680-148-02 Ex3001 User
Contents
1. selecting the CANCEL ALL TESTS option will cancel all zone tests The Test LED will then extinguish ee ie TS Alternatively it is possible to leave the Zone Test Function with one or more Zones still in Test by selecting the CONTINUE TESTS option This will enable the inspection or use of other menu functions and return the display to the normal operating mode The Test LED will stay illuminated if this option is selected 2 4 2 2 Display The Test Display option checks the operation of all the Indicators and the Graphic Display All of the Indicators are turned on and the entire display is shown in reverse During this test it is possible to test the operation of the 4 V gt and 0 9 buttons When a button is pressed it is LCD amp KEY TEST indicated on the display For example Press the ESC button to cancel the test and return to the previous menu 1 2 4 2 3 Buzzer On selection the buzzer will sound for approximately 10 seconds Page 16 of 20 2 4 3 Extinguishant Modes Mode Select Press the AY buttons to scroll through the list and highlight the OJD F MANUAL ONLY required option EXTRACT START 2 4 3 1 Mode The methods for initiating the release of extinguishant can be selected Press the Y button to select between MANUAL ONLY and AUTO MANUAL CA dvanced PA Y In AUTO MANUAL the release of extinguishant can be established if either a manual release button is pressed or if the one or more
2. En x 3000 Series User Manual for Ex 3001 Product Data Sheet O technology A E people Table of Contents 1 INTRODUCTION 1 1 Standards 1 2 Cautions and Warnings 1 3 Description 2 OPERATION 2 1 Introduction 2131 2 1 2 2 1 2 1 2 1 2 2 2 1 2 3 2 1 2 4 2a 20 2 1 2 6 2 1 2 7 2 1 3 2 1 4 2 1 5 Access Levels Front Panel Controls and Indications Display LED Indications Manual Release Button Control Buttons Menu and Navigation Buttons Key Switches Buzzer Enable Controls Navigating through menus Numeric data entry 2 2 Operating Conditions Fire Alarm Condition Release Activated Condition Hold Condition Abort Condition Fault Condition Warning Condition 2 3 Level 1 Menu Functions 2 3 1 Enable Controls 2 3 2 View 2 3 3 LED Test 2 4 Level 2 Menu Functions 2 4 1 View 2 4 1 1 Faults 2 4 1 2 Disables 2 4 1 3 Warnings 2 4 1 4 Log 2 4 1 5 Software Versions 2 4 2 Test 2 4 2 1 Zones 2 4 2 2 Display 2 4 2 3 Buzzer 2 4 3 Extinguishant Modes 2 4 3 1 Mode 2 4 3 2 Extract 2 4 4 Disable Enable 2 4 5 Date Time Page 2 of 20 ODODODWDWDANNNDOGTAAAH A OOO O 1 Introduction 1 1 Standards The Ex 3001 Gas Extinguishing Control Panel conforms to the following standards BS EN12094 1 2003 Extinguishing Control Device BS EN54 2 1998 Control and Indicating Equipment BS EN54 4 1998 Power Supply Equipment BS EN60950 2000 Safety of information technology equipment BS EN50130 4 199
3. function affected Line 4 shows specific details In the above examples 1 The control panel recognised and recorded an open circuit fault condition on the wiring of Detection Zone 3 2 User 4 disabled the operation of and fault reporting from Detection Zone 3 3 The control panel recognised and recorded a fire alarm condition on Detection Zone 3 2 4 1 4 2 Alarm Counter Alarm Counter The Panel records the number of times that the fire alarm condition has occurred at the panel On selection the display shows the alarm count ALARM COUNT In the example the panel has entered the fire alarm condition 4 0000000004 times since it was installed Press the ESC button to return to the previous menu The panel increments the count by one each time it changes from the normal condition to indicate a fire alarm condition Whilst in the fire alarm condition and until it is reset further fire alarm events do not increment the counter 2 4 1 5 Software Versions Software Versions On selection the display shows a list containing the panel and any PANEL 99 00 configured remote status indicators along with the version of RSl L A 22900 software installed in each device Ro L Z 5 99 00 RSI 3 99 00 Press the AY buttons to scroll through the list of entries Rois 27 00 Press the ESC button to return to the previous menu 2 4 2 Test Test Menu Press the AV buttons to scroll through the list and pre
4. remaining before the extinguishant is released 2 1 2 2 LED Indications The LED Status Indications show the basic operational state of the panel and whether the panel The display shows the time elapsed since the extinguishant release commenced is in a fire alarm fault disabled or test condition 2 1 2 2 1 GENERAL STATUS Function Colour BREA FIRE Red FAULT Yellow DISABLE Yellow TEST Yellow POWER Green SILENCED Yellow SOUNDER FAULT Yellow SOUNDER DISABLED Yellow DELAYED Yellow SYSTEM FAULT Yellow Indicates that the system has detected a fire alarm condition Indicates that the system has detected a fault condition Indicates that part of the system has been disabled i e isolated Indicates that part of the system is in a test condition Indicates the presence of power Indicates that the geneal fire alarm sounders have been silenced Indicates the presence of a fault in either or both of the general fire alarm sounder wiring circuits Indicates that either or both of the general fire alarm sounder circuits have been disabled i e isolated Not used Indicates the presence of a system fault 2 1 2 2 2 DETECTION ZONE STATUS Function Colowr Bescon S FIRE Red FAULT TEST DISABLE Yellow Indicates that the system has detected a fire alarm condition in the respecitve zone Indicates that the system has flashing indication detected a fault condition in the respecitve zone or steady in
