Home
        iTrust Adapt UPS 20kVA User Manual
         Contents
1.                                                    Figure 2 12 Shorted copper bars connection for single POD user terminal block    2  Connect the live line  mains phase A  mains phase B and mains phase C   N line and PE line respectively to the  user terminal block  mA  mB and mC terminals   shorted copper bar 4 of mN and bN terminals  and PE terminals of  the single POD     3  Connect the shorted copper bar 8 to one end of the shorted copper bar 7  see Figure 2 12   and connect the live  line  bypass phase A  to the shorted copper bar 8     4  Connect the bypass N line to the shorted copper bar 4 of of the single POD user terminal block  mN and bN  terminals      5  Connect the live line  output phase A   N line and PE line respectively to the shorted copper bar 5 of the user  terminal block  shorted copper bar 4 of two oN terminals  and PE terminals of the single POD     6  Remove all the shorted copper bars 3 from the UPS I O terminal block  and connect the UPS terminal block of the  single POD with the same silkprint terminal of the UPS I O terminal block using one to one correspondence method     7  As shown in Figure 2 10  you can paste the insulating film  accessory  to the shorted copper bar 10  and insert the  buckles into the corresponding holes on the shorted copper bar 10    8  As shown in Figure 2 11  you can short two PE terminals of the UPS I O terminal block using the shorted copper  bar 10 with an insulating film  and connect two screw holes of the shorted c
2.                       Figure 2 14 Shorted copper bars connection for UPS I O terminal block    3  Connect the live line  mains phase A  mains phase B and mains phase C   N line  PE line respectively to the I O  terminal block  mA  mB and mC terminals   shorted copper bar 4 of mN and bN terminals  and one screw hole of the  shorted copper bar 10 of the UPS    4  Connect the shorted copper bar 8 to one end of the shorted copper bar 7  see Figure 2 14   and connect the live  line  bypass phase A  to the shorted copper bar 8     5  Connect the bypass N line to the shorted copper bar 4 of mN and bN terminals of the UPS I O terminal block     6  Connect the live line  output phase A   N line and PE line respectively to the shorted copper bar 5  shorted copper  bar 4 of two ON terminals  and the other screw hole of shorted copper bar 10 of the UPS I O terminal block     LD Avenir    Before the commissioning engineer arrival  if the load is not ready for accepting the power  please take good care of the safety  insulation located at the end of the output cable              After the I O cables connection  you should find the label shown in Figure 2 15 on the UPS chassis protective cover  for convenient maintenance  and then tick    V    at the right side of    OUTPUT    and    BYPASS     according to the actual  conditions        EMERSON    Network Power       5 MODEL  UHA3R 0200L   ii  amp  B OUTPUT CAPACITY  20kVA 18kW   35 tii H AC OUTPUT  220 230 240V  18 N PE 50 60Hz 90A MAX  38
3.       Assembling Completed status  Figure 2 10 Pasting the insulating film to the shorted copper bar 10    7  As shown in Figure 2 11  you can short two PE terminals of the UPS I O terminal block using the shorted copper  bar 10 with an insulating film  and connect two screw holes of the shorted copper bar 10 to PE terminals of the single  POD       Trust Adapt UPS 20kKVA User Manual    Chapter 2 Installation 15                   B o  olo lolo                                                                                                                                                         Figure 2 11 Shorted copper bar 10 for PE terminals of the UPS I O terminal block  e 3 in 1 out  split bypass configuration    1  Short bA  bB and bC terminals of the single POD user terminal block using the shorted copper bar 7  short oA  oB  and oC terminals using the shorted copper bar 5  and then short mN and bN terminals  two oN terminals respectively  using two shorted copper bars 4  as shown in Figure 2 12                                                                                                                                         e   aS ESO BOI   BN EDO COENE  ABU    A  e o E 8  o       o T o   amp     lollollolollollollollolo   Olle J  m      a i eel    gt   pleljeefe e ell ar  o 4 4 H 85     o4 138 Hlo  oN oN oA oB oC mN bN mA bA mB bB mC bC  Lo  U  cS  lt  gt  o da     7   4 a   a   f   o o     PE PE oN oN oA oB oC mN bN mA bA mB bB mC bC PE PE                         
4.     and    Bat      terminals  see Figure 2 7  of the  corresponding UPS single I O terminal block in parallel system  through each battery MCB     2  Setting  Power on the system  set each UPS single to shared battery configuration through the LCD menu     Settings      gt     Shared Battery    from each UPS single  set the LCD menu    Settings      gt     Battery Cells Number    and     Single Group Batt Cap    from each UPS single  and each single setting must be the same       Trust Adapt UPS 20kKVA User Manual    Chapter 2 Installation 23    When the parallel system uses the shared battery  the    Single Group Batt Cap    of the LCD setting of each UPS single stands for  the gross capacity of battery string  and each single can calculate the battery capacity itself automatically        3  Close the battery MCB of each single     2 10 Double Bus System    2 10 1 System Installation    The double bus system is composed of two independent UPS system  and each UPS system can be composed of  one or two parallel UPS singles  The double bus system has high reliability  which is suitable for the load with many  input terminals  For single input load  you can add a selected static trigger switch  STS  to start the load bus  synchronization  LBS      The double bus system uses LBS to realize the output sync of the two independent  or parallel  UPS systems  One is  the main system  and the other is the slave system  The operation mode of the double bus system contains main  system 
5.    Ltd  The UPS offers reliable and high quality AC power to your precision instrument   The UPS adopts modular design  and rack tower installation can be used depending on your requirements  lt is  applicable to supplying AC power to small scale computer center  network  communication system  automatic control  system and precision instrument     This chapter gives a brief description of the UPS  including the UPS features  model configuration  appearance   components  operating principle  state  operation mode and specifications     1 1 Features      Trust Adapt UPS is compatible with   Trust Adapt 20kVA UPS  The UPS features include     e Compatible with two modes  3 phase mains output and single phase mains output  You should check the  system wiring and conduct the panel setting manually    e Capable of parallel connection to achieve up to 3   1 parallel redundant power    e High frequency double conversion topology structure  with high input power factor  wide input voltage range  and  output immune to grid interference  thus adaptable to areas with unstable mains supply       High power density    e Full digital control technology based on digital signal processor  DSP  to achieve high system reliability with  self protection and fault diagnosis functions    e Intelligent battery management to extend the battery module life    e Operation and display panel with both LCD and LED indication to help you learn about the system operation  state and operating parameters     
6.    Rectifier in setting    Rectifier starting up and synchronizing       Battery reverse    Reconnect the battery  check the battery connection             No battery Check the battery and the battery wiring   Auto start After UPS was shutdown at EOD  inverter auto starts when utility restore  REC FLASH   qe ATE S Ongoing update of rectifier firmware       INV FLASH UPDATE    Ongoing update of inverter firmware       MONITOR FLASH  UPDATE    Ongoing update of monitor firmware       DSP softwar error       Inverter software does not match the rectifier software          Note  If the alarm is caused through setting the software value by Emerson authorized engineer  and when you wish to change  the setting values  please get in touch with the Emerson local customer service center          32    4 1    4 1 1    4 1 2    4 2    4 2 1    Chapter 4 UPS Operation Instructions    Chapter 4 UPS Operation Instructions    This chapter gives a detailed description of the UPS operation procedures    Refer to Chapter 3 Operation And Display Panel for all buttons operation and LED display in operation  During the  operation  the buzzer alarm may appear  at this point  you should press the ALARM CLEAR button for audible alarm  silence     AN DM Warning  Hazard mains and or battery voltage exists behind the protective cover       No user accessable parts are located behind the protective covers that require a tool for removal  Only qualified service personnel  are authorized to remove such cov
7.   Description  This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass  voltage is beyond the normal range  The amplitude threshold is fixed for  10  rating   This alarm will automatically recover when the bypass voltage goes normal   1  First verify that the bypass voltage and frequency displayed on the operator control and display panel  is within the selected range  Note that the rated voltage and frequency are specified by the    Output  Voltage Level    and    Output Frequency Level    respectively   2  If the displayed voltage is abnormal  please verify the actual bypass voltage and frequency presented  to the UPS  Check the external power if it is found to be faulty       Bypass protection    This alarm is triggered by an inverter software program when the amplitude or frequency of bypass  voltage is too high or too low  The amplitude threshold is fixed for  10  rating  This alarm will  automatically recover when the bypass voltage goes normal    1  First check if there are some relevant alarms  such as    Bypass Phase Reverse        Input Disconnect  Fault     If so  solve them first    2  Then verify that the bypass voltage and frequency displayed on the LCD are within the limit  Note that  the rated voltage and frequency are specified by the    Output Voltage Level    and    Output Frequency  Level    respectively    3  If the displayed voltage is abnormal  please verify the actual bypass voltage and frequency presented  to 
8.   Trust Adapt UPS 20kVA User  Manual    Emerson Network Power provides customers with technical support  Users may contact the nearest  Emerson local sales office or service center     Copyright O 2010 by Emerson Network Power Co   Ltd     All rights reserved  The contents in this document are subject to change without notice     Emerson Network Power Co   Ltd   Address  No 1 Kefa Rd   Science  amp  Industry Park  Nanshan District 518057  Shenzhen China  Homepage  www emersonnetworkpower com cn    E mail  support emersonnetwork com cn    Safety Precautions    This manual contains the information concerning the installation and operation of Emerson   Trust Adapt   20kVA UPS  hereinafter referred to as UPS   Please    carefully read this manual prior to installation     The UPS must be installed  commissioned and serviced by engineers designated by the manufacturer or its  agent  Failure to observe this could result in personnel safety risk  UPS malfunction and invalidation of warranty     The UPS has been designed for commercial and industrial use only  and is not recommended for use in life  support applications     This is a Class A UPS product  In a residential environment  this product may nevertheless cause radio  interference  in which case  the user may be required to take additional measures     Conformity And Standards    The UPS complies with 2006 95 EC  93 68 EEC  LV Safety  and 2004 108 EC  EMC   with Australia and New Zealand EMC  Framework  C Tick  and with the f
9.   taa 23  Chapter 3 Operation And Display Pannel           ccccesceeseseseesseeeeeeeseaeeeseeseaeeeaeeesaeesaeeeeeseaeesaaeseaeeseaeseaeeseeeesaeeseaeseaeeseeeseeeseaees 24  A A O 24  Sal LED INdICAtONS e desa 24  3 1 2 Audible Alarm   BUZZ  coi o ocipa 24  31 3  Control BUTLONS unta ta 25  3 1 4 LCDrAnd  Menu Buttons  ii Aa es 25   3 2 LGD Seren TYPOS tardar   rca 25  A 1 Start Screen  O O dee ele 25  322 Primary SCreen iii ei ed eed aed hs ne a ed LE Se Ge ee el a 26  3 2 9 Default  Screen sites Piet a eee ee a oe ads 26   3 3 Detailed Description Of Menu ltemS 00 2    eeceeeeeeeeteneeeeeeeeeeeaeeeseeesaeecaeesaaeeeaeesaeessaeesaeesaeeeseeseaeeeaaeseaeeeaeesaee es 27  3 4 Prompt WiINGOW 525 titan dt lc hates 29  3 5 UPS Alarm Message  ista iii iO Ti Aida 29  Chapter 4 UPS Operation INStruCtiONS yssiron aane ran ro nn 32  del UPS StartUp n rs od ra il isa 32  4 1 1 Normal Module Start up Procedure c oooccococccocccconanoocconccnonnnnnncconcnnano conc n nn n nn nc encarna ran rn cnn naar ran ca rncranccans 32  4 1 2 Battery Module Start up Procedure           ceceeceeeeceeeeeeeeeeeeeeeeeeeeseeeeecaeecaeeeaeeeneesaeesaeesaeeeaeeeaeseaeseeesneeeeeeea 32  4 2 Transferring Procedures Between Operation Modes              eccceeceeeeeeeeeeeeeeeeeeeteeeeeaeeeaeeeeeeeeeeeseaeeeaeeeeeteaeeneeeeaees 32  4 2 1 Transferring From Normal Mode To Battery Mode    ooooocococcccconccccnoncccnonccononcnonarononono cnn non nc naar n nn nn rn nnnnr nn 32  4 2 2 Transferring From Normal Mode To By
