Home
Installation Instructions
Contents
1. 29 62 0399 02 CLASS 500 METER 6 9 4 Dip Switch Settings COMMUNICATION PROTOCOLS PROTOCOL BAUD RATE Ethernet Firmware Option RS 485 Port Port PN SW1 SW2 SW3 SW4 01 EZ7 EZ7 Modbus ON ON ON ON 02 Modbus RTU EZ7 Modbus OFF ON ON ON 03 BACnet MS EZ7 BACnet OFF ON ON OFF TP MS TP 04 EZ7 Modbus Modbus ON OFF ON ON TCP IP 05 EZ7 BACnet BACnet IP OFF ON ON 06 Modbus RTU Modbus Modbus OFF OFF ON ON TCP IP 07 LonWorks EZ7 LonWorks X ON ON ON TP FT 10 08 LonWorks Modbus LonWorks X OFF ON ON TP FT 10 TCP IP 09 EZ7 w EZ7 Modbus ON ON ON ON Modem 10 EZ7 w Modbus Modbus ON OFF ON ON Modem TCP IP 11 EZ7 w BACnet BACnet IP OFF ON ON Modem NOTE Protocol selections are done via DIP Switch S2 pos 1 for RS 485 and pos 2 for Ethernet When the DIP switch is in the ON position EZ7 protocol will be active Changing protocol setting requires restarting the CPU DIP Switch indicating by X means don t care NOTE Pass Through Feature S2 position 8 to off ethernet to RS485 pass 62 0399 02 through only valid with EZ7 protocol S2 position 8 on true dual protocol settings 30 CLASS 500 METER 6 10 Modbus RTU Wiring The Class 500 Modbus meter communicates with building automation equipment over a 2 wire 3 conductor RS 485 network using Modbus RTU protocol The meters are networked in a daisy chain
2. stand alone or in an AMR application This meter is intended to be used with the appropriate high voltage Potential Transformers PTs and Current Transformers CTs supplied by others The meter application is centered around a 120 VAC secondary output from the high voltage PTs and a 5 amp secondary output from the high voltage CTs Items addressed by this document include the installation of the H50 12025HV meter on high voltage circuits as well as the calculations to provide the correct meter multiplier based on the PT and CT sizes used on the high voltage conductors Installation should be performed by qualified personnel and only according to all applicable electrical codes High Voltage CTs supplied by others reduce the primary current amps to a directly proportional 0 5 amp secondary output As an example a 0 400 amp primary becomes a 0 5 amp proportional signal from the secondary output In our application the high voltage CT secondary is installed as a continuous loop with a single conductor connected to both secondary terminals To convert the 0 5 amp signal to a 0 2 volt signal Honeywell s Current Sensors are installed on the CT secondary conductor A set of 25 amp sensors is used in this application These sensors have the high voltage CT secondary conductor passed through them five 5 times see below by looping the secondary conductor as shown in the drawing The reason for this is so that the 5 amp secondar
3. 80 PT 4200 120 35 1 PTr 35 Wraps Passes 5 METER MULTIPLIER PTr x CTr Wraps 35 x 80 5 35 x 16 560 62 0399 02 60 CLASS 500 METER 14 0 METER LIMITED WARRANTY Subject to the exclusions listed below Honeywell will either repair or replace at its option any product that it manufactures and which contains a defect in material or workmanship The following exclusions apply 1 oo N This Limited Warranty is only effective for a period of 5 five years following the date of manufacture when installed in accordance with manufacturer s instruc tions by qualified personnel Honeywell must be notified of the defect within ninety 90 days after the defect becomes apparent or known Buyer s remedies shall be limited to repair or replacement of the product or com ponent which failed to conform to Honeywell s express warranty set forth above Buyer shall be responsible for all freight costs and shall bear all risk of loss or damage to returned goods while in transit This Limited Warranty does not cover installation removal reinstallation or labor costs and excludes normal wear and tear Buyer shall provide labor for the removal of the defective component or item and installation of its replacement at no charge to Honeywell This Limited Warranty does not cover any product if i a product is altered or modified from its original manufactured condition ii any repairs alter
4. SNVT volt f Voltage line to line phase C A Volts L 62 0399 02 56 CLASS 500 METER Lonworks SNVT Types Point Map CL500 nvoPhase AngleA SNVT angle f Phase angle Degree R phase A nvoPhase AngleB SNVT angle f Phase angle Degree R phase B nvoPhase AngleC SNVT angle f Phase angle Degree R phase C nvoReserve A SNVT count f Reserve A No units R nvoReserve B SNVT count f Reserve B No units R nvoReserve C SNVT count f Reserve C No units R nvoExt Input 1 SNVT count f External Pulse R Input 1 nvoExt Input 2 SNVT count f External Pulse R E Input 2 1 To clear single meter kWh kVARh select reset kW kWh on the display menu of the meter This function will also reset external inputs Jumper J6 must be closed Remove J6 after changes have been completed 2 External inputs are standard on Class 500 meters and optional on Class 3400 meters Part of Expanded Feature Package To clear external inputs select reset kW kWh on the display menu of the meter This function will also reset KW KVARh Jumper J6 must be closed Remove J6 after changes have been completed 57 62 0399 02 CLASS 500 METER 13 0 HIGH VOLTAGE METERING kWh Meter Installation Instructions for Use with Honeywell Meters in High Voltage Applications The Honeywell model H50 12025HV kWh meter is designed to be used for monitoring high voltage 2400 4160 13200 etc circuits either
5. To change the date and time complete the following steps 1 Press the MENU button 2 The following screen will appear gt DATE amp TIME DEVICE ID IP SETTINGS RESET KW KWH READ 3 Pressthe SELECT button The Date and Time Screen will appear and the 2 digit month will be blinking DATE 02 16 2012 TIME 01 57 36 4 Use UP or DOWN button to make changes press the SELECT button to advance to the next setting Repeat this step until all the date and time settings have been updated 5 If changes were made you ll be asked to save press UP or DOWN to select Y or N Save changes Y N 6 Press SELECT to save new settings This will also return you to main menu In main menu select EXIT to get out of programming mode and return to normal display mode 41 62 0399 02 CLASS 500 METER 10 3 2 Device D Display Screen To change Device 1 D complete the following steps 1 2 Press the MENU button The following screen will appear DATE amp TIME DEVICE ID IP SETTINGS RESET KW KWH READ Use UP or DOWN button until the arrow is on the Device ID line DATE amp TIME gt DEVICE ID IP SETTINGS RESET KW KWH READ Press the SELECT button The Device ID Screen will appear EZ7 ID 1A MODBUS ID 2 Locate the number to be changed in the menu press and hold Button 4 Down Button for 3 seconds release the button the last digit for this number
6. Communication 01 EZ 7 EZ 7 ETHERNET Protocol MODBUS RTU EZ 7 ETHERNET 02 03 BACNET MSTP EZ 7 ETHERNET 04 EZ 7 MODBUS TCP IP 05 EZ 7 BACNET IP 06 MODBUS RTU MODBUS TCP IP 07 LONWORKS TP EZ 7 ETHERNET 08 LONWORKS TP MODBUS TCP IP 09 EX 7 EZ 7 ETHERNET WITH MODEM 10 EZ 7 MODBUS TCP IP WITH MODEM 11 EZ 7 BACNET IP WITH MODEM Current Sensors KIT Split Core SCS Solid Core SP Single or Two Phase Options 2 element Ordering Information Define brand class input voltage current sensor rating enclosure protocols options and sensor type in the format A BB CCC DDDD E FF G HHH where A Brand H for Honeywell BB designates Class 320 32 or 500 50 meter CCC input voltage 208 480 600 120 volt for high voltage applications only DDDD current sensor rating 100 200 400 800 1600 3200 25HV E enclosure J metal type 1 R non metallic type 4X FF protocol option G no package blank S Single or Two Phase Optional HHH Sensor Type kit split core scs solid core non supplied blank 62 0399 02 8 CLASS 500 METER 3 0 METER TECHNICAL SPECIFICATIONS CONTINUED Input Voltage Single Phase 3 wire Delta or 4 wire Wye Configuration Mains Voltage Input Up To 480 VAC RMS Available Input Power 6 VA Maximum Rating Current Sensor Up To 3200 Amps RMS AC Available Rating Power Factor 0 5 Leading
7. Flags L2 Power Failure Date 1 To clear single meter kWh kVARh set multiple points at 40001 or 41001 for 8 points with data set to 0000 0000 0000 0000 0000 0000 0000 0000 2 External inputs are standard on Class 500 meters and optional on Class 3400 meters Part of Expanded Feature Package To clear external inputs set multiple points at 41083 or 41085 for 2 points with data set to 0000 0000 Jumper J6 must be closed Remove J6 when changes have been completed 3 To set the interval data day block set multiple points at 44001 for 6 points with data set to OCOI 0000 MMDD YYYY 0000 0000 OG Channel 01 Interval OF 15 minute intervals 05 5 minute intervals 4 Each register represents a 15 or 5 minute kWh pulse value based on the interval day block 96 registers max with 15 minute intervals 288 registers max with 5 minute intervals The first interval data register 44007 represents the pulse count for the first 15 or 5 minute interval beginning at midnight 5 The interval data headers represent days with available interval data Each day represents 2 registers Format MMDD YYYY 6 To set the date and time set multiple points at 46025 for 4 points with data set to HHMM SSDW MMDD YYYY DW day of week 7 To change the ModBus ID set single point at 46050 with data set to new ModBus ID e g 1 to 247 Jumper J6 must be closed Remove J6 when changes have been completed 62 0
