Home
OneWireless-XYR 6000 Transmitters
Contents
1. SINGLE THERMOCOUPLE OR DI TWO THERMOCOUPLE OR DI CONNECTION CONNECTION l A par Geh m en Pen amp o o e 1 C 1 7 E rer x BL Ca Ki ol Mim SI mi x UEM SE GE 4 JUMPER WIRES TC OR DI MAY BE GROUNDED TYPE ER WIRES ONLY OME T C OR DI MAY BE GROUNDED TYPE SINGLE THREE WIRE RTD 2 JUMPER WIRES ONLY ONE TAC OR DI MAY BE GROUNDED TYPE TWO THREE WIRE RTDs TIC OR DI MUST BE FLOATING UNGROUNDED TYPE IS FIELD WIRING PARAMETERS WITH OPTION DC Ca 2 7 UF 2 Comm La 100 mH Lou WITH OPTION BA Ca 93uF gt C TIC OR DI MUST BE FLOATING s Em UNGROUNDED TYPE a La 100 mH L caus NOTES 1 Shielded thermocouple mV or RTD Ohms cable is required for EMC conformity and is recommended for all remote sensor installations The shield shall be grounded at the transmitter end only When remote mounted probe sensors are used and the shield is grounded at the probe the shield shall not be connected at the transmitter end Duplex redundant sensors that are bonded to the probe are not permitted All thennocouple m inputs and RTD Ohms inputs must be insulated from ground the probe and from each other as noted above Jumper wires the same gauge and stranding as the thermocouple wires are required for single and dual thermocouple input combinations Digital input switches DI must be dry contact type simple apparatus and property segregated from all other sources of power c amp M 90033269 S
2. BA Battery DC 24Vdc Supply Maximum Process Temperature eo AME 125 C 85 C Probe Rating Sensor Rating Process Limits BA Battery DC 24Vdc Supply Probe Probe Thermo wels No ess ee OOO MAWP Rating MAWP Rating Maximum Allowable Pressure MAWP CSA FM ATEX Meter Body IECEx amp SAEx MAWP Rating BA Battery DC 24Vdc Supply Hazardous Location Protection Type CSA FM ATEX XP IS NI IS NI IS NI XP IS NI XP IS NI XP IS NI IECEx amp SAEx Non Sparking Non Sparking Non Sparking Non Sparking Non Sparking Non Sparking Men cr DNDN 40 to 85 C 30to 85 C 40to 85 C 40 to 85 C 40 to 85 C 2 Zonen 1 amp 2 DC 24Vde CSA amp FMDiv1 Div f 7 m Je elle Supply 2 Zone0 1 amp 2 40 to 80 C 40 to 80 C 30 to 80 C 40 to 809C 40 to 80 C 40 to 80 C Wireless Transmitters Miu SAEX 40to 70 40to 70 C 30to 70 40to 70 C 40to 70 C 40 to 70 C en BA Battery imits AUS 2 SAEX 4010 84 C 40to 84 C SOto 84 C 4010 84 C 40 to 84 C 40 to 84 C ATEX IEGEX 8 SAEX _4010 70 C 40 to 702 30to 70 C 40to 70 C 40to 70 C 40 to 70 C Zone 0 amp 1 DC 24Vde Supply ATEX IECEx amp SAE ps X _40t0 80 C 40to 80 30 to 802 4010 80 C 4010 80 C 40 to 80 C 4 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2
3. ELBOW ANTENNA XYR 6000 TRANSMITTER STRAIGHT TYPICAL ANTENNA REMOTE ven lf CONNECTOR LISHTNING SURGE ARRESTOR ALTELECON AL NFNFB 8 gt 0018279 090 Honeywell SCALE NONE REV D DATE 091610 SH 10 of 11 Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 89 October 2010 6 Certification Installation Requirements REMOTE ANTENNA CABLES LE IE CABLE A LMR 400DB 50018110 001 1m TNC R 50018110 003 3m 50018110 010 10m CABLE B LMR 400DB TYPE N MALE 50018278 001 1m TYPE N MALE 50018278 003 3m 50018278 010 10m REMOTE ANTENNA XYR 6000 WIRELESS TRANSMITTER REMOTE ANTENNA XYR 6000 Cable B WIRELESS TRANSMITTER m CableA LIGHTNING SURGE ARRESTOR CABLE PARAMETERS LIGHTNING SURGE ARRESTOR CABLE A B LENGTH CAPACITANCE PARAMETERS im 78 4 pF 0 2 uH CAPACITANCE 1 pF 3m 235 2 pF 0 6 uH INDUCTANCE 10 nH 10m 784 pF 2 0 uH Honeywell 90 OneWireless XYR 6000 Transmitters Quick Start Guide SCALE NONE REV D DATE 09 16 10 SH 11 of 11 Revision 9 October 2010 Sales and Service For application assistance current specifications pricing or name of the nearest Authorized Distributor contact one of the offices below ASIA PACIFIC Malaysia mE Control Products Honeywell Engineering Sdn Bhd Asia Pacific Headquarters Phone 65 6355 2828 Fax 65 6445 3033
4. a WM py 90036277 Honeywell A4 84 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings WIRELESS UNIVERSAL I O STUW700 amp STUW701 HAZARDOUS LOCATION Ex ia IIB T4 Ta s 70 C DIP A20 IP66 T90 C Ex nA nL IIC T4 Ta s 84 C s 80 C WITH OPTION DC DIP A22 IP66 T90 C AMBIENT LIMITS 40 s Ta s 84 C s 80 C WITH OPTION DC 2 TUW700 POSSIBLE CONNEC TIONS TC mV DIGITAL DIGITAL OUTPUT ONLY d a HIGH LEVEL ANALOG INPUT amp DIGITAL INPUT AND T C DIGITAL OUTPUT ENTITY FIELD WIRING PARAMETERS PARAMETERS Ui Vmax 30 V Ca 2 7 pF 2 Coane Ii Imax 125 mA La 100 mH Le Pi 1 0 W LJ 6 8 nF Li 0 1 uH NOTES 1 Shielded HLAI DI DO thermocouple mV or switch input cable is required for EMC confommiby and is recommend ed for all installations The shield shall be grounded atthe transmitter end only If the shield is grounded at the switch remote HLAI transmitter lacation or remote DO supply the shield shall not be connected at the Wireless transmitter end Honeywes i SCALE NONE REV D DATE 08 16 10 SH 6 of 11 Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 85 October 2010 6 Certification Installation Requirements XYR 6000 MODEL CETW6000M W WIRELESS CORROSION TRANSMITTER AND CETW6000M D SmartCET CORROSION DATALOGGER Ex ia IIB T4 Ta 70 C DIP A20 IP66 T90
5. 24 viii OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Contents Symbol Definitions 3 9 COPFOSION ue EE 26 PODE MOUNUNGIOCAION gt OOO T TOO TS TEE 26 miele INS Tall al e REIN TEE 29 CONHECE WINING memi 30 4 ANTENNA ADJUSTMENT AND MOUNTING eese 31 4I heguiremenls EE 31 Radio installation requirements occccccconncnncccnnnnnncnnnnncnnnnonnnnonnnonnncnnnn nennen nnne nnn nnns nain nnns na aser n rss snas nnns sina nnn nnns 31 4 2 integral antenna ien eie cese ous e reU elite 31 zoe ee HEIL ERE 32 Straight eR R ee 32 43 Re m teantenna eege Ee 33 Outdoor EE ee Le EE 33 Ghoosing a Mounting Location n ne 34 See ee ee ee ue ee M CE MEE ME 34 MOUNLNG TNE ANIEHNa MERE RT E Ew 35 Directional Mounting Procedure RD TD 37 Omnidirectional MOUNTING pr cedure u ken 38 GrOUnGING TNE ANCONA EE 38 CE ag A CA ET 40 5 1 Battery Power ODHOD vacancia ea 40 COM CR TEE 40 IS Battery Holder 50025288502 2 oisi bati cus us ed ee 41 IS Ball ry Packs 500475 1 7250 aan ae seele 43 24 Vdc Power Supply Option DC System Diagramm 45 5 2 jDiSplay sequeriG6 a eee deseen aa eben den wall see 46 S PROVISIONING mec 46 6 CERTIFICATION INSTALLATION REQUIREMENTS 47 6 1 Certification Drawings sia en nu
6. 87 6 Certification Installation Requirements SYSTEM DIAGRAM E HAZARDOUS LOCATION Ex ia IIB 14 Ta 70 C DIP A20 IP66 T90 C Ex nA nL IC T4 Ta 80 C DIP A22 IP66 T90 C AMBIENT LIMITS 40 lt Ta lt 80 C xyR 6000 152m 500 ft M TRANSM ITTER Maximum Cable er nF TYPICA L and Maximum Cable Inductance 0 01mH See Note 5 Terminate and insulate shield as close to terminal block as possible Cable to be shielded twisted pair 7 with total loop resistance 6 64 NON HAZARDOUS or ZONE 2 LOCATION MTL 728P IECEx BAS 05 0019 MTL 7728P IECEx BAS 004 0025 Ex ia IIB 209C Ta 600C Ex ia DC 209C Ta 60 C MTL 7728P IECEx BAS 05 0036X Ex ia IIC 209C lt Ta 609C BARRIER CO IT LOAD PARAMETER RMINAL E d Uo 28 V Io 171 m Po 1 2 W Rmin 234 6 Z2 Co 2 15 pF 14 mH LR 340 uH x n p CIE RATED FOR THE ENVIRONMENT WHERE INSTALLED MTL 28P MIL 7728P 24 Vde Supply 21 Vmin 25 0 Vmax GROUND SHIELD AT THIS END ONLY NON HAZARDOUS LOCATION 24 Vdc n Supply zw 4 1 6 0 V min i IT GROUND SHIELD AT 28 0 Vmax di THIS END ONLY 11 KI Honeywell 50036277 AERE 88 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings REMOTE ANTENNAS MUST BE PASSIVE ELEMENTS ONLY
7. 1 Only lightning surge arrestors determined to be simple apparatus may be installed Honeywell SCALE NONE REV E DATE 09 24 10 Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 57 October 2010 6 Certification Installation Requirements COPYRIGHT 2010 HONEYWELL INTERNATIONAL INC NEITHER THES DOCUMENT NOR THE PERL l INFORMATION CONTAINED HEREIN SHALL BE REPRODUCED USED OR DISCLOSED TO OTHERS WITHOUT THE WRITTEN AUTHORIZATION OF HONEYWELL USE DUPLICATION OR REVISION amp DATE APPD DISCLOSURE OF THIS DOCUMENT IS SUBJECT TO THE RESTRICTIONS SET FORTH IN A WRITTEM AGREEMENT NOTHING CONTAINED HEREIN SHALL BE CONSTRUED AS 09 24 10 CONFERRING BY IMPLICATION ESTOPPEL OR OTHERWISE ANY LICENSE TO ANY PATENT E ECO 0069377 VM TRADEMARK COPYRIGHT OR OTHER INTELLECTUAL PROPERTY RIGHT OF HONEYWELL OR ANY THIRD PARTY XYR 6000 WIRELESS TRANSMITTERS CSA CERTIFIED amp FM APPROVED DIVISION 1 ZONE 0 INSTALLATION CONTROL DRAWING NOTES 1 intrinsically safe installation shall be in accordance with the Canadian Electrical Code CEC part Section 18 for Canada ANSI NFPA 70 NEC Articles 504 and 505 for the USA and ANSINSA RP12 06 01 2 CSAorFM ENTITY approved apparatus shall be installed in accordance with the manufacturer s Intrinsic Safety Control Drawing or shall be Simple Apparatus Simple Apparatus are devices that will neither generate nor store more tha
8. 2 this device must accept any interference received including interference that may cause undesired operation i The installer of this radio equipment must ensure that the Zar antenna is located or pointed such that it does not emit RF Industry Canada IC or fields in excess of Health Canada limits for the general population consult Safety Code 6 obtainable from Health IC 5731 50025034 Canada s web site www hc sc gc ca rpb Radio Frequency RF statement To comply w th FCC s and Industry Canada s RF exposure requirements the following antenna installation and device operating configurations must be satisfied e Remote Point to Multi Point antenna s for this unit must be fixed and mounted on outdoor permanent structures with a separation distance between the antenna s of greater than 20cm and a separation distance of at least 20cm from all persons e Remote Fixed Point to Point antenna s for this unit must be fixed and mounted on outdoor permanent structures with a separation distance between the antenna s of greater than 20cm and a separation distance of at least 100cm from all persons e Furthermore when using integral antenna s the XYR 6000 Wireless Transmitter unit must not be co located with any other antenna or transmitter device and have a separation distance of at least 20cm from all persons European Union restriction The XYR 6000 Wireless Transmitters are in conformity with the applicable portions
9. Attach transmitter to bracket Align appropriate mounting holes in transmitter with holes in bracket and secure the transmitter to the bracket with bolts and washers provided If the meter body is hexagonal you must use the additional bracket supplied If meter body is round discard the bracket Transmitter type Attachment to bracket Example DP type with double ended Alternate mounting holes process heads and or remote in end of heads seals Dual head GP Mounting holes in end of process head In line GP and AP LGP Smaller U bolt model Smaller U bolt Smaller U bolt Smaller U bolt Smaller U bolt Smaller U bolt 14 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 2 Transmitter Mounting 2 6 Rotate transmitter housing 2 6 Rotate transmitter housing You can rotate the transmitter for better viewing access or antenna position Loosen set screw see A in Figure 2 8 on outside neck of transmitter one full turn Rotate transmitter housing up to 180 degrees in either direction to desired position Do not rotate the housing past 180 degrees in any direction or you CAUTION could damage the internal wiring Tighten set screw CAUTION Do not rotate more than 180 Figure 2 8 Rotating transmitter housing 2 Rotate display If the transmitter s mounting is such that the display is not horizontal you can rotate the display in 90 degree increments to
10. SITW820 SITW830 Wireless Temperature Transmitter Transmitter Integrally Mounted to Thermowell STTWB840 or Probe Assembly STIWODO Wireless High Level Input Interface 4 20 mA Analog Input cETW6eODOM w SmartCET Wireless Transmitter Millrvolt Input from Remote Mounted Corrosion Monitoring Corrosion Probe Millivolt Input from Remote Mounted CETWSG000M D SmartCET Corrosion Data Logger Corrosion Probe Data via IrDA Port There is no Antenna for this version The above listed wireless transmitters may include an mni directional or unidirectional high gain antenna The high gain antenna may be installed remote from the XY R 6000 with the cable length not to exceed 20m The antenna cable shield shall be bonded to earth ground IS Entity parameters for remote antennas cables amp lightning arrestor Ca 43 uF La 0 1 mH 90021730 Honeywell Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide October 2010 65 6 Certification Installation Requirements 24Vdc IS POWER SUPPLY OPTION DC C S SYSTEM DIAGRAM HAZARDOUS CLASSIFIED LOCATION CLASS DIV 1 GROUPS A B C D CLASS II GROUPS E F amp G CLASS III T4 CLASS ZONE 0 Ex AEx ia GROUP IIC T4 AMBIENT LIMITS 40 s Ta s 80 C XYR 6000 152m 500 ft Max TRAN S Mi ITTER Maximum Cable Capacitance s SOnr TY P C AL and Maximum Cable Inductance D 01mH See Note 5 Terminate and insulate shield as close
11. AEx nA GROUP IIC T4 AMBIENT LIMITS 30 lt Ta lt 85 C lt 80 C WITH OPTION DC RED MEER AE d au 7 WHITE J I SERI BLACK TO CORROSION I I PROBE ASSEMBLY PROBE AND PROCESS ELECTRODES MUST BE PASSIVE ELEMENTS ONLY PROBE AND CABLE PARAMETERS MUST NOT EXCEED 100 pF Corone Cease AND 100 mH l proge l capLE OTE Probes used with the Corrosion Transmitter must be acceptable to the authority having jurisdiction with respect to pressure and temperature rating Honeywell SCALE NONE REV E DATE 09 24 10 Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 53 October 2010 6 Certification Installation Requirements The following models may be supplied with internal battery power or externally supplied 24Vdc only when connected per the following system diagram NOTE AYR 6000 ambient limits with 24V Power Supply are 40 C to 80 C Series 900 Wireless Transmitter Dual Head Gage Pressure GP STE AD Senes 900 Wireless Transmitter 0 100 psi 0 7 bar Differential Pressure DP pu STDW974 0 3000 psi 0 210 bar STGWS4L 0 500 psi 0 35 bar SIGWS7L 0 3000 psi 0 210 bar Senes 900 Wireless Transmitter er In Line Gage amp Absolute Pressure Ziel TESTS i STGWSSL 0 10 000 psig 0 690 bar 0 500 psi 0 35 barA Transmitter Only with Remote Sensors 3 VC s or 2 RTD s Wireless Temperature and Digital Transmitter Only with Remote Sensors Input Transmitter 1 T C AND 2 D
12. Phone 48 22 6060900 FAX 48 22 6060901 Portugal Honeywell Portugal Lda Phone 351 21 424 5000 FAX 351 21 424 50 99 Romania Honeywell Bucharest Phone 40 0 21 2316437 FAX 40 0 21 2316439 Russian Federation RF ZAO Honeywell Phone 7 095 796 98 00 FAX 7 495 797 99 64 Slovak Republic Honeywell s r o Phone 421 2 58247 410 FAX 421 2 58247 415 Spain Honeywell S A Phone 34 0 91313 61 00 FAX 34 0 91313 61 30 Sweden Honeywell AB Phone 46 8 775 55 00 FAX 46 8 775 56 00 Switzerland Honeywell AG Phone 41 18552448 FAX 41 1 855 24 45 Turkey Honeywell Turkey A S Phone 90 216 578 71 00 FAX 90 216 575 66 35 Ukraine Honeywell Tel 380 44 201 44 74 Fax 380 44 201 44 75 United Kingdom Honeywell Control Systems Ltd Phone 44 0 1344 655251 FAX 44 0 1344 655554 MIDDLE EAST Abu Dhabi UAE Middle East Headquarters Honeywell Middle East Ltd Phone 971 2 4041246 FAX 971 2 4432536 Sultanate of Oman Honeywell amp Co Oman LLC Phone 968 24 701153 Ext 33 FAX 968 24 787351 Saudia Arabia Honeywell Turki Arabia Ltd Jubail Office Phone 966 3 341 0140 Fax 4966 3 341 0216 Honeywell ATCO Dammam Office Phone 0096638304584 Fax 0096638338059 Kuwait Honeywell Kuwait KSC Phone 965 242 1327 to 30 Fax 4965 242 8315 And Phone 4965 326 2934 1821Fax 4965 326 1714 AFRICA Mediterranean amp African Distributors
