Temperature Control of A Gas Flow

image

Contents

1. nitens 24 PE TUDE eR 26 2 5 Gas Flow Apparatus 28 2 5 1 Optimizing the Omega cn9000A eis eeesee tentent tnnt tent tents ttt tentato nis 28 2 5 2 Explanation the Omega PID controller esset tnnttnntnnn 30 2 5 3 AUtO tU nIng ite deu de oet on ete o dfe s utor 36 2 5 4 Manual Tuning dte erat tie deed b de e debe erre e etel eee 37 3 Methodology b a e RE RR RAI etae Pre x dde e DR Rede 39 3 1 Ife tlie 39 3 2 fea ba iced ote deaurato Doe Seen rad rue 40 3 2 1 Manual Tuning iiie c te nd t de d ER e a e 40 3 2 2 PALIN 41 9 3 eee ie o dau cus diee ea deu ra eru petet a 42 3 3 1 LabVIEW OVerview i depo de ccu ed ER aed rg 42 3 3 2 LabVIEW Virtual Experiment essent tnnt a i 42 3 3 3 LabVIEW Physical Experiment se sseiee tentent tnnt tente tnnt natat tton testen 54 3 3 4 Experimentation with LabVIEW 59 24 Vortex Tube iniecit edidit ete i eni e Sed n Eie obe 60 Results and DiSCussloT istae eet peer dee tre d annie rie b reduc edd arg 64 4 1 Manual Tuning Results
2. 112 6 5 e sacra ed ertet es 114 6 5 1 Energy Balance Derived iinitan tents 114 6 5 2 Entropy Equation Derived ses iessee tette ttnnttnn oa 114 6 6 RaWwoDatao de aeu ea ane ieee 115 6 6 1 Omega Tuning c etate epe hc d ue dete ee de pei eee 115 6 6 2 Muro r M 120 6 72 References eti 122 Table of Figures Figure 1 Picture of the RPI concentration experiment with equipment labels Bequette et al 2000 Vioc pa fb Mod RA ec pA va eth en Md 5 Figure 2 Process Schematic of the Villanova University experiment 7 Figure Block diagram depicting the cooling system for a house ee 10 Figure 4 Process variable response to varying proportional gains Wescott 2000 15 Figure 5 Process variable response to varying integral gain terms Wescott 2000 16 Figure 6 PID process variable response curve showing integrator windup Cooper 2008 17 Figure 7 simple operation in LabVIEW s block diagram where the numbers 2 and 4 are added together The symbol to the right is an indicator which appears on the front 21 Figure 8 The same sim
3. esses tte tren ttn tante ttt tenait 64 42 LabVIEW nce ti a D ien tee i eb ro Ri d cbe EUER a Eee ciel 66 4 2 1 Virtual LabVIEW e i eti hated he nde Ue a Ae ett deus 66 4 2 2 Physical LabVIEW BIB ttt t fttt ttt tpe ente 71 43 Vortex Tube citet o odo Sa o Sti ibo ibo ecce 74 4 3 1 Calculated Hot Temperature vs Recorded Hot Temperature sss 74 4 3 2 Calculated Cold Mass Flow vs Recorded Cold Mass Flow sss 77 4 3 3 Digne 80 ro ete 83 Sateen cig etes tueatur ers 84 61 Classroom a a Ed dados 84 6 1 1 Classroom Procedures for PID 84 6 1 2 Classroom Procedures For Vortex Tube esiste 97 6 2 _ a a a aco o n eee Fate e a 100 6 2 1 DEfINItl EL 100 6 2 2 M M 103 6 3 Schematiczissu etd aie de tede labente ebd tote idt lob itd 104 6 3 1 Gas Flow Apparatus esent tente 104 6 3 2 Wiring Diagram teet e tb ere t ted Cete ie eei ern 105 6 4 LabVIEW eite ode ed seo de be iei nated i e eec pe toin 106 6 4 1 eee teneret a uie p eene dette 106 6 4 2 Idee Cc E
4. 2012 from http www controlguru com 2008 021008 html Desborough L amp Miller R 2002 Increasing customer value of industrial control performance monitoring Honeywell s experience Proceedings from the Sixth International Conference on Chemical Process Control AIChE Symposium Series 98 326 Gao C Bosschaart J Zeegers C H amp de Waele A T A M 2005 Experimental study on a simple ranque hilsch vortex tube Cryogenics 45 1 173 183 Hilsch R 1947 The use of the expansion of gasses in a centrifugal field as cooling process The Review of Scientific Instruments 18 2 108 113 Johnstone A H amp Al Shuaili A 2001 Learning in the laboratory some thoughts from the literature University Chemistry Education 5 Love J 2007 Process Automation Handbook A guide to Theory and Practice London England Springer Verlag London Massa John 2005 Pulse Width Modulation PWM Tutorial Datadog Systems web Retrieved 10 Apr 2012 from http www datadog com pwm tutorial pdf Ming da amp Xin jian 7 2006 A simple auto tuner in frequency domain Computers and Chemical Engineering 30 4 581 586 Retrieved on Mar 13 2012 from http www sciencedirect com Motion Systems Design Staff 2000 Oct MS 101 Pulse width modulation Motion Systems Design Penton Publications Cleveland Ohio Retrieved 5 Apr 2012 from http fab cba mit edu classes MIT 961 04 top
5. gt 77 For discussion the differences in temperature will be represented by dimensionless value theta 7 i 8 4 5 Te Ti i So that dic 18 0 4 6 lt 9 1 other values were recorded using equipment Refer to Appendix 6 3 for details as to how each variable was recorded Below is a chart comparing the values of recorded cold mass flow to calculated cold mass flow 140 Recorded mc Calcularted mc 3 z c z 5 o FIGURE 37 RECORDED COLD MASS FLOW VS CALCULATED COLD MASS FLOW BY TRIAL 78 The recorded mass flow was always greater than calculated mass flow This is because calculated mass flows depend on the temperatures from the thermocouples Any heat loss from the vortex tube to the surroundings will increase the value of 0 the dimensionless temperature difference As seen in previous equations this will multiply the inlet mass flow by a number less than 1 which will decrease the predicted cold mass flow rate m Percent Difference 1 3 5 7 9 1113 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 Trial FIGURE 38 PERCENT DIFFERENCE BETWEEN RECORDED AND CALCULATED COLD MASS FLOW The percent differences were slightly higher than the differences found between calculated and recorded hot temperatures The average percent was 7 7296 The standard deviation of the percent difference was 4 11 This means th
6. Temperature Control of a Gas Flow A Major Qualifying Project Submitted to the Faculty of Worcester Polytechnic Institute In Partial Fulfillment of the Requirements for the Degree of Bachelor of Science Thaddeus Adams Ben Baranowski Rodrigo Ma Date April 26 2012 Advised by William M Clark TABLE OF CONTENTS Executive Summary ausu ae eco die radere ch dette delve PER dudo a det caa vi T Introductio M M 1 2 Background iiie ed ah e n cde ce ig Eo 3 2 1 Existing Classroom Experiments asini diiidan tnnt tento ttes 3 2 1 1 Studio Control Lab with PID Controller eene nnne 3 2 1 2 University of Loughborough Learning Object 5 2 1 3 Process Control Laboratory Experience at Villanova 6 2 1 4 University of Kentucky s Chemical Process Control Course 8 2 2 Process Control 2e tele ied t dedi sia E C etude ee c Dude ne ANAN 8 2 2 1 Types of Control eto e A atas a s EA AR 10 2 2 2 cnet 12 2 2 3 IM PMID 19 2132 oett ce pete te ince tue fate d fibus 20 2 3 1 Constructing DR 20 2 3 2 Signaling ceci stated n eu iato ron Ete ate desuper da nd 23 2 3 3 Pulse Width Modulation
7. into the swirl chamber resulting in a vortex The understanding of the in depth fluid mechanics that cause this vortex is beyond the scope of this course 97 Compressed air Throttling valve http www pdbuchan com ranque hilsch ranque hilsch html The diagram above shows the Vortex Tube and a simple explanation of how it works A control valve at the end of the hot leg determines the quantity and temperature of both streams This particular experiment does not need a specific position of the valve but it does need to be open some hot air must be flowing out of the hot leg The First Law of Thermodynamics From the Applied Chemical Engineering Thermodynamics class you should be familiar with the three laws of thermodynamics This experimentis specifically concerned with the first law With the temperatures that the Vortex Tube allows on both streams it gets hot enough to boil water at the hot end and freeze water at the cold end How is this possible This would seem to violate the first law of thermodynamics which postulates the conservation of energy In order to prove that the Vortex Tube is not violating the First Law of Thermodynamics an energy balance needs to be performed around it Measurements You need to evaluate what measurements to take in order to perform the balance At your disposal you have thermocouples and rotometers both before and after the Vortex Tube Hint Don t forget to correct the
8. remembers The function was found to already be set to the absolute minimum at 12 seconds Changing this to a higher value consistently resulted in a longer rise time and a longer settling time The results of changing this function are shown in Table 10 TABLE 10 RESULTS WHEN THE INTEGRAL TIME IS CHANGED Integral Time Results Setting Parameter Comparison to Initial Initial 8 8 12 Sec N A Run 1 2 8 30 Sec Long Settling Time Run 2 3 8 1 Min Longer Settling Time Run 3 0 8 5 Min Longest Settling Time The derivative band was the last parameter studied to see if it had any effect on goal 4 This parameter was also set to the minimum possible time It was found that any increase in this function would result in integral destabilization Results are summarized in Table 11 TABLE 11 RESULTS WHEN THE DERIVATIVE BAND IS CHANGED Derivative Band Results Setting Parameter Comparison to Initial Initial 7 6 1 Sec N A Run 1 11 6 15 Sec Large Integral Destabilization Run 2 10 6 7 Sec Integral Destabilization 65 It was found that the initially selected parameters Integral Time Derivative Band Proportional Band were already optimized for the system These values are the currently used parameters for the controller 4 2 LABVIEW 4 2 1 VIRTUAL LABVIEW PID The final product of the virtual VI was a functioning digital replica of the existin
9. 12S DERIVATIVE TIME 1S 116 e o 100 150 Time seconds FIGURE 44 P BAND 100 INTEGRAL TIME 125 DERIVATIVE TIME 15 Temperature C 100 Time seconds FIGURE 45 P BAND 14 INTEGRAL TIME 305 DERIVATIVE TIME 15 117 o o o o o 9 5 N m 0 50 100 150 200 250 300 350 400 Time seconds FIGURE 46 P BAND 14 INTEGRAL TIME 60S DERIVATIVE TIME 1S Temperature 9 600 800 1000 1200 1400 Time seconds FIGURE 47 P BAND 14 INTEGRAL TIME 3005 DERIVATIVE TIME 1S 118 gt 100 Time seconds FIGURE 48 P BAND 14 INTEGRAL TIME 125 DERIVATIVE TIME 75 119 6 6 2 VORTEX TUBE Trial Os Pai mV C T4 C T C 1 0 3 65 7 21 6 45 8 0 33 15 2 18 6 2 0 305 65 7 21 6 45 4 0 325 18 75 18 3 3 0 29 59 7 20 2 5 7 41 8 0 28 19 19 6 3a 0 29 59 7 20 4 5 8 41 9 0 28 17 4 19 3 3b 0 29 59 7 20 4 5 9 42 0 28 16 1 19 3c 0 29 59 7 20 4 5 8 42 0 28 15 4 18 6 3d 0 29 59 7 20 4 5 7 42 0 28 13 9 18 1 3e 0 29 59 7 20 4 5 6 42 1 0 28 13 2 17 9 3f 0 29 59 7 20 4 5 6 42 1 0 28 12 2 17 4 3g 0 29 59 7 20 4 5 8 42 2
10. 2005 Although the calculations predicting the behavior of the airflow inside vortex tubes can become quite complex the basic theory is relatively simple The tube itself is generally T shaped with a spiral coil spanning the length of the top of the T and the air inlet located at the bottom of the T This coil is referred to as the swirl chamber The inside diameter of the coil increases towards one end of the tube out of which hot air is exhausted This end of the vortex tube is referred to as the hot end A control valve is located after the coil in order to vary the flow rate of hot air The opposite narrower end ofthe coil becomes the cold end as cold air blows through it Figure 11 displays a simple sketch of the vortex tube currently installed in the Unit Operations Laboratory 26 Compressed Air in 70 F 21 1 C Hot Air 230 F 110 C gt 00000000T MUG GU o Cold Air 40 F 40 C Control Valve FIGURE 11 SKETCH DISPLAYING AIRFLOW THROUGH AN AIRTX VORTEX TUBE AIRTX INTERNATIONAL 2007 As pressurized air is fed into the vortex tube inlet the coil forces the faster molecules to flowina spiral around the outside of the coil towards the wider end Since the faster moving molecules will have more thermal energy the tube on the same side as the wide end of the coil will have air exit at a higher temperature than that of the inlet The suction created by the f
11. 48 Increased integral term and decreased derivative terms ss 69 Final touches to tuning eiiis a e de Ege cbe ER cb 70 lt 72 Omega PID vs Labview dentes to bee ec 73 Recorded Temperature vs Calculated Temperature by Trial 75 Percent Difference Between 76 Recorded Cold Mass Flow vs Calculated Cold Mass Flow 78 Percent Difference Between Recorded and Calculated Cold Mass Flow 79 Recorded vs Calculated Cold Mass Flow Through Drift e 81 Recorded Temperature vs Calculated Temperature Through 82 P band 0 5 Integral Time 12s Derivative Time 1s see 115 P band 7 Integral Time 125 Derivative Time 15 116 P band 20 Integral Time 12s Derivative Time 1s esee 116 P band 100 Integral Time 12s Derivative Time 1s ees 117 P band 14 Integral Time 30s Derivative Time 1s sees 117 P band 14 Integral Time 60s Derivative Time 1s eese 118 P band 14 Integral Time 300s Derivative Time 1s ees 118 P Band 14 Integral Time 12s Derivative Time 7s sse 119 iv Table of Tables Table 1 Available Functions
12. 9 0 29 59 7 20 4 3 1 35 3 0 23 9 6 14 3mm 0 29 59 7 20 4 2 9 33 5 0 22 9 8 14 0 29 59 7 20 4 2 9 30 9 0 2 10 14 2 0 29 59 7 20 4 3 1 30 2 0 21 10 2 14 4 0 29 59 7 20 4 2 9 30 1 0 195 10 4 14 4 0 29 59 7 20 4 2 6 29 0 19 10 7 14 6 3rr 0 29 59 7 20 4 2 6 28 8 0 19 10 9 14 7 3ss 0 29 59 7 20 4 2 2 28 5 0 18 11 1 14 8 0 29 59 7 20 4 2 2 28 5 0 19 11 3 13 9 3uu 0 29 59 7 20 4 1 8 29 1 0 18 11 8 13 3w 0 29 59 7 20 4 2 1 28 9 0 19 11 7 15 1 121 6 7 REFERENCES Abdulwahed Nagy 7 amp Blanchard R 2009 Online laboratories embracing the reusable learning objects metaphor Twentieth Annual Conference of The Australian Association for Engineering Education Adelaide Australia Acroname Robotics 2012 Description of pulse width modulation Acroname Robotics Retrieved from http www acroname com robotics info concepts pwm html AiRTX International 2007 Catalogue 29 3620 Wiehe Road Cincinnati OH 45327 AiRTX International Retrieved 10 24 2011 from http www axxosales com Newsdocs AiRTX Catalog 29 pdf AiRTX International n d AiRTX stainless steel vortex tubes 6320 Wiehe Road Cincinnati OH 45327 AiRTX International Retrieved 10 24 2011 from http site wtech services com clients wtechservices Downloads HeatingCooling612200924135PM2 pdf Ang K H Chong G C Y amp Li Y 2005 PID control system analysis design and
13. CSTR 10 Manual V alves For Trimming FIGURE 1 PICTURE OF THE RPI CONCENTRATION EXPERIMENT WITH EQUIPMENT LABELS BEQUETTE ET AL 2000 While replication and testing of the RPI laboratory process is not a goal of this MQP the RPI lab is a good example of a process control experiment that is both scientifically sound and relatively simple to operate 2 1 22 UNIVERSITY OF LOUGHBOROUGH LEARNING OBJECT EXPERIMENT The University of Loughborough currently instructs their engineering students in process control via learning objects A learning object LO is defined by Loughborough s faculty as a digital or web based resource that can be used and re used to instruct students in certain learning activities Abdulwahed et al 2009 The particular learning objects used by the University of Loughborough are online laboratory learning objects OLLO which are used to remotely control an experiment One of the strengths behind Loughborough s OLLO is that it cannot only control an experiment in the laboratory remotely but can also virtually mimic an experiment based on past runs This allows students to get an accurate first estimate of how their process will respond to different control settings before running the experiment The OLLO used by the University of Loughborough controls the level of water in a tank In this experiment both liquid flow rate and liquid levels are variables manipulated by students Students first attempt to
14. TO Ts THE VALUE OF T IS USED AS THE VALUE OF T FOR THE NEXT ITERATION The entire program was enclosed in a while loop with a few exceptions This loop was given a stop control which placed a button on the front panel This stop button allowed the user to end the simulation by halting the whileloop The number of iterations of the while loop were recorded and displayed as Data Points on the front panel A time delay of 200 milliseconds between iterations was created which corresponds to a sampling rate of five data points per second The Temperature Setpoint and Output Q variables were all bundled together into a cluster From this cluster a graph was created on the front panel Numerical indicators of the values of each variable at the current iteration were also included on the front panel three variables were programmed to be graphed simultaneously which allowed the user to view the quality of the PID control on the simulated airflow The property node History Data was created for the graph placed outside the while loop and given a constant input This purpose of this property node is to reset the graph history every time a new simulation was run Temperature C FIGURE 16 ALL THREE VARIABLES ENTER A CLUSTER AND ARE GRAPHED IN REAL TIME 45 FIGURE 17 THE PROPERTY NODE CREATED TO CLEAR THE GRAPH S HISTORICAL VALUES It is recommended that the students using this VI set the temperature set point to 70 C and the
15. a rapid change from ON to OFF will require a great amount of resistance and can be damaging to the equipment It is possible to control large voltages by using smaller voltage and a solid state relay which basically 25 acts as an ON OFF switch between a high voltage device and a low voltage control device Motion Systems Design Staff 2000 This type of signaling can be used with an analog based PID controller With PWM signaling the PID signal can be interpreted correctly by the digital device With proper tuning of the PID the device will turn on and off rapidly while approaching the set point allowing for smooth control 2 4 VORTEX TUBE The WPI chemical engineering department has recently purchased a Model 20025 vortex tube from AiRTX International This vortex tube has been added to the gas flow apparatus but has never been used in a Unit Operations laboratory Vortex tubes take in compressed air and separate the air into hot and cold streams Thermocouples currently record the inlet outlet cold and outlet hot stream temperatures The cold fraction can be changed by varying a control valve on the hot stream exit The cold fraction is the ratio ofthe cold mass flow to the hot mass flow Cold fraction is examined in greater detail later in this document The vortex tube sometimes referred to as a Ranque Hilsch tube was discovered by Georges Ranque and was later examined and described in detail by Rudolf Hilsch Gao et al
16. is constant to four significant figures from 15 to 70 degrees Celsius and can be assumed to be constant in the airflow experiment The value of m was found via Equation 3 3 m Q p 3 3 where Q is the volumetric flow rate of air in m3 s and p is the density of air in kg m at 70 degrees Celsius The volumetric flow rate of air was taken from a representative run during experimentation The results of Equations 3 2 and 3 3 are shown in Table 5 Since the inlet temperature is constant at 20 C and the set point is constant at 70 C Equation 3 2 applies for every second of the heater s operation This requires the heat transfer qu to be independent of the while loop s iterations For this reason itis helpful to define qi terms ofa heat transfer coefficient Equation 3 4 was derived from Newton s Law of Cooling 48 m 5 where A is internal surface area of the gas flow apparatus heater The results for Equation 3 4 are shown in Table 5 The derivation of Equation 3 4 can be found in Appendix 6 4 The temperature T after each iteration of the while loop is given by Equation 3 5 q2 A aT 3 5 where is the heat transfer into the flow As is the internal surface area of the heater h is the heat transfer coefficient and dT is the temperature difference T3 T2 between the initial and final temperature of each iteration All variables except for T3 were either known or calculated The equation w
17. is multiplied by every other term and the constant gain c is left out de t dt t 1 X K e t f e t dt Ta 0 The reason for this change is to increase the contribution of the proportional term which is almost always the most important term in throttling type controllers Ziegler et al 1942 Proportional control alone is occasionally adequate and can be commonly found in industry but derivative or integral control without proportional control is often an inappropriate control setup Equation 2 6 13 prevents control without a proportional term defined Exclusion of the proportional term is often an incorrect method of control but possible using Equation 2 5 There are many reasons to use a PID controller in a system The main reasons are 1 They be used whenever a process is difficult to manually control 2 They can control a system that is too dangerous for manual control 3 They are accurate enough to control a process that requires great precision 4 They can control a complex multi variable process Wescott 2000 The proportional term in the PID equation allows the controller to respond according to the magnitude of the deviation from the set point In other words if the current deviation from the set point were to be large the controller would have a proportionally large response forcing the manipulated variable to approach the set point Visioli 2006 3 4 Proportional control is especially use
18. only values that have the proper significant figures in Table 12 are the inside diameter in inches and the heated length of the heater in inches The extraneous figures are retained for accurate calculations The volumetric flow rate SCFM was taken from Run 3 in the vortex tube calculation sheet Appendix 6 6 2 The required heat transfer to make any change in temperature is given by equation 3 2 q dT where dT is given by dT Ti The mass flow rate is unknown for a given experiment However the volumetric flow rate is known Assuming density will not greatly change over 40 degrees the mass flow rate can be calculated via equation 3 3 108 lt 0 Substituting values and unit analysis yields k 0 003128502 1 028 0 0032161 2 kg kg ti CS C2 S m S Obviously the figures for the resulting mass flow rate of air are not significant However they will be retained for accurate calculations as will the other equations in this section With the mass flow rate solved the required heat transfer for the flow can be solved q M Cp q 0 0032161 1007 70 20 q 161 9306402 W q 3 Watts This result for required heat transfer applies at every second of the heater s operation transfer resistance theory states that since the driving force of heat transfer is a temperature gradient within a syste
