Home
        Recorders: Honeywell MiniQX Specification for
         Contents
1.    2 11 8  2 11 9    2 11 10    2 11 11    Physical Layer standards    2 11 1 1 Ethernet  IEEE 802 3  shall be supported   Protocol Standards   2 11 2 1 TCP IP and FTP shall be supported     Software Utilities shall use Microsoft Dialog Boxes   i e   no command text  strings      2 11 3 1 Alias or DNS  Domain Name Service  names shall identify recorders   IP addressees shall be retained in a    look up    listing     2 11 3 2 A data transfer scheduler shall be provided  The scheduler will initiate  data transfers over the network at predefined times     Multiple Users shall be supported within a networked environment  Each User  shall have access to the archive records     2 11 4 1 A login password utility shall be included  The administrator shall have  the ability to create user profiles with enumerated permissions to  specific functions and data     A network connected user shall have the ability to import copies of the archive  data without impairing the integrity of the original encrypted data     2 11 5 1 The user shall have the ability to view archive data simultaneously  from multiple recorders on the graphic trend analysis tool     2 11 5 2 Each user shall have access to the recorder   s set up and data base  functions using a browser     The recorder shall have the capability to export data to other computer systems     2 11 6 1 A utility that permits automated transfers on a predetermined schedule  shall be provided  FTP shall be supported     2 11 6 2 The schedule
2.    5 44    x 5 44      cutout     Construction  The front bezel shall be made from flame retardant materials  The  recorder case shall be of metal construction     Display  The display shall be no less than 5 5 inches diagonally and utilize  Digital TFT LCD technology  Resolution  320 x 240 pixels    Length  The recorder shall be no more than 205 mm   8 07     in length     Mounting Angle  The instrument shall be mountable at angle up to 65 degrees  upward from horizontal and 40 degrees downward from horizontal with no  impairment on the operation of the storage device     Operator Keys  The recorder shall be equipped with a touch screen interface that  provides easy navigation through the operator displays and menus     Page 1 of 10    2 4 7    2 4 8    2 4 9    A means of rapid menu navigation and selection shall be available to review  historic trend data and system messages  This device shall be intuitive by  design     A means of entering alphanumeric data that is intuitive and does not require any  peripheral equipment shall be included  Unique and spontaneous operator  comments shall be accommodated and integrated with other system messages     Visibility  Critical data should be visible at distances of ten feet  Line thickness  and numeric data should be configurable to accommodate this need where  required  When an alarm is in force  an operator should be alerted by color  change or other posting that would be visible from a distance of ten feet     Electrical connec
3.   will permit the user to time synchronize archive data     Data shall be collected by the recorder and transferred to a PC for analysis using  removable media such as Compact Flash or USB Memory key  Data shall also  be transferable via network connection     The archive analysis software shall provide a utility for the transfer of archive  data in Spreadsheet format  Microsoft Excel 97 or later compatibility is  required  Data types shall include trend data  totalizer data  and event data     The Trend analysis software shall permit the user to build graphs using drag and  drop operating technology  Data trends shall be selected from pick and place  lists     2 12 5 1 The software shall permit any combination of pens from the archive  files     2 12 5 2 The software shall permit selectable scaling of the axes   2 12 5 3 The software shall provide a means of naming each graph   2 12 5 4 Graphs shall be exportable to excel spreadsheets    2 12 5 5 Graphs shall be printable directly for the analysis software     2 12 5 6 The software shall permit the viewing of the trend data in a tabular  format  including value  time and date stamp     Navigation tools shall be provided that enable    find    and    zoom    on the vertical  value axis to magnify the variations of the trend line     Navigation tools shall be provided that enable    find    and    zoom    on the  horizontal time axis to magnify variations  The tool shall permit zooming from  time periods of seconds to minutes 
