  mp  CH  m        O               S104113 ISISL UON 104 Buryoeuy Z     4    1 Overview of Errors       Checking Errors in the EtherCAT Master Function Module and EtherNet IP  Function Module    For the EtherCAT Master Function Module and EtherNet IP Function Module  use the EtherCAT and  EtherNet IP NET ERR indicators to determine whether a minor fault level error or higher level error  has occurred  The indicators let you check the status given in the following table     Indicators Indicated status  EtherCAT EtherCAT Master Function Module Status  NET ERR e Lit  Errors for which normal status cannot be recovered through user actions  i e   errors    for which you must replace the CPU Unit or contact your OMRON representative    e Flashing  Errors for which normal status can be recovered through
179. on Failed error   6458000 hex  was detected for  the auxiliary axis of a synchro   nized instruction     A communications error  occurred for the EtherCAT slave  that is allocated to an axis     Performance of positioning  operation is poor and the actual  motion is slower than the com   mand     The command velocity  exceeded the velocity warning  value     The command acceleration rate  exceeded the acceleration  warning value     The command deceleration rate  exceeded the deceleration  warning value     The torque command value  exceeded the positive torque  warning value     The torque command value  exceeded the negative torque  warning value     In Linear Mode  the command  position when converted to  pulses exceeded the upper limit  of signed 40 bit data           weal O     a ee    NJ series  CPU Unit  Motion Con   trol User   s  Manual  Cat   No  W507     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     The number of  pulses for the com   mand position  exceeded the valid  range   It under   flowed      64530000 hex    64540000 hex    64550000 hex    74320000 hex    743C0000 hex    94200000 hex    94210000 hex    94220000 hex    Command  Position  Underflow    Actual Posi   tion Overflow    Actual Posi   tion Under   flow    Slave Obser   vation  Detected    Cannot Exe   cute Save  Cam Table  Instruction
180. on Module    Operation stops     EtherCAT Master  Function Module    Operation stops     EtherNet IP Func   tion Module    Partial fault level    All axes stop   The  stop method  depends on the  error      EtherCAT commu   nications stop     EtherNet IP com   munications stop    A software con   nection from the  Sysmac Studio or  an NS series PT is  not possible         Minor fault level       Operation continues     The affected  axes axes group  stops   The stop  method depends  on the settings      The motion con   trol instruction is  not executed  for  instructions  related to axis  operation      EtherCAT commu   nications stop or  continue according  to the setting of the  fail soft operation in  the master     Part of the Ether   Net IP communica   tions stop   A  software connec   tion from the Sys   mac Studio or an  NS series PT is  possible if the com   munications con   nection is not the  cause of the error         UO Operation for Major Fault Level Controller Errors  e The following table gives the operation for the following errors     e Unsupported Unit Detected  e I O Bus Check Error  e End Cover Missing    e Incorrect Unit Expansion Rack Connection    e Duplicate Unit Number  e Too Many I O Points  e   O Setting Check Error    Unit  EtherCAT slaves    CJ series Basic I O Units    CJ series Special Units    CPU Unit operation    The slave operates in Safe Opera   tional state  tings        Refreshing stops     Refreshing stops     e All outputs are turned 
181. on methods     25    Revision History    Revision History       A manual revision code appears as a suffix to the catalog number on the front and back covers of the    Cat  No    W503 E1 01          Revision code    Revision code   Date Revised content  01 July 2011 Original production    26 NJ series Troubleshooting Manual  W503        Overview of Errors  EES    This section provides information that is required to troubleshoot errors  It introduces  the types of errors that can occur on an NU series Controller  the operation that occurs  in response to errors  and the methods you can use to check for errors  Refer to Sec   tion 2 Error Troubleshooting Methods for information on troubleshooting errors        1 1 Overview of NJ series Errors          00 00  eee es 1 2  1 1 1 THES OL SE Sint ih oS ele eee e4 ey eee base ee ee eet ae 1 2  dee EE Eed ie ee   tt ee Ae athe aes teats A ete ee a has 1 3  des  Fatal Errors ee heh earn e Pee a eee 1 4  1 2 1 ypes of Fatal ENOS aos 4 cease eres ca eee se ee a eee eee EEN 1 4  1 2 2 Checking for Fatal Errors        0 0 0    cc ees 1 4  Jeck  epes  Errors camerae iadGe eet 1 5  1 3 1 Types of Non fatal Errors    0 20    0  ccc eee 1 5  1 3 2 Checking for Non fatal Errors    1 11  1 3 3 Resetting Non fatal org    1 13    NJ series Troubleshooting Manual  W503  1 1       1 Overview of Errors    1 1 Overview of NJ series Errors    You manage all of the errors that occur on the NJ series Controller as events  The same methods are  used for 
182. ons W508  Same Axis   Master Slave Axis Numbers Not in Motion Control Instructions W508  Ascending Order    Incorrect Cam Table Specification Motion Control Instructions W508    NJ series Troubleshooting Manual  W503     3 Error Tables    Event code   Eventname     Functional classification Reference  543A0000 hex Synchronization Stopped Motion Control Instructions W508    543B0000 hex Motion Control Instruction Re execu    Motion Control Instructions W508  tion Disabled    543C0000 hex Motion Control Instruction Multi exe    Motion Control Instructions W508  cution Disabled   543D0000 hex Instruction Not Allowed for Encoder Motion Control Instructions W508  Axis Type   543E0000 hex Instruction Cannot Be Executed dur    Motion Control Instructions W508  ing Multi axes Coordinated Control    543F0000 hex Multi axes Coordinated Control Motion Control Instructions W508  Instruction Executed for Disabled  Axes Group    54400000 hex Axes Group Cannot Be Enabled Motion Control Instructions W508    54410000 hex Impossible Axis Operation Specified   Motion Control Instructions W508  when the Servo is OFF    54420000 hex Composition Axis Stopped Error Motion Control Instructions W508    54430000 hex Motion Control Instruction Multi exe    Motion Control Instructions W508  cution Buffer Limit Exceeded    54440000 hex Insufficient Travel Distance Motion Control Instructions W508    54450000 hex Insufficient Travel Distance to Achieve   Motion Control Instructions W508  Blending Transit 
183. ontrol W507  Detected   Homing Limit Inputs Detected in Both   General Motion Control W507  Directions   Home Proximity Homing Opposite General Motion Control W507  Direction Limit Input Detected   Home Proximity Homing Direction General Motion Control W507  Limit Input Detected   Home Input Homing Opposite Direc    General Motion Control W507  tion Limit Input Detected   Home Input Homing Direction Limit General Motion Control W507  Input Detected    ve  waor  waor  W507  wee  W507  waor  W507    NJ series Troubleshooting Manual  W503     3 Error Tables    Event code Event name Functional classification Reference    74350000 hex Latch Position Underflow General Motion Control W507  74360000 hex Master Sync Direction Error General Motion Control W507    74370000 hex Slave Disconnection during Servo ON   General Motion Control W507  74380000 hex Feed Distance Overflow General Motion Control W507    74390000 hex Error in Changing Servo Drive Con    General Motion Control W507  trol Mode    743A0000 hex Master Axis Position Read Error General Motion Control W507  743B0000 hex Auxiliary Axis Position Read Error General Motion Control W507    743C0000 hex Cannot Execute Save Cam Table General Motion Control W507  Instruction    74600000 hex Master Function Enable Disable CJ series DeviceNet Units W497  Failed   74610000 hex Master Fixed Allocation Area Setting   CJ series DeviceNet Units W497  Failed   74620000 hex Scan List Register Clear Failed CJ series DeviceNet Units W497   7
184. or NJ   series CPU  Unit  Cat  No   Z317     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables    p Level O     64910000 hex   Results Infor    ID system error 2 e System error 2 occurred  CJ series ID  mation  ID occurred  Sensor Units  System Error Operation  2 Manual for NJ   series CPU  Unit  Cat  No   Z317   64920000 hex   Results Infor    ID system error 3 System error 3 occurred  Same as  mation  ID occurred  above   System Error  3  64930000 hex   Results Infor    One of the following The number of writes was Same as  mation  ID occurred  exceeded for a Number of above   Tag Status e The number of Writes Control command   writes was An overflow or underflow  exceeded for a occurred for a Calculation Write  Number of Writes command   Control com  The data did not verify for a  mand  Data Check command   An overflow or An error occurred in the data for  underflow a Read with Error Correction  occurred for a command   Calculation Write An error occurred when writing  command  for a Copy command   The data did not  verify for a Data  Check command   An error occurred  in the data for a  Read with Error  Correction com   mand   An error occurred  when writing for a  Copy command   64940000 hex   Results Infor    A Write with Error e There is ambient noise where Same as  mation  Error   Correction 
185. or or limit  sensor is installed in the wrong  location     The contact logic of the home  input signal or limit signal is not  correct     The home input signal output  device or limit sensor failed     The wiring of the home input  signal or limit signal is incorrect     The home input sensor or limit  sensor is installed in the wrong  location     The contact logic of the home  input signal or limit signal is not  correct     The home input signal output  device or limit sensor failed     The set value of the home input  mask distance when the oper   ating mode of the MC_Home  instruction is set to Proximity  Reverse Turn Home Input Mask  Distance is insufficient to decel   erate from the homing velocity  to the homing approach veloc   ity    There was no home signal input  during the homing operation     A limit signal was detected  before there was a home input     There was no home proximity  signal input during the homing  operation when a home proxim   ity input signal was specified     An error was detected for the  EtherCAT slave that is allocated  to the axis     An error occurred for an axis in  an axes group that was in  motion        Partial fault level MC common  error occurred       Level O     a ee    NJ series  CPU Unit  Motion Con   trol User   s  Manual  Cat   No  W507     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  
