FactoryCast HMI 140 NWM 100 00 Instruction

image

Contents

1. if brand of Schneider Elmit Modicon FactoryCast HMI 140 NWM 100 00 Instruction Sheet 31004691 04 Version 1 0 FactoryCast HMI 140 NWM 100 00 Instruction Sheet ReadMe First CF Patent Registration User Configured IP Address 31004691 03 September 2003 Before you can use your 140 NWM 100 00 module you must configure it with an Internet Protocol IP address Configure your module by using either one of the two following methods e Create a new user configured IP address e Use the derived default address Note Operating on a Corporate Network Before placing the 140 NWM 100 00 on a corporate network Schneider Electric recommends that you discuss the installation with your MIS department Quantum Automation Series equipment is protected by U S Patent number 5 302 136 and by European Patent number 93202982 0 The NWM is protected by U S Patent numbers 4897777 4992926 4969083 5131092 5151978 5159673 5245704 5251302 5805442 5975737 5982362 6061603 6151625 6285454 Other patents pending A user configured IP address requires you to assign the IP address Therefore if a new IP address must be assigned obtain it from your system administrator Assign the new IP address using your Concept Programming Panel Record the IP network address on the space located on the front panel of the module behind the door For more information refer to the latest version of the Concept for Quantum
2. User Manual 840USE42800 Derived If you choose not to assign the module an IP address from a DHCP or Default IP BOOTP server you may connect the module using its default IP Address Address which is derived from its Mac address To do this proceed as follows IEEE GLOBAL ADDRESS 1 Locate the global address label on 0000540B72A8 the front panel of the module 2 Note the right most eight digits 540B72A8 3 Convert the digits from hexadecimal to decimal Each pair of hexadecimal numbers will result in a decimal number between 0 and 255 This is the default IP address 84 11 114 168 The hexadecimal conversion can be done with a scientific calculator or CF a computer based calculator program Record the IP network address on the writable label located on the front panel of the module Other Tools BootP Lite and the EthCfg tool included in Concept for IP Address Assignment A1 Channel The 140 NWM 100 00 module is capable of communicating over either Devices e 10 Base T or 100 Base T network e 100 Base FX Ethernet network at any given time but not both networks at the same time Note Do not attempt to connect module directly to another cr device The cable for each device must be routed through an Ethernet hub switch for the network to function properly 2 31004691 03 September 2003 Illustration This illustration depicts the 140 NWM 100 00 Model Number l ri Module Des
3. Cast Application yes User Programmable Webpages yes Java Virtual Machine yes Perform the following steps to install a 140 NWM 100 00 module Step Action 1 Holding the module at an angle mount it on to the two hooks located near the top of the backplane Hook Backplane Connector Module Backplane w kaea Swing the module down so its connector engages the backplane connector Using a Phillips head screw driver tighten the screw at the bottom of the module between 2 and 4 in lbs or between 22 and 45 Newton meters of torque 31004691 03 September 2003 Concept V2 6 Configuration for NWM 100 00 Module Additional Information 31004691 03 September 2003 As the first step of configuring this module you need to use the ModConnect tool once This tool is supplied with Concept V2 6 and will install the supplied NWM 100 mdc file This process will import the 140 NWM 100 00 module into the Concept moduledatabase and will copy the associated help file NWM100 hlp into the Concept directory For complete information concerning the 140 NWM 100 00 modules please obtain a copy of the FactoryCast HMI User Guide from your distributor or local sales office A copy of this manual can also be obtained from the Schneider Electric web site 31004691 04 04 3100469 1 Visit http www schneider electric com for your nea
4. abit network Fduplex Green On when Ethernet is operating in the full duplex mode Appl Green On when crash log entry exists Bus Current 900 mA Required Power 4 5 W Dissipation Fuse None Programming Software Type and Version Concept Ver 2 6 with SR2 Please also see the Concept V2 6 Configuration for NWM 100 00 Module section of this document Firmware NOE Upgradable Field upgradable via FTP or Programming Panel 4 31004691 03 September 2003 Run LED The state of the Run LED indicator is either steady or flashing Thus the Status Run LED indicator provides diagnostic information The following table lists each available state of the Run LED indicator Indicator State Status On steady Normal operation The NWM module is ready for network communication Number of Flashes in sequence One Not used Two Not used Three No Link The network cable is not connected or is defective Four Duplicate IP address Five No IP address The module is attempting to obtain an IP address from a BOOTP server Six Using default IP address Seven No valid executive NWM present Eight Invalid IP configuration Likely cause Default gateway is not on the same subnet mask as the module Nine Flash file system is corrupted FactoryCast This module contains an enhanced embedded Web server called the Web Server FactoryCast Web server whic
5. cription NWM 100 00 o FactoryCast HMI Color Code D cen erm Run Coll Link LED Display ape Rx Act 10MB Removable Door 100MB Fduplex Kernel Appl a q IP Address Area oH Global Address Label 100 Base Fx MT RJ Cable Connector Base 10 100 Base T RJ 45 Cable Connector 31004691 03 September 2003 Module Key specifications for the Quantum 140 NWM100 00 module are Specification Table Communication One auto sensing 10 100Base T shielded twisted pair RJ 45 connector port Ports One 100Base FX MT RJ connector port Both ports work in the same way but only one at a time LED Indicators Label Color Description Active Green Indicates that the backplane is operating Ready Green Indicates that the module is healthy Fault Red Indicates when the NWM is in a crash state Run Green Flashes to indicate diagnostic code as described in the Run LED Status table below Coll Red Flashes when Ethernet collisions occur Link Green On when Ethernet link is active TxAct Green Flashes to indicate Ethernet transmission RxAct Green Flashes to indicate Ethernet reception Kernel Amber On when in Kernel mode Flashing while in download mode 10MB Green On when the module is connected to a 10 Megabit network 100MB Green On when the module is connected to a 100 Meg
6. h you may customize 31004691 03 September 2003 This Web server allows the following browser functions e Display controller s configuration real time register values and personality e Display Ethernet statistics for the node e Display status configuration and register values of any remote distributed I O e Create and view graphic real time templates using Java beans e Create and view real time templates in spreadsheet format e Create custom Web pages e Use Concept symbols or direct addresses e Use SNMP with private MIB Note The embedded Web site must be viewed using Internet Explorer Version 4 0 with SP2 or higher Once the module has been installed these pages can be viewed across the World Wide Web Obtain the IP address or URL from you system administrator Then type the address into your browser For more information on the FactoryCast Web server obtain a copy of the latest version of the FactoryCast User s Guide 31001229 from your distributor or local sales office Key Features Installation This module is a FactoryCast HMI that provides a PLC with access to an Ethernet network The module can plug into any available slot ina Quantum backplane and is capable of being hot swapped The key features are listed below Feature 140 NWM 100 00 HTTP Server yes SNMP V2 Agent yes Flash File System yes FTP Server yes Modbus Messaging yes Schneider Private MIB yes Factory
7. rest Schneider Electric affiliate Printed in September 2003 8 31004691 04 Septiembre 2003