8. M33276 Fig 14 Modem Configuration 6 9 1 Built In Modem RS 232 KEY RM The RS 232 key with built in modem connects the entire RS 485 network of Class 500 meters to a telephone line Refer to Section 6 7 for RS 485 network connections On the back panel of the RS 232 key modem the left jack RS232 is not used in most cases since there is no local host computer The two jacks at the top center of the rear panel on the RS 232 key modem are for connecting the phone line Connect either one of these two jacks to the telephone line IMPORTANT The telephone line should be dedicated exclusively to the automatic meter reading system Never connect to a telephone line used by other modems or fax machines If there are telephones connected to this phone line the propri etor must be aware that all phones must be on hook in order for the modem to work A dedicated phone line is suggested for system reliability 27 62 0399 02 CLASS 500 METER 6 9 2 External Modem 1 All meters should be connected to the RS 232 key as described in 6 8 2 2 2 DISCONNECT POWER TO THE RS 232 KEY Remove the cover by removing the 2 screws from the bottom of the enclosure 3 On the circuit board locate the blue jumpers J7 MODEM and J8 ex MODEM If these jumpers are set in the DIRECT position you must move the jumpers so they are set in the MODEM position Re place the cover and secure the enclo sure 4 Connect the RS 232 key to the ex
9. Secondary output of 120v This secondary is connected to the Honeywell meter voltage inputs as shown in the wiring diagram High voltage CTs reduce the primary current amps to a directly proportional 0 5 amp output As an example a 0 400 amp primary becomes a 0 5 amp proportional signal from the secondary output This allows much smaller wiring to be utilized in the meter hookup The high voltage CT secondary is installed as a continuous loop with a single lead connected to both secondary terminals Honeywell meters accept a 0 2 volt signal from their Current Sensors To convert the 0 5 amp signal the Current Sensors are installed on the CT secondary lead A set of 25 amp sensors is used in this application These sensors have the high voltage CT secondary lead passed through them five 5 times by looping the wire as shown in the drawing This allows a direct conversion of the CTs primary current to a directly proportional 0 2 volt signal which is used by the meter Since there is a signal ratio introduced by the high voltage CTs and PTs it will be necessary to multiply the number on the meter s display for a correct reading The meter multiplier is calculated by using the CT ratio and the PT Ratio PTr x CTr Number of Secondary Lead Passes Through Sensor The Honeywell 25 amp HV kWh meter with 5 wraps of the high voltage CT secondary will have its multiplier calculated by the formula shown below EXAMPLE CT 400 5 80 1 CTr
10. VAC NOTE Meters are powered by phases A and B The displayed voltages will be the measured AC voltage between phases 15 62 0399 02 CLASS 500 METER 6 3 Phasing of Line Voltage The 3 phase AC power input must be in proper phase sequence Single phase option AC power input must be in proper phase sequence If the sequence is incorrect or a phase is missing there will be a message on the meter s display PH Sequence Error or PH Missing Refer to the section on Line Voltage Diagnostics if this message is present When the line voltage is connected correctly the meter s display will be blank no message Wait for the meter display to scroll to the voltage display Verify that the meter reads correct voltages on all three phases Repeat Step 6 2 5 F Once the meter displays the correct line voltages and there are no error messages you are ready to connect the current sensors to the meter Before continuing with the installation verify that the seven screens display as follows Screen 1 kWh Should read 0 0 kWh if not should be reset Screen 2 kW Peak Demand kW peak should read 0 0 kW There will not be a date time stamp yet If there is a KW peak recorded it should be reset later Screen 3 Load Clock Calendar Should read 0 0 kW load Screen 4 Amps per Phase There should be 0 0 on all three phases Or in the Single Phase option 0 0 in A and B phases Screen 5 Volts RMS Phase to Neutr
11. confirm this requirement with your local and national electrical code requirements What size wire should use to extend the current sensor leads These wires are normally 14 22 AWG twisted pair arrangement Consult your electrical code for proper wiring requirements 62 0399 02 46 CLASS 500 METER Q The load I need to monitor has parallel feeds How do I install the current sensors for this application A There are two ways you can monitor parallel feeds The easiest and preferred method is to clamp the sensors around all feed wires for each phase The second way to monitor parallel feeds is to clamp the sensor around one of the feed wires for each phase When you read the Class 500 meter the final reading must be multiplied by the number of feed wires for each phase Q I have two subpanels I would like to monitor with one Class 500 meter These subpanels are fed by different transformers in the building Can I parallel sensors and monitor both panels with one meter A No These panels cannot be monitored with one meter because they are different power sources When you parallel current sensors all loads being monitored must be from the same voltage source Q have 5 breakers in one subpanel would like to monitor with one class 500 meter Can this be done without having to parallel current sensors A Yes Simply run all the breaker wires through one set of current sensors Make sure all A phase circuits are run
12. current sensors to the chart below to confirm the correct current sensor is being used Sensor Arrow Color Code Sensor Rating Brown 100A Red 200 A Yellow 400 A Black 800 A Blue 1600 A White Black 3200 A 62 0399 02 CLASS 500 METER N CAUTION Internal circuit card components are extremely sensitive to electrostatic discharge Prior to handling or touching internal circuitry discharge any static buildup on your person To discharge yourself touch a grounded metal object such as conduit or an earth grounded metal enclosure AWARNING Use of this instrument Class 500 in a manner inconsistent with this manual or not specified by the manufacturer in writing can cause permanent damage to the unit and or serious injury to the operator The protection and safety features provided by this equipment may become impaired or otherwise compromised NOTE If any trouble arises during installation or functional verification operations do not immediately remove unit Before removing the unit contact Honeywell s technical support department Honeywell s technical department will assist you in detailed troubleshooting of the Class 500 installation 2 0 INTERNAL ELECTRONIC ASSEMBLIES The unit is comprised of two major subassembly boards the main power board and the display board Both circuit boards are mounted inside a NEMA 4X rain tight enclosure MAIN POWER DISPLAY BOARD BOARD M33270 Fig 1
13. each terminal block screw is securely fas tened by gently tugging on each conductor NOTE On Single phase connections Connect two AC main power wires to phases A and B Connect jumper from B to C factory installed for Single Phase option Verify that no conductor wires are frayed or shorting to adja cent terminal block positions e Turn ON the AC main power input The meter display will light up and scroll through 7 displays Each display is visible for 5 seconds Display screens are as follows Screen 1 Total kilowatt hours kWh consumed Screen 2 Peak demand kW with date amp time stamp Screen 3 Actual load kW with preset date amp time Screen 4 Average current amps per phase Screen 5 Average voltage volts per phase Screen 6 Average voltage volts phase to phase Screen 7 Power factor PF per phase f Verify the voltage readings on Screen 5 using an AC voltmeter Typical read ings shown below are measured phase to neutral for 4 wire and phase to phase for 3 wire Readings should be 10 of nominal Meter Type Nominal Voltage Limits 10 120 208V 3 4 Wire 120 VAC L N 108 to 132 VAC 120 240V 19 3 Wire 120V 19 2 Wire 277 480V 4 Wire 277 VAC L N 249 to 305 VAC 277V 19 2 Wire 240V 39 3 Wire 240 VAC L L 216 to 264 VAC 400V 4 Wire 380 415 230 VAC L N 207 to 253 VAC 480V 39 Wire 480 VAC L L 432 to 528 VAC 600V 4 Wire wye only 347 VAC L N 312 to 380
