Home
        506185-01 CG90s CB TB UB Issue 0938.pmd - Aire-Flo
         Contents
1.                    FOR VENTING MATERIAL  SEE MATERIALS  SECTION IN THESE INSTRUCTIONS           CONDENSATE THE VENT SYSTEM OF  COLLAR  gt  THE FURNACE MUST  BE SELF SUPPORTING  AND  MUST NOT APPLY ANY  WEIGHT LOAD TO THE  COMBUSTION  BLOWER                          A IMPORTANT    DO NOT INSTALL THE  RESTRICTOR PLATES IN  ANY DIRECT VENT  APPLICATIONS                          Figure 8    Page 11 of 36    CG90UB  CG90TB  CG92TB  amp  CG95TB Upflow Models        Non Direct Vent Installation Upflow Non Direct Vent Vertical Venting    Aninlet air restrictor plate  see Figure 2 on page 5  is supplied  CG90UB  CG90TB  CG92TB  amp  CG95TB Only   with this furnace and can be found in the plastic bag    containing these Installation Instructions and the User s  Information Manual  This restrictor plate is to be used                only in non direct vent applications  See pages 5 and 6 HEIGHT TO EIE c      Q    for more information on installing the restrictor plate in non direct coe    vent applications  p FLASHING    Two inlet air restrictor plates are supplied with each furnace      a 2  plate and a 3  plate  Use the proper restrictor plate  for the furnace model           For horizontal venting  refer to Figure 9  For vertical venting   refer to Figure 10  The vent pipe on horizontal runs must  slope upward  away from the furnace  at a minimum pitch of  1 4  per foot of run  to prevent accumulation of condensate           SEE TABLE FOR VENT    i i LENGTH AND NUMBER  Prime the trap 
2.   BLOWER                                SEE TABLE FOR VENT  LENGTH AND NUMBER  OF ELBOWS ALLOWED     SEE TABLE FOR AIR INTAKE  LENGTH AND NUMBER  OF ELBOWS ALLOWED                       RUN PITCH   1 4         PER FOOT MINIMUM             VENT PIPE                       SEE TABLE FOR  PROPER PIPE SIZE     AIR INTAKE PIPE    FOR VENTING MATERIAL  SEE MATERIALS  SECTION IN THESE INSTRUCTIONS              pvc cOLLARS      VENT PIPE      _               A IMPORTANT    DO NOT INSTALL THE  RESTRICTOR PLATES IN  ANY DIRECT VENT  APPLICATIONS           CONDENSATE  COLLAR                                  Figure 12    Page 13 of 36    CG90CB Counterflow Models       Non Direct Vent Installation   An inlet air restrictor plate  see Figure 2 on page 5  is supplied  with this furnace and can be found in the plastic bag  containing these Installation Instructions and the User s  Information Manual  This restrictor plate is to be used  only in non direct vent applications  See pages 5 and 6  for more information on installing the restrictor plate in non   direct vent applications     Two inlet air restrictor plates are supplied with each furnace   a 2    plate and a 3  plate  Use the proper restrictor plate for  the furnace model     For horizontal venting  refer to Figure 13  For vertical venting   refer to Figure 14  The vent pipe on horizontal runs must  slope upward  away from the furnace  at a minimum pitch of  1 4  per foot of run  to prevent accumulation of condensate   Prime the tra
3.   NR  NR      so   25  3   3   NR  NR  NR  NR NR  NR  NR           3  3 PNR  NRE NR   NR  NR  NR  NR  vn      NR   Not Recommended    2    not recommended at altitude above 4 000 feet  3    required for altitude above 5 000 feet       Figure 4    Page 8 of 36 Issue 0938 506185 01    Sidewall Vent Terminal Clearances  Direct Vented Furnaces     A    Minimum 12   30 cm  above grade or  12   30 cm  above average snow accumulation     Vent Terminal    9 Air Supply Inlet    j Area Where Terminal Is  Not Permitted      ar Clearance above grade  veranda  porch  deck  or balcony 12 inches  30cm  12 inches  30cm     6 inches  15cm  for appliances       6 inches  15 cm  for appliances  lt   10 000 Btuh  3 KW   12 inches  30   10 000 Btuh  3 kW   9 inches  23  cm  for appliances  gt  10 000 Btuh  3   cm  for appliances  gt  10 000 Btuh  KW   and  lt 100 000 Btuh  30 KW      8 KW   and    50 000 Btuh  15  36 inches  81 cm  for appliances  gt  kW   12 inches  30 cm  for  100 000 Btuh  30 KW  appliances    50 000 Btuh  15 KW     Vertical clearance to ventilated soffit located above the  terminal within a horizontal distance of 2 feet  61 cm  from the  center line of the terminal    3 feet  91 cm  within a height 15  feet  4 5 m  above the  meter regulator assembly    Clearance to service regulator vent outlet 3 feet  91 cm  BUM a    6 inches  15cm  for appliances     6 inches  15 cm  for appliances     10 000 Buh  3 KW   12 inches  30  f 10 000 Btuh  3 KW   9 inches  23  Clearance to nonme
4.  01    High Altitude   In both the United States and Canada  this furnace is approved  for operation at altitudes from 0 to 4500 feet above sea level  without any required modifications  From 4500 to 7500 feet   the gas manifold pressure needs to be adjusted according to  the information shown in Table 4 on page 29     To adjust the manifold pressure  refer to previous section  Checking and Adjusting Gas Input  For installations above  7500 feet  refer to the latest issue of the National Fuel Gas  Code and or contact your Technical Services Support     For installations above 4500 feet  fill in the appropiate  information on the furnace label that has the words  This    furnace was converted on             Manifold Pressure vs  Altitude    Value     Pressure   Value    Pressure   Btu ft3  1  in  we    Btu ft3    in  w c      914 2196  865 2077   10 00    Altitude   Heating   Manifold   Heating   Manifold   Input   ft  Factor    849 2039 941  833 2000 9 35  818 1964   929  771 1853   912      Consult local utility for actual heating value   Furnace Input   Input Factor x Nameplate Input    Above 7500 feet  refer to the National Fuel Gas Code and or  contact your Technical Service Support        Table 4    For installation above 4 000 ft refer to section Vent Pipe  Size and Length on page 7 and Figure 4 on page 8 vent  pipe sizing     506185 01 Issue 0938 Page 29 of 36    MAINTENANCE             A WARNING    ELECTRICAL SHOCK  FIRE   OR EXPLOSION HAZARD  Failure to follow the sa
5.  RIGHT TO  LEFT AIRFLOW SHOWN    Figure 1    Inspection of Shipment   This furnace is shipped in one package  completely  assembled and wired  The thermostat is shipped in a  separate carton when ordered     Upon receipt of equipment  carefully inspect it for possible  shipping damage  If damage is found  it should be noted on  the carrier s freight bill  Damage claims should be filed with  the carrier immediately  Claims of shortages should be filed  with the seller within 5 days     506185 01          Issue 0938    Location   To provide proper operation and satisfactory performance  care  must be taken in choosing the location for this furnace  The  atmosphere in which the furnace operates must be free of  contaminants such as chlorides and sulfates     The furnace must be installed so that electrical components  are protected from water  Unit must be level for proper  condensate drainage              A WARNING    The condensate drain on this furnace is incorporated  within the furnace and must be primed before start up        The condensate system must not be exposed to  temperatures under 32 F  Use of heat tape is  permissible provided the rate temperature of the tape  does not exceed 155 F     Never install any furnace on its back    To avoid property damage caused by condensate drain  blockage  install a field fabricated auxiliary drain pan with a  separate drain line to the outside under the entire furnace  and drain system  Install according to local codes     All mod
6.  door interlock switch  Combustion blower assembly  Flame rollout protector switch  Hot surface igniter    Heat Exchanger Group  Heat exchanger     primary  Heat exchanger     secondary  Condensate drain pan    Blower Group   Blower housing assembly  Blower wheel   Blower motor   Blower motor mount  Blower motor capacitor    Burner Group  Gas manifold  Burner orifices  Burners    506185 01    Issue 0938    ACCESSORIES    ALPKT572 Natural Gas to Propane Conversion Kit   CG90UB  amp  CG90TB    ALPKT574 Natural Gas to Propane Conversion Kit   CG90CB  CG92TB  amp  CG95TB    ANGKT557 Propane to Natural Gas Conversion Kit   CG90UB  amp  CG90TB    ANGKT556 Propane to Natural Gas Conversion Kit   CG90CB  CG92TB  amp  CG95TB    ATWIN579 Twinning Kit   ABASE512 Combustible Floor Base  17 5  cabinets    ABASE568   Combustible Floor Base  21 0  cabinets    ABASE569 Combustible Floor Base  24 5  cabinets    Concentric Vent Kits  ACVK2 For US Applications  only    For Canadian Application use  IPEX Kit  196005 locally available           For a local IPEX Canadian Customer Service Center and kit  availability call IPEX at 1 866 473 9462     Page 31 of 36    CONTROL DIAGNOSTICS    Failure Codes    Troubleshooting    The following visual checks should be made before iru   troubleshooting  LED Status Fault Description   1  Check to see that the power to the furnace and the LED Off No power to control or control  integrated ignition blower control board is on  hardware fault detected   2  Thema
7.  exchanger causing burner flame  to  roll out  into the vestibule area or burner box     This switch must be manually reset by pushing the button  on top to restore furnace operation     Primary Limit Control   This is a normally closed control that opens if abnormally  high circulating air temperatures occur  It is an automatic  reset control     Auxiliary Limit Control   This is a normally closed control that opens under abnormal     reverse air flow    conditions that could occur in a counterflow  or horizontal installation if the circulating blower fails  It is an  automatic reset control     CG90TB  amp  CG92TB models have two auxiliary limit controls     CG90UB upflow models do not include an auxiliary limit  control     Interlock  Blower Door  Switch   When the blower door is removed  the interlock switch  breaks the power supply to the burner controls and blower  motor  The switch operation must be checked to confirm it  is operating correctly     Page 27 of 36    Integrated Ignition Blower Control Board   The integrated ignition blower control board operates all  functions of the furnace and any accessories connected to it   These models feature user selectable blower    off    delay times   60  90  120  and 180 seconds  that are factory set to provide  a 120 second blower  off  delay on heating  see connection  diagram on page 33      Refer to the furnace wiring diagram while using the following  procedure to change motor speed     1  Turn off electrical power to th
8.  in for more than 5 seconds before releasing     Page 32 of 36 Issue 0938 506185 01           LINE VOLTAGE   FACTORY   PU GNITOR       LINE VOLTAGE   FIELD         LOW VOLTAGE   FACTORY   LOW VOLTAGE   FIELD             INTERLOCK  SWITCH    CIRCULATION  WHT  NEUT  BLOWER    INDUCED    DRAFT NOT ON ALL MODELS  BLOWER    YEL    WHT  BLK WHT STRIPE  3     YELBLK STRIPE    TRANSFORMER    IF USED  i ORN ote ORN    ROLLOUT ROLLOUT  SWITCH SWITCH                                           NEUTRALS                HUM                                       FLAME  SENSOR                                                                            5A FUSE                FAULT CODE  HISTORY      _ BUTTON eis   SEENOTE1   5668                               o  90   60   gt     120   J 1 8 S sis   180   lt  TWIN  Swi uu oTo oTo    PRESSURE  BLOWER OFF   PRESSURE EUCH    DELAY TIMING i SWITCH                                                                                                    IF USED                   THERMOSTAT  amp  SUB BASE CONDENSER  HEAT ANTICIPATOR   60 AMP    1  PRESS AND RELEASE FAULT CODE 3  DO NOT CONNECT C  COMMON   HISTORY BUTTON TO DISPLAY FAULT CONNECTION BETWEEN INDOOR UNIT  CODES  TO ERASE CODES  PRESS AND THERMOSTAT EXCEPT WHEN  AND HOLD BUTTON IN FOR MORE REQUIRED BY THE INDOOR THERMOSTAT   THAN 5 SECONDS  REFER TO THE THERMOSTAT INSTALLATION  INSTRUCTIONS     IF ANY OF THE ORIGINAL WIRE AS  SUPPLIED WITH THE FURNACE MUST   CHECK CODES FOR PROPER WIRING AND  BE RE