186. ore than one I O Control Unit on the CPU Rack or there is an I O Control Unit on an  Expansion Rack        Incorrect Power Supply Unit Connected    There is a CJ series Power Supply Unit connected to the CPU Rack  The operation of the Controller  is stopped     CPU Unit Watchdog Timer Error    This error occurs in the CPU Unit  This error occurs when the watchdog timer times out because a  hardware failure or when temporary data corruption causes the CPU Unit to hang     1 2 2 Checking for Fatal Errors    You can identify fatal errors based on the status of the PWR indicator on the Power Supply Unit and the  RUN and ERROR indicators on the CPU Unit  as well as by the ability to go online with the CPU Unit  from the Sysmac Studio  Refer to Section 2 Error Troubleshooting Methods for information on identify   ing errors and corrections     Indicators Going online from    PWR  green  RUN  green  ERROR  red  the Sysmac Studio  Not lit Not lit Not lit Not possible   Power Supply Error  Lit Not lit Not lit CPU Unit Reset    Lit Flashing  8 s Lit Incorrect Power Supply Unit  intervals   Connected  Lit Not lit Lit CPU Unit Watchdog Timer  Error      Power Supply Errors and Incorrect Power Supply Unit Connected errors can be differentiated with the indicators   There is no need to see if you can go online with the CPU Unit from the Sysmac Studio     CPU Unit operating status    NJ series Troubleshooting Manual  W503     1 Overview of Errors    1 3 Non fatal Errors    Non fatal errors 
187. ormally and a request for the NTP above   and a request for server to obtain the time  the NTP server to started   obtain the time  started     940C0000 hex   SNMP The SNMP agent e The SNMP agent started nor  d Same as  Started started normally  mally  above        3 38 NJ series Troubleshooting Manual  W503     3 Error Tables    3 1 5 Errors in the EtherCAT Master Function Module    i Built in EtherCAT Master in CPU Unit  a          GA  10200000 hex   User Pro  The user program e The user program or Controller NJ series m  gram Con  or Controller Con  Configurations and Setup are CPU Unit S  troller figurations and not correct because the power Built in Ether     Configura  Setup were not supply to the Controller was CAT Port    tions and transferred cor  interrupted or communications User s Manual o  Setup Trans    rectly  with the Sysmac Studio were  Cat  No  5  fer Error disconnected during a down  W505  Ve  load of the user program or the  Controller Configurations and  Setup   The user program or Controller  Configurations and Setup are  not correct because the power EA  supply to the Controller was cn  interrupted during online edit  m  ing  S  The user program or Controller    Configurations and Setup are    not correct because the power E  supply to the Controller was S  interrupted during a Clear All e  Memory operation   gt   Non volatile memory failed     04400000 hex   Communica    An error was The CPU Unit has failed  Same as 7  tions Control    detected in the 
188. ort is already in use     The domain name specified for the instruc   tion is not correct     The hosts and DNS settings in the Control   ler are incorrect     The DNS server settings are incorrect        NJ series Troubleshooting Manual  W503     NJ series  Instructions  Reference  Manual  Cat   No  W502     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above        Event code   16 2003 Status Error   16 2004 Local IP Address  Not Set   16 2006 Socket Timeout   16 2007 Socket Handle Out  of Range   16 2008 Socket Communi     cations Resource  Overflow    NJ series Troubleshooting Manual  W503     The status was not suit   able for execution of the  instruction     The local IP address was  not set when a socket ser   vice instruction was exe   cuted     A timeout occurred for a  socket service instruction     The handle that is specified  for the socket service  instruction is not correct     The maximum resources  that you can use for socket  service instructions at the  same time was exceeded     3 Error Tables    e SktUDPRcv Instruction    NJ series  Instructions  Reference  Manual  Cat   No  W502     e The socket is receiving data   e The socket is not open   SktUDPSend Instruction   e The socket is sending data   e The socket is not open     SktTCPAccept Instruction  The specified TCP port is in one of the fol   lowing states     e The port is being opened   e The port is bei
189. oting Manual  W503     Safety Precautions    Safety Precautions       Definition of Precautionary Information    The following notation is used in this manual to provide precautions required to ensure safe usage of  the NJ series Controller  The safety precautions that are provided are extremely important to safety   Always read and heed the information provided in all safety precautions    The following notation is used    Refer to the following manuals for precautions for the safe use of the NJ series Controller    Installation precautions are also provided for the NJ series CPU Unit and the NJ series Controller sys   tem     e NJ series CPU Unit Hardware User   s Manual  W500   e NJ series CPU Unit Software Users Manual  W501     Indicates a potentially hazardous situation which  if not avoided   could result in death or serious injury  Additionally  there may be  severe property damage     Indicates a potentially hazardous situation which  if not avoided   may result in minor or moderate injury  or property damage        ED precautions for Safe Use    Indicates precautions on what to do and what not to do to ensure safe usage of the product     D Precautions for Correct Use  Indicates precautions on what to do and what not to do to ensure proper operation and performance     NJ series Troubleshooting Manual  W503  15    Safety Precautions    Symbols    16       The circle and slash symbol indicates operations that you must not do   The specific operation is shown in the c
190. otion Control Instructions  Selection Out of Range  Enable External Latch Instruction Motion Control Instructions    Execution Disabled    NJ series Troubleshooting Manual  W503     W508  W508    W507    W508  W508  W508    W508    W508    W508    W508    W508    W508    W508  W508    W508    W508    W507  W507    W508    W508    W508    W508  W508    W508  W508  W508    W508    W508    W508    W508    3 83    Wi  N  m   lt   OD   gt   mr       5  O     Q   OD     O  mb  m   lt        gt   mp  O  O  Q   ui            SOT 1013   t    3 Error Tables    3 84    Event code  54930000 hex  54940000 hex  54950000 hex    54960000 hex    54970000 hex    54980000 hex    54990000 hex    549A0000 hex    549B0000 hex    549C0000 hex    54A00000 hex    54A10000 hex    54A20000 hex  54A80000 hex    54A90000 hex    54AA0000 hex    54E00000 hex    60010000 hex    60020000 hex    60030000 hex    60040000 hex    60050000 hex  64010000 hex  64200000 hex  64400000 hex    64410000 hex    64420000 hex    64430000 hex  64440000 hex      Eventname     Functional classification Reference  Master Axis Offset Out of Range Motion Control Instructions W508  Slave Axis Offset Out of Range Motion Control Instructions W508    Command Current Position Count Motion Control Instructions W508  Selection Out of Range   Master Axis Gear Ratio Numerator Motion Control Instructions W508  Out of Range   Master Axis Gear Ratio Denominator   Motion Control Instructions W508  Out of Range   Auxiliary Axis Gear Ratio Num
191. plicate  Latch ID for  Trigger Input  Condition    546F0000 hex   Jerk Over   ride Factor  Out of Range    54700000 hex   Accelera   tion Deceler   ation  Override Fac   tor Out of  Range    54710000 hex   First Position  Method  Specification  Out of Range    3 28    The parameter  specified for the  LastPosition input  variable to a motion  control instruction is  smaller than the  parameter speci   fied for the FirstPo     sition input variable     The parameter  specified for the  MasterSyncPosi   tion input variable to  a motion control  instruction is out of  range     The parameter  specified for the  SlaveSyncPosition  input variable to a  motion control  instruction is out of  range     The same latch ID  was specified for  more than one  motion control  instruction     The parameter  specified for the  JerkFactor input  variable to a motion  control instruction is  out of range     The parameter  specified for the  AccFactor input  variable to a motion  control instruction is  out of range     The parameter  specified for the  StartMode input  variable to a motion  control instruction is  out of range     e The value of the LastPosition    input parameter is less than the  value of the FirstPosition input  variable for the instruction when  the Count Mode is set to Linear  Mode     Instruction input parameter  exceeded the valid range of the  input variable        Instruction input parameter  exceeded the valid range of the  input variable     The same latch ID is u
192. r CJ series DeviceNet Units W497   Slave User Allocation Area Setting CJ series DeviceNet Units W497   Failed   Data Setting Warning G5 series Servo Drives with Built in   1576  EtherCAT Communications   Servo Drive Overheat G5 series Servo Drives with Built in 1576  EtherCAT Communications    NJ series Troubleshooting Manual  W503        Event code  34E20000 hex    34E30000 hex    34E40000 hex    34E50000 hex    34E60000 hex    34F00000 hex    38010000 hex    38020000 hex  383C0000 hex    383D0000 hex    383E0000 hex    383F0000 hex    38400000 hex    38410000 hex    38420000 hex    38430000 hex    38440000 hex    38450000 hex    38460000 hex    38470000 hex    38480000 hex    38490000 hex    384A0000 hex    384B0000 hex    384C0000 hex    384D0000 hex    384E0000 hex    3 Error Tables      Eventname    _ Functional classification Reference    G5 series Servo Drives with Built in 1576  EtherCAT Communications    Overload    G5 series Servo Drives with Built in 1576  EtherCAT Communications    Regeneration Overload    G5 series Servo Drives with Built in 1576  EtherCAT Communications    Excessive Velocity Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   Overspeed G5 series Servo Drives with Built in   1576  EtherCAT Communications   PDO Setting Error MX2 series Inverters with EtherCAT  1574  Communications Units    Error Counter Overflow    Scaling Data Setting Error Ratio Con    CJ series Analog I O Units W490  version Use Setting Error    Ratio S
193. r Error        CPU Unit operating status          Fatal errors    ply Unit Connected 1          Partial fault 2    Ge ECH    Obeervation d    Lit Flashing Continues 2 cations can be con     1 s inter  nected from an NS    vals   series PT if Ether    Flashing Continues Net IP is operating  it        1 s inter  normally         vals     1 Refer to 1 2 Fatal Errors for information on individual errors    2 Refer to 1 3 Non fatal Errors for information on individual errors    3 The function module where the error occurred stops     NJ series Troubleshooting Manual  W503  1 3    ok   I  mmh   O   lt   OD               O   A     pa       OD      ui       m         e      Vu       SNES HUN NdO ect     1 Overview of Errors    1 2    Fatal Errors    1 2 1    Types of Fatal Errors    This section describes the errors that cause the operation of the NJ series CPU Unit to stop   Software connections to the Sysmac Studio or an NS series PT cannot be made if there is a fatal error  in the Controller        Power Supply Error    Power is not supplied  the voltage is outside of the allowed range  or the Power Supply Unit is faulty        CPU Unit Reset    The CPU Unit stopped operation because of a hardware error  Other than hardware failures  this  error also occurs at the following times   e The power supply to an Expansion Rack is OFF   e The I O Connecting Cable is incorrectly installed   e The IN and OUT connectors are reversed   e The connectors are not mated properly     e There is m