19. process for the purpose of the classroom procedures To solve the problem all possible information provided by airflow instruments was recorded but the energy balance was performed with all but one of the values supplied by the instruments Two values were chosen to be calculated through the energy balance exclusively One such variable was cold mass flow usually provided by the second rotometer The recorded value was then compared to the calculated mass flow of air in the cold stream The other variable calculated using an energy balance was the temperature reading from thermocouple 10 located on the hot stream which was then compared to the recorded value from thermocouple 10 Initially the values were far too different It was determined that a draft from a vent in the laboratory was blowing on thermocouple and causing an erroneous reading In addition the thermocouple was initially too far away from the vortex tube resulting in an error The thermocouple was adjusted to be much closer to the vortex tube and a draft shield was created using notebook paper to protect the thermocouple from the draft These actions helped to lessen the difference between the calculated and actual values ofthe cold mass flow and hot temperature More information on the differences can be found in the results and discussion section of the report 62 In addition after a prolonged amount of time recorded temperatures showed that system was driftin
20. refer to the LabVIEW Appendix Appendix 6 4 for an image of the entire block diagram if the following sections become difficult to understand Variables The Virtual Instrument designed for the virtual experiment of this MQP was originally constructed using a simulated signal based approach This approach proved to be very difficult and was shortly abandoned in favor of a purely mathematical VI In this approach three variables Initial Temperature Setpoint and Output Q were defined as double integers Initial Temperature is user defined in degrees Celsius and was manipulated by the VI to produce the Temperature which is the current temperature at the completion of an iteration double integer This is described in detail under the Passive Heating Cooling section of this document The PID sub VI reads the Temperature double integer as the process variable input Setpoint is also user defined in degrees Celsius and is the set point the PID attempts to approach The Output Q variable was read from the resulting PID signal Here the letter Q in the variable name is the heat transfer in Watts that the PID produces A block diagram of this process is shown in Figure 15 44 Passive Cooling Heating PID Control Next Iteration FIGURE 15 BLOCK DIAGRAM FOR SIMULATED VI WIRING THE INITIAL TEMPERATURE T VALUE CHANGES AFTER THE PASSIVE COOLING amp HEATING LOOP TO T THIS TEMPERATURE IS CONTROLLED BY THE PID AND IS CHANGED
21. respond to deviations in proportion to their speed as the derivative term sees current slope of the line required to reach the set point The derivative term on its own does not result in a controlled process it merely resists change and slows the response of the controller In doing so the derivative expression in the main PID equation resists the integral s tendency to destabilize the system The main weakness with including a differential expression is the occurrence of a phenomenon called derivative kick Any change in the set point of the controller will result in an infinite slope at that time itis changed It is possible to observe this when using Equation 2 3 as a new set point will clear the time history and the dt term will be equal to 0 This will create a sudden sharp increase or kick in the controller s output This sudden increase is usually brought back to a normal set point by the proportional term Derivative control is also sensitive to noise as an improperly tuned PID cannot respond as quickly to small changes Noise occurs when the signal given by the transmitter is not accurate enough for the range prescribed by the controller This causes the transmitter signal to jump in and out of the controller range and the controller cannot establish a consistent response as it sees a rapid and random deviation Since noise is generally a high frequency signal noise has large positive and negative slopes the derivative contr
22. rotometers 98 Step by step procedures Steps to control the vortex tube 1 2 3 4 Results Turn on the air flow Open the ball valve before and after the vortex tube Close the bypass valve Verify that air is flowing out of the hot end of the vortex tube If not open the control valve INLET CONTROL COLD END HOT END Record temperature from the appropriate thermocouples Record the reading from the rotometer after the vortex tube Record the gage pressure Wait for the vortex tube to reach steady state Record the temperature from the appropriate thermocouples Record the reading from the rotometer near the beginning of the flow Record the gage pressure Mathematically prove that the Vortex Tube doesn t violate the first law of thermodynamics Hint Are the predicted and measured variables similar Qualitatively prove that the Vortex Tube doesn t violate the second law of thermodynamics 99 6 2 GLOSSARY 6 2 1 DEFINITIONS Analog signal An analog signal is a continuous time varying sinusoidal electrical signal For the purposes of this document an analog signal represents a variable that is being read by an object An analog signal registers all variances that occur Bang bang control Bang bang control is a type control that administers a signal to turn on a device if the process variable is below the set point or turn off the device if the process variab
23. smaller signal to activate the switch completing a circuit for a larger load The signal sent to the solid state relay is 5 volts when the DAQ was operating at the high setting 3 volts are sent to the solid state relay when the DAQ was operating at the low setting The solid state relay needs 4 volts to activate so the high setting is essentially the on setting and the low setting is essentially an off setting in the case of this experiment When the solid state relay is active the heater would be turned on When the solid state relay is inactive the heater does not receive power from the Variac controller and is off The second DAQ installed was the NI USB 9213 This DAQ is purely an input device and is used to read the ten thermocouples attached to the gas flow apparatus The thermocouples were already physically wired to an analog thermocouple reader that displayed one temperature at a time The wires were moved from the analog reader to the NI USB 9213 Next the VI was developed For a picture of the complete VI please refer to Appendix 6 4 First the entire VI is encased in while loop DAQ Assistants were created for NI USB 6501 and NI USB 9213 A DAQ Assistant is a programming function in LabVIEW that processes data from a DAQ The NI USB 9213 DAQ Assistant had channels one through 10 selected where each channel is a signal pathway from an individual thermocouple Each channel had an indicator created so that the front panel woul
24. tasks of PID control PID tuning can be divided into two categories mathematical and experimental Mathematical tuning is often avoided due to the numerous combinations of complex equations Ziegler et al 1942 Some of the auto tuning functions performed by computers use a selection of these mathematical equations in their algorithms Ming da amp Xin jian 2006 Experimental tuning can be performed by an established systematic method or can be accomplished using a hit or miss procedure where the experimenter adjusts the PID gain terms until one combination works A common drawback to the hit or miss approach is that it can take a long time to reach the ideal setting or sweet spot Experimental tuning rules of thumb for PID control systems were first suggested by Ziegler and Nichols 1942 and have since been simplified and expanded upon by many other researchers This has resulted in other generally accepted tuning rules such as those created by Tyreus and Luyben O Dwyer 2006 78 The Ziegler Nichols tuning rules involve running a handful of trial experiments where the proportional gain of a controller is increased until permanent oscillations are observed Once this maximum or critical value of proportional gain is observed each resulting gain term proportional integral and derivative is multiplied by a constant The exact value of each constant depends on if the controller functions as P only a PI or a PID The result is ge
25. technology IEEE Transactions on Control Systems Technology 13 4 559 576 Astrom amp Hagglund T 2004 Revisiting the Ziegler Nichols step response method for PID control Journal of Process Control 14 635 650 Retrieved on Mar 12 2012 from http www sciencedirect com Astrom amp Hagglund T 2001 The future of PID control Control Engineering Practice 9 11 1163 1175 Retrieved on Mar 13 2012 from http www sciencedirect com Bequette B W 2003 Process control modeling design and simulation Upper Saddle River NJ Prentice Hall Bequette B W Aufderheide B Prasad V amp Puerta F 2000 A process control experiment designed for a studio course Unpublished manuscript Retrieved 10 1 2011 from http 128 113 2 9 dept chem eng WWW faculty bequette ramesh publications CEE pdf Bucknell University 2012 An Introduction to Signals Bucknell University web Retrieved 11 Apr 2012 from http www facstaff bucknell edu mastascu elessonshtml Signal Signal2 htm 122 Carnegie Mellon amp University of Michigan 1997 Control tutorials for matlab PID tutorial Retrieved 10 28 2011 from http www engin umich edu group ctm PID PID html controller Cengel Y amp Cimbala J 2010 Fluid mechanics fundamentals and applications 2 4 ed New York NY McGraw Hill inc 930 Cooper D J 2008 Integral Reset Windup Jacketing Logic and the Velocity PI Form Retrieved 20
26. the set point is user defined Stop FIGURE 23 CONDITION TO SHUT OFF HEATER Once all issues were resolved a write to file block was added so that the data collected in each run could be exported to a Microsoft Excel file The data from all thermocouples was bundled and sent to the write to file block A control for the write to file block was added so that when the indicator says enabled the data is being exported to a file and while it says disabled the data is not being exported This block was included so that students do not have to export data they feel they do not need to record The data exported is displayed in Excel as 20 columns The even numbered columns titled Untitled are the readings of the thermocouples and the odd number columns titled X value are the times that the readings from each thermocouple were taken in seconds The time is displayed next to every temperature reading rather than in one column due to 57 LabVIEW s limited options for displaying data Controls were added to front panel so that students can choose which file path the data should be exported Filename FIGURE 24 WRITE TO FILE BLOCK Once the programming on the back panel was complete a design of the gas flow apparatus was drawn on the front panel and the thermocouple indicators were moved to illustrate where in the gas flow apparatus the reading was located The controls were organized so that they were in the Same
27. to make the process run more smoothly Usually optimization is focused around four specific system dynamics listed below Zhong 8 1 Risetime the time it takes for the output value to reach 9096 of the set point value for the first time 2 Overshoot expresses by how much the highest output value is different to the set point value normalized against steady state 3 Settling time the time it takes for the system to converge to steady state 4 Steady state error the difference between the converged steady state output and the desired set point value These represent the four major characteristics of a closed loop step response system This experiment will focus on optimizing these four properties and each should be addressed separately when attempting to measure the progress made in optimizing the system 87 Virtual LabVIEW PID It is important that students familiarize themselves with LabVIEW s front panel and with the application of PID theory For this purpose a completely digitalized version of the GFA has been created and is available for students to explore In order to open up this file download the VirtualPID vi file from myWPI Once it is loaded in LabVIEW you should see the front panel shown in the figure below The gain values be changed by entering desired number and are located at the bottom of the graph The graph plots 3 curves simultaneous
28. to change how the controller operates Functions 26 to 50 are labeled as Advanced Functions and are not designated to be changed in the controller s normal operation It is recommended by the manufacturer that the Advanced Functions should only be changed by qualified personnel Omega n d a For the purposes of this research only the Standard Functions will be investigated and changed in attempting to achieve a better more stable set point temperature value Table 1 shows all the 25 Standard Functions included in the PID controller 32 TABLE 1 AVAILABLE FUNCTIONS IN CONTROLLER OMEGA N D A Function Function Function Function 0 Operating Modes Output 2 1 Manual Reset 22 C F Selection 2 Set point 2 Adjust 23 Software Version Number 3 Set point 1 Lock 24 Upper Set point Limit SPAN 4 Cycle time On off Output 1 25 Not Used 5 Proportional Band Deadband Output 1 6 Derivative Time Rate Output 1 7 Derivative Approach Control Output 1 8 Integral Time Output 1 9 Sensor Offset Calibration 10 Cycle time On off Output 2 11 Proportional Band Deadband Output 2 12 Loop Break Alarm Time 13 Activate Advanced Functions 26 to 50 14 Not Used 15 Resetting Functions 0 to 24 to Default Settings 16 Input Sensor Select amp Range Table 17 Negative Temperatures 18 Display Resolution 19 20 Sensor B
29. which is a 16 channel USB thermocouple measurement device The other is an NI USB 6501 which is a 24 channel low cost USB digital input output device The 9213 collects thermocouple data while the 6501 sends a signal to the Omega AHP 5051 inline heater 2 3 2 SIGNALING In order for LabVIEW to control a device it must send either an analog or digital signal via a DAQ The PID sub VI used for this project does not require any additional alterations to their export signals if an analog device is used However if a digital device is used certain changes must be made to the export signal The required changes are described below In electrical engineering different types of signals can be described by their waveform While in depth descriptions of signals are outside the scope of this project a brief overview is necessary in order to understand some of the basic methods used to control the LabVIEW PID Most signals from electrical devices are the analog signals The waveform of analog signals is sinusoidal and the average voltage from an analog signal can be found from waveform characteristics such as the amplitude or phase of the signal Bucknell 2012 Digital devices are usually not powered by analog signals as analog signals cause noise Noise is random fluctuations that cause the signal to deviate from a perfect sinusoidal signal Because of this digital devices are not usually powered by analog signals They are instead powered by dig
30. 0 28 11 5 17 3h 0 29 59 7 20 4 6 42 2 0 28 10 8 16 5 3i 0 29 59 7 20 4 6 2 42 2 0 28 10 4 16 2 3j 0 29 59 7 20 4 6 3 42 2 0 28 9 9 15 8 3k 0 29 59 7 20 4 6 2 42 2 0 28 9 6 15 4 3l 0 29 59 7 20 4 6 1 42 2 0 28 9 3 15 2 3m 0 29 59 7 20 4 5 9 42 1 0 28 9 14 9 3n 0 29 59 7 20 4 5 8 421 0275 8 9 14 7 3o 0 29 59 7 20 4 5 6 419 0275 8 7 14 4 0 29 59 7 20 4 5 4 418 0 275 8 5 14 2 3q 0 29 59 7 20 4 5 4 41 5 0 275 8 5 14 1 3r 0 29 59 7 20 4 5 6 412 0 27 8 4 14 35 0 29 59 7 20 4 5 8 41 5 0 27 84 13 8 3t 0 29 59 7 20 4 6 41 3 0 27 8 3 13 7 3u 0 29 59 7 20 4 6 41 0 27 8 3 13 6 3v 0 29 59 7 20 4 5 8 40 7 0 27 8 4 13 6 3w 0 29 59 7 20 4 5 3 398 0 265 8 4 13 5 3x 0 29 59 7 20 4 5 5 40 9 0 265 8 4 13 5 0 29 59 7 20 4 5 1 40 3 0 26 84 13 5 120 Trial Ori Pai Ti PC T C 3z 0 29 59 7 20 4 4 6 39 0 26 8 5 13 5 3aa 0 29 59 7 20 4 4 4 38 8 0 26 8 6 13 5 3bb 0 29 59 7 20 4 4 5 38 6 0 26 8 7 13 5 0 29 59 7 20 4 4 4 38 0 255 8 9 13 6 0 29 59 7 20 4 4 5 37 7 0 255 9 1 13 6 3ee 0 29 59 7 20 4 4 5 37 5 0 255 9 2 13 6 3ff 0 29 59 7 20 4 4 4 37 3 0 25 9 3 13 7 0 29 59 7 20 4 4 2 37 2 0 25 9 4 13 7 3hh 0 29 59 7 20 4 4 36 9 0 245 9 4 13 8 0 29 59 7 20 4 3 7 36 6 0 25 9 5 13 8 3ji 0 29 59 7 20 4 3 7 36 9 0 245 9 5 13 8 3kk 0 29 59 7 20 4 3 3 36 5 0 24 9 5 13
31. 93 trials had a percent difference less than 1096 between the recorded and calculated values With this established agreement between calculated values and recorded values at most experimental trials it is likely that a simple energy balance will reasonably estimate the temperature or mass flow of a stream exiting the vortex tube The consistent percent differences between the calculated and recorded values support the reliability of this method Should this particular method be adapted for classroom use it is recommended that any difference between recorded and calculated data be within 1096 This level of accuracy has been demonstrated to be easily attainable and any larger error is an indication that there is either something wrong with the energy balance or that the data was recorded in an inappropriate manner 4 3 3 DRIFTING For some reason the cold end outlet flow of the vortex tube decreases with time This phenomenon cannot be explained by anything observed Possible causes are that the temperature change affects the physical shape of the vortex tube decreasing its ability to separate air before it exits the hot end Another suggestion is that as the cold temperature decreases the pressure in the swirl chamber decreases The vortex tube s ability to separate the air is dependent on the pressure of the incoming air If the pressure decreases then the vortex tube s ability to separate decreases as well Since the cold mass flow is decrea
32. ERNAL FOR LOOP THAT CONTROLLED PASSIVE HEATING AND COOLING Once the data from the Temperature variable was output into the for loop it was subjected to the Equation 3 1 3 1 27 100 47 where is the entering temperature and T is temperature after passive heating and cooling The equation takes any difference between the current temperature and 20 degrees Celsius and divides this difference by 100 This allows for a slow approach of the current temperature to 20 degrees when the heater and PID are deactivated The number in the divisor can be increased for a slower approach or decreased for a more rapid approach to 20 degrees A value of 100 was chosen arbitrarily because it clearly displayed passive cooling to the user when the PID was deactivated without taking a long time or converging too quickly The result T2 was subtracted from the temperature entering the for loop and the final value exited the for loop via a shift register and was wired as the PID input PID Control In reality the PID controls the output of the heater connected to the airflow experiment It is therefore necessary to attempt to simulate this behavior virtually as well For this reason Equation 3 2 was used q M Cy AT 3 2 where dT is the temperature difference between the entrance and exit of the heater T and Ts respectively The value of the heat capacity of air cp is 1007 J kg K Cengel 2010 The heat capacity of air
33. NING It was understood that Auto tuning should be plausible for the gas flow apparatus experiment as it is not of a highly complex nature and does not use custom settings on most of the provided functions The following steps were taken during attempts to auto tune the PID 1 The gas flow apparatus was turned on 2 The P button on the controller was pressed to enter set up mode The numbers 0 0 Option 0 Function 0 were displayed on the screen The Auto tune routine is located in Function 0 which is the Operating Modes function 3 The x star button was pressed to switch from the Function menu to the Option menu 4 The default Option number was changed from the Option 0 to Option 1 to turn on the Auto tune program 41 5 The button was again pressed to start the Auto tune process The heater was turned simultaneously when the button was pressed At this point the display alternated between the words AT and TEMP which indicated that the Auto tune program was running Any error messages were recorded The temperature results from each run were graphed using the NI USB 01 thermocouple reader 3 3 LABVIEW METHODS 3 3 1 LABVIEW OVERVIEW LabVIEW 2010 was used with the optional PID and control modules installed Using these modules it was possible to construct a Virtual Instrument VI that would simulate the gas flow unit operation After the VI for the simulated experiment was complete ano
