Home
Commercial CO Monitor
Contents
1. and the current CO level will be displayed If the monitor continues to detect CO levels of 20ppm or more the audible and visual alarm signals will automatically reactivate within 5 minutes If the CO level drops below 20ppm the alarm signals will not reactivate 7 WARNING Carbon monoxide monitors respond to the presence of CO They do not detect smoke IF YOU HAVE BEEN AWAY FROM THE BUILDING AND RETURN TO FIND THE ALARM S SOUNDING DO NOT ENTER THE BUILDING CALL THE FIRE DEPARTMENT FROM ANOTHER LOCATION DO NOT RE ENTER BUILDING FOR ANY REASON UNTIL YOU HAVE BEEN ASSURED THAT IT IS SAFE TO DO SO 8 MAINTENANCE CLEANING YOUR MONITOR You can clean your CO monitor by using a vacuum cleaner brush to vacuum around the openings on the CO monitor The outside of the CO monitor can be wiped with a soft cloth slightly dampened with water only AFTER CLEANING TEST YOUR CO MONITOR TO MAKE SURE THAT IT IS WORKING PROPERLY DO NOT PAINT ON OR NEAR THE ALARM The paint will block the vents and affect the alarm function NOT SPRAY AIR REFRESHENER CLEANING SUPPLIES OR INSECT KILLER ON OR NEAR THE ALARM Certain kinds of aerosol chemicals will damage the sensor and cause improper operation The area must be well ventilated when using cleaning supplies or similar contaminants 9 LIMITATIONS OF CARBON MONOXIDE MONITORS Carbon monoxide monitors are devices that can provide an early warning of the presence of CO gas at a reasonable cost Howe
2. CO level detected from 10 to 999ppm and update the detected value every 1 second The number Oppm will be displayed if less than 10ppm CO is detected The display accuracy may be affected by environmental conditions and other circumstances beyond manufacturer s control LCD BACKLIGHT FUNCTION In normal operation the LCD backlight is turned off to preserve battery life The backlight will automatically turn on for 5 minutes when alarm is activated The backlight will also turn on when the TEST RESET MUTE button is pressed to test the monitor or the DISPLAY MEMORY button is pressed to read the peak CO level and TWA record The backlight will automatically turn off when the TEST or DISPLAY MEMORY functions are completed DO NOT TRY TO TEST THIS CO MONITOR IN ANY OTHER WAY If no alarm sounds during a test check battery power If monitor still does not sound the unit may be malfunctioning and should be returned for service SEE SECTION 12 TEST THE CO MONITOR WEEKLY TO ENSURE PROPER OPERATION Erratic or low sound coming from your CO monitor may indicate a malfunctioning unit and it should be returned for service SEE SECTION 12 RESET MUTE Once the CO monitor activates an alarm it will not automatically reset mute itself Press the TEST RESET MUTE button once to temporarily silence the monitor for 5 4 minutes The muted alarm symbol X will be displayed the red LED will blink 4 times per minute
3. LCD will display the recorded data in the following order 1 The highest peak CO level detected within last 30 days from 10 E to 999 PPM 2 The total length of time in hours and minutes the highest CO level ET ay was detected over last 30 days including levels within 1096 of the Min peak 3 How many days hours and minutes ago a CO level within 10 of D the peak was last detected Min 4 The Time Weighted Average TWA concentration of CO detected over the previous 8 hours The monitor maintains the 30 most recent days of peak CO level history and the most recent TWA value To manually erase the record press the DISPLAY MEMORY button once and while the readings are being displayed press TEST RESET MUTE button once The monitor will sound one short beep and Lf will appear on the LCD display Disconnecting the battery will not erase memory TESTING To test your monitor press the TEST RESET MUTE button for 2 seconds The red LED will flash and the monitor s horn will beep 4 times remain silent 5 seconds then beep 4 times again if horn and electronic circuitry are working properly The current CO level detected will be displayed f the unit is already in the service condition the monitor will double beep and display Err and must be serviced immediately LCD DISPLAY FUNCTION In normal operation the LCD screen will display the current
