Home
        PowerLogic PM1000 Series Power Meters User Manual
         Contents
1.                                                                                                                              Parameter PM1000 PM1200  RMS VLL V12  V23  V31  VLN V1  V2  V3 s s  AA1 A2 A3      An   Neutral current m    F       L     Amps   C     V Unbal    A Unbal      PF PF1 PF2 PF3       A FS  Analog color coded load bar      RPM         Phase Angle  A1 A2 A3 a a  W W1 W2 W3      VA VA1 VA2 VA3      VAR VAR1 VAR2 VAR3      THD V 1 V 2 V 3      A 1 A2 A3      DM Demand VA  W  A m    Rising demand      Time remaining      MD Maximum demand m    Hr MD occurred m m  INTG Wh      FWD VAh F E  VARh       VARh      Run hours      ON hours m    INTR      INTG R Wh      REV R VAh      R VARh       R VARh      Run hours      ON hours m m  INTG t Wh      TOT t VAh      t VAR       t  VAR      t Run      On h      INTR      OLD Wh   C   FWD VAh      VARh       VARh      Run hours m n                      14    2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters    Chapter 1   PM1000 Series Power Meters Product Description                                                    Parameter PM1000 PM1200  OLD R Wh      REV R VAh      R VARh       R VARh      Run hours m m  OLD t Wh      TOT t  VAN      t VAR       t  VAR      t Run      RS 485 _    NOTE     FWD  Forward indicating the import of power into the plant grid  REV  Reverse indicating the export of power from the plant grid    The PM1000 series displays    e Voltage  Thr
2.                      Parameter Description Address Type PM1200  VA Apparent power  total 3001 Float    W Active power  total 3003 Float e  VAR Reactive power  total 3005 Float e  PF Average PF 3007 Float     VLL Average line to line voltage 3009 Float    VLN Average line to neutral voltage 3011 Float    A Average current 3013 Float     F Frequency  Hz 3015 Float     Reserved Reserved 3017 Long   Intr Number of interruption 3019 Long e   R phase RMS Block    e Function Code  03H Read   e Number of registers  20   e No scaling required   e Read as block only   Table 6 6  R phase RMS block   Parameter  Description Address Type PM1200  VA1 Apparent power  phase1 3031 Float     w1 Active power  phase1 3033 Float    VAR1 Reactive power  phase1 3035 Float     PF1 Power factor  phase1 3037 Float    v12 Voltage phase1 to phase2 3039 Float     V1 Voltage phase    to neutral 3041 Float     A1 Current  phase1 3043 Float    F1 Frequency  Hz 3045 Float     Reserved Reserved 3047 Long   Intr1 Number of interruption 3049 Long                                  2010 Schneider Electric  All rights reserved     55                                                                                     PM1000 Series Power Meters PLSED309039EN  Chapter 6     Data Communication 08 2010   Y phase RMS Block    e Function Code  03H Read   e Number of registers  20   e No scaling required   e Read as block only   Table 6 7  Y phase RMS block   Parameter  Description Address Type PM1200   VA2 Apparent power  
3.                   50mA to 6A    SIN COYYWWDXXXX Acc CI  1 0  Option List  RS 485 THD DM IE    44 to 277 V 50 60 Hz  lt 5 VA              gt  gt  Aux supply   Control Power     ___     44 to 277 VAC DC                   2  a   gt       a    Communication   PM1200                 NOTE   Make sure WYE Star is programmed in the power meter PROG menu  Setup   For High     leg  US connection    L1 N 120V   L2 N 208 V   L3 N 120V          2010 Schneider Electric  All rights reserved  43    PM1000 Series Power Meters  Chapter 5     Installation    PLSED309039EN  08 2010       3 phase 3 wire delta connection with two CTs and three PTs  Direct voltage connections for the input voltages L L up to 480 VAC     Figure 5 4  3 phase 3 wire delta connection    LT L2 13 LINE          4  gt          gt     hh               Use PT  if H  VAC LL  gt  481 V    st      QE    S2        0 25A       VER 03 04 00          80 to 480 Vac LL    50 mA to 6A    SIN COYYWWDXXXX Acc Cl  1 0   gt    amp  Option List  RS 485 THD DM IE           Control Power   44 to 277 VAC DC          12   gt     Aux supply      r             44 to 277 V 50 60 Hz  lt 5 VA    Communication  ra  PM1200     2  a          Y Y   LOAD          NOTE   Make sure Delta is programmed in the power meter PROG menu  setup  Leave the Vn  terminal disconnected     3 phase 3 wire open delta connection with two CTs and two PTs  Direct voltage connections for the input voltages L L up to 480 VAC     Figure 5 5  3 phase 3 wire open delta connect
4.    FwdWh Forward active energy 3123 Float      FwdVARh Forward reactive inductive 3125 Float e  energy   Reserved Reserved 3127 Float   Reserved Reserved 3129 Float   FwdVARh Forward reactive capacitive 3131 Float    energy   Reserved Reserved 3133 Float   Reserved Reserved 3135 Float   Reserved Reserved 3137 Long   FwdRunsecs   Forward run seconds 3139 Long     Reverse Integrated Block    e Function Code  03H Read   e Number of registers  20   e No scaling required   e Read as block only   Table 6 10  Reverse integrated block   Parameter  Description Address Type PM1200   RevVAh Reverse apparent energy 3151 Float      RevWh Reverse active energy 3153 Float     RevVARh Reverse reactive inductive energy 3155 Float      Reserved Reserved 3157 Float   Reserved Reserved 3159 Float   RevVARh Reverse reactive capacitive energy  3161 Float     Reserved Reserved 3163 Float   Reserved Reserved 3165 Float   Reserved Reserved 3167 Long   RevRunsecs  Reverse run seconds 3169 Long                                  2010 Schneider Electric  All rights reserved     57    PM1000 Series Power Meters PLSED309039EN  Chapter 6     Data Communication 08 2010       Total Integrated Block    e Function Code  03H Read  e Number of registers  20   e No scaling required   e Read as block only    Table 6 11  Total integrated block                                        Parameter  Description Address Type PM1200  TotVAh Total apparent energy 3181 Float     TotWh Total active energy 3183 Float    TotVARh T
5.   PM1000 Series Power Meters Technical Specification    The PM1000 series is a high accuracy  low cost  ultra compact  power  and  energy meter series  It offers ISO 9001 quality  accuracy and functional flexibility   Selective models of this series have Modbus RTU communications capability  The  standard unit flush mounts in a DIN 96 cutout and conforms to UL product  standards     The power meters are designed for retrofit applications such as replacement of  analog meters  Each can be used as standalone meter in electrical control panels   power distribution unit  PDU   switch boards  uninterrupted power supply  UPS    generator sets  and motor control center  MCC  systems  It also provides easy  communication to program logic control  PLC   distributed control system  DCS    building management system  BMS   and other systems     The following table gives the technical specifications of the power meters  Refer to     Technical data    on page 71 for more information     Table 1 6  Technical specifications       Description  Sensing Measurement    Accuracy    Specification    True RMS  one second update time  four quadrant power  and energy    1 0  of reading        Auxiliary supply   Control power     44 to 277 VAC DC          Burden Voltage and current input  lt  0 2 VA per phase  Auxiliary supply  Control power   lt  3 VA at 240 V   Display Alphanumeric bright LED   Resolution RMS four digits  INTG eight digits       Input voltage    Four voltage inputs  V1  V2  V3  VN 
6.   energy values  The value at which the power meter overflows is given below     The overflow value depends on the product of the primary voltage and current  rating     Table 2 1  Integrator overflow                                  V PRI x A PRI x Max reading Max time to Max time to   1 732  Wh VAh  reset the overflow in  integrator in months at full  Run Hours scale   1 VA to 1000 VA 9999 k 9999 13 88   1 kVA to 1000 kVA 9999 M 9999 13 88   1 MVA to 1000 MVA 9999 G 9999 13 88    gt  1000 MVA  lt 9999  lt 1 year       OLD Data Register  The power meters have an OLD data register  where the cleared INTG values will  be stored     The energy values in the integrator are transferred to the OLD register when the  INTG is cleared  manually due to overflow   Thus the OLD energy values are not  lost even after the integrator is cleared and can be viewed with the OLD  parameter     The values of parameters Wh  VAh  VARh   VARh  and Run h are stored in the  OLD register when the INTG is cleared           2010 Schneider Electric  All rights reserved  25    PM1000 Series Power Meters PLSED309039EN  Chapter 2     Quick Start Guide 08 2010       Demand Power Calculation Methods    Demand power is the energy accumulated during a specified period divided  by the length of that period  How the power meter performs this calculation  depends on the method you select  To be compatible with electric utility billing  practices  the power meter provides the following types of demand power  calcu
7.  08 2010    PM1000 Series Power Meters  Chapter 5     Installation       Auxiliary Supply  Control Power     The PM1000 power meter requires a single phase AC DC auxiliary  control  power  supply to powerup its internal electronic circuitry  External surge suppressors are  necessary in the auxiliary supply circuit for proper operation during extreme surge  conditions  where the voltage surges exceed the auxiliary supply limits  e g  rural  areas and outlying areas prone to lightning strikes    Range   e 44 to 277 VAC DC   e Burden  load   lt  3 VA at 240 V   e The control power may be derived from the voltage signals   e If you have a 440 V 3 wire delta system and a reliable neutral is not  available  use a 440 V  240 V supply transformer to provide the standard 240 V  auxiliary supply     NOTE  It is much easier to set up the meter before you mount the meter on the panel  See    Quick  setup    on page 17 for more information     PTs  VTs  and CTs    Large electrical installations have high voltages and currents  which may exceed  the direct connection rating of the power meter  In this case  potential transformers   PTs  and current transformers  CTs  are used to precisely step down or reduce  the voltage and current levels to suit the power meter rating  Potential  transformers usually have a full scale output of 110 VAC RMS line line and current  transformers usually have a full scale output of 5 A or sometimes 1 A     The PTs  VTs  and CTs must be planned  installed  and
8.  110 or 415 VACLL  nominal  Range 80 to 480 VAC LL        Input current   Energy measurement     Current inputs  A1  A2  A3   Class 1 0  50 mA to 6 A   5 mA is the starting        Frequency    45 to 65 Hz       Overload    10 A max continuous       Environmental    Operating temperature   10   C to 60   C  14   F to 140   F   Storage temperature   25   C to  70   C   13   F to 158   F   Humidity 5  to 95  non condensing          Standard CATIIl   Measurement category Ill    Pollution Degree 2    o    Double insulation at user accessible area  Weight 400 gms  0 9 lb  approx  unpacked    500 gms  1 1 Ib  approx  shipping       Communication   PM1200     RS 485 serial channel connection Industry standard Modbus  RTU protocol       PM1000 Series  conforms to    Emission   CISPR11 class A  Fast Transient  4kV IEC  61000 4 4  Surge withstand  IEC 61000 4 5    Damped Oscillatory  IEC 61000 4 12  ESD  IEC 61000 4  2   Impulse voltage  6 kV  IEC 60060  1 2 50 us       Protection against dust  and water          Front     IP 51  Back     IP 40          NOTE    Additional error of 0 05  of full scale  for power meter input current below 100 mA       16       2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 2     Quick Start Guide       Chapter 2  Quick Start Guide    PROG Menu     Setup    e The power meter must be configured to match the application settings  before  use  Otherwise  the readings will be wrong    e All the setup 
9.  15 and 16 for single point writes    To be used in cases where the slave does not support the  single point write functions 05 and 06      cme       For Help  press Fi Polls  396 Resps  394    4  The Modscan software starts polling the configured COM port for the Device ID  1    Modscan Demo software will stop polling after 3 5 minutes on successful  communication     esa File Connection Setup View Window Help  Dj celta  Eaa a e   gagga  aa aa                                           Device Id    1    paor Number of Polls  453  Address  ET MODBUS Point Type alid Slave Responses  451  Length   2  03  HOLDING REGISTER     y  Halai    3733283 2500    For Help  press F1 Polls  453 Resps  451    This shows that the power meter is communicating with the Modbus Modscan  master software successfully on the PC  The power meter is Modbus RTU  compliant        52       2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 6     Data Communication       Data Address    The PM1200 power meter supports the transfer of whole block and also of   individual data values  two registers are used for storing single data value     e In the transfer of individual data values  it treats two registers as an object with  the starting address  e g   3900  considered as the object name  This enables  you to transfer required data values for energy management    e In the transfer of the whole block  it basically treats each block as an object wit
10.  3743 Long    Reserved Reserved 3745 Float   Reserved Reserved 3747 Long   Reserved Reserved 3749 Float   Reserved Reserved 3751 Long   Reserved Reserved 3753 Float   Reserved Reserved 3755 Long   Reserved Reserved 3757 Float   Reserved Reserved 3759 Long   Reserved Reserved 3761 Float   Reserved Reserved 3763 Long   Reserved Reserved 3765 Float   Reserved Reserved 3767 Long   Reserved Reserved 3769 Float   Reserved Reserved 3771 Long   Reserved Reserved 3773 Float   Reserved Reserved 3775 Long          Note  The address 3741 is overlapped between the Demand and Max Demand blocks    Old Forward Integrated Block  e Function Code  03H Read   e Number of registers  20   e No scaling required   e Read as block only    Table 6 14  Old forward integrated block                                  Paramete  Description Address Type PM1200  OldFwdV  Old forward apparent energy  3122 Float e  OldFwdW  Old forward active energy 3124 Float e  RUE MEL  reactive inductive 3126 Float E  Reserved  Reserved 3128 Float   Reserved  Reserved 3130 Float   oa ae HS reactive capacitive 3132 Float i  Reserved  Reserved 3134 Float   Reserved  Reserved 3136 Float   Reserved  Reserved 3138 Long   er Old forward run seconds 3140 Long                                  2010 Schneider Electric  All rights reserved  59                                                                                     PM1000 Series Power Meters PLSED309039EN  Chapter 6     Data Communication 08 2010  Old Reverse Integrated Bloc
