MFCM-CM_Users_Manual
Contents
1. TestS cript01 txt Browse Remove Open Folder Terminal Interface SFCM Serial Shell gt Version 0 30 Script gt SRAM memory test passed gt Connection State Baud Rate _ Pl MFl UC Alarm Limit Pl MFZ UC Alarm Limit Pl MF3 UC Alarm Limit P1 MF4 UC Alarm Limit P1 MF1l Source Number P1 MFZ Source Number P1 MFS Source Number P1 MF4 Source Number calioffset 1 All save Delay Settings Run St write Del S 700 ep rite Delay mS Pause Read Delay m 100 _Save The program will load the last script file used To load another script file click the Browse button and select an existing script file in the Open dialog box which will appear The Script File Transfer window can also be opened from the Create Script File window by click the Run Script button in that window When opened this way the current script file in the Create Script File window will be loaded into the Script File Transfer window When you have the correct script file loaded click the Run button in the Script File Transfer window You should see the highlighter bar shift down in the Script list box and the commands being echoed in the Terminal Interface textbox in the Terminal window Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453
2. may be a good idea to create another script file to use for verifying that the new settings have been actually been saved in the MFCM after being configured This Verify Script File or Read File can be easily created from an existing setup script file as follows With the script file text in the Script File Text box e g after saving the script file in the procedure above click the Make Read File button This changes the text in the Script File Text box into commands for reading data instead of writing data to the MFCM Then save the text to a new file by clicking the Save Script File button In the Save As dialog box which will appear enter a new file name that distinguishes this as a Verify Script File or Read File Running Service Port Script Files This application can be used to run service port script files for configuring MFCM units and for verifying the settings after configuring This feature works only in RS 232 mode and when logged in to Security Level 2 To open the Script File Transfer window select Scripts gt Run Script in the main menu bar The window will open and the Terminal window should open a few seconds later as shown below Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Page 14 of 14 J Script File Transfer J Terminal Script Files C YVB MFCM CM WIP O01_ 1 4 0 0 Scripts
3. must be in RS 232 mode and logged in on Level 2 to use the MFCM Configurator Monitor application for upgrading or downgrading the MFCM firmware To see the Upgrade page as shown below click on the Upgrade tab on the Main Control window When the program is installed it is not configured with any Software Upgrade File paths which would appear in the combo box in the Upgrade Software page as shown below Software upgrade file paths can be added removed and saved by the program so that they will still be there when the program is closed and reopened later A new software upgrade file path can be added by dragging from Windows Explorer and dropping into the white Software Upgrade File combo box Then it can be saved for future use by clicking the Save button You can also add a new software upgrade file path by clicking the Browse button just below the Software Upgrade File combo box A new window will open as shown in Figure 10 2 below This is a Standard File gt Open dialog box that lets you browse through folders so that you can find and select the upgrade file that you need Click the Open button after selecting the correct upgrade file as shown below Once a new software upgrade file path selected the Save button below the white combo box will become enabled You can then save the new software upgrade file path in the list by clicking the Save button To see the software upgrade file paths in the list click on the down arrow butt