9.  intake of at least 18    is highly  recommended to minimize the  chance of flue gases ECUEIPIPE  recirculating and freezing in the SS ee  air intake pipe  This distance P  may be reduced in milder  climates or where wind is  unlikely to blow flue products to  the intake pipe  but should not  be less than 6        Overhead View    THIS PIECE     IS OPTIONAL        INTAKE PIPE  3    MIN    48  MAX     Figure 7    506185 01       Issue 0938    Do not cement air intake into the connector on burner  box  Use high temperature RTV silicone sealant so  intake pipe can be removed if service is required     In horizontal venting applications  the vent and air intake  pipe must be installed on the same side of the house  within the parameters shown in Figure 7     Prime the trap system by slowly pouring 1 cup of water down  the vent pipe  On initial start up of the unit  some of the  water used to prime the trap system may run down into the  combustion blower and cause noise     Upflow Direct Vent     Vertical Venting   CG90UB  CG90TB  CG92TB  amp  CG95TB Only             6 5  MIN    24    MAX        T  HEIGHT TO PROVIDE  12  CLEARANCE TO          STORM COLLARS       AVERAGE SNOW LEVEL   cJ FLASHING                      SEE TABLE FOR VENT  LENGTH AND NUMBER     J SEE TABLE FOR AIR INTAKE  OF ELBOWS ALLOWED  A    LENGTH AND NUMBER  OF ELBOWS ALLOWED                             RUN PITCH   1 4  4  VENT PIPE  PER FOOT MINIMUM             SEE TABLE FOR  PROPER PIPE SIZE     AIR INTAKE PIPE
10.  intake pipe  A non direct vent   one pipe  installation uses air from inside the dwelling for  combustion     The furnace is shipped with the air inlet pipe terminated to the  top panel for either inside or outside combustion air  An inlet  air restrictor plate  see Figure 2  is supplied with this furnace  and can be found in the plastic bag containing these Installation  Instructions and the User s Information Manual  The inlet  restrictor plate must be used in all installations using inside  air for combustion  non direct vent      Inlet Air Restrictor Plate  The inlet air restrictor plate must be    installed in all installations using inside  air for combustion  non direct vent         Figure 2    Page 5 of 36    The inlet restrictor plate must be installed in the air inlet in  one of three ways       ARestrictor plate in inlet collar  Install the restrictor plate  in the inlet pipe collar in the top panel of the furnace   Insert a 3  to 36  section of PVC pipe  field supplied   into the collar  Use high temperature RTV sealant to  attach PVC pipe to collar  A 90  elbow  field supplied   may be attached to the PVC pipe  but the elbow is not  required  Use high temperature RTV sealant to attach  elbow to PVC pipe  if applicable         Restrictor plate in inlet pipe  Insert a 3  to 36  section of  PVC pipe  field supplied  into the collar  Use high  temperature RTV sealant to attach PVC pipe to collar   Install the restrictor plate in the end of the inlet pipe just  insta
11.  most current  edition of NFPA 54 as adopted by the Board  and    2  Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure  separate from the dwelling  building or structure used in whole or in part for residential purposes      506185 01 Issue 0938 Page 35 of 36        c  MANUFACTURER REQUIREMENTS   GAS EQUIPMENT VENTING SYSTEM PROVIDED  When  the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting  System design or venting system components with the equipment  the instructions provided by the  manufacturer for installation of the equipment and the venting system shall include     1  Detailed instructions for the installation of the venting system design or the venting system components   and  2  Acomplete parts list for the venting system design or venting system      d  MANUFACTURER REQUIREMENTS   GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED  When  the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not  provide the parts for venting the flue gases  but identifies  special venting systems   the following  requirements shall be satisfied by the manufacturer     1  The identification of each  special venting system  shall include the listing of either the website  phone  number or manufacturer s address where the venting system installation instructions can be obtained   and   2  The    special venting systems  shall be Product Approved by the Bo
12.  one opening shall be within 12  of the ceiling and  one opening within 12  of the floor  If combustion ducts are  vertical  each opening shall have a free area of 1 square inch  per 4000 BTU HR of the total input rating of all appliances  within the enclosure  If horizontal combustion ducts are run  1  square inch per 2000 BTU HR is required     Contaminated Combustion Air   Excessive exposure to contaminated combustion air will result  in safety and performance related problems  The  recommended source of combustion air is outdoor air   However  the use of indoor air in most applications is  acceptable if the following guidelines are followed     1  If the furnace is installed in a confined space  it is  recommended that the necessary combustion air come  from the outdoors by way of an attic  crawl space  air duct   or direct opening     2  If indoor combustion air is used  there must be no exposure  to the substances listed in item 5     3  All provisions for indoor combustion air must meet the  requirements for combustion air indicated in the National  Fuel Gas Code  ANSI Z223 1 NFPA 54  latest edition    and or any applicable local codes  In Canada  see CSA  B149 1  Natural Gas and Propane Installation Codes   latest edition      4  The following types of installation may require outdoor  air for combustion  due to chemical exposures     e Commercial buildings     Buildings with indoor pools     Furnaces installed in laundry rooms      Furnaces installed in hobby or craf
13.  sized in accordance with the information found in  the appropriate table in Figure 4  One 90 elbow is equivalent  to 5  of pipe  Two 45   elbows are equivalent to one 90  elbow   The minimum length certified for use with this furnace is 5   and one elbow  not including the vent and air intake terminals     In the event that the pipe length is in between the lengths  listed in the table  use the next larger length listed  For  example  if a length of pipe needed to install the furnace is  27   use the diameter values for the 30  row in the tables   For direct vent installations  if the vent and air intake pipe  are not equal in length and number of elbows  then determine  the minimum pipe diameter for both the vent and air intake   If the results indicate different diameters  use the larger of  the two for both the vent and air intake  Under no  circumstances should the vent and air intake pipe size  be different in diameter  For installation details  refer to  the appropriate section in pages 10     17 for the unit model  and type of installation     High Altitude Installation  2  pipe not recommended at  altitude above 4 000 feet  3  pipe required for altitude above  5 000 feet     Horizontal Venting   The vent for this appliance shall not terminate over public  walkways  or near soffit vents or crawl space vents or other  areas where condensate or vapor could create a nuisance or  hazard or cause property damage  or where condensate vapor  could cause damage or could be de
14.  switch to the inducer  Remove and discard the  plastic cap from the tee and connect the hose from the 0 10   drain pressure switch to the tee   See Figure 31      Condensate Drain Trap Installation     Tight Clearance Below Unit    End View   IMPORTANT  If vent tee is not located over the  auxiliary drain pan  it must be extended over the  pan with an elbow facing down to prevent  overflow in the event of a blocked drain  The  elbow must be installed downward over the  auxiliary pan to prevent wicking back down the  condensate line                                                        NOTE  Vent tee to avoid  Two 3 4  90   Elbows   vapor lock  If connecting  to waste drain pipe  a  second trap must be  installed downstream                                      Field Supplied Fittings    gi       1 2  NPT x 1 2  PVC           ud  Adapter and Trap Assembly   supplied     Do not install trap assembly any farther than 10  from unit  The pressure switch and vent  hoses must be able to reach the barbed fittings on the trap assembly        Figure 30    Page 20 of 36 Issue 0938 506185 01    Pressure Switch Connection  Upflow Installation    a        Primary Pressure  f a Switch Assembly       Blower  lousing    Tap Tee     Yellow Cap     supplied     Figure 31    Be sure that the pressure switch hose does not form a  trap to hold condensation that could form from the flue  gas  Hose may be cut shorter to avoid forming a trap  if  required     Horizontal Installation   The CG90TB  CG
15.  switches are  closed and pressure switch is open  The induced draft blower  relay closes causing the blower to run  As vent pressure is  developed by the induced draft blower  the pressure switch  closes  After a 15 second pre purge  the control energizes the  hot surface ignitor  After the 7 second warmup time  the control  energizes the gas valve causing the burners to ignite  The hot  surface ignitor is de energized 3 seconds after the valve opens   If flame is sensed during this time the valve remains energized  and the control starts the 30 second heat blower  on  delay     As heating demand is met  the thermostat de energizes the  R W circuit  The control de energizes the gas valve causing  the burners to shut off  The induced draft blower shuts off  after a 15 second post purge delay  The circulating air blower  will continue to operate until the user selectable heat blower   off  delay expires  The control return to standby mode once  the heat blower  off  delay expires     Fan  On    During a fan  on  call  the thermostat energizes the R G  circuit of the control board  immediately causing the fan to  energize the heat speed  The fan remains energized as long  as the thermostat calls for fan  on  operation     If a call for heat is energized during a fan  on  call  the fan  continues to operate at the heat speed  If a call for cooling is  energized during a fan  on  call  the fan switches to cooling  speed     At the end of the fan  on  call the thermostat de energi
16.  the floor  sized to provide 1  clearance  between all four sides of the duct and the edge of the  flooring  The four angles on the base assembly should  recess into the floor joists and the base should rest on  all four outside flanges     2  Construct duct connections with right angle flanges     Page 22 of 36       Issue 0938                      Combustible Floor Installation   CG90CB Counterflow Models Only     Base F  Assembly urnace  N        Woven  Glass Tape Duct    N          Combustible     1     Flooring                         Outlet Duct   Drops Into Base  Assembly     Woven Glass Tape    Between Flanges   of Outlet Duct and  Base Assembly     Combustible Floor  Base Assembly    Figure 34    3  Drop the duct connections through the top of the base  assembly with the right angle flanges in good contact  with the glass tape on top of the base assembly     4  Carefully position the furnace over the right angle duct  flanges     Gas Supply and Piping  Refer to the furnace rating plate to make sure the furnace is  equipped to burn the gas supplied  natural or propane               A WARNING    Any conversion of a natural gas unit to propane gas must  be done by qualified personnel using a conversion kit  available from the manufacturer  following the instructions       in the conversion kit  If done improperly  overfiring of the  burners and improper burner operation can result  This  can create carbon monoxide which could cause  asphyxiation     506185 01    Gas sup
17. 92TB and CG95TB multi position units  are shipped from the manufacturer with a black hose having  one end connected to the 0 10  drain pressure switch and  the other end shipped loose  FOR HORIZONTAL  INSTALLATIONS the loose end MUST be connected to the  external drain trap     Route hose through gas line access hole in cabinet  Then  connect to 1 4  barbed fitting on drain trap assembly     For right to left airflow installations  see Figure 32  For left  to right airflow installations  see Figure 33     Be sure that the pressure switch hose does not form a  trap to hold condensation that could form from the flue  gas  Hose may be cut shorter to avoid forming a trap  if  required     506185 01 Issue 0938       Pressure Switch Connection  Horizontal Installation     R to L Airflow    0 10  w c   Pressure Switch    ma  Black Hose         Figure 32    Pressure Switch Connection  Horizontal Installation     L to R Airflow       Figure 33    Page 21 of 36    Circulating Air Supply   When the furnace is installed so that the supply ducts carry  air circulated by the furnace to areas outside the space  containing the furnace  the return air shall be handled by a  duct or ducts sealed to the furnace casing and terminated  outside the space containing the furnace     A return air duct system is recommended  If the unit is  installed in a confined space or closet  a return connection  must be run  full size  to a location outside the closet  The  air duct in the closet must be tight t