11.  Float    W2 Active power  phase 2 3933 Float    W3 Active power  phase 3 3947 Float    VAR Reactive power  total 3905 Float    VAR1 Reactive power  phase 1 3921 Float    VAR2 Reactive power  phase 2  3935 Float e  VAR3 Reactive power  phase3 3949 Float e  VA Apparent power  total 3901 Float    VA1 Apparent power  phase 1  3917 Float    VA2 Apparent power  phase 2  3931 Float    VA3 Apparent power  phase 3  3945 Float            O 2010 Schneider Electric  All rights reserved  53    PM1000 Series Power Meters  Chapter 6     Data Communication    PLSED309039EN  08 2010          Metering     Power Factor                                        PF Power factor average 3907 Float    PF1 Power factor  phase 1 3923 Float e  PF2 Power factor  phase 2 3937 Float    PF3 Power factor  phase 3 3951 Float    Parameter Description Address Type PM1200  Metering   Frequency   F Frequency  Hz 3915 Float    Power Quality   THD   21 Voltage THD  phase 1 3861 Float     V2 Voltage THD  phase 2 3863 Float    23 Voltage THD  phase 3 3865 Float     A1 Current THD  phase 1 3867 Float     A2 Current THD  phase 2 3869 Float     A3 Current THD  phase 3 3871 Float                     NOTE  The PM1200 power meter shows current THD  as      in the display and  999 0 in    communications during the following conditions   When the secondary current is  lt  0 49 A or 2 5 4 A   When the frequency is  gt  65 Hz                                                                         Energy   FwdVAh Forward appare
12.  PM1000 Series Power Meters  Chapter 5     Installation       CT Connections    Mount the current transformers  CTs  as close as possible to the power meter for  best accuracy  The following table illustrates the maximum recommended  distances for various CT sizes  assuming the connection is via 2 5 mm   14 AWG   cable     Table  5 5  CT size and maximum distance                         5 ACT size Maximum Distance in metres  in feet inch    CT to PM1000 power meter    2 5 VA 3 05 m  10 ft 120 in     5 0 VA 4 6 m  15 ft 181 in     7 5 VA 9 15 m  30 ft 360 in     10 0 VA 12 2 m  40 ft 480 in     15 0 VA 18 3 m  60 ft 720 in     30 0 VA 36 6 m  120 ft 1441 in                  e User programmable CT primary range  1 A to 99 kA AC   e CT secondary  1 Aor5A AC  programmable    Other values are also programmable to compensate CT errors if desired   e Power meters CT burden  0 2 VA maximum per input     See the    PROG menu     Setup    on page 17 for more information     NOTE     The PT primary and secondary values must be user programmed before using the power meter   Otherwise  the readings will be wrong     With dual  range CTs  select the best range for programming the power meter  If you change the range  thereafter without re programming the power meter  the power meter will read erroneous values     CT Polarity    When the power meter is connected using the CTs  you must maintain correct CT  polarities  CT polarities are dependent upon correct connections of CT leads  and  up
13.  Sane lees sence 77  o Xo fee ence sso rer T OT TTT 79       6    2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 1   PM1000 Series Power Meters Product Description       Chapter 1   PM1000 Series Power Meters  Product Description    The PM1000 series power meters are digital power meters that offer  comprehensive 3 phase electrical instrumentation and load management facilities  in a compact and rugged package     This chapter contains the main operating instructions  The remaining chapters  explain the installation and set up steps  before the meter is ready for use  and  maintenance and troubleshooting procedures for the power meter after installation     The PM1000 series power meter is an universal power meter  Before use  please  program the SYS  measurement system configuration  and the PT  VT  and CT  ratios through the front panel keys  Otherwise  it will read your system incorrectly   Other settings  such as communication parameters  must also be programmed as  needed     Schneider Electric stands behind your PM1000 power meters with complete user  support and service     Intended use  PM1000 series power meter is designed for use in industrial and  commercial installations by trained and qualified professionals  not for domestic  use     Physical Description    FRONT  The front panel has three rows of four digits characters each  with auto  scaling kilo  K   Mega  M   and minus     indications  The K and M 
14.  The display shows SET     Press    The display shows VIEW     A    Press    Use and W to scroll and view the setup parameters and their    current settings     Enter Setup Menu in Edit Mode       2      CLR EDIT 5    SET VIEW                         lt  EDIT  RMS CODE   PASS      A PRI   1 000 100 0       NOTE      means blinking    A O N a    2 Means blinking 2      From RMS  press    The display shows CLR      Press  The display shows SET      Press 2  The display shows VIEW      Press Y  The display shows EDIT  CODE entry is required to enter the setup    menu in edit mode       Press  2 for two seconds  The display shows CODE 2000 with 2 blinking  The    factory set code is 1000     6  Press Y  The display shows CODE 1000 with 1 blinking     7  Press       once or    four times to accept the new CODE value  The display  shows PASS and then EDIT A PRI 100 0 indicating the successful entry to  the setup menu in edit mode     NOTE  If you enter a wrong code  the display flashes FAIL  and then displays EDIT  Repeat the  procedure and make sure that you enter correct code        O 2010 Schneider Electric  All rights reserved     PM1000 Series Power Meters PLSED309039EN  Chapter 2     Quick Start Guide 08 2010       Setup Parameters in View and Edit Modes    NOTE  Default setup values are given in BOLD     Changing these values while device is in use is not recommended   BAUD  PRTY  and ID are applicable only for PM1200                                         20    2010 Schnei
15.  The power  meter calculates and updates the demand at the end of each interval        76       2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Appendix C     Glossary                                                                                                                                           Abbreviations   A FS   Amperes full scale  A  Amps Amperes  An Neutral current  A PRI Current primary winding  A SEC Current secondary winding  Avg Average  CLR Clear  CT Current transformer  Dia  DIAG Diagnostic  ft Feet foot  FW Firmware  FWD Forward  Hz Hertz  ID Identity  in  Inch  INTG Integrator  IP Ingress protection  kVAh Kilo volt ampere hour  kVARh Kilo volt ampere reactive hour  kWh Kilo watt hour  LSB Least significant bit  MD Maximum demand  Min Minimum  ms Milliseconds  MSB Most significant bit  O F Overflow  PF Power factor  PT Potential transformer  R d Rising demand  Rev Reverse  RPM Revolution per minute  SYS System configuration  THD Total harmonic distortion  ULOC Unlock  Unb Unbalance  V Voltage  VA Apparent power  VAh Apparent energy  VAR Reactive power  VARh Reactive energy  inductive    VARh Reactive energy  capacitive   V PRI Voltage primary winding  V SEC Voltage secondary winding  VT Voltage transformer  W Active power  Wh Active energy                2010 Schneider Electric  All rights reserved     77    PM1000 Series Power Meters PLSED309039EN  Appendix C     Glossary 08 2010          78    20
16.  block only    Table 6 17  Phase angle block                                     Parameter Description Address Type PM1200  Neutral voltage Neutral voltage 3701 Float     An Neutral current 3703 Float    V1 Voltage phase angle  phase 1 3705 Float     V2 Voltage phase angle  phase 2 3707 Float    V3 Voltage phase angle  phase 3 3709 Float     A1 Current phase angle  phase 1 3711 Float    A2 Current phase angle  phase 2 3713 Float     A3 Current phase angle  phase 3 3715 Float    RPM Rotations per minute 3717 Float                         Note  The parameters V1  V2  V3  voltage phase angles  and neutral voltage are available only through  communication     Setup Block    e Function Code  03H Read  10H Write  e Number of registers  40   e No scaling required   e Read and write as block only    Table 6 18  Setup block                         Parameter  Description Address   Type  Range Default  PM1200  value  A Pri Current primary  0101 Float  1 0 to99k 100 0    A Sec Current secondary 0103 Float  1 0 to 6 5 5 000    V Pri Voltage primary  0105 Float  100 0to999k 415 0    V Sec Voltage secondary 0107 Float  50 00 to 601 0  415 0    SYS System 0109 Float  2 0 to 6 0 3 000     Configuration 2 0     Delta  3 0     Star  4 0     Wye  5 0     2 Ph  6 0     1 Ph  LABL Phase Labeling  0111 Float 0 0 to 4 0 0 000 e  0 0     123  1 0     ABC  2 0   RST  3 0  PQR  4 0  RYB  VA Fn VA Function 0113 Float  0 0 to 1 0 0 000     selection 0 0     3D  1 0     Arth  D sel Demand Selection 0115 F
17.  iii hante dette Manette 49  Parameter Settings for Different SCADA Software sis 50  Communication Tests mini ia ele deni av ie ieee 51  Data Address sion ee i id Peed es Peeves ed Rena Deen ts 53  Individual Parameter Address    ee 53  Block Parameter Address  iii decides aiaei etienne let eal 55  Chapter 7  Maintenance and Troubleshooting                                                              nn sntre rnan annene neen 67  OJUO 2 228 san nt e AA anatase an Ten dan Ms tates saan T teen M e 67  Troubl  shooting  28e nee ie tein dt Ras ee RSR Serres annee nant sd nec lea ane ar O ant nt ete ae 68  Appendix A     Technical Data                                                                     see 71  ACCUrAC Ve nm te dette of ent an na ie dr t   ee entire ne ee 71  Auxiliary  Supply  Control POW  T  enoi AEE ER AE EAE A ENA E cldee tasdsdceebenncexsenee dist atte 71  Front Pane  l DISplay ociosos ete distrib cdot dirt niet een fie et een ne rien ee 71  Installationand INnput Ratings  2218 shegetend dota it 72  Environmental Conditions fenetres at et Net te ie tte dun tes A ma 72  ConstructiON ecos oral 72  Dimensions and Shine este id atraido 72  Appendix B  SIM  simulation  Mode         ooooooooocconcocococccccccccocononononnnccnnoncnnononncnnnnnnnn nn nn nnnnnnnnnnnn nn nn nnn nn nr nnmnnn eenn 73  Appendic Ce GIOSSAMY ii is 75  TMS  tn heed ee citi ng alts od Sd ai ne Me ee ne Me ner de Sed A dit el Ait dao Sot eee 75  ADDIE VIATONS 222  aa ane tt ane ee ata eee Rte e
18.  into decimal values   Apply the formula   MSB 256  LSB     The resulting value will be 30400 for the hexadecimal value 0x76 OxCO   Insert a 0 before the result and parse it from the right with two digits each   The result will be the FW version   03 04 00     GE ONS    Table 6 23  Firmware version interpretation                            MSB LSB  Hexadecimal 0x76 0xCO  Decimal 118 192  VALUE   MSB 256  LSB  30400  FW Version 03 04 00          NOTE  Firmware version representation only  To determine your power meter s present firmware  version  refer the diagnostic page in the power meter  See    PM1000 series power meters menu  hierarchy     on page 27 to navigate through the diagnostic page        64    2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 6     Data Communication       NOTE    e Most of the reserved and unavailable parameters return zero value    e The SCADA software must support register blocks consisting of different data types  integers and   floats  to transfer of whole block    Each Modbus register size is 16 bits  All PM1200 readings are 32 bits  Therefore  each PM1200   reading occupies two consecutive Modbus registers  For example  VA parameter absolute address is   3901  It occupies both 3901 and 3902 Modbus registers    e Address configuration  All addresses are in decimal  Some SCADA software supports Modbus  register address instead of absolute register address  In this case add 40000 to
19.  is equipped with an energy integrator function  It  provides several parameters for Energy Management  VAh  Wh  VARh  Ind      VARh  Cap   run h  run hours   on h  on hours   INTR  Interruptions   outages      A few of these need explanation    RUN h  Indicates the period the load has been ON and has run  This counter  accumulates as long as the load is ON    On h  The period for which the power meter  supply  is ON    INTR  Number of supply outages  means the number of auxiliary supply  interruptions  If the power meter auxiliary supply is from a UPS then the INTR   number of interruptions  will be zero  as long as the UPS stays ON   even if the  voltage signals die out from time to time     Integrator Overflow    The PM1000 series power meters contain a comprehensive Integrator to support  energy management  It accumulates several parameters over time  as explained  above  All values are direct readings and have a high resolution  This is necessary  for accurate energy analysis over short intervals of time  It also means that the  readings max out and reset sooner or later  as given below  Since the Integrator  contains counters for several parameters  VAh  Wh  VARh   VARh  Run Hours  On  Hours  Interruptions   they all reset together when any one of them overflows   usually Wh     but can be changed to VAh via the OF Setup   This makes energy  management calculations such as Average PF very easy     The maximum number that the power meter handles is 9 999 Giga for RMS and
20.  readings will be wrong     Selecting the voltage fuses    We strongly recommend using fuses on each of the sense voltages  except for  neutral  and the control   auxiliary power     Table 5 4  Fuse recommendation                Power Source Source voltage Fuse  A   Line voltage 80 to 600 VLL 0 25  Auxiliary supply  Control 0 25  power                 Current Signal Connections    The power meter accepts up to 6 AAC RMS per channel directly  Above that  a  current transformer must be interposed to scale down the current    There are three pairs of current input terminals marked A1  A2  and A3  Each pair  of input terminals is labeled as S1  S2 and has an arrow indicating the direction of  current flow  For proper measurements  the phase identification  and the polarity  of the current signals must be correct  The forward flow  import by consumer   current direction must be into the S1 terminal and the exit from the S2 terminal   Maintain the correct sequence and polarity to avoid wrong readings     Any unused current input terminals must be shorted together  e g   in Delta  connection  the terminals A2  S1  S2  must be shorted together  The shorted  terminals do not need to be grounded     Install the wiring for the current circuit at 480 VAC insulation as a minimum  The  cable connection should be rated for 7 5 A or greater and have a cross sectional  area of 2 5 mm     14 AWG  minimum        40       2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010   
