ETCR8600 Manual
Contents
1. ETCR Leakage protector tester ETCR 8600 gt ETCR 8600 75 15mA 30mA 50mA Leakage protector tester MANUAL ETCR Electronic Technology Co Ltd Content AULONtiONn Aish deisel anne a china aides 0 E BrlehintrOGuction s sieni eanan aoe alee Gite oa ae tela eet ll Electrical Symboli isis aerie enn IIl Technical SSO SCIICALION 1 3 4j ats tntsrais aynchbbedi aces apeatinlls ease eabocts elhare IV Instrument Structure ssahitensatieniteniaa a ieede eek wie V Instrument TSE ALIO eties cau Pops htvsteehdeSerapes tweed de Sem ttus snebene timate eestor 1 bootup Shutdown tietoineen E E E 2 Manual automatic switch cee eeccceescceeteceeneeceeceeesceeeeaeeesaeeesaes 3 Switch the gear of rated operating current eee A MRESCl aS cnt titania se ctunceie vent e A et cat teeters S Measurement sinir iieii E e a ie VI Replacing Battery 0 ec ceesseeseeceteeeeseeeeseseeeeseeessesesecseeesaeeeeees VID ACCESSONGES mii n e E deat eines Attention Thank you for purchasing ETCR8600 Leakage Protector Tester of our company In order to make better use of the product please be certain To read this user manual carefully To comply with the operating cautions presented in this manual u Pay special attention to safety when using this instrument in any case u Observe the text and symbols attached to the front and rear panels of the instrume
2. e Direct current DC lll Technical Specification Measurement of leakage operating current Function leakage non operating current leakage oper ating time of the leakage protector Test line Vol Do not exceed AC 250V tage rated voltage AC 220V Leakage cur rent gear 15 30 50 75 100 150 200 250 500mA 300 range of the leakage oper 0 999ms ating time accuracy of the leakage 0 5 operating time accuracy of the current for 1 0 each gear Fail When the LCD display fault it may be the ure informatio measured rated operating current gear is too n small or the leakage protector has some faults length of the 1 8m test line Test mode Manually or automatically Dimension 170mmx75mmx30mm Weight 290g including the batteries Total weight 350g including the packing LCD Dimen Display field 44mmx27mm sion battery voltage A Low Battery symbol is displayed and the user should replace the battery with a new one when the battery voltage drops to 4 8V In this case the measured values are still accurate Working Cur AOMA Max rent Working Hu _19 C 40 C below 80 rh miture Storage Hu _49 C 60 C below 70 rh miture Insulating 2100MQ AC2kV rms between the alloy of the Strength clamp and the housing Applicable IEC 1010 1 1EC1010 2 032 Pollution degree 5 sa
3. fety rules 2 CAT III 600V IEC61326 EMC standard IV Instrument Structure 1 N interface connect ground wire 2 L interface connect fire wire 3 LCD 4 AT auto key 5 RANGE key gear up 6 MT manual key 7 RANGE key gear down 8 RESET reset key 9 POWER boot up shutdown 7 10 Crocodile clip test line g 11 Probe test line 12 Socket test line V Instrument Operation 1 boot up shutdown Boot up the instrument by pressing the POWER key The LCD will light up If the LCD display is dim the battery voltage may be low If so replace the battery with a new one Press the POWER key again to shutdown the instrument This instrument will be shut down automatically after starting 5 minutes 2 Manual automatic switch This instrument has the manual MT and AT automatic test mode Press MT and AT key to switch to manual or automatic mode After boot up it is default to the manual MT test mode In the manual mode the top left corner of the LCD shows MT symbol in the automatic mode the top left corner of the LCD shows MT symbol In the automatic mode start the measurement from the lowest gear 15mA rated operating current If the leakage protector does not trip the instrument will increase a gear automatically after 2 seconds If the leakage protector also does n
4. nt u Don not use the instrument to measure a line with a voltage higher than 250V u Before measurement disconnect the load fuse of the measured leakage protector u L interface must connect to the fire wire N interface must connect to the ground wire u The Socket test line of the instrument is custom made forbid to use other plug with cord instead of it u After measurement removed the test wire from the measured wire first u lt is forbidden to use the instrument when neither rear cover of the instrument nor the batter cover is in place u Never use the instrument when the instrument case or mea suring wire is broken and therefore any metallic part is exposed u Don not place the instrument at a environment with high tem perature high humidity condensation and direct sunshine for a long time u It is necessary to maintain the instrument periodically to keep it clean Don not wipe the instrument by using corrosive medium or abrasive object u Please observe the correct polarity when replacing the battery Remove the battery from the instrument if you expect not to use the instrument for a long time u Please replace the battery with a new one when the batter vol tage is so low that the LCD display is dim 2 Operation disassembly and maintenance of the instrument must be carried out only by a authorized and qualified person When there is an instrument fault never use it because conti nual use may result in danger In
