1. Multi Language User Manual on CD Liebert Shutdown Software and User Manual on CD DB 9 Serial Cable USB Cable Input Power Cord 2200 3000 only 2 EC Output Cable 1000 1500 only 2 EC Output Cable 2200 3000 only 3 Tower Stand Rack Mount Handles Battery UPS Tab Figure4 Accessories Liebert Shutdown Software CD Battery UPS Tab DB 9 Cable 1 8 m 6 ft 1 8 m 6 ft Input Power Cables l 2 with 2200 and 3000VA models Mounting Hardware Screws amp Washers Rack Mount Tower Stand Handles Output Power Cable 2 with 1000 and1500VA models 3 with 2200 and 3000VA models IT and Instrumentation for industry z Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Installation 3 0 INSTALLATION 3 4 Preparation Inspect the UPS for freight damage Report any damage to the carrier and your local dealer or Emer son representative A CAUTION Risk of injury from heavy unit May cause equipment damage or personal injury The UPS and battery cabinets are heavy see Table 6 and Table 7 Take proper precautions when lifting or moving either the UPS or battery cabinets The Liebert PSI XR may be installed in either a tower or rack configuration Determine the method that suits the application and proceed Decide where to install the Liebert PSI XR The UPS must be installed indoors in a contro
2. C F 15 to 40 5 to 104 Relative Humidity 096 to 9096 non condensing Maximum Operating Altitude 3000m 10 000 ft at 35 C 95 F without derating Agency Safety IEC EN AS 62040 1 1 Emissions IEC EN AS 62040 2 2nd Ed Class A Transportation ISTA Procedure 1A Certification 21 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Specifications Table 8 Liebert PSI XR battery run times Number of Batteries Load 1000VA 1500VA 2200VA 3000VA 10 82 81 76 75 25 43 32 32 32 Internal Battery 50 15 13 14 13 75 9 8 8 8 100 6 5 5 5 10 272 222 161 142 Internal Battery 25 139 109 80 To 1 External 50 73 55 45 31 Battery Cabinets 75 51 31 25 17 100 31 18 15 12 10 438 357 241 205 Internal Battery 25 231 1 3 128 106 2 External 50 129 95 67 56 Battery Cabinets 75 84 61 47 31 100 65 46 29 18 10 614 492 322 267 Internal Battery 25 324 241 170 139 3 External 50 181 131 95 73 Battery Cabinets 75 126 84 62 50 100 96 64 48 31 10 789 627 483 329 Internal Battery id 309 BUB 29s T 4 External 50 233 167 143 95 Battery Cabinets 75 162 114 100 62 100 124 82 72 47 10 964 762 564 392 Internal Battery 25 509 374 298 204 5 External 50 285 203 167 113 Battery Cabinets 75 197 139 116 74 100 151 106 84 56 10 1140 897 644 454 In
3. IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual 7 0 BATTERY MAINTENANCE 0 00 cece eee ees 19 7 1 Battery Charging torage oooorrrr cette n 19 7 2 Internal Battery Replacement Procedure 0 00 c cece eee eee 19 8 0 SPECIFICATIONS iia rr exse ada ra eX eee Ra VR PEE ee Seb EEG woods 20 9 0 TROUBLESHOOTING eere ee hah hh nh n nnm 23 FIGURES ligure l Front view ot URS isso ua tb eae ay 4 Figure2 1000 and 1500VA rear View 1 1 ccc hh Rh hehehe 4 Figure3 2200 and 3000VA rear view lees here 4 Hisure4 ACCESOS Loser caa Qo RESP PE PONAT roads 5 Figure b Placing the Liebert PSLXR iioc ecgca hk Rem DP VERG EO MASA A eae aS 6 Figure6 Tower configuration attach Tower Stand 0 0 cece hne 7 Figure 7 Convert the Liebert PSI XR for rack installation 0 00 ect ene 8 Figure 8 Orienting the UPS display 0 0 0 eee tent eens 9 Figure 9 Connect mains power and load 0 cette hh 9 Figure 10 Connect network surge protection 1 0 20 0 ccc eee mn 10 Figure 11 Connect computer interface port 0 0 cece ent n teens 10 Figure 12 EPO connection for normally open operation 0 0 0 cece teen ene 11 Figure 13 Install the external battery cabinet in tower installation l l 11 Figure 14 Connect battery cabinets to UPS
4. The five LEDs at the top of the front panel illuminate with a steady glow to indicate the load level on the output of the UPS The LEDs show the load level as a range 5 The LEDs load level meanings and colors are LED 1 LED 2 LED 3 LED 4 LED 5 10 24 Green 25 49 Green 50 74 Yellow 75 99 Yellow 100 or greater Red 14 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Controls and Indicators 4 2 3 Battery Level Indicator The five LEDs illuminate with a steady glow to indicate battery capacity Battery capacity is shown for five seconds after the Status Change Button is pressed The LEDs show the battery capacity as a range 5 The LEDs battery level meanings and colors are LED 1 LED 2 LED 3 LED 4 LED 5 100 76 Green 75 51 Green 50 26 Yellow 25 11 Yellow 10 or less Red 4 2 4 UPS Status Indicators LEDs on the display panel illuminate with a steady glow or flash to indicate the UPS s status Mains Mode The Mains Mode indicator illuminates LED 9 with a steady glow when mains power is available and within the input specifications Battery Mode The Battery Indicator illuminates LED 10 with a steady glow when the UPS is operating on battery AVR Boost AVR Buck When the UPS is in AVR Boost Buck