21.  tested by a qualified  electrical contractor before wiring the power meter  The accuracy of the  measurement also depends on the accuracy and phase angle error of the PTs   VTs  and CTs  Instrument class 1 or better PTs and CTs are recommended  Do  not use protection class  10P10  etc   CTs to feed the power meters  they have  poor accuracy and phase characteristics    Ensure that the CT primary rating has been selected so that your normal load  variation lies between 40  and 80  of its full scale  If your CT is over rated  say if  the load is always less than 10  of the CT primary rating  accuracy suffers  On  the other hand  if the CT is under rated  then you may exceed its full scale and  burn out both the CT and the power meter     PT  VT   CT Wiring    The PTs  VTs  and CTs must have adequate VA rating to support the burden   loading  on the secondaries  You may want to support the auxiliary supply burden  from one of the PTs  VTs   CT wiring can impose additional burden  loading  on  the CT  For example  if the CT has a 5 A secondary and the wire resistance is 1 0  Q  then the CT has to support an additional burden of 5 VA  If the wiring distance  from the CT secondary is greater than stated in Table 5 5 on page 41  then the CT  could get over burdened and give large errors  Choosing a 1 A CT secondary can  reduce this error  The CT secondary value must be user programmed into the  power meter     The power meters should be conveniently located for easy connections of 
22.  the above address  and use it  For example  VA parameter absolute address is 3901  Modbus address can be 43901   40000 3901     e Phase Angle Block  Voltage phase angles  0 120 240  are hard coded  not measured   Hence  these  values are also available in communication in the absence of input signals  however  these voltage  phase angles are not available in the power meter display    e TURBO  and Percentage of Load Blocks  These parameters can be read individually or as a block   e TURBO block  50 parameters maximum   e Percentage of Load block  5 parameters maximum   e All power meters addresses should be set between 1 and 247    e All power meters should have uniform communication settings like Baud rate  parity and stop bit    e Use Diagnostic mode display in the power meter to analyze the problem in communication    e Error  u    Invalid unit ID   A     Invalid Address   c     CRC error  cyclic redundancy checking   t  Transmitting   r    Receiving   F     Invalid function code   o     Parity  framing or overrun error   O  Buffer overflow          2010 Schneider Electric  All rights reserved     65    PM1000 Series Power Meters PLSED309039EN  Chapter 6     Data Communication 08 2010          66    2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 7     Maintenance And Troubleshooting       Chapter 7  Maintenance and Troubleshooting    Introduction    This chapter describes information related to maintenance of
23.  the work area for tools and objects that may  have been left inside the equipment    e When removing or installing panels do not allow them to extend into the energized bus    e The successful operation of this equipment depends upon proper handling  installation   and operation  Neglecting fundamental installation requirements may lead to personal  injury as well as damage to electrical equipment or other property    e NEVER bypass external fusing    e NEVER short the secondary of a PT    e NEVER open circuit a CT  use the shorting block to short circuit the leads of the CT before  removing the connection from the power meter    e Before performing Dielectric  Hi Pot  or Megger testing on any equipment in which the  power meter is installed  disconnect all input and output wires to the power meter  High  voltage testing may damage electronic components contained in the power meter    e The power meter should be installed in a suitable electrical enclosure     Failure to follow these instructions will result in death or serious injury                   2010 Schneider Electric  All rights reserved  33    PM1000 Series Power Meters PLSED309039EN  Chapter 4     Safety Precautions 08 2010          34    2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 5     Installation       CHAPTER 5  Installation    Mechanical Installation  The PM1000 series power meters are panel mounted and have reliable  rear   mounted terminal stri
24.  your power meter     The power meter does not contain any user serviceable parts  If the power meter  requires service  contact your local sales representative  Do not open the power  meter  Opening the power meter voids the warranty     CAUTION    HAZARD OF EQUIPMENT DAMAGE   e Do not perform a Dielectric  Hi Pot  or Megger test on the power meter  test  voltages may damage the power meter     e Before performing Hi Pot or Megger testing on any equipment in  which the power meter is installed  disconnect all input and output  wires to the power meter                 Failure to follow this instruction will result in equipment damage              2010 Schneider Electric  All rights reserved     67    PM1000 Series Power Meters PLSED309039EN  Chapter 7     Maintenance And Troubleshooting 08 2010       Troubleshooting    The information in Table 7   1 describes potential problems and their possible  causes  It also includes possible checks to perform or solutions to the problems   After referring to this table  if you cannot resolve the problem  contact your local  Schneider Electric sales representative for assistance     A DANGER    HAZARD OF ELECTRIC SHOCK  EXPLOSION  OR ARC FLASH   e Apply appropriate personal protective equipment  PPE  and follow safe electrical  practices  For example  in the United States  see NFPA 70E    e This equipment must be installed and serviced only by qualified personnel    e Turn off all power supplying this equipment before working on or insid
25. 0       Save the New Value to Setup         m4 D    d       NOTE   means blinking    means blinking y  i    1  After you edit the parameter as described above  press 9  The display shows  SAVE y with blinking y     2  Press 9 or  lt  to save the new value  The display flashes PASS and then  shows EDIT     3  Press    to return to SET     NOTE  If you do not want to save the new value  press v to change the value from SAVE y to SAVE n  in step 1  Then press 2 or 9  The display flashes FAIL and shows EDIT  Proceed to step 3        22       2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 2     Quick Start Guide          Clear INTG and MD    The power meters are equipped with energy integrator INTG  where the energy  parameters are accumulated   e INTG CLR  Clear both INTG and MD values   e INTG MD  Clear only MD values  where MD is maximum demand        NOTE  means blinking    imeans blinking y    INTG Clear    1  From RMS  press  The display shows CLR   CODE entry is required to clear the INTG values     2  Press  gt  for two seconds  The display shows CODE 2000 with blinking 2   The factory set CODE is 1000     3  Press Y  The display shows CODE 1000 with blinking 1     Press     once or  gt  four times to accept the new value   After the successful CODE entry  the display shows CLR INTG     5  In order to clear INTG  press  gt    The display shows CLR INTG y with  blinking y    6  Press 2 to clear INTG  The displa
26. 010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 4     Safety Precautions       Chapter 4  Safety Precautions    This section contains important safety precautions that must be followed before  attempting to install  service  or maintain electrical equipment  Carefully read and  follow the safety precautions outlined below        DANGER    HAZARD OF ELECTRIC SHOCK  EXPLOSION  OR ARC FLASH   e Apply appropriate personal protective equipment  PPE  and follow safe electrical work  practices  In the USA  see NFPA 70E    e Only qualified electrical workers should install this equipment  Such work should be  performed only after reading this entire set of instructions    e If the equipment is not used in a manner specified by the manufacturer  the protection  provided by the equipment may be impaired    e NEVER work alone    e Before performing visual inspections  tests  or maintenance on this equipment  disconnect  all sources of electric power  Assume that all circuits are live until they have been  completely de energized  tested  and tagged  Pay particular attention to the design of the  power system  Consider all sources of power  including the possibility of back feeding    e Turn off all power supplying the power meter and the equipment in which it is installed  before working on it    e Always use a properly rated voltage sensing device to confirm that all power is off    e Before closing all covers and doors  inspect
27. 10 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Index       INDEX  AC Power Measurement    3D kVA Measurement  32  Consumption and Poor PF  32  3 phase systems  31  Auto scroll  Within page group  column of pages and TURBO  pages  12  Block parameter address    B Phase RMS block  55  Clear block  63    Forward Integrated block  Reverse Integrated  block  57    Max Demand block  OLD Forward Integrated  block  59    Model Info block  63    OLD Reverse Integrated block  OLD Total  Integrated block  60    Phase angle block  SETUP block  61  Total Integrated block  Demand block  58  Total RMS block  R phase RMS block  55  Y Phase RMS block  56  Clear  INTG  23  MD  24  Communication Test  51  Connections  Connection diagram symbols  43  Delta connection  44  Fuse recommendations  40  Open delta connection  44  Single phase connection  45  2 phase connection  45  WYE Star connection  43  Data Address  Block parameter address  53  Individual parameter address  55  Data communication  47  Daisy chaining devices to the power meter  48  Data formats and settings 49  Default display  View  page  Display lock and unlock  12  Demand Power Calculation Methods  Auto   Sliding block  User   Fixed block  26    Electrical installation  38  Energy Integrator   Integrator overflow  OLD data register  25  Front panel    Kilo  Mega  Giga and negative indicators  9  LED display  Load bar  8  INTR  25  Keys  Left  Right  Up  Down keys  10  Operati
28. 2   RMS current  phase 2  A3   RMS current  phase 3    L1      of load  phase 1  L2      of load  phase 2  L3      of load  phase 3    A  1   Current phase angle  phase 1 in degrees  A  2   Current phase angle  phase 2 in degrees  A  3   Current phase angle  phase 3 in degrees    A UNB   Current unbalance  V UNB   Voltage unbalance  RPM   RPM of the motor       An   Neutral current    VA1   Volt amperes  phase 1  VA2   Volt amperes  phase 2  VA3   Volt amperes  phase 3    W1   Watts  phase 1  W2   Watts  phase 2  W3   Watts  phase 3    VAR1   VAR  phase 1  VAR2   VAR  phase 2  VAR3   VAR  phase 3    PF1   Power factor  phase 1  PF2   Power factor  phase 2  PF3   Power factor  phase 3             2010 Schneider Electric  All rights reserved     27    PM1000 Series Power Meters PLSED309039EN  Chapter 2     Quick Start Guide 08 2010                         28    2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 2     Quick Start Guide                                      2010 Schneider Electric  All rights reserved  29    PM1000 Series Power Meters PLSED309039EN  Chapter 2     Quick Start Guide 08 2010          30    2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010    Chapter 3     AC Power Measurement       Chapter 3  AC Power Measurement    3 Phase Systems    A 3 phase system delivers higher levels of power for industrial and commercial  applications  The three phases cor
29. Baud Rate Maximum communication distances 1 to 32 devices  Meters   Typical with Belden 3105A cables    9600 1200   19200 900             NOTE  Distances listed should be used as guide only and cannot be guaranteed for non  PowerLogic  devices  Above distances subject to vary based on the quality of the cable     Daisy chaining Devices to the Power Meter    RS 485 slave port allows the power meter to be connected in a daisy chain with up  to 31 2 wire devices  In this bulletin  communications link refers to a chain of  devices that are connected by a communications cable  See Figure 6 3     Figure 6 3  Daisy chaining 2 wire devices    Belden 3105A 9841 or  equivalent    on the last device of  the daisy chain    CSSS    Towards PC    a MCT2W 485 terminator    Power Meter 1200 or other POWERLOGIC 2 wire compatible devices    NOTE  Belden 3105A 9841 colors  Blue      White           48 O 2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 6     Data Communication       e  f the power meter is the first device on the daisy chain  connect it to the host  device using a RS 232 to RS 422 RS 485 converter or RS 485 to Ethernet  converter    e If the power meter is the last device on the daisy chain  terminate it with the  terminator provided    e See    Table 6 1    on page 48  for the maximum daisy chain communications  distances for 2 wire devices    e The terminal s voltage and current ratings are compliant with the requir
30. Mode    sise 19  Enter Setup Menu in Edit Mode    eee 19  Setup Parameters in View and Edit Modes     cooooccocococccccccccccoconnonononnnnnnnnnnnononnnnnnnnnnnnnnn mn nnnnnnnnnnannnnnnncnnnnnnnanns 20  Edit Set Parameters in PROG Menu    iii 21  Editand ACCEPESO U P  gt   ardid rl en IA a A euch Da eee anne 2eme Tran 21  Save the New Value to Setup    sise 22  Cl  ar INTG and MD   into O RAR Te nt 23  Energy Integrate terne sent 25  Integrator OVA edad iaa 25  OLD   Data Register eE ee mA Tan ened nent ooh cae eee nes dite diem Hour 25  Demand Power Calculation Methods se 26  Auto  SIDING block  Fars si fics fe ceiaes cack eee RS ot dE ea 26  User  fixed block   liinda diras 26  PM1000 Series Power Meters Menu Hierarchy sise 27  Chapter 3  AC Power Measurement    31  Phase SyS enaa EE eed Pet er a AR bettas eect ete Tee Et 31  Consumption and  Poor Power Factor ia han ee rte M td ladera iia abi 32     SDS KVA   Measurement italiana 32  Chapter 4  Safety Precautions ss 33  CHAPTERS  Installation    sfr ss LE Re A Sr ns en fist mae abet cies 35  Mechanical  Installation     sota mien a A A AA dt 35  Installation Procedure  esmas A aia ir 36  US ER En EE EL RA  36  Panel Considerations and Environment sise 36  VMIOWINO atole 36  MOUNUINO cesiones 37  Electrical installations  Sane II 38  Auxiliary Supply  Control Power     iii 39  PTS   VIS  LE k DI EE IE ne A S O E E E E E A E 39  AR EVA PAG ATO PAETE EETA EE O lata neti A E E N 39  Voltage  Signal  Conne CUOMS eisor aaora en 