10.   the CSA is 10mm   20kVA  3 in 3 out   25mm   20kVA  3 in 1 out  as usual     2  When selecting the battery cables  according to the current value shown in Table 2 2  the Max allowable voltage  drop is 4Vdc  Do not ring the cables  so as to avoid increasing the electrical magentic interference  EMI      2 6 2 Connecting I O Cables    Distribution mode and terminal block    1  Distribution mode   There are two modes for UPS distribution  single power output distribution  POD  unit options provided by Emerson   external distribution by the user    According to the actual requirements  the I O cable connections are divided into four types  3 in 3 out  common  source configuration  factory default   3 in 3 out  split bypass configuration  3 in 1 out  common source configuration   3 in 1 out  split bypass configuration  In accordance with the four types of the two distribution methods  this section  will introduce the I O cables connection procedures respectively     This product is compatible with 3 in 3 out 3 in 1 out  factory default  3 in 3 out  Change the format according to the following steps   if you need the 3 in 1 out system     1  After the 3 in 1 out I O connections are finished by following the instructions in this section  power on the system  then press the  emergency power off  EPO  button immediately    2  Set the system to    Single Phase Output    through the LCD menu    Settings      gt     3 in 3 out 3 in 1 out     3  Power off the system completely  then pow
11.  3U thickness  Tower installation and rack installation are optional to meet different installation requirements  e Capable of ECO power supply mode  which helps you save energy to the maximum extent   e Flexible network management with Emerson monitoring software   e Fan fault self test and automatic recognition functions   e SNMP card optional  providing network communication function    e Capable of connecting multiple battery strings  extending the power supply time of Battery mode    1 2 Model Configuration    The description of model configuration is shown in Table 1 1     Table 1 1 Model configuration    Ae O        UHA3R 0200L  For single and parallel 1   1 system  four battery modules are available  for parallel system above 1   1     battery connection is required    2 Chapter 1 Product Introduction    1 3 Appearance And Components    1 3 1 Appearance    The UPS appearance is shown in Figure 1 1                                                                                               Ventilation holes Operation and DIP switch  battery cold start  display panel button  with protective cover     Figure 1 1 UPS appearance       Non authorized personnel are prohibited from opening the UPS chassis cover  Otherwise  electric shock may occur     1 3 2 Components    Front panel    As shown in Figure 1 1  the UPS front panel provides ventilation holes  operation and display panel  DIP switch and  battery cold start button  with protective cover   The operation and displa
12.  And Bypass Inputting    Overcurrent   The appropriate overcurrent protective device should be installed on the mains input distribution  and the current  capacity of power cable and the system overload requirements should be taken into account in installation  see Table  1 2   It is generally recommended to use the thermomagnet circuit breaker of IEC60947 2 tripping curve C  normal    when the current value reaches 125  of the current value listed in Table 2 2    Split bypass  When the system adopts split bypass  the protective devices should be respectively installed at the  mains input distribution for mains and bypass     Main Bypass reflected protection    When using the main bypass reflected protection function  the gross mains input needs to be equipped with the  protective device with auxiliary contact function  The recommended model is S1N125 R125 TM FFC 4P  1A 1B   YO  220Vac      The same neutral must be used for the rectifier and bypass power   For IT power grid system  the protective device with four poles must be installed at the UPS external I O distribution     Earth leakage current       The residual current detector  RCD  for the UPS upstream input distribution should be   e Sensitive to the DC unidirectional pulse  level A  in distribution network  e Insensitive to the transient current pulse    e General sensitivity type  settable  0 3A   1A      Trust Adapt UPS 20kKVA User Manual    Chapter 2 Installation 11    The residual current circuit breaker  RCCB  
13.  Figure 3 4 Default screen    iTrust Adapt UPS 20kVA User Manual    Chapter 3 Operation And Display Panel 27    3 3 Detailed Description Of Menu Items    The description in the following refers to the LCD primary screen shown in Figure 3 3   System information window    The system information window displays the current time and the UPS name  You are not required for operating the  information of this window  For details  see Table 3 5     Table 3 5 System information window       ltem Explanation  ITA 020kVA UPS name  which stands for   Trust Adapt 20kVA UPS  12  30  36 Current time  format  24 Hours  h  min  s                       Menu window and UPS data window    The menu window displays the menu name of the data window  The data window displays the items of the menu  selected from the menu window  UPS parameters can be browsed and functions can be set through the menu  window and data window  Details are given in Table 3 6     Table 3 6 Menu window and data window                                                                                                          Menu Item Explanation  L N voltage  V  Phase voltage  L N current  A  Phase current  Mains Frequency  Hz  Input frequency  L L voltage  V  Line voltage  Power factor Power factor  L N voltage  V  Phase voltage  Bypass Frequency  Hz  Bypass frequency  L L voltage  V  Line voltage  L N voltage  V  Phase voltage  L N current  A  Phase current  Output Frequency  Hz  Output frequency  L L voltage  V  Line voltag
14.  If any problem is found  please notify the carrier  immediately     2  Check the accessories and model against the delivery list  If any problem is found  please notify the dealer  immediately     2 2 Location    To extend the UPS life  the selection of the UPS location should be   e Convenient wiring  e Adequate operator access area  e Well ventilated location to meet the heat rejection requirement  e Non corrosive gas surrounded  e No excessive moisture and heat sources      Free of dust  e Compatible with fire fighting requirements    e Temperature of operation environment complies with the specifications  see Table 1 2 for details      Trust Adapt UPS 20kKVA User Manual    Chapter 2 Installation 7  2 2 1 Distribution Room    The UPS is designed for indoor installation  which should be installed in clean and well ventilated environment  so as  to keep the ambient temperature within the specifications range     The internal fans provide the forced air cooling for the UPS  Cooling air enters the UPS through the front ventilation  holes  and exhausts the hot air through the back ventilation holes  Therefore  do not restrict the ventilation holes  The  front  rear and side panels of the UPS should be kept at least 200mm distance from the wall or consecutive  equipment  so as not to obstruct the UPS ventilation and heat rejection  Otherwise  the UPS internal temperature will  rise  which will shorten the UPS life     If necessary  an indoor extractor fan should be installed to
15.  Si aS al Al A ve   3 3 3 2 ee ae D oO oo  oO   zl uw  O O  Dry contact port 1 Dry contact port2  Drycontactport3 Dry contact port 4 Dry contact port 5  Figure 2 16 Pin distribution of dry contact ports  Table 2 3 Description of the dry contact ports  Silkprint Port name Pin NO  Pin name Meaning  1 1 S_ALARM The signal level is 12V  when the system alarms  1 Output port of alarm       1 2 GND GND  The signal level is 12V  when the system runs in battery       Output port of battery 2 1 ON_BATTERY                            2 inversion mode  status 22   GND GND   3 Output port of bypass 3 1 ON_BYPASS The level is 12V  when the system runs in bypass mode  status 3 2 GND GND       iTrust Adapt UPS 20kVA User Manual       Chapter 2 Installation 19                                        Silkprint Port name Pin NO  Pin name Meaning  4 1 EPO_NC EPO activated  when opened to 4 2  4 Input port of remote 4 2  12V EPO activated  when opened to 4 1  EPO   4 3  12V EPO activated  when shorted to 4 4  4 4 EPO_IN EPO activated  when shorted to 4 3  Bypass reflected protection relay  normally open   the bypass  5 1 BFP_O silicon controlled rectifier  SCR  will close when short circuit  5 Output port of bypass appears  reflected 5 2 BFP_S The middle point of the bypass reflected protection relay  Bypass reflected protection relay  normally open   the bypass  5 3 BFP_C   eee  SCR will open when short circuit appears  Note   Pin1 and pin2  or pin3 and pin4 of the dry contact port 4 reserves the
16.  UPS executes the system self test  and the start screen will appear and remain about 15  seconds  as shown in Figure 3 2     EMERSON     Network Power     O Liebert    F4 HELP          Fl F2 F3       Figure 3 2 Start screen    26 Chapter 3 Operation And Display Panel    3 2 2 Primary Screen    After the UPS system self test  the primary screen shown in Figure 3 3 will appear  The primary screen is composed  of four windows  system information window  data window  menu window and keypad window     ES RES  JUA CANLA 20 6A i System information window    A AB   510   07  07 9   L N voltage  V  220 220 220  L N current  A    20 5 20 5 20 5       Frequency  Hz  50 1 50 1 50 1 i  L L voltage  V  380 380 380 Data window    Power factor  o MeTo   ORe  0 99  Output    Menu window    Keypad window       Figure 3 3 Primary screen    The current icons on top of the F1   F4 and HELP menu buttons give the explanations of each button  From any  menu in primary screen  press the F1 button can return to the  Output  menu  For details about the primary screen     refer to 3 3 Detailed Description Of Menu Items     3 2 3 Default Screen    During the UPS operation  if there is no alarm within 2 minutes  the default screen shown in Figure 3 4 will appear   After a short while  the LCD backlight will turn off  Press any menu button  F1   F4  HELP   the primary screen will    appear again     ITA 020kVA    EMERSON      Network Power    lO Liebert    Press any button to return to the main menu      
17.  UPS on the guide rails in the rack  and push it completely into the rack  Take out four M6 16 screws to fix  the UPS on the rack through brackets  as shown in Figure 2 4           Wa    UPS                   Bracket        a                            Screw  4 pcs   P    Figure 2 4 Installing the UPS    Installation procedures for battery modules included    The installation method of the battery module is the same as that of the UPS  Repeat the above procedures to install  and fix the four battery modules and UPS on the rack one by one  As the battery module is heavy  you should pay  attention to the following items in installation     e Two persons or more are required for the installation    Install the battery module  start the installation from the bottom  and then place the UPS onto the top  as shown  in Figure 2 5    e Moving the UPS and battery modules through brackets is prohibited    10    Chapter 2 Installation    UPS  1 piece     Battery module       4 pcs                                                                                      Figure 2 5 UPS installation diagram of battery modules included    2 5 External Protective Device    2 5 1    The circuit breaker or other protective devices must be installed at the external AC input port of the UPS  This section  provides the general guidance for qualified installation engineer  The qualified installation engineer should learn about  the local wiring regulations for the equipment to be installed     Rectifier
18.  correct  and rectify it if it is  found to be in error       Load impact transfers  bypass    A transfer to bypass occurred due to a large step load  The UPS should recover automatically  Turn on  connected equipment in sequential order to reduce the step loading of the inverter          Transfer time out    Bus abnormal       The load is on bypass power due to excessive number of transfers that occurred within the last hour   The UPS will recover automatically and will transfer the load back to inverter power within an hour  DC input voltage to inverter beyond limits  Inverter shuts down  Load transfers to bypass      Trust Adapt UPS 20kKVA User Manual       Chapter 3 Operation And Display Panel 31       Alarm message    DC bus over voltage    Description  Rectifier and inverter were shut down because DC bus voltage is too high  Check whether there is a  fault in rectifier side  If not  check whether there is an overload  After recovering the fault  restart the  inverter       Bypass over current    Bypass current is over limit above 135  rating  The UPS just alarms without any action       Setting save error    History records not saved  Reserved        Input Disconnect  Fault    AC mains input neutral is not checked out       Protocol version clash    Firmware incompatibility between Monitor Board and Digital Signal Processor Board             Manual on Manual Turn On through operator control and display panel  Manual off Manual Turn Off through operator control and displ