5. Model Number PS1000RT3 230XR PS1500RT3 230XR PS2200RT3 230XR PS3000RT3 230XR Power Rating Vaw 1000VA 900W 1500VA 1350W 2200VA 1980W 3000VA 2700W Dimensions W x D x H mm in Unit 440 x 490 5 x 88 440 x 490 5 x 88 440 x 700 5 x 88 440 x 700 5 x 88 17 3 x 19 3 x 3 5 17 3 x 19 3 x 3 5 17 3 x 27 6 x 3 5 17 3 x 27 6 x 3 5 Shipping 560 x 612 x 228 560 x 612 x 228 560 x 821 x 228 560 x 821 x 228 22 x 24 1 x 9 22 x 24 1 x 9 22x 32 3 x 9 22x 32 3 x 9 Weight kg Ib Unit 25 55 28 61 42 93 46 102 Shipping 29 64 32 70 47 104 51 111 Input AC Parameters Surge Protection 220J wien E e 165 to 300 VAC configurable Frequency Range 45 65Hz 0 5Hz Input Socket IEC 320 C14 IEC 320 C14 IEC 320 C20 IEC 320 C20 Output Sockets 6 IEC 320 C13 6 IEC 320 C13 e EC I t E Voltage Normal Mode 220 230 240 VAC configurable Voltage Battery Mode 220 230 240 VAC configurable 5 before low battery warning Transfer Time 4 6 ms typical On Battery Waveform Sinewave Overload Warning gt 100 Overload Shutdown Normal Mode Overload Shutdown Battery Mode Battery Parameters gt 120 shutdown after one cycle normal mode gt 130 shutdown after one cycle normal mode Type Valve regulated nonspillable lead acid Quantity x Voltage x Rating 4x12x7 2 4x12x9 8x12x7 2 8x12x9 Recharge Time 5 hours to 90 of rated capacity a
6. 0 eect nee teens 12 Figure 15 Display and status indicators 0 0 0 cette he 13 Figure 16 DIP switch settings for 230V system 0 2 ck eee he 18 Figure 17 Battery replacement sisis solide se ed RR dane a SORS a a Re or Redes davies 19 TABLES Table 1 Battery cabinet connector color key 0 0 0 0 cece eee ene teen ene 12 Table 2 Display and status indicators function legend 20 0 0 c eese 13 Table 3 Status indicators color illumination mode 0 0 ec teeta 15 Table 4 DB 9 pin assignment 55 acecet eden neers Rese ac au ae A hE DSRS baa S aaro ce ds 17 Table 5 Voltage configurations iu sac pex o erage ae OR UR Rc Re ego 18 Table 6 Liebert PSI XR specifications lisse hh hr 20 Table 7 Liebert PSI XR battery cabinet specifications llle 21 Table 8 Liebert PSI XR battery run times o coco ehm 22 Table 9 Troubleshooting problems causes and solutions saunaa cece eee eee ene ee 23 ii IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries Read this manual thoroughly before attempting to install or operate this UPS The equipment can be installed and operated by individuals wit
7. 1 Control Buttons sc iy gw se tee ooh ea bie arr Cos ee RAs ede ae gan econ On DR TR ones 14 4 1 1 On Alarm Silence Manual Self Diagnostic Test 0 0 0 cece eee 14 412 Ot Button rms a RRA ea hee ede spatia d nor 14 4 2 Status IndiCaloES oue Ir ER e eti gra een us ed ddr gael RUE ere hoe abo 14 421 Status Change Button bra erp d Ga ad QUU eae eae 14 49 Load Level Indicatorii menr eter ong YO Rhe p Per age g quie Re ated 14 423 Battery Level Indicator re Sigg gan bak ween Pp UE QE aA ia Patres 15 424 UPS Status Indicators o a REI deesse te Pee E dyed debe sede eig 15 5 0 OPERATIONAL MODES seen ee ees 16 5 1 Normal Mode 56 we titan 4 edd A A ae dea 16 5 2 Buck Boost Mode cnr DER m ERRARE dee RP Geman Rak bdo oe hag eese putc gute 16 5 3 Battery Mode Rep mek fete oe E NE ere woke RE S E EN MEER E A SEE ERES 16 5 4 Battery Recharge Operation 0 00 cece n 16 6 0 COMMUNICATION occ 17 6 1 DB 9 Connector 6 200460 ea waste I Rd ee ay dr epee dne ie Cede ee REN SU Se 17 6 2 Remote Shutdown Via the DB 9 Connector 0 0 c eee eee eee 17 6 2 1 Any Mode Shutdown Via Pins 5 amp 6 0 0 0 ete eee 17 6 2 2 Battery Mode Shutdown Via Pins 4 amp 5 1 lees es 17 6 3 RJ 45 Data Line Protection Connectors 0 eee n eens 18 6 4 UPS Communications ser sc ied ev gaa ees GEA ee eine eee E oe RO ds 18 6 5 UPS Inverter Transfer Voltage Configurations 00 c cece eee 18 i
8. Mode 3 LED 3 Battery Condition Battery Fault Weak 4 LED 4 Grounding Site Wiring Fault UPS Grounding Site Wiring Fault 5 LED 5 Overload UPS Overload 1to5 Load Battery Level Indicate Load Battery Level 6 Status Change Button Switches Display from Load Level Indicators to Battery Level Indicators 7 OFF Button UPS Off Turn on UPS Manual Self Diagnostic Normal Mode 8 ON Button Silence Alarm Battery Mode 9 LED 9 Normal Mode UPS Operation in Normal Mode 10 LED 10 Battery Mode UPS Operation in Battery Mode 11 LED 11 UPS Fault UPS Fault 13 IT and Instrumentation for industry E Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Controls and Indicators 4 1 Control Buttons 4 1 1 On Alarm Silence Manual Self Diagnostic Test This button controls output power to connected load s It has three functions On Alarm Silence Manual Self Diagnostic Test ON Start the UPS by pressing this button for more than 3 seconds then releasing the button an alarm will sound briefly If the ON button is pressed and mains is outside input parameters the UPS will start on battery dark start Alarm Silence Silence a Battery Mode audible alarm by pressing this button for longer than one second then releasing it Manual Self Diagnostic Test To initiate a Manual Self Diagnostic press this button for at least three 3 seconds while operating from the mains UPS w