5. MANUAL Yellow Indicates that the extinguishant can be released by both the automatic detection of a fire alarm and by means of a manual release button 2 1 2 3 Manual Release Button To manually release the extinguishant pull down the flap and press the button marked with the circle 2 1 2 4 Control Buttons Reset Press to reset the panel from a fire alarm condition and or a gas release sequence Only available with Level 2 Access Mute Available in both Press to mute the internal buzzer Level 1 and Level 2 Silence Only available with Press to silence the sounders Level 2 Access Resound Sound Alarms Press again to re activate the sounders Press to initiate a manual evacuation and sound the alarms Only available with Level 2 Access 1 SILENCE will silence all sounders except for the flooding zone protected area sounders when the system is in the activated state Once the extinguishant has been released it is possible to silence the flooding zone sounders Page 6 of 20 2 1 2 5 Menu and Navigation Buttons Press to scroll through Menu Options Press to display more information Press to scroll through menu Options Press to scroll through lists of zones or devices Press to confirm entry of numeric information entry Press to confirm selection of a menu option Press to change some of the configuration options Used to enter numbers Press to exit the menu functions and return to the norm
6. MUTE the internal buzzer e A Level 2 Authorised User can view the operational condition of the system and may MUTE the internal buzzer In addition the RESOUND SOUND ALARMS SILENCE and RESET buttons are enabled and access to the Level 2 Menu functions is available This requires a password or key switch e NOTES There are up to 4 User ID codes available each with its own password The panel can be configured to automatically cancel access to Level 2 functions after a specified period 2 1 2 Front Panel Controls and Indications LCD Navigation Buttons Detection Zone Status Manual Release Button General Status Control Buttons Number Buttons Extinguishant Status Key Switch Assembly 2 1 2 1 Display The LCD along with the LED Indicators shows the operating status of the system Examples of the information presented is shown below Page 4 of 20 Normal Display SYSTEM NORMAL 22 AUG 2001 16239200 Release Imminent Release status RELEASE IMMINENT Non normal Display System status l of 1 Conditions DETECTION ZONE3 OPEN CIRCUIT Release status UNAFFECTED Release Activated RELEASE ACTIVATED 00 00 05 Elapsed GAS RESET INHIBITED Typical Menu Display Level 2 Menu TEST MODES DISABLE ENABLE EXIT LEVEL 2 Release Complete RELEASE ACTIVATED 00 00 24 Elapsed DISCHARGE COMPLETE No Flow Detected RESET ALLOWED The display shows a countdown timer with the amount of time
7. alarm and trigger events that could result in the release of the extinguishant In addition a total fire alarm count is also available Event Log Menu ALL EVENTS FIRES MRE Es ALARM COUNT 2 4 1 4 1 View Events On selection a menu is presented to select the required view Press the AY buttons to scroll through the list and press the Y button to select the required view option Press the ESC button to return to the previous menu Select either the ALL EVENTS or the FIRES TRIGGERS option On selection the latest recorded entry is shown For example Event Log Viewer EVENT 55755 207 0972007 LOrE CONTROL PANEL DETECTION ZONE 3 POPPEN CIRCULI Event Log Viewer EVENT 41 58 2070972007 09322318 USER4 DETECTION ZONE 3 gt DISABLE Event Log Viewer EVENT 11 58 LO POT ZOO 2 eo Be ED CONTROL PANEL DETECTION ZONE 3 gt FIRE ALARM Page 14 of 20 The upper two lines show the menu option and the number of the entry currently being viewed Press the AV buttons to scroll through the list of entries Press the ESC button to return to the previous menu The next four lines show the details of the log entry Line 1 shows the date and time the entry was recorded Line 2 shows the origin Line 3 shows the circuit function affected Line 4 shows specific details Line 1 shows the date and time the entry was recorded Line 2 shows the origin Line 3 shows the circuit