4.  2 4 RTD  PT100  PT200  PT500  PT1000  100Q Nickel  120Q Nickel   10Q Copper  53Q Copper  Resistance up to 4000 Q    2 5 2 5 Frequency input of 1 Hz to 25 000 Hz  2 5 2 6 Digital Input  Dry contact    2 5 2 7 Alarm Outputs     C Form    relays  NO NC  3 ampere 240VAC rating   minimum     2 5 2 8 Analog outputs capable of re transmitting selected signals shall be 4 20  ma 0 20ma  At least 4 analog outputs shall be available     Auxiliary Power Supply  An isolated 24VDC power supply shall be supplied  for each channel for field transmitter power  200ma max      Page 2 of 10    2 6 Display  amp  Presentation Technology    2 6 1    2 6 2    2 6 10    2 6 11    2 6 12    A custom screen building engineering tool that permits the development of  screens is strongly preferred     Screen creation shall not require vendor firmware or vendor software  engineering  All design and modifications of the screens shall be achieved by  using a graphic building software tool  The software shall be suitable for use by  the end user     A graphic change shall not affect the manufacturer   s firmware revision  Screen  changes shall not require re certification of the recorder     The vender   s authorized representative shall demonstrate upon request  how  these screens can be created and modified  Modification shall not require a  firmware modification by the vendor or a vendor supplied software download   Modification of any screen format shall be achieved at the site with minimal  interruption
5.  made between Enhancements and Maintenance Revisions     2 9 10 1 Enhancements are defined as software revisions that add functionality  or improve product performance  but do not directly affect the safety of  operational integrity of the installed recorder or its associated software     2 9 10 2 Maintenance Revisions are defined as software changes developed to  fix any product flaw or update the software to be compatible with other  software products   Example  Updating the application for a new  version of Windows or a revised communication standard      The vendor shall describe the quality methodology used to develop software     The vendor shall supply all applicable certificates and documents that attest to  level of compliance with any appropriate industrial or professional standards   Independent audits are the most credible     2 10 Communications    2 10 1    The equipment shall be Ethernet  IEEE 802 3  compatible and support TCP IP   2 10 1 1 Physical  10 100 BASE T shall be supported directly from the recorder     2 10 1 2 TCP IP  Transmission Control Protocol  Internet Protocol shall be  supported  IP addresses shall be assigned to each recorder     Page 7 of 10    2 10 1 3 IP resolution  The unit shall accommodate FIXED and DHCP   2 10 1 4 FTP  File transfer Protocol shall be provided     2 10 1 5 Recorders shall be accessible through network routers     2 11 Networking Application Software    2 11 1    2 11 2    2 11 3    2 11 4    2 11 5    2 11 6    2 11 7 
6.  of data acquisition     Screens objects  Each display requires a mix of various display formats or  objects that can be combined to meet the operator   s needs  Color coding of bar  indicators  trend lines  numeric displays  and other graphic elements shall be  fully configurable     Screen Content  All Events that pertain to a pen shall be displayed on the trend  graphs in which the pen is included     Chart displays shall have adjustable chart speeds  Chart speeds of 1 millimeter  per hour to 6 000 millimeters per hour shall be selectable without access to  configuration tools or interruption of data collection     Screen Update  The display shall update a minimum frequency of once per  second     All events shall be posted on an audit trail display with the associated time and  date stamp  This display shall be accessible easily using the touch screen or  keyboard or mouse via the USB port  The event listing shall provide a utility  for scrolling through the listed events     Display screens shall be saved on a removable media for archive purposes  A  utility to save and copy the screen graphics to another recorder shall be  provided     A calibration screen shall be provided  The calibration screen shall include  instructions and intuitive graphics to support calibration procedures  This  screen shall not require a vendor firmware change to adjust the screen to a  specific application     Screen Time Out  The recorder   s display will revert back to a default screen  aft