4. the PC Comm Settings dialog box above show the settings that will be applied in RS 485 Mode Note that these settings are disabled grayed out when RS 232 Mode is selected as shown in the figure above The Panel Window When the program is started and the polling begins the Panel window will appear as shown below Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Updated 07 16 09 8 0 Version 1 4 0 Page 5 of 14 il Panel Panel Upgrade Current Readings Amps Hain Feed 1 HHH GRE 28E RASS RASS BBs H T a e 1851 1999 185 1 1999 163 2 193 9 199 9 193 9 1939 aB 1999 B A es ae r E MFT a9 1 74 TT T1 Ja Figure 7 1 Panel Window Left clicking on any of the CB buttons on the Main Control window will cause the associated Main Feed window to open as shown in a later section below Multiple Main Feed windows can be opened at the same time Any of the Main Feeds can be disabled or enabled by right clicking on any of the corresponding CB buttons on the Main Control window and clicking the Disable or Enable popup as shown below Main Feed 2 nT CBS i CBE et 00 When a Main Feed is disabled its CB buttons will appear grey on the Main Control window as shown below When a Main Feed is enabled its CB buttons will appear green if no alarms or warnin
5. BRANCH SUBFEED MAIN FEED CIRCUIT MANAGEMENT Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Tel 800 238 5000 Fax 804 236 4047 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 2 0 3 0 4 0 Updated 07 16 09 Page 2 of 14 TABLE OF CONTENTS TABERE OF CONTENU euisechceccistetaicec ee sscasitnas a gave ageatamieacmeavatentostea soutien 2 TOC Program DosSchipUomM essi a aa a 2 20 PG System REGUTEMENS aaien a a a a aa a 2 90 INSANA es a a ncetasoaueian sumnanesnceaistalaiems 2 A AS AMUA EON ness e e aaa aeaa 2 50 PC COMM SOT ING Seater tite a a tease lana eu islea baat 4 6 0 General Comm Port Usage on the MFCM ccccccccccccecceeeeseeeeeeeeeaeeseeeeeeeessaeeeseeeeeesessaeeaeeseeeeseaas 4 730 TGP ANSI WINGOW vicmccss scones een a seit ciianse lol acct essdianasTeanit age a bars aedaseasereens 4 8 0 The Mam Feed WindOWS os2i5iteesctoicoes eoecedatoainecectdysheacahidanateln a a ae a aai 5 8 1 Changing Settings on the Main Feed WINdOWS cccccseeeeeeeeeeeeeeeeeeeeeeeeeeeaeeeceeeeeeesaeeseeeeeeeeeseaas 6 8 2 Resetting Latched Alarms and Warnings ccccccsseeeeceeeseeeeeeeecaeeseeeesaaeeeeeeesaeeeeeessaaeeeesesaeeeees 7 8 3 Calibrating tre MFOM iaie a a E 7 90 The System setings VVINGOW erossa a a a 8 10 0 Upgrading Downgrading the MFCM Firmware cccccsssscc
6. am you have the option of logging out or remaining logged in for the next use To log out click File gt Logout in the main menu bar Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Page 4 of 14 5 0 PC Comm Settings 6 0 7 0 Once you are logged in and you are connected to the DB9 RS 232 connector on an MFCM unit via a null modem serial cable the MFCM Configurator Monitor program should start polling the unit If not you may need to change settings on the PC Comm Settings dialog box File gt PC Comm Settings on the main menu bar as shown below PC Comm Settings Mode RS 232 Comm Port COM PC Baud Slave ID IP Addr Defauts Cancel Figure 5 1 The PC Comm Settings Dialog Box The program defaults to the RS 232 Mode and the COM1 Port as shown above If needed select a different Comm port and click the OK button to save the new setting General Comm Port Usage on the MFCM The MFCM is designed to be configured using the RS 232 Mode via the DB9 connector When using this mode the baud and Slave ID settings can be changed without affecting the communications The various baud and Slave ID settings on the MFCM affect only the RS 485 Mode via the terminal block In RS 232 Mode the baud is always 9600 and the Slave ID is always 7 The Baud and Slave ID settings on
7. ceceeeeeeeeeaeseceeeseeeeeeeeesseaeeeesesaaseeeeesaess 8 11 0 LGM VVINOOW se e vein cesasanshileaatwodlanehabinadrcdlamuaaaminisaheie diaminidaha males 11 12 0 Temporarily Closing the PCs Serial Port ccccccccssccceeescesessseeeeeeeceeeeeseceeesesseeeaeeceeeesesaaaeeeeees 11 13 0 Creating Service Port SCripl FIE Sansa a btadehegekehed ea teadiedeeiaeeeteieias 11 13 1 Procedure for Creating a New Script File ccccccccssssececcceesseceeeceeeeeeeeeeueeceeeseeaeeeeeeseaneeeessaas 12 13 2 Procedure for Creating a Verify Script File ccceeccceccssseeeeeeeaeeseeeeeseeeeseeseeeaeeeeesaeeeeeeeeas 13 14 0 Running Service Port Script Files ccccccccccccssssseecceeeeceeeeeeeeeeeeeeeeeeeeeeeeeeeseeeaseeeeeeeeessaeaaeeeeeeees 13 1 0 Program Description This program can be used for configuring and monitoring the data on the Cyberex Main Feed Circuit Monitor MFCM It can be used in either of the following communications modes RS 232 RS 485 or TCP Limited configuration can be done when in the RS 485 or TCP modes PC System Requirements e IBM Pentium or higher or compatible PC with a free serial port network interface card anda minimum screen resolution setting of 1024 by 768 e Microsoft Windows 2000 or higher Installation This program can be installed by double clicking the MFCM CM_Setup vX_X_X_X exe file provided and following the on screen instructions This setup program will put a shortcut on the Desktop a