9. Mode the LED display will indicate the relative load level on the output of the UPS and will flash LED 1 boost or LED 2 buck to indi cate the mode Weak Battery When the UPS battery voltage is low the LED display will indicate the relative load level on the output of the UPS and LED 3 will flash as a warning Site Wiring Fault In case of a site wiring fault the LED display will indicate the relative load level on the output of the UPS and LED 4 will flash as a warning Overload When UPS operates in overload status the LED display will indicate the relative load level on the output of the UPS and LED 5 will flash as a warning Table 3 Status indicators color illumination mode Status LED 1 LED 2 LED 3 LED 4 LED 5 LED 9 LED 10 LED 11 Green Steady Green Green Flashes Steady Normal Mode AVR Boost Green Green AVR BUCK Flashes Steady Battery Mode Yellow dark start Steady Yellow Flashes Weak Battery Yellow Site Wiring Fault Flashes Red Overload Flashes Battery Fault Yellow Red Shutdown Steady Steady Overload Red Red Shutdown Steady Steady UPS Output Abnormal Shutdown Yellow Red Steady Steady 15 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Operational Modes 5 0 OPERATIONAL MODES 5 1 Norm
10. and high short circuit current The following precautions must be observed when working on batteries Remove watches rings and other metal objects Use tools with insulated handles Do not dispose battery or batteries in a fire The battery may explode Do not open or mutilate the battery or batteries Released electrolyte is toxic It may cause injury to the skin and eyes When replacing the battery use the type of battery as is listed in Tables 6 and 7 Handle transport and recycle batteries in accordance with local regulations IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual CONDITIONS OF USE The mains supply socket must be within 1 8m 6ft of the UPS and be eas ily accessed This UPS provides conditioned power to connected equipment It is designed for commercial use only It is not intended for use with life support and other designated critical devices Maximum load must not exceed that shown on the UPS rating label If uncertain consult your local Liebert or Emer son Network Power Liebert Applications The Liebert PSI XR 1000 and 1500 models are not supplied with an input power cable for connection to the mains supply socket Use the input mains supply power cable from your data processing equip ment to connect the UPS to the mains supply For the Liebert PSI XR 2200 and 3000 models
11. use the supplied 16A rated input mains supply cables For UK supply systems consult a properly trained and qualified electrician to connect the lead sup plied for the 2200 and 3000 models to the mains supply The UPS and connected load total earth leakage current must not exceed 3 5mA If the connected load earth leakage current is likely to exceed 2 5mA or if you are unsure then convert the input cable attachment to either a fixed wiring installation or an industrial plug socket e g CEE 17 connector This alteration should be carried out by a properly trained and qualified electrical engineer who is conversant with local electrical codes and regulations When installing the UPS or making input and output connections comply with all relevant safety codes and standards e g IEC60950 VD E0805 EN62040 1 Placing magnetic storage media on top of the UPS may result in data corruption ELECTROMAGNETIC COMPATIBILITY The Liebert PSI XR series complies with the require ments of EMC Directive 89 336 EEC and the published technical standards Continued compliance requires installation in accordance with these instructions and use of Emerson Network Power approved accessories only When using the communication features on this UPS ensure the cabling connected to the DB 9 or UPS communications ports are kept separated from the power leads to the UPS input and output NOTICE Do not connect equipment that could overload the UPS or demand