19.  corresponding terminals for configuring the EPO  function  The external EPO device also needs the shielded cable to connect to the normally open close remote EPO switch  between the two terminals  If not necessary  you should disconnect pin3 and pin4 of the dry contact port 4  or short pin1 and pin2  of the dry contact port 4  Pin1 and pin2 of the dry contact port 4 have been shorted before delivery             The EPO action of the UPS will close the rectifier  inverter and static bypass  but it can not disconnect the UPS mains input inside   If you want to disconnect the UPS completely  just disconnect the upstream input switch when generating the EPO          2 7 2 Connecting USB Communication Cable    Insert one end of the USB communication cable accessory into the USB port on the UPS rear panel  see Figure 1 2    and insert the other end of the USB communication cable into the computer USB port     2 7 3 Connecting SNMP Card Communication Cable    The UPS provides the installation communication components of the SNMP card port  see Figure1 2   including   SNMP card  dry contact card and MODBUS card  For the installation and usage of the communication components   refer to the delivered documentation of each communication component  SNMP card port and USB port can be used  together     The pin distribution of each SNMP card port is shown in Figure 2 17                                                           GND_SNMP   9 SNMP 4 O 1  AN at  e RXD_SNMP o3   lt  TXD_SNMP o
20.  keep the indoor temperature from rising  An air filter should  be used where the UPS is to operate in a dirty environment     The UPS is only suitable for installing on the concrete surface or other non flammable surfaces        2 2 2 Battery Room    A small amount of hydrogen and oxygen will be generated at the end of battery charging  therefore  you must ensure  the fresh air ventilation of battery installation environment to meet the EN50272 2001 requirements     The battery ambient temperature should be the constant temperature  for the ambient temperature is the main factor  to affect the battery capacity and life  The battery standard operating temperature is 20  C  operation above this  temperature will shorten the battery life  and operation below this temperature will reduce the battery capacity  If the  battery average temperature in operation rises from 20  C to 30  C  the battery life will be reduced by 50   if the  battery temperature in operation exceeds 40  C  the battery life will be decreased exponentially  In general  the  enabled ambient temperature of the battery is 15  C   25  C  The battery should be kept away from heat and  ventilation holes     When the UPS uses an external battery  you must install a battery protective device  such as fuse or circuit breaker   in areas near the battery  and use the shortest wiring distance for the protective device and battery connection     2 2 3 Storage    The UPS must be stored indoors to protect against the exces
21.  situation into account  and refer to Table 3B of IEC60950 1     1  Before carrying out the UPS wiring  ensure that you have learned about the location and state of the UPS input and mains    distribution switch  Make sure that the switches are in open state  and put up the warning mark to prevent the switches from  operating by others    2  Failure to follow adequate earthing procedures can result in electromagnetic interference  electric shock hazard to personnel   and risk of fire        Cables Selection    Select the cables according to Table 2 2     Table 2 2 Maximum steady state AC and DC current                                           Rated current  A   UPS rated Mens input curent upon Paller Gross output current  at full load Battery discharging current upon  power  kVA  charging with Max ability Min battery voltage  380V 400V 415V 380V 400V 415V  20  3 in 3 out  36 36 36 30 29 28 67  20  3 in 1 out  36 36 36 90 87 84 67  Note     1  The mains current input of the rectifier and bypass   2  Non linear load  switch mode power  affects the neutral cable design of output and bypass  The neutral cable current may  exceed the rated phase current  in general  1 732 times the rated current             12    Chapter 2 Installation    1  PE line  Use the shortest wiring route when connecting the cabinet earth cable  The cross sectional area  CSA  of  the earth cable should be selected according to the AC power fault level  cable length and protection type  From  AS IEC60950 1
22.  the I O  terminal block  shorted copper bar 4 of two oN terminals and the other screw hole of shorted copper bar 10 of the  UPS    e 3 in 1 out  split bypass configuration  1  As shown in Figure 2 10  you can paste the insulating film  accessory  to the shorted copper bar 10  and insert the  buckles into the corresponding holes on the shorted copper bar 10     2  Short two PE terminals of the UPS I O terminal block using the shorted copper bar 10 with an insulating film  short  bA  bB and bC terminals using the shorted copper bar 7  and short oA  oB and oC terminals using the shorted copper  bar 5  and then short mN and bN terminals  two oN terminals using two shorted copper bars 4  as shown in Figure  2 14       Trust Adapt UPS 20kKVA User Manual    Chapter 2 Installation 17                                                                                                                                                                                                                                                                                                                                                       oN 0A 0B oC PE MNbN bA bB bC     ollo eS a Pa Tp  Bo 5  4 5 210    4 o   H  i Oo O DO     O VO  Fi LO  Z y  uo  a    Xa o                                                                                                                                                                                                                                                         
23. 0 400 415V  3  N PE 50 60Hz 30A MAX O   35 tii A AC INPUT  380 400 415V  3  N PE 50 60Hz 36A MAX   35 RiR A BYPASS INPUT  220 230 240V  10 N PE 50 60Hz 90A MAX O   380 400 415V  3  N PE 50 60Hz 30A MAX    jth if  A BATT INPUT   432V    67A MAX  FF 5  S SERIAL NO      SEERA PUR BEAR BORA al Y A    Emerson Network Power Co   Ltd      MADEIN CHINA    Figure 2 15 Label    2 6 3 Connecting Battery Cables    If the battery module is not selected  this product needs to be equipped with positive and negative batteries  Each battery string  ranges from 15 cell to 20 cell  and 12V for each cell        Connection procedures for battery cables are as follows   1  Confirm that all UPS external I O switches are open   2  Connect the battery cables     e Selected battery modules  4 pcs     18 Chapter 2 Installation    1  Take out the UPS options and select battery cables  insert the battery cables marked with    Battery Module 1         Battery Module 2        Battery Module 3    and    Battery Module 4    respectively into any battery port on the rear panel of  the four battery modules  see Figure 2      2  Ground one end of the battery cable marked with    UPS PE        3  Connect the other end of the battery cables marked with    BAT          BAT N        BAT    respectively to    Bat          Bat N         Bat   terminals of the UPS I O terminal block  see Figure 2 7      4  Tighten the fixing screws on both battery port sides of the battery module through screwdriver  so as to prevent 
24. 4    RXD232 Os  o     TXD232 o6  A o 8   SNMPSIG  gt    O 9   9 TR   O 19       14 PIN    Figure 2 17 Pin distribution of SNMP card ports    20 Chapter 2 Installation    The pin description of each SNMP card port is shown in Table 2 4     Table 2 4 Pin description of SNMP card ports       Pin Description  1 9 GND of SNMP card  2 SNMP card power provided by DSP panel  Signal from the SNMP card  which connects with RXD of the DSP  Signal to SNMP card  which connects with TXD of the DSP  Connect with RX of the RS232 communication port of the host  Connect with TX of the RS232 communication port of the host  Reserved  Selected communication signal   9_TR is introduced into this pin after the SNMP card is plugged  The power supplied by DSP panel  for selecting the card                            Co  N  O  Oo  A                    ae  o       If you wish to connect the SNMP card  model  UF SNMP810  to Emerson temperature sensor  model  RDU A S01T  to make it be  the battery temperature compensation  please connect the COM1 port of the SNMP card  and set the temperature sensor DIP  address to    1        The DIP switch on the UPS front panel  see Figure1 1  is used to set the parallel address for each UPS single in parallel system  installation  You are not required for setting the DIP switch in UPS single system installation  Set the DIP switch at will can result in  UPS fault        2 8 Parallel System    The UPS parallel system provides the user with N   X  2 lt N   X lt 4  paral
25. 5 2 Battery Input ide 11  ZO UPS Output  A A A ol ee eee ae 11  2 6  Connecting Power  Cable Sasi erneer e a a a es ieee seeded its 11  26V Cables  S  lection  a iaa 11  2 6 2 Connecting 1 0 Cables  aaa io Bata ete a dai 12  2 6 3  Connecting  Battery Cables  a r a a e a aaa Ra aa aa aaae E aa aT a AAE An arane 17  2 7 Connecting Communication CableS   omconninnnninnnccnncnnnconncnccn nc nrncn rc rra 18  2 7 1 Connecting Dry Contact Communication Cable          ccecceeeceeeceeeeeeeeeeeeeeeeaeeseeeeeaeeseaeeeeeseaeeseeesnaeeseeeeeatees 18  2 7 2 Connecting USB Communication Cable oo    ecceeceesceeeeeeeeeeteeeeeeeeeeeeeeeeeeeeeeeeeeeeseeeesaeeseaeeeseeesieeseeeeeaeees 19  2 7 3 Connecting SNMP Card Communication Cable            cccecceesceeseeeeeceeeteeeeeeeeeeeeaeesaeeeseescaeseeesaeseaeeeaeeeneeaees 19    2 8 Parallel SM ii ita a neni 20    2 81  Mechanical Installation a a 0 20    2 8 2 Setting Parallel Addresses  coca ir id 21  2 8 3 Connecting Parallel Cables           ceccecsececeeeseeeseeeeaeeeeeeceeseaeeseeceaeeseeesaeceeaeesseeecaeesaeseaeesaaeseaeesieeeeeeesaeees 21  2 8 4 Connecting 1   1 Parallel POD CableS    oonccnccnninnnnnncnnncccnconnncnnnconc conc nana nnna ron ccnn crac rana ranrirarnncnnr 22  2 9 Shared Ballena a de o S 22  2 10  Double Bus  System ici ia 23  2101 System Installation sciatic erat wheats Aa ied iaa 23  2 10 2 External Protective  Device  cui ives 23  2 10 3 PowerGables ca ie bli ea Gs Aha idee wend eee ies ee ee 23  210 4EBS Control  Cables
26. S CIRCUIT     VAN DM Maintainable Components    All equipment internal maintenance and servicing procedures should be carried out only by trained personnel  Removal of  components behind the protective cover requires the use of a tool and is restricted to service personnel    The UPS meets the safety requirements completely in operator access area  Only the service personnel can contact with the  hazardous voltage inside the UPS  However  the risk of contacting with these voltages is minimized as the components with  hazardous voltage may be contacted only uses a tool to remove the protective cover  No risk will exist if you follow the  general norms and in accordance with the procedures recommended in this manual on equipment operation        VAN Dn Battery Voltage Above 400Vdc    Tools or keys must be used for all batteries maintenance  which should be carried out by trained personnel   Battery use requires special care  After the battery is connected  the voltage of the battery terminal will exceed 400Vdc  and    physical contact would be fatal    Battery manufacturer provides the precautions to be observed when working on  or in the vicinity of the battery string  These  precautions should be followed implicitly at all times  Particular attention should be paid to the recommendations concerning  local environmental conditions and the provision of protective clothing  first aid and fire fighting facilities        Contents    Chapter 1  Product  Inthoduction es ae e estas c
27. S assembly used in UPS  UFMOD21Z1     R5     ONENESS    B     AS   Used for battery module selection  components selection  B inet with     alloy count U20 24C2 Used for battery perparation by the user  two layer  B binet with     ene camer U20 38C3 Used for battery perparation by the user  three  layer         Trust Adapt UPS 20kKVA User Manual    
