Home

LabPro User`s Manual - Newmatic Engineering

image

Contents

1. And you can Miscellaneous Supply T hese four fields identify the miscellaneous supply devices that serve this Flow pressurization zone U se an office supply to provide temperature control to an office within the lab pressurization zone O ffice supplies provide conditioned supply air to the office they serve and unconditioned infiltration flow rate into the adjoining main room Use a Constant Volume Room supply to provide additional supply air into the main room Enter a value for the total minimum office supply flow rate entering the room from Flow all office supply sources within this pressurization zone Enter a value for the total maximum office supply flow rate entering the room Flow from all office supply sources within this pressurization zone CV Room Supply Flow Enter a value for the total minimum additional supply flow rate entering the room from constant volume additional supply sources within this pressurization zone 45 LabPro U ser s M anual Table 3 25 Edit Menu Room Add Room Ventilation Information Tab Selections Number of CV Room Enter the number of constant volume supply sources in this room Supply Sources M inimum Ventilation Enter a value for the number of air changes per hour ACH for the room lab Rate Occupied Air during occupied hours Changes per H our ACH Minimum Ventilation This value represents the total flow rate of exhaust air that must leave the room to Rate Oc
2. operator absent fume hoods in the facility then determine how long the occupied hoods are in use during a typical day and select a control approach which enables you to safely downsize mechanical systems Several studies have shown that typical hood usage is about one hour per day LabPro uses data from a study in which actual usage of hundreds of fume hoods were monitored T he results reveal average usage ranges from about one hour per day for a typical research hood to four and five hours for some analytical and process hoods Employing a simulation program which can run thousands of simulations in seconds LabPro can predict the number of fume hoods in the facility that will be occupied at any given time It also predicts average number of fume hoods being used during a typical day By entering the number of fume hoods on a manifold the probability that the users are in front of their hoods example one hour in a ten hour day equals a 10 percent probability and the percent design criteria defined as the design point such that the system requirements are met a given percent of time along with the airflow levels for occupied and unoccupied fume hoods LabPro can determine both design and average airflow requirements for the facility Once LabPro determines the design flow requirements it uses accepted sizing calculations to estimate the size of supply exhaust and central plant equipment After calculating the equipment size LabPro again u
3. Corridor GEX Max Flow e CV UBC Design Flow CV UBC Design Flow Room Other Exhaust Flow Corridor GEX M ax Flow Corridor GEX M ax Flow e VAV UBC Design Flow VAV UBC Design Flow Room Other Exhaust Flow Corridor GEX M ax Flow Corridor GEX M ax Flow So END Calculate Cooling Energy Costs General Equations LabPro uses Simplified Bin W eather D ata Calculations to calculate cooling and heating energy use In the Bin Cooling T ons equations the Flow is dependent on the control system used and the subsequent design and average cfm Since all of the cooling equations are linear the average flow represents a good approximation for the energy use calculations SAT Supply Air Temperature OSAH Outside Air H umidity Gr lb ACF Altitude Correction Factor LCH Leaving Coil H umidity Gr lb 8 1 Outside Air Temperature OSAT Bin Min EE M ax Temperature 1 08 x Hourly Flow x ACF x O SAT m sto x OSAH LCH d 8 2 Bin Cooling Tons 8 2 Bin Cooling T ons 12 000 12 000 8 3 Kwh Bin Cooling Tonsx Annual H oursof O perionx352x y P where cop motos Cost 8 4 Cooling Energy Cost kW h x 8 4 g Energy WR Calculate Heating Energy Costs General Equations 8 5 Bin H eating BTUsper Hour 1 08xFlow x ACF x SAT OSAT Bin H eating BTU s per H our x Annual H ours of O peration 8 6 Bin Heating BTUs 8 6 9 H eating Efficiency Bin H eating BTU sx H eating Fuel Cost per Unit H eating Fu
4. Calculate CV automatic temperature control first costs Eq 10 9 Calculate CV automatic temperature control interface first costs Eq 10 10 Calculate CV lab controls first costs Eq 10 12 Calculate CV PH X lab controls first costs Eq 10 11 Calculate CV balancing costs Eq 10 18 Calculate CV PH X balancing costs Eq 10 17 Calculate CV hood certification costs Eq 10 20 Calculate CV PH X hood certification Eq 10 19 alculate project first costs for each control option Calculate CV PH X cooling system first costs Eq 10 1 Calculate C V PH X heating system first costs Eq 10 2 Calculate CV PH X reheat system first costs Eq 10 3 Calculate CV PH X duct system first costs Eq 10 4 Calculate C V PH X supply air handler first costs Eq 10 5 Calculate C V PH X exhaust fan first costs Eq 10 6 Calculate C V PH X variable frequency drive first costs Eq 10 7 Calculate C V PH X automatic temperature control first costs Eq 10 9 Calculate C V PH X automatic temperature control interface first costs Eq 10 10 Calculate C V PH X lab controls first costs Eq 10 12 Calculate C V PH X lab controls first costs Eq 10 11 Calculate C V PH X balancing costs Eq 10 18 Calculate CV PH X balancing costs Eq 10 17 Calculate C V PH X hood certification costs Eq 10 20 N lt xXS lt CAVIPIODO rrrrrrprrrprprrrrprprrryre YEr es CC aA tco TOZAATrC ATT TOA 7M VO gt AV Appendix A Calculations
5. Backward Incline Fan Vane axial Fans Inlet Vane Control Airfoil Inlet Vane Control Forward Curve Fan Central Plant Cooling Efficiency Enter the cooling efficiency of the central plant air chiller s in kilowatts of power per ton of refrigeration Central Plant H eating Efficiency Enter a value for the thermal efficiency of the central plant heating system asthe ratio expressed as a percentage of total useful heat output versus the total energy input Central Plant Supply Air Cooling Enter the default supply air cooling temperature to be used whenever a Temperature supply air handling unit AH U is added to a project T his value represents the air temperature measured in degrees Fahrenheit or Celsius after the discharge of a cooling coil Central Plant Supply Air H eating Enter the default supply air heating temperature to be used whenever a Temperature supply air handling unit AH U is added to a project T his value represents the air temperature measured in degrees Fahrenheit or Celsius after the discharge of a pre heater coil 15 LabPro U ser s M anual Setup System Defaults Initial Costs You can define default initial costs for H VAC systems and for different types of laboratory air controls N ote that if you change values here you will not affect existing projects Edit Program Default Values x Room E Coridor Gema O Y Fede J Fant Cenal Pleni HVAC Systems Initial Costs Lab
6. Central Plant LabPro U ser s M anual Chapter 2 Getting Started and Using LabPro Getting Started Computer System Requirements The minimum system requirements to run LabPro are 16 MB RAM CD ROM drive Pentium 100 M H z or greater 10 MB of available hard drive space Windows 95 98 2000 ME or NT Setting Up LabPro on a Hard Drive Please take a few minutes before you install LabPro to read the LabPro READ M E TXT file that is on the last installation disk If there are corrections or additions to online help or to the printed manual they will be listed in this file After the installation this file can be read by double clicking the LabPro ReadM eicon in the LabPro active window Running Setup Before running the setup program make sure you have at least 10 M B available on your hard drive to store the program To start Setup from Windows 1 Insert the LabPro CD Press the Start button choose Run from the M enu Press the Browse button Select the I nstall exe file OTe E h3 Follow the Setup instructions on the screen Running LabPro on a Hard Drive LabPro can only berun from your PC s hard drive To run the program select the LabPro icon from within the LabPro Group Backing Up Your LabPro Project Files As you create and develop projects in LabPro you will want to be sure to backup your Ipr files which are the project files onto a floppy disk or in your normal hard drive backup You can either cop
7. Enter the value you want to be the default suction static pressure measured in Exhaust Fan Suction inches of water wc or Pascals Pa This value represents the static pressure Static Pressure measured in the ductwork at the inlet of the exhaust fan Default Attributes Fan Select the default control type for the exhaust fans from the drop down list Control Type Variable Frequency D rive Constant Air Volume Discharge D amper Forward Curve Fan Discharge D amper Backward Incline Fan Vane axial Fans Inlet Vane Control Airfoil Inlet Vane Control Forward Curve Fan EU LabPro U ser s M anual Edit Menu Edit Project Supply Fans Edit Project DEI Main Supply 65 1250 Vane Axial Fan Figure 3 3f Edit Menu Edit Project Supply Fans Tab Right button click in the open area at the right to expose a pop up menu You can choose from these four options Add Supply Fan Edit Supply Fan Copy Supply Fan D elete Supply Fan Table 3 16 Edit Menu Edit Project Supply Fans Tab Selections Default Attributes Fan Enter a number for the default efficiency percentage of the supply fans Efficiency D efault Attributes Enter the value you want to be the default suction static pressure measured in Supply AHU Discharge inches of water wc or Pascals Pa T his value represents the static pressure Static Pressure measured in the ductwork at the outlet of the supply fan D efault Attributes Select t
8. TOoOmmocoosomr Calculate bin CV heating BT Us Eq 8 5 Calculate bin CV heating energy costs Eq 8 7 Select coolest bin to determine CV design heating BTU s Calculate bin CV U BC heating BT U s Eq 8 5 Calculate bin CV U BC heating energy costs Eq 8 7 Select coolest bin to determine CV U BC design heating BTUs Calculate bin VAV heating BT Us Eq 8 5 Calculate bin VAV heating energy costs Eq 8 7 J K L Appendix A Calculations and Equations Select coolest bin to determine VAV design heating BTU s Calculate bin VAV UBC heating BT Us Eq 8 5 Calculate bin VAV UBC heating energy coss Eq 8 7 Select coolest bin to determine VAV design heating BTU s 15 Sum total energy usage and energy costs from each bin to determine energy use and energy cog by control option 16 17 18 Sum cooling energy cost heating energy cost reheat energy cost supply air handler energy cost and exhaust fan energy cost to determine total energy cost for each control option Calculate project first costs by control option A TITIOoOms gt mOoOOoOw Z ET A Calculate CV cooling system first costs Eq 10 1 Calculate CV heating system first costs Eq 10 2 Calculate CV reheat system first costs Eq 10 3 Calculate CV duct system first costs Eq 10 4 Calculate CV supply air handler first costs Eq 10 5 Calculate CV exhaust fan first costs Eq 10 6 Calculate CV variable frequency drive first costs Eq 10 7
9. V AV PH X Lab Controls M aintenance Cost VAV Filter Cost VAV PH X Downtime C osts Annual Other VAV M aintenance Cost 2 Phoenix H ood Certification Cost Phoenix Balance Cost AT C maintenance C ost O ther VAV Lab Controls M aintenance Cost VAV Filter Cost O ther VAV Downtime C osts Annual CV PH X UBC M aintenance Cost Phoenix H ood Certification Cost Phoenix Balance Cost ATC maintenance Cost CV PH X UBC Lab Controls M aintenance Cost CV UBC Filter Cost CV U BC Downtime C osts Annual VAV PH X UBC M aintenance Cost 2 Phoenix H ood Certification Cost Phoenix Balance C ost ATC maintenance Cost V AV PH X UBC Lab Controls M aintenance Cost VAV UBC Filter Cost VAV UBC Downtime Costs 11 15 11 16 11 17 11 18 11 19 Calculate Life Cycle Costs For each Life Cycle Analysis control option e G amp thefirst cost e Getthefirst year energy cost e Get the first year non energy O amp M cost Calculate the total energy costs over the life of the analysis using the inflation rate and number of years that were input on the O perating Costs tab of the main project screen n 12 2 Total Energy Costs First Year Energy Cost Y Energy Cot x 1 Inflation Rate y 2 y Calculate the total non energy operation and maintenance costs over the life of the analysis using the inflation rate and number of years that were input on the O perating Costs tab of the main project screen
10. the analysis period the inflation rate and the hurdle rate are set for the current project in the Financial tab of the Edit Costs menu 69 LabPro U ser s M anual System Flows Exhaust Systems Airflow G raph This graph shows expected occupied and unoccupied exhaust system flows by hour based on project definition Design exhaust airflow for Constant Volume VAV Constant Volume U sage Based Controls CV UBC and Variable Air V olume U sage Based C ontrol VAV UBC controlled systems are shown along with minimum ventilation ACH flows and estimated maximum cooling flows Supply Systems Airflow Graph This graph shows expected occupied and unoccupied exhaust system flows by hour based on project definition Design supply airflow for Constant Volume VAV Constant Volume U sage Based Controls CV UBC and Variable Air Volume U sage Based Control VAV UBC controlled systems are shown along with minimum ventilation ACH flows and estimated maximum cooling flows Central Plants Airflow Graph This graph shows expected occupied and unoccupied exhaust system flows by hour based on project definition Design Central Plant airflow for Constant Volume VAV Constant Volume U sage Based Controls CV UBC and Variable Air Volume U sage Based Control VAV UBC controlled systems are shown along with minimum ventilation ACH flows and estimated maximum cooling flows 70 Appendix A Calculations and Equations Appendix A Ca
11. 11 5 Calculate first year VAV PH X VAV maintenance costs Eq 11 4 Calculate first year AT C maintenance costs Eq 11 1 alculate project first year downtime hours and costs Calculate first year CV downtime hours Eq 11 7 Calculate first year CV PH X downtime hours Eq 11 6 Calculate first year CV U BC downtime hours Eq 11 10 Calculate first year VAV UBC downtime hours Eq 11 11 Calculate first year VAV downtime hour Eq 11 9 Calculate first year V AV PH X downtime hours Eq 11 8 Calculate laboratory first year downtime costs Eq 11 12 alculate project total first year non energy O M costs Calculate total first year CV non energy O amp M costs Eq 11 15 Calculate total first year C V PH X non energy O amp M costs Eq 11 13 Calculate total first year CV UBC non energy O amp M costs Eq 11 18 Calculate total first year VAV UBC non energy O amp M costs Eq 11 19 Calculate total first year VAV non energy O M costs Eq 11 17 Calculate total first year VAV PH X non energy O amp M costs Eq 11 16 alculate project life cycle costs Calculate total energy costs Eq 12 2 Calculate total non energy O M costs Eq 12 3 Calculate total O amp M costs Eq 12 4 Calculate total life cycle costs Eq 12 5 Calculate annual cost of ownership Eq 12 6 Calculate series of periodic cost differences for period of analysis Eq 12 7 12 8 and 12 9 24 Calculate Project in the W hat If M ode
12. Calculate VAV hood flows 1 Calculate VAV occupied hood flow 2 Calculate VAV unoccupied hood flow Calculate CV U BC hood flows 1 Calculate CV U BC occupied hood flow 2 Calculate CV UBC unoccupied hood flow Calculate VAV UBC hood flows 1 Calculate VAV UBC occupied hood flow 2 Calculate VAV UBC unoccupied hood flow Calculate CV horsepower if requested Eq 9 1 5 Calculate individual supply air handler flow A Sum supply air handler room data for associated rooms and corridors 1 Sum individual room and corridor maximum supply flows Eq 5 6 Sum individual room and corridor minimum supply flows Sum individual room and corridor occupied ACH supply flows Eq 5 6 e wU no Sum individual room and corridor unoccupied ACH supply flows Eq 5 6 5 Sum individual room and corridor fume hood demand flows See Labsim methodology 6 Calculate Central Plant flow data A B C Sum exhaust fan room data 1 Sum individual room total exhaust flows Eq 5 1 and 5 2 2 Sum maximum hood and corridor exhaust flows Eq 5 3 3 Sum minimum hood and corridor exhaust flows Eq 5 4 4 Sumroom and corridor ACH flows Eq 5 6 Sum exhaust fan hood data Calculate CV horsepower if requested Eq 9 1 7 Calculate Project T otals A Sum project hood data 1 Sum CV exhaust flows Sum total number of hoods Sum hood maximum flows Sum hood minimum flows Sum CV UBC design flows E Do Uni Appendix A Calculations an
13. Cost per H ood Phoenix Annual Costs VAV VAV UBC M aintenance Cost per H ood Phoenix Annual Costs ATC M aintenance Cost per Room Enter a value for the average cost to re certify a fume hood system within a laboratory space including material and labor costs LabPro will use this value to estimate the annual operating and maintenance cost and initial cost for the complete system LabPro will also use the total entered costs to determine initial costs to install the mechanical system Enter a value for the average cost to re certify a fume hood system with a Phoenix Controls valve installed on the hood including material and labor costs LabPro will use this value to estimate the annual operating and maintenance cost and initial cost for a complete Phoenix C ontrols system LabPro will also use the total entered costs to determine initial costs to install the mechanical system Enter a value for the average cost to maintain a constant volume CV or two state fume hood system within a typical laboratory space Include material and labor costs LabPro will use this value to estimate the annual operating and maintenance cost for the complete system Enter a value for the average cost to maintain a variable air volume VAV fume hood system within a typical laboratory space Be sure to include material and labor costs LabPro will use this value to estimate the annual operating and maintenance cost for the complete system Enter a value f
14. Costs Specify energy HVAC lab and operating costs and define financial analysis information Room D efinethe design parameters for each laboratory including laboratory use supply and exhaust fans the adjacent corridor serving the laboratory the types and quantity of fume hoods and a cooling load profile Also select laboratory attributes i e area air change rate etc Corridor D efinethe design parameters for each corridor including the supply and exhaust fans serving the corridor and a cooling load profile Also select corridor attributes i e area air change rate etc Exhaust Fan D efine the design parameters for each exhaust fan Central Plant D efine the design parameters for each Central Plant including Cooling H eating efficiency and Supply air temperature Analyze Menu Click on Analyze on the menu bar to display the Analyze menu as shown in Figure 2 3 C LabPro Projects project 1 Ipr Analyze Figure 2 3 Analyze Menu The Analyze menu permits you to perform balancing project simulation and cost calculations for the project Project Simulation for a project which includes each of the previously mentioned elements can be performed simply by selecting this one menu item Table 2 3 Analyze Menu Selections Project Simulation Perform balancing simulation and cost calculations for the project W hat If Examine the effect that changes in one or more variables have on up to three diff
15. Data 3 1 Room VolumezRoom AreaxRoom Ceiling H eight 60 3 2 ACH 2 ACH Flow x Room Volume Appendix A Calculations and Equations ACH 60 Room Maximum Cooling Flow W atts per Square Foot or Square M eter x Room Areax 3 413 1 08 x Room T emperature Supply Air Temperature 3 3 ACH Flow Room Volumex 3 4 Room M ax Cooling Flow Room Zone Balance induding Room Supply M aximum Flow Supply M inimum Flow G eneral Exhaust M aximum Flow G eneral Exhaust M inimum Flow Room O ffset Flow Laboratory Zone Balancing Worksheet Instructions Refer to the Laboratory Engineering Guide for instructions on completing a Room Balance W orksheet Calculate Fan System Flow Calculate Maximum and Minimum Constant Volume Exhaust Fan Flows per fan system n m 5 1 Fan M ax Flow Y M aximum Room Flow M aximum Corridor Flow m 1 1 n m 5 2 Fan Min F Minimum Room Flow Y Minimum Corridor Flow m 1 1 Sum all Maximum Hood and Corridor exhaust flows per fan system n m 5 3 Fan Hood Max Flow Y M ax Hood Flow Y M ax Corridor Exhaust Flow m I 1 Sum all Minimum Hood and Corridor exhaust flows per fan system n m 5 4 Fan Hood Min Flow Y M in Hood Flow Y Min Corridor Exhaust Flow m 1 1 Sum all Room and Corridor Total Supply Maximum Flows for each fan system n m 5 5 Max Fan Supply Flow Y Max Room Supply Flow y YM ax Corridor Supply Flow m 1 1 Sum all room and corr
16. Hours Foo Offset Percentage ho Room Name Offset Flow Supply Max Supply Min GEX Max GEX Min Max Exhaust m3 h m3 h m3 h m3 h m3 h m3 h 103 848 76 306 Room 1 1077 Figure 3 3b Edit Menu Edit Project Rooms Tab Right button click in the open area at the bottom to expose a pop up menu You can choose from these four options Add Room Edit Room Copy Room D elete Room Table 3 12 Edit Menu Edit Project Rooms Tab Selections Clickon Andyucm S O Room D efaults Enter a value for the default room temperature set point in degrees Fahrenheit for T emperature Set Point all new rooms Room D efaults Ceiling Enter a valuefor the default ceiling height in feet or meters for all new rooms H eight Room D efaults ACH Enter a value for the default air changes per hour ACH for the building during O ccupied occupied hours Room D efaults ACH Enter a value for the default air changes per hour ACH for the building during U noccupied unoccupied hours Room D efaults H eat Enter a value to be used asthe default maximum watts per square foot or meter Gain W atts Sq Ft or for all new rooms T he watts per square foot or meter value represents the total W atts m maximum heat gain in watts within a room divided by the total floor area of the room in square feet or meters T otal maximum heat gain includes both sensible and latent heat from peo