14. or Lagging Line Frequency 50 60 Hz Metering Accuracy ANSI C12 20 Voltage Operating 10 of Rated Load Range Temperature Range 20 C To 50 C Standard indoor enclosure Temperature Range 20 C To 70 CNEMA 4X NEMA 4X outdoor enclosure Relative Humidity 0 95 Non condensing Range Altitude 2000 Meters Maximum Voltage Overload 25 Continuously 100 For 20 Cycles Current Sensor 10096 For 1 Minute Without Damaging Meter Overload Pollution Degree Degree 2 In Accordance With IEC 664 Installation Category 111 Overvoltage Category Measurement Category 111 Category Enclosure Material Indoor Housing Rating JIC Steel Standard NEMA 12 Outdoor Housing Rating Rain Tight Display Readout 4 Line LCD Standards EN 61326 1 2006 IEC 61010 1 2001 2nd Edition Standard Ranges 2 Wire Delta 120 VAC 100 200 400 800 1600 3200 Amp 4 Wire Wye 120 208 VAC 100 200 400 800 1600 3200 Amp 3 Wire Delta 120 240VAC 100 200 400 800 1600 3200 Amp 4 Wire Wye 277 480 VAC 100 200 400 800 1600 3200 Amp 2 Wire Wye 277 VAC 100 200 400 800 1600 3200 Amp 4 Wire Wye 400 VAC 100 200 400 800 1600 3200 Amp 3 Wire Delta 480 VAC 100 200 400 800 1600 3200 Amp 4 Wire Wye 600 VAC 100 200 400 800 1600 3200 Amp 9 62 0399 02 CLASS 500 METER Modem Interface Cable UL listed Telephone Cord 6 cond 300 VAG Stranded Cond 22 26 AWG Cable Connecto
15. 399 02 50 CLASS 500 METER BACnet Object Descriptors CL500 Instance BACnet BACnet CL ID Object Description Units Property 11 Analog Energy delivered kWh Present Value R Input PL Analog Energy received kWh Present Value R Input 3 Analog Reactive energy delivered kVARh Present Value R Input 41 Analog Reactive energy received kVARh Present Value R Input 5 Analog Real power kW Present Value R Input 6 Analog Reactive power KVAR Present Value R Input 7 Analog Apparent power KVA Present Value R Input 8 Analog Power factor PF Present Value R Input 9 Analog Peak demand kW Present Value R Input 10 Analog Current average Amps Present Value R Input 11 Analog Voltage line neutral Volts N Present Value Input 12 Analog Voltage line line Volts L Present Value Input 13 Analog Frequency Hz Present Value R Input 14 Analog Phase angle Degree Present Value R Input 15 Analog Real power phase A kW Present Value R Input 16 Analog Real power phase B kW Present Value R Input 17 Analog Real power phase C kW Present Value R Input 18 Analog Reactive power phase A KVAR Present Value R Input 19 Analog Reactive power phase B KVAR Present Value R Input 51 62 0399 02 CLASS 500 METER BACnet Object Descriptors CL500 Instance BACnet BACnet CL ID Object Description U
16. 41039 Float Reactive power phase C kVAR 41041 Float Apparent power phase A kVA 41043 Float Apparent power phase B kVA 41045 Float Apparent power phase C kVA 41047 Float Power factor phase A PF 41049 Float Power factor phase B 96 PF 41051 Float Power factor phase C 96 PF 41053 Float Current phase A Amps 41055 Float Current phase B Amps 41057 Float Current phase C Amps 41059 Float Voltage line to neutral phase A Volts N N 41061 Float Voltage line to neutral phase B Volts N N 41063 Float Voltage line to neutral phase C Volts N N 41065 Float Voltage line to line phase Volts L 41067 Float Voltage line to line phase B C Volts L 41069 Float Voltage line to line phase C A Volts L 41071 Float Phase angle phase A Degree 41073 Float Phase angle phase B Degree 41075 Float Phase angle phase C Degree 49 62 0399 02 CLASS 500 METER ModBus Customer Point Map CL500 Address Registers Format Description Units CL500 Float External Input 1 Float External Input 2 Custom Interval Day Block 1 per Integer Interval Data interval 2 per day Custom Interval Data Headers Custom RTC Date Time Custom EZ7 ID ModBus ID Serial Number Custom Recorder Info Demand Interval Custom Flags L1 Power Failure Battery Custom
17. FEET TOTAL UP TO 52 x CLASS 5000 METERS PC CHANNEL 1 RS 232 SERIAL PORT COM1 OR COM2 RS 232 KEYS 15 FEET MAX AC ADAPTER CHANNEL 3 UP TO 4000 FEET TOTAL UP TO 52 gt gt CLASS 5000 METERS M33275 Fig 13 RS 232 Configuration 6 8 2 Connecting the RS 232 Key to the Computer The RS 232 key is supplied with a 1 8 conductor cable fitted with RJ 45 plugs b 1 DB 9 serial COM port adapter c 1 AC adapter that converts 120VAC to 9VDC for powering the RS 232 key Connection Steps 1 Connect the 8 conductor cable to the left side jack labeled RS232 on the rear panel of the RS 232 key 2 Connect the appropriate COM port adapter DB 9 to the serial port on the back of the computer Plug the 8 conductor cable from the RS 232 key into the COM port adapter 3 Connect the provided AC adapter into the rear panel input on the RS 232 key Plug the adapter into a 120VAC outlet On the front panel of the RS 232 key two LEDs POWER ON and AC ON will light up 25 62 0399 02 CLASS 500 METER NOTE When the Honeywell Energy software is accessed on the computer a third LED RS232 READY will turn on This indicator will light up as soon as the Honeywell Energy software is booted up and the correct COM port is set up via the settings provided in the software s Locations menu 6 8 3 Connecting Class 500 Meters to the RS 232 Key using RS 485 On the rear panel of the
18. Honeywell Class 500 Meter ADVANCED KWH DEMAND METER INSTALLATION INSTRUCTIONS 62 0399 02 CLASS 500 METER TABLE OF CONTENTS Section 1 0 Section 2 0 Section 2 1 Section 2 2 Section 2 3 Section 3 0 Section 4 0 Section 5 0 Section 6 0 Section 6 1 Section 6 2 Section 6 3 Section 6 4 Section 6 5 Section 6 6 Section 6 7 Section 6 8 Section 6 9 Section 6 10 Section 6 11 Section 6 12 Section 6 13 Section 7 0 Section 8 0 Section 9 0 Section 10 0 Section 10 1 Section 10 2 Section 10 3 Section 11 0 Section 12 0 Section 13 0 Section 14 0 62 0399 02 Introduction Internal Electronic Assemblies Main Power Board Display Board Input Board Meter Technical Specifications Safety Label Definitions and Information Precautionary Safety Information Meter Installation Mounting the Class 500 Meter Main Power Board Connections Phasing of Line Voltage Current Sensor Installation amp Wiring Main Power amp Current Sensor Wiring Diagram Line Voltage Current Sensor Diagnostics RS 485 Wiring RS 232 Communications Modem Wiring Modbus RTU Wiring BACnet Wiring Connecting Class 500 Meters to USB Key using RS485 Ethernet Communications Multiple Load Monitoring Preventative Scheduled Maintenance Lithium Battery Replacement Class 500 Meter Operating Modes Start Up Screens Normal Mode Display Screens How to Program the Display Screens Frequently Asked Questions Protocol Descriptions High Voltage Metering Meter Limited Warr
19. Internal Electronic Assemblies 62 0399 02 4 CLASS 500 METER 2 1 Main Power Board Connections to this board include the MAIN Power Input and current sensors The MAIN Power Input terminals are positions one through four on the four position screw terminal block TB1 These terminals are covered with a protective shield for safety purposes The current sensor assemblies interface to the TB2 TB3 and TB4 Each terminal block corresponds to an input voltage phase care must be exercised to ensure that each current sensor is connected to the correct terminal block One three terminal screw connector TB42 is provided for RS 485 communications One RJ 45 jack J8 is provided for 10 100 base T Ethernet The contact is a solid state switch for the phase loss alarm function Switching is limited to 100 ma 0 1 amp and voltage should not exceed 60 Volts AC or DC The N O contact closes within the meter due to the loss any one of the three lines of voltage inputs to the meter The contact closure may be used to activate an audible alarm light control coil or other indicator device This alerts appropriate personnel to the loss of voltage An emergency phone dialer may also be programmed to send notification automatically by phone text or pager Alarming devices to be supplied by others and are not included by with the Honeywell Class 500 meter One two terminal screw connector provides phase loss alarming Optional card header J4 is a 10 p
20. Multiply the meter display readings by the number of sets of current sensors installed Example Meter readings of 5 kWh with 2 sets of current sensors 10 kWh is the actual usage 5 x 2 10 NOTE One set of current sensors equates to three sensors one per phase The multiplier only applies when extra sets of current sensors are installed on one meter If you are using only one set of three current sensors the multiplier is not required LINE VOLTAGE CURRENT SENSORS A B ZA B SC W B B W CURRENT SENSOR LEADS LOAD SOURCE LINE M34643 Fig 19 Three Phase Multiple load Wiring Diagram 62 0399 02 34 CLASS 500 METER LINE VOLTAGE CURRENT SENSORS A C OAOBOCN B W B W B W N SOURCE gt e eM LOAD SOURCE LOAD B A INSTALL JUMPER WIRE M34644 Fig 20 Single Phase Multiple Load Diagram 8 0 PREVENTATIVE SCHEDULED MAINTENANCE The unit is shipped in a calibrated and fully functional tested condition Since the unit is factory calibrated using proprietary firmware algorithms no internal unit adjustments are necessary This unit contains no internal adjustments so no preventative or scheduled maintenance is required No cleaning or decontamination procedures are required for this instrument 35 62 0399 02 CLASS 500 METER 9 0 LITHIUM BATTERY REPLACEMENT INSTRUCTIONS The Class 500 kWh Demand meter has a Lithium Battery Cell which is used t