4. LED are OFF displaying the Level How long ago a CO level sex wm While displaying peo record within 10 of the peak Day the peak record was last detected and Min The Time Weighted Average TWA TWA concentration of CO detected over the previous PPM 8 hours CI i Li is G d red LED One short beep wh ear Peak Displays LLf when record is reen and re are ne short beep when Record cleared OFF record is cleared Low Battery Displays IL 1 and current Green LED blinks once Chirps once per Power CO reading in PPM per minute minute a T Red LED flashes once Chirps once per endo Die Displays per minute minute Red LED blinks twice Chirps twice per Trousle sewice Displays per minute minute 12 SERVICE AND WARRANTY IMPORTANT SAFETY INSTRUCTIONS In the event of any malfunctions with the monitor do not attempt to repair the unit This product should be serviced by a qualified service technician Return the monitor for service to the address listed below ONE YEAR LIMITED WARRANTY The manufacturer PPI warrants to the original end user purchaser that this commercial CO monitor shall be free from defects in materials and workmanship from the date of purchase for one year If this CO monitor is determined to be defective in original materials or workmanship during the warranty period return the monitor to the address indicated below with delivery costs prepaid Do not attempt to repair this product yourself If determin
5. optional second screw 3 to 3 inches directly below it Leave the screw heads about 4 inch out from the wall Hang monitor onto the top screw head and gently pull down to secure Slide bottom of monitor from right to left until it seats firmly onto the lower screw if installed After installation TEST your CO monitor by pressing the TEST RESET MUTE button for two seconds Complete instructions regarding testing are outlined in SECTION 6 Be sure that the monitor is not obstructed by furniture equipment etc 6 OPERATION TESTING OPERATION The CO monitor is operational once a battery is installed A 3 minute start up test will EU ma BH BS display all words numbers and symbols J and flash the green LED every second When the test is complete the display should read Oppm and green LED blink once per minute LOW BATTERY CONDITION When the battery voltage drops below an acceptable level the monitor will chirp once per minute the green LED will blink once per minute and the low battery voltage symbol IL will appear on the LCD display Replace the battery immediately in order to provide uninterrupted protection Please see SECTION 5 for information regarding battery replacement SERVICE CONDITION The internal microcontroller continuously monitors the sensor and other critical components If an internal failure of any of these components should occur the CO monitor will double chirp once per m
6. 8505 Battery Powered Commercial CO Monitor OWNER S MANUAL IMPORTANT READ ALL INSTRUCTIONS BEFORE INSTALLATION AND SAVE THIS MANUAL FOR FUTURE REFERENCE CAUTION THIS MONITOR WILL ONLY INDICATE THE PRESENCE OF CARBON MONOXIDE GAS AT THE SENSOR CARBON MONOXIDE GAS MAY BE PRESENT IN OTHER AREAS THIS CARBON MONOXIDE MONITOR IS DESIGNED TO DETECT CARBON MONOXIDE GAS FROM ANY SOURCE OF COMBUSTION IT IS NOT DESIGNED TO DETECT SMOKE FIRE OR ANY OTHER GAS TABLE OF CONTENTS INFORMATION ABOUT CARBON MONOXIDE CO MONITOR FEATURES amp SPECIFICATIONS RECOMMENDED LOCATIONS OF CO MONITORS LOCATIONS TO AVOID INSTALLATION INSTRUCTIONS OPERATION AND TESTING WARNING MAINTENANCE LIMITATIONS OF CARBON MONOXIDE MONITORS 10 GOOD SAFETY HABITS WHAT TO DO WHEN THE MONITOR SOUNDS 11 DESCRIPTION OF AUDIBLE AND VISUAL SIGNALS 12 SERVICE AND WARRANTY uuu edm WARNING a DISCONNECTED OR LOW VOLTAGE BATTERY WILL RENDER THIS UNIT INOPERATIVE Do not try to repair this CO monitor yourself Refer to the instructions in SECTION 12 for service The UL 2034 Standard for Residential Carbon Monoxide CO Alarms does not permit UL Listed CO alarms to activate an alarm signal below 30 PPM CO The Pro Tech 8505 provides visual signals at 10 PPM and audible and visual alarm signals at 20 PPM and is not UL Listed This monitor is intended for commercial applications 1 INFORMATION ABOUT CARBON MONOXIDE WHAT IS CARBON MONOXIDE Ca