17. Temperature Controls ATC including material costs and all installation labor HVAC ATC Interface cost per Enter a value for the average cost per room to integrate to the building Unit Flow management system the laboratory controls with the Automatic Temperature Controls AT C including material costs and all installation labor CFM or l s or mh CV laboratory controls including material costs and all installation labor Laboratory Phoenix Constant Enter a value for the average cost per fume hood for Phoenix Controls Volume constant volume laboratory controls including material costs and all CV PHX installation labor D o not include the cost of the Fume H ood or balancing costs Laboratory C onstant Volume Enter a value for the average cost per fume hood for Phoenix C ontrols Usage Based Controls CV U BC Constant Volume U sage Based Controls laboratory controls including material costs and all installation labor D o not include the cost of the Fume H ood or balancing costs Laboratory VAV Enter a value for the average cost per fume hood for traditional VAV VAV laboratory controls including material costs and all installation labor Do not include the cost of the Fume H ood or balancing costs Laboratory Phoenix VAV Enter a value for the average cost per fume hood for Phoenix Controls VAV PH X VAV laboratory controls including material costs and all installation labor D o not include the cost of the F ume H ood or balanci
18. air change rate has the effect of raising both the exhaust and supply air rate which will increase the dilution of contaminants in the air If the ventilation of a space provides for a thorough mixing of the air within the space then six ACH will result in more than 98 4 of the original air being exchanged H andbook of Laboratory Safety Room Offset Room offset is the flow rate of air which enters or leaves the room from to the corridor or adjacent areas W hen the room is under negative pressure the offset is a supply component air flows into the room out of adjacent areas W hen the room is under positive pressure the offset is an exhaust component air flows out of the room into adjacent areas T ypically laboratory rooms are maintained at a negative pressurization with respect to adjacent spaces while non laboratory rooms may be maintained at either a negative or positive pressurization dependent upon their use Offset CFM Calculating room offsets as a percentage of the maximum total room exhaust or room supply for positively pressurized rooms ensures proper pressurization polarity of aroom during normal operating conditions It is prudent to use a percentage at least twice the tolerance of the equipment controlling the room supply and exhaust volumes For example if VAV devices within a room have a tolerance of 5 you should select an offset percentage of not less than 10 In a worst case condition i e the supply
19. and Equations Calculate CV PH X hood certification Eq 10 19 Calculate CV UBC cooling system first costs Eq 10 1 Calculate CV UBC heating system first costs Eq 10 2 Calculate CV U BC reheat system first costs Eq 10 3 Calculate CV U BC duct system first costs Eq 10 4 Calculate CV U BC supply air handler first costs Eq 10 5 Calculate CV U BC exhaust fan first costs Eq 10 6 Calculate CV U BC variable frequency drive first costs Eq 10 7 Calculate CV U BC automatic temperature control first costs Eq 10 9 Calculate CV U BC automatic temperature control interface first costs Eq 10 10 Calculate CV U BC lab controls first costs Eq 10 15 Calculate CV U BC balancing costs Eq 10 17 Calculate CV U BC hood certification costs Eq 10 19 Calculate VAV U BC cooling system first costs Eq 10 1 Calculate VAV U BC heating system first costs Eq 10 2 Calculate VAV U BC reheat system first costs Eq 10 3 Calculate VAV U BC duct system first costs Eq 10 4 Calculate VAV U BC supply air handler first costs Eq 10 5 Calculate VAV U BC exhaust fan first costs Eq 10 6 Calculate VAV U BC variable frequency drive first costs Eq 10 7 Calculate VAV UBC automatic temperature control first costs Eq 10 9 Calculate VAV UBC automatic temperature control interface first costs Eq 10 10 Calculate VAV U BC lab controls first costs Eq 10 16 Calculate VAV UBC balancing costs Eq 10
20. ep af nim co e e Balance Sheet Cancel Figure 3 5c Edit Menu Room Add Room Thermal Information Tab Table 3 26 Edit Menu Edit Project Add Room Thermal Information Tab Selections Clikon Ad ya 0 Thermal Requirements Enter a value for the floor area in square feet or square meters for this room L ud d Tr Temperature Sepoint room Thermal Requirements Enter a value for the default maximum watts per square foot or W atts per square H eat Gain meter for this room T he watts per square foot value represents the total maximum heat gain in watts within a room divided by the total floor area of the room in square feet or meters T otal maximum heat gain includes both sensible and latent heat from people lighting and equipment as well as external heat sources such as sunlight Thermal Requirements Enter a value for the ceiling height area in feet or meters for this room Ceiling H eight 47 LabPro U ser s M anual Table 3 26 Edit Menu Edit Project Add Room Thermal Information Tab Selections And you can Thermal Requirements Select this option and LabPro automatically calculates the flow rate of air required Calculate M aximum to maintain the desired room temperature setpoint based on the watts per square Cooling Flow foot or square meter entered for this room LabPro s default is to enable this option and create a generic profile For a more
21. hood will be occupied T his yields a 90 user absent presence probability Calculations You can access the results of LabPro s calculations in four sections Project Summary LabPro provides the total design and average airflow requirements for different control approaches along with specifying minimum ventilation maximum cooling and minimum heating volumes Reports LabPro can generate the following reports Project D efaults Room D etail Report Room Balance Report FumeH ood Summary Corridor D etail Report Fan Systems Summary System Summary System D iversity Summary System Cost Comparison Financial Analysis N VP IRR Simple Payback and Life C ycle Costs Comparison W eather D ata System D efaults D efault Fume H ood T ypes Graphs and Charts LabPro can generate the following graphs and charts Energy Cost Comparison C hart First Cost Comparison C hart Life C ycle Cost Comparison C hart Exhaust System Flow G raph Supply System Flow G raph Central Plant Flow Graph What If LabPro lets you change the following factors and instantly analyze their airflow diversity and cost impacts on 3 different control strategies e Daily User Present Hours H eat Gain ACH Occupied ACH Unoccupied Fume hood turndown x 1 Sash Position U ser Present Sash Position U ser Absent U BC Hood M ode Standby U BC H ood M ode N ormal D esign Percentile Exhaust Design Percentile Supply Design Percentile
22. project U se any combination of alphanumeric characters to enter the description of the project i e Chemistry Laboratory or Life Sciences Building U se any combination of alphanumeric characters to enter the project s location by city and state T he project location can be different from the customer s location W eather Station U sethe pull down menu to changethe location of your project Cities are listed alphabetically by state If you cannot locate the exact city use the closest geographic location in the table T his will enter the U nited States Climatic Center s Engineering W eather D ata for that location LabPro uses this data in its energy use calculations company name owner s customer s name owner s customer s street address owner s customer s street address 226 LabPro U ser s M anual Table 3 11 Edit Menu Edit Project General Information Tab Selections city and state You can use any combination of alphanumeric characters zip code or postal code phone number Building H ours Enter the normal operating hours for the building T hese are the hours when the majority of the people who use the facility U se the hh mm ss time format i e 8 00 a m to 9 00 p m Usethe a m or p m designation when entering the time If you wish enter the time using 0001 2400 and LabPro will convert the display to the hh mm ss time format automatically T he maximum occupied time for building hours cannot excee
23. the same screens while deleting a room is simpler In addition the Balance Sheet button is located at the bottom of each Edit Add Room screen Clicking this button displays a completed Room Balance Report for the room Edit Menu Room Add Room General Information Tab The Add Room menu item allows you to enter a new room with room specific information as shown in the following 4 T ab screens Edit Room Attributes General Information Wentilation Information Thermal Information Room Name Room 2 Supply AHU an 1 O Exhaust Fan Efan 1 z Corridor Corridor il Default Offset Other Percentage of Total Flow Percentage 10 Positive Pressure Room O Fixed Flow Flow f 70 00 m3 h Percentage of total flow up to Flow Balance Sheet Cancel Figure 3 5a Edit Menu Room Add Room General Information Tab Table 3 24 Edit Menu Room Add Room General Information Tab Selections Room Name Enter the name or number of the room using any combination of alphanumeric Benes cnr en nd a alphanumeric characters Supply AH U Choose the name of the supply air handler that will be associated with this room Exhaust Fan Choose the name of the exhaust fan that will be associated with this room Choose the name of the corridor that will be associated with this room D efault O ffset W hen selected LabPro takes the value entered in the Percentage field and Percentag
24. volume is 5 of set point and the exhaust volume is 596 of set point a room designed for negative pressurization would still maintain a slightly negative state In this example entering an offset percentage of less than 10 could result in a loss of negative pressurization during normal operation Duct Static Pressure Fans are selected based on an analysis of the total system which can be represented by a pressure wc versus flow curve T he system curve is a graphical representation which displays the total net pressure drops for the entire system including the ductwork terminal units and air valve pressure drops with respect to the total airflow passed through the system By plotting both the fan and system characteristic pressure versus flow curves together you can find the condition of operation of the fan and system Because the fan can only perform at conditions on the fan curve and the system can only perform at conditions on the system curve the point of intersection of the system and fan curves is the operating point of the system The generation of the system curve will help ensure that the air valves will have sufficient pressure drop across them in order to function to their specifications User Presence Probability Studies have shown that fume hood occupancy is nearly statistically independent over the time span of occupied building hours Independence of fume hood occupancy allows the use of a statistical tool to calcula
25. well as fuel costs per unit for heating cooling and power N ote that if you change values here you will not affect existing projects Edit Program Default Values Natural Gas mcf E Natural Gas mcf E Figure 3 1i Setup System Defaults Energy Costs Screen Table 3 9 Setup Menu System Defaults Energy Costs Screen Selections Clikon Andyoucans Cooling Fuel From the drop down list select one of the pre defined fuels and their H eating Fuel associated units and BT Us per unit to be used as the heating fuel Select again to designate the reheat fuel You cannot modify the units and BT Us per unit The pre defined list of fuel types and their units of measurement includes Reheat Fuel 2 Fue Oil gal Bituminous Coal Ib Natural Gas m h 2 Fue Oil metricton Bituminous Coal kWh 4 Fuel Oil gal metric ton Propane gal 4 Fuel Oil metricton Electricity kWh Propane metric ton 6 Fue Oil gal Kerosene gal Steam 1 000 Ibs 6 Fue Oil metricton Kerosene metric ton Steam metric ton Anthracite Coal Ib N atural Gas ccf SubBituminous C oal Anthracite Coal metric Natural Gas mcf Ib ton Natural Gas therm SubBituminous C oal metric ton 23 LabPro U ser s M anual Table 3 9 Setup Menu System Defaults Energy Costs Screen Selections Click on Cooling Fue field H eating Fuel Cost per Unit Enter a value for the local
26. 10578 VAV with Variable Frequency D rive VFD Fan Percent H orsepower 99 Y X The minimum 96 flows 25096 for Backward Incline Fan with Discharge D ampers 20 for all other VAV type M inimums kW is 20 of full flow kW for all fan types Drive efficiency is 97 for VFD applications only 1 00 for all others 9 10 Constant Air VolumeFan kW ranti orsapowe x 0 740 Fan Efficiency Fan H orsepower x 0 746 Fan Efficiency xD rive Efficiency 9 11 Variable Air VolumeFan kW 9 12 kWh kW xH ours Appendix A Calculations and Equations Cost 9 13 FanE Cost kW h 9 13 Fan Energy Wh Calculate Mechanical Equipment Initial Costs 10 1 Cooling Plant Equipment Costs D esign Cooling T ons x Cost per Ton 10 2 H eating Plant Euipment C osts D esign unit of flow x H eating System Cost per unit of flow 10 3 Reheat System Euipment Costs D esign unit of flow x Reheat System C ost per unit of flow 10 4 Supply and Exhaust Air D uct Costs D esign unit of flow x D uct Cost per unit of flow 10 5 Supply Air H andler Costs D esign unit of flow x Supply Air H andler Cost per unit of flow 10 6 Exhaust Fan Costs D esign unit of flow x Exhaust Fan Cost per unit of flow 10 7 Variable Frequency D rive Costs D esign H orsepower x VFD Cost per H orsepower 10 8 Filter Costs D esign unit of flow x Filter C ost per unit of flow 10 9 ATC Cost N umber of Rooms N umber of Corridors x ATC Cost per Room 10 10 ATC Interface C os
27. 12 3 Total Non Energy O amp M Costs First Year Non Energy O amp M Cost Y Non Energy O amp M Cos 2 YT y 1 x 1 Inflation Rate 12 4 Total O amp M Costs Total Energy Costs T otal N on Energy O amp M Costs for the Analysis Period A 20 Appendix A Calculations and Equations Calculate the total life cycle cost 12 5 Total Life Cycle Cost Initial System Cost T otal O M Costs for the Analysis Period Calculate the annual cost of ownership O ption T otal Life Cycle Cost Years of Analysis Period 12 6 Annual Cost of O wnership Calculate the series of periodic cost differences for the period of the analysis 12 7 Periodic D ifferenceg O ption Y First Cost Option X First Cost 12 8 Periodic Difference O ption Y First Year O amp M Cost Option X First YearO amp M Cost 12 9 Periodic Difference Periodic Difference x 1 Inflation Rate 12 10 If the First Cost D ifference is less than or equal to 0 the Simple Payback equals 0 O therwise the Simple Payback equals the First Cost D ifference divided by the First Year O amp M Cost Difference Net Present Value and Internal Rate of Return are calculated for the analysis period with the user input analysis period inflation rate and hurdle rate using standard functions T he series of periodic cash flows are from Periodic Difference calculated above A 21 Exhaust Fan Attributes Fan Motor Efficiency Y ou can calculate the value u
28. 17 Calculate VAV U BC hood certification costs Eq 10 19 Calculate VAV cooling system first costs Eq 10 1 Calculate V AV heating system first costs Eq 10 2 Calculate VAV reheat system first costs Eq 10 3 Calculate VAV duct system first costs Eq 10 4 Calculate VAV supply air handler first costs Eq 10 5 Calculate VAV exhaust fan first costs Eq 10 6 Calculate VAV variable frequency drive first costs Eq 10 7 Calculate VAV automatic temperature control first costs Eq 10 9 Calculate VAV automatic temperature control interface first costs Eq 10 10 AW Calculate VAV lab controls first costs Eq 10 14 AX AY AZ BA Calculate VAV PH X lab controls first costs Eq 10 13 Calculate VAV balancing costs Eq 10 18 Calculate VAV PH X balancing costs Eq 10 17 Calculate VAV hood certification costs Eq 10 20 Appendix A Calculations and Equations BB Calculate VAV PH X hood certification Eq 10 19 19 Calculate total system first cost for each control option Eq 10 21 20 Calculate project first year maintenance costs for each control option A 21 22 23 namoovronmoovwvwroonmoowvwroonmoom Calculate first year CV maintenance costs Eq 11 3 Calculate first year C V PH X maintenance costs Eq 11 2 Calculate first year CV U BC maintenance costs Eq 11 2 Calculate first year VAV U BC maintenance costs Eq 11 4 Calculate first year VAV maintenance costs Eq
29. A Recalculate project with user modified W hat If parameters see Calculate Project Appendix A Calculations and Equations Equations General Equations 1 1 Barometric Pressure 2 0000068745x Altitude 2559 x14 696x 2 036 Barometric Pressure 1 2 Altit tion Factor 1 2 itude Correction Factor 29921 Corridor Data Calculations Corridor Air Changes per Hour ACH Data 2 1 Corridor Volume C orridor AreaxCorridor Ceiling H eight 60 Corridor Volume ACH 60 Corridor Maximum Cooling Flow W atts per Square Foot x Corridor Areax 3 413 1 08x Corridor T emperature Supply Air T emperature 2 2 ACH 2 ACH Flowx 2 3 ACH Flow Corridor Volumex 2 4 Corridor M ax Cooling Flow Corridor Offset Flow n 2 5 Corridor O ffset Flow Y Room O ffset Flow for each corridor 1 Corridor Supply Maximum Flow 2 6 Maximum value of Corridor ACH Flow Corridor maximum cooling Flow Corridor Room O ffset Flow Corridor Supply Valve Minimum Flow 2 7 Lookup based on Corridor Supply M aximum Corridor Supply Minimum Flow 2 8 M aximum value of Corridor ACH Flow Corridor Room O ffset Flow Corridor Exhaust Maximum Flow 2 9 Corridor Supply M aximum Flow Corridor Room O ffset Flow Corridor Exhaust Valve Minimum Flow 2 10 Lookup based on Corridor Exhaust M aximum Flow Corridor Exhaust Minimum Flow 2 11 Corridor Supply M inimum Flow Corridor Room O ffset Flow Room Data Calculations ACH
30. Automatic T emperature C ontrols ATC including material costs and all installation labor ATC Interface Cost per Enter a value for the average cost per room to integrate the laboratory controls Room with the Automatic Temperature Controls AT C including material costs and all installation labor Filter Cost per U nit Flow Enter a value for the average cost for Air Filter replacement per CFM or l s or m h 38 LabPro U ser s M anual Lab Controls im Edit Costs al ES Operating Lab Controls Initial Costs per Hood Unit JPY Constant Volume CV E 80 000 00 JPY Phoenix Controls Constant Volume CW PHx 240 000 oo JPY Adaptive Constant Volume CW UBC 480 000 00 JPY VAV VAV 660 000 00 JPY Phoenix VAV VAV PHX 660 000 00 JPY Adaptive Face Velocity VAW UBC 720 000 00 JPY NOTE All costs include Material and Installation Labor coca Figure 3 4e Edit Costs Lab Controls Tab Table 3 21 Edit Costs Lab Controls Tab Selections laboratory controls including material costs and all installation labor Phoenix Controls Constant Enter a value for the average cost per fume hood for Phoenix Controls Volume CV PH X constant volume laboratory controls including material costs and all installation labor D o not include the cost of the Fume H ood or balancing costs Adaptive Constant Volume CV Enter a value for the average cost per fume hood for Phoenix Controls UBC Adaptiv
31. C Room Hood Flow CV UBC H ood Flow e VAV UBC Room H ood Flow VAV UBC Room Hood Flow VAV UBC H ood Flow Calculate T otal Room Exhaust Flow Appendix A Calculations and Equations e VAV Total Room Demand M ax2 VAV Total Room Exhaust Flow Limit T erm e CV UBC Total Room Demand M ax2 CV UBC Total Room Exhaust Flow Limit T erm e VAV UBC Total Room Demand M ax2 VAV UBC Total Room Exhaust Flow Limit T erm 4 Place value in temp hold variable corresponding to appropriate manifold 5 Repeat number 8 13 for each room 6 Add Total Room Exhaust to Design Flow e VAV Design Flow VAV Design Flow VAV Total Room Exhaust e CV UBC Design Flow CV UBC Design Flow CV UBC Total Room Exhaust e VAV UBC Design Flow VAV UBC Design Flow VAV UBC Total Room Exhaust 7 When complete with all room add 1 to the M anifold Bin that corresponds to the D esign Flow If VAV CV UBC or VAV UBC then loop through process 10 000 times and stop 9 When complete select the design percentile Flow that corresponds to the bin that equals the design percentile Complete for each bin If the design percentile is greater than the previous run then T ransfer each manifold bin and design percentile to access database 10 Else process to number 1 if you are running process of multiple profile hours or end subroutine 11 Add each corridor GEX M ax Flow and Room O ther Exhaust Flow to Design Flow e VAV Design Flow VAV Design Flow CV Room Other Exhaust Flow Corridor GEX M ax Flow