34. PID Controller Omega 33 Table 2 Relevant Functions for this investigation esistente 35 Table 3 How proportional integral and derivative gain affect the controller s performance 36 Table 4 Potential errors encountered in auto tuning Omega n d a sss 37 Table 5 Tuned settings for the Omega PID sisse 40 Table 6 The settings for each Function that were studied No additional Options remained in the range of values studied etae e t td t dtu ede d ted ie dec teet e tee 41 Table 7 Calculations for various parameters required for Equations 3 1 to 3 8 52 Table 8 Physical properties of the air flow at 70 C Cengel 2010 52 Table 9 Results when the proportional band is changed esee 65 Table 10 Results when the integral time is changed essent tentes 65 Table 11 Results when the derivative band is changed 65 Table 12 Data from a typical experiment esee 108 ABSTRACT This MQP addresses the lack of laboratory process control at WPI by expanding the Gas Flow Apparatus experiment in the Unit Operations course A LabVIEW PID controller and a vortex tube were installed in the experiment The PID controller successfully controls the heater on the gas flow The vortex
35. This number would be multiplied by 10 so the duty cycle would supply a 5 to the for loop for the PWM period For the first 5 iterations the number the duty cycle supplied would be greater than or equal to the iteration number so the output signal would be high This would turn on the heater for the first 50 milliseconds of the PWM period During the sixth through tenth iteration the number provided by the duty cycle would no longer be larger than the iteration number so the Boolean would command a low output shutting off the heater for the remaining 50 milliseconds of the PWM period After each PWM period the for loop would restart and would receive a new value from the PID restarting the process again with 10 new iterations It was noted that once the experiment stopped the DAQ would sometimes still administer a high signal and the heater would be continuously active despite the VI being shut off This could potentially damage the equipment as the heater would have no control while operating In order to solve this issue a condition was added to the VI The condition was true when the while loop encasing the VI was stopped and false while the while loop and the VI was active The true condition administered a set point of 1009C to the PID so that when the while loop was stopped the PID would automatically shut off the heater due to the temperature being above the set point When the condition is false and the VI and while loop are active
36. a PID controller operates and how to tune a specific system In this experiment the heater located in the Airflow Experiment in GH 220 UO lab will be used The experiment will consist of tuning an un optimized system with the ability to change specific functions Specific goals will have to be achieved including an acceptable rise time acceptable oscillation around the set point and acceptable time to reach steady state CONTROL THEORY As mentioned above the PID controller works under three variable terms Each of these has a set of specific ways in which it affects the system it controls The Proportional term is expressed mathematically as X X where all of the terms are by the process except for the value that is controlled by the operator The proportional term allows the controller to respond in proportion to deviations from the set point This term is especially useful for increasing the controller s speed of response although if the term is too large the process variable will begin to oscillate If increased even further then the system might become unstable and even oscillate out of control The Integral term is expressed mathematically as t 1 f x dt 0 This term allows the controller to respond to errors that have occurred historically over time So if the system has deviated from the set point in a consistent manner this term will force the PID 85 controller to correct th
37. aches when determining how the while loop will calculate the process temperature 1 Start with a constant initial temperature for each run 2 Usethe temperature from the previous iteration or 3 Usea combination of constant initial temperature and the temperature from the previous iteration Approach 1 allows for accurate readings but the virtual experiment behaves unrealistically Because the initial temperature is a constant value the PID module controls the process variable perfectly There is no settling time at all and the temperature is steady and constant as soon as it 43 rises to set point Approach 2 allows realistic control but power output of heater is incorrectly shown as being low around 1 3 watts It was determined that students needed an accurate gauge of the heater s power output during the virtual experiment in order to see if PID was controlling the heater properly Oftentimes certain PID settings can cause the output signal to fluctuate between high and low power which can lead to wear on the equipment and it is this situation that students should be wary of Approach 3 was used to construct the simulated VI as it allowed for the benefits of approaches 1 and 2 without either of the major errors However there was some difficulty in programming this loop as it required more variables and was more complex than other options The following sections are extremely technical Please
38. ained at the set point for the entirety of the experiment with very little steady state error The Omega 9000 PID controller is programmed with 24 functions and most functions come with a number of options These are selected as two numbers on the Omega controller separated by a decimal To the user this appears as the form Option Function For example option 3 on function 5 would be punched into the controller as 3 5 All of the results discussed are not quantitative but instead record general observations from monitoring the effect of changing each parameter Goals 1 and 4 were met by changing the proportional band The proportional band function 5 15 the allowable span i e distance from the set point If the current temperature is inside this defined range the proportional band is active according to the set percentage Omega 2011 Above this span the proportional band is off 096 and below this span the proportional band is on 10096 The results of changing this function are shown in Table 9 64 TABLE 9 RESULTS WHEN THE PROPORTIONAL BAND IS CHANGED Proportional Band Results Setting Gain Comparison to Initial Initial 13 5 1496 N A Run 1 7 5 2096 Less stable set point Run 2 1 5 0 596 Oscillations Run 3 11 5 796 Oscillations Goals 2 and 3 were achieved by changing the integral time function function 8 Integral time is the length of historical data the PID
39. area 58 FIGURE 25 FRONT PANEL 3 3 4 EXPERIMENTATION WITH LABVIEW In order to determine if the VI functioned as a proper PID controller and to prevent possible damage to the equipment on the gas flow apparatus a water bath experiment was performed The water bath experiments consisted of an Erlenmeyer flask filled with water A Screw Plug Immersion Heater was fully inserted into the water For the water bath experiment the NI USB 6501 was wired to a different solid state relay than the one used with the gas flow apparatus When activated the solid state relay would complete a circuit that would send power to a heater ina water bath via the Variac A thermocouple was placed in the water bath as well and connected to a 01 thermocouple reader The NI USB 9213 was not used for the water bath experimentation so the VI constructed for the water bath experiment required using a DAQ assistant for the 01 The signal from the TC01 DAQ 59 assistant replaced signal from channel 3 of the NI USB 9213 as current process variable input for the PID sub VI The rest of the VI is identical to the one described in the section LabVIEW Physical Experiment Once the VI was constructed the circuit was plugged into the Variac controller for power When the VI was running the activity of the solid state relay was observed Since the specific heat of water is very high the water bath would not cool down quickly enough to observe t
40. as then put in terms of the temperature after PID control q2 A h T 3 6 The output range of the PID was bound between 400 and 0 which corresponds to the power output in watts by the heater The temperature after passive heating and cooling T2 was wired as the PID input The internal surface area of the pipe was multiplied by the heat transfer coefficient of the flow The heat transfer q was divided by the resulting value and the temperature before PID control was added resulting in the value for T2 All of these manipulations can be seen in Figure 19 The application of Equation 3 6 into the VI resulted in stable PID control with easily tuned parameters and a realistic temperature response curve Unfortunately the output power of the PID was only 3 watts This was unrealistically low as the PID output was shown to be around 170 watts experimentally The flaw with Equation 3 6 was that it did not include the required heat transfer per second it only showed the required heat transfer per iteration In order to model the PID power output properly the heat transfer from Equation 3 2 had to be included This produced Equation 3 7 42 q 3 7 its extended form 49 q2 h As d m cp dT and Equation 3 6 was rearranged to become Equation 3 8 q2 91 T4 3 As h T 3 8 The result for was then connected to the while loop via a shift register and
41. aster moving molecules forces the slower moving molecules to flow in the opposite direction towards the narrow end of the coil The relatively small amount of thermal energy in the slower moving particles translates into a lower exit temperature than the inlet flow Hilsch 1947 These flow patterns are characteristic of a vortex which is why the equipment earned the label of vortex tubes The exit temperature at the cold end of the vortex tube depends on the inlet pressure and the airflow based on the amount that the control valve is open In general to change exit temperature of the cold end the pressure is held constant while the control valve on the hot end of the vortex tube is manipulated The shift in temperature from the inlet to the cold end is thermodynamically described as the cold fraction The cold fraction can be found through a simple energy balance around the tube and is a measure of the efficiency of refrigeration The cold fraction is given by the following equations Gao et al 2005 Me 2 7 T 4 100 2 8 T 27 Since vortex tubes have no moving parts and use no electricity they are often used as spot cooling solutions for manufacturing processes Cooling in manufacturing is usually done with liquid coolants but not every process can use these methods Spot cooling is cooling from a point source and is one solution in manufacturing when the use of a liquid coola
42. at all values in the range of 3 6 11 8 difference were all within one standard deviation of the average 8096 41 of 51 values were within this range 1096 of the values 5 of 51 were between one and two standard deviations away from the average Three of the values were below 3 696 difference and two of the values were between 11 896 and 15 996 different 1096 5 of 51 were more than two standard deviations above the average No values were more than two standard deviations below the average and no values were greater than three 79 standard deviations above value Since standard deviation is so large if a calculated value was more than one standard deviation above the average then it is an indication that the data being recorded may be flawed since There were seven trials that had this issue of these trials occurred after significant drifting had occurred The later trials show an increase in percent difference but this is due to a lack of precision in reading rotometer 2 and is an example of why due diligence is required while recording data the rotometer readings were taken while the rotometer reading was fluctuating This consistency of the percent difference through the most trials suggests that this is an appropriate method to estimate mass flow while the rise in percent difference in later trials serve as a reminder that itis only appropriate if readings are done within a minute of each other Of the 102 trials
43. because they would not be able to comprehend or explain this phenomenon One last deficiency to the virtual PID is that the gains used were not same as those used in the Omega PID or physical PID This is because the virtual PID does not count for heat loss and other factors that could affect the system Even though the gains will not be identical this will not detract from the students ability to learn the art of tuning a PID 4 2 2 PHYSICAL LABVIEW PID For an image of the front panel and back panel please refer to Appendix 6 4 The physical PID was very different than the virtual PID The most noticeable change on the front panel was the GFA schematic which is shown by itself in Figure 33 below 71 FIGURE 33 GFA SCHEMATIC The schematic simplified the task of viewing and recording temperatures because the analog temperature display was replaced by the LabVIEW interface In Figure 33 on the top right corner a white rectangular box can be seen with a button on the side labeled Data Collection This feature allowed for the collection of temperature from all 10 thermocouples with the option of exporting the data using a program such as excel This made it possible for students to not only display the real time temperature on the screen but also to log it so that they could graph it analyze it and use itin their report 72 o gt Time s Omega sa
44. ble tis the time elapsed cisaproportional constant 15 the proportional control gain 1 the integral control gain also called integral time and e Tais the derivative control gain also called derivative time Omega n d b 12 The proportional integral and derivative control gain terms are generally adjusted by user if the controller is not responding correctly or if the system is not behaving as desired The three terms are added together to form the main PID equation t E 1 d Xset E x 4 Kc Xset x T Xset tc 24 0 The driving force in each equation 2 1 2 3 is a given difference between set point and variable s current value Xset The gain term in each of these equations is multiplied by the driving force They therefore determine the relative contribution of each of the PID equations Equations 2 1 2 3 to the controller s final response to a deviation as shown in Equation 2 4 It is these gain terms that are manipulated by the user to tune the controller The difference from the set point xs x is often abbreviated as the error e This simplifies to Equation 2 5 t 1 d X Kce t f e t dt Ta Felt 2 5 0 This equation is called ideal PID equation However this theoretically derived equation is often altered in industry to a different form Bequette 2003 168 211 In a commonly used form the proportional gain
45. by students this error should not result in poor data This error should not affect the study of heat on a compressible flow However this error might confuse students as they try to 73 tune LabVIEW PID It possible that students could use both Omega PID and LabVIEW PID and compare their control results 43 VORTEX TUBE 4 3 1 CALCULATED HOT TEMPERATURE VS RECORDED HOT TEMPERATURE Hot Temperature is Ty or the temperature of air exiting the hot end of the vortex tube This temperature was recorded using thermocouple 10 This temperature can also be considered an unknown and the mass flow rate can be used to calculate the value of thermocouple 10 using Equation 3 13 for a derivation of this equation please refer to Appendix 6 5 0 cy rh Tc Ti mn TD 3 13 Rearranged the equation is mcT 09 4 1 mi m All other values were recorded using equipment Refer to Appendix 6 3 for details as to how each variable was recorded 74 Th Recorded B Th Calculated e gt FIGURE 35 RECORDED TEMPERATURE VS CALCULATED TEMPERATURE BY TRIAL As seen in the chart calculated temperatures were consistently greater than recorded temperatures This can be attributed to heat loss throughout the system which was not accounted for in the experiment Also the thermocouple is currently positioned slightly outside the vort
46. cess using PID controllers and also try to optimize them by trial and error Shortly after this tedious approach the students are instructed in tuning techniques which are introduced in order to optimize the process control loops as the final stage of the experiment These experiments are performed during several different class periods during the semester and each one is scheduled between series of lectures on the appropriate topics The three controlled variables in this experiment inlet flow temperature and conductivity are difficult to control manually as any changes to one input radically changes the other variables Through hands on experience with a PID controller the students learn the effectiveness of process control systems and their superiority over manual control Proper tuning of the PID controller provides students with a deeper understanding of how easy itis to introduce controllers in order to radically improve the control of a process RPI s experiment uses LabVIEW for real time data acquisition This program uses a simple interface and allows the student the opportunity to directly observe the experiment The small scale RPI experiment is shown in Figure 1 Control Valve Fresh Water 6 Inline Conductivity Probe Control V alve Salt Water 7 Conductivity Measutem ent Display Heater for Fresh Water 8 Temperature Measutem ent Display Differential Pressure To Infer T ank L evel 9 Salt Water T ank Temperature ProbeIn
47. cond and off for 3 seconds It can be deduced that the shorter the cycle time the more precise the control This is also known as a PWM period See section PWM SECTION Proportional Band Deadband Kp The output from the controller is proportional to the error or change in measurement This means that if a large error needs to be corrected a large correction will be applied Derivative Time Rate Kp The output from the controller is proportional to the rate of change of the measurement or error This should inhibit more rapid change of the measurement than from the proportional band This function is usually used to avoid overshoot Derivative Approach Control Used to eliminate the action of Derivative Time during warm up of the system During warm up the user is not looking to control any parameters but is trying to get close to the set point value Integral Time The output from the controller is proportional to the amount of time the error is present This function should eliminate steady state offset by outputting a signal that corrects repeati ng errors Changing these functions by using the different preset options within each of these will affect the way the PID controller responds to any offset Table 3 shows how the three PID parameters from Equations 2 1 2 3 affect the system dynamics when their values are increased The changes on 35 system dynamics from alterin
48. control the experimental variables manually and are later taught how to use a PID controller In this way students are first exposed to the difficulties of manual control and then are taught the usefulness of PID control The University of Loughborough uses their process control OLLO to teach students different types of process control depending on which academic year the students are in Freshmen students are taught process dynamics sophomores are taught process control and instrumentation and juniors are taught PID control and tuning Additional elective classes use the experiment to teach students in depth PID theory The entire experiment is controlled through a software interface built using LabVIEW which gathers process data using a USB DAQ By using the OLLO based experiment the students from the University of Loughborough can learn how to operate an experiment remotely which prepares them later for the actual hands on laboratory experiments Itis noteworthy that the Loughborough faculty felt it was important to include the actual experimental rig for instruction as there is a large consensus that hands on laboratory experiments are vital to science and engineering education Johnstone amp Al Shuaili 2001 The Loughborough OLLO is a good example of using two complimentary methods laboratory experiments to teach students process control 2 1 3 PROCESS CONTROL LABORATORY EXPERIENCE AT VILLANOVA UNIVERSITY Villanova University pr
49. could result in an unacceptable operating condition or in the worst case a complete system shutdown PID control allows the system to be stable for suitable study and safe for the equipment 2 5 1 OPTIMIZING THE OMEGA CN9000A Tuning the Omega cn9000A PID controller is an arduous task The nature and equations of a PID controller have been previously described but are displayed again below for reference 28 Proportional X x t 2 1 Integral fy Eset x t dt 2 2 Differential X 2 3 Students in the Unit Operations course should never have to optimize the Omega PID The following sections describe how one would optimize the Omega PID This is necessary to understand the experimentation that was done to tune the controller There are a number of parameters within the Omega PID controller that can be fine tuned to produce an optimized process control This research will investigate how the PID parameters affect system dynamics Zhong 2006 such as 1 Risetime Defined as the time it takes for the output value to reach 9096 of the set point value for the first time 2 Overshoot Expressed by how much the highest output value is different to the set point value normalized against steady state 3 Settling time Defined as the time it takes for the system to converge to steady state 4 Steady state error Defined as the difference between the converged steady state outpu