8. option NOTE If the programming of the panel is such that the release condition is immediately invoked on detection of a single fire alarm then the display will immediately show the release status information 2 2 2 Release Activated Condition The activated condition is established when one or more fire alarms have occurred or when the manual release button is pressed The number of zones and which zones that must be in a fire alarm condition before the activated condition is invoked depends on the installation programming of the panel SILENCE will silence all sounders except for the flooding zone protected area sounders when the system is in the activated state Once the extinguishant has been released it is possible to silence the flooding zone sounders by pressing the silence button again Page 9 of 20 Release status RELEASE IMMINENT 15 RELEASE ACTIVATED 00 00 05 Elapsed GA ME Ela Ene iin RELEASE ACTIVATED 10 Seconds Elapsed DISCHARGE COMPLETE No Flow Detected GAS RESET INHIBITED RELEASE ACTIVATED 10 Seconds Elapsed RELEASE CONFIRMED DISCHARGE COMPLETE GAS RESET INHIBITED RELEASE ACTIVATED 20 Seconds Elapsed DISCHARGE COMPLETE EXTRACT RUNNING RESET ALLOWED When the activated condition is established the display indicates that the release is imminent and also shows a countdown timer with the number of seconds remaining before the extinguishant is released In addition t
9. through the list and press the Y FAULTS button to select the required view option DISABLES WARNINGS LOG SW VERSIONS Fault Status If there are no conditions present the display will show Nothing to Report Nothing to Report 2 4 1 1 Faults Fault Status If there are fault conditions present the display will show the DOr 3 number of conditions and a list of the fault conditions 1D ys Ou ON ACI IN 2 SHORT CIRCULT DETECTION ZONE 2 Press the ESC button to return to the previous menu gt OPEN CIRCUIT Press the AY buttons to scroll through the list of faults Page 13 of 20 2 4 1 2 Disables Disable List Zone 1 DISABLED Man Release DISABLED 2 4 1 3 Warnings Warning Status OE VALVE MONITOR INPUT gt VALVE CLOSED PRESSURE MONITOR gt LOW PRESSURE 2 4 1 4 Log If there are disablement conditions present the display will show the number of conditions and a list of the disablements Press the AY buttons to scroll through the list of disablements Press the ESC button to return to the previous menu If there are warning conditions in the extinguishant system present the display will show the number of conditions and a list of the warning conditions Press the AV buttons to scroll through the list of warnings Press the ESC button to return to the previous menu The panel contains a history log of fires faults and other conditions This can be filtered to show only the fire
10. 6 Product Family Standard Electromagnetic Compatibility Directive 89 336 EEC and the amending directive 92 23 EEC Low Voltage Directive 73 23 EEC 1 2 Cautions and Warnings y Only Trained service personnel should undertake the Installation Programming and Maintenance of this equipment 1 3 Description This manual covers the use and how to operate the Ex 3000 Series Extinguishing Control Panels Refer to the Installation Manual Document No 680 147 for details of installation programming and commissioning of the panel The Ex 3007 is a Single Flooding Zone Control Panel with up to three detection zone circuits The detection zones are compatible with conventional detectors and call points Page 3 of 20 2 Operation 2 1 Introduction These instructions cover the operation and use of the panels 2 1 1 Access Levels The panel operation is protected from inadvertent and erroneous misuse by means of four access levels These levels are as follows e Level 1 Untrained user e Level 2 Authorised User e Level 3 Commissioning Service and Maintenance e Level 4 Commissioning Service and Maintenance Special Tools Required This document covers the Level 1 and Level 2 User functions For details on the installation programming and commissioning of the panel refer to Manual 680 147 Full details are supplied with any special tools e ALevel 1 Untrained User can view the current operational condition of the system and may
11. Extinguish ENABLED Disabled LED is illuminated along with any specific circuit function disablement LED indicators ZONE 3 ENABLED The table below lists all of the items that can be disabled CO corms Detection Zones Zone 1 2 and 3 Disables any fault reporting on these circuits The zone will not enter the fire alarm condition even if there is smoke present Man Release Manual Release of the extinguishant Prevents the release of extinguishant due to the activation of any manual release button Extinguish The Output to activate the release of Disables any fault reporting on the extinguishing the extinguishant and Sounder output circuit and flooding zone sounder circuit Circuit 3 Flooding zone sounders Prevents the operation of the extinguishing output and flooding zone sounder circuit even if the release condition is established Sounder 1 General Fire Alarm Sounder Output Disables any fault reporting on the sounder 1 circuit 1 circuit General fire alarm sounder circuit 1 will remain off irrespective of the operating condition of the panel Sounder 2 General Fire Alarm Sounder Output Disables any fault reporting on the sounder 2 circuit 2 circuit General fire alarm sounder circuit 2 will remain off irrespective of the operating condition of the panel Fault Relay The Fault Relay Output Prevents the fault relay output from operating Fire Relay The Fire Relay Output Prevents the fire relay output from opera