7. at they were not well they were too disoriented to save themselves by either calling for assistance or exiting the building Also due to size small children and pets are generally the first affected The following are the symptoms related to CARBON MONOXIDE POISONING Discuss them with all persons that may be affected MILD EXPOSURE Slight headaches nausea vomiting running nose sore eyes fatigue often described as Flu like symptoms MEDIUM EXPOSURE Severe throbbing headache dizziness drowsiness confusion fast heart rate EXTREME EXPOSURE Unconsciousness convulsions cardiorespiratory failure brain damage death 2 CO MONITOR FEATURES e Battery Powered Commercial CO Monitor e Accurate and Reliable Electrochemical Sensor e Integrated Filter for Removing Nuisance Gases e Samples for Carbon Monoxide Every Second e Alpha Numeric LCD Readout with Smart Back Light e Continuous Display of Current CO Levels Detected from 10 to 999 PPM e Records and Displays Peak CO Level with Duration and When Occurred e Calculates and Displays 8 Hour Time Weighted Average TWA Concentration e Stores 30 Days of Data e Audible and Visual Alarm Signals e Self Diagnostic Circuitry and Sensor Life Monitor e Complies with ACGIH Cal OSHA NIOSH and OSHA Workplace Exposure Limits e One Year Limited Factory Warranty Smart CO value Al
8. eaches the Threshold Limit TLV Recommended REL or Permissible PEL Time Weighted Average TWA carbon monoxide exposure limits established by the American Conference of Governmental Industrial Hygienists ACGIH National Institute for Occupational Safety and Health NIOSH and Occupational Safety and Health Administration OSHA Workers who are known to be at high risk to CO exposure should also wear personal gas monitors 3 RECOMMENDED LOCATION OF CO MONITORS CO poisoning can happen anywhere in a building At the minimum CO monitors should be located on every level of the building near the persons who may be potentially affected by CO poisoning and where workers can hear any alarm More than one CO monitor may be required within different areas of the building A space which contains fuel burning equipment and areas and rooms adjacent to this space or any parking garage should also have a CO monitor installed If the monitor is installed in a hallway and any office doors are kept closed install a CO monitor in each of these rooms If the monitor is installed in a large open area one monitor should be installed for every 1000 square feet of vertically unobstructed space A monitor should also be installed near each exit from the building to alert employees of a CO alarm condition prior to entering Mount CO monitors onto an interior wall about three inches above eye level for the best view of the display readout CO detection
9. ed to be defective in original materials or workmanship the CO monitor will be repaired or replaced at the sole discretion of the manufacturer This warranty does not cover normal wear of parts or damage resulting from any of the following improper storage negligent use or misuse of the product use contrary to the operating instructions operation in unconditioned space below 40 F or above 100 F disassembly or repair or alteration by anyone other than the manufacturer or an authorized service center Further the warranty does not cover acts of God such as fire flood earthquakes hurricanes and tornadoes The liability of the manufacturer or of any of its parent or subsidiary corporations arising from the sale of this product or under the terms of this limited warranty shall not in any case exceed the cost of the replacement of the CO monitor In no case shall the manufacturer or any of its parent or subsidiary corporations be liable for consequential loss or damages resulting from the failure of the CO monitor to activate or for the breach of this or any other warranty expressed or implied even if the loss or damage is caused by the manufacturer s negligence or fault These limitations or exclusions may not apply in some states where limitations on the duration of an implied warranty or exclusions or limitations of incidental or consequential damages are not allowed This warranty extends to the original end user purchaser only a
