Home
        •Compact cassette installation
         Contents
1.      Swing motor installation cover         Chart 13    Swing motor side    i Bolt  washer                         11  Inlet air    Body          Panel sealing foam        Ceiling Panel foam 2  Hexagonal nut  Horizontal adjustment                 6006       KKK KY           Panel foam          Outlet air    Air plate Panel foam    Chart 14  Chart 12    DRAIN PIPE INSTALLATION    1  Install the drainpipe of the indoor unit    e You can use a polyethylene tube as the drainpipe  out dia  31 32mm  in dia  25mm   It could be bought at local market  or from your dealer        Set the mouth of the drainpipe onto the root of the body s pump pipe  and clip the drainpipe and the out let pipe sheath   fittings  together firmly with the out let pipe clasp  fitting         CAUTIONS    Use your strength carefully to prevent the pump pipe from breaking     e The body s pump pipe and the drainpipe  especially the indoor part  should be covered evenly with the out let pipe  sheath  fittings  and be bound tightly with the constrictor to prevent condensation caused by entered air        To prevent water from flowing backwards into the air conditioner while the air conditioner stops  please lean the drainpipe  down toward outdoor  outlet side  at a degree of over 1 50  And please avoid any bulge or water deposit   Refer to Chart  15 a     e Do not drag the drainpipe violently when connecting to prevent the body from being pulled  Meanwhile  one support   point should be set every 1 1 5m to preve
2.    4    o                      Manual Switch    TEST OPERATION    1  The test operation must be carried out after the entire installation has been completed   2  Please confirm the following points before the test operation       The indoor unit and outdoor unit are installed properly       Tubing and wiring are correctly completed       The refrigerant pipe system is leakage checked    e The drainage is unimpeded       The heating insulation works well    e The ground wiring is connected correctly    e The length of the tubing and the added stow capacity of the refrigerant have been recorded      The power voltage fits the rated voltage of the air conditioner    e There is no obstacle at the outlet and inlet of the outdoor and indoor and indoor units   e The gas side and liquid side stop valves are opened    e The air conditioner is pre heated by turning on the power     3  According to the user s requirement  install the remote controller frame where the remote controller s signal can reach  the indoor unit smoothly     4  Test operation    Set the air conditioner under the mode of  COOLING  with the remote controller  and check the following points per the   Owner s Manual  If there is any malfunction  please resolve it through chapter  Trouble shooting      1  The indoor unit   a  Whether the switch on the remote controller works well    b  Whether the buttons on the remote controller works well    c  Whether the air flow louver moves normally    d  Whether the room tempe
3.    Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit  This refrigerant may then be  re used  if appropriate  or returned to the manufacturer for disposalUnder No circumstances should refrigerant be vented to atmosphere  Where  appropriate  drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing  disposal of oily wastes    Packaged unit can generally be removed in one piece after disconnection as above  Any fixing down bolts should be removed and then unit lifted from  position using the points provided and equipment of adequate lifting capacity  Reference MUST be made to the unit installation instructions for unit  weight and correct methods of lifting  Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above    After removal from position the unit parts may be disposed of according to local laws and regulations     Johnson WN    Controls          E II YDCS 0907    ns ENGLISH    
4. Refer  to chart 11 1 and 2     A CAUTIONS    The installation cover of the swing motor must sink into the corresponding water receiver   c  Install the panel on the main body with bolt  M5x16  and washer   Refer to chart 11 4   d  Adjust the four panel hook screws to keep the panel horizontal  and screw them up to the ceiling evenly     e  Regulate the panel in the direction of the arrow in Chart 11 3 slightly to fit the panel s center to the center of the ceiling s  opening  Guarantee that hooks of four corners are fixed well     f  Keep fastening the screws under the panel hooks  until the thickness of the sponge between the body and the panel s  outlet has been reduced to about 4 6mm  The edge of the panel should contact with the ceiling well   Refer to chart 12     e Malfunction described in Chart 13 can be caused by inappropriate tightness the screw           the gap between the panel and ceiling still exists after fastening the screws  the height of the indoor unit should be  modified again  You can modify the height of the indoor unit through the openings on the panel s four corners  if the lift  of the indoor unit and the drainpipe is not influenced  refer to chart 14 right       3  Hang the air in grid to the panel  then connect the lead terminator of the swing motor and that of the control  box with corresponding terminators on the body respectively      4  Relocate the air in grid in the procedure of reversed order  install the air in grid        Ceiling           