21. OWN to select Y or N Save changes Y N 7 Press SELECT to save new settings This will also return you to main menu In main menu select EXIT to get out of programming mode and return to normal display mode 43 62 0399 02 CLASS 500 METER 10 3 4 Peak Demand Reset To reset the recorded peak KW demand complete the following steps 1 Press the MENU button until Reset kW kWh Read is indicated by the arrow on the display DATE amp TIME DEVICE ID IP SETTINGS gt RESET KW KWH READ 2 Press the SELECT button The following screen will appear on the display Reset kW only N Reset all N 3 Press the UP button to change the N to a Y after Reset KW only 4 The peak demand will be reset to zero and the meter will return to its normal scrolling display mode 62 0399 02 44 CLASS 500 METER 10 3 4 Display Hold Feature You can lock the scrolling display so that it will stay locked on any one of the six screens To stop the display from scrolling complete the following steps 1 Press the UP and DOWN buttons to choose which of the six screens you would like to display Press the Select button At the top of the display you will see the message HOLD1 This will lock the display for 1 HOUR NOTE The display hold feature has different selectable time periods 3 Pressing Select again will show the message HOLD6 This will lock the display for 6 HOURS Con
22. RS 232 key there are three jacks labeled as channels A B and C These are RS 485 serial communications ports used to connect the meters Each of these channels can be connected to as many as 52 individual meters over a total cable distance of 4 000 feet The channels are independent and must not be connected to each other Modular Plug Method This simple method requires using 4 stranded conductors inside a cable that is fitted with an RJ 11 type plug for 4 conductor modular systems at each end of the cable Do not use any pre made telephone cables 1 Plug the 4 wire RJ 11 cable plug assembly into Channel A on the RS 232 key Connect the other end of this cable to the meter via the RS 485 port PORT 2 at the bottom right of the Class 500 meter main power board NOTE The total combined cable length must not be more than 4000 feet 2 Each meter has one yellow TX and one green RX LED located on the right side of meter board just below the ribbon cable If the system is properly wired these two LEDs will be OFF These LEDs will fl ash when the computer and meter are communicating 62 0399 02 26 CLASS 500 METER 6 9 Modem Wiring UP TO 4000 RS 232 SERIAL FEET TOTAL PORT COM1 THROUGH COM3 MAXIMUM 15 FEET CHANNEL 1 UP TO 52 CLASS 5000 METERS PER CHANNEL PC OR WINDOWS COMPATIBLE TO 4000 CHANNEL 3 FEET TOTAL UP TO 52 zx CLASS 5000 METERS PER CHANNEL
23. S ON CHANGING ID AND IP ADDRESSES CONTROL UNIT WITH MODBUS COMMUNICATION M32786 ETHERNET NETWORK M32787 Fig 18 Ethernet IP Communications 33 62 0399 02 CLASS 500 METER 7 0 MULTIPLE LOAD MONITORING The Honeywell Class 500 meter provides extreme flexibility by allowing additional sets of current sensors to be used in parallel so multiple load locations can be monitored by one meter This feature allows a totalized display readout from two or more load circuits You may use parallel sensors to monitor specific breakers from one panel specific breakers from more than one panel two or more complete panels etc When paralleling current sensors the following rules must be followed for accurate readings 1 Current sensors must be installed in complete sets of three with a maximum of three sensors installed in parallel per phase NOTE In 1 phase option sensors must be installed in set of 2 with maximum of three sensors per phase 2 All sensors used in parallel must be of the same amperage rating all 100 amp all 400 amp etc The rating is determined by the current rating of the meter For example a 200 amp meter must use extra sets of 200 amp current sensors 3 All locations being monitored must have the same power source 480 volt meter cannot monitor a 208 volt load nor can a meter monitor two 480 volt loads if they are from different originating power sources or from different transformers 4 4
24. SNVT count inc f Real power kW R phase C nvoReact Pwr PhA SNVT count inc f Reactive kVAR R power phase A nvoReact Pwr PhB SNVT count inc f Reactive kVAR R power phase B 55 62 0399 02 CLASS 500 METER Lonworks SNVT Types Point Map CL500 nvoReact Pwr SNVT count inc f Reactive power phase C kVAR nvoAppar Pwr PhA SNVT count inc f Apparent power phase A kVA nvoAppar Pwr PhB SNVT count inc f Apparent power phase B kVA Pwr PhC SNVT count inc f Apparent power phase C kVA nvoPwr Fact PhA SNVT pwr fact f Power factor phase A PF nvoPwr Fact PhB SNVT pwr fact f Power factor phase B PF nvoPwr Fact PhC SNVT pwr fact f Power factor phase C PF nvoCurrent PhA SNVT amp f Current phase A Amps nvoCurrent PhB SNVT amp f Current phase B Amps nvoCurrent PhC SNVT amp f Current phase C Amps nvoVolt LN PhA N SNVT volt f Voltage line to neutral phase A N Volts N nvoVolt LN PhB N SNVT volt f Voltage line to neutral phase B N Volts N nvoVolt LN PhC N SNVT volt f Voltage line to neutral phase C N Volts N nvoVolt LL PhA B SNVT volt f Voltage line to line phase A B Volts L nvoVolt LL PhB C SNVT volt f Voltage line to line phase B C Volts L nvoVolt LL PhC A
25. SSAGES SHOULD NOT BE ON CONTINUOUSLY WHEN THE METER IS INSTALLED PROPERLY AND IS IN WORKING ORDER 6 6 1 Line Voltage Diagnostics The diagnostics program detects line voltage faults by displaying one of two messages PH Missing B C or Phase sequence error PH Missing B C Indicates that the line voltage is missing on Phase B and or Phase C This message will appear whenever the power on either Phase B or Phase C is off Screen 5 Voltage per Phase will also indicate a loss of line voltage Phase sequence error Indicates that the single phase or the three phase line voltage is not hooked up in the proper phase sequence This message should never be seen continuously on the display during normal operation The meter will not display correct electrical data in this condition The phase sequence problem must be remedied in order for the meter to work properly 21 62 0399 02 CLASS 500 METER 6 6 2 Current Sensor Diagnostics The load current must be at least 1 of the meter s rated load in order to use the diagnostic function Current sensor diagnostics can detect 1 Reversed current sensors 2 Incorrect phase correspondence 3 Unusually low power factor 0 642 or lower CT Error ABC is used to detect the swapping of current sensor phases This message could in some rare cases indicate a low lt 65 power factor condition This message may appear intermittently due to changes in line conditions It should not be on continuou
26. STRIB UTED BUT NOT MANUFACTURED BY HONEYWELL ARE NOT WARRANTED BY HONEYWELL AND BUYER MUST INSTEAD RELY ON THE REPRESENTATIONS AND WARRANTIES IF ANY PROVIDED DIRECTLY TO THE BUYER BY THE MANUFACTURER OF SUCH PRODUCT OR COMPONENT 61 62 0399 02 CLASS 500 METER 62 0399 02 62 63 CLASS 500 METER 62 0399 02 CLASS 500 METER Automation and Control Solutions Honeywell International Inc Honeywell 1985 Douglas Drive North U S Registered Trademark Golden Valley MN 55422 2013 Honeywell International Inc customer honeywell com 62099902 JFG Rav 07 19 Printed in United States
27. Value Reserve C No units Present Value External Input 1 Pulse Present Value External Input 2 Pulse Present Value 1 To clear single meter kWh kVARh select reset kW kWh on the display menu of the meter This function will also reset external inputs Jumper J6 must be closed Remove J6 when changes have been completed 2 External inputs are standard on Class 500 meters and optional on Class 3400 meters Part of Expanded Feature Package To clear external inputs select reset kW kWh on the display menu of the meter This function will also reset kW kVARh Jumper J6 must be closed Remove J6 when changes have been completed 53 62 0399 02 CLASS 500 METER 62 0399 02 54 Instance ID BACnet Object BACnet Property CL500 BACnet Device ID Device Object identifier R BACnet Device ID Device Object name R BACnet Device ID Device Object type R BACnet Device ID Device System status R W BACnet Device ID Device Vendor name R BACnet Device ID Device Vendor Identifier R BACnet Device ID Device Model name R BACnet Device ID Device Firmware revision R BACnet Device ID Device Application software version R BACnet Device ID Device Location R W BACnet Device ID Device Description R W BACnet Device ID Device Protocol version R BACnet Device ID Device Protocol services supported R BACnet Device ID Device Protocol object types supported R BACn