10. hen they first turn on IN DUSTY AREAS Dust can build up on the monitor and cause failure to alarm IN CLEANING SUPPLY ROOMS Cleaning chemicals and painting supplies may cause nuisance alarms IN VERY HOT OR COLD AREAS Do not install the monitor onto an exterior wall or in unconditioned spaces or areas which are below 40 F 4 4 C or above 100 F 37 8 C IN HAZARDOUS LOCATIONS This monitor is not suitable for installation in a hazardous location as defined in the National Electrical Code 5 INSTALLATION INSTRUCTIONS NOTE REVIEW SECTION 3 RECOMMENDED LOCATIONS OF CO MONITOR AND SECTION 4 LOCATIONS TO AVOID PRIOR TO INSTALLING YOUR CO MONITOR The proper power for the Pro Tech 8505 commercial CO monitor is a 9V battery Constant exposure to high or low temperatures or humidity may reduce battery life BATTERY INSTALLATION AND REPLACEMENT Slide down and remove battery door and attach a new 9 Volt alkaline battery to the battery cable Battery must snap firmly onto both connectors Use an Ultralife U9VL J lithium battery for a longer life Place the battery in the battery compartment and slide the battery door upward and over the compartment until the door latches firmly in place Press the TEST RESET MUTE button to verify activation See TESTING in section 6 MOUNTING INSTRUCTIONS After selecting the proper location as described in SECTION 3 drive one screw into the wall about three inches above eye level and an
11. inute the red LED will blink twice per minute and will appear on the LCD display The trouble condition indicates a problem with the unit and it will not alarm if exposed to CO See SECTION 12 for service information SENSOR LIFE MONITOR The electrochemical sensor has a life expectancy of 2 years however the monitors CO readings will decrease in accuracy after the first year A microcontroller counts the total time that the CO monitor is under power After 2 years the Sensor End of Life signal will activate indicating that the sensor life has expired The CO monitor will chirp once per minute the red LED will blink once per minute and will appear on the LCD display When the sensor life expires the monitor may still work for a period of time but it may not alarm when exposed to CO It is recommended that you replace the monitor annually but once the sensor life expires you must replace the monitor immediately ALARM CONDITION When CO gas is detected at a level and duration specified in SECTION 2 the monitor will alarm and the red LED will flash The monitor will display the current CO level detected sound 4 short beeps every 5 seconds for 5 minutes and thereafter 4 short beeps every minute until the TEST RESET MUTE button is pressed and the CO level detected drops below 20ppm DISPLAY PEAK CO EXPOSURE RECORD To manually display the highest CO level detected press the DISPLAY MEMORY button for 2 seconds The
12. is best achieved by installing monitors in all rooms and areas of building DO NOT install monitor within 5 feet of combustion equipment DO NOT install monitor on any exterior wall or within 1 foot of exterior door or window Conditions which can result in CO production or exposure 1 Excessive spillage or reverse venting of fuel burning appliances caused by outdoor ambient conditions such as i Wind direction and or velocity including high gusts of wind Heavy air in the vent pipes cold humid air with extended periods between cycles ii Negative pressure differential resulting from the use of exhaust fans iii Several fuel burning appliances competing for limited internal air iv Vent pipe connections vibrating loose from furnaces boilers or water heaters v Obstructions or unconventional vent designs which amplify the above situations vi Poorly designed or maintained chimneys and or vents 2 Extended operation of unvented fuel burning devices Temperature inversions which can trap exhaust gases near the ground 4 Truck car or forklift operating or idling in an open or closed attached garage or warehouse or near a building 4 WARNING LOCATIONS TO AVOID NEAR COOKING APPLIANCES To avoid nuisance alarms and grease build up which may cause monitor failure do not install monitor within five feet of cooking appliances WITHIN FIVE FEET OF FURNACE BOILER SPACE HEATER OR WATER HEATER These devices often spill out CO w