32. Comparison Choose Energy Cost Comparison First C ost CR Compete lec omarion chats Choose Exhaust System Flow Supply System Flow or Central Plant Flow graphs Setup Menu Click on Setup on the menu bar to display the Setup menu as shown in Figure 2 6 C LabPro Projects project 1 Ipr Figure 2 6 Setup Menu Table 2 6 Setup Menu Selections Click on System D efaults D efine standard building equipment usage and costs in an Edit Program D efault V alues screen Units Setup Select national currency and English or M eric units of measurement LabPro U ser s M anual Windows Menu Click on Windows on the menu bar to display the Windows menu as shown in Figure 2 7 C LabPro Projects project 1 Ipr Windows Figure 2 7 Windows Menu Table 2 7 Windows Menu Selections Help Menu Click on H elp on the menu bar to display the H elp menu as shown in Figure 2 8 C LabPro Projects project 1 Ipr Help Figure 2 8 Help Menu Table 2 8 Help Menu Selections View the main table of contents for H elp on LabPro inde Serch for any word in the H dp file About D isplay the current version number of this software and the software agreement In addition pressing the F1 key within any field within LabPro will bring you into the H elp topic for that field 10 LabPro U ser s M anual Chapter 3 Explanations of Inputs Introduction T his chapter pre
33. Copy Supply menu item allows you to copy a previously created supply fan Delete Supply Fan TheD elete Supply Fan menu item allows you to delete a supply fan 58 LabPro U ser s M anual Edit Central Plant Add Central Plant Screen m Edit Central Plant Figure 3 9 Edit Menu Central Plant Add Central Plant Screen Table 3 33 Edit Menu Central Plant Add Central Plant Screen Selections General Information N ame Enter a unique name as the unique central plant identifier in this field If you use a number in a central plant s name such as CP 1 and you have more than ten central plants use a leading 0 before the single digits i e CP 01 instead of CP 1 so that the supply fans will remain sequentially listed i e CP 02 will come before CP 10 Area fans that the central plant serves plant in kilowatts of power per ton of refrigeration Attributes H eating Efficiency Enter a value for the thermal efficiency of the complete central plant heating system as the ratio expressed as a percentage of total useful heat output versus the total energy input Attributes Supply Air Cooling Enter the value you want to be the default supply air temperature T his Temperature value represents the air temperature measured in degrees Fahrenheit or Celsius after the discharge of a preheater or cooling coil Attributes Supply Air H eating Enter the value you want to be the default supply air temperatur
34. EXDOR ui E ERR 66 LOU 66 COMPARISON TAB crucero ala 66 LabPro U ser s M anual Control Types drop down box e edt gere tee d ec deed en eee ite 67 System Comparison 4 ei ee siet depre dei RV d ege eei Ri RR pre du aaa El uia 67 CHAPTER 5 REPORTS AND GRAPHS eeeeeeeeee eene entente tata sins tn tns tn stata sons ta sn sins ta tns en statu sno 68 REPORTS amp cre UU elus ene nid ensuite ede Rd 68 Project Summary ie Eae ee E P E pete viet A 68 Project Defaults ise ot o ar aO Re aee p e e da pan Sed UR ca dna E Ue 68 Room Balance Report RU EAS E EL Rae sda 68 Room Detail Report tn NI e 68 Fume Hood Summary ii dise di tee esee o eer ee eee e eet den 68 Corridor Detail Report eerte e EP REFUS SR Ea via ep 68 Fan Systems SUMMA octo ta tp Eee et ER RE Eee fers 68 System Summ ty NN 68 System Diversity Comparison esses nennen nette tene tene trente entren trennen rennen nenne enne 68 System Cost Comp Fis H A NN 69 Financial Analysis COMPATIS ON 5 ses dt do pets ee es a eas Is OM eas EE 69 System Default id exce safa de aie 69 Weather Data Bin Weather Data esses eene enne enne entere nennen nennen enne 69 Default Fume Hood Type egere dr Er aso oe SE oie pee et spa iaa 69 GRAPHS CHARTS rosada 69 COMPATISON COS S EH 69 System Flo WS AAA A AA 70 LabPro U ser s M anual Vi LabPro U ser s M anual Chapter 1 Introducti
35. Eq 8 2 Calculate bin CV UBC cooling BT Us cooling tons x 12 000 BTU cooling ton Calculate bin CV U BC cooling energy costs Eq 8 4 Select hottest bin to determine CV U BC design cooling tonnage Calculate bin VAV U BC cooling tons Eq 8 2 Calculate bin VAV UBC cooling BT Us cooling tons x 12 000 BTU cooling ton Calculate bin VAV U BC cooling energy costs Eq 8 4 Select hottest bin to determine VAV U BC design cooling tonnage Calculate bin VAV cooling tons Eq 8 2 Calculate bin VAV cooling BT Us cooling tons x 12 000 BT U cooling ton Calculate bin VAV cooling energy costs Eq 8 4 Select hottest bin to determine VAV design cooling tonnage Calculate project reheat energy costs for each bin and control option TITIosmonow gt A L Calculate bin CV heating BTUs Eq 8 8 Calculate bin CV heating energy costs Eq 8 10 Select coolest bin to determine CV design heating BTU s Calculate bin CV UBC heating BT Us Eq 8 8 Calculate bin CV UBC heating energy costs Eq 8 10 Select coolest bin to determine CV UBC design heating BTUs Calculate bin VAV heating BTUs Eq 8 8 Calculate bin VAV heating energy costs Eq 8 10 Select coolest bin to determine VAV design heating BTU s Calculate bin VAV UBC heating BT Us Eq 8 8 Calculate bin VAV UBC heating energy costs Eq 8 10 Select coolest bin to determine VAV design heating BT U s Calculate project heating energy coss for each bin and control option
36. H Flow M aximum Cooling Flow M inimum H ood Flow Calculate hourly kW for each fan system by control option A Calculate CV exhaust fan hourly kW Eq 9 10 Calculate CV U BC exhaust fan hourly kW Eq 9 11 Calculate VAV U BC exhaust fan hourly kW Eq 9 11 Calculate VAV exhaust fan hourly kW Eq 9 11 Calculate CV supply fan hourly kW Eq 9 10 Calculate CV U BC supply fan hourly kW Eq 9 11 Calculate VAV U BC supply fan hourly kW Eq 9 11 H Calculate VAV supply fan hourly kW Eq 9 11 Calculate hourly design and average reheat BT U s by control option Calculate CV hourly design reheat BT U s Eq 8 8 Calculate CV UBC hourly design reheat BT U s Eq 8 8 Calculate VAV UBC hourly design reheat BT Us Eq 8 8 Calculate VAV hourly design reheat BT U s Eq 8 8 Calculate CV hourly average reheat BT Us Eq 8 8 Calculate CV UBC hourly average reheat BT Us Eq 8 8 Calculate VAV U BC hourly average reheat BT U s Eq 8 8 Calculate VAV hourly average reheat BT U s Eq 8 8 oO mm gogo o TOoOmmocooomr Appendix A Calculations and Equations 12 Calculate project cooling energy costs for each bin and control option 13 14 A cC c ommgcoosstu vozzr7a Calculate bin CV cooling tons Eq 8 2 Calculate bin CV cooling BT Us cooling tons x 12 000 BT U cooling ton Calculate bin CV cooling energy costs Eq 8 4 Select hottest bin to determine CV design cooling tonnage Calculate bin CV U BC cooling tons
37. Maintenance Cost per Room 11 2 Phoenix CV M aintenance Cost N umber of H oodsx Phoenix CV M aintenance Cost per H ood 11 3 Other CV Maintenance Cost N umber of H oodsx Other CV Maintenance Cost per H ood 11 4 Phoenix VAV M aintenance Cost N umber of H oodsx Phoenix VAV M aintenance Cost per H ood Appendix A Calculations and Equations 11 5 Other VAV Maintenance Cost N umber of H oods x Other VAV Maintenance Cost per H ood 11 6 CV PH X DowntimeH ours CV PH X Maintenance Cost 100 11 7 Other CV Downtime H ours O ther CV M aintenance Cost 100 11 8 VAV PH X Downtime H ours VAV PH X M aintenance Cost 100 11 9 Other VAV DowntimeH ours O ther VAV M aintenance Cost 100 11 10 CV PH X UBC DowntimeH ours 2 CV PH X UBC M aintenance Cost 100 11 11 VAV PH X UBC Downtime H ours VAV PH X UBC Maintenance Cost 100 11 12 Laboratory D owntime Costs N umber of H ours of M aintenancex D owntime Cost per H our 11 13 CV PH X Maintenance Cost 2 Phoenix H ood Certification Cost Phoenix Balance Cost ATC maintenance C ost C V PH X Lab Controls M aintenance Cost CV Filter Cost CV PH X Downtime Costs Annual Other CV M aintenance Cost O ther H ood Certification Cost O ther Balance Cost ATC maintenance C ost O ther CV Lab Controls M aintenance Cost CV Filter Cost O ther CV Downtime C osts Annual VAV PH X M aintenance Cost Phoenix H ood Certification Cost Phoenix Balance Cost AT C maintenance C ost
38. NERAL The export of the Software from the United States and re export from any other country is governed by the U S Department of Commerce under the export control laws and regulations of the United States and by any applicable law of such other country and the Software shall not be exported or re exported in violation of any such laws or regulations This Agreement is the complete and exclusive statement of the agreement between you and Phoenix and supersedes any proposal or prior agreement oral or written and any other communications relating to the subject matter of this Agreement This Agreement shall be governed by and interpreted under the laws of the Commonwealth of Massachusetts United States of America without regard to conflicts of law provisions however if you acquired the Software outside the United States local law may override this sentence and apply instead Should you have any questions about this Agreement or Phoenix s software use policies or if you desire to contact Phoenix for any other reason please write to Customer Service Phoenix Controls Corporation 75 Discovery Way Acton MA 01720 or call 1 800 474 9832 LabPro User s M anual CHAPTER 1 INTRODUCTION sitsssscsseshcocsstavsasdscestossonsattdestsvtost seastocastevsassensstaeesedntesaassspoedsdastescesssaeensneess 1 INTRODUCTION TOSEABPRO cds WHAT LABPRO Si taa WHAT S IN THIS DOCUMENT csscescccocessenscouccesceseensneuecseceseenscauecsecesesnsnauecsecsce
39. Phoenix Controls L a b P r o Airflow System Modeling Software EXPERIENCE A YE A DRAMATICALLY TN As Version 1 2 DIFFERENT Vision This product is licensed to User s Manual LabPro U ser s M anual PHOENIX SOFTWARE AGREEMENT This is a legal agreement between you and Phoenix Controls Corporation Phoenix Read this Agreement carefully before you open the package containing the diskettes By opening the installing the software you agree that you have read and understand this Agreement and will be bound by its terms and conditions If you do not agree with these terms and conditions return the CD package to your supplier within 30 days Software and Version Phoenix LabPro Version 1 2 Number of Licenses 1 Notice Software is inherently complex and may contain errors Various defaults are set in LabPro which may not be appropriate for any particular design circumstance and you should independently determine in each use of LabPro that appropriate values are set as the defaults You should verify your work and the results produced by this or any other software Under no circumstances should you base design decisions on the results generated by LabPro without verification of such results by other methods including the independent exercise of your professional judgment Phoenix controls corporation does not guaranty the data or results produced by the LabPro software and shall have no liabilit
40. Room Occupied Exhaust Flow VAV UBC H ood Occupied Flow Room Other Exhaust Flow 9 Calculate Room U noccupied Exhaust Flow CV Room U noccupied Exhaust Flow CV H ood U noccupiedFlow CV Room Other Exhaust Flow VAV Room U noccupied Exhaust Flow VAV H ood U noccupied Flow Room Other Exhaust Flow CV UBC Room Unoccupied Exhaust Flow 2 CV UBC Hood Unoccupied Flow Room Other Exhaust Flow VAV UBC Room U noccupied Exhaust Flow VAV UBC H ood U noccupied Flow Room Other Exhaust Flow Begin Loop 1 Calculate Average Flow for each hour in flow grid Setting the vent demand equal to corresponding occupied or unoccupied value and the M ax Cooling Flow equal to the corresponding hour in the room profile store resultsin Room T able Calculate V entilation Demand Flow If Room is N egative T hen O ccupied V ent D emand Flow 2ACH O ccupied Flow U noccupied V ent D emand Flow 2ACH U noccupied Flow Else O ccupied V ent Demand Flow 2 ACH Occupied Flow 0 ffset U noccupied V ent Demand Flow 2ACH U noccupied Flow 0 ffset Calculate Supply M inimum Flow gt CV Supply M in Flow 2 CV Supply VAV Supply Valve M in 0 ffset Additional Supply Valve M ax Office Supply Valve M ax Supply M in Flow CV Supply VAV Supply Valve M in 0 ffset Additional Supply Valve M ax Office Supply V alve M ax Calculate M ax Cooling D emand Flow CV Max Cooling Demand Flow M ax Cooling Flow 0 ffset 0 ffice Supply Valve M ax Additional S
41. UP SYSTEM DEFAULTS INITIAL COSTS ccsessccecececsessaececececsesseaececececeensnaecesececseseaaeaeeeeseseneneaeees 16 SETUP SYSTEM DEFAULTS OPERATING COSTS ccs cccccecsesesssceeececseseuececcesceeneaeseceeeeeesensaaeeeeeeeesenssaeees 18 SETUP SYSTEM DEFAULTS FUME HOODS ccccococononnnonccnnonononononccnonannonnnnncononnnnnnnnnncononnnnnnnnoncnnonnanananonos 20 SETUP SYSTEM DEFAULTS ROOM AND CORRIDOR cccccccocononnnononccnnnnnnnnononccnononnnonnncnnonnnnononnncononann conoces 21 LabPro U ser s M anual SETUP SYSTEM DEFAULTS ENERGY COSTS ccssccesscessseceseceesseceseeeenaeceeeeecsaeceeeecaeceeeecsaeceeneeenaeeeeee 23 SETUP UNITS SETUP SCREEN 4 34 scccdscsecesnncsdebeatescevetocsdensdavdecueddsesdvoaoshcen absnectdencdevacv oeu loses erbe dette venies 25 EDIT MENU EDIT PROJECT GENERAL INFORMATION TAB ce ccescesseeesceeceseceseesecnaecaeecneeeneeeneeeeeenees 26 EDIT MENU EDIT PROJECT ROOMS TAB esses eene ennt enne nter nent nennen trennen 28 EDIT MENU EDIT PROJECT CORRIDORS essere enne entente sre ne sienne tese 30 EDIT MENU EDIT PROJECT CENTRAL PLANTS esses eene enn enne enne nen rennen ne nnns ne nere serene 31 EDIT MENU EDIT PROJECT EXHAUST FANS ccccesssesssecssseeesceceseeesseecsaeceseeecaeseeeeecueceeseecaeseeseeesseenees 32 EDIT MENU EDIT PROJECT SUPPLY FANS sccsseesseesceeseeeseeeceseee
42. VAV UBC Constant Volume Variable Air Volume Phoenix Controls Variable Air Volume Phoenix Controls Constant Volume U sage Based C ontrols Phoenix Controls Variable Air Volume U sage Based Control Asthe control types are selected the relevant airflow and cost data are displayed for each type System Comparison Entry Is used to D esign Airflow Flow Calculate the system design exhaust flow for this project LabPro sumsthe system design exhaust flow for all the rooms and corridors in the project Average Flow Calculate the system average exhaust flow for this project LabPro sums the System average exhaust flow based on 24 hours for all the rooms and corridors in the project D esign D iversity Show the ratio of Design flow to the CV flow Average D iversity Display the ratio of Average flow i e 50 D esign flow to the CV flow M echanical System Initial Cost Calculate a summary cost of all mechanical costs associated with the air handling systems LabPro sums the variables entered under the First Costs tab Lab Controls Initial Cost Calculate a summary cost of all laboratory controls LabPro calculates the value from the variables entered under the First Costs tab T hese costs include the hood controls the room controls and the supply and exhaust airflow devices for both the room and the lab equipment Total Initial System C ost Calculate the total initial cost for the proj
43. air chiller s in kilowatts of power Cooling Efficiency per ton of refrigeration D efault Attributes Enter the heating efficiency of the central plant heating system as the ratio H eating Efficiency expressed as a percentage of total useful heat output versus the total energy input Supply Air Cooling Enter a value for the default supply air temperature whenever you add a supply air Temperature handling unit AH U to a project T his value represents the air temperature measured in degrees Fahrenheit or Celsius after the discharge of a pre heater or cooling coil Supply Air H eating Enter a value for the default supply air temperature whenever you add a supply air Temperature handling unit AH U to a project T his value represents the air tenperature measured in degrees Fahrenheit or Celsius after the discharge of a pre heater or cooling coil 31 LabPro U ser s M anual Edit Menu Edit Project Exhaust Fans at Edit Project Figure 3 3e Edit Menu Edit Project Exhaust Fans Tab Right button click in the open area at the right to expose a pop up menu You can choose from these four options Add Exhaust Fan Edit Exhaust Fan Copy Exhaust Fan D elete Exhaust Fan Table 3 15 Edit Menu Edit Project Exhaust Fans Tab Selections Clickon Andyucm Default Attributes Fan Enter a number for the default efficiency percentage of the exhaust fan Efficiency D efault Attributes
44. al supply system Total Central Plants 5 1989 1988 198 139 199 15389 Ss ima 1398 1718 138 1715 189889 17i8 138 G 17i8 amp 0 1388 178 198 azia 188 MALA 1716 HERES NRI PERE CI a AA Suis TO 2S eum auae 125400 107010700 IEEE SONS As 45055 Figure 4 2 Analyze Menu Simulate Project Project Summary Screen Table 4 1 Analyze M enu Full Calculation Project Summary Screen Entry Total Numbers N umber of Rooms Total N umbers N umber of Exhaust Fans Total N umbers N umber of Fume H oods Total Numbers N umber of Supply AH Us Total N umbers N umber of Central Plants Flow hoods simultaneously System Flows Minimum Fume H ood Flow hoods simultaneously exchange rate to provide maximum cooling 62 LabPro U ser s M anual Table 4 1 Analyze M enu Full Calculation Project Summary Screen System Flows T otal O ccupied Ventilation Display the exhaust flow required to provide the necessary air System Flows T otal U noccupied Display the exhaust flow required to provide the necessary air VAV CVUBC VAV UBC flow and corresponding energy calculations can be performed VAV CVUBC VAV UBC while remaining at the designers specified confidence level System Costs You can print a detailed cost comparison to view individual costs per item see Chapter 5 R eports C harts for more information The system costs are displayed in a gr
45. and reheat requirements the specified percent of time Each central plant system that you define will use this factor Building H ours Enter the normal operating hours for the building U se the hh mm ss a m p m time From format e g 8 00 a m to 9 00 p m If you wish enter the time using 0001 2400 and and LabPro will convert the display to the hh mm ss time format automatically The Building H ours maximum occupied time for building hours cannot exceed 23 hours 59 minutes To 12 LabPro U ser s M anual Setup System Defaults Hood Usage You can define the default fume hood mode and sash positions N ote that if you change values here you will not affect existing projects Edit Program Default Values Figure 3 1b Setup System Defaults Hood Usage Screen Table 3 3 Setup Menu System Defaults Screen Hood Usage Selections Clikon Andyoucans SO M ode Flow operating in N ormal mode M ode Flow operating in Standby mode Sash Position U ser Present Enter a value that you want to be the default sash position when a user is present at a fume hood LabPro will automatically fill the U ser Present field with this number whenever you add a new fume hood to the project Sash Position U ser Absent Enter a value that you want to be the default sash position when a user is absent from a fume hood LabPro will automatically fill the U ser Absent field with this number whenever you add a new fume hoo
46. ations and Equations e VAV Average Flow VAV Average Flow N umber of trials e CV UBC Average Flow CV UBC Average Flow N umber of trials e VAV UBC Average Flow VAV UBC Average Flow N umber of trials l Set Average Flow equal to corresponding Bin H our Flow Complete Flow Grid for each H our Go back to number 10 Begin Loop End of loop Calculate Project Totals Subroutine 1 10 11 If all Standard Cooling Profile boxes are checked then Thermal Demand Sum of M ax Cooling for each room on manifold Complete for each manifold Else Compare each room profile If M ax hour is equal for all Rooms then Thermal Demand 2 Sum of M ac Cooling for each room on manifold Complete for each manifold Else Run complete subroutine for each occupied hour each time calculating T hermal D emand Thermal Demand 2 Sum of M ac Cooling for each occupied hour for each room on manifold Complete for each manifold Calculate Cooling D emand for each exhaust supply and temperature control manifold e Cooling Demand Flow M ax Thermal D emand Flow 0 ffset 0 ffice Supply Valve M ax Additional Calculate Limit T erm of each manifold e CV Limit Term M ax3 0 ccupied V ent Demand Cooling D emand Flow CV Supply M in Flow e Limit Term M ax3 0 ccupied Vent D emand Cooling Demand Flow Supply M in Flow e Places valuesin room table M erge hood and room tables and transfer data to C DLL Creating temporary holding values for each exhaust supply and temp c
47. aximum flows Sum hood minimum flows Sum CV UBC design flows Sum VAV design flows Sum VAV UBC design flows Sum CV UBC average flows E oq ck Sum VAV average flows ta o Sum VAV UBC average flows Sum CV UBC unoccupied flows Sum VAV unoccupied flows 13 Sum VAV UBC unoccupied flows F Sum project central plant data ta pp N FP Sum central plant CV flows Sum total number of hoods Sum hood maximum flows Sum hood minimum flows Sum CV UBC design flows Sum VAV design flows Sum VAV UBC design flows Sum CV UBC average flows 9 00 rn O MM Pw m a Sum VAV UBC average flows mn e Sum VAV average flows Sum CV UBC unoccupied flows Sum VAV unoccupied flows 13 Sum VAV UBC unoccupied flows ta pp N FP Appendix A Calculations and Equations 8 Construct flow grid T he flow grid is an hour by hour comparison of project flows that were obtained in the previous calculations For each hour LabPro will insert the following values e CV exhaust flow e Minimum supply system heatin e CV UBC supply system average flow hood flow e CV supply flow e Minimum central plant heating e CV UBC supply system unoccu flow hood flow e CV central plant flow e VAV exhaust system design hoc CV UBC central plant design h flow flow e Occupied ACH flow e VAV exhaust system average ho e CV UBC central plant average flow hood flow 9 10 11 Appendix A Calculations and Equations e Unoccupied ACH flow e VAV exhaust syst