13. WITH OPTION DC Las 2 7 UF gt Conta La 100 mH L css WITH OPTION BA La 100 mH L casas TAC OR DI MUST BE FLOATING UNGROUNDED TYPE NOTES 1 Shielded thermocouple mV or RTD Ohms cable is required for EMC conformity and is recommended for all remote sensor installations The shield shall be grounded at the transmitter end only When remote mounted probe sensors are used and the shield is grounded at the probe the shield shall not be connected at the transmitter end Duplex redundant sensors that are bonded to the probe are not permitted All thermocouple mV inputs and RTD Ohms inputs must be insulated from ground the probe and from each other as noted above Jumper wires the same gauge and stranding as the thermocouple wires are required for single and dual thermocouple input combinations Digital input switches DI must be dry contact type simple apparatus and property segregated from all other sources of power be m a w 50021730 Honeywell Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 61 October 2010 6 Certification Installation Requirements WIRELESS TEMPERATURE AND DIGITAL INPUT DI TRANSMITTERS STTW400 STTW401 STXW500 STTW820 STTW830 amp STTW840 HAZARDOUS CLASSIFIEDJLOCATION CLASS DIV 1 GROUPS A B C D CLASS II DIV 1 GROUPS E F amp G CLASS Ill DIV 1 T4 CLASS I ZONE 0 EwAEX ia GROUP IIC 14 AMBIENT LIMITS 40 Ta 85 C lt 80 C WITH OPTION
14. Wiring for calibration XYR6000 Universal I O Wiring Diagrams for Al DI Model STUW700 PV1 Possible Connections T C DI or HLAI PV 1 0 20 4 20 mA Input SM AD et PV1 PV2 Possible Connections T C DI or HLAI 0 20 4 20 mA Input 24V Amir PV3 Possible Connections HLAI only 0 20 4 20 mA Input 1 Note any combination of the above are allowed For example PV1 is a DI PV2 is 4 20mA PV3 is 0 20mA Or PV1 is 0 20mA PV2 is a T C PV3 is 0 20mA Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 23 October 2010 3 Process insertion 3 4 Universal I O Wiring for calibration XYR 6000 Universal I O Wiring Diagrams for Al DI DO Model STUW701 PV1 Possible Connections T C DI or HLAI PV 1 0 20 4 20 m Input 2 PV 1 mtr PV2 Possible Connections T C DI or HLAI 0 20 4 20 m Input ais ve Ow D a PV2 24V Amtr HO PV3 Possible Connections DO only Voltage Current Supply vum 30v DC max Supply 30V Peak AC 21 2vrms max Note any combination of the above are allowed For example PV1 is a DI PV2 is 4 20mA PV3 is DO Or PV1 is 4 20mA PV2 is a T C PV3 is DO 24 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 3 Process insertion 3 4 Universal I O SI TW 401 T C AND 2 DI CONNECTION TB1 Ee ve inii Al PV1 FG CS TB2 S2 S1 2 JUMPER WIRE
15. undesired operation Industry Canada IC The installer of this radio equipment must ensure that the antenna is located or pointed such that it does not emit RF fields in excess of Health Canada limits for the general population consult Safety Code 6 obtainable from Health Canada s web site www hc sc gc ca rpb 4 2 Integral antenna A Revision 9 October 2010 WARNING POTENTIAL ELECTROSTATIC CHARGING HAZARD The integrally mounted antenna shroud is made of Teflon and has a surface resistance greater than 1Gohm per square When the XYR 6000 transmitter is installed in potentially hazardous locations care should be taken not to electrostatically charge the surface of the antenna shroud by rubbing the surface with a cloth or cleaning the surface with a solvent If electrostatically charged discharge of the antenna shroud to a person or a tool could possibly ighite a surrounding hazardous atmosphere OneWireless XYR 6000 Transmitters Quick Start Guide 31 4 Antenna adjustment and mounting 4 2 Integral antenna Elbow ANTENNA RLDTATILINAL ADJUSTMENT SCREW M3 SOCKET SET SCREW HEX KEYSIZE loam 4 Figure 4 1 Elbow antenna adjustment 2 dBi Antenna Configuration Shown If your model has the integral elbow antenna you can adjust it to improve reception Typically pointed straight up gives best performance but your installation may vary Loosen the 1 5mm set screw located near the antenna base Rotate a
16. 24 Weight Transmitter model Weight STDWOxx 11 lbs 5 kg STGW9x4 STGW9xL 7 Ibs 3 2 kg STAW94L STIW400 6 Ibs 2 7 kg STTW40x STTW500 STIW600 STUW700 STUW701 STTW8x0 CETW6000M 2 2 Dimensions 174 1 6 85 127 0 10 0 104 is 226 6 3 00 2 16 4 10 9 00 CLEARANCE CLEARANCE FOR FOR CAP CAP REMOVAL 8 REMOVAL amp BATTERY REPLACEMENT DISPLAY MANIPULATION CONDUIT CONNECTION OPTIONALLY 1 2 NPT OR M20 EXTERNAL GROUND Figure 2 1 Temperature DI Multi DI HLAI Corrosion transmitter dimensions 6 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 2 Transmitter Mounting 2 2 Dimensions Figure 2 2 Universal UO Temperature DI Multi DI HLAI Corrosion antenna dimensions 1 Add 139 0mm 5 47 in To these dimensions for transmitters supplied with 4 dBi Antenna option Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 7 October 2010 2 Transmitter Mounting 2 2 Dimensions 174 6 85 127 0 28 6 5 00 9 00 CLEARANCE CLEARANCE FOR FOR CAP CAP REMOVAL 4 REMOVAL amp BATTERY REPLACEMENT DISPLAY MAN PULAT ON ONDUIT CONNECTION OPTIONALLY I WPT OR M 123 3 4 85 PTIONAL elo VENT DRAIN 8 27 EXTERNAL BR POSITION GROUND b 36 8 Y 45 HIGH PRESSURE LOW PRESSURE CONNECTION CONNECTION 1 4 WPT 4 NPT 34 2 13 120 1 4 75 Figure 2 3 DP DHGP Pressure transmitter dimensions 8 OneWireless XYR 6000 Transmitters Quick Start
17. 6000 WIRELESS TRANSMITTERS NOTES 1 Electrical apparatus and circuits can be used in zone 0 if they are in accordance with IEC 60079 11 category ia intrinsic safety the applicable parts of IEC 60079 0 and with the requirements of IEC 6007914 12 3 see also 5 2 4 2 Electrical apparatus and circuits can be used in zone 2 if they are in accordance with IEC 60079 15 the applicable parts of IEC 60079 0 and with the requirements of IEC 60079 14 12 2 A ATEX certified intrinsically safe apparatus shall be installed in accordance with the manufacturer s Intrinsic Safety Control Drawing or shall be Simple Apparatus Simple Apparatus are devices that will neither generate nor store more than 1 2W 0 14 25mW or 2014 such as switches thermocouples and RTDs ATEX certified non sparking apparatus shall bee installed per this control drawing 4 Intrinsic Safety system parameters shall comply with the following Uo Ui lo li Coz Ci Ccable Lo gt Li Leable Po x Pi Where two separate barrier channels are required one dual channel or two single channel barners may be used where in either case both channels have been Certified for use together with combined entity parameters that meet the above equations 5 System Parameters AYR 6000 and Field Transmitter Ui Uo li gt lo AYR 6000 Ci Field Transmitter Ci Ccable Associated Apparatus Co AYR 6000 Li Field Transmitter Li Lcable Associated Apparatus Lo D When the
18. 7160 8 1 3 6730 7228 Honeywell Japan Inc New Pier Takeshiba South Tower Building 20th Floor 1 16 1 Kaigan Minato ku Tokyo 105 0022 Japan Global TAC JapanJA25 honeywell com Honeywell Solution Support Online http www honeywell com ps Elsewhere Call your nearest Honeywell office Training Classes Honeywell Automation College http www automationcollege com Revision 9 October 2010 OneWireless XYR 6000 Transmitters Quick Start Guide Notices and Trademarks References Notices and Trademarks Symbol Definitions Symbol Definitions The following table lists those symbols used in this document to denote certain conditions Symbol Definition n ATTENTION Identifies information that requires special consideration TIP Identifies advice or hints for the user often in terms of performing a task CAUTION Indicates a situation which if not avoided may result in equipment or work data on the system being damaged or lost or may result in the inability to properly operate the process CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices CAUTION symbol on the equipment refers the user to the product manual for additional information The symbol appears next to required information in the manual result in serious injury or death WARNING symbol on the equipment refers the user to
19. Asia Pacific Global Technical Support Field Instruments Phone 65 6580 3156 Fax 65 6445 3033 Process Instruments Phone 603 76950 4777 Fax 603 7958 8922 Phone 60 3 7950 4776 Fax 60 3 7958 8922 New Zealand Honeywell Limited Phone 64 9 623 5052 Fax 64 9 623 5060 Toll Free 0800 202 088 Philippines Honeywell Systems Philippines Inc Phone 63 2 633 2830 Australia 31 Honeywell Limited 636 1661 62 Phone 61 7 3846 1255 Fax 63 2 638 4013 FAX 61 7 3840 6481 Toll Free 1300 36 39 36 Toll Free Fax 1300 36 04 70 Singapore Honeywell Pte Ltd Phone 65 6580 3278 Fax 65 6445 3033 China PRC Beijing Honeywell China Inc Phone 86 10 8458 3280 Fax 86 10 8458 4650 South Korea Honeywell Korea Co Ltd Phone 822 799 6315 Fax 822 792 9015 China PRC Shanghai Honeywell China Inc Phone 86 21 5257 4568 Fax 86 21 6237 2826 Thailand Honeywell Systems Thailand Ltd Phone 662 693 3099 FAX 662 693 3089 China PRC Chengdu Honeywell China Inc Phone 86 28 8678 6348 Fax 86 28 8678 7061 Taiwan R O C Honeywell Taiwan Ltd Phone 886 2 2245 1000 FAX 886 2 2245 3241 China PRC Xi an Honeywell China Ltd SE Asia Countries see Honeywell Pte Ltd Xi an Singapore Phone 86 29 8833 for Pakistan Cambodia 7490 Guam Laos Myanmar Fax 86 29 8833 7489 Vietnam East Timor China PRC
20. DC SINGLE TWO WIRE RTD TWO TWO WIRE RTD JUMPER WIRE T C OR DI MUST BE FLOATING T C OR DI MUST BE FLOATING UNGROUNDED TYPE UNGROUNDED TYPE IS FIELD WIRING PARAMETERS WITH OPTION DC La 100 mH L cas WITH OPTION BA Ca 9 3 UE 2 Come La 100 mH Less NOTES 1 Shielded thermocouple mVv or RTD Ohms cable is required for EMC conformity and is recommended for all remote sensor installations The shield shall be grounded at the transmitter end only 2 When remote mounted probe sensors are used and the shield is grounded at the probe the shield shall not be connected at the transmitter end 3 Duplex redundant sensors that are bonded to the probe are not permitted All thermocouple mV inputs and RTD Ohms inputs must be insulated from ground the prabe and from each other as noted above 4 Jumper wires the same gauge and stranding as the thermocouple wires are required for single and dual thermocouple input combinations 5 Digital input switches DI must be dry contact type simple apparatus and property segregated from all other sources of 50021730 Honeywell 62 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings WIRELESS UNIVERSAL I O STUW700 amp STUWT701 HAZARDOUS CLASSIFIED LOCATION CLASS DIV 1 GROUPS A B C D CLASS II DIV 1 GROUPS EF amp G CLASS Ill DIV 1 T4 CLASS ZONE 0 Ex AEx ia GROU
21. DOCUMENT IS SUBJECT TO THE RESTRICTIONS SET FORTH IN A 09162010 ECO 0069377 VM IECEx INTRINSICALLY SAFE ia AND NON SPARKING n INSTALLATION CONTROL DRAWING XYR 6000 WIRELESS TRANSMITTERS NOTES 1 Electrical apparatus and circuits can be used in zone 0 if they are in accordance with IEC 60079 11 category ia intrinsic safety the applicable parts of IEC 60079 0 and with the requirements of IEC 60078 14 12 3 see also 5 2 4 2 Electrical apparatus and circuits can be used in zone 2 if they are in accordance with IEC 60079 15 the applicable parts of IEC 60079 0 and with the requirements of IEC 60079 14 12 2 A IECEx certified intrinsically safe apparatus shall be installed in accordance with the manufacturer s Intrinsic Safety Control Drawing or shall be Simple Apparatus Simple Apparatus are devices that will neither generate nor store more than 1 2W 0 14 25mW or 20uJ such as switches thermocouples and RTDs IECEx certified non sparking apparatus shall bee installed per this control drawing 4 Intrinsic Safety system parameters shall comply with the following Uo Ui lo li Co Ci Ccable Lo Li Leable Po Pi Where two separate barrier channels are required one dual channel or two single channel barners may be used where in either case both channels have been Certified for use together with combined entity parameters that meet the above equations 5 System Paramete
22. Definition The Factory Mutual Approval mark means the equipment has been rigorously tested and certified to be reliable The Canadian Standards mark means the equipment has been tested and meets applicable standards for safety and or performance The Ex mark means the equipment complies with the requirements of the European standards that are harmonised with the 94 9 EC Directive ATEX Directive named after the French ATmosphere EXplosible For radio equipment used in the European Union in accordance with the R amp TTE Directive the CE Mark and the notified body NB identification number is used when the NB is involved in the conformity assessment procedure The alert sign must be used when a restriction on use output power limit by a country at certain frequencies applies to the equipment and must follow the CE marking The C Tick mark is a certification trade mark registered to ACMA Australian Communications and Media Authority in Australia under the Trade Marks Act 1995 and to RSM in New Zealand under section 47 of the NZ Trade Marks Act The mark is only to be used in accordance with conditions laid down by ACMA and RSM This mark is equal to the CE Mark used in the European Union N314 directly under the logo is Honeywell s unique supplier identification number OneWireless XYR 6000 Transmitters Quick Start Guide vii Symbol Definitions Contents SUPPO and CONTACL info a re ee iv e INTRODUCTION sarna 1 Se Ce E E
23. Guide Revision 9 October 2010 2 Transmitter Mounting 2 2 Dimensions 08 0v2 ILISOd V NIVYO INGA Y NO L d0 A M Ni Dl n A in Win m d F E 1 E FR FOR 1 2 NPT OPTIONAL were Figure 2 4 DP DHGP Pressure antenna dimensions 1 Add 139 0mm 5 47 in To these dimensions for transmitters supplied with 4 dBi Antenna option Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 9 October 2010 2 Transmitter Mounting 2 2 Dimensions LE 1 CO 4 CLEARANCE CAP REMOVA DISPLAY MANIPULAT 77 P EXTER e d GROUND 1 91 CLEARANCE FOR CAP REMOVAL 4 BATTERY REPLACEMENT CONDUIT CONNECT ON OPTIONALLY 2 NPT OR M20 Figure 2 5 GP AP Pressure transmitter dimensions 10 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 2 Transmitter Mounting 2 2 Dimensions Figure 2 6 GP AP Pressure antenna dimensions 1 Add 139 0mm 5 47 in To these dimensions for transmitters supplied with 4 dBi Antenna option Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 11 October 2010 2 Transmitter Mounting 2 3 Transmitter location 2 3 Transmitter location Pressure models Suggested location Explanation Gases Above the gas line The condensate drains away from the transmitter Liquids e Below but close to the e This minimizes the static head elevation of the process effec
24. LOCATION Ex nA nL IIC T4 Ta 84 C DIP A22 IP66 T90 C s 80 C WITH OPTION DC AMBIENT LIMITS 40 lt Tas 84 C lt s 80 C WITH OPTION DC ENTITY PARAMETERS ASSOCIATED APPARATUS Ui 30V IS FIELD WIRING li 125 mA PARAMETERS Dr Uo 30 V RM Io lt 125 mA Po 1 0 W Du C la Crisis Transmitter 6 4 nF LO 2 Laane Lrea Transmitter 1 0 pH E ATEX CONTROL CERTIFIED 7 EQUIPMENT ASSOCIATED APPARATUS ZONE 2 CONTROL EQUIPMENT ho amp Ex nL OUTPUT PARAMETERS Uo 30 V Io lt 125 mA Po 10 W Co 2 cable F C Fiend Transmitter Y 6 4 nF Lo 2 Leable Lrieia Transmitter Y 1 0 HH FIELD TRANSMITTER TRANSMITTER 0 4 20 mA ACE SHIELD AT 10 THIS END ONLY SHALL BE CERTIFIED INTRINSICALLY SAFE FOR USE IN ZONE D 1 LOCATIONS OR NON SPARKING Ex nA FOR USE IN ZONE 2 LOCATIONS Honeywell 90036277 SCALE NONE NONE REV D DATE 09 15 10 SH 3 of 11 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings WIRELESS TEMPERATURE AND DIGITAL INPUT DI TRANSMITTERS STTW400 STTW401 STXW500 STT820 STTW830 amp STTW840 HAZARDOUS LOCATION Ex ib ia B T4 Ta 70 C DIP A20 IP66 T90 C WITH OPTION BA Ex nA NL IIC T4 Ta 84 C DIP A22 IP66 T90 C lt 80 C WITH OPTION DC AMBIENT LIMITS 40 lt Ta lt 84 C lt 80 C WITH OPTION DC SINGLE