8. e Select All button can be used to select or unselect all items in all columns 13 1 4 3 Enter the new value you want to for this item in the Value textbox This value will be used for all Main Feeds selected 13 1 4 4 Click the Add to Script button to add this item to the script file The new command line s should appear in the Script File Text box on the right hand side of the window 13 1 4 5 You can repeat this process to add other Main Feed Settings items if required 13 1 5 Current Offset Calibration This application provides the option of putting Current Offset Calibration for each panel into script file Perform the following steps to add Current Offset Calibration to the script file 13 1 5 1 To open the Calibration window click the Calibration button at the lower right hand side of the Main Feed Settings frame 13 1 5 2 Click the Add to Script button See below w Calibration Current Offset Calibration 13 1 6 Save the Script File as Follows 13 1 6 1 You can edit or delete text in the Script File Text box if necessary When ready save the 13 2 14 0 finished script file by clicking the Save Script File button A Save As dialog box will appear prompting you for a new file name for the new script file The default folder for saving script files is the Scripts subfolder in the application s folder Procedure for Creating a Verify Script File After a new script file has been created it
9. e main menu bar HEM Terminal E 5 Ed Connection State Terminal nberface SFCM Serial Shell Version 0 30 SRAM memory test passed Figure 11 1 Terminal Window When the Terminal window is open enter service port commands into the smaller lower textbox Temporarily Closing the PCs Serial Port The PCs serial port can be temporarily closed and reopened without exiting the MFCM Configurator Monitor application by selecting Connection gt Disconnect and Connection gt Connect on the main menu bar This is convenient to use when you want to temporarily communicate with the MFCM with another application Creating Service Port Script Files This application can be used to create service port script files to use for configuring MFCM units and for verifying the settings after configuring This feature works only in RS 232 mode and when logged in to Security Level 2 To open the Create Script File window select Scripts gt Create Script in the main menu bar The window will open as shown below Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Updated 07 16 09 a Create Script File System Settings ltem TLH Description B50 Modbus Slave ID O 9600 1 19200 2 57600 3 115200 Panel Settings Description Main Feed OnOFH Voltage Rating Frequency Rating Latching Set Bit m Hain Feed Settings ltem Selection Firs
10. elected click the Upgrade button to start the upgrade The File Transfer Progress bar should start growing and the Upgrade in process message should appear as shown below The Cancel button can be clicked to stop the upgrade if needed il Panel Panel Upgrade File Transter Progress Total bytes sent 13440 Throughput S68 bytes s Cancel Upgrade Status aat in process Software Upgrade File CAMFEM Smiem _ dsp v0 _30 bin ka Browse Remove Open Folder s Darasa Figure 10 4 Software Upgrade in Process The upgrade file transfer takes about 1 1 2 minutes After the file transfer has completed you should see the following message box pop up Cyberex MFCM Contigurator Monitor x The upgrade file transfer was successful After clicking the OK button you should see the following message box pop up After acknowledging these two messages the MFCM should start running with the new software upgrade loaded Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Page 11 of 14 Cyberex MFCM Configurator Monitor The upgrade was successfully verified The device will now be rebooted for the upgrade to take effect 11 0 Terminal Window 12 0 13 0 When logged in on Level 1 or 2 you can open the Terminal window as shown below by selecting Connection gt Terminal on th