48. ck on the Calculate button LabPro will display the results on the C omparison tab Represents what percentage of the hood exhaust design flow will be when an operator is present at the hood Enter a new value in this field and click on the Calculate button LabPro will display the results on the C omparison tab Represents what percentage of the hood exhaust design flow will be when an operator is absent from the hood Enter a new valuein this field and click on the Calculate button LabPro will display the results on the C omparison tab Represents what percentage of the worst case design the exhaust system has been designed to T he worst case design is based on the variable listed in the Set Parameters section Enter a new value in this field and click on the Calculate button LabPro will display the results on the C omparison tab This field represents what percentage of the worst case design the supply System has been designed to T he worst case design is based on the variable listed in the Set Parameters section Enter a new value in this field and click on the Calculate button LabPro will display the results on the Comparison tab This field represents what percentage of the worst case design the cooling System and heating system have been designed to T he worst case design is based on the variable listed in the Set Parameters section Enter a new value in thisfield and dick on the Calculate button LabPro will display the results on t
49. cost per unit of the fuel and units selected in the pu T mmu SE Reheat Fuel Cost per U nit Enter a value for the local cost per unit of the fuel and units selected in the ee ru hour 24 LabPro U ser s M anual Setup Units Setup Screen Y ou can specify English or M etric units in this screen Your changes will be automatically displayed on the other screens and tabs w Unit Configuration Japanese Yen Cubic Metre per Hour Degree Celsius E Mae a Poca gl eva H Figure 3 2 Setup Units Setup Screen Table 3 10 Setup Menu Units Setup Screen Selections Currency Select US Dollar USD Canadian Dollar CAD European Currency Unit ECU UK Pound GBP Swiss Frank CHF Japanese Y en JPY Chinese Renmimbi CN Y Hong Kong Dollar HKD Thai Baht THB South Korean Won KRW Singapore D ollar SG D or Australian Dollar AUD Select CFM Cubic m h or Liters Second Select D egrees F or Degrees C Select feet or meters Select Inch of Water Column or Pascal Select H orsepower or Kilowatt 25 LabPro U ser s M anual Edit Menu Edit Project General Information Tab SW Edit Project Conglomo United AA Err EA 0 00PM Born OOOO O Be 9300 3300 9900 Figure 3 3a Edit Menu Edit Project General Information Tab Table 3 11 Edit Menu Edit Project General Information Tab Selections U se any combination of alphanumeric characters to enter the name of the
50. cupied Air provide the required air changes per hour when the room is occupied LabPro Changes per H our in automatically calculates this flow rate from the entered values for the room s Floor Flow Area Ceiling H eight and U noccupied ACH M inimum Ventilation Enter a value for the number of air changes per hour ACH for the room during Rate Unoccupied Air unoccupied hours Changes per H our ACH M inimum V entilation This value represents the total flow rate of exhaust air that must leave the room to Rate Unoccupied Air providethe required air changes per hour when the room is unoccupied LabPro Changes per H our in automatically calculates this flow rate from the room s Floor Area Ceiling H eight Flow and U noccupied ACH Total Ancillary Exhaust Enter a value for the total maximum volume of constant volume and two position Flow M aximum exhausts i e canopy hoods snorkels maximum exhaust for two position hoods for the room Total Ancillary Exhaust Enter a value for the total minimum volume of constant volume and two position Flow Minimum exhausts i e canopy hoods snorkels maximum exhaust for two position hoods for the room N ote If the exhaust device is constant volume you should enter the total minimum value which is equal to the maximum exhaust for those devices For two position devices enter total minimum for those devices General Exhaust Valve Enter a value for the quantity of VAV GEX valves serving the ro
51. cy 65 PS o Kw Supply AHU Discharge 1250 Pa Static Pressure Control Type Parameters Drive Efficiency Minimum Load Percentage Cancel HP Part Load Performance Formula coefficients fA f fe fp 01534 Mores 3055 ose Figure 3 8 Edit Menu Supply Fan Add Supply Fan Screen Table 3 32 Edit Menu Supply Fan Add Supply Fan Screen Selections And you can General Information Enter a unique supply fan identifier in this field You can use any combination of Fan Name alphanumeric characters If you use a number in a supply fan s name such as SF 1 and you have more than ten supply fans use a leading 0 before the single digits i e SF 01 instead of SF 1 so that the supply fans will remain sequentially listed i e SF 01 will come before SF 10 General Information Enter any combination of alphanumeric characters to name the pressurization Service Area zones that the supply fan serves General Information Enter the name of the central plant that is associated with this fan Central Plant General Information Enter a number for the default supply fan efficiency percentage Fan Efficiency General Information Enter the value in inches of water wc or Pascals Pa for the default discharge Supply AHU Discharge static pressure measured in the ductwork at the outlet of the supply fan Static Pressure Horsepower Calculate Click this button to have LabPro automatica
52. d 23 hours 59 minutes Design Percentile Enter a value for the design percentile factor used for calculating exhaust system Exhaust Systems diversity U sing this factor results in a system that will meet systen design fume hood exhaust requirements the specified percent of time Each exhaust system that you define will use this factor Design Percentile Enter a value for the design percentile factor used for calculating supply air Supply Systems handling system diversity U sing this factor results in a system that will meet system design supply air requirements the specified percent of time Each supply air handling system that you define will use this factor Design Percentile Enter a value for the design percentile factor used for calculating central plant Central Plant Systems diversity U sing this factor results in a central plant that will meet system design cooling heating and reheat requirements the specified percent of time Each central plant system that you define will use this factor 27 LabPro U ser s M anual Edit Menu Edit Project Rooms Tab st Edit Project Bipks Central Plants Genera roman Room Defaults l Fume Hood Defaults Temperature Setpoint 3 33 Degl Sash Position User Present fion 2 Ceiling Height 274 m Sash Position User Absent n 1 ACH ccupied 8 00 hour UBC Normal Mode Flow ho Z ACH Unoccupied 400 hour UBC Standby Mode Flow o 1 Heat Gain 107 64 Watts m2 Daily Presence
53. d Equations Sum VAV design flows Sum VAV UBC design flows 10 Sum CV UBC average flows 11 Sum VAV average flows 12 Sum VAV UBC average flows 13 Sum CV UBC night flows 14 Sum VAV night flows 15 Sum VAV UBC night flows Sum project corridor data Sum corridor volumes Sum corridor areas Sum corridor maximum cooling flows Sum corridor minimum heating flows Sum corridor ACH flows Sum 24 hour cooling profiles by hour Calculate average corridor watts per square foot or per square meter Qo ide eov pes e Ie ES Calculate average corridor temperature Sum project room data Sum total number of rooms Sum room volumes Sum room areas Sum room maximum cooling flows Sum room occupied and unoccupied ACH flows Sum room hood minimum flows Sum room hood maximum flows Sum 24 hour cooling profiles by hour po ON On FPF wWNnN rp Calculate average room watts per square foot 10 Calculate average room temperature Sum project exhaust fan data Sum exhaust fan CV flows Sum total number of hoods Sum hood maximum flows Sum hood minimum flows Sum CV UBC design flows Sum VAV design flows Sum VAV UBC design flows Sum CV UBC average flows OD O9 IL Y OY Dg ROSES Sum VAV average hood flows ta o Sum VAV UBC average flows 11 Sum CV UBC unoccupied flows 12 Sum VAV unoccupied flows 13 Sum VAV UBC unoccupied flows E Sum project supply air handler data Sum supply fan CV flows Sum total number of hoods Sum hood m
54. d to the project 2134 LabPro U ser s M anual Setup System Defaults Fan and Central Plant You can define the default supply exhaust and central plant efficiencies and characteristics Be sure to check your local and federal regulatory standards and guidelines before selecting an exhaust fan control type N ote that if you change values here you will not affect existing projects ii Edit Program Default Values x Operating Costs Fume Hoods Room amp Corridor General Hood Usage F Initial Costs l Supply Systems Static Pressure AHU Fan Efficiency 65 00 Exhaust Fan Efficiency 55 00 Supply AHU Discharge fi 250 0 Pa Exhaust Fan Suction f 250 0 Pa Control Control Type Vane Axial Fan y Type Constant Air Volume Exhaust Systems Static Pressure l Central Plant Efficiency Heating 80 00 Efficiency Cooling f 40 kw Ton Supply Air Cooling Temperature f 3 Deg C Supply Air Heating Temperature f 3 Deg C Figure 3 1c Setup System Defaults Fans amp Central Plants Screen Table 3 4 Setup Menu System Defaults Fan amp Central Plants Screen Selections Click on Supply System AH U Fan Efficiency Supply System Supply AH U Discharge Static Pressure Supply System Supply Air T emp Supply System Control T ype Enter a number for the default efficiency percentage of the supply fans Enter the value you want to be the de
55. data including total room offset flow for each room that is adjacent to the corridor maximum and minimum corridor supply air flow and maximum and minimum corridor exhaust flow Exhaust Systems Calculations LabPro calculates exhaust system data by summing maximum and minimum exhaust requirements from all the corridors and rooms that are associated with each exhaust fan It also updates horsepower and annual kW h at this time Supply Systems Calculations LabPro calculates supply system data by summing maximum and minimum supply requirements from all the corridors and rooms that are associated with each supply fan It also updates horsepower and annual kW h at this time Central Plant Systems Calculations LabPro calculates central plant system flows by summing maximum and minimum supply requirements from all the corridors and rooms for the entire systen LabPro assumes that each project will have one central plant so all rooms fume hoods and corridors are included for these calculations Diversity Based Airflow Calculations LabPro calculates design flows based on laboratory control type using Phoenix Controls methodology for calculating system diversity as described in the M ethodology section D esign flows represent an expected worst case for exhaust or supply flow based on your input Appendix A Calculations and Equations Energy Use and Cost Calculations LabPro calculates estimated energy use and costs based on average flows b
56. default values individually in each data field The only data that you cannot overwrite is the Lab Usage T ype and the database that contains the U nited States Climatic Center s Engineering W eather Data for approximately 256 cities worldwide For a more detailed description see Chapter 3 Output Overview LabPro s outputs include Estimates of System D iversity Room Balances Schedules Initial and O perating Cost Estimates Economic Analyses For a more detailed description of the outputs available see Chapter 5 Reports and Graphs Basic Concepts The next few paragraphs explain basic concepts that are fundamental to designing a laboratory airflow control system Air Changes per Hour ACH Air change rate is defined as the ventilation rate of a space divided by the total volume of a space You can calculate air changes per hour ACH by dividing the total exhaust rate the volume of all air leaving the space per hour in cubic feet per hour cfm x 60 by the total volume of the space in cubic feet Conversely by selecting an ACH you can calculate the required supply air rate exhaust rate room offset to provide that ACH LabPro U ser s M anual Y ou should select air change rates based on the ventilation requirements of the materials present within a space as well as the number of occupants T he generally accepted range of air change rates for laboratories is four to twelve air changes per hour Increasing the
57. detailed analysis perform a load profile analysis using data specific to this project If this option isn t selected and the room has a cooling requirement you must enter a value for the M aximum Cooling flow M aximum Cooling Flow the room during its peak thermal load Thermal D enand Each hourly value represents a percentage of maximum cooling flow required for Profile varying sensible and latent heat loadsin a space During a 24 hour period aroom will have varying cooling flow requirements as a result of the heat generated by people lights and equipment as well as building skin loads which are a function of geographic location You may choose to use the default values by entering the geographic location or override some or all of the displayed values based on a more detailed analysis of cooling requirements 48 LabPro U ser s M anual Edit Menu Room Add Room Fume Hoods Tab You can add copy edit and delete fume hoods from this room as shown in this screen Edit Room Attributes Figure 3 5d Edit Menu Room Add Room Fume Hood Tab Right button click in the open area to expose a pop up menu You can choose from these four options Add H ood Edit H ood Copy H ood D elete H ood Table 3 27 Edit Menu Room Add Room Fume Hood Tab Selections Enter a unique identifier for the fume hood using any combination of alphanumeric characters if you do not enter a name LabPro w
58. e T his Temperature value represents the air temperature measured in degrees Fahrenheit or Celsius after the discharge of a preheater or cooling coil Edit Central Plant The Edit Central Plant menu item allows you to edit a previously created C entral Plant 59 LabPro U ser s M anual Copy Central Plant The Copy Central Plant menu item allows you to copy a previously created C entral Plant Delete Central Plant The D elete Central Plant menu item allows you to delete a Central Plant 60 LabPro U ser s M anual Chapter 4 Analysis and What If Click on Analyze to bring up the Analyze menu two choices are available And LabPro will Perform balancing simulation and cost calculations for the project W hat If Examine the effect that changes in one or more variables have on up to three different design approaches C LabPro Projects project 1 Ipr Analyze Figure 4 1 Analyze Menu 61 LabPro U ser s M anual Analyze Simulate Project Simulate Project Project Summary Selecting Simulate Project displays the Project Summary screen which shows the T otal Systen flows and the Cost Summary information T he costs are calculated using the Edit C osts values and the Average and D esign flows for a system T he system Flows section of the screen shows the T otal N umbers of rooms lab hoods fans etc and the System T otal Flows nf Project Summary Total exhaust system Tot
59. e Constant V olume U sage Based Controls laboratory controls including material costs and all installation labor D o not include the cost of the Fume H ood or balancing costs VAV VAV Enter a value for the average cost per fume hood for traditional VAV laboratory controls including material costs and all installation labor D o not include the cost of the Fume H ood or balancing costs Phoenix Controls VAV VAV Enter a value for the average cost per fume hood for Phoenix Controls PHX VAV laboratory controls including material costs and all installation labor D o not include the cost of the Fume H ood or balancing costs Adaptive Face V elocity VAV Enter a value for the average cost per fume hood for Phoenix Controls UBC Adaptive Face V elocity laboratory controls including material costs and all installation labor Do not include the cost of the Fume H ood or balancing costs 39 LabPro U ser s M anual Operating Costs w Edit Costs Lab Controls Annual Recurring Operating Costs Unit JPY Balancing Cost per Room 30 000 00 JPY Balancing Cost per Room Phoenix 1200000 JPY Certification Cost per Fume Hood 600000 JPY Certification Cost per Fume Hood Phoenix 100000 JPY CW Maintenance Cost per Hood 36 000 00 JPY WAW Maintenance Cost per Hood 80 000 00 m CV CV LUBC Maintenance Cost per Hood Phoenix 0 00 JPY VAM A AV LIBC Maintenance Cost per Hood Phoenix 0 00 n ATC Maintenance Cost
60. e LabPro automatically sum the total exhaust CFM or l s H orsepower or m h served by the selected fan and calculate the horsepower of the fan motor needed to drive the fan If you do not select the Calculate H orsepower option you must enter a value in the Power field H orsepower T otal LabPro totals all the exhaust air flow rates for all the rooms associated to the Flow selected fan LabPro displays the value in this field 55 LabPro U ser s M anual Table 3 31 Edit Menu Exhaust Fan Add Exhaust Fan Screen Selections And you can Displays the motor horsepower hp required to drive the selected fan Control T ype Select the default control type for the exhaust fans from the drop down list Parameters Control e Variable Frequency Drive Type Constant Air Volume Discharge D amper Forward Curve Fan Discharge D amper Backward Incline Fan Vane axial Fans Inlet Vane Control Airfoil Inlet Vane Control Forward Curve Fan Control Type Parameters Select the control type from the drop down list after checking with your local and federal regulatory standards and guidelines T he control types are described here Variable Frequency D rive The exhaust fan operates at variable speed using a variable frequency drive As the demand for airflow increases or decreases a control signal is used to command the variable frequency drive to increase or decrease the speed of the fan resulting in increased decreased airf
61. e available leave blank VAV UBC Rebate Enter a value for the amount of the rebate for your VAV UBC system If there is Amount no rebate available leave blank 36 LabPro U ser s M anual HVAC Costs wm Edit Costs a ES HVAC Lab Controls HWAC Systems Initial Costs Unit JPY Cooling System Cost per Ton f240 000 00 JPY Heating System Cost per Unit Flow f4118 SPY mavh Reheat System Cost per Unit Flow 56 47 JPY m3 h Supply AHU Cost per Unit Flow 211 76 JPY m3 h Exhaust Fan Cost per Unit Flow 52394 JPY m3 h VFD Cost per kw 36 000 DO JPY kW Duct Cost per Unit Flow fi 34 12 JPY m3 h ATC Cost per Room fi 08 000 00 JPY ATC Interface Cost per Room 60 000 oo JPY Filter Cost per Unit Flow f 7 65 JPY m3 h NOTE All costs include Material and Installation Labor coca Figure 3 4d Edit Costs HVAC Costs Tab Table 3 20 Edit Costs Energy Costs Tab Selections Cooling System Cost per Enter a value for the average cost per installed ton of cooling including chiller Ton cooling tower pumps piping variable frequency drives V F D s and all installation costs Do not include supply fans air handlers or cooling coils costs H eating System C ost per Enter a value or the average cost for heating equipment per installed CFM or l s Unit Flow or m h including boiler piping pumps variable frequency drives V FD s and all installation costs Reheat System Cost per Ente
62. e of Total Flow multiplies it by the total flow to calculate the offset expressed as a percentage of total flow exhaust 43 LabPro U ser s M anual Table 3 24 Edit Menu Room Add Room General Information Tab Selections D efault O ffset Enter a value in this field Percentage D efault O ffset Fixed W hen selected LabPro sets the offset to the value entered in the Flow field Flow D efault O ffset Flow Enter a value to be used in calculating the D efault O ffset Fixed Flow value and the D efault O ffset Percentage of T otal Flow up to value D efault O ffset LabPro will calculate the offset expressed as the percentage specified in the Percentage of Total Flow Percentage field of total flow up to but not exceeding the value specified in the up to Flow field Other Positive If the room requires that the pressurization is positive or the air migrates out of Pressure Room the room then place an X in this box and LabPro will make the necessary calculations to determine the project totals 44 LabPro U ser s M anual Edit Menu Room Add Room Ventilation Information Tab TheAdd Room menu item allows you to enter room specific ventilation information as shown in the following Screen Edit Room Attributes Figure 3 5b Edit Menu Room Add Room Ventilation Information Tab Table 3 25 Edit Menu Room Add Room Ventilation Information Tab Selections Clickon
63. ect LabPro calculates this value by summing the M echanical System Initial Costs and the Lab Controls Initial Costs Annual Energy Costs Calculate the annual energy cost LabPro calculates this value from the variables entered under the Energy T ab Variables under thistab include cooling fuel heating fuel reheat fuel and their associated costs per unit of fud Other variables include electricity cost per kW h and central plant efficiency for the project Annual O amp M Costs Display a summary of the operation and maintenance costs LabPro calculates this value from the variables entered under the O perating Costs tab T hese are annual costs such as re certification of the fume hoods re balancing the rooms and regular equipment maintenance Inflation and financing rates are also included in this calculation Total Annual Costs Display the total annual cost LabPro calculates this value by summing the Annual Energy Costs and the Annual O amp M Costs 67 LabPro U ser s M anual Chapter 5 Reports and Graphs Reports Project Summary This report lists the total number of rooms fume hoods exhaust and supply fans and central plants for the project along with the total demand the total design and total average airflow requirements for the different control approaches along with specifying the different costs associated with each control approach Project Defaults This report provides a summar