5. ot trip the instrument 6 will increase a gear automatically again after 2 seconds until the trip breaking At this time the displayed gear on the button of LCD screen is the actual leakage operating current value the displayed time is the leakage operating time 3 Switch the gear of rated operating current The rated operating current of the instrument from 0 to 500mA were divided into ten gears 15mA 30mA 50mA 75mA 100mA 150mA 200mA 250mA 300mA 500mA Press RANGE or RANGE to switch the gears On the bottom of the LCD indicates the current gear After boot up it is default to the lowest gear 15mA to start test 4 Reset After each test press the RESET key to reset the leakage oper ating time will be zero clearing then can be tested again 5 Measurement Electric shock dangerous The instrument can be operated only by the trained and authorized person The operators must keep to the safety rules strictly otherwise electric shock will result in personal injury or damage to the equipment Don not use the instrument to measure the lines with a voltage of higher than 250V Otherwise electric shock will result in personal injury or damage to the equipment L interface must connect to the fire wire of the meas ured leakage protector N interface must connect to the ground wire of the measured leakage protector Otherwise electric shock will result in damage to the equipment The Socket tes
6. t and confirm that the instrument can operate properly as shown in the following fig ures Battery cover Battery cover Loosen Tighten Vil Accessories Tester Shoulder bag Probe test line Crocodile clip test line 1 PCS Socket test line 1 PCS Packing box 1 PCS Alkaline dry battery AAA 1 5V 4 PCS User manual Warranty card Quality certificate 1 Copy Manufactured by ETCR Electronic Technology Company Address F 3F No 4 Pengshang Zhifu Road Jiahe Baiyun District Guangzhou Guangdong China Post Code 510440 Tel 86 20 62199556 Fax 86 20 62199550 E mail info etcr cc Website www etcr cc
7. t line of the instrument is cus tom made the red plug connect to the fire wire the black plug connect to the ground wire Forbid to use other plug with cord instead of it Otherwise electric shock will result in personal injury or damage to the equipment 7 Before measurement disconnect the load fuse of the measured leakage protector to avoid damage to the load equipment Then check the nameplate rating of the measured leakage protector According to the nameplate rating to determine the current gear Generally for the indoor type single phase two wire mode leakage protector the rated operating current is 30mA the rated non operating current is 15mA The break duration lt 0 1s that is lt 100ms Boot up select the test mode and the gear of the rated leakage operating current it is default to the manual MT test mode The connection as shown below Connection 1 one end of black crocodile clip test line insert to the black N interface of the instrument the other end crocodile clip clip to the grounding pile of the leakage protector one end of red probe test line insert to the red L interface of the instrument the other end probe touch the fire wire of the leakage protector s output end to measurement Connection 2 the black plug of the dedicated socket test line in sert into the N interface of the instrument the red plug insert into the L interface of the instrument the three pin plug insert into or to
8. this case isolate the instru ment immediately and delivered to an authorized agency for dealing with it The user must follow the safety instructions preceded by A warning symbol on the instrument and manual The user must strictly follow the instructions preceded by danger symbol on the instrument and manual l Brief introduction ETCR8600 Leakage Protector Tester is well designed and man ufactured for online measuring the leakage operating current leakage non operating current leakage operating time of the lea kage protector adopt 128dotsx64dots displayed it is convenient and intuitive The range of leakage current is O0 500mA 10 gears 15 30 50 75 100 150 200 250 300 500mA range of the lea kage operating time is 0 999ms It is a product with high accuracy small size light weight exquisite appearance easy to carry is an ideal tool for variety of leakage protector in site or in laboratory testing ll Electrical Symbol Extremely dangerous The operators must keep to the safety rules strictly otherwise electric shock will result in death or injury Dangerous The operators must keep to the safety rules strictly otherwise electric shock will result in will result in death or injury Warning The operators must keep to the safety rules strictly otherwise personal injury or equipment damage will occur Double insulation Alternating current AC Ilem amp
9. uch the socket to measurement At this time if the performance of the leakage protector is normal it will trip breaking the breaking time displayed in the LCD screen such as 075ms If the leakage protector does not trip fault failure information will display in the LCD it may be the measured rated operating current gear is too small or the leakage protector has some faults Press the RESET key to reset then can be tested oee be He Pe VI Replacing Battery To avoid electric shock when replacing the batte ries the test line must be pulled away from the in strument and do not connect with the measured A wire Observe the correct battery polarity otherwise the instrument will be damaged Replace the battery with a new one as soon as possible when the battery voltage is low Do not mix the old and new battery together 1 When the battery voltage drops to 4 8V a Ml symbol will be displayed on the instrument indicating the battery voltage is low Replace the battery immediately 2 Press the POWER key to shutdown the instrument After con firming that the instrument has been shutdown f open the battery cover and replace with a new battery recommended by the manu facturer Pay special attention to the correct battery polarity Re place the battery cover boot up the instrumen