28. abled       3 in 3 out 3 in 3 out    Set the output system  3 in 3 out 3 in 3 out   This setting can only be carried out after the EPO operation  After the  setting  you must power off the system  and confirm that the system  actual connection mode complies with the setting  Power on again   and the setting can come into force       Command  start  stop  battery  system test or  frocing boost charge     Battery maintenance  test    The battery maintenance test will lead to the battery being partly  discharged  for rough assessment of the battery capacity  The load  must range from 20    100        Battery capacity test    The battery capacity test will lead to the battery being completely  discharged  for accurate assessment of the battery capacity  The load  must range from 20    100        System test    For UPS self test  The user actives this function  5 seconds later  a  pop window will appear to show the result of this test       Stop testing    Manually stop the test  including maintenance test  capacity test and  system test       Forcing charge    Manually conduct the forcing charge for battery       Stop forcing charge    Manually stop the forcing boost charge for battery          Version    Keypad window    Monitor Version    Provide the monitor software version          Rectifier Version  Inverter Version       Provide the rectifier software version  Provide the inverter software version    The function of menu buttons  F1   F4 and HELP  is shown in icon mode for 
29. and or slave system for running in Normal or Bypass mode  The typical double bus system is shown in Figure                                                                                                                                                    2 20   Bypass Bypass  eee Ue URS ee Ce pe re es  UR Aa ea 23  aag aay e    1 1 1   i  j 1    fee yo     io   E    TAE 6 ZH   pte PE    De ex A a  EF    a   el  27 l Tot    Pafalle    a E control  21 Z       control     1 1 I 1  1 I                                                 X  Load connection    Figure 2 20 Typical double bus system  with the STS and LBS   2 10 2 External Protective Device  See 2 5 External Protective Device     2 10 3 Power Cables    See 2 6 Connecting Power Cables     2 10 4 LBS Control Cables    Just connect the LBS cables respectively to any two LBS ports  see Figure 1 2  of the two parallel systems     24 Chapter 3 Operation And Display Panel    Chapter 3 Operation And Display Panel    This chapter introduces the functions and use of the components on the UPS operation and display panel  and    provides LCD display information  including the LCD screen types  detailed menu messages  prompt windows and  UPS alarm message list     3 1 Introduction    The operation and display panel is located on the front door of the UPS  Through the operation and display panel     you can conduct the UPS operation control and query all the UPS parameters  UPS and battery states  and alarm  message     As shown in Figu
30. and so on    3  Check if the battery is discharging  When AC mains is normal  the battery should not discharge  if the UPS  operates in Battery mode  you should find out the reason  such as mains failure  battery test  operator intervention   and so on     5 5 Checking UPS Functions       UPS functions check procedures may cause power interruption to load       Trust Adapt UPS 20kKVA User Manual    Chapter 5 Maintenance 37    It is recommended to check the UPS functions once every half year   Backup the load data before conducting the UPS functions check  Procedures are as follows   1  Press the OFF button to check if the buzzer beeps  indicators are on and the LCD display is normal     2  Press the ALARM CLEAR button to check again if the indicators are on  the LCD display is normal and the UPS  has been transfered to the inverter mode     38 Appendix 1 Battery Module    Appendix 1 Battery Module    Appearance    The protective panel has been installed before delivery to avoid the damage to the battery module during the  transportation  Remove six fixing screws to take off the protective panel after the battery module arrival  The  appearance of the battery module is shown in Figure 1     y  Y     A J Fixing screw   6 pcs                    Protective            panel                                          N AN F  Y AAT    A E EEEE ESTEE EEEE EL ELL                                     Figure 1 Appearance of the battery module  Rear panel    Operation panel on the front pan
31. ay panel  EPO Press the EPO switch directly or receive the external EPO command       Transfer confirm    Prompt to press the Enter button to acknowledge that an interrupted load transfer to bypass will happen       Transfer cancel    Prompt to press the ESC button to avoid that an interrupted load transfer to bypass will happen       Fault clear    Press FAULT CLEAR       Alarm silence    Press ALARM CLEAR       Turn on fail    Inverter failed to turn on when INVERTER ON direct access button was pressed  This may be as a  result of Invalid Operation  maintenance bypass on  or DC bus or rectifier not ready       Alarm silence cancle    Press FAULT CLEAR or ALARM CLEAR       Bypass mode    The UPS is in Bypass mode       Normal mode    The UPS is in Normal mode       Battery mode    The UPS is in Battery mode                Check UPS output The UPS is off and has no output  Battery float charging Battery status  Float charge mode   Battery boost   y Battery status  Boost charge mode   charging  Battery discharging Battery status  discharge mode        Battery period testing    Automatic periodic battery maintenance discharge test  20  capacity discharge        Batt  capacity testing    User initiated battery capacity discharge test  100  capacity discharge        Batt  maint  testing    User initiated maintenance discharge test  20  capacity discharge        UPS system testing    User initiated system test       Inverter in setting    Inverter starting up and synchronizing    
32. ble 3 3     Table 3 3 Description of control buttons                               Control button Silkprint Description    en    EPO switch EPO Used to disconnect the load power and close the rectifier  inverter  static  bypass and battery   Inverter on ON Used to start the inverter  Inverter off OFF Used to close the inverter  Fault recovery on off FAULT CLEAR Recover the UPS function  clear fault in advance    i i i i i il h ibl  Alarm sound silence ALARM CLEAR When an audible alarm is active  press this button to silence the audible  on off alarm  Press this button again can restart the buzzer          3 1 4 LCD And Menu Buttons    The operation and display panel provides an LCD and five menu buttons  F1  F2  F3  F4  HELP   Table 3 4 gives the  menu buttons function description     Table 3 4 Menu buttons function description                                  Button FA F2 F3 F4 HELP  ESC cH  Function 1 O  lt   HOME Escape Left Right Enter  Function 2 T 7v  Up Down                            LCD provides you with the user friendly interface and the 320 x 240 dot matrix image display  The user friendly and  menu driven LCD allows you to easily browse through the input  output  load and battery parameters  learn about the  current UPS status and alarm message  perform functional setting and control operation  The LCD also stores up to  512 historical alarm records that can retrieve for reference and diagnosis     3 2 LCD Screen Types    3 2 1 Start Screen    Upon UPS start  the
33. card port       Communication address    This setting is suitable for RS485 communication       Communication mode    Set the communication mode       Callback times    If the communication mode of the SNMP card port is Modem  you can  set alarm callback times here       If the communication mode of the SNMP card port is Modem  you can          Ph No 1  oe set phone No 1 here  If the communication mode of the SNMP card port is Modem  you can  Phone No 2  set phone No 2 here  Phone No 3 If the communication mode of the SNMP card port is Modem  you can    set phone No 3 here       Command password    You can change the command password  Default     123456          Single Group Batt Cap    Battery capacity       Battery cells Number    Set the battery cell  The setting options include  30 cell  32 cell   34 cell  36 cell  38 cell  40 cell       Equalize Charge  Allowed    Enabled or disenabled       Temp Compensation    Enabled or disabled       Temp Sensor Position    Set the position of the temperature sensor     Remote    only       Shared Battery    Set each single in parallel system to share the battery group or not       System Configuration    Set the single parallel       Parallel Requisite Units    Set the parallel number       Parallel Redundant  units    Set the redudant number       ECO Mode    ECO function enabled       Output Frequency Level    Set the output frequency       Output Voltage Level    Set the output voltage system       LBS Function    LBS function en
34. d mN terminals  and PE terminals of the single POD   3  Connect the live line  bypass phase A  bypass phase B and bypass phase C   N line and PE line respectively to  the single POD user terminal block  bA  bB  bC and bN terminals    4  Connect the live line  output phase A  output phase B and output phase C  and N line respectively to the single  POD user terminal block  0A  oB  oC and ON terminals    5  Remove all the shorted copper bars 3 from the UPS I O terminal block  connect the UPS terminal block of the    single POD with the same silkprint terminal of the UPS I O terminal block using one to one correspondence method   and connect two PE terminals of the UPS I O terminal block to the single POD PE terminals     14    Chapter 2 Installation      3 in 1 out  common source configuration    Except for the shorted copper bar 3  all the shorted copper bars mentioned in the installation procedures are the delivery  accessories        1  Short bA  bB and bC terminals of the single POD user terminal block using the shorted copper bar 7  short oA  oB  and oC terminals using the shorted copper bar 5  and short mA and bA terminals using the shorted copper bar 6  then  short mN and bN terminals  two oN terminals respectively using two shorted copper bars 4  as shown in Figure 2 9                                                                                                                                                                                           o   HI i ni  llo L
35. e  1     r  e  F  Yo       a oo o sik   ol  a o    o  ty A y    e      o 4  25 a  Br  oN oN oA oB oC mN bN mA bA mB bB mC bC      i  T       ale ollo ojo o ollojollo ollo ollo a o   Or  o  e  o     A   e O o    PE PE   oN oN 0A oB oC mN bN mA bA mB bB mC bC   PE PE                                            Figure 2 9 Shorted copper bars connection for single POD user terminal block  2  Connect the shorted copper bar 8 to one end of the shorted copper bar 7  see Figure 2 9   and connect the live line   input phase A  to the shorted copper bar 8   3  Connect the live line  input phase B and input phase C   N line and PE line respectively to the user terminal block   mB and mC terminals   shorted copper bar 4 of mN and bN terminals  and PE terminals of the single POD   4  Connect the live line  output phase A   N line and PE line respectively to the shorted copper bar 5 of the user  terminal block  shorted copper bar 4 of two oN terminals  and PE terminals of the single POD   5  Remove all the shorted copper bars 3 from the UPS I O terminal block  and connect the UPS terminal block of the  single POD with the same silkprint terminal of the UPS I O terminal block using one to one correspondence method     6  As shown in Figure 2 10  you can paste the insulating film  accessory  to the shorted copper bar 10  and insert the  buckles into the corresponding holes on the shorted copper bar 10     S  a 1l Shorted copper       bar10             A    Buckle              Insulating film 
36. e  Power factor Power factor  Sout  kVA  Sout  Apparent power  Pout  kW  Pout  Active power  Load Qout  kVAR  Qout  Reactive power  Load level     The percentage of the UPS rated load  Crest factor Output current crest factor  Sout  kVA  Sout  Apparent power  System Pout  kW  Pout  Active power  Qout  kVAR  Qout  Reactive power  Battery voltage  V  Battery bus voltage  Battery current  A  Battery bus current  Battery temperature Battery temperature    C      C   Battery pal OS Battery run time remaining   Min    Battery capacity     Battery capacity      compared to the new battery capacity  Battery boost charging Battery is boost charging  Battery float charging Battery is float charging  Battery is not connected   Battery is not connected  Event  Current alarm  Display current alarm  See Table 3 8 for UPS alarm message list  Records  Historical alarm  Display all historical alarms  See Table 3 8 for UPS alarm message list  Language  Language selection  Options are displayed in Chinese or English          Chapter 3 Operation And Display Panel       Menu    Settings    Item  Display contrast    Explanation  Adjust the LCD contrast       Date format set    YYYY MM DD  DD MM YYYY and MM DD YYYY formats can be  selected        Date  amp  time    Set the date and time       Comm1 baud rate    Set the communication baud rate of the USB port       Comm2 baud rate    For internal communication only  can not be set       Comm3 baud rate    Set the communication baud rate of the SNMP 