50. d display all the temperatures read by the thermocouples Channel three the reading from thermocouple 3 was used as the current process variable input in the PID sub VI Also a graph of the temperature recorded by thermocouple 3 was created This allowed the user to watch the temperature change as a function of time and also to see the approach settling time and steady state of the PID control Thermocouple 3 was the PID input used for the Omega PID as well Figure 20 54 po H Waveform Ct FIGURE 20 NI USB 9213 ASSISTANT AND INDICATORS PID Control FIGURE 20A THERMOCOUPLE 3 SENDING SIGNAL TO PID Since the NI USB 6501 sent a digital signal pulse width modulation PWM had to be programmed into the VI in order to simulate an analog signal and achieve actual PID control The sequence for the PWM began by receiving the signal from the PID sub VI After the PWM sequence occurred it delivered a Boolean array response of 0 or 1 to the DAQ assistant for the NI USB 6501 A value of 0 would set the DAQ to its low setting deactivating the solid state relay and turning off the heater A value of 1 would set the DAQ to its high setting activating the solid state relay and turning on the heater Figure 21 55 FIGURE 21 NI USB 6501 DAQ ASSISTANT WITH BOOLEAN INPUT In order to program PWM the PID signal was given a range of 0 through 100 which is the duty cycle A forloop was created and
51. depth study of the drifting issue from the vortex tube could help identify the cause of this phenomenon This was beyond the scope of the project because the drifting phenomenon did not affect the energy balance In addition for the defined classroom procedures students are unlikely to operate the vortex tube for a prolonged period of time and will not encounter the phenomenon 83 6 APPENDICES 6 1 CLASSROOM PROCEDURES 6 1 1 CLASSROOM PROCEDURES FOR PID CONTROL BACKGROUND What is Process Control Process control is defined as the control of system parameters in a specified process This discipline is applied widely in academia and industry to maintain stable processes and experiments activities ranging from home heating systems to nuclear plants use process control systems of varying complexity For the control of a specific process a set point is needed for the controller Based on this set value the controller will drive the actuator a device that performs a mechanical response to an input signal as close to the desired value or effect as possible As a representative example consider the cooling system of a room The person inside the room sets the temperature of Air Conditioning AC to a certain temperature given his needs to cool down hot summer day This temperature is the set point of the system The AC will work to reach and maintain that temperature The AC will have a sensor that monitors temperature and pro
52. ds if it sees a true function it will return the false response 101 Offset Offset or error from a set point is the difference between the value of the process variable and desired value set point of the process variable Proportional time Proportional time is the cycle time with which a proportional gain reacts to error while within a Proportional Band Proportional integral and derivative PID control PID control is a self described feedback control type The proportional integral and derivative terms are all defined in a PID equation discussed in the background that determine the strength with which the controller responds to offset in a process Pulse A pulse is a rapid change in a signaling value from a low value to a high value This is followed by another rapid change from the high value to the previous low value PWM period PWM period is the arbitrary cycle time in a pulse width modulation process Each distinct duty cycle is administered throughout one PWM period Set point Set point is the predetermined value that the user wants the process variable to attain Shift register A shift register is a programming tool in LabVIEW that lets a loop structure carry over a value in the structure from iteration to iteration Tunneling Tunneling is a LabVIEW programming option where a value entering a loop structure is unaffected by the loop s functions and is available for indexing t
53. e cooling structure was programmed and a constant heattransfer was defined The virtual PID also contained a graph that displayed the process variable set point and signal strength as a function of time This graph allows students to see how different tuning combinations affect the approach settling time and steady state of the PID process as well as determine if their tuned gains would overtax the equipment The virtual LabVIEW PID was a success so a physical LabVIEW PID was constructed Appropriate equipment was identified purchased and installed This equipment allowed LabVIEW to communicate with the Gas Flow Apparatus Two Data Acquisition Devices DAQs were selected for this task The first was a NI USB 6501 The NI USB 6501 is a digital input and output device Digital 1 0 that was used to communicate to the heater The DAQ received a signal from the PID sub VI and transmits the signal to a solid state relay Dependent on the signal the solid state relay either activates and turns the heater on or deactivates and turns the heater off The second DAQ purchased was a NI USB 9213 The NI USB 9213 is a thermocouple input device This DAQ was used to relay the readings of all ten thermocouples on the Gas Flow Apparatus to LabVIEW The reading from the appropriate thermocouple was fed to the PID sub VI as the current process variable and all temperature readings were displayed in the simulation Once the DAQs were appropriately connected t
54. e in the first PI simulation Figure 28 was about four seconds while the rise time with the re tuned integral term was about 30 seconds The addition of an appropriate derivative time would reduce the magnitude of the overshoot in the system and introduce overall system stability 67 2 70 00 aliia S HQ 1 000 0 010 0 050 FIGURE 30 ADDITION OF A DERIVATIVE TERM Figure 30 above displays a control graph with unchanged gains except for the derivative term The derivative term is relatively large This caused a much larger overshoot reaching a temperature 90 9C where the PI controller with the same proportional and integral term reached a max temperature of about 80 9C on the overshoot The signal displayed in Figure 30 shows that the PID was rapidly reacting to error This led to overcorrection and a higher overshoot This was because the derivative term was too strong and influenced error correction on the rise time 68 FIGURE 31 INCREASED INTEGRAL TERM AND DECREASED DERIVATIVE TERMS Figure 31 displays the system being controlled with gains of K 1 00 0 020 minutes and 0 001 minutes A much faster rise time and minimal overshoot of the set point was observed and overall system stability was achieved The increased integra
55. eb portal browse display EXT KNOVEL DISPLAY bookid 34 42 amp VerticalID 0 Seborg D E Edgar T F Mellichamp D A amp Doyle F J 2010 Process dynamics and control Hoboken NJ John Wiley and Sons Technological Education Institute of Chalkis 2001 How pulse width modulation works what is PWM and why is it useful Technological Education Institute of Chalkis Retrieved 6 Apr 2012 from http www ee teihal gr labs electronics web downloads What_is_PWM_and_why_is_it_u seful pdf Wescott T 2000 PID without a PhD Embedded Systems Programming 86 108 124 University of Michigan 2009 12 chemical process PID control chem 466 Wolf P Director 2009 Video DVD Youtube University of Michigan Visioli A 2006 Pratical PID Control London England Springer Verlag London Ziegler J G amp Nichols N B 1942 Optimum settings for automatic controllers Transactions of the American Society of Mechanical Engineers ASME 759 768 Zhong J 2006 PID controller tuning A short tutorial Presentation West Lafayette Indiana Purdue University 125
56. eers Process control is a systematic means of improving the function or efficiency of operations Process control is defined as the control of system parameters in a specified process This discipline is applied widely in academia and industry examples range from home heating systems to controlling large chemical plants Currently the Department of Chemical Engineering ChE at Worcester Polytechnic Institute WPI offers a Process Control class CHE 4405 Chemical Process Dynamics and Control Laboratory but does not offer a comprehensive laboratory component on this subject This deficiency keeps students from experiencing how this essential aspect of chemical engineering works first hand In order to round out the aspiring chemical engineering student s education it is imperative to expand the curriculum to include hands on laboratory experience Furthermore the need to pursue the upgrade became apparent when the Accreditation Board for Engineering and Technology ABET visited WPI and suggested that more exposure to process control experiences be offered to the undergraduates The purpose of this Major Qualifying Project MQP was to develop a laboratory learning experience on process control WPI currently has a Gas Flow Apparatus located in Goddard Hall which is used as the Unit Operations experiment to teach students about compressible fluid flow This experiment has been identified by WPI faculty as being unusually brief and does not c
57. esently conducts a Process Control Laboratory Experiment in conjunction with its Process Simulation and Control course In this experiment students use a 50 gallon gravity drained tank which has two inlet valves a manual and a control valve and one outlet manual valve A diagram of the system is shown below in Figure 2 Manual Inlet Valve Control Valve LCJ Sp LT Manual Outlet Valve FIGURE 2 PROCESS SCHEMATIC OF THE VILLANOVA UNIVERSITY EXPERIMENT The experiment consists of two three hour lab sessions During the first session students become familiar with the equipment and perform experimental work For this session the tank is operated at steady state with proportional control only and the liquid level set point of the tank is 50 The students are asked to eliminate a steady state offset in the tank level and after some discussion on how to resolve this issue the students are instructed to tune the proportional gain The second session consists of a dynamic simulation of the tank system with a specific disturbance chosen by students introduced into the scenario Although the available disturbances will not be listed their aim is to upset the otherwise steady system Designated roles such as time keeping data logging and disturbance initiator are distributed among the students in each group Having recorded the necessary data the students are engaged in a process simulation In this phase s
58. et and outlets 60 m 4 g FIGURE 26 VORTEX TUBE FLOW DIAGRAM IMAGE CREDIT WWW PDBUCHAN COM Before the vortex tube was physically used an energy balance had to be derived This was achieved by assuming the hot and cold outlets as completely separate streams throughout the entirety of the process even though this does not accurately represent how the system works this is shown in Figure 27 Working with these assumptions the next step was to find the difference in enthalpy in each stream In accordance with the first law of thermodynamics if there is not heat loss these two enthalpies should be equal and opposite to one another The derived energy balance is shown with Equations 3 9 3 13 mi Me 3 9 0 AH AH 3 10 AH m dT SE 0 me Tz Tj TD 3 12 0 Cp pots Ti mi mac eT 3 13 61 COLD END HOT END FIGURE 27 ASSUMED SPLITTING OF STREAMS Having derived this energy balance the gas flow apparatus was run using the vortex tube to determine if Equation 3 13 was an accurate representation of the physical experiment The measuring equipment on the gas flow apparatus can be used to find every unknown in the derived equation however some numerical discrepancies arise when specific variables are used to solve the energy balance Some of the discrepancies in the energy balance can be explained through heat loss Even still it was necessary to treat the system as isothermal
59. et and outlet of the apparatus The only pieces of equipment that will be listed in this section are those devices that are vital in the implementation of process control for this project For a schematic refer to Appendix 6 3 The heater used to heat the gas flow is a 400 watt model AHP 5051 T Type Air Process Heater from Omega Engineering Inc Stamford CT The original PID controller is a CN9000A from Omega Engineering All temperature data is provided by 10 J Type Iron Constantine Thermocouples which are read through the model NI USB 9213 Data Acquisition Device from National Instruments Austin TX The data from the USB 9213 is transmitted into a computer using the LabVIEW 2010 software with the optional Control Design and Simulation Module installed To turn the heater on the LabVIEW VI transmits a 5 Volt signal via a model NI USB 6501 Low Cost USB Digital I O Device from National Instruments This signal is sent through a model SSR330DC10 solid state relay Omega Engineering to Variable Autotransformer Variac Controller For the purposes of this project the Variac controller was always set to the maximum setting to supply 120 volts The vortex tube used in this study is a Model 20025 Stainless Steel Vortex Tube from AiRTX International Cincinnati OH The vortex tube was installed into the gas flow apparatus as a bypass component and does not receive airflow from the apparatus until all the necessary ball valves are opened For
60. etric flow Qi mi Use thermocouple 1 for temperature J Rotometer 2 Outlet volumetric flow mc Use an average of T4 and Ts K Heater Controlled by PID Vortex Tube Bypass option 104 6 3 2 WiRING DIAGRAM HTR JACKET LIMIT CONTOL OVER TEMP HEATER LIMIT Pressure Limit OMEGA Temperature Control 105 6 4 LABVIEW 6 4 1 VIRTUAL Front Panel 9452 pact ei A 106 Back Panel Initial Temperature Passive Heating Cooling to Room Temperature EH mp Max Temperature setpoint C tan Air Heat Transfer Coefficient W m 2 K Heater Interior Surface Area 2 Derived Equation and Sample Calculations for PID output Representative values from a sample experimental run are given in Table 12 107 TABLE 12 DATA FROM TYPICAL EXPERIMENT Inlet Temperature 20 Controlled Temperature 70 Inside Diameter in 0 62 Inside Diameter m 0 015748 Heated Length in 4 5 Heated Length m 0 1143 Internal Heater Surface Area m 0 111316052 Cross Sectional Area m2 0 000194778 Representative Volumetric Flow SCFM 6 628931334 Representative Volumetric Flow m3 s 0 003128502 Representative Velocity m s 16 06185681 The
61. ex tube and so the hot air had some time to diffuse into the surrounding cold air in the room and drop in temperature before reaching thermocouple 10 Below is a chart illustrating the difference between the percent differences between the recorded and calculated Tn throughout each trial 75 o a 4 21 23 25 27 29 31 33 35 37 Trial FIGURE 36 PERCENT DIFFERENCE BETWEEN The chart illustrates that there is not much significant difference between the calculated Tn and recorded Ty This similarity between calculated and recorded values holds true as long as all measurements are taken within the same minute to account for drifting in temperature as the airflow experiment runs If the experimenters wait too long to take measurements the temperatures or flow rate may drift The largest difference was 10 8 percent The average percent difference is 5 9996 and there are very few outliers throughout the process The standard deviation of these percentages is 1 72 This means that most results lie in the range of 4 2796 7 7 206 difference 75 38 of 51 of the values were within the standard range 15 8 of 51 were within two standard deviations a range of 2 5 9 4 This leaves 5 values that had percent difference greater than two standard deviations but none of values were greater than three standard deviations from the average a range of 0 8 11 2 Of the values outside o
62. f one standard deviation only 6 of the 51 were above 7 7296 and only 3 were above 9 496 error 7 values 76 were below 4 27 difference and 2 values were lower than 2 5 error The lack of outliers and consistent percent differences also justifies the experiment as an accurate way to estimate the temperature exiting the hot stream so long as all data points are recorded within the same minute The largest percent difference in this experiment 10 8 96 between the calculated and recorded values for hot end outlet temperature is likely due to a drift towards room temperature that was Observed over 45 minutes The consequences of drifting will be addressed in section 4 3 3 4 3 2 CALCULATED COLD MASS FLOW VS RECORDED COLD MASS FLOW Cold Mass Flow is or the airflow exiting the cold end of the vortex tube The mass flow was recorded by gathering the volumetric flow from rotometer 2 and converting the flow from standard cubic feet per minute SCFM to grams per minute This was accomplished using the following series of equations which are used in the existing classroom experiment to correct the rotometer reading to account for gas compressibility 04 0 4 2 3048 m 4 3 m Q Pair To find the m calculated through energy balance the Equation 3 13 was used from the methodology 0 rac T Ti rh TD 3 13 This was rearranged to H 4 4 m FIRE
63. f thermodynamics Both the virtual LabVIEW PID and physical LabVIEW PID can attain good control if tuned properly The correct tuning for each differs and both also differ from the Omega PID s optimum tuning specifications Despite the values of the appropriate PID gains being different the LabVIEW controllers offer an easy to use interface that can be used to teach students Also the energy balances around the vortex tube produced minimal differences between calculated and recorded variables This justifies the vortex tube as a teaching agent because the experiment used is easily reproducible and students should be able to record good data Classroom procedures were developed for both the PID controllers and the vortex tube The additions to the Gas Flow Apparatus are ready to be implemented as soon as possible The classroom procedures developed offer a way for the WPI Chemical Engineering Department to address the lack of process control and expand on an existing experiment 1 INTRODUCTION Chemical engineering is a field not only responsible for plant and process design but also is the discipline for the optimization and proper operation of a chemical process It is crucial that a chemical plant is designed with the proper safeguards to ensure the desired system function This subsection of the manufacturing process is called control engineering or process control and represents an important concept for current and future chemical engin
64. ful as the proportional term can greatly increase the controller s speed of response However using proportional control alone will result in offsets oscillating around the set point Increasing the proportional gain will result in much smaller offsets but does not always yield good control Love 2007 151 A good controller forces the system to reach the set point quickly and remain stable at the set point One method of determining if a controller s performance is acceptable is to examine a graph of the process variable over time This graph generally records the change in the process variable from system startup until sometime after the process reaches the set point It is important to evaluate this to be able to gauge the efficiency of the system to achieve stability under the prescribed PID gains The proportional gain term K is a user modified parameter that directly affects how powerfully the controller will respond to an error Figure 4 shows a number of different response curves 14 08 Command pGain 20 0 5 dGain 100 s pGain 20 iGain 0 1 dGain 100 pGain 10 iGain 0 1 dGain 50 mms pGain 5 iGain 0 1 dGain 50 02 FIGURE 4 PROCESS VARIABLE RESPONSE TO VARYING PROPORTIONAL GAINS WESCOTT 2000 When a small Ke value is used the controller response is weaker as shown by the dashed blue line in Figure 4 This results in a process that approac
65. g gas flow experiment For the complete front panel and back panel please refer to Appendix 6 4 Following the completion of the VI the system was set at the same set point and initial temperature that occur in the gas flow apparatus The set point was 70 and the initial temperature was 20 With a functioning VI the program was used to test different scenarios that could be presented to students during the laboratory 1 000 0 010 10 000 FIGURE 28 THE VIRTUAL PID WITHOUT DERIVATIVE CONTROL 66 Figure 28 above demonstrates how PI controller works with a 1 00 and a Ki 0 010 minutes As seen a reasonable approach was achieved and a steady state occurred in an acceptable time The initial overshoot of the set point was an error that is usually unwanted tuning of the integral time would fix this error 70 00 10 100 10 000 FIGURE 29 VIRTUAL PI WITH RE TUNED INTEGRAL In Figure 29 above the integral time was changed to 0 1 minutes whilst the proportional and derivative terms remained unchanged By increasing the Ki term the controller output a larger response to the perceived error This resulted in a much more controlled approach to the set point with no overshoot however the rise time was long relative to previous simulations The rise tim