12. E AC Power For Business Critical Continuity Liebert PSI XR User Manual 1000 1500 2200 3000VA 50 60Hz 230VAC AAA DIOE EMERSON Liebert MI AD Liebert UPS user manual EMERSON IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual BLANK PAGE IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual TABLE OF CONTENTS 1 0 INTRODUCTION ist ice eue pete aa bee idee ne bed Mo e Ie 4 2 0 WHAT S INCLUDED 1 cece eee 5 3 0 INSTALLATION coc os Oe alae CR ACE EREDE a WR ode ew 6 3 1 Prep r ti n i e soe e e eR peg ne aoe eB ep ep a RR Y pune 9 8H Nor puma pla e 6 3 2 Tower UPS Installation ios ara eR Ea Ree RUE dee an UR A ce ek Oe OPE OR Ree etes 7 3 8 Rack Mount UPS Conversion and Installation 0 0 0 eee eee 8 3 4 Orient Display for Installation 0 0 ccc n eee eeeee 9 3 5 Connect Input Power and Load 0 0 cee een e tenes 9 3 6 Connect Network Surge protection 0 cee eee e teens 10 3 7 Connect Computer Interface Port 1 0 0 e teenies 10 3 8 EPO Swit MP P Gok ace Re sow See arth og a ag ees a nat Sate E w E JS 11 3 9 External Battery Cabinet Installation 0 0 ce tenets 11 4 0 CONTROLS AND INDICATORS 6 00 cee ees 13 4
13. S input feeder breaker to interrupt all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations Figure 12 EPO connection for normally open operation 1 EPO 2 Ground Short Pin 1 and Pin 2 to enable the EPO function 3 9 External Battery Cabinet Installation Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS The batteries have a maximum run time of three hours at full load 1 Shut down any connected equipment and turn Off the UPS 2 Install the external battery cabinet in a tower configuration or in a rack see Figure 13 or 3 3 Rack Mount UPS Conversion and Installation 3 Connect the external battery cabinet cable to the rear of the external battery cabinet then to the rear of the UPS see Figure 14 Figure 13 Install the external battery cabinet in tower installation Connect the top of the UPS to the top of the battery cabinet with the Battery UPS Tab and hardware If two or more battery cabinets are used in a tower setup the tower stand must be extended with the spacers included with each battery cabinet Install tower stands and set the UPS and battery cabinet in them check to ensure stability NOTICE External battery cabinet connectors are color coded as noted in Table 1 Do not try
14. al Mode When the UPS is in Normal Mode the Normal Mode Indicator illuminates green 5 2 Buck Boost Mode The Automatic Voltage Regulator AVR circuitry compensates for fluctuations in mains power such as voltage surges and sags The Liebert PSI XR compensates for these by raising the undervoltage boost or lowering the overvoltage buck The AVR operates automatically and maintains the output voltage to the connected equipment without utilizing the batteries 5 3 Battery Mode The UPS switches to Battery Mode in the event of an extreme input voltage frequency condition or mains failure When the UPS is in Battery Mode the Battery Indicator illuminates amber and an alarm sounds at 2 second intervals As capacity decreases fewer indicators remain illuminated When a Low Battery condition occurs the Battery Indicator flashes amber and an alarm sounds at one second intervals For approximate battery run times refer to Table 8 5 4 Battery Recharge Operation Once mains power is restored the UPS resumes normal operation and the Battery Charger begins recharging the batteries 16 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Communication 6 0 COMMUNICATION 6 1 DB 9 Connector The UPS has a DB 9 9 pin female connector on the rear to allow UPS status communications with a computer running Liebert shu
15. ebsite www amplicon co uk Email sales amplicon co uk Liebert UPS user manual BLANK PAGE IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Ensuring The High Availability Of Mission Critical Data And Applications Emerson Network Power the global leader in enabling business critical continuity ensures network resiliency and adaptability through a family of technologies including Liebert power and cooling technologies that protect and support business critical systems Liebert solutions employ an adaptive architecture that responds to changes in criticality density and capacity Enterprises benefit from greater IT system availability operational flexibility and reduced capital equipment and operating costs While every precaution has been taken to ensure the accuracy and completeness of this literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2008 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice Liebert is a registered trademark of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners SLI 23315 REVO 04 08 Emerson Network Power The global leader in enabling Busi