194. r Errors Tab in the Troubleshooting Window to read information on cur   rent errors in the Controller     The Controller Errors Tab Page lists the current errors in order of their levels     E35  Tr publeshooting  Controller Errors Controller Event Log User defined Errors User defined Event Log    Level   Source   Source Details   Event Name   Event Code        f Obu Mater   End Cover Missing  0x24030000  Partial fault EtherNet IP Communications port IP Address Duplication Error 0x84010000  Minor fault PLC Real Time Clock Stopped 0x00070000  Minor fault EtherNet IP Communications port DNS Server Connection Error 0x84030000    The End Cover is not connected to right end of the CPU Rack or an Expansion Rack  Cause    1  The End Cover is not connected to right end of the CPU Rack or an Expansion Rack    2  The End Cover is not connected properly        Display item Description   Level   This is the event level of the error    Source and Source Details This is the physical location and functional location of the error   Event Name Error name   Event Code This is the code of the error     You can click the column headings in the Controller error list  such as the Level or Source  to reorder  the table rows according to that heading  For example  the following change occurs when you click  the Source heading     Before Source heading is clicked     SS Troubleshooting E3   Controller Errors Controller Event Log User defined Errors User defined Event Log    Level   Soure   Source Det
195. r Status Error 4    G5 series Servo Drives with Built in 1576  EtherCAT Communications    External Encoder Status Error 5    G5 series Servo Drives with Built in 1576  EtherCAT Communications    Phase A Connection Error    G5 series Servo Drives with Built in 1576  EtherCAT Communications    Phase B Connection Error    G5 series Servo Drives with Built in 1576  EtherCAT Communications    Encoder Data Restoration Error G5 series Servo Drives with Built in 1576  EtherCAT Communications    Phase Z Connection Error    NJ series Troubleshooting Manual  W503     3 75    Wi  N  m   lt   OD   gt   mr       5  O     Q   OD     O  mb  m   lt        gt   mp  O  O  Q   ui            SOT 1013   t    3 Error Tables    3 76    Event code  08180000 hex    10010000 hex    10020000 hex  10030000 hex  10040000 hex    10060000 hex  10070000 hex    10080000 hex  10090000 hex  10200000 hex    10210000 hex    10230000 hex    10240000 hex    10250000 hex    10260000 hex    14010000 hex    14200000 hex  14210000 hex  14220000 hex  14400000 hex  14600000 hex    14610000 hex    14620000 hex  14630000 hex  14800000 hex    148C0000 hex  148D0000 hex  148E0000 hex  14A00000 hex    14A80000 hex    14A90000 hex    14AA0000 hex      Eventname     Functional classification Reference    External Encoder Data Restoration G5 series Servo Drives with Built in 1576  Error EtherCAT Communications    Non volatile Memory Restored or For    Errors for Self Diagnosis W500  matted    Non volatile Memory Data Corrupted  
196. r details on the instructions that get error status  refer to the NU series Instructions Reference Manual   Cat  No  W502      ff Checking with System defined Variables    You can check the Error Status variable in the system defined variables to determine the status of  errors in a Controller  You can read the Error Status variable from an external device by using communi   cations  Refer to the NJ series CPU Unit Software User s Manual  Cat  No  W501  for information on  system defined variables     sch  I   p  GA  J  d  H   O   a  J          O   gt   as  pa    r  2  m   x     O     wn    1 3 3 Resetting Non fatal Errors    Unless you reset an error  the CPU Unit will retain the error status until you turn OFF the power supply  to the Controller or reset the Controller     To reset a Controller error  it is necessary to eliminate the cause of the error  The same error will occur  again if you reset the error  but do not eliminate the cause of the error     Precautions for Safe Use    Always confirm safety at the connected equipment before you reset Controller errors with an  event level of partial fault or higher for the EtherCAT Master Function Module  When the error is  reset  all slaves that were in any state other than Operational state  in which outputs are dis   abled  due to the Controller error with an event level of partial fault or higher will go to Opera   tional state and the outputs will be enabled  Before you reset all errors  confirm that no Controller  error
197. r must be connected to the power supply line     Noise Filter  Manufacturer Model  Cosel Co   Ltd  TAH 06 683  Trademarks    e Sysmac and SYSMAC are trademarks or registered trademarks of OMRON Corporation in Japan  and other countries for OMRON factory automation products     e Windows  Windows 98  Windows XP  Windows Vista  and Windows 7 are registered trademarks of  Microsoft Corporation in the USA and other countries     e EtherCAT   is a registered trademark of Beckhoff Automation GmbH for their patented technology   e The SD logo is a trademark of SD 3C  LLC  SS P    Other company names and product names in this document are the trademarks or registered trade   marks of their respective companies        Software Licenses and Copyrights    This product incorporates certain third party software  The license and copyright information associ   ated with this software is available at http   www fa omron co jp nj_info_e      20 NJ series Troubleshooting Manual  W503     Unit Versions    Unit Versions       Unit Versions  A    unit version    has been introduced to manage CPU Units in the NJ Series according to differences in  functionality accompanying Unit upgrades   i Notation of Unit Versions on Products    The unit version is given on the ID information label of the products for which unit versions are man   aged  as shown below     Example for NJ series NJ501 OUULI CPU Unit          R ID information label    Unit model Unit version    i NJ501  1500 1 Dei   PORT1 MAC ADDR
198. rCAT Error    ResetECError Resets current Controller errors from the EtherCAT Mas     ter Function Module   Refer to the NJU series Instructions Reference Manual  Cat  No  W502  for details on these instructions     NJ series Troubleshooting Manual  W503     2 Error Troubleshooting Methods    2 3 4 Checking for Errors with System defined Variables    The system defined variables include an Error Status variable  which shows the error status  The fol   lowing diagram shows the structure of this variable  The system determines the error status of each  level by logically ORing the error status information of the next lower level  You can read the Error Sta   tus variable from an external device through communications  Refer to the NJ series CPU Unit Soft   ware User   s Manual  Cat  No  W501  for information on system defined variables     Level 1 Level 2 Level 3 Level 4          T  oo     o     o  D  o     O  O     5         O  5  A  D  mp  CH  m        O     oO    Error Status variable  for the entire Controller     _PLC_ErrSta   Error status variable for PLC Function Module  _CJB_ErrSta   Error status variable for I O bus    _CJB_MstrErrSta   Error status variable for master       _CJB_UnitErrSta Error status variable for Units    _MC_ErrSta Error status variable for Motion Control Function Module  _MC_ComeErrSta Common error status variable  _MC_AX_ErrSta Axis error status variable    MC_GRP_ErrSta  Axes group error status variable    EC _ErrSta Error status variable for Et
199. rame transmission jitter  exceeded the limit   The Ethernet cable is broken     The Ethernet cable for Ether   Net IP is disconnected     A general purpose Ethernet  hub is connected     The master failed   The slave failed   The Ethernet cable is too long     The CPU Unit task period is too    short   Noise    A slave left the network even    though the disconnection oper     ation was not performed   Noise  Moving Slaves    An emergency message was  received from a slave     Refer to the attached informa   tion to check the error          Level O     a aee ee    NJ series  CPU Unit  Built in Ether   CAT Port  User   s Manual   Cat  No   W505     d Same as  above     d Same as  above    d Same as  above       Same as  above     d Same as  above     d Same as  above    d Same as  above    d Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Level    A slave was discon   nected for a discon   nection command     94400000 hex   Slave Dis     connected    A slave was recon   nected for a recon   nection command     Slave Con   nected    94410000 hex    94430000 hex A command was  received to reset    errors     Errors Reset    NJ series Troubleshooting Manual  W503        e An operation to disconnect the NJ series  slave was executed from the CPU Unit  Sysmac Studio  Built in Ether   The EC_DisconnectSlave CAT Port  instruction was executed  User s Manual    Cat  No    W505   An operation to reconnect the Same as  slave was executed from the above
200. rection  Limit Input  Detected    Invalid Home  Input Mask  Distance    No Home  Proximity  Input    Slave Error  Detected    Axes Group  Composition  Axis Error    MC Com     mon Error  Occurrence    The home proxim   ity input and the  limit signal in the  homing direction  were detected at  the same time dur   ing a homing opera   tion     The home input and  the limit signal in  the direction oppo   site to the homing  direction were  detected at the  same time during a  homing operation     The home input and  the limit signal in  the homing direc   tion were detected  at the same time  during a homing  operation     The setting of the  home input mask  distance is not suit   able for the  MC_Home instruc   tion     There was no home  signal input during  the homing opera   tion  Or  a limit sig   nal was detected  before there was a  home input     There was no home  proximity signal  input during the  homing operation     An alarm was  detected for the  EtherCAT slave that  is allocated to an  axis     An error occurred  for an axis in an  axes group     An MC common  error occurred     e The wiring of the home proxim   ity signal or limit signal is incor   rect    The home proximity sensor or  limit sensor is installed in the  wrong location     The contact logic of the home  proximity signal or limit signal is  not correct    The home proximity sensor or  limit sensor failed     The wiring of the home input  signal or limit signal is incorrect     The home input sens
201. ries Servo Drives with Built in   1576  EtherCAT Communications   Life Expectancy Warning G5 series Servo Drives with Built in 1576  EtherCAT Communications   External Encoder Error Warning G5 series Servo Drives with Built in   1576  EtherCAT Communications   External Encoder Communications G5 series Servo Drives with Built in 1576   Warning EtherCAT Communications   Encoder Communications Disconnec    G5 series Servo Drives with Built in 1576   tion Error EtherCAT Communications   Encoder Communications Error G5 series Servo Drives with Built in 1576  EtherCAT Communications   Encoder Communications Data Error   G5 series Servo Drives with Built in   1576  EtherCAT Communications   Safety Input Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   External Encoder Connection Error G5 series Servo Drives with Built in 1576  EtherCAT Communications   External Encoder Communications G5 series Servo Drives with Built in   1576   Data Error EtherCAT Communications   External Encoder Status Error 0 G5 series Servo Drives with Built in 1576  EtherCAT Communications    External Encoder Status Error 1 G5 series Servo Drives with Built in 1576  EtherCAT Communications    G5 series Servo Drives with Built in 1576  EtherCAT Communications    External Encoder Status Error 2    G5 series Servo Drives with Built in 1576  EtherCAT Communications    External Encoder Status Error 3    G5 series Servo Drives with Built in 1576  EtherCAT Communications    External Encode