12. al display Press to show or return to Menu Functions One or two key switches can be fitted to the panel The functions of these are programmable and the installer will have inserted a label to indicate their use Typical uses are AUTO MANUAL MANUAL ONLY Selection LEVEL 1 LEVEL 2 ACCESS Selection Depending on the key switch mechanism fitted the key may be removable in only one position or removable in both operating positions 2 1 2 7 Buzzer The buzzer produces two different sounds to differentiate between fire alarm conditions and fault warning conditions The buzzer operates with a continuous tone The buzzer operates intermittently Page 7 of 20 2 1 3 Enable Controls Controls are normally disabled If a level 2 Access key switch is fitted use this in preference to passwords To enable the control keys or gain access to the Level 2 press the Menu button The display shows the following CONTROLS DISABLED Enter Your Password Enter Your Password xk ENABLE CONTROLS VIEW LED TEST Press the Y button to select the The display prompts for entry of Enter the password As each Enable Controls option the password number is pressed an character is displayed Finally press the Y button to confirm Level 2 Menu Enter Your Password VIEW Not Recognized dol EXTINGUISH MODES DISABLE ENABLE EXIT LEVEL 2 The display then shows the Level 2 If the password is incorrect or i
13. cific FAULT LED indications will be illuminated L 0 ot CONdartrons PRESSURE MONITOR OPEN CIRCUIT Release status UNAFFECTED Press the AY buttons to scroll through the list of faults Press the MUTE button to silence the internal buzzer 2 3 Level 1 Menu Functions 2 3 1 Enable Controls Controls and User Level 2 Menu functions are normally disabled Refer to Section 2 1 3 for further details 2 3 2 View On selection the current status of any Faults Disablements and Warnings along with the history Log can be shown These are the same as the Level 2 View function Refer to Section 2 4 1 for further details 2 3 3 LED Test On selection the front panel LED Indicators will be illuminated for a short period of time Page 12 of 20 2 4 Level 2 Menu Functions The following table gives a list of the Level 2 Menu Functions and a brief description for each function ltem and in remote status indicator panels EXTINGUISH MODES MANUAL Select Manual Only mode Auto Manual mode EXTRACT Turn on the extract output if configured DISABLE ENABLE Disable Zone Sounder Input and Output circuits and disable functions Enable any current disablement conditions EXIT LEVEL 2 L M Cancels access to Level 2 menu functions and control key functions DATE TIME Allows entry of the current date and time COMMISSION Engineer use only requires separate password 2 4 1 View View Menu Press the AN buttons to scroll
14. dication that the zone is either in a test state or in a disabled state Page 5 of 20 2 1 2 2 3 EXTINGUISHANT Funcion eoru BREA RELEASE IMMINENT Red Indicates flashing that the release of extinguishant is imminent The indication will turn to steady when the signal to release the extinguishant has been activated RELEASED Red Indicates that the release of extinguishant has occurred and the panel has detected the flow of the extinguishant released TIMER HELD Yellow Indicates that the imminent release of extinguishant is temproraily suspended ABORTED Yellow Indicates that the imminent release of the extinguishant has been aborted DISABLED Yellow Indicates that the extinguishant release control signal has been disabled The release of extinguishant is prevented even if a fire alarm or manual release are present FAULT Yellow Indicates that the system has detected a fault condition within part of the extinguishing control device ECD circuits The General Fault LED will also be illuminated MANUAL DISABLED Yellow Indicates that one or more buttons for manual release have been disabled VALVE CLOSED Yellow Indicates that the extinguishant is blocked by a manual shut off valve and that there may be no extinguishant available to suppress a fire Ensure immediate remedial action is taken to address the problem MANUAL ONLY Yellow Indicates that the extinguishant can only be released by means of a manual release button AUTO