16. fter full discharge into resistive load Battery Backup Time Full Load 5 min Half Load 10 min Environmental Operating Temperature C F 0 to 40 32 to 104 Storage Temperature C F 15 to 40 5 to 104 Relative Humidity 0 to 90 non condensing Operating Altitude Up to 3000m 10 000 ft at 35 C 95 F without derating Audible Noise lt 40 dBA internal fan s Off lt 45 dBA internal fan s On Agency Safety 1EC62040 1 1 EMC IEC EN AS 62040 2 2nd Ed Class A Transportation ISTA Procedure 1A Certification Battery backup times are approximate and may vary depending on the load and battery charge 20 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Specifications Table 7 Liebert PSI XR battery cabinet specifications Model Number PSRT3 24VBXR PSRT3 48VBXR PS1000RT3 230XR PS2200RT3 230XR Used w UPS Model PS1500RT3 230XR PS3000RT3 230XR Dimensions W x D x H mm in Unit 440 x 490 5 x 88 17 3 x 19 3 x 3 5 Shipping 560 x 675 x 228 22 x 26 6 x 9 Weight kg Ib Unit 29 64 Shipping 33 73 Batteries Type Valve regulated nonspillable lead acid Quantity x Voltage x Rating 8x12x72 8x12x7 2 Battery Manufacturers CSB YUASA or Equivalent Environmental Operating Temperature C F 0 to 40 32 to 104 Storage Temperature
17. half wave rectification from the UPS for example electric drills vacuum cleaners laserjet inkjet printers hair dryers overhead projectors IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual GLOSSARY OF SYMBOLS LA Risk of electrical shock A Indicates caution followed by important instructions G zu Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Alarm Silence Manual Self Diagnostic Test OFF Status Change Button YOOQct OI IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk EA o Liebert UPS user manual Introduction 1 0 INTRODUCTION The Liebert PSI XR is a 2U line interactive UPS that may be installed in a rack or used as a tower UPS Status indicators on the front of the Liebert PSI XR display load level battery level buck boost site wiring fault and battery status Controls include a combination ON Alarm Silence Manual Self Diag nostic button an Off button and a Display Status Change button The Liebert PSI XR has USB DB 9 RS 232 contact closure and SNMP interface ports The DB 9 and USB ports provide detailed operating information including voltages currents and alarm status to the hos
18. hout previous training A WARNING Install the UPS indoors in a temperature and humidity controlled room free of conductive contaminants moisture flammable liquids gases and corrosive substances Some components are live even when AC power is disconnected For service contact a properly trained and qualified technician Do not remove the cover the UPS has no user serviceable parts inside except the internal battery pack Operate the UPS only from a properly grounded earthed 220 240 VAC 50Hz or 60Hz AC supply Do not supply this UPS from electrical power systems of the IT type IEC 364 Electrical Installation of Buildings A WARNING Although the UPS has been designed and manufactured to ensure personal safety improper use can result in electrical shock or fire To ensure safety observe the following rules Turn Off and unplug the UPS before cleaning it Clean the UPS with a dry cloth Do not use liquid or aerosol cleaners Do not install or operate the UPS in or near water Never block or insert any objects into the ventilation holes or other openings of the UPS Keep all vents free of dust accumulation that could restrict air flow Do not place UPS power cord anywhere it might be damaged Battery Handling Precautions A WARNING Batteries should be replaced only by properly trained and qualified personnel knowledgeable of batteries and required precautions A battery can present a risk of electrical shock
19. ill switch to Battery Mode to detect battery voltage and whether the UPS is operating normally If LED indicates the battery is weak Allow the UPS to recharge the batteries for 8 hours Retest the battery after recharge If LED still indicates that the battery is weak after the battery has been retested contact your local dealer local Emerson representative or Liebert Applications If LED indicates a Battery Fault Contact your local dealer Emerson representative or Liebert Applications If LED indicates a UPS Fault Remove the load retest the self diagnostic test if LED indicated UPS Fault Contact your local dealer Emerson representative or Liebert Applications NOTE Refer to Figure 15 and Table 2 for details about the LEDs meaning 4 1 2 Off Button When the UPS is operating in either Normal Mode or Battery Mode pressing the Off button for more than three seconds will shut down the UPS 4 2 Status Indicators 4 2 1 Status Change Button The Status Change Button determines the information displayed by the five LEDs on the front panel The default information shown by the LEDs is the load level on the UPS Pressing the Status Change Button while the UPS is On prompts the LED display to show battery capacity for 5 seconds This function assists in assessing the meaning of status indicators as described in 4 2 4 UPS Status Indicators See Figure 15 and Table 2 for the Status Change Button s location 4 2 2 Load Level Indicator
