Home
Genius Modular Redundancy for Fire and Gas Applications, c
Contents
1. PLC Fault System Fault Display VOFaut O Fei l O Fault Display Fault 1 Fault 3 Fault 4 LampTest S Q 1 Buzze On Timer p R Q Tone OnTimer Mute R Q Reset T On Timer Detector Supply I On Timer Extended Reset Lo V On Timer Latch Reset HMI Remote System Interface Optionally Series 90 70 PLC Ethernet Modules could be used to facilitate the interface to an HMI system e g CIMPLICITY HMI or a remote system e g DCS system Alternatives for remote system interfacing include Genius Bus and other GE Fanuc Series 90 70 communication modules C 6 Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Output Configuration The extinguishant output for the example application is implemented using an H block output group This allows manual override and or manual release of the extinguishant output Independent indications are provided for these switches at the same time the individual signals are input to the GMR system via a non voted discrete I O block These inputs are used to prevent autotest faults from being reporting on this output when either of these controls are activated Extinguishant Output Bus A Manual Release Bus B Group Extinguishant Release Non Voted Discrete I
2. Input Units 1 6 Interfaces to External Systems 1 7 IP 1 2 IR Logic Control System 1 6 Logic Unit Maintenance Logic Units 3 6 MAC 1 2 Maintenance 4 1 MAE N O NFPA 72 NFPA 85 O Operation Index 1 Index Output Configurations Options 2 4 Output Unit Maintenance 4 4 Output Units 1 8 3 6 P PFD 12 5 2 5 4 PFD Calculations B 1 Power Supply 3 3 Probability to Fail on Demand Processor Configurations Options 2 2 Proof Test Interval 1 9 Redundant sensors 3 4 Reliability and Availability 1 8 Response Time S Sensor Maintenance 4 3 Sensors Series 90 70 PLC 3 1 L2 System Architecture 3 2 System Inputs 3 4 T Terms and Abbreviations 1 2 TUV 2 1 Index 2 Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A
3. Introduction This document describes the requirements for Fire and Gas Systems based on E E PE systems It explains how Genius Modular Redundancy GMR can be applied to produce Fire and Gas Systems that conform with the requirements of IEC 61508 Additional important information is provided in the GMR User Manual GFK 1277B Assessment of the Genius Modular Redundancy system by T V Rheinland has been completed in accordance with IEC 61508 for a range of system configurations capable of meeting up to SIL3 requirements for both Fire and Gas and Emergency Shutdown applications This assessment continues to build upon GE Fanuc s proven product manufacturing capabilities and Silvertech s experience in Fire and Gas applications This chapter provides background information about Fire and Gas Systems their components and performance requirements Later chapters highlight the issues of and configurations for creating Fire and Gas Systems using GMR The appendices provide the information necessary to calculate individual Probability to Fail on Demand for each safety function an example application and information concerned with the configuration of Fire and Gas Systems 1 1 1 2 Terms and Abbreviations 1001 1oo1d 1002 1002d 2002 2003 DCS E E PE ESD F amp G GBC GMR HHM HMI HSB HVAC 1 0 Genius Modular Redundancy for Fire and Gas Applications September 1999 One out of One Voting One out of One Voting with 2 0 Degradatio
4. GE Fanuc Automation Programmable Control Products Genius Modular Redundancy for Fire and Gas Applications GFK 1649A September 1999 GFL 002 Warnings Cautions and Notes as Used in this Publication Warning notices are used in this publication to emphasize that hazardous voltages currents temperatures or other conditions that could cause personal injury exist in this equipment or may be associated with its use In situations where inattention could cause either personal injury or damage to equipment a Warning notice is used Caution notices are used where equipment might be damaged if care is not taken Note Notes merely call attention to information that is especially significant to understanding and operating the equipment This document is based on information available at the time of its publication While efforts have been made to be accurate the information contained herein does not purport to cover all details or variations in hardware or software nor to provide for every possible contingency in connection with installation operation or maintenance Features may be described herein which are not present in all hardware and software systems GE Fanuc Automation assumes no obligation of notice to holders of this document with respect to changes subsequently made GE Fanuc Automation makes no representation or warranty expressed implied or statutory with respect to and assumes no responsibility for the accuracy c
5. lt lt RUNG 12 gt gt 4 T CALL FILTER1 SUBROUTINE T00003 B001 BOO1 INP OUT AL1 OP WOO1 W001 CONST ON CNT CNT1 AL 0003 WOO1 NONE CONST OFF Y3t 0008 specececececemm Ladder Logic from the Example Filter Block The logic from the filter block is shown below lt lt RUNG 3 gt gt INP 01 OUT 01 MOVE_ INT CONST IN Q CNT 01 00000 LEN 00001 T lt lt RUNG 4 gt gt INP 01 OUT 01 e pee 9 MOVE_ INT OFF 01 IN Q CNT 01 LEN 00001 pee lt lt RUNG 5 gt gt INP 01 OUT 01 J ADD GT INT INT CNT 01 I1 Q CNT 01 CNT 01 I1 Qe CONST 12 ON 001 12 OFF O1 00001 lt lt RUNG 6 gt gt INP 01 OUT 01 quee n t SUB LEO INT INT CNT 01 I1 Q CNT 01 CNT 01 4I1 Qs CONST 12 CONST I2 00001 00000 t OUT 01 MOVE 4 S IN Q CNT 01 LEN 00001 OUT 01 R Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Appendix D TUV Guidance for Fire and Gas Systems This section describes t
6. 1 GMR Fire and Gas System Configurations 2 2 Processor Configuration Options esses enne enne nnne nnne 2 2 Input Configuration Options essen nennen nennen nennen nere nennen nennen 2 3 Output ContiPuration Options 5 5 2 2 c poti ioco cose Sueco se uero esie DER o eai ge Loo d eS To Uo eR ete pa 2 4 Application Design P 3 1 Software Lifecycle Techniques And Methods seeeeee 3 1 Application Design Principles eeeeeeeeeeeeeeeeenen eene ener nnn 3 2 System Architeeture ede ette obe eU ete EL e e ee EUREN UE EET e EE YE PURI et Te e tee u on dn 3 2 Environmbefit 2 5 2 alk anne ens We eee RET RT Rest er rr repere er E rS 3 3 Power Supply ascceccen eorr cerunt on er ce e ceu ce ur un UD M Unc MMC 3 3 Genius Buses cioe lUe LUN DIDI UCM EA 3 4 SETISOFS oor ise et tbe Hee Pese e bod eere ER ebbe PER Ee BERN Ebo E REPE REB Ebo ELE REP ERR EOS ER ee 3 4 System Inputs reto ot titii tip 3 4 Lo81C UIS i00 ette et let lette Debe fee Lebe eke tabi Seka te Fete babe fete obo Fete bee FL EP N ELM E np ere 3 6 ZAmnunclatioDs teo eR PEERS RV etse meteo 3 6 Output DIa TRENE E oe hates violated ioter s tore cock saci iectosc Locos ioo os eie Ges SMS ce 3 6 Operation and Maintenance crece eene eee eee eee eee teens aee eese teet etas sa sese ee 4 1 Dico la AAAA AARAA AARAA AAAA AAAA AAAA 4 2 Maintenance sann naaar EE 4 3 Sensor Maintenance ETE 4 3 Input Uni
7. 2 and SIL 3 rated applications dual Genius busses are required The details of these processor configurations are described in the GMR User Manual Processor Redundancy Expected Safety Function SIL Rating Duplex 1002 Triplex Simplex D 1001d Duplex 1002d The voting option designation 1oo2d implies voting 200221001 Default Action Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Input Configuration Options GFK 1649A The following input configuration options meet the SIL ratings indicated if the associated detector reliability meets the PFD requirement for that SIL level Under IEC61508 for SIL 3 requirements simplex detector redundancy is not permitted for type B components with a safe failure fraction below 99 In the table below digital input units are assumed to be two state signals and include Genius tri state Analog inputs are more than two state signal inputs See Appendix D for information concerning configuration requirements for Fire and Gas applications The table shows the application voting required for a given sensor configuration The data presented to the application is voted by GMR where duplex or triplex input unit redundancy is used GMR voting offers 1002 1oo2d and 2003 for digital input and Mid Value Select High Low and Average for analog inputs For Fire and gas applications it is assumed that application voting is performed on the alarm signals produc
8. 2B A Y tet se BAppMTTR 2B py E umm PFD Formula 2002 t Ae Serre o arra D D D DE PED yg 2Apt PFD Formula 1002d Ay 4 MTTR ny A 5 MTTR fy DE Apu ue App Ay mE MTTR ny A 5 MTTR i DE T Apu App Asp T PFD yg 20 z 2B Apu 2B Any m I B Asp Yor tsp E AS MTTR 2 B 4 umm Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A GFK 1649A PFD Formula 2003 DE nv 7 verre 7o MTIR AD Ay D t Ai T L MTIR Ao MTTR Ay 3 A SE D D T PFD yo 21 28 1 28 4 1 B Au Ay Mtoe tge BAS MTTR 20A amp rra Genius Input PFD The worst case PFD for various Genius input configurations per channel are shown below The calculations assume the probability of failure of the I O power supply is at least a magnitude better than path for the arrangement under consideration Configuration PFD Comment Per Channel 68040 Dupex lood L34xI Duplex 1002 13540 o O 13ed J ooo O Series 90 70 Logic Unit PFD The worst case PFD for Series 90 70 Logic Units are shown below The calculations assume that only 10 of rack PSU failures are fail to danger Configuration PFD Comment Per Path Simplex Configuration is 9 Slot Rack PSU CPU and Simplex GBC Voting occurs in output block SimplexD 8 24x10 Configuration is 9 Slot Rack PSU CPU and Duplex GBC Voting occurs i
9. be considered for such factors as temperature shock vibration EMC and dust water The Series 90 70 PLC and Genius equipment are designed and rated for the wide range of industrial environments Special measures are not normally required Note that if CPU model IC697CPM790 is used fan kit IC697ACC721 for AC or IC697ACC724 for DC should be installed for cooling where the ambient temperature may exceed 40 C Protection against particle water infiltration and mechanical damage are provided by mounting the equipment in suitable IP rated cabinets Where high shock and vibration levels are expected for example marine based applications anti vibration mounts can be used on the cabinets The EMC rating of the equipment is suitable for industrial environments when it is installed in accordance with GE Fanuc s installation instructions Power Supply GFK 1649A In accordance with EN54 Fire Detection and Fire Alarm Systems the power source for a Fire and Gas System should incorporate battery backup so system detection is retained if the power supply fails The power supplied to the Fire and Gas System can be DC or AC from suitable inverters Where AC power is supplied two or more independent feeds should be provided The state of the power sources and battery backup should be monitored and reported Most of the I O devices and I O units used in Fire and Gas Systems are low voltage and DC operated The GMR system requires close matching lt