66. g these values affect four major characteristics of a closed loop system Carnegie Mellon amp University of Michigan 1997 TABLE 3 HOW PROPORTIONAL INTEGRAL AND DERIVATIVE GAIN AFFECT THE CONTROLLER S PERFORMANCE Response Rise Time Overshoot Settling Time S S Error Kp Decrease Increase No Trend Decrease Ki Decrease Increase Increase Eliminate Kp No Trend Decrease Decrease No trend Using these three functions important changes can be made to the overall operation of the system Logic dictates that a desirable system would be one that had a low rise time reduced overshoot reduced settling time and no steady state error Auto tuning and manual tuning are two methods of tuning that are available for the Omega cn9000A PID Controller A simple tuning approach is one of trial and error yet this method alone may not yield the most desirable PID response 2 5 3 AUTO TUNING The Omega 9000 PID Controller comes with an auto tuning feature This feature allows for the PID controller itself through complex mathematical algorithms to determine the optimum operating conditions for the controller based on the deviation of a process variable during a representative run A logical starting point in investigating how to optimize the PID controller and its functions is to use the auto tune feature as a first step From previous testing it was determined that the auto tune option does not work for this specific exper
67. g towards room temperature To quantify this values were taken every minute in an attempt to evaluate whether or not this affected the validity of the energy balance It was determined that the drifting condition did not affect the energy balance so long as all measurements were taken within one minute More information on the drifting can be found in the results and discussion section of the report Since the energy balance was found to be within reason classroom procedures that instruct students to derive and justify an energy balance around the vortex tube were designed The mathematical analysis of entropy throughout the vortex tube was determined to be beyond the scope of the Unit Operations course so it was decided to include the second law of thermodynamics in the classroom procedures qualitatively 63 4 RESULTS AND DISCUSSION 4 1 MANUAL TUNING RESULTS Before the LabVIEW PID was constructed and implemented into the airflow experiment it was necessary to understand the Omega cn9000A PID Even in the event that the LabVIEW PID was successful the Omega PID would be maintained as a safe backup As the backup the Omega PID had to be set up to run conservatively and must not trip the system alarms Four main goals were required of the Omega PID 1 The settings must result in a quick rise time 2 Thetemperature must not initially overshoot 3 The settings must result in a rapid settling time 4 Thetemperature must be maint
68. ght green is displayed when the SP1 output is on 4 2 Set point 2 Indicator the light red is displayed when the SP2 output is on 5 Control Keys allow for the display of set values and change of control parameters 5 1 star displays the SP1 temperature 5 2 star up arrow pressed simultaneously will allow the increase of the set point 5 3 star down arrow pressed simultaneously will allow the decrease of the set point 5 4 P allows entry intro set up mode where Function and Option commands can be changed at user s criteria 5 5 up arrow down arrow allows change of Function and Option numbers when in set up mode 5 6 star When in set up mode allows the change between sub modes from Function to Options and vice versa In the gas flow apparatus experiment a set point temperature value described above as set point 1 SP1 has already been chosen at 70 C There is no second set point 5 2 The deviation indicators are only useful for steady state error as different indicators will flash quickly and will not be useful during the rise time or settling time of the temperature of the system A thermocouple is located close to the heater outlet in the piping configuration and this is used to monitor the real time temperature the process variable response curve instead ofthe built in indicators 31 Any analysis by students in the lab must therefore be focused on changing control para
69. h had the next possible higher percent proportional band and two which had the next possible lower percent proportional bands In other words there were no other possible predefined options within the range of values that were studied Function 6 Derivative Time was already set to the lowest value For the Derivative Time function the next two highest option values were studied It was determined from the results of the second test that no additional values were needed for the derivative time function For Integral Time the next three highest settings were selected for testing The exact values used for every test are shown in Table 6 Only one function was changed at a time in order to isolate the effect of each PID variable Whenever one function was changed the other two were set to the previous faculty tuned values as shown in Table 5 40 TABLE 6 THE SETTINGS FOR EACH FUNCTION THAT WERE STUDIED NO ADDITIONAL OPTIONS REMAINED IN THE RANGE OF VALUES STUDIED Function Setting 1 Setting 2 Setting 3 5 7 2096 1 0 5 11 796 2 30seconds 3 1minute 0 5 minutes 8 11 15 seconds 10 7 seconds N A The results from each run were graphed using an NI USB TC 01 thermocouple reader to gather the temperature data The results are described qualitatively as it was obvious the data trends did not require any statistical analysis to determine which tuning parameters were superior 3 2 2 AUTO TU
70. he PWM periods are uniform throughout the process This type of signaling is useful when it is necessary for a digital signal to mimic the behavior of an analog signal such as in a PID control setup An example of PWM is shown in Figure 9 Square Wave Duty Cycle AAT ON 0 Off FIGURE 9 GRAPH OF A SQUARE WAVE PWM DUTY CYCLE FROM INSTRUMENTATION COMPANY SCIENTIFIC INSTRUMENTS 2007 24 For example consider the desired voltage of a signal output is 10 volts but the digital device can only output 20 volts when active In this example the PWM period is selected to be 100 milliseconds The PWM signal would administer maximum voltage 20 volts for the first 50 milliseconds and then would not administer any voltage for the remaining 50 milliseconds of the PWM period The controlled device would see an average of 10 volts over the PWM period and operate as if it had received a 10 volt signal throughout the whole PWM period Technical Educational Institute of Chalkis 2001 The PWM periods are very short allowing the control to change duty cycles quickly to adjust to changes in the required voltage smoothly Figure 10 shows how a PWM signal can be generated from a comparable analog signal Analog signals PWM signal Time FIGURE 10 GENERATING A DIGITAL SIGNAL WITH PWM FROM AN ANALOG SIGNAL ACRONAME ROBOTICS 2012 One of the disadvantages to PWM is that under large voltages such
71. he VI construction began The back panel required the NI USB 9213 DAQ assistant to be wired to the PID sub VI In order to attain proper PID control with the digital output device PWM signaling had to be used A PWM structure was built using a for loop and a case structure The PID signal was then sent to the NI USB 6501 DAQ assistant after passing through the PWM structure A schematic of the Gas Flow Apparatus was drawn on the front panel so that all temperature indicators could be placed where their respective thermocouples were located on the real Gas Flow Apparatus The front panel also contains a real time graph of the PID appropriate temperature for analysis of PID control During the construction of the LabVIEW PID controllers testing on the vortex tube was performed as well The testing was to determine if the vortex tube was an appropriate method to further expand on the thermodynamic lessons in the Gas Flow Apparatus experiment Trials were performed and energy balances were performed for each trial For each trial an energy balance was used to determine the temperature of the hot stream This temperature was then compared to the thermocouple reading of the hot stream The same process was used to compare the calculated viii cold mass flow with mass flow value obtained from rotometer If the compared values were found to be close in value then the vortex tube would be determined to be an appropriate tool to teach the laws o
72. he basics of PID control i e oscillations settling time etc The goal of the experiment was simply to have the solid state relay be active until the water bath temperature reached the set point The solid state relay would then become inactive when the water bath temperature was above the set point If the heater could switch off at all it was an indicator that all PID signals were being properly sent This is further discussed in results and discussion After it was determined that the VI functioned properly the NI USB 6501 was physically wired into gas flow apparatus via the existing solid state relay There was a switch installed before the solid state relay to allow users to switch between using the NI USB 6501 or the Omega PID to send a signal to the solid state relay This was included so that it would be easy to compare the Omega PID to the LabVIEW PID Also the switch allows for a user to switch quickly if one PID should be broken rather than having to rewire the system Power to the in line airflow heater was still supplied by the Variac 3 4 VORTEX TUBE The purpose of integrating the vortex tube into airflow experiment 15 to have students gain a better understanding of the first law and second law of thermodynamics This is because the vortex tube separates the incoming air into a hot stream and a cold stream and therefore creates an interesting energy balance Figure 26 below shows a diagram ofthe vortex tube with its inl
73. hes the set point but slower than an ideally controlled process would When a slow approach is unacceptable the proportional gain is increased to speed up the initial response of the system However a high value of could possibly result in overshooting the set point which may be unacceptable for the process as shown by the dashed green line in Figure 4 The desired value of the proportional gain generally lies between the two extremes a value at which it approaches the set point rapidly but does not overshoot the target too greatly The best representation of this can be seen as the solid pink line in Figure 4 The integral term in the PID equation allows the controller to anticipate errors that have already occurred If the system has deviated from the set point multiple times in the same manner then the integral term will force the controller to respond more powerfully to that previous deviation than to a new deviation Figure 5 shows this 15 Temperature E Command pGain 2 iGain 0 1 pGain 2 iGain 0 05 pGain 2 iGain 0 02 m o 1 0 02 FIGURE 5 PROCESS VARIABLE RESPONSE TO VARYING INTEGRAL TERMS WESCOTT 2000 The largest benefit from the integral term is that it allows the controller to eliminate the oscillations inherent in the proportional term In doing so the integral term adds long term stability to the control
74. hroughout each iteration While loop A while loop is a programming structure that operates its interior functions continuously until a certain condition is met 102 6 2 2 NOTATION As Internal surface area of heat element c Proportional constant Specific heat capacity dT Temperature difference at entrance and exit of heater Cold fraction H Enthalpy K Proportional control gain Mass flow rate P Pressure p Density q Heat transfer Q Volumetric flow rate T Temperature t Time elapsed Derivative control gain 1 1 Integral control gain t Integral time 0 Dimensionless temperature X Parameter of system that can be controlled x Current value of manipulated variable Set point of manipulated variable 103 6 3 SCHEMATIC 6 3 1 GAS FLOW APPARATUS gt XV i 2 Designation Equipment Description Variable calculations A Thermocouple 1 Inlet temperature Ti B Thermocouple2 Temperature before heater C Thermocouple 3 Temperature after heater T PID process variable D 4 Temperature after valve Ts E Thermocouple 5 Temperature after rotometer 2 Ts F Thermocouple6 Temperature exiting system G Thermocouple9 Temperature of cold mass flow Te H Thermocouple 10 Temperature of hot mass flow Th I Rotometer 1 Inlet volum
75. ics pwm pdf Muske K R 2003 Simulation and Experiment in an Introductory Process Control Laboratory Experience Chemical Engineering Education 37 4 306 315 123 National Instruments 2012 NI LabVIEW control design and simulation module for windows web http sine ni com nips cds view p lang en nid 209850 National Instruments 2010 LabVIEW 2010 help web http zone ni com reference en XX help 371361G 01 O Dwyer A 2006 Handbook of PI and PID controller tuning rules 274 ed Covent Garden London UK Imperial College Press OMEGA ENGINEERING Inc n d CN9000A series autotune temperature controller User Manual Retrieved from http www omega com manuals manualpdf m1191 pdf OMEGA ENGINEERING Inc n d b Temperature control Tuning a PID three mode controller User Manual No ERG05 Online Omega Osei Prempeh G amp Silverstein D L 2010 Making a Chemical Process Control Course an Inductive and Deductive Learning Experience Chemical Engineering Education 44 2 119 126 Parallax Inc 2006 Process control student guide Parallax Inc Retrieved from http www parallax com dl docs prod sic Web PC v1 0 pdf Scientific Instruments 2007 Electrical heating PWM Scientific Instruments Retrieved from http www imagesco com articles nitinol 07 html Seal A M 1998 Practical process control Elsevier Online version available at http www knovel com w
76. ill be properly tuned and kept on a switching device in case the LabVIEW PID cannot be used In addition to PID control a vortex tube was installed to the Gas Flow Apparatus A vortex tube is a T shaped tube that separates fluids by density If the fluid is pure the vortex tube will separate the fluid by temperature A vortex tube requires no moving parts or power supply This is an interesting thermodynamic study To gain an initial understanding of PID control the Omega PID was tuned to study the effect of changing PID gains on temperature Proportional band integral time and derivative time were all modified independently of the other variables and data was recorded This study also attempted to program the auto tuning function but it was found that errors occurred too often to properly use the auto tuning function Once an understanding of PID tuning was developed a LabVIEW simulation was constructed First a virtual PID was built The virtual PID was a simulation entirely contained in LabVIEW This virtual PID was constructed to assess the feasibility of using LabVIEW as a PID in the Gas Flow Apparatus The virtual PID also offers a medium for students to gain an understanding LabVIEW and to vii experiment with PID tuning without running the risk of damaging equipment attached to Gas Flow Apparatus The construction of the virtual PID was made to emulate the Gas Flow Apparatus as much as possible To achieve this a passiv
77. iment however the reason for this failure had not been thoroughly examined This MQP will attempt to examine why the auto tuning feature of the Omega 9000 controller was inadequate and will solve the problem if possible Some of the anticipated errors expected during the investigation and their possible solutions are shown in Table 4 36 TABLE 4 POTENTIAL ERRORS ENCOUNTERED IN AUTO TUNING OMEGA N D A Errorcode Problem Potential solution EE5 Outside time limit Make adjustments to Function number 4 EE6 Overshoot exceeds limit Adjust derivative gain EE7 Unable to run Auto tune SP1 in ON OFF Make adjustments at Functions number mode 20 and 21 A more thorough explanation on how to correct any of the errors displayed in Table 4 is detailed in the user manual However it is entirely possible that other errors and not only the ones displayed above could be found in the system For a detailed method of troubleshooting the auto tuning function refer to the methodology 2 5 4 MANUAL TUNING The Simplified Method found in the PID controller s user manual is a method of manual tuning using a logical step by step approach The simplified method uses the default factory settings of the PID controller for the initial run The intention is for the user to gather data of this run by taking readings at regular intervals in order to create a graph of how the process variable changes over time Depending on ho
78. initial temperature to 20 C room temperature which are the values used during the unit operation experiment This is because the history data property node is set to clear the graph s historical values for each variable to the values defined in Figure 17 If the values are set to anything else it would result in an initial jump on the graph This initial jump in temperature may confuse students Passive Heating Cooling One of the early concerns about the VI was the active heating that takes place when the heater is switched on without PID control and the passive cooling that takes place when the heater is off For the purposes of the simulated experiment VI it was assumed that the heater would not be on without PID control and therefore active heating was not considered Passive cooling to room temperature 20 degrees Celsius was considered and an internal loop addressing the issue was programmed With the addition of the vortex tube it was shown that temperatures could drop below 20 degrees Celsius and therefore passive heating could occur The internal loop was designed with both conditions in mind A for loop was programmed inside the while loop with the number of iterations of the for loop set to one per every execution of the while loop A True False statement was created with the condition being true when the total number of iterations in the while loop is equal to zero and false otherwise When the condition is true the for loop
79. is deviation more powerfully This term adds long term stability to the system as it eliminates the repetitive deviations caused by the proportional term and serves to eliminate steady state error A common error associated with this term is integral windup where integral term is so large that its action saturates the controller without the controller driving the error signal towards zero The Derivative term is expressed mathematically as d Xset X tq dt Knowing that the proportional term responds to present error and that the integral responds due to past errors the derivative term sure enough responds to correct future error The way this works is the derivative term is able to see where the set point is and is able to steer the process variable regarding how fast to approach it The derivative term especially affects the start up of the system rise time as it helps the process variable reach the set point much faster One issue associated with this term is that it is extremely sensitive to noise in the process variable so if this term is too large any small variance will cause it to destabilize the system 86 How to evaluate a system Overshoot Steady State Error Amplitude Settling Time 200 400 600 800 1000 1200 http nasa olin edu projects 2010 tec work introCT htm When attempting to optimize a system there are many system properties which can be changed
80. is your job to properly tune the PID so that the system achieves this temperature To get the system started Log into the computer CHEMO07 right next to the gas flow apparatus Open LabVIEW and load the file PIDGFA vi from myWPI Turn on the main air line and all subsequent valves Check that the rotometers are giving a flow reading Set the flow of air to 8 SCFM Type the value of 70 into the set point text box in the front panel of LabVIEW Tune the PID gains to your desired settings N o WN e Be sure that the switch next to computer has LabVIEW PID enabled and NOT the Omega PID 9 Ifthe team wishes to record the data the run make sure the Data Collection button at the top right is clicked and says Enabled 10 Wait for the hot wire anemometer to recognize that the flow of air is sufficient by displaying a red light 11 Turn the Variac ON and then run the LabVIEW program 90 12 After every run is complete be sure to press STOP button on front panel 13 Turn off the Variac 14 Allow the GFA to return to room temperature before another run is executed Repeat steps 7 13 until you have achieved good control and have logged all necessary data This is accomplished when the GFA reaches the established set point In low rise time b With minimal overshooting c In Short settling time d And maintain steady state with minimal oscillation Be sure to run the system within the
81. ital signals which work on time based pulses A pulse is an electrical signal that is not sinusoidal but is flat and constant at a certain value In computer science this value is either on or off where on is represented by a 1 and off is represented by a 0 in binary code Pulses and digital signals are more useful for transmitting information as the voltage from a wire can be immediately determined if it is known that that wire is on or off Bucknell 2012 PID control is designed for analog signals as the average voltage of an analog signal can change by varying either the maximum voltage amplitude or the time it takes to complete a sine cycle 23 However this cannot done with digital signals which are designed to pulse at only one voltage level In order to change the average voltage of a digital signal it is necessary to change the length of time the signal is pulsed 2 3 3 PULSE WIDTH MODULATION Pulse width modulation PWM is a technique used in digital signaling to control the power output of a device PWM accomplishes this by sending out a certain amount of pulses throughout a duty cycle A duty cycle is defined as the ratio between the time the device is active and the time the device is inactive Massa 2005 A continuous process runs through duty cycles for as long as necessary The duration of a duty cycle is defined as a PWM period Massa 2005 The length of the PWM period is determined by the programmer and t