20. l voltages of 220V 230V or 240V This feature will change the high and low points at which the UPS switches to battery power It also will change the UPS output voltage when the UPS is operating in battery mode The factory default setting is 230 VAC Figure 16 DIP switch settings for 230V system FUNCTION 1 Voltage 220V Voltage 230V 4 Voltage 230V Y y gt gt e cp Voltage 240V Table 5 Voltage configurations Setting Input Voltage Range Output Voltage Battery Mode 220 165 275 220VAC 230 173 288 230VAC 240 180 300 240VAC 18 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Battery Maintenance 7 0 BATTERY MAINTENANCE 7 1 Battery Charging Storage The batteries are valve regulated nonspillable lead acid and must be kept charged to retain their design life The Liebert PSI XR continuously charges the batteries when connected to the mains sup ply even while the UPS is switched Off If the Liebert PSI XR will be stored for an extended period Liebert recommends connecting the UPS to input power for at least 8 hours every four to six months to keep the batteries charged 7 2 Internal Battery Replacement Procedure NOTICE This UPS is equipped with internal batteries that the user can replace without shutting down the UPS or connected loads hot swappab
21. le Caution must be exercised when replacing the batteries because the load is unprotected from power fluctuations and power failures To replace the batteries Remove the two screws on the left side of the front bezel Pull the front bezel off the UPS Remove the two screws on the battery bracket Remove the screw on the battery connectors holder Disconnect the two slotted red gray and black battery connectors Grasp the battery pack assembly by the handle and pull it out of the front of the UPS Unpack the new battery assembly taking care not to destroy the packing Compare the new and old battery assemblies to make sure they are the same If so proceed with replacement If they are different STOP and contact your local dealer Emerson representative or Liebert Applications 9 Slide the new battery pack into the UPS 10 Reattach the battery bracket with the two screws 11 Reconnect the slotted red gray and black battery connectors 12 Reinsert the screw on the battery connectors holder 13 Reattach the front bezel Qo l9 Or m co Bo r Figure 17 Battery replacement Step 1 Step 2 Step 6 19 IT and Instrumentation for industry z Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Specifications 8 0 SPECIFICATIONS Table 6 Liebert PSI XR specifications
22. lled envi ronment Place it in an area with unrestricted airflow around the unit away from water flammable liquids gases corrosives and conductive contaminants see Figure 5 Maintain a minimum clearance of 305mm 12 inches in the front and rear of the UPS Maintain an ambient temperature range of 0 C to 40 C 32 F to 104 F see Figure 5 Figure 5 Placing the Liebert PSI XR 0 C 32 F 40 C 104 F Relative humidity Y o non condensing 0 90 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Installation 3 2 Tower UPS Installation See Figure 6 when using the Liebert PSI XR in a tower configuration Figure 6 Tower configuration attach Tower Stand Step 1 IT and Instrumentation for industry z Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Installation 3 3 Rack Mount UPS Conversion and Installation See Figure 7 when installing the Liebert PSI XR in a rack External battery cabinets are installed in racks in the same manner Figure7 Convert the Liebert PSI XR for rack installation Step 1 A WARNING Risk of top heavy unit falling over May cause equipment damage personal injury or death Placing heavy equipment near the top of a rack may increase the risk of tipping Place the UPS or bat
23. mentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Installation 3 6 Connect Network Surge protection Connect a 10 base T 100 network cable to the RJ 45 network surge protection IN jack on the rear of the UPS Connect from the OUT jack with network cabling to network equipment see Figure 10 Figure 10 Connect network surge protection Network Equipment Network Surge Network Surge Protection IN Jack Protection OUT Jack 3 7 Connect Computer Interface Port Determine what type of communication connection to use to manage the UPS The Liebert PSI XR can be monitored with any of these communication methods serial contact closure USB SNMP See the Liebert shutdown software installation guide on the included CD ROM for details and instal lation information Also refer to 6 4 UPS Communications Figure 11 Connect computer interface port USB connector is to left of DB 9 port on the UPS USB port on computer varies 10 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Installation 3 8 EPO Switch The Liebert PSI XR is equipped with an Emergency Power Off EPO switch The user must supply a means of interfacing with the EPO circuit to allow disconnecting the UP