28. al See the section 6 2 5 F Screen 6 Volts RMS Phase to Phase See the section 6 2 5 F Screen 7 Power Factor Per Phase There should be 0 0 PF on all three phases Or in the Single Phase option 0 0 in A and B phases NOTE The meter will be reset later via the software during startup procedures 62 0399 02 16 CLASS 500 METER 6 4 Current Sensor Installation amp Wiring Once the AC voltages have been confirmed to be within acceptable limits you are ready to install the current sensors TB2 is the input for Phase A TB3 is the input for Phase B and TB4 is the Phase C input For the Single Phase option use TB1 pos 5 amp 6 are for the A Phase TB1 pos 788 are for the B phase factory installed jumper wire on positions 9 amp 10 Factory installed Jumper should not be removed The Class 500 meter can only be used with two types of 0 2V current sensors 1 Split core current sensor This sensor opens so that it can be attached around the circuit being monitored without interrupting power Unless otherwise speci fied all Class 500 meters are supplied with this sensor type Solid core current sensor This sensor does not open and requires the monitored conductor to be removed from the circuit to install the current sensor This type is only supplied when specified at time of order 6 4 1 Installing the Split Core Current Sensor Assembly 1 Each phase being monitored will require one two piece current sensor assembly Op
29. als of PORT 1 of each meter so that the GND terminals on all meters are linked GND to GND to GND RS 485 TERMINAL M33274 Fig 12 RS 485 Terminal After performing these steps all of the meters will be connected in a daisy chain configuration This network of meters can then be connected to the RS 485 network and communication can be established Internal Modem An optional internal modem inside one meter will communicate with the others via the RS 485 network Simply connect one of the two telephone jacks on the modem to the telephone line to complete the installation Local Computer A local computer installed in the building can communicate with the RS 485 network The computer must be connected to an RS 232 key The RS 232 key is then connected to an available RS 485 jack in the meter using an RJ 11 cable NOTE Don t confuse the modem s telephone jacks with the RS 485 jacks NOTE When using one meter with an external modem only the telephone line is connected RS 485 is not needed 62 0399 02 24 CLASS 500 METER 6 8 RS 232 Communications 6 8 1 Hardwired System using the RS 232 Communication Key The RS 232 communications key allows you to connect Class 500 meters to a personal computer that has the Honeywell Energy software installed The computer communicates with the meters through the RS 232 key The RS 232 key must be located within 15 feet of the host computer UP TO 4000
30. anty NO Q RO 12 13 13 14 16 17 20 21 23 25 27 31 31 32 33 34 35 36 38 38 39 43 46 48 58 61 CLASS 500 METER 1 0 INTRODUCTION The Honeywell Class 500 meter is a 3 phase meter with communications The device is used to monitor electric power usage of individual loads after the utility meter and store kW and kVAR data for automatic meter reading The Class 500 meter is dual protocol capable and provides both RS485 and Ethernet communications Installation must only be performed by qualified personnel and in accordance with these instructions and all applicable local and national electrical codes Honeywell and its representatives assume no responsibility for damages or injury resulting from the improper installation of this meter Verify the input voltage rating and configuration on the unit panel label to ensure that it is suitable for the intended electrical service For example Class 500 meters labeled for 120 208V service MUST NOT be installed on service feeds of 277 480 volts or 347 600 and vice versa Meter Labeled Works On 120V 120V Single Phase 120 240V 120 240V Single Phase 277V 277V Single Phase 208V 208V Three Phase 240V 240V Three Phase 400V 380 415 400V Three Phase 480V 480V Three Phase 600V 600V Three Phase Verify that the Class 500 meter s current sensors are sized suitably for the load to be monitored Compare the color of the arrows on the
31. arging any static buildup on your person To discharge yourself touch a grounded metal object such as conduit or an earth grounded metal enclosure WARNING High voltages present on main PCB terminal block TB1 screw terminals Risk of serious injury and or electrical shock exists Prior to performing any wiring operations review all contents of the user manual and de energize the MAINS power switch Only qualified personnel should perform installation wiring Installation wiring must comply with all local and national electrical codes WARNING NEVER open front panel of unit while unit has MAINS power applied Failure to comply can increase the risk of serious injury and or electrical shock 62 0399 02 12 CLASS 500 METER 6 0 METER INSTALLATION 6 1 Mounting the Class 500 Meter l 5 8 16 6 35 64 166 7 51 64 198 1 3 32 28 THROUGH NEAR SIDE ONLY 3 25 64 86 M34684 Fig 5 Enclosure Dimensions Use appropriately sized mounting hardware to fasten the meter enclosure to the selected mounting surface The four housing mounting holes are centered 6 75 H x 4 W NOTE Units housed in UL Type 1 JIC steel enclosures must only be installed in indoor environments where they will not be affected by the elements 13 62 0399 02 CLASS 500 METER 6 2 Main Power Board Connections 1 Installing a temporary groun
32. ations or other work has been performed by Buyer or others on such item other than work performed with Honeywell s authorization and according to its approved proce dures iii the alleged defect is a result of abuse misuse improper maintenance improper installation accident or the negligence of any party iv damaged as a result of events beyond Honeywell s control or other force majeure events or v used in conjunction with equipment components accessories parts or materi als not supplied or approved by Honeywell This Limited Warranty is limited to the obligation to repair or replace the manufac tured product This is the sole and exclusive remedy for any breach of warranty IN NO EVENT SHALL HONEYWELL BE LIABLE FOR ANY INDIRECT INCIDENTAL SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES INCLUDING ANY DAM AGE FOR LOST PROFITS ARISING OUT OF OR IN CONNECTION WITH THE FURNISHING OF PRODUCTS PARTS OR SERVICES OR THE PERFORMANCE USE OF OR INABILITY TO USE ANY PRODUCTS PARTS OR SERVICES SALE OF OR OTHERWISE WHETHER BASED IN CONTRACT WARRANT Y TORT INCLUDING WITHOUT LIMITATION NEGLIGENCE OR ANY OTHER LEGAL OR EQUITABLE THEORY EXCEPT AS EXPRESSLY PROVIDED HEREIN HONEYWELL MAKES NO WAR RANTY OF ANY KIND EXPRESS OR IMPLIED WITH RESPECT TO ANY PROD UCTS PARTS OR SERVICES PROVIDED BY HONEYWELL INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FIT NESS FOR A PARTICULAR PURPOSE PRODUCTS OR COMPONENTS DI
33. blinks To change the number of the digit use Button 3 Up Button to cycle through O to 9 Press Button 4 to move to the next digit and repeat Step 5 To exit the mode of changing number by digit press Select Button 9 To save the new number Save changes Y N press Main Menu Button and select Y to save NOTE The menu items that can be changed by digit are IP address Gateway Subnet Mask BACnet Device ID BACnet MSTP MAC Address max mas ters Modbus ID and dollar cost CO2 lbs for Green Net meters This will also return you to main menu In main menu select EXIT to get out of programming mode and return to normal display mode 62 0399 02 42 CLASS 500 METER 10 3 3 IP Setting Display Screen To Change the IP settings complete the following steps 1 Press the MENU button 2 The following screen will appear gt DATE amp TIME DEVICE ID IP SETTINGS RESET KW KWH READ 3 Use UP or DOWN button until the arrow is on the IP Setting line DATE amp TIME DEVICE ID gt IP SETTINGS RESET KW KWH READ 4 Press the SELECT button The IP Setting Screen will appear ENABLE DHCP N IP 192 168 0 168 MSK 255 255 255 0 GWY 192 168 0 1 5 Use UP or DOWN button to make changes press the SELECT button to advance to the next setting Repeat this step until all the settings have been updated 6 If changes were made you ll be asked to save press UP or D
34. configuration Section 6 7 with BELDEN 1120A cable or equivalent The cable rating of 600V allows the RS 485 network to be connected to 480 volt meters Up to 52 meters can be installed on a network string The maximum combined length of all daisy chained cables must not exceed 4000 feet The meter to network connection is through the 3 screw terminal which is located on the Main Power Board of the meter M33274 Fig 16 Modbus R Wiring The meter is shipped with a Modbus ID number of 01 This must be changed if the network has more than one meter installed The change must be done before the meter is introduced into the network The meter can be numbered from 1 to 247 There can be no duplicate numbers on a network so caution must be taken when assigning a meter ID number prior to its installation on the RS 485 network SEE SECTION 10 FOR INSTRUCTIONS ON CHANGING ID AND IP ADDRESSES 6 11 BACnet MS TP Wiring BACnet MS TP wiring is the same as Modbus and EZ7 wiring See Sections 10 and 11 for instructions on changing and IP addresses 31 62 0399 02 CLASS 500 METER 6 12 Connecting Class 500 Meters to the USB Key using RS485 The USB Key plugs into the PC s USB port and provides a termination point for the RS485 wiring from the meters Up to 52 meters can be Daisy chained with up to 4000 feet total RS485 wiring The USB Key is labeled for plus minus and ground and the wiring must match the same positio