37. e UPS      3 in 1 out  common source configuration  1  As shown in Figure 2 10  you can paste the insulating film  accessory  to the shorted copper bar 10  and insert the  buckles into the corresponding holes on the shorted copper bar 10   2  As shown in Figure 2 13  you can short two PE terminals of the UPS I O terminal block using the shorted copper  bar 10 with an insulating film  short bA  bB and bC terminals using the shorted copper bar 7  short oA  oB and oC  terminals using the shorted copper bar 5  and short mA and bA terminals using the shorted copper bar 6 and then  short mN and bN terminals  two oN terminals using two shorted copper bars 4     oN oA 0BoC PE mN bN mA bA bB bC                                                       O                                                                                                                                                                   Figure 2 13 Shorted copper bars connection for UPS I O terminal block    3  Connect the shorted copper bar 8 to one end of the shorted copper bar 7  see Figure 2 13   and connect the live  line  input phase A  to the shorted copper bar 8   4  Connect the live line  input phase B and input phase C   N line  PE line respectively to the I O terminal block  mB  and mC terminals   shorted copper bar 4 of mN and bN terminals  and one screw hole of shorted copper bar 10 of the  UPS   5  Connect the live line  output phase A   N line and PE line respectively to the shorted copper bar 5 of
38. ed ede desks a a cates tas E Aa E A cased Aaaa Saas Ea S A EAA ERRE EEan 1  O 1  1 2 Model Configuration  titanio di Aa Aa 1  1 3 Appe  rance And Components cited ie rita dd ie ae 2   1 31 Appearance mrena ca ai aa e aa Aaa a a a Ea a a aE aaa a Ea 2  1 3 2 COMPONE N  S mi i a a a a ae 2  U aaloele are Principles 3  1 5 UPS State And Operation Mode     cooconcccncccocicocanaccnnncnnncnncnnnonnncnn nro nr non nn anne nana reai i are ana eiea 3  1 51 Normal Modest cn 3  125 2 Bypass  Mode cia bl a 3  1 5 3 Ba  ttery Mode  sci aie Ae a a 4  1 5 4 ECO Mode  For Single System Only           eccescceesceeeeeeeneeceaeeeeeeseaeesenesaeeceeceaeeaeeesaeseaeesaeesaeeeeeseaeeseeetnaees 4  1 5 5 Fault  States ia het ea Ao a ida een adnan enamine s 4  1 60  Specification il it tod cit 5   Chapter 2 Installation   vicios rt ds 6  2 1 Unpacking Inspections  ii ias 6  2  ArOCAlON a sate hte  cl A seed tn te oe eee dee ee 6   2 21 Distribution ROOM iii ee a Ee 7  2 22 Battery    ROOM sc  atest tii ethic nee aod ibe al digg A E E Se eect 7  Play se EOIR  O    REPRE EEE EET ld 7  2 3  Installation tools    scence devin aA Sealand een das 7  2 4 Mechanical Installation ade reed aes 8  2 41 Tower Installation  ji    ee ei es eee ee 8  2 4 2 Rack Install iii NEEE 9  2 5 External Protective  DOV e a E a r T a EEr a e E a Aaaa aaa A Aa rada A Eaa i 10  2 5 1 Rectifier And Bypass INputting         ooocconnccnonicinnonononnnnornnncancnorcn non nnon cnn r nn nr na rr rr nr rre nr ne nnr na rnn nn 10  2 
39. el Parallel  port 1 port 1  Parallel Parallel  port 2 port 2  Parallel cable                                        UPS3 UPS4  Parallel cable  Parallel Parallel  port 1 port 1  Parallel Parallel  port 2 port 2                         Parallel cable          Figure 2 19 Parallel cables connection schematic diagram  3   1 parallel system     22 Chapter 2 Installation   2 8 4 Connecting 1   1 Parallel POD Cables  Connecting 1   1 parallel POD cables includes  connecting cables between the UPS and 1   1 parallel POD and  connecting input and output cables of the 1   1 parallel POD     Connecting cables between the UPS and 1   1 parallel POD    Connect the UPS1 terminal block  silkprint  UPS1  on the 1   1 parallel POD rear panel to the same silkprint terminal  on the UPS1  rear panel I O terminal block using the one to one correspondence method  Connect the UPS2  terminal block  silkprint  UPS2  on the 1   1 parallel POD rear panel to the same silkprint terminal on the UPS2    rear panel I O terminal block using one to one correspondence method     1  When connecting cables  connect the UPS end at first  and then connect the 1   1 parallel POD end     2  For kinds of system connection differences such as 3 in 3 out  common source configuration   3 in 3 out  split bypass  configuration   3 in 1 out  common source configuration   3 in 1 out  split bypass configuration   refer to 2 6 2 Connecting I O  Cables        Connecting I O cables of the 1   1 parallel POD    1  An upstream pr
40. el addresses for all the UPS singles in parallel system should be set  The parallel addresses can be set  through the DIP switch on the UPS front panel  see Figure 1 1   Remove the DIP switch protective cover  and set the    DIP switch according to Table 2 5  The parallel address must be unique for each UPS single     Table 2 5 DIP switch settings       Parallel addresses Parallel 1  Parallel 2  Parallel 3  Parallel 4   ON ON ON ON    DIP switch position E                   DIP1                                                          DIP2 DIP3 DIP4 DIPS                      DIP1 DIP2 DIP3 DIP4 DIPS                                                                   DIP1 DIP2 DIP3 DIP4 DIPS                      DIP1 DIP2 DIP3 DIP4 DIPS                      The default setting for DIP switch is   1     you can set the DIP switch to 2  3 or 4  However  you should set the DIP switch position  according to the description listed in Table 2 5  Otherwise  the UPS fault will occur     2 8 3 Connecting Parallel Cables       The parallel system provides the parallel cable options  Through the parallel ports  see Figure 1 2  on the UPS rear    panel  the parallel cables are connected in close loop mode one by one  Taking the 3   1 parallel system for example   the schematic diagram of the parallel cables connection is shown in Figure 2 19                                                                       Parallel cable                                  UPS1 UPS2  Parallel cable  Parall
41. el of the battery module is not available  The battery module provides battery ports   battery fuse box and ventilation holes on the rear panel  as shown in Figure 2     Battery port 1 Battery port 2    i 2 eo epee o    mos erro orate       E                               SS a O OS O 2      Q  ae o m D a   lt  gt  2  o SO O  DO 0             D  Ventilation holes Battery fuse box    Figure 2 Rear panel of the battery module      Trust Adapt UPS 20kKVA User Manual    Appendix 1 Battery Module 39    Replacing the battery fuse   If the battery internal fuse is damaged  loosen the protective cover of fuse box on the battery module rear panel and  replace the damaged fuse with a new one  then tighten the fixing screws of the protective cover of fuse box to prevent  electric shock risk during the UPS operation  as shown in Figure 3           gt  Protective cover  of fuse box       e          Figure 3 Schematic diagram of replacing fuse    1  The battery loop and AC input are not insulated  a hazardous voltage may exist between the battery ports and ground  so it is    prohibited to touch them for avoiding electric risk   2  The length of the standard battery cable delivered with the battery module is 0 5m  If you need more length cable  please    consult the dealer        40 Appendix2 Optional Part List    Appendix 2 Optional Part List    The optional part list is given in Table 1     Table 1 Optional part list    Rezzo component O    UF RS485 RS232 to 485 component  UFMOD21Z1 MODBU
42. er it on again  the system will run in 3 in 1 out mode        2  Terminal block  The power cables connection of the UPS should be connected through the I O terminal block located on the UPS rear  panel  Figure 2 7 gives the terminals distribution of the l O terminal block     Bat  Bat   oN oAoB oC   BatN PE mN bN mAbA mB bB mC bC                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                        a Q 7 A F  Q MT  L     3 3 s  l    la  8 le  e e ol olollo o o o loo So   o BOE  Ro D  pii  z E 7  F                      Note  1  Maininput  mA  mB  mC  mN  Bypass input  bA  bB  bC  bN  Output  oA  oB  oC  oN  Battery  Bat    Bat N  Bat    GND  PE  2  Infactory  four shorted copper bars 3 have been used to short terminals between mA and bA   mB and bB  mC and bC  mN and bN respectively    Figure 2 7 Term
43. erminal block and UPS terminal block all have protective covers   Before the connection  you should remove the protective cover of each terminal block  after the connection  you  should reinstall these protective covers     NN    After the cables connection  you must reinstall the protective cover of each terminal block  so as to avoid the electric shock when  the UPS is in operation state        Single POD options  Recommended     3 in 3 out  common source configuration  factory default     1  Connect the live line  input phase A  input phase B and input phase C   N line and PE line respectively to the user  terminal block  mA  mB  mC and mN terminals  and PE terminals of the single POD    2  Connect the live line  output phase A  output phase B and output phase C   N line and PE line respectively to the  user terminal block  oA  oB  oC and ON terminals  and PE terminals of the single POD     3  Remove all the shorted copper bars 3 from the UPS I O terminal block  connect the UPS terminal block of the  single POD with the same silkprint terminal of the UPS I O terminal block using one to one correspondence method   and connect two PE terminals of the UPS I O terminal block to the single POD PE terminals    e 3 in 3 out  split bypass configuration  1  Remove all the shorted copper bars 3 from the single POD user terminal block   2  Connect the live line  mains phase A  mains phase B and mains phase C   N line and PE line respectively to the  user terminal block  mA  mB  mC an
44. ers     UPS Start up    The start up procedures can be performed after the installation is finished  the system has been commissioned by  authorized personnel and the external input switches are closed     This procedure results in mains voltage being applied to the UPS output terminals  Confirm that the load power is safe  if there is a  load to be connected with the UPS output terminal  Ensure that the load is isolated with the UPS output terminal  if the load is not  ready for accepting the power        Normal Module Start up Procedure    This procedure is suitable for UPS start up when the UPS is in complete disconnection state  Procedures are as  follows     1  Close the UPS external output switch and input switch on by one     At this point  LCD displays the start screen  and the rectifier starts  After the rectifier runs in normal state about 30s   the rectifier start up is finished     2  Press the ON button for 2 seconds     At this point  the inverter starts  and the inverter indicators are blinking green  After the inverter runs in normal state   the UPS transfers from bypass state to inverter state  The inverter indicators turn green  and the UPS runs in Normal  state     Battery Module Start up Procedure    1  Check that the batteries have been well connected    2  Press the battery cold start button on the UPS front panel  see Figure1 1     At this point  LCD displays the start screen  After the rectifier start up is finished  the fault indicator is off   3  Pre
45. g should occur  After this pre warning        B             oO    kana battery should have the capacity for 3 minutes discharging with full load  The time is user configured   PE from 3 minutes to 60 minutes  Shut down the load in time   Battery sto a       face p Inverter turned off due to low battery voltage  Check the utility failure and try to recover it       Mains volt  abnormal    Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown  Check the input  line to neutral voltage amplitude of rectifier       Mains undervoltage    Mains voltage is undervoltage  Derate for running and check the input line voltage       Mains freq  abnormal    Mains frequency is out of limit range and results in rectifier shutdown  Check the input frequency       Rectifier block    Rectifier detected faulty  Rectifier shuts down  Battery discharges       Rectifier overtemp     The temperature of heat sink is too high to keep the rectifier running  The UPS can recover  automatically  Check the environment and ventilation       Battery charger fault    Battery charger is over voltage       Control power 1 fail    UPS operates but Control Power is not available       Mains phase reversed    Rectifier AC input phase sequence is reversed       Rectifier overcurrent    Rectifier is over current       Soft start fail       Rectifier could not start due to low DC bus voltage          30    Chapter 3 Operation And Display Panel       Alarm message    Bypass unable to  trace  
46. he battery life depends on  the ambient temperature  charge and discharge times  High ambient temperature and deep discharge shortens the  battery life     To ensure the battery life  it is required to     Keep the ambient temperature ranging from 15  C to 25  C   e Prevent small current discharge  Continuous battery operation time exceeding 24 hours is strictly prohibited     e Charge the battery for at least 12 hours  if the battery hasn t been charged for three months at specified ambient  temperature  or two months at high ambient temperature     1  Never short circuit the battery terminals  which will result in fire   2  Never open the battery  as the electrolyte is harmful to human body  In the event of inadvertent contact of the electrolyte  wash  the affected area immediately with plenty of clean water and go to see the doctor        Cleaning UPS    Clean the UPS periodically  especially the ventilation holes  to ensure free airflow inside the UPS  If necessary  clean  the UPS with a vacuum cleaner  Confirm that the ventilation holes are unobstructed     Checking UPS State    It is recommended to check the UPS operation status once every half year   Procedures are as follows   1  Check if the UPS is faulty  Is the FAULT indicator on  Is the UPS giving any alarm     2  Check if the UPS is operating in Bypass mode  Normally  the UPS operates in Normal mode  if it is operating in  Bypass mode  find out the reason  such as operator intervention  overload  internal fault  