202. rmation by itself is not sufficient for a  complete determination of the suitability of the products in combination with the end product  machine   system  or other application or use     The following are some examples of applications for which particular attention must be given  This is not  intended to be an exhaustive list of all possible uses of the products  nor is it intended to imply that the uses  listed may be suitable for the products     e Outdoor use  uses involving potential chemical contamination or electrical interference  or conditions or  uses not described in this manual    e Nuclear energy control systems  combustion systems  railroad systems  aviation systems  medical  equipment  amusement machines  vehicles  safety equipment  and installations subject to separate  industry or government regulations    e Systems  machines  and equipment that could present a risk to life or property     Please know and observe all prohibitions of use applicable to the products     NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR  PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO  ADDRESS THE RISKS  AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND  INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM        PROGRAMMABLE PRODUCTS    OMRON shall not be responsible for the user s programming of a programmable product  or any  consequence thereof        12 NJ series Troubleshooting Manual  W503     Read and U
203. ror Tables    i CJ series DeviceNet Units    The section provides tables of the events that can occur in the following Units     04880000 hex    04890000 hex    148D0000 hex    148E0000 hex    24480000 hex    34BC0000 hex    3 68    CJ1W DRM21    e There is a source of noise    Unit Memory  Error    Network  Power Error    Invalid Scan  List Data    Invalid Setup  Data    Node  Address  Duplicated  Error    Routing Table  Error    An error occurred  when writing to  internal memory  where the error his   tory is saved     Network power is  not being supplied     There is an error in  the contents of the  slave scan list or  master scan list  stored in non vola   tile memory     There is illegal data  in the settings for  the slave function     An error was dis   covered during the  node address dupli   cation check when  starting the  DeviceNet Unit     There is illegal data  in the routing tables  set in the CPU Unit     nearby   Non volatile memory failure    Communications power is not  being supplied normally from  the network     The power was interrupted dur   ing writing the scan list to the  non volatile memory     The power was interrupted  while the system was writing  the parameters     Non volatile memory life  The node address of the    DeviceNet Unit is also set for  another node     The local DeviceNet Unit is not  in the routing tables    The routing table format is  incorrect    Reading the routing tables  timed out        p Level    a aE inated    CJ series 
204. ror e In Protocol Macro Mode  the CJ series  Error occurred  SDL  indicator does not flash at Serial Com   all   The Serial Communica  munications  tions Unit received a command  Units Opera   but the step transition of the tion Manual for  protocol macro communica  NJ series  tions sequence is suspended CPU Unit  Cat   for one of the following reasons  No  W494   e The next step is a RECEIVE  command   e A WAIT command is pres   ently in execution   In Serial Gateway Mode or Pro   tocol Macro Mode  the SDL   indicator flashes  but the RDLI  does not flash    e There is no remote device to  receive the command after  conversion at the specified  destination address   The sent command frame is  illegal   The settings for the communi   cations conditions and baud  rate of the serial communica   tions path do not match the  remote device   The communications cable  wiring is faulty or incorrect   the terminating resistance  settings of the RS 424A 485  port are incorrect  or the  adapter wiring or terminating  resistance settings for the NT   ALOO1 are incorrect   The protocol of the sent com   mand was unable to be inter   preted by the remote device   Remote device hardware fail   ure  In Serial Gateway Mode or Pro   tocol Macro Mode  RDLJ SDL 1  indicator flashes    eThe response from the remote  device was too fast  and the  data received by the Serial  Communications Unit was  discarded   eThe Serial Gateway Response  Timeout Monitoring Time for  the    P1_PmrSgwRespTimeout
205. rors  Refer to the NJ series CPU Unit Software User s Manual  Cat  No  W501  for information on  operation authority     All Controller errors are reset when you reset the Controller from the Sysmac Studio  If the cause of the  error is not removed  the error will occur again     2 8 NJ series Troubleshooting Manual  W503     2 Error Troubleshooting Methods    2 3 2 Identifying and Resetting Errors with an NS series PT    You can connect one of the following OMRON NG sees PTs to an NJ series CPU Unit through an Eth   erNet IP network  and use it to read and reset errors that occurred in the Controller   The Trouble   shooter of the PT is used    e NS8  NS10  NS12  and NS15   NSLJ T_J01 V2  The V2 versions have an Ethernet port    e NS5   NS5 L1Q11 V2  These models have expanded memory and an Ethernet port    e NSJ8  NSJ10  and NSJ12   All models    e NSJ5  NSJ5 LJQ11 _   These models have expanded memory and an Ethernet port      Ce  oo   I  O     z  D  o  St      O     5  Q  Z  O  5   h  D  mp  D  m        O     o       The above models of NS series PTs with system version 8 5 or higher are compatible with the NJ   series Controllers     i Checking for Current Errors with an NS series PT    You can check for errors in the Controller using the Troubleshooter of an NS series PT that is compati   ble with NJ series Controllers  You can also use the Troubleshooter to read detailed error information  and corrections for current errors  Refer to the NS series Programmable Terminal
206. rror occurred in There is a source of noise Same as  Unit Busy an ID Sensor Unit  nearby  above     The ID Sensor Unit failed        NJ series Troubleshooting Manual  W503  3 59    3 Error Tables    e The setting of the Connected    24400000 hex    34980000 hex    54A00000 hex    54A10000 hex    54A20000 hex    648C0000 hex    648D0000 hex    648E0000 hex    648F0000 hex    64900000 hex    3 60    Unit Status   Antenna  Error    Results Infor   mation  Data  Storage Area  Specification  Error    Results Infor   mation  ID  Tag Address  Error    Results Infor   mation  Write  Protection  Error    Results Infor   mation  Com   mand Error    Unit Status   Command  Error End    Results Infor   mation  Veri   fication Error    Results Infor   mation  ID  Tag Commu   nications  Error    Results Infor   mation  ID  Tag Missing  Error    Results Infor   mation  ID  System Error  1    An error occurred in  the Antenna     The data storage  area specification is  not correct     The address of the  ID Tag is wrong     An attempt was  made to write toa  write protected  area of the ID Tag     The command to  the ID Sensor Unit  is not correct     A processing error  occurred     The correct data  could not be writ   ten to the ID Tag     An error occurred in  communications  with an ID Tag  pre   venting a normal  end     There is no ID Tag  in the communica   tions area     ID system error 1  occurred     Antenna Setting  device vari   able  _Ch _AntConn  does not  agree with the Anten
207. rror was Hardware has failed  Same as 5  Processing detected in the Eth  above     Error erNet IP Function A  Cc  Module     34210000 hex   Basic Ether    An error was Power was interrupted when a Same as  net Setting detected in the download was in progress for above   Error Ethernet settings  the Ethernet basic settings   Memory error  34220000 hex   TCP IP Basic   An error was Power was interrupted when a Same as  Setting Error   detected in the IP download was in progress for above    Local bot IP   address settings  the TCP IP basic settings   Address  Memory error  The IP address acquired from  BOOTP server is illegal   84010000 hex   IP Address The same IP The IP address of the built in Same as  Duplication address is used EtherNet IP port is also used as above   Error more than once  the IP address of another node   84020000 hex   BOOTP Connection with the Server is down  Same as  Server Con  BOOTP server An error occurred in the com  above   nection Error   failed  munications path   The IP address acquired from  BOOTP server is illegal   14210000 hex   Identity Error   The CIP identity Non volatile memory failure Same as  information in non  above   volatile memory  was not read cor   rectly   NJ series Troubleshooting Manual  W503  3 35    3 Error Tables    34200000 hex   Tag Data Link    Setting Error    TCP IP  Advanced  Setting Error   IP Router  Table     34230000 hex    FTP Server  Setting Error    34240000 hex    NTP Client  Setting Error    34250000 hex    S
208. rrup   tion occurred     The Servo Drive failed     The voltage between the posi   tive and negative terminals in   the control power supply con    verter exceeded the specified   value     The voltage was suddenly  increased by the phase  advance capacitor or the unin   terruptible power supply  UPS      The Regeneration Resistor wir   ing is broken    The External Regeneration  Resistor is not suitable     The Servo Drive failed     Insufficient power supply  Capacity   The electromagnetic contactor  in the main circuit power supply  was tripped    A momentary power interrup   tion occurred     A Servo Drive with 3 phase  input specifications was oper   ated with a single phase power  supply    The Servo Drive failed     Insufficient power supply  Capacity  The electromagnetic contactor    in the main circuit power supply    was tripped    A momentary power interrup   tion occurred    A Servo Drive with 3 phase  input specifications was oper     ated with a single phase power    supply   The Servo Drive failed     3 Error Tables    Level  GE Ee    AC Servomo   tors Servo  Drives G5  Series with  Built in Ether   CAT Commu   nications  User s Man   ual  Cat  No   1576     Same as  above     Same as    3 43    OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       SOAR S LYOJOUIF U  S1013 9           3 Error Tables    04AC0000 hex   Overcurrent    04AD0000 hex    04AE0000 hex    04AF0000 hex    04B00000 hex    04B10000 hex    08080000 hex    08090000 hex    3 44    
209. s NENNEN 2 13  T  E E 3 6  Troubleshooter EE 1 12  2 9   gell e e rn Le WEE 1 12  2 5  SIE IR E 2 4  non fatal errors         ccceececccseseeecceseeeeceeeeeceeeeeeeeeeneees 2 5  U  Unitconfigura  N siron a lade  3 5  user defined events             cccccccssseeececeeseeeeceeeeeeseseeseeeeeas 1 5    NJ series Troubleshooting Manual  W503     Index    Index 3       Index    Index 4 NJ series Troubleshooting Manual  W503     Authorized Distributor        
