1. Nora e ss 6 o o JL Tee Surga Suppreesar Mod Om e Om e o FC WARNIN WHEN OPERATING THE BYPASS SWITCH ALLOW A 20 SECOND r E11 INTERVAL BETWEEN SWITCH STRIKESAFE Surge Suppreesor Moduls POSITION TO ALLOW THE UPS TO PHASE LOCK Town 00 STRKESAFE Surge Suppressct Modul E Tz Ojo o PS Er Li L2 L3 N E 9 DANGER HIGH VOLTAGE O ELECTRICAL SHOCK HAZARD US E Service to be performed by qualified personnel O WARNING REFER TO INSTRUCTIONS BEFORE REMOVING THIS PANEL N Ea N PN 3 position Rotary Switch Upper Cover Lower Cover Gland Plate TVSS viewing access window optional Typical TVSS device optional nS dd Man 440 Issue 7
2. tight 2 4 Connection of the Protected Equipment Feed the protected equipment cables through the gland plate and secure terminate the protected equipment cables to the terminals marked SUPPLY TO LOAD as follows For Single Phase Load Wire Terminal For Three Phase Load Wire Terminal Live Brown Terminal Marked L Phase 1 Red Terminal Marked L1 Neutral Blue Terminal Marked N Phase 2 Yellow Terminal Marked L2 Earth Gn Yw Terminal Marked E Phase 3 Blue Terminal Marked L3 Neutral Black Terminal Marked N Earth Gn Yw Terminal Marked E Ensure that all terminals and glands are tight 2 5 Connection of the Auxiliary Contacts optional The auxiliary contacts are only to be used if required they allow the position of the bypass switch to be monitored as follows Switch Position Volt free Contact Status Normal Open Bypass 8 UPS Closed Bypass Closed Contact Rating 20A 230Vac 2 6 Initial switch on Before the mains supply is applied to the WBS Refit all of the covers that were removed during installation not forgetting the earth connections With the bypass switch in the normal position switch on the supply Start the UPS and confirm that the UPS operates correctly as described in its User Manual Confirm that the TVSS device if fitted is operating correctly as described in it s Us
3. Marked E Phase 3 Blue Terminal Marked L3 Neutral Black Terminal Marked N Earth Gn Yw Terminal Marked E Ensure that all terminals and glands are tight Man 440 Issue 7 3 2 2 Connection of the Input to the UPS Feed the UPS input cables through the gland plate and secure terminate the UPS input cables to the terminals marked UPS IN as follows For Single Phase Input Wire Terminal For Three Phase Input Wire Terminal Live Brown Terminal Marked L Phase 1 Red Terminal Marked L1 Neutral Blue Terminal Marked N Phase 2 Yellow Terminal Marked L2 Earth Gn Yw Terminal Marked E Phase 3 Blue Terminal Marked L3 Neutral Black Terminal Marked N Earth Gn Yw Terminal Marked E Ensure that all terminals and glands are tight 2 3 Connection of the Output from the UPS Feed the UPS output cables through the gland plate and secure terminate the UPS output cables to the terminals marked UPS OUT as follows For Single Phase Output Wire Terminal For Three Phase Output Wire Terminal Live Brown Terminal Marked L Phase 1 Red Terminal Marked L1 Neutral Blue Terminal Marked N Phase 2 Yellow Terminal Marked L2 Phase 3 Blue Terminal Marked L3 Neutral Black Terminal Marked N Ensure that all terminals and glands are
4. WBS HARDWIRED SERIES 4 60KVA MAINTENANCE BYPASS SWITCH Man440 Issue 7 INTRODUCTON en ee cateo 3 DIN A A RA eee Man 440 Issue 7 2 1 INTRODUCTION The Maintenance Bypass Switch WBS is a wall mounted unit specially designed to allow maintenance and removal of the UPS without any disruption of the supply to the protected equipment i e the load It is fitted with a three position switch that can be locked in 2 positions only NORMAL and BYPASS thus preventing accidental switching during normal and bypass operation When the WBS is switched to the NORMAL position backup is available from the UPS in the event of a mains supply failure In the BYPASS amp UPS position no backup is available but mains supply remains connected to the UPS Finally when the WBS is switched to the BYPASS position no backup is available and the mains supply is disconnected from the UPS The T versions have additional transient voltage surge suppressor TVSS devices fitted WARNING The WBS should only be installed and operated by authorised and trained personnel 2 INSTALLATION WARNING The following procedure must be followed exactly Failure to do so could lead to exposure to hazardous voltages and disruption of the supply to the protected equipment It is recommended that the following procedure be only carried out by a qualified electrician THIS EQUIPMENT MUST BE EARTHED Before commencing the installation ensure tha
5. ance or replacement purpose s is as follows WARNING Hazardous voltages are always present within the WBS unless completely isolated from the UPS and Mains Supply Confirm that the device can be worked upon safely whilst connected to the mains supply if itis not safe to work upon the device the mains supply will have to be isolated prior to cover removal some TVSS devices utilise hot swap capability To gain access if safe to do so remove the four screws that secure the TVSS viewing window to the upper cover Refer to the TVSS user manual for further information Once all the work has been carried out on the TVSS device replace the TVSS viewing window and secure Man 440 Issue 7 6 4 Appendix 1 4 10kVA Diagram Note Versions may differ slightly PN WARNING WHEN OPERATING THE BYPASS SWITCH ALLOW A 20 SECOND INTERVAL BETWEEN SWITCH POSITIONS TO ALLOW THE UPS TO PHASE LOCK y BYPASS 8 UPS a os lt lt 5H 1 gt C m O N ZN o A N a X IN CAL SHOCK HAZARD Service to be performed by qual if le anne WARN ING De ot trans er load dur ing tion of Inverter Co 1 3 Position Rotary Switch 2 Terminal Cover 3 Gland Plate Man440 Issue 7 5 Appendix 2 10 60kVA Diagram Note Versions may differ slightly BYPASS amp