25. NOT EXCEED 43 UF 2 Corore cami AND 100 mH 2 Laroge Loan NOTE Probes used with the Corrosion Transmitter must be acceptable to the authority having jurisdiction with respect to pressure and temperature rating Honeywell SCALE NONE REV E DATE 09 24 10 SH 7 of 11 64 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings The following models may be supplied with internal battery power or externally supplied 24Vdc only when connected to the MTL Associated Apparatus listed on the following system diagram NOTE XYR 6000 ambient limits with 24V Power Supply are 40 C to 80 C Description Series 900 Wireless Transmitter Dual Head Gage Pressure GP 3 STR eries 900 Wireless Transmitter CE Differential Pressure DP jon PEE SEE EXE STDW974 0 3000 psi 0 210 bar STGW94L 0 500 psi 0 35 bar STGWOS7L idum e 0 3000 psi 0 210 bar STEWSBL Penes e ees Irarsmiler 6 6000 psi 0 415 bar STGWSSL Mi c D 0 10 000 psig 0 690 bar STAWIAL 0 500 psi 0 35 barA STTW400 Wireless Temperature Transmitter ee eee Remote Sensors STTW401 Wireless Temperature and Digital Transmitter Only with Remote Sensors Input Transmitter 1 T C AND 2 Digital Inputs 3 TXW500 Wireless Digital Input Transmitter Three DI Switch Inputs STUW700 Wireless Universal I O Interface Med v ad 4 20 mA Analog T C s or DI STUW701 ir a Analog T C or DI and
26. On EE 1 12 European Union EE 1 1 3 Gertifications and ALO SA a 2 Hazardous localion cenitiealionsz EET ia 2 Radio COMIC ato Sa isa 9 Radio Frequency RF statement EE 3 EE Unon TESTICUON MR 3 FC SUI CUI ON es este ee ee ee e 3 Japanes HOS WICHONG md aedi le 3 2 TRANSMITTER MOUNTING civic 6 PP A 6 2 2 DIMENSIONS ii A A A IATA 6 23 Transmitter loca lO inside 12 Pressure IOC Si EO mc 12 24 ee alte T IERT 12 2 0 ie cione 13 Atach DIACKEL 10 PIDO na ee es ne EDT 13 Altach transmitter tO Drack een ee ea 14 2 6 Rotate transmitier Housing ns an 15 2 Cen A A E aa r aa 15 THOOIS FEQUINC Gi en e AO 15 OG CCE e TERES 15 3 PROCESS INSERTION asien 17 31 Pressure Model ini ee 17 o A E M ML t MR M A aM A 17 PROCESS CONNECLHONS zu TOU Dmm c 19 General DIDING e Ile Ic s OO 19 3 2 Temperature and Discrete Input models 111eeeeee crecer eee eee nennen nena 20 Je geleet INO lte 20 lios Tm 20 Remote KODE WINING nase 20 33 NR E ne EE 21 Connect inso osc T 21 34 Universal nee 22 A a a 22 Wiring for calibration XYR6000 Universal I O Wiring Diagrams for Al DI Model STUW 700 23 Wiring for calibration XYR 6000 Universal I O Wiring Diagrams for AI DI DO Model STUW 701
27. THERMOCOUPLE OR DI TWO THERMOCOUPLE OR DI 4 JUMPER WIRES 3 JUMPER WIRES TiS OR DI MAY BE GROUNDED TYPE ONLY ONE TAG OR DI MAY BE GROUNDED TYPE SINGLE THREE WIRE RTD ONLY ONE T C OR DI MAY BE GROUNDED TYPE TWO THREE WIRE RTD s T C OR DI MUST BE FLOATING UNGROUNDED TYPE IS FIELD WIRING PARAMETERS WITH OPTION DC Ca 2 7 UF Zeen La 100 mH 2 Lenin WITH OPTION BA Ca 9 3 PF Z Cos TC OR DI MUST BE FLOATING A UNGROUNDED TYPE G La 100 mH 2 Lowe NOTES 1 Shielded thermocouple mV or RTD Ohms cable is required for EMC conformity and is recommended for all remote sensor installations The shield shall be grounded at the transmitter end only When remote mounted probe sensors are used and the shield is grounded at the probe the shield shall not be connected at the transmitter end Duplex redundant sensors that are bonded to the probe are not permitted All thermocouple mV inputs and RTD Ohms inputs must be insulated from ground the probe and from each other as noted above Jumper wires the same gauge and stranding as the thermocouple wires are required for single and dual thermocouple input combinations Digital input switches DI must be dry contact type simple apparatus and property segregated from all other sources of power A Honeywell 50036277 py in Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 83 October 2010 6 Certification Installation
28. Temperature and Digital Input Transmitter STXWBDO Wireless Digital Input Transmitter SITUWTDOD Wireless Universal I O Interface STUW7O1 Wireless Universal I O Interface STTW820 SITW830 Wireless Temperature Transmitter SITW840 STIW600 igh Level Input Interface CETW6oO00M w 9martCET Wireless Transmitter Corrosion Monitoring CETW6000M D SmartCET Corrosion Data Logger Description Transmitter Only with Remote Sensors 3 T C 5 or 2 RTD s Transmitter Only with Remote Sensors 1 T C AND 2 Digital Inputs Three DI Switch Inputs Three Inputs 4 20 mA Analog T C s or DI Switch Two Inputs 4 20 mA Analog T C or DI and One Digital Output Solid State Transmitter Integrally Mounted to Thermowell or Probe Assembly Millivolt Input from Remote Mounted Corrosion Probe Millivolt Input from Remote Mounted Corrosion Probe Data via IrDA Port There is no Antenna for this version The above listed wireless transmitters may include an Omni directional or unidirectional high gain antenna The high gain antenna may be installed remote from the XYR 6000 with the cable length not to exceed 20m The antenna cable shield shall be bonded to earth ground IS Entity parameters for remote antennas cables amp lightning arrestor Ca 43 pF La 0 1 mH Honeywell 90033269 76 OneWireless XYR 6000 Transmitters Quick Start Guide SCALE NONE REV E DATE 08 15 10 SH 8 of 11 Revision 9 O
29. WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT Figure 5 2 IS Battery Pack 3 Remove top of battery pack by using a 1 Philips or 1 8 slotted screwdriver for the screws identified as 1 in Figure 5 2 4 Remove the old batteries and dispose of them promptly according to local regulations of the battery manufacturer s recommendations 5 Install the batteries following the polarity as noted on the lid 6 Re install top of the battery pack and tighten screws 7 Insert the Battery pack into the transmitter Reattach the screws as indicated in Figure 5 1 item 3 to 0 4 to 0 6 N M 3 5 5 3 Lb in Heconnect the Batter Pack connector Honeywell recommends lubricating the end cap with a silicone grease such as Dow Corning 55 or equivalent before replacing the end cap 8 Screw the cap back on and tighten the M3 locking screw Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 43 October 2010 5 Start up 5 1 Battery Power Option 24V Wiring Connector M3 Locking Screw Power Connector Power Module Mounting Screws Figure 5 3 Power Option 24V J2 Connector Figure 5 4 External 24V Power Module 44 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 5 Start up 5 1 Battery Power Option 24 Vdc Power Supply Option DC System Diagram Ordinary Non Hazardous Locations 24Vdc POWER SUPPLY OPTION DC SYSTEM DIAGRAM ORDINARY NON HAZARDOUS LOCATIONS PS XYR 6000 TRANSMITT
30. in a Class Division 2 Hazardous Classified location if so approved 8 Non Galvanically isolated apparatus grounded ener Barriers must be connected to a suitable ground electrode per NFPA 70 Article 504 and 505 in the USA and CEC Part Section 10 in Canada The resistance of the ground path must be less than 1 0 ohm AD Transmitters shall have the enclosure bonded to ground in accordance with CEC part Section 18 074 Bonding in hazardous locations and Rule 10 814 AR Shielded two wire cable is required for EMC conformity and is recommended for all installations The 4 20 mA loop shield shall be grounded at the supply barrier end to the barrier ground bus only when grounded Zener barriers are used The 4 20 mA loop shield shall be qrounded at the transmitter end only when galvanically isolated barriers are used MASTER FILE TYPE MS WORD CERTIFICATION 1 3 08 ag Honeywell ENGINEERING un CSA amp FM Control Drawing se NOTE m AYR 6000 Wireless Transmitters arprovars wome 0 dee APPROVALS Jee A 90021730 TOLERANCE UNLESS NOTED ANGULAR DIMENSION SCALE USED ON SH 1 OF 11 58 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings 12 Divisions 1 amp 2 and Zone 0 WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS 13 Division 2 WARNING EXPLOSION HA
31. m 0 020 uHrft 4 For Class ll and Class lll installations and Type 4X IP66 applications where rigid metal conduit is not used seal all cable and unused entries against dust and fibers using a NRTL listed cable gland or seal fitting k Transmitters shall have the enclosure bonded to ground in accordance with CEC part section 18 0 4 Bonding in hazardous locations and Rule 10 814 8 shielded two wire cable is required for EMC conformity and is recommended for all installations The 4 20 mA loop shield shall be grounded at the supply end ONLY 7 Division 2 WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS 8 NO REVISION OF THIS INSTALLATION DRAWING IS PERMITTED WITHOUT AUTHORIZATION FROM CSA AND FM APPROVALS 9 For release approvals see ECO 0031900 DOCUMENT pore Honeywell ENGINEERING CHECKED CSA Installation Drawing V RUNS UE NOTE 9 EE AYR 6000 Wireless Transmitters AUTHORIZED BY wore Division 2 Zone 2 APPROVALS SES ENGINEERING A QA ENG 50026071 MASTER FILE TYPE TOLERANCE UNLESS NOTED MS WORD ANGULAR DIMENSION SCALE USED ON SH 1 OF 10 48 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings CSA CERTIFIED DIVISION 2 ZONE 2 INSTALLATION DRAWING TWO WIRE CONFIGURATION XYR 6000 STIW600 0 20 mA 4 20
32. mA HIGH LEVEL INPUT INTERFACE NON HAZARDOUS LOCATION XYR 6000 WIRELESS TRANSMITTER CLASS I DIV 2 GROUPS A B C D CLASS II DIV 2 GROUPS F amp G CLASS III DIV 2 T4 CLASS I ZONE 2 Ex AEx nA GROUP IIC T4 AMBIENT LIMITS 40 Ta lt 85 C lt 80 C WITH OPTION DC ES x NON IMCENDIVE FIELD WIRING PARAMETERS CONTROL APPARATUS Ui Vmax 30 Y NON INCENDIVE FIELD Ii Imax 125 mA WIRING PARAMETERS Pi 10 W Uo Voc or Vt 30 V to lo Isc or It 125 mA Pos 1 0 W Ca gt Coatia Leed Transmitier 6 8 nF La gt Lane Lega Transminer 1 0 pH GROUND SHIELD AT A THIS END ONLY FIELD TRANSMITTER CSA CERTIFIED FOR USE IN CLASS I Il DIV 2 ZONE 2 FM APPROVED FOR USE IN CLASS I I DIV 2 ZONE 2 Honeywell SCALE NONE REV E DATE 09 24 10 Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 49 October 2010 FIELD TRANSMITTER 0 4 20 mA 6 Certification Installation Requirements WIRELESS TEMPERATURE AND DIGITAL INPUT DI TRANSMITTERS STTWADO STTW401 STXW500 STT820 STTW830 amp STTW840 HAZARDOUS CLASSIFIED LOCATION CLASS 1 DIV 2 GROUPS A B C D CLASS II DIV 2 GROUPS F amp G CLASS III DIV 2 T4 CLASS I ZONE 2 EX AEx nA GROUP Il T4 AMBIENT LIMITS 40 lt Ta lt 85 C lt 80 C WITH OPTION DC SINGLE THERMOCOUPLE OR DI TWO THERMOCOUPLE OR DI 4 JUMPER WIRES 3 JUMPER WIRES TG OR DI MAY BE GROUNDED TYPE ONL
33. of the ETSI standards as required by the R amp TTE Directive 1999 5 EC Restriction France restricts outdoor use to 10mW 10dBm EIRP in the frequency range of 2 454 2 483 5 MHz Installations in France must limit EIRP to 10dBm for operating modes utilizing frequencies in the range of 2 454 2 483 5MHz Japanes Restrictions For locations in Japan the transmitter power is restricted to 12 14dBm Mhz 32mW 15 4 dBm maximum EIRP including the antenna ATTENTION THIS PRODUCT IS SUPPLIED WITH PLASTIC DUST PLUGS IN THE CONDUIT CABLE GLAND ENTRIES IT IS THE USERS RESPONSIBILITY TO PROVIDE CABLE GLANDS ADAPTORS AND OR BLANKING PLUGS SUITABLE FOR THE ENVIRONMENT IN WHICH THIS PRODUCT IS INSTALLED WHEN INSTALLED IN A HAZARDOUS LOCATION THE CABLE GLANDS ADAPTORS AND OR BLANKING PLUGS SHALL ADDITIONALLY BE SUITABLE FOR THE HAZARDOUS LOCATION THE PRODUCT CERTIFICATION AND ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION FOR THE INSTALLATION Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 3 October 2010 Product Ratings Temperature Power Option Temperature Corrosion Discrete High Level Code Certification Integral with Remote Input Analog Input Universal I O Probe DI Probe Remote HLAI Inputs Rating Description WARNING Division 2 Zone 2 apparatus BA Battery must only be connected DC 24Vdc to a non hazardous Supply process Process Connections CSA FM ATEX IECEx amp SAEx
34. or Vt lt 30 V Da 01 UH lo Ise or It 125 mA Po 1 0 W Ca Es Ceable C fisia Transmilber 6 8 nF La 2 Lesse Errata Transmitter 0 1 pH CONTROL T ASSOCIATED EQUIPMENT APPARATUS GROUND SHIELD AT THIS END ONLY FIELD TRAMSMITTER CSA CERTIFIED FOR USE IN CLASS I Il DIV 1 ZONE 0 FM APPROVED FOR USE IN CLASS DIV 1 ZONE 0 Honeywell SCALE NONE REV E DATE 09 24 10 SH 3of 11 TRANSMITTER 0 4 20 mA 60 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings WIRELESS TEMPERATURE AND DIGITAL INPUT DI TRANSMITTERS STTW400 STTW401 STXW500 STT820 STTW830 amp STTW840 HAZARDOUS CLASSIFIED LOCATION CLASS I DIV 1 GROUPS A B C D CLASS II DIV 1 GROUPS E F amp G CLASS Ill DIV 1 T4 CLASS I ZONE 0 EX AEx la GROUP IIC T4 AMBIENT LIMITS 40 Ta 85 C lt 60 C WITH OPTION DC SINGLE THERMOCOUPLE OR DI TWO THERMOCOUPLE OR DI CONNECTION CONNECTION TH TEZ 4 JUMPER WIRES TG OR DI MAY BE GROUNDED TYPE 3 JUMPER WIRES ONLY ONE T C OR DI MAY BE GROUNDED TYPE SINGLE THREE WIRE RTD ONLY ONE T C OR DI MAY BE GROUNDED TYPE SINGLE THREE WIRE RTD amp T C OR DI TWO THREE WIRE RTO s EI TE _ Tel TAG or m F T j 4 pose Pee am Tale Salo a pv 11s S TiC OR DI MUST BE FLOATING UNGROUNDED TYPE IS FIELD WIRING PARAMETERS
35. provide horizontal viewing Tools required e 1 Phillips Screwdriver or 1 8 Slotted Screwdriver e Torque Screwdriver e 1 5 mm hex key Procedure WARNING Risk of death or serious injury by explosion Do not open transmitter enclosure when an explosive gas atmosphere is present Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 15 October 2010 2 Transmitter Mounting 2 7 Rotate display Step 16 CAUTION Take precautions against electrostatic discharge to prevent damaging the display sensor module Table 2 1Display adjustment Action Honeywell recommends that the transmitter be removed from service and moved to a clean area before servicing Loosen the M3 locking set screw on the display end cap See item 1 in Figure 2 9 Unscrew and remove the end cap Loosen the two captive screws on the display sensor module See items 2 in Figure 2 9 Rotate the display 90 or 180 degrees in either direction so the screws line up with the threaded holes Do not rotate more than 180 degrees or you could damage the wires behind the display Re attach the display s two captive screws Tighten to 0 4 0 6 N m 3 5 5 3 Ib in Replace end cap and tighten M3 locking screw Figure 2 9 Display rotation OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 3 Process insertion 3 1 Pressure models 3 Process insertion 3 1 Pressure models Piping The actual piping ar
36. the transmitter Remove the old batteries from the battery holder If needed pry out the batteries by using a slotted screwdriver as a lever in the holder s side slots See item 4 in Figure 5 1 Install batteries as follows to avoid snagging the battery terminal on the clip and damaging the battery Align the new battery with the clips and angle the positive end of the battery into the positive battery terminal clip Using a thumb and forefinger pull the negative terminal clip outward and push down on the battery until fully seated in the clips Do not apply excessive force when pushing battery down Repeat this process for the second battery Insert the battery holder into the transmitter Reattach the screws and tighten to 0 4 0 6 N M 3 5 5 8 Lb in Re connect battery connector Honeywell recommends lubricating the end cap O ring with a Silicone Grease such as Dow Corning 55 or equivalent before replacing the end cap Screw the end cap back on and tighten the M3 locking screw Dispose of used battery promptly per local regulations or the battery manufacturer s recommendations Keep away from children Do not disassemble and do not dispose of in fire OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 5 Start up 5 1 Battery Power Option IS Battery Pack 50047517 501 Table 5 2 IS Battery Pack replacement procedure Step Action 1 Follow steps 1 4 as above WARNING DO NOT ASSEMBLE