7.  user   s personal computer  These specifications shall be applied to  software that is used to configure the recorder  and analyze recorder data     All application software shall be supplied directly from the recorder  manufacturer     Application software used for the creation of screens  database building   hardware configuration  logic and math  history analysis shall be classified as  application software     All applications intended for operation on a Personal Computer shall operate  within Window NT version 4 0  service Pack 6 or higher  Windows 2000  or  Windows XP  Proprietary operating systems are not acceptable     Process History files shall be exportable to and compatible with other Microsoft  Windows applications  namely  Microsoft Excel     The software shall support messaging via email  SMTP is acceptable  Microsoft  Outlook is preferred     The vendor shall provide information regarding the revision history of each  software application     The vendor shall provide information on the time that the applications have  been in use by other in process connected applications     Software shall be provided on CD for installation  Downloadable Internet  sources of the application software should be identified     Revision Management  The vendor shall define and propose a methodology for  revision and updates  The vendor shall describe the means of notification for  new revisions  and define the procedure for delivery of software revisions  A  distinction should be
8. 1 Administrator  Users with this level of access have full access  to all areas and functions including the clearing of all  passwords     2 7 6 1 2 Engineer Level  Users with this level of access have full  access to all areas and functions except the clearing of  passwords     2 7 6 1 3 Supervisor level  has access to all areas designated for  Supervisor access and by default shall have access to areas  available to the Technician and Operator levels     2 7 6 1 4Technician  has access to all areas designated for Technician  access and by default shall have access to areas available to  Operator level     2 7 6 1 5 Operator  access to unsecured areas and Alarm  acknowledgement  set point changes  Batch Control and  Recording function based on password access     Secured Areas     2 7 6 2 1 The following areas shall be independently secured  Web  Access  Remote Viewing  Messages  Screen functions  Status   View Totals  View Alarms  View Min Max  Acknowledge  Alarms  Configure Alarms  Batch Control  Recording   Configure Totals  Configure Min Max  Load Save Setups   Main Menu  Setup Menu  Edit Setup  General menu  Printer  set up  Batch Setup  Configure Settings  Configure Layout   screen setup  Pens  General  all   Comms  Comms Modbus   Comms Web  Coms SNTP  Comms Ethernet  Field I O and  Passwords     2 7 6 2 2 Security shall be defined by the Administrator  The  Administrator shall be able to assign a security level to each  area consistent with section 2 7 6 1    2 8 Reco
9. 2  1 3 3    2 7 3 4    2 7 3 5    2 7 3 6    Analog Input Channels  The attributes of each analog input channel  shall be menu selectable  Input type  units  and options  A minimum of  10 characters is required for the tag name     Pens  A data pointer or Pen shall be configurable to include math  expressions  color assignment  and trend line thickness  Alarm limits  shall be configurable  Pens shall also be directly assignable to an  analog Input channel  Each pen shall have an independent scaling  legend  A 20 character tag name shall configurable to the Pen     Logging rate  Each Data point shall be configurable for an independent  logging rate  Rates shall be selectable from various time ranges  The  sample rates shall range from milliseconds  seconds  minutes  hours  to  days     Math  a complete set of mathematical operations shall be configurable  to each pen or data pointer  Math functions to be included are add   multiply  subtract  divide  sine  cosine  tangent  arcsine  arccosine   arctangent  square root  natural logarithm  exponential function   absolute value  parenthetical  and rolling average  100 characters of  math expression shall be provided     The recorder will be capable of supporting a Math Scripting language  that allows the recorder to do logical decisions based on various input  conditions     Events  The recorder shall be capable of causing certain actions to  occur based on various events which are configurable by the users   Causes include Into A