10. by maintaining the discrete input active or it can be done by providing a control input to act upon the system logic The system should indicate report if an inhibit is active The system should incorporate measures to rapidly remove inhibits on critical inputs under operator control for example by means of a remove all inhibits keyswitch This function is particularly important where software based inhibits are used Forcing I O at the Genius block is only recommended for non commissioned loops because such forces cannot easily be removed by operator command on a system basis Intrinsically Safe I S circuits must be adequately separated from non LS circuits in the hazardous environment in accordance with the separation requirements laid down by the IS and IS Installation standards Note that the PDF calculations described in Appendix B do not include I S circuits this additional hardware with its associated MTBF figures will change the results of PFD calculations GFK 1649A Chapter 3 Application Design 3 5 3 6 Logic Units AC powered redundant logic units should be powered from separate power sources so that loss of a power supply would only affect one processor The Series 90 70 PLC can tolerate a 20mS interruption in its supply A fast switch to an alternate supply can maintain full system operation if the primary power supply fails In determining the system response time the interaction of the Genius bus and CPU swee
11. designed developed and released into the marketplace using these processes and procedures The product has been independently inspected and approved by TUV Rheinland to a number of recognized standards as noted in chapter 1 The GMR system is based upon field proven Series 90 70 PLCs and Genius I O blocks The installed base is in excess of tens of thousands of PLC CPUS and several hundred thousand Genius blocks Building on these proven components GE Fanuc and Silvertech jointly developed the design concepts for the GMR system The system design and implementation followed the principles and ideals set out in IEC61508 GFK 1649A 3 1 3 2 Application Design Principles As required by IEC61508 a Fire and Gas System design must consider the complete safety lifecycle GMR based Fire and Gas Systems should be designed and implemented by skilled practitioners who are knowledgeable in the theory of operation of the GMR system and its components To implement a Fire and Gas System using GMR the following system design principals should be observed Some of these principles are generic to Fire and Gas SysGas Systems others are specific to GMR System Architecture A well designed Fire and Gas System achieves a balance between the PFD Probability of Failure on Demand and spurious trip rate Simple configurations may achieve the required performance target for one of these parameters at the expense of the other However over specification c
12. on Demand For outputs with a high SIL requirement 16 channel Genius DC discrete output blocks should be considered These blocks no load detection and pulse test capabilities provide a high level of diagnostic coverage for the output actuator and associated field wiring Output points on these blocks are rated for 2 Amp duty with a high surge capacity The block rating of 16 Amp total load current should not be exceeded on a continuous basis The 8 point Genius AC discrete block provides a no load diagnostic of the state of the output load Output points are rated for a 2 Amp with a high surge capacity The block rating of 15 Amp total Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A load current should not be exceeded and the leakage current should not cause any problem with low powered loads For annunciation purposes and low power load ratings 32 point Genius DC blocks may be suitable The block diagnostic capabilities provide detection of field wiring faults Output point rating is 0 5 Amp per channel and 16 Amps per block If No load reporting is enabled on 16 point DC blocks the minimum load for an H block group is 100mA for an I block group it is 50mA The appropriate normal state for the load On or Off must be configured for H T block and I block output groups For the I block configuration to avoid unnecessary shutdowns control actions during maintenance activities some way of maintai
13. output redundancy is required however the GMR system provides the I block loold as an alternatives to the H block Input Configurations The example Fire amp Gas application requires full line monitoring for open and short circuit faults on input devices The sensors used are two state devices i e normal and alarm Because Genius 16 point tri state input blocks can only detect one of these faults at a time the example instead uses analog inputs to interface to the sensors Thus the input signals to the GMR system are analog not discrete Because the GMR software provides signal voting but not alarm level processing that function must be included in the application program logic To illustrate interfacing discrete sensors consider a convention ionization smoke detector A simplified equivalent circuit of a smoke detector is shown below Typical Smoke Detector Equivalent Circuit HI Sensor Conditioning amp Amplifier LO GFK 1649A Appendix C An Example System C 3 C 4 These sensors generally require a minimum operating voltage of 18V To operate a remote indicating LED requires a source impedance capable of delivering 20mA or more The detector draws about 50p A in the non alarm state and will sink 60mA with a standoff voltage of 6V in the alarm state Several detectors can be placed on a single input loop for greater coverage however there will be a loss of dis
14. provide alternative protection during the period any inhibits are active TUV Rheinland has provided a number of recommendations re printed in GFK 1277B Genius Modular Redundancy User s Manual Appendix B concerning procedural and other measures including checklists pertaining to the use of maintenance overrides Fire and Gas Systems are normally multi sensor with no input unit redundancy dual processors and de energized outputs voting 1002 Such system can normally be easily maintained without inhibiting the system The maintenance actions required for a Fire amp Gas System that is in service typically include E Replacing a defective unit such as a sensor input unit processor unit output unit or actuator W Handling an abnormal facility plant operating condition for example arc welding deluge pump taken out of service B Upgrading the application software and or adding new units E Routine Proof Testing of each system safety function including field devices A GMR Fire amp Gas System can accommodate maintenance actions as described below Sensor Maintenance The system must allow isolating and inhibiting of the input signal It should be possible to remove inhibits on critical inputs upon operator command Input Unit Maintenance GFK 1649A GMR adapts input voting of a redundant input group if a block in the group is removed or powered down Make sure that removing an input unit does not cause undesired outputs to
15. such as watchdog timers to bring the system to a pre determined state in the event of erroneous logic program operation Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Annunciation Fire and Gas Systems often include both display panels and or computer generated displays to alert operators to problems The display normally indicates the plant or process areas and the presence absence of hazardous conditions The display can also indicate faults with the field devices or the control system Indicators such as LEDs or lamps may flash or stay on The operator interface usually includes controls to inhibit detection disable or permit automatic actions initiate manual actions and acknowledge hazards Computer generated displays can provide more information about alarm conditions and a greater degree of operator interaction with the system They can also generate electronic or printed reports of alarms faults inhibits overrides trips and other significant events Audible Alarms The low incidence of hazards in a well designed and operated plant usually means the operator s attention will have to be drawn to a potentially hazardous situation This is normally done with an audible signal such as a buzzer The operator can turn off the signal when responding to the problem Some systems use different sounds to identify different types of hazards In addition Fire and Gas Systems often control plant wide au
16. the modules is controlled by the power switch on the Series 90 70 power supply module To replace the power supply itself requires an isolation switch in the power feed to the power supply module It is recommended that individual Genius I O blocks be de powered for replacement Follow the instructions in GFK 1277 Genius Modular Redundancy User s Manual revision A or later for block power isolation Chapter 3 Application Design 3 3 3 4 With careful system design and selection of appropriate I O configuration replacement of faulty units will not affect system operation Genius Bus Sensors The Genius bus must be connected so as to permit addition or removal of a Genius I O block or Bus Controller on the bus without affecting integrity of the bus connections When installing the bus cable the Shield In Shield Out connections must be made to the correct terminals and Serial 1 2 must not be swapped from device to device Rules for topology cable type length and baud rate must be adhered to Sensors must be located according to the manufacturer s recommendations and the guidance provided in BS 5345 IEC 79 10 Codes Of Practice Relating To The Selection Installation And Maintenance Of Electrical Equipment For Use In Hazardous Areas Suitable weatherproof fixings mountings must be used where the sensor is located in exposed positions Sensors must be accessible for maintenance and testing For example it may be necessary for gas