210. s Programming Man   ual  Cat  No  V073  for details on the NS series PT   s Troubleshooter     The following example demonstrates the procedure used to check for errors with an NS8  NS10  NS12   or NS15 PT     You can check the event source in the Function Module View of the Troubleshooter  If you click the  Select Button for a function module in the Event source Table  you can display the Source details for  events for that function module  You can select the list in the Source details Table to display the List  View     Ld S  H  s S  N ue UM SION Bumes  y pue Hul  yuep  Z E Z    NJ series Troubleshooter    Event source    i Error   EtherNet 1P Error    1 Te   Panel capture    Reset error    RUN   192  168  25   1   Control ler    The List View displays a list of the errors produced by the event source that you selected in the Function  Module View        NJ series Troubleshooting Manual  W503  2 9    2 10    2 Error Troubleshooting Methods    Ee Partial fault  84M 1AMMA  IP Address Duplication Error  a   ner faut   BAAP DN Server Connection Error      Panel capture   Reset error_        RUN   192  168  250  1   Controller    i Resetting Errors with an NS series PT    You can use the Troubleshooter in an NS series PT to reset errors that occur in the Controller  Before  you attempt to reset a Controller error  isolate and remove the cause of the error     Click the Select Button in the List View to display information such as the errors causes and correc   tions  If you sele
211. s Special Units are not included   Refer to the manuals for the slaves or Special Units for the procedures to read their error logs       User defined Events  These are events that occur in applications that the user developed     Refer to the NJU series CPU Unit Software User s Manual  Cat  No  W501  for information on user   defined events     Non fatal errors are managed as Controller events  This section describes mainly the Controller events     NJ series Troubleshooting Manual  W503  1 5    1 Overview of Errors    i Details on Controller Events  Errors and Information       Sources of Controller Events    The Event source information indicates the location where an event occurred  The event source  identifies the particular function module in the CPU Unit in which the event occurred  For some func   tion modules  there is more detailed information about the event source  This information is called  the Source details  The following information is provided as the event source details     Event source Source details   PLC Function Module I O bus master or CJ series Unit   Motion Control Function Module Common  axis  or axes group   EtherCAT Master Function Module Communications port  EtherCAT master  or EtherCAT slave  EtherNet IP Function Module Communications port  CIP  FTP  NTP  or SNMP    The event source is displayed on the Sysmac Studio or NS series PT     Levels of Controller Events  Errors and Information     The following table classifies the levels of Controller
212. s W497  Invalid Scan List Data CJ series DeviceNet Units W497  Invalid Setup Data CJ series DeviceNet Units W497    Non volatile Memory Checksum Error   Block I O  GX series EtherCAT Slave   W488  Units    Object Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   Object Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   Object Error G5 series Servo Drives with Built in   1576  EtherCAT Communications    NJ series Troubleshooting Manual  W503     3 Error Tables    Event code Event name Functional classification Reference    14AB0000 hex Object Corrupted G5 series Servo Drives with Built in   1576  EtherCAT Communications    14AC0000 hex Object Corrupted G5 series Servo Drives with Built in   1576  EtherCAT Communications  14AD0000 hex Object Corrupted G5 series Servo Drives with Built in   1576    EtherCAT Communications    18200000 hex Absolute Encoder Overspeed Error G5 series Servo Drives with Built in   1576  EtherCAT Communications    18210000 hex Encoder Initialization Error G5 series Servo Drives with Built in 1576  EtherCAT Communications  18220000 hex Absolute Encoder One rotation G5 series Servo Drives with Built in 1576  Counter Error EtherCAT Communications  18230000 hex Absolute Encoder Multi rotation G5 series Servo Drives with Built in 1576  Counter Error EtherCAT Communications  24010000 hex Unsupported Unit Detected Errors Related to Unit Configuration   W500    24020000 hex Too Many I O Points Errors Related
213. s with an event level of partial fault have occurred for the EtherCAT Master Function Module     Always confirm safety at the connected equipment before you reset Controller errors for a CJ   series Special Unit  When the Controller error is reset  the Unit where the Controller error with an  event level of observation or higher will be restarted  Before you reset all errors  confirm that no  Controller errors with an event level of observation or higher have occurred for the CJ series  Special Unit  Observation level events do not appear on the Controller Error Tab Page  so it is  possible that you may restart the CJ series Special Unit without intending to do so  You can  check the status of the _CJUJB_UnitErrSta 0 0  to _CUB_UnitErrSta 3 9  Error Status variables on  a Watch Tab Page to see if an observation level Controller error has occurred        Precautions for Correct Use    Resetting an error is not the same as eliminating the cause of the error  Always eliminate the  cause of an error before you perform the procedure to reset the error     NJ series Troubleshooting Manual  W503  1 13    1 Overview of Errors    Error Resetting Methods       Method    Commands from  Sysmac Studio    Commands from an  NS series PT    Commands from the  user program    Commands from a  host computer    Cycling the Control   lers power supply    reset    Resetting Controller  errors    Downloading    Memory All Clear    Controller reset    Resetting Controller  errors    Resetting Contr
214. sed  simultaneously for more than  one of the following instruc   tions  MC_TouchProbe  Enable  External Latch  instruction   MC_MoveLink  Synchronous  Positioning  instruction  and  MC_MoveFeed  Interrupt Feed   ing  instruction     The MC_AbortTrigger  Disable  External Latch  instruction was  executed to cancel a latch that  was used by an instruction  other than the MC_TouchProbe   Enable External Latch  instruc   tion     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable       Level O     a aTe SE    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Level O           54720000 hex   Motion Con    An attempt was e A parameter for an input vari  NJ series   trol Instruc  made to change the able that cannot be changed for Motion Con    tion Re  StartMode input re execution was changed  trol Instruc    execution variable when re  tions   Disabled executing a motion Reference    First Position   control instruction  Manual  Cat    Method   This input variable No  W508  W  cannot be changed    when re executing    an instruction   S   54740000 hex   Unused Axis   The axis specified Th
215. series Servo Drives with Built in   1576  EtherCAT Communications   Encoder Phase Z Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   Encoder CTS Signal Error G5 series Servo Drives with Built in   1576  EtherCAT Communications   Node Address Setting Error G5 series Servo Drives with Built in   1576  EtherCAT Communications    NJ series Troubleshooting Manual  W503     W490  W498    Event code  04BA0000 hex    04BB0000 hex    04BC0000 hex    08010000 hex    08020000 hex    08030000 hex    08040000 hex    08050000 hex    08060000 hex    08070000 hex    08080000 hex    08090000 hex    O80A0000 hex    O80B0000 hex    080C0000 hex    O80D0000 hex    O80E0000 hex    O80F0000 hex    08100000 hex    08110000 hex    08120000 hex    08130000 hex    08140000 hex    08150000 hex    08160000 hex    08170000 hex    3 Error Tables    Event name Functional classification Reference    Connection Error between Inverter MX2 series Inverters with EtherCAT   1574   and Communications Unit Communications Units   Inverter Warning MX2 series Inverters with EtherCAT  1574  Communications Units    Inverter Trip MX2 series Inverters with EtherCAT  1574  Communications Units    Battery Warning G5 series Servo Drives with Built in 1576  EtherCAT Communications   Fan Warning G5 series Servo Drives with Built in   1576  EtherCAT Communications   Encoder Communications Warning G5 series Servo Drives with Built in   1576  EtherCAT Communications   Encoder Overheating Warning G5 se
216. shooting Manual  W503        Index       NJ series Troubleshooting Manual  W503  Index 1    Index    Index                   A  assumed causes             3 3  3 5  3 6  3 7  3 8  3 10  3 18   Bebe 3 35  3 39  3 42  3 43  3 55  3 56   ests ioscan cata ana  3 58  3 59  3 61  3 62  3 68  3 90  B  BOCK VO axis Breet cet ti ee eet teh ot teste 3 42  built in EtherCAT master oo    ceccceseeeseeseeseeeeeees 3 39  built in EtherNet IP port                ccccccssseseeeceeeeeeeeeeeeeeees 3 35  C  CJ1W AD041 V1 AD081 V  nnnc 3 56  SCHER EN 3 56  CSAWrA DOA  eebe ee ee e eene 3 58  SNE e   re tee een ee ee ere es oe ee ero 3 61  CJ1W DA021 DA041   ask AER  3 56  CIA WW DAOAO Ate eeh gg een seent 3 56  CJ1W DAO8V DAOS8C o oo  ieee cccccccecccecceecseeceueeeeeeeeeeeeaues 3 56  CIA WHDARM2 WEE 3 68  CIV WMA DAD EE 3 56  e A  eo cel 8  Seu Ic eet eege 3 58  CJAWsPAG TU WEEN 3 58  yaks  ES  BEE 3 62  CIV WSC EEN 3 62  CHW Sec eeng ee Oe Oe ence 3 62  CSAW    GOO 8  reegen ee EEN 3 59  IA WT GOO A fies lice a te tbe es ete oe teste 3 59  CIV WT CVO8  EE 3 59  CJIW TOCI04 nasia ne E LENES 3 59  CJIW VO8OG TT rrei E E E 3 59  SENAT KEE 3 59  CJ series Analog I O Units              cccccceessseeeeeeseeeeeeeeees 3 56  CJU series DeviceNet UnitS   3 68  CJ series High speed Counter Units                   2cccee 3 61  CJU series ID Sensor Units 20 0    ceccseceeeeeeeeeeeeeeeees 3 59  CJU series Process I O Units 2 00    ceccceceseeeeeeeeeeeeeees 3 58  CJ series Serial Communications Units        
217. si   tion Count  Selection Out  of Range    54960000 hex   Master Axis  Gear Ratio  Numerator  Out of Range    3 32    The same axis was  specified for the  Auxiliary and Slave  input variables to a  motion control  instruction     The parameter  specified for the  Relative input vari   able to a motion  control instruction is  out of range     The parameter  specified for the  CamtTransition input  variable to a motion  control instruction is  out of range     The parameter  specified for the  OutMode input vari   able to a motion  control instruction is  out of range     _mclmmediateStop    was specified for  the StopMode input  variable when the  MC_TouchProbe   Enable External  Latch  instruction  was executed in  Drive Mode  but the  Control Mode was  not CSP Mode     The parameter  specified for the  MasterOffset input  variable to a motion  control instruction is  out of range     The parameter  specified for the  SlaveOffset input  variable to a motion  control instruction is  out of range     The parameter  specified for the  CmdPosMode input  variable to a motion  control instruction is  out of range     The parameter  specified for the  RatioNumerator   Master input vari   able to a motion  control instruction is  out of range     e The parameter is the same for    the Auxiliary and Slave input  variables to the instruction     Instruction input parameter  exceeded the valid range of the  input variable        Instruction input parameter  exceeded the valid range o