35. corner a Connect the NEUTRAL wire to the appropriate terminal block position AKA PHASE PHASE PHASE UTRAL pi SENSOR N i Xe mi JA ET POWER INPUTS CURRENT SENSO Fig 6 Terminal Block TB1 NOTE For 3 wire delta type applications do NOT connect the NEUTRAL wire Remove the terminal block screw for this position b Earth Ground Connect the Earth Ground to the PCB mounting screw in the lower right corner 62 0399 02 14 CLASS 500 METER c External Switch Mechanism In Line Fuse Installation To ensure a Safe installation the Class 500 meter requires an external switch mechanism such as a circuit breaker be installed on the Class 500 MAINS input wiring The switch mechanism must be installed in close proximity to the meter and easily reachable for the operator This device must also be marked as the disconnecting device for the Class 500 meter Install 1 10 Amp Slow Activation in line fuses with the suitable voltage rating for each conductor phase at the MAINS input to the meter The fuses must be labeled to indicate voltage and current rating as well as element characteristics The fuse element must be slow activating type d Connect the three AC main power wires Phases A B and C to their respec tive positions as labeled on terminal block TB1 and tighten to 7 in Ib After all conductors are connected to each of their respective terminal block positions and tightened down verify that
36. d for ESD protection With all circuits de energized connect a temporary protective earth ground connection for ESD protection Prior to performing any unit wiring be sure to discharge any static on your per son 2 Installing the Class 500 protective earth ground Connect an earth ground wire to the Class 500 protective earth ground lug with a torque of 7 N m for meters in metal enclosures WARNING Failure to attach the protective earth ground wire securely to the meter creates a potential shock hazard Do not operate the meter without a protective earth ground connection securely installed 3 Wire Entry One 3 4 conduit opening is located on the bottom of the unit enclo sure This opening is used for bringing in MAINS power and for current sensor wiring Route the appropriate cabling to and through the respective enclosure opening 4 After installing the conduit fitting and conduit verify that each conduit slip nut is securely tightened to its respective conduit fitting Any unused openings must be sealed with a UL rated plugging device suitable for the rating of the enclosure check formatting NOTE Metallic enclosure has one additional 1 2 conduit opening at top of unit 5 Unit MAINS wiring The first four positions of terminal block TB1 located at the bottom left corner of the main power board are clearly labeled Phase A B C N neutral Earth Ground MUST be connected to the PCB mounting screw in the lower right
37. en the two piece current sensor assembly by releasing the nylon clamp using a fl at head screwdriver Fig 7 Split Core Current Sensor 2 Reassemble the current sensor assembly around the conductor s to be moni tored Ensure the current sensor halves marked Load are both facing the load side of the conductor The colored arrow will be on the source side of the con ductor being monitored and MUST be pointed in a clockwise direction around the conductor being monitored Tighten the nylon clamp to complete the assem bly 17 62 0399 02 CLASS 500 METER SOURCE M33213 Fig 8 Installation of a Split Core Sensor IMPORTANT When looking from the source side of the conductor s being monitored you should see the arrow on the current sensor assembly The arrow should be pointing in a clockwise direction around the conductor s being monitored If the arrow is not positioned on the source side inaccurate readings will result 6 4 2 Current Sensor Wiring Once the current sensors are installed onto their appropriate phase conductors you can begin terminating the current sensors onto the Class 500 main board The current sensors can be extended up to 500 feet for remote monitoring applications To extend the length of the wires use 22 AWG twisted pair wire with one white and one black wire The easiest way to connect the current sensors is to use the meter s built in current sensor diagnostics To do this there mus
38. er may be applied to the circuit board There are three LEDs located in the upper right corner of the Meter Board labeled BEAT STATUS and LOAD The BEAT and STATUS LEDs will blink once per second when the meter is operating normally twice per second if there is a problem If the monitored circuit is under load the LOAD LED will actively blink A heavy load will cause the LED to blink faster than a light load Very light loads will result in an extended blink time 19 62 0399 02 CLASS 500 METER 6 5 Main Power amp Current Sensor Wiring Diagram TERMINAL BLOCK LOCATED INSIDE E MON D MON METER LINE VOLTAGE CURRENT SENSORS A B C N N LOAD SOURCE RECOMMENDED FUSES OR CIRCUIT BREAKER PER THE NATIONAL ELECTRICAL CODE METER LOAD 6VA A NEUTRAL NOT USED IN DELTA SYSTEM A SPLIT CORE CURRENT SENSORS INSTALL ACCORDING TO INSTRUCTIONS M34291 Fig 9 3 Phase 3 Wire or 3 Phase 4 Wire Installation Diagram TERMINAL BLOCK LOCATED INSIDE METER LINE VOLTAGE CURRENT SENSORS OA OB OC N W B LOAD SOURCE RECOMMENDED FUSES OR CIRCUIT BREAKER PER THE NATIONAL ELECTRICAL CODE METER LOAD 6VA A CURRENT SENSORS INSTALLED ACCORDING TO INSTRUCTIONS A INSTALL JUMPER WIRES M34842 Fig 10 Single Phase 3 Wire Volt Installation Diagram 62 0399 02 20 CLASS 500 METER 6 6 Line Voltage Current Sensor Diagnostics Following is a list of diagnostic messages that may appear on the meter display DIAGNOSTIC ME
39. et Device ID Device Protocol revision R BACnet Device ID Device Object list R BACnet Device ID Device Max APDU length supported R BACnet Device ID Device Segmentation supported R BACnet Device ID Device Local time R BACnet Device ID Device Local date R BACnet Device ID Device APDU time out R W BACnet Device ID Device Number of APDU retries R W BACnet Device ID Device Device address binding R CLASS 500 METER Lonworks SNVT Types Point Map CL500 Network Variable Name SNVT Type Description Units CL500 nvoKWh Del 1 SNVT count inc f Energy kWh R delivered nvoKWh Rec SNVT count inc f Energy kWh R received nvoKVarh Del SNVT count inc f Reactive kVARh R 2 energy delivered nvoKVarh Rec SNVT count inc f Reactive kVARh R received nvoReal Pwr SNVT count inc f Real power kW R nvoReact Pwr SNVT count inc f Reactive kVAR R power nvoAppar Pwr SNVT count inc f Apparent kVA R power nvoPwr Fact SNVT pwr fact f Power factor PF R nvoPeak Dem SNVT count inc f Peak demand kW R nvoCurrent Avg SNVT amp f Current Amps R average nvoVolt LN SNVT volt f Voltage line Volts N R neutral nvoVolt LL SNVT volt f Voltage line Volts L R line nvoFrequency SNVT freq f Frequency Hz R nvoPhase Angle SNVT angle f Phase angle Degree R nvoReal Pwr PhA SNVT count inc f Real power kW R phase A nvoReal Pwr PhB SNVT count inc f Real power kW R phase B nvoReal Pwr PhC
40. interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Standards Compliance BACnet MS TP and IP protocol is BTL listed LonWorks TP FT 10 protocol is LonMark certified The presence of this label is a cautionary indicator identifying a danger risk The manual should be consulted prior to proceeding The presence of this label indicates an electrical shock hazard exists in the location or area where the label is placed Prior to proceeding the MAINS power must be disconnected and the manual consulted for safety information 11 62 0399 02 CLASS 500 METER 5 0 PRECAUTIONARY AND SAFETY INFORMATION N CAUTION Internal circuit card components are extremely sensitive to electrostatic discharge Be careful not to touch internal circuitry prior to disch
41. iring Communication will be over both RS485 and Ethernet for increased flexibility with various BAS equipment Class 500 dual protocol capable with choices of EZ7 Modbus BACnet and LON talk The BAS meter will be fully capable of interfacing with a BAS and an AMR Automated Meter Reading system simultaneously and independently RS 485 communication allows a computer or modem to communicate with one or more Class 500 meters You can connect as many as 52 meters along a 4000 foot RS 485 cable run Class 500 Smart meters are available with your choice of RS 485 communication options Modbus BACnet and E Mon Energy EZ7 There are four communication protocols available through the Class 500 RS 485 connection They are EZ7 Modbus RTU BACnet MS TP and Lonworks FT 10 The protocol is chosen when ordering the Class 500 meter A second protocol is available through the Ethernet port The Ethernet protocol is also chosen when the meter is ordered See ordering information for the available choices Daisy Chain Method This is the simplest method for connecting meters together Fig 11 Daisy Chain Configuration M32776 1 Connect the high terminal of PORT 1 of each meter together so that the ter minals on all meters are linked to to 2 Connect the low terminal of PORT 1 of each meter together so that the termi nals on all meters are linked to 23 62 0399 02 CLASS 500 METER 3 Connect the GND termin