15. f Menu options not entered in time the above message Is shown If a control button is pressed at Level 1 the display prompts for password entry To continue enter the password If the password is valid the relevant control function will be activated and the display will remain at Level 1 2 1 4 Navigating through menus When a menu is displayed use the AY buttons to highlight the required menu option and then press the Y button to select it Press the ESC button from within a menu option to return to the previous menu The display will revert to the status mode display after 60 seconds on no activity 15 seconds in a fire alarm condition Press the Menu button again to return to the menu option A programmable timer can be configured to automatically cancel Level 2 access This time can be between 1 and 5 minutes If no buttons are pressed for the timeout period then Level 2 access will be cancelled It will be necessary to re enter the password to regain access to control and Level 2 Menu functions 2 1 5 Numeric data entry Numbers are entered by moving to the required field and then typing in the required number followed by the Y button The display returns to the previous menu If the number is entered incorrectly press the button to clear the entry and then re enter the required number Alternatively press the ESC button to cancel the number entry and return to the previous menu Page 8 of 20 2 2 Operating Conditio
16. he Release Imminent LED flashes If programmed the bells sounders will ring with pulsed alert tone When the countdown timer has elapsed the actuating output is activated to start the release of the extinguishant The display now shows the time elapsed since the release of extinguishant commenced In addition the Release Imminent LED turns ON steady When the discharge is complete either time elapsed or flow detected the display indicates the discharge is complete It is now possible to silence the flooding zone sounders If confirmed by the detection of the flow of the extinguishant the display shows RELEASE CONFIRMED Released Condition and the RELEASED LED turns ON steady If previously silenced the internal buzzer will re sound Press the MUTE button to silence the buzzer When the extinguishant has been fully released and if programmed the panel will either automatically or will prompt for manual confirmation activate the output to control the extract fan This is indicated on the display as EXTRACT RUNNING or PRESS Y to EXTRACT When the discharge is complete the display prompts that the panel can be reset To reset the panel press the RESET button A Reset Control menu may appear use the AY buttons to highlight the appropriate option then press the Y button to select NOTE In accordance with EN 12094 1 the ECD shall not permit a reset until either the RELEASED condition has been established fl
17. lect PRES ome TO REE 2 2 5 Fault Condition System status If the panel detects a fault condition the display will indicate the number and nature of the faults The internal buzzer will sound with an intermittent tone and the GENERAL FAULT LED and any other specific FAULT LED indications will be illuminated L of 1 eco altions DETECTION ZONES OPEN CIRCUIT Press the AY buttons to scroll through the list of faults Release status UNAFFECTED Press the MUTE button to silence the internal buzzer NOTE The fault condition is non latching except System Fault and the indications will automatically be cleared when the fault is remedied Press the RESET key to clear a System Fault a Reset Control menu may appear use the AV buttons to highlight the RESET GAS amp FIRE option then press the Y button to select NOTE If silenced the buzzer will re sound when a new fault occurs System status l or 1 conditions DETECTION ZONE3 When the MUTE button is pressed the bottom two lines of the display will show the telephone number to call for service if OPEN CIRCULT For service call programmed for four seconds 01234 567 890 Page 11 of 20 2 2 6 Warning Condition System status If the panel detects an extinguishant warning condition the display will indicate the number and nature of the warnings The internal buzzer will sound with an intermittent tone and the GENERAL FAULT LED and any other spe
18. ns 2 2 1 Fire Alarm Condition Fire Detected The display shows location origin of the fire alarm and the total FIRE STARTED ZONE 1 number of zones in a fire alarm condition If two or more zones enter the fire alarm condition the display also TOTAL FIRES 1 shows the location of the last zone to enter a fire alarm condition Release Status In addition the General Fire LED and the respective Zone Fire STACE 1 LED will be illuminated Fire Detected The status of the extinguishant release is also indicated If a fire FIRE STARTED ZONE 1 alarm occurs in a zone that has no effect on the extinguishant LAST FIRE ZONE 3 control then the display shows UNAFFECTED TOMATES Hy Release Status STAGE 1 The fire alarm bells sounders will activate depending on how they are programmed to respond To silence the internal buzzer press the MUTE button To silence the bells press the SILENCE button the SILENCED LED will illuminate To reset the panel press the RESET button If a Reset Control menu is presented use the AY buttons to highlight the RESET FIRE 8 GAS option then press the Y button to select RESET Control The Reset Control menu may be presented when the reset control key is pressed this is dependant on how the control panel has RESET GAS ONLY been configured by the installer CANCEL RESET Use the AY buttons to highlight the required option then use the Y button to select the highlighted