82. l term and decreased derivative term allowed for correction of error without overcorrecting or destabilizing the PID Eliminating the overshoot and reaching a steady state were the goals for tuning the PID In order to do this the integral term had to be increased so the controller would output a larger signal to correct this error 69 FIGURE 32 FINAL TOUCHES TO TUNING Figure 32 displays the final tuned gains used for the virtual VI As seen a low rise time no overshoot virtually no settling time and negligible steady state error are all achieved This means all of the parameters mentioned in section 2 5 1 were optimized to produce a stable process This demonstrates how the VI can be helpful for students in the pre lab phase as they start getting a feel for tuning a PID controller The students will be able to find how to tune the PID gains with respect to each other in order to develop a stable process With proper tuning the virtual PID can properly control a process On this basis it was determined that this VI would be helpful as part of the pre lab where students would be able to gain a feel of how LabVIEW works and how the PID gains can be tuned More importantly by using this program before the actual experiments students can understand what is safe and what is unsafe in the actual laboratory experiment For example students will be able to play with the PID gains without a
83. le is above or at the set point Bang bang control does not offer variance in the power administered Boolean Boolean is a logic algorithm in programming In the scope of this project it offers a true or false condition Case structure A case structure is a programming structure that alters a signal based on conditions being met throughout the program The condition is either true or false The case structure offers a response for both situations Cluster cluster is a LabVIEW programming operation that bunches several different types of data together for communication with another device in the program Cold fraction Cold fraction is the ratio of cold product produced to the warm product exiting the system In the case of a vortex tube this can be more easily defined as the ratio between the cold exhaust flow to the warm exhaust flow Control loop A control loop is a system which includes a controller that communicates with a regulating device The regulating device is examined by an indicator device The indicator device then communicates with the controller DAQ assistant assistant is a programming device in LabVIEW that allows the programmer to use the information supplied by the Data Acquisition Device DAQ in his her virtual instrument 100 Derivative kick Derivative kick is a phenomenon in which user changes the set point and an error is registered by the PID because the proce
84. ler One problem that can result from integral control is that it can destabilize the system by remembering errors from the past that are no longer occurring This issue can be solved by properly tuning the integral gain term System stability is important as it results in process reliability If the integral gain term 1 1 on a PID controller is too small is too large the controller will take too long to reach the set point An example of this can be seen in Figure 5 by the dashed blue line and the solid pink line Eventually the system should reach steady state at the set point however the amount of time this takes is unacceptable A different problem occurs if the integral gain term 1 t is too large This is shown in Figure 5 as the dashed green line An ideal setting for the integral gain term should reach the set point quickly but also must not overshoot or oscillate around the set point Another problem with integral term is a phenomenon referred to as integrator windup This is illustrated in Figure 6 below 16 process variable set point 60 58 5 e3 56 amp integral calculation 54 based on sum of error e t SP PV Copyright 2008 by Douglas J Cooper All Rights Reserved 10 20 30 40 50 60 70 80 90 Time minutes FIGURE 6 PID PROCESS VARIABLE RESPONSE CURVE SHOWING INTEGRATOR WINDUP COOPER 2008 Integrator windup occurs when the integral term tries to force the controller to correct a
85. ly 1 Set point blue 2 Process variable red 88 3 Signal green For the purpose of this experiment first take and record a run with the unoptimized PID settings save this graph and data for reference Then input your initial values and keep all data for further processing Physical LabVIEW PID This experiment will be using LabVIEW for the PID controller This means that the physical Omega controller will not be used but a LabVIEW one will be used instead This is an easier to tune PID and provides visuals as to what is occurring Below is a screenshot of the entire control panel of the LabVIEW PID used in this experiment 89 The physical PID control is same as the virtual PID control A schematic of the gas flow system is displayed above the graph with real time displays of the temperatures at their respective thermocouples This will allow for an instantaneous monitoring of temperatures around the system Finally this LabVIEW controller allows you to record the data and export it to Excel This should be done for the runs that demonstrate good control in order to plot the data and include the graphs in your reports EXPERIMENT For this experiment the gas flow apparatus in the second floor of the UO lab will be used The heater will be the focus of this experiment because it is controlled by the PID It is required that the system operates at a constant temperature of 70 degrees Celsius It
86. m any other effects can be lumped into a single total resistance dT Newton s Law of Cooling can be used to define heat transfer into a heat transfer coefficient if the heater s internal surface area is known q h A With this equation the total resistance is However h must first be solved 109 41 A dT _ 161 9306402 0 111316052 70 20 The units of h are apparent The heat transfer coefficient can then be applied to more general situations As an aside if the temperature difference dT and dT the difference between the controlled temperature and the inlet temperature is the considered to be the same then the heat transfer coefficient can be found in a different way This is true initially 41 mc dT A dT A aT mE As The result is equation 3 4 The heat transfer required of each iteration the controller output heat transfer in the VI is then defined as 9 q2 h dT where dT is df T T3 This controller output heat transfer is considered to be dynamic unlike required heat transfer which is constant given a constant set point Here the controller output heat transfer can be considered to be the required amount of power to overcome a difference between the currently controlled temperature and the set point The reason this dynamic heat transfer is included as an equation is out of necessity the VI works only by
87. me tuning Labview re tuned FIGURE 34 OMEGA PID VS LABVIEW PID Several tests were done to study the behavior of the physical PID in comparison to the Omega PID As shown by Figure 34 when the same gains are used for both controllers the physical PID shows the signal oscillating around 60 C This is an appreciable steady state error The Omega PID still had very good control implying that the LabVIEW physical PID tuning process would be slightly different To correct this error the physical PID integral term was retuned from 12 seconds to 2 seconds As shown above in Figure 34 the rise time is similar to the Omega PID There was still steady state error This error is not characteristic of steady state error due to tuning because the temperature does not oscillate around the set point the temperature reaches the set point and drops Other tunings were attempted but the steady state error did not change This led to the conclusion that the issue stemmed from the PWM programming used to operate the LabVIEW PID If the low signal was too long during a PWM period the gas flow would cool down too quickly One way to solve this issue would be to reduce the length of a PWM period but it is possible that the equipment could not operate with a smaller PWM period Another solution would be to use distributive PWM instead of one pulse PWM Despite these observations it was concluded that for the purposes of this process and the experiment done
88. meters described above as the Function and Option commands via the control keys to optimize the process The Function commands refer to specific parameters which will define how the PID controller operates while the Option commands refer to specific sub parameter within each Function command An easier way to represent this Function and Option concept is through an example shown below Op Fn Parameter Comment 08 5 min 300 sec 1 8 OUT Manual Reset Function 1 used 28 0 5 min 30 sec 3 8 1 min 60 sec 48 2 min 120 sec 58 3 min 180 sec 6 8 10 min 600 sec 7 8 18 min 1080 sec 88 0 2 min 12 sec 98 7 min 420 sec 10 8 13 min 780 sec 11 8 25 min 1500 sec 12 8 33 min 1980 sec 13 8 43 min 2580 sec 14 8 AT value FIGURE 13 AVAILABLE OPTIONS FOR THE INTEGRAL TIME FUNCTION OMEGA N D A The Option and Function commands are represented as Op Fn where the decimal separates the two numbers Figure 13 displays the Integral Time function Fn 8 and the several Options 0 14 each of which will change the integral time function itself As can be observed the Option numbers are assigned a specific integral time value which will affect how the set point is maintained The Omega cn9000A PID Controller has 50 adjustable Functions 1 50 which are separated into two groups Functions 1 to 25 are designated Standard Functions which are accessible to the user and are often manipulated
89. n Table 8 Full calculations are discussed in Appendix 6 4 A full page screenshot of the entire VI is also in Appendix 6 4 for further reference 51 TABLE 7 CALCULATIONS FOR VARIOUS PARAMETERS REQUIRED FOR EQUATIONS 3 1 TO 3 8 Inside Diameter in 0 62 Inside Diameter m 0 016 Heated Length in 4 5 Heated Length m 10 1143 Internal Heater Surface Area m 0 11 Cross Sectional Area m 0 0019 Representative Volumetric Flow SCFM 6 6 Representative Volumetric Flow 013 5 0 0031 Representative Velocity m s 16 Mass Flow Rate kg s 0 0032 Heat Transfer Watts 160 Heat Transfer Coefficient W m2 s 29 TABLE 8 PHYSICAL PROPERTIES OF THE AIR FLOW AT 70 C CENGEL 2010 Viscosity m s 0 00002052 Density kg m3 1 028 Specific Heat J kg K 1007 Prandtl Number 0 7177 Reynolds Number 123000 Summary The behavior of the VI is as follows 1 10 11 12 The Initial Temperature T4 Setpoint and PID gains are set by user When the experiment is run the Initial Temperature is read outside the while loop and is sent through a shift register and inside the while loop The Temperature is recorded before entering the for loop In the for loop the exiting temperature T2 is calculated by Equation 3 1 The first true false statement is applied If itis the first iteration the Initial Temperature Ti i
90. n also be textured to aid the visual distinction between them Ensuring the compatibility of wires is vital to creating a working VI 20 LabVIEW works using independent mathematical or programming functions These displayed as icons on the block diagram and generally have a number of terminals at the left and or right of them These terminals define the functions input and outputs and are generally where the required arguments are wired to the function This is shown in Figures 7 and 8 FIGURE 7 A SIMPLE OPERATION IN LABVIEW S BLOCK DIAGRAM WHERE THE NUMBERS 2 AND 4 ARE ADDED TOGETHER THE SYMBOL TO THE RIGHT IS AN INDICATOR WHICH APPEARS ON THE FRONT PANEL File Edit View Project Operate Tools Window FIGURE 8 THE SAME SIMPLE OPERATION AS SEEN THROUGH THE FRONT PANEL INITIALLY ALL UNKNOWN VALUES ARE DISPLAYED AS 0 THE SOLUTION WILL BE CALCULATED WHEN THE RUN BUTTON THE ARROW SYMBOL LOCATED IN THE TOP LEFT ON THE LOWER TOOLBAR IS PRESSED Some programming functions are of particular interest to this project This includes some programming loops which in LabVIEW are displayed as a square structure with a blank interior 21 Functions placed inside these loops are only active when loop is active and can be turned or Off by certain conditions One of these programming loops is the while loop which is controlled by the user via a conditional button on the front panel A while loop runs ce
91. n error faster than the control device can respond As the controlled variable takes longer to correct the error the controller will translate this lack of response as a need for a larger correction During startup a controller suffering from integrator windup will attempt to run the controller at an unreal maximum output as the controller tries to correct a false error Once the set point is reached the controller has already been subject to windup and as a consequence the controlled variable will overshoot the set point significantly Furthermore it will take more time than usual for the controller to decrease the process variable to the set point This error can be avoided by using sufficiently powerful equipment as it will be difficult to hit a maximum output thereby lowering the chance of integrator windup It is possible to only use the proportional and integral terms to form what is called a PI controller Wescott 2000 PI controllers generally control a system well but are still susceptible to integrator windup PI control can also fail due to the integral term s historical errors In general when defining a PI controller it is often necessary to introduce limits of integration and the range of the integrator to avoid these problems The main reason for including a differential term in a controller is that a derivative expression reduces problems inherent in PI control Including a derivative term forces the controller to 17
92. nerally a good first guess and if successful the amount of manual tuning afterwards will be greatly reduced or eliminated entirely Problems with the Ziegler Nichols tuning rules have been identified and much more complex solutions have been proposed Astrom amp Hagglund 2004 but given the simplicity of the gas flow apparatus used in this project it can be expected that the Ziegler Nichols rules apply While the Ziegler Nichols tuning rules give a good first solution they do take time to perform It was determined that the time it takes to instruct students in the theory and application of these rules of thumb outweigh the benefits of teaching them to students in the Unit Operations Laboratory The tuning rules are mentioned here in case they are later determined to be valuable for student education For the remainder of this study tuning rules are considered to be outside the scope of this MQP 19 2 3 LABVIEW The LabVIEW software program is visual programming application created by National Instruments It is programmed in G a graphical programming language and is used to create Virtual Instruments or VI s These VI s can be programmed to interact with instruments and control devices in real time or they can be used to simulate the behavior of a system virtually The main layout of LabVIEW consists of two windows that can be edited These windows are termed the Front Panel and Block Diagram The front panel is the G
93. ning classroom procedures and guidelines which will enable future students to hone their process engineering and thermodynamics knowledge skills and abilities by having hands on exposure on these topics 2 BACKGROUND In recent years process control has become an increasingly important topic for chemical engineers This trend can be attributed to many changes in the industry namely tougher competition tighter environmental controls and changes in the economy Seborg et al 2010 1 It is therefore important that chemical engineering students receive at least a basic background in process control Worcester Polytechnic Institute has historically provided an elective class CHE 4405 Chemical Process Dynamics and Control Lab to cover this requirement However ABET has suggested that students be exposed to some process control in the laboratory setting for the required Unit Operations course 2 1 EXISTING CLASSROOM EXPERIMENTS In looking for potential experiments to replicate or modify four objectives have to be met The experiment has to be 1 easy to replicate 2 easy to use by students 3 must be reliable and 4 economical to perform The proposed changes to the gas flow apparatus experiment have the opportunity to fulfill each of these requirements Although a process control experiment is not currently used in WPI Unit Operations courses other universities teach process control through various experiments Some of these experimen
94. not clear 2 Which of these is not considered a system property to be optimized a Risetime b Sampling time C Steady state d Overshoot FIGURE A OSCILLATION OF PROCESS VARIABLE AROUND A SET POINT http www widexconnect ca hip images sine wave lg gif 3 Figure A shows the oscillation of a process variable around the set point If the system s speed of response is set by outside parameters what term could be changed to obtain less oscillation around the set point a Proportional term b Integral term Derivative term Oscillation is only dependent on the quality of the controller 93 4 In reference to Figure A if decided that a specific term would decrease oscillation around set point would the term be a Increased b Decreased Oscillation is only dependent on the quality of the controller 94 reference signal 0 2 4 8 10 12 14 16 18 20 Figure B Three process variable curves each with distinct integral term values http wiki aasimon org lib exe fetch php cache cache amp media marvin lab4 ki png 5 Figure B shows three process variable curves plotted on the same graph These graphs have the same P and D terms but different I terms Which curve is the most likely to display the highest integral term a Black b Green c Red d Blue 6 Inreference to Figure B which term would be best to reduce the overshoot of the process variable above the set point a Proporti
95. nt is inappropriate Because vortex tubes require no electricity they also have an advantage over other devices where the possibility of an electrical fire is of concern An application where vortex tubes offer a distinct advantage is when combustible substances are involved Another example of this technology s application is the use of vortex tubes in refrigerated suits for workers in foundries or other extreme heat environments 2 5 GAS FLOW APPARATUS EXPERIMENT The previous gas flow apparatus experiment instructed students to analyze the effects of operating pressure and mass flow on the pressure drop through the system There was also a section that required students to analyze the effects different temperatures would have on the compressible flow Lastly students were required to perform an energy balance around the heater on the gas flow apparatus A schematic of the gas flow apparatus can be found in Appendix 6 3 In the Unit Operations Laboratory an Omega 9000 PID controller is currently located the gas flow apparatus The controller is used to regulate the amount a heater changes the air temperature within the airstream The heater used in the unit operations laboratory is a powerful device with a maximum output of 400 watts When the heater is operating at full power it can easily surpass the maximum operating temperature of the Coriolis meter attached further downstream For this process manual control is difficult and
96. ny consequence of damaging equipment Furthermore the front panel was created and organized in such a way that the students have a user friendly experience as well as an intuitive approach to the program Also the simultaneous plot of three data sets temperature set point and signal allows the user to easily see how the temperature relates to the set point and how the signal strength of the PID relates to the error and PID gains 70 However one minor error was detected in final version of the virtual It was discovered that whenever the initial temperature had a value different from 209C the graph would spike to zero and would then immediately settle at the prescribed initial temperature Although it was detected early in the project stages and a correction was attempted several times it was not possible to solve the issue because of the passive cooling equation that is essential to the process Although this error is small and innocuous to the long term controlling functions of the PID package in LabVIEW it did represent a setback for two reasons First the virtual PID package would not be able to replicate the GFA experiment with 10096 accuracy because of varying room temperatures This is also relevant because it will not be able to replicate the process when using the vortex tube for proposed disturbances Second this deficiency in the virtual experiment could lead to confusion by students and also to misleading conclusions