37. voltage or current but not both See Figure 3 5 or Figure 3 6 For hazardous locations see info starting on page 47 4 Plug battery connector into batteries 5 Close rear end cap and cable gland 6 Tighten M3 locking screw on the rear end cap To voltage current source See Figure 3 5 and Figure 3 6 Figure 3 6 Current input wiring Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 21 October 2010 3 Process insertion 3 4 Universal I O 3 4 Universal I O STUW 700 Three inputs 1 3 HLAI 1 2 T C 1 2 Discrete Inputs STUW 701 Two inputs 1 2 HLAI T C DI One 1 Discrete Output Connect wiring Step 1 22 Action See Figure 3 7 Open the rear end cap opposite end from display by loosening the M3 locking screw and unscrewing the end cap Open the cable gland on right side below antenna Cable gland must be ordered as an option Feed wiring allowed diameter 6 to 8 mm from other transmitter through the cable gland and connect to terminal block using either voltage or current but not both See wiring diagrams pages Plug battery connector into batteries Close rear end cap and cable gland Tighten M3 locking screw on the rear end cap To voltage current source See wiring diagrams for all models on pages 24 and 25 Figure 3 7 Universal I O Connection OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 3 Process insertion 3 4 Universal I O
38. 010 BA Battery 40 to 85 C 1 Introduction 1 3 Certifications and approvals Product Ratings continued Temperature Discrete Input Remote High Level Analog Input Universal I O Temperature Corrosion Integral with Remote Probe DI Probe Power Option Code Certification Rating Description Quantitv of BA Battery uantity o Required Supplied by CSA amp FM Div 1 amp 1 0 0 the User DC 24Vdc Div 2 Suppl PPY ATEX IECEx amp SAEx Zone 0 amp 1 BA Battery c Pd SE seen YES YES YES Rigid Metal Conduit per P Bol Electrical Code DC 24Vdc CSA amp FM Supply Explosion proof Div 1 Lu M NEL N WES WE CSA amp FM Non BA Battery E d RR mn mn YES YES YES Ordinary Location SAEx Zone 0 1 amp 2 Field Wiring Dos cr PVC nne n DC 24Vdc i 2 Supplied b ne y Supply ATEX IECEx amp YES YES YES YES SAEx Zone 0 1 amp 2 CSA amp FM Non BA Battery E T RR mn mn YES YES YES SAEx Zone 0 1 amp 2 Cable and Cable Gland CSA amp FM Non DC 24Vdc Incendive Div 2 YES YES YES YES Supply ATEX IECEx amp SAEx Zone 0 1 amp 2 12 NPT entries may be specified for ATEX IECEx and SAEx certifications Cable gland supplied by the user is required for Corrosion Probe Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 5 October 2010 2 Transmitter Mounting 2 1 Weight 2 Transmitter Mounting
39. 1m 3 3 ft TNC R 50018110 003 3m 10 ft 50018110 010 10m 33 ft CABLE B LMR 400DB set TYPE N MALE 50018278 001 2 1m 3 3ft TYPE N MALE 20018278 003 3m 10 ft 50018278 010 10m 33ft REMOTE ANTENNA XYR 6000 WIRELESS TRANSMITTER Cable A REMOTE ANTENNA XYR 6000 WIRELESS TRANSMITTER yo Cable A m Cable B_ J ucuruucs EL SURGE ARRESTOR T NDUCTANCE 0 2 uH 0 6 pH NOTES 1 Only lightning surge arrestors determined to be simple apparatus may be installed 50021730 Honeywell 68 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings COPYRIGHT 2010 HONEYWELL INTERNATIONAL INC NEITHER THIS DOCUMENT NOR THE a eS Sr m INFORMATION CONTAINED HEREIN SHALL BE REPRODUCED USED OR DISCLOSED TO REVISION amp DATE APPD OTHERS WITHOUT THE WRITTEN AUTHORIZATION OF HONEYWELL USE DUPLICATION OR 09152010 ECO 006937 7 es DISCLOSURE OF THIS DOCUMENT IS SUBJECT TO THE RESTRICTIONS SET FORTH IN A ER WRITTEN AGREEMENT NOTHING CONTAINED HEREIN SHALL BE CONSTRUED AS CONFERRING BY IMPLICATION ESTOPPEL OR OTHERWISE AMY LICENSE TO ANY PATENT TRADEMARK COPYRIGHT OR OTHER INTELLECTUAL PROPERTY RIGHT OF HONEYWELL OR ANY THIRD PARTY ATEX INTRINSICALLY SAFE ia AND NON SPARKING n INSTALLATION CONTROL DRAWING XYR
40. 21 Figure 16 Universal I O Ee lee EE 22 Figure 17 Corrosion transmitter with remote probe nnne 30 Figure 18 Elbow antenna adjustment ccccceeeeccceceeseeceeeeeeeeceeeeeeeeceeeseeaeeeeeseeeaeeeeessaaseeesseeseeeeeesnageeeees 32 Figure 19 Integral straight amtennag eene nennen menn nnn nnne nennen nn nnne nans ns 32 Figure 20 Directional antenna mounting esses nnne nnne nnn nennen nns 37 Figure 21 Omnidirection antenna mounting ssseanneesenneessennnnnsrnrnressnrrrensrnrnresrnnrrensnnrensnnrrresrnrrrensnenrnrenne 38 Figure 22 Battery assemily E 41 Elgure 2215 Battely Packs ani dues eoa ne uscita arose ee nee ee 43 Figure 24 POWER ODIIOI DEE 44 Figure 25 External 24V Power e Le TEE 44 Figure 26 Power Supply 24 Vdc Option DC System DiagraM ooooccccnncccncccnonnccnnnncnnnnnoncnnnnnnnnnnnannnnnnnnnnos 45 X OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 1 1 Site preparation Wireless devices require proper site preparation to ensure optimum performance and safety compliance Do not proceed until you have done the proper planning described in the Wireless Planning Guide 1 2 European Union Usage Introduction Introduction Site preparation This product may be used in any of the following European Union nations Country Austria Belgium Bulgaria Cyprus Czech Republic Denmark Estonia Finland France Germany Greece Hungary Iceland Ireland I
41. 88 502 eege P pm em em eg e Le e e e a See Figure 5 1 Battery assembly Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide October 2010 41 5 Start up 5 1 Battery Power Option 42 Step Table 5 1 Battery replacement procedure Action ATTENTION You must replace both batteries Both batteries must be the same model from the same manufacturer Mixing old and new batteries or different manufacturers is not permitted Use only the following 3 6V lithium thionyl chloride Li SOCI2 batteries non rechargeable size D No other batteries are approved for use in XYR 6000 Wireless Transmitters e Xeno Energy XL 205F e Eagle Picher PT 2300H e Tadiran TL 5930 s e Honeywell p n 50026010 001 Two 3 6V lithium thionyl chloride batteries 1 transmitter e Honeywell p n 50026010 002 Four 3 6V lithium thionyl chloride batteries 2 transmitters e Honeywell p n 50026010 003 Ten 3 6V lithium thionyl chloride batteries 5 transmitters Loosen the M3 locking set screw on the battery end cap opposite end from display See item 1 in Figure 5 1 Unscrew and remove the end cap Using thumb and forefinger squeeze the battery connector at top and bottom to disengage the locking mechanism then pull to disconnect See item 2 in Figure 5 1 Loosen the two battery holder retaining screws closest to the batteries See item 3 in Figure 5 1 The screws are captive Pull the battery holder out of
42. BE PASSIVE ELEMENTS ONLY ELBOW DIER XYR 6000 TRANSMITTER STRAIGHT TYPICAL ANTENNA REMOTE ANTENNA ME CONNECTOR LIGHTNING SURGE ARRESTOR ALTELECON AL NFNFB 9 20018279 090 Honeywell SCALE NONE REY E DATE 09 15 10 SH 10 of 11 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings 15 parameters for remote antennas cables amp lightning arrestor Ca 43 pF La 0 1 mH d i e mes CABLE A LMR 400DB 30018110 001 Im 20018110 003 3m 50018110 010 10m CABLE B LMR 400DB 50018278 001 1m 50018278 003 3m 50018278 010 10m REMOTE ANTENNA Cable A AYR 6000 WIRELESS TRANSMITTER REMOTE ANTENNA XYR 6000 Cable A SU Cable B WIRELESS F ge dior ad A eu TRANSMITTER ARRESTOR El Cyt CAPACITANCE 1 pF INDUCTANCE 10 nH 90033269 SCALE NONE REV E DATE 09 15 10 Honeywell Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 79 October 2010 6 Certification Installation Requirements COPYRIGHT 2010 HONEYWELL INTERNATIONAL INC NEITHER THIS DOCUMENT NOR THE PREREL INFORMATION CONTAINED HEREIN SHALL BE REPRODUCED USED OR DISCLOSED TO OTHERS WITHOUT THE WRITTEN AUTHORIZATION OF HONEYWELL USE DUPLICATION OR REVISION amp DATE APPD D DISCLOSURE OF THIS
43. C Ex nA nL IIC T4 Ta 84 C DIP A22 IP66 T90 C s 80 C WITH OPTION DC AMBIENT LIMITS 30 C Ta 84 C s 80 C WITH OPTION DC RED WHITE BLACK FE TO CORROSION _ PROBE ASSEMBLY PROBE AND PROCESS ELECTRODES MUST BE PASSIVE ELEMENTS ONLY PROBE AND CABLE PARAMETERS MUST NOT EXCEED 43 pF gt Cprose Cease AND 0 25 mH 2 Lerose Lease NOTE The Probe connections are ia for connection to Zone 0 processes The Frobe used with the Corrosion Transmitter must be acceptable to the competent body having jurisdiction with respect lo pressure and temperature ratings A Honeywell eieiei HEV D DATE 09 16 10 86 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings The following models may be supplied with internal battery power or externally supplied 24Vdc only when connected to the MTL Associated Apparatus listed on the following system diagram NOTE AYR 6000 ambient limits with 24V Power Supply are 40 C to 80 C STGW944 series 900 Wireless Transmitter 0 500 psi 0 35 bar STGW974 Dual Head Gage Pressure GP 0 3000 psi 0 210 bar SIDWS24 0 400 H 0 0 1000 mb STDW930 seres 900 Wireless Transmitter 0 400 10 7 bar Differential Pressure DP SIDWS74 0 3000 psi 0 210 bar SIGWSAL 0 500 psig 0 35 bar SIGWST7L e E 0 3000 psig 0 210 bar Seres 900 Wireless Transmitter er In Line Gage amp Absolute Pre
44. CALE NONE REV E DATE 09 15 10 Honeywell 72 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings WIRELESS TEMPERATURE AND DIGITAL INPUT DI TRANSMITTERS STTW400 STTW401 STXW500 STTW820 STTW830 STTW840 HAZARDOUS LOCATION Ex ib ia IIB T4 Ta 70 C DIP A20 IP66 T90 C WITH OPTION BA Ex nA nL IC T4 Ta 84 C DIP A22 IP66 T90 C lt 80 C WITH OPTION DC AMBIENT LIMITS 40 Ta 84 C 80 C WITH OPTION DC SINGLE TWO WIRE RTD TWO TWO WIRE RTD JUMPER WIRE JUMPER WIRE T C OR DI MUST BE FLOATING T C OR DI MUST BE FLOATING UNGROUNDED TYPE UNGROUNDED TYPE IS FIELD WIRING PARAMETERS WITH OPTION DC Ca 2 7 UF 2 Coun La 100 mH L catie WITH OPTION BA Ca 9 3 UF 2 Cos La 100 mH L caba NOTES 1 Shielded thermocouple mV or RTD Ohms cable is required for EMC conformity and is recommended for all remote sensor installations The shield shall be grounded at the transmitter end only 2 When remote mounted probe sensors are used and the shield is grounded at the probe the shield shall not be connected at the transmitter end 3 Duplex redundant sensors that are bonded to the probe are not permitted All thermocouple mV inputs and RTD Ohms inputs must be insulated from ground the probe and from each other as noted above 4 Jumper wires the same gauge and stranding as the thermocouple wires
45. ER TYPICAL Cable to be shielded twisted pair with total loop resistance lt 6 60 24 Vdc Supply JB Vgl a 7 28 0 Vias O 100 MAmax 7 qa GROUND SHIELD AT THIS END ONLY Figure 5 5 Power Supply 24 Vdc Option DC System Diagram Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 45 October 2010 5 Start up 5 2 Display sequence 5 2 Display sequence After power up the transmitter does a brief self test of the LCD display Then it proceeds to Power On Message which is the model name of the transmitter The name is displayed for 2 seconds after which the transmitter displays the process variables and associated status 5 3 Provisioning Before the transmitter can be configured 1t must be unlocked with a security key so 1t can join the network Use the Provisioning Device Pocket PC software to receive security keys from the Key Server manager then aim the Pocket PC at the transmitter and transmit a key See Getting Started with Honeywell OneWireless Solutions for more information 46 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 6 Certification Installation Requirements 6 1 Certification Drawings 6 Certification Installation Requirements 6 1 Certification Drawings Use the following drawings and accompanying notes and text for hazardous locations Any deviation from the For non hazardous locations you can use the same drawings without
46. GTAC honeywell com Honeywell Global TAC India 91 20 6603 9400 91 20 6603 9800 Honeywell Automation India Ltd 56 and 57 Hadapsar Industrial Estate Hadapsar Pune 411 013 India Global T AC India 9 honey well com Honeywell Global TAC Korea 82 2 799 6317 82 11 9227 6324 82 2 792 9015 Honeywell Co Ltd 17F Kikje Center B D 191 Hangangro 2Ga Yongsan gu Seoul 140 702 Korea Global TAC Korea honeywell com OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 People s Republic of China Contact Phone Mail Email Singapore Taiwan Japan World Wide Web Contact Phone Facsimile Mail Email Contact Phone Facsimile Mail Email Contact Phone Facsimile Mail Email Honeywell Global TAC China 86 21 5257 4568 Honeywell China Co Ltd 33 F Tower A City Center 100 Zunyi Rd Shanghai 200051 People s Republic of China Global TAC ChinaQ honey well com Honeywell Global TAC South East Asia 65 6580 3500 65 6580 3501 65 6445 3033 Honeywell Private Limited Honeywell Building 17 Changi Business Park Central 1 Singapore 486073 GTAC SEA honeywell com Honeywell Global TAC Taiwan 886 7 536 2567 886 7 536 2039 Honeywell Taiwan Ltd 17F 1 No 260 Jhongshan 2nd Road Cianjhen District Kaohsiung Taiwan ROC Global TAC Taiwan Ohoneywell com Honeywell Global TAC Japan 8 1 3 6730
47. Honeywell OneWireless XYR 6000 Transmitters Quick Start Guide 34 XY 25 21 Revision 9 October 2010 Notices and Trademarks Copyright 2008 by Honeywell International Inc Revision 9 October 2010 While this information is presented in good faith and believed to be accurate Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers In no event is Honeywell liable to anyone for any indirect special or consequential damages The information and specifications in this document are subject to change without notice Honeywell PlantScape Experion PKS and TotalPlant are registered trademarks of Honeywell International Inc Other brand or product names are trademarks of their respective owners Honeywell Process Solutions 1860 West Rose Garden Lane Phoenix AZ 85027 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Notices and Trademarks Heferences About This Document This document describes mounting installation and wiring of the XYR 6000 Wireless Transmitters and antennae Configuration authentication and operation are covered in other documents Honeywell does not recommend using devices for critical control where there is a single point of failure or where single points of failure result in unsafe conditions OneWireless is targeted at open loop con
48. Honeywell SpA Phone 39 02 250 10 604 FAX 39 02 250 10 659 South Africa Republic of and sub saharan Honeywell Southern Africa Honeywell S A Pty Ltd Phone 27 11 6958000 FAX 27 118051504 NORTH AMERICA Canada Honeywell LTD Phone 1 800 737 3360 FAX 1 800 565 4130 USA Honeywell Process Solutions Phone 1 800 423 9883 Or 1 800 343 0228 Email ask ssc honeywell com SOUTH AMERICA Argentina Honeywell S A l C Phone 54 11 4383 3637 FAX 54 11 4325 6470 Brazil Honeywell do Brasil amp Cia Phone 55 11 7266 1900 FAX 55 11 7266 1905 Chile Honeywell Chile S A Phone 56 2 233 0688 FAX 56 2 231 6679 Mexico Honeywell S A de C V Phone 52 55 5259 1966 FAX 52 55 5570 2985 Puerto Rico Honeywell Inc Phone 809 792 7075 FAX 809 792 0053 Trinidad Honeywell Inc Phone 868 624 3964 FAX 868 624 3969 Venezuela Honeywell CA Phone 58 2 238 0211 FAX 58 2 238 3391 Honeywell 34 XY 25 21 Rev 9 October 2010 2010 Honeywell International Inc
49. IC T4 Ta s 84 C s 80 C WITH OPTION DC Ex tD A22 IP66 T90 C AMBIENT LIMITS 30 C lt Tas 84 C s 80 C WITH OPTION DC ENTITY PARAMETERS ASSOCIATED APPARATUS Ui 30 Y 15 FIELD WIRING Ii 125 mA PARAMETERS Pe a Uo lt 30 V E i 10 pH Io 125 mA Po 1 0 W Co Cable Field Trans miller 6 4 nF Lo z Leabie Lriek Transmitter Y 1 0 pH E ATEX o NTROL fr CERTIFIED EQUIPMENT associated IL IT N APPARATUS CT ZONE 2 CONTROL EQUIPMENT i Ex nL OUTPUT PARAMETERS Uo 30 V Io amp 125 mA Po 1 0 W Co adn D Creta Transmitter 6 4 nF FIELD TRANSMITTER SHALL BE ATEX CERTIFIED Lo gt b cabe Leg Transmitter 1 0 WH TRANSMITTER INTRINSICALLY SAFE FOR USE IN ZONE 0 4 20 m i 0 1 LOCATIONS OR NON SPARKING Ex n FOR USE IN ZONE 2 LOCATIONS GROUND SHIELD AT THIS END ONLY Honeywell 90033269 DATE 09 15 10 S CALE NONE REV E SH 3of 11 Hevision 9 October 2010 OneWireless XYR 6000 Transmitters Quick Start Guide 71 6 Certification Installation Requirements WIRELESS TEMPERATURE AND DIGITAL INPUT DI TRANSMITTERS sTTW400 STTW401 STXW500 STT820 STTW830 amp STTW840 HAZARDOUS LOCATION Ex ib ia IIB T4 Ta 70 C DIP A20 IP66 T90 C WITH OPTION BA Ex nA NL IIC T4 Ta 84 C DIP A22 IP66 T90 C lt 80 C WITH OPTION DC AMBIENT LIMITS 40 lt Ta lt 84 C lt 80 C WITH OPTION DC
