User`s Manual
Contents
1. DI RZ ey 7 Input Circuit Breaker O The circuit breaker serves to provide input overload and fault protection 8 Input Power Cord Heavy duty extra long power cord 12 USB port to PC 9 SNMP HTTP Network slot This is a connectivity port allowing communication and control between the UPS and the Slot to install the optional SNMP card for remote connected computer You should install the PowerPanel Business Edition Agent software on network control and monitoring the PC Server connected with the USB cord 10 Serial Port Primary Serial port provides bi directional communication between the UPS and the computer The UPS can control the computer s shutdown in case of an emergency and at the same time the computer can monitor the UPS and alter its various programmable parameters 11 Serial Port Il Secondary Serial Port Il allows the UPS to initiate a connected computer s graceful auto shutdown in case of an emergency BASIC OPERATION o O P o Ye Hal Pagin CEI fh 6 IH i z BER 13 EPO Emergency Powe
2. The Temperature screen displays the internal temperature of the UPS in degrees Fahrenheit Normal ranges are 32 F 104 F If the temperature exceeds 104 F additional methods should be implemented to cool the UPS i e air conditioning additional ventilation isolation from other heat producing equipment etc MAINTENANCE Storage To store your UPS for an extended period cover it and store with the battery fully charged Recharge the battery every three months to ensure battery life Battery Replacement Please read and follow the Safety Instructions before servicing the battery Battery replacement should be performed by trained personnel Who are familiar with the procedures and safety precautions Safety Precautions e CAUTION Only use replacement batteries which are certified by CyberPower Systems Use of incorrect battery type is an electrical hazard that could lead to explosion fire electrical shock or short circuit e CAUTION Batteries contain an electrical charge that could cause severe burns Before servicing batteries please remove any conductive materials such as jewelry chains wrist watches and rings Battery Installation e CAUTION Do not open or mutilate the batteries Electrolyte fluid is harmful to the skin eyes and may be toxic e CAUTION To avoid electrical shock turn off and unplug the UPS from the wall receptacle before servicing the battery e CAUTION Only use to
3. Step 1 Rack mount ears installation Attach the two rack mount ears to the UPS using the provided screws VIRA Take the rack mount rail inscribed with an L Left and attach it to the rear bracket of the rack mount rail using three 3 of the six 6 rack mount rail screws Do not fully tighten the rack mount rail screws as the rack mount rails will need to be adjusted to fit your rack Once complete perform the same steps for assembling the rack mount rail inscribed with an R Right Note Now the internal battery pack can be installed Please refer to page 9 BATTERY INSTALLATION for more details Step 4 Carefully align the front panel connector and latches with the PR5000LCDRTXL5U PR6000LCDRTXL5U Step 2 Rack mount rail Installation Ensure rack stability prior to installing devices in the rack CAUTION The UPS must be installed at the bottom of the rack system CAUTION Do not lift the front panel when removing the UPS unit Attach the rack mount rails to your rack using fasteners that are designed for your rack system HARDWARE INSTALLATION VERTICAZL TOWER INSTALLATION Step 1 Attach the base stands Step 2 Attach dust covers REI slide the base stands onto the bottom of the UPS roughly 8 10 Insert dust covers into the rack mount ear screw holes that are not being apart used Step 3 Rotate the Multifunction LCD Reado
4. AC outlet The unit must be connected to a 220 230 240V outlet Batteries are worn out Contact CyberPower Systems about replacement batteries at tech cpsww com Mechanical problem Contact CyberPower Systems at tech cpsww com PowerPanel Business Edition is inactive The serial cable or USB cable is not connected Connect the cable to the UPS unit You must use the cable that came with the unit The cable is connected to the wrong port Try another port of your computer The unit is not providing battery power Shutdown your computer and turn the UPS off Wait 10 seconds and turn the UPS back on This should reset the unit The serial cable is not the cable that was provided with the unit You must use the cable included with the unit for the software Additional troubleshooting information can be found at Support area of www CPSww com PRODUCT REGISTRATION amp WARRANTY Product Registration CyberPower requests that you complete and return the Warranty Registration Card enclosed with the Product or register the Product at its website www CPSww com to establish that you are the Initial Customer of the Product and therefore entitled coverage under the Limited Warranty and the Connected Equipment Guarantee Registration is not required for coverage but note if you do not register your purchase you will be required to provide proof of purchase Limited W