5. acid or alkaline gas    J  Other special areas     NOTES BEFORE INSTALLATION    1  Decide the correct carry in path    2  Move this unit as originally packaged as possible    3  If the air conditioner is installed on a metal part of the building  it must be electrically insulated according to the relevant  electrical code    4  installing in a lonely building or at a high position where it is hot and humid with frequent thunderstorm  lightning   protection equipment is necessary     INDOOR UNIT INSTALLATION    1  Install the main body   A  The existing ceiling  to be horizontal    a  Please cut a quadrangular hole of 600 600mm in the ceiling according to the shape of the installation paper board     Refer to Chart3 4       The center of the hole should be at the same position of that of the air conditioner body       Determine the lengths and outlets of the connecting pipe  drain pipe and cables       To balance the ceiling and to avoid vibration  please enforce the ceiling when necessary    b  Please select the position of installation hooks according to the hook holes on the installation board       Drill four holes of 812mm  50 55mm deep at the selected positions on the ceiling  Then embed the expansible  hooks fittings        Face the concave side of the installation hooks toward the expansible hooks  Determine the length of the installation  hooks from the height of ceiling  then cut off the unnecessary part          the ceiling is extremely high  please determine the le
6. before installation       The Air Conditioner must be installed by qualified service personnel    e When installing the indoor unit or its tubing  please follow this manual as strictly as possible    e When all the installation work is finished  please turn on the power only after a thorough check   e This manual is subject to changes due to technological improvement without further notices   Note     e The installer should illustrate how to correctly use and repair the appliance to user and remind the user carefully reading  and keeping both Installation Manual and Owner s Manual after the air conditioner is installed     e Pictures in this manual are based on standard model  The shape shown may be slightly different from the air conditioner  you purchased     ACCESSORIES    Please make sure the accessories are complete and keep those accessories carefully                       Select the location   Install the indoor unit   Install the outdoor unit                                                                               Install the connecting pipe  gt  Connect the drain pipe e Wiring    D Test operation    Cautions on remote controller installation                                Do not throw or beat the remote controller   e Before installation  operate the remote controller to determine its location in a reception range        Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment   It is necessary to prevent  image disturbances or no
7. d operate the air conditioner under the  COOLING  mode  Listen to the sound of the drain pump   Check whether the water is discharged well  a lag of 1min is allowed before discharging  according to the length of  the drain pipe   and check whether water leaks from the joints     A CAUTIONS    If there is any malfunction  please resolve it immediately     3  Stop the air conditioner for there minutes  check if everything is ok  If the drain hose is located unreasonable  water  overflow will cause the Alarm indicator lamp flashing  For both cooling and heating type or cooling only type   even  the water leak out from the water receiver     10    MATERIAL AND SIZE OF THE PIPES    Three length  8m 5m 10m  of pipes are available to purchase                                   Pipe Material Copper Pipe for Air Conditioner  Refrigerant   R22 R407C R410A  Gas side 619 0 16 0  Size mm   Liquid side 9 53 9 53  ELECTRIC WIRING    A CAUTIONS    mi           A OQ    co N      The air conditioner should use separate power supply with rated voltage  the voltage of power supply must be  within90  110  of rated value       The external power supply to the air conditioner should have ground wiring  which is linked to the ground wiring of the    indoor and outdoor unit       The wiring work should be done by qualified persons according to circuit drawing       A disconnection device having an air gap contact separation in all active conductors should incorporated in the fixed    wiring according 