50. N It is your responsibility to supply a suitable sealing method or gasket and mounting hardware for the probe s service conditions Integral Integral Remote Remote Rigid Spring Rigid Spring KAES ed loaded CL LT Figure 3 3 Temperature probes Integral probe wiring The integral probe is pre wired to the transmitter at the factory Remote probe wiring Step Action 1 See Figure 3 3 Open the transmitter s rear end cap opposite end from display by loosening the M3 locking screw and unscrewing the end cap 2 Open the cable gland on right side below antenna Cable gland must be ordered as an option 3 Feed wiring 6 to 8 mm allowed diameter through the cable gland and connect to terminal block For terminal connections see info starting on page 47 4 Plug battery connector into batteries See page 40 5 Close rear end cap and cable gland 6 Tighten M3 locking screw on the rear end cap 20 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 3 Process insertion 3 3 HLAI models 3 3 HLAI models Connect wiring Step Action 1 See Figure 3 4 Open the rear end cap opposite end from display by loosening the M3 locking screw and unscrewing the end cap 2 Open the cable gland on right side below antenna Cable gland must be ordered as an option 3 Feed wiring allowed diameter 6 to 8 mm from other transmitter through the cable gland and connect to terminal block using either
51. NEERING an I 90036277 TOLERANCE UNLESS NOTED ANGULAR DIMENSION SCALE USED ON SH 1 OF 11 80 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings 12 Zone 0 or Zone 1 WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS 13 Zone 2 WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS 14 NO REVISION OF THIS CONTROL DRAWING 15 PERMITTED WITHOUT AUTHORIZATION FROM THE NOTIFIED BODY 15 For release approvals see ECO 0049814 Bu o 6000 STIW600 a Transmitter Associated E Aw 30 V Vot3NV Associated Apparatus Co Ci 64 nF Ccable Ci of other transmitter connected to two channel barrier Associated Apparatus Lo Lcable L 1 0 uH Liofother transmitter connected to two channel barrier 50036277 Honeywell Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 81 October 2010 6 Certification Installation Requirements IECEx CERTIFIED INTRINSICALLY SAFE ia AND NON SPARKING n INSTALLATION CONTROL DRAWING TWO WIRE CONFIGURATION XYR 6000 STIW600 0 20 mA 4 20 mA HIGH LEVEL INPUT INTERFACE HAZARDOUS LOCATION AYR 6000 WIRELESS TRANSMITTER NON HAZARDOUS Ex ia IIB T4 Ta 70 C DIP A20 IP66 T80 C
52. P IW T4 AMBIENT LIMITS 40 s Tas 35 C s 80 C WITH OPTION DC 2 TUW 7DO POSSIBLE CONNECTIONS T C mV DIGITAL INPUT DI AND HIGH LEVEL ANALOG INPUT HLA PV 1 FV2 HIGH LEVEL ANALOG INPUT amp DIGITAL INPUT AMD T C DIGITAL OUTPUT ENTITY FIELD WIRING PARAMETERS PARAMETERS Ui Vmax 30 V Ca 2 7 HF 2 Ceana Ii Imax 125 mA La 100 mH 2 Leste pj 1 0 W Ci 6 8 nF Lj 0 1 pH NOTES 1 Shielded HLAI DI DO thermocouple mV or switch input cable is required for EMC conformity and is recommended for all installations The shield shall be arounded at the transmitter end only If the shield is grounded at the switch remote HLAI transmitter location or remote DO supply the shield shall nct be connected at the VVireless transmitter end Honeywell SCALE NONE REV E DATE 092410 SH 6 of 11 Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 63 October 2010 6 Certification Installation Requirements XYR 6000 MODEL CETW6000M W WIRELESS CORROSION TRANSMITTER AND CETW6000M D SmartCET CORROSION DATA LOGGER HAZARDOUS CLASSIFIED LOCATION CLASS I DIV 1 GROUPS A B C D CLASS Il GROUPS E F amp G CLASS Ill DIV 1 T4 CLASS I ZONE 0 Ex AEX ia GROUP IIC T4 AMBIENT LIMITS 30 lt Ta lt 85 C lt 80 C WITH OPTION DC d j WHITE A BLACK Kan TO CORROSION PROBE ASSEMBLY PROBE AND PROCESS ELECTRODES MUST BE PASSIVE ELEMENTS ONLY PROBE AND CABLE PARAMETERS MUST
53. Requirements WIRELESS TEMPERATURE AND DIGITAL INPUT DI TRANSMITTERS STTW400 STTW401 STXW500 STT820 STTW830 amp STTW840 HAZARDOUS LOCATION Ex ib ia IIB T4 Ta 70 C DIP A20 IP66 T90 C WITH OPTION BA Ex nA nL IIC T4 Ta 84 C DIP A22 IP66 T90 C lt 80 C WITH OPTION DC AMBIENT LIMITS 40 lt Ta lt 84 C lt 80 C WITH OPTION DC SINGLE TWO WIRE RTD TWO TWO WIRE RTD JUMPER WIRE T C OR DI MUST BE FLOATING T C OR DI MUST BE FLOATING UNGROUNDED TYPE UNGROUNDED TYPE IS FIELD WIRING PARAMETERS WITH OPTION DC Ca 2 7 UF 2 Cru La 100 mH L case WITH OPTION BA Ca 8 3 UE 2 Coss La 100 mH gt L cabo NOTES 1 Shielded themrmocouple mV or RTD Ohms cable is required for EMC conformity and is recommended for all remote sensor installations The shield shall be grounded at the transmitter end only When remote mounted probe sensors are used and the shield is grounded at the probe the shield shall not be connected at the transmitter end Duplex redundant sensors that are bonded to the probe are not permitted All thennocouple m inputs and RTD Ohms inputs must be insulated from ground the probe and from each other as noted above Jumper wires the same gauge and stranding as the thermocouple wires are required for single and dual thermocouple input combinations 5 Digital input switches DI must be dry contact type simple apparatus and property segregated from all other sources of power
54. S STTW 500 MULTI DI CONNECTION TB1 ss TZAL S et Aoc S3 S2 2 JUMPER WIRES NOTES 1 Shielded switch input cable is required for EMC conformity and is recommended for all remote switch installations The shield shall be grounded at the transmitter end only If the shield is grounded at the switch location the shield shall not be connected at the transmitter end 2 Jumper wires the same gauge and stranding as the switch wires are required for all switch input combinations 3 Switches shall be isolated from each other and from earth ground to avoid common mode noise problems Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 25 October 2010 3 Process insertion 3 5 Corrosion models 3 5 Corrosion models Probe mounting locations The corrosion probe must be installed in a location that is most susceptible to corrosion In most cases corrosion tends to occur where water is trapped or stagnant However it can also accelerate at the bend of the pipe or where corrosion has occurred previously but is accelerated by high flow or turbulence rem mmm Incorrect probe location The probe should not be mounted in a pipe drop since the corrosive liquid may not be in full contact with the electrodes Correct probe location The probe should be mounted in the riser of a pipe near an elbow where the velocity is the highest In general probe should be mounted in pipes or tanks at locat
55. SIFIED LOCATION CLASS lI DIV 1 GROUPS A B C D CLASS II DIV 1 GROUPS E F amp G CLASS III DIV 1 14 CLASS I ZONE 0 EX AEX la GROUP IIC TA AMBIENT LIMITS 40 Ta 85 C lt 60 C WITH OPTION DC SINGLE TWO WIRE RTD TWO TWO WIRE RTD JUMPER WIRE JUMPER WIRE T C OR DI MUST BE FLOATING T C OR DI MUST BE FLOATING UNGROUNDED TYPE UNGROUNDED TYPE I8 FIELD WIRING PARAMETERS WITH OPTION DC Ca 2 7 UF gt Oceans La 100 mH Leos WITH OPTION BA Ca 9 9 UF gt C os La 100 mH gt Lea NOTES 1 Shielded thermocouple mV or RTD Ohms cable is required for EMC conformity and is recommended for all remote sensor installations The shield shall be grounded at the transmitter end only 2 When remote mounted probe sensors are used and the shield is grounded at the probe the shield shall not be connected at the transmitter end 3 Duplex redundant sensors that are bonded to the probe are not permitted All thermocouple mV inputs and RTD Ohms inputs must be insulated from ground the probe and from each other as noted above 4 Jumper wires the same gauge and stranding as the thermocouple wires are required for single and dual thermocouple input combinations 5 Digital input switches DI must be dry contact type simple apparatus and property segregated from all other sources of power 50026071 Honeywell Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 51 October 2010 6 Certif
56. Shenzhen Honeywell China Inc SE Asia Countries see Honeywell Automation Phone 86 755 2518 India Ltd for 1226 Bangladesh Fax 86 755 2518 1221 Nepal Sri Lanka Indonesia PT Honeywell Indonesia Phone 62 21 535 8833 EUROPE Austria lee er MOD Honeywell Austria GmbH Phone 43 316 400123 FAX 43 316 40017 India Automation India Ltd Honeywell Ltd Phone 91 5603 9400 Fax 91 5603 9600 Belgium Honeywell SA NV Phone 32 0 2 728 24 07 Japan FAX 32 0 2 728 22 45 Honeywell Inc Phone 81 3 6730 7150 Fax 81 3 6730 7228 Honeywell Process Solutions 1860 West Rose Garden Lane Phoenix Arizona 85027 www honeywell com ps hfs Bulgaria Honeywell EOOD Phone 359 2 40 20 900 FAX 359 2 40 20 990 Czech Republic Honeywell spol s r o Phone 420 242 442 232 FAX 420 242 442 131 Denmark Honeywell A S Phone 45 39 55 55 55 FAX 45 39 55 55 58 Finland Honeywell OY Phone 358 0 20752 2753 FAX 358 0 20752 2751 France Honeywell SA Phone 33 0 1 60198075 FAX 33 0 1 60198201 Germany Honeywell AG Phone 49 69 8064 299 FAX 49 69 806497336 Hungary Honeywell Kft Phone 36 1 451 4300 FAX 36 1 451 4343 Italy Honeywell S p A Phone 390292146307 FAX 39 0292146377 The Netherlands Honeywell B V Phone 31 0 20 5656200 FAX 31 0 20 5656210 Norway Honeywell A S Phone 45 39 55 55 55 Poland Honeywell Sp zo o
57. Y ONE TC OR DI MAY BE GROUNDED TYPE SINGLE THREE WIRE RTD ONLY ONE T C OR DI MAY BE GROUNDED TYPE TWO THREE WIRE RTD s TC OR DI MUST BE FLOATING UNGROUNDED TYPE IS FIELD WIRING PARAMETERS WITH OPTION DC Ca 2 7 UF gt Coss La 100 mH L cass u WITH OPTION BA Ca 93uF gt G T C OR DI MUST BE FLOATING A Cem NOTES 1 Shielded thermocouple mv or RTD Ohms cable is required for EMC conformity and is recommended for all remote sensor installations The shield shall be grounded at the transmitter end only When remote mounted probe sensors are used and the shield is grounded at the probe the shield shall not be connected at the transmitter end Duplex redundant sensors that are bonded to the probe are not permitted All thermocouple m inputs and RTD Ohms inputs must be insulated from ground the probe and from each other as noted above Jumper wires the same gauge and stranding as the thermocouple wires are required for single and dual thermocouple input combinations Digital input switches DI must be dry contact type simple apparatus and property segreqated from all other sources of power Honeywell HERNE 50 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 mr gd dw fw Certification Installation Requirements Certification Drawings WIRELESS TEMPERATURE AND DIGITAL INPUT DI TRANSMITTERS STTWAOO STTW401 STXW500 STTW820 STTW830 amp STTW840 HAZARDOUS CLAS
58. ZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS 14 NO REVISION OF THIS CONTROL DRAWING IS PERMITTED WITHOUT AUTHORIZATION FROM CSA AND FM Approvals 15 For release approvals see ECO 0036573 AYR 6000 STIW600 e E Transmitter Associated Apparatus Ji or Ymax 30V Ui Vmax or VE Vmax or Vt gt Uo Voc or Vt 30V li or Imax ih li imax or It gt lo Isc orit amp 125 mA Vi Vt Associated Apparatus Ca Ccable Ci of other transmitter Ca or Co gt 6 8 nF connected to two channel barrier Associated Apparatus La Lcable Li of other transmitter connected La or Lo gt 0 mH to two channel barrier 90021730 Honeywell SCALE NONE REV E DATE 09 2410 SH 2 of 11 Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 59 October 2010 6 Certification Installation Requirements CSA CERTIFIED amp FM APPROVED INTRINSICALLY SAFE INSTALLATION CONTROL DRAWING TWO WIRE CONFIGURATION XYR 6000 STIW600 0 20 mA 4 20 mA HIGH LEVEL INPUT INTERFACE NON HAZARDOUS LOCA TION CLASS DIV 1 GROUPS A B C D CLASS Il GROUPS E F amp G CLASS III DIV 1 14 CLASS I ZONE 0 EX AEX ia GROUP IIC T4 AMBIENT LIMITS 40 Ta 85 C s 80 C WITH OPTION DC dies ENTITY PARAMETERS ASSOCIATED APPARATUS Ui Vmax 30 V IS FIELD WIRING li Imax 125 mA PARAMETERS B hp a Uo Voc
59. allation Requirements Certification Drawings XYR 6000 MODEL CETW6000M WIRELESS CORROSION TRANSMITTER Ex la IIB 14 Ta s 70 C Ex tD A20 IP66 T90 C Ex nA nL IIC T4 Ta s 84 C s 80 C WITH OPTION DC Ex tD A22 IP66 T90 C AMBIENT LIMITS 30 C lt Ta s 84 C s 80 C WITH OPTION DC fp WHITE f ILS BLACK i TO CORROSION PROBE ASSEMBLY PROBE AND PROCESS ELECTRODES MUST BE PASSIVE ELEMENTS ONLY PROBE AND CABLE PARAMETERS MUST NOT EXCEED 43 UF CPROBE CCABLE AND 0 25 mH 2 Leroge Lease NOTE Probe used with the Corrosion Transmitter must be acceptable to the competent body having jurisdiction with respect to pressure and temperature rating Honeywell SCALE NONE REV E DATE 09 15 10 SH 7 of 11 Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 75 October 2010 6 Certification Installation Requirements The following models may be supplied with intemal battery power or externally supplied 24 vdc only when connected to the MTL Associated Apparatus listed on the following system diagram NOTE XYR 6000 ambient limits with 24V Power Supply are 40 C to 80 C STGWS944 Series 900 Wireless Transmitter STGW974 Dual Head Gage Pressure GP u Series 900 Wireless Transmitter STDWOT4 Differential Pressure DP SIGWS4L STGW9 L z STGWOSBL Series 900 Wireless Transmitter STEWSOL In Line Gage amp Absolute Pressure STAWSAL ST TW400 Wireless Temperature Transmitter STTWAD1 Wireless
60. angement Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 17 October 2010 3 Process insertion 3 1 Pressure models Another piping arrangement uses a block off valve and a tee connector in the process piping to the transmitter as shown in Figure 3 2 Tank wall 1 NPT Connection Figure 3 2 Typical Arrangement for 1 2 NPT Process Connection Piping n ATTENTION For liquid or steam the piping should slope a minimum of 25 4 mm 1 inch per 305 mm 1 foot Slope the piping down towards the transmitter if the transmitter is below the process connection so the bubbles may rise back into the piping through the liquid If the transmitter is located above the process connection the piping should rise vertically above the transmitter then slope down towards the flowline with a vent valve at the high point For gas measurement use a condensate leg and drain at the low point freeze protection may be required here CAUTION Property damage may result if operating temperature limits of transmitter are exceeded Electronics housing must not exceed 85 C 185 F meterbody temperature limit may be rated higher Consult transmitter nameplate for meterbody temperature limits To reduce the temperature of the process that comes into contact with the transmitter meter body install impulse piping As a general rule there is a 56 degree C drop 100 degrees F in the temperature of the process for every foot 305 mm of 1 2 i
61. ardware 3 Adjust antenna to desired tilt and lock into place using the antenna tilt adjustment nut Antenna Antenna Tilt Adjustment U Bolts Mast Mounting Bracket Mast 2 50 8mm O D Max Figure 4 3 Directional antenna mounting Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 37 October 2010 4 Antenna adjustment and mounting 4 3 Remote antenna Omnidirectional mounting procedure Step Action 1 Secure mast mounting bracket to mast as shown using 2 U bolts and supplied hardware 2 Remove antenna mounting bolt and washer from antenna base 3 Insert antenna into mounting bracket and secure with washer and antenna mounting bolt Do not overtighten 4 Any drain holes in the antenna base must be kept clear for proper operation Antenna Base Mast 2 50 8mm O D Max Drain Holes Antenna Mounting Nut amp Washer U Bolts Note Antenna Base may vary from photo Mounting Bracket Figure 4 4 Omnidirection antenna mounting Grounding the antenna Follow these guidelines to ground the antenna in accordance with national electrical code instructions Step Action 1 Use No 10 AWG copper or No 8 or larger copper clad steel or bronze wire as ground wires for both mast and lead in Securely clamp the wire to the bottom of the mast 2 Secure the lead in wire to a lightning arrestor and mast ground wire to the building with stand off insulators spaced from 4 feet 1 2 meters to 8 fe