17. to activate Its operation is independent of the GMR system and has priority over manual override The status of this switch is monitored by the GMR system for autotest reporting purposes System fault LED CF O P Indicates entry in PLC fault table entry I O fault LED CF O P Indicates field fault or I O fault table entry Buzzer CF O P Activates two tone sounder Tone CF O P Two tone sounder High tone has priority and indicates single confirmed fire low tone indicates system or I O fault Reset P B CF UP Resets latching detectors and attempts to clear input fault and alarm latches During this time system outputs do not change until it is certain that there are no standing alarms This ensures that devices activated by the alarm condition are not turned off then back on again Mute P B CF UP Silences audible In addition the common facilities implements the control logic to handle resetting the detector i e Detector Reset and alarm level processing logic i e Extended Reset and Latch Reset GFK 1649A Appendix C An Example System Common Facilities Logic The common facilities logic is shown below Trip Trip Output Overide Override Zone Inhibit Q Zone Inhibit Confirmed Fire Confirmed Fire Display Confrmed Fire QU Incipient Fire Single Fire Display R R
18. 5 of the Genius block power supplies to assure correct operation To minimize the problem of matching tracking supply voltages an AC powered GMR based Fire and Gas System should use a high integrity DC distribution bus bar supply based on a M N arrangement see below This is done by combining the outputs of the power supplies through suitable blocking diodes The blocking diodes prevent internal faults within a supply from affecting the bus bar The base number of supplies required M is determined by calculating the load demand and dividing the load demand by the individual power supply capacity To accommodate individual supply failures an additional N units are added The design and calculation must accommodate the loss of one of the AC supplies A simple technique to avoid excessive numbers of power supplies is to share the load equally on the AC feeds and provide a fast switchover to an alternate supply in the event of a loss of a supply feed The system must monitor each of the supplies to check that its output remains within limits and to warn of failures Power wiring must meet with the requirements of control equipment Wire capacity and wire color AC DC segregation temperature rating MCB fusing etc should be in accordance with internationally recognized standards Fuse and MCB trip must be reported to the system for annunciation purposes Hot insertion removal of Series 90 70 PLC equipment is not recommended Power to
19. 97BBA020 The Rim was 5600hms and Rsense was 2500hms Rpap and FUSE were not used In this example for a 24VDC supply rail the maximum loop current is 29mA and the maximum input voltage is 7 4V For the heat detector interface the internal current sense resistor was not connected and an single external resistor used For the smoke detector the internal 250 Ohms sense resistor was used The input range for all channels was selected to be 0 10V The scaling factor of the channels was set to 0 3071 corresponding to 0 30000 The effect of which is to give an output reading in HA The Genius block signal fault detection was disabled as this is being handled by the application logic Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A F amp G circuits often need explosion hazards protection the most common form of which uses Intrinsic Safety techniques Barriers have a safety description that defines the maximum voltage and current that can be delivered to the field A typical barrier safety description for a smoke detector would be 28V and 93mA The input signal in this example is ground referred so it would be necessary to use either a dual zener barrier or an isolation barrier Smoke detectors latch in the alarm state until power is removed Therefore some means of removing power is required In this example a single output of the common facilities discrete I O block has been used to remove power to the smoke detect
20. FD Configuration PFD Configuration PFD Simplex 6 81x10 0 Simplex 7 11x10 Simplex 6 81x10 Simplex 6 81x10 Duplex 1002 1 63x10 5 Simplex 6 81x10 0 Simplex 6 81x10 Duplex 1oo2d 1 71x10 Simplex 6 81x10 0 Simplex 6 81x10 Triplex 2003 2 19x10 Simplex 6 81x10 0 Duplex 1002d 1 34x10 06 SimplexD 824x104 I Block 1oold 1 34x10 06 Duplex 1002d 1 34x10 06 Duplex 1002d 1 63x10 gt I Block loold 1 34x10 06 Duplex 1002d 1 34x10 06 Duplex 1002d 1 63x10 95 H block 1002d 1 35x10 96 Simplex 6 81x10 SimplexD 824x10 I Block 1oold 1 34x10 6 Duplex 1002 1 35x10 96 SimplexD 824x104 I Block loold 1 34x10 06 Duplex 1002 1 35x10 96 Duplex 1002 1 71x10 9 I Block loold 1 34x10 96 Duplex 1002 1 35x10 06 Duplex 1002 171x109 H Block 1002d 1 35x10 06 Simplex 6 81x10 7 SimplexD 824x10 I Block loold 1 34x10 6 Triplex 2003 1 36x10 06 Triplex 2003 2 19x10 9 I Block 1oold 1 34x10 06 Triplex 2003 1 36x 1006 Triplex 2003 2 19x 10 H Block 1002d 1 3 5x10 Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Appendix C GFK 1649A An Example System This section describes a simple example of a Fire and Gas System to illustrate how the GMR system can be applied The example includes Single Heat sensor with system inhibit 2003 voting Smoke sensor group with system inhibit and detector reset Triplex Processors H Block 1002d Extin
21. GMR system builds upon the extensive diagnostic features of the Series 90 70 PLC These diagnostic features facilitate straight forward maintenance of a GMR Fire and Gas System These diagnostic features include W I O Fault Table identifies module faults and field faults with locating reference and online help B CPU Fault Table identifies system faults with locating reference and online help WI System Status References flags indicating system status e g any force present E Fault locating references these indicate fault status to an I O channel level In addition to these features the GMR executive software adds the following diagnostics capabilities Fault reporting module this is a user accessible program block that can be used to access specific fault data GMR fault table messages the executive software logs a number of messages to the fault tables GMR system status bit references these provide status on such points as autotest PLCs online etc Full details of these standard features can be found in the GE Fanuc Series 90 70 Genius I O block and GMR User Manuals Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Maintenance The maintenance of a system requires that no unintended changes in state occur when performing a maintenance action If possible the system should not be inhibited from responding to a demand If an inhibit is necessary appropriate measures must be taken to
22. O Block Manual L Release GFK 1649A Appendix C An Example System C 9 C 10 System Logic The complete system logic includes the application logic and the common facilities matrix logic for the system The following figure gives the simplified block diagram Inhibit Enable Confirmed Fire l l Inputs Application GMR Outputs l l 9 x 8 gE 8 Nc M9 3 g L 5 S Os mo lt Zone rt Inhibit 5 A Detector a 3 supply S F o J _ I ox Pe 2 E 9 oO 94 5 iz 2 Te 9 l 58 x o 5 3 a z o Lm N 5 o l l l l l l l i Logic l Mute i ER i 3 Q i Heat IBigekS aie 3 Q Trip 52 fixed temp ault I Ps 2 2509 i o rS S Smoke Output Reset L9 O ride 9i Detector Reset os z Q z a l Common Facilities gt l l Inhibit l I l l Silvertech has many years of experience in designing Fire and Gas applications using GMR and other GE Fanuc PLC s This knowledge has been captured in a library of software Function Blocks for Fire and Gas ESD and other safety related systems and process control systems Contact Silvertech International for further information Genius Modular Redundancy for Fire and Gas Applicati
23. a function of the number of months since the module was shipped The model was developed through field experience and makes the following assumptions e 90 of total months shipments are used 5 of shipments cover warranty returns 5 of shipments never go into use User stock etc 693 hours per operation month 95 of time Processes c CPU Memory continuous cycling T O holding or cycling MTBF calculations are based on one year 12 months accumulated run hours and warranty returns for a corresponding 12 month period To gain statistical validity each module type must have accumulated a minimum of 500 000 run hours during this 12 month period before a reliable prediction will be made MTBF and reliability are not calculated for modules with less than 500k run hours A 1 Appendix PFD Calculations b The following assumptions have been used for the basis of calculating the Probability to Fail on Demand as determined in EC61508 Functional Safety of Electrical Electronic Programmable Electronic Safety Related Systems To avoid excessive number of configurations the PFD calculations have been made by computing individual sub system PFD based on the worst case channel path reliability figures within the sub system for the specified configuration By combining the PFD results of these sub systems the PFD of a safety function can be computed Standard Parameters Parameter Value Comment Proof Test Period T I
24. an action 1002D voting In addition to signaling the hazard the Fire and Gas outputs would also be de energized in the event of total Fire and Gas System failure This could provide a fail safe mechanism for a Fire and Gas System failure either by annunciation to allow operator action and or by automatically de energizing a signal to the Emergency Shutdown system GFK 1649A Chapter 1 Introduction 1 7 Output Units Actuators Output units convert signals from the logic control system and use them to control or actuate output devices Where logic controller redundancy is used output units normally perform the voting function They do that by combining information from two or more logic controllers to produce a single voted output signal An output unit generally includes diagnostic capabilities to report both internal faults and output faults such as open circuit short circuit or out of range An output unit can also indicate output status and permit manual control and testing of the output circuit actuator Output actuators provide control and protection for the plant Fire and Gas actuator outputs are usually digital Typical actuators include Solenoid Operated Valves for controlling ventilation dampers or extinguishers and indicators Certain outputs are normally energized so that failure of the Fire and Gas System causes automatic action Examples of normally energized outputs include fire dampers and a shutdown interface to an Emergency S