11. gs exist for that circuit or will appear red or yellow if there are any alarms or warnings respectively Hain Feed 2 cea fea or ces feb of cee ec or The Main Feed Windows The metering alarm warning states and configuration settings for each Main Feed can be seen in its Main Feed window as shown below Active alarms and warnings will appear as red or yellow respectively Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 8 1 Page 6 of 14 These windows can be opened by either clicking a corresponding CB button on the Main Control window or by selecting it from View gt Main Feed x in the main menu bar il Main Feed 1 H T S ELE cae e 1939 199 9 185 1 199 9 99 9 fam sess Load Demand Rating Amps 400 iLine CT Scale Figure 8 1 Main Feed Window ne ean oon cw vats cn tie te ve Fray Hz 60 2 Rezet Meters r Calibration 1 Phase Current Scale w OV Alarm love Warning ji i j a a Co r UV Alarm ee ce Changing Settings on the Main Feed Windows When logged in on Level 1 or 2 you can change the settings in the Main Feed windows by double clicking in the setting you want to change When this is done enter the new number into the popup dialog box that appears as shown below Any setting inside the A
12. l 1 or 2 you can calibrate the MFCM using the controls on the Calibration frame on the Main Feed windows There are 7 calibration types that can be selected using the dropdown box in the Main Feed window as shown below For calibration instructions refer the proper Field Service procedure Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Page 8 of 14 9 0 10 0 Calibration 1 Phase Current Scale 1 Phase Curent Scale 2 Voltage Scale L N 3 Phase Curent Offset 4 Voltage Offset L N Time 6 Figure 8 3 Calibration Type Selection in the Main Feed Window The System Settings Window The system level configuration settings can be seen in the System Settings window as shown below This window can be opened by selecting View gt System Settings in the main menu bar lt System Settings x Voltage Rating 120 O Labehing Alans earnings Module Baud S600 r Slave ID 3 Figure 9 1 System Settings Window When logged in on Level 1 or 2 you can change the settings in the System Settings window The first three items are changed by double click just like previously mentioned for the settings on the Main Feed windows The remaining items can be changed by clicking the checkboxes or selecting a different value in the combo dropdown boxes Upgrading Downgrading the MFCM Firmware You
13. larms Warning and Settings frame can be changed like this Also when logged in on Level 1 or 2 you can reset the Min Max Currents and the KWH readings by clicking the Reset Meters button on the Main Feed window Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Page 7 of 14 8 2 8 3 i Main Feed 1 Metering Calibration i af Eg rr j 0 FTHD Curent 0 226 cance OV Alam ON nO NG IOV Warning OK GK GK o JUV Waring o OK Do Phase Loss oe a ok Neut CT Scale 22 Win Delay 5 5 z Figure 8 2 Changing Settings in the Main Feed Window Resetting Latched Alarms and Warnings When logged in on Level 1 or 2 and the Latching Alarms Warnings option is enabled see the Latching Alarms Warnings checkbox on the System Settings window you can reset latched alarms and warnings by double clicking on the red or yellow alarm warning boxes on the Main Feed window This will reset all of the alarms and or warnings that are common with a certain Modbus register These alarms warnings are grouped as follows e OC Alarms A B aC Neut e OC Warnings A B C e UC Alarms A B aC e Over KW Alarms A B C e All OV UV Alarms Warnings e Phase Loss Alarm Calibrating the MFCM Note This function is available only in RS 232 mode When logged in on Leve
14. nd in the Windows Start gt Programs folder The Initial Login When the program is started the main window will appear as shown in Figure 4 1 below Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Page 3 of 14 lt Panel Bee You are not logged in Current Readings Amps Hain Feed 1 fae ial x A 5 Tl D ih s Mi 8 alals TLE EEE A ELL Z n m m ae gael la nee T E a ER 535 331315 els mp me T E z ha I T E Figure 4 1 The Main Screen An initial login is required before using the program Once you are logged in you have the option of logging out between uses or remaining logged in for future uses To log in click File gt Login in the main menu bar The Login dialog box will open as shown below User Name Default Password ce There are three login levels as follows Default ray Level UserName pelawa Permissions Ez Default Default Permission to view meter readings and settings only n Permission to configure and calibrate the MFCM in addition to those of ss a Permission to upgrade downgrade the MFCM firmware to change the 2 Supervisor Super MFCM passwords and to use configuration script files in addition to those of Level 1 above When you are finished using the progr