24. ness Critical Continuity EmersonNetworkPower com Mi AC Power I3 Embedded Computing I Outside Plant I Racks amp Integrated Cabinets HI Connectivity HI Embedded Power I3 Power Switching amp Controls E Services Mi DC Power I3 Monitoring I Precision Cooling I Surge Protection Business Critical Continuity Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co 2008 Emerson Electric Co IT and Instrumentation for industry Amplicon Sales 44 0 1273570220 Website www amplicon co uk Email sales amplicon co uk
25. o signal a shutdown Signals for less than 2 seconds are ignored After Pin 4 receives the shutdown signal a 2 minute shutdown timer begins a countdown The shut down timer cannot be stopped If mains power returns during the 2 minute countdown the shutdown timer continues until the end of 2 minutes and the UPS turns Off The UPS will restart 10 seconds after mains power returns 17 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Communication 6 3 RJ 45 Data Line Protection Connectors Data line in and out connectors on the rear of the UPS provide transient voltage surge suppression TVSS for network devices 6 4 UPS Communications The Liebert PSI XR is equipped with a Liebert IntelliSlot port to provide advanced communication and monitoring options Liebert s shutdown software continually monitors the UPS and can shut down your computer or server via USB and RS 232 in the event of an extended power failure The Liebert IS WEBRTS provides SNMP and Web based monitoring and control of the UPS across the network NOTE The USB and Contact Closure communications operate in parallel Using the Liebert IS WEBRTS disables the serial communications of the DB 9 6 5 UPS Inverter Transfer Voltage Configurations A two pin DIP switch on the rear of the Liebert PSI XR permits setting the UPS to operate at nomina
26. t plugged in Plug in the power cord securely Circuit breaker tripped Reset the circuit breaker UPS starts on battery but will not switch to AC dark start Wait until voltage drops to an appropriate level or have the utility power checked by a properly trained and qualified electrician AC overvoltage Short circuit or UPS output is Remove the load and turn on the abnormal LED 10 and LED 11 UPS again For help contact your local dealer Emerson illuminate and sound audible i alarm representative or Liebert Applications UPS shuts down pa ocr dd E Overload LED 5 and LED 11 s Recalculate the load and reduce illuminate and sound audible i alam equipment connected to UPS the total wattage must not exceed the capacity of the UPS LED 3 and LED 11 illuminate and Recharge the battery for 8 hours sound audible alarm then turn ON the UPS Consult the Liebert shutdown Liebert shutdown software software user manual or contact your LAN administrator Batteries weak Recharge batteries Battery Weak LED LED 3 flashing Batteries need to be replaced Replace batteries 23 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Troubleshooting Notes BLANK PAGE 24 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 W
27. t system when used in conjunction with Liebert shutdown software Figure 1 Front view of UPS Liebert PSI XR tower configuration Liebert PSI XR Display rotates for use in rack rack mount configuration Display rotates for use as tower Figure 2 1000 and 1500VA rear view RS 232 Liebert 1000VA 8A Input Circuit Breaker DB 9 Port IntelliSlot 1500VA 10A Input Circuit Breaker Port 1000VA 8A Output Circuit Breaker 1500VA 10A Output Circuit Breaker USB Port EPO IEC 320 C13 Voltage Configura RJ 45 Data Line External Battery IEC 320 C14 Output tion DIP Switch Connectors Cabinet Connector Input Socket Sockets Figure3 2200 and 3000VA rear view Liebert 2200VA 15A Input Circuit Breaker 10A Output Circuit Breaker IntelliSlot 3000VA 20A Input Circuit Breaker for Upper Row of Output Sockets RS232 Port IEC 320 C13 DB 9 Port IEC 320 C19 Output Socket Output Sockets USB Port q IIO ALI ES o gt ogm DULL 7A Voltage Configuration RJ 45 Data Line DIP Switch Connectors External Battery 10A Output Circuit Breaker for Cabinet Connector Lower Row of Output Sockets IEC 320 C20 Input Socket IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual What s Included 2 0 WHAT S INCLUDED The Liebert PSI XR is shipped with the following items