64. el BTU per Unit 8 7 H eating Energy Cost Appendix A Calculations and Equations Calculate Reheat Energy Costs General Equations H ourly Flow Cooling D emand Flow x1 08x Room Temp Supply Air T emp H eating efficiency 8 8 Reheat BT U s per H our 8 9 Reheat BT Us H ours of O peration x Reheat BT Us per H our Reheat BT Us 10 R tE H eating F EX 8 10 Reheat Energy Cost H eating Fuel Cost per Uni tina ua BTUs pe Unit Calculate Fan Energy Costs Calculate Constant Volume Fan Horsepower H ourly Flow x Duct Static Pressure 9 1 Fan H orsepower m d 6356 x Fan Efficiency x Altitude Correction Factor Calculate Fan Horsepower for Part Load Performance Fan part load performance curves are calculated using the general equation 9 2 Y AX BX 4CX 4D W here Y Fan Percent H orsepower X Flow required Constant Air Volume Fan Percent H orsepower 9 3 Y 1 Backward Incline Fan with D ischarge D ampers Percent H orsepower 9 4 Y 94868X 12381X 26418X 4 19355 Air Foil with Inlet Guide Vanes Percent H orsepower 9 5 Y 22663X 25530X 51261X 51311 Forward Curve Fan with Discharge D ampers Percent H orsepower 9 6 Y 66992X 07037X 17926X 08 Forward Curve Fan with Inlet Guide Vanes Percent H orsepower 9 7 Y 39225X 90543X 25487X 23174 VAV with Vane Axial Fan Percent H orsepower 9 8 Y 15342X 74548X 30553X
65. em unoccupie e CV UBC central plant unoccup hood flow hood flow e VAV exhaust system minimum e VAV supply system design hooc e VAV UBC exhaust system desic hood flow flow hood flow e VAV supply system minimum F e VAV supply system average hoc e VAV UBC exhaust system aver flow flow hood flow e VAV central plant minimum hc e VAV supply system unoccupied e VAV UBC exhaust system flow hood flow unoccupied hood flow e CV UBC exhaust system minim e VAV central plant design hood e VAV UBC supply system desigr hood flow hood flow e CV UBC supply system minimi e VAV central plant average hooc e VAV UBC supply system avera hood flow flow hood flow e CV UBC central plant minimui e VAV central plant unoccupied e VAV UBC supply system hood flow hood flow unoccupied hood flow e Maximum exhaust system coolii e CV UBC exhaust system design e VAV UBC central plant design flow hood flow hood flow e Maximum supply system coolin e CV UBC exhaust system averag e VAV UBC central plant average flow hood flow hood flow e Maximum central plant cooling e CV UBC exhaust system e VAV UBC central plant flow unoccupied hood flow unoccupied hood flow e Minimum exhaust system heatii e CV UBC supply system design flow hood flow Calculate hourly design and average flow for each systen by control option A System Design Flow Greater of D esign H ood flow ACH Flow M aximum Cooling Flow Minimum H ood Flow B System Average Flow Greater of Average H ood Flow AC
66. epower Service rea x Total Flow XD Fan Efficiency 65 Exhaust Fan Suction 1250 Pa Power 7 kw Static Pressure x Control Type Parameters Drive Efficiency fi 0 00 onstant Air Volume z Minimum Load Percentage Cancel HP Part Load Performance Formula coefficients fA fE fe fp lo 0000 lo 0000 i 0000 1 0000 Figure 3 7 Edit Menu Exhaust Fan Add Exhaust Fan Screen Table 3 31 Edit Menu Exhaust Fan Add Exhaust Fan Screen Selections And you can General Information Enter a unique exhaust fan identifier in this field You can use any combination of Fan Name alphanumeric characters If you use a number in a exhaust fan s name such as EF 1 and you have more than ten exhaust fans use a leading 0 before the single digits i e EF 01 instead of EF 1 so that the exhaust fans will remain sequentially listed i e EF 01 will come before EF 10 General Information Enter any combination of alphanumeric characters to name the pressurization Service Area zones that the exhaust fan serves General Information Enter a number for the default exhaust fan efficiency percentage Fan Efficiency General Information Enter the value in inches of water wc or Pascals Pa for the default suction Exhaust Fan Suction static pressure measured in the ductwork at the inlet of the exhaust fan Pressure Horsepower Calculate Click this button to hav
67. erent design approaches LabPro U ser s M anual Reports Menu Click on Reports on the menu bar to display the Reports menu as shown in Figure 2 4 C LabPro Projects jtn Ipr Figure 2 4 Reports Menu The Reports menu provides a list of available reports see Chapter 5 for a detailed explanation of each report Click on the desired report and either print or preview the information Table 2 4 Reports Menu Selections Fan Systems Summary Read asummary of all the individual exhaust supply and central plant systems on the project Read a report providing a diversity comparison for the different types of laboratory airflow control methods Read a listing of all the major system components annual costs and energy costs associated for the project based on the method of lab control being used Financial Analysis Comparison Read a report providing key financial information to help analyze the your computer Center s Engineering W eather D ata for the location selected D efault Fume H ood T ypes Read a summary of what fume hoods types are available in the database for use within a project Print Report Select more than 1 report to be printed in a batch print job LabPro U ser s M anual Graphs 8 Charts Menu Click on Graphs Charts on the menu bar to display the Graphs amp Charts menu as shown in Figure 2 5 Figure 2 5 Graphs 8 Charts Menu Table 2 5 Graphs amp Charts Menu Selections Cost
68. fault suction static pressure measured in inches of water wc or in Pascals Pa T his value represents the static pressure measured in the ductwork at the outlet of the supply fan Enter the default supply air temperature to be used whenever a supply air handling unit AH U is added to a project T his value represents the air temperature measured in degrees Fahrenheit or Celsius after the discharge of a pre heater or cooling coil Select the default control type for the supply fans from the drop down list Variable Frequency D rive Constant Air Volume Discharge D amper Forward Curve Fan Discharge D amper Backward Incline Fan Vane axial Fans Inlet Vane Control Airfoil Inlet Vane Control Forward Curve Fan 14 LabPro U ser s M anual Table 3 4 Setup Menu System Defaults Fan 8 Central Plants Screen Selections Click on Exhaust Systems Exhaust Fan Enter a number for the default efficiency percentage of the exhaust fans Efficiency Exhaust Systems Exhaust Fan Enter the value you want to be the default suction static pressure measured Suction Static Pressure in inches of water wc or in Pascals Pa T his value represents the static pressure measured in the ductwork at the inlet of the exhaust fan Exhaust Systems Control Type Select the default control type for the exhaust fans from the drop down list Variable Frequency Drive Constant Air Volume Discharge D amper Forward Curve Fan Discharge D amper
69. he Comparison tab 65 LabPro U ser s M anual Calculate W hen you dick on the Calculate button LabPro recalculates the project totals based on the current system entries For example if the project has an average ACH rate of 20 when you begin your W hat If session you can see the impact of an average of only 10 ACH Simply enter 10 in the ACH edit box and click the Calculate button LabPro will update the project flows energy costs first costs and life cycle costs You can seethe effect of your change on all control types on the main W hat If screen immediately You can also view any control type with original or W hat If values Export W hen you click this button LabPro will export the W hat If version of the Ipr file to a new filename and that file can be opened like any Ipr file Return W hen you dick this button LabPro will return to the M ain screen Comparison Tab w What If Analyzer New ions no E ww Elf luvas E 3199 se 1888 poto fo f 10 m Jime To ms el s Figure 4 4 Analyze Menu What If Comparison Tab Three different project configurations can be viewed at once You can choose to view the U ser Input data as Original or the W hat If tab parameter changes as N ew 66 LabPro U ser s M anual Control Types drop down box For each project configuration you can select one of the following control types CV VAV VAV PHX CV UBC
70. he default control type for the supply fans from the drop down list Control Type Variable Frequency Drive Constant Air Volume Discharge D amper Forward Curve Fan Discharge D amper Backward Incline Fan Vane axial Fans Inlet Vane Control Airfoil Inlet Vane Control Forward Curve Fan 33 LabPro U ser s M anual Edit Edit Costs Tabs Use this screen to specify energy HVAC lab and operating costs and define financial analysis information for the current project Some data is automatically filled in with the values that were entered into the System D efaults screen m Edit Costs Figure 3 4a Edit Costs Tabs Table 3 17 Edit Costs Menu Selections O perating Define the annual recurring costs e g maintenance costs re certification costs Financial D efine financial analysis information and annual recurring operating costs 34 LabPro U ser s M anual Energy Costs im Edit Costs x Lab Controls Unit JPY Cooling Fuel Electricity kWh Cooling Fuel Cost 6 000 JPY per Unit Heating Fuel Cost 540 000 JPY per Unit Reheat Fuel Cost 540 000 JPY per Unit Heating Fuel Natural Gas mcf x ReheatFuel Natural Gas mcf 2 Electricity Cost per 6 000 JPY kwh Rebate NOTE All costs include Material and Installation Labor cars Figure 3 4b Edit Costs Energy Costs Tab Table 3 18 Edit Costs Energy Costs Tab Selections Cool
71. hour and V ent Demand Flow Flow or M in Supply Flow gt M ax Cooling Demand set average flow for this hour equal to values from previous hour If they aretrue return to item 10 Begin Loop If Vent Demand Flow O ccupied or U noccupied M ax Cooling D emand Flow and M in Supply Flow are Room O ccupied Exhaust Flow and V ent D emand Flow O ccupied or U noccupied M ax Cooling D emand Flow and M in Supply Flow are Room U noccupied Exhaust Flow then A Select a random number between 0 and 1 B Compare the random number to the Average H ood Presence Probability 1 If the Random N umber is less than or equal to the Average H ood Presence Probability set the H ood Flow e CV Hood Flow CV Hood Occupied Flow e VAV Hood Flow VAV Hood Occupied Flow e CV UBC Hood Flow CV UBC Hood Occupied Flow e VAV UBC Hood Flow VAV UBC Hood Occupied Flow 2 If the Random N umber is greater than the D esign H ood Presence Probability set the H ood Flow e CV Hood Flow CV H ood U noccupied Flow e VAV Hood Flow VAV H ood U noccupied Flow e CV UBC Hood Flow CV UBC Hood Unoccupied Flow e VAV UBC Hood Flow VAV UBC Hood U noccupied Flow C Run A B on next hood in room H ood Flow and add to the Room H ood Flow e CV Room Hood Flow CV Room H ood Flow CV H ood Flow e VAV Room H ood Flow VAV Room Hood Flow VAV Hood Flow e CV UBC Room Hood Flow CV UBC Room Hood Flow CV UBC H ood Flow e VAV UBC Room Hood Flow VAV UBC Room Hood Flow VAV UBC H o
72. id with each control type assigned to a column and each of the following costs assigned to a row Cost T ype M echanical System Initial C ost Laboratory Controls C ost Total Initial System Cost Annual Energy Costs Annual M aintenance Costs Total Annual Costs Control T ype CV Constant Volume CV PH X Phoenix Controls C onstant Volume VAV Variable Air Volume VAV PH X Phoenix Controls Variable Air Volume CV UBC Phoenix Controls Constant V olume U sage Based Controls VAV UBC Phoenix Controls Variable Air Volume U sage Based Control 63 LabPro U ser s M anual What If Overview TheW hat If feature is a decision making tool that allows you to instantly view the impact of your design decisions in terms of airflow mechanical system first cost energy costs and operation and maintenance cost W hat If comparisons are made on two screens You can change any of the values in the Set Parameters tab but your changes will have no effect until you check each parameter s box and click on the Calculate button The Comparison tab shows these results for 3 control types you can select any of the control types available from the currently defined project or values that you have edited Set Parameters Tab ii What If Analyzer Gl x Daily User Present Hours Hours day Heat Gain Watts m2 ACH Occupied ed ACH Unoccupied hour Fume Hood Turn Down x 1 Sash Position User Present Sash Position Use
73. idor ACH flows occupied and unoccupied n m 5 6 Fan ACH Flow Y Room ACH Flow Corridor ACH Flow m 1 1 Calculate the number of hoods per fan system n 5 7 Fan Hood Count Room Hood Count 1 Calculate the maximum hood flow n 5 7 1 M ax Hood Flow YM ax H oodFlow 1 Calculate the minimum hood flow n 5 7 2 Min Hood Flow Y Min H oodFlow 1 Appendix A Calculations and Equations Project Simulation Algorithm Hood Subroutine 1 Calculate H ood O ccupied Flow e CV Hood Occupied Flow H ood M ax Flow e VAV Hood Occupied Flow M ax2 H ood M ax Flow H ood O ccupied Sash Position H ood M in Flow e CV UBC Hood Occupied Flow M ax2 H ood M ax Flow UBC Normal M ode H ood M in Flow e VAV UBC Hood Occupied Flow M ax2 H ood M ax Flow UBC Normal M ode H ood Occupied Sash Position H ood M in Flow 2 Calculate H ood U noccupied Flow e CV Hood Unoccupied Flow H ood M ax Flow e VAV Hood Unoccupied Flow M ax2 H ood M ax Flow Hood Unoccupied Sash Position H ood M in Flow e CV UBC Hood Unoccupied Flow M ax2 H ood M ax Flow UBC Stand By M ode H ood M in Flow e VAV UBC Hood Unoccupied Flow M ax2 H ood M ax Flow UBC Stand By M ode H ood Unoccupied Sash Position H ood M in Flow Room Subroutine 1 Run Hood Subroutine 2 SumH ood Data e Hood Count H oodcount Hood M ax Flow H oodM axF low Hood Min Flow H oodM inFlow CV Hood O ccupied Flow 2 CVH oodO ccupiedF
74. ill enter one automatically when you click on the Add H ood button If you use a number in a hood s name such as HOOD 1 and you have more than ten hoods use a leading 0 before the single digits i e HOOD 01 instead of HOOD 1 so that the hoods will remain sequentially listed i e HOOD 01 will come before HOOD 10 Daily Present H ours Enter a value for the number of hours that a user is apt to bein front of the hood This value cannot exceed the total number of the building s O ccupied H ours M aximum Flow Enter the maximum flow through the hood M inimum Flow Enter the minimum flow through the hood 49 LabPro U ser s M anual Table 3 27 Edit Menu Room Add Room Fume Hood Tab Selections Click on N ormal operating in N ormal mode Standby operating in Standby mode Sash Position Present Enter a value for the percentage of sash opening when a user is present at his or her fume hood A value of 100 means that the sash is completely open and a value of 0 means that the sash is completely closed Sash Position Absent Enter a value for the percentage of sash opening when a user is absent from his or her fume hood A value of 100 means that the sash is completely open and a value of 0 means that the sash is completely closed H ood T ype Click on this button and select a fume hood from the drop down list of fume hood types in the H ood T ype field For each hood the table contains wid
75. ing Fuel Select the cooling heating and reheat fuels The pre defined list of fuel types pu and their units of measurement includes H eating Fuel 32 Fue Oil gal Bituminous Coal Ib Natural Gas m h 2 Fue Oil metricton Bituminous Coal metric kWh 4 Fud Oil gal ton Propane gal Reheat Fuel 4 Fue Oil metricton Electricity kWh Propane metric ton 6 Fud Oil gal K erosene gal Steam 1 000 Ibs 6 Fue Oil metricton Kerosene metric ton Steam metric ton Anthracite C oal Ib N atural Gas ccf SubBituminous Coal Ib Anthracite Coal metric Natural Gas mcf SubBituminous C oal ton N atural Gas therm metric ton Cooling Fuel Cost per Enter a value for the local cost per unit of the fuel and units selected in the Unit Cooling Fue field Unit H eating Fuel field Reheat Fuel Cost per Enter a value for the local cost per unit of the fuel and units selected in the Electricity Cost per kWh Enter a value for the local cost per kilowatt hour of electricity Rebate button Enter data about any rebate or incentives 35 LabPro U ser s M anual Energy Costs Rebate Information You can enter information about rebates or incentives for your project If your local gas or electric utility provides incentives for energy saving laboratory control systems this is where you enter that amount You must specify which systems will be given rebates For example many utilities will not provide rebates or incentives for t
76. lculations and Equations This appendix has three sections 1 Calculation O verview provides a simple overview of LabPro s calculation methodology 2 Calculation Procedure provides a detailed outline of LabPro s calculation methodology 3 Equations lists all of LabPro s formulas Calculation Overview The following section describes LabPro s basic calculation sequence User Input User input includes definition of e project information such as customer name location building occupancy hours the number and type of supply fan systems used in this project the number and type of exhaust fan systems used in this project the corridors used in this project the rooms and fume hoods exhaust sources used in this project energy types used for cooling heating and reheating the air required for this project including appropriate rebate information first cost information and e operating cost information including life cycle analysis information Room Flow Calculations LabPro calculates room airflow data using the room balance method described in the Phoenix Controls Laboratory Engineering Guide T his includes offset flow maximum and minimum supply air flow and maximum and minimum general exhaust flow LabPro also calculates the total maximum and minimum room exhaust flow along with maximum and minimum flows associated with all the fume exhaust sources in each room Corridor Flow Calculations LabPro calculates corridor airflow
77. ll use this data in the economic reports to escalate energy and maintenance costs in future years Period Y ears for a competing investment choice Annual Costs Balancing Cost per Enter a value for the average cost to balance the airflow control system Room within a laboratory space including material and labor costs LabPro assumes that a laboratory airflow controls system needs to be re balanced annually T herefore it will add half of the entered cost to the total annual maintenance cost Also LabPro uses the total entered costs to determine initial costs to install the mechanical system Annual Costs Balancing Cost per Enter a value for the average cost to balance a Phoenix Controls airflow Room Phoenix flow control system within a laboratory space including material and labor costs LabPro assumes that a laboratory airflow controls system needs to be re balanced annually T herefore it will add half of the entered cost to the total annual maintenance cost Also LabPro uses the total entered costs to determine initial costs to install the mechanical system 18 LabPro U ser s M anual Table 3 6 Setup Menu System Defaults Operating Costs Screen Selections And you can Annual Costs Certification Cost per Fume H ood Annual Costs Certification Cost per Fume H ood Phoenix Annual Costs CV M aintenance Cost per Fume H ood Annual Costs VAV M aintenance Cost per Hood Annual Costs CV CV UBC M aintenance
78. lly sum the total supply CFM or l s H orsepower or m h served by the selected fan and calculate the horsepower of the fan motor needed to drive the fan If you do not select the Calculate H orsepower option you must enter a value in the Power field H orsepower Total LabPro totals all the supply air flow rates for all the rooms associated to the selected Flow fan LabPro displays the value in this fied 57 LabPro U ser s M anual Table 3 32 Edit Menu Supply Fan Add Supply Fan Screen Selections And you can Displays the motor horsepower hp required to drive the selected fan Control T ype Select the control type from the drop down list after checking with your local and Parameters Control federal regulatory standards and guidelines Type e Variable Frequency Drive Constant Air Volume Discharge D amper Forward Curve Fan Discharge D amper Backward Incline Fan Vane axial Fans Inlet Vane Control Airfoil Inlet Vane Control Forward Curve Fan The selection made here controls the values displayed in the next two fields Control Type Displays the number for the supply fan efficiency percentage for the selected Parameters D rive control type Efficiency Control Type Displays the number for the minimum load percentage for the selected control Parameters Minimum type Load Percentage Edit Supply Fan TheEdit Supply Fan menu item allows you to edit a previously created supply fan Copy Supply Fan The
79. low Constant Air Volume The exhaust fan operates at a fixed fan speed regardless of airflow changes within the system Discharge D amper Forward Backward The exhaust fan operates at a fixed fan speed H owever as the system demands less airflow flow rate a discharge relief air damper is opened to maintain a constant flow rate of airflow to the inlet of the exhaust fan Vane axial Fan The exhaust fan operates at a fixed fan speed As the system demands less airflow flow rate the pitch of the fan blade is changed while the fan is turning restricting the flow rate of air that the fan is moving resulting in variable volume operation Inlet Vane Control Air Foil Forward The exhaust fan operates at a fixed fan speed As the system demands less airflow flow rate however an inlet vane is modulated to restrict the flow rate of air to the inlet of the supply fan permitting variable volume operation Edit Exhaust Fan The Edit Exhaust Fan menu item allows you to edit previously created exhaust fans Copy Exhaust Fan The Copy Exhaust menu item allows you to copy a previously created exhaust fan Delete Exhaust Fan The D elete Exhaust Fan menu item allows you to delete an exhaust fan 56 LabPro U ser s M anual Edit Supply Fan Add Supply Fan Screen ia Edit Supply iol xl General Information Horsepower Fan Name fahu 2 x Calculate Horsepower Service Area Central Plant ok Total Flow m3 h SA z Fan Efficien
