MVI69-EGD User Manual
Contents
1. Move the Bus Lever to the left until it clicks Bus Lever Engaged position 1 Top View 4 Close all DIN rail latches Page 14 of 96 ProSoft Technology Inc November 3 2008 Start Here MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 5 Press the DIN rail mounting area of the controller against the DIN rail The latches will momentarily open and lock into place DIN rail clasp DIN rail gt Y M TAY AY at ProSoft Technology Inc Page 15 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module 1 6 Connect your PC to the Processor 1 Connect the right angle connector end of the cable to your controller at the communications port CHANNEL 1 CHANNEL 0 2 Connect the straight connector end of the cable to the serial port on your computer Page 16 of 96 ProSoft Technology Inc November 3 2008 Start Here MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 1 7 Download the Sample Program to the Processor Important For most applications the sample program will work without modification Note The key switch on the front of the CompactLogix processor must be in the REM position 1 If you are not already online to the processo
2. Exch ID Value Status OK Set to Defaults Add Row Insert Row Delete Row Move Up Move Down Edit Row Copy Row Paste Hot OK Cancel 2 5 EGD Multicast Group List This section contains the list of multicast group addresses the EGD server should process consumer messages for this server produced on other units This list may contain up to 16 IP addresses The reserved group addresses for the EGD protocol are 224 0 7 1 to 224 0 7 32 The module will support other group addresses than this data set Important Use Multicast whenever the module produces data to at least two other modules Using Unicast for these applications can cause data transmission delay when at least one of the consumer modules is powered down 2 6 Ethernet Configuration Use this procedure to configure the Ethernet settings for your module You must assign an IP address subnet mask and gateway address After you complete this step you can connect to the module with an Ethernet cable 1 Determine the network settings for your module with the help of your network administrator if necessary You will need the following information o IP address fixed IP required o Subnet mask 2 Gateway address Click to expand the tree for the MVI69 EGD module ProSoft Technology Inc Page 33 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Configuring the MVI69 EGD Module GE Ethernet Global Data Communication Module
3. Back 2 Pages P Previous Page Skip 2 Pages N Next Page M Return to EGD Main Menu Redisplaying the Menu Press to display the current menu Use this command when you are looking at a screen of data and want to view the menu choices available to you Redisplaying the Current Page Press S to display the current page of data Going Back Two Pages of Data Press from the Database View menu to skip back to the previous 200 registers of data Viewing the Previous Page of Data Press P to display the previous page of data Going Ahead Two Pages of Data Hold down Shift and press to skip forward to the next 200 registers of data Viewing the Next Page of Data Press N to display the next page of data Returning to the Previous Menu Press M to return to the Previous Menu Page 56 of 96 ProSoft Technology Inc November 3 2008 Diagnostics and Troubleshooting MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 4 2 LED Status Indicators The LEDs indicate the module s operating status as follows Module Color Status Indication CFG Green On Data is being transferred between the module and a remote terminal using the Configuration Debug port Off No data is being transferred on the Configuration Debug port APP STATUS Amber Off The MVI69 EGD is working normally On The MVI69 EGD module program has recognized a
4. 3 Double click the Ethernet Configuration object This action opens the Edit dialog box xi my aD 192 168 0 100 my ip netmask 255 255 2550 gateway 192 168 0 1 Comment Default private class 3 address a Reset Tag Reset All OK Cancel 4 Edit the values for my ip netmask subnet mask and gateway default gateway 5 When you are finished editing click OK to save your changes and return to the ProSoft Configuration Builder window 2 7 Download the Project to the Module In order for the module to use the settings you configured you must download copy the updated Project file from your PC to the module To Download the Project File 1 In the tree view in ProSoft Configuration Builder click once to select the MVI69 EGD module 2 Open the Project menu and then choose Module Download The program will scan your PC for a valid com port this may take a few seconds When PCB has found a valid com port the following dialog box will open Download files from PC to module x Step 1 Select Port Com 1 E F Use Default IP Address Step 2 Transfer Files Download Cancel amp bort Lese ree Page 34 of 96 ProSoft Technology Inc November 3 2008 Configuring the MVI69 EGD Module MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 3 Choose the com port to use from the dropdown list and then click the Download button The mo
5. 0 Block read ID 1 Block write ID requested 2ton Input data 60 120 or 240 words where n 60 120 or 240 depending on the Block Transfer Size parameter refer to the configuration file Normal Input Empty Data Block Words Description 0 Block read ID 0 or 1 1 Block write ID requested 2 Program scan counter 3 Block write counter 4 Block read counter 5 Block parse counter 6 Block error counter 7 SNTP valid time 8 SNTP request count 9 SNTP response count 10 SNTP computation count 11 SNTP set count 12 SNTP timeout error count 13 SNTP seconds LSW 14 SNTP seconds MSW 15 SNTP microseconds LSW 16 SNTP microseconds MSW 17 ton Reserved where n 60 120 or 240 depending on the Block Transfer Size parameter refer to the configuration file ProSoft Technology Inc November 3 2008 Page 81 of 96 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module Normal Output Data Block These blocks of data transfer information from the CompactLogix or MicroLogix processor to the module and source the input monitored data to be used by the remote master The structure of the output image used to transfer this data is shown in the following table Words Description 0 Block write ID 1 ton Output data 60 120 or 240 words where n 60 120 or 240 depending on the Block Transfer Size par
6. Connection DownLoad Config Log ToFile Email Log to Support I Clear File Close Important The illustrations of configuration debug menus in this section are intended as a general guide and may not exactly match the configuration debug menus in your own module If there is no response from the module follow these steps 1 Verify that the null modem cable is connected properly between your computer s serial port and the module A regular serial cable will not work 2 On computers with more than one serial port verify that your communication program is connected to the same port that is connected to the module If you are still not able to establish a connection contact ProSoft Technology for assistance Navigation All of the sub menus for this module contain commands to redisplay the menu or return to the previous menu You can always return from a sub menu to the next higher menu by pressing M on your keyboard The organization of the menu structure is represented in simplified form in the following illustration Main Menu Child Menu B Child Menu C Child Sub Menu 1 Child Sub Menu 2 Child Menu A Child Sub Menu 1 Child Sub Menu 2 Child Sub Menu 3 Child Sub Menu 1 ProSoft Technology Inc Page 47 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Diagnostics and Troubleshooting GE Ethernet Global Data Communication Module Th
7. L43 and L45 L43 and L45 supported with RSLogix 5000 v16 03 or later Also supports MicroLogix 1500 LRP ProSoft Technology Inc Page 59 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module 5 1 2 Hardware Specifications Specification Description Dimensions Standard 1769 Single slot module Current Load 800 mA max 5 VDC Power supply distance rating of 2 L43 and L45 installations on first 2 slots of 1769 bus Operating Temp 0 to 60 C 32 to 140 F Storage Temp 40 to 85 C 40 to 185 F Relative Humidity 5 to 95 non condensing LED Indicators Power and Module Status Application Status CFG Port Activity Ethernet Port Activity Error Status CFG Port CFG RJ45 DB 9M with supplied cable RS 232 only No hardware handshaking App Port Ethernet modules 10 100 Base T Ethernet compatible interface Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s applied as specified in section 5 3 2 of IEC 60950 1991 Ethernet Broadcast Storm Resiliency less than or equal to 5000 ARP frames per second and less than or equal to 5 minutes duration Shipped with Unit RJ45 to DB 9M cables for each port 6 foot RS 232 configuration Cable 5 1 3 Functional Specifications The driver interfaces with a common internal database in the module This permits the sharing of data across many different networks The mod
8. Requires 1 0 Card Type ID 3 On the I O Configuration dialog box select Other Requires I O Card Type ID at the bottom of the list in the right pane and then double click to open the Module dialog box Page 42 of 96 ProSoft Technology Inc November 3 2008 Ladder Logic MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 4 Enter the values shown in the following illustration to define the module correctly for the MicroLogix processor and then click OK to save your configuration Module 1 OTHER 1 0 Module ID Code 89 x Expansion General Configuration Vendor ID Product Type Product Code Series Major Rev MinorRev Input Words Output Words Extra Data Length IBN Ignore Configuration Error Cancel App Help The input words and output words parameter will depend on the Block Transfer Size parameter you specify in the configuration file Use the values from the following table Block Transfer Size Input Words Output Words 60 62 61 120 122 121 240 242 241 5 Click Next to continue 6 After completing the module setup the I O configuration dialog box will display the module s presence The last step is to add the ladder logic If you are using the example ladder logic adjust the ladder to fit your application Refer to the example Ladder Logic section in this manual Download the new application to the
9. or 240 depending on the Block Transfer Size parameter refer to the configuration file Block 2000 C P Status Data Format Words Description 0 Status O invalid 1 producing healthy 2 pending unhealthy 1 Status bit mapped bitO error or invalid bit1 not time synchronized bits 2 to 15 reserved 2 Number of times C P LSW 3 Number of times C P MSW 4 Missed count LSW 5 Missed count MSW 6 Refresh count error LSW 7 Refresh count error MSW 8 Invalid error bit set by producer 9 Time sync error set by producer 10 Short message error in exchange 11 Long message error in exchange 12 Protocol PVN not set to 1 13 Configuration signature not set correctly where n 60 120 or 240 depending on the Block Transfer Size parameter refer to the configuration file Block 9250 Request Block General Status Words Description 0 9250 Command code value 1ton Reserved where n 60 120 or 240 depending on the Block Transfer Size parameter refer to the configuration file Block 9250 Response Block General Status Words Description 9250 Command code value Block write ID requested Program scan counter Product code bytes 0 amp 1 Product code bytes 2 amp 3 Revision bytes 0 amp 1 Revision bytes 2 amp 3 Op bytes 0 amp 1 Op bytes 2 amp 3 INIIAI 0 o ProSoft Technology Inc Page 83 of 96 Novem
10. that specified by ProSoft or shipped without an RMA number will be returned to the Customer freight collect Contact ProSoft Technical Support for further information d A 1096 restocking fee applies to all warranty credit returns whereby a Customer has an application change ordered too many does not need etc Page 88 of 96 ProSoft Technology Inc November 3 2008 Support Service amp Warranty MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 6 2 2 Procedures for Return of Units Under Warranty A Technical Support Engineer must approve the return of Product under ProSoft s Warranty a A replacement module will be shipped and invoiced A purchase order will be required Credit for a product under warranty will be issued upon receipt of authorized product by ProSoft at designated location referenced on the Return Material Authorization Procedures for Return of Units Out of Warranty Customer sends unit in for evaluation If no defect is found Customer will be charged the equivalent of 100 USD plus freight charges duties and taxes as applicable A new purchase order will be required If unit is repaired charge to Customer will be 30 of current list price USD plus freight charges duties and taxes as applicable A new purchase order will be required or authorization to use the purchase order submitted for evaluation fee The following is a list of non rep
11. Configuration Form Use this form to design the exchange list for an application 1 2 3 4 5 6 7 8 9 10 Exchange Cast Database Register Swap Prod Cons IP Exchange CFG Signature Type Type Address Count Code Time Address ID Version CP B M U Major X Minor ProSoft Technology Inc Page 85 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module Page 86 of 96 ProSoft Technology Inc November 3 2008 Support Service amp Warranty MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 6 6 1 Support Service amp Warranty In This Chapter How to Contact Us Technical Support 87 Return Material Authorization RMA Policies and Conditions 88 LIMITED WARRANTY 2 c ccecceeceeeceeeeeeeeeeeeeeeeeeeeceeeeaeecaeeeaeeeaeenneenes 90 ProSoft Technology Inc ProSoft is committed to providing the most efficient and effective support possible Before calling please gather the following information to assist in expediting this process 1 Product Version Number 2 System architecture 3 Network details If the issue is hardware related we will also need information regarding 1 Module configuration and contents of file o Module Operation o Configuration Debug status information o LED patterns 2 Information about the processor and user data files as viewed through and
12. Configure Shortcuts Configure Client Applications Configure CIP Options Driver Diagnostics CIP Diagnostics This action opens the Configure Drivers dialog box r Available Driver Types Cose R5 232 DF1 Devices Add New see Help Configured Drivers Name and Description IT Staus AB DF1 1 DH Sta 0 COM1 RUNNING Configure Startup Start Stop Delete Note If the list of configured drivers is blank you must first choose and configure a driver from the Available Driver Types list The recommended driver type to choose for serial communication with the processor is RS 232 DF1 Devices Page 18 of 96 ProSoft Technology Inc November 3 2008 Start Here MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 3 Click to select the driver and then click Configure This action opens the Configure Allen Bradley DF1 Communications Device dialog box Configure Allen Bradley DF1 Communications Device Device Name AB DF1 1 Comm Port cout M Device Logix 5550 Serial Port Baud Rate 19200 x js aa ctal Parity None Error Checking cnc z Stop Bits 1 Protocol Full Duplex Auto Configure Configure Dialer Use Modem Dialer Cancel Delete Help 4 Click the Auto Configure button RSLinx will attempt to configure your
13. E MER 26 se SNIP amp lient 5S ROI DO ERRARE 27 es EGB Exchandges 3 1 iore ond uper obire e ERERERS 28 EGD Multicast Group List eeeeeem 33 Ethernet Configuration senina eA nennen 33 Download the Project to the Module eeeeeee 34 2 1 ProSoft Configuration Builder ProSoft Configuration Builder PCB provides a quick and easy way to manage module configuration files customized to meet your application needs PCB is not only a powerful solution for new configuration files but also allows you to import information from previously installed known working configurations to new projects ProSoft Technology Inc Page 21 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Configuring the MVI69 EGD Module GE Ethernet Global Data Communication Module 2 1 1 Set Up the Project To begin start ProSoft Configuration Builder If you have used other Windows configuration tools before you will find the screen layout familiar ProSoft Configuration Builder s window consists of a tree view on the left an information pane and a configuration pane on the right side of the window When you first start ProSoft Configuration Builder the tree view consists of folders for Default Project and Default Location with a Default Module in the Default Location folder The following illustration shows the ProSoft Configuration Builder window with a new project Untitle