15. on on the right hand side of the combo box as shown below in Figure 10 3 Then you can select the file that you want to use for the upgrade Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Page 9 of 14 Note To remove a path from the list simply select the path and click the Remove button in that frame When a software upgrade file is selected like shown in Figure 10 3 you can click the Open Folder button in the same frame to open its folder with the file selected in Windows Explorer This is handy for checking file dates etc il Panel File Transter Progress 0 Throughput ed Upgrade Status Software Upgrade File CAM FCM rmifcm dsp vO 30 bin ka Browse Remove Open Folder Upgrade Downgrade Figure 10 1 Upgrade Page w My Recent Documents e My Metwork File name mfcm_dsp_v0_30 bin T Places K Files of type Binary Files bir Cancel Figure 10 2 Browsing Software Upgrade Files Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Page 10 of 14 CAMFCH Smiem dep vO 29 bin CA MPFCM Arferm dep vO 30 bin bh Upgrade Figure 10 3 Selecting Saved Software Upgrade Files Once the software upgrade file is s
16. t Description Main Feed Current Rating On Off CT Scale OC warming Limit 2 OC Alarm Limit 2 UC Alarm Lirit 2 Warming Delay 5 Alarm Delay 5 Reset Minhas and EMH OM Alarm Limit 2 U Alarm Lirit 2 OM Warming Limit 2 LU Warming Lirit 72 Over Kwi KWA Lirit 4 Select All Calibration Neutral OC Limit 7 Neutral CT Scale Source Number Script Filename CAYESMFCM CMSWIPSOO1 v1 4 0 08S crptsT estS cript tat Figure 13 1 The Create Script File Window 13 1 Procedure for Creating a New Script File Script File Text B53 3 40 0 110 0 180 250 0 47 1 47 1 247 1 247 1 Baud Bate _ P1 MF1l UC Alarm Limit iFl1 F UC Alarm Limit P1 MFS UC Alarm Limit P1 MF4 UC Alarm Limit PIL HFL Source MNWumber PL MFZ Source Number PL HFS Source Number P1 HF4 Source MWumber Calioffser 1 All Save Clear Text Make Read File Save Script File Open Existing File Open Folder Run Script The following procedure can be used for creating a new script file Version 1 4 0 Page 12 of 14 KEk Exit 13 1 1 Clear the Script File Text Box 13 1 1 1 Clear the Script File Text Box by clicking the Clear Text button 13 1 2 Add System Settings to the Script File Text as Follows 13 1 2 1 Starting at the upper left hand corner of the window select a System Setting you want to add to the script file by clicking the item in the Item frame 13 1 2 2 Enter
17. the new value you want to for this item in the Value textbox 13 1 2 3 Click the Add to Script button to add this command to the script file The new command line should appear in the large Script File Text box on the right hand side of the window Note The text in the Script File Text box can be manual edited or deleted like using Notepad 13 1 2 4 You can repeat this process to add other System Settings items if required 13 1 3 Add Panel Settings to the Script File Text as Follows 13 1 3 1 Select a Panel Setting you want to add to the script file by clicking the item in the Panel Settings Item frame 13 1 3 2 Enter the new value you want to for this item in the Value textbox 13 1 3 3 Click the Add to Script button to add this item to the script file The new command line should appear in the Script File Text box on the right hand side of the window Thomas amp Betts Power Solutions 5900 Eastport Boulevard Richmond VA 23231 4453 Cyberex MFCM Configurator Monitor User s Manual Version 1 4 0 Updated 07 16 09 Page 13 of 14 13 1 3 4 You can repeat this process to add other System Settings items if required 13 1 4 Add Main Feed Settings to the Script File Text as Follows 13 1 4 1 Select a Main Feed Setting you want to add to the script file by clicking the item in the Main Feed Settings Item frame 13 1 4 2 In the Selection frame select the Main Feed s you want to add by checking the appropriate checkboxes Th