IPMv2 Technical Data Sheet

image

Contents

1. 3 to 10 times in 0 5 increments times full load Trip Time 20 40 60 80 100 120 160ms Selectable from 20 to 80 in 10 increments Trip Delay 800ms Selectable from 32 to 96 in 8 increments and none Trip Delay 800ms Earth Leakage Protection Earth Continuity Protection Short Circuit Protection Under Voltage Protection Under Current Protection Insulation Test Lockout resistance is selectable at 1 2 5 10 20 Meg Ohm and none i 1 O O O O C rrent balance Trip Settings 5 10 20 50 and off Trip Delay 2s Trip Setting 10 to 250 and off Trip Time 100ms to 5s Back EMF Timer Trip Delay Settings 2 5 10 15 and 20s Machine Numbers Can be allocated from 1 to 40 No Pulses Setting 1 to 6 any none Time On Time Off Setting 0 6 0 8 1 0 1 2 1 5 2 0 2 5 and 3 0s Snore Function None 5 10 15 20 8F 15F 20F 30F 60F Time in Minutes F Fixed delay Outputs Residual Current Burp Function RS485 Slave MODBUS Baud Rate 1200 to 19200 Monitoring 4 20mA Analogue Output lave O L E L MQ MCR 1 NO 1 C O CBR and ALM 1 C O 5A 190VAC 100VA max Communications Relay Contacts Ordering Information Part Number Description 121503 IPM Integrated Protection Relay 24V 121504 ITM 415 Insulation Test Module 121505 ITM 1000V Insulation Test Module 121506 RTM Remote Termination Module 101703 88mm Earth leakage Toroid 141548 Current Transformer 100 1 500 5 101272 Current Transform
2. TECHNICAL DATA SHEET wo N 6 AMPCONTROL INTEGRATED PROTECTION RELAY IPM Version 2 Applications The IPM Integrated Protection Relay provides all the necessary protection functions to control the various types of mining machinery The default Status Screen allows unskilled personnel to determine what is required to apply power to the machine See IPM User Manual 121549 for full details Alarms Alarms can be programmed to warn of a pending trip condition Earth Leakage The earth leakage protection function uses a 1000 1 core balance toroid to measure the earth fault current A Residual 4 Current Device RCD operating characteristic is provided with adjustable trip sensitivity and time delay When the earth leakage reaches 100 of the selected trip level a trip occurs START eser STOP The higher the fault current measured the faster the trip time and vice versa See IPM User manual 121549 for full details Earth Continuity The earth continuity function tests for the continuity of the earthing between the outlet and the machine via the pilot core in the trailing cable The pilot core is also used to transfer data when a Remote Termination Module is used to achieve Machine Data Transfer Short Circuit The short circuit function has a definite time characteristic If the current exceeds the selected level for the pre set time then a trip occurs The short circuit function trips the CBR relay which in turn can
3. ased e Status messages to indicate what is required to energise the outlet Product description The Ampcontrol IPM Integrated Protection Relay Version IPM V2 0 is an intelligent protection relay based on microprocessor technology All of the tripping logic and outlet control is performed by the microprocessor so that virtually no external control is required The IPM Integrated Relay provides the necessary functions required for protecting electrical outlets supplying underground mining machinery powered by reeling or trailing cables in the metalliferous industry The relay can also be used to provide optimum overload protection of motors used on conveyors pumps fans and compressors All of the protection functions are combined into a compact plug in unit which can be easily changed out to minimise down time in the event of a problem with the relay The IPM Integrated Protection Relay can provide Machine Data Transfer through the use of a Remote Termination Module RTM connected between the pilot and earth at the machine end of the trailing cable Through the use of the RTM the relay parameters are automatically up loaded from a remote machine when a cable is inserted into a power outlet The IPM s remote start capability can also be access by use of the Ampcontrol s Remote Termination Module A RS485 Modbus communication port is available that can be connected to Motor Starter PLC s or a central monitoring system for continuous monito
4. er 1000 1 121549 IPM User Manual
5. ring and fault finding The IPM Relay provides an isolated 4 20mA analogue output to continuously monitor Average Current Overload Earth Leakage and the Insulation level of the relay An automatic Insulation Test can be initiated once all starting conditions are met A high voltage DC Insulation Test to earth of the cable is carried out If the result of the Insulation Test is above the preset resistance level the IPM s MCR relay energises which in turn closes the main contactor A manual Insulation Test is provided as a maintenance fault finding tool A Burp Function allows for the progressive inflation of ventilation bags tubes by pulsing the motor contactor controlling a ventilation fan several times at start up A Snore Function is available for controlling pumps the Snore function automatically stops the output on detection of low current and restarts the outlet after a fixed or automatically adjustable time delay The standard current transformers supplied with the IPM Integrated Protection Relay enables protection of motors with full load currents ranging from 0 5A to 640A The selected full load current can be set to one of 224 values across the range The IPM Relay can be set to automatically reset or require a manual reset by pressing the keypad RESET button or activating the RESET digital input following an overload trip condition once the thermal accumulator falls below the set value The IPM Relay
6. s 50 event log and adjustable settings are battery backed A four line 20 character backlit LCD display combining with a keypad provides an easy to operate user interface The display provides easy access to all available information A simple procedure allows adjustment of the relay s settings The IPM Relay is housed in an enclosure suitable for flush mounting in a 135mm square cut out and has robust plug in connectors on the rear of the relay Note Torque setting for mounting screws on Main Mounting Bracket 0 8Nm Protection Functions The Ampcontrol IPM Integrated Protection Relay provides protection functions for e Earth Leakage e Overload e Contactor Fail e Earth Continuity e Short Circuit e Residual Current e Phase Current Balance e Under Voltage Under Current General Auxiliary Supply Volts 24VAC DC 20 Power Consumption lt 10W Protection Settings Trip setting 25 500mA and off Time Delay Instantaneous lt 80ms 50ms 150ms Reset if resistance is lt 45 ohms Trip if resistance is gt 45 ohms Trip Time Delay 80 120 160 200 300 400 500ms Shunt Leakage Trip if lt 1500 ohms Current Range 0 5 to 640 224 steps See Overload Protection Section above Trip time 6x FLC 3 4 5 6 7 8 10 12 14 16 20 24 28 32 40s Overload Protection Overload Reset Level 30 40 50 60 70 80 90 A 30 A 40 A 50 A 60 A 70 A 80 A 90 Cooling Multiplier 1 1 5 2 2 5 3 4 5 Trip Setting
7. trip the main circuit breaker Main Contactor Fail The Main Contactor Fail MCF protection operates if the Main Contactor MC fails to function by either 1 Failing to open when required 2 Failing to maintain insulation across the contacts when the contactor is open Residual Current The three phase current signals are summed electronically in the IPM Relay to produce a residual current signal that can be used to detect earth fault currents See User Manual 121549 for full details Remote Start This functionality is similar to that of the IPB C D The remote start can be set in two modes In one mode it is always active and in the other mode it is active only when the auxiliary digital input is closed Overload Protection Optional CT s can extend the relays current range e 1 100 0 5A 64A e 1 1000 5 125A 640A Features e Automatic and Manual High Voltage e Diode or Remote Termination Module Insulation Test operation e Machine Recognition e 50 Event Log with real time clock e RS485 communication port interfaces to e Relay amp Digital Input Status to aid fault SCADA system via Modbus protocol finding e 420mA Analogue output Local or remote operation e Thermal modelling Plug in for quick change out e User friendly Relay and Remote Burp Function for controlled fan starting Termination Module are programmed from Snore Function for controlling pumps the IPM Display Remote Start Capability e Microprocessor b