Home

Installationsanleitung PND

image

Contents

1. a JX3 COM PND Jetter x A a SYS SF BF LEDs LED R E D1 D2 SYS SF BF Color Green Red Red Red Green amber Red Red Description OS is running Generic error Special conditions Boot loader is running System is running green LED is lit Accumulative error Bus error LED indications when the JX3 COM PND is switched on Step 1 2 3 R ME 1 w w I N I N 1Hz E ha O OFF D1 X O OFF D2 X Description Reset Boot loader is running and is checking the OS The OS is reading the backplane DIP switch settings and checking if an Ethernet switch exists The OS is initializing the Ethernet port and the file system The OS is initializing the Jetter Ethernet system bus Normal operating condition LED indications of the PROFINET IO Device after first power up SYS SF BF Description On Cor 9m SYS is lit green SF is off BF is lit red Note Depending on the configuration LED indications may vary LED indications of the PROFINET IO Device LED State Description SYS Ow SYS is lit green The OS is running without errors He SYS is flashing amber green The boot loader is waiting for firmware on SYS is lit amber The boot loader is waiting for soft
2. Aderendh lse mit Kragen 0 2 mm 1 0 mm Anschlussbeschreibung X14 X15 3 No 1 Teil 4 gt 1 EN 22 IR 3 a X15 4 Le a eee 5 6 Funktion Buchse X14 Ethernet Port Buchse X15 Ethernet Port LED LINK X14 ist mit dem Jetter Ethernet Systembus verbunden LED ACT JX3 COM PND sendet oder empfangt Uber X14 LED LINK X15 ist mit dem Jetter Ethernet Systembus verbunden LED ACT JX3 COM PND sendet oder empfangt Uber X15 Technische Daten X14 X15 Ubertragungsrate Auto cross over Klemmenart Leitungsart Schnittstelle Kommunikation 10 MBit s 100 MBit s Ja RJ45 Buchse Cat 5e geschirmt Jetter Ethernet Systembus Anschlussbeschreibung X16 X17 1 Teil Funktion LED ACT JX3 COM PND sendet oder empf ngt ber X16 LED LINK X16 ist mit PROFINET IO verbunden LED ACT JX3 COM PND sendet oder empfangt Uber X17 LED LINK X17 ist mit PROFINET IO verbunden Buchse X16 Ethernet Port Buchse X17 Ethernet Port Technische Daten X16 X17 Ubertragungsrate Auto cross over Klemmenart Leitungsart Schnittstelle Kommunikation 100 MBit s Ja RJ45
3. on Die SYS LED leuchtet gelb Der Bootloader wartet auf Software om Die SYS LED ist aus Das Ger t hat keine Versorgungsspannung oder die Hardware ist defekt SF O ore Die SF LED ist aus Es ist kein Sammelfehler vorhanden Die SF LED leuchtet rot Einer der folgenden Fehler liegt vor Watchdog Timeout Channel Generische oder Erweiterte Diagnose vorhanden Systemfehler LED Zust nde des PROFINET IO Device LED Zustand BF O OFF Beschreibung Die SF LED blinkt zyklisch mit 2 Hz 3 s lang Ein DCP Signal Service wird ber den Bus ausgel st Die BF LED ist aus Es ist kein Busfehler vorhanden Die BF LED leuchtet rot Einer der folgenden Fehler liegt vor Die Konfiguration fehlt Die physikalische Verbindung fehlt Die physikalische Verbindung ist zu langsam Die BF LED blinkt zyklisch mit 2 Hz Es ist kein Datenaustausch m glich Anschlussbeschreibung X10 P X10 Klemmpunkt Funktion Try X10 DC24V Versorgungsspannung de f r das Modul JX3 COM PND X10 0V Bezugspotenzial Technische Daten X10 Spannungsbereich DC 24 V 15 20 Leistungsaufnahme Max 0 27 Ax 24 0 V 6 5 W Potenzialtrennung Keine Leiteranschluss X10 Technologie Zugfederanschluss Schraubendreher SD 0 4 x 2 5 DIN 5264 A AWG 16 28 Eindrahtig H05 07 V U 0 2 mm 1 5 mm Feindr htig H05 07 V K 0 2 mm 1 5 mm Mit Aderendh lse 0 2 mm 1 5 mm