5. keep the LCD screen illuminated at all times No The LCD display will only light up when the Select button is pressed This extends the life of the LCD screen and is part of the energy saving design of our UPS systems NEED ADDITIONAL HELP Contact the Tech Support department with installation troubleshooting or general product questions CyberPower Technical Support Phone 1 877 297 6937 Email tech cpsww com Web www CPSww com Mail 4241 12th Avenue E Suite 400 Shakopee MN 55379 Hours of Operation Monday Friday 8 00am 5 00pm CST FCC Compliance Statement This device complies with part 15 of the FCC rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will
6. use of any adapters or other connectors 2 The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected to the Product and not daisy chained together in serial fashion with any extension cords another Product or device similar to the Product surge suppressor or power tap Any such installation voids the Limited Warranty 3 The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any license instruction manual or warnings provided with the Product and the equipment connected to it 4 The Product must have been used at all times within the limitations on the Product s VA capacity Where Can I Get More Information For further information please feel free to contact CyberPower at Cyber Power Systems USA Inc 4241 12th Ave E STE 400 Shakopee MN 55379 call us at 877 297 6937 or send us an e mail message at claims cpsww com Recycle Policy CyberPower Systems encourages environmentally sound methods for disposal and recycling of its UPS products Please dispose and or recycle your UPS and batteries in accordance to the local regulations of your state SERVICE INFORMATION FREQUENTLY ASKED QUESTIONS FAQs What types of equipment are NOT allowed to be plugged into the UPS Any device which exceeds the unit s VA Watt rating should not be plugged into the UPS High drai
7. CyberPower Reliability Quality Value 5 User s Manual PR5000LCDRTXL5U PR6000LCDRTXL5U K01 0000124 04 IMPORTANT SAFETY INSTRUCTIONS This manual contains important instructions Please read and follow all instructions carefully during installation and operation of the unit Read this manual thoroughly before attempting to unpack install or operate the UPS CAUTION The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection DO NOT plug the UPS into an outlet that is not grounded If you need to power drain this equipment turn off and unplug the unit CAUTION The battery can power hazardous components inside the unit even when the AC input power is disconnected CAUTION The UPS should be near the connected equipment and easily accessible CAUTION To prevent the risk of fire or electric shock install in a temperature and humidity controlled indoor area free of conductive contaminants Please see specifications for acceptable temperature and humidity range CAUTION To avoid electrical shock turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer component CAUTION Never install a UPS or associated wiring or equipment during a lightning storm CAUTION When installing the equipment ensure that the sum of the leakage current of the UPS and the connected equipment does not exceed 3 5mA CAUTION Do not unplug t
8. R On Battery Output Voltage Pure Sinewave 208 220 230 240V 5 On Battery Output Frequency 50 60Hz 0 1Hz Transfer Time Typically 4ms Overload Protection On Utility Circuit Breaker On Battery Internal Current Limiting o ata line Protection Surge Protection 2430J 2430J Phone Network Protection RJ11 RJ45 One In One Out Battery Battery Mode RB1290X16 Sealed Maintenance Free Yes User Replaceable Yes Recharge Time Typically 6 hours 90 Status Indicators Indicator LEDs Power On LCD Display Using Battery AVR Load Level Battery Level Audible Alarms On Battery Low Battery Overload Environment Operating Temperature 32 F to 104 F 0 C to 40 C Operating Relative Humidity 0 to 95 Non Condensing Management On Device Features Self Test Auto Charge Auto Restart Connectivity Ports 1 USB 2 Serial SNMP HTTP Capable Yes with optional RMCARD 205 Software Power Management Software PowerPanel Business Edition Physical Dimensions LxWxH 25 25 x 17 x 8 75 in 640x430x222 mm Weight 222 Ibs 101 kg 226 Ibs 103 kg Safety Conformance Approvals UL1778 cUL107 FCC Part 15 Class A CSA Warranty Product Warranty 3 years Limited Connected Equipment Guarantee 400 000 The Nominal Input Voltage and Input Adjustable Vo
9. UPS 2 Power on Indicator Indicates the UPS is on and supplying power free of surges and spikes LCD Readout Toggle Button se to rotate through multiple screens of UPS atus information cw wn 4 Multifunction LCD Readout An illuminated digital screen that displays the UPS power status information 5 Battery Backup amp Surge Protected Outlets This unit provides a total of five outlets with battery a 3921 backup and surge protection They ensure that a das connected equipment will provide power to equipment over a period of time during a power i Pa Pg po pr FA PAR Hee failure o 7 8 9 10 1112 Critical Non Ccritical L It is possible to program the unit so that the outlet 7 hi i block marked as Non Critical 3 ports will stop ci the supplying to connected equipment after a certain period of time This allows for additional o Bo o sE runtime for the equipment connected on the outlets marked as Critical 2 port This allows the creation of load priorities ensuring the critical i AN equipment is given priority under specific WS JJ circumstances ea i By D 6 Output Circuit Breaker The circuit breaker serves to provide output overload and fault protection