10. Specification for Electronic Data Recorder    1 0 GENERAL SPECIFICATION    An    electronic data recorder    is required  These recorders are also known as    paperless    or    video  recorders     The primary attributes of these recorders are a Color LCD display  electronic data storage  on removable media  and networkable data communications  Data Analysis Software is also required     2 0 SPECIFICATIONS OF ELECTRONIC DATA RECORDER    2 1 Power Specification     2 1 1    2 1 2    The recorder shall be available for use with 90 264VAC  47  63 Hertz  Power  Consumption shall be less than 40 VA     In some applications 24VAC DC or 48VDC shall be required     2 2 Environmental Requirements for Operation    2 2 1  2 2 2  2 2 3  2 2 4  2 2 5    Ambient temperature  0  C to 50  C  32  F to 122  F   Vibration  5 to 100 Hertz  10 meters sec      Shock  1G   Magnetic Field  450 AT M  0  60Hz    Relative Humidity  10  to 90      2 3 Standards and Regulatory Agency Compliance    2 3 1    The recorder shall conform to the following  The vendor shall supply  documentation that demonstrates compliance     2 3 1 1 Safety Standard  EN61010 1 1993   2 3 1 2 Immunity  EN50082 2   2 3 1 3 Emissions  EN5008 1 1   2 3 1 4 Disturbances  EN60555 2 and EN600555 3    2 4 Physical and Mounting Requirements    2 4 1    2 4 2    2 4 3    2 4 4    2 4 5    2 4 6    Bezel and Cutout  The recorder should be standard DIN size bezel  144 mm  X  144 mm   5 67    x 5 67     and shall fit into a 138mm x 138mm
11. be logged  The log shall include  alarm occurrence and alarm clearing     2 7 4 2 3 Manual entries  Operators shall a have a means to enter  comments  A keyboard should not be required  but there must  be a provision to use an external keyboard     2 7 4 2 4 Data Integrity  All data shall be unalterable by any normal  means  Data log files shall be encrypted     2 7 4 2 5 Data Security  Any changes to the Set up files shall be  protected by password  Each password shall be assigned a  level of privilege that authorizes the user for access to specific  recorder functions  The access by an operator to secured  functions shall be logged     2 7 4 2 6Any change to the configuration or set up shall be logged on  the storage media along with the trend and event history     2 7 4 2 7 Operator Notification  A message or icon shall alert the  operator as the data storage status of the data buffer  A  message or graphic that informs the operator of the remaining  capacity is preferred     Recording  Archival Data Structure    2 7 5 1 Stored data shall be recorded as a true archival database  The archived  data shall be stored in a Contiguous File Structure  Data shall not be  segmented into separate files or folders  Transitions for day to day and  hour to hour shall be seamless  Each data record shall be item and date  stamped     Security  Password and Definition of Users    2 7 6 1 Access Levels  A least five levels of access shall be provided     Page 5 of 10    2 7 6 2    2 7 6 1 
12. er a pre set amount of time has transpired without operator activity  The time  out shall be capable of being set for shift type operations  on during the shift but  the screen time out active outside the defined shift hours     2 7 Recorder Software  and Functions    2 7 1    General    2 7 1 1 Once configured  the recorder shall operate as a stand alone data  acquisition device  The operation of the recorder shall not be  dependent on external hardware or software to capture and store data  for the process  The operator shall have full operational access from    Page 3 of 10    2 7 1 2    2 7 1 3    2 7 1 4    ARIS    the recorder   s HMI and or operating devices affixed to the recorder  itself     The recorder shall commence full operation      boot up      in less than  30 seconds     Recovery from Power loss  the recorder shall resume data collection  with 15  20 seconds after a power outage  It should be assumed that no  UPS  Un interruptible Power Supply  will be available     Internal Real Time Clock  The clock shall be accurate to 30 parts per  million or better     The real time clock shall accommodate Daylight Saving Time  No data  shall be lost due to time overlaps or gaps created during clock  changeovers     Operations Technology    2 7 2 1    2 7 2 2    Language  The recorder is to support multiple languages   English   German  and French    Hierarchical Menus with intuitive prompts and selection are preferred     Data Base Configuration    2 7 3 1    24352    