4. Buchse Cat 5e geschirmt PROFINET IO Jetter JX3 COM PND automation Communication Module Jetter AG Communication Graeterstrasse 2 E mail Sales sales jetter de D 71642 Ludwigsburg E mail Hotline hotline jetter de Germany Phone Hotline 49 0 7141 2550 444 Installation Manual Item 60879893 Revision 1 01 August 2015 Printed in Germany Download the user manual from www jetter de Support gt Downloads Scope of delivery 1x 10000902 JX3 COM PND 1x 60870409 2 pin connector spring cage connection 1x 60870410 Keying pins 10x 60870411 Terminal labels 1x 60879893 Installation Manual Overview Interfaces and connections No Description oO o PR w 10 11 Upper latches LEDs of the PROFINET lO Device right hand side of the module JX3 backplane module Connector JX3 module enclosure X16 and X17 are Ethernet ports for PROFINET IO right hand side of the module DIN rail latch Lower latches not visible in the illustration X10 for power supply left hand side of the module X14 and X15 are Ethernet ports for the Jetter Ethernet system bus left hand side of the module LEDs of the bus node left hand side of the module Installation on DIN rail to EN 50022 Step Action 1 Pr Place the module JX3 COM PND on the upper edge of the DIN rail Snap the JX3 C
5. Jetter JX3 COM PND automation Jetter AG Gr terstra e 2 D 71642 Ludwigsburg E Mail Hotline hotline jetter de Germany 1x 1x 10x 1x Kommunikationsmodul Kontakte E Mail Vertrieb sales jetter de Telefon Hotline 49 0 7141 2550 444 Installationsanleitung Artikel Nr 60879893 Version 1 01 10000902 60870409 60870410 60870411 60879893 August 2015 Printed in Germany Laden Sie die Betriebsanleitung von www jetter de unter Support gt Downloads herunter Lieferumfang JX3 COM PND 2 poliger Stecker Zugfederanschluss Kodierstifte Klemmenmarkierer Installationsanleitung Schnittstellen und Anschl sse im berblick oO I PR w 10 11 Beschreibung Obere Rastlaschen LEDs des PROFINET IO Device rechte Modulseite JX3 Backplane Modul Stecker JX3 Modulgehause X16 X17 sind Ethernet Ports fur PROFINET IO rechte Modulseite Entriegelungslasche Untere Rastlaschen in Abbildung nicht sichtbar X10 fur die Spannungsversorgung linke Modulseite X14 X15 sind Ethernet Ports fur Jetter Ethernet Systembus linke Modulseite LEDs des Busknotens linke Modulseite Montage auf Hutschiene EN 50022 Schritt Vorgehen 1 Setzen Sie das Modul JX3 COM PND auf die Hutschiene oben auf Lassen Sie das JX3 COM PND auf der Hutschiene einrasten Das JX3 COM
6. OM PND into place on the DIN rail Installation of the JX3 COM PND on the DIN rail is completed Setting the IP address Step Action 1 Remove power from the JX3 COM PND 2 Press the upper and lower latches 3 Pull off the JX3 enclosure of the JX3 COM PND 4 Now the DIP switches 1 on the JX3 backplane module can be accessed Setting the IP address Step Action 5 Set the IP address of the bus node on the side of the Jetter Ethernet system bus using the DIP switches 1 12 ON IP address 192 168 1 1 i Factory settings 123456 7 8 9 1011 12 En IP address 192 168 10 15 283 5 7 8 9101112 Default IP address 6 Reattach the JX3 enclosure of the JX3 COM PND to the JX3 backplane module 7 Restore power to the JX3 COM PND 8 In JetSym set the address of the PROFINET IO Device
7. PND ist auf der Hutschiene montiert Einstellen der IP Adresse Schritt Vorgehen 1 Schalten Sie das Modul JX3 COM PND spannungslos Drucken Sie auf die obere und untere Rastlasche 2 Ziehen Sie das JX3 Gehause des JX3 COM PND nach vorne ab Auf dem JX3 Backplane ma Modul sind nun die 2029594 DIP Schalter 1 erreichbar Einstellen der IP Adressen Vorgehen ndern Sie die IP Adresse des Busknotens Jetter Ethernet Systembus Seite ber die DIP Schalter 1 12 ON Schritt 5 IP Adresse 192 168 1 1 Auslieferungszustand 123456 7 8 9 1011 12 ON IP Adresse 192 168 10 15 Default IP Adresse 121374 56 7 8 9101112 6 Setzen Sie das JX3 Geh use des JX3 COM PND wieder auf das JX3 Backplane Modul Versorgen Sie das JX3 COM PND wieder mit Spannung Stellen S