10. Your equipment operates normally when power problems such as shout brownouts and blackouts The unit s powerful sealed lead acid batteries will provide power during the incoming voltage drops below 131V or increases above 268V Default SYSTEM BLOCK DIAGRAM Input gt Normal Mode Battery Mode HARDWARE INSTALLATION GUIDE 1 Battery charge loss may occur during shipping and storage Before using the UPS it s strongly recommended to charge batteries for twelve 12 hours typically to ensure that the batteries maximum charge capacity is met To recharge the batteries simply plug the UPS into an AC outlet 2 When using the included software connect either the serial or the USB cable between the computer and the corresponding port on the UPS Note If the USB port is used the serial port will be disabled They cannot be used simultaneously The computer with the PowerPanel Business Edition Agent software connects to the USB port or the Serial port on the UPS It can control the operating schedule battery test outlet etc and obtain information on the UPS status However other computers with PowerPanel Business Edition Client software can only obtain UPS status information via a LAN connection 3 With the UPS off and unplugged connect your computer monitor and any externally powered data storage device Hard drive Tape drive etc into the outlets DO NOT plug a laser printer copier space heater vacuum
11. arranty and Connected Equipment Guarantee Read the following terms and conditions carefully before using the CyberPower UPS the Product By using the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty and Connected Equipment Guarantee together referred to as this Warranty If you do not agree to the terms and conditions of this Warranty you should return the Product for a full refund prior to using it Who Is Providing This Warranty CyberPower Systems USA Inc CyberPower provides this Limited Warranty What Does This Warranty Cover This warranty covers defects in materials and workmanship in the Product under normal use and conditions It also covers equipment that was connected to the Product and damaged because of the failure of the Product What Is The Period of Coverage This warranty covers the Product for three years and connected equipment for as long as you own the Product Who Is Covered This warranty only covers the original purchaser Coverage ends if you sell or otherwise transfer the Product How Do You Get Service 1 Callus at 877 297 6937 or write to us at Cyber Power Systems USA Inc 4241 12th Ave E STE 400 Shakopee MN 55379 or send us an e mail message at claims cpsww com for instructions 2 When you contact CyberPower identify the Product the Purchase Date and the item s of Connected Equipment Have information on a
12. be required to correct the interference at his own expense Important Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment Canadian Compliance Statement This device complies with Industry Canada licence exempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause interference and 2 this device must accept any interference including interference that may cause undesired operation of the device Le pr sent appareil est conforme aux CNR d Industrie Canada applicables aux appareils radio exempts de licence L exploitation est autoris e aux deux conditions suivantes 1 l appareil ne doit pas produire de brouillage et 2 l appareil doit accepter tout brouillage radio lectrique subi m me si le brouillage est susceptible d en compromettre le fonctionnement CAN ICES 3 A NMB 3 A
13. damage to the unit from battery leakage 9 The unit has one Primary Serial Port I one Secondary Serial Port II and one USB port paired with the Primary Serial Port to allow connection and communication between the unit and any attached computers The Primary Serial Port I as well as its paired USB port allow for bi directional communication among the UPS and the primary connected computer running the PowerPanel Business Edition Agent software The UPS can control the computer s shutdown in case of an emergency and at the same time the computer can monitor the UPS and alter its various programmable parameters On the other hand secondary Serial Port Il only allows the UPS to initiate the connected computer s graceful shutdown in case of an emergency 10 EPO Emergency Power Off Port Use the provided gray cable to connect to a special EPO contact switch Follow the appropriate circuit diagram on page 4 to wire the cable to your EPO configuration The EPO remote switch is a switch installed in an outside area connected to the unit via an ordinary RJ 11 phone line In case of an emergency it can be used to immediately cut off power from the UPS unit 11 To avoid electrical shock before hardwiring the UPS in out power cord turn the unit OFF and disconnect the unit from utility power The in out power cord MUST be grounded BASIC OPERATION FRONT REAR PANEL DESCRIPTION 1 Power Switch aster On Off switch for the