25. an lead to increased costs and result in an overly complex system with greater risk of configuration and maintenance induced errors A key design consideration is selecting the performance requirements of each safety function System performance must be viewed in the context of all safety measures System performance must also consider such contributing factors as detectors and actuators Fire amp Gas SysGas Systems are typically SIL1 or SIL2 rated systems however GMR is approved upto SIL3 rating The usual configuration of the executive control path of a typical Fire and Gas SysGas System is B Redundant simplex sensors with simplex input unit W High reliability simplex sensors with dual input unit redundancy voting 1002 B Dual Processors CPUs Normally de energized duplex 1002D voting simplex output block for initiating fire protection measures for example deluge CO2 systems and annunciation B Normally energized outputs voting 200221001 for signaling higher order safety systems for example ESD and other actuators that have a de energized safe state W Manual controls for override initiation of critical outputs acting upon the output signal This type of system is easily operated and maintained achieving the required PFD while avoiding an excessive spurious trip rate Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Environment The environment where the system will be installed must
26. change state due to pre existing discrepancies check PLC I O tables and system logic Also make sure that removing an input unit does not cause an unexpected output trip as a consequence of an I O shutdown check no pending I O shutdown and temporarily disable autotest After analyzing the effect of the removal of an input unit bypass any critical outputs that are expected to change state It should be possible to manually activate critical outputs that are inhibited by the removal of the unit Check that input units can be de powered and removed without electrically affecting the other redundant channels Take care to include the effects of power being fed through the field device The GMR termination input boards provide the necessary de coupling The GMR system adapts the input voting to ignore an input unit that has been removed from a voted input group so the system can still respond to a genuine plant alarm condition Restoring an input unit may require system Reset and or Force Logon before the unit can resume normal operation Chapter 4 Operation and Maintenance 4 3 4 4 Logic Unit Maintenance GE Fanuc recommends isolating power before removing modules Take care to consider the effects and bypass any outputs that are expected to change state where this is undesired The output block will adapt its voting to ignore a logic unit that is stopped or powered down Note that for Fire amp Gas Systems Simplex CPU Shutdown would no
27. cing a F amp G detector are E Loop operating current and voltages Explosion Hazards Protection Fault v Alarm signal detection margins Fault v Alarm timing detection margins Resetting of latching detectors GMR Application Voting GFK 1649A Appendix C An Example System C 5 C 6 Alarm Level Processing Logic Analog Inpu Short Circuit Trip Level COMP FILTER E iu Overcurrent Trip Level Alarm Trip Level VL I Fault FILTER e Eie nx FILTER b 1 d COMP COMP Extended Reset aope 4 Alarm Alarm Reset The block compares each analog input to fixed thresholds for open circuit alarm and short circuit The output of these comparisons is filtered with the open circuit and short circuit filters having a shorter leading time constant and longer falling time constant than the alarm filter This difference provides the discrimination to allow transition between states The output signals are latched in a resettable seal circuit These latches give priority to the set term the reset timing ensures that the logic stabilizes after power has been removed before an attempt is made to reset the latches Genius Modular Redundancy for Fire and Gas Application
28. crimination Typical NON I S Smoke Detector Loop Analog Interface To interface this detector to the system using analog interface requires that four discrete signal bands be defined corresponding to open circuit normal alarm and short circuit This can easily be accomplished using resistors Rumit 24V r eoo Fuse Reo Heap Voltage Input Dim module Rsense The elements of this interface are R mrr sets the short circuit current limits input voltage for the loop FUSE sets the short circuit current for the loop E n E Ryo sets the normal loop current E Rpap sets the short circuit current limits input voltage E Rsensg current sensing resistor sets the short circuit current With the detector in the quiescent state the combination of Reo RpAp and Rsense resistors sets the normal loop current A typical normal loop current is 4mA There must also be sufficient operating voltage for the detector typically 18v minimum With the detector tripped the loop current rises as determined by the combination of Vpgr atm Rumir Reap and Rsense A typical loop current with the detector in the alarm state is 25mA An open circuit or ground short will cause the input current seen at the system input to drop to zero A line to line short will either cause the input current to rise the maximum set by the resistor or if this exceeds the fuse rating zero The example uses a 6 channel analog input block IC6
29. ctors are usually located where they may be exposed to explosive gas air mixtures Appropriate measures should be taken to prevent ignition Such measures are described in BS 5345 IEC 79 10 amp 11 and in BS 5501 ENS0 015 EN50 020 Electrical Apparatus for Potentially Explosive Atmospheres Types of Fire and Gas Sensors The common sensors for detecting Fire and Gas hazards include Gas Combustible sensitive to combustible gases The three most common types are catalytic or pellistor electro chemical and IR absorption Gas Toxic sensitive to toxic gases e g hydrogen sulfide carbon monoxide dioxide etc The most common type is electro chemical Smoke sensitive to smoke particles The two most common types are ionization and optical detectors Heat sensitive to temperature The two most common types are rate of rise and fixed temperature detectors Flame detectors sensitive to the flames of a fire The most common type is IR Break glass or MAC simple switches Detector Interfaces to the Fire and Gas System In a Fire and Gas System detectors may be single devices multiple devices on a loop or multiple independently addressable devices on a loop Addressable devices on a loop are interfaced to a Fire and Gas System by a proprietary unit from the detector manufacturer This interface is usually external to the system as described later in this section Addressable schemes can localize a hazard to a single detector They provide re
30. dancy for Fire and Gas Applications September 1999 GFK 1649A Availability is the probability that a system will perform its intended function per unit time It can be calculated using the Mean Time To Repair MTTR and Mean Time Between Failures MTBF as follows Availability 1 MTTR MTBF where A 1 Industry practice is to assume a MTTR of 8 hours Diagnostic Coverage Diagnostic coverage is the ratio of revealed to unrevealed faults that will be detected by the internal diagnostic checks of the unit or system The diagnostic coverage of a Fire and Gas System as a low demand system is expected to be 90 or greater The time interval between diagnostic runs should be significantly less than the proof test interval to ensure correct operation of the system safety functions The usual time between diagnostic runs is 24 hours or less Demand Rate Demand rate is the probability of a demand being placed upon the system per unit time Fire and Gas Systems are low demand systems The expected demand rate for a Fire and Gas System is typically less than once per year per safety function Proof Test Interval Proof test interval is the number of hours between manual proof tests of each of the system s intended functions Testing must include the system detectors and actuators that are normally dominant in calculations of system reliability The proof test demonstrates correct system function and reveals dormant faults not detected by the
31. dible alarms to warn of hazards and protect personnel These audible alarms are normally accompanied by visual signals such as flashing rotating beacons Interfaces to External Systems A Fire and Gas System can exchange data with an external system over a communications link and or through the use of physical I O devices In distributed applications data can be shared among multiple Fire and Gas Systems and other safety systems A communications interface allows the transfer of system data and system control if enabled This type of communications interface is needed when the system includes a HMI display system or data logging capability The interface can be dedicated communications units or a direct link to the logic controller Typical examples of communications links are RS232 RS422 RS485 serial links running a variety of protocols and high performance links such as Ethernet Genius Modbus Plus ProfiBus etc Interfacing through physical I O can be done using standard I O units This type of interface is useful where no convenient communication link exists or no compatible communication protocol can be conveniently provided Physical I O interfaces can also be used to bypass and or trip the signals for maintenance or system test Sometimes a Fire and Gas System must interface with an ESD System That should be done using normally energized outputs which can set up so that the receiving system requires a trip on two outputs to initiate
32. duced wiring cost but increase the risk of common mode failure Addressable systems are usually restricted to lower risk areas such as the accommodation module in offshore installations Non addressable devices on a loop are interfaced to a Fire and Gas System by a digital or analog signal An analog interface can indicate line and detector faults by out of range readings It is possible to use conditioning components for digital type sensors to produce multiple signal states for varying field loop conditions such as open circuit short circuit and normal or tripped states Digital input configurations are available that can indicate the presence of a fault such as a ground fault as a trip condition A Genius block s tri state discrete input improves this by being able to report a field fault i e open wire or shorted wire while allowing the input to respond to a trip condition A number of detectors latch an alarm condition An example of this type of device is a smoke detector Detectors that latch an alarm condition must be de energized after a trip so that they can be reset and re armed If this is required it is important to be sure that protective measures already taken by the system are not removed without positive confirmation that the hazards are no longer present Chapter 1 Introduction 1 5 1 6 Barriers Input Units A barrier is a device that limits the amount of power present in a field circuit so that it cannot ignite an