8. ect the shielded layer to  E     12       CONTROL    Please number the indoor units during the installation   For example  for the first outdoor unit  the number of the first  indoor unit is 1 1  the second indoor unit is 1 2  and the set address is 1 and 2 respectively   the others is analogical                                                                                               Hoursepower code System address code  POWER_S 16 31 NUM_S  0 15  16 31 16 31  0 15 0 15  ENC2 ENC2  Model 1 show the address  0 F  respectively  Model 2 show the address  0 F  respectively   that is   0 15  indoor unit that is   16 31  indoor unit    CAUTION    1 The system together have 32units 0 31  everyone has only system addresscode   If two addresses are the same in one system   the abnormal operation will occur     2 Please switch off the power before setting otherwise the unexpected error will occur                          ENC1 DIAL SWITCH For set horsepower  Note  The horsepower has Code Capacity  Horsepower   been set before leaving the  0  2200W  0 8HP   factory  anyone can t modify it  except the maintenance 1 2800W  1 0HP   person  2 3600W  1 2HP   A500W  1 5HP                 SW1 ENC2 DIAL SWITCH SETTING ADDRESS    The system together have 32units 0 31  everyone has only system addresscode        If two addresses        the same      one system   the abnormal operation will occur        13          NETWORK ADDRESS SETTING    Every air conditioner in network has only one networ
9. ise interferences         Do not install the remote controller in a place exposed to direct sunlight or close to a heating source  such as a stove   e Make sure to install the battery in correct direction   e Please read the Remote controller User s Manual carefully before using     INSTALLATION LOCATION    INDOOR UNIT SHOULD BE INSTALLED AT     e A place where there is enough room for installation and maintenance       The ceiling is structurally sound to hold the Indoor Unit    e A place that is well ventilated and the influence of weather is the least    e A place that the airflow can reach every corners of the room    e A place where the refrigerant connecting pipe and drain pipe can reach out easily    e A place free of flammable gas or corrosive gas leakage    e A place where there is no direct affection from man made high voltage current and highfrequency wave   e A place which is far from noises and vibration     A CAUTIONS    Location in the following places may cause malfunction of the machine   If unavoidable  please consult your local dealer      A  There is mineral oil like the oil of cutting machine    B  There is much salty air   Near the coast    C  There is caustic gas such as sulfuric gas   Near the hotspring    D  Factory where the voltage fluctuate greatly    E  In the car or in the cabin    F  In the kitchen or a place full of oil steam     G  There is strong electromagnetic wave    H  There is combustible gas or materials    1  There is much evaporating 
10. k address to distinguish each other  Address code of air conditioner  in LAN is set by code switch on Network Interface Module  NIM   and the set range is 0 63        Toggle switch set       z    Network address code          a    00 15        E  a       16 31       1       32 47                               48 63          TROUBLE SHOOTING                            N   Type Contents LED Lamp flash Remarks  The evaporator sensor     inti After the malfunctions     check point is abnomal  Run lamp flashes       1 Malfunction   or room temp sensor is at 2 pi disappear  it restores  abnormal          automatically        After the malfunctions     Indoor outdoor unit The timer lamp       2   Malfunction   communication is abnormal   flashes at 2 5Hz  disappear  it restores  automatically   Condenser sensor check                     After the malfunctions  3   Malfunction   point is abnormal or outdoor    i i hat Oat disappear  it restores  temp  sensor is abnormal    2  5 tasn at 0 012    automatically   If the malfunctions can t be  Water level switch Alarm   flash solved in three min  all the  4   Malfunction     a eve wae ree            indoor alarm lamps flash at                         0 5Hz  Turn off the power to  restore   When the indoor unit turns to  5   Alarm Mode conflict  Defrost lamp flashes   heating mode or is turned off              at 2 5Hz        the alarm will disappear           14    Run lamp    Timer lamp    Defrost lamp    Alarm lamp       g  mo  gt   os