97. ocess control including the inherent ability to reduce sensitivity and the ability to provide a corrective action regardless of the source of disturbance The control described for Figure 3 is a feedback loop Feedforward loops by contrast are loops where the sensor takes a measurement of the process variable sometimes specified as the disturbance variable or the input variable before it has been affected by the process For example in a vessel with inlet feed a feedforward loop would attempt to correct any problem with the inlet feed before filling the vessel Feedforward control allows for corrective action before large deviations occur in a process One limitation of feedforward control is that it can at times result in offsets An offset is when a process variable is held steady at a value other than the set point This is because feedforward control monitors the process variable before it is affected by the control device In doing so the controller cannot always properly estimate the difference between the current value of the process variable and the set point It is possible for feedback and feedforward control loops to be combined into more complex control loops However this is not common A more complex controller can become expensive and can occasionally require more oversight from a technician Often times an inexpensive feedback or feedforward loop will accomplish the same task to satisfaction A widely used type of cont
98. ol responds to the noise and can introduce instability to the process One of the challenges with tweaking the derivative gain term is limiting the amount of derivative kick when the system is subjected to a disturbance or change in the set point If the derivative gain term is too large the controller will pick up the instrument noise which will be reflected in the behavior of the manipulated variable A large derivative gain term will also be sensitive to derivative kick A small derivative gain term will not contribute much to the PID controller and the controller may begin to show some integral destabilization Again achieving ideal behavior relies on picking a derivative gain term that is between the two extreme conditions Due to the differential term PID controllers can be noise sensitive Wescott 2000 However the main symptoms of poor tuning overshooting oscillations noise sensitivity are generally easy to spot if graphed against a constant set point Proper tuning based on manual manipulation or even better a theoretical basis should result in acceptable process control One benefit of PID control is the ease at which the controller can be tuned without a dedicated mathematical model The main advantage to PID controllers is the long term stability offered by using the proportional integral and derivative terms in concert with each other 18 2 2 3 TUNING Tuning a controller is generally one of the more tedious
99. onal term b Integral term c Derivative term d Overshoot is a property inherent of the system itself and can t be controlled 95 7 Whatis main drawback of using high derivative term a b 4 Will affect set point value Extreme sensibility to process variable noise Increased overshoot None of the above 96 6 1 2 CLASSROOM PROCEDURES FOR VORTEX TUBE Goal of the experiment Develop an energy balance around a Ranque Hilsch Vortex Tube What is a Vortex Tube Vortex tubes are T shaped tubes that are able to separate compressed air into simultaneous hot and cold streams A picture of a Vortex Tube is shown below http www process controls com techsales Nex Flow images vortex tubes vortex tube new jpg This equipment requires no moving parts to separate the streams Inside has a corkscrew shaped lining referred to as a swirl chamber It is this design that separates the faster moving particles from slower moving particles This can be used in multicomponent separation by density Vortex tubes have several practical applications such as a method of point cooling in manufacturing or as a method for enriching Uranium In Goddard Lab we will be performing a single component separation using compressed air In this single component separation the faster and slower particles correspond with hot and cold molecules As compressed air is fed through the inlet at the top of the T shaped tube the air flows
100. orical values 46 Figure 18 The internal for loop that controlled passive heating and cooling 47 Figure 19 The PID sub VI and related equations as they appear in LabVIEW The PID gains were set by the user Signals travel from left to 50 Figure 20 NI USB 9213 DAQ assistant and indicators sese 55 Figure 21 NI USB 6501 DAQ assistant with Boolean 56 Figure 22 PWM programming The True case is shown for the case structure 56 Figure 23 Condition to shut off 57 Figure 24 Write to file block tante ttn ttn tent tetto tta tentoria 58 Figure 25 Front Panel de cde og dra E s dep Rer did deed 59 Figure 26 Vortex tube flow diagram Image Credit www pdbuchan com s 61 Figure 27 Assumed Splitting of streams sese senten tnnt tente 62 Figure 28 The virtual PID without Derivative CONtIO 66 Figure 29 Virtual PI with re tuned 67 Figure 30 Addition of a derivative term eese tentent 68 iii Figure 31 Figure 32 Figure 33 Figure 34 Figure 35 Figure 36 Figure 37 Figure 38 Figure 39 Figure 40 Figure 41 Figure 42 Figure 43 Figure 44 Figure 45 Figure 46 Figure 47 Figure
101. ple operation as seen through the front panel Initially all unknown values are displayed as 0 The solution will be calculated when the run button the arrow symbol located in the top left on the lower toolbar is pressed essent tentent tente tna tante 21 Figure 9 Graph ofa Square Wave PWM Duty Cycle from instrumentation company Scientific Instruments 2007 b iet eit eredi i e Ru e diee t P bie iae codo bends 24 Figure 10 Generating a digital signal with pwm from an analog signal Acroname Robotics 2012 D OPES 25 Figure 11 Sketch displaying airflow through an AiRTX vortex tube AiRTX International 2007 27 Figure 12 Front view of CN9000A PID Controller Omega 30 Figure 13 Available Options for the Integral Time Function Omega n d a sss 32 Figure 14 Characteristics from data needed to optimize process Omega 38 Figure 15 Block diagram for Simulated VI wiring The Initial temperature value changes after the passive cooling amp Heating loop to T This temperature is controlled by the PID and is changed to The value of T is used as the value of T for the next iteration 45 Figure 16 three variables enter a cluster and are graphed in real time 45 Figure 17 The property node created to clear the graph s hist
102. programmed to operate throughout the PWM period of 100 milliseconds The for loop was set to run an iteration every 10 milliseconds and ran ten iterations per PWM period The duty cycle was divided by 100 to express it as a percentage and then multiplied by 10 This was done because there are 10 iterations for every PWM period and the percentage multiplied by 10 is the number of pulses administered throughout the PWM period The duty cycle percent value multiplied by 10 is compared to the number offor loop iterations If the duty cycle percent value is greater than or equal to the iteration number then this creates a true response to the case structure In this case the case structure does not alter the value and a 1 response would be sent to the Boolean array As previously mentioned this triggers a high output from the DAQ and ultimately activates the solid state relay and powers the heater If the duty cycle percentage multiplied by 10 is less than the iteration number then this creates a false response in the case structure In this case a not node is triggered and a value of 0 is sent to the Boolean array signaling a low output from the DAQ and leaving the solid state relay deactivated ub E 1 Output Signal FIGURE 22 PWM PROGRAMMING THE TRUE CASE IS SHOWN FOR THE CASE STRUCTURE 56 As an example the PID outputs a signal with a value of 50 out of a possible 100 This would create a 5096 duty cycle or a 0 5 duty cycle
103. ranges given since this will ensure the safety of the airflow system its equipment which is expensive and the students themselves who are doing the experiment Variable Range Proportional gain 0 20 Integral time min 001 5 Derivative time min 001 05 Set Point 70 9C Some questions to be thinking about as the experiment is being ran How did each term affect the system Werethere any terms that were best kept at low values relative Wasthere instability in the system that could be easily attributed to a specific term REPORT For this experiment a report is to be handed in highlighting the team s findings difficulties and final results Please discuss What gains worked and what gains did not work in this experiment Why did the final set of gains work so effectively Include a graph of the final control run and any other appropriate runs What was the hardest gain to tune in the experiment 91 Imagine the Vortex Tube was turned on during middle of the experiment What kind of effect would this have on the control of the process and the PID What potential sources of error can you think of human ambient etc 92 PRE LAB QUESTIONS 1 What does the term PID stand for Proportional Instantaneous Derivation a b Proportional Integral and Derivative Piping and Instrumentation Diagram a The acronym cannot be defined as the context is
104. raphical User Interface GUI that is commonly found in distributed software packages This window generally contains all of the necessary graphs icons and indicators to inform the user about what is happening to the system being studied The front panel also often contains numerical inputs controls and other devices to allow them to manipulate the system to achieve the desired behavior The block diagram of LabVIEW is the area where the graphical code is manipulated National Instruments 2010 It is named the block diagram because the window appears to be a simplified diagram often drawn by engineers to quickly communicate the basics of a system In the block diagram common programming operations are represented by different icons These icons can represent mathematical operations loops arrays strings and many other different types of operations 2 3 1 CONSTRUCTING A VI Each programming operation in LabVIEW is connected with wires which are visually representative of how each operation is interdependent Data moves down the wires from input to output of each operation Wires are categorized into several types string numerical double integer dynamic data et cetera depending on which particular type of operation is being performed These wires are all colorized depending on their data type The wire colors used in this paper VI s are yellow double integer blue numerical amp dynamic data and brown cluster data Wires ca
105. rature Input Controller ACSystem L Controlled Process FIGURE 3 BLOCK DIAGRAM DEPICTING THE COOLING SYSTEM FOR A HOUSE Figure 3 shows that once the set point is defined the sensor will force some response from the AC controller Every control system is made with the same general components a sensor a controller and some type controlled equipment 2 2 1 TYPES OF CONTROL In process control the type of control is often defined by its control loop The basics of a control loop have been developed in the previous example A control loop is a concept involving a process a controller a control element and a sensor The sensor transmits data to the controller which forces the control element to change its operation which creates an effect measured by the sensor If this cycle is continuously repeated each element can be symbolically represented as a circular loop The simple example of a bang bang control loop has been described in the example given with Figure 3 Many different types of control exist with several explained in the following paragraphs A feedback loop is a loop where the sensor takes a measurement of the process variable sometimes specified as the control variable after it has been affected by the process Seborg et al 2010 The measurement is then sent to the controller which creates a corrective action if necessary 10 Feedback loops have many distinct advantages in pr
106. reak Protection Output 1 21 Sensor Break Protection 33 Not every function is relevant to this investigation As examples Function 9 is only used for calibration and Function 11 controls an unused second output This research will only focus on the functions that are seen as especially significant in stabilizing the set point temperature value for the heater in the gas flow apparatus The main part of this investigation is focused on researching how changing certain Functions of the PID controller could affect the stability of the set point temperature As seen in Table 1 there area significant number of functions that can be varied that change how the controller functions After analyzing the list carefully it was determined that only five of these Functions would be investigated in this research as they should have the greatest effect on the operation of the controller This shortlist is shown in Table 2 with a much more thorough explanation of the functions and their effect on the quality of control of the system 34 TABLE 2 RELEVANT FUNCTIONS FOR THIS INVESTIGATION Function Comment Cycle time On Off Also known as the Proportional Time cycle time will determine the total length of time that the output will cycle on and off when the temperature is within the Proportional Band This means that if the PID control calls for an output duty of 2596 and the cycle time is 4s the output will be on for 1 se
107. rol is Proportional Integral and Derivative control Wescott 2000 Often abbreviated to PID control this control system is used because of its simplicity stability and adaptability The majority of loops in industry are feedback loops and a large percentage of these feedback loops are PID loops Astrom amp Hagglund 2001 It has been estimated that over 9096 of all control loops are PID loops In some fields the estimated figure is even greater Desborough amp Miller 2002 Itis therefore necessary to instruct chemical engineering students in the basics of PID control to better prepare them for industry Itis this method of control that is the primary focus of this MQP and is the method that will be taught to students in the Unit Operations class should this project s conclusions be implemented 11 2 2 2 PID CONTROL The term PID Controller stands for Proportional Integral and Derivative Controller In this case the nomenclature is straightforward the controller is made up of proportional integral and derivative mathematical components University of Michigan 2009 The three main equations in their simplest forms are Proportional A x t c 2 1 Integral 1 t ot 22 0 Differential d X Xset 6 23 dt Where Xisthe parameter of the system that can be controlled xisthecurrent value of the manipulated variable e 15 set point of the manipulated varia
108. rtain programming functions continuously until a specific condition is met For the purposes ofthe VI s developed in this project the stop if true condition was used which adds a button labeled STOP to the front panel This button is a terminal condition to the while loop and activating it stops all calculations under the while loop s control This condition is important because until the button is pressed the heater in the gas flow will be active The for loop is another important programming loop The for loop executes its interior functions a set number of times every time the VI is run case structure was also used which is a way to perform different mathematical operations depending on whether or not a set loop condition is true or false Case structures used when calculations need to be changed based on certain conditions of the overall program A true condition will activate one set of calculations while a false condition will use a different set of calculations Another LabVIEW function important to this project is the cluster A cluster is a function used to group several different data types together This grouping reduces the number of wires and allows the values of each data source to be manipulated and recorded together For this project the cluster function is especially useful for graphing many different data sources together on one chart Also important are property nodes which can force a function to behave in a cer
109. ry simple processes to much more complex systems An example of a simple process is a household thermostat while a more complex system may be a centralized control room operating an entire chemical plant For the control of a particular process a specific attribute is often monitored using a sensor This could be a pressure gauge thermometer manometer or other measurement device Measurement devices are often called transmitters as they take the physical phenomenon as measured by the sensor and change it into a useful signal Seal 1998 xvii The signal from this sensor is relayed via the transmitter which uses pneumatics electrical impulse or other signals to a controller that reads the information and compares it to a set point or target value If the reading deviates more than a prescribed range the controller will command an action to reach the set point such as opening or closing a valve The device that responds to the controller is termed the control device Based on the set point the controller will drive a device to as close to the desired value as possible More complex controllers offer a greater degree of modulation with the aim of maintaining more precise control on the system Controllers that can vary the strength of the control device response were Classically termed throttling controllers Ziegler et al 1942 These devices will sample at a higher frequency and react more rapidly than other commonly found de
110. s chosen If it is not the first iteration the temperature calculated in step 4 T2 is chosen The result exits the for loop The temperature T2 exiting the for loop is used as the PID input while also continuing on to solve the controlled temperature T3 in Equation 3 8 The PID responds according to the user defined gains and tries to approach the set point The PID Output q2 is recorded The current temperature Setpoint and PID output q2 are graphed The static heat transfer q1 is calculated If the difference between the static heat transfer and the PID output is negative then a value of 0 for 4115 used in Equation 3 8 instead Equation 3 8 is solved yielding the controlled temperature T3 200 milliseconds later the value of T from the while loop s exit shift register is sent to the entrance shift register and the calculations are repeated The experiment ends when the loop is stopped or the VI is aborted 53 3 3 3 LABVIEW PHYSICAL EXPERIMENT In order to develop a VI for the physical LabVIEW PID the Data Acquisition Devices DAQs needed to be physically wired to the appropriate hardware The first DAQ used was the NI USB 6501 This DAQ is a digital input and output Digital 1 0 device capable of sending a digital signal of 5 volts For this project the NI USB 6501 sent an output signal to a solid state relay A solid state relay is a type of electrical switching device It requires a device sending a
111. sing this causes the hot mass flow to increase Since the hot mass flow is larger the hot temperature must decrease so that the energy balance is still satisfied 80 Drifting occurs after an extended period of time and is illustrated in the figures below Recorded mc Calcularted mc 20 3 9 2 gt o 20 30 40 Time minutes FIGURE 39 RECORDED VS CALCULATED COLD MASS FLOW THROUGH DRIFT 81 99 w Th Recorded N Calculated a E 9 5 25 E 29 30 Time minutes FIGURE 40 RECORDED TEMPERATURE VS CALCULATED TEMPERATURE THROUGH DRIFT As discussed previously the drifting does not detract from the validity of the energy balance as long as values are all recorded within the same minute 82 5 CONCLUSION This study determined that both LabVIEW PID and vortex tube improved existing Gas Flow Apparatus experiment in both content and length Classroom procedures were developed which will explain to students how the additions to the GFA could be effectively used in the Unit Operations course These procedures also includ instruction in a digital replication of the PID in LabVIEW which will allow students to learn the basics of PID control without the danger of damaging equipment on the Gas Flow Apparatus The LabVIEW PID successfully controlled the temperature of
112. ss variable is identified as being no longer at the set point This causes a rapid response to reach the new set point usually resulting in drastic overshooting Digital signal A digital signal is a pulse train signal that switches between a high value and low value voltage Duty cycle A duty cycle is the percentage of time a digital device is emitting a high signal pulse throughout a PWM period Feedback loop A feedback loop is a control loop in which a controller responds to errors after the process has affected the process variable Feedforward loop A feedforward loop is a control loop where the controller responds to errors before the process has affected the process variable For loop A for loop is a programming structure that operates its interior functions programming predetermined number of times while the program is running Integrator windup Integrator windup is a phenomenon that occurs when the integrator control causes a controller to change a process faster than the device can operate This causes the controller to see more error and thus the problem builds on itself Local variable A local variable is a LabVIEW programming function that allows the programmer to define a value to a variable Noise Noise is a random fluctuation in an electric signal Not node A not node is a LabVIEW programming function that sees a function and returns the logical opposite In other wor