14. eceptacle This can be used as a diagnostic tool to identify poor quality input power Units are listed in V Volts Output Frequency The Output Frequency screen displays the current frequency at which the UPS is operating Units are listed in Hz Hertz Load Capacity Similar to the Load Current Level screen this displays the total load current of the connected equipment expressed as a percentage Temperature The Temperature screen displays the internal temperature of the UPS in degrees Centigrade Normal ranges are 0 C 40 C If the temperature exceeds 40 C additional methods should be implemented to cool the UPS i e air conditioning additional ventilation isolation from other heat producing equipment etc Load This displays the total load of the connected equipment Output Voltage The Output Voltage screen measures the AC voltage that the UPS is providing to your connected equipment via the UPS outlets Units are listed in V Volts Estimated Runtime The Estimated Runtime Screen displays how many minutes of runtime can be expected of the UPS if it were to experience a power outage Note The number displayed may be less than actual runtimes for low loads Battery Capacity The Battery Capacity screen displays the batterys current charge level and is expressed as a percentage of the battery s total capacity of 100 Temperature
15. eens press the Select button which is located directly next to the Screen illumination After 30 seconds of inactivity the LCD backlight will automatically turn off to conserve energy Keeping the LCD screen lit at all times is not an option on this UPS Select Button Test Mode on the UPS Select Button MAIN FEATURES Load Level The total load of the connected equipment shown in Battery Capacity The LOAD CAPACITY battery s current charge level shown in 20 increments Normal Icon This icon appears when the UPS is working under normal conditions Battery Icon This icon appears when the UPS is operating using battery power The UPS will also sound alarms two short beeps followed by a pause When this icon is lit When the Battery Icon is lit and the Battery Capacity falls to 20 the frequency of the alarms will increase indicating that the UPS batteries are nearly out of power If this occurs it is recommended that you either restore AC power or manually power down your equipment that may be negatively affected by sudden power loss Silent icon This icon appears when the UPS is in silent mode During Silent mode the units alarm does not sound until the 20 increments Battery Capacity falls to lt 20 e Ifthe LCD screen is not lit pressing the Select button once will turn the LCD on If the LCD screen is lit then pressing the Select button once will toggle through the status screens e Pressing a
16. he unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT Under no circumstances this unit should be used for medical applications involving life support equipment and or patient care CAUTION DO NOT USE WITH OR NEAR AQUARIUMS To reduce the risk of fire do not use with or near aquariums Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE DO NOT BLOCK VENTILATION OPENINGS AROUND THE HOUSING DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR HAIR DRYERS SPACE HEATERS VACUUM CLEANER ETC TO THE TO UPS OUTPUT SOCKETS UNPACKING ng Po Ue vo I SD NO Rack mount rails 1 set left and right sides dr 3 Se 3 Ta Ue i De NO DO 7 Rack mount ear amp rails screws 34 User s manual Warranty Card Screw hole dust covers 8 Warranty registration card INSTALLING YOUR UPS SYSTEM AUTOMATIC VOLTAGE REGULATOR AVR The PR5000LCDRTXL5U PR6000LCDRTXLSU stabilizes damaging inconsistent utility power The Automatic Voltage Regulator automatically regulates low or high voltages to keep equipment working at safe AC power levels 208 220 230 240V without switching to battery
17. ll applicable insurance or other resources of recovery payment that are available to the Initial Customer and Request a Claim Number 3 You must provide a purchase receipt or other proof of the original purchase and provide a description of the defect 4 Pack and ship the product to CyberPower and if requested the item s of Connected Equipment a repair cost estimate for the damage to the Connected Equipment and all claim forms that CyberPower provides to you Show the Claim Number on the shipping label or include it with the product You must prepay all shipping costs you are responsible for packaging and shipment and you must pay the cost of the repair estimate How Long Do Have To Make A Claim All claims must be made within ten days of the occurrence What Will We Do To Correct Problems CyberPower will inspect and examine the Product If the Product is defective in material or workmanship CyberPower will repair or replace it at CyberPower s expense or if CyberPower is unable to or decides not to repair or replace the Product if defective within a reasonable time CyberPower will refund to you the full purchase price you paid for the Product purchase receipt showing price paid is required If it appears that our Product failed to protect any equipment plugged into it we will also send you forms for making your claim for the connected equipment We will repair or replace the equipment that was damaged because of the fai