80. low VAV Hood Occupied Flow VAVH oodO ccupiedF low CV UBC Hood Occupied Flow 2CV UBCH oodO ccupiedFlow VAV UBC Hood Occupied Flow VAV UBCH oodO ccupiedF low CV Hood U noccupied Flow CVH oodO ccupiedFlow VAV Hood Unoccupied Flow VAVH oodU noccupiedF low CV UBC Hood Unoccupied Flow CV UBCH oodU noccupiedFlow VAV UBC Hood Unoccupied Flow VAV UBCH oodU noccupiedFlow ake snap shot of each hood CV Hood O ccupied Flow VAV Hood Occupied Flow CV UBC Hood Occupied Flow VAV UBC Hood Occupied Flow CV Hood Unoccupied Flow VAV Hood Unoccupied Flow CV UBC Hood U noccupied Flow e VAV UBC Hood Unoccupied Flow 4 Run all Room Balance subroutines 5 Calculate D esign H oods Presence Probability e Design H ood Presence Probability H ood U sage H ours Building O ccupied H ours 6 Calculate Average H oods Presence Probability e Average H ood Presence Probability H ood U sage H ours 24 H ours 7 Calculate Room Other Exhaust Flow e CV Room Other Exhaust Flow CV Gex Other CV Exhaust M ax Gex Valve M in Flow e Room Other Exhaust Flow CV Gex O the CV Exhaust M ax Gex Valve M in Flow 8 Calculate Room Occupied Exhaust Flow e CV Room Occupied Exhaust Flow CV Hood Occupied Flow CV Room Other Exhaust Flow eoeeee eeoeoe 7y4eeeeee080 Eso O Appendix A Calculations and Equations VAV Room O ccupied Exhaust Flow VAV H ood O ccupied Flow Room Other Exhaust Flow CV UBC Room Occupied Exhaust Flow CV UBC Hood Occupied Flow Room Other Exhaust Flow VAV UBC
81. nd Payback will be calculated LabPro will show a comparison of the Base system with its associated control type to O ption 1 and O ption 2 and also show a comparison of O ption 1 against O ption 2 Calculation Procedure Calculate Project 1 Calculate total occupied and unoccupied hours per day Labsim 2 Calculate individual room flows A Estimate room offset Solve for unoccupied ventilation demand Solve for occupied ventilation denand Solve for thermal demand Size general exhaust valves Solve for hood denand Size supply valves cT 0mmugo sou Validate room flows Validate room offset 3 Calculate individual corridor flows A Calculate corridor offset Eq 2 5 B Sizesupply and exhaust valves Eq 2 6 2 7 2 8 2 9 2 10 2 11 4 Calculate individual exhaust fan flow data A Sum exhaust fan room data for associated rooms and corridors 1 Sum individual room total exhaust flows Eq 5 1 and 5 2 2 Sum maximum hood and corridor exhaust flows Eq 5 3 3 Sum minimum hood and corridor exhaust flows Eq 5 4 4 Sum fan maximum flow Eq 5 5 H Appendix A Calculations and Equations 5 Sum room and corridor ACH flows Eq 5 6 Sum exhaust fan hood data 1 Sum hood count Eq 5 7 2 Sum maximum hood flows Eq 5 7 1 3 Sum minimum hood flows Eq 5 7 2 Calculate design and average hood presence probability Eq 5 10 and 5 11 Run Simulation to determine O cc or U nO cc for each hood See Labsim methodology
82. ng costs Laboratory Adaptive Face Enter a value for the average cost per fume hood for Phoenix Controls Velocity VAV UBC Variable Air Volume U sage Based Control laboratory controls including material costs and all installation labor D o not include the cost of the Fume H ood or balancing costs San ee LabPro U ser s M anual Setup System Defaults Operating Costs You can specify recurring operating costs and factors used in financial calculations here N ote that if you change values here you will not affect existing projects mi Edit Program Default Values Hood Usage Fan amp Central Plant Room amp Coridor ISE Annual Recurring Operating Costs in JPY ein Fate 00 Balancing Cost per Room 30 000 00 Balancing Cost per Room Phoenix 112 000 00 Analysis Period 5 Certification Cost per Fume Hood 6 000 00 earl Certification Cost per Fume Hood Phoenix 300000 CW Maintenance Cost per Fume Hood 36 000 00 VAV Maintenance Cost per Hood 90 000 00 CV CV LIBC Maint Cost per Fume Hood Phoenix ooo VAVAVAV LIBC Maint Cost per Fume Hood Phoenix noo ATC Maintenance Cost Per Room 60 000 00 Hurdle Rate 5 00 Figure 3 1e Setup System Defaults Operating Costs Screen Table 3 6 Setup Menu System Defaults Operating Costs Screen Selections Financial Analysis Inflation Rate Enter a value for the expected general inflation rate LabPro wi
83. od Flow D Run A through C on remaining hoods in the room each time adding the result to the Room H ood Flow e CV Room Hood Flow CV Room H ood Flow CV H ood Flow e AV Room H ood Flow VAV Room Hood Flow VAV H ood Flow e CV UBC Room H ood Flow CV UBC Room Hood Flow CV UBC H ood Flow e VAV UBC Room H ood Flow VAV UBC Room Hood Flow VAV UBC H ood Flow E Calculate T otal Room D enand Flow e CV Total Room Demand M ax4 CV Room Flow CV Room Other Exhaust Flow Vent Demand Flow CV M ax Cooling Demand Flow CV Supply M in Flow e VAV Total Room Demand M ax4 VAV Room Flow VAV Room Other Exhaust Flow Vent D emand Flow M ax Cooling Demand Flow Supply M in Flow e CV UBC Total Room Demand M ax4 CV UBC Room Flow CV UBC Room Other Exhaust Flow Vent Demand Flow M ax Cooling Demand Flow Supply M in Flow e VAV UBC Total Room Demand M ax4 VAV UBC Room Flow VAV UBC Room Other Exhaust Flow Vent Demand Flow M ax Cooling D emand Flow Supply M in Flow F Add T otal Room D emand to Average Flow e CV Average Flow CV Average Flow CV T otal Room Demand e VAV Average Flow VAV Average Flow VAV T otal Room D emand e CV UBC Average Flow CV UBC Average Flow CV UBC Total Room Demand e VAV UBC Average Flow VAV UBC Average Flow VAV UBC Total Room Demand Repeat A through F 300 to 500 times each time adding to the final Average Flow Set Average Flow e CV Average Flow CV Average Flow N umber of trials TO 11 Appendix A Calcul
84. om Q uantity VAV Qty Supply Valve Q uantity Enter a value for the quantity of VAV supply valves providing make up air to this VAV Qty room 46 LabPro U ser s M anual Edit Menu Room Add Room Thermal Information Tab The Add Room menu item allows you to enter room specific thermal information as shown in the following screen In addition there are two buttons of interest available located at the bottom of this screen e The Default Profile button will reset the Thermal Profile to the system default values e The Balance Sheet button will display a completed Room Balance Report for the room Edit Room Attributes General Information Ventilation Information Thermal Requirements Floor Area 27 87 m2 Temperature Setpoint 2333 DegC Heat Gain 107 64 Watts m2 Ceiling Height 274 m x Calculate Maximum Cooling Flow Maximum Cooling Flow E 48 m3 h Thermal Demand Profile Flow Unit m3 h 12 00am 01 00am 355 08 00am 09 00am 01 00am 02 00am 365 03 00am 10 00am 02 00am 03 00am 56 10 00am 11 00am 03 00am 04 00am 11 00am 1 2 00pm 04 00am 05 00am 12 00pm 01 00pm 05 00am 06 00am 01 00pm 02 00pm 06 00am 07 00am 02 00pm 03 00pm O7 00am 08 00am 03 00pm 04 00pm 04 00pm 05 00pm 05 00pm 06 00pm 06 00pm 07 00pm O7 00pm 08 00pm 08 00pm 09 00pm 09 00pm 10 00pm 10 00pm 11 00pm 37 11 00pm 12 00am 373 Reset Profile cop cof cof mp cof cof co cog Co Bl O RE I8 DD i Tai Ee mp
85. on Introduction to LabPro LabPro is a software tool that simplifies the laboratory airflow decision making process by allowing you to easily compare laboratory airflow control configurations W ith these comparisons you can define the laboratory configuration that achieves the lowest capital costs optimum energy savings and most efficient operations LabPro will help you compare costs and benefits of different airflow designs What LabPro is LabPro is a planning and decision support tool operating in a M icrosoft Windows environment LabPro will help you specify optimum airflow ranges and room pressurization to determine the most efficient control configuration for mechanical and airflow systems in a laboratory LabPro features e Mechanical system diversity analysis Airflow analysis functions Room balance schedules Comparisons of initial costs life cycle costs and energy costs analyses An intelligent W hat If analysis tool that instantly compares the cost impact of variations in fume hood turndown ratios watts per square foot sash positions air change rates and design confidence levels e On line help that gives you access to extensive references that can assist you with the concepts and technical issues of laboratory design What s in this Document You will find this document divided into 5 chapters Chapter 1 Introduction This chapter covers general information on LabPro its methodology input and output overview
86. ontrol manifold Set Random N umber equal to 1 and maker first pass steps 13 through 17 Set value equal to bin max for each manifold Also set CV U BC value equal to CV design Flow Set Random N umber equal to 0 and make second pass steps 13 through 17 Set value equal to bin min for each manifold W hen complete with first two passes set up storage bins Add result from 6 and 7 and divide by 200 Establish Bin tables for each manifold Select a random number between 0 and 1 Compare the random number to the D esign H ood Presence Probability e ftheRandom N umber is less than or equal to the D esign H ood Presence Probability set the H ood Flow VAV Hood Flow VAV H ood Occupied Flow CV UBC Hood Flow CV UBC Hood Occupied Flow VAV UBC Hood Flow VAV UBC Hood Occupied Flow e ftheRandom N umber is greater than the D esign H ood Presence Probability set the H ood Flow VAV Hood Flow VAV H ood U noccupied Flow CV UBC Hood Flow CV UBC Hood Unoccupied Flow VAV UBC Hood Flow VAV UBC Hood Unoccupied Flow Run 10 amp 11 on next hood in room H ood Flow and add to the Room H ood Flow e VAV Room H ood Flow VAV Room Hood Flow VAV Hood Flow e CV UBC Room H ood Flow CV UBC Room Hood Flow CV UBC H ood Flow e VAV UBC Room H ood Flow VAV UBC Room Hood Flow VAV UBC H ood Flow Run 11 through 12 on remaining hoods in the room each time adding the result to the Room H ood Flow e VAV Room H ood Flow VAV Room Hood Flow VAV Hood Flow e CV UBC Room H ood Flow CV UB
87. ontrols Constant Volume or Constant Volume U sage Based Controls fume hood system LabPro will use this value to estimate the annual operating and maintenance cost for a complete Phoenix Controls system Enter a value for the average cost to maintain a Phoenix C ontrols variable air volume VAV or Variable Air Volume U sage Based Control VAV UBC fume hood system LabPro will use this value to estimate the annual operating and maintenance cost for a complete Phoenix Controls system Enter a value for the average cost to maintain the Automatic T emperature C ontrol AT C system within the laboratory LabPro will use this value to estimate the annual operating and maintenance cost for a complete tenperature control system Enter the average cost incurred for downtime due to HVAC mechanical system maintenance and repair per hour per room LabPro will determine the annual number of maintenance hours by dividing the total maintenance cost for each system by 100 U SD hour a realistic average hourly maintenance cost It then multiplies the total number of maintenance hours by the average downtime costs to determine the cost impact of having a laboratory not in use because of maintenance 41 LabPro U ser s M anual Financial Analysis Edit Costs Mi E Financial Analysis Base Control System Inflation Rate Option 1 Analysis Period VAY Years Option 2 Hurdle Rate VAV UBC NOTE All costs include Ma
88. or the average cost to maintain a Phoenix Controls Constant Volume or Constant V olume U sage Based C ontrols fume hood system LabPro will use this value to estimate the annual operating and maintenance cost for a complete Phoenix Controls system Enter a value for the average cost to maintain a Phoenix Controls variable air volume VAV or Variable Air Volume U sage Based Control VAV UBC fume hood system LabPro will use this value to estimate the annual operating and maintenance cost for a complete Phoenix Controls system Enter a value for the average cost to maintain the Automatic T emperature Control AT C system within the laboratory LabPro will use this value to estimate the annual operating and maintenance cost for a complete temperature control system 19 LabPro U ser s M anual Setup System Defaults Fume Hoods You can define the names and characteristics of fume hoods in this tab N ote that if you change values here you will not affect existing projects Edit Program Default Values Figure 3 1f Setup System Defaults Fume Hoods Screen Table 3 7 Setup Menu System Defaults Fume Hoods Screen Selections Type N ame Enter a name identifying this hood type Sash width Specify the sash width for this hood type M ax Flow Specify the maximum flow CFM or l s or m h for this hood type M in Flow Specify the minimum flow CFM or I s or m h for this hood type TypeName Cid Sash width ooo O Sa
89. oratory Controls Initial Costs per Hood Cooling System Cost per Ton 240 000 00 Constant Volume CV 180 000 00 Heating System Cost per Unit Flow 141 18 Phoenix Constant Volume CV PHX 240 000 00 Reheat System Cost per Unit Flow 56 47 Adaptive Constant Volume CV UBE 480 000 00 Supply AHU Cost per Unit Flow 211 76 VAVIVAV 660 000 00 Exhaust Fan Cost per Unit Flow 5294 PhoenixWAW VAV PHX 660 000 00 VFD Cost per kw 3600000 Adaptive Face Velocity VAV UBC 720 000 00 Duct Cost per Unit Flow 13412 ATC Cost per Room 108 000 00 ATC Interface Cost per Unit Flow 60 000 00 Filter Cost per Unit Flow fi 7 65 NOTE All costs include Material and Installation Labor All costs are in JPY Flow Unitis m3 h Figure 3 1d Setup System Defaults Initial Costs Screen Table 3 5 Setup Menu System Defaults Initial Costs Screen Selections HVAC Cooling System Cost per Enter a value for the average cost per installed ton of cooling including Ton chiller cooling tower pumps piping variable frequency drives VFD s and all installation costs Do not include supply fans air handlers or cooling coils costs HVAC Heating System Cost per Enter a value for the average cost for heating equipment per installed Unit Flow CFM or l s or m h including boiler piping pumps variable frequency drives VFD s and all installation costs HVAC Reheat System C ost per Enter a value for the ave
90. per Room 60 000 00 dey Downtime Cost per Hour per Hood 2 400 00 dei NOTE All costs include Material and Installation Labor tc Figure 3 4f Edit Costs Operating Costs Tab Table 3 22 Edit Costs Operating Costs Tab Selections And you can Balancing Cost per Enter a value for the average cost to balance the airflow control system within a Room laboratory space including material and labor costs LabPro assumes that a laboratory airflow controls system needs to be re balanced annually and will add the entered cost to the total annual maintenance cost Also LabPro uses this cost to determineto initial costs to install the mechanical system Balancing Cost per Enter a value for the average cost to balance a Phoenix Controls airflow flow control Room Phoenix system within a laboratory space including material and labor costs LabPro assumes that a laboratory airflow controls system needs to be re balanced annually and will add the entered cost to the total annual maintenance cost Also LabPro uses this cost to determine to initial costs to install the mechanical system Certification Cost per Enter a value for the average cost to re certify a fume hood system within a Fume H ood laboratory space including material and labor costs LabPro will use this value to estimate the annual operating and maintenance cost and initial cost for the complete system LabPro will also use this cost to determine initial costs to in
91. percentage whenever you define a new room O ffset flow rate percentage is the Percent difference between room supply air flow rate and room exhaust flow rate expressed as a percentage of the maximum total room exhaust You can change individual room values in the G eneral screen within the Room tab as you define or edit each room Corridor D efaults Enter a value to be the default air changes per hour ACH You can change ACH individual corridor values in the Ventilation screen within the Corridor tab as you define or edit each corridor Corridor D efaults Enter the value to be used as the default maximum watts per square foot for all Energy Consumption new corridors T he watts per square foot or W atts per square meter value W atts Sq Ft or represents the total maximum heat gain in watts within a corridor divided by the W atts m total floor area of the corridor in square feet or square meters T otal maximum heat gain includes both sensible and latent heat from people lighting and equipment as well as external heat sources such as sunlight You can change individual room values in the T hermal Info screen within the Corridor tab as you define or edit each corridor Corridor D efaults Enter the default size of floor area in square feet or meters Floor Area Sq Ft or m 22 LabPro U ser s M anual Setup System Defaults Energy Costs You can define the default types of heating and cooling as
92. ple lighting and equipment as well as external heat sources such as sunlight 285 LabPro U ser s M anual Table 3 12 Edit Menu Edit Project Rooms Tab Selections And you can Room Defaults Offset Enter a value to be used as the default room offset CFM or l s or m h percentage CFM or l s or m h whenever you define a new room O ffset flow rate percentage is the difference Percent between room supply air flow rate and room exhaust flow rate expressed as a percentage of the maximum total room exhaust Sash Position U ser Enter a value to be the default sash position when a user is present at a fume hood Present LabPro will automatically fill the U ser Present field with this number whenever you add a new fume hood to the project Sash Position U ser Enter a value to be the default sash position when a user is absent from a fume Absent hood LabPro will automatically fill the U ser Absent field with this number whenever you add a new fume hood to the project Normal Normal mode Standby Standby mode Fume H ood Presence Enter the total cumulative time per day that the user s are apt to bein front of H ours their hoods N ote Presence hours cannot exceed the total building occupied hours 29 LabPro U ser s M anual Edit Menu Edit Project Corridors at Edit Project Pe Conidort General 1 566 Pos Figure 3 3c Edit Menu Edit Project Corridors Tab Right but
93. projects Weather Data Bin Weather Data This report lists the Bin W eather D ata from U nited States Climatic C enter s Engineering W eather D ata for the location selected Default Fume Hood Type This is a summary of fume hoods that have been predefined for use in a LabPro project file Graphs Charts LabPro can produce graphical representations of various aspects of your project Graphs are available in the Reports menu Comparison Costs Energy Costs Graph The Energy Costs graph shows energy use for the current project based on control system type For each stacked bar supply air handler exhaust fan cooling heating and reheat costs are shown for the first year of operation Initial M echanical System C osts G raph The Initial M echanical System Cost graph shows estimated first costs for the current project based on control system type For each bar T otal Initial Cost is the sum of all related first costs as entered on the HVAC sub screen of the E dit C osts menu Life Cycle C osts Graph The Life Cycle Costs graph shows estimated total cost of mechanical system ownership over the life of the building defined in the current project For each stacked bar the initial mechanical system cost is shown at the bottom of the bar total operation and maintenance costs over the analysis period are shown on the top of the stacked bars T otal operation and maintenance costs include energy and non energy related costs T he length of
94. r a value for the average cost for reheat equipment per installed CFM or l s or Unit Flow m h including reheat coils piping and all installation labor Supply Air Handler Cost per Enter a value for the average cost for supply AH U equipment per installed CFM Unit Flow or l s or m h including air hander fan motor cooling coils filter housing and all installation labor Exhaust Fan Cost per Unit Enter a value for the average cost for exhaust fan equipment per installed CFM or Flow l s or m h including fan dampers and all installation labor VFD Cost per HP Enter a value for the average cost for variable frequency drive VFD equipment per installed H P including VFD damper and all installation labor costs LabPro will use this value to estimate the total mechanical system initial costs 37 LabPro U ser s M anual Table 3 20 Edit Costs Energy Costs Tab Selections And you can Duct Cost per Unit Flow Enter a value for the average cost for ductwork per installed CFM or l s or m h including ductwork material costs and all installation labor Duct Cost per CFM or l s or m h includes both stainless steel and non stainless steel duct T o calculate this value you must first determine a ratio of stainless steel to non stainless steel duct the cost per CFM or l s or m h of non stainless duct and then determine an average duct cost per CFM or l s or m h Enter a value for the average cost per room for