13. l peak CO level detected duration and when occurred Peak Level Memory History prior 30 days Time Weighted Average TWA calculates average CO concentration for prior 8 hours Display Backlight automatic for alarm manual for memory and testing functions Power On Signal flashing green LED Audible Alarm Signal 85dB at 10 feet 4 short beeps every 5 seconds for 5 minutes and thereafter 4 short beeps every minute Visual Alarm Signal Red LED flashes in sync with audible alarm signal Mute Button silences audible signal for up to 5 minutes green LED blinks once min Test Functions self diagnostic circuitry and manual test button Low Battery Signal low battery icon green LED blinks once min one chirp min Malfunction Signal displays Err red LED blinks twice min two chirps min Sensor Expiration Signal displays End red LED blinks twice min one chirp min Storage Temperature and Humidity 30 F to 120 F 30 95 RH Operating Temperature and Humidity 40 F to 100 F 1096 90 RH Unit Weight 8 oz w battery Unit Dimensions 5 9 16 h x 3 7 16 w x 1 5 16 d Color White Life Expectancy Two years Warranty One year limited warranty The accuracy of the display is an estimate for the first year only The accuracy may also be affected by environmental conditions and other circumstances beyond manufacturer s control This fixed CO monitor is designed to activate audible and visual alarm signals before the immediate area r
14. lt to local code Have a meeting to discuss your escape plan and show everyone what to do in case an alarm sounds Determine a place outside the building where you can all meet if an alarm occurs Familiarize everyone with the sound of the alarm and train them to leave the building when they hear it Practice a CO and fire drill at least once every six months Practice allows you to test your plan before an emergency You may not be able to reach everyone t is important that they all know what to do WHAT TO DO WHEN THE ALARM SOUNDS If alarm signal sounds the red LED will flash and the alarm will sound 4 short beeps every 5 seconds 1 Operate TEST RESET MUTE button to temporarily silence alarm 2 Immediately move to fresh air outdoors or by an open door or window Check that all persons are accounted for Do not re enter the premises or move away from the open door window until the premises have been aired out and your monitor remains in its normal condition 3 After following steps 1 and 2 if the alarm reactivates within a 24 hour period repeat steps 1 and 2 and call a qualified appliance technician if you have not already Fuel burning equipment appliances and vehicles must be inspected for proper operation and the source of CO must be investigated If problems are identified during this inspection have the equipment serviced immediately Note any combustion equipment not inspected by the technician and consult the ma
15. nd may not be altered by any agents representatives dealers distributors or employees To return this product for service pack carefully in a padded container Include a copy of your original sales receipt an explanation of the problem and your return address Ship prepaid and insured to Pro Tech Safety Products P O Box 493727 Redding CA 96049 Tel 877 955 TECH 8324 www protechsafety com 240 1089 06 5 29 2015 12
16. nufacturers instructions or contact the manufacturers directly for more information about CO safety and this equipment Make sure that motor vehicles or forklifts are not and have not been operating in an attached garage or warehouse or adjacent to the building 10 11 AUDIBLE AND VISUAL SIGNALS Condition LCD Readout LEDs Horn Displays Oppm continuously Green LED blinks once Silent Normal Operation Backlight is OFF every minute i Beeps 4 times pauses Displays current CO readingin Red LED flashes 4 for 4 seconds Alarm Activation PPM Backlight turns ON for 5 times every 5 seconds Repeats this pattern a civa minutes and thereafter in sync in synchronous with for first 5 minutes with beeping horn Then pause time increases to 1 minute AX Green LED blinks once Mute Alarm Displays 7S and current CO per minute red LED Silent Audible Signal reading in PPM Backlight is blinks 4 times per OFF minute Displays current CO level Beeps 4 times pauses Testing Alarm detected Backlight is ON while el meet E for 5 seconds beeps 4 synchronous with horn in testing sequence times Displays the highest CO a level detected within last ER from 10 to 999 The total length of time the highest CO level was PEAK FOR detected over last 30 days hr including levels within 10 Green and red Silent while Recall Peak CO of the peak