14. English Return Material Authorization RMA Policies and Conditions The following RMA Policies and Conditions collectively RMA Policies apply to any returned Product These RMA Policies are subject to change by ProSoft without notice For warranty information see Limited Warranty In the event of any inconsistency between the RMA Policies and the Warranty the Warranty shall govern 6 2 1 All Product Returns a In order to return a Product for repair exchange or otherwise the Customer must obtain a Returned Material Authorization RMA number from ProSoft and comply with ProSoft shipping instructions b In the event that the Customer experiences a problem with the Product for any reason Customer should contact ProSoft Technical Support at one of the telephone numbers listed above page 87 A Technical Support Engineer will request that you perform several tests in an attempt to isolate the problem If after completing these tests the Product is found to be the source of the problem we will issue an RMA C All returned Products must be shipped freight prepaid in the original shipping container or equivalent to the location specified by ProSoft and be accompanied by proof of purchase and receipt date The RMA number is to be prominently marked on the outside of the shipping box Customer agrees to insure the Product or assume the risk of loss or damage in transit Products shipped to ProSoft using a shipment method other than
15. Fax http www prosoft technology com Copyright ProSoft Technology Inc 2000 2008 All Rights Reserved MVI69 EGD User Manual 11 3 2008 ProSoft Technology ProLinx inRAx ProTalk and RadioLinx are Registered Trademarks of ProSoft Technology Inc ProSoft Product Documentation In an effort to conserve paper ProSoft Technology no longer includes printed manuals with our product shipments User Manuals Datasheets Sample Ladder Files and Configuration Files are provided on the enclosed CD and are available at no charge from our web site http www prosoft technology com Printed documentation is available for purchase Contact ProSoft Technology for pricing and availability Asia Pacific 603 7724 2080 Europe Middle East Africa 33 5 34 36 87 20 Latin America 1 281 298 9109 North America 1 661 716 5100 Contents MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Contents Please Read This Notice 2 Battery Life AOVISOTV uo e t a rf Hot te E re dt b PU Pe re eui 2 YourFeedback Please und e t e i ee tee v eat boe e Rv eve EL a dE US 2 FroSon e ProducEDOCHmentellODi qs roba khi oecu shut ciae oi E Se hie e Leo cesi mtd ple eint edurk ea Dese 3 Guide to the MVI69 EGD User Manual 7 1 Start Here 9 1 1 System Requirements inset ene te eee t cabe nee td 9 1 2 Package Contents uu sitio ep etd aret m dette edt on lh eta 10 1 3 Install ProSoft Configura
16. LED patterns on the processor 3 Details about the serial devices interfaced if any How to Contact Us Technical Support Internet Web Site http www prosoft technology com support http www prosoft technology com support E mail address support prosoft technology com mailto support prosoft technology com Asia Pacific 603 7724 2080 support asia prosoft technology com mailto support asia prosoft technology com Languages spoken include Chinese English Europe location in Toulouse France 33 0 5 34 36 87 20 support EMEA prosoft technology com mailto support emea prosoft technology com Languages spoken include French English ProSoft Technology Inc Page 87 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Support Service amp Warranty GE Ethernet Global Data Communication Module 6 2 North America Latin America excluding Brasil location in California 1 661 716 5100 support prosoft technology com mailto support prosoft technology com Languages spoken include English Spanish For technical support calls within the United States an after hours answering system allows pager access to one of our qualified technical and or application support engineers at any time to answer your questions Brasil location in Sao Paulo 55 11 5084 5178 eduardo prosoft technology com mailto eduardo prosoft technology com Languages spoken include Portuguese
17. Menu G Multicast Group List S Status Data Menu Display Menu M Exit Menu Opening the Producer Consumer List Menu Press C to open the Producer Consumer List menu Use this command to view the status of producers and consumers currently communicating on the network PRODUCER CONSUMER LIST 0 TO 9 P C U B ADDR REG CNT SWP PROD TIME IP ADDRESS EX ID CFG VER 1 0 100 192 168 0 20 0 0 i 0 100 192 168 0 20 T 70 100 192 168 0 20 i _ 0 100 192 168 0 20 Viewing the Multicast Group List Press G to view the Multicast Group List Use this command to see a list of IP addresses in the radio s configured multicast group Page 54 of 96 ProSoft Technology Inc November 3 2008 Diagnostics and Troubleshooting MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Opening the Status Data Menu Press S to open the Producer Consumer Status Data menu Use this command to view communication status for each of the configured producers and consumers RODUCER CONSUMER STATUS O TO MSG COUNT MISS COUNT REF COUNT INVALID TM SYNC SHORT LONG PROTO CFG SIG 0 0 0 0 0 0 0 0 P S P 00 0 20 573908 00 0 20 573908 0 0 0 Redisplaying the Menu Press to display the current menu Use this command when you are looking at a screen of data and want to view the menu choices available to you Returning to the Main Menu Press M to return to the Main Menu 4 1 7 Producer Consume
18. ProSoft Technology Inc Page 41 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Ladder Logic 3 2 Adding the Module to an Existing MicroLogix Project If you are installing and configuring the module with a MicroLogix processor follow these steps If you are using a CompactLogix processor refer to the previous section The first step in setting up the processor ladder file is to define the I O type module to the system Start RSLogix 500 and follow these steps 1 In RSLogix open your existing application or start a new application depending on your requirements 2 Double click the I O Configuration icon located in the Controller folder in the project tree This action opens the I O Configuration dialog box I O Configuration Read I0 Config Hide All Cards Current Cards Available Pati Description 4 1769 0416 1769 088 1769 0816 Filter an 10 16 Output 120 240 VAC 8 Dutput High Current 24 VDC 16 Output 24 VDC Source 16 Output 24 VDC Source w Protectior 32 Output High Density 24 VDC Analog 2 Channel Output Module Analog 8 Chan Current Output Analog 9 Chan Voltage Output 16 Output 24 VDC Sink 8 Output Relay 16 Output Relay 8 Dutput Isolated Relay DeviceNetScanner DPI SCANport Module Power Supply Power Supply Power Supply Power Supply Any 1763 PowerSupply Any 1769 UnPowered Cable Other
19. Required Hardware 45 Resetting diagnostic data 50 Retrieve Configuration PDUs Example 62 63 Return Material Authorization RMA Policies and Conditions 88 Returning to the Main Menu 53 54 55 Returning to the Previous Menu 56 Rules for CS Validation 32 S Set Module Parameters 24 Set Up the Project 22 Setting Jumpers 12 Skipping 500 Registers of Data 52 Start Here 7 9 Statistics PDUs 62 69 Summary PDUs 62 67 Support Service amp Warranty 7 87 Swap Code 30 System Requirements 9 T The Configuration Debug Menu 46 Time Limit for Bringing Suit 93 Time Zone 28 Transferring the Configuration File from MVI69 module to PC 50 Transferring the Configuration File from PC to MVI69 module 49 Transferring WATTCP CFG to the module 53 Transferring WATTCP CFG to the PC 53 Troubleshooting 58 U Use Daylight Savings Time 28 Using the Diagnostic Window in ProSoft Configuration Builder 46 V Viewing Block Transfer Statistics 49 Viewing Data in ASCII Text Format 53 Viewing Data in Decimal Format 52 Viewing Data in Floating Point Format 53 Viewing Data in Hexadecimal Format 52 Viewing Module Configuration 49 Viewing Register Pages 52 Viewing SNTP Status 49 Viewing the Multicast Group List 54 Viewing the Next 100 Registers of Data 52 Viewing the Next Page of Data 56 Viewing the Previous 100 Registers of Data 52 Viewing the Pre
20. Run Whenever the module detects that the processor has gone out of the Run mode that is Fault or PGM backplane communications will halt between processor and module but not on the EGD network When the processor is returned to a running state the module will resume communication with the Processor Backplane Data Transfer The MVI69 EGD module communicates directly over the CompactLogix or MicroLogix backplane Data is paged between the module and the CompactLogix or MicroLogix processor across the backplane using the module s input and output images The update frequency of the images is determined by the scheduled scan rate defined by the user for the module and the communication load on the module Typical updates are in the range of 1 to 10 milliseconds This bi directional transference of data is accomplished by the module filling in data in the module s input image to send to the processor Data in the input image is placed in the Controller Tags in the processor by the ladder logic The input image for the module is set to 60 120 or 240 words This large data area permits fast throughput of data between the module and the processor The processor inserts data into the module s output image to transfer to the module The module s program extracts the data and places it in the module s internal database The output image for the module is set to 60 120 or 240 words This large data area permits fast throughput of data from the process
21. Technology Inc November 3 2008 Page 57 of 96 MVI69 EGD CompactLogix or MicroLogix Platform Diagnostics and Troubleshooting GE Ethernet Global Data Communication Module 4 2 2 Clearing a Fault Condition Typically if the OK LED on the front of the module becomes illuminated red for more than ten seconds a hardware problem has been detected in the module or the program has exited To attempt to clear the condition 1 Remove the card from the rack and re insert the card in the rack 2 Verify the configuration data being transferred to the module from the CompactLogix or MicroLogix processor If the module s OK LED does not turn green make sure the module is inserted completely into the rack If this does not cure the problem contact ProSoft Technology Support 4 2 3 Troubleshooting Use the following troubleshooting steps if you encounter problems when the module is powered up If these steps do not resolve your problem please contact ProSoft Technology Technical Support Processor Errors Problem Description Steps to take Processor Fault Verify that the module is plugged into the slot that has been configured for the module Verify that the slot in the rack configuration has been set up correctly in the ladder logic Processor I O LED This indicates a problem with backplane communications Verify that all flashes modules in the rack are configured in the ladder logic Module Errors Problem Description Ste
22. Troubleshooting GE Ethernet Global Data Communication Module Viewing Register Pages To view sets of register pages use the keys described below Command Description 0 Display registers 0 to 99 1 Display registers 1000 to 1099 2 Display registers 2000 to 2099 And so on The total number of register pages available to view depends on your module s configuration Displaying the Current Page of Registers Again DATABASE DISPLAY 8 TO 99 lt DECIMAL gt 100 161 162 4 11 12 13 14 T B eeeocegoggnn como cOcOOOOOSOo cmo Seegoqgegqggggg 5 5 a 8 a a a a 8 a This screen displays the current page of 100 registers in the database Moving Back Through 5 Pages of Registers Press from the Database View menu to skip back to the previous 500 registers of data Viewing the Previous 100 Registers of Data Press P from the Database View menu to display the previous 100 registers of data Skipping 500 Registers of Data Hold down Shift and press to skip forward to the next 500 registers of data Viewing the Next 100 Registers of Data Press N from the Database View menu to select and display the next 100 registers of data Viewing Data in Decimal Format Press D to display the data on the current page in decimal format Viewing Data in Hexadecimal Format Press H to display the data on the current page in hexadecimal format Page 52 of 96 ProSoft Technology Inc November
23. are correctly configured Before trying to connect the module to the network the remote device must be able to communicate with ProSoft Configuration Builder You must understand and document all parameters Page 28 of 96 ProSoft Technology Inc November 3 2008 Configuring the MVI69 EGD Module MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 2 4 1 Exch Type Producer exchange will be producing data to other stations Consumer exchange will be consuming data from another station The Exchange Type field defines the type of exchange used in the exchange as either producer or consumer Producer exchanges P are generated by the driver using the module s database Consumer exchanges C are those received from other EGD devices with the data in the message being placed in the module s database 2 4 2 Cast Type When the Exchange Type is Producer the cast type field determines if the exchange is a unicast U point to point exchange multicast M multicast group or a broadcast B all nodes exchange Producer Unicast produce message to another station Producer Multicast produce message to a group of stations In order to use this option you need to configure the same Multicast IP address used in the exchange also at the EGD MULTICAST ADDRESS section Important For Multicast mode use transmit rates of 1 or 2 for best results Producer Broadcast produce
24. communication error on one of its ports BP ACT Amber On The LED is on when the module is performing a write operation on the backplane Off The LED is off when the module is performing a read operation on the backplane Under normal operation the LED should blink rapidly on and off OK Red Off The card is not receiving any power and is not securely Green plugged into the rack Green The module is operating normally Red The program has detected an error or is being configured If the LED remains red for over 10 seconds the program has probably halted Remove the card from the rack and re insert the card to restart the module s program BATT Red Off The battery voltage is OK and functioning On The battery voltage is low or battery is not present Allow battery to charge by keeping module plugged into rack for 24 hours If BAT LED still does not go off contact ProSoft Technology as this is not a user serviceable item If the APP BP ACT and OK LEDs blink at a rate of every one second call ProSoft Technology support There is a serious problem with the module and it will have to be sent back to ProSoft 4 2 1 Ethernet LED Indicators LED State Description Data Off No activity on the port Green Flash The port is either actively transmitting or receiving data Link Off No connection to hub or network is detected Green Solid Connected to hub or network correctly This is the normal operating state ProSoft
25. exchange list defining the database and register count If the production consumption time is set to zero the exchange will never be produced or consumed and will only be valid for command processing These functions should be used for data that is not time critical and does not require periodic updating The maximum length of the message is 1400 bytes The module supports the masked write request command to alter one or more bits Multiple cells can be provided in the request to alter more than one byte of data The maximum length of the message is 1400 bytes Refer to EGD Protocol Specific Configuration for information on the data structures required for each command Command support is usually not available in most EGD devices or drivers Most devices only support the producer consumer services Therefore this service may not be utilized by those devices Page 62 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Retrieve Configuration PDUs Example PDU Type 3 Retrieve Configuration Request The retrieve configuration request PDU command permits an application program to request the configuration details associated with a matching Producer and Exchange ID A retrieve configuration request sent from a requesting node must be followed by a retrieve configuration response message from the responding node Packet Description In