33. ed by alarm processing the analog signal which is taken directly from the input reference tables for simplex input units or from the GMR voted data for duplex or triplex input unit redundancy The details of the GMR voting for these input configurations are described in the GMR User Manual Detector Safety Input Unit Minimum Minimum Expected Redundancy Function Type Input Number of Safety Voting Channels Inputs Units Function SIL per Detector Rating Simplex Analog Simplex Digital Analog Simplex Digital Analog 3 Duplex Digital 1 1 1 2 WINTN TR de Duplex Digital Analog Triplex or Digital Higher Analog WEN TM TN t2 GMR Voting must be set to 1002 This configuration is only permitted under IEC 61508 if it conforms with the requirements of IEC 61508 Part 2 Table 2 Architectural Constraints on Type A Safety Related sub systems and Table 3 Architectural Constraints on Type B Safety Related sub systems The voting option designation 1002d implies voting 2002 1001 Default Action Chapter 2 System Design 2 3 2 4 Output Configuration Options The following digital output configuration options meet the SIL ratings indicated shown if the actuator reliability meets the PFD requirement of that SIL level Since Fire and Gas Systems seldom include analog output safety functions these have not been included TUV carefully assessed the I block and H block configurations and confir
34. explosive gas air mixture The normal field signals carried by a barrier are small analog voltage 30V or current 100mA signals Two common types of barriers are safety barriers and isolation barriers Safety barriers are simple passive devices based upon zener diodes and resistors They do not require a power supply to operate Power to the field device is supplied from the protection system power supply and or input unit These devices require a reference potential for operation Isolation barriers are active electronic devices They perform power conversion and power limiting functions and may require a separate power source These devices do not require a reference potential for their operation If barriers are used they must be correctly rated for the application e g safety description voltage current resistance ratings cable properties etc and they must conform to any system certification requirements for the sensors Input units condition and convert the detector signal for transfer to the logic control unit Many types of signal conversion are available including analog to digital conversion analog level trip detection and detector excitation with amplification and conversion In some Fire and Gas Systems the input unit also indicates field conditions such as alarms signal values and faults and permits manual testing and inhibiting of the field signal Depending upon the system architecture input units can incorpora
35. groups Also output discrepancy reporting is only available with the Genius block in GMR mode It is important to make sure that the Genius I O block configuration selections for Redundancy Mode GMR Duplex Hot Standby or No Redundancy and Duplex Default On or Off are consistent with the output group type See GFK 1277 for detailed information on configuring Genius I O Blocks in output groups PFD calculations should also account for any additional output devices such as I S barriers and interposing relays GFK 1649A Chapter 3 Application Design 3 7 Chapter 4 GFK 1649A Operation and Maintenance The operation and maintenance of a Fire and Gas System requires consideration of the complete safety lifecycle The development of operation and maintenance procedures is the responsibility of operators maintainers It should be done by skilled practitioners who are knowledgeable in the application of Fire and Gas Systems The development of these procedures is outside the scope of this document However general information about generic and GMR specific Fire and Gas System operation and maintenance is given below CAUTION Maintenance on a live system requires careful planning adherence to operating and maintenance procedures and the appropriate permits and permissions These matters are the responsibility of the owner operator of the system and are outside the scope of this document 4 1 4 2 Overview The
36. guishant Output with manual overrides release Matrix Indications Common Facilities Interface to HMI and or Remote System The example does not cover the wider aspects of engineering a Fire and Gas System such as evaluating the system safety functions and SIL level s required to meet the safety functions Information about the principles and methodologies is contained in IEC61508 Other sections of this document provide information needed to determine the required system architecture for a given application It is further to be noted that to meet a given SIL rating in accordance with IEC61508 requires detailed evaluation of the complete lifecycle of the system as described in IEC61508 from conception through to de commissioning and covering all aspects of design operation and maintenance C 1 Example F amp G System Block Diagram Discrete I O L 00 8 Common Facilities e e e e Control Matrix Simplex Sensor z e Triplex s TELENGE Sensor 9 g Group e z e e e e e Analog Input Group E Tue H Block Application Logic The example F amp G system illustrates the basics of a simple F amp G system implemented using GMR The application logic is correspondingly simple and is shown in the figure below The application com
37. h faults by for example an earth leakage detection unit The system ground should be connected to earth unless otherwise required by the earth leakage measure If line monitoring is not used and no other special measures are applied then field wiring must be checked within or during the proof test The test interval for analog inputs as described in Appendix A of GFK 1227A shall be aligned with the proof test For each discrete input used with a safety related function the vote adapt mode i e 3 2 0 or 3 2 1 0 duplex default i e O or 1 and default state i e O or 1 must be set according to the safe state For each analog input used with a safety related function the vote adapt mode i e 3 2 0 or 3 2 1 0 duplex default i e high low or average and default state i e min max or hold must be set according to the safe state or demand state respectively Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Outputs For discrete output groups the normal state must be set to ON for outputs with a de energized safe state OFF for outputs with an energized safe state Critical normally de energized outputs should be located on 16 point H block with no load reporting enabled Output loads that fall below the minimum required 100mA load current should include an additional resistive load in the field to fulfill the minimum load requirement Definitions Fire amp Gas System These types of
38. he changes to the GMR Configuration Utility from those described in GFK 1277B and TUV conditions relevant to Fire and Gas applications A list of the certified components for use in GMR systems is maintained by GE Fanuc and regularly verified by TUV in the TUV Change Log It is available online at www gefanuc com Configuration Utility GFK 1649A Version 7 01 of the configuration utility introduces a new configuration option from that described in GFK 1277B for output discrepancy filtering Configuration Update Configurations created with previous versions of the configuration utility should be imported into the latest version and saved to a new file The configuration should then be carefully checked to confirm that all settings are identical to the original version and where new configuration options have been introduced the default settings are appropriate for the application Output Discrepancy Filter The output discrepancy filter is found under S ystem D iscrepancy Filter The dialog box is shown below Input Filter seconds Output Filter seconds The output discrepancy filter can be set to increase the time interval needed to detect an output discrepancy This time defaults to 0 seconds Configuration Settings for Fire and Gas The following specific settings are recommended for Fire and Gas applications M The normal state for redundant outputs must be set to OFF check box clear for normally de energized outpu
39. hutdown System On a Fire amp Gas System outputs for which failure is undesirable should be de energized Examples include extinguisher systems Deluge CO Halon systems and outputs to annunciation devices Critical system outputs such as extinguishant release outputs permit manual initiation independent of the Fire and Gas System This is sometimes described as a diverse path Performance Typical performance figures for a Fire and Gas System are detailed below Response Time The system executive action response time not including field devices is normally less than 1 second and should not exceed 2 seconds Note that some types of detector have detection times of 10 seconds or more Reliability and Availability Reliability is the probability that a component will fail to perform its intended function per unit time System reliability is calculated on a loop function basis using the individual failure rates of the components of the loop A loop comprises the units and devices necessary for the intended function taking account of any redundancy from input to output for the executive path Including all field devices If the failure of one component will result in the failure of the path the reliability of path is N 2 MTBF where A 1 Calculation for other levels of redundancy is described in Functional Safety of Electrical Electronic Programmable Electronic Safety Related Systems IEC61508 Genius Modular Redun