13. larm  Out of Alarm  Start  Stop and Reset  Totalizers Digital Inputs On  Off or Change State and Thermocouple  Burnout  Effects include Chart marking with a defined message  start  and stop totalizing  Start and Stop Logging  output relay activation  and  Alarm Acknowledge     Recording  Data Acquisition    2 7 4 1    Scanning and Sampling Methods    Page 4 of 10    2 7 4 1 1 Scanning and Sampling Rate  Data scanning and sampling  shall be collectable at a rate of 20 milliseconds or 50 hertz for  linear input signals  Data shall be written to the storage media  with a resolution of 20 milliseconds  Each datum shall be  time and date stamped     2 7 4 1 2 Minimum  Maximum Mode  A selection to capture the  minimum and maximum value between logged points shall be  required  The recorder shall capture the highest and the lowest  value detected during the sample interval to a resolution of 20  milliseconds  At the end of the sample interval both values  are logged to the data storage media  The shortest sampling  interval shall be 20 milliseconds     2 7 4 1 3 Average Mode  A selection to collect the average value during  a sampling interval shall be required  In this mode the average  of the sample interval is logged     2 7 4 2 Audit Trail  on recorder     2 7 4 2 1 Events logging  A utility to record all events shall be  provided  Events are to include system messages  operator  actions  alarms  configured events  diagnostic messages  etc     2 7 4 2 2 Alarms  All alarms shall 
14. ly appreciate the  impact and value of each exception     Exceptions to this specification that are not identified will result in disqualification of the  vendor   s bid     Any relevant information or documents that may assist the buyer in evaluating the suitability  of the proposed instrumentation is should be included  Certificates of compliance  site  references  and applications notes may be included     4 0 Buyers Qualification Checklist     4 1    The following is to be completed by the buyers as a critical item checklist  This list addresses  the minimum requirements of the recorder specifications  This checklist is intended to  provide the buyer a means of quickly determining the suitability of the bidder and the  equipment offered           4 2 Ratings  An answer of Yes means that the vendor   s offering fully meets the requirement  An  answer of NO means that the vendor   s offering fails to meet the requirement   4 3 What is the minimum scan rate  20 milliseconds or less  Yes or No  4 4 What is the minimum logging rate  20 milliseconds or less  Yes or No  4 5 Is the recorder qualified for seismic application  Yes or No  4 6 Will the standard product offering require modification to meet the graphic requirement  specified in Section 2 6  Yes or No  4 7 How accurate is the internal clock   30 parts per million   Yes or No  4 8 Does the real time clock accommodate Daylight Savings Time  Yes or No  4 9 Are events integrated with trend data  Yes or No  4 10Can an opera
15. r shall have the ability to define the date  day  time  and  source of the data transfer  Recurring schedules shall be supported     There shall be no limit to the number of recorders that can be connected to a  network  IP addressing shall be the only limiting factor     The data on the Host or Server PC shall be accessible by other client PC   s     Clients PC   s shall have the ability to access a data server over the World Wide  Web or Internet     A complete Audit Trail shall be logged that documents user access and all  system events that may affect the integrity of the data or the system  User  time   date  and event shall be captured in a non cryptic format  Events shall include   all set up changes to the recorders  all data imports and exports  system changes   device additions and deletions  operational setting changes  All information  related to user log ins  passwords  etc  shall be logged in the Audit trail     There shall be a utility that synchronizes the clocks of all recorders within the  networked system     Page 8 of 10    2 11 12    Software Upgrades for the recorders and associated software shall be  downloadable by Internet access     2 12 Analysis Software    2 12 1    2 12 2    2 12 3    2 12 4    2 12 5    2 12 6    2 12 7    2 12 8    2 12 9    2 12 10    Trend analysis software shall be provided that will permit the user to review  archived process data as recorded     The trend analysis viewing software shall provide multiple viewing formats that