31. NS PLC 3900 03 HOLDING  2 Real Direct   Master  REGISTERS  12_ MOVICON 43901 Nil 2 Real Direct  13  RSVIEW 43901 03 HOLDING  2 Real Direct  REGISTERS  14  ABB Microscada  3900 Format     9 Interval     2  Real Direct          50    O 2010 Schneider Electric  All rights reserved        PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 6     Data Communication          Communication Test    Communication test  PM1200 power meter can be successfully used for    communication using Modscan software as Modbus master in PC  Details of the  settings in Modscan are given below     Settings in Modscan v3 D05 00 software to establish communication with  PM1200 power meters     e Free download demo Modscan software from http   www win tech com     e The following explains how to read apparent power total  VA total  from  register 3901       gt  ModScan32    ModSca1   em File Connection Setup View Window Help    osal fea  S  2  re   gane  aa aa                            Device Id   1  Address   3901 Number of Polls  284  ress  MODBUS Point Type Valid Slave Responses  282                                        Length   2  03  HOLDING REGISTER  gt   EC       3733283 2500       1  After starting the Modscan  to read Apparent power total  VA total   enter    address as 3901  decimal   length as 2  device ID as 1  Modbus point type as  03  and HOLDING REGISTER     2  Modify the connection details  Click connection  gt  connect  to see the    connection detail window  Change all t
32. PowerLogic    PM1000 Series Power Meters    PLSED309039EN    08 2010    10    1 0  schneider     a     gt     powerLogi  pM1000       Schneider  Electric       Hazard Categories and Special Symbols    Read these instructions carefully and look at the equipment to become familiar with  the device before trying to install  operate  service or maintain it  The following  special messages may appear throughout this manual or on the equipment to warn  of potential hazards or to call attention to information that clarifies or simplifies a  procedure     SAFETY SYMBOLS    an electrical hazard exists which will result in personal injury if the instructions are    SN The addition of either symbol to a    Danger    or    Warning    safety label indicates that  A not followed     This is the safety alert symbol  It is used to alert you to potential personal injury  hazards  Obey all safety messages that follow this symbol to avoid possible injury  or death     SAFETY MESSAGES       DANGER    DANGER indicates an imminently hazardous situation which  if not avoided  will  result in death or serious injury              WARNING    WARNING indicates a potentially hazardous situation which  if not avoided  can  result in death or serious injury                 CAUTION       CAUTION indicates a potentially hazardous situation which  if not avoided  can  result in minor or moderate injury              CAUTION    CAUTION used without the safety alert symbol  indicates a potentially hazardous  si
33. RUN     e Press Y   The display shows SIM     e Press 2  The display shows RMS SIM  You have successfully  entered the SIM mode of the power meters     To Exit from SIM mode   e Press and hold the      Until you reach the RMS page    e Press     The display shows SIM    e Press Y  The display shows RUN    e Press2  The display shows RMS indicating the exit from SIM mode           2010 Schneider Electric  All rights reserved  73    PM1000 Series Power Meters PLSED309039EN  Appendix B     SIM Mode 08 2010          74    2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Appendix C     Glossary       Appendix C  Glossary    Terms    Auto  sliding block   An interval selected from five to 30 minutes  The power  meter calculates and updates the demand every 15 seconds     Baud rate  Specifies how fast data is transmitted across a network port     Communications link  A chain of devices connected by a communications cable  to a communications port     Current Transformer  CT   Current transformers for current inputs     Demand  Average value of a quantity  such as power  over a specified interval of  time     Firmware  Operating system within the power meter     Float  A 32 bit floating point value returned by a register  See    Data Address    on  page 53 for more information      Forward  Importing the power into the plant grid   Frequency  Number of cycles in one second   Line to line voltages  Measurement of the RMS line to line v
34. ages sequentially  every five  seconds  without constant key pressing  This is convenient for viewing from a  distance  The power meter shows the parameter name  one second  followed by  the value  four seconds  on the same large displays     e To auto scroll within a page group  e g   Within RMS group     Go to a particular page in the desired page group  Press   continuously for  three seconds and then release  The display flashes AUTO and starts auto scroll  within the page group    e To auto scroll down the entire column of pages    Go to the desired page  Press Y continuously for three seconds and then  release  The display flashes AUTO and starts auto scroll down the entire column  of pages    e To auto scroll through TURBO pages    Press of 3 continuously for three seconds and then release  The display  flashes AUTO and starts auto scroll through the TURBO pages     NOTE   Press any key to revert to manual scrolling   Auto scrolling is not possible in the setup parameters     Default Display  View  Page    You can select any page as user set default display page  You can scroll to other  display pages  The user set page is displayed two minutes after manual scrolling  was stopped by the user    To lock the user set default page    e Go to the page you want to set as default page     e Press and 2 simultaneously to lock the page  The power meter displays  LOCK   To unlock the user set default page     e Once default display page is active  press    and 2 simultaneously 
35. al and  phase to phase   currents  per phase and average   Watts  VARs  VA  power  factor  frequency  kWh  kVAh  and kVARh    e The power meters display average volts  amps  and frequency simultaneously    e Load bar graph for the indication of consumption in terms of   amperes total    e Set of four red LED   s in the load bar start blinking when the load is greater than  120   to indicate overload           2010 Schneider Electric  All rights reserved  71    PM1000 Series Power Meters PLSED309039EN  Appendix A     Technical Data 08 2010       e Easy setup through keys located on the faceplate for common configuration  parameters     e Password protection for setup parameters   e User selectable default display page through keypad lock     Installation and Input Ratings    e Auto ranging voltage inputs should allow direct connection up to 277  VLN 480VLL AC systems  no PTs  VTs  required up to 480 VLL phase to  phase     e Supports the following configurations  field configurable     Direct 4 wire Wye  Star   3 wire Wye  Star   3 wire Delta  2 phase 3 wire  2   phase   and single phase    e 3 phase voltage  and current inputs    e Volts   46 to 277 VAC phase neutral  80 to 480 VAC phase phase   Overload  Continuous 480 VLL with full accuracy  750 VLL Max  Hz  50   60     Amps  50 mA to 6 A  Overload  10 A continuous  50 A for three seconds     User programmable for 5 A or 1 A secondary CTs     Burden  Load   Less than 0 2 VA per Volt   Ampere input     Frequency  Both input 
36. and auxiliary   50   60 Hz  45 to 65 Hz    Environmental Conditions    e Sealed dust  proof construction  Meets IP51 for the front panel and IP40 for rear  panel     e Operating temperature   10   C to 60   C    14   F to 140   F   e Storage temperature   25   C to 70   C    13   F to 158   F   e Humidity  5  to 95   non condensing    Construction    e Self extinguishable VO plastic  double insulation at accessible areas   e Pollution Degree Il   e Measurements Category Ill     Dimensions and Shipping    e Basic unit installed depth 82 mm  3 23 in   with the protected cover with 92 x 92  mm  3 62 x 3 62 in   panel cutout  flush mount    e Bezels dimension 96 x 96 mm  3 78 x 3 78 in    Panel Cut out 92x92 mm  3 62  x 3 62 in      e Weight 400 gms  0 9 Ib  approx unpacked  500 gms  1 1 Ib  approx shipping   See    Mechanical Installation    on page 35 for more information        72    2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Appendix B     SIM Mode       Appendix B  SIM  simulation  Mode    The PM1000 series power meters are provided with SIM mode for demo and  exhibition display  where the user can see the functioning of the power meter  without any input signals  The power meter will show a fixed voltage  current   frequency  and 0 5PF  Power and energy parameters are calculated based on the  V      and PF displayed     To Enter SIM mode    e Keep the  lt  pressed  while powering up the power meter  The display shows  
37. c  All rights reserved     49    PM1000 Series Power Meters  Chapter 6     Data Communication    PLSED309039EN  08 2010       Parameter Settings for Different SCADA Software    The following table explains how to read the parameter VA  See    Individual  parameter address    on page 53 for more information  in different Modbus master  software PLC   s     Table 6 3  Parameter settings                                                             SL  SCADA software  Start Function No  of Data Type Remarks  No Address  Code Register  1  ION    Enterprise  43901 Internally 2 Swapped Float Direct  configured conversion  2  PowerLogic 43901 Internally 2 Real Direct  SCADA configured conversion  3  Vijeo Citect 43901 Internally 2 Real Direct  configured conversion  4  Intouch 43901 F Nil 2 Float Direct  conversion  5  Modscan 3901 03     2 Floating point  Unswapped FP   Master  HOLDING mode  REGISTERS  6  MODTEST 43901 03     Points  1  Float   Rosemount Rosemount  7  CIMPLICITY 43901 Nil 100 Real Direct  conversion  The  array concept  can be used  here to poll all  the data in  single scan   8  Allenbradly     43901 03 HOLDING  2 Floating point  Direct  Micrologix PLC REGISTERS   Slave Master   9  GE Fanuc PLC 43901 03 HOLDING  2 Real Direct  REGISTERS  10  ABB RTU 560 Index 3900  03  Read Query MFI     Analog  Under sub   Mater  HOLDING Range  2  measured parameters   REGISTERS Floating value     Sign and  Exponent in  First Register     should be  disabled   Unchecked   11  SEIME
38. chneider Electric ConPAD  Power meter programming and basic data reading  utility    Data port has built in impedance matched design for low reflectance on long  data cables at high Baud rates  Eliminates need for complicated impedance  matching resistors at the ends of long data cables     Fast 16 ms power meter response  average time to read 10 parameters is 90 to  100 ms  9600 Baud  Even parity  One stop bit     Direct reading  pre scaled Float readings  Accurate  full precision low  and high  readings  No need for additional scaling factors or decimal adjustment    Fast  easy to use grouping of parameters tuned for field requirements    TURBO area for single point polling  upto 50 per query    Block area for even faster access to pre configured data blocks    Figure 6 1  2 wire half duplex communication connection    PM1200 power meters rear view    RS 485  communication port                                                                            O 2010 Schneider Electric  All rights reserved     47    PM1000 Series Power Meters    PLSED309039EN  Chapter 6     Data Communication    08 2010       Figure 6 2  Closed loop  2 wire half duplex   Advantage     Reliable communications  tolerant to one break in the cable     PM1200 power meters rear view    RS485  communication port          RS485 Data  Converter                 a  N  w  N                   0 sevsy                           Communication Capabilities    Table 6 1  RS 485 communication distances                
39. der Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 2     Quick Start Guide       Edit Set Parameters in PROG Menu    This example explains how to edit the value of A SEC from 5 000 to 1 000 in  PROG menu setup of the power meter    For easy understanding  setup parameter editing is explained two parts  edit and  accept setup  and to save the new value in the setup     NOTE  After entering into setup  when there is no key press for  gt  2 min  the power meter will exit from  the setup automatically     Edit and Accept Setup                                SET  gt  view       FA  CLR EDIT      ODE    12 000  p   gt    DE    KES 171000 PASS  J y C  EDIT  A PRI  100 0  EDIT EDIT    ASEC   A SEC  5 000    5 000      se i    EDIT    4 EDIT  A SEC     A SEC    13000 1000    ve    NOTE    means blinking  2 Means blinking 2    1  After you have successfully entered setup menu in edit mode   Refer to    Enter    setup menu in Edit mode    on page 19 for more information  press Y    The  display shows EDIT A SEC 5 000     2  Press      The display shows EDIT A SEC 5 000 with blinking 5  The value can  be edited     3  Press v four times  The display shows EDIT A SEC 1 000 with blinking 1     4  Press    to accept the new value     To edit the next parameter  press Y    and repeat the above steps           2010 Schneider Electric  All rights reserved  21    PM1000 Series Power Meters  Chapter 2     Quick Start Guide    PLSED309039EN  08 201
40. e    e Always use a properly rated voltage sensing device to confirm that all power is  off    e Carefully inspect the work area for tools and objects that may have been left  inside the equipment    e Use caution while removing or installing panels so that they do not extend into  the energized bus  avoid handling the panels  which could cause personal injury    Failure to follow these instructions will result in death or serious injury              Table 7 1  Trouble shooting       Potential Problem Possible Cause Possible Solution   The data being displayed Incorrect setup values Check that the correct   is inaccurate or not what values have been entered  you expect  for power meter setup    parameters  CT and PT  ratings  system type  and  so on   See    PROG menu    Setup    on page 17 for  setup instructions     Usage of protection class Use instrument class 1 or   10P10 etc   CTs PTs better CTs PTs  which will  have better accuracy than  the protection class  CTs PTs     Improper wiring Check whether all the PTs  and CTs are connected  properly  proper polarity is  observed  and that they  are energized  Check  shorting terminals  See     connection diagrams    on  page 43 for more                information   Active Power  W  reading CT may be reversed Check and correct the CT  is negative connections   Power may be in export 1 Check the mode  If the  mode mode is in import  s1 s2    need to be interchanged  in one or two or in all the  three phases  Under  this condi
41. ed in  This means that two voltage  terminals and one current terminal described in the following section need to be  wired  For Single phase wiring configuration  see    Single phase connection with  1 CT    on page 45 for more information        42    O 2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 5     Installation       Phase Labels    The phase labels shown on the display are programmable via the power meters  front panel PROG menu  You can setup the meter to display phase labels  convenient to your practice  The choices available are  123  factory set   RYB   RST  PQR  ABC     Connection Diagrams    Choose the diagram below that best describes your application  You must ensure  that the CT phase and corresponding PT phase are identical and that the CT  polarity is correct  Follow the outlined procedure to verify correct connection     Connection Diagram Symbols  Table 5 6  Connection diagrams symbols                                              Symbol Description   AT Fuse      an Current transformer    Shorting block   Et Potential transformer             3 phase 4 wire WYE connection with three CTs and three PTs  Direct voltage connection for the input voltages L L up to 480 VAC     Figure 5 3  3 phase 4 wire WYE connection    L1 L2 L3 N LINE       gt         1      4  gt     4   t    PTI                         Use PT  if  VAC LL  gt 481 V                    VER 03 04 00       S2     80 to 480 Vac LL  