218. ss Data Transmission Error Built in EtherCAT Master in CPU Unit   W505    NJ series Troubleshooting Manual  W503     3 87    Wi  N  m   lt   OD   gt   mr       5  O     Q   OD     O  mb  m   lt        gt   mp  O  O  Q   ui            SOT 1013   t    3 Error Tables    3 88    Event code  842B0000 hex  842C0000 hex  842D0000 hex  84400000 hex    84680000 hex    84690000 hex    846A0000 hex    846B0000 hex    846C0000 hex    846D0000 hex    84740000 hex  84750000 hex  84760000 hex    84770000 hex  84B00000 hex    84B10000 hex    84B20000 hex    84B30000 hex    84B40000 hex    84B50000 hex    84B60000 hex    84B70000 hex    84B80000 hex    84B90000 hex    90010000 hex    90020000 hex    90080000 hex    90090000 hex    900A0000 hex    W506  W506  ve    EtherCAT Slave Communications General Motion Control W507   Error   Transmission Error CJ series Serial Communications W494  Units   Overrun Error CJ series Serial Communications W494  Units   Framing Error CJ series Serial Communications W494  Units   Parity Error CJ series Serial Communications W494  Units   Overrun Error  Framing Error  or Par    CJ series Serial Communications W494   ity Error  Transmission Error  Units    Transmission Error  CRC Error  CJ series Serial Communications W494  Units    Bus Off Detected CJ series DeviceNet Units W497  Remote I O Communications Error CJ series DeviceNet Units W497    Remote I O Communications Error CJ series DeviceNet Units W497   during Slave Operation     Slave COS Send Failed CJ s
219. ss I O Units    Cold Junction Sensor Error CJ series Temperature Control Units   W491    Unit Status  Antenna Power Supply CJ series ID Sensor Units Z317  Error    Unit Status  Memory Error CJ series ID Sensor Units Z317  Results Information  Antenna Error CJ series ID Sensor Units Z317  CJ series ID Sensor Units Z317    Unit Status  Unit Busy    Error Log Data Error CJ series Serial Communications W494  Units   DTR Check Error CJ series Serial Communications W494  Units   CTS Check Error CJ series Serial Communications W494  Units    Unit Memory Error CJ series DeviceNet Units W497  Network Power Error CJ series DeviceNet Units W497  File Read Write Error CJ series DeviceNet Units W497    Non volatile Memory Hardware Error   MX2 series Inverters with EtherCAT   W488  1574  Communications Units   Control Power Supply Undervoltage   G5 series Servo Drives with Built in   1576  EtherCAT Communications   Overvoltage G5 series Servo Drives with Built in   1576  EtherCAT Communications    Main Circuit Power Supply Undervolt    G5 series Servo Drives with Built in   1576    age  Undervoltage between positive   EtherCAT Communications    and negative terminals     Main Circuit Power Supply Undervolt    G5 series Servo Drives with Built in   1576  age  AC Cutoff Detected  EtherCAT Communications       Overcurrent G5 series Servo Drives with Built in 1576  EtherCAT Communications   IPM Error G5 series Servo Drives with Built in 1576  EtherCAT Communications   Regeneration Tr Error G5 
220. st by using the  error code as the upper four digits and 0000 hex as the lower four digits of the event code  Refer to  the NJ series CPU Unit Motion Control User s Manual  Cat  No  W507  and NJ series Motion  Control Instructions Reference Manual  Cat  No  W508  for lists of errors        Exporting the Error Log    You can use the Sysmac Studio or an NS series PT to export the displayed event log to a CSV file   Refer to the NJ series CPU Unit Software User s Manual  Cat  No  W501  for information on export   ing event logs    1 3 2 Checking for Non fatal Errors    g Checking Methods    Use the following methods to check for non fatal errors     Checking method What you can check   Checking the indicators You can use the indicators to confirm the Controller error level  the error  status of the EtherCAT Master Function Module  and the error status of  the EtherNet IP Function Module     Checking with the Troubleshooting You can check for current Controller errors  a log of past Controller errors     Function of Sysmac Studio error sources  error causes  and corrections    Checking with the Troubleshooter of   You can check for current Controller errors  a log of past Controller errors   an NS series PT error sources  error causes  and corrections    Instructions that read function mod    You can check the highest level status and highest level event code in the  ule error status current Controller errors    Checking with system defined vari    You can check the current Contr
221. struction that support multi execution of instructions was   above   does not support it  specified more than once    16 0800 FINS Error An error occurred when a e An error occurred when a FINS command Same as  FINS command was sent was sent or received  above   or received    16 0801 FINS Port Already   The FINS port is being e The FINS port is being used  Same as   in Use used  above   16 0C00 Illegal Serial Com    The Serial Communica  e The serial communications port for the Same as  munications Mode tions Unit is not in the serial Serial Communications Unit is not set to the   above   communications mode mode expected by the instruction   required to execute an  instruction    16 0C02 Port Setup Already   A Change Port Setup e A Change Port Setup instruction was exe  Same as  instruction was executed cuted during execution of another Change above   during execution of another Port Setup instruction    Change Port Setup instruc   tion    16 1400 SD Memory Card   SD Memory Card access e An SD Memory Card is either not inserted Same as  Access Failure failed when an instruction or is not inserted properly  above    was executed  e The SD Memory Card is broken   e The SD Memory Card slot is broken    16 1401 SD Memory Card   An attempt was made to e An attempt was made to write to a write pro    Same as   Write protected write to a write protected tected SD Memory Card  above   SD Memory Card when an  instruction was executed    16 1402 SD Memory Card   The capacity of the S
222. ter point exceeded the per   mitted value specified for the  correction allowance ratio in the  axes group settings when the  center designation method was  specified for the  MC_MoveCircular2D  Circular  2D Interpolation  instruction     An axis in Rotary Mode was  used with the  MC_MoveCircular2D  Circular  2D Interpolation  instruction     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable    The parameter specification  and the data type of the setting  value do not agree        NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     3 23    OO  I      m        O     Vu  o   lt   GU  O  c     O  OD       BINDO  uonouny  O1 UOD uono 3y  Ul s1013 E L       3 Error Tables    e Instruction input parameter  exceeded the valid range of the  input variable     54500000 hex    54510000 hex    54530000 hex    54540000 hex    54550000 hex    54560000 hex    3 24    Trigger Input  Condition  Mode Selec   tion Out of  Range    Drive Trigger  Signal Selec   tion Out of  Range for  Trigger Input  Condition    Motion Con   trol Instruc   tion Re   execution  Disabled   Axis Specifi   cation     Motion 
223. that  occurs due to user settings in the Controller   For exam   ple  if the task period is exceeded or if a position outside  of the motion range is detected    7 Control errors An error caused by a control process   For example  if  the operating status does not meet the required condi     tions or if the timing is incorrect      8 Communications errors An error caused by communications with an external  device or host system    9 Information Events that are classified as information and provide  information that do not indicate errors     Some of the function modules output part of the event code as an error code when an error occurs   You can check the error codes for the following function modules     e Motion Control Function Module          or   amp        You can check error codes with the following variables   e ErrorlD output variable for motion control instructions  e The following system defined variables for motion control     1 10 NJ series Troubleshooting Manual  W503     1 Overview of Errors    Variable name Meaning  _MC_COM PFaultLvl Code MC Common Partial Fault Code  _MC_COM MFaultLvl Code MC Common Minor Fault Code  _MC_COM Obsr Code MC Common Observation Code  _MC_AX 0  63  MFaultLvl Code Axis Minor Fault Code  _MC_AX 0  63  Obsr Code Axis Observation Code  _MC_GRP 0  31  MFaultLvl Code Axes Group Minor Fault Code  _MC_GRP 0  31  Obsr Code Axes Group Observation Code    The upper four digits of the event code is output as the error code  Check the error li
224. that occur are managed as events in the NJ series Controller  You can check the event  to find out what type of error occurred        h  I  oo  Z  O   gt   ds  D  mp     m        O     GA    1 3 1 Types of Non fatal Errors    i Overview of Controller Events  Errors and Information     You use the same methods to manage all of the events that occur on the NJ series Controller  The  events that occur are saved in battery backup memory in the CPU Unit  You can use the Sysmac Studio  or an NS series PT to confirm current Controller events and the log of events that occurred before  This  log is called an event log            Check current Controller  events and the event log  of past events          S101143           UON Jo s  d  L                 Sysmac Studio NJ series CPU Unit  Event source PLC Function Motion Control EtherCAT Master EtherNet IP Errors in  Module Function Module    Function Module Function Module Special Units      f     Create User defined  Error instruction   Event logs SetAlarm                Create User defined  Information  instruction  SetInfo           Backup battery  Check current Controller  events and the event log  of past events               EtherCAT  slave       The following events can occur       Controller Events    The Controller automatically detects these events  Controller events include events for the function  modules in the CPU Unit  EtherCAT slaves  and CJ series Units     The error logs from within the EtherCAT slaves and the CJ serie
225. the  composition axes in the Axes  Group Settings     The same axis was specified  for both axes of CircAxes     The parameters for the Auxil   iary and Slave input variables to  the instruction are not in  ascending order     A phase that was not in  ascending order was found  when calculating the number of  valid data     After calculations  the number  of valid data is 0     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable          Level O     a aTe ee    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     Master Dis   tance in    54830000 hex The parameter    specified for the    e Instruction input parameter    54840000 hex    54870000 hex    54880000 hex    Acceleration  Specification    Out of Range    Master Dis   tance in  Deceleration  Specification  Out of Range    Execution  Mode Selec   tion Out of  Range    Permitted  Following  Error Out of  Range    MasterDistance   ACC input variable  to a motion control  instruction is out of  range     The parameter  specified for the  MasterDistance   DEC input variable  to a motion control  instruction is out of  range     The parameter  specified for the  ExecutionMode  input variable to a  motion 