62. are required for single and dual thermocouple input combinations 5 Digital input switches DI must be dry contact type simple apparatus and property segregated from all other sources of power 90033269 Honeywell Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 73 October 2010 6 Certification Installation Requirements WIRELESS UNIVERSAL I O STUW700 STUW701 HAZARDOUS LOCATION Ex ia IIB T4 Ta 70 C Ex tD A20 IP66 T90 C Ex nA nL IIC T4 Ta lt 84 C 80 C WITH OPTION DC Ex tD A22 IP66 T90 C AMBIENT LIMITS 40 C lt Ta 84 C s 80 C WITH OPTION DC SIUWTOD POSSIBLE SONDERN UG mv DIGITAL PV1 PY T C i my 4 TR TL i mv HIGH LEVEL ANALOG INPUT A DIGITAL INPUT AND T C DIGITAL OUTPUT ENTITY FIELD WIRING PARAMETERS PARAMETERS Ui Vmax 2 30 V Ca 100 pF 2 Cesc Ii Imax 125 mA La 100 mH x Lecane Pi 1 0 W Ci 6 8 nF Li 0 1 uH NOTES 1 Shielded HLAI DI DO thermocouple mV or switch input cable Is required for EMC conformity and is recommended for all installations The shield shall be grounded at the transmitter end only If the shield is grounded at the switch remate HALA transmitter location or remote DO supply the shield shall not be connected at the Wireless transmitter end Honeywell SCALE NONE NONE REV E DATE 0915 10 SH 6 of 11 74 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Inst
63. ay be damaged Do not apply excessive force e Do not drop Dropping the battery may cause damage If a battery is dropped do not install the dropped battery into the transmitter Dispose of dropped battery promptly per local regulations or per the battery manufacturer s recommendations ATTENTION Both batteries must be the same model from the same manufacturer Mixing old and new batteries or different manufacturers is not permitted Use only the following 3 6V lithium thionyl chloride Li SOCI2 batteries non rechargeable size D No other batteries are approved for use in XYR 6000 Wireless Transmitters e Xeno Energy XL 205F e Eagle Picher PT 2300H e Tadiran TL 5930 s e Honeywell p n 50026010 501 Two 3 6V lithium thionyl chloride batteries e Honeywell p n 50026010 502 Four 3 6V lithium thionyl chloride batteries e Honeywell p n 50026010 503 Ten 3 6V lithium thionyl chloride batteries These instructions are divided into two procedures for e IS Battery Holder 50025288 502 e S Battery Pack 50047517 501 40 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 5 Start up 5 1 Battery Power Option e 1 Phillips Screwdriver or 1 8 Slotted Screwdriver Tools l Torque Screwdriver required 3 e 1 5mm hex key Procedure It is the User Installer s responsibility to install the XYR 6000 Wireless Transmitters in accordance with national and local code requirements IS Battery Holder 500252
64. ay be wires in the wall Before drilling check that the area is clear of any obstructions or other hazards 6 Pull the cable through the hole and form a drip loop on the outside close to where the cable enters the building The drip loop should have a radius of at least 12 inches 30 cm 12 30cm Drip loop To lightning arrestor amp antenna 7 Thoroughly waterproof the lead in area 8 Connect the lead in cable to the XYR 6000 Transmitter Tighten cables by hand only do not use tools or you could overtighten Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 39 October 2010 5 Start up 5 1 Battery Power Option 5 Startup 5 1 Battery Power Option Connect batteries A WARNING e Risk of death or serious injury from explosion or fire e lf IS Battery Pack Honeywell 50047517 501 has been installed in the Wireless Transmitter the transmitter enclosure maybe opened when an explosive gas atmosphere is present Otherwise do not open transmitter enclosure when and explosive gas atmosphere is present When not in use the Battery Pack must be stored in a non Hazardous Area e Do not change batteries in an explosive gas atmosphere e The batteries used in this device may present a risk of fire or chemical burn if mistreated Do not recharge disassemble heat above 100 C 212 F or incinerate e When installing batteries do not snag the battery terminal on the clip or the battery m
65. ctober 2010 Certification Installation Requirements Certification Drawings 24Vdc IS POWER SUPPLY OPTION DC SYSTEM DIAGRAM HAZARDOUS LOCATION Ex ia IIB 14 Ta 70 C DIP A20 IP66 T909C Ex nA nL IIC 14 Ta 80 C DIP A22 IP66 T90 C AMBIENT LIMITS 40 lt Ta lt 80 C XYR 6000 TRA NSM TTER Tum ee 5 nf TYPICAL and Maximum Cable Inductance SD 01mH Ses Hole 5 Terminate and insulate shield as close lo terminal block as possible Cable to be shielded twisted pair D with total loop resistance s 6 613 NON HAZARDOUS or ZONE 2 LOCATION MTL 726P BASOLATEXT 202 EEx ia TIC 209 Ta s 60 BASOLATEX7203 EEx la IIC 116 20 C lt Ta 60 C MTL 7728 BASO1ATEX7217 EEx ia IIC 209C Ta 60 0 BARRIER ENTITY OUTPUT LOAD PARAMETERS TERMINALS 3 amp 4 Uo 28 V Io 171 mA Po 1 2 W Rmin 234 6 0 Co 2 15 uF Lo 14 mH LR 340 pts ASSOCIATED APPARATUS ENCLOSURE ROTTED FOR THE ENVIRONMENT WHERE INSTALLED Ogee eas rene ET pee els ee i MTL 728P l MTL 7728P 24 Vde Supply 21 Vimin de 26 0 Vmax xs i ashy TE EE ete a eae Angrowne SHIELD AT THIS END ONLY NON HAZARDOLUS LOCATION GROUND SHIELD AT A i THIS END ONLY P 90033269 REV E DATE 09 15 10 Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide T7 October 2010 6 Certification Installation Requirements 78 REMOTE ANTENNAS MUST
66. e to terminal block as possible UM en Tr Cable to be shielded twisted pair Tb with total loop resistance 6 60 NON HAZARDOUS LOCATION 24 Vdc Supply 16 0 V min LL 28 0 Vines 100 MAmax N ANSA SHIELD AT THIS END ONLY Honeywell SCALE NONE REV E DATE 09 240 Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 55 October 2010 6 Certification Installation Requirements REMOTE ANTENNAS MUST BE PASSIVE ELEMENTS ONLY ELBOW ANTENNA XYR 6000 TRANSMITTER TYPICAL STRAIGHT ANTENNA REMOTE ANTENNA mi CONNECTOR A Honeywell nami 56 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings Non Incendive Field Wiring parameters for remote antennas cables amp lightning arrestor Ca x 43 uF La s 48 mH aay CABLE A LMR 400DB TYPE N MALE 90018110 001 Im 3 3 ft 300181 10 003 3m 10 ft 30018110 010 10m 33 ft CABLE B LMR 400DB o TYPE N MALE 50018278 001 1m 3 311 TYPE N MALE 50018278 003 3m 10 ft 50018278 010 10m 33ft REMOTE ANTENNA Cable A XYR 6000 WIRELESS TRANSMITTER PTS REMOTE KE ANTENNA AYR 6000 WIRELESS TRANSMITTER LIGHTNING SURGE ARRESTOR Cable A Cable B my mm EI d 4 F d a 1 a de fe d T E st CABLE PARAMETERS 0 2 pH 0 6 pH 2 0 pH NOTES
67. electrical parameters of the cable are unknown the following values may be used Capacitance 197pF m Inductance 0 66uH m Z For ATEX tx ll 1 2 3 GD EC 60079 0 Ex IVI installations where rigid metal conduit is not used seal cable entnes against dust and fibers using a certified cable gland fitting 8 Control equipment that is connected to associated apparatus must not use or generate more than 250 V D Associated apparatus must be ATEX certified Associated apparatus may be installed in a Zone 2 location if so approved A di Non Galvanically isolated apparatus grounded ener Barriers must be connected to a suitable ground electrode per IEC 60079 14 Clause 12 2 4 The resistance of the ground path must be less than 1 0 ohm 11 Shielded two wire cable is required for EMC conformity and is recommended for all installations The 4 20 mA loop shield shall be grounded at the supply barrier end to the barrier ground bus only when grounded Zener barriers are used The 4 20 mA loop shield shall be grounded at the transmitter end only when galvanically isolated barriers are used MASTER FILE TYPE MS WORD DOCUMENT Honeywell ENGINEERING oeoenl ATEX Control Drawing CHANGE ORDERS We FR ege ECOs MUST BE NOTE wu AYR 6000 Wireless Transmitters AUTHORIZED BY meene Zones 0 1 amp 2 APPROVALS ENGINEERING ose A TOLERANCE UNLESS NOTED AA 90 0332 69 ANGULAR DIMENSION SCALE USED ON 5H 1 OF 11 Hevision 9 OneWir
68. eless XYR 6000 Transmitters Quick Start Guide 69 October 2010 6 Certification Installation Requirements 70 12 Zone D or Zone 1 WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS 13 Zone 2 WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA 15 KNOWN TO BE NON HAZARDOUS 14 NO REVISION OF THIS CONTROL DRAWING IS PERMITTED WITHOUT AUTHORIZATION FROM THE NOTIFIED BODY 15 For release approvals see ECO 0048814 XYR 8000 STIWOD Associated Apparatus uww uww 30 V WUos3V WUos3V 30 V ini i E 5 S i EL INE E i Associated Apparatus Co Ci 64 nF cable Ci of other transmitter connected to two channel barrier Associated Apparatus Lo Leable L 10 uH Liofother transmitter connected to two channel barrier 90033269 SCALE NONE REV E DATE 09 15 10 Honeywell OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings ATEX CERTIFIED INTRINSICALLY SAFE ia AND NON SPARKING n INSTALLATION CONTROL DRAWING TWO WIRE CONFIGURATION XYR 6000 STIW600 0 20 mA 4 20 mA HIGH LEVEL INPUT INTERFACE HAZARDOUS LOCATION XYR 6000 WIRELESS TRANSMITTER NON HAZARDOUS Ex ia IIB T4 Ta lt 70 C Ex tD A20 IP66 T90 C LOCATION Ex nA nL I
69. et 1 8 meters apart 38 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 4 Antenna adjustment and mounting 4 3 Remote antenna Step Action 3 Using coaxial cable connect the antenna base to the transmitter s remote antenna connector located at top right as you face the transmitter display Antenna cable shield is bonded to earth ground via either the transmitter earth ground connection and or by the lightning arrestor earth ground connection The lightning arrestor must be bonded to earth ground in order to function properly Tighten cables by hand only do not use tools or you could overtighten See pages 57 68 79 and 90 for cable types and connection information 4 If the coax cable is to enter a building then the lightning arrestor should be mounted as close as possible to where the lead in wire enters the building The lightning arrestor sold by Honeywell features a bulkhead N Female connector with a rubber O ring seal which can be used for mounting through an enclosure wall The lightning arrestor can also be mounted using the included stainless steel mounting bracket Both connector ports of the lightning arrestor provide equal protection no matter which way it is installed Either port can face the antenna and either port can face the Transmitter 5 Drill a hole in the building s wall as close as possible to the equipment to which you will connect the lead in cable CAUTION A There m
70. formance Follow these steps to determine a safe distance from wires power lines and trees Step Action 1 Measure the height of your antenna 2 Add this length to the length of your tower or mast and then double this total for the minimum recommended safe distance d CAUTION If you are unable to maintain this safe distance stop and get professional help OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 4 Antenna adjustment and mounting 4 3 Remote antenna Generally speaking the higher your antenna is above the ground the better it performs Good practice is to install your antenna about 5 to 10 feet 1 5 to 3 meters above the roof line and away from all power lines and obstructions If possible find a mounting place directly above your wireless device so that the lead in cable can be as direct as possible Mounting the Antenna Antennas are provided with a mast mounting kit consisting of a mounting bracket and two U bolt clamps This kit allows you to mount the antenna to masts with outside diameters O D from 1 25 inches 3 2 centimeters to 2 inches 5 1 centimeters Honeywell recommends that a 1 5 inch 3 8 centimeter or larger tubing mast be used Omnidirectional antennas are vertically polarized It is very important to mount the antenna in a vertical not leaning position for optimal performance Follow these steps to mount the antenna on a mast Step Action 1 Assemble your ne
71. ication Installation Requirements WIRELESS UNIVERSAL UO STUW700 STUW701 HAZARDOUS CLASSIFIED LOCATION CLASS I DIV 2 GROUPS A B C D CLASS II DIV 2 GROUPS F amp G CLASS III DIV 2 TA CLASS ZONE 2 Ex AEx nA GROUP IIC T4 AMBIENT LIMITS 40 Ta s 85 C 5 80 C WITH OPTION DC STUW700 POSSIBLE CONNECTIONS T C mV DIGITAL DIGITAL INPUT AND T C NON INCENDIVE FIELD WIRING PARAMETERS Ca 2 7 pF gt Coane La 100 mH Leine HIGH LEVEL AMALOG INPUT NON INCENDIVE FIELD WIRING amp DIGITAL OUTPUT NON INCENDIVE FIELD CIRCUIT PARAMETERS Ui Vmax 30 V li Imax 125 mA Pj 1 0 W Cj 6 8 nF Li 0 1 uH NOTES 1 Shielded HAI DI DO thermocouple mV or switch input cable is required for EMC conformity and is recommended for all installations The shield shall be grounded at the transmitter end only If the shield is grounded at the switch remote HL A transmitter location or remcte DO supply the shield shall not be connected at the Wireless transmitter end Honeywell SCALE NONE REV E DATE 03 24 10 Revision 9 October 2010 52 OneWireless XYR 6000 Transmitters Quick Start Guide Certification Installation Requirements Certification Drawings XYR 6000 MODEL CETW6000M W WIRELESS CORROSION TRANSMITTER AND CETW6000M D SmartCET CORROSION DATA LOGGER HAZARDOUS CLASSIFIED LOCATION CLASS I DV 2 GROUPS A B C D CLASS Il GROUPS F amp G CLASS III DIV 2 T4 CLASS I ZONE 2 Ex
72. igital Inputs Wireless Temperature Transmitter STUW701 Wireless Universal UO Interface STTW820 SITWS830 Wireless Temperature Transmitter SITTW840 STIW6DD Wireless High Level Input Interface 4 20 mA Analog Input pee SmartCET Wireless Transmitter Millrvolt Input from Remote Mounted CETW6000M W Corrosion Monitoring Corrosion Probe n Milivolt Input from Remote Mounted CETW6000M D SmartCET Corrosion Data Logger C mosi n Probe Data via KDA Port There is no Antenna for this version The above listed wireless transmitters may include an Omni directional or unidirectional high gain antenna The high gain antenna may be installed remote from the XY R 6000 with the cable length not to exceed 20m The antenna cable shield shall be bonded to earth ground Transmitter Integrally Mounted to Thermowell or Probe Assembly NON INCENDIVE FIELD CIRCUIT PARAMETERS for remote antennas cables amp lightning arrestor Ca 43 pF La 0 1 mH Honeywell SCALE NONE REV E DATE 09 2410 54 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Certification Installation Requirements Certification Drawings DIV 2 ZONE 2 HAZARDOUS AND NON HAZARDOUS LOCATIONS CLASS I DIV 2 GROUPS A B C D CLASS Il GROUPS F amp G CLASS IIl T4 grs CLASS ZONE 2 Ex AEx nA GROUP IIC T4 AMBIENT LIMITS 40 lt Ta 80 C XYR 6000 TRANSMITTER TYPICAL Terminate and insulate shield as clos