26. for which it was designed vi any other abuse misapplication neglect or misuse by the Customer vii accident improper testing or causes external to the Product such as but not limited to exposure to extremes of temperature or humidity power failure or power surges or viii disasters such as fire flood earthquake wind and lightning c The information in this Agreement is subject to change without notice ProSoft shall not be liable for technical or editorial errors or omissions made herein nor for incidental or consequential damages resulting from the furnishing performance or use of this material The user guide included with your original product purchase from ProSoft contains information protected by copyright No part of the guide may be duplicated or reproduced in any form without prior written consent from ProSoft 6 3 3 Disclaimer Regarding High Risk Activities Product manufactured or supplied by ProSoft is not fault tolerant and is not designed manufactured or intended for use in hazardous environments requiring fail safe performance including and without limitation the operation of nuclear facilities aircraft navigation of communication systems air traffic control direct life support machines or weapons systems in which the failure of the product could lead directly or indirectly to death personal injury or severe physical or environmental damage collectively high risk activities ProSoft specifically disclaims an
27. other failures Only use these commands if you are specifically directed to do so by ProSoft Technology Technical Support staff Some of these command keys are not listed on the menu but are active nevertheless Please be careful when pressing keys so that you do not accidentally execute an unwanted command Press W from the Main Menu to warm boot restart the module This command will cause the program to exit and reload refreshing configuration parameters that must be set on program initialization Only use this command if you must force the module to re boot Page 50 of 96 ProSoft Technology Inc November 3 2008 Diagnostics and Troubleshooting MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Opening the Network Menu Press to open the network menu The network menu allows you to send receive and view the WATTCP CFG file that contains the IP gateway and other network specification information You can find more information about the commands on this menu in the Network Menu page 53 section Exiting the Program Caution Some of the commands available to you from this menu are designed for advanced debugging and system testing only and can cause the module to stop communicating with the processor or with other devices resulting in potential data loss or other failures Only use these commands if you are specifically directed to do so by ProSoft Technology Technical Support
28. over an IP network The user defines the data to be produced and consumed in a configuration file downloaded to the module GE Fanuc Automation and GE Drive Systems developed an Ethernet Global Data or EGD exchange for PLC and computer data in 1998 Ethernet Global Data EGD offers versatility where a mix of control devices requires cooperation with each other This involves sharing of information across the applications regardless of device or network type often at high speed and with high reliability High reliability means fewer communication failures and having the ability to detect failures upon occurrence Particular emphasis is delivered for applications requiring periodic or frequent updates and time synchronization of devices The protocol supports Unicast Broadcast and Multicast group messaging Efficiency is based on the fact each device on the network can produce these types of messages and each device determines which of these messages to consume 5 1 1 General Specifications Single Slot 1769 backplane compatible The module is recognized as an Input Output module and has access to processor memory for data transfer between processor and module Ladder Logic is used for data transfer between module and processor Sample ladder file included Configuration data obtained from configuration text file downloaded to module Sample configuration file included Supports all CompactLogix processors L20 L23 L30 L31 L32 L35
29. reference specifies an offset into the specified Exchange or target specific address the number of bytes to write and the Data Each Data field must be padded to the nearest 4 byte boundary Based on the address type the Domain ID must contain an Exchange and Producer ID or target specific address which is valid on the destination node A write request sent from a requesting node must be followed by a write response message from the responding node See the discussion in the section entitled Exchange Data Handling for information about coherency in the write Packet Description Data mo Source Port Po 7937 0x 1F01 Destination Por 7957 0x 1FO1 Length xx bytes 0x 00 XX Checksum Checksum exxx 0x XX XX EGOS POU Fiid Offset Bytes Hex code a a cp cis Regesto p 2 omm wi 4 p E Option eng fs aos coiguraton snare p Js m sacom fa eem nn I I I I I I mn The following two items are referred to as the Sache Cell Each Cell targets one EGD Exchange command line present in the EGD Module s configuration file Offset reads the DB Register specified in the Command Length is Bytes count not Words Multiple Cells may be requested dependent on the Cell Count field specified above Offset zz pmm Length a 2 ox m ns Data depends on length oes E HH HH requested Padding to 32 bit Ox HH HH boundary ProSoft Technology Inc Page 73 of 96
30. retrieve configuration request message Packet Description Data Hex Info Ethernet Source MAC 00 12 3F AE 5C AE 0x 00 12 3F AE 5C AE i Destination MAC 00 0D 8D 00 13 83 0x 00 OD 8D 00 13 83 Type 0x0800 IPv4 0x 08 00 IPv4 Version 0x45 0x 45 Header Size Type of 000 0 Routine 0x 00 service 0 0 Normal Delay 0 0 Normal throughput Sete 0 0 Normal reliability uis E 00 Normal Monetary cost Total Length 104 bytes 0x00 68 Identification 2645 0x00 04 Flags 00 May Fragment 0x 00 0 0 Last Fragment Fragment Offset 0 bytes 0x00 00 Time to Live 254 0x FE Protocol 17 UDP 0x 11 Header Checksum 8168 correct 0x E8 1F Source Address 105 102 0 200 0x 69 66 00 C8 Destination Address 105 102 0 205 0x 69 66 00 CD UDP Source Port 1025 0x 04 01 Destination Port 7937 0x 1F 01 Length 84 bytes 0x 00 54 Checksum 62188 correct 0x EC F2 EGD EGD s PDU Offset Bytes Hex code Field PDU Type 0 il Ox 04 Message Flag 1 i Ox 00 Page 64 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Request ID 2 2 Os dd did PVN1 4 i 0x 01 Status 5 il Ox 00 Message 6 2 0x 4C 00 Length Producer ID 8 4 0x 69 66 00 C8 Exchange ID 12 4 Ox El 2E 00 00 Production 16 4 Ox
31. settings and return to the ProSoft Configuration Builder window Adding a Project To add a project to an existing project file 1 Select the Default Project icon 2 Choose Project from the Project menu then choose Add Project A new project folder appears Adding a Module To add a module to your project 1 Double click the Default Module icon to open the Choose Module Type dialog box 2 Onthe Choose Module Type dialog box select the module type Or 1 Open the Project menu and choose Location 2 Onthe Location menu choose Add Module ProSoft Technology Inc November 3 2008 Page 23 of 96 MVI69 EGD CompactLogix or MicroLogix Platform Configuring the MVI69 EGD Module GE Ethernet Global Data Communication Module To add a module to a different location 1 Right click the Location folder and choose Add Module A new module icon appears Or 1 Select the Location icon 2 From the Project menu select Location then select Add Module 2 1 2 Set Module Parameters Notice that the contents of the information pane and the configuration pane changed when you added the MVI69 EGD module to the project f Untitled ProSoft Configuration Builder joy x File Edit View Project Tools Help 1 2 Default Project Name 5 3 5 stas Information E3 Gg Default Location v MVI69 EGD Configured MVI69 EGD a h ZEN MVI69 EGD6 2 02 gt Module 69 Module Values OK E a EGD Conf
32. the driver will update the status of the exchange When the driver again receives the exchange the status will be updated Exchanges received by the consumer driver that are not defined in the exchange list will be discarded Up to 700 words of data can be consumed in a single message Therefore to fill the whole database with values would only require 6 exchanges 4000 word registers in the module s database ProSoft Technology Inc Page 77 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module Central to the functionality of the module is the internal database This database is shared between all the drivers in the module and is used as a conduit to pass information from one device on one network to one or more devices on another network This permits data from devices on one communication port to be viewed and controlled by devices on another port The consumer functionality provided in the EGD driver is used to transfer data from other nodes on the network into the module s database The following diagram describes the flow of data between the consumer the internal database and the remote EGD devices Remote 1 Consumer I Databases Device i i LI I I I i f Virtual DB Wate for Database I Consumed i Data L I I Produced Data 1 Read Exchange List 5 2 5 General Concepts The following topics describe several concepts that are i
33. which apply to the all of the individual cell references in the message Each cell reference specifies an offset into the specified Exchange or target specific address and the number of bytes to read Based on the address type the Domain ID must contain an Exchange and Producer ID or target specific address which is valid on the destination node A read request sent from a requesting node must be followed by a read response message from the responding node Packet Description Data Info Source Pot Source Pot 7937 0x 1F01 Checksum Xxxxx 0x XX XX esser 3 pw E Emewws E opem ame pe s Yon carcan fa ho em The following two items are referred to as the exchange Cell Each Cell targets one EGD Exchange command line present in the EGD Module s configuration file Offset reads the DB Register specified in the Command Length is Bytes count not Words Multiple Cells may be requested dependent on the Cell Count field ee above ProSoft Technology Inc Page 71 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module PDU Type 33 Read Response The read response PDU Read Resp is used to return the contents of one or more contiguous groups of memory from the local node to the requesting controller The header defines parameters which apply to the all of the individual cell references in the me
34. 0 None No Change is made in the byte ordering 1234 1234 1 Words The words are swapped 1234 3412 2 Words amp Bytes The words are swapped then the bytes in each word are swapped 1234 4321 3 Bytes The bytes in each word are swapped 1234 2143 2 4 6 P C Time The P C Time field defines the number of milliseconds between productions of the exchange data and for consumed exchanges This value defines the number of milliseconds to wait for a produced exchanged before a timeout condition is present Fora producer exchange it defines the number of milliseconds between consecutive producer exchanges Fora consumer exchange it defines the number of milliseconds to wait for a produced message before a timeout error is set It is suggested to use a value at least four times greater than the value used in the producer exchange For consumed messages set this value to approximately 4 times the produced time of the exchange on the other device This will prevent the exchange from constantly timing out on a busy network If this parameter is set to zero the message will not be produced A zero value for a consumed message indicates that the exchange will never timeout The zero value can be used for exchanges that will interface with the command service port 7937 to handle data read and write requests from another device 2 4 7 IP Address The IP Address field should be set to the IP address of destination device produce
35. 2008 MVI69 EGD CompactLogix or MicroLogix Platform Configuring the MVI69 EGD Module GE Ethernet Global Data Communication Module The purpose of the Configuration Signature CS is to guarantee that the produced exchange will contain data in a format expected by a consumer module Therefore it prevents the consumer module to process received data if it is not compatible because of later modifications Whenever a consumer module receives an exchange message it will look for a configured consumer exchange that contains the same Exchange ID If it finds a matching consumer exchange it will compare the Configuration Signature for validation If the exchange is not validated then the data will not be consumed Because this functionality is optional the modules will exchange data even if the Configuration Signature validation is disabled To disable this functionality configure all exchanges with both CS Major and CS Minor values equal to zero The following rules are used by the consumer module to validate an exchange based on its Configuration Signature Rules for CS Validation An exchange will be considered valid if at least one of the following conditions is true Producer CS Major and CS Minor are both equal to 0 Consumer CS Major and CS Minor are both equal to 0 Producer CS Major is equal than Consumer CS Major AND Producer CS Minor is greater or equal than Consumer CS Minor The following table contains some example
36. 3 2008 Diagnostics and Troubleshooting MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Viewing Data in Floating Point Format Press F from the Database View menu Use this command to display the data on the current page in floating point format The program assumes that the values are aligned on even register boundaries If floating point values are not aligned as such they are not displayed properly Viewing Data in ASCII Text Format Press A to display the data on the current page in ASCII format This is useful for regions of the database that contain ASCII data Returning to the Main Menu Press M to return to the Main Menu 4 1 5 Network Menu The network menu allows you to send receive and view the WATTCP CFG file that contains the IP and gateway addresses and other network specification information M Main Menu Network Menu Display Menu R Receive WATTCP CFG E Upload WATTCP CF G to module Send WATTCP CFG Download WATTCP CFG to PC V View WATTCP CFG View WATTCP CFG file on module M Main Menu I Return to Main Menu Redisplays refeshes this menu Transferring WATTCP CFG to the module Press R to transfer a new WATTCP CFG file from the PC to the module Use this command to change the network configuration for the module for example the module s IP address Press Y
37. 37 LED Status Indicators 7 57 Limitation of Remedies 92 LIMITED WARRANTY 89 90 M Main Logic Loop 79 Main Menu 48 Masked Write PDUs 62 75 Module Entries 25 Moving Back Through 5 Pages of Registers 52 N Navigation 47 Network Menu 51 53 No Other Warranties 93 ProSoft Technology Inc November 3 2008 Page 95 of 96 MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Index Normal Data Transfer 81 Normal Input Data Block 81 Normal Input Empty Data Block 81 Normal Output Data Block 82 NTP Server IP Address 27 O Opening the Database Menu 49 Opening the EGD Menu 49 Opening the Network Menu 51 Opening the Producer Consumer List Menu 54 Opening the Status Data Menu 55 P P C Time 30 Package Contents 10 Please Read This Notice 2 Printing a Configuration File 25 Procedures for Return of Units Out of Warranty 89 Procedures for Return of Units Under Warranty 89 Producer Consumer List Menu 55 Producer Consumer Status Menu 56 Product Specifications 7 59 ProSoft Configuration Builder 21 ProSoft Product Documentation 3 Purchasing Warranty Extension 89 R Read PDUs 62 71 Read Register Count 26 Read Register Start 26 Reading Status Data from the Module 45 Redisplaying the Current Page 55 56 Redisplaying the Menu 48 55 56 Reference 7 59 Reg Count 29
38. 40 06 00 00 Period Reserved 20 2 0x 00 00 Destination 22 2 0x 01 00 Type Destination 24 92 obs 69 66 00 Ces address 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 0 00 O0 00 00 00 00 00 00 00 00 00 00 Configuration 56 2 0x 02 00 State Exchange 58 2 Ox 78 05 Length Reserved 60 4 Ox 00 00 00 00 UDP IP Port 64 2 0x 46 47 Configuration 66 2 Ox 00 00 Type Configuration 68 2 Ox 00 00 Sig Mode 70 2 Ox 02 00 Reserved 72 2 0x 00 00 Configuration 74 2 0x 00 00 Data This is an example of The Module s EGD Configuration Response to the Command Production Data Unit This is the Hexadecimal representation of the Retrieve configuration Response from the above table It includes the Ethernet II IPv4 UDP and within UDP the EGD Server s Reply PDU Type 4 depicted in bold font ProSoft Technology Inc Page 65 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Reference Capabilities PDUs PDU Type 9 Capabilities Request The capabilities request PDU command permits an application program to request the supported capabilities of the EGD implementation on the destination node A capabilities request sent from a requesting node must be followed by a capabilities response message from the responding node Packet Description Data Info UDP Source Port 7937 0x 1F01 Destination Port 7937 0x 1