18. ANT    DO NOT INSTALL THE  RESTRICTOR PLATES IN  ANY DIRECT VENT  APPLICATIONS                         Maintaining a vertical separation  between the flue outlet and the  air intake of at least 18  is highly  recommended to minimize the  chance of flue gases    recirculating and freezing in the  air intake pipe  This distance    may be reduced in milder    climates or where wind is    unlikely to blow flue products to  the intake pipe  but should not    be less than 6      506185 01    Figure 11    FLUE PIPE IS y apnd  r4  ELT     di   E                      INTAKE PIPE    Overhead View    THIS PIECE             3    MIN    48    MAX        Issue 0938    Do not cement air inlet pipe  Use high temperature RTV  silicone sealant so inlet pipe can be removed if service  is required     In horizontal venting applications  the vent and air intake  pipe must be installed on the same side of the house  within the parameters shown in Figure 11     Prime the trap system by slowly pouring 1 cup of water down  the vent pipe  On initial start up of the unit  some of the  water used to prime the trap system may run down into the  combustion blower and cause noise     Counterflow Direct Vent     Vertical Venting   CG90CB Only         1    6 5  MIN    24  MAX     ENG  HEIGHT TO PROVIDE      12  CLEARANCE    STORM COLLARS  TO AVERAGE    SNOW LEVEL  FLASHING             A CAUTION    THE VENT SYSTEM OF  THE FURNACE MUST  BE SELF SUPPORTING  AND MUST NOT APPLY  ANY WEIGHT LOAD TO  THE COMBUSTION
19. Clearance Installation    3  Long Piece of  2  Diameter Pipe   supplied       IIIJ  Floor oq  77 TT    Vent Pipe     ewe       supplied     2 2  90   Elbows Air Intake Pipe   ee    Canadian Installations  See    Canadian Applications Only    on page 7   Figure 19    Horizontal Non Direct Vent     Horizontal Venting  Low Clearance Installation    3   Long Piece of  2  Diameter Pipe      Vent Pipe   supplied       Drain Tee   supplied     FE  Inlet Air Restrictor Plate   see page 5        2  2   90   Elbows      Canadian Installations  See    Canadian Applications Only    on page 7     Figure 20    506185 01          Issue 0938    result in spillage of flue products into the living space  the  formation of condensate  leakage  etc  See the WARNING  box below for proper test procedure              A WARNING    CARBON MONOXIDE POISONING HAZARD    Failure to follow the steps outlined below for each  appliance connected to the venting system being  placed into operation could result in carbon monoxide  poisoning or death        The following steps shall be followed for each appliance  connected to the venting system being placed into  operation  while all other appliances connected to the  common venting system are not in operation     1  Seal any unused openings in the common venting  system     Visually inspect the venting system for proper size  and horizontal pitch  as required in the National Fuel  Gas Code  ANSI Z223 1 NFPA 54  latest edition  or  the CSA B149 1  Natural Gas 
20. INSTALLATION INSTRUCTIONS    CG90CB  CG90UB  CG90TB  CG92TB  amp  CG95TB  High Efficiency 90  Condensing Gas Furnace       Save these instructions for future reference    A WARNING    Improper installation  adjustment  alteration  service  or maintenance can cause injury or property damage   Refer to this manual  For assistance or additional information  consult a qualified installer  service  agency  or the gas supplier              A WARNING TABLE OF CONTENTS    Do not store combustible materials  including gasoline and   other flammable vapors and liquids  near the furnace  vent SAFETY   pipe  or warm air ducts  The homeowner should be   cautioned that the furnace area must not be used as a INSTALLATION  broom closet or for any other storage purposes  Such uses       may result in actions that could cause property damage  START UP  personal injury  or death   OPERATION    MAINTENANCE             A WARNING    This furnace is not approved for installation in a mobile REPAIR PARTS  home  Do not install this furnace in a mobile home     Installation in a mobile home could result in actions that CONTROL SYSTEM DIAGNOSTICS    32  could cause property damage  personal injury  or death   WIRING DIAGRAMS       Manufactured By  Allied Air Enterprises Inc   A Lennox International Inc  Company    215 Metropolitan Drive  A WARNING    West Columbia  SC 29170  The installation of the furnace  wiring  warm air ducts  venting  etc  must conform to the requirements of the National Fire  Pro
21. PLACED  IT MUST BE REPLACED CIRCUIT PROTECTION BEFORE INSTALLATION   WITH WIRING MATERIAL HAVING A TEMP   RATING OF AT LEAST 90 C     Connection Diagram  P N 45198 006       Figure 40    506185 01 Issue 0938 Page 33 of 36       120 1 60       INTERLOCK  SWITCH                NEUTRALS  o   lt  e    HOT SURFACE IGNITOR                         NEUTRALS  HUMIDIFIER  lt                         NEUTRALS          INDUCED DRAFT  BLOWER       NEUTRALS l           gt  AIR CLEANER    Xt  gt  HEAT  K5  gt  ap NEUTRALS   gt  COOL BLOWER MOTOR         K5                                        120 VAC NEUTRALS  NACL                TRANSFORMER          re     24 VAC n    PIN 3 PIN 6                            X JE USED  FLAME SENSOR   gt  PIN2 PIN 5  lt  OO                            J  ROLLOUT SWITCH ROLLOUT SWITCH   gt  PIN 12 PIN11  lt        GAS VALVE   gt  PIN 9 PIN 1 oTo                      LIMIT SWITCH   lt     eee IF USED  PIN 10 zZ Ho oto oTo oTo  J    WYG n PRESSURE PRESSURE  AUX LIMIT SWITCH AUX LIMIT SWITCH  QOO x SWING SWITCH SWITCH    CN  md  CONDENSER    PIN 8 PIN 7                PIN                      4  C  e    R  2                                                                                     THERMOSTAT                      Schematic Diagram  P N 45198 006       Figure 41    Page 34 of 36 Issue 0938 506185 01    FOR MASSACHUSETTS ONLY       AIMPORTANT             For Side Wall Horizonal Venting    The installation must comply with 248 CMR 5 08 Modifications to sect
22. RESTRICTOR PLATE     SEE TABLE FOR  PROPER PIPE SIZE              VENT PIPE    CONDENSATE    COLLAR                            A CAUTION  THE VENT SYSTEM OF  THE FURNACE MUST  BE SELF SUPPORTING  AND MUST NOT APPLY  ANY WEIGHT LOAD TO  THE COMBUSTION   BLOWER                             Figure 14    CG90TB  CG92TB  amp  CG95TB Horizontal Models    Direct Vent Installation   An inlet air restrictor plate  see Figure 2 on page 5  is supplied  with this furnace and can be found in the plastic bag containing  these Installation Instructions and the User s Information Manual   This restrictor plate is to be used only in non direct vent  applications  See pages 5 and 6 for more information on  installing the restrictor plate in non direct vent applications     Maintaining a vertical separation between the flue outlet and  the air intake of at least 18    is highly recommended to minimize  the chance of flue gasses re circulating and freezing in the air  intake pipe  The 18  separation is shown for horizontal  installations in Figure 15  This distance may be reduced in  milder climates or where wind is unlikely to blow flue products  to the intake pipe  but should not be less than 6      506185 01    For horizontal venting  refer to Figure 15  For vertical venting   refer to Figure 16  It is permissible to run the vent vertically  through the roof and terminate it as shown in Figure 16  and  to run the combustion air intake pipe horizontally through a  side wall and terminate as sho
23. Right to Left Airflow   Furnace must be mounted such that the side through which  the condensate will drain is elevated a minimum of 9  above  a surface such as a floor  Flue Pan    Install Trap Assembly    Install unit at a slight pitch forward  see Figure 22      1  Relocate the 1 2  NPT plug installed on the flue pan to  one side of the internal trap assembly  as shown in  Figure 23      2  Connect the 1 2  NPT plug  supplied  to the opposite  side of the internal trap assembly from the plug installed    in Step 1  1 2  NPT x 1 27 PVC  m Adapter and Trap Assembly  3  Inserttrap assembly  supplied  into flue pan  see Figure  supplied     24         Figure 24    Page 18 of 36 Issue 0938 506185 01    4  Connect a length of 3 4  PVC pipe  3  minimum  to the  trap assembly  see Figure 25      Tilt Unit Forward    5  Install 3 4  tee  supplied  as shown in Figure 25     Completing Condensate  Drain Installation                                                                                              3 4  Tee    3 8  Vinyl Hose   supplied  1 2  NPT Plug     supplied in kit     Be sure to avoid double trapping the vinyl hose   Hose must be installed as shown        Figure 25    6  Fromthe tee  connect the drain to disposal area  The top  of the tee must be left open for proper condensate  drainage  The open end of the tee must be oriented so 1 2  NPT Plug  that condensate does not run out of the opening   supplied on unit        7  Remove 72  vinyl hose supplied with unit and c
24. Table 2    506185 01    The solvent shall be free flowing and contain no lumps   undissolved particles  or any foreign matter that adversely  affects the joint strength or chemical resistance of the  cement  The cement shall show no gelation  stratification   or separation that cannot be removed by stirring     Refer to Table 2 for approved piping and fitting materials   Canadian Applications Only  PVC pipe  fittings  primer  and solvent cement used to vent this applicance must be  certified to ULC S636 and supplied by a single manufacturer  as part of an approved venting system  In addition  the first  three feet of vent pipe from the furnace flue collar must be  accessible for inspection  Models that may be installed as a  horizontal furnace include a horizontal drain kit  In Canada  this drain kit must be replaced by a locally available IPEX  Drain Kit   196014  For Local IPEX Canadian Customer  Service Center and Kit abailability call IPEX at 1 866 473   9462     The primers and solvents used must also meet ASTM  specifications  PVC primer is specified in ASTM F656  Use  PVC solvent as specified in ASTM D2564 and ABS solvent  cement as specified ASTM D2235  Low temperature solvent  cement is recommended  Metal or plastic strapping may be  used for vent pipe hangers     When making ABS joints  pieces can be prepared with a clean  dry cloth to clean inside socket surface of fitting and male end  of pipe to depth of socket  Refer to procedure specified in  ASTM D3138  When j
25. and Propane  Installation Codes and these instructions   Determine that there is no blockage or restriction   leakage  corrosion  or other deficiencies which could  cause an unsafe condition     As far as practical  close all building doors and  windows between the space in which the  appliance s  connected to the venting system are  located and other spaces in the building     Close fireplace dampers     Turn on clothes dryers and any appliance not  connected to the venting system  Turn on any  exhaust fans  such as range hoods and bathroom  exhausts  so they are operating at maximum speed   Do not operate a summer exhaust fan     Follow the lighting instructions  Place the unit  being inspected in operation  Adjust the thermostat  so appliance is operating continuously     Test for spillage from draft hood equipped  appliances at the draft hood relief opening after 5  minutes of main burner operation  Use the flame  of a match or candle     If improper venting is observed during any of the  above tests  the venting system must be corrected  in accordance with the National Fuel Gas Code   ANSI Z223 1 NFPA 54  latest edition  and or the  CSAB149 1  Natural Gas and Propane Installation  Codes     After it has been determined that each appliance  remaining connected to the venting system  properly vents when tested as outlined above   return doors  windows  exhaust fans  fireplace  dampers  and any other gas fired burning  appliance to their previous conditions of use        Pa
26. ard  and the instructions for provided  with that system shall include a parts list and detailed installation instructions      e  A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled  equipment and all the venting instructions  parts lists  and or design instructions for the venting system  shall remain with the appliance or equipment at the completion of the installation           Text from Commonwealth of Massachusetts Official Website of the Office of Consumer Affairs  amp  Business Regulation   OCABR        Text from Joseph A Peluso  Jr   Executive Director Board of State Examiners of Plumbers and Gas Fitters   Commonwealth of Massachusetts  letter of April 24  2007 to GAMA     Page 36 of 36 Issue 0938 506185 01    