42. ee voltage measurements line to line  1 2  2 3  3 1  and average   Three voltage measurements line to neutral  1 4  2 4  3 4  and average    e Current  Three current measurements phase wise  1  2  3   average current of  all three phases  neutral current  and three current phase angles  A1  A2  A3   with respect to the corresponding voltage line neutral vector    e Phase wise load in    Three currents in   of the FS   A FS     e Unbalanced load in    Current and voltage unbalance    e Frequency  Measures from whichever phase is active    e RPM  Measures the speed of the generator    e Power  VA  W  VAR  per phase and total  PF per phase and average  Per Phase  W readings provide a quick CT Polarity Check  A negated W phase reading  indicates CT reversal    e Energy  VAh  Wh   VARh  Ind    VARh  Cap   Run hours  On Hrs  supply  interruptions  outage     e Energy  OLD   VAh  Wh   VARh  Ind    VARh  Cap   Run hours    e   Amperes load bar graph  Load bar graph indicates consumption in terms of   Amperes total  You can quickly estimate the load by viewing the display  without operating any keys  The bar graph consists of 12 segments  Each  segment indicates a current load of 10  of CT primary    e Kilo  Mega  Giga indication for the above parameters  See    The indicators    on  page 9 for more information        O 2010 Schneider Electric  All rights reserved  15    PM1000 Series Power Meters PLSED309039EN  Chapter 1     PM1000 Series Power Meters Product Description 08 2010     
43. ements of  the ElA RS 485 communications standard     Data Formats and Settings    Your SCADA software must be configured for Modbus RTU communication   before integrating the Schneider Electric PM1200 power meter     The mode of transmission is defined in the following which is compatible with  Modbus RTU Mode     Table 6 2  Power meter communication and protocol settings       Power meter communication settings                            Protocol Modbus RTU  Data bits 8  Baud rate 9600 Baud  User set 1200 to 19200  Range 1200  2400  4800  9600  19200  Normal use  9600 Baud  Noisy  EMI  RFI  long data cable  4800 2400 Baud  Short cable   lt 300 meters or 975 feet   19200 Baud  Parity Even  Device Address 1  Stop bit 1  Modbus Protocol  Device Address 1 to 247    Upto 247 meters per COM port with repeaters             Function Code 03  Read   Data Address Refer to  Data address    on page 53 for more information  Data type 32 bit float  real       e All parameters     e Direct reading  little endian float  no scaling required    32 bit unsigned integer      e INTR  number of interruptions  outages    RMS Blocks     e RunSec  Run seconds     Integ Block        No of Registers          2 to 50  optional  per PM1200 data block of 10 x 32 bit values must    be configured to suit the power meter          NOTE  The polling interval to poll the data from PM1200 will depend on baud rate  We recommend    polling interval of one second at 9600 Baud rate           2010 Schneider Electri
44. esired direction     Follow these simple steps   e First take a quick look at what the keys do     Navigation Concept        RMS    VLL    v12  A 23      PF 4 31    Y       The following example explains how you can navigate from the RMS page to the  VLN A F page  back to RMS in the power meters     1  From the RMS page  press 2 The display shows VLL    A  PF  2  Now press Y  The display shows VLN  A  F    3  To return to RMS  press  lt  The display shows RMS     Using the left key  you can go back towards to the main parameter pages from the   sub parameter pages    e Now  try getting around to other parameters  by moving up  down  right  and left   The readings are organized as display pages to the right of RMS and INTG    e The Kilo  Mega  and Negative Indicators are automatic  Kilo and Mega light up  together to show Giga  See    The indicators    on page 9 for more information    e You cannot go right into CLR  to clear INTG and MD values  unless you enter a  code    e Going right through SET  you can go down to VIEW or EDIT  Going right through  EDIT requires code entry to program these power meter settings  When done    e Go Left all the way back to SET    e Go down to CLR    e Go Right into RMS to view the display pages again        O 2010 Schneider Electric  All rights reserved  11    PM1000 Series Power Meters PLSED309039EN  Chapter 1     PM1000 Series Power Meters Product Description 08 2010       Auto scroll   Auto scroll allows you to monitor a group of display p
45. eter name right on the large  alphanumeric readouts    e For the first time in a panel meter  the parameter name is as clearly readable as  the value    e In order to know which parameter value is currently displayed  the power meter  displays the parameter name for two seconds  as well as each time you press a  key  and then the value for eight seconds    e This method also allows programmable phase soft Labels in the power meters   You can choose from 123  factory setting   ABC  RYB  PQR or RST     Analog Load Bar    e Unique indication of total load   with respect to the full scale through the 12 LEDs  at the right side of the display    e This is bar graph  where each LED indicates 10  of load    e To find the total load  count the number of illuminated LEDs  then multiply by 10     Table 1 1  Load percentage and bar graph indication          Load Bar graph display  percentage  Less than No LEDs are lit     10   Between 10 to Amber LEDs are lit              40     Between 50 to Green LEDs are lit to indicate that the load is acceptable and should not  80  increase further    Above 80  Red LEDs are lit to indicate that the load has exceeded the sanctioned             limit and is dangerous           8    2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 1     PM1000 Series Power Meters Product Description       The Indicators     Kilo  Mega  and Negative    Table 1 2 Indicators       Kilo  When lit  indicates tha
46. eters PLSED309039EN  Chapter 7     Maintenance And Troubleshooting 08 2010          70    2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Appendix A     Technical Data       Appendix A     Technical Data    Accuracy    Table A 1  Accuracy                                                    Measurement Accuracy   of Reading  Class 1 0   Voltage LN per phase and average 1 0   Voltage LL per phase and average 1 0   Amp per phase and average 1 0   Amp  phase angle per phase 2     Frequency 0 1   Active power   kW  per phase and total 1 0   Reactive power   kVAR  per phase and 2 0   total   Apparent power   kVA  per phase and 1 0   total   Active energy  kWh  Import Export 1 0   Reactive energy  kVARh   Inductive   2 0   Capacitive    Apparent energy   KVAh  1 0   RPM 1 0  NOTE     Additional error of 0 05   of full scale for input current below 100 mA   PF error limit is same as W error limit in       Auxiliary supply  Control power     The power meter needs a single phase AC or DC control supply to power its  internal electronics     Range  44 to 277 VAC DC     Burden  load   0 2 VA max for each phase input voltage and current 3 VA max on  Auxiliary supply     Front Panel Display    e Brilliant three lines four digit  digit height 14 2 mm 0 56 in   per line  high  readability alpha numeric LED display with auto scaling capability for Kilo  Mega   Giga    e The display provides the user access to all phase voltages  phase to neutr
47. ficient setup  read the setup parameters first and then edit the required setup  parameter value        62       2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 6     Data Communication       Clear Block   e Function Code  10H Write  e Number of registers  2   e No scaling required   e Write as block only    Table 6 19  Clear block       Parameter Description Address  Type Range PM1200  CLR_INTG_DMD  INTG and demand 0311 Long  1  INTG and     _SETDEFAULT _ clearing and setting up MD Clear  the setup default 2   MD Clear  256   Setup  default                            NOTE  For setup default  the power meter will send an exception for values other than 256     Model Info Block    e Function Code  03H Read  e Number of registers  14   e No scaling required   e Read as block only    Table 6 20  Model Info Block                Parameter Description Address  Type  Range PM1200  Reserved Reserved 0081 Long  Reserved Reserved 0083 Long  Model Version Model  Options and 0085 Long  Bits 30 to 24 for  e  version numbers model number   Bits 23 to 16 for  options    Bits 15 to O for  version number  E g   PM1200  model no is 22                               Reserved Reserved 0087 Long  Reserved Reserved 0089 Long  Reserved Reserved 0091 Long  Reserved Reserved 0093 Long       Model Register Details   This section explains about the model register and helps you to understand the  model number  version number  and options    The f
48. h  the starting address  e g  3000  considered as the object name  This enables  fast block transfers  since energy management usually requires a block of  related readings for the same point of time  This method also eliminates time   skew within readings of that block    e The device address  block start address  number of registers  must be  configured to suit the power meter  You must also make the related SCADA  settings for polling priority  logging  and viewing the data  Refer your SCADA  software instructions to learn how to do this     Individual Parameter Address    e Function Code  03 Read  e No scaling required  e Read as block or individual parameters    Table 6 4  Individual parameter address                                                                                                       Parameter Description Address Type PM1200  Metering   Metering   Current   A Current average 3913 Float    A1 Current  phase 1 3929 Float d  A2 Current  phase 2 3943 Float    A3 Current  phase 3 3957 Float     Metering     Voltage   VLL Line to line average voltage  3909 Float     VLN Line to neutral voltage 3911 Float    V12 Voltage phase 1 to phase 2  3925 Float e  V23 Voltage phase 2 to phase 3  3939 Float    31 Voltage phase 3 to phase 1  3953 Float     V1 Voltage phase 1 to neutral  3927 Float e  V2 Voltage phase 2 to neutral  3941 Float e  V3 Voltage phase 3 to neutral  3955 Float    Metering   Power   Ww Active power  total 3903 Float    W1 Active power  phase 1 3919
49. he settings to match the following  screen  These are default settings of PM1200 power meter     7 ModScan32    ModSca1     Disul ERA 82w     aajne m a 9 8        Device Id             Address   3901 Number of Polls  396       MODBUS Point Type             Length   2 03  HOTTE       Connect Using     Direct Connection to COM4       Configuration  Hardware Flow Control           Device NOT CONNE    R  3733283 2500 cane    I Wait for DSR from slave   Delay  0 msafterRTS before  transmitting fest character   I Wait for CTS from slave   Delay fo ms after last character  before releasing RTS       Word Length        Parity           Le  Le  Let Le          Stop Bits     Protocol Selections  Corea    For Help  press F1          2010 Schneider Electric  All rights reserved     51    PM1000 Series Power Meters  Chapter 6     Data Communication    PLSED309039EN  08 2010       3  Set the Modbus protocol selections  On Connection details window  shown in  previous step   click on Protocol Selections  Enter the protocol settings as  shown below and click OK in all the windows        77 ModScan32    ModSca1         olsa  Blk  S  2  r  aaa  a a E   Device Id   MODBUS Point Tune   Length   2  03  HO Connection Details                         Address   3901       Number of Polls  396                L   Modbus Protocol Selections    STANDARD DANIEL ENRON OMNI     ascil   ATU C ASCII C RTU       Device NOT CONNECT d Slave Response Timeout    3733283 2500 1200  msecs     IT Force modbus command
50. indicators lit  together to show Giga readings  The load bar graph to the right of the display  gives the indication of consumption in terms of the   amperes load with respect to  the FS  full scale  selected  Five smart keys make navigating the parameters very  quick and intuitive for viewing data and configuring the power meter     REAR  The voltage and current terminals and the communication port are located  on the back of the power meter  Refer to    Rear Panel    on page 13 for more  information           2010 Schneider Electric  All rights reserved  7    PM1000 Series Power Meters PLSED309039EN  Chapter 1     PM1000 Series Power Meters Product Description 08 2010       Front Panel    The front panel contains the following indicators and controls    e Three rows of alphanumeric displays  four digits each  display three RMS  parameters simultaneously or one energy parameter  The displayed readings  update every second    e For each row  Kilo  Mega  Kilo   Mega   Giga  indicator  and a Negative      indicator    e Load bar  which gives a unique analog indication of   loading    FS CT Pri     e Five keys to scroll through the display page     Figure 1 1  Parts of PM1000 series front panel    120  AFS    ue   Eight segment  Indicators 7 LED die    gt  Analog  load bar    G Electri    Schneider    lt   Q ga Keys  PowerLogic    d  v   PM1200       Eight segment LED display   e The power meter solves the problem of tiny cluttered indicators by prominently  displaying the param
51. ion    L1 L2 L3                                 LINE     gt     t  gt    gt  m  Use PT  if    VAC LL 481V    S e     Ss 0 25A  es  oF  sz     2  CT o                      50mA to 6A    SIN COYYWWDXXXX Acc Cl  1 0  Option List  RS 485 THD DM IE    44 to 277 V 50 60 Hz  lt 5 VA           LE        gt  Aux supply   Control Power   44 to 277 VAC DC       7      Aux Supply          f            AN             Communication   PM1200     2  a   gt    amp   a    NOTE  Make sure Delta is programmed in the power meter PROG menu setup        44       2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 5     Installation       2 phase 3 wire connection with two CTs    Direct voltage connections for the input voltages L L up to 480 VAC  Otherwise   two PTs    Figure 5 6  2 phase 3 wire connection                                                                            L1 L2 N  LINE     gt            PT if VAC LL  gt 481 V  st 2 3  0      0   g 0 25A  Ss  oo a    S2 El  CT 8  Ss a      amp S  2e ow   lt  Y 3  lt   E 8     gt   s2 8    a9  TFE  AE a  gif    OO 2 Bhg Aux supply  p  gt   B  Control Power   oa E 44 to 277 VACIDC  O s e    533  T Y Y Loan RS 485 Communication   PM1200     NOTE  Make sure 2 phase is programmed in the power meter PROG menu  setup     Single phase connection with 1 CT    Direct voltage connections for voltages up to 480 VAC LL  Otherwise  use one PT    1  Program the power meter in single phase mode   Howeve