11. ngth of the installation hook according to facts       Cut the installation hook open in the middle position  then use appropriate length of reinforcing rod   12  to weld together     Drain side          Inlet Outlet             Chart 1       650 Panel        580  Body   600 Ceiling hole                         401 Hook location     580 Body   600 Ceiling hole          611 Hook location         650 Panel        Chart 3       The length could be calculated from Chart5   Length 210 L  in general  L is half of the whole length of the installation hook   c  Please adjust the hexangular nuts on the four installation hooks evenly  to ensure the balance of the body     e Use the transparent hose filled with water to check the lever of the main body from the four sides or diagonal line  direction  the lever indicator also can check the lever from four sides of the main body Refer to chart 6           the drainpipe is awry  leakage will be caused by the malfunction of the water level switch     e Adjust the position to ensure the gaps between the body and the four sides of ceiling are even  The body s lower part  should sink into the ceiling for 10 12mm  Refer to chart5         Locate the air conditioner firmly by wrenching the nuts after having adjusted the body s position well           Electric  throttle device                Central hole    Electricthrottle                      Hook hole          Fixing hole  Installation  paper board        H ceiling height     Installation  pape
12. nt the drainpipe from yielding  Refer to Chart15 b   Or you can tie the drainpipe  with the connecting pipe to fix it   Refer to Chart 15 c     e In the case of prolonged drainpipe  you had better tighten its indoor part with a protection tube to prevent it from loosing           the outlet of the drainpipe is higher than the body s pump joint  the pipe should be arranged as vertically as possible   And the lift distance must be less than 200mm  otherwise the water will overflow when the air conditioner stops   Refer  to Chart 16     The end of the drainpipe should be over 50mm higher than the ground or the bottom of the drainage chute  and do not  immerse it in water  If you discharge the water directly into sewage be sure to make a U form aquaseal by bending the  pipe up to prevent the smelly gas entering the house through the drain pipe     A CAUTIONS    All the joints of the drain system must be sealed to prevent water leakage     Lean over 1 50       aO Lean over 1 50  A    1 Li         Pump pipe clasp           the fittings     Constrict here Lean over 1 50    Drainpipe Chart 16      ars Connecting pipe    Chart 15    2  Drainage test      Check whether the drainpipe is unhindered      New built house should have this test done before paving the ceiling    1  Remove the test cover  and stow water of about 1500ml      the water receiver through the stow tube   Refer to Chart 17     Body Drain pipe           Water receiver Drip tray    Chart 17    2  Turn on the power  an
13. r board    Screw   5   16     Accessory        Chart 7 Chart 8                            Colourless     transparent pipe    7    Chart 6    Horizontal  indicator    B  New built houses and ceilings        In the case of new built house  the hook        be embedded in advance  refer to the       mentioned above   But it should  be strong enough to bear the indoor unit and will not become loose because of concrete shrinking     b  After installing the body  please fasten the installation paper board onto the air conditioner with bolts  M5x16  to determine  in advance the sizes and positions of the hole opening on ceiling     Please first guarantee the flatness and horizontal of ceiling when installing it   Refer to the A a mentioned above for others   c  Refer to the A c mentioned above for installation     d  Remove the installation paper board     2  Install The Panel  e Never put the panel face down on floor or against the wall  or on bulgy objects        Never crash or strike it      1  Remove the inlet grid   a  Slide two grid switches toward the middle at the same time  and then pull them up   Refer to chart 9     b  Draw the grid up to an angle of about 30   and remove it   Refer to chart 10        Grid switch       Chart 10    2  Install The Panel  a  Align the swing motor on the panel to the water receiver of the body properly   Refer to chart 11     b  Hang the four fixed rope of the main body to the installation cover and the other three covers of the swing motor   
14. rature is adjusted well    e  Whether the indicator lights normally    f  Whether the temporary buttons works well    g  Whether the drainage is normal    h  Whether there is vibration or abnormal noise during operation       Whether the air conditioner heats well in the case of the HEATING COOLING type   2  The outdoor unit   a  Whether there is vibration or abnormal noise during operation    b  Whether the generated wind  noise  or condensed water by the air conditioner have influenced your neighborhood     c  Whether any of the refrigerant is leaked     CAUTION    Protection function will delay the startup of compressor for 3 minutes in case the unit is turned on immediately after power  on or restarted after shutdown     15    DE   COMMISSIONING DISMANTLING  amp  DISPOSAL    This product contains refrigerant under pressure  rotating parts  and electrical connections which  may be a danger and cause injury   All work must only be carried out by competent persons using suitable protective clothing and safety precautions                A    Read the Manual Risk of electric shock Unit is remotely controlled  and may start without warning    Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit  Ensure that all points of electrical and gas  isolation are secured in the OFF position  The supply cables and gas pipework may then be disconnected and removed  For points of connection refer  to unit installation instructions 