39. F01 xx bytes 0x 00 XX Checksum Xxxxx 0x XX XX ume p e eje mIo m o pera poo p p mw T eco eek bo iis Message ena fe p o MfRTRI mo om mya m T PDU Type 10 Capabilities Response The capabilities response command PDU is sent in response a capabilities request This message returns the functional capabilities and limits of the supported EGD implementation on the responding controller Packet Description Data Info Source Pot Port Source Pot P237 0x 1F01 Destination Port 7937 0x 1F01 SSS xx bytes 0x 00 XX Checksum Xxxxx OX XX XX Message TA Ir MEN E mw p pe pa NN NU CE mm Page 66 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module rai RN aedi eosin Type B p HH HH Identification String 28 HH HH up to 80 characters Summary PDUs PDU Type 7 Summary Request The summary request PDU command permits an application program to request a summary of the exchanges configured on a given node This allows a user to get a complete list of all exchanges defined The Index field is normally 0 and is used to request a block of summaries in nodes which contain a large number of exchanges A summary request sent from a requesting node must be followed by a summary response message from the respondin
40. GD support VersaMax CPU E05 Several drives and turbines Ethernet Global Data Service for NT CIMPLICITY HMI software Several HMI products ProSoft Technology Inc Page 61 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module 5 2 2 EGD Command Server The module supports UDP service port 7937 0x1F01 to handle all command requests made of the module The module will only service the requests and generate response messages It will not generate command requests The module supports the following functions specified in the EGD protocol Code Description 3 Retrieve Configuration Request page 63 example provided 4 Retrieve Configuration Response page 63 example provided 7 Summary Request page 67 8 Summary Response page 67 9 Capabilities Request page 66 10 Capabilities Response page 66 15 Statistics Request page 69 16 Statistics Response page 69 18 Command NAK page 70 32 Read Request page 71 33 Read Response page 71 34 Write Request page 73 35 Write Response page 73 36 Masked Write Request page 75 37 Masked Write Response page 75 The module only supports address type 0 for the read and write commands Therefore the data requested is relative to the EGD exchange delimited in the request In order to use these functions an exchange must first exist in the module s
41. LIENT NTP SERVER IP ADDRESS 132 163 4 102 IP address for NIST Boulder Colorado TI E ZONE 57 Number of hours from GMT 11 to 11 USE DAYLIGHT SAVINGS TIME No Yes or No DATABASE REGISTER 2500 database word location to store time l ignore This register value should be an even number The database register parameter defines a database register where the SNTP time and date values are copied It occupies 4 words as follows Word Offset Description 0 and 1 Date and time in Unix format long integer 2 and 3 Microseconds long integer 2 3 1 NTP Server IP Address Enter in dotted notation This parameter sets the IP address of the NTP server to contact for time acquisition Select an NTP server with the greatest accuracy that is available all the time from your network Set this IP address to 0 0 0 0 to disable SNTP server requests ProSoft Technology Inc Page 27 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Configuring the MVI69 EGD Module GE Ethernet Global Data Communication Module 2 4 2 3 2 Time Zone 11 to 11 This parameter sets the time zone offset from UTC Positive values are for time zones west of UTC and negative values are for time zones east of UTC Set this value to 0 to use UTC in the module 2 3 3 Use Daylight Savings Time Yes or No This parameter specifies if daylight savings time will be us
42. MicroLogix Platform GE Ethernet Global Data Communication Module 6 3 7 Time Limit for Bringing Suit Any action for breach of warranty must be commenced within 39 months following shipment of the Product 6 3 8 No Other Warranties Unless modified in writing and signed by both parties this Warranty is understood to be the complete and exclusive agreement between the parties suspending all oral or written prior agreements and all other communications between the parties relating to the subject matter of this Warranty including statements made by salesperson No employee of ProSoft or any other party is authorized to make any warranty in addition to those made in this Warranty The Customer is warned therefore to check this Warranty carefully to see that it correctly reflects those terms that are important to the Customer 6 3 9 Allocation of Risks This Warranty allocates the risk of product failure between ProSoft and the Customer This allocation is recognized by both parties and is reflected in the price of the goods The Customer acknowledges that it has read this Warranty understands it and is bound by its Terms 6 3 10 Controlling Law and Severability This Warranty shall be governed by and construed in accordance with the laws of the United States and the domestic laws of the State of California without reference to its conflicts of law provisions If for any reason a court of competent jurisdiction finds any provisions of t
43. November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module PDU Type 35 Write Response The write response is returned from a destination controller in response to a write request message It serves as an acknowledgment for the original request A positive response indicates that all of the data has been written to the responding device An error response indicates that one or more of the transfers to the responding device failed Responders shall use all available means to assure that a write is performed in its entirety or not performed at all Requesting applications are advised that if partial failures of the write can cause problems with the control algorithm they should include only one cell in each write to assure complete knowledge of the disposition of the write request Packet Description Data Info Source Port Port Source Port 7937 Ox 1F01 a e p s Bei p p p s Message tenn fe gt Signature s CO m E co s m d Page 74 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Masked Write PDUs PDU Type 36 Mask Write Request The masked write request PDU is used to change individual bits in one or more bytes in the destination controller The header defines parameters which apply to the all of the indiv
44. ProSoff TECHNOLOGYY Where Automation Connects inRAoc MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module mim gym gu omes e ot 4n T un 11 3 2008 USER MANUAL Please Read This Notice Successful application of this module requires a reasonable working knowledge of the Rockwell Automation CompactLogix or MicroLogix hardware the MVI69 EGD Module and the application in which the combination is to be used For this reason it is important that those responsible for implementation satisfy themselves that the combination will meet the needs of the application without exposing personnel or equipment to unsafe or inappropriate working conditions This manual is provided to assist the user Every attempt has been made to ensure that the information provided is accurate and a true reflection of the product s installation requirements In order to ensure a complete understanding of the operation of the product the user should read all applicable Rockwell Automation documentation on the operation of the Rockwell Automation hardware Under no conditions will ProSoft Technology be responsible or liable for indirect or consequential damages resulting from the use or application of the product Reproduction of the contents of this manual in whole or in part without written permission from ProSoft Technology is prohibited Information in this manual is subject to change wit
45. Some of these command keys are not listed on the menu but are active nevertheless Please be careful when pressing keys so that you do not accidentally execute an unwanted command MVI56 EGD COMMUNICATION MODULE MENU Display Menu B Block Transfer Statistics C Module Configuration D Database View E EGD Menu I SNTP setup R Transfer Configuration from PC to MVI Unit S Transfer Configuration from MVI Unit to PC U Reset diagnostic data V Version Tnformation w Warm Boot Module Network Menu Esc Exit Program Redisplaying the Menu Press to display the current menu Use this command when you are looking at a screen of data and want to view the menu choices available to you Page 48 of 96 ProSoft Technology Inc November 3 2008 Diagnostics and Troubleshooting MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Viewing Block Transfer Statistics Press B to view the Block Transfer Statistics screen Use this command to display the configuration and statistics of the backplane data transfer operations between the module and the processor The information on this screen can help determine if there are communication problems between the processor and the module Tip Repeat this command at one second intervals to determine the number of blocks transferred each second Viewing Module Configuration Press C to view the Module Configuration screen Use this command to dis
46. airable units OO0O00000000 0 6 2 4 3150 All 3750 3600 All 3700 3170 All 3250 1560 Can be repaired only if defect is the power supply 1550 Can be repaired only if defect is the power supply 3350 3300 1500 All Purchasing Warranty Extension ProSoft s standard warranty period is three 3 years from the date of shipment as detailed in Limited Warranty page 90 The Warranty Period may be extended at the time of equipment purchase for an additional charge as follows e Additional 1 year 10 of list price e Additional 2 years 20 of list price e Additional 3 years 30 of list price ProSoft Technology Inc Page 89 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Support Service amp Warranty GE Ethernet Global Data Communication Module 6 3 LIMITED WARRANTY This Limited Warranty Warranty governs all sales of hardware software and other products collectively Product manufactured and or offered for sale by ProSoft and all related services provided by ProSoft including maintenance repair warranty exchange and service programs collectively Services By purchasing or using the Product or Services the individual or entity purchasing or using the Product or Services Customer agrees to all of the terms and provisions collectively the Terms of this Limited Warranty All sales of software or other intellectual property are in addition subje
47. ameter refer to the configuration file The Write Block ID is an index value used to determine the location in the module s database where the data will be placed Each transfer can move up to 200 words block offsets 1 to 200 of data 5 2 7 Command Control Blocks Command control blocks are special blocks used to control the module The current version of the software supports the following command control blocks Code Description 1 or 0 Empty data blocks 1 to 20 Data read or write blocks 2000 C P status data 9250 General status data 9998 Warm boot module same effect as 9999 9999 Cold boot module Block 2000 Request Words Description 0 2000 Command Block ID 1 Number of C P messages 1 to 4 2 First C P index 0 to 99 3ton Reserved where n 60 120 or 240 depending on the Block Transfer Size parameter refer to the configuration file Block 2000 Response Words Description 0 2000 Command Block ID 1 Block write ID requested 2 Number of C P messages 0 to 4 Will be set to 0 if error in request 3 First C P index 0 to 99 4to 17 C P Status Data 18 to 31 C P Status Data 32 to 45 C P Status Data Page 82 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Words Description 46 to 59 C P Status Data 60 to n Reserved where n 60 120
48. ation Module Pentium Il 450 MHz minimum Pentium Ill 733 MHz or better recommended Supported operating systems o Microsoft Windows XP Professional with Service Pack 1 or 2 o Microsoft Windows 2000 Professional with Service Pack 1 2 or 3 o Microsoft Windows Server 2003 128 Mbytes of RAM minimum 256 Mbytes of RAM recommended 100 Mbytes of free hard disk space or more based on application requirements 256 color VGA graphics adapter 800 x 600 minimum resolution True Color 1024 x 768 recommended CD ROM drive HyperTerminal or other terminal emulator program capable of file transfers using Ymodem protocol 1 2 Package Contents The following components are included with your MVI69 EGD module and are all required for installation and configuration Important Before beginning the installation please verify that all of the following items are present Qty Part Name Part Number Part Description 1 MVI69 EGD MVI69 EGD GE Ethernet Global Data Communication Module Module 1 Cable Cable 15 RS232 For RS232 Connection to the CFG Port Null Modem 1 Cable RJ45 to DB9 Male For DB9 Connection to Module s Port Adapter 1 inRAx Contains sample programs utilities and Solutions CD documentation for the MVI69 EGD module If any of these components are missing please contact ProSoft Technology Support for replacement parts Page 10 of 96 ProSoft Technology Inc November 3 2008 Start Here MVI69 EGD CompactLog
49. atus Offline Cancel ipply Hep 6 Select the Request Packet Interval value for scanning the I O on the module This value represents the minimum frequency the module will handle scheduled events This value should not be set to less than 1 millisecond Values between 1 and 10 milliseconds should work with most applications Page 40 of 96 ProSoft Technology Inc November 3 2008 Ladder Logic MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 7 Save the module Click OK to dismiss the dialog box The Controller Organization window now displays the module s presence The following illustration shows the Controller Organization window I Controller MVI69 i Controller Tags Z3 Controller Fault Handler 73 Power Up Handler Tasks 8 MainTask Ez C MainProgran 3 Unscheduled Programs Motion Groups Trends Data Types i User Defined om Strings Tih Predefined i Module Defined I O Configuration E 8j Backplane ComaactLogix System ff 1769 L35E MVI69 E 1769 L35E Ethernet Port LocalENB 88 CompactBus Local 8 0 ComaactBus Local BE 1 1769 MODULE MVI69 Sample 1 m f 3i pg 1 Q H A m Q 8 Copy the Controller Tags from the sample program 9 Copy the User Defined Data Types from the sample program 10 Copy the Ladder Rungs from the sample program 11 Save and Download the new application to the controller and place the processor in run mode
50. ber 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module Words Description 9 Run bytes 0 amp 1 10 Run bytes 2 amp 3 11 Block write counter 12 Block read counter 13 Block parse counter 14 Block error counter 15 SNTP valid time 16 SNTP request count 17 SNTP response count 18 SNTP computation count 19 SNTP set count 20 SNTP timeout error count 21 SNTP seconds LSW 22 SNTP seconds MSW 23 SNTP microseconds LSW 24 SNTP microseconds MSW 25 ton Reserved where n 60 120 or 240 depending on the Block Transfer Size parameter refer to the configuration file Warm Boot 9998 or Cold Boot 9999 If the processor places a value of 9998 in this register the module will perform a warm boot operation If the processor places a value of 9999 in this register the module will perform a cold boot operation In this application module both of these operations perform the same function They exit the program and then restart the program Many of the program parameters set in the user configuration must be set at program initialization and cannot be set while the program is running Therefore both functions operate the same way Page 84 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 5 3 Exchange
51. controller and place the processor in run mode If you encounter errors refer to Diagnostics and Troubleshooting page 45 for information on how to connect to the module s Config Debug port to use its troubleshooting features ProSoft Technology Inc Page 43 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Ladder Logic GE Ethernet Global Data Communication Module Page 44 of 96 ProSoft Technology Inc November 3 2008 Diagnostics and Troubleshooting MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 4 Diagnostics and Troubleshooting InThis Chapter Reading Status Data from the Module see 45 LED Status Indicators sssessssssssseseeeeeeeeeneeeennne nn 57 The module provides information on diagnostics and troubleshooting in the following forms Status data values are transferred from the module to the processor Data contained in the module can be viewed through the Configuration Debug port attached to a terminal emulator LED status indicators on the front of the module provide information on the module s status 4 1 Reading Status Data from the Module The MVI69 EGD module returns a 20 word Status Data block that can be used to determine the module s operating status This data can be located in the module s database at registers at the location specified in the configuration This data is transferred