18. ltage Range can only be configured through software Input Voltage Range and Input Adjustable Voltage Range will change when Nominal Input Voltage setting is changed UPS firmware version must be 4 27 or above Pressing and holding the LCD screen Select button for ten 10 seconds while UPS is in Normal operation will display the UPS firmware version TROUBLESHOOTING Problem Possible Cause Solution Outlet does not provide power to equipment Circuit breaker has tripped due to an overload Turn the UPS off and unplug at least one piece of equipment Wait 10 seconds reset the circuit breaker by depressing the button and then turn the UPS on Batteries are discharged Recharge the unit for at least 4 hours Unit has been damaged by a surge or spike Contact CyberPower Systems about replacement batteries at tech cpsww com Uncritical outlets have turned off automatically due to an overload Push the toggle button to make the uncritical outlets turn on The UPS does not perform expected runtime Batteries are not fully charged Recharge the batteries by leaving the UPS plugged in Batteries are degraded Contact CyberPower Systems about replacement batteries at tech cpsww com The UPS will not turn on The on off switch is designed to prevent damage by rapidly turning it off and on Turn the UPS off Wait 10 seconds and then turn the UPS on The unit is not connected to an
19. lure of our Product or pay you the fair market value NOT REPLACEMENT COST of the equipment at of the time of the damage We will use Orion Blue Book or another a third party valuation guide or eBay craigslist or other source to establish that amount Our liability is limited to the Connected Equipment Guarantee amount as stated in the Technical Specifications section Who Pays For Shipping We pay when we send items to you you pay when you send items to us What Are Some Things This Warranty Does Not Cover 1 This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that is lost as a result of the failure or the restoration of data or records or the reinstallation of software 2 This Warranty does not cover or apply to misuse modification operation or storage outside environmental limits of the Product or the equipment connected to it nor for damage while in transit or in storage nor if there has been improper operation or maintenance or use with items not designed or intended for use with the Product such as laser printers appliances aquariums medical or life support devices etc What Are The Limitations 1 This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded outlets including compliance with electrical and safety codes of the most current electrical code without the
20. n devices medical equipment and aquatic equipment also void the unit s warranty Below is a list of other devices that also void the warranty Laser printers Space heaters Copiers Paper shredders Vacuums Curling Irons Can increase the runtime by hooking up multiple UPS units in a row This configuration is called daisy chaining and will void the UPS s warranty Can hookup a surge strip to the UPS unit No Surge strips cannot be installed before or after the UPS unit Doing so will void the UPS s warranty If you require additional outlets upgrade your UPS to a model that has more outlets or simply add an additional UPS to your existing configuration If you need a longer input cord you can purchase a UL certified extension cord that is rated for the respective current of the unit This cord MUST be a single outlet extension cord Should the cooling fan on my CyberPower UPS be running at all times No The internal cooling fan will only run when it s required CyberPower UPS systems utilize an internal thermal sensor which activates the fan when the temperature exceeds a certain threshold When the UPS is running Online off AC power it is completely normal for the fan to not be running Do have to have the UPS turned on in order for it to charge No The UPS will charge the battery whether the unit is turned on or turned off My LCD screen shuts off after 15 30 seconds of inactivity Is there a way to
21. nd holding the Select button for four 4 seconds while UPS is in Normal operation will initiate the Self e Pressing and holding the Select button for four 4 seconds while UPS is in Battery Offline mode will activate Silent Overload icon This icon appears when the Battery Surge outlets on the UPS are overloaded The UPS will also sound an alarm at this point To clear the overload the total load of the connected equipment must be less than the unit s maximum capability The easiest way to correct this problem is to remove noncritical equipment from the Battery Surge outlets Fault icon This icon appears if there is an internal problem with the UPS Please contact Technical Support if this icon is lit Automatic Voltage Regulation AVR icon This icon appears when the UPS is automatically correcting AC input line voltage without using battery power This is a normal automatic operation of your UPS and no action is required The AVR in this UPS continuously conditions the power to a nominal 208V output to connected equipment In the event of a complete power loss severe brownout or over voltage the UPS relies on its internal battery back up to supply a consistent 208V output DEFINITION FRO ILLUMINATED LCD INDICATORS TOGGLE SCREENS De i 2 CMOo Input Voltage The Input Voltage screen displays the AC voltage that the UPS system is receiving from the utility wall r