19. of the detection zone circuits is activated due to detection of smoke SYSTEM NORMAL 22 BUG 2004 08 39200 dvanced In MANUAL ONLY the release of extinguishant can only be T established if one of the manual release buttons is pressed SYSTEM NORMAL Manual Only Mode 22 AUG Z00OK 10439300 NOTE If a key switch is provided on the front panel or separately for this function then use the key switch in preference to the menu option 2 4 3 2 Extract If the panel is configured and programmed to provide control of an extract fan then the operation of the extract fan can be manually controlled via the menu option The display is context sensitive and will present different options depending on whether the fan is on running or off If the fan is off the display shows EXTRACT START Press the Y button to start the extract fan for the pre programmed time If the fan is on the display shows EXTRACT STOP Press the Y button to stop turn off the extract fan NOTE If a key switch is provided on the front panel or separately for this function then use the key switch in preference to the menu option Page 17 of 20 2 4 4 Disable Enable Disabled List Press the AY buttons to scroll through the list and highlight the ZONE1 ENABLED required option a NABDED press the J button to select between ENABLED and DISABLED Man Release ENABLED conditions If a circuit or function is disabled then the General
20. ow detected or until after a programmable time following activation of the mechanism to release the extinguishant NOTE Depending on programming the EXTRACT condition may persist after the panel is reset for up to 120 minutes This will be indicated on the normal status display Extract Running Page 10 of 20 Reset of the Activated Condition Release Signal Released Condition NOTE In accordance with EN 12094 1 the activated release condition may be established without the detection of a fire alarm or manual release If the panel detects the release of extinguishant it will immediately indicate the released condition 2 2 3 Hold Condition COUNTDOWN ON HOLD If any hold button is activated the imminent release countdown is Remove HOLD resume held for as long as the button is pressed The display shows the HOLD condition and the TIMER HELD LED is illuminated 5 When the hold button is released the panel will resume the imminent release countdown either from the time remaining or from the maximum time programmed 2 2 4 Abort Condition If an abort button is activated the imminent release countdown is RELEASE ABORTED aborted The display prompts for the panel to be reset and the ABORTED LED is illuminated Ensure that the abort button is de activated and then press the RESET button A Reset Control menu may appear use the AY buttons to highlight the appropriate option then press the Y button to se
21. ss the Y button to select the required test option DISPLAY BUZZER 2 4 2 1 Zones The Test Zones function provides the means to implement a one person walk test in order to test specific call points or detectors in one or more zones To test the detection zone circuits in accordance with the recommended weekly monthly and annual test requirements select the Test Zones option The devices connected to the circuit can then be tested without activating the extinguishing system and release Use the test key supplied for testing manual call points and either a heat source or smoke test aerosol for testing heat detectors smoke detectors Page 15 of 20 Zone Test Select On selection the display prompts for whether the sounders bells WITHOUT SOUNDERS should ring for a short period about 10 seconds when the WITH SOUNDERS detection zone enters a test fire alarm condition Press the AY buttons to scroll through the list and press the Y button to select the required test option The display then shows a list of the detection zone circuits Zone Test Select Press the AY buttons to scroll through the list and highlight the ZONE 1 TEST OFF required zone circuit ZONE 2 TEST HR ZONE 3 TEST OFF Press the button to select between TEST OFF and TEST ON To leave the Zone Test menu press the ESC button If there are still any zones in a test condition the display will show the following options Zones in Test
22. ting Prog Relays All other relay control outputs Prevents all other relay output circuits from operating 2 4 5 Date Time Set TIME DATE Press the AY buttons to scroll through the list and highlight the required option 13 95 Enter the required time or date using the number buttons Enter all 29 09 07 digits including zeros i e 09 then 09 for 9 09 AM After all digits are entered the time or date is set if it is a valid time or date Page 18 of 20 This page is intentionally left blank Page 19 of 20 This page is intentionally left blank Document Number 1S O 9001 TH AS MA Fire Industry Association Page 20 of 20 680 148 Revision cre SON f u B NFPA 7 MEMBER REVES Y gt wow Le 02 34 Moorland Way Nelson Park Cramlington Northumberland NE23 1WE Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 www Advel co uk Email Sales Advel co uk ELECTRONICS LTD