47. he inverter output to the load  and the mains supplies DC power to the inverter through the rectifier PFC  circuit  The inverter then converts DC power into pure sine wave AC power  and supplies AC power to the load  through the electronic transfer switch     3  When the mains is abnormal  the rectifier PFC circuit boosts the battery voltage and supplies it to the inverter  The  inverter then converts it into pure sine wave AC power  and supplies AC power to the load through the electronic  transfer switch     4  After the mains returns to normal state  the UPS will automatically transfer from Battery mode to Normal mode  the  mains power supplies DC power to the inverter through the rectifier PFC circuit  and then the electronic transfer  switch supplies DC power to the load     1 5 UPS State And Operation Mode    1 5 1    The UPS state and operation mode include  Normal mode  Bypass mode  Battery mode  ECO mode and Fault state   For the indicators introduced in this section  refer to Chapter 3 Operation And Display Panel     Normal Mode    When the mains input is normal  the load is powered with voltage stabilizing and frequency stabilizing power by the  mains after processing of the rectifier and the inverter  and meanwhile  the operation mode that the charger charging  the battery is the Normal mode  In Normal mode  the inverter indicators are on  green      1 5 2 Bypass Mode    If the overload overtime  inverter or rectifier failure appear during the UPS operation in Nor
48. inals distribution of the I O terminal block      Trust Adapt UPS 20kKVA User Manual    Chapter 2 Installation 13    When using the single POD options  the UPS power cables should be connected through the user terminal block  UPS  terminal block and PE terminals of the single POD rear panel  The terminal distribution of each terminal block on  the POD rear panel and PE terminals are shown in Figure 2 8     User terminal block                                                                                                                                                                                                                                           o   no p p p p prp po p p p p p   o  2   j E    E ej ollollololollol o olla llallollollollollol  tal    a lelelelelelol   La   gt  H H H H H H H H3H Hah Us  lus        o   A H H  J o  oN oN 0A oB oC mN bN mA bA mB bB mC bC  U U  TO    a O ollo a   O   p A al o or  o o 2 2 2 S 2 e A 7 E z E 2 Z e o o     PE PE _  oN oN oA oB oC mN bN mA bA mB bB mC bC PE PE                                                          UPS terminal block  Note  1  Main input  mA  mB  mC  mN  Bypass input  bA  bB  bC  bN  Output  oA  oB  oC  oN  Battery  Bat    Bat N  Bat    GND  PE  2  In factory  four shorted copper bars 3 have been used to short terminals between mA and bA   mB and bB  mC and bC  mN and bN respectively    Figure 2 8 Terminals distribution of the terminal blocks and PE terminals    The UPS I O terminal block  the single POD user t
49. lel configuration  N stands for the basic  parallel sets  X stands for the redundant sets     The UPS parallel system has 1   1 parallel POD options  which can provide safe and reliable distribution function for  parallel system  The 1   1 parallel system only needs one 1   1 parallel POD  if N22  the self distribution will be  required for the parallel system     Parallel system installation includes   e Mechanical installation  e Setting parallel addresses  e Parallel cables connection    e 1   1 parallel POD cables connection    2 8 1 Mechanical Installation    Taking the rack installation of the 1   1 parallel system including battery module for example  the mechanical  installation method of the parallel system is as follows     1  The installation method of 1   1 parallel POD is the same as that of the UPS  Refer to 2 4 2 Rack Installation for  details     2  As shown in Figure 2 18  the battery module should be installed at the bottom  the UPS should be installed in the  middle  and the 1   1 parallel POD should be installed on the top  so as to facilitate the cable connection and  operation       Trust Adapt UPS 20kKVA User Manual    1   1 parallel POD  1 piece     UPS  2 pcs         Battery module  4 pcs  4    Figure 2 18    2 8 2 Setting Parallel Addresses          Chapter 2 Installation 21                                                                                                                1   1 parallel system including battery modules    SS    The parall
50. mal mode  the UPS will  transfer to Bypass mode  that is  the load is powered by the bypass source  which comes directly from the mains  input  if the rectifier is normal  the internal charger will charge the battery  In Bypass mode  the inverter indicators are  off        In the event of mains failure or mains voltage out of range in Bypass mode  the UPS will shut down and stop the output     4    Chapter 1    Product Introduction      Trust Adapt UPS 20kKVA User Manual    Chapter 1 Product Introduction 5    1 5 3 Battery Mode    Upon mains failure  rectifier overload or mains voltage out of range  the rectifier and internal charger will become  inoperative  and the battery will supply power to the load through the inverter  The inverter indicators are on together  with buzzer alarming  which notifies you that the UPS is in Battery mode     1  The battery has been fully charged before delivery  However  transportation and storage will inevitably cause some capacity    loss  Therefore  it is required to charge the battery for eight hours before putting the UPS into operation  so as to ensure the  adequate stand time for battery     2  The battery cold start can also be used to start the UPS from the Battery  charged  mode upon mains failure  Therefore  the  battery power can be used independently for improving the system availability to some extent        1 5 4 ECO Mode  For Single System Only     1 5 5    In ECO mode  the load is powered by bypass when the bypass voltage is 
51. must be sensitive to the DC unidirectional pulse  level A  in distribution  network  but insensitive to the transient current pulse  as shown in Figure 2 6 respectively     AR  NY    Figure 2 6 RCCB symbols    When using the earth RCD in split bypass system or parallel system  the RCD should be located at the upstream  input distribution terminal to avoid generating the false alarm    The earth leakage current introduced by the RFI filter in the UPS ranges from 3 5mA to 1000mA  It is recommended  to confirm the sensitivity of each differential device of the upstream input distribution and downstream distribution  to  load      2 5 2 Battery Input    2 5 3    The overcurrent protective device has been placed into the battery module  when you choose the battery module  options provided by Emerson  Otherwise  the external battery cabinet should provide DC compatible circuit breaker   so as to provide the overcurrent protection for the UPS and its batteries     UPS Output    The protective device must be installed for the UPS output distribution  The protective device must be different from  the input distribution protection switches  and it also provides the overload protection  see Table 1 2      2 6 Connecting Power Cables    2 6 1    I O cables and battery cables are required for connection  Battery modules provide the battery cable options     When designing the cables  you should follow the instructions in this section and the local wiring regulations  take the  environment
52. n    1 6 Specifications    The UPS specifications are listed in Table 1 2     Table 1 2 UPS specifications  Product model UHA3R 0200L    3 phase  380Vac  304Vac   478Vac  at full load  Voltage range 228Vac   304Vac  linear derating  228Vac  at half load  Rated   Ratedfrequency   50Hz 60Hz  raras   Rated power  220Vac   1   3 phase balance load   1Hz s  Range is settable  0 1Hz s   3Hz s  single   0 2Hz s  parallel    Fred powertaslor  09     Output  lt 2   linear load    lt 5   non linear load   Dynamic response   125    150   1min   Upper limit   10    15  or  20   default   15   Lower limit   10    20    30  or  40   default   20     gt 93   up to 94   Type Sealed  lead acid  maintenance free battery  Cell No  30  32  34  36  38  40    Rated voltage 360Vdc   480Vdc      Chargepower     Chargepower   4 5kW    Mains      Battery      transfer   lt 1ms  Transfer time  Inverter      Bypass Asynchronous transfer  default    lt 20ms  Or 40ms  60ms  80ms and 100ms are available    Po Nose    lt 58dB  Y display mode LED and LCD  Safety IEC EN62040 1 1    FECIENGROA02      Immunity   I lt 16A  IEC EN61000 3 3  16A lt IS75A  IEC EN61000 3 11    E IS16A  IEC EN61000 3 2  16A lt I lt 75A  IEC EN61000 3 12   ame Pano YD T1095 2001  level 2  15     IEC EN 61000 4 5  enduration level 4 A ol  live line to earth   level 3  2kV   A ol live lines   Protection level IP20  00400  Ambient  40  C    70  C  battery excluded    20  C    55  C  battery included   condition  35  Weight    58    Bypas
53. normal  and the load is powered by inverter  when the bypass voltage is abnormal  ECO mode is an energy saving operation mode  For some power equipment    that insensitive to power grid quality  you can use the ECO mode for power supply through bypass to reduce the  power loss     1  In ECO mode  if the bypass failure or abnormal bypass voltage appears when the output is not overloaded  the UPS will transfer  to Normal mode  However  if the bypass failure or abnormal bypass voltage appears when the output is overloaded  the UPS will  not transfer to Normal mode  but shut down the bypass    2  In ECO mode  the efficiency of the UPS is up to 98         Fault State    In Normal mode  the UPS will transfer to Bypass mode if the inverter failure or UPS overtemperature appears  In  Battery mode  the UPS will shut down and stop the output if the inverter failure or UPS overtemperature appears  In  Fault state  the fault indicators will turn on  the buzzer will keep beeping  and the corresponding fault information will  be displayed on LCD panel     In Fault state  if the bypass failure or abnormal bypass voltage appears when the output is not overloaded  the UPS will shut down    and be transfered to the inverter for power supply  such as radiator overheat  However  if the bypass failure or abnormal bypass    voltage appears when the output is overloaded  the UPS will not be transfered to the inverter for power supply  but shut down the  bypass        6 Chapter 1 Product Introductio
54. ollowing product standards for UPS      1EC62040 1 1  General and safety requirements for use in operator access area     1EC62040 2  EMC requirements  Class C2 compliant     1EC62040 3  Performance requirements and test methods   The UPS installation should follow the above instructions and use the accessories specified by manufacturer     Earth connection is essential before connecting the input power  AC mains and battery included   This equipment must be  earthed in accordance with the local electrical codes    Earth leakage current ranges from 3 5mA to 1000mA    Transient and steady state earth leakage currents  which may occur when starting the equipment  should be taken into  account when selecting instantaneous residual current circuit breaker  RCCB  or residual current detector  RCD     RCCB must be selected  which is insensitive to DC unidirectional pulses  Class A  and transient current pulses    Note that the earth leakage current of the load will be carried by RCCB or RCD     The UPS has a zero voltage contact closure signal available for use with an external automatic circuit breaker  single  power   to protect against backfeeding voltage to input terminal through the static bypass circuit  If the installation engineer  do not need to use this signal  the external bypass switchgear must be labelled to advise service personnel that the circuit is  connected to a UPS system    The label can be written  ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THI