226. the slave  For a Servo  Drive  operation depends on the setting of object 605E hex  Fault Reaction Option Code            Event Code    Events that occur in a Controller have an event code  When an event occurs  the Sysmac Studio or  PT will display the event code  You can use the instructions that get error status to read the error  codes of current errors from the user program     The event codes are 8 digit hexadecimal values  The first digit of a Controller event represents its  category  These categories are listed in the table below     First digit of the eg l  code  hex  Classification Meaning    0 Hardware errors An error caused by a hardware problem such as an inter   nal part malfunction  contact failure  temperature error   undervoltage  overvoltage  or overcurrent     1 Data errors An error caused by incorrectly saved data or data cor   ruption in the Controller     2 Hardware setting errors An error caused by incorrect handling of hardware set   tings  e g   hardware switches  or restrictions  e g   Unit  assignment locations     3 Configuration errors An error caused by incorrect parameter values  parame   ters and hardware configurations that do not match  or  configurations set by the user     Software errors An error caused by Controller software     User software errors An error that is caused by the user program   For exam   ple  an input value to an instruction that is out of range    6 Observation errors An error that was detected in monitoring operation 
227. tings are  incorrect     The send destina   tion node is not  known     The FINS TCP con   nection table is  incorrect     troller was interrupted or com   munications with the Sysmac  Studio were disconnected while  downloading the CPU Bus Unit  Settings     The IP address conversion  method is set to the combined  method or the IP address table  method  but the IP address  table settings are incorrect     The send destination node was  not found when a FINS mes   sage was sent     The power supply to the Con   troller was interrupted or com   munications with the Sysmac  Studio were disconnected while  downloading the FINS TCP  connection table        p Level       Reference    NJ series  CPU Unit  Hardware  User   s Manual   Cat  No   W500     NJ series  CPU Unit Soft   ware User   s  Manual  Cat   No  W501     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Reference    NJ series  CPU Unit Soft   ware User   s  Manual  Cat   No  W501     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     80100000 hex   Packet Dis  One or more pack   le A FINS response addressed to NJ series  carded ets were discarded  the CPU Unit was received  CPU Unit Soft     The send designation Unit for ware User s    the FINS response does not Manual  Cat   exist  No  W501     80110000 hex   Packet D
228. travel  distance to accelerate the cur   rent command to the transit  velocity when the Accelera   tion Deceleration Over parame   ter was set to generate a minor  fault and stop     The constant velocity travel dis   tance of the master axis is  below O for the MC_MoveLink   Synchronous Positioning   instruction     For the MC_GearlnPos  Posi   tioning Gear Operation  instruc   tion  the value of the Velocity   Target Velocity  input variable  is smaller than the master axis  velocity multiplied by the gear  ratio when the instruction was  executed           weal O     a SE    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     54480000 hex    54490000 hex    544A0000 hex    544C0000 hex    544D0000 hex    544E0000 hex    544F0000 hex    Same Start  Point and  End Point for  Circular Inter   polation    Circular Inter   polation Cen   ter  Specification  Position Out  of Range    Circular Inter   polation Can   not Be  Executed  with Rotary   Infinite  Axis    Parameter  Selection Out  of Range    Stop Method  Selection Out  of Range    Latch ID  Selection Out  of Range for  Trigger Input  Condition    Setting Out of  Range for  Writing MC  Setting    The start point and  end point were the  same when the  radius method was  specified for the  MC_MoveCircular
229. trol Function Module    The section provides tables of the errors  events  that can occur in the Motion Control Function Module   They are divided into the following functional classifications     e General motion control  e Motion control instructions    Motion control instruction errors occur when a motion control instruction is executed  Notification of  these errors is provided as events  but also the upper four digits of the event code is output to the  ErrorlD output variable of the motion control instruction and to the   Lv  Code system defined variable    for motion control     d General Motion Control    e The user program or Controller    10200000 hex    14600000 hex    14610000 hex    14620000 hex    34600000 hex    3 10    User Pro   gram Con   troller  Configura   tions and  Setup Trans   fer Error    Absolute  Encoder  Home Offset  Read Error    Motion Con   trol Parame   ter Setting  Error    Cam Data  Read Error    Required  Process Data  Object Not  Set    The user program  or Controller Con   figurations and  Setup were not  transferred cor   rectly     The absolute  encoder current  position that is  retained during  power interruptions  was lost     The MC parameters  that were saved in  non volatile mem   ory are missing     The cam data that  was Saved in non   volatile memory is  missing    The object that is  required for the axis    type is not allocated  to PDO     Configurations and Setup are  not correct because the power  supply to the Controller 
230. trol is  set to both RTS CTS flow  control and Xon Xoff flow  control     Noise    The monitor time is shorter than  the actual completion time     Noise    The monitoring time is shorter  than the actual completion time     Noise    The monitoring time is shorter  than the actual completion time        3 Error Tables      Level O     a me Tae Ga    CJ series  Serial Com   munications  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W494     Same as  above     Same as  above     Same as  above     3 63    OO  I      m        O     Vu  CH   lt   GA  O  c     O  OD       SIU  s  n  s f9 Ul S1013 J          3 Error Tables       weal O     One of the following  errors occurred in  the converted pro   tocol at the serial  gateway     64A30000 hex    3 64    FCS Check  Error    e When converting  to CompoWay F  command  BCC  error    When converting  to Modbus RTU  command  CRC  error    When converting  to Modbus ASCII  command  CRC  error    When converting  to Host Link FINS  command  FCS  error    Protocol Macros    e The check code  attached to the  received mes   sage does not  match the check  code that was  calculated from  the received mes   sage     e Noise    e There was a mistake in the  CRC code that was attached to  the command frame        CJ series  Serial Com   munications  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W494     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     64A40000 hex   Timeout A timeout er
231. uction  set that is provided by  OMRON     Learning about the specifi   cations of the motion con   trol instructions that are  provided by OMRON     Learning how to use CJ   series Units with an NJ   series CPU Unit        Description    An introduction to the entire NJ series system is  provided along with the following information on  a Controller built with an NJ501 CPU Unit     e Features and system configuration  e Introduction   e Part names and functions   e General specifications   e Installation and wiring   e Maintenance and inspection    Use this manual together with the NJ series  CPU Unit Software User s Manual  Cat  No   W501      The following information is provided on a Con   troller built with an NJ501 CPU Unit     e CPU Unit operation  e CPU Unit features  e Initial settings    e Programming based on IEC 61131 3 lan   guage specifications    Use this manual together with the NJU series  CPU Unit Hardware User s Manual  Cat  No   W500      The settings and operation of the CPU Unit and  programming concepts for motion control are  described  Use this manual together with the  NJ series CPU Unit Hardware User s Manual   Cat  No  W500  and NJU series CPU Unit Soft   ware User   s Manual  Cat  No  W501      The instructions in the instruction set  IEC  61131 3 specifications  are described  When  programming  use this manual together with the  NJ series CPU Unit Hardware User   s Manual   Cat  No  W500  and NU series CPU Unit Soft   ware User s Manual  Cat  No
232. uction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable        Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable        3 Error Tables    p Level O     a Tae ies    NJ series  Motion Con   trol Instruc   tions  Reference  Manual  Cat   No  W508    d Same as  above    d Same as  above    d Same as  above    y Same as  above    d Same as  above    d Same as  above    d Same as  above    d Same as  above    d Same as  above     3 19    OO  I      m        O     Vu  o   lt   GU  O  c     O  OD       BINDO  uonouny  O1 UOD uono 3y  Ul s1013 E L       3 Error Tables    e Instruction input parameter    54320000 hex    54330000 hex    54340000 hex    54350000 hex    54360000 hex    54370000 hex    54380000 hex    54390000 hex    3 20    Transition  Mode Selec   tion Out of  Range    Continue  Method  Selection Out  of Range    Combine  Mode Selec   tion Out of  Range    Synchroniza   tion Start  Condition  Selection Out  of Range    Master and  Slave   Defined as  Same Axis    Master and  Auxiliary   Defined as  Same Axis    Master Slave  Axis Num   bers Not in  Ascending  Order    Incorrect  Cam Table  Specification    The parameter  specified for the  TransitionMode  input variable to a  motion control  instruction is out of  range     The value of the  reserved input vari   able 
233. umber G5 series Servo Drives with Built in   1576    Error 2    EtherCAT Communications    External Latch Input Allocation Error   G5 series Servo Drives with Built in   1576  EtherCAT Communications   Overrun Limit Error G5 series Servo Drives with Built in 1576  EtherCAT Communications   Absolute Encoder System Down G5 series Servo Drives with Built in   1576   Error EtherCAT Communications   Absolute Encoder Counter Overflow   G5 series Servo Drives with Built in 1576   Error EtherCAT Communications    NJ series Troubleshooting Manual  W503     3 79    Wi  N  m   lt   OD   gt   mr       5  O     Q   OD     O  mb  m   lt        gt   mp  O  O  Q   ui            SOT 1013   t    3 Error Tables    3 80    Event code  384F0000 hex    38500000 hex    38510000 hex    38520000 hex    40160000 hex    44010000Hex  44200000 hex  54200000 hex    54210000 hex    54220000 hex  54230000 hex  54240000 hex  54250000 hex  54270000 hex  54280000 hex    54290000 hex    542A0000 hex    542B0000 hex  542C0000 hex    542D0000 hex    542E0000 hex  542F0000 hex  54300000 hex  54310000 hex  54320000 hex    54330000 hex    54340000 hex    54350000 hex    54360000 hex    54370000 hex    54380000 hex    54390000 hex      Eventname     Functional classification Reference    Object Setting Error 1 G5 series Servo Drives with Built in   1576  EtherCAT Communications    G5 series Servo Drives with Built in 1576  EtherCAT Communications    Object Setting Error 2    G5 series Servo Drives with Built in 1576 