113. t and the desired set point value 29 These attributes represent four major characteristics of a closed loop step response system Within this experimental framework itis possible to use these concepts as guidelines to evaluate how effective the LabVIEW and Omega PID controllers are 2 5 2 EXPLANATION THE OMEGA PID CONTROLLER This section offers a thorough explanation of the Omega PID system as students will still be able to use it even after the LabVIEW PID is installed Figure 12 below shows the front view of the controller and labels the main interface FIGURE 12 FRONT VIEW OF CN9000A PID CONTROLLER OMEGA N D A Where each numbered feature is explained below Omega n d a 1 LED Display a four digit display that usually shows the process temperature of the system When in set up mode it shows Function number on the right and Option numbers on the left relative to the floating decimal point 2 Deviation Indicators these three lights show the difference between the set point temperature and the process temperature as detailed below 3 Error Indicators when 30 3 1 Flashing up triangle 396 above set point value 3 2 Steady up triangle 196 to 396 above set point value 3 3 Steady square 190 about set point 3 4 Steady down triangle 196 to 396 below set point value 3 5 Flashing down triangle 396 below set point value 4 SetPoint Indicator 4 1 Set point 1 Indicator the li
114. tain way Property nodes of a function are created in reference to a single function and can control many details about it For example property nodes are used in one of the VI s produced for this project to clear the data history of a graph The LabVIEW software package comes with many such functions but occasionally operators of the equipment find that more complex functions are required For this project the optional Control Design and Simulation Module was required and was installed on a WPI owned laboratory computer description of this module can be found on the National Instruments website 2012 There is much more that can be said about LabVIEW s functions such as branching wires and creating complex programming arguments However many of these functions are outside the scope of this project After the VI has been completed the programmer typically locks out the editing feature before handing it over to the user This action ensures that the user will not be able to accidentally alter a VI which could potentially corrupt the file and render it unusable 22 LabVIEW is most useful when Data Acquisition Devices DAQ s are used in conjunction with it DAQ s are real world instruments which monitor and record various system parameters such as temperature pressure or voltage A DAQ can also be used to output signals to the system which is especially helpful for process control This project uses 2 DAQ s One is an NI USB 9213
115. ter a square route extractor I P transducers and a storage tank Osei Prempeh amp Silverstein 2010 This setup can be connected to a control panel that includes an industrial type PID controller The second device is a Process Plant Trainer which includes three plate heat exchangers two feed tanks various solenoid valves control sensors and thermocouples This setup allows for the simulation of simple and complex operations that chemical engineers might encounter in industry This setup is also connected to a control panel with a PID which allows for stable control of the system There are five experiments performed on the two devices in this semester long class All of the experiments touched on process control One of the experiments is centered on PID controllers and feedback in a closed loop system this experiment can be performed on either of the devices The experiment itself consists of students tuning the controller to make the system either stable or unstable Students are then able to observe the difference between a proportional and a proportional integral control of the system by tuning the PID appropriately 2 2 PROCESS CONTROL Process Control refers to the regulation of one or more system parameters in an experiment such as temperature pressure or flow rate Parallax Inc 2006 Generally speaking these parameters are variables that can be measured by sensors and instrumentation The systems may range from ve
116. the compressible fluid in the experiment and offered a more user friendly interface to users than the Omega PID controller Students using this experiment will now have a real time display of the individual temperatures around the system and a real time graph that will allow them to see how well controlled the process variable is with regards to the set point Furthermore students would have the option to collect data from the run which will allow them to plot the recorded information and analyze these visual results The other component of this study the vortex tube was also tested and was confirmed to be reliable The vortex tube will pose a feasible and interesting challenge in thermodynamics for future users This study determined that the exercise of defining and solving an energy balance around the vortex tube is appropriate for students taking Unit Operations and will reinforce their knowledge of thermodynamics Moreover the vortex tube can also be used to introduce a disturbance for the LabVIEW PID This disturbance will show students that a properly tuned controller can operate within a wide range of conditions Future recommendations include a more in depth study of PWM The current model of PWM creates a steady state error It was determined that programming PWM as a distributed signal instead of a single pulse signal may solve the error but the methods to accomplish this were beyond the scope of the project Additionally a more in
117. the initial water bath experiments a model EMH 060 120V Screw Plug Immersion Heater was purchased from Omega Engineering A model NI USB TCO1 Thermocouple Measurement Device from National Instruments was used to read the temperature of the water bath experiments and transmitted it to the computer for the LabVIEW PID to read This model of thermocouple reader was also used for the gas flow apparatus while the NI USB 9213 was on back order 39 3 2 OMEGA TUNING The Omega PID had already been tuned by WPI faculty before the project began It was necessary to validate that the PID was tuned to the best possible settings if it was to continue being used for the gas flow apparatus experiments In addition the LabVIEW PID would likely use similar settings and it was possible that changing the most important functions would result in a better understanding of the necessary PID parameters 3 2 1 MANUAL TUNING The only functions changed were functions 5 6 and 8 These functions correspond to the 3 gain terms from each PID parameter The faculty tuning settings are shown in Table 5 TABLE 5 TUNED SETTINGS FOR THE OMEGA PID Operation Function Function Operation Value 13 5 Proportional Band Deadband 1496 7 6 Derivative Time Rate 1 second 8 8 Integral Time 12 seconds Function 5 Proportional Band was at a setting where both higher and lower values were possible Three new options were tested one whic
118. ther VI was programmed to control the gas flow apparatus s heater The main component to each VI design was the PID sub VI which read the data and controlled the temperature Any variable categorized as user defined in the following paragraphs can be manipulated via the front panel 3 3 2 LABVIEW VIRTUAL EXPERIMENT Assumptions The virtual VI had to use a representative data set in order to be accurate For this data set the inlet volumetric flow was assumed to be 6 6 SCFM at 20 C which was the operating condition used for all data in this experiment This should be similar or identical to the operating conditions used by students during the gas flow apparatus laboratory The following assumptions were made while setting up each calculation 42 1 The properties of air are constant 2 Theinlet flow temperature is constant 3 The set points and initial conditions of operation will not be changed These assumptions made it possible to construct a simple VI that still properly demonstrates both the gas flow apparatus conditions and the basics of PID control A while loop was essential to the simulated VI as this loop can operate continuously Continuous operation of a VI allows the user to view the development of a process parameter over time The difficulty with modeling the gas flow apparatus with a while loop is that the loop can only make calculations based on each iteration This leads to a few different possible appro
119. ts are worth mentioning in this paper as they highlight the teaching methods used by other institutions as well as the importance placed ona basic knowledge of process control Some of these experiments are described below 2 1 1 RPI STUDIO CONTROL LAB WITH PID CONTROLLER Rensselaer Polytechnic Institute RPI currently uses PID controllers in a salt water concentration experiment for chemical engineering students to study in a studio laboratory class Bequette et al 2000 In this experiment fresh water is provided on tap while concentrated salt water is stored in atank The fresh water flow rate is manipulated by a manual valve while the salt water flow rate is inferred by the pressure in the closed tank Fresh feed water is heated by an electric heater before mixing with the salt water in a continuous stirred tank reactor CSTR The CSTR contains a temperature probe which measures temperature of the mixture before discharging mixture The effluent flows past a conductivity sensor before being emptied into a sink The goal of the experiment is to regulate the fluid level temperature and conductivity of the salt water in a tank This is accomplished by regulating the power to the heater as well as the inlet flow rates of the fresh and salt water streams After attempting fully manual control the students are taught the theoretical basis of modeling control loops and feedback control Students then attempt to control the pro
120. tube separates compressed air into hot and cold streams An energy balance was derived for the vortex tube Classroom procedures were developed to use these devices for the Unit Operations course vi EXECUTIVE SUMMARY Process control is important in today s world and needs to be taught to chemical engineering students Currently several institutions other than WPI teach process control in a laboratory setting Since ABET has recommended that the WPI department of chemical engineering offer students more process control instruction in laboratory settings it is in the best interest of the chemical engineering faculty to comply PID control is one of the most common forms of process control and it is already used for a Unit Operation experiment This Gas Flow Apparatus experiment has been identified as being brief and plans were in place to expand on it By adding a PID control module and a vortex tube it is possible to expand the current experiment to a more thorough and interesting laboratory investigation A PID from Omega Engineering is currently installed on the Gas Flow Apparatus but is difficult to use as an instructional tool The LabVIEW software is relatively easy to program without extensive prior experience By programming a PID controller into LabVIEW it can be used to control the current gas flow heater This Virtual Instrument will also allow students to directly modify the PID parameters The Omega PID will not be discarded It w
121. tudents can predict the behavior of the tank level over time by making appropriate assumptions and using mathematical correlations Through this laboratory students are able to experience the actual response time of a physical system Furthermore by using the proportional only controller adjusting the valves manually and using the system in both open and closed loop settings students are exposed to a hands on process control experience Chemical engineering students at Villanova have claimed this laboratory is a valuable addition to their process simulation and control education Muske 2003 This feedback emphasizes the importance of laboratory experiments 2 1 4 UNIVERSITY OF 5 CHEMICAL PROCESS CONTROL COURSE The University of Kentucky currently offers a senior level process control course with both a lecture and a laboratory component This class is focused on offering students an inductive learning experience where specific observations are used to lead the student to more general conclusions Additionally the experimental portion offers hands on experience that reinforces the theory learned in class The lab component of this course uses two experiments to demonstrate the theory in practice The firstis a pressure regulation apparatus This apparatus is similar to the gas flow experiment currently operated at WPI The experimental setup consisted of a pneumatic control valve various pressure gauges an orifice me
122. urrently meet its full potential as an instructional laboratory tool It is possible to add a process control component into the existing gas flow experiment which will hopefully solve both the brevity of the experiment and also address the ABET requirement of increased process control experiences In order to accomplish this task the existing gas flow experiment in the unit operations laboratory was modified A PID controller regulates a heater in the gas flow apparatus which increases the air temperature in the experiment The increase in temperature causes the density of the air to change which affects readings on various instruments downstream from the heater Although this PID acceptably controlled heater it was cumbersome to operate and was not useful for instruction This MQP proposed that the current PID be replaced by a digital PID controller that is easier to use and a better process control learning device In addition while the airflow experiment was being updated there was an opportunity to add a small and interesting thermodynamics component to the experiment This was accomplished by installing a vortex tube further described in the background The main objectives of this project were e Digitizing the current PID controller using the LabVIEW software program Including a vortex tube in the circuit in order to expand the thermodynamics based laboratory The completion of these objectives was finalized by desig
123. via previous values of iteration Without both heat transfers defined the VI was shown to record a drastically incorrect PID output power Since the PID output is recorded the controlled temperature can then be solved for 110 q2 91 A h The result is equation 3 6 Since q As h and T are known at any given iteration can be solved if the value of is recorded by LabVIEW 111 6 4 2 PHYSICAL Front Panel labview vs omega labview 112 Back Panel 113 6 5 VORTEX TUBE 6 5 1 ENERGY BALANCE DERIVED PaTs Qa Qn PT 3048 mJ Qa L Dair tit 0 AH AH m cy dT 0 cy mc CT Tj m T 0 co mc CT mi T 6 5 2 ENTROPY EQUATION DERIVED 5 gt 0 Q AH mcAT AH mAT mAT dS mAT mAT Cp dt T 114 6 6 RAW DATA 6 6 1 OMEGA TUNING 80 70 CN f NEN VNNVVVVVVV ME of J 30 Temperature C 20 10 o N o 40 60 80 100 120 Time seconds FIGURE 41 P BAND 0 5 INTEGRAL TIME 125 DERIVATIVE TIME 1S 115 e gt 60 Time seconds FIGURE 42 P BAND 7 INTEGRAL TIME 125 DERIVATIVE TIME 15 w Temperature 9C B o N nd 60 Time seconds FIGURE 43 P BAND 20 INTEGRAL TIME
124. vices As a representative example consider the cooling system for a room A person inside the room sets the temperature for the Air Conditioning Unit AC Typically this is done by adjusting the setting on a thermostat sensor On a hot summer day the occupant may lower the set point temperature to cool down the room This system set point is then compared with the temperature measured by the thermostat s sensor If there is an appreciable difference between these two values the AC will work to drive the temperature to the set point In this example the main process variable is temperature and the control system will require a sensor that monitors temperature and provides feedback to the controller If the temperature sensor reads a temperature different from the set point it will drive the cooling equipment to get it tothe target The cooling system will accomplish this by delivering cold air to the room until the thermostat reaches the prescribed temperature set by the occupant If the temperature of the room is equal to or lower than the set point the controller will stop the flow of cold air This control method is referred to as Bang Bang control also called On Off control and cyclic control where a device can only be fully on or fully off at any given time and is one of many possible control scenarios Figure 3 is a simple block diagram that illustrates this example of process control Temperature Tempe
125. vides feedback to the controller This means that if the temperature sensor gets a reading off the set point it will drive the cooling equipment to get it to target either by varying the supply of cold air to the room or by ceasing to do so depending if the temperature is too high or too low A PID controller is a controller system widely used in industry and which will be used in this experiment via the instrument control and data acquisition program LabVIEW What is a PID Controller and what are its uses in industry The term PID Controller stands for Proportional Integral and Derivative Controller In this case the nomenclature is straightforward the controller is made up of proportional integral and derivative mathematical components Ang 2005 which will be discussed in depth later in this document 84 PID controllers are extremely important instruments in the chemical industry Their usage is extremely adaptable and extends to the chemical petrochemical paper food amp beverage water treatment sewage facilities and many more PID controllers are used to control process variables as diverse as fluid flow fluid level pressure temperature pH consistency density position concentration etc Having some idea or instruction in this control device and in process control in general will be extremely beneficial when working in the industry This pre lab will introduce the student to some basic theory on how
126. w well the pre set settings of the controller fit the current system the resulting graphs will show how the process variable differs from the desired system behavior A sample graph is illustrated below 37 _ amplitude Period FIGURE 14 CHARACTERISTICS FROM DATA NEEDED TO OPTIMIZE PROCESS OMEGA N D A As shown in Figure 14 once a graph is plotted information such as the response period T ofa complete cycle and the amplitude of the oscillation is extracted from the graph Parameter values can be calculated using a set of equations shown below once the period and amplitude of a cycle are recorded Operator Adjustments Omega n d a 1 Proportional Time T 20 If 10 seconds or less use pulse output model 2 Proportional Band 96 A 1 5 100 Full Scale Set to next larger 96 setting 3 Derivative Rate Time T 20 Set to next shorter setting 4 Integral Reset Time T The resulting values from these equations are input into the controller instead of the initial default PID gains The system is run again and re evaluated under these new conditions This method is usually good for estimating values for controlling a system and often yields acceptable results These values can be further adjusted to give optimum performance 38 3 METHODOLOGY 3 1 EQUIPMENT The gas flow apparatus consists of a series of interconnecting inch schedule 40 piping Several instruments are installed between the inl
127. was displayed graph located on the front panel At the next iteration all calculations would occur again This process is shown graphically in Figure 19 mep PID gains ESI als 0075 Heater Surface Area m 2 FIGURE 19 THE PID SUB VI AND RELATED EQUATIONS AS THEY APPEAR IN LABVIEW THE PID GAINS WERE SET BY THE USER SIGNALS TRAVEL FROM LEFT TO RIGHT The application of Equation 3 8 does result in a few unfortunate consequences as 1 15 constant when the total temperature difference is defined Firstly the set point temperature cannot be very different from 70 Otherwise the wattage output by the heater will not be accurate This issue was originally addressed by having LabVIEW read the values of the initial temperature Ti and the current temperature T3 instead of defining dT as 40 C However this resulted in some unusual bugs in the VI and was abandoned in favor of a constant value of q1 Secondly the temperature response curve shows no change until q becomes larger than 41 This is inaccurate as even a minuscule wattage will result in some appreciable temperature difference 50 Luckily this delay is usually only second so long and is not considered to be significantly disruptive to the laboratory experience The results from Equations 3 1 3 5 are shown in Table The physical properties of air used to calculate some of the results in Table 7 are listed i
128. would execute using the Initial Temperature variable When the condition is false a passive heating and cooling equation described in the next few paragraphs would execute in the for loop 46 A local variable of the Initial Temperature was created and programmed outside both the for loop and while loop A local variable is a LabVIEW function which allows the program to either read or write a double integer value to a variable This particular local variable was set to read the value from Initial Temperature and write the value to the Temperature variable so that the initial temperature would be used for the first set of calculations during startup refer to Figure 15 The calculations then used the value after each iteration refer to Figure 15 for the Temperature variable at every other point in time This setup also allowed the Temperature variable to read the Initial Temperature and display it on the graph at zero time The local variable was first wired via a shift register into the while loop A shift register allows the variable entering a loop to be affected by the function of the loop The alternative to shift register is tunneling where the variable travels through the loop independent of the loop s functions The Temperature variable was then wired via another shift register into the for loop which contained the calculations for passive cooling and heating Initial Temperature fiData Points FIGURE 18 THE INT