73. ions of highest liquid velocity and constant immersion Correct Pipeline Position Probe can be located at any point on the pipeline but should always be immersed in the corrosive material 26 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 3 Process insertion 3 5 Corrosion models Located in Tee Probe can be located at any point on the pipeline but should always be immersed in the corrosive material Located in Bypass Loop Probe should be located downstream of a control valve for best performance and can also be located in the deadleg portion of a by pass Note that the probe located in the by pass leg should be mounted before the valve for best performance This guarantees the electrodes will always be immersed in the corrosive material Mounted with Different Electrodes Installing with different electrode materials on the suction side of the pump will ensure monitoring of the pump impeller and the pipe Installed in a Condensate Flash Tank A condensate flash tank is also a good application Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 27 October 2010 3 Process insertion 3 5 Corrosion models un Pere Mounted in Y Strainer The probe is shown in the blow down of a Y strainer Mounted in Basket Strainer The probe is shown in the discharge side of the basket strainer The electrodes should be selected to reflect the same metal propertie
74. martCET Corrosion Transmitter User s Manual 34 XY 25 18 OneWireless XYR 6000 Multi Discrete Input Transmitter User s Manual 34 XY 25 27 OneWireless XYR 6000 Universal Input Output User s Manual 34 XY 25 30 Revision OneWirelessXYR 6000 Transmitters Quick Start Guide di October 2010 Notices and Trademarks Heferences Support and contact info United States and Canada Europe Pacific India Korea Contact Honeywell Process Solution Global Technical Support Phone 001 800 423 9883 Customer Service HFS Phone 001 800 343 0228 Outside United States Phone 001 215 641 3610 Calls are answered by dispatcher between 6 00 am and 4 00 pm Mountain Standard Time Emergency calls outside normal working hours are received by an answering service and returned within one hour Email support ask ssc honeywell com Mail Contact Phone Facsimile Mail Contact Phone Facsimile Mail Email Contact Phone Facsimile Mail Email Contact Phone Facsimile Mail Email Honeywell Process Solutions 1860 West Rose Garden Lane Phoenix Arizona 85027 Honeywell TAC EMEA 32 2 728 2732 32 2 728 2696 TAC BEO2 Hermes Plaza Hermeslaan IH B 1831 Diegem Belgium Honeywell Global TAC Pacific 1300 300 4822 toll free within Australia 61 8 9362 9559 outside Australia 61 8 9362 9564 Honeywell Limited Australia 5 Kitchener Way Burswood 6100 Western Australia
75. mast e Attach guy wires to a mast using guy rings 7 Carefully connect the antenna and mast assembly to its mounting bracket and tighten the clamp bolts In the case of a guyed installation you must have at least one assistant to hold the mast upright while the guy wires are attached and tightened to the anchor bolts 8 Attach the provided self adhering DANGER label at eye level on the mast 9 Install ground rods to remove any static electricity buildup and connect a ground wire to the mast and ground rod Use ground rods designed for that purpose do not use a spare piece of pipe Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 35 October 2010 4 Antenna adjustment and mounting 4 3 Remote antenna Step Action 10 When attaching the coax cable to the XYR 6000 it is recommended that a drip loop with a radius of at least 12 inches 30 cm be formed close to the XYR 6000 This will minimize ice and water buildup on the transmitter itself Tighten cables by hand only do not use tools or you could overtighten To lightning arrestor amp antenna 12 30cm Drip loop 36 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 4 Antenna adjustment and mounting 4 3 Remote antenna Directional mounting procedure Step Action 1 Secure mast mounting bracket to mast as shown using 2 U bolts and supplied hardware 2 Attach antenna to mast mounting bracket as shown using supplied h
76. n 12 0 1A 25mW or 204 such as switches thermocouples and RTDs 3 The Intrinsic Safety ENTITY concept allows the interconnection of two ENTITY Approved Intrinsically safe devices with ENTITY parameters not specifically examined in combination as a system when Uo or Voc or Vt in the USA Ui or Ymax lo or lsc or Itin the USA li or Imax Ca or Co gt Ci Ccable La or Lo Li Leable Po Pi Where two separate barrier channels are required one dual channel or two single channel barriers may be used where in either case both channels have been Certified for use together with combined entity parameters that meet the above equations d System Parameters AYR 6000 and Field Transmitter Vmax Voc or Uo Imax Isc or lo AYR 6000 Ci Field Transmitter Ci Ccable Control Apparatus Ca AYR 6000 Li Field Transmitter Li Leable Control Apparatus La 5 When the electrical parameters of the cable are unknown the following values may be used Capacitance 187pF m 60 pF ft Inductance Q0 66uH m 0 020 uH ft 6 For Class Il and Class Ill installations where rigid metal conduit is not used seal cable entries against dust and fibers using a NRTL listed cable gland fitting T Control equipment that is connected to Associated apparatus must not use or generate more than 250 V B Associated apparatus must be CSA Certified under the ENTITY Concept in Canada and FM ENTITY listed in the USA Associated apparatus may be installed
77. n 47 Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide IX October 2010 1 Introduction Tables Table 2 1Display adjustment sessi nn nnn nni nnn nnns nana nnns nain nnns 16 Table 5 1 Battery replacement procedure oooncccnccccncccncccnoncnnnononanonnnnnnnnnnnnononnnnnnnnnnnnnrnnnonnnnrnnnnrnnnnnnnnnnnannons 42 Table 5 2 IS Battery Pack replacement orocedure nennen nnne nnns 43 Figures Figure 1 Temperature DI Multi DI HLAI Corrosion transmitter dimensions esses 6 Figure 2 Universal I O Temperature DI Multi DI HLAI Corrosion antenna dimensions 7 Figure 3 DP DHGP Pressure transmitter dimensions cccccoconcnnccccnnnnnncnononnnonnncnncnnnononancnnnnnonancnnnnnnnanennnoss 8 Figure 4 DP DHGP Pressure antenna dimensions nn nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 9 Figure 5 GP AP Pressure transmitter dumensions nennen nnne nnns 10 Figure 6 GP AP Pressure antenna dmensions nennen nennen nnns nnn nnns 11 Figure 7 Common bracket Orientations nennen nennen nnns nnns nnn na nn nen rrr sna 13 Figure 8 Rotating transmitter housing E 15 Figure 9 DISDIAY te Le coins cad 16 Figure 10 Typical 3 valve manifold and blow down piping arrangement nennen nennen 17 Figure 11 Typical Arrangement for 12 NPT Process Connection Piping nn 18 Figure T2 Temperature ite e 20 Figure 13 BEAT COMMECHON aaa 21 Figure 14 Voltage INDUL WIFIDIQusae dta did 21 Figure 19 GUrrent IOUT WIEIFIGE see sel
78. nch uninsulated piping 18 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Process connections 3 Process insertion 3 1 Pressure models Differential Pressure Gauge Pressure Absolute Pressure General piping guidelines Process heads with 1 4 inch NPT female connection Flange adapters and manifolds with 1 2 inch female connection are optional Process head with 1 2 inch NPT female connection In line Ya inch NPT female connection In line 1 2 inch NPT male 9 16 Aminco DIN19213n Process heads with 1 4 inch NPT female connection Flange adapters and manifolds with Y inch female connections are optional Process head with 1 2 inch NPT female connection In line Y inch NPT male 9 16 Aminco DIN19213n When measuring fluids containing suspended solids install permanent valves at regular intervals to blow down piping Blow down all lines on new installations with compressed air or steam and flush them with process fluids where possible before connecting these lines to the transmitter s meter body Be sure all the valves in the blow down lines are closed tight after the initial blow down procedure and each maintenance procedure after that Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 19 October 2010 3 Process insertion 3 2 Temperature and Discrete Input models 3 2 Temperature and Discrete Input models Insert probe into process n ATTENTIO
79. nd Figure 3 8 Corrosion transmitter with remote probe 30 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 4 Antenna adjustment and mounting 4 1 Requirements 4 Antenna adjustment and mounting 4 1 Requirements Radio installation requirements ATTENTION Professional Installation is required to insure conformity with Federal Communications Commission FCC in the USA Industry Canada IC in Canada and the Radio and Telecommunications Terminal Equipment Directive 1999 5 EC R amp TTE in the European Union EU Professional installation is required for the selection and installation of approved antennas and setup of the maximum allowable radiated power from the XYR 6000 Wireless Transmitter as configured for the particular installation site The antenna used for this transmitter must be installed to provide a separation distance of at least 20 cm 8 inches from all persons and must not be co located or operating in conjunction with any other antenna or transmitter For remote antenna see antenna installation requirements to satisfy FCC RF exposure requirements ATTENTION Federal Communications Commission FCC The XYR 6000 Wireless Transmitters comply with part 15 of the FCC rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause
80. ntenna for best reception Do not rotate antenna more than 180 degrees either direction or you could damage internal wiring Tighten set screw Straight Figure 4 2 Integral straight antenna Straight Antenna ONLY available in 2 dBi configuration If your model has the integral straight antenna Figure 4 2 you can adjust its position by rotating the transmitter housing See page 15 Typically pointed straight up gives best performance but your installation may vary 32 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 4 Antenna adjustment and mounting 4 3 Remote antenna 4 3 Remote antenna Outdoor installation warnings WARNING LIVES MAY BE AT RISK Carefully observe these instructions and any special instructions that are included with the equipment you are installing WARNING Contacting power lines can be lethal Look over the site before beginning any installation and anticipate possible hazards especially these Make sure no power lines are anywhere where possible contact can be made Antennas masts towers guy wires or cables may lean or fall and contact these lines People may be injured or killed if they are touching or holding any part of equipment when it contacts electric lines Make sure there is NO possibility that equipment or personnel can come in contact directly or indirectly with power lines Assume all overhead lines are power lines The horizontal distance f
81. ps A B C amp D CL Il Div 2 Groups F G CL Ill Div 2 T4 CL I Zone 2 AEx nA IIC T4 Il 3 GD Ex na llc T4 Ta 85 C Zone 2 111 GD Ex ia IIB TA Ta 70 C Ex tD A20 IP66 T90 C 112 GD Ex d ia IIB T4 Ta 70 C Ex tD A21 IP66 T90 C o 113 GD Ex na nt IIC T4 Ta 85 C Ex tD A22 IP66 T90 C Ex ia IIB T4 Ta 70 C DIP A20 IP66 T90 C Ex d ia IIB T4 Ta 70 C DIP A21 IP66 T90 C Ex nA nL IIC T4 Ta 85 C DIP A22 IP66 T90 C A Division 2 Zone 2 apparatus may only be connected to processes classified as non hazardous or Division 2 Zone 2 Connection to hazardous flammable or ignition capable Division 1 Zone O or 1 process is not permitted Enclosure Type Type 4X IP 66 Canadian Registration Number Class II and Ill installations and Type 4X IP66 applications require that all cable and unused entries be sealed with a NRTL National Recognized Testing Laboratory listed cable gland or conduit plug Cable glands and conduit plugs are not supplied with the product OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Introduction Certifications and approvals Radio certifications The XYR 6000 Wireless Transmitters comply with part 15 of FCC ID 85750016517 the FCC rules Operation is subject to the following two Federal conditions Communications Or I 1 this device may not cause harmful interference and Commission FCG Ecc ID 85750025034
82. rangement will vary depending upon the process measurement requirements and the transmitter model Except for flanged and remote diaphragm seal connections process connections are made to 4 inch or Y inch NPT female connections in the process head of the transmitter s meter body For example a differential pressure transmitter comes with double ended process heads with 1 4 inch NPT connections but they can be modified to accept 1 2 inch NPT through optional flange adapters Some gauge pressure transmitters may have a 1 2 inch NPT connection which mounts directly to a process pipe The most common type of pipe used is Y2 inch schedule 80 steel pipe Many piping arrangements use a three valve manifold to connect the process piping to the transmitter A manifold makes it easy to install and remove or rezero a transmitter without interrupting the process It also accommodates the installation of blow down valves to clear debris from pressure lines to the transmitter Figure 3 1 shows a diagram of a typical piping arrangement using a 3 valve manifold and blow down lines for a differential pressure transmitter being used to measure flow To Downstream Tap To Upstream Tap Biow Down CN 3 Valve 7 Blow Down Valve Manifold Valve V V Ko Blow Down gt lt Blow Down Be eg To Low Pressure To High Pressure Side of Transmitter Side of Transmitter To Waste To Waste 21010 Figure 3 1 Typical 3 valve manifold and blow down piping arr
83. rods using 1 OAWG ground wire and corrosion resistant connectors Refer to the National Electrical Code for grounding details Lightning arrestors for antenna feed coaxial cables are available from HyperLink Technologies Inc WARNING If a person comes in contact with electrical power and cannot move DON T TOUCH THAT PERSON OR YOU MAY BE ELECTROCUTED Use a non conductive dry board stick or rope to push or drag them so they no longer are in contact with electrical power Once they are no longer contacting electrical power administer CPR if you are certified and make sure that emergency medical aid has been requested Choosing a Mounting Location The location of the antenna is important Objects such as metal columns walls etc will reduce efficiency Best performance is achieved when antennas for both Multinodes and XYR 6000 Transmitters Leaf Nodes are mounted at the same height and in a direct line of sight with no obstructions If this 1s not possible and reception is poor you should try different mounting positions to optimize reception Antennas should be mounted clear of any obstructions to the sides of the radiating element If the mounting location for an omnidirectional antenna is on the side of a building or tower then the antenna pattern will be degraded on the building or tower side Site Selection 34 Before attempting to install your antenna think where you can best place the antenna for safety and per
84. rom a tower mast or antenna to the nearest power line should be at least twice the total length of the mast antenna combination This will ensure that the mast will not contact power if it falls either during installation or later WARNING To avoid falling use safe procedures when working at heights above ground Select equipment locations that will allow safe simple equipment installation Don t work alone A friend or co worker can save your life if an accident happens Use approved non conducting ladders and other safety equipment Make sure all equipment is in good repair If a tower or mast begins falling don t attempt to catch it Stand back and let it fall If anything such as a wire or mast does come in contact with a power line DON T TOUCH IT OR ATTEMPT TO MOVE IT Instead save your life by calling the power company Don t attempt to erect antennas or towers on windy days Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 33 October 2010 4 Antenna adjustment and mounting 4 3 Remote antenna WARNING MAKE SURE ALL TOWERS AND MASTS ARE SECURELY GROUNDED AND ELECTRICAL CABLES CONNECTED TO ANTENNAS HAVE LIGHTNING ARRESTORS This will help prevent fire damage or human injury in case of lightning static build up or short circuit within equipment connected to the antenna The base of the antenna mast or tower must be connected directly to the building protective ground or to one or more approved grounding