234. ust   ment Mode is not  enabled or the input  number is wrong     The output number  specified in Adjust   ment Mode is not  enabled or the out   put number is  wrong     The I O numbers  specified in Adjust   ment Mode are not  enabled or the I O    numbers are wrong        e The input number that was  specified in Adjustment Mode is  not enabled    The setting of the Adjustment  Input Number  device variable     AdjCh  is incorrect  so adjust   ment is not possible     The output number that was  specified in Adjustment Mode is  not enabled     The setting of the Adjustment  Output Number  device variable    AdjCh  is incorrect  so adjust   ment is not possible     The I O numbers that were  specified in Adjustment Mode  are not enabled     The setting of the Adjustment  I O Number  device variable     AdjCh  is incorrect  so adjust   ment is not possible     Reference    CJ series  Analog I O  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W490     Same as  above     Same as  above     7 CJ series Process I O Units    The section provides tables of the events that can occur in the following Units     CJ1W PDC15  CJ1W AD04U  CJ1W PH41U    pc Level O     EE Eventname   Meaning EE a aee    04600000 hex    04610000 hex    04620000 hex    348D0000 hex    647A0000 hex    647D0000 hex    647E0000 hex    3 58    A D Conver   sion Error    Cold Junction    Sensor Error    Non volatile  Memory  Error    Input Error    Zero Span  Adjustment  Period End    Zero Span  Ad
235. variable to a motion  control instruction is  out of range     The parameter  specified for the  FeedVelocity input  variable to a motion  control instruction is  out of range     The parameter  specified for the  BufferMode input  variable to a motion  control instruction is  out of range     The parameter  specified for the  CoordSystem input  variable to a motion  control instruction is  out of range     The parameter  specified for the Cir   CMode input vari   able to a motion  control instruction is  out of range     The parameter  specified for the  Direction input vari   able to a motion  control instruction is  out of range     The parameter  specified for the  PathChoice input  variable to a motion  control instruction is  out of range     The parameter  specified for the  Reference Type  input variable to a  motion control  instruction is out of  range     The parameter  specified for the  MoveMode input  variable to a motion  control instruction is  out of range     NJ series Troubleshooting Manual  W503     exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     The Feed Velocity  input vari   able FeedVelocity  is still at the  default  0      Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instruction input parameter  exceeded the valid range of the  input variable     Instr
236. was  interrupted or communications  with the Sysmac Studio were  disconnected during a down   load of the user program or the  Controller Configurations and  Setup     The user program or Controller  Configurations and Setup are  not correct because the power  supply to the Controller was  interrupted during online edit   ing    The user program or Controller  Configurations and Setup are  not correct because the power  supply to the Controller was  interrupted during a Clear All  Memory operation     Non volatile memory failed     The life of the Battery in the  CPU Unit has expired     Backup memory failure    The power supply to the Con   troller was interrupted or com   munications with the Sysmac  Studio were disconnected while  downloading the motion control  parameter settings or clearing  memory     Non volatile memory failure    Power was interrupted during  save processing for cam data    Non volatile memory failure    The required PDOs are not  mapped when the axis type is  set to a Servo axis or encoder  axis     Non volatile memory failure       pi Level O     a aTe DEE    NJ series  CPU Unit  Motion Con   trol User   s  Manual  Cat   No  W507     Same as  above     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     Event code    34630000 hex    34640000 hex    44200000 hex    74200000 hex    14630000 hex    54770000 hex    54850000 hex    54860000 hex    64450000 hex    64460000 hex    64470000 hex       3 Error T
237. was made to enable  the master function when it was  already enabled     An attempt was made to dis   able the master function when it    was already disabled     CPU Unit is not in PROGRAM  mode     More than one software switch  changed to TRUE at the same  time  Or  another software  switch changed to TRUE before  processing was completed for a  previous software switch     The master function is not  enabled     The scan list is not disabled     CPU Unit is not in PROGRAM  mode     More than one software switch  changed to TRUE at the same  time  Or  another software  switch changed to TRUE before  processing was completed for a  previous software switch       Level O     Reference    CJU series  DeviceNet  Units Opera   tion Manual for  NJ series  CPU Unit  Cat   No  W497     Same as  above     Same as  above     Same as  above     NJ series Troubleshooting Manual  W503     3 Error Tables       Lwa O     74620000 hex   Scan List An operating error        CPU Unit is not in PROGRAM CJ series  Regis  occurred when reg  mode  DeviceNet  ter Clear istering or clearing Request processing is not pos  Units Opera   Failed the scan list by per  sible in this status or the tion Manual for   forming one of the request was made when the NJ series  following opera  operation was already in CPU Unit  Cat   tions  progress  The following are the No  W497   main causes of Unit status  errors     e A software switch operation  for the master function was  executed when the master  funct
238. with Built in EtherCAT Communications               Control  Power Sup   ply Under   voltage    04A80000 hex    04A90000 hex   Overvoltage    Main Circuit  Power Sup   ply Under   voltage   Undervolt   age between  positive and  negative ter   minals     04AA0000 hex    Main Circuit  Power Sup   ply Under   voltage  AC  Cutoff  Detected     04AB0000 hex    The voltage  between the posi   tive and negative  terminals in the  control power sup   ply converter  dropped below the  specified value     The power supply   voltage exceeded   the allowable input  voltage range     If the Undervoltage  Error Selection   3508 hex  is set to  1  amomentary  power interruption  occurred between  L1 and L3 for longer  than the value  specified for the  Momentary Hold  Time  The voltage  between the posi   tive and negative  terminals in the  main power supply  converter dropped  below the specified  value while the  Servo was ON     If the Undervoltage  Error Selection   3508 hex  is set to  1  amomentary  power interruption  occurred between  L1 and L3 for longer  than the value  specified for the  Momentary Hold  Time  The voltage  between the posi   tive and negative  terminals in the  main power supply  converter dropped  below the specified  value while the  Servo was ON     NJ series Troubleshooting Manual  W503     e Power supply undervoltage  Or   the power supply voltage  dropped because there was  inrush current when the main  power supply was turned ON     A momentary power inte
239. xecuted when EtherCAT packet moni    above   Started executed when EtherCAT toring was stopped   packet monitoring was  stopped     16 1807 Packet Monitoring   A Start EtherCAT Packet e The Start EtherCAT Packet Monitor instruc    Same as  Function in Opera    Monitor instruction was tion was executed again while the EtherCAT   above   tion executed when EtherCAT packet monitoring function was already in   packet monitoring was operation        already being executed     NJ series Troubleshooting Manual  W503  3 93    3 Error Tables    Event code   16 1808 Communications  Resource Overflow   16 1C00 Explicit Message  Error   16 1C01 Incorrect Route  Path   16 1C02 CIP Handle Out of  Range   16 1C03 CIP Communica   tions Resource  Overflow   16 1C04 CIP Timeout   16 2000 Local IP Address  Setting Error   16 2001 TCP UDP Port  Already in Use   16 2002 Address Resolu   tion Failed   3 94    More than 32 EtherCAT  communications instruc   tions were executed at the  same time     An error response code  was returned for an explicit  message that was sent with  a CIP communications  instruction     The format of the route  path that is specified for a  CIP communications  instruction is not correct     The handle that is specified  for the CIP communications  instruction is not correct     The maximum resources  that you can use for CIP  communications instruc   tions at the same time was  exceeded     A CIP timeout occurred  during execution of a CIP  communications instruc   tio
240. y  After you  remove the cause of the error  execute one of the following to return to normal status     e Reset the error from the user program  the Sysmac Studio  or an NS series PT   e Cycle the power supply   e Reset the Controller from the Sysmac Studio     e Minor Fault Level  These errors prevent part of the control operations in a certain function module in the Controller   The troubleshooting for minor fault level errors is the same as the processing for partial fault level  errors     e Observations  These errors do not affect the control operations of the Controller  The observation notifies you of  potential problems before they develop into a minor fault level error or worse     NJ series Troubleshooting Manual  W503     e Information    1 Overview of Errors    Events that are classified as information provide information that do not indicate errors     Operation for Each Level    The way that the Controller operates when an event occurs depends on the level of the Controller    These errors  prevent all of  the control in a    event   Event level   Controller errors  ltem  These errors  are serious  errors that pre   Definition vent control    operations for  the entire Con   troller     e I O Bus  Check Error   PLC Func   tion Module     Event examples   Only a few exam   ples are provided  here  Refer to Sec   tion 3 Error Tables  for a list of all of  the errors     function mod   ule other than  PLC Function  Module     e Motion Con   trol Period  Exceeded  
241. y of the items from the error list to display the following information about that error  Click the  Display Switch Button to switch between displaying details and attached information and displaying  actions and corrections     Display item Description   Details Detailed information on the error is displayed  such as the probable causes   Attached information 1 Detailed information about the source of the error is displayed    through 4   Action and Correction Methods to correct the probable causes of the error are displayed     After confirming the cause of the displayed error and the conditions in which it occurred  perform the  displayed error corrections to eliminate the cause of the error     NJ series Troubleshooting Manual  W503  2 7    2 Error Troubleshooting Methods    Si Troubleshooting Sele    ontrotier Event Log    Level   Source   Source Details   Event Name      I O bus Master End Cover Missing  Partial fault EtherNet IP Communications port IP Address Duplication Error  Minor fault PLC Real Time Clock Stopped  Minor fault EtherNet IP Communications port DNS Server Connection Error 0x84030000    The End Cover is not connected to right end of the CPU Rack or an Expansion Rack  Cause    1  The End Cover is not connected to right end of the CPU Rack or an Expansion Rack    2  The End Cover is not connected properly        To eliminate the cause of the error  first select the item to perform from the Action and Correction list   When you select the appropriate step 
    