95. r versions NO WARRANTIES This software is provided to you AS IS TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW PHOENIX DISCLAIMS ALL OTHER WARRANTIES EITHER EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Phoenix does not warrant that the Software will meet your requirements or that the Software will operate uninterrupted or error free The warranty and remedies set forth herein are exclusive and in lieu of all others oral or written express or implied The limited warranty set forth herein gives you specific legal rights and you may have others under applicable law which may vary depending on your location No dealer distributor agent or employee of Phoenix is authorized to change or add to the warranty and remedies set forth herein Any other software furnished with or accompanying the Software is not warranted by Phoenix LIMITATION OF LIABILITY Because software is inherently complex and may contain errors you should verify your work and backup frequently To the maximum extent permitted by applicable law Phoenix shall have no liability for any damages whatsoever arising out of the use of or inability to use the Software including without limitation damages or costs for loss of profits business goodwill data or other assets or computer programs or for incorrect data or results even if Phoenix has been advised of the possibility of such damages GE
96. rAbsent UBC Hood Mode Normal UBC Hood Mode Standby Design Percentile Exhaust Design Percentile Supply Design Percentile Central Plant Calculate Export Return Figure 4 3 Analyze Menu What If Set Parameters Tab Note W hen analyzing the results understand that the new value may or may not have an impact on the system sizing or operation If you get unexpected results perform a detailed analysis to completely understand the impact of the change Table 4 2 Analyze M enu What If Set Parameters T ab Daily User Present H ours Enter the number of hours that a user is apt to bein front of their hood This value cannot exceed the total number of the building s O ccupied H ours H eat Gain Represent the total heat gain in watts within a room divided by the total floor area of the room in square feet or square meters T otal heat gain includes both sensible and latent heat from people lighting and equipment Enter a value in this field and click on the Calculate button LabPro will display the results on the Comparison tab 64 LabPro U ser s M anual Table 4 2 Analyze M enu What If Set ParametersT ab ACH Occupied ACH Unoccupied Indicates the air change rate for the building during the occupied hours Air change rate is defined as the ventilation rate of a space divided by the total volume of a space Air Changes per H our ACH can be calculated by dividing the total exhaust rate
97. raditional VAV systems since the energy savings is dependent on fume hood sash position something over which the utility has no control A rebate may be provided to use a traditional VAV system but a larger rebate may be given if U sage Based Controls are used since U sage Based Controls are not dependent on sash position for minimum energy savings For each VAV Constant Volume U sage Based Controls and Variable Air Volume U sage Based Controls control option enter the rebate amount if any T he default value of zero dollars 0 indicates that there is no rebate provided for this control system option Constant volume systems are not eligible for rebates since they provide no energy savings W hen you click on this button LabPro displays the R ebate screen T he rebate will be applied only to Constant Volume U sage Based Controls Variable Air Volume or Variable Air Volume U sage Based Control systems Rebate Information Figure 3 4c Edit Menu Edit Costs Energy Costs Rebate Screen Table 3 19 Edit Menu Edit Costs Energy Costs Rebate Screen Selections Rebate Provider Enter any combination of alphanumeric characters for the name of the rebate provider T his name will be used on the Life Cycle C ost report If there is no rebate available leave this field blank CV UBC Rebate Enter a value for the amount of the rebate for your CV UBC system If there is no Amount rebate available leave blank rebat
98. rage cost for reheat equipment per installed CFM Unit Flow or l s or m h including reheat coils piping and all installation labor HVAC Supply AH U Cost per Enter a value for the average cost for supply AH U equipment per installed Unit Flow CFM or l s or m h including air hander fan motor cooling coils filter housing and all installation labor HVAC Exhaust Fan Cost per Enter a value for the average cost for exhaust fan equipment per installed Unit Flow CFM or l s or m h including fan dampers and all installation labor 16 LabPro U ser s M anual Table 3 5 Setup Menu System Defaults Initial Costs Screen Selections HVAC VFD Cost per HP Enter the average cost for variable frequency drive V FD equipment per installed H P or kW including VFD damper and all installation labor costs LabPro will use this value to estimate the total mechanical system initial costs HVAC Duct Cost per Unit Flow Enter a value for the average cost for ductwork per installed CFM or l s or m h including ductwork material costs and all installation labor Duct Cost per CFM or l s or m h includes both stainless steel and non stainless steel duct To calculate this value you must first determine a ratio of stainless steel to non stainless steel duct the cost per CFM or l s or m h of non stainless duct and then determine an average duct cost per CFM or l s or m h Enter a value for the average cost per room for Automatic
99. riable Air Volume supply the amount of supply air delivered to the corridor can vary depending upon the thermal requirements within the space Edit Menu Corridor Add Corridor Attributes Tab You can add copy edit and delete corridors as shown in this screen Edit Corridor General Information Attributes Thermal Profile Floor Area 62 5 m2 ACH FE Temperature Setpoint 22 22 DegC Required Flow hr 019 m3 h Ceiling Height 2 74 m Calculate Maximum Cooling Flow Heat Gain 2153 Walls m2 Maximum Cooling Flow 632 m3 h Figure 3 6b Edit Menu Corridor Add Corridor Attributes Tab Table 3 29 Edit Menu Corridor Add Corridor Attributes Tab Selections Floor Area Enter a value for the corridor s area in square feet or meters M ultiply the corridor s length in feet or meters by its width in feet or meters to get the area in square feet or meters Temperature Setpoint Enter a value for the default room temperature set point in degrees Fahrenheit or Click on And you can Celsius for this corridor Enter a value for the ceiling height in feet or meters for this corridor H eat Gain W atts Sq Enter a value for the total W atts per square foot or W atts per square meter for Ft or W atts m the corridor T he value represents the total heat gain in watts within a corridor divided by the total floor area of the corridor in square feet or meters T otal heat gain includes bo
100. ry This report provides a summary of all the fan systems and central plants on the project T he summary is listed alphabetically then numerically by system name System Summary This report provides a summary of the total flows and systems costs for the system System Diversity Comparison This report provides a diversity comparison for the different types of laboratory airflow control methods It shows the design percent and flow requirements of each of the control methods for the exhaust systen supply system and central plant This report also includes a summary of the three major systen components exhaust supply and central plant 68 LabPro U ser s M anual System Cost Comparison This report lists the initial energy and operation and maintenance costs of all major system components for the project based on the method of lab control being used Financial Analysis Comparison This report provides key financial information to help analyze the financial benefits of different control approaches T he report compares two or three different control approaches T he report totals the annual benefits savings and provides a cumulative present value up to 15 years System Defaults This report provides a summary of the system defaults that are produced when you install LabPro onto a computer You can edit these defaults in the Edit Program D efaults V alues screen and then store them as the program s new defaults for future
101. s eee e ee esses enne enne nete thee tren tene teen trennen eren etre nee nennen nnne 5 Setting Up LabPro on a Hard Drives is eI OP EE eu eee RUNNING Setup addi dier elite ves tp e egt eade ois re e d ie od Running LabPro on a Hard Drive esses eene nnne eene enne carreata trennen rennen Backing Up Your LabPro Project Files eese eene eene nennen trennen eene ene USINGLABPRO d ERE de Ene E ER QN REC RS 2 Starting LabPro Ex cb hele Sd 5 PROJECTIMEND 3 osten tme atu ttam od ad 6 EDIT MENU ss EE P MT 6 ANALYZE MENU A td Sra 7 REPORTS MENO hd co te ee co id e doe i Dei dti talit cde c Or e Rie cb E Te UO 8 GRAPHS amp CHARTS MENU iis etie etr iicet eee t retreat er end E AE teres reir e Ene dT 9 SETUP MENU ER 9 rA INIBE ANTAL DU 10 A N TM 10 CHAPTER 3 EXPLANATIONS OF INPUTS u ccssccsssscsssscsssscsssccssescssscssssssssscsssessssssssesssssssseescsees 11 INTRODUCTION EEE E E EEEE A E E b ite E O 11 SETUP SYSTEMDERAUL TS a O EE E N a des 11 SETUP SYSTEM DEFAULTS GENERAL TAB ccsesessesececeeseaececececseneaaeeeceescseneaeeesececeesessaeeeeeeeesensaaeees 12 SETUP SYSTEM DEFAULTS HOOD USAGE ccsesscccececsessaececececsessaececececsensaaececececsessaaeaeseesesesenseaeees 13 SETUP SYSTEM DEFAULTS FAN AND CENTRAL PLANT coooooooonncnccononnnonononccnonnnnnnnnonconononnnnnnnncocononnnanonos 14 SET
102. s Chapter 2 Getting started and Using LabPro T his chapter covers system requirements setting up running and using LabPro T he sections provide detailed information on how to use all of the functions of LabPro s graphical user interface Chapter 3 Explanations of Inputs This chapter provides a detailed explanation of each input field including how to set up defaults as well as a range for valid input Chapter 4 Analysis and What If This chapter provides a description of LabPro s analysis functions as well as how to use the W hat If function Chapter 5 Reports and Graphs This chapter provides a description of LabPro s output functions a description of what to expect in and how to print each report or graph Fume Hood Usage Diversity Methodology Overview Until recently there has not been a repeatable method for calculating laboratory mechanical system diversity M uch caution and fear exists around this topic T he question has always been H ow can know where to size my mechanical system As a result many people have ignored diversity and installed full capacity mechanical systems that have high initial costs operate inefficiently and are costly to operate and maintain LabPro uses a simple empirically based method that reflects real laboratory situations T he foundation for this methodology is the ability to accurately predict the number of occupied operator present and unoccupied LabPro U ser s M anual
103. s Sisto eR In den gu MI Gai e a era 54 Copy Corrida Oed qup e URN ee e Re t ees 54 DeletesCOFridoE z us ORE ERR oda 54 EDIT EXHAUST FAN ADD EXHAUST FAN SCREEN sese ener enne nene 55 Control Type Parameters iu iie redes HR ERES SEE rae ipe ea ied ines 56 Edit Exhaust RAN see ente P a e aee ea da eee gu dde SEES 56 Copy Exhaust FQN sive ic ti ene rete i dp 56 Delete Exhaust Fan eie O 56 EDIT SUPPLY FAN ADD SUPPLY FAN SCREEN esses eene nennen erret 57 Edit Supply Fan saec te tte Rr e etait ett tr nite e e eet 58 Copy Supply M ia 58 Delete Supply Edo As 38 EDIT CENTRAL PLANT ADD CENTRAL PLANT SCREEN isses ener nnne 59 Edit Gentral Plant sec ee REIR RR ee de 59 Copy Central Plants ee a d e oon sve ede de ee e eiue ener pads 60 Delete Central Pl nt 3 eee ede ea eee eire oci tee ee Eve do Line eee APL nasc e eee e Pv ed 60 CHAPTER 4 ANALYSIS AND WHAT IF Leere eese ee eee eee enero etta seen estan setae e teas tasse ens tease eaae 61 ANALYZE SIMULATE PROJECT etre tere eee tre sino ces Renee PEE ene uen eh Renee MR OPER Poe eee Vds errado 62 Simulate Project Project Summary eese eene teen neen eene eene enne eneene tenete 62 System COSTS ii das os A a RnB A ad ens int ang A aie 63 WHAT EA e tia 64 A RC PP EE x ET 64 Det Parameters Tab ic er ede ier titi 64 AA e ert EE E ete ee E eerte erede eee ei 66
104. seceeeceaeceaeceaecaaecaeecaeeeaeeeneeeseeereerens 33 EDIT EDIT COSTS TABS aii AA 34 Energy COSTS A DIES Ng iue Nep Rei eee BA pr 35 Energy Costs Rebate Information esee eene nennen rennen tne tete teneret neen ne 36 HVAC COS S E ahi ERE e rn EO ipe uin casar d 37 LGD Controls tte tti tete nhau nca tede 39 Operating COStS ee t e v Ede Peter De Ere E D qa pr e qe ele Us 40 Financial ANGLYSI8 MN 42 EDIT MENU ROOM ADD ROOM 55 rrt ens retire rrr DRY once ier terree T Leer eter a 43 Edit Menu Room Add Room General Information Tab eene 43 Edit Menu Room Add Room Ventilation Information Tab eene 45 Edit Menu Room Add Room Thermal Information Tab eee 47 Edit Menu Room Add Room Fume Hoods Tab eese eene ener 49 Edit AA ln the pe e eet eene onset ee eet eerte 50 Copy ROOMS m E 50 Deleite ROOM m E 50 EDIT MENU CORRIDOR ADD CORRIDOR csscesseesseeseeesseeeeseceseeeecseenseceaecnaecaaecaeeeaeeeaeeeeeeeeeeereerees 51 Edit Menu Corridor Add Corridor General Information Tab se 51 Edit Menu Corridor Add Corridor Attributes Tab essen eee 52 Edit Menu Corridor Add Corridor Thermal Profile Tab se 54 FEdIBCOFFIOGOT
105. sents a detailed explanation of each input item for LabPro T he descriptions include a general explanation of the type of data formatting any special features and how the input tems relate to the rest of the program The input fields are organized by screen with each screen presented in the following order Setup System Defaults You can define standard building equipment usage and costs in an Edit Program D efault Values screen N ote that if you change values here you will not affect existing projects Table 3 1 Setup Menu Systems Defaults Screen Selections Initial Costs T ab Define the initial cost of laboratory controls per hood and of the H VAC equipment O perating Costs T ab D efine the annual recurring costs e g maintenance costs and re RS I certification costs FumeH ood Tab D efine hood type sash width sash height min mem E oo rae O D efine the air changes per hour ACH size and heat gain for rooms and corridors Tip if you right click on an empty space in any tab except the G eneral tab a menu pops up to add edit copy or delete whatever is being defined in that tab See Figure 3 1a Setup System D efaults G eneral T ab Screen TT LabPro U ser s M anual Setup System Defaults General Tab Dperating Costs Fume Hoods Room amp Corridor General Hood Usage Fan amp Central Plant Initial Costs Weather Station Design Percentile i Building Hours Exhaus
106. ses standard practices to estimate the initial capital cost of the mechanical and control systems Costs associated with energy savings are another important area that LabPro helps you analyze when designing a laboratory J ust as mechanical system sizing is determined from the design airflow energy costs and savings estimates are calculated from the average airflow requirements U sing the U nited States Climatic C enter s Engineering W eather D ata for the location of the facility along with the calculated average flow requirenent LabPro uses standard ASH RAE calculations to estimate the energy usage and costs for different control approaches Input Overview You can enter data into LabPro by typing values in tables and input fields in each of the program s section tabs LabPro comes pre loaded with default values for most data fidds T here are two kinds of defaults global and project The system defaults allow you to preset the common parameters that are used in the determination of exhaust supply and temperature control applications You can edit these itens individually within a project or globally so that the next project will have most of the input pre entered LabPro inserts the global defaults defined in the System D efaults screen into all new projects as you create them If you make changes to the System D efaults screen after you create a project LabPro will not change the values within your existing projects You can overwrite the
107. sh H eight Specify the sash height for this hood type MaxFlow Cd MinFow 20 LabPro U ser s M anual Setup System Defaults Room and Corridor You can define the default air changes per hour and energy consumption of the rooms and corridors in this project mi Edit Program Default Values x al Y hodis Y Fant Cenal Pan l Room Defaults Corridor Defaults Temperature Setpoint 23 DEG DegCl ACH 4 00 Ceiling Height 274 om Heat Gain 31 53 Watts m2 Floor Area 2787 m2 Floor Area 9230 m2 ACH Occupied 200 ACH Unoccupied son Heat Gain 10764 Walts m2 Offset Percentage no amp Figure 3 1g Setup System Defaults Room amp Corridor Screen Table 3 8 Setup Menu System Defaults Rooms and Corridor Tab Selections Room D efaults Enter a value to bethe default room temperature set point in degrees Temperature Setpoint Fahrenheit C elsius for all new rooms As you define or edit each room change individual room set points in the Add Room or Edit Room screens of the Rooms tab Room D efaults Ceiling Enter a value to be the default ceiling height in feet for CFM or meters for m h H eight for all new rooms As you define or edit each room change individual room ceiling heights in the T hermal Info screen in the Rooms tab Room D efaults Floor Enter a value to be the default floor area in square feet or meters for all new Area rooms As yo
108. sing the formula 131 Efficiency power output kW x100 power input kW Calculate Horsepower LabPro calculates the value using the formula D esign Flow x Static Pressure 6356 x Fan Efficiency x Altitude Correction Factor 13 2 M otor H orsepower Corridor Tab Calculate Cooling CFM LabPro calculates this value using the formula 13 3 Cooling Flow watts sq ft or sq meter carr area sq ft oi sq meter x 3 413 1 08 x AT Supply Air Temp Corridor T emp Calculate Maximum Cooling Flow LabPro uses the equation 13 4 M ax Cooling Flow watts sq ft or sq MERCON area sq ft or sq meter x 3 413 1 08x T Supply Air Temp Corridor T emp Room Tab Calculate Maximum Cooling Flow LabPro uses the equation 15 1 MaxCoolingFlow watty sq ft or sq meter x roomarea sq ft or sa meter x 3 413 1 08x T SupplyAir Temp RoomAir T emp Appendix A Calculations and Equations to automatically fill in the M aximum Cooling Flow field in the T hermal Information portion of the Edit Room Attributes section of the Room tab A 22
109. snsnacecseescesnsnncecscescesseeneesses Chapter Intfoduction 3s i ER UR RETE ee ean ae as dd ee Ni ico eo 1 Chapter 2 Getting started and Using LabPro eese eene nennen rennen 1 Chapter 3 Explanations of Inputs oinei i eese enne ene cnn cone cone cone enne SE ais 1 Chapter 4 Analysis and What If eret rre et eo 1 Chapter 5 Reports and Graphs eese eee enne non enn eene teee trennen nes en rennen enne nnne 1 FUME HOOD USAGE DIVERSITY METHODOLOGY OVERVIEW ccccccccscecssssseeecececsesseaeeeeceecsesseaeeeeseeeeensaaeees INPUT OVERVIEW eerie eerte recae Per Or ORI RETE ERE PER SNP Wei E ee eir OUTPUTOVERVIEW 41 avoue dann neni od n RINT BASIC CONCEPTS 6 oce iiec ter utc aive nia Air Changes per Hour ACH ss iie oe a re B ge ede epi t 2 Room Offset aei aet erede Uie 3 Offset GFM Dora rei eei er ern PER HUI OD ID erum Raten 3 D et Statie Pressure li etse eter eter CATE deep ure eret ete edere ore dee ete eere druide do 3 User Presence Probability te ett ma en WR ERR NA CREER ana dota RU ERES EAE REFERRE devotes 3 User Absence Probability 2 ito e de Eee deed eese rite en e eto eei N RE 3 CATCUDATIONS5 Moe ii dt ne 4 Project Sufmmaky e ss su eden m eee 4 REPOSO id 4 Graplis and Chal AI A ia 4 WAI dd dt A 4 CHAPTER 2 GETTING STARTED AND USING LABPRO ccsccssscsssscssscsscccsscccssscsssssssssseasssssees 5 GETTING STARTED ae tentat mates tui ie mete tee NA PT 5 Computer System Requirement
110. stall the mechanical system Certification Cost per Enter a value for the average cost to re certify a fume hood system with a Phoenix FumeH ood Phoenix Controls valve installed on the hood including material and labor costs LabPro will use this value to estimate the annual operating and maintenance cost and initial cost for a complete Phoenix Controls system LabPro will also use this cost to determine initial costs to install the mechanical system 40 LabPro U ser s M anual Table 3 22 Edit Costs Operating Costs Tab Selections And you can CV Maintenance Cost per Hood VAV Maintenance Cost per Hood CV CV UBC M aintenance C ost per H ood Phoenix VAV VAV UBC M aintenance C ost per H ood Phoenix O perating Costs ATC M aintenance C ost per Room O perating Costs D owntime Cost per H our per H ood Enter a value for the average cost to maintain a constant volume CV or two state fume hood system within a typical laboratory space Include material and labor costs LabPro will use this value to estimate the annual operating and maintenance cost for the complete systen Enter a value for the average cost to maintain a variable air volume VAV fume hood system within a typical laboratory space Be sure to include material and labor costs LabPro will use this value to estimate the annual operating and maintenance cost for the complete systen Enter a value for the average cost to maintain a Phoenix C
111. t z From 03 00 AM Systems Supply S300 Z To 06 00 PM Systems Central Plant 3 Systems 93 00 Figure 3 1a Setup System Defaults General Tab Screen Table 3 2 Setup Menu General Tab Selections W eather Station Use the pull down menu to select the location of your project Cities are listed alphabetically If you cannot locate the exact city use a similar geographic location in the table T his will enter the U nited States Climatic C enter s Engineering W eather D ata for that location LabPro uses this data in its energy use calculations System Sizing Enter a value for the design percentile factor used for calculating exhaust system Exhaust Systems diversity U sing this factor results in a system that will meet systen design fume hood exhaust requirements the specified percent of time Each exhaust system that you define will use this factor System Sizing Enter a value for the design percentile factor used for calculating supply air handling Supply Systems system diversity U sing this factor results in a system that will meet system design supply air requirements the specified percent of time Each supply air handling system that you define will use this factor System Sizing Enter a value for the design percentile factor used for calculating central plant Central Plant diversity U sing this factor results in a central plant that will meet system design Systems cooling heating