27. chanical air supply inlet to building or the   cm  for appliances  gt  10 000 Btuh  3   cm  for appliances  gt  10 000 Btuh  combustion air inlet to any other appliance KW   and x 100 000 Btuh  30 KW    3 KW   and     50 000 Btuh  15  f 36 inches  91 cm  for appliances  gt  kW   12 inches  30 cm  for  100 000 Btuh  30 kW  appliances    50 000 Btuh  15 KW             3 feet  91 cm  above if within 10  Clearance to a mechanical air supply inlet 6 feet  1 83 m  feet  3 m  horizontally  Clearance above paved sidewalk or paved driveway located 7 feet  2 13 m     on public property      M   Clearance under veranda    Clearance under veranda  porch  deck  or balcony     Clearance under veranda  porch  deck  or balcony   or balcony 12   tBinches Oem        tBinches Oem      cm  t    Clearance to window or door that may be opened    Clearance to each side of center line extended above  meter regulator assembly    1  n accordance with the current CSA B149 1  Natural Gas and   Permitted only if veranda  porch  deck  or balcony is fully open on a  Propane Installation Code minimum of two sides beneath the floor       n accordance with the current ANSI Z223  1 NFPA 54  National   For clearances not specified in ANS  Z223  1 NFPA 54 or CSA  Fuel Gas Code B149 1  the following statement shall be included      Avent shall not terminate directly above a sidewalk or paved  Clearance in accordance with local installation codes and the  driveway that is located between two single family dwelling
28. ctrical Wiring          A WARNING    Risk of electrical shock  Disconnect electrical power at  the circuit breaker or service panel before making  electrical connections  Failure to disconnect power  supplies can result in property damage  personal injury   or death           The furnace must be grounded and wired in accordance  with local codes or  in the absence of local codes  with the  National Electrical Code ANSI NFPA No  70  latest edition   and or CSA C22 1 Electrical Code  latest edition  if an  external electrical source is utilized     In all instances  other than wiring for the thermostat  the  wiring to be done and any replacement of wire shall conform  with the temperature limitation for Type T wire    63   F  35  C   rise     Connect a sufficiently sized wire with ground to the furnace s  line voltage connections and ground lug  Refer to the furnace  rating plate for electrical characteristics to be used in sizing  field supply wiring and over current protection     The line voltage supply should be routed through a readily  accessible disconnect located within sight of the furnace   A junction box on the furnace side panel is provided for line  voltage connections  Refer to the furnace wiring diagram  for specific connection information     Proper polarity of the supply connections     HOT    and     NEUTRAL     must be observed to ensure that safety  controls provide the protection intended     A connection to the ground lug and actual earth ground   typicall
29. d during construction       Air filters must be replaced upon construction completion       The input rate and temperature rise must be set per the  furnace rating plate       One hundred percent  100   outdoor air must be provided  for combustion air requirements during construction   Temporary ducting may supply outdoor air to the furnace   Do not connect duct directly to the furnace  Size the  temporary duct following the instructions provided on this  page in the Combustion and Ventilation Air section  regarding confined space with air from outside       The furnace heat exchanger  components  duct system   air filters  and evaporator coils must be thoroughly cleaned  following final construction cleanup       All furnace operating conditions  including ignition  input  rate  temperature rise  and venting  must be verified  according to these installation instructions     If the furnace is to be installed in an attic or other insulated  space  it must be kept free and clear of insulating materials     Clearances   All servicing and cleaning of the furnace can be performed  from the front  If installed in a closet or utility room  provide  18  clearance in front for service if the door to the room is  not in line with the front of the furnace     Refer to Table 1 forthe minimum clearances to combustibles  required for construction and proper unit operation     Accessibility clearances must take precedence over fire  protection clearances     Minimum Clearances to Combustib
30. e unit     2  Connectthe desired speed tap for cooling on the  control board     3  For heating speed  check the temperature rise and  if  necessary  adjust blower speed tap to maintain  temperature rise within the range shown on the furnace  rating plate     To use the same speed tap for both heating and cooling   install a piggyback terminal on the speed tap using a  short jumper  Wire 1 4  quick connect terminals on both  ends to jumper the    HEAT    and    COOL    speed on the  control board     4  Theremaining speed taps must be connected to dummy  terminals marked  PARK  on the control board     Checking and Adjusting Gas Input   The minimum permissible gas supply pressure for the purpose  of input adjustment is 5  W C  for natural gas and 11  W C  for  propane gas  This furnace requires conversion for use with  propane  see Accessories section on page 29 for correct  kit   The maximum inlet gas supply pressure is 10 5  W C  for  natural gas and 13  W C  for propane     Checking and Adjusting Gas Input    Regulator  Adjustment   under cap     Gas Control Switch                                                                      Figure 38    Page 28 of 36       Issue 0938    Gas input must never exceed the value shown on the furnace  rating plate  The furnace is equipped for rated input at  manifold pressures of 3 5  W C  for natural gas or 10 0  W C   for propane gas     To measure inlet or outlet pressure  remove plug from  desired pressure tap  inlet or outlet  as s
31. els are suitable for closet or utility room installation     The furnace is suitable for installation in buildings constructed  on site  The furnace should be centralized in respect to the  heat distribution system as much as practicable  When  installed in a utility room  the door should be wide enough to  allow the largest part of the furnace to enter  or permit the  replacement of another appliance  such as a water heater     A gas fired furnace for installation in a residential garage must  be installed so the burner s  and the ignition source are located  not less than 18  above the floor  The furnace is to be located  or protected to avoid physical damage by vehicles     This furnace is not recommended to be used as a construction  heater during any phase of construction  Very low return air  temperatures  harmful vapors  and operation of the unit with  clogged or misplaced filters will damage the unit     The furnace may be used for heating of buildings or structures  under construction  if the following conditions are met        Theventsystem must be permanently installed per these  installation instructions     e  Aroom thermostat must control the furnace  The use of  fixed jumpers that will provide continuous heating is not  allowed     e The return air duct must be provided and sealed to the  furnace     Page 3 of 36      Return air temperature range between 60  F and 80  F  must be maintained       Air filters must be installed in the system and must be  maintaine
32. fety warnings exactly could result    in dangerous operation  serious injury  death  or property  damage        Improper servicing could result in dangerous operation   serious injury  death  or property damage       Before servicing  disconnect all electrical power to  furnace     When servicing controls  label all wires prior to  disconnecting  Reconnect wires correctly     Verify proper operation after servicing     It is recommended that this furnace be inspected by a  qualified service technician at the beginning of each heating  season     Filters   Filters should be checked at least every 6 weeks  Disposable  filters should be replaced when dirty  and cleanable filters  should be cleaned regularly  It is important to keep the air  filters clean  as dirty filters can restrict airflow and the blower  and induced draft motors depend upon sufficient air flowing  across and through them to keep from overheating     Lubrication   The blower motor and induced draft motor are pre lubricated  by the manufacturer and do not require further lubricating  attention  However  the motors should be cleaned periodically  to prevent the possibility of overheating due to an accumulation  of dust and dirt on the windings or on the motor exterior     Condensate Collection and Disposal System   Check the condensate drain line periodically for blockage   Visual inspection of condensate flow can be done easily while  the furnace is in operation  Use a flashlight to illuminate the  discharge e
33. for the furnace model     Horizontal Non Direct Vent     Horizontal Venting   CG90TB  CG92TB  amp  CG95TB Only     6  Airflow Right to Left    Inlet Air Restrictor Plate  1  see page 5     Height to  provide 12     clearance  to average  snow level  3  Long Piece of  2  Diameter Pipe   supplied     Drain Tee   supplied       Airflow Left to Right    Drain Tee   supplied with unit       3    Long Piece of  2  Diameter Pipe   supplied       Height to  provide 12   clearance  to average  snow level    Ed      Canadian Installations  See  Canadian Applications Only  on page 7     Inlet Air Restrictor Plate   see page 5           Figure 17    Page 16 of 36    Issue 0938    For horizontal venting  refer to Figure 17  For vertical venting   refer to Figure 18  The vent pipe on horizontal runs must  slope upward  away from the furnace  at a minimum pitch of  1 4  per foot of run  to prevent accumulation of condensate     Prime the trap system by slowly pouring 1 cup of water down  the vent pipe  On initial start up of the unit  some of the  water used to prime the trap system may run down into the  combustion blower and cause noise                   Horizontal Non Direct Vent     Vertical Venting   CG90TB  CG92TB  amp  CG95TB Only     Height to  provide 12  clearance  to average  snow level    Airflow Right to Left    See table for  vent length        and number  of elbows  allowed    inlet Air Restrictor Plate   see page 5      supplied       3    Long Piece of 2  Diameter Pipe   su
34. ge 17 of 36    Condensate Disposal Installation  The condensate drain should be routed directly to a locally Tilt Unit Forward  acceptable disposal area  The condensate drain line should  not be run directly to the outdoors especially in colder  climates where temperatures may cause the condensate to  freeze in the drain line     1 4  Max    In horizontal installations where clearance beneath the unit  is limited  an alternate method for condensate disposal trap  installation may be used  see Horizontal Installation     Tight  Clearance Below Unit on page 20      Upflow Installation   Install the condensate drain line to the unit as follows  The  condensate can be drained from either the right or left side  of the furnace  Install the 1 2  NPT x 3 4  PVC adapter   supplied  in the drain on the side that the draining will occur   Install the plastic pipe plug opposite of the drain  Using 3 4   PVC pipe  make a connection from the adapter just installed  to extend just outside the unit  Install a 3 4  PVC tee as  shown in Figure 21  From the tee  install the drain to the  disposal area  The top of the tee must be left open for proper  condensate drainage        1 2  NPT Plug   supplied in kit     Condensate Disposal     Upflow    3 4  PVC  TEE MUST REMAIN  a OPEN             3 4    PVC    1 2 NPT PLUG 45   r  1 2  NPT x 3 4  PVC ADAPTER   SUPPLIED   SUPPLIED                                                                       Figure 21 Figure 23    Horizontal Installation     