15. s can select it when necessary     NOTE   1  Please remember the surroundings  environmental temperature  direct sunlight  rain etc      2  We consider the minimal size of the metal core as the wire size  So it is recommended you adopt a thicker one as the  power conducting wire so as to avoid power decrease     3  Connect the grounded wire to both indoor and outdoor units   4  This chart is just an on site wire connecting example  For details  please refer to relative National criteria     Distance between outdoor unit and the farthest indoor      BS20m unit  lt  1200m  Note  The length of signal wire depen    ds  A on actual wiring condition  not longer than 1200m  B  Indoor Outdoor  Unit Unit     Entrance Entrance      of the Indoor Unit of the outdoor Unit    Terminal Board Diagram             Please refer to the indoor unit wiring diagram for the wiring     Note  The air conditioners can connect with Central Control Monitor  CCM   Before operation  please wiring correctly and  set system address and network address of indoor units              BLACK                XT1                    05 BLACK  09       09 YELLOW  Dog GRAY          E                09 WHITE  09 Brue                                                                                            XT3                             INDOOR POWER      Central Control Monitor  TO OUTDOOR  220 240V 5 0 60  2  CCM COMM  BUS   COMM  BUS          Y G      09  amp     Please adopt the shielded twisted pair wire   and conn
16. to the National wiring regulation       Be sure to locate the power wiring and the signal wiring well to avoid cross disturbance and their contact with connecting    pipe or stop valve body       The wiring attached to this air conditioner is 6m long  Be sure to prolong it with wiring of the same type and proper    length if necessary  Generally  do not twist two wiring together unless the joint is soldered well and covered with insulator  tape       Do not turn on the power until you have checked carefully after wiring     The yellow and green wire can only be used to link to the ground wiring     The Specification of Power                                              MODEL 28 45  PHASE 1 PHASE  POWER  FREQUENCY AND VOLT 220 240V  50 60Hz  CIRCUIT BREAKER FUSE  A  30 25  INDOOR UNIT POWER WIRING  mm  22 5  GROUND WIRING 22 5  INDOOR OUTDOOR        POWER WIRING 2 5  CONNECTING WIRING HEAVY CURRENT SIGNAL 1 5 2 5  A CAUTIONS    A    disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed    wiring according to the National Wiring Regulation     Ground the air conditioner properly to obtain a good anti interference effect      11    Wiring Chart       Power 2 20 240   5 0Hz          INDOOR UNIT    CENTRAL CONTROL  MONITOR CCM  COMPUTE         INDOOR UNIT         OUTDOOR UNIT    AN shielded twisted pair wire             INDOOR UNIT                 Caution   The reserved function is indicated in broken line table user
17. uw YORK  lt  lt     ENGLISH       E Il YDCS 0907    INSTALLATION MANUAL    DIGITAL SCROLL SERIES  AIR CONDITIONER COMPACT FOUR WAY CASSETTE       Models    YDCS 28C A B 15A  YDCS 36C A B 15A  YDCS 45C A B 15A    For correct installation  read this manual before starting installation   Only trained and qualified service personnel should install  repair or service air conditioning equipment  Users    should not install the air conditioner by themselves   All pictures are only sketches  If there is any difference between pictures in this manual and the actual shape    of the air conditioner you purchased  the actual shape shall prevail     CONTENTS    INSTALLATION INFORMATION               tee ezaevstces scieandandatesscteateaeassteatateavceee 4  INSTALLATION  LOCATION                      iaaa 5  INDOOR UNIT INSTALLATION ocecos                                                                6  DRAINPIPE INSTALLATION                  a               9  ELECTRIC                            11  CONTROL                                                                      aria aE                                      13  NETWORK ADDRESS SEU MUNG                          14                                                                                   cxcestceneacescaceteateaatoscateecederalausecetetecteeatecceteeaaoane 14    TEST OPERATION Neen reer        nn errr errr         eter rere tener    rere 15    INSTALLATION INFORMATION    e Please read this Installation Manual carefully 
    