40. is intended to detect and annunciate Fire and or Gas hazards at the earliest possible time and to automatically initiate protective measures Although primarily a physical measure a Fire and Gas System requires procedural measures to ensure its effectiveness Components of a Fire and Gas System A Fire and Gas System is mainly concerned with detection annunciation and mitigation of fire and or gas hazards It must perform this function without itself creating further hazards Fire and Gas Systems typically have the following basic components and sub systems Each of these components sub systems is described on the following pages Detectors Barriers Input Units Logic Control System Annunciation Displays Audible Alarms Manual Controls Interface to other safety systems Output Units Actuators 1 4 Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Detectors GFK 1649A Detectors are placed in areas or zones where a fire or gas hazard may exist The document BS 5345 IEC 79 10 Codes of Practice Relating to the Selection Installation and Maintenance of Electrical Equipment for use in Hazardous Areas provides guidance on the placement of detectors Using several detectors of the same type in an area provides protection against device failure Combining the outputs of a group of detectors protects against spurious system response due to a fault in the detector or communications line Dete
41. med that these configurations correspond to the industry designations of 1oold and 1002d respectively on an individual channel basis Accordingly they are shown in the tables for completeness The details of the simplex I block and H block output configurations are described in the GMR User s Manual Actuator Safety Output Configuration Expected Redundancy Function per actuator Safety Voting Function SIL Rating Duplex or Higher 1002 Simplex L block loold 3 H block 1002d The voting option designation 1oo2d implies voting 200221001 Default Action This configuration is only permitted under IEC 61508 if it conforms with the requirements of IEC 61508 Part 2 Table 2 Architectural Constraints on Type A Safety Related sub systems and Table 3 Architectural Constraints on Type B Safety Related sub systems Output signals must be on different output units The corresponding safe state for these options is shown below Output Configuration Energized Simplex H block 1 oo2d Simplex I block 1001d H block 1002d The voting option designation 1oo2d implies voting 200221001 Default Action Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Chapter Application Design 3 Software Lifecycle Techniques And Methods GE Fanuc and Silvertech are ISO9001 accredited companies with declared design and development processes and procedures The existing GMR system has successfully been
42. ms using industry standard communication modules B Genius I O units with extensive diagnostic and voting features For more information about GMR refer to GFK 1277B Genius Modular Redundancy Users Manual and GFT 177 Genius Modular Redundancy Technical Guide 2 1 2 2 GMR Fire and Gas System Configurations Several GMR configurations can be used for Fire and Gas Systems The sections below list these configurations for each sub system together with their expected achievable SIL ratings in an application The SIL rating achieved for a safety function can only be determined by a complete analysis of the loop including the input and output field devices IEC61508 permits including a lower SIL function in a higher SIL rated system if there is adequate separation of the safety functions and if system operation and maintenance are based on the highest SIL rating Processor Configuration Options The extensive diagnostics of the GMR CPU family have been examined by T V The designation Simplex D describes a single CPU with dual Genius Bus Controllers providing two paths to shutdown the output via either an I block 1001D output group or an H block 1002D output group For SIL 2 rated systems the minimum redundancy requirement is a simplex D or duplex voting 1oo2d in the output blocks CPU For SIL 3 rated applications the minimum redundancy requirement is duplex voting 1002 in the output blocks or triplex processor redundancy For both SIL
43. n One out of Two Voting One out of Two Voting with 2 0 1 Degradation Two out of Two Voting Two out of Three Voting Distributed Control System Electrical Electronic and Programmable Electronic Emergency Shutdown Fire and Gas Genius Bus Controller Genius Modular Redundancy Hand Held Monitor Human Machine Interface Hot Standby Heating Ventilation and Air Conditioning Input Output Ingress Protection Infra Red Manual Alarm Call Point Miniature Circuit Breaker Mean Time Between Failures Mean Time To Repair Normally Closed Normally Open Probability of Failure on Demand Safety Integrity Level GFK 1649A References Standards IEC61508 DIN VDE 0801 DIN VDE 19250 Functional Safety of Electrical Electronic Programmable Electronic Safety Related Systems Principles for Computers in Safety Related Systems Fundamental Aspects to be Considered for Measurement and Control Equipment EN 50178 Electrical Equipment to be used in Electrical Power Installations and their assembly into Electrical Power Installations DIN VDE 0116 Electrical Equipment for Furnaces NFPA 72 National Fire Protection Association Part 72 Fire Suppression Systems NFPA 85 01 National Fire Protection Association Part 85 01 standard for the prevention of Furnace explosions implosions in single burner boilers NFPA 85 02 National Fire Protection Association Part 85 02 standard for the prevention of Furnace explosions implosions in multiple
44. n correctly control the load If in doubt set the outputs to a designated state using the bypass inhibit facilities Output bypass inhibit is required for I block maintenance to prevent spurious tripping of energized outputs during block removal Actuator Maintenance For manual proof testing of the output device lamps should be illuminated audible alarms sounded and mechanical acting devices set to travel and return to the rest position Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Appendix A GFK 1649A Reliability Data Calculation of system reliability and availability as well as safety function PFD and spurious trip rates requires module specific reliability data GE Fanuc has a well established procedure for determining module reliability data This data is available on request from GE Fanuc GE Fanuc calculates failure rate based on modules returned in warranty Factory tests are performed on returned modules The results place returned modules in one of three categories e No Defect Customer Induced Failure Proven Product Failure Only proven product failures are included in the failure rate calculation Modules not tested are assumed to have the same ratio of proven defects as those for which test results are available Calculation of the number of in warranty operating hours for a given module type is based on a model that predicts the fraction of shipped modules operating as
45. n output block Duplex 1002d 1 63x10 5 Configuration is 9 Slot Rack PSU CPU and Duplex GBC Voting occurs in output block Duplex 1002 1 71x10 9 Configuration is 9 Slot Rack PSU CPU and Duplex GBC Voting occurs in output block Triplex 2 19x10 9 Configuration is 9 Slot Rack PSU CPU and Triplex GBC Voting occurs in output block Appendix B PFD Calculations B 3 Genius Output PFD The worst case PFD for various Genius output groups are shown below The calculations assume the probability of failure of the I O power supply is at least a magnitude better than path for the arrangement under consideration Configuration Comment per um Simplex 68b109 81x10 68b109 I Block loold 1 34x10 96 per 1002 H Block 1oo2d 1 35x10 6 Calculated per 1oo2d PFD Summary The following table provides a range of typical Fire and Gas subsystem configurations and indicates the worst case safety function PFD for each of these subsystems for the electronic control system only It is intended to provide a quick check cross reference for system designers Note that only the Logic Unit PFD is additive to the total PFD of each safety function under consideration The input and output PFD has to be re calculated including the field devices and associated control modules barriers with due consideration for environmental factors Genius Input 90 70 Logic Unit Genius Output Configuration P
46. ndustry accepted value Mean Time To Repair MTTR Repair within shift All GE Fanuc units incorporate extensive internal diagnostic Common cause design failures have been minimized through mature design and long service combined with a high degree of segregation between paths and modules Average probability of failure per hour A Module Specific Contact GE Fanuc for module reliability data Diagnostic Coverage DC Fraction of failures with common cause B Probability of dangerous failure per hour Ap culation Probability of undetected dangerous failure per see calculation hour Apu ulation Probability of detected dangerous failure per hour C Ano Device equivalent mean down time toe see calculation System equivalent mean down time tse see calculation Average probability of failure on demand PFDave see calculation GFK 1649A V ue depends on Arch ue depends on Architecture Va Value depends on Architecture a itecture Value depends on Architecture Value depends on Architecture Value depends on Architecture B 1 B 2 The formulas for calculating the PFD for various architectures have been taken or are based on those in IEC61508 as follows A A p Anu pp E Apu 1 pe A E PFD Formula 1001 tu Ape Se urri m ree D D PFD yg App Apy Mog PFD Formula 1002 toe Ae Se mre e Spe ree D D t EAE MTTR y on MTTR D D PFD yc 22 1 28 A 0
47. ning energized outputs active is needed during replacement of a block This can be done with bypass links For example on the GMR termination boards the unused connectors provide a convenient bypass access point For SIL2 and SIL 3 rated outputs the output autotest must be configured The GMR output autotest uses the block pulse test feature which is performed on all outputs of a block Pulse test can only be enabled or disabled on a per block basis The pulse test can activate small or high speed loads so it may be necessary to pre load the output or fit high inertia output relays e For 16 point blocks output pulses start at 1 mS and if the load current is below the no load threshold the block progressively increases the duration in several steps to approximately 18 mS as it searches for a load demand e For the 32 point blocks the pulse test is of a fixed duration approximately 1 mS Critical system outputs may be provided with manual bypass and trip capabilities with trip normally taking precedence over bypass The system should provide the ability to remove manual bypasses on critical outputs Outputs that have been bypassed must be annunciated Due to the asynchronous nature of GMR frequently changing outputs can exhibit phasing effects if the Genius block voting is either GMR or duplex For this reason frequently changing outputs should be voted using the Genius Hot Standby voting which is incompatible with H block and I block