35. hown in Figure 38  and connect a water manometer or gauge to the proper  pressure tap     To adjust the regulator  disconnect the hose and remove  the barbed fitting in the downstream side of the gas valve   Turn the adjusting screw on the regulator clockwise to  increase pressure and input  counterclockwise to decrease  pressure and input     Replace the barbed fitting and reconnect the hose after adjusting  the regulator  Be sure to replace the inlet and outlet pressure  tap plugs after testing and or adjusting gas input              A CAUTION       The furnace rate must be within     2  of the appliance  rating input        For Natural Gas  Check the furnace rate by observing the  gas meter  when available  making sure all other gas  appliances are turned off  The test hand on the meter should  be timed for at least one revolution  Note the number of  seconds for one revolution     BTU HR _ Cubic Feet Per Revolution   3600 x Heating  INPUT     Seconds Per Revolution Value    The heating value of the gas can be obtained from the local  utility company     For Propane Gas  The only check for the furnace rate is to  properly adjust the manifold pressure using a manometer and  Table 4 on page 29  Typical manifold set point for installations  at altitudes from 0 to 4500 feet above sea level is 10 0  W C     Temperature Rise  Check the temperature rise and  if necessary  adjust blower  speed to maintain temperature rise within the range shown on  the unit rating plate     506185
36. in a fire hazard or carbon  monoxide injury        Unconfined Space   An unconfined space is defined as  a space whose volume  is more than 50 cubic feet per 1000 BTU per hour of the  combined input rating of all appliances installed in that  space   When afurnace is installed in an unconfined space  in a building  it can be assumed that the infiltration will be  sufficient to supply the required air  If the furnace is installed  in a ventilated attic or crawl space  it is assumed that the  infiltration is sufficient to supply the required air  However   in a building of unusually tight construction  additional outdoor  air should be provided     506185 01    Confined Space   Aconfined space is defined as    a space whose volume is less  than 50 cubic feet per 1000 BTU per hour of the combined  input rating of all appliances installed in that space        If the furnace is installed in a confined space within the  building and combustion air is taken from a heated space   the combustion air and ventilating air must enter and leave  the space through two permanent openings of equal area   One opening shall be located within 12  of the ceiling and  the other within 12  of the floor  each having a free area of  1 square inch per 1000 BTU HR of total input rating of all  appliances within the space and not less than 100 square  inches each     If the furnace is installed in a space within a building of tight  construction  makeup air must be supplied from outdoors  In  this case 
37. ions of NFPA 54   Chapter 10 as listed below            a  For all side wall horizontally vented gas fueled equipment installed in every dwelling  building or structure  used in whole or in part for residential purposes  including those owned or operated by the Commonwealth  and where the side wall exhaust vent termination is less than seven  7  feet above finished grade in the  area of the venting  including but not limited to decks and porches  the following requirements shall be  satisfied     1  INSTALLATION OF CARBON MONOXIDE DETECTORS  At the time of installation of the side wall  horizontal vented gas fueled equipment  the installing plumber or gasfitter shall observe that a hard wired  carbon monoxide detector with an alarm and battery back up is installed on the floor level where the gas  equipment is to be installed  In addition  the installing plumber or gasfitter shall observe that a battery  operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the  dwelling  building or structure served by the side wall horizontal vented gas fueled equipment  It shall be  the responsibility of the property owner to secure the services of qualified licensed professionals for the  installation of hard wired carbon monoxide detectors  a  Inthe eventthat the side wall horizontally vented gas fueled equipment is installed in a crawl space or   an attic  the hard wired carbon monoxide detector with alarm and battery back up may be insta
38. iping  system              A WARNING    The gas valve supplied with this furnace is rated at 1 2  psig maximum  Any higher pressure may rupture the       pressure regulator diaphragm and may cause overfiring  of the burners and improper burner operation  The  overfiring may result in the creation of carbon monoxide  which could cause asphyxiation     After gas piping is complete  carefully check all piping  connections  factory and field  for gas leaks  Use a leak  detecting solution or other preferred means  Some soaps  used for leak detection are corrosive to certain metals   Carefully rinse piping thoroughly after leak detection has  been completed     506185 01 Issue 0938          Gas Piping Connection    Manual Gas Valve    1 8  NPT Plugged Tapping  Union    Tee  in   TT  Cap i          i               Upflow  1 8  NPT Plugged Tapping    Manual Gas Valve   _   Union  Tee  3  EH    Drip Leg  ll    ict             Cap    Counterflow    Manual Horizontal  Gas Valve 1 8  NPT Installation    Union    Tee    Drip Leg  N    Cap          Figure 35             A WARNING  FIRE OR EXPLOSION HAZARD    Failure to follow the safety warnings exactly could result  in serious injury  death  or property damage        Never test for gas leaks with an open flame  Use a  commercially available soap solution made specifically  for the detection of leaks to check all connections  A  fire or explosion may result causing property damage   personal injury  or loss of life     Page 23 of 36    Ele
39. is method  follow proper instructions on the previous pages  for completing condensate drain installation     A CAUTION    To avoid property damage caused by condensate drain    Completing Condensate  Drain Installation                         blockage  install a field fabricated auxiliary drain pan with  aseparate drain line to the outside under the entire furnace  and drain system  including open vent tees     3 4  Tee  3 8  Vinyl Hose     supplied        Be sure to avoid double trapping the vinyl hose   Hose must be installed as shown        Drain Pressure Switch Connection  Figure 29  for CG90TB  CG92TB and CG95TB multi position units  only  The CG90BU dedicated upflow and CG90BC dedicated  counterflow units do not require a drain switch    6  From the tee  connect the drain to disposal area  The  top of the tee must be left open for proper condensate    drainage  The open end of the tee must be oriented so Upflow Installation  that condensate does not run out of the opening  The CG90TB  CG92TB  AND CG95TB multi position units  are shipped from the manufacturer with a black hose having  7  QConnectone end of 72  vinyl hose  supplied  to 3 8  barbed one end connected to the 0 10  drain pressure switch and  fitting of the 2  x 2  x 1 2  tee in vent and the other end to the other end shipped loose  FOR UPFLOW  3 8  barbed fitting on drain trap assembly  INSTALLATIONS the loose end is to be connected to the    capped tee in the hose assembly leading from the primary  pressure
40. led by  one thermostat   An accessory kit must be ordered from  the manufacturer  Specific wiring and operating instructions  are included with the kit     Each furnace must have its own dedicated vent system     Page 25 of 36    START UP  Lighting Instructions    For Your Safety  Read Before Operating          A WARNING          If you do not follow these instructions exactly  a fire or  explosion may result causing property damage  personal  injury  or loss of life     These furnaces are equipped with an ignition device which  automatically lights the burners  Do not try to light the  burners by hand     Before operating  smell all around the appliance area for  gas  Be sure to smell next to the floor because some gas is  heavier than air and will settle on the floor    What to do if you smell gas    e Do not try to light any appliances     e  Extinguish any open flame        Donottouch any electric switch  do not use any phone  in your building       Immediately call your gas supplier from a neighbor s  phone  Follow the gas supplier s instructions        f you cannot reach your gas supplier  call the fire  department     Do not use this furnace if any part has been under water   Immediately call a qualified service technician to inspect the  furnace and to replace any part of the control system and  gas control which has been under water     IMPORTANT  Refer to the Lighting Instruction label on    the furnace for instructions on operating the specific  controls used on yo
41. les  Upflow    Counterflow    ma    v   o     ren  rf    Table 1    Page 4 of 36          Issue 0938    CG90UB  CG90TB  CG92TB and CG95TB models may be  installed on wood flooring but shall not be installed directly on  carpeting  tile  or any other combustible material     CG90CB counterflow models are certified for installation on  combustible flooring provided a special base assembly is  used   Refer to the Duct Connection     Counterflow  Models section on page 22 for more information on using  the special base assembly      When a counterflow unit is installed on a combustible floor   1  clearance must be provided between the supply duct and  the floor     Combustion and Ventilation Air   Adequate provisions for combustion air and ventilation of  furnace must be made  Refer to Section 5 3   Air for  Combustion and Ventilation   of the National Fuel Gas Code   ANSI Z223 1 NFPA54  latest edition   Sections 7 2  7 3  or  7 4 of CSA B149 1 Natural Gas and Propane Installation  Codes  latest editions   or applicable provisions of the local  building codes              A WARNING    Insufficient combustion air can cause headaches   nausea  dizziness  or asphyxiation  When considering  combustion air requirements  enough air must also be  provided to meet the needs of all fuel burning  appliances and exhaust fans                 A WARNING    Air openings in the front of the furnace must be kept  free of obstructions  Any obstruction may cause improper  operation that can result 
42. lled  Attach either a field supplied coupler or 90   elbow to the end of the PVC pipe to keep the restrictor  plate in place  Use high temperature RTV sealant to attach  the coupler or elbow to PVC pipe        Restrictor plate in elbow  Insert a 3  to 36  section of  PVC pipe  field supplied  into the collar  Use high  temperature RTV sealant to attach PVC pipe to collar   Attach a 90  elbow  field supplied  to the PVC pipe  Use  high temperature RTV sealant to attach elbow to PVC pipe   Install the restrictor plate into the elbow     Two different sized inlet restrictor plates are supplied with the  furnace  2  and 3    Use the proper restrictor plate for the  furnace model              A WARNING    If at any time in the future the installation of this furnace  is changed to require outside fresh air for combustion        the inlet air restrictor plate must be removed  Failure to  remove the inlet air restrictor could cause improper  operation that can result in a fire hazard or carbon  monoxide injury     For either type of installation  direct or non direct vent    special venting considerations must be followed  Refer to  the proper section in pages 10     17 for the type of furnace  and venting being installed     The venting system must be supported with mounting straps  to prevent any weight load from being applied to the vent  blower  Horizontal vent pipe must be supported every 5  and  vertical pipe should be supported every 10  to prevent  sagging and provide rigid 
43. lled  on the next adjacent floor level    b  Inthe event that the requirements of this subdivision can not be met at the time of completion of  installaiton  the owner shall have a period of thirty  30  days to comply with the above requirements   provided  however  that during said thirty  30  day period  a battery operated carbon monoxide detector  with an alarm shall be installed    2  APPROVED CARBON MONOXIDE DETECTORS  Each carbon monoxide detector as required in  accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS  certified    3  SIGNAGE  A metal or plastic identification plate shall be permanently mounted to the exterior of the  building at a minimum height of eight  8  feet above grade directly in line with the exhaust vent terminal  for the horizontally vented gas fueled heating appliance or equipment  The sign shall read  in print size no  less than one half  1 2  inch in size   GAS VENT DIRECTLY BELOW  KEEP CLEAR OF ALL  OBSTRUCTIONS     4  INSPECTION  The state or local gas inspector of the side wall horizontally vented gas fueled equipment  shall not approve the installation unless  upon inspection  the inspector observes carbon monoxide  detectors and signage installed in accordance with the provisions of 248 CMR 5 08 2  a 1 through 4      b  EXEMPTIONS  The following equipment is exempt from 248 CMR 5 08 2  a  1 through 4   1  The equipment listed in Chapter 10 entitled  Equipment Not Required To Be Vented  in the