52. ct to any license agreement accompanying such software or other intellectual property 6 3 1 What Is Covered By This Warranty a Warranty On New Products ProSoft warrants to the original purchaser that the Product that is the subject of the sale will 1 conform to and perform in accordance with published specifications prepared approved and issued by ProSoft and 2 will be free from defects in material or workmanship provided these warranties only cover Product that is sold as new This Warranty expires three years from the date of shipment the Warranty Period If the Customer discovers within the Warranty Period a failure of the Product to conform to specifications or a defect in material or workmanship of the Product the Customer must promptly notify ProSoft by fax email or telephone In no event may that notification be received by ProSoft later than 39 months Within a reasonable time after notification ProSoft will correct any failure of the Product to conform to specifications or any defect in material or workmanship of the Product with either new or used replacement parts Such repair including both parts and labor will be performed at ProSoft s expense All warranty service will be performed at service centers designated by ProSoft b Warranty On Services Materials and labor performed by ProSoft to repair a verified malfunction or defect are warranteed in the terms specified above for new Product provided said warranty w
53. d ProSoft Configuration Builder OF xi File Edit View Project Tools Help EC Default Project Name Stats information E Default Location Default Module Please Select Module Type EAEDefault Module Unknown Product Line 1 Last Change Never Last Download Never Module Information MAC Address ConfigEdit rsion 2 0 13 Build 18 Module configuration module Module Type Module Name Default Module Updating data from new database Your first task is to add the MVI69 EGD module to the project 1 Use the mouse to select Default Module in the tree view and then click the right mouse button to open a shortcut menu Page 22 of 96 ProSoft Technology Inc November 3 2008 Configuring the MVI69 EGD Module MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 2 On the shortcut menu choose Choose Module Type This action opens the Choose Module Type dialog box Choose Module Type xi Product Line Filter C All C PLXSK C PTQ C MVI 56 C MVI71 C PLX4K C PLX6K C MVI 46 MVI 69 C MVI 94 STEP 1 Select Module Type MVI69 3964R MVI69 EGD MVI69 PDPMV1 MVI69 N2 Search Module Type Module Definition Action Required 3 Inthe Product Line Filter area of the dialog box select MVI69 In the Select Module Type dropdown list select MVI69 EGD and then click OK to save your
54. d data or source device consumed data Producer Exchange IP address If the cast type is set to U for a produced exchange the address should be set to IP address of the specific node to receive consume the data If the cast type is set to B for produced data set the IP to either a network 255 255 255 255 or subnet 192 168 0 255 broadcast address If the cast type is set to M for produced data set the IP address to a valid multicast address Page 30 of 96 ProSoft Technology Inc November 3 2008 Configuring the MVI69 EGD Module MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Multicast Address Assignments Important Use Multicast whenever the module produces data to at least two other modules Using Unicast for these applications can cause data transmission delay when at least one of the consumer modules is powered down Multicast group addresses 224 0 7 1 to 224 0 7 32 are reserved The module does not place this limit for messages but the user should consider using the reserved group addresses The following table shows the relationship between multicast group parameters and IP addresses Refer to Underlying Protocol Requirements and Constraints for more detailed information on IP and UDP addresses Parameter IP Address Group 1 224 0 7 1 Group 2 224 0 7 2 Group 32 224 0 7 32 Important For Multicast mode use transmit rates of 1 or 2 for best res
55. duced data as defined in the user configuration exchange list This data is derived from the module s internal database and is produced at the set frequency defined in the exchange list This data can be broadcast to all nodes or to a specific node on the network Up to 700 database registers can be transferred in a single produced message Therefore to transfer the whole database would only require 6 messages 4000 word registers in the module s database Central to the functionality of the module is the internal database This database is shared between all the drivers in the module and is used as a conduit to pass information from one device on one network to one or more devices on another network This permits data from devices on one communication port to be viewed and controlled by devices on another port The producer functionality provided in the EGD driver is used to transfer portions of the module s database to other EGD nodes on the network The following diagram describes the flow of data between the producer the internal database and the remote EGD devices Producer Databases 1DE Read for Producton 1 E Read Exchange List Produced Data 5 2 4 EGD Data Consumer The EGD driver will consume data as defined in the user configuration exchange list This data is derived from other nodes on the network and is placed in the module s internal database If a consumer exchange is not received at the specified timeout
56. dule will perform a platform check to read and load its new settings When the platform check is complete the status bar in ProSoft Configuration Builder will be updated with the message Module Running Download files from PC to module x Module Running TT Step 1 Select Port Com 1 X F Use Default IP Address Step 2 Transfer Files ProSoft Technology Inc Page 35 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Configuring the MVI69 EGD Module GE Ethernet Global Data Communication Module Page 36 of 96 ProSoft Technology Inc November 3 2008 Ladder Logic MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 3 1 Ladder Logic In This Chapter Adding the Module to an Existing CompactLogix Project 37 Adding the Module to an Existing MicroLogix Project 42 Ladder logic is required for application of the MVI69 EGD module Tasks that must be handled by the ladder logic are module data transfer special block handling and status data receipt Additionally a power up handler may be needed to handle the initialization of the module s data and to clear any processor fault conditions The sample ladder logic on the ProSoft Solutions CD ROM is extensively commented to provide information on the purpose and function of each rung For most applications the sample ladder will work withou
57. e Allen Bradley Specialty Find Add Favorite By Category Favorites cows te _ 4 Page 38 of 96 ProSoft Technology Inc November 3 2008 Ladder Logic MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 2 Select the 1769 Module Generic 1769 Module from the list and click OK Type 1769 MODULE Generic 1769 Module Parent Local Connection Parameters Assembly Instance Size Name MVIB3 Sample Input 101 ES 16 bit Description Output 100 E 16 bit Configuration 102 nes Comm Format Data INT m Slot 1 ES v Open Module Properties Cancel Help 3 Enter the Name Description and Slot options for your application using the values in the illustration above You must select the Comm Format as Data INT in the dialog box otherwise the module will not communicate over the backplane of the CompactLogix rack 4 Configure the Connection Parameters to match to the Block Transfer Size parameter in the configuration file Use the values in the table corresponding with the block transfer size you configured Block Transfer Size 60 Field Recommended Value Type 1769 MODULE Generic 1769 Module Parent Local Name MVI69 Description MVI69 Application Module Comm Format Data INT Slot The slot number in the rack where the module is installed Input Assembly Ins
58. e for implementation can complete the application without exposing personnel or equipment to unsafe or inappropriate working conditions Safety quality and experience are key factors in a successful installation 1 4 System Requirements The MVI69 EGD module requires the following minimum hardware and software components Rockwell Automation CompactLogix or MicroLogix processor with compatible power supply and one free slot in the rack for the MVI69 EGD module The module requires 800mA of available power Important The MVI69 EGD module has a power supply distance rating of 2 L43 and L45 installations on first 2 slots of 1769 bus Important For 1769 L23x processors please make note of the following limitations 1769 L23 QBFC1B 800mA at 5Vdc 1 MVI69 EGD will use all 800mA of available power No other modules can be used with an MVI69 module connected to this processor 1769 L23E QB1B 1000mA at 5Vdc 1 MVI69 EGD will use 800mA of available power One other module can be used on this rack provided it consumes less than 200mA at 5Vdc 1769 L23E QBFC1B 450mA at 5Vdc no MVI69 module can be used with this processor Rockwell Automation RSLogix 5000 CompactLogix or RSLogix 500 MicroLogix programming software Rockwell Automation RSLinx communication software ProSoft Technology Inc Page 9 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communic
59. e is used to specify the parameters for the Simple Network Time Protocol SNTP client provided with the protocol driver This client is required in order to keep the driver s internal clock set correctly This version of the driver supports the unicast implementation of the SNTP Revision 3 and stratum between 1 and 14 The module can be configured to periodically synchronize its clock with a remote SNTP server Approximately every 6 minutes the module sends 10 consecutive requests to the remote SNTP client at approximately 6 second intervals You can check these requests and responses by looking at the SNTP Client Configuration Menu press the N key at the Configuration Debug Main Menu If the module receives a valid response from the SNTP server the computations value will be also be incremented After 10 consecutive successful requests and responses the module will synchronize its internal clock an average is performed based on all 10 responses for better accuracy The Time Set Cnt value is incremented every time the clock is synchronized After the synchronization is performed the time valid register is set to Yes If the module cannot connect to the remote SNTP server after 3 consecutive attempts the time valid register is set to No You can also configure the GMT settings to use and the database address where the date and time information can be copied The following parameters in the configuration file set up the SNTP client TP C
60. e remainder of this section shows you the menus available for this module and briefly discusses the commands available to you Keystrokes The keyboard commands on these menus are almost always non case sensitive You can enter most commands in lower case or capital letters The menus use a few special characters that must be entered exactly as shown Some of these characters will require you to use the Shift Ctrl or Alt keys to enter them correctly For example on US English keyboards enter the command as Shift Also take care to distinguish capital letter I from lower case letter I L and number 1 likewise for capital letter O and number 0 Although these characters look nearly the same on the screen they perform different actions on the module 4 1 3 Main Menu When you first connect to the module from your computer your terminal screen will be blank To activate the main menu press the key on your computer s keyboard If the module is connected properly the following menu will appear on your terminal screen Caution Some of the commands available to you from this menu are designed for advanced debugging and system testing only and can cause the module to stop communicating with the processor or with other devices resulting in potential data loss or other failures Only use these commands if you are specifically directed to do so by ProSoft Technology Technical Support staff
61. ed in the time computation 2 3 4 Database Register 1 or 0 to 3992 as an even value This parameter specifies if the NTP time computed by the driver is to be placed into the module s database If a value of 1 is specified the time will not be placed into the database If the value is between 0 and 3992 the time will be placed in the database The first 4 bytes represent the seconds since 1 1 1970 and the second 4 bytes represent the number of microseconds An even value should be used for the register value in order for the data to be stored correctly EGD Exchanges In order to interface the module with EGD devices you must construct an exchange list The exchanges specify messages that will be produced or consumed at a user defined frequency using the module s internal database Messages can be broadcast to all nodes on the network sent to a multicast group on the network or associated with a single node on the network Up to 100 exchanges can be defined for the driver Up to 680 word registers can be produced or consumed in a single exchange The EGD Exchanges section defines the messages that will be produced and consumed by the driver The UDP protocol on the IP network is used to transport these over Ethernet between all the EGD devices For the exchanges to operate correctly the other EGD devices must be configured and correctly set up The primary reason for user problems with the module is failure to provide devices that
62. eter in the left pane and make your changes in the right pane Click OK to save your changes Comment Entries To add comments to your configuration file 1 2 3 Click the plus sign to the left of the a comment icon to expand the Module Comments Double click the 8 sie comment icon The Edit Module Comment dialog appears Comment Put Comment Here Definition Reset Tag Reset All OK Cancel Enter your comment and click OK to save your changes Printing a Configuration File To print a configuration file 1 Select the Module icon and then click the right mouse button to open a shortcut menu 2 Onthe shortcut menu choose View Configuration This action opens the View Configuration window 3 Onthe View Configuration window open the File menu and choose Print This action opens the Print dialog box 4 Onthe Print dialog box choose the printer to use from the dropdown list select printing options and then click OK ProSoft Technology Inc Page 25 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Configuring the MVI69 EGD Module GE Ethernet Global Data Communication Module 2 2 Module69 This section designates database addresses for input and output on the module and on the processor and identifies the method of failure for the communications for the module if the processor is not in run mode 2 2 1 Read Register Start Range 0 to 3999 This parameter specifies the s
63. fo Ethernet Destination MAC 00 0D 8D 00 13 83 II Source MAC 00 12 3F AE 5C AE iP 0 0 Normal Delay Normal throughput Ox 00 0 0 Normal throughput L 0 0 _ Normalreliabilty oo Normal Monetary cost 2615 0x0A55 Fes E May Fragment 0x 00 0 0 LastFragmnt 17 0x11 UDP UDP Checksum 32236 correct 0x 7DEC EGD sPDUField Offset Bytes Hexcode po mp o xo a 2 e This is an example of an EGD Configuration Request Command Production Data Unit ProSoft Technology Inc Page 63 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module This is the Hexadecimal representation of the Retrieve configuration Request from the above table It includes the Ethernet II IPv4 UDP and within UDP the EGD Command PDU Type 3 depicted in bold font 00 OD 8D 00 13 83 00 12 3f AE 5C AE 08 00 45 00 00 2C OA 55 00 00 40 11 9C Ob 69 66 00 C8 69 66 00 CD 1F 01 1F 01 00 18 7D EC 03 00 11 11 01 00 10 00 69 66 00 C8 E1 2E 00 00 PDU Type 4 Retrieve Configuration Response The retrieve configuration response PDU supports the retrieval of exchange configurations for Ethernet Global Data This message packet will be sent in response to a
64. g node Packet Description Data Info Source Pot Port Source Pot 7937 Ox 1F01 ProSoft Technology Inc Page 67 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module PDU Type 8 Summary Response The summary response PDU is used to respond to a summary request This PDU returns a list of exchanges which are currently defined on the responding node This message is of variable length the number of summaries or cells included in the message is returned in the header of the message If the number of cells returned is less than the total number of cells remaining summaries can be retrieved by subsequent requests with a larger index variable Packet Description Data Info Source Port 7937 0x 1F01 Checksum 0 xxxxx Ox XX XX Wesen Ss mw fo memes p p o pem me Eis r Total Cells HH HH Qty of exchange cells mai defined for this node Cells contained in the Ox HH HH message The following six items are referred to as the exchange Cell Each Cell targets one EGD Exchange command line present in the EGD Module s configuration file Cell Qty is limited to EGD Exchange command lines present in the module s configuration file odes aso Bem e p pem Page 68 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platf