55. opper bar 10 to PE terminals of the single  POD     Self distribution    Before carrying out the self distribution  you should prepare the protective devices such as the mains miniature circuit  breaker  MCB   bypass MCB  output MCB and maintenance MCB  It is recommended to use the 63A mains MCB   125A bypass MCB  and 100A output MCB      3 in 3 out  common source configuration  factory default   1  Connect the live line  input phase A  input phase B and input phase C   N line and PE line respectively to the I O  terminal block  mA  mB  mC and mN terminals  and PE terminals of the UPS     2  Connect the live line  output phase A  output phase B and output phase C   N line and PE line respectively to the  I O terminal block  0A  oB  oC and ON terminals  and PE terminals of the UPS     16    Chapter 2 Installation    e 3 in 3 out  split bypass configuration  1  Remove all the shorted copper bars 3 from the UPS 1 O terminal block   2  Connect the live line  mains phase A  mains phase B and mains phase C   N line and PE line respectively to the  I O terminal block  mA  mB  mC and mN terminals  and PE terminals of the UPS   3  Connect the live line  bypass phase A  bypass phase B and bypass phase C   N line and PE line respectively to bA   bB  bC and bN terminals of the UPS I O terminal block   4  Connect the live line  output phase A  output phase B and output phase C   N line and PE line respectively to the  I O terminal block  0A  oB  oC and ON terminals  and PE terminals of th
56. otective MCB must be series connected between the 1   1 parallel POD and the mains  It is recommended to  use 80A MCB in mains and 150A MCB in bypass   2  Confirm reliable connection for the earth cable        1  Connect the input cables     e For 3 in 3 out parallel system  connect the input cables  U  V  W  N  PE  respectively to the corresponding  terminals on the user terminal block  silkprint  USER  of the 1   1 POD rear panel     e For 3 in 1 out parallel system  connect the input cables  L  N  PE  respectively to the corresponding terminals on  the user terminal block of the 1   1 POD rear panel     2  Connect the output cables     Connect one end of the output cable to the user terminal block of the 1   1 parallel POD  and connect the other end  of the output cable to the load     2 9 Shared Battery    All the UPS singles in parallel system not only can share the battery string  but also can use the battery string  independently  The use of the shared battery in parallel system can save money for you     The following section will introduce the wiring and setting operation of the shared battery in parallel system     Each UPS single should be equipped with the independent battery MCB  Refer to Table 2 2 and voltage of battery string for  battery MCB type        1  Wiring  Power off the system completely and disconnect all battery MCBs of the UPS single  and then connect              N    and         terminals of the shared battery respectively to    Bat          Bat N
57. pass Mod    ooooccocccconccconcconocccnonccnnnnonon cc non cnn nan n rro norris 33  4 2 3 Transferring From Bypass Mode To Normal Mod     oooocccinccccnocncnoncnnoncnnonccnnnnononc conan nn nn nor n cn rar n craneo 33  4 2 4 Transferring From Normal Mode To Maintenance Bypass Mode     ooocccoocccnocccnocccnonccnoncononnnnnnnnnnnnnnnnn nn 33   4 3 Complete Shutdown Procedure           sccceccseceesceseeeeseeeeeecseeeaeeeaeeeaeesaeeeaeseaeesaeceeaeeaaeseeesaaecaeeseeeaeesaeeeaeeseeeeseaeeeaas 33  4 4EPO Procedures cia hides eta ete acheive eee ee eee et 34  AS    AUtO  Restar iii le a re ae at eee ache ite ene Oe 34  4 6 UPS Reset Procedure 34  4 7 Language Selection  naine a ee hen ee ee N 34  4 8 Changing Current Date And Time     eeeeeceeeceeeseceneeseaeeeeceseseeseneeeaeeseaeseaeeesaesaaeseaeessaeseaeaeaaeeeseesaaeseaeeseaeeeaeeeaeees 35    4 9  Controlling  Password ienai eh AA A ins 35    Chapter  5  Maintenance cita a a 36    5  Fan  Maintenance   6 estas ne asset A a 36  5 2 Batte Maintenance ti 36  5 3 Cleaning UPS witha fannie AA E N ie 36  5 4  Checking URS States  autos Aeon tae ia io eb al athens dened ats a a 36  5 5 Checking UPS Functions aa ba iad aaa Nee 36  Appendix 1  Battery Module  cuarta A as ne a ee 38    Appendix 2 Optional  Pam EST id orcos 40    Chapter 1 Product Introduction 1    Chapter 1 Product Introduction      Trust Adapt and 20kVA UPS  UPS for short  is an intelligent online UPS system with sine wave output developed by  Emerson Network Power Co
58. r prepare the maintenance bypass switch by yourself  so as to realize this function        1  Press the OFF for 2 seconds     The inverter indicators are off  and the buzzer alarms  The load transfers to the static bypass  and the inverter shuts  down     Press the ALARM CLEAR button can silence the alarm  but the alarm message of the the LCD is not disappeared until the alarm  status is cleared     2  Close the maintenance bypass switch on the single POD front panel  and the maintenance bypass can supply  power to the load     If you wish to maintain the UPS  you should wait 10 minutes for the internal DC bus capacitance voltage discharging    3  Disconnect the main bypass input switch and output switch           1  When the UPS is in Maintenance Bypass mode  the load does not have the mains abnormal protection   2  After the UPS transfers to maintenance bypass  the UPS is not in operation  and the LCD is no display  and only the user  terminal block of the single POD is electrified  Be careful when removes the UPS to be maintained        4 3 Complete Shutdown Procedure    If you wish to shut down the UPS completely  the procedures in 4 2 4 Transferring From Normal Mode To  Maintenance Bypass Mode should be followed  so as to transfer the UPS from Normal mode to Maintenance Bypass  mode     Disconnect the external input switch  if you wish to isolate the UPS from AC power     34    4 4    4 5    4 6    4 7    Chapter 4 UPS Operation Instructions  EPO Procedure    The UPS ope
59. ration and display panel has an EPO switch  which is designed to switch off the UPS in emergency  conditions  such as fire  flood  and so on   The system will turn off the rectifier  inverter and stop powering the load  immediately  inverter and bypass included   and the battery stops charging or discharging     If the mains input is present  the UPS control circuit will remain active  however  the output is closed  To remove all  mains power from the UPS  the external input switch should be disconnected     Auto Restart    When the mains power failure  the UPS draws power from the battery to supply the load until the batteries are  depleted  then the UPS will shut down     The UPS will automatically restart and recover output power supply     After the mains power is restored   e The UPS Auto Restart function is enabled     After the Auto Restart is delayed  default  10 minutes   During the Auto Restart delay  the UPS will charge the  battery to provide a safety margin for equipment shutdown if input power fails again     If the Auto Restart function is disabled  you can restart the UPS manually by pressing the FAULT CLEAR button   UPS Reset Procedure    The EPO action or the following reasons such as inverter overtemperature  power off overload  battery overvoltage  and excessive switching may result in the UPS power off  After all appropriate measures have been taken to clear the  faults indicated by the alarm message appearing on the LCD  you can carry out the following s
60. re 3 1  the operation and display panel provides LCD  menu buttons  F1   F4  HELP   LED  indicators  inverter indicator and fault indicator    control buttons  FAULT CLEAR  ON  OFF  ALARM CLEAR  EPO      LCD    Fault indicator    Inverter indicator       Figure 3 1 Operation and display panel    3 1 1 LED Indicators    The LED indicators are composed of inverter indicator and fault indicator  Table 3 1 gives the indicators description     Table 3 1 Description of LED indicators       LED Color State                      Meaning  Steady green Load power is supplied by the inverter  Inverter indicator   Green Blinking green Inverter on  starting up  synchronizing  or standing by  ECO mode   Off Inverter not operating  Blinking red General fault  such as no battery   Fault indicator Red Steady red Serious fault  such as inverter fault   Off No fault                      3 1 2 Audible Alarm  Buzzer     The UPS activity is accompanied with the following two different kinds of audible alarms shown in Table 3 2     Table 3 2 Audible alarm description                   Sound Meaning  One beep every second Sound is generated when the UPS alarm appears  such as AC input failure  Continuous beep Sound is generated when the UPS fault appears  such as fuse or hardware failure            Trust Adapt UPS 20kKVA User Manual    Chapter 3 Operation And Display Panel 25    3 1 3 Control Buttons    The operation and display panel provides five control buttons  which functions are described in Ta
61. s voltage    Battery    Surge protection         Trust Adapt UPS 20kKVA User Manual    6 Chapter 2 Installation    Chapter 2 Installation    This chapter introduces the UPS installation  Each site has its peculiarity  so this chapter provides the guidance with  general installation procedures and methods for the installation engineer  who should conduct the installation  according to the actual conditions     The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this chapter  If any  problem is found  please get in touch with Emerson local service center immediately   Approved by the commissioning engineer  the UPS can be powered on     Special care should be taken into account when installing the battery  When connecting the battery  the voltage of the battery  terminal will exceed 400Vdc hazardous voltage    Eyeshade should be worn to prevent injury from accidental electric arcs   Remove rings  watches and all metal objects   Use tools with insulated handles   Wear rubber gloves   If a battery leaks electrolyte  or is physically damaged  it must be replaced  stored in a container resistant to sulfuric acid and   disposed in accordance with local regulations   If your skin contacts with the electrolyte by accident  wash it immediately with water       2 1 Unpacking Inspection    After the UPS arrival  you should unpack it and check the following items     1  Visually inspect the UPS appearance for transportation damage 
62. sive moisture or overtemperature environment  when  the UPS does not need to be installed immediately  The battery requires dry and low temperature  well ventilated  environment for storage  and the most suitable storage temperature is 20  C   25  C     During the battery storage period  the battery must be periodically charged according to the battery instructions  You can connect  the UPS to the mains temporarily when charging the battery  so as to charge the battery for battery activation        2 3 Installation tools    Prepare installation tools according to Table 2 1  The tools must be insulated and ESD proof processed prior to use     Table 2 1 Installation tools list       Installation tool Specification Application   Remove the protective cover of terminal  block  connect power cables  Wire pressure plier YT 12 Press wires for terminal block   Diagonal plier MTC3C Make cables       Cross screwdriver EJ5100mm                         8 Chapter 2 Installation    2 4 Mechanical Installation    The UPS is suitable for resistive capacitive load  like computer   resistive load and micro inductive load  It is not suitable for purely  inductive load or purely capacitive load  like motor  air conditioner and duplicator   nor can it be connected to half wave rectifier  load        Two installation modes are available  tower installation and rack installation  You can select an appropriate installation  mode according to the actual conditions     According to different configura
63. ss the ON button for 2 seconds  the UPS will run in Battery mode     Transferring Procedures Between Operation Modes    Transferring From Normal Mode To Battery Mode    In the event of mains failure  the UPS will transfer to Battery mode  If you wish to transfer the UPS from Battery mode  to Normal mode  you should wait few seconds for mains input recovery  10 seconds later  the rectifier will restart  automatically  and the inverter will restore the power       Trust Adapt UPS 20kKVA User Manual    Chapter 4 UPS Operation Instructions 33    4 2 2 Transferring From Normal Mode To Bypass Mode    In Normal mode  press the OFF for 2 seconds  you can transfer the UPS to Bypass mode     In Bypass mode  the load accepts the power not from the pure power outputted by the inverter  but from the mains power directly        4 2 3 Transferring From Bypass Mode To Normal Mode    In Bypass mode  press the ON button for 2 seconds  After the inverter runs in normal state  the UPS transfers to  Normal mode     4 2 4 Transferring From Normal Mode To Maintenance Bypass Mode    When the UPS is running in Normal mode  you can use this procedure to make the load transfer from inverter output    2N casion    to maintenance bypass     1  Before performing this procedure  you should check the LED information first  and make sure the bypass is normal and  synchronizes with the inverter  Otherwise  it may result in the load power interruption for a while   2  You should select the single POD options o