48. ompleteness sufficiency or usefulness of the information contained herein No warranties of merchantability or fitness for purpose shall apply The following are trademarks of GE Fanuc Automation North America Inc Alarm Master GEnet PowerMotion Series Six CIMPLICITY Genius ProLoop Series Three PowerTRAC Helpmate PROMACRO VersaMax CIMPLICITY 90 ADS Logicmaster Series Five VersaPro CIMSTAR Modelmaster Series 90 VuMaster Field Control Motion Mate Series One Workmaster Copyright 1999 GE Fanuc Automation North America Inc All Rights Reserved Chapter 1 Chapter 2 Chapter 3 Chapter 4 GFK 1649A Contents NUMERO AUCH ON Me CM 1 1 scr Sacer M T 1 3 COVE VIC Wc esee seo eer ee Prove eee Boose rete hac et eeu b b etes atte cse ecu 1 4 Components of a Fire and Gas System essen eene 1 4 Bore up 1 5 Barriers eco eoe e UL Ant Metabo ete Contr tene Contr pene enin mM RI E 1 6 Input Uritsccuc coton ttem 1 6 Ixogic ControlSysteimn ce en RE RO es ee a Reg 1 6 Annunciation D 1 7 Audible Alarms 2 3 22 tH EE HEHERERERERE EHE HEREM MERE RE MERE HELE MERE kkkh 1 7 Interfaces to External Systems eesesessseeeeeeeeeeeeee eene n nere 1 7 Output Units 3 56 56 EEEE hate sh testet ah Cal Dos at teal steht as DM Sit EE 1 8 ACLUAEOFS err Heer nen nendmesc nene 1 8 Pertormance 4 ost ccm anm uM M M mM 1 8 System d BS ON PR tette ens MEM MEM EN 2
49. ons September 1999 GFK 1649A Ladder Listing Ladder Logic for the Alarm Processing Logic In the example logic below rungs 7 9 and 11 are the comparators for short circuit open circuit and alarm conditions respectively In each case the filter block is called to perform the operations described in the filter logic pseudo code in this case Analog 1 is the Heat Detector lt lt RUNG 7 gt gt 4 GT INT T00001 ANALOGTZCET OAA A R a eR eee e CONST 12 28000 4 lt lt RUNG 8 gt gt pg ag ao CALL FILTER1 SUBROUTINE T00001 B001 B001 INP OUT SC1_OP W001 W001 CONST ON CNT CNT1_SC 0003 W001 NONE CONST OFF Y34 0008 4 lt lt RUNG 9 gt gt LT_ INT T00002 ANALOGI CHIT QreL oececeuecenceeseoceeseeesceisepsrsceseus seris sees eise euserei C ye CONST 12 02000 4 lt lt RUNG 10 gt gt eee RUE 4 CALL FILTER1 SUBROUTINE T00002 B001 B001 INP OUT OC1_OP W001 wool CONST ON CNT CNT1 OC 0003 W001 NONE CONST OFF Y34 0008 lt lt RUNG 11 gt gt D gt 4 GT INT T00003 ANALOGlI HII Qke ee e 5c 0 00 045 69 oo coc oueecoueo ouo cocTESRESA Cs CONST 12 15000 4 GFK 1649A Appendix C An Example System C 11
50. or under operator control In a real application this function should also have some form of redundancy While power is removed the loop current drops to zero This situation must be handled by the application to avoid erroneous fault reports When interfacing two state detectors it is important to ensure that alarms and faults are correctly reported This requires adequate analog signal and timing margins For example a short circuit fault causes the input signal to traverse the alarm region so it is important that there be proper discrimination between stable and transient states In this example the heat sensor is subject to voting by GMR as a standard triplex analog input group The voted result is then subjected to the alarm logic processing Although the smoke sensors are a triplex group their inputs are individual signals that are not GMR voted The analog input signals are directly processed by the alarm processing logic Because these signals have been wired on the same blocks as the heat sensor signals in this example GMR performs a vote on the smoke signals However this data is not used in the application A side effect of this voting is that it would generate apparent voting discrepancies based on time differences in detecting a smoke hazard This would cause unnecessary fault table messages This can be avoided by setting the discrepancy thresholds for a channel to the limits of the input range In summary the issues for interfa
51. p times should be examined Calculation of Genius bus time and CPU sweep time can be made as instructed in the Series 90 70 PLC and Genius I O system documentation For the CPU sweep time include the GMR base scan time into the calculations as detailed in the GMR User s Manual Genius bus scan times greater than 60mS are to be avoided Longer scan times can cause problems with the operation of the autotest functions especially if the Genius bus is also the inter PLC communications bus Consider re distributing the Genius devices or adding more busses to lower the scan time if necessary The application must determine what data has to be synchronized when a PLC is brought on line where other PLC s are online Typical data that will need to be synchronized are latched states and timer counters Annunciation The annunciation sub system must provide the basic annunciation requirements of E alarms by zone WI overrides inhibits by zone WI system faults e g Fault Table Entry CPU Table Entry Fuse Fail etc E audible s The annunciation sub system must also provide the basic system control requirements of Wi reset to clear latching detectors and system faults B6 manual trips permissives by zone WI manual overrides by zone m mute audible s Output Units Output units should be selected on rating and diagnostic capability Several redundant output configurations are available to provide reduced PFD Probability of Failure
52. prises a single fire zone with a heat detector 3 smoke detectors and extinguishant system The extinguishant is released if any 2 smoke detectors are tripped or the heat detector is tripped Facilities are to be provided for manual release of the extinguishant together with warnings if any single smoke has tripped Example F amp G System Application Logic Smoke 1 Alarm Trip Incipient Fire Smoke2 Alarm Trip Confirmed Smoke 3 Alarm Trip Fire Extinguishant Heat Release Zone Inhibit Inhibit Enable C 2 Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Redundancy This example illustrates the ability of GMR to optimize the degree of I O redundancy The example Fire amp Gas application is an extension to an existing triplicated Emergency Shutdown system that features triplicated processors For most F amp G applications duplex processors are adequate to meet the system PFD requirements The heat sensor a high reliability device is not redundant To meet the system PFD requirements the example uses triplicated input units The smoke sensors provide smoke detection in a single area forming a redundant sensor group In this case only a single input unit is required to interface each detector to meet the PFD The example output configuration is the H block 1oo2d form It conveniently provides external manual override and release capabilities For most normal F amp G system outputs no
53. rmally be disabled GMR configuration changes can only be performed with the system stopped Program changes can be performed with the system operational However great care must be taken to ensure that there are no unexpected output actions Online program changes are possible if there is enough free memory for the CPU to load the revised program software and then switch over It is important to be sure that all application logic states are correctly initialized by the application In accordance with the guidance of IEC61508 Functional Safety of Electrical Electronic Programmable Electronic Safety Related Systems development of program changes with a live system is possible but is not advised for anything beyond minor changes When re starting a PLC the log on control feature is intended to prevent unexpected changes in block outputs arising for including the newly initialized CPU in the block vote Before forcing a log on check for and resolve any latent discrepancies that could cause block outputs to change state as a consequence of enabling the CPU in the block voting Output Unit Maintenance GE Fanuc recommends isolating output block power before removing modules Take care to consider the effect of removing output modules Bypass energized outputs that would otherwise experience an undesired change of state For the redundant H block and I block output groups check that the correct block is to be removed and that the remaining units ca
54. s September 1999 GFK 1649A Common Facilities The example uses a common facilities panel to monitor the status of the Fire and Gas hazards as well as the GMR system operation This type of panel is normally located in one of the equipment cabinets The common facilities panel gives operators maintenance staff a range of indications via LED s such as alarm and fault status In the example system the panel is controlled by a non voted Genius I O block The common facilities matrix implements the following operator functions Description Single Fire LED Function F amp G T O Type O P Comment Indicates one of the three smoke detectors tripped in zone Confirmed Fire LED F amp G O P Indicates any two smoke or heat tripped in zone Zone Inhibit LED F amp G O P Illuminated when valid Zone Inhibit present Zone Inhibit S W F amp G UP When enabled see Zone Inhibit Enable prevents automatic release of extinguishant Does not affect incipient confirmed fire indications Zone Inhibit Enable S W F amp G UP Enables Zone inhibit switch Manual Override F amp G UP Is used to prevent an output device from activating i e for maintenance of the device Its operation is independent of the GMR system The status of this switch is monitored by the GMR system for autotest reporting purposes Manual Release F amp G UP Is used to force an output device
55. safety systems are defined as low demand mode of operation in IEC61508 T V s inspection of GMR for use in Fire and Gas System application was made on this basis 1001d 1002d TUV have carefully assessed the I block and H block configurations and confirmed these correspond to the industry designations of loold and 1oo2d respectively on an individual channel basis Simplex D Processor The designation Simplex D Processor describes a single CPU with dual GBCs providing two paths to shutdown the output via either an I block 1001D or H block 1002D GFK 1649A Appendix D TUV Guidance for Fire and Gas Systems D 3 GFK 1649A 2002 2003 A Actuator Maintenance 4 4 Actuators Annunciation Annunication ANSI ISA S 84 Application Design Principles Audible Alarms B Barriers 1 6 BS EN ISO 9001 1 3 C Components of a Fire and Gas System D Demand Rate 1 9 Detector redundancy Detectors SS Diagnostic Coverag DIN VDE 0116 1 3 DIN VDE 0160 1 3 DIN VDE 0801 DIN VDE 19250 Distributed Control System 1 2 E E E PE 1 2 Emergency Shutdown Systems 2 1 Environment 3 3 ESD 1 2 F F amp G 1 2 Index Field loops 3 5 G GBC 1 2 Genius Bus Genius VOB Em E Ji PP B 3 GMR 1 2 GMR E m Gas Config gurations 2 2 4 GMR termination boards VO vole ET IEE Wiring Regulations 1 3 Input Configurations Options 2 3 Input Unit Maintenance