65. hen the download is complete locate and open the file and then follow the instructions on your screen to install the program If you do not have access to the Internet you can install ProSoft Configuration Builder from the ProSoft Solutions CD ROM included in the package with your MVI69 EGD module To install ProSoft Configuration Builder from the CD ROM 1 Insert the ProSoft Solutions CD ROM into the CD drive of your PC Wait for the startup screen to appear 2 Onthe startup screen click Product Documentation This action opens an explorer window ProSoft Technology Inc Page 11 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module 3 Click to open the Utilities folder This folder contains all of the applications and files you will need to set up and configure your module 4 Double click the ProSoft Configuration Builder Setup program and follow the instructions on your screen to install the software on your PC Note Many of the configuration and maintenance procedures use files and other utilities on the CD ROM You may wish to copy the files from the Utilities folder on the CD ROM to a convenient location on your hard drive 1 4 Setting Jumpers Note The Setup Jumper acts as write protection for the module s flash memory In write protected mode the Setup pins are not connected and the module s firmware cannot be overwritten Do not jumpe
66. her intellectual property Failure to do so may void this Warranty with respect to such software and or other intellectual property 6 3 5 Disclaimer of all Other Warranties The Warranty set forth in What Is Covered By This Warranty page 90 are in lieu of all other warranties express or implied including but not limited to the implied warranties of merchantability and fitness for a particular purpose 6 3 6 Limitation of Remedies In no event will ProSoft or its Dealer be liable for any special incidental or consequential damages based on breach of warranty breach of contract negligence strict tort or any other legal theory Damages that ProSoft or its Dealer will not be responsible for included but are not limited to Loss of profits loss of savings or revenue loss of use of the product or any associated equipment loss of data cost of capital cost of any substitute equipment facilities or services downtime the claims of third parties including customers of the Purchaser and injury to property Some areas do not allow time limitations on an implied warranty or allow the exclusion or limitation of incidental or consequential damages In such areas the above limitations may not apply This Warranty gives you specific legal rights and you may also have other rights which vary from place to place Page 92 of 96 ProSoft Technology Inc November 3 2008 Support Service amp Warranty MVI69 EGD CompactLogix or
67. his Warranty or a portion thereof to be unenforceable that provision shall be enforced to the maximum extent permissible and the remainder of this Warranty shall remain in full force and effect Any cause of action with respect to the Product or Services must be instituted in a court of competent jurisdiction in the State of California ProSoft Technology Inc Page 93 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Support Service amp Warranty GE Ethernet Global Data Communication Module Page 94 of 96 ProSoft Technology Inc November 3 2008 Index MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Index EGD Exchanges 28 EGD Multicast Group List 33 Module69 26 SNTP Client 27 A Adding a Module 23 Adding a Project 23 Adding the Module to an Existing CompactLogix Project 37 Adding the Module to an Existing MicroLogix Project 42 All Product Returns 88 Allocation of Risks 93 Backplane Data Transfer 79 Battery Life Advisory 2 Block 2000 C P Status Data Format 83 Block 2000 Request 82 Block 2000 Response 82 Block 9250 Request Block General Status 83 Block 9250 Response Block General Status 83 Block Transfer Size 26 C Capabilities PDUs 62 66 Cast Type 29 Clearing a Fault Condition 58 Command Control Blocks 82 Command NAK PDU 62 70 Comment Entries 25 Com
68. hout notice and does not represent a commitment on the part of ProSoft Technology Improvements and or changes in this manual or the product may be made at any time These changes will be made periodically to correct technical inaccuracies or typographical errors Battery Life Advisory All modules in the MVI series use a rechargeable Lithium Vanadium Pentoxide battery to backup the 512K SRAM memory real time clock and CMOS The battery should last for the life of the module The module must be powered for approximately twenty hours before it becomes fully charged After it is fully charged the battery provides backup power for the CMOS setup and configuration data the real time clock and the 512K SRAM memory for approximately 21 days Before you remove a module from its power source ensure that the battery within the module is fully charged A fully charged battery will hold the BIOS settings after being removed from its power source for a limited number of days When the battery is fully discharged the module will revert to the default BIOS settings Note The battery is not user replaceable Your Feedback Please We always want you to feel that you made the right decision to use our products If you have suggestions comments compliments or complaints about the product documentation or support please write or call us ProSoft Technology 1675 Chester Avenue Fourth Floor Bakersfield CA 93301 1 661 716 5100 1 661 716 5101
69. identification codes in each data block determine the function to be performed or the content of the data block The module uses the following block numbers Block Range Descriptions 1 or 0 Empty Data Blocks 1 to 67 Data Read or Write Blocks 2000 CP Status Data 9250 General Status Data 9998 Warm boot control block 9999 Cold boot control block Page 80 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Each image has a defined structure depending on the data content and the function of the data transfer 5 2 6 Normal Data Transfer Normal data transfer includes the paging of the user data found in the module s internal database in registers 0 to 3999 and the status data These data are transferred through read input image and write output image blocks Refer to the Module Configuration and Ladder Logic sections for a description of the data objects used with the blocks and the ladder logic required The structure and function of each block is discussed in the following topics Normal Input Data Block These blocks of data transfer information from the module to the CompactLogix or MicroLogix processor and transfer output control data sent to the module from the remote master unit The structure of the input image used to transfer this data is shown in the following table Words Description
70. idual cell references in the message Each cell reference specifies which bits to change in the byte specified by the offset given Based on the address type the Domain ID must contain an Exchange and Producer ID or target specific address which is valid on the destination node A masked write request sent from a requesting node must be followed by a masked write response message from the responding node Some devices may not support writing individual bits and others may support writing only one bit at a time Such devices shall return a status of MEMORY ACCESS ERROR for masked write attempts that they do not support Packet Description Info UDP Source Pos reer x 1FOT 7937 0x TFOI ix bytes 0x 00 XX ioco 0x XX XX c x N y T d e td x pei I I H I I ojo o xT xT xX LX 1X I I I I T E gt I I T m ojo x x 1X I I I I ojolo xXx T T I I I I HH HH HH gt c x T T Reserved The following three items are referred to as the exchange Cell Each Cell targets one EGD Exchange command line present in the EGD Module s configuration file Offset writes into the DB Register specified in the EGD Exchange command line Mask example 0x AA AA Bin 1010101010101010 Data is ANDed with the Mask Bytes on the target server Offset 0x HH HH HH HH Hex code Option Type 5 Signature 1 1 ProSoft Technology Inc Page 75 of 96 Novembe
71. iguration EGD Configuration Values OK lg Comment Comment Values OK E Ethernet Configuration WATTCP Values OK Last Change Never Last Download Never tt Module Information Last Change Ne Last Download V Application Rev OS Rev Loader Rev MAC Address ConfigEdit version 2 0 13 Build 18 ik te te te te k H EtherNet Configuration my_ip 168 0 100 netmask 255 255 0 gateway 168 0 1 Module Configuration Module Module Type MVI69 EGD Module Name MVI69 EGD Error Status Pointer 3000 Read Register Start 270 Read Register Count 100 write Reqister Start 100 lUpdating data from new database At this time you may wish to rename the Default Project and Default Location folders in the tree view To rename an object 1 Select the object and then click the right mouse button to open a shortcut menu From the shortcut menu choose Rename 2 Type the name to assign to the object 3 Click away from the object to save the new name Page 24 of 96 ProSoft Technology Inc November 3 2008 Configuring the MVI69 EGD Module MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Module Entries To configure module parameters 1 2 3 4 Click on the plus sign next to the icon a commet to expand module information Double click the B Module comment icon to open the Edit dialog box To edit a parameter select the param
72. iguration exchange list This data is derived from other nodes on the network and is placed in the module s internal database If a consumer exchange is not received at the specified timeout the driver will update the status of the exchange When the driver again receives the exchange the status will be updated Functional Overview GE Fanuc Automation and GE Drive Systems developed an Ethernet Global Data or EGD exchange for PLC and computer data in 1998 GE Ethernet Global Data EGD offers versatility where a mix of control devices requires cooperation with each other This involves sharing of information across the applications regardless of device or network type often at high speed and with high reliability Bandwidth utilization is optimized by using efficient communication methods High reliability means fewer communication failures and having the ability to detect failures upon occurrence Particular emphasis is delivered for applications requiring periodic or frequent updates and time synchronization of devices The protocol supports Unicast Broadcast and Multicast group messaging Efficiency is based on the fact each device on the network can produce these types of messages and each device determines which of these messages to consume 5 2 1 Ethernet Global Data Compatible Devices List of devices that support the Ethernet Global Data protocol GE Series 90 70 PLC CPU CMM742 with EGD support GE Series 90 30 PLC CPU 364 with E
73. ill be for the period remaining on the original new equipment warranty or if the original warranty is no longer in effect for a period of 90 days from the date of repair 6 3 2 What Is Not Covered By This Warranty a ProSoft makes no representation or warranty expressed or implied that the operation of software purchased from ProSoft will be uninterrupted or error free or that the functions contained in the software will meet or satisfy the purchaser s intended use or requirements the Customer assumes complete responsibility for decisions made or actions taken based on information obtained using ProSoft software Page 90 of 96 ProSoft Technology Inc November 3 2008 Support Service amp Warranty MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module b This Warranty does not cover the failure of the Product to perform specified functions or any other non conformance defects losses or damages caused by or attributable to any of the following i shipping ii improper installation or other failure of Customer to adhere to ProSoft s specifications or instructions iii unauthorized repair or maintenance iv attachments equipment options parts software or user created programming including but not limited to programs developed with any IEC 61131 3 C or any variant of C programming languages not furnished by ProSoft v use of the Product for purposes other than those
74. ix or MicroLogix Platform GE Ethernet Global Data Communication Module 1 3 Install ProSoft Configuration Builder Software You must install the ProSoft Configuration Builder PCB software in order to configure the MVI69 EGD module You can always get the newest version of ProSoft Configuration Builder from the ProSoft Technology web site To install ProSoft Configuration Builder from the ProSoft Web Site 1 Open your web browser and navigate to http www prosoft technology com pcb 2 Click the Download Here link to download the latest version of ProSoft Configuration Builder 3 Choose Save or Save File when prompted The following illustrations show the file download prompt for two of the most common web browsers Opening PCB_2 0 12 13 0054 exe xi You have chosen to open zjj PCB_2 0 12 13 0054 exe whichisa Application from http www prosoft technology com Would you like to save this file File Download Security Warning x Do you want to run or save this file Name PCB_2 0 12 13 0054 exe Type Application 17 3MB From www prosoft technology com Run Save While files from the Intemet can be useful this file type can i potentially harm your computer If you do not trust the source do not run or save this software What s the risk 4 Make a note of the location where you saved the file for example Desktop or My Documents so you can start the installation program 5 W
75. message to all stations set exchange IP address to 255 255 255 255 When the Exchange Type is Consumer the cast type field determines how the local database area associated to this exchange will be updated in case an RF Error timeout occurs Consumer No DB Change on HF Error Consumer Set DB to 1 On RF Error Consumer Set DB to 0 On RF Error Consumer Set DB to 1 On RF Error 2 4 8 DB Reg The DB Register field defines the starting database register in the module where data sourced produced data or placed consumed data is determined by the value entered in the DB Reg column This parameter can have a value of 0 to 3999 The validity of the entry is dependent on the number of registers Reg Count to be produced or consumed The sum of the two values cannot exceed 4000 as this would be outside the range of the module s database 2 4 4 Reg Count Number of database registers to transfer accept in message ProSoft Technology Inc Page 29 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Configuring the MVI69 EGD Module GE Ethernet Global Data Communication Module 2 4 5 Swap Code 0 1 20r 3 The Swap Code field sets byte and word swapping of data produced or consumed Swapping of words and or bytes in the message may be required for different protocol and operating systems as their representation of multi byte values may not be the same as that of the EGD protocol Swap Code Description
76. mportant for understanding the operation of the MVI69 EGD module On power up the module begins performing the following logical functions 1 Initialize hardware components o Initialize CompactLogix or MicroLogix backplane driver o Testand Clear all RAM o Initialize the serial communication ports 2 Reads configuration from Compact Flash Disk 3 Initialize Module Register space 4 Enable Slave Driver on selected ports After the module has received the Module Configuration the module will begin communicating with other nodes on the network depending on the configuration Page 78 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Main Logic Loop Upon completing the power up configuration process the module enters an infinite loop that performs the functions shown in the following diagram From Power Up Logic Call l O Handler Call I O Handler Transfers data between the module and processor user status etc Call CFG DEBUG Port Call Serial Port Driver Rx and Tx buffer routines are interrupt driven Call to serial port routines check to see if there is any data in the buffer and depending on the value will either service the buffer or wait for more characters Driver Call Network Server Call Network Server Drivers Drivers Respond to messages received CompactLogix or MicroLogix Processor Not in