44. n the plastic bag containing these  Installation Instructions and the User s Information Manual  This  restrictor plate is to be used only in non direct vent  applications  See pages 5 and 6 for more information on installing  the restrictor plate in non direct vent applications     For horizontal venting  refer to Figure 7  For vertical venting   refer to Figure 8  It is permissible to run the vent vertically  through the roof and terminate it as shown in Figure 8  and  to run the combustion air intake pipe horizontally through a  side wall and terminate as shown in Figure 7  The vent pipe  on horizontal runs must slope upward  away from the furnace   at a minimum pitch of 1 4  per foot of run  to prevent  accumulation of condensate     Upflow Direct Vent     Horizontal Venting   CG90UB  CG90TB  CG92TB  amp  CG95TB Only     THIS PIECE    RUN PITCH   1 4  IS OPTIONAL     PER FOOT MIN            SEE TABLE FOR       FLUE PIPE    PROPER PIPE SIZE      ue             X  AIR INTAKE PIPE    BE  e      AIR INTAKE PIPE    HEIGHT TO PROVIDE  12    CLEARANCE TO  AVERAGE SNOW LEVEL                                                     CONDENSATE A CAUTION  COLLAR THE VENT SYSTEM OF   2 THE FURNACE MUST   BE SELF SUPPORTING   AND  MUST NOT APPLY ANY  WEIGHT LOAD TO THE  COMBUSTION  BLOWER                 A IMPORTANT  DO NOT INSTALL THE  RESTRICTOR PLATES IN  ANY DIRECT VENT   APPLICATIONS                                Maintaining a vertical separation  between the flue outlet and the  air
45. nd of the condensate drain that is placed in the  sewer opening  If the condensate drain line becomes  blocked or plugged  the furnace will not operate properly     Page 30 of 36       Issue 0938    Burners   Light the burners and allow to operate for a few minutes to  establish normal burning conditions  Observe the burner  flames  Compare this observation to Figure 39 to determine if  proper flame adjustment is present  Flame should be  predominantly blue in color and strong in appearance  Check  that all burners are lit  and that the flame does not impinge on  the sides of the heat exchanger     Distorted flame or yellow tipping of the natural gas burner  flame  or long yellow tips on propane  may be caused by lint  accumulation or dirt inside the burner or burner ports  at the  air inlet between the burner and manifold pipe  or  obstructions over the burner orifice     Use a soft brush or vacuum to clean the affected areas     Typical Flame Appearance    Heat    Exchanger  Burner                pa       Gas Burner  Manifold Flame     Blue Only     Figure 39    506185 01    REPAIR PARTS    The following repair parts are available from the local  distributor  When ordering parts  include the complete  furnace model number and serial number which are printed  on the rating plate located on the furnace     Control Group   Transformer   High limit control   Auxiliary limit  if used    Gas valve   Integrated ignition blower control board  Flame sensor   Pressure switch   Blower
46. nterflow Models     Direct Vent Installation  Aninletair restrictor plate  see Figure 2 on page 5  is supplied with  this furnace and can be found in the plastic bag containing these  Installation Instructions and the User s Information Manual  This  restrictor plate is to be used only in non direct vent  applications  See pages 5 and 6 for more information on installing  the restrictor plate in non direct vent applications     For horizontal venting  referto Figure 11  For vertical venting   refer to Figure 12  It is permissible to run the vent vertically  through the roof and terminate it as shown in Figure 12  and  to run the combustion air intake pipe horizontally through a  side wall and terminate as shown in Figure 11  The vent  pipe on horizontal runs must slope upward  away from the  furnace  at a minimum pitch of 1 4  per foot of run  to prevent  accumulation of condensate     Counterflow Direct Vent Horizontal Venting   CG90CB Only     THIS PIECE             A CAUTION  THE VENT SYSTEM OF  THE FURNACE MUST  BE SELF SUPPORTING  AND MUST NOT APPLY  ANY WEIGHT LOAD TO  THE COMBUSTION   BLOWER                    RUN PITCH   1 4   PER FOOT MIN     SEE TABLE FOR  PROPER PIPE SIZE           IS OPTIONAL   M FLUE PIPE    TE    IL                   AIR INTAKE PIPE       AIR INLET  PIPE          VENT PIPE      __       CONDENSATE       PVC COLLARS                COLLAR                   e     HEIGHT TO PROVIDE  12  CLEARANCE  TO AVERAGE  SNOW LEVEL     H                A IMPORT
47. nual shutoff valves in the gas line to the furnace LED On  must be open  1 Flash Flame Present with gas valve off    2 Flash Pressure switch closed with  eee inducer off    3  Make sure all wiring connections are secure     4  Review the Sequence of Operation  see page 27       3 Flashes Pressure switch open with  Start the system by setting the thermostat above the room inducer on  temperature  Observe the system s response  Then use 4 Flashes  the information provided in this section to check the system   s a a  operation  5 Flashes Rollout switch open  The furnace has a built in  self diagnostic capability  If a 6 Flashes Pressure switch cycle lockout  system problem occurs  a fault code is shown by an LED on  the control board  The control continuously monitors its own 7 Flashes Lockout due to no ignition  operation and the operation of the system  Ifa failure occurs   the LED will indicate the failure code  The flash codes are Flashes _  Lockout due to too many flame  presented in Table 5  dropouts     9 Flashes   Incorrect line voltage phasing   Fault Code History Button    The control stores the last five fault codes in memory  A Table 5  pushbutton switch is located on the control  see Figure 40   on page 33   When the pushbutton switch is pressed and   released  the control flashes the stored fault codes  The   most recent fault code is flashed first  the oldest fault code   is flashed last        To clear the fault code history  press and hold the pushbutton  switch
48. o prevent any entrance  of air from the closet into the circulating air     If there is no complete return air duct system  the return air  connection must be sealed to the furnace casing and run   full size  to a location outside the utility room or space housing  the furnace to prevent a negative pressure on the venting  system              A CAUTION    When an air conditioning unit is used in conjunction with  the furnace  the evaporator coil must be installed in the       discharge  supply  air  Do not install an evaporator coil  in the return air  excessive condensation will occur within  the furnace     Outlet Duct   For installations not equipped with a cooling coil  a removable  access panel must be provided in the outlet duct  The  opening should be accessible when the furnace is placed in  service  Smoke or reflected light may be observed inside  the casing to indicate the presence of leaks in the heat  exchanger  The cover for the opening shall be attached in  such a manner as to prevent leaks  The recommended  opening size is 6  x 14  for all sizes     Duct Connection     CG90CB Counterflow Models   If a unitis installed on a noncombustible floor  it may be installed  directly over the supply duct or plenum  For installations on  combustible flooring  a special base must be ordered and used    See the Accessories section on page 31 for more  information   To install using the special base assembly  see  Figure 34 and the following instructions     1  Cut a hole in
49. oining ABS to PVC materials  use  transition solvent     Preferred fittings are DWV style or long sweep  Seal all joints  gas tight with appropriate cement  In areas where vent and air  intake pipes are exposed to abnormal stress or are subject to  damage  schedule 80 pipe should be used     Category IV Furnace Limitations   This furnace shall not be connected to any Type B  BW  or L  vent or vent connector and shall not be connected to any portion  of a factory built or masonry chimney  This furnace is not to be  common vented with any other appliance  The vent pipe  must not be connected to a chimney flue serving a separate  appliance designed to burn solid fuel     Concentric Vent Kit Dimensions    4      11        1     i 1  8 5                                         f              os 5  gt     Elbow  Field Supplied           2  nominal pipe size  For 3  venting   use  2  3  x 2  Schedule 40 PVC reducers        Figure 3    506185 01    Issue 0938    Concentric Vent Kit   A concentric vent kit  see Accessories section on page 31 for  correct kit  is available for use when installing this furnace as  a direct vent furnace and the air intake and vent pipe are to be  run through the same hole  whether horizontally through the  wall or vertically through the roof  see Figure 3   Refer to the  instructions included with the concentric vent kit for installation  specifics     Vent Pipe Size and Length   The vent pipe and air intake pipe  in direct vent installations   should be
50. or vent  length and number  of elbows allowed     See table for air intake  length and number of  elbows allowed      supplied     3    Long Piece of 2  Diameter Pipe   supplied       Airflow Left to Right   Mi  g SN 6 5  Min      24  Max  Height to  provide  12  clearance  to average    snow level    See table for vent  length and number  of elbows allowed     See table for  air Intake length    and number of  3  Long Piece of elbows allowed   2  Diameter Pipe 4   supplied           supplied         Canadian Installations  See  Canadian Applications Only  on page 7    Figure 16    Page 15 of 36    Prime the trap system by slowly pouring 1 cup of water down  the vent pipe  On initial start up of the unit  some of the  water used to prime the trap system may run down into the  combustion blower and cause noise     CG90TB  CG92TB  amp  CG95TB Horizontal Models   Non   Direct Vent Installation   An inlet air restrictor plate  see Figure 2 on page 5  is supplied  with this furnace and can be found in the plastic bag  containing these Installation Instructions  This restrictor plate  is to be used only in non direct vent applications  Place the  restrictor plate into the inlet collar  insert 3  section of PVC  pipe  field supplied   then attach a 90  elbow  field supplied   to the PVC pipe in all non direct vent installations  see  Figures 17 and 18      Two inlet air restrictor plates are supplied with each furnace      a 2  plate and a 3  plate  Use the proper restrictor plate  
51. p system by slowly pouring 1 cup of water down  the vent pipe  On initial start up of the unit  some of the water  used to prime the trap system may run down into the  combustion blower and cause noise     Counterflow Non Direct Vent Horizontal Venting   CG90CB Only              RUN PITCH   1 4   PER FOOT MIN     A CAUTION  THE VENT SYSTEM OF  THE FURNACE MUST  BE SELF SUPPORTING  AND MUST NOT APPLY  ANY WEIGHT LOAD TO  THE COMBUSTION   BLOWER           SEE TABLE FOR  PROPER PIPE SIZE              M    GROMMET COUPLER ee  HEIGHT TO PROVIDE  12  CLEARANCE  TO AVERAGE  SNOW LEVEL           PVC COLLAR    VENT PIPE L          THE INLET AIR  RESTRICTOR PLATE  MUST BE INSTALLED   ON ALL NON DIRECT  VENT INSTALLATIONS   SEE PAGE 5 FOR  INFORMATION ON  INSTALLING THE INLET  AIR RESTRICTOR PLATE        CONDENSATE  COLLAR                                                 Figure 13    Page 14 of 36       Issue 0938    Counterflow Non Direct Vent Vertical Venting   CG90CB Only         HEIGHT TO PROVIDE   12  CLEARANCE  TO AVERAGE  SNOW LEVEL     STORM COLLAR  we       FLASHING                SEE TABLE FOR VENT  LENGTH AND NUMBER  OF ELBOWS ALLOWED           RUN PITCH   1 4       PER FOOT MINIMUM             VENT PIPE       FOR VENTING MATERIAL    SEE MATERIALS SECTION   IN THESE INSTRUCTIONS   INLET    GROMMET    COUPLER          Pvc COLLAR THE INLET AIR  RESTRICTOR PLATE  MUST BE INSTALLED   ON ALL NON DIRECT  VENT INSTALLATIONS   SEE PAGE 5 FOR  INFORMATION ON  INSTALLING THE INLET  AIR 