42. nits Property 500 20 Analog Reactive power phase C kVAR Present Value R Input 21 Analog Apparent power phase A kVA Present Value R Input 22 Analog Apparent power phase B KVA Present Value R Input 23 Analog Apparent power phase C KVA Present Value R Input 24 Analog Power factor phase A PF Present Value R Input 25 Analog Power factor phase B PF Present Value R Input 26 Analog Power factor phase C PF Present Value R Input 27 Analog Current phase A Amps Present Value R Input 28 Analog Current phase B Amps Present Value R Input 29 Analog Current phase C Amps Present Value R Input 30 Analog Voltage line neutral phase A Volts N Present Value R Input N 31 Analog Voltage line neutral phase B Volts N Present Value R Input N 32 Analog Voltage line neutral phase C Volts N Present Value R Input N 33 Analog Voltage line line phase A B Volts L Present Value R Input 34 Analog Voltage line line phase B C Volts L Present Value R Input 35 Analog Voltage line line phase C A Volts L Present Value R Input 36 Analog Phase angle phase A Degree Present Value R Input 37 Analog Phase angle phase B Degree Present Value R Input 38 Analog Phase angle phase C Degree Present Value R Input 62 0399 02 52 CLASS 500 METER BACnet Object Descriptors CL500 Instance BACnet ID Description Units Property Reserve A No units Present Value Reserve B No units Present
43. ns on the meters If more than 52 meters are to be monitored additional USB Keys can be utilized to connect them to the PC UP TO 52 CLASS 5000 METERS ON RS485 CABLING E ZZZ USB KEY PC WITH USB PORT UP TO 4000 FEET TOTAL 2 RS485 CABLE LENGTH M33406 Fig 17 Connecting Class 500 Meters to the USB Key using RS485 62 0399 02 32 CLASS 500 METER 6 13 Ethernet Communications Ethernet IP communications connections are provided through an RJ 45 connector J8 in the lower right corner of the main power board This port can be connected directly to a network port of a PC using a Cat 5e crossover cable Two LEDs are provided directly above the connector The LINK LED is yellow and when lit indicates ethernet connectivity The ACT led is green and when lit indicates communication activity The communication protocol for the Ethernet port is selected when ordering the meter The available choices are EZ7 Modbus TCP IP and BACnet IP See the ordering information for the available choices in combination with the RS 485 output Class 500 Ethernet IP Addressable meters can be tied into a local Ethernet network individually or a single Ethernet connected meter can communicate with multiple RS 485 daisy chained conventional class 500 meters using a single IP address Each device that is connected directly to the ethernet network requires a unique IP address SEE SECTION 10 FOR INSTRUCTION
44. o retain the contents of SRAM and the RTC during power outages The battery has a life expectancy of greater than 5 years Nominal Working Voltage 3 Vdc Output Nominal Current Capacity 225 mAHr Cell Chemical Manganese Dioxide Lithium Operating Temperature Range 30 to 60 Degrees Celsius Manufacturer Panasonic Manufacturer s Part Number CR2032 Fig 21 Battery Specifications at 25 Degrees Celsius A WARNING Only replace battery with Panasonic part number CR2032 only Use of another battery may present a risk or explosion See owners manual for safety instructions Internal circuit card components are extremely sensitive to electrostatic discharge Be careful not to touch internal circuitry prior to discharging any static buildup on your person To discharge yourself touch a grounded metal object such as conduit or a metal enclosure exterior 62 0399 02 36 CLASS 500 METER The battery cell is mounted in a coin cell on the upper right side of the main power board Replace the battery if the low battery warning is on display Fig 22 Lithium Battery Cell Use the following procedure to replace the battery cell STEP 1 Disconnect power from the meter at the unit external circuit breaker STEP 2 Remove the battery from its holder and place on a non conductive surface STEP 3 Install new battery into the battery holder NOTE Care should be taken to insure that the replacement battery is ins
45. ositions for use with modem and LonWorks TP FT 10 J3 J4 TBI POSITIONS 1 4 MAIN POWER INPUT ETHERNET CONNECTION TB1 POSITIONS 6 10 CURRENT SENSOR RS 485 PHASE OUTPUT INPUTS CONNECTION M33271 Fig 2 Main Power Board 5 62 0399 02 CLASS 500 METER 2 2 Display Board The display board connects to the main power board via a flex ribbon cable and the board mounts on the inside of the housing door No additional connections to the display board are required The display board s LCD readout indicates the metered values as well as errors associated with the Class 500 meter such as phase loss or sensor error conditions UP SELECT Fig 3 Display Board 62 0399 02 6 CLASS 500 METER 2 3 Input Board The Class 500 meter is supplied with an input board which allows it to accept pulses dry contact from third party meters such as gas water BTU etc 20000000 INP1 INP2 OUT1 OUT2 INPUT TERMINALS CL5000 METER INPUT BOARD M33272 Fig 4 Input Board 7 62 0399 02 CLASS 500 METER 3 0 METER TECHNICAL SPECIFICATIONS c o Q S 2 5 8 Q 9 Q Eg 18 jeg 182 2 23 alo S G 68 88 Example H 50 208 100 J 103 KIT H50 208100 JO3KIT Brand Honeywell Class 500 Voltage 120 208 400 380 415 480 600 Amperage 2HV 100 200 400 800 1600 3200 Enclosure J JIC Steel I Interior only R Rain tight
46. r RJ 45 male IDC Input Output Voltage 5 VDC 18 VAC Ckt Input Isolation 5 3K VAC for 1 Minute Baud Rate 9600 IDR Interface Port Cable UL listed rated Telephone Cord 4 cond Input output Voltage Ground isolated 5 4VDC Cable Connector RF 45 Male IDC Or Screw Terminal Termination Circuit Input Isolation 5 3kVAC Circuit output Isolation 21 5kVAC Isolated Pulse Alarm Outputs TB5 TB6 Output Voltage Potential 0 VDC to 5 VDC Logic Levels Mating Plug Connector Weidmuller PN 152876 Signal Isolation Voltage 5 3K VAC for 1 Minute Recommended Manufacturer Littlefuse In line Fuse Mfg Part No KLDR 100 Rating 100mA Time delay 600VAC Cartridge Fuse Battery Cell Description Non rechargeable Cell Used For Memory Retention Manufacturer Panasonic Mfg Part No CR2032 Working Voltage 3 VDC Current Capacity 225 mAHr Electrolyte Manganese Dioxide Lithium 62 0399 02 CLASS 500 METER 4 0 SAFETY LABEL DEFINITIONS AND INFORMATION The 500 meter may contain one or more of the following labels Operator s should familiarize themselves with the meaning of each label to minimize risk FCC Notice This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful
47. re as follows Screen 1 Total Kilowatt Hours kWh Delivered TOTAL 123 KWH Screen 2 Peak Demand kW with Date amp Time Stamp Screen 3 Actual Load kW with Present Time 24 0 KW 06 14 11 08 46 58 Screen 4 Average Current amps Per Phase Note Single Phase option will only state PH A and PH B Screen 5 Average Voltage volts Per Phase Note Single Phase option will only state PH A and PH B Screen 6 Average Voltage volts Phase to Phase Note Single Phase option will only state P AB and P BA Screen 7 Power Factor pf Per Phase Note Single Phase option will only state PH A and PH B 39 62 0399 02 CLASS 500 METER DOWN ijp MENU M33279 Fig 23 Push Buttons 10 3 How to Program the Display Screens The display information can be programed using four push buttons switches The push buttons DOWN UP SELECT MENU are located at the top of the display board on the inside front door of the meter The buttons are used to program the following Date amp Time This field sets the month day year and time Device ID This field changes the default setting which is 1A for EZ7 and 2 for ModBus IP Settings This field allows you to select the DHCP or static IP address mask and gateway information Reset KW KWH Read This field resets the Peak kW Demand to zero 62 0399 02 40 CLASS 500 METER 10 3 1 Date amp Time Display Screen
48. sly NOTE f you have connected the current sensor to all three terminals and the error message is still appearing reverse the black and white wires and repeat the previous steps until the correct connection is found If the C7 Error message disappears you have found the correct sensor connection however the current sensor was not installed properly around the conductor or the sensor wires were extended and not spliced together correctly Correct the sensor installation reconnect the black wire to the black terminal and the white wire to the white terminal on the plug and reinstall the plug into the correct phase terminal for that current sensor The error message should disappear and the current sensor is now installed properly If the C7 Error message does not disappear at any time while trying all 3 inputs both ways check the AC voltage input from the current sensor between the black and white wires using an AC voltmeter It will read approximately zero volts indicating that the load current is very small or zero or the current sensors are not secured properly tight connection between core halves or lead splices not secure Once the first current sensor is connected properly and the error message disappears repeat the previous procedure for the remaining two current sensors When all error messages have disappeared and all sensors are installed correctly the meter is operational 62 0399 02 22 CLASS 500 METER 6 7 RS 485 W