22. ols with insulated handles Do not lay tools or metal parts on top of UPS or battery terminals Replacement Batteries Please refer to the Technical Specifications of the user manual for the model number of the correct replacement batteries To purchase these batteries log onto www CPSww com or contact your local dealer Battery Disposal Batteries are considered hazardous waste and must be disposed of properly Contact your local government for more information about proper disposal and recycling of batteries Do not dispose of batteries ina fire 4 Remove the front panel protection cover and then remove the cover itself 4 Put the new battery modules back into the compartment 2 Remove the retaining screws of the cable 3 Pull the plastic sticker out slowly to remove the battery module 5 Tighten the screws and replace the cable protection cover and the front panel TECHNICAL SPECIFICATIONS Model PR5000LCDRTXL5U PR6000LCDRTXL5U Configuration Capacity VA 5000VA 6000VA Capacity Watts 4000W 4500W Energy saving Technology GreenPower UPS Bypass Input Nominal Input Voltage 208 220 230 240V Default 208V Input Voltage Range 148 254V Default Input Adjustable Voltage Range 131 268V Default Frequency Range 50 60Hz 3Hz Input Plug Type NEMA L6 30P Cold Start Yes Output UPS Outlets 3 NEMA L6 30R 2 NEMAL6 20
23. paper shredder or other large electrical device into the UPS The power demands of these devices will overload and possibly damage the unit 4 To protect a fax telephone modem line or network cable connect the telephone or network cable from the wall jack outlet to the jack marked IN of the UPS Then connect a telephone cable or network cable from the jack marked OUT on the UPS to the modem computer telephone fax machine or network device 5 Press the power switch to turn the UPS on The Power On indicator light will illuminate If an overload is detected an audible alarm will sound and the UPS will emit one long beep In order to reset it turn the unit off and unplug some equipment from outlets Make sure your equipment carry a load current within the unit s safe range refer to the technical specifications and then turn the unit on 6 Your UPS is equipped with an auto charge feature When the UPS is plugged into an AC outlet the battery will automatically charge even when the unit is switched off Suppressor AC DC 7 To maintain an optimal battery charge leave the UPS plugged into an AC outlet at all times 8 Before storing the UPS for an extended period of time turn the unit OFF Then cover it and store it with the batteries fully charged Recharge the batteries every three months to ensure good battery capacity and long battery life Maintaining a good battery charge will help prevent possible
24. r Off Port 14 Surge Protected Communication Ports RJ11 RJ45 Allows for an emergency UPS Power Off from a remote location These ports are used to protect standard RJ 45 RJ 11 based ADSL LAN Phone Modem Lines and cabling systems from surges el A SUPPLIED NORMALLY OPEN SWITCH 15 Extended Runtime XL Battery Pack Connector Provides a connection for additional CyberPower XL Battery Packs Ft res BPL48V75ART2U 16 Ground Stud Use the Ground Stud to ground the UPS NO CONNECTION DI RJ11 l l PLUG OE OPTION 2 USER SUPPLIED NORMALLY CLOSED SWITCH 3 4 JUMPER RJ11 PLUG N C EPO SWITCH NO CONNECTION HARDWARE INSTALLATION HARDWARE INSTALLATION Step 3 Adjust rack mount rails to fit your rack These versatile UPS systems can be mounted in a rack mount or vertical Itower orientation This versatility is especially important to growing organizations with changing needs that value having the option to position a UPS on a floor or in a rack mount system Please follow the instructions below for the respective mounting method SAFETY PRECAUTIONS CAUTION To prevent the risk of fire or electric shock use only the supplied hardware to attach the mounting brackets RACKMOUNT INSTALLATION Note Before the rack mount installation the internal battery pack shall be removed first Please refer to page 9 BATTERY INSTALLATION for more details COTAN NAN
25. ut Separate the front panel and the UPS Gently lift the LCD out Rotate it to the preferred orientation Reinstall the display for a tower configuration ELECTRICAL INSTALLATION After completing the hardware installation of the UPS you are now ready to plug in the UPS and attach your equipment SAFETY PRECAUTIONS e CAUTION Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity range CAUTION Never install a UPS or associated wiring or equipment during a lightning storm CAUTION Do not work alone under hazardous conditions CAUTION To reduce the risk of electric shock do not remove the top cover CAUTION The battery can energize hazardous live parts inside even when the AC input power is disconnected DEFINITION FRO ILLUMINATED LCD INDICATORS MULTIFUNCTION LCD READOUT a a LOAD CAPACITY wa BATT CAPACITY mi Ba ci I OOENnHAN INPUT OUTPUT ESTIMATE RUNTIME The screen is also rotatable so the UPS can be used in either rack mount or vertical tower The multifunction LCD readout provides ready access to power battery condition vitals such as Runtime Load Temperature and much more X 2 m Dal v orientation BASIC OPERATION LCD Screen toggle To toggle through the status scr