52. ply piping should be installed in accordance with local  codes and the regulations of the utility  Piping must be of  adequate size to prevent undue pressure drop  Consult the  local utility or gas supplier for complete details on special  requirements for sizing gas piping     If local codes allow the use of a flexible gas appliance  connector  always use a new listed connector  Do not use a  connector which has previously serviced another gas  appliance     Pipe connections must be tight  and a non hardening pipe  compound resistant to liquefied petroleum gases should be  used     Connect the gas pipe to the furnace controls providing a  ground joint union as close to the controls as is possible to  facilitate removal of controls and manifold  Provide a drip  leg on the outside of the furnace  A manual shutoff valve  shall be installed in the gas line  outside the unit  5  above  the floor  or in accordance with any local codes  A test  gauge connection must be installed with a 1 8  NPT plugged  tapping immediately upstream of the shutoff valve  see  Figure 35      The furnace must be isolated from the gas supply piping  system by closing the individual manual shutoff valve during  any pressure testing of the gas supply piping system at test  pressure equal to or less than 1 2 psig  3 5 kPa  or 14  W C   If the piping system is to be tested at pressures in excess of  1 2 psig  3 5 kPa   the furnace and its appliance main gas  valve must be disconnected from the gas supply p
53. pplied       Airflow Left to Right    Height to  provide 12   clearance to  average  snow level       For venting material   see venting section  in these instructions     3  Long Piece of  2  Diameter Pipe   supplied           supplied       Inlet Air Restrictor Plate   see page 5       Canadian Installations  See  Canadian Applications Only  on page 7     Figure 18    506185 01    CG90TB  CG92TB  amp  CG95TB Horizontal Models   Horizontal Venting     Low Clearance Installations  Vent pipe on horizontal runs must slope upward  away from  the furnace  at a minimum pitch of 1 4  per foot of run  to  prevent accumulation of condensate  In certain horizontal  left   to right airflow applications  the furnace s close proximity to  the floor joists above the unit may make it difficult to obtain the  required pitch slope  Figure 19 and 20 show the accepted  vent practice to obtain proper pitch slope back to furnace for  proper drainage  For direct vent applications  see Figure 19   For non direct applications  see Figure 20     In all applications  minimum clearances to combustibles must  be observed  as shown in Table 1 on page 4  as well as all  other required clearances shown in Figures 15 and 17 on  pages 15 and 16     Existing Venting Systems   Whenan existing furnace is removed or replaced  the original  venting system may no longer be sized to properly vent the  attached appliances  An improperly sized venting system can    Horizontal Direct Vent     Horizontal Venting  Low 
54. s and requirements of the gas supplier and the manufacturer s installation  serves both dwellings  instructions         Figure 5    506185 01 Issue 0938 Page 9 of 36    Sidewall Vent Terminal Clearances  Non Direct Vented Furnaces     A    Minimum 12   30 cm  above grade or  12   30 cm  above average snow accumulation     Vent Terminal     amp  Air Supply Inlet    Ru  Area Where Terminal Is  N Not Permitted    US Installations   Clearance above grade  veranda  porch  deck  or balcony 12 inches  30 cm  12 inches  30 cm     6 inches  15 cm  for appliances     10 000 Btuh  3 KW   12 inches  30    cm  for appliances    10 000 Btuh  3 4 feet  1 2 m  below or to side of  kW   and  lt   100 000 Btuh  30 kw        Pening  1 foot  30 om  above  36 inches  91 cm  for appliances  gt  opening  100 000 Btuh  30kW     Clearance to window or door that may be opened    Clearance to  permanently closed window    Vertical clearance to ventilated soffit located above the  termina  within a horizontal distance of 2 feet  61 cm  from the  center line of the terminal    Clearance to unventilated soffit  Clearance io outside corner  Clearance to inside corner    3 feet  91 cm  within a height 15  Clearance to each side of center line extended above d Ris above Hi    meter regulator assembly meter regulator assembly    Clearance to service regulator vent outlet 3 feet  91 cm     6 inches  15 cm  for appliances     10 000 Btuh  3kW   12 inches  30 cm   Clearance to nonmechanicai air supply inlet to b
55. scharged outdoors   Connect this furnace to an approved vent system only   as specified in the Venting section beginning on page 5  of these instructions     Never test for gas leaks with an open flame  Use a  commercially available soap solution made specifically  for the detection of leaks to check all connections  as  specified in Gas Supply and Piping beginning on  page 22 of these instructions     T     Always install furnace to operate within the furnace s  intended temperature rise range with a duct system  which has an external static pressure within the  allowable range  as specified in Temperature Rise  on page 28 of these instructions  See furnace rating  plate     When a furnace is installed so that the supply ducts  carry air circulated by the furnace to areas outside  the space containing the furnace  the return air shall  also be handled by duct s  sealed to the furnace  casing and terminating outside the space containing  the furnace  See Circulating Air Supply on page 22  of these instructions     A gas fired furnace for installation in a residential  garage must be installed as specified in the Location  section on page 3 of these instructions       The furnace is permitted to be used for temporary    heating of buildings or structures under construction as  specified in the Location section beginning on page 3  of these instructions     In the State of Massachusetts    This product must be installed by a licensed Plumber  or Gas Fitter  When flexible connec
56. support     Page 6 of 36       Issue 0938    When a furnace is installed as direct vent  provisions for  ventilation air should follow the same requirements as if  installed as non direct vent  Proper ventilation air is  necessary to maintain furnace component temperatures  within acceptable limits     All vents passing through floors  ceilings  and walls must be  installed in accordance with National Fuel Gas Code  ANSI  Z223 1 NFPA 54  latest edition      The length of flue pipe exposed to outdoor conditions should  be kept to a minimum  When the installation requires more  than 3 feet of flue pipe be exposed to outdoor conditions   insulating the exposed flue pipe with 1 2  Armaflex or  equivalent is recommended   n climates with design  temperatures below zero degrees  F   3 4  Armaflex or  equivalent is recommended     Materials   All pipe  fittings  primer  and solvent cement must conform  with American National Standard Institute and the American  Society for Testing and Materials  ANSI ASTM  standards     Piping and Fitting Specifications    Piping  amp  Fitting ASTM  Material Specification  Schedule 40 PVC  Schedule 40 PVC F891   Cellular Core Pipe   Schedule 40 PVC     Fittings  D2465    SDR 26   Pipe  D2241  Schedule 40 ABS D1527   Pipe      Fittings   Schedule 40  amp  80 CPVC F441   Pipe     Schedule 40  amp  80 CPVC F438     Fittings   ABS DWV  D2661    Drain Waste  amp  Vent   Pipe  amp  Fittings     PVC DWV  Drain Waste  amp  Vent   Pipe  amp  Fittings        
57. system by slowly pouring 1 cup of water down Exc pas    the vent pipe  On initial start up of the unit  some of the  water used to prime the trap system may run down into the  combustion blower and cause noise                    A RUN PITCH   1 4     VENT PIPE PER FOOT MINIMUM       EOR VENTING MATERIAL     SEE MATERIALS SECTION  IN THESE INSTRUCTIONS                 SEE TABLE FOR INLET  PROPER PIPE SIZE    COUPLER THE INLET AIR RESTRICTOR PLATE  wA MUST BE INSTALLED ON ALL  NON DIRECT VENT INSTALLATIONS   SEE PAGE 5 FOR INFORMATION ON  INSTALLING THE INLET AIR  RESTRICTOR PLATE        Upflow Non Direct Vent Horizontal Venting   CG90UB  CG90TB  CG92TB  amp  CG95TB Only                    CONDENSATE       RUN PITCH   1 4   A CAUTION  PER FOOT MIN     THE VENT SYSTEM OF  THE FURNACE MUST BE  SELF SUPPORTING AND SEE TABLE FOR   MUST NOT APPLY ANY PROPER PIPE SIZE     WEIGHT LOAD TO THE  INLET    COMBUSTION BLOWER   4  COLLAR rre  THE INLET AIR        HEIGHT TO PROVIDE                         A CAUTION    THE VENT SYSTEM OF  THE FURNACE MUST BE  SELF SUPPORTING AND   MUST NOT APPLY ANY   WEIGHT LOAD TO THE  COMBUSTION BLOWER                                RESTRICTOR PLATE 12  CLEARANCE  MUST BE INSTALLED TO AVERAGE  ON ALL NON DIRECT SNOW LEVEL   VENT INSTALLATIONS   SEE PAGE 5 FOR  INFORMATION ON CONDENSATE  INSTALLING THE INLET i  AIR RESTRICTOR Figure 10  PLATE                            Lo 04                         Figure 9    Page 12 of 36 Issue 0938 506185 01    CG90CB Cou
58. t rooms      Furnaces installed near chemical storage areas    506185 01    Issue 0938    5  Exposure to the following substances in the combustion  air supply may also require outdoor air for combustion       Permanent wave solutions   e Chlorinated waxes and cleaners   e  Chlorine based swimming pool chemicals     Water softening chemicals     M Deicing salts or chemicals   e Carbon tetrachloride      Halogen type refrigerants     Cleaning solvents  such as perchloroethylene     Printing inks  paint removers  varnishes  etc   e Cements and glues   e Antistatic fabric softeners for clothes dryers  e Masonry acid washing materials   e Chlorinated laundry products   e Hydrochloric acid    Venting   The high efficiency of this furnace is accomplished by the  removal of both sensible and latent heat from the flue gases   The removal of latent heat results in the condensation of  moisture in the flue gases  This condensation occurs in the  secondary heat exchanger and in the vent system  Therefore   this furnace requires special venting considerations and the  instructions must be followed to insure proper operation  All  venting must be in accordance with the codes having  jurisdiction in the area and these instructions     CG90UB  CG90TB  CG92TB  CG95TB and CG90CB  models can be installed as either direct vent or non direct  vent units  A direct vent  two pipe  installation requires that  all the air necessary for combustion be supplied from outside  the dwelling through an air
59. tection Association  the National Fuel Gas Code  ANSI Z223 1 NFPA No  54  latest edition  and the National Electrical           b    CERTIFIED       506 18 5 001                Code  ANSI NFPA No  70  latest edition  in the United States  CSA B149 1  latest edition  Natural Gas and Propane Installation  Codes and the Canadian Electrical Code Part 1  CSA 22 1  latest edition  in Canada  and any state or provincial laws  local  ordinances  including plumbing or wastewater codes   or local gas utility requirements  Local authorities having jurisdiction  should be consulted before installation is made  Such applicable regulations or requirements take precedence over the general  instructions in this manual        506185 01 Issue 0938 Page 1 of 36    IMPORTANT SAFETY INFORMATION    The following is a list of safety rules and precautions that  must be followed when installing this furnace     1     Page 2 of 36    Use only with the type of gas approved for this furnace   Refer to the furnace rating plate     Install this furnace only in a location and position as  specified in the Location section on page 3 of these  instructions     Provide adequate combustion and ventilation air to the  furnace space as specified in the Combustion and  Ventilation Air section on page 4 of these instructions     Adequate clearance must be provided around the vent   air intake terminals as specified in the Venting section  beginning on page 5 of these instructions     Combustion products must be di
60. tion blower control board as indicated on the  wiring diagram     Humidifier   Terminals are provided on the integrated ignition blower control  board for connection to a 120 volt humidifier  The    HUM    terminal  is energized whenever the thermostat calls for heat  Refertofumace  wiring diagram for specific connection information     Continuous Low Speed Blower   If continuous blower operation on low speed is desired   connect the lowest speed motor tap to the  CONT  terminal  on the integrated ignition blower control board  refer to the  furnace wiring diagram   The blower will operate on low  speed whenever main power is connected to the furnace   except when it operates on heating or cooling speed during  thermostat call for heat or cooling  This constant air  terminal is intended for low speed only  If a motor is  wired for a higher speed  the increased amp draw could  cause the control board to fail and void the warranty     506185 01    Issue 0938    Electronic Air Cleaner   Terminals are provided on the integrated ignition olower  control board for connection of a 120 volt electronic air  cleaner  The    EAC    terminal is energized whenever the  thermostat is calling for heat  cooling  or continuous blower   Refer to the furnace wiring diagram for specific connection  information     Twinning   The integrated ignition blower control board is designed to  permit    twinning    of furnaces  two furnaces connected to a  common supply and return air system  and control