52. is class A digital apparatus complies with Canadian ICES 003     Modifications  Modifications to this device which are not approved by Schneider  Electric may void the authority granted to the user by the FCC to operate this  equipment           2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters       08 2010 Table of contents  Chapter 1     PM1000 Series Power Meters Product Description                                                        7  PhYSICAlDSSCrPUON fiat ares mn nn Prague nn Faas EE an Tears ena aaah inate Mea oti ee 7  Front Panela Ae oera an lente A ica 8  Eight s  gment LED display  ntm Re Aia 8  Analog Load Bari a dira 8  The Indicators     Kilo  Mega  and Negative                                                 ana EEEn nn nn rra nannnnnnns 9  SMART KREVS ER etes aa 10  Keypad Operation talas 11  VOETE OIl AE RE aia 12  Default Display  View  Paga aeara EN EER AAE E A AAEE T EAEE E E E REA 12  RearPanel EE AE EE T E E A A A  13  Parameters with PM1000 Series Power Meters                                                        14  PM1000 Series Power Meters Technical Specification                                                             nnne ee nt 16  Chapter 2   Quick  Start Guide  irrino id fe Aten de ave asda aed Sage rate 17  PROG Menu Setup e traia ai bet it ibi Deut baat 17  Quick setup     While powering ON    nn nn anne nn nnnn nn nana nnnnnnnnnnnnnnnannnnnnnnnnininanns 17  Enter Setup Menu in View  Read Only  
53. k   e Function Code  03H Read  e Number of registers  20  e No scaling required  e Read as block only  Table 6 15  Old reverse integrated block  Parameter Description Address Type PM1200  OldRevVAh Old reverse apparent energy 3152 Float     OldRevWh Old reverse active energy 3154 Float    OldRevVARh pee reactive inductive 3156 Float    Reserved Reserved 3158 Float  Reserved Reserved 3160 Float  OldRevVARh oy reactive capacitive 3162 Float    Reserved Reserved 3164 Float  Reserved Reserved 3166 Float  Reserved Reserved 3168 Long  OldRevRunsecs  Old reverse run seconds 3170 Long    Old Total Integrated Block   e Function Code  03H Read  e Number of registers  20  e No scaling required  e Read as block only  Table 6 16  Old total integrated block  Parameter Description Address Type PM1200  OldTotVAh Old total apparent energy 3182 Float e  OldTotWh Old total active energy 3184 Float e  OldTotVARh Old total reactive inductive energy 3186 Float e  Reserved Reserved 3188 Float  Reserved Reserved 3190 Float  OldTotVARh Old total reactive capacitive energy 3192 Float e  Reserved Reserved 3194 Float  Reserved Reserved 3196 Float  Reserved Reserved 3198 Long  OldTotRunsecs   Old total run seconds 3200 Long e                            60       2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 6     Data Communication       Phase Angle Block    e Function Code  03H Read  e Number of registers  18   e No scaling required   e Read as
54. lations    e Auto  sliding block    e User  fixed block     Auto  sliding block     In the auto demand power calculation  you select an interval between five and 30  minutes in steps of five minutes  The demand calculation updates every 15  seconds     Auto demand power calculation is the default calculation for PM1000 series power  meters     User  fixed block     In the user demand power calculation  you select an interval between five and 30  minutes in steps of five minutes  The demand calculation updates at the end of the  interval  User demand power calculation can be selected through setup  See     Setup parameters in View and Edit modes    on page 20 for more information     15 minute interval   Demand value is the       average for the last    Calculation updates completed interval    every 15 seconds    Time  15 30 45 60  second   Auto  Sliding block  demand calculation    4 Demand value is the  average for the last  completed interval    15 minute interval 15 minute interval    Time   Second        User  Fixed block  demand calculation       26    2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 2     Quick Start Guide       PM1000 Series Power Meters Menu Hierarchy             V12   RMS voltage  phase 12  V23   RMS voltage  phase 23  V31   RMS voltage  phase 31    V1   RMS voltage phase 1 to neutral  V2   RMS voltage phase 2 to neutral  V3   RMS voltage phase 3 to neutral    A1   RMS current  phase 1  A
55. loat  0 0 to 1 0 0 000     0 0     Auto  1 0     User  D Par Demand 0117 Float  0 0 to 2 0 0 000     parameter 0 0  VA  1 0  W  2 0 A                                     2010 Schneider Electric  All rights reserved  61    PM1000 Series Power Meters  Chapter 6     Data Communication    PLSED309039EN  08 2010          Parameter    Description    Address    Type    Range    Default  value    PM1200       D Prd    Demand period    0119    Float    1 0 to 6 0  1 0     5 Min  2 0     10 Min  3 0     15 Min  4 0     20 Min  5 0     25 Min  6 0     30 Min    3 000       BAUD    Baud rate    0121    Float    1 0 to 5 0  1 0     1200  2 0     2400  3 0     4800  4 0     9600  5 0     19200    4 000       PRTY    Parity and stop bit    0123    Float    0 0 to5 0  0 0     Even 1  1 0     Even 2  2 0     Odd 1  3 0     Odd 2  4 0     No 1  5 0     No 2    0 000       Unit ID    0125    Float    1 0 to 255 0    1 000       F S       Full scale    0127    Float    1 to 100    100 0       OFLo    Overflow  parameter  selection    0129    Float    0 0 to 1 0  0 0     Wh  1 0   VAh    0 000       POLE    Number of poles  for RPM    0131    Float    1 0 to 8 0  1 0 2  2 0 4  3 0 6  4 0     8  5 0     10  6 0     12  7 0     14  8 0     16    2 000       PWD    Password    0133    Float    1000    1000       Reserved    Reserved    0135    Float    2 0       Reserved    Reserved    0137    Float    4126          Reserved       Reserved       0139       Float          0 0             NOTE  For ef
56. mental bezel dimension 96 x 96 mm  3 78 x 3 78 in     Depth behind bezel 80 mm  3 15 in    82 mm  3 23 in   with terminal  cover  Leave clearance for wires    Mounting clamps screws Slotted  two numbers   Terminal screws Combination Phillips and Slotted head       The cut out should be punched with the proper tool and should be free from burrs   The following figure explains the mounting of the power meter     Figure 5 2  Mounting       Remove the  mounting clamps  from the power    meter     2    Gently slide the power meter  through the cut out           Put the mounting clamps back in the power meter  and tighten the mounting clamps screws     While supporting the power meter from the front  tighten both side clamp screws in  a criss cross pattern till all slack is taken up and then apply one full turn  Do not  over tighten  Over tightening could result in breaking of the clamps     The power meter should be separated from other equipments and sufficient space  must be provided all around the power meter  to allow air to rise vertically around  the power meter  Lack of sufficient air for cooling may result in over heating of the  power meter     NOTE  It is much easier to set up the meter before you mount the power meter on the panel  See     Quick setup    on page 17 for more information           2010 Schneider Electric  All rights reserved  37    PM1000 Series Power Meters PLSED309039EN  Chapter 5     Installation 08 2010       Electrical Installation    This section de
57. net ERA AA TREE R E TORE 40  PTCONNeClOnS a TE EE O EE E E E ET 40  S  lectingithe Voltage USOS ici OREA EORR TR 40          2010 Schneider Electric  All rights reserved  5    PM1000 Series Power Meters PLSED309039EN    Table of contents    08 2010       Current Signal Connections cia animent a etre da 40  CT Conn  ctions ssh aa tated leads and tein a eaa aa aa eee aaa aes ed 41   GT Polatity ir td ii die ad aoe otic vos reed Medinek 41   GT Connection  Reversal sitter rm lee den A ee Hauge on di 41  Setup    System Types catch int nt nda atten deine ad tre trente ser 42  Phase Labels  ssl en A A eae en ras A 43  Connection  Diagrams x  hentai A en et ade eee 43  Connection Diagram Symbols aroi a a padre ta 43  3 phase 4 wire WYE connection with three CTs and three PTS               cccceceeeeceeceeeeeeeeeeeeeeaeceeeeeeeeeeseaeees 43  3 phase 3 wire delta connection with two CTs and three PTS               cccceceeeeeeeeeeceeeeeeeseeeeecaeeeeeeeeeteesnaeees 44  3 phase 3 wire open delta connection with two CTs and two PTs                                                          44  Figure 5 5  3 phase 3 wire open delta connection ss 44  2 phase 3 wire connection with two CTS iii 45  Single phase connection with 1 CT    iii 45  Chapter 6  Data Communication    47  RS 485 Data Port  25 a ia T A dde A Gada ate at dl 47  Installation voii a Aileen aaa eine ied 47  Communication Capabilities sense 48  Daisy chaining Devices to the Power Meter    sis 48  Data Formats  anid Settings
58. nt energy  3959 Float   FwdWh Forward active energy 3961 Float   FwdVARh Forward reactive inductive  3963 Float  energy   FwdVARh Forward reactive capacitive  3965 Float    energy   RevVAh Reverse apparent energy  3967 Float   RevWh Reverse active energy 3969 Float   RevVARh Reverse reactive inductive  3971 Float  Energy   RevVARh Reverse reactive capacitive  3973 Float e  Energy   On hrs On hours 3993 Long   FwdRun secs  Forward run seconds 3995 Long   RevRun secs   Reverse run seconds 3997 Long   Intr Number of power 3999 Long e  interruptions   Demand   Present Present demand 3975 Float     Demand   Rising Demand  Rising demand 3977 Float   Max MD Maximum demand 3979 Float   Max DM Maximum demand 3981 Long   Occurrence occurrence time   Time   Percentage of Load parameters     Avg Load Average load percentage  3881 Float    L1 Percentage of phase 1 3883 Float  load    L2 Percentage of phase 2 3885 Float    load    L3 Percentage of phase 3 3887 Float    load   Unbalanced Unbalanced  load 3889 Float e   Load   Unbalanced    Unbalanced   voltage 3891 Float            voltage                      54    O 2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters    Chapter 6     Data Communication       Block Parameter Address    Total RMS Block   e Function Code  03H Read  e Number of registers  20   e No scaling required   e Read as block only    Table 6 5  Total RMS block                                                             
59. ollowing figure explains how the bits are organized in the model register     Figure 6 4  Bits in model register    MSB LSB       31 28  27  26 21 20 19 18  17   16  15  14  13  12  11  10 9  8  7  6  5 4  3  2  1  0    30   29 25  24  23  22  30     24 23 16 15 0  gt      Model No    rle    Options   ie Version No                                                                                                                2010 Schneider Electric  All rights reserved  63    PM1000 Series Power Meters PLSED309039EN  Chapter 6     Data Communication 08 2010       Meter Model and Number  The following table bitwise explanation for Meter  model and number     Table 6 21  Meter model and number          Meter model Model no  5A  Model Options  PM1200 22  0x16  IE   DM   THD                   Model options description  The following table gives the model options  bitwise description     Table 6 22  Model options description                         Bit23 Bit22 Bit21 Bit20 Bit19 Bit18 Bit17 Bit16 Remarks   0 0 0 No options  available   0 0 1 Imp Exp  option  available   0 1 0 DM option  available   0 1 1 Imp Exp and  DM option  available   1 0 0 THD option  available   1 0 1 Imp Exp and  THD available   1 1 0 DM and THD  available   1 1 1 Imp exp  DM  and THD  available                                     Interpretation of firmware version number  The following steps clearly explain  how to interpret the firmware  FW  version number    Convert the hexadecimal values both MSB and LSB
60. oltages of the circuit     Line to neutral voltages  Measurement of the RMS line to neutral voltages of the  circuit     LOCK  Default display page lock  See    Default display  View  page    on page 12 for  more information      Long  A 32 bit value returned by a register  See    Data Address    on page 53 for  more information      Maximum demand  Highest average load during a specific time interval   Nominal  Typical or average    Parity  Refers to binary numbers sent over the communications link  An extra bit is  added so that the number of ones in the binary number is either even or odd   depending on your configuration  Used to detect errors in the transmission of data     Power factor  True power factor is the ratio of real power to apparent power using  the complete harmonic content of real and apparent power     Reverse  Exporting the power from the plant grid   RMS  Root mean square  The power meters are true RMS sensing devices     Run mode  This is the normal operating mode of the power meter  where the  readings are taken     Total Harmonic Distortion  THD   Indicates the degree to which the voltage or  current signal is distorted in a circuit           2010 Schneider Electric  All rights reserved  75    PM1000 Series Power Meters  Appendix C     Glossary    PLSED309039EN  08 2010       ULOC  Default display page unlock  See    Default display  View  page    on page 12  for more information      User  fixed block   An interval selected between five to 30 minutes 
61. on  11  Maintenance and troubleshooting  67  Mechanical Installation  35  Panel considerations and Environment  36  on h  25  Parameters with PM1000 series power meters 14  PM1000 Series Menu hierarchy  27  PM1000 series power meters product description  7  PROG menu     Setup  List of setup parameters in View and Edit  modes 20  Quick setup   While powering on  17  Setup entry in View mode  18  Setup entry in Edit mode  19  Editing setup parameters  21  Rear Panel  13  Safety  Precautions 33  Symbols  3  SIM  simulation  mode  73  Technical specifications  16    TURBO Key  10          2010 Schneider Electric  All rights reserved     79    Schneider Electric Industries SAS  35  rue Joseph Monier   CS 30323   F   92506 Rueil Malmaison Cedex    For technical support   Global PMC Tech support schneider   electric com    00    1 250 544 3010    Contact your local Schneider Electric sales  representative for assistance or go to  www schneider electric com     PowerLogic and ION Enterprise are either trademarks or registered trademarks  of Schneider Electric     Electrical equipment should be installed  operated  serviced  and maintained only by  qualified personnel  No responsibility is assumed by Schneider Electric for any  consequences arising out of the use of this material        2010 Schneider Electric All Rights Reserved  v03 04 d15    