77. or to the module ProSoft Technology Inc Page 79 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module The following illustration shows the data transfer method used to move data between the CompactLogix or MicroLogix processor and the MVI69 EGD module MicroLogix Processor MVIBS EGD Module Read Data m a i I O EGD TCP AP Stack E Interface i and Ethernet Ethernet Jang auejdpeg driver 3 Interface Network Write D ata files aseqeje ol Special Control Blocks files All data transferred between the module and the processor over the backplane is through the input and output images Ladder logic must be written in the CompactLogix or MicroLogix processor to interface the input and output image data with data defined in the Controller Tags All data used by the module is stored in its internal database The following illustration shows the layout of the database Module s Internal Database Structure 4000 registers for user data 0 Register Data 3999 Data contained in this database is paged through the input and output images by coordination of the CompactLogix or MicroLogix ladder logic and the MVI69 EGD module s program Up to 248 words of data can be transferred from the module to the processor at a time Up to 247 words of data can be transferred from the processor to the module The read and write block
78. orm GE Ethernet Global Data Communication Module Statistics PDUs PDU Type 15 Statistics Request The statistics request PDU command permits an application program to obtain the current operating statistics of the specified Exchange The exchange must be valid on the destination node A statistics request sent from a requesting node must be followed by a statistics response message from the responding node Packet Description Data Info UDP Source Pot oa 0x 1F01 Port 7937 Ox 1F01 Length xx bytes 0x 00 XX Checksum Checksum xxxxx 0x XX XX EGD s PDU Field Offset Bytes Hex code PDU Type jp h C Message Flag PIN pw 1 1 19 Reserved o i o Message Length e 2 om maeb p p oct Exchange o po o e o HH HH HH HH HH HH HH PDU Type 16 Statistics Response The statistics response PDU command returns the operating statistics for the Producer and Exchange ID specified in the request message Packet Description Info UDP Length Checksum Source Port Destination Port EGD EGUSPDUFi fons PpuTpe D Message Flags Request ID ew Ce so NN ie Be I m ProSoft Technology Inc November 3 2008 Page 69 of 96 MVI69 EGD CompactLogix or MicroLogix Platform Reference GE Ethernet Global Data Communication Module Packe
79. out prior written consent from ProSoft b ProSoft s technical specifications and documentation that are included with the Product are subject to editing and modification without notice c Transfer of title shall not operate to convey to Customer any right to make or have made any Product supplied by ProSoft d Customer is granted no right or license to use any software or other intellectual property in any manner or for any purpose not expressly permitted by any license agreement accompanying such software or other intellectual property e Customer agrees that it shall not and shall not authorize others to copy software provided by ProSoft except as expressly permitted in any license agreement accompanying such software transfer software to a third party separately from the Product modify alter translate decode decompile disassemble reverse engineer or otherwise attempt to derive the source code of the software or create derivative works based on the software export the software or underlying technology in contravention of applicable US and international export laws and regulations or use the software other than as authorized in connection with use of Product f Additional Restrictions Relating To Software And Other Intellectual Property In addition to compliance with the Terms of this Warranty Customers purchasing software or other intellectual property shall comply with any license agreement accompanying such software or ot
80. pactLogix or MicroLogix Processor Not in Run 79 Configuring RSLinx 18 Configuring the MVI69 EGD Module 21 Connect your PC to the Module 20 Connect your PC to the Processor 16 Controlling Law and Severability 93 CS Major CS Minor 31 D Database Register 28 Database View Menu 51 DB Reg 29 Diagnostics and Troubleshooting 7 43 45 Disclaimer of all Other Warranties 92 Disclaimer Regarding High Risk Activities 91 Displaying the Current Page of Registers Again 52 Download the Project to the Module 34 Download the Sample Program to the Processor 17 E EGD Command Server 62 EGD Data Consumer 77 EGD Data Producer 77 EGD Exchange Command List Example 33 EGD Menu 54 Ethernet Configuration 33 Ethernet Global Data Compatible Devices 61 Ethernet LED Indicators 57 Exch ID 31 Exch Type 29 Exchange Configuration Form 85 Exiting the Program 51 F Failure Flag Count 26 Functional Overview 7 61 Functional Specifications 60 G General Concepts 78 General Specifications 59 Going Ahead Two Pages of Data 56 Going Back Two Pages of Data 55 56 Guide to the MVI69 EGD User Manual 7 H Hardware Specifications 60 How to Contact Us Technical Support 87 88 Install ProSoft Configuration Builder Software 11 Install the Module in the Rack 13 Intellectual Property Indemnity 91 IP Address 30 K Keystrokes 48 L Ladder Logic
81. play the current configuration and statistics for the module Opening the Database Menu Press D to open the Database View menu Use this menu command to view the current contents of the module s database Opening the EGD Menu Press E to open the EGD Menu Use this command to view the configuration and status of EGD Producer Consumer Exchanges Viewing SNTP Status Press I to view configuration information about the SNTP client SNTP CLIENT CONFIGURATION NTP SERVER IP 0 0 0 0 DB REGISTER 3000 TIME ZONE 8 USE DST No TIME VALID NO REQUESTS 0 RESPONSES 0 COMPUTATIONS 0 TIME SET CNT 0 TIMEOUT ERRS 0 SNTP Local time is Fri Dec 14 08 22 38 2007 OSNTP GMT is Fri Dec 14 16 22 38 2007 Refer to SNTP Support for more information on configuring and using this function Transferring the Configuration File from PC to MVI69 module Press R to send upload the configuration file from your PC to the module and store the file on the module s Compact Flash Disk Press Y to confirm the file transfer and then follow the instructions on the terminal screen to complete the file transfer process ProSoft Technology Inc Page 49 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Diagnostics and Troubleshooting GE Ethernet Global Data Communication Module After the file has been successfully downloaded the module will restart the program and load the new configuration informa
82. ps to take BP ACT LED remains This indicates that backplane transfer operations are failing Connect to off or blinks slowly the module s Configuration Debug port to check this To establish backplane communications verify the following items The processor is in Run mode The backplane driver is loaded in the module The module is configured for read and write block data transfer The ladder logic handles all read and write block situations The module is configured in the processor OK LED remains red The program has halted or a critical error has occurred Connect to the Configuration Debug port to see if the module is running If the program has halted turn off power to the rack remove the card from the rack and re insert the card in the rack and then restore power to the rack Page 58 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 5 1 Reference InThis Chapter S Product Specificatioris 3 obe eDb RR MEHERDESRAR 59 jFurictional Overview 2 eee MEHR 61 Exchange Configuration Form eesseseeee 85 Product Specifications The Ethernet Global Data EGD module can be used to interface many different protocols with EGD devices The EGD driver supports both the producer consumer service port 18246 and the command service port 7937 using the UDP protocol
83. r open the Communications menu and then choose Download RSLogix will establish communication with the processor 2 When communication is established RSLogix will open a confirmation dialog box Click the Download button to transfer the sample program to the processor Download x Download to the controller s Name MYI69 Type 1769 L32E CompactLogix5332E Controller Path AB_DF1 1 Security None A The controller is in Remote Run mode The mode will be changed to Remote Program prior to download Cancel Help 3 RSLogix will compile the program and transfer it to the processor This process may take a few minutes 4 When the download is complete RSLogix will open another confirmation dialog box Click OK to switch the processor from Program mode to Run mode RSLogix 5000 Done downloading Change controller mode back to Remote Run E No Note If you receive an error message during these steps refer to your RSLogix documentation to interpret and correct the error ProSoft Technology Inc Page 17 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module 1 7 1 Configuring RSLinx If RSLogix is unable to establish communication with the processor follow these steps 1 Open RSLinx 2 Open the Communications menu and choose Configure Drivers Communications Station DDE OPC RSWho Configure Drivers
84. r 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Reference PDU Type 37 Masked Write Response The Masked Write Response provides an acknowledgment to the masked write request message A positive response indicates that all of the data has been written to the responding device An error response indicates that one or more of the transfers to the responding device failed Responders shall use all available means to assure that a write is performed in its entirety or not performed at all Requesting applications are advised that if partial failures of the write can cause problems with the control algorithm they should include only one cell in each write to assure complete knowledge of the disposition of the write request Requesters should be aware that some responding devices are not capable of setting more than one bit in a request Before sending a mask with more than one bit set the requester should assure that the responding device supports multiple bit writes Packet Description Info ress Type T Cercon n Producer az Reserve 5 ce x m T o x o oeojojojojo o jo jo x x x x x x x x e x Page 76 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 5 2 3 EGD Data Producer The EGD driver will generate pro
85. r List Menu Press C to open the Producer Consumer List menu Use this command to view a list of the configured producers and consumers PRODUCER CONSUMER LIST MENU Display Menu S Show Again Back 2 Pages P Previous Page Skip 2 Pages NzNext Page M Return to EGD Main Menu Redisplaying the Menu Press to display the current menu Use this command when you are looking at a screen of data and want to view the menu choices available to you Redisplaying the Current Page Press S to display the current page of data Going Back Two Pages of Data Press from the Database View menu to skip back to the previous 200 registers of data Viewing the Previous Page of Data Press P to display the previous page of data ProSoft Technology Inc Page 55 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Diagnostics and Troubleshooting GE Ethernet Global Data Communication Module Going Ahead Two Pages of Data Hold down Shift and press 2 to skip forward to the next 200 registers of data Viewing the Next Page of Data Press N to display the next page of data Returning to the Previous Menu Press M to return to the Previous Menu 4 1 8 Producer Consumer Status Menu Press S to open the Producer Consumer Status menu Use this command to view communication status for each of the configured producers and consumers PRODUCER CONSUMER STATUS MENU Display Menu S Show Again
86. r the Setup pins together unless you are directed to do so by ProSoft Technical Support SETUP NOT JUMPERED Page 12 of 96 ProSoft Technology Inc November 3 2008 Start Here MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 1 5 Install the Module in the Rack This section describes how to install the module into a CompactLogix or MicroLogix rack Before you attempt to install the module make sure that the bus lever of the adjacent module is in the unlocked fully right position Waming This module is not hot swappable Always remove power from the rack before inserting or removing this module or damage may result to the module the processor or other connected devices 1 Align the module using the upper and lower tongue and groove slots with the adjacent module and slide forward in the direction of the arrow 2 Move the module back along the tongue and groove slots until the bus connectors on the MVI69 module and the adjacent module line up with each other ProSoft Technology Inc Page 13 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module 3 Push the module s bus lever back slightly to clear the positioning tab and move it firmly to the left until it clicks Ensure that it is locked firmly in place DIN Rail Latches Bus Lever Free position Top View
87. s 61 5 3 Exchange Configuration Form sssssssssssssseeeeeeen nennen nennen 85 ProSoft Technology Inc Page 5 of 96 November 3 2008 Contents MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 6 Support Service amp Warranty 87 6 1 How to Contact Us Technical Support 87 6 2 Return Material Authorization RMA Policies and Conditions 88 6 3 LIMITED WARRANT iit inerte ber ete teet eere te edP eie 90 Index 95 Page 6 of 96 ProSoft Technology Inc November 3 2008 Start Here MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Guide to the MVI69 EGD User Manual Function Section to Read Details Introduction Start Here page 9 This Section introduces the customer to the Must Do module Included are package contents system requirements hardware installation and basic configuration Verify Communication Diagnostic and Troubleshooting Verifying Communication page 57 Diagnostics and Troubleshooting page 45 This section describes how to verify communications with the network Diagnostic and Troubleshooting procedures Reference Product Specifications Functional Overview Glossary Reference page 59 Functional Overview page 61 Product Specifications page 59 These sections contain general references associa
88. s that will help you to understand the consumer criteria to validate received exchanges based on the Configuration Signature Producer Producer Consumer Consumer Will Data be Comment CS Major CS Minor CS Major CSMinor Consumed 0 0 0 0 Yes Same CS value of 0 0 Major Minor validates the exchange 0 0 1 2 Yes Producer CS value of 0 0 Major Minor validates the exchange 1 2 0 0 Yes Consumer CS value of 0 0 Major Minor validates the exchange 1 2 1 2 Yes Same CS value 1 2 validates the exchange 2 2 1 2 No CS Major mismatch exchange is not validated 1 2 2 2 No CS Major mismatch exchange is not validated 1 2 1 1 Yes Same CS Major and Consumer CS Minor is less than Producer CS Minor exchange is validated 1 2 1 3 No Same CS Major but Consumer CS Minor is greater than Producer CS Minor exchange is not validated Page 32 of 96 ProSoft Technology Inc November 3 2008 Configuring the MVI69 EGD Module MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 2 4 10 EGD Exchange Command List Example The following is an example section from the EGD Exchanges section Edit EGD EXCHANGES x Exch Type Cast Type DB Reg RegCount SwapCode P C Time IP Address ExchID CS Major CS Minor Consumer Producer Unicast 3005 5 No Change 400 172 16 10 201 12010 0 0 Producer Producer Unicast 3000 1 No Change 100 172 16 10 201 S 0 a
89. serial port to work with the selected driver 5 When you see the message Auto Configuration Successful click the OK button to dismiss the dialog box Note If the auto configuration procedure fails verify that the cables are connected correctly between the processor and the serial port on your computer and then try again If you are still unable to auto configure the port refer to your RSLinx documentation for further troubleshooting steps ProSoft Technology Inc Page 19 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module 1 8 Connect your PC to the Module With the module securely mounted connect your PC to the Configuration Debug port using an RJ45 DB 9 Serial Adapter Cable and a Null Modem Cable 1 Attach both cables as shown 2 Insert the RJ45 cable connector into the Configuration Debug port of the module 3 Attach the other end to the serial port on your PC or laptop Configuration Debug Port Null Modem Cable to wi RJ45 DB9 Serial Null Modem Cable Adapter Cable Page 20 of 96 ProSoft Technology Inc November 3 2008 Configuring the MVI69 EGD Module MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 2 Configuring the MVI69 EGD Module In This Chapter ProSoft Configuration Builder em 21 Module69 mites e a a