61. tors are used  the  maximum length shall not exceed 36   When lever   type gas shutoffs are used  they shall be T handle    type     Issue 0938       506185 01    INSTALLATION    These instructions must be placed on or near the furnace in  a conspicuous place     The furnace design is certified by CSA International as a  Category IV furnace in compliance with the latest edition of  American National Standard Z21 47 CSA Standard 2 3 for  Gas Fired Central Furnaces  for operation with natural gas  or propane  Consult the rating plate on the furnace for gas  type before installing     The maximum hourly heat loss of space shall be calculated  in accordance with the procedure described in the current  manuals of Air Conditioning Contractors of America  or by  any other recognized method which is suitable for local  conditions  provided the results obtained are in substantial  agreement with  and not less than  those obtained using the  procedure described in the manuals     CG90UB models shall be installed only as upflow furnaces   CG90CB models shall be installed only as counterflow   downflow  furnaces     CG90TB and CG92TB  amp  CG95TB models may be installed  as upflow or horizontal right to left or left to right airflow fur   naces  When installed horizontally  the installer must install  a sheet metal screw to retain the upper door as shown in  Figure 1     Horizontal Installations    hil Locate Screw Here When Horizontal  installation is Airflow Left to Right    HORIZONTAL
62. trimental to the operation  of regulators  relief valves  or other equipment     See Figures 5 and 6 on pages 9 and 10 for additional  information on where the horizontal vent terminal can and  cannot terminate     For Massachusetts Installations  The installation must  comply with Massachusetts 248 CMR 5 08 Modifications to    sections of NFPA 54  Chapter10   See pages 35 and 36     Page 7 of 36    Vent Tables     numbers in inches unless specified otherwise     Minimum Pipe Diameter  40 000     75 000 BTU HR Models    Vent Pipe Number of 90   Elbows    Length   py folst2 s atsi st 7  s  9     20  2  2 2  2 2  2 2  2  22s    212 1212 2 2 2  29 29 25 25    0o L2 212 2   2   25  28  25  25  25     5   2  2125 25 2s 2s 25 25  25  3      90   2   26  26  25  25  25  25  3  3  3      e  2s 25 25  s   3  3  3  3  nr  NR   L f2s  25  3  8  3  3  2  nal na  ne     Minimum Pipe Diameter  80 000     100 000 BTU HR Models    Vent Pipe Number of 90   Elbows    Length   m  ol  2 s 4 s  e 7  el     2   2  2  2  2  2   26  25  zs  25  3             2 2 es zs 25 3   BL  3  8  3     so  25 25 25  3   sj 3   3   3  s fir    L8  25 3 3 3   3 3 5  w  NR  nn       3   3  3 PNR  NRE NR INR  NR  NR ENR         3  3 PP RP WR ENR TR eR ENR E hR     Minimum Pipe Diameter  112 000     125 000 BTU HR Models    Vent Pipe Number of 90  Elbows    Length  m jo tia2jsje s e r s e      20   25  255 25  25 25 25 25  3   3   NE       30  25 25  25  25 25  3   3   NR  NRT NR      40   25 25 25 25  3  NR  NRI NR
63. uilding or the for appliances  gt  10 000 Btuh  3 KW       4 feat  1 2 m  below or to side of  combustion air inlet to any other appliance and  lt  100 000 Btuh  30 KW       opening  1 foot  30 cm  above  36 inches  91 cm  for appliances  gt  opening  100 000 Btuh  30kW     Clearance to a mechanical air supply inlet 6 feet  1 83 m  3 api alee i10    Clearance above paved sidewalk or paved driveway located  on public property 7 feet  2 13 m f 7 feet  2 13 m f  Clearance under veranda  porch  deck  or balcony 12 inches  30 cm  t RENE EN    In accordance with the current CSA B149 1  Natural Gas and   Permitted only if veranda  porch  deck  or balcony is fully open on a  Propane Installation Code minimum of two sides beneath the floor    In accordance with the current ANSI Z223  1 NFPA 54  National   For clearances not specified in ANSI Z223  1 NFPA 54 or CSA   Fuel Gas Code B149 1  the following statement shall be included    A vent shall not terminate directly above a sidewalk or paved  Clearance in accordance with local installation codes and the  driveway that is located between two single family dwellings and requirements of the gas supplier and the manufacturer s installation  serves both dwellings  instructions         Ex  25   in  EN  ER       Figure 6    Page 10 of 36 Issue 0938 506185 01    CG90UB  CG90TB  CG92TB and CG95TB Upflow  Models     Direct Vent Installation   Aninletair restrictor plate  see Figure 2 on page 5  is supplied with  this furnace and can be found i
64. ur unit     Page 26 of 36          Issue 0938    To Start Furnace              A CAUTION       Be sure the manual gas control has been in the  OFF   position for at least 5 minutes before starting the unit   Do not attempt to manually light the burners     1  Setthe room thermostat to lowest setting    2  Remove burner access door    3  Move the gas control knob to the  ON  position  Use  only your hand to turn the gas control knob  never use  tools  If the knob will not turn by hand  don t try to repair  it  call a qualified service technician  Force or attempted  repair may result in a fire or explosion    4  Replace the burner access door    5  Turnon the electrical power to the furnace    6  Set the room thermostat to a point above room  temperature to light the burners  After the burners have  ignited  set the room thermostat to desired temperature    To Shut Down Furnace    1  Setthe room thermostat to the lowest setting    2  Turn off all electric power to the furnace     3  Remove burner access door     4  Shutoff the gas by moving the gas control knob to the   OFF  position     5  Replace the burner access door        A WARNING             Should overheating occur or the gas supply fail to shut  off  shut off the manual gas valve to the appliance before  shutting off the electrical supply     506185 01    OPERATION    Sequence of Operation    Heating   During a call for heat the thermostat closes the R W circuit of  the control board  The control board verifies limit
65. ut in half  Figure 27  Connect one end of the vinyl hose to the 3 8  barbed fitting  of the 2  x 2  x 1 2  tee in vent and the other end to the    3 8  barbed fitting on the drain trap assembly  Install Trap Assembly    Horizontal Installation     Left to Right Airflow Piue Man    Furnace must be mounted such that the side through which  the condensate will drain is elevated a minimum of 9  above  a surface such as a floor     Install unit at a slight pitch forward  see Figure 26      1  Relocate 1 2  NPT plug installed on flue pan to one side  of the internal trap assembly  as shown in Figure 27      1 27 NPT x 1 2  PVC    2  Connect the 1 2  NPT plug  supplied  to the opposite Adapter and Trap Assembly  side of the internal trap assembly from the plug installed  supplied   in Step 1        o  Figure 28  3  Inserttrap assembly  supplied  into flue pan  see Figure    28      4  Connecta length of 3 4  PVC pipe  3  minimum  to the 5  Install 3 4  tee  supplied  as shown in Figure 29   trap assembly  see Figure 29      506185 01 Issue 0938 Page 19 of 36    Horizontal Installation     Tight Clearance Below Unit   In certain horizontal installations  clearance between unit and  drain pan beneath unit may be limited  In these applications   an alternate method may be used to install the condensate  drain trap assembly  Using two 90  elbows  field supplied    bring condensate trap out to side of unit beyond drain pan   see Figure 30   After trap assembly has been attached using  th
66. wn in Figure 15  The vent  pipe on horizontal runs must slope upward  away from the  furnace  at a minimum pitch of 1 4  per foot of run  to prevent  accumulation of condensate     Horizontal Direct Vent     Horizontal Venting   CG90TB  CG92TB  amp  CG95TB Only     Alr intake Airflow Right to Left    clearance    to average      sn  w level 3  Long Piece of    2  Diameter Pipe  Yo Drain Tee  supplied      supplied       Airflow Left to Right    3  Long Piece of Vent  2   Diameter Pipe Drain Tee Pipe     supplied    Supplied       Air intake  Pipe Height to  provide 12   clearance  to average  snow level    4    Intake may be raised as  shown to obtain minimum snow  clearance requirements     Overhead View    THIS PIECE    FLUE PIPE IS OPTIONAL        mm 1                         INTAKE PIPE  3  MIN    48  MAX       Canadian installations  See  Canadian Applications Only  on page 7    Figure 15    506185 01       Issue 0938    Do not cement air intake into the connector on burner  box  Use high temperature RTV silicone sealant so  intake pipe can be removed if service is required     In horizontal venting applications  the vent and air intake  pipe must be installed on the same side of the house  within the parameters shown in Figure 15     Horizontal Direct Vent     Vertical Venting   CG90TB  CG92TB  amp  CG95TB Only   6 5  Min  24  Max    Height to  provide 12    clearance  to average  snow level    Airflow Right to Left    Vent Pipe            Air Intake Pipe    See table f
67. y a ground stake or buried steel pipe  must be  maintained for proper operation     Filters   Filters are not supplied with these furnaces since filters are  commonly located behind a return grille for ease of servicing   It sthe installer s responsibility to install properly sized filters  in accordance with Table 3 on page 24     Page 24 of 36       Issue 0938        Minimum Filter Requirements    i i i in  Size  Descriptor t LE S  an  Lom pes Toe res   o  ae fare  af  L      p sepas  2  29 pes   T   Lm oe pes   a pes 5     1  The Airflow Descriptor is the two digits following the  D  in the  model number     2  Areas and dimensions shown for cleanable filters are based  on filters rated at 600 feet per minute face velocity     3   Typicalfilter sizes are shown  however  any combination of filters  whose area equals or exceeds the minimum area shown is  satisfactory     Table 3    Filter Rack Installation    Filter Rack Mounting Hole  T d age  Screw       Filter Rack    Front of Cabinet Corner Embossments    Figure 36    Bottom Filter Location  Upflow Models       Filter       Figure 37    506185 01    Thermostat   Install a room thermostat according to the instructions  furnished with it  Select a location on an inside wall that is  not subject to drafts  direct sunshine  or other heat sources   The initial heat anticipator setting should be equal to the  total current draw of the control circuit     Low voltage thermostat connections are to be made to the  integrated igni
68. zes  the R G circuit of the control  causing the fan to be de   energized immediately     Cooling   During a call for cooling  the thermostat energizes the R Y  circuit of the control board  After a 1 second cooling    on    delay   the control energizes the cooling fan speed  If the fan is already  energized  it remains running and does not de energize for  the 1 second cooling fan    on    delay     The call for cooling has priority over continuous fan operation  while a call for heating has priority over both a call for cooling  or continuous fan  Ignition lockouts for any reason do not  affect cooling operation     506185 01    Issue 0938    As cooling demand is met  the thermostat de energizes the  R Y circuit of the control board  After a 60 second cooling   off  delay  the control de energizes the cooling speed fan   At the end of the cooling  off  delay period  the control returns  to the standby mode     Controls   Following is a description of the operation of some of the  controls used in this furnace  All models use one of each  control  except as noted     Pressure Switch   The pressure switch is a normally open switch that monitors  combustion air flow  Inadequate air flow resulting from  excessive venting system restriction or a failed combustion  blower will cause the switch to remain open     Rollout Switch   The rollout switch is a normally closed switch that opens when  abnormal temperatures exist in the burner area  This can be  caused by a restricted heat
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
ASUS (ME302C) User's Manual    取扱説明書    Copyright © All rights reserved. 
   Failed to retrieve file