62. on the direction the CTs are facing when clamped around conductors  The dot   on the CT must face the line side  the corresponding secondary connection must   connect to the appropriate input on the power meter     Failure to connect CTs properly results in inaccurate power readings  If your power  meter is not reading power properly  it is more than likely that the CT is incorrectly  wired  If one or two CTs are reversed  then energy parameters accumulate only  one phase value  If two or all the phases of the CT are reversed  energy will not  accumulate   Energy import will not be measured      CT Connection Reversal    To check the polarity of the CT after the power meter has been installed  simply  look at the phase wise W  Watt  readings to see that each of the readings are  positive  assuming you are consuming power   If one of the W readings is  negative  that particular phase CT is reversed and must be corrected  On the other  hand if you are exporting power  all three phase wise W readings must be  negative           2010 Schneider Electric  All rights reserved  41    PM1000 Series Power Meters  Chapter 5     Installation    PLSED309039EN  08 2010       Setup     System Type    The power meter needs to know the type of system to which it is connected to   This information is programmed in the setup procedure  before using the power  meter  The power meter does allow you to change this setting while it is running   however  this capability is meant for correcting a gro
63. otal reactive inductive energy 3185 Float    Reserved Reserved 3187 Float   Reserved Reserved 3189 Float   TotVARh Total reactive capacitive energy  3191 Float    Reserved Reserved 3193 Float   Reserved Reserved 3195 Float   Reserved Reserved 3197 Long  TotRunsecs  Total run seconds 3199 Long                        Demand Block    e Function Code  03H Read  e Number of registers  22   e No scaling required   e Read as block only    Table 6 12  Demand block                                  Parameter Description Address Type PM1200  Reserved Reserved 3721 Long  Reserved Reserved 3723 Float  Reserved Reserved 3725 Float  Reserved Reserved 3727 Float  Reserved Reserved 3729 Float  Reserved Reserved 3731 Float  Reserved Reserved 3733 Float   Present demand   Present demand 3735 Float     Rising demand Rising demand 3737 Float    Time remaining Time remaining 3739 Long     Reserved Reserved 3741 Float                         Note  The address 3741 is overlapped between the demand and max demand blocks        58    2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 6     Data Communication       Max Demand Block    e Function Code  03H Read  e Number of registers  36   e No scaling required   e Read as block only    Table 6 13  Max demand block                                                                   Parameter Description Address Type PM1200  MaxDM Maximum demand 3741 Float e  MaxDMTime  Maximum demand occurrence time 
64. phase 2 3061 Float e   W2 Active power  phase 2 3063 Float     VAR2 Reactive power  phase 2 3065 Float     PF2 Power factor  phase 2 3067 Float     V23 Voltage phase 2 to phase 3  3069 Float e   V2 Voltage phase 2 to neutral 3071 Float e   A2 Current  phase 2 3073 Float      F2 Frequency  Hz 3075 Float e   Reserved Reserved 3077 Long   Intr2 Number of interruption 3079 Long      B phase RMS Block    e Function Code  03H Read   e Number of registers  20   e No scaling required   e Read as block only   Table 6 8  B phase RMS block   Parameter  Description Address Type PM1200   VA3 Apparent power  phase 3 3091 Float      W3 Active power  phase 3 3093 Float      VAR3 Reactive power  phase 3 3095 Float     PF3 Power factor  phase 3 3097 Float      V31 Voltage phase 3 to phase 1 3099 Float      V3 Voltage phase 3 to neutral 3101 Float      A3 Current  phase 3 3103 Float     F3 Frequency  Hz 3105 Float      Reserved  Reserved 3107 Long   Intr3 Number of interruption 3109 Long                              56    O 2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 6     Data Communication       Forward Integrated Block  e Function Code  03H Read  e Number of registers  20   e No scaling required   e Read as block only    Table 6 9  Forward integrated block                                                                                     Parameter Description Address Type PM1200   FwdVAh Forward apparent energy 3121 Float   
65. ps rated at 480 V   The 92 x 92 mm  3 62 x 3 62 in   cut out and 96 x 96 mm  3 78 x 3 78 in   bezel  dimensions adhere to IEC 61554 and DIN 43700   The diagram below displays the various dimensions of mechanical installations     Figure 5 1  Mechanical dimensions and recommended panel cut out                                        2010 Schneider Electric  All rights reserved  35    PM1000 Series Power Meters  Chapter 5     Installation    PLSED309039EN  08 2010       Installation Procedure    Usage    First  decide how the power meter is to be used  If you do not already have an  energy management program in operation  then your energy consultant should be  able to help you identify which load s  offer maximum savings potential  This will  help you decide which point is to be monitored  where the readings will be viewed  from  who must have access to the instrument and how often  Otherwise  decide the  location of the power meter and install it  For best performance  choose a location  that provides all the required signals with minimum wiring lengths     Panel Considerations and Environment    The power meter is high precision measuring instrument  and its operating  environment is of utmost importance  For maximum performance  the instrument  should be mounted in a dry  dust free location  away from heat sources and strong  electromagnetic fields  To operate reliably  the following conditions must be met     Table 5 1  Environmental Conditions          Description Specifica
66. ption and Poor Power Factor  CONSUMPTION  Wh   W x T  where W   instantaneous power  T   time in hours     The total electric energy usage over a time period is the consumption of Wh   Typically  the unit in which consumption is specified is the kilowatt hour  kWh   one  thousand watts consumed over one hour  Utilities use the Wh equation to  determine the overall consumption in a billing period     Poor power factor  Results in reactive power consumption  Transferring reactive  power over a distribution network causes energy loss  To force consumers to  correct their power factor  utilities monitor reactive power consumption and  penalize the user for poor power factor        3D    kVA Measurement    The power meters are equipped with 3D Measurement of kVA  This advanced  method provides the most accurate and predictable measurement under  unbalanced as well as distorted waveform conditions     However  in case the power meters need to match the reading of older or simpler  power meters  which use the Arithmetic kVA definition  this too is available as a  Setup option     Table 3 1     3D    kVA Measurement                   kVA Other 2     Function Formula Nas Which one   3D Factory a Y 7  7 y U  Best  all around  setting kVA    D wW    VAR  2D Apparent   Where D   Distortion Power per IEEE 100 Vector kVA  Arth 2 Arithmetic    Good under  KVA Arth   VA    KVA   kVA  Scalar kVA   Low unbalance   to match  simpler meters  without 3D  capability                         32    2
67. r  voltages primary and secondary need to be programmed as Line to  Line    2  Connect the voltage and current inputs only to the V1 and A1 voltage and  current terminals of the power meter    3  The unused current terminals  A2 and A3  must be shorted together to reduce  noise picked up in the power meter    4  However  the energy parameter readings will be accurate     Figure 5 7  Single phase connection    L1  LINE       gt                      PT if VAC LL 2481 V              1  CT       0 25 A          80 to 480 Vac LL    82        IK            50mA to 6A    SIN COYYWWDXXXX Acc Cl  1 0  Option List  RS 485 THD DM IE         Lt    aS     Aux Supply              gt _ gt    Aux supply   Control Power      44 to 277 VAC DC    N       44 to 277 V 50 60 Hz  lt 5 VA    LOAD  Communication  A    PM1200                 O 2010 Schneider Electric  All rights reserved  45    PM1000 Series Power Meters PLSED309039EN  Chapter 5     Installation 08 2010          46    2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 6     Data Communication       Chapter 6  Data Communication    This section is applicable only for PM1200 power meter     RS 485 Data Port    Data Port advantages     Installation    Rapid  on line  real time readings into your own SCADA software or PLC   Schneider Electric energy management software products such as ION  M  Enterprise  Vijeo Citect  PowerLogic SCADA for pinpointing energy usage and  waste    S
68. respond to three potential lines  A 120   phase  shift exists between the three potential lines     A typical configuration has either a Delta connection or a Wye  Star  connection    In a 3 phase system  the voltage levels between the phases and the neutral are  ideally defined by V1   V2   V3   V12   V3   V23   V3   V31   V3  In practice  there  will be some unbalance  difference      1  Delta       Voltages between the phases vary  depending on loading factors and the quality of  distribution transformers     Power measurement in a poly phase system is governed by Blondel s Theorem   Blondel   s Theorem states that  in a power distribution network  which has N  conductors  the number of measurement elements required to determine power is  N 1  A typical configuration of a poly phase system has either a Delta connection  or a Wye  Star  connection  see Figure below      A Emp la  1  Delta P  Elat Ecsle  E PNY B    l Ecele  Epi    ANA                                                                            Where E p  Voltage across points A and B  Ecs  Voltage across points C and B  Enn  Voltage across points A and N  Neutral   Esn  Voltage across points B and N  Neutral   Ecn  Voltage across points C and N  Neutral   la   Current through conductor A  lg   Current through conductor B  lc   Current through conductor C          2010 Schneider Electric  All rights reserved  31    PM1000 Series Power Meters PLSED309039EN  Chapter 3     AC Power Measurement 08 2010       Consum
69. ri  A sec  Set these values to match your CT primary and secondary  values  For example  if your CT Ratio is 200 5  set  A pri   200 0 and A sec   5 000     e V pri  V sec Set these values to match the input voltage VLL of circuit   if the input voltage  lt  480 VAC LL  For example  if input voltage   300  VAC LL  set V pri   300 0 and V sec   300 0     e Use potential transformer  PT VT   if the input voltage  gt  480 VAC LL   Set the V pri and V sec values to match the primary and secondary of  the PT VT  respectively  For example  if PT VT  ratio is 11 kV  110  set  V pri   11 00 k and V sec   110 0     3  Select one of the following systems according to your wiring configuration   e SYS  DLTA for 3 phase 3 wire system  e SYS  WYE Star for 3 phase 4 wire system  e SYS  2 phase for 2 phase 3 wire system  e SYS  single phase for single phase 2 wire system    4  Connect the current transformers  CTs         CT1 CT2 CT3                   1 2 3  4 5  6       5  Connect the voltage inputs  Use PT VT   if voltage exceeds 480 VAC LL           PT1 PT2 PT3 Neutral       8 9 10 11                   6  RS 485 terminals  PM1200         ve  ve                         2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 2     Quick Start Guide       Enter Setup Menu in View  Read Only  Mode       SET VIEW                ke    A    VIEW   A PRI   1  A    A     pp    CLR    RMS       From RMS  press    The display shows CLR   Press 
70. s reserved     PM1000 Series Power Meters PLSED309039EN  Chapter 1     PM1000 Series Power Meters Product Description 08 2010       Smart Keys    Operating the power meter is easy  using the five smart keys to navigate through  the keypad operations Table  The display pages expand as you go to the right   much like the directory or explorer tree displayed on any computer  The display  shows where you   re headed     Table 1 4  Smart keys description       Right Key   gt  e Go forward into sub parameter pages     e Going right past EDIT in SET and CLR requires code entry to enter  PROG menu  setup and clear     e During setup  select next  right side  digit        Left Key     lt  e Go back towards to the main parameter pages    e During edit setup  selects previous  left side  digit   e Exits from Edit mode  back to the PROG menu   setup    e The meter enters the SIM  simulation  mode when you press the left  key continuously during powerup of the power meter  See    SIM   Simulation  mode    on page 73 for more information    Up Key    A e Scroll up through display pages at the same level  within the same   function     e Continuous pressing for three seconds initiates limited auto   scroll  within the same function   See    Auto scroll    on page 12  for more information     e While editing  increases the value of the blinking digit during edit   Down Key     V e Scroll down through other display pages at the same level  through all  functions     e Continuous pressing for 
71. scribes the following   e The need for  and selection of  potential transformers  PTs  and current  transformers  CTs      e Auxiliary supply  control power   PT  VT   and CT connections     For best results  ensure the following specifications    e Torque driver preferred  hand screwdriver OK    e TIP  Phillips head is preferred  but flat head is acceptable  Do not use Pozidriv  tips     Screw head diameter   3 5 mm  0 14 in    TIP shaft diameter  lt  5 mm  0 2 in     IMPORTANT   Screwdriver shafts inserted angularly or of diameter 2 5 mm  0 2  in   will get stuck in the cover   Tightening Torque  0 25 to 1 N m  2 21 to 8 85 Ib in    Loosening Torque  0 8 to 1 N m  7 08 to 8 85 Ib in     Screw Travel  6 mm  0 24 in   less wire thickness  Torque  gt  1 N m  8 85 Ib in  may strip the screw or break the cover     Connecting cable    Table 5 3  Connecting cable             Insulation Rating Current Rating  Voltage Circuit  gt  600 VAC  gt  0 1A  Current Circuit  gt  600 VAC  gt  7 5A  Or 2 5 mm     14 AWG  minimum                       Schneider Electric recommends the use of insulated sleeved U lugs  2 5  mm  14 A WG  for wiring terminals     NOTE  Installations should include a disconnecting device  like a switch or circuit breaker  with clear  ON OFF markings to turn off the auxiliary supply  control power   The disconnecting device should be  placed within the reach of the equipment and the operator        38    2010 Schneider Electric  All rights reserved     PLSED309039EN 