16. rder Data Storage    2 8 1    Internal Memory  The recorder shall have a minimum buffer memory of 70  Megabytes  This will be capable of being partitioned between display buffered  data and data for archiving to the media     2 8 1 1    2 8 1 2    The buffer memory shall not require a battery back up to insure data  retention in the event of any power loss     The vendor shall provide information on the archive capacity of the  buffer area of the Internal Memory     Long term Archive Storage    2 8 2 1    2 8 2 2  2 8 2 3    Media  Mass storage media shall be capable of accepting Compact  Flash card up to 2 0 Gigabytes     A redundant storage capability shall be available     Removable media components  The media shall be commercially  available and not unique to the recorder manufacturer  The media shall  not require any special preparation other than routine formatting before  use  Commercially available preformatted media is preferred     Compression algorithms  The vendor shall describe any data compression  algorithms that are available for use to compact data storage  The vendor may    Page 6 of 10    not assume the use of compression algorithms when calculating buffer or  storage capacity as required in sections 2 8 1 and Error  Reference source not  found      2 9 Software Qualification   Personal Computer Development and Analytical Tools     2 9 1    2 9 10    2 9 11  2 9 12    All software referred to in Section 2 5 refers to software that would be installed  in the
17. tions  Termination shall be made from the rear of the recorder   These connections shall be made using quick disconnect terminals  Change out  of a recorder shall not require termination of field wiring     Communications  Ports shall be accessible from the rear of the recorder  EIA   RS485  2 wire  and Ethernet 10 100BASE T shall be included standard on the  product  The Ethernet port shall comply with the IEEE 802 3 standard     2 5 Input  Output Requirements    2 5 1    The recorder shall be supplied with Analog Input circuitry that will resolve the  analog field signals to 16 bits of resolution  The input circuitry should be  configurable to accommodate various signal types on the same card  This type  of input card is often called a Universal Analog Input Card  Up to 16 analog  channels will be required for the relevant applications     2 5 1 1 Note  some applications may require 48 analog inputs  The vendor  shall provide information on other models that can support this  requirement     Signals types   2 5 2 1 Current types  0 20 ma  4 20ma  Accuracy   0 2  full scale or better    2 5 2 2 Voltage types   10mV   50mV   100mV   500mV   1 Volt   6Volts   12Volts   25Volts   50Volts                Accuracy    0 1  full scale or better     2 5 2 3 Thermocouples  K  R  S  B  J  T  E  and N types shall be configurable   Characterization shall be in accord with the International  Thermocouple Tables  Burnout indication is required     Accuracy    0 1  of span or better     2 5
18. to hours using    click and drag    mouse  technology     The graphs shall display actual data sample measurements by displaying dots or  markers on the trend line     Events shall be displayed on the graph with full text descriptions  Events shall  be time linked with the trend data     A utility to add comments to specific times shall be provided  Once a comment  has been added  it shall be an unalterable modification of the graph     2 13 Documentation    2 13 1    2 13 2    2 13 3    A User Manual shall be provided with each recorder that addresses the  operation  configuration  maintenance  and software operation     The configuration shall be retained on removal media such as compact flash or  USB memory key     The recorder will have contextual Help documentation accessible from various  recorder screens     2 14Training and Technical Support    Page 9 of 10    2 14 1 The vendor shall include a description of the services available for operator and  technician training     2 14 2 The vendor shall describe the services available for ongoing technical and  application support     3 0 Bid Documentation    3 1    3 2    3 3    3 4    The vendor shall provide a complete specification and description of his offering  Specific  model numbers and options required to meet this specification shall be included     The vendor shall note by paragraph any deviation from these specifications  A description of  the deviation shall be included  if appropriate  so that the buyer can ful
19. tor enter an original comment into the event log  Yes or No  4 11Can the recorder be secured by multiple password access  Yes or No  4 12Can data be stored to multiple removable media types  Yes or No  4 13Is the archive file structure contiguous   rather than segmented   Yes or No  4 14Does the recorder support Ethernet and TCP IP  Yes or No  4 15Does the recorder support RS485 Modbus  Yes or No  4 16Does the data analysis software export archive files in Microsoft Excel  Yes or No    4 17How many recorders will the network data server software support     4 18How many PC clients will the network data server software support           4 19Does the manufacturer provide telephone application assistance  Yes or No    Page 10 of 10    
    