85. rs AYR 6000 and Field Transmitter Ui Uo li lo AYR 6000 Ci Field Transmitter Ci Ccable Associated Apparatus Co AYR 6000 Li Field Transmitter Li Leable Associated Apparatus Lo D When the electrical parameters of the cable are unknown the following values may be used Capacitance 197pF m Inductance 0 66uH m T ForlECEx 60079 0 Ex III installations where rigid metal conduit is not used seal cable entries against dust and fibers using a certified cable gland fitting 8 Control equipment that is connected to associated apparatus must not use or generate more than 250 Y D Associated apparatus must be IECEXx certified Associated apparatus may be installed in a Zone 2 location if so approved 10 Mon Galvanically isolated apparatus grounded Zener Barriers must be connected to a suitable ground electrode per IEC 60079 14 Clause 12 2 4 The resistance of the ground path must be less than 1 0 ohm 11 Shielded two wire cable is required for EMC conformity and is recommended for all installations The 4 20 mA loop shield shall be grounded at the supply barrier end to the barrier ground bus only when grounded Zener barriers are used The 4 20 mA loop shield shall be grounded at the transmitter end only when galvanically isolated barriers are used MASTER FILE TYPE MS WORD CERTIFICATION Honeywell SEN DOCUMENT ENGINEERING Ed IECEx Control Drawing LEE pevewe NOTE mg XYR i apg Denge Io one one ENGI
86. s as the piping or other components that might be susceptible to corrosion For example in applications where the pipe is made of stainless steel and the water pump s impeller is made of carbon steel the impeller will corrode faster than the pipe In this case it is advisable to select the electrodes to be the same material as the pump s impeller 28 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 3 Process insertion 3 5 Corrosion models Probe installation A Step Revision 9 October 2010 WARNING If the pipe or vessel into which the probe is to be inserted is under pressure and or contains any hazardous substance such as steam caustic solutions acids toxins or other substances specified by OSHA as physical or health hazards the pipe or vessel must first be depressurized and any hazardous substance purged there from and appropriate lockout tagout procedures observed in accordance with Section 1910 147 of the OSHA Regulations before the probe can be installed Failure to follow these procedures may result in serious injury or death Action 41 8 EJ Hex Flat Hex Flat 2 x TY Some probes are supplied with an adjustable compression NPT fitting e g Swagelok With this fitting follow this tightening sequence to ensure a tight seal a The Swagelok fitting should be held onto place with a plastic zip tie around the probe body The zip tie should be removed b Determine the depth
87. ssure sisemi psig d STGW9SL 0 10 000 psi 0 690 bar SITAWSAL 0 500 psi 0 35 barA STTW400 Wireless Temperature Transmitter ERO Remote Sensors STTIWA401 Wireless Temperature and Digital Transmitter Only with Remote Sensors Input Transmitter 1 T C AND 2 Digital Inputs STXW500 Wireless Digital Input Transmitter Three DI Switch Inputs SIUWTDO Wireless Universal HO Interface STUW701 Wireless Universal VO Interface Co puts 2 m Analog TG or DI and STTW820 1 STTW830 Wireless Temperature Transmitter Transmitter Integrally Mounted to Thermowell STTWB840 or Probe Assembly S TIWW600 Wireless High Level Input Interface 4 20 mA Analog Input T smartCET Wireless Transmitter Millrvalt Input from Remote Mounted ENDE NE Corrosion Monitoring Corrosion Probe Millivolt Input from Remote Mounted CETW6000M D SmartCET Corrosion Data Logger Corrosion Probe Data via IrDA Port There is no Antenna for this version The above listed wireless transmitters may include an Omni directional or unidirectional high gain antenna The high gain antenna may be installed remote from the X YR 6000 with the cable length not to exceed 20m The antenna cable shield shall be bonded to earth ground IS Entity parameters for remote antennas cables amp lightning arrestor Ca 43 pF La 0 1 mH Honeywell Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide October 2010 SCALE NONE REV D DATE 09 16 10 SH 8 of 11
88. t of the condensate connection This requires a siphon to protect e Level with or above the the transmitter from process process connection steam The siphon retains water as a fill fluid 2 4 Conduit Cable Entries NOTICE THIS PRODUCT IS SUPPLIED WITH PLASTIC DUST PLUGS IN THE CONDUIT CABLE GLAND ENTRIES IT IS THE USERS RESPONSIBILITY TO PROVIDE CABLE GLANDS ADAPTORS AND OR BLANKING PLUGS SUITABLE FOR THE ENVIRONMENT IN WHICH THIS PRODUCT IS INSTALLED WHEN INSTALLED IN A HAZARDOUS LOCATION THE CABLE GLANDS ADAPTORS AND OR BLANKING PLUGS SHALL ADDITIONALLY BE SUITABLE FOR THE HAZARDOUS LOCATION THE PRODUCT CERTIFICATION AND ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION FOR THE INSTALLATION 12 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 2 Transmitter Mounting 2 5 Bracket mounting 2 5 Bracket mounting Attach bracket to pipe Figure 2 7 shows some commonly used bracket and pipe orientations Not all possibilities are shown you can use any bracket flat or angle and orientation parallel or transverse to get the desired transmitter positioning Position bracket on 2 inch 50 8 mm pipe and install U bolt around pipe and through holes in bracket Secure with nuts and lockwashers provided Figure 2 7 Common bracket orientations Revision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 13 October 2010 2 Transmitter Mounting 2 5 Bracket mounting
89. taly Hevision 9 October 2010 B C C G Y Z K E ISO 3166 2 letter code OneWireless XYR 6000 Transmitters Quick Start Guide Country Latvia Liechtenstein Lithuania Malta Netherlands Norway Poland Portugal Romania Slovakia Slovenia Spain Sweden Switzerland United Kingdom ISO 3166 2 letter code 1 Introduction 1 3 Certifications and approvals Hazardous location certifications Refer to product label for applicable approvals Approval Item Ratings Description CSAcus Intrinsically Safe FM Approvals FM Approvals FM Approvals HON ATEX KEMA 08 ATEX0062X Intrinsically Safe Flameproof Non Sparking IECEx CSA 08 0007X Intrinsically Safe Flameproof Non Sparking Process Connections in Division 2 Zone 2 CL I Div 1 Groups A B C amp D CL II Div 1 Groups E F amp G CL Ill T4 CL I Zone 0 Ex ia IIC T4 CL I Zone 0 AEx ia IIC T4 CL I Div 1 Groups A B C D CL Il Div 1 Groups E F amp G CL III T4 CL I Zone 1 Ex d IIC T4 CL I Zone 1 AEx d IIC T4 CL I Div 2 Groups A B C amp D CL II Div 2 Groups F G CL Ill Div 2 T4 CL I Zone 2 Ex nA IIC T4 CL Zone 2 AEx nA IIC T4 CL I Div 1 Groups A B C amp D CL II Div 1 Groups E F amp G CL IIl T4 CL I Zone 0 AEx ia IIC T4 CL I Div 1 Groups A B C amp D CL II Div 1 Groups E F amp G CL Ill T4 CL I Zone 1 AEx d IIC T4 CL I Div 2 Grou
90. that the probe should extend into the pipe c Tighten the larger upper nut until the tubing will not rotate freely by hand d Make a mark on the nut This mark will serve as a reference as the 6 o clock position e While holding fitting body steady tighten the large upper nut 1 1 4 turns to the 9 o clock position f This tightening sequence will crimp the internal ring onto the probe body and should lock the fitting in place now g Tighten the lower nut onto the pipe nipple or access point For fixed type probes without the adjustable compression fitting only the 1 1 16 hex nut needs to be tightened and the safety bracket is not required Ensure the flow rate of the process fluid does not exceed 20 feet per second fps Stronger flow might damage probes with three finger electrodes and interfere with the reading If the flow rate exceeds the recommendation a different probe style may be required OneWireless XYR 6000 Transmitters Quick Start Guide 29 3 Process insertion 3 5 Corrosion models Connect wiring Step Action 1 See Figure 3 8 Open the transmitter s rear end cap opposite end from display 2 Open the cable gland on right side below antenna Cable gland must be ordered as an option 3 Feed probe wiring through the cable gland and connect to terminal block See Figure 3 8 For terminal connections see info starting on page 47 4 Plug battery connector into batteries 9 Close rear end cap and cable gla
91. the accompanying notes and text 47 OneWireless XYR 6000 Transmitters Quick Start Guide 6 Certification Installation Requirements COPYRIGHT 2010 HONEYWELL INTERNATIONAL INC NEITHER THIS DOCUMENT NOR THE PREREL INFORMATION CONTAINED HEREIN SHALL BE REPRODUCED USED OR DISCLOSED To OTHERS WITHOUT THE WRITTEN AUTHORIZATION OF HONEYWELL USE DUPLICATION OR Iss REVISION amp DATE APPD DISCLOSURE OF THIS DOCUMENT IS SUBJECT TO THE RESTRICTIONS SET FORTH IN A WRITTEN AGREEMENT NOTHING CONTAINED HEREIN SHALL BE CONSTRUED AS 09 24 10 CONFERRING BY IMPLICATION ESTOPPEL OR OTHERWISE ANY LICENSE TO ANY PATENT E ECO 0069377 VM TRADEMARK COPYRIGHT OR OTHER INTELLECTUAL PROPERTY RIGHT OF HONEYWELL OR 7 AHY THIEN PARTY XYR 6000 WIRELESS TRANSMITTERS CSA CERTIFIED amp FM APPROVED DIVISION 2 ZONE 2 INSTALLATION DRAWING NOTES 1 Division 2 Zone 2 installation shall be in accordance with the Canadian Electrical Code CEC part Section 18 for Canada ANSI NFPA 70 NEC Articles 501 4 b or 505 15 c for the USA and ANSI ISA 12 12 01 2 System Parameters AYR 6000 and Field Transmitter Vmax Voc or Uo Imax Isc or lo AYR 6000 Ci Field Transmitter Ci Ccable Control Apparatus Ca AYR 6000 Li Field Transmitter Li Lcable Control Apparatus La 3 When the electrical parameters of the cable are unknown the following values may be used Capacitance 19 pF m 60 pF ft Inductance 0 66uH
92. the product manual for additional information The symbol appears next to required information in the manual WARNING Risk of electrical shock Potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms 42 4 Vpeak or 60 VDC may be accessible WARNING Indicates a potentially hazardous situation which if not avoided could ESD HAZARD Danger of an electro static discharge to which equipment may be sensitive Observe precautions for handling electrostatic sensitive devices P ab Protective Earth PE terminal Provided for connection of the protective earth green or green yellow supply system conductor Functional earth terminal Used for non safety purposes such as noise immunity improvement NOTE This connection shall be bonded to Protective Earth at the source of supply in accordance with national local electrical code requirements Earth Ground Functional earth connection NOTE This connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements Chassis Ground Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements i IF ab continued vi OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 October 2010 Revision 9 October 2010 Notices and Trademarks Symbol Definitions
93. to terminal block as possible Cable to be shielded twisted pair with total loop resistance 6 60 NON HAZARDOUS LOCATION or CSA Class Div 2 Gps A B C D Ex nA ia 116 T4 Class Zone 2 AEx nA IIC T4 FM A2 II Entity ABCDEFG NII 2 ABCD TA VO AEx ia IC Entity NITIA AMBIENT LIMITS 20 Ta 60 C ASSOCIATED APPARATUS INSTALLATION SHALL BE IN ACCORDANCE WITH THESE MTL CONTROL DRAWINGS BARRIER CSA CERTIFIED FM APPROVED MTL 728P SCI 344 SCI 328 MTL 7728P sCI 3r0 01 942 ASSOCIATED APPARATUS ENCLOSURE RATED FOR THE ENY NMED HT WHERE INSTALLED I MTL 728P E MTL 7728P eor 24 Vde Supply TT 21 Vmin C AR e a Don SR i me Sor s ui GROUND SHIELD AT THIS END ONLY 90021730 SCALE NONE REV E DATE 09 24 10 SH 9 of 11 Honeywell OneWireless XYR 6000 Transmitters Quick Start Guide Revision 9 66 October 2010 Certification Installation Requirements Certification Drawings REMOTE ANTENNAS MUST BE PASSIVE ELEMENTS ONLY ELBOW ANTENNA XYR 6000 TRANSMITTER TYPICAL STRAIGHT ANTENNA REMOTE ANTENNA il CONNECTOR amp Honeywell m Hevision 9 OneWireless XYR 6000 Transmitters Quick Start Guide 67 October 2010 6 Certification Installation Requirements IS Entity parameters for remote antennas cables amp lightning arrestor Ca 43 pF La x 0 1 mH CABLE A LMR 400DB LES 50018110 001
94. trol supervisory control and controls that do not have environmental or safety consequences As with any process control solution the end user must weigh the risks and benefits to determine if the products used are the right match for the application based on security safety and performance Additionally it is up to the end user to ensure that the control strategy sheds to a safe operating condition if any crucial segment of the control solution fails Revision Information Document Name Document No Publication Date XYR 6000 Transmitters Quick Start Guide 34 XY 25 21 Rev No ATEX and IECEx control drawings and Multi DI manual added Product Ratings tables STUW700 701 8x0 Universal IO 2dBi and 4dBi antenna and 24V Power Supply details added FM CSA IECEx approval updates Nov 2009 April 2009 Sept 2009 ATEX approval updates March 2010 ISA Battery Pack added August 2010 References The following list identifies all documents that may be sources of reference for material discussed in this publication Document Title Document number Getting Started with Honeywell OneWireless Solutions OW CDX010 OneWireless Wireless Builder User s Guide OW CDX060 OneWireless Builder Parameter Reference OW CDX070 OneWireless XYR 6000 Pressure Transmitter User s Manual 34 XY 25 15 OneWireless XYR 6000 Temperature and DI Transmitter User s Manual 34 XY 25 16 OneWireless XYR 6000 HLAI Transmitter User s Manual 34 XY 25 17 OneWireless XYR 6000 S
95. w antenna on the ground at the installation site See the instructions on the following pages for your type of antenna 2 Attach the antenna to the mast and connect its coaxial cable while you are on the ground using the mounting kit provided with the antenna Tighten cables by hand only do not use tools or you could overtighten After the cable is attached to the antenna make sure that the connections are sealed if outdoors the prevent moisture and other weathering elements from effecting performance Honeywell recommends using a weathering tape such as Coax Seal for outdoor connections Silicon sealant or electrical tape is not recommended for sealing out door connections 3 Using tie wraps cable ties secure the coax cable to the mast using a tie wrap every ten to twelve inches 25 to 30 cm 4 Follow standard strain relief practice when installing the antenna cable Avoid excessive strain bending kinks or crushing stepping on or placing any weight on cable before during or after the coax cable is secured in its final position 5 Make sure the mast does not fall the wrong way should you lose control as you raise or take down the mast Use a durable non conductive rope Have an assistant tend to the rope ready to pull the mast clear of any hazards such as power lines should it begin to fall 6 If the installation will use guy wires e Install guy anchor bolts e Estimate the length of guy wire and cut it before raising the
Download Pdf Manuals
Related Search
Related Contents
Manual - Smart Program Services P/L SOP Milking - LandbrugsInfo manual de usuario PR Thorium SMS/GPRS Communicator User Manual MC68340, Integrated Processor With DMA Guía del usuario para los sistemas de sala Polycom® HDX RITES PERSONNELS DE PASSAGE Samsung ST50 Инструкция по использованию User's Manual - Blackbox-av Kingston Technology ValueRAM 8GB 1333MHz DDR3 Non-ECC CL9 DIMM Copyright © All rights reserved.
Failed to retrieve file