64. stem date and time      e      From the    Output    menu  press F3 or F4  left or right arrow  to select the    Settings    menu     Press F5  Enter  to move the cursor to the data window of the LCD       Use F3 and F4  up and down arrows  to select    Date  amp  time    option  then press F5  Enter      2  3  4  Move the cursor to the row in which the date and time are displayed  then press F5  Enter    5  Use F3 or F4  up or down arrows   and enter the current time and date information    6      Press F5  Enter  to confirm  and then press F2  ESC  to return to the    Output    menu     4 9 Controlling Password    The system provides the password protection for the UPS operation control  The default password is    123456     Only  through the password verification can you conduct the UPS and battery test operation     36    5 1    5 2    5 3    5 4    Chapter 5 Maintenance    Chapter 5 Maintenance    This chapter focuses on the UPS maintenance  including the fan maintenance  battery maintenance  UPS cleaning   UPS state check  UPS function check     Fan Maintenance    The UPS fans are expected to run for 20000 hours   40000 hours continuously  The higher the ambient temperature   the shorter the fan life is  During the UPS operation  please verify the fan status once every half year by confirming  that air blows out from the ventilation holes on the rear panel     Battery Maintenance    The internal battery module of the UPS is sealed  lead acid  maintenance free battery  T
65. switches of inverter side is open or short circuit  This fault is locked until power  off       Bypass STS fail    At least one of the static switches of bypass side is open or short circuit  This fault is locked until power  off       Operation invalid    Incorrect operation          Neighbor bypass At least one of the static switches of single bypass side in parallel systemis open or short circuit  This  SSTS fail fault is locked until power off  Output fuse fail At least one inverter output fuse blowou  The inverter shuts down  the load transfers to bypass       Unit over load    The UPS is confirmed to be overload when the load arises above 105  nominal rating  The alarm  automatically resets once the overload condition is removed  1  Confirm that the alarm is true by  checking the load percent indicated on the LCD to determine which phase is being overloaded  2  If the  alarm is true  measure the actual output current to verify that the indications are valid  Disconnect  unnecessary load and ensure the safety        Byp  abnormal  shutdown    Both bypass and inverter voltages unavailable  Load interruption       Inverter over current    Inverter pulse width modulation module overloaded       Bypass phase reverse    The phase sequence direction of bypass voltage is reversed  Normally  the phase of phase B lags 120  degrees behind phase A  and the phase of phase C lags 120 degrees behind phase B    Verify that the phase rotation of the bypass supply presented to the UPS is
66. teps to restore the  UPS to normal operation state    1  Press the FAULT CLEAR button to make the system exit the EPO state    2  Press the ON button for 2s     1  The rectifier restarts  and the bypass supplies power to the load  When the rectifier starts  the fault indicator blinks  When the  rectifier runs in normal operation state  about 30 seconds later   the fault indicator will turn off     2  5 minutes after the overtemperature signal disappears  that is  when the overtemperature fault is eliminated  the rectifier will  automatically start    3  After the EPO button is pressed  if the mains input is disconnected  the UPS will shut down completely  When the mains input is  available  the UPS will start and run in Bypass mode  and also the output is available        Language Selection    The LCD menus are available in two languages  Chinese  English    Procedures for selecting the language    1  From the    Output    menu  press F3 or F4  left or right arrow  to select the    Language    menu   2  Press F5  Enter  to move the cursor to the data window of the LCD    3  Use F3 and F4  up and down arrows  to select the required language     4  Press F5  Enter  to confirm     5  Return to the    Output    menu by repeatedly pressing F2  ESC   At this point  all texts on the LCD will be displayed in  the selected language       Trust Adapt UPS 20kKVA User Manual    Chapter 4 UPS Operation Instructions 35    4 8 Changing Current Date And Time    Procedures for changing the sy
67. the  battery cable from loosing or coming off     e Non selected battery modules    Connect the external battery with terminals             N    and         respectively to    Bat          Bat N    and    Bat    terminals of the  UPS I O terminal block  see Figure 2 7      1  It is prohibited to reverse the positive pole and negative pole of the battery     2  Before replacing the battery module and connecting the battery cables  ensure that the UPS system is in maintenance mode   3  The length of the battery cable option is 1 5m  If you need more length cables  please consult the dealer  It is recommended that  the battery cable be shorter than 3m  Otherwise  the UPS cannot operate normally        2 7 Connecting Communication Cables    Communication cables include  dry contact communication cable  USB communication cable and SNMP card  communication cable     All communication cables are the dual insulation cables which must be separated from the power cables for wiring   When the longest connection distance ranges from 25m to 50m  the CSA should be ranged from 0 5mm  to 1 5mmY     2 7 1 Connecting Dry Contact Communication Cable    The UPS provides five dry contact ports  see Figure 1 2 for specific positions  The silkprints of the five dry contact  ports are 1  2  3  4  5  The pin distribution of each dry contact port is shown in Figure 2 16  and the port description is    shown in Table 2 3     N  K    RD  kip           gt   4  gt  Q 9  A o  gt   gt  Z o o o  t 5    6 2  
68. the UPS  Check the external power if it is found to be faulty  If the utility is likely to trigger this alarm  frequently  the bypass limit can be changed a little larger through the configuration software according to  the user feedback       Inverter asynchronous    This alarm is triggered by an inverter software program when the inverter and bypass waveforms are  misaligned by more than 6 degrees in phase  The amplitude threshold is fixed for  10  rating  This  alarm will recover automatically when the alarm condition disappears    1  First check if the alarm    Bypass Unable To Trace    or    Bypass Protection     If so  solve it first    2  Verify the waveform of the bypass voltage  If it is too distorted  ask the user to verify it and seek any  possible measurement       Inverter fault    Inverter output voltage beyond limits  Load transfers to bypass       Inverter overtemp     The temperature of the inverter heat sink is too high to keep inverter running  This alarm is triggered by  the signal from a temperature monitoring thermostat on the inverter bridge heat sink  The UPS will  recover automatically after 5 minutes delay from the disappearance of the overtemperature signal  If the  overtemperature condition is true  check the following items    1  high ambient temperature  2  blocked cooling airway  3  any fan failure  4  prolonged inverter overload       Fan fault    At least one of the cooling fans has failed       Inverter STS fail    At least one of the static 
69. the current display screen       Trust Adapt UPS 20kKVA User Manual       3 4 Prompt Window    Chapter 3 Operation And Display Panel 29    A prompt window is displayed during the operation of the system to alert you to certain conditions and or to require  your confirmation of a command  The prompts and meanings are given in Table 3 7     Table 3 7 Prompts and meanings       Prompt    Meaning       Transfer with interrupt  confirm or cancel    Inverter and bypass supplies are not synchronized  and any load transfer between  the supplies will cause a brief load interruption       This operation leads to output shutdown   confirm or cancel    The bypass is in abnormal state  inverter shut down will cause the load power off       Turn on more UPS to carry current load    The number of paralleled inverters already turned on is insufficient to carry the  existing load       Battery will be depleted  confirm or cancel    Battery maintenance test discharges the battery 100   This prompt apears to  require your confirmation  Cancelling the test will ends the test and transfers the  UPS to Normal mode       System self test finished  everything is ok    No action required       System self test finished  please check the  current warnings    Check the current alarm message       Enter control password    Required for battery or UPS test       Battery self test condition is low  please  check battery state and load level    Battery test condition is not met  Please check whether the ba
70. tion requirements  the UPS has two configurations  battery modules excluded  and    four battery modules  For tower installation  you should prepare the battery rack and battery cabinet for installing the  battery modules  for rack installation  the battery modules and the UPS can be installed in the same rack together     2 4 1 Tower Installation    1  Assemble a pair of support bases  accessories  and a support base extension  accessory  together through  fastenings  as shown in Figure 2 1   Support base e Al    f    A    L Fastening       Figure 2 1 Connecting the support base with support base extension    2  Repeat step 1 to connect another pair of support bases with a support base extension     3  Place the UPS on the support bases and support base extensions  as shown in Figure 2 2        l Support base    Support base    Figure 2 2 Installation complete    For tower installation  two pairs of support bases should be placed respectively at both sides of the UPS  as shown in Figure 2 2   Otherwise  the UPS may be dumped          Trust Adapt UPS 20kKVA User Manual    Chapter 2 Installation 9    2 4 2 Rack Installation    Installation procedures for battery modules excluded    1  Take out eight M4 10 screws  and fix two brackets  accessories  respectively on both sides of the UPS front panel   as shown in Figure 2 3               f  Bracket  2 pcs           Screw  8 pcs     Figure 2 3 Installing brackets       Moving the UPS through brackets is prohibited     2  Place the
71. ttery is in boost  charge state and the load level is over 20        Forcing charge condition is low  please  check battery state    This prompt appears when you select the forcing charge command while the  forcing charge condition is not met  such as no battery  charger failure        Check the wiring according to the settings   power off takes effect  3 phase  1 phase     After setting the menu option    3 in 3 out 3 in 1 out     you can power off the system  completely  and then power on again after the wiring is changed according to the          output       settings       3 5 UPS Alarm Message List    The following list gives the UPS alarm message list based on the    Current records    and    Historical records    menus in    Table 3 8     Table 3 8 UPS alarm message list       Alarm message    Description       Inverter comm  fail    Internal communication failure between the monitoring board and inverter       Rectifier comm  fail    Internal communication failure between the monitoring board and rectifier       Parallel comm  fail    The CAN communication between different UPSs within a parallel system fails  1 Check if there are  some UPSs not powered on in the parallel system  If so  power on these UPSs and check if the alarm  disappears  2  Press the FAULT CLEAR button       Battery fault    Battery detected faulty  Reserved        Battery replaced    Battery test failed  Battery should be replaced       Before the end of discharge  battery undervoltage pre warnin
72. y panel provides LCD  menu buttons  LED  indicators and control buttons  Refer to Chapter 3 Operation And Display Panel for details     Rear panel    As shown in Figure 1 2  the UPS rear panel provides parallel ports  load bus synchronization  LBS  ports  dry contact  I O port  SNMP card port  USB port  I O terminal block and ventilation holes     Parallel ports LBS ports I O terminal block  with protective cover                  Sm f                                        sual    SNMP card port     5 j      with protective cover                                                                                    eye       Dry contact I O port USB port Ventilation holes    Figure 1 2 UPS rear panel      Trust Adapt UPS 20kKVA User Manual    Chapter 1 Product Introduction 3    1 4 Operating Principle    The operating principle of the UPS is shown in Figure 1 3                                                                                         Bypass ra      1 0 filter  gt Rectifier PFC  gt  Inverter e       Mains y Output  Lo  DC DC charger  Y  L         Battery  GND GND    Figure 1 3 Operating principle    1  The UPS is composed of mains input  I O filter  rectifier PFC  DC DC charger  inverter  bypass  battery and UPS  output     2  When the mains is normal  the rectifier will start  and the DC DC charger will charge the battery string  Before  turning on the UPS  the output voltage is the bypass voltage  After turning on the UPS  the electronic transfer switch  connects t
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
plesk-10-control-panel-user-guide.  Fujitsu CELSIUS W480  Echo 99944230001 User's Manual    Page 1 of 13 - State of New Jersey  StorageTek Host Software Component (HSC)  3次元変位計測システム(ダムシス)  お使いになる前に、付属のソフトウェア使用許諾契約書  OSO 240B MKII operator DMX controller User manual - Bax  Deco Wall Mode d`emploi    Copyright © All rights reserved. 
   Failed to retrieve file