8. ie in JetSym die Adresse des PROFINET IO Device ein LEDs LED Farbe e D1 D2 REDE R gr n Jetter E rot D1 rot X14 Puh AN Jil D2 rot SYS gr n gelb SF rot BF rot Beschreibung Betriebssystem l uft Allgemeiner Fehler Spezielle Zust nde Bootloader l uft System l uft gr ne LED leuchtet Sammelfehler Busfehler Stufe 1 2 LED Zust nde des JX3 COM PND beim Einschalten R E ha O OFF D1 X O OFF D2 X Beschreibung Reset Der Bootloader l dt und berpr ft das Betriebssystem Das Betriebssystem liest den DIP Schalter der Backplane und pr ft das Vorhandensein des Ethernet Switches Das Betriebssystem initialisiert Ethernet Schnittstelle und Dateisystem Das Betriebssystem initialisiert den Jetter Ethernet Systembus Normaler Betriebszustand Status der LEDs des PROFINET IO Device nach erstmaligem Einschalten SYS SF BF Beschreibung On Cor 9a SYS LED leuchtet gr n SF LED ist aus BF LED ist leuchtet rot Hinweis Der LED Status kann je nach Konfiguration abweichen LED Zust nde des PROFINET IO Device LED Zustand Beschreibung SYS Die SYS LED leuchtet gr n Das Betriebssystem l uft fehlerfrei KK Die SYS LED blinkt gelb gr n Der Bootloader wartet auf Firmware
9. ort 3 LED LINK X14 is connected with the Jetter Ethernet system bus 4 LED ACT JX3 COM PND is transmitting or receiving signals via X14 5 LED LINK X15 is connected with the Jetter Ethernet system bus 6 LED ACT JX3 COM PND is transmitting or receiving signals via X15 X14 X15 Technical specifications Bit rate 10 Mbit s 100 Mbit s Auto cross over Yes Terminal type RJ45 Ethernet jack Cable category Cat 5e shielded Interface communication Jetter Ethernet system bus X16 X17 Description of connections Element 5 6 Function LED ACT JX3 COM PND is transmitting or receiving signals via X16 LED LINK X16 is connected with PROFINET IO LED ACT JX3 COM PND is transmitting or receiving signals via X17 LED LINK X17 is connected with PROFINET IO X16 Ethernet port X17 Ethernet port X16 X17 Technical specifications Bit rate Auto cross over Terminal type Cable category Interface communication 100 MBit s Yes RJ45 Ethernet jack Cat 5e shielded PROFINET IO
10. ware O ore SYS is off Loss of power supply or defective hardware SF O or SF is off No accumulative error SF is lit red One of the following errors is present Watchdog timeout Channel generic or extended diagnostics error System error Mow SF is flashing at 2 Hz Duration 3 s A DCP signal service has been triggered via bus BF one BF is off No bus error LED indications of the PROFINET IO Device LED State Description BF is lit red One of the following errors is present Missing configuration Missing physical connection Physical connection is too slow Mow BF is flashing at 2 Hz No data exchange possible Connector X10 Description X10 Terminal Description oc point X10 DC24V Power supply for module JX3 COM PND X10 0V Reference potential POWER Connector X10 Technical specifications Input voltage range DC 24 V 15 20 Power consumption 0 27 Ax 24 0 V 6 5 W max Electrical isolation None Connector X10 Wiring Technology Spring cage connection Screwdriver SD 0 4 x 2 5 DIN 5264 A AWG 16 28 Solid conductor H05 07 V U 0 2 mm 1 5 mm Flexible conductor H05 07 V K 0 2 mm 1 5 mm With wire end ferrule 0 2 mm 1 5 mm Wire end ferrule with sleeve 0 2 mm 1 0 mm X14 X15 Description of connections 1 Element Description 1 X14 Ethernet port 2 2 X15 Ethernet p