28. tdown software The connection provides serial communication On Battery and Low Battery signals Liebert shutdown software and a 1 8m 6 ft DB 9 serial cable are shipped with the UPS When power is interrupted and battery power is low Liebert shutdown software can signal the host computer to gracefully shut down the operating system Table 4 DB 9 pin assignment DB 9 Pin Assignment Description Low Battery open collector UPS TxD UPS RxD Remote Shutdown 5 12V on battery operation Common Output Off short to Pin 5 non latching any mode operation Low Battery open emitter Mains Fail open emitter OO CO NID om AJ Ww dM Mains Fail open collector Pin Assignment Collector to Emitter Open Collector Open Emitter 6 2 Remote Shutdown Via the DB 9 Connector The Liebert PSI XR can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB 9 connector 6 2 1 Any Mode Shutdown Via Pins 5 amp 6 When Pin 6 is shorted to Pin 5 the UPS output is shut Off no matter what mode the UPS is operat ing The UPS cannot be started as long as the pins are shorted When the short is removed the UPS output can be enabled by pressing the ON Alarm Silence Manual Self Diagnostic Test button 6 2 2 Battery Mode Shutdown Via Pins 4 amp 5 While the UPS is operating on battery a 5 12VDC signal for 2 seconds or longer is required t
29. ternal Battery 29 Spi 29 341 208 6 External 50 336 239 191 131 Battery Cabinets 75 233 163 133 85 100 179 124 102 65 Run times are in minutes assume fully charged batteries and are typical at 77 F 25 C with resistive loads 22 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Troubleshooting 9 0 TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the Liebert PSI XR experiences a problem See Table 9 for suggested solutions 1 An alarm sounds alerting that the UPS requires attention The alarm can be silenced except for low battery and overload warnings 2 One or more additional indicators will be illuminated to provide a diagnostic aid to the operator as described below If the UPS fails to operate properly turn Off the unit and repeat the steps in 3 0 Installation If the problem persists refer to Table 9 Table 9 Troubleshooting problems causes and solutions Problem Cause Solution Check the circuit breaker on the rear of the UPS If itis tripped reset it and restart the N UPS For help contact your local UPS will not start dealer Emerson representative or Liebert Applications Short circuit Battery is disconnected or Check for proper connection of completely discharged battery or batteries UPS no
30. tery cabinet if one is being used in the bottom of the rack A CAUTION Risk of strain from lifting heavy equipment May cause personal injury Lifting equipment into rack may be a two person job depending on weight of equipment NOTICE When rack mounted the UPS must be supported by a shelf slide rails brackets or fixed rails on each side The rack mount handles WILL NOT support the weight of the UPS They are used to move the UPS into and out of the rack IT and Instrumentation for industry z Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Installation 3 4 Orient Display for Installation The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installa tions To set the display for your installation pull out on the display and rotate it until it is oriented cor rectly then press it into the UPS until it is seated Figure 8 Orienting the UPS display 3 5 Connect Input Power and Load The 1000VA and 1500VA models do not include an input power cable the 2200VA and 3000VA UPSs include an input power cable Connect input power to the UPS then plug the equipment into the sockets on the rear of the UPS These UPS sockets provide battery backup and surge protection to the equipment when mains power fails spikes or sags see Figure 9 Figure 9 Connect mains power and load LL IT and Instru
31. to install external battery cabinets with connectors that are a different color from the battery connector on the UPS 11 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Installation Table 1 Battery cabinet connector color key Nominal System Voltage External Battery UPS Model connector color Cabinet Model PS1000RT3 230XR 24VDC Red PSRT3 24VBXR PS1500RT3 230XR PS2200RT3 230XR 48VDC Gray PSRT3 48VBXR PS3000RT3 230XR Figure 14 Connect battery cabinets to UPS O 5 A ilill e uL J MM m m Y I AMOO See Table 8 for approximate battery run times 12 IT and Instrumentation for industry Amplicon Sales 44 0 1273 570 220 Website www amplicon co uk Email sales amplicon co uk Liebert UPS user manual Controls and Indicators 4 0 CONTROLS AND INDICATORS Buttons on the front panel display control the Liebert PSI XR Eight LEDs on the panel indicate the UPS s status Refer to Figure 15 and Table 2 Figure 15 Display and status indicators Load Level Battery Level 6 7 8 9 10 11 Table 2 Display and status indicators function legend Item Name Status Indicators Description 1 LED 1 AVR Boost UPS Operation in AVR Boost Mode 2 LED 2 AVR Buck UPS Operation in AVR Buck