72. ss error  or for training or  educational purposes  it is not to be changed on regular basis  The options are     e Wye Star  For 3 phase 4 wire  three Watt meter or three Element circuits   Here  all three voltage phase signals  the neutral voltage connection  and all  three current input signals need to be wired in  This means all the four voltage  terminals  and six current terminals described in the following section  need to be  wired  For wye star wiring configuration  see    3 phase 4 wire WYE connection  with 3 CTs and 3 PTs    on page 43 for more information    e Delta  For 3 phase 3 wire  two Watt meter or two Element circuits  For delta  and open delta wiring configuration  see    3 phase 3 wire Delta connection with 2  CTs and 3 PTs    and    3 Phase 3 Wire Open Delta connection with 2 CTs and 2  PTs    on page 44 for more information    e 2 phase  For 2 phase 3 wire  two Watt meter or two Element circuits  Here   the two voltage phase signals  the neutral voltage connection  and two current  input signals need to be wired in  This means that the three voltage terminals  and four current terminals described in the following section  need to be wired   For two phase wiring configuration  see    2 phase 3 wire connection with 2 CTs     on page 45 for more information    e Single phase  For single phase 2 wire  one Watt meter or one Element  circuits  Here a single voltage Phase signal  the neutral voltage connection  and  a single current input signal need to be wir
73. t the reading is in Kilo  10     10 000 is displayed  as 10 00 K and 1 0 K as 1000        Mega  When lit  indicates that the reading is in Mega   10     10 000 K is  shown as 10 00 M  and 1 0 M as 1000 K        Giga  When Kilo and Mega are lit together  the reading is in Giga  10      10 000 M is shown as 10 00 G and 1 0 G as 1000 M        Negative  When lit  indicates that the reading is negative as per IEEE 100  and industry standard practice by meter men    When PF  power factor  is lead  capacitive load   Both PF and VAR   reactive power  sign will be negative  When current is reversed  W  active  power  is negative              Table 1 3  Giga  Mega  M   Kilo  K   and decimal point scaling       RMS Reading    Indicator       Less than 0 001    K  M OFF  displays 0 000             Less than 9999 K  M OFF  Above 9999 K ON  M OFF  Above 9999 K M ON  K OFF       Above 9999 M  Up to 9999 G  Above 9999 G          Giga  k   M indicators ON   Giga    Display shows Hi for positive numbers  Lo for negative numbers          RMS readings are four digits  Energy readings have eight digits  including four  additional fractional digits  The maximum number the power meter handles is  9 999 G for RMS and energy values     This means that the energy readings of the power meter will overflow at three  values of Wh  active energy  or VAh  Apparent energy   selectable through  PROG menu   setup  depending upon the PT  VT  and CT ratios programmed           2010 Schneider Electric  All right
74. three seconds initiates the full auto   scroll mode  through all functions  See    Auto scroll    on page 12  for more information     e While editing  decreases the value of the blinking digit   TURBO Key   Z 2 TURBO key is simple one touch access to the most commonly used       parameters pages  Factory set   The TURBO pages for PM1000 series  are given below    RMS  home page   VLL  A  PF VLN A F VA  W  PF VA  W VAR W   VAR  PF PF1  PF2  PF3  V  1 23  A  123  VAd RD TR  MD HR   VAh  Wh  RVAh  RWh  tVAh  tWh  This gives simple one touch access  to the most commonly used parameters  even for unskilled operators    If you   re lost  the TURBO key is a quick way to get back to the RMS  home page    Continuous pressing for three seconds initiates auto scrolling through  the above TURBO pages  See    Auto scroll    on page 12 for more  information    During the powerup  if the TURBO key is pressed  power meter will  go in to PROG menu   Setup directly  This is the easiest way to  enter in to the setup menu    See    Quick setup     While powering on    on page 17 for more  information                    10 O 2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 1   PM1000 Series Power Meters Product Description          Keypad Operation   Navigating with the power meter is very easy and intuitive  Press the key in the  direction you want to go  The display shows where you   re headed  Press the key  that takes you in the d
75. tion   Storage temperature  25  C to 70   C    13 F to 158 F   Operating temperature  10  C to 60   C   14 F to 140 F   Relative humidity 5  to 95   non condensing                The power meters should be separated from other equipment  and sufficient space  must be provided all around for cooling air to rise vertically past the instrument   The cooling air temperature must be below the specified operating temperature     The panel or housing  in which the PM1000 power meter is mounted  should  protect it from dust  moisture  oil  corrosive vapors  etc     The panel doors must be easily opened to provide easy access to the power meter  wiring for troubleshooting  Allow clearance if the unit is going to swing out  as well  as adequate slack in the wiring  Allow space for terminal blocks  CT shorting  blocks  fuses  auxiliary contactors  and other necessary components     Viewing  For ease of operation  the location should be preferably at  or slightly above  eye     level  For viewing comfort  minimize glare and reflections from strong light  sources        36       2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 5     Installation          Mounting  The power meters are panel mountable     Table 5 2  Mounting                                  Description Specification   Panel cut out 92   mm  w  x 92  mm h   3 62     x  3 62  in    IEC 61554 and DIN 43700   Panel thickness 0 5 to 4 0 mm  0 02 to 0 16 in     Instru
76. tion  the  energy will update in  INTG Rev    2 Check the mode  If it is  in export  then the    energy will update in  INTG Rev                       68    2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters    Chapter 7     Maintenance And Troubleshooting          Potential Problem    Possible Cause    Possible Solution       The display went blank  suddenly     Over voltage temperature    Interrupt the power supply  or reduce the voltage or  temperature within the  limit        Fuse connection    Check whether a fuse with  rating of 0 25 Ais  connected on each  voltage input  If not  connect the 0 25 A rated  fuse to the voltage input        The power meter stopped  communication abruptly     Communications lines are  improperly connected     Verify the power meter  communications  connections  See    Chapter  6     Data communication     on page 47 for more  information        Over voltage temperature    Interrupt the power supply  or reduce the voltage or  temperature within the  allowable limits        Wrong Load bar indication    Incorrect F S  selection    Select the full scale load  percentage setting as per  your circuit           The Power meter is over  heated       Lack of sufficient air for  cooling       Provide sufficient space all  around the power meter   Separate the power meter  from other equipment for  cooling air                 2010 Schneider Electric  All rights reserved     69    PM1000 Series Power M
77. to  unlock the key page  The power meter displays ULOC     NOTE  Entry into setup  PROG  is allowed only when the display page is unlocked        12    2010 Schneider Electric  All rights reserved     PLSED309039EN  08 2010    PM1000 Series Power Meters  Chapter 1   PM1000 Series Power Meters Product Description       Rear Panel    The power meter terminals are located on the rear panel  14 terminals are  provided  seven terminals on each side     e Six terminals for current  one in and one out per phase  e Four terminals for voltage  for three phases and neutral  e Two terminals for auxiliary power supply  control power   e Two terminals for the RS 485 communication port  PM1200     Figure 1 2  Rear panel         Input Voltage  terminals   V1  V2  V3  VN  Input current  lt   terminals  A1  A2  A3        80 to 480 Vac LL    50mA to 6A    SINCOYYWWDXXXX Acc Cl  1 0      Auxiliary supply   Control power   terminals    Option List  RS 485 THD DWIE  VER 03 04 00    ww LAS LA       44 to 277 V 50 60 Hz  lt 5 VA    aa A   4b Ah Ah Ah Ah  m    RS 485 Communication  terminals  PM1200           2010 Schneider Electric  All rights reserved  13    PM1000 Series Power Meters PLSED309039EN  Chapter 1     PM1000 Series Power Meters Product Description 08 2010       Parameters with PM1000 Series Power Meters    The power meter can measure  locally display and remotely transfer over  Modbus RTU  PM1200   the following parameters     Table 1 5  Models and parameters with PM1000 series        
78. tuation which  if not avoided  can result in property damage                 OTHER SYMBOLS    This symbol indicates direct and alternating currents    protected throughout by double insulation or reinforced insulation      0  This is double insulation symbol which indicates that  the user accessible area is          2010 Schneider Electric  All rights reserved        PLEASE NOTE   Electrical equipment should be installed  operated  serviced  and maintained only by  qualified personnel  No responsibility is assumed by Schneider Electric for any  consequences arising out of the use of this material     REACH Compliance   Complies with Regulation  EC  n   1907 2006 of Dec 18 2006 named REACH   related to the Registration  Evaluation  Authorization and restrictions applicable to  Chemical substances     FCC Notices   This equipment has been tested and found to comply with the limits for a class A  digital device  pursuant to Part 15 of the FCC Rules  These limits are designed to  provide reasonable protection against harmful interference when the equipment is  operated in a commercial environment  This equipment generates  uses  and can  radiate radio frequency energy and  if not installed and used in accordance with  the instruction manual  may cause harmful interference to radio communications   Operation of this equipment in a residential area is likely to cause harmful  interference in which case the user will be required to correct the interference at  his own expense     Th
79. values can be re programmed at any time  using SET However  the  settings  SYS  WYE  Star  Delta single phase   2 Phase   Vpri  Vsec  Apri  Asec  critically determine the scaling of measured readings    e The scaling may be used to reduce the errors in readings due to Instrument  Transformer errors  However  wrong settings will introduce errors in readings of  other running systems        HAZARD OF UNINTENDED OPERATION  Only qualified personnel are authorized to set up the power meter        Failure to follow these instructions can result in injury or equipment  damage              You can enter the PROG menu   setup in  e View only mode  To view the set parameters   e Edit mode  To view or edit set parameters     Quick setup     While powering ON    e This is the easiest way to enter the PROG menu setup   e To make connections  see    Connection diagrams    on page 43  Here are few  tips     Figure 2 1  Quick setup   connections                                                       2010 Schneider Electric  All rights reserved  17    PM1000 Series Power Meters  Chapter 2     Quick Start Guide    PLSED309039EN  08 2010       1  Connect auxiliary supply  control Power  44     277 VAC DC to terminals 12  and 13 in order to power ON the power meter     e Keep g pressed for two seconds  while powering up the power meter   The power meter directly enters into PROG menu setup and displays  EDIT A PRI 100 0     2  Program the following setup parameters for accurate readings     e A p
80. voltage   PT   current  CT  signals  and auxiliary  control  supply     NOTE  The power meters user programmable PT and CT primary or secondary settings  may be  utilized to Calibrate out the PT and CT amplitude error  for improved accuracy           2010 Schneider Electric  All rights reserved  39    PM1000 Series Power Meters  Chapter 5     Installation    PLSED309039EN  08 2010       Voltage Signal Connections    For proper power meter operation  the voltage connection must be maintained   The voltage must correspond to the correct terminal  The cable required to  terminate the voltage sense circuit should have an insulation rating greater than  480 VAC and a current rating greater than 0 1 A    There are four input voltage terminals marked V1  V2  V3  and Vn  See the  connection diagrams that follow  for details  For Delta connection  the Vn terminal  should be left unconnected     PT Connections    The power meters directly accept LV voltage inputs of up to 480 VAC RMS line to  line  277 VLN   Voltages greater than this  typically HV systems  must be  connected through Potential transformers  PTs   The power meters allow user  programming of both PT primary and secondary voltages    e User programmable PT primary range  0 1 to 999 KVAC RMS LL   e User programmable PT secondary range  80 to 481 VAC RMS LL   e Power meter voltage Input burden  0 2 VA per input    NOTE  The PT primary and secondary values must be user programmed before using the power  meter  Otherwise  the
81. y flashes PASS and then CLR INTG   Press 9  The display shows CLR   Press  Y to return to RMS page     NOTE  If you do not want to clear the integrators  press Q to change the value from CLR INTG y    to CLR INTG n in step 5  Then press   The display flashes FAIL and shows CLR INTG  Proceed to  step 7           2010 Schneider Electric  All rights reserved  23    PM1000 Series Power Meters  Chapter 2     Quick Start Guide    PLSED309039EN  08 2010       MD Clear   1  From RMS  press    The display shows CLR   CODE entry is required to clear the INTG values    2  Press     for two seconds  The display shows CODE 2000 with blinking 2   The factory set CODE is 1000    3  Press Y  The display shows CODE 1000 with blinking 1    4  Press    once or  gt  four times to accept the new value        ON On    After the successful CODE entry  the display shows CLR INTG   Press Y  The display shows CLR MD    Press     The display shows CLR MD y with blinking y    Press   to clear MD  The display flashes PASS and then CLR MD   Press    The display shows CLR    Press Y to return to RMS page     NOTE  If you do not want to clear the maximum demand  press v to change the value from CLR    MD y to CLR MD n in step 6  Then press  gt    The display flashes FAIL and shows CLR MD  Proceed  to step 8        24       2010 Schneider Electric  All rights reserved     PLSED309039EN PM1000 Series Power Meters  08 2010 Chapter 2     Quick Start Guide       Energy Integrator    The PM1000 series power meter
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
BF-PRO  Ilumipanel 90 IP Optic RGBWA User Manual Rev. 11  L`Investisseur Or et Matières  MANUALE D`INSTALLAZIONE Daitem DP8000    Copyright © All rights reserved. 
   Failed to retrieve file