49. t be at least 1 of the meter s current rating amps fl owing in each of the conductors being monitored The Class 500 meter s diagnostic program will provide data to ensure that the current sensor installation is done properly The current sensor connection points are located at the bottom right of the main power board These are terminals 5 through 10 of terminal block TB1 Each sensor connects to two terminals one labeled Black and the other White Current sensors should be connected to the meter one at a time and verified using the current sensor diagnostic program Connect one of the current sensors to TB1 terminals 5 and 6 Phase A Wait 5 seconds and look at the meter display 62 0399 02 18 CLASS 500 METER 6 4 2 Current Sensor Wiring continued If the meter displays an error message see below remove the wires from terminals 5 and 6 and install them on terminals 7 and 8 Phase B if an error message occurs with the sensor attached to terminals 7 and 8 try again on terminals 9 and 10 Phase C The CT Error message will disappear when the current sensor is connected to the correct terminals phase Error Messages CT ERROR A CT ERROR AB CT ERROR AC NOTE The 1 Phase option will only display errors for A and B Refer to the section on Current Sensor Diagnostics for assistance in troubleshooting these errors 6 4 3 Main Power After the meter circuit wiring has been examined for correctness pow
50. talled the same polarity as the battery that was removed No damage to unit or battery will occur if battery is inadvertently installed in the wrong direction STEP 4 Dispose of the used battery in accordance with the manufacturers Panasonic instructions 37 62 0399 02 CLASS 500 METER 10 0 CLASS 500 METER OPERATING MODES The Honeywell Class 500 meter is used to monitor electric power usage of individual loads after the utility meter and store kW and KVAR data for automatic meter reading 10 1 Start Up Screens When the meter starts up the screen first displays the meter name and firmware image type After approximately 4 seconds the screen displays misc information such as active configurations meter configurations phase voltage amperage calibration factors serial number Date time and firmware version 62 0399 02 38 CL500 M Starting Up 110608TR 1 38400 EZ7x EZ7x MD 3P 208V 200A CF 1 057 1 056 1 057 DT 00000000 06 21 01 Single Phase option will state MD 2P 208V 200A CLASS 500 METER 10 2 Normal Mode Display Screens The Class 500 meter features seven Normal Mode Display Screens for monitoring the meter Each screen is displayed for 5 second intervals before scrolling onto the next screen You can lock the scrolling display on any one of the seven screens This will be explained in detail on following pages Explanations of the Normal Mode Display Screens a
51. ternal modem using the supplied 8 conductor fl at modular cable 5 Connect the 9VDC adapter to the power input on the back of the RS 232 key and plug it into a 120VAC outlet IMPORTANT The modem should use a phone line that is dedicated exclusively to the AMR system Do not use a phone line that is shared by another modem or fax machine 62 0399 02 28 CLASS 500 METER 6 9 3 Baud Rate Selection The communication baud rate is selected by means of a jumper on the circuit board There are four 4 selections 9600 factory default 19200 38400 and 76800 Select 9600 when using the Class 500 meter with a modem The baud rate on the meter must always match the baud rate selected in the Honeywell Energy software otherwise communications will not work After a baud rate change press CPU Reset to register the change All meters in the daisy chain circuit must be set at the same baud rate The DIP switch is located above the RS 485 terminals Using other than 9600 BAUD will reduce the maximum cable length allowed for communication NOTE USE ONLY POSITIONS 3 AND 4 DO NOT CHANGE ANY OTHER POINTS N gt The selections are noted below gt gU 9 9 9 9 0 9 9 9 8 ra3438783h Fig 15 Baud Rate Selection 3 4 Baud rate ON JON 9600 EZ 7 modbus RTU BACnet MS TP OFF ON 19200 EZ 7 modbus RTU BACnet MS TP ON OFF 38400 Modbus RTU BACnet MS TP OFF OFF 78600 Bacnet MS TP
52. through the A phase sensor and the same for B amp C phases The meter should be sized by the highest amount of current being monitored by one sensor 47 62 0399 02 CLASS 500 METER 12 0 PROTOCOL DESCRIPTIONS Address Registers Format Description Units CL500 400011 2 Integer Energy delivered Wh Pulse 40003 2 Integer Energy received Wh Pulse 40005 2 Integer Reactive energy delivered VARh Pulse R W 40007 2 Integer Reactive energy received VARh Pulse R W 41001 2 Float Energy delivered kWh R W 41003 2 Float Energy received kWh R W 41005 2 Float Reactive energy delivered KVARh R W 41007 2 Float Reactive energy received kVARh R W 41009 2 Float Real power kW R 41011 2 Float Reactive power kVAR R 41013 2 Float Apparent power KVA R 41015 2 Float Power factor PF R 41017 2 Float Peak demand kW R 41019 2 Float Current average Amps R 41021 2 Float Voltage line neutral Volts N R 41023 2 Float Voltage line line Volts L R 41025 2 Float Frequency Hz R 41027 2 Float Phase angle Degree R 41029 2 Float Real power phase A kW R 41031 2 Float Real power phase B kW R 41033 2 Float Real power phase C kW R 62 0399 02 48 CLASS 500 METER ModBus Customer Point Map CL500 Address Registers Format Description Units 41035 Float Reactive power phase A KVAR 41037 Float Reactive power phase B kVAR
53. tinuing to press the Select button will provide additional timing choices HOLD12 Locks the display for 12 HOURS HOLD24 Locks the display for 24 HOURS HOLD Locks the display indefinitely To exit the HOLD mode Press the Select button as many times as needed until the HOLD message dis appears from the display Be sure to exit from the HOLD mode when you are done using this feature 45 62 0399 02 CLASS 500 METER 11 0 FREQUENTLY ASKED QUESTIONS Q A When providing line voltage to the meter can I tap off of the same breaker I am monitoring Yes the voltage can be pulled from the same breaker being monitored Q Can the meter s line voltage wires be run in the same conduit as the sensor leads Yes There will be no effect if the sensor leads and line voltage wires are run in the same conduit Can the meter s communication wires and line voltage be run in the same conduit It is not recommended to run these wires together due to noise concerns and their effects on the communications signal integrity Communications wires can be routed separately using a 1 2 conduit port How do find the cost for kWh and kW to bill my tenants Your local utility bill should list the cost per kWh and kW If not simply call your utility and ask them to provide you with the cost per kWh and kW What size wire do use for the line voltage leads These wires are normally sized at 14 AWG but be sure to
54. y now appears to the current sensor as a 0 25 amp signal This creates a conversion of the CT s primary current to a directly proportional 0 2 volt signal which is utilized by the Honeywell meter The example from the first paragraph has now become a 400 amp to 2 volt device by this technique 62 0399 02 58 CLASS 500 METER PASS 1 PASS 2 M34227 Fig 24 High Voltage CTs A HIGH B VOLTAGE CIRCUIT c High Volt CT with Secondary High Volt PT with Secondary 120 V M34228 Fig 25 Wiring Diagram For 3 wire High Voltage Circuits 59 62 0399 02 CLASS 500 METER This special high voltage meter installation shows the correct wiring procedure for 4 wire high voltage circuits In this application the 3 element meter connection is used on the secondary circuits of the user supplied high voltage PTs and CTs The Honeywell meter used in this application is the model H50 12025HV Installation of these meters requires the use of three 3 current sensors mounted on the secondaries of the high voltage Current Transformers See the drawing above for proper wiring For correct operation the meter must be installed correctly This special high voltage meter installation utilizes high voltage PTs Potential Transformers and CTs Current Transformers supplied by others The Honeywell meter is installed using the secondary outputs of these devices High voltage PTs reduce the primary voltage 4160v 13200v etc to a
Download Pdf Manuals
Related Search
Related Contents
Guía del usuario KX3300 - Black & Decker Service Technical Home Page Copyright © All rights reserved.
Failed to retrieve file