6. er Manual The unit is now installed Man440 Issue 7 3 MAINTENANCE BYPASS SWITCH OPERATION WARNING Always allow a 20 second break between switching positions 3 1 Switching to Bypass Operation for UPS maintenance and testing only NOTE Check that the UPS is working normally and that it is not working in battery operation mode refer to UPS user manual If these conditions are not met disruption or even damage can occur to the UPS or protected load if the switch is operated Turn the switch to the BYPASS 8 UPS position central The load is now supplied directly from the mains supply and the UPS still has input supply connected The UPS may now be switched off or tested refer to UPS user manual without disrupting the load 3 2 Switching to Bypass Operation for UPS maintenance and complete isolation only NOTE Check that the UPS is working normally and that it is not working in battery operation mode refer to UPS user manual If these conditions are not met disruption or even damage can occur to the UPS or protected load if the switch is operated Turn the switch to the BYPASS amp UPS position central The load is now supplied directly from the mains supply and the UPS still has input supply connected The UPS may now be switched off refer to UPS user manual without disrupting the load Turn the switch to the BYPASS position fully clockwise The load will be continually supp
7. lied from the mains supply and the input supply to the UPS will now be disconnected The UPS may now be maintained without disrupting the load always check the terminals using a meter prior to touching 3 3 Disconnection of the UPS WARNING Hazardous voltages are always present within the WBS unless completely Isolated from the UPS and Mains Supply NOTE Check that the UPS is working normally and that it is not working in battery operation mode refer to UPS user manual If these conditions are not met disruption or even damage can occur to the UPS or protected load if the switch is operated Turn the switch to the BYPASS amp UPS central position The load is now supplied directly from the mains supply and the UPS still has input supply connected Switch the UPS off completely following the UPS User Manual ensuring the batteries are also isolated Turn the switch to the BYPASS fully clockwise position The load is still supplied directly from the mains supply but the mains supply to the UPS is now disconnected WARNING Hazardous voltages are always present within the WBS unless completely isolated from the UPS and Mains Supply Lock the switch in position if necessary Remove the cover from the WBS Using a meter confirm that no voltage is present Disconnect the cables from the terminals marked UPS IN and UPS OUT 99 Man440 Issue 7 5 Disconnect the cables connected to the UPS input o
8. t the WBS is suitable for the UPS system for which it is to be used the connection cable sizes can be found in the UPS user manual Remove the gland plate blanking grommets if fitted and front panel panels from the WBS all plates and panels are secured by several retaining screws and are connected to the unit via an earth connection this earth connection may be removed temporarily during the installation the removable gland plate must be drilled to suit your particular gland requirements Mount the WBS securely to an even surface e g wall this can be achieved using the four mounting holes located in the rear of the enclosure Once the WBS is securely mounted the connections can be made as described in the next section WARNING Hazardous voltages will be present on the terminal blocks if the UPS or mains supply is switched on Always ensure that the UPS and mains supply is switched off and isolated before proceeding Refer to UPS operation manual for correct indications 2 1 Connection of the Mains Supply Feed the mains supply cables through the gland plate and secure terminate the mains supply cables to the terminals marked SUPPLY IN as follows For Single Phase Input Supply For Three Phase Input Supply Wire Terminal Wire Terminal Live Brown Terminal Marked L Phase 1 Red Terminal Marked L1 Neutral Blue Terminal Marked N Phase 2 Yellow Terminal Marked L2 Earth Gn Yw Terminal
9. utput terminals The UPS can now be removed for maintenance The load will continue to be supplied through the WBS Replace all of the covers of the WBS and UPS 3 4 Reconnection of the UPS 4 4 WARNING Hazardous voltages are always present within the WBS unless completel isolated from the UPS and Mains Supply Reconnect the UPS following section 2 2 2 amp 2 3 found earlier within this manual Once all connections have been made replace all covers and refer to section 3 5 3 5 Switching back to Normal Operation WARNING Always allow a 20 second break between switching positions Turn the switch to the BYPASS amp UPS central position The UPS now has input supply available whilst the load is still supplied directly from the mains supply Switch on the UPS ensuring correct operation refer to UPS user manual Check that the UPS is working normally and that it is not working in battery operation mode refer to UPS user manual If these conditions are not met disruption or even damage can occur to the UPS or protected load if the switch is operated Turn the bypass switch to the NORMAL fully anti clockwise position The load is now protected by the UPS 4 Transient Voltage Surge Suppressor or TVSS Optional 4 1 TVSS Operation For the operation of the TVSS device located within the bypass switch refer to the separate TVSS user manual 4 2 TVSS Access Access to the TVSS device for mainten
Download Pdf Manuals
Related Search
apm_wbs apmsetup apm_bios apm_aps1604m-3sqr apm_system apm_setup 5 apm_signal apm_sim_not_pwdn
Related Contents
LUXTELLA STREET manual de instalacion Samsung SGH-U700B Lietotāja rokasgrāmata Bicycle Wireless Turn Indicator User Manual User Manual: TASMANIAN Sparse Grids Manual de usuario AXIS P55–E Series AXIS P5532–E PTZ Dome Network Camera Benutzerhandbuch Version 2.9.7. DVD-700 - Aerne Menu carte - boucle 4 - Office des Sports GFI Backup 2010 Business Edition Agent User Guide Copyright © All rights reserved.