17. pha Numeric Alpha Numeric LCD Display Backlight in PPM LCD Display Power Indicator A BC D PEAKTWAFORWHEN E Alarm Indicator H y Day F ma Ta Min t m POWER al al PPM G ar Test Reset Mut A D Bul i A PEAK Highest CO level detected CO LEVEL PPM is ae Display Memory B TWA Average CO level detected for previous 8 hours ON HB C FOR Duration of Peak CO in Hr and Min PRO TECH Ll uration of Peal 8 COMMERCIAL MEMORY D WHEN Howlong ago Peak detected in Day Hr and Min CARBON MONOXI DE MONITOR Style White E Day Hr Min For how long or how long ago event occurred Housing F Emu Low Battery Voltage icon G XI Muted Alarm icon Loud Piercing Alarm AND S mmm s SS H1 gag 3 digit display for CO level and event timing m Te Electro chemical H2 Er M Monitor malfunction signal Service required Sensor H3 End End of sensor life signal Replace monitor VI Battery Compartment in Back H4 L L f Monitor s memory has been cleared SPECIFICATIONS Commercial Carbon Monoxide Monitor Battery Powered 9VDC Sensor Type electrochemical Sample Frequency every second Display continual LCD readout of CO levels detected from 10 999ppm Display Resolution 1ppm Display Accuracy 5 or 5ppm whichever is greater TLV alarm time 20 ppm x 7 hrs REL alarm time 30 ppm lt 3 hrs PEL alarm time 45 ppm lt 90 minutes STEL alarm time 190 ppm lt 5 minutes Peak Level Memory records actua
18. rbon monoxide CO is a highly toxic invisible odorless tasteless gas HOW IS CO GENERATED Carbon monoxide is a byproduct of the incomplete combustion of fuel Faulty ventilation of furnaces boilers water heaters kitchen appliances and space heaters are a major of cause of high CO levels in a building Automobile forklift and small engine exhaust are another potential source of CO HOW DOES CO POISON PEOPLE The human body depends on oxygen for the burning of fuel food to provide us with the energy that allows our cells to live and function Oxygen makes up approximately 21 of the atmosphere and enters our lungs when we breathe In our lungs the oxygen combines with the hemoglobin in the blood oxyhemoglobin and is carried in the blood stream throughout the body where it releases oxygen to the cells Carbon monoxide is dangerous because it bonds more tightly to the hemoglobin carboxyhemoglobin COHb than oxygen does When CO combines with hemoglobin the hemoglobin s ability to combine with oxygen is lost As the COHb concentration rises people become nauseous unconscious and ultimately die see below WHAT ARE THE SYMPTOMS OF CARBON MONOXIDE POISONING Many people often confuse carbon monoxide poisoning with the flu the initial symptoms being very similar Different concentrations of CO over various lengths of time cause different symptoms Many cases of carbon monoxide poisoning indicate that while the victims were aware th
19. ver monitors have sensing limitations and may not always sound a warning in the presence of CO The monitor will not operate if the battery power is low or dead CO monitors must be tested regularly to ensure that they are receiving power and operating properly Carbon monoxide monitors cannot sense CO that does not reach the monitor and therefore CO monitors may not detect CO which is in another area of the building Furthermore if the CO monitor is located on a different level of the building or on the other side of a closed door it may not alert everyone at risk The use of drugs and alcohol may impair ones ability to hear the alarm If you have a multi level building install CO monitors on each level If the monitor is installed in a hallway and any office doors are kept closed install a CO monitor in each room If the monitor is installed in a large open area one monitor should be installed for every 1000 square feet of vertically unobstructed space Although CO monitors can help save lives by providing an early warning to the presence of carbon monoxide they are not a substitute for an insurance policy Property owners leaseholders and renters should have adequate insurance to protect everyone s health lives and property 10 GOOD SAFETY HABITS DEVELOP AND PRACTICE A PLAN OF ESCAPE Make a floor plan indicating all doors and windows and at least two escape routes from each room Second story and higher windows may need fire escape bui
Download Pdf Manuals
Related Search
Related Contents
Installation and Service Manual PrintSYS – CGI User Manual Eight-Channel Divide by 16 Fixed Attenuator Mode d`emploi - Indesit Company UK Manual de usuario A2k4NG - STARLIGH Importador y Distribuidor AccuBANKER AB4000 money counting machine CUBE - User Manual 取扱説明書・料理集 Fichas de manejo seguro en equipos de trabajo 地と智で耕し、協同の力で明日の農業を実践します Copyright © All rights reserved.
Failed to retrieve file