56. sensors located in the ceilings to be provided with a tube for facilitating remote gassing from floor level System Inputs For best PFD Probability of Failure on Demand and spurious trip performance detector redundancy is recommended Detector redundancy combines the advantages of spurious trip rejection easier maintenance and generally high SIL ratings Input unit redundancy is not normally required for multiple sensor voting group configurations such as voted gas detectors Redundant sensors within a voting group must be distributed across different input modules and Genius busses to avoid common cause failure Because hazard detection times can differ significantly depending on detector locations the discrepancy function within the GMR logic will declare the first up signal as discrepant and reject it Therefore application voting is recommended for redundant Fire amp Gas sensors where alternate appropriate responses are required For critical high reliability non redundant input sensors use duplex or triplex input unit redundancy with GMR voting For Voted DC discrete inputs the GMR termination boards or equivalent devices provide de coupling between input blocks with the option for asynchronous autotest The autotest feature must be activated for SIL2 and SIL3 applications using discrete inputs For input signals requiring line monitoring for either analog and discrete sensors consider using analog inputs or tri state discre
57. single burner boilers ANSI ISA S 84 International Society for Measurement amp Control ISA Standards and Practices Committee No 84 Application of Safety Instrumented System for Process Industries BS 5345 Codes of Practice relating to the Selection Installation and IEC 79 10 Maintenance of Electrical Equipment for use in hazardous areas BS 5501 Electrical Apparatus for Potentially Explosive Atmospheres EN50 015 EN50 020 BS EN ISO 9001 Quality Systems IEE Wiring IEE 16 Edition Wiring Regulations Regulations Related Documents GFT 177 GMR Flexible Triple Modular Redundant TMR System Technical Product Overview GFK 1277B GMR Flexible Triple Modular Redundant TMR System GEK 90486D 2 Chapter 1 Introduction User Manual Genius I O Discrete and Analog Blocks 1 3 Overview Legislation throughout the world makes clear that businesses and individuals alike share a responsibility for the health and safety of other individuals and the environment In addition businesses have vested commercial interests in ensuring the safe operation of plant and processes The document IEC61508 Functional Safety of Electrical Electronic Programmable Electronic Safety Related Systems describes a Lifecycle Safety Management Framework from which to take a structured approach in the assessment and control of such hazards Fire amp Gas Systems fall under the scope of safety systems covered by this standard A Fire amp Gas Systems
58. system diagnostics Industry expectations for proof test interval is between 6 and 12 months Probability to Fail on Demand Probability to fail on demand is the likelihood that the system will fail to perform its intended function when demanded A Fire and Gas System being a low demand system would normally be expected to meet per safety function including the associated field devices one of the following SIL in accordance with IEC61508 Safety Integrity Level Probability to Fail on Demand Low Demand Mode of Operation SIL 1 107 to 10 SIL2 10 to 10 SIL 3 10 to 10 GFK 1649A Chapter 1 Introduction 1 9 Chapter 2 GFK 1649A System Design The Fire and Gas System described in this document is based upon the Genius Modular Redundancy GMR system GMR is a flexible system specifically designed for industrial control applications including applications with safety related requirements T V Rheinland has approved GMR systems for safety related applications in which the de energized state is the safe state ESD Systems GMR systems can also be designed for Fire and Gas applications by utilizing the following features B Simplex duplex or triplex redundant processing units utilizing Genius I O Blocks Failsafe or Fault tolerant input structures utilizing Genius I O Blocks Wi Failsafe or Fault tolerant H block and I block output structures utilizing Genius I O Blocks Wi Interface to external syste
59. t Maintenance nnn ene Estere nE EAE EEEE TEE EET TE E EEE REE EELE FEE 4 3 opie Unt Ma AO E Si ose oec os AOA Once CRA e a na e cM 4 4 iii Contents Appendix A Appendix B Appendix C Appendix D Output Unit Maintenance ecececcccccceesseesnneeceeceeeeeesnnneeeeeeeeeeeeeannaeeeeeeeeseeeeaaaeeeeeeeeeeees 4 4 Actuator Maintenances e o eene nennen nnne sese enn nnne nensis esee tenere een 4 4 R lhability Dat ahs c S A 1 PFD Calculations eiciessiccescscaieicaiocisasscaes sgateses estosta anenee ier eeaeee B 1 Standard Parameters eoe dtes d e en B 1 Ait Example SysStel entre en e PIS MR NE CER EUR YHAN ENTRE CEU EAR ENERO aesa C 1 Application Eu oies anie a a a a a a C 2 Redund ncy 25 EE C 3 Inp t Configurations rne eerte tee C 3 Common Bacilitiess c iore eye Gee Lees hood raed oes enger te pente tenete re pip EE DAP CHR C 7 HMI Remote System Interface eeeeesseeesseeeeeeeeee eene enne enne nennen C 8 Output Configuration nee Rr C 9 System OIC 22 EN EAE EE SE hh eh etae oe Deren snos C 10 eadder Tistin gy 2e C 11 TUV Guidance for Fire and Gas Systems cccccssssssssssssccccsssssssssssccceecees D 1 Configuration Utility enone SESE T DEE EAS D 1 T V Guidance for Fire and Gas Systems nth D 2 DeMi meer elect dans oe eec hd tet DD AR DD LE ED D 3 Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Chapter GFK 1649A l
60. te inputs 16 channel Genius blocks Non line monitored inputs can be input via 32 channel Genius blocks Ground Fault Detectors per EN54 Fire Detection and Fire Alarm Systems are not normally required because field faults such as short circuit to ground are detected by the Genius block diagnostics Redundant sensors using simplex analog input unit redundancy can be accommodated alongside sensors using duplex triplex input unit redundancy as illustrated below by setting the input discrepancy limits to their maximum and using the input signal directly from the block in the configured reference address Genius Modular Redundancy for Fire and Gas Applications September 1999 GFK 1649A Mixing redundant sensors with input unit redundancy as shown below cannot be done for discrete inputs This is a feature of GMR input voting that may cause erroneous fault reports due to sustained differences in the input signal states CRITICAL SENSOR O L GENIUS BUS RL REDUNDANT S Serena O X O INPUT UNIT x3 The input signal sense of tri state discrete inputs normally open or normally closed must be the same for all points on a Genius block The correct block mode GMR for N C or non GMR for N O must be configured Field loops should provide a way to electrically isolate field circuits for maintenance It should be possible to inhibit field inputs This can be done at a physical level for example
61. te self checking and diagnostic functional checks to ensure that the units are operating correctly In addition to interfacing field devices to the system input units also interface internal protection system signals such as fuse failure and over temperature In this way the protection system provides a high level of diagnostic and fault reporting Logic Control System In the Fire and Gas System the logic control unit receives the input signal performs the logic for annunciation and control actions and interfaces to external systems The logic control unit performs such functions as inhibiting I O alarm tripping analog signals handling detector actuator faults detector voting control of local and field annunciation control of extinguishing system control of output devices such as fans and dampers and interfacing to other systems such as HVAC ESD systems The critical role of the logic control unit means that some type of redundancy is usually desirable Fire and Gas Systems are normally dormant or inactive systems In Fire and Gas Systems input signals and internal logic states may remain unchanged for long periods of time If a fault develops while the system is inactive it is important to be sure the system will respond appropriately Therefore thorough periodic background diagnostic tests must be performed to be sure the system remains able to function on demand In addition a Fire and Gas System should have built in measures
62. ts D 2 T V Guidance for Fire and Gas Systems The following guidance from T V should be observed when applying GMR to Fire and Gas Systems in addition to that provided in Appendix A of GFK 1277B System Fire amp Gas application CPU simplex shutdown should be disabled for 3 2 1 0 operation For safety relevant applications a safe state must exist e g de energized for ESD systems or the demand to trip must be defined If a simplex redundancy system configuration is used for applications requiring SIL2 performance then additional measures must be specified and implemented to maintain the safe state during the time that it takes to restore the system to normal operation Due to this requirement a simplex redundancy system can only be used with applications having a high process safety time Inputs 16 channel blocks configured for tri state operation can be used for discrete inputs that require line monitoring and or earth fault detection Operation of the inputs is as follows BLOCK FAULT GMR MODE NON GMR MODE normally on normally off Source Open Wire Off Fault Source Shorted Wire Fault On Source Ground Short Off Fault Sink Open Wire Off Fault Sink Shorted Wire Fault On Sink Ground Short Fault On d Assumes a ground short to positive line interrupts power flow to the field Additionally or alternatively other special measures may be applied for the detection of eart
Download Pdf Manuals
Related Search
Related Contents
Guía de instalación rápida Sistema de cine en casa de 5.1 平 成 14 年 度 Stamina Products 55-1539A User's Manual Char-Broil 463244012 User's Manual Storage Central Turbo Model SC101T and Storage Avaya Troubleshooting Routers Troubleshooting Samsung 172S Käyttöopas Philips AE6780 User's Manual Samsung DVD-HR773 Uživatelská přiručka Copyright © All rights reserved.
Failed to retrieve file