112. t N umber of Rooms x Interface C ost per Room 10 11 Phoenix CV Controls Costs N umber of Fume H oods x Phoenix CV Cost per H ood 10 12 Other CV Controls C osts N umber of Fume H oodsx Other CV Cost per H ood 10 13 Phoenix VAV Controls Costs N umber of Fume H oods x Phoenix VAV Cost per H ood 10 14 Other VAV Controls C osts N umber of Fume H oodsx Other VAV Cost per H ood 10 15 Phoenix ACV Controls C osts N umber of Fume H oods x Phoenix ACV Cost per H ood 10 16 Phoenix AFV Controls Costs N umber of FumeH oods x Phoenix AFV Cost per H ood 10 17 Phoenix System Balance C ost N umber of Rooms x Phoenix System Balancing C ost per Room 10 18 Other System Balance Cost N umber of Rooms x O ther System Balancing Cost per Room 10 19 Phoenix System H ood Certification Cost N umber of Roomsx Phoenix System H ood CertificationC ost per Room 10 20 Other System H ood Certification Cost N umber of Roomsx O ther System H ood Certification Cost per Room You enter the Rebate amount on the Initial C osts tab in the main Project screen 10 21 Total First Cost Cooling Plant Equipment Costs H eating Plant Equipment C osts R eheat System Equipment Costs D uct Costs Supply AH U Costs Exhaust Fan Costs VFD Costs Filter Costs ATC Cost ATC Interface Cost Lab Controls Costs System Balance Costs H ood Certification Costs Rebate Amount Calculate Total Annual Maintenance Costs 11 1 ATC Maintenance Cost N umber of Roomsx AT C
113. te how many operators will be in front of a given number of fume hoods for a given percent of the time T his will vary depending on the type of lab and number of users per hood LabPro s default is one user per hood U ser presence probability is defined as the number of hours per day that a fume hood user is in front of his or her fume hood divided by thetotal number of building occupied hours For example one hour per day of fume hood occupancy in a chemistry research facility is assumed T he building is open from 8 a m to 6 p m or ten hours per day Since each fume hood s occupancy is independent from that of other hoods and there is one hour of fume hood occupancy in a ten hour day one hour per day is the average use of a fume hood in the average lab there is a one in ten chance that any fume hood will be occupied T his yields a 10 user presence probability User Absence Probability The user absence probability is defined as the number of hours per day that a fume hood user is away from his or her fume hood divided by the total number of building occupied hours As an example one hour per day of fume hood occupancy in a chemistry research facility is assumed T he building is open from 8 a m to 6 p m or LabPro U ser s M anual ten hours per day Since each fume hood s occupancy is independent from that of other hoods and since there is one hour of fume hood occupancy in the ten hour day there is a one in ten chance that any fume
114. terial and Installation Labor coca Figure 3 4g Edit Costs Financial Analysis Tab Table 3 23 Edit Costs Financial Analysis Tab Selections Click on the economic reports to escalate energy and maintenance costs in future years Base Control System Select from the drop down list the type of airflow controls for your base control system against which you want to compare the life cycle costs initial rate of return IRR and net present value N PV of control systems for options 1 and 2 Y our choices are e CV e VAV PHX CV PHX e VAVUBC e VAV Option 1 Control Sytem Select from the drop down list the type of airflow controls for the option 1 control system against which you want to compare the life cycle costs initial rate of return IRR and ne present value N PV of control systems for the base control system and option 2 Your choices are e CV e VAV PHX e CV PHX VAVUBC VAV O ption 2 Control Sytem Select from the drop down list the type of airflow controls for the option 2 control system against which you want to compare the life cycle costs initial rate of return IRR and ne present value N PV of control systems for the base control system and option 1 Your choices are e CV e VAV PHX e CV PHX VAVUBC VAV 42 LabPro U ser s M anual Edit Menu Room Add Room There are 4 actions grouped together Add Room Edit Room Copy Room and D elete Room Adding editing and copying rooms all use
115. th type and minimum and maximum typical ranges N ote enter only fume hoods that have the potential to be VAV controlled if the fume hood must always run at a constant volume or as a two position valve the total exhaust should be entered under the T otal Ancillary Exhaust Flow Edit Room The Edit Room menu item allows you to edit previously created room specific information for the currently selected room Copy Room The Copy Room menu item allows you to copy the currently selected room Delete Room The Delete Room menu item allows you to delete the currently selected room 50 LabPro U ser s M anual Edit Menu Corridor Add Corridor There are 4 actions grouped together Add Corridor Edit Corridor Copy Corridor and D elete Corridor Adding editing and copying corridors all use the same screens while deleting a corridor is simpler Edit Menu Corridor Add Corridor General Information Tab You can add copy and edit corridors as shown in this screen Edit Corridor General Information Thermal Profile ComdorName Forido2 Service rea Supply AHU an u1 gt Exhaust Fan Efan 1 E Supply Type Figure 3 6a Edit Menu Corridor Add Corridor General Information Tab Table 3 28 Edit Menu Corridor Add Corridor General Information Tab Selections Corridor N ame Enter a name for the corridor using any combination of alphanumeric characters or
116. th sensible and latent heat from people lighting and equipment as well as external heat sources such as sunlight 289 c LabPro U ser s M anual Table 3 29 Edit Menu Corridor Add Corridor Attributes Tab Selections Air Changes per H our ACH Required Flow Calculate M aximum Cooling Flow M aximum Cooling Flow And you can Enter a value to be used as the air changes per hour ACH for this corridor This value represents the flow of air in cubic feet per minute CFM or l s or m h that will deliver the defined air change rate per hour ACH Once you enter a value in the ACH field LabPro automatically calculates the flow units based on the volume of air in the corridor and the watts per square feet or square meters Select this button and LabPro automatically calculates the flow rate of air required to maintain the desired corridor temperature set point based on the W atts per square foot or W atts per square meter entered for this corridor If you do not select this option and the corridor has a cooling requirement you must enter the M aximum Cooling Flow If you do not select this option and do not enter a value in the M aximum Cooling Flow field LabPro will treat the corridor as being constant volume Choose LabPro s default to use C alculate M aximum Cooling Flow based on the watts per square foot or meter It creates a generic profile For a more detailed analysis perform a load profile analysis
117. the volume of all air leaving the space per hour in cubic feet per hour cfm x 60 by the total volume of the space in cubic feet Enter a value in this field and click on the Calculate button LabPro will display the results on the Comparison tab Indicates the air change rate for the building during the unoccupied hours Air change rate is defined asthe ventilation rate of a space divided by the total volume of a space Air Changes per H our ACH can be calculated by dividing the total exhaust rate the volume of all air leaving the space per hour in cubic feet per hour cfm x 60 by the total volume of the space in cubic feet Enter a value in this field and click on the Calculate button LabPro will display the results on the Comparison tab FumeH ood Turn Down Enter a new value in this field and click on the Calculate button LabPro will display the results on the Comparison tab Sash Position U ser Present Sash Position U ser Absent U BC H ood M ode N ormal U BC H ood M ode Standby D esign Percentile Exhaust D esign Percentile Supply D esign Percentile Central Plant Contains the expected sash position when an operator isin front of or present at the hood Enter a new valuein this field and click on the Calculate button LabPro will display the results on the Comparison tab Contains the expected sash position when an operator is away from or absent from the hood Enter a new valuein this field and di
118. ton click in the open area at the bottom to expose a pop up menu Y ou can choose from these four options Add Corridor Edit Corridor Copy Corridor D elete Corridor Table 3 13 Edit Menu Edit Project Corridors Tab Selections And you can AAA Corridor D efaults Enter a value for the default air changes per hour ACH ACH Corridor D efaults Enter a value to be used as the default maximum watts per square foot or meter Heat Gain W atts Sq for all new corridors T he watts per square foot or meter value represents the total Ft or Watty m maximum heat gain in watts within a corridor divided by the total floor area of the corridor in square feet or meters T otal maximum heat gain includes both sensible and latent heat from people lighting and equipment as well as external heat sources such as sunlight 30 LabPro U ser s M anual Central Plants Default Attributes Cooling Efficiency 80 Heating Efficiency Supply Air Cooling Temperature Supply Air Heating Temperature Figure 3 3d Edit Menu Edit Project Central Plants Tab Right button click in the open area on the right to expose a pop up menu You can choose from these four options Add Central Plant Edit Central Plant Copy Central Plant Delete Central Plant Table 3 14 Edit Menu Edit Project Central Plants Tab Selections D efault Attributes Enter the cooling efficiency of the central plant
119. u define or edit each room change individual room floor areas in the Thermal Info screen in the Rooms tab Room D efaults ACH Enter a value for the default air changes per hour ACH for the building during O ccupied occupied hours You can change individual room values in the V entilation screen within the Room tab as you define or edit each room 21 LabPro U ser s M anual Table 3 8 Setup Menu System Defaults Rooms and Corridor Tab Selections And you can Room D efaults ACH Enter a value for the default air changes per hour ACH for the building during U noccupied unoccupied hours You can change individual room values in the V entilation screen within the Room tab as you define or edit each room Room D efaults H eat Enter the value to be used as the default maximum watts per square foot or meter Gain W atts Sq Ft or of all new rooms T he watts per square foot or square meter value represents the W atts m total maximum heat gain in watts within a room divided by the total floor area of theroom in square feet or meters T otal maximum heat gain includes both sensible and latent heat from people lighting and equipment as well as external heat sources such as sunlight You can change individual room values in the Thermal Info screen within the Room tab as you define or edit each room Room D efaults Offset Enter the value to be used as the default room offset CFM or l s or m h CFM or l s or m h
120. upply Valve M ax Max Cooling Demand Flow M ax Cooling Flow 0 ffset 0 ffice Supply Valve M ax Additional Supply Valve M ax Compare Room O ccupied Exhaust Flow to V ent Demand Flow O ccupied or U noccupied M ax Cooling Demand Flow Min Supply Flow gt IfMax3 Vent Demand Flow CV M ax Cooling D emand Flow CV Min Supply Flow gt CV Room O ccupied Exhaust Flow Then Set CV Average Flow M ax3 Vent Demand Flow M ax Cooling D emand Flow CV Min Supply Flow Else Proceed T o next step gt IfMax3 Vent D emand Flow M ax Cooling Demand Flow M in Supply Flow gt VAV Room O ccupied Exhaust Flow Then Set VAV Average Flow M ax3 Vent Demand Flow M ax Cooling Demand Flow M in Supply Flow Else Proceed T o next step IfMax3 Vent Demand Flow M ax Cooling Demand Flow M in Supply Flow gt CV UBC Room O ccupied Exhaust Flow Then Set CV UBC Average Flow M ax3 Vent Demand Flow M ax Cooling Demand Flow M in Supply Flow Else Proceed T o next step gt IfMax3 Vent Demand Flow M ax Cooling Demand Flow M in Supply Flow gt VAV UBC Room O ccupied Exhaust Flow UULU Appendix A Calculations and Equations Then Set VAV UBC Average Flow M ax3 Vent D emand Flow M ax Cooling Demand Flow M in Supply Flow Else Proceed T o next step If Vent Demand Flow M ax Cooling Demand Flow and M in Supply Flow equal values from previous hour or V ent Demand Flow and M in Supply Flow equal values from previous
121. using data specific to this project 53 LabPro U ser s M anual Edit Menu Corridor Add Corridor Thermal Profile Tab Edit Corridor 6 ps En mel mol a o mb f ofl ofl of o mi wp Sop sp sy S Dl opu T m ps e Figure 3 6c Edit Menu Corridor Add Corridor Thermal Profile Tab Table 3 30 Edit Menu Corridor Add Corridor Thermal Profile Tab Selections Thermal Demand Flow Each hourly value represents a percentage of maximum cooling flow required for varying sensible and latent heat loads in a space During a 24 hour period a room will have varying cooling flow requirements as a result of the heat generated by people lights and equipment as well as building skin loads which are a function of geographic location You may choose to use the default values by entering the geographic location or override some or all of the displayed values based on a more detailed analysis of cooling requirements Edit Corridor TheEdit Corridor menu item allows you to edit previously created corridor specific information Copy Corridor The Copy Corridor menu item allows you to copy a previously created corridor Delete Corridor TheD el amp e Corridor menu item allows you to delete a corridor 54 LabPro U ser s M anual Edit Exhaust Fan Add Exhaust Fan Screen Edit Exhaust Fan Bl x General Information i Horsepower Fan Name EFan 3 x Calculate Hors
122. y control system type It usesthe ASH RAE simplified bin method to calculate primary cooling and heating energy use LabPro uses the average flow for each system type because cooling and heating energy calculations are linear It also calculates fan energy hourly based on flow requirements and calculates reheat energy hourly using the difference between actual flow and required cooling flow See ASH RAE Fundamentals 1994 for more details on the simplified bin method First Cost Calculations LabPro estimates mechanical system initial costs based on design flows by control system type and cost inputs It calculates system design flows based on your input You also enter information about the estimated cost of each system component typically based on flow requirements LabPro then combines these two pieces of information to produce an estimated mechanical system initial cost Life Cycle Cost Calculations LabPro calculates life cycle cost for selected control system options O n the O perating C osts tab of the System D efault screen you select three laboratory control system types as options for comparison Enter an expected inflation rate a number of years for the analysis period and the customer s hurdle rate for investments LabPro will calculate the total first costs first year energy costs first year non energy operating costs and the total operating and maintenance costs for the analysis period N et Present Value Internal Rate of Return a
123. y for any damages whatsoever arising out of the use of or inability to use the software including without limitation damages or costs for loss of profits business goodwill data or other assets or computer programs or for incorrect data or results even if phoenix has been advised of the possibility of such damages Some jurisdictions do not allow exclusion or limitation of liability for consequential or incidental damages so this limitation may not apply to you COPYRIGHT The copyright trade secrets and all other intellectual property rights in the Software and documentation including any images photographs animations video audio music and text incorporated in them are owned by Phoenix or its suppliers and are protected by the copyright and other laws of the United States and other countries and by international treaty provisions Phoenix retains all rights not expressly granted in this Agreement OTHER RESTRICTIONS You may not modify adapt decompile disassemble or otherwise reverse engineer the Software except to the extent this restriction is expressly prohibited by applicable law You may not loan rent lease or license the Software but you may permanently transfer your rights under this Agreement provided you transfer this Agreement the Software and all accompanying printed materials and retain no copies and the recipient agrees to the terms of this Agreement Any such transfer must include the most recent update and all prio
124. y of the project s defaults that have been entered while the user is in the project The system defaults that are produced when you install LabPro onto a computer will be superceded for this project and only this project by any changes you made in the Edit Project screen Room Balance Report This is a report that identifies the four critical conditions for room balance The upper section of the report details the information from the room attributes screen Each equation illustrates how the supply into the room shall equal the exhaust out of the room by identifying the flows of each supply and exhaust source T he two equations within each section are identified by and A and a B The A equation looks at the condition when the office and additional supplies are at their minimum flow rate while the B equation looks at the condition when the office and additional supplies are at their maximum flow rate The exhaust portion is then totaled for each line of equation Room Detail Report This report provides a summary of all the attributes for an individual room Fume Hood Summary This report provides a summary of all the fume hoods on the project T he summary lists numerically then alphabetically by Room N ame Within each room the hoods are listed alphabetically then numerically by hood name Corridor Detail Report This report provides a summary of all the attributes and flows for an individual corridor Fan Systems Summa
125. y them to a floppy disk using the DOS copy command drag and drop in Windows Explorer or File M anager in Windows Using LabPro Starting LabPro To run the program double click on the LabPro icon from within the LabPro Group W hen you launch LabPro it will show a startup screen while the program is loading T his screen shows the program version number the name of the person to whom it is licensed and the corresponding registration number O nce loaded LabPro displays an empty screen with only the toolbars showing Begin by clicking on Project on the menu bar to display the Project menu as shown in Figure 2 1 LabPro U ser s M anual Project Menu Click on Project on the menu bar to display the Project menu as shown in Figure 2 1 C LabPro Projects project 1 Ipr Lo A Meal vi u o Derant PELD Saye minjan Mijke Figure 2 1 Project Menu Table 2 1 Project Menu Selections Edit Menu Click on Edit on the menu bar to display the Edit menu as shown in Figure 2 2 If you choose you can right button click the mouse to bring up the Add Edit Copy and D elete choices instead C LabPro Projects project 1 Ipr z col als wea 2 xe Central Plant gt Figure 2 2 Edit Menu LabPro U ser s M anual Table 2 2 Edit Menu Selections And you can Edit Project Enter project locations project owner owner project address and select the building occupancy hours and weather site location Edit
126. you can accept the default that LabPro automatically assigns a default number Corridor 1 You can change or add to this number If you use a number in a corridor s name such as Corridor 1 and you have more than ten corridors use a leading 0 before the single digit i e Corridor 01 instead of Corridor 1 so that the corridors will remain sequentially listed i e Corridor 01 will come before Corridor 10 Service Area Enter any combination of alphanumeric characters as a description of the area associated with the corridor Supply AH U Use the drop down list to select the supply fan that serves the corridor You can add edit delete or copy a supply AH U in the Supply AH U Tab You must associate each corridor with a specific supply fan serving the building Exhaust Fan Use the drop down list to select the associated exhaust fan that serves the corridor You can add edit delete or copy an exhaust fan in the Exhaust Fan T ab You must associate each corridor with a specific exhaust fan serving the building Supply T ype Select the type of supply control method that you will use in this room The two control types are CV constant volume and VAV variable air volume 51 LabPro U ser s M anual Constant Volume CV With a Constant Volume supply the amount of supply air delivered to the corridor will be constant regardless of the thermal requirements within the space Variable Air Volume VAV With a Va

Download Pdf Manuals

image

Related Search

Related Contents

Copyright © All rights reserved.
Failed to retrieve file