90. ssage Each cell reference specifies an offset into the Packet Description Info E ID e HH HH HH specified Exchange the number of bytes of Data and the Data itself All data Source Port Port 7937 0x 1FO1 sd 0x 1F01 uus EDR oe are ere Message Fags p p em mE p es pion Leva p em wie n E e MES oleafeped gt nu i nofeJjelrnfie returned must be padded to the nearest 4 byte boundary Configuration Sina a E E HH HH Producer ID h2 4 ox HH HH HH HH The E four items are referred to as the exchange Cell Each Cell contains data from one EGD Exchange command line present in the EGD Module s configuration file Offset reads the DB Register specified in the EGD Exchange command Length is Bytes Qty not Words Multiple Cells may be returned dependent on the Cell Count field specified in the see PDU a i ae Data depends on length 36 CEE HH requested Padding to 32 bit 0x HH HH boundary Page 72 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Write PDUs PDU Type 34 Write Request The write request PDU is used to change the contents of one or more contiguous groups of memory on a specific peer controller The header defines parameters which apply to the all of the individual cell references in the message Each cell
91. staff Some of these command keys are not listed on the menu but are active nevertheless Please be careful when pressing keys so that you do not accidentally execute an unwanted command Press Esc to restart the module and force all drivers to be loaded The module will use the configuration stored in the module s Flash ROM to configure the module 4 1 4 Database View Menu Press D from the Main Menu to open the Database View menu Use this menu command to view the current contents of the module s database Press to view a list of commands available on this menu D Database Menu Display Menu Redisplays refre shes this menu Selects page 0 1000 2000 or 3000 Redisplays last selected page of data Goes back fie pages of data Goes back one page of data Goes fonward five pages of data Goes fornnard one page of data Displays data in decimal format Displays data in hexformat 5 0 3 Pages 0 to 3000 5 Show Again Back 5 Pages T T P Previous Page Skip 5 Pages N Next Page T G E D Decimal Display H Hexadecimal Display vy remo EA Displays data in floating point format A ASCII Display Displays data in test format M Main Menu Goes up one level to main menu ProSoft Technology Inc Page 51 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Diagnostics and
92. t Description Info Sae o o a pe oee OSU Exchange Length 28 e osm m mmm 32 Missed Count s ox aH s aH um Refresh Error Count io i oem m mmm Reserved fa s ox m m m Command NAK PDU PDU Type 18 Command NAK Response The command NAK response may be sent by a responder to any command received on the command port that is in error Use of the command NAK allows the responder to give more precise and detailed information about the nature of the error to the requester The command NAK shall not be sent in response to a NAK message The NAK message is returned to indicate a syntactic error in a request message It should only be used if the request is unintelligible Thus whenever possible the corresponding response to a received request message shall be returned Packet Description Data Info UDP Source Port 7937 0x 1F01 Destination Port 7937 0x 1F01 Length xx bytes 0x 00 XX Checksum Xxxxx 0x XX XX Message Error String 36 XX Ox HH HH up to 80 characters Page 70 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module Read PDUs PDU Type 32 Read Request The read request PDU is used to request the contents of one or more contiguous groups of memory from a specific peer controller The header defines parameters
93. t modification Adding the Module to an Existing CompactLogix Project Important The MVI69 EGD module has a power supply distance rating of 2 L43 and L45 installations on first 2 slots of 1769 bus If you are installing and configuring the module with a CompactLogix processor follow these steps If you are using a MicroLogix processor refer to the next section ProSoft Technology Inc Page 37 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Ladder Logic GE Ethernet Global Data Communication Module 1 Add the MVI69 EGD module to the project Right click the mouse button on the I O Configuration option in the Controller Organization window to display a pop up menu Select the New Module option from the I O Configuration menu B Controller MVI69 2 Controller Tags Controller Fault Handler 3 Power Up Handler Tasks B fal MainTask El CS MainProgram 73 Unscheduled Programs Motion Groups 73 Ungrouped Axes Trends Data Types User Defined um Strings C Predefined Ce Module Defined J 1 0 Configuration 1 1769 L35E Ethernet Port LocalENB aa 1 id m Baa D 3 o ti i New Module B Cop e El Delete Cross Reference Ctrl4E Properties This action opens the following dialog box Select Module xi Module F Analog Communications Digital E Other 1769 MODULE Generic 1769 Modul
94. t respond to mouse movements or clicks The command executes as soon as you press the command letter you do not need to press Enter When you type a command letter a new screen will be displayed in your terminal application Using the Diagnostic Window in ProSoft Configuration Builder To connect to the module s Configuration Debug serial port 1 Start PCB program with the application file to be tested Right click over the module icon Default Project B a Default Location EH g Demo Module 2 On the shortcut menu choose Diagnostics Default Project B a Default Location s mm Delete Rename Copy Paste Choose Module Type Configure Verify View Configuration Write to Compact Flash Export Configuration File s Load Config File Add External File Download from PC to Device Upload from Device to PC Page 46 of 96 ProSoft Technology Inc November 3 2008 Diagnostics and Troubleshooting MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 3 This action opens the Diagnostics dialog box Press to display the Main Menu Time 11 58 39 MODULE MENU Display Menu B Block Transfer Statistics C Module Configuration D Database View R Transfer Configuration from PC to Unit S Transfer Configuration from Unit to PC U Reset diagnostic data V Version Information W Warm Boot Module Network Menu Esc Ex1t Program Com 1 w
95. tance 101 Input Size 62 Output Assembly Instance 100 Output Size 61 Configuration Assembly Instance 102 Configuration Size 0 Block Transfer Size 120 Field Recommended Value Type 1769 MODULE Generic 1769 Module Parent Local Name MVI69 Description MVI69 Application Module Comm Format Data INT Slot The slot number in the rack where the module is installed ProSoft Technology Inc November 3 2008 Page 39 of 96 MVI69 EGD CompactLogix or MicroLogix Platform Ladder Logic GE Ethernet Global Data Communication Module Block Transfer Size 120 Field Recommended Value Input Assembly Instance 101 Input Size 122 Output Assembly Instance 100 Output Size 121 Configuration Assembly Instance 102 Configuration Size 0 Block Transfer Size 240 Field Recommended Value Type 1769 MODULE Generic 1769 Module Parent Local Name MVI69 Description MVI69 Application Module Comm Format Data INT Slot The slot number in the rack where the module is installed Input Assembly Instance 101 Input Size 242 Output Assembly Instance 100 Output Size 241 Configuration Assembly Instance 102 Configuration Size 0 5 Click Next to continue Mi Module Properties Local 1 1769 MODULE 1 1 x General Connection Requested Packet Interval RPI J 2 0 zi ms a m Module Fault St
96. tarting register in the module where data will be transferred from the module to the processor Valid range for this parameter is 0 to 3999 2 2 2 Read Register Count Range 0 to 3999 This parameter specifies the number of registers to be transferred from the module to the processor Valid entry for this parameter is 0 to 3999 2 2 3 Write Register Start 0 to 3999 This parameter specifies the starting register in the module where the data will be transferred from the processor to the module 2 2 4 Write Register Count Range 0 to 3999 This parameter specifies the number of registers to be transferred from the module to the processor Valid entry for this parameter is 0 to 3999 2 2 5 Failure Flag Count 0 to 65535 This parameter specifies the number of successive transfer errors that must occur before the communication ports are shut down If the parameter is set to 0 the communication ports will continue to operate under all conditions The value range should be between 0 and 6900 2 2 6 Block Transfer Size 60 120 or 240 This read only parameter specifies the number of words in each block transferred between the module and processor Valid values for this parameter are 60 120 and 240 Page 26 of 96 ProSoft Technology Inc November 3 2008 Configuring the MVI69 EGD Module MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 2 3 S SNTP Client The SNTP CLIENT section of the CFG fil
97. ted with this product Specifications and the Functional Overview Support Service and Warranty Index Support Service and Warranty page 87 This section contains Support Service and Warranty information Index of chapters ProSoft Technology Inc November 3 2008 Page 7 of 96 MVI69 EGD CompactLogix or MicroLogix Platform Start Here GE Ethernet Global Data Communication Module Page 8 of 96 ProSoft Technology Inc November 3 2008 Start Here MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 1 Start Here In This Chapter System Requirements sssssssssssseeeneeneennneenene nennen 9 Package Contents sesssssssssseseeeeenee enne nennen nnns 10 Install ProSoft Configuration Builder Software 11 Setting Jumpers essessssesssseseeee eene neret nenne nnne nnne nens 12 Install the Module in the Rack see 13 Connect your PC to the Processor 16 Download the Sample Program to the Processor ssss 17 Connect your PC to the Module em 20 Installing the MVI69 EGD module requires a reasonable working knowledge of the Rockwell Automation hardware the MVI69 EGD Module and the application in which they will be used auos It is important that those responsibl
98. tion Review the new configuration using menu commands 6 and 0 to verify that the module is configured correctly Transferring the Configuration File from MVI69 module to PC Press S to receive download the configuration file from the module to your Press Y to confirm the file transfer and then follow the instructions on the terminal screen to complete the file transfer process After the file has been successfully downloaded you can open and edit the file to change the module s configuration Resetting diagnostic data Press U to reset the status counters for the client and or servers in the module Viewing Version Information Press V to view Version information for the module Use this command to view the current version of the software for the module as well as other important values You may be asked to provide this information when calling for technical support on the product Values at the bottom of the display are important in determining module operation The Program Scan Counter value is incremented each time a module s program cycle is complete Tip Repeat this command at one second intervals to determine the frequency of program execution Warm Booting the Module Caution Some of the commands available to you from this menu are designed for advanced debugging and system testing only and can cause the module to stop communicating with the processor or with other devices resulting in potential data loss or
99. tion Builder Software ssssseseeeess 11 1 4 Setting Julmpers ies sete ct teed et siecle E e dicet edt dinette 12 1 5 Install the Module in the Rack ssssssesssseseeeseeeneeen nennen nennen 13 1 6 Connect your PC to the Processor nnne 16 1 7 Download the Sample Program to the Processor 17 1 8 Connect your PC to the Module sees enne 20 2 Configuring the MVI69 EGD Module 21 2 1 ProSoft Configuration Builder sees 21 2 2 Mod le69 5 ite erro b te eG n d e REED aces 26 2 3 SNTP Glient ci to remp eee td rea Ete ani aera 27 24 EGD Exch ariges e o Eee Eee er e e P en te rr dp aa 28 2 5 EGD Multicast Group List 33 2 6 Ethernet Configuration sesssssssssssssees eene eene nennen nennen snnt ren 33 2 7 Download the Project to the Module een eme 34 3 Ladder Logic 37 3 1 Adding the Module to an Existing CompactLogix Project ssusss 37 3 2 Adding the Module to an Existing MicroLogix Project seeeeeeees 42 4 Diagnostics and Troubleshooting 45 4 1 Reading Status Data from the Module sese 45 4 2 LED Status IndiCators er hi eae teer e e iet ret den ip ee 57 5 Reference 59 5 1 Product Spechlications 3 i we bo ted nt d ie IR REM IE a ERR aloes 59 5 2 Functional Ove W E a a a a aaa T entente nnns snnt enne s nensi nnns intre
100. to confirm the file transfer and then follow the instructions on the terminal screen to complete the file transfer process Transferring WATTCP CFG to the PC Press S to transfer the WATTCP CFG file from the module to your PC Press Y to confirm the file transfer and then follow the instructions on the terminal screen to complete the file transfer process After the file has been successfully transferred you can open and edit the file to change the module s network configuration ProSoft Technology Inc Page 53 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Diagnostics and Troubleshooting GE Ethernet Global Data Communication Module Viewing the WATTCP CFG file on the module Press V to view the module s WATTCP CFG file Use this command to confirm the module s current network settings letwork Menu Selected ATTCP CFG FILE ProLinx Communication Gateways Inc Ht Default private class 3 address y ip 192 168 0 135 tt Default class 3 network mask etnask 255 255 255 8 it The gateway I wish to use kateuay 192 168 0 1 Parameters used by the ProLinx Communication Gateways Inc module Local Domain Name mycompany com iPassword PASSWORD Returning to the Main Menu Press M to return to the Main Menu 4 1 6 EGD Menu Press E to open the EGD Menu Use this command to view configuration and status for the EGD protocol ETHERNET GLOBAL DATA EGD MENU CzProducer Consumer List
101. to the CompactLogix or MicroLogix processor continuously with each read block 4 1 1 Required Hardware You can connect directly from your computer s serial port to the serial port on the module to view configuration information perform maintenance and send upload or receive download configuration files ProSoft Technology recommends the following minimum hardware to connect your computer to the module 80486 based processor Pentium preferred megabyte of memory At least one UART hardware based serial communications port available USB based virtual UART systems USB to serial port adapters often do not function reliably especially during binary file transfers such as when uploading downloading configuration files or module firmware upgrades Anull modem serial cable ProSoft Technology Inc Page 45 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Diagnostics and Troubleshooting GE Ethernet Global Data Communication Module 4 1 2 The Configuration Debug Menu The Configuration and Debug menu for this module is arranged as a tree structure with the Main Menu at the top of the tree and one or more sub menus for each menu command The first menu you see when you connect to the module is the Main menu Because this is a text based menu system you enter commands by typing the command letter from your computer keyboard in the diagnostic window in ProSoft Configuration Builder PCB The module does no
102. ule supports UDP of service port 7927 0x1F01 to handle all requests made of the module The module will only service the requests and generate response messages It will not generate command requests The module supports the following functions specified in the EGD protocol Code Description 3 Retrieve Configuration Request 4 Retrieve Configuration Response 7 Summary Request 8 Summary Response 9 Capabilities Request 10 Capabilities Response 15 Statistics Request 16 Statistics Response 18 Command NAK 32 Read Request 33 Read Response Page 60 of 96 ProSoft Technology Inc November 3 2008 Reference MVI69 EGD CompactLogix or MicroLogix Platform GE Ethernet Global Data Communication Module 5 2 Code Description 34 Write Request 35 Write Response 36 Masked Write Request 37 Masked Write Response The producer functionality provided in the EGD protocol is used to transfer portions of the module s database to other EGD nodes on the network The consumer functionality is used to transfer data from other nodes on the network into the module s database The EGD module generates produced data as defined in the user configuration exchange list from the module s internal database and is produced at the frequency defined in the exchange list This data can be broadcast to all nodes or to a specific node on the network The EGD module consumes data as defined in the user conf
103. ults Consumer Exchange IP address For consumed messages both Broadcast and Multicast type messages should be set to the IP address of the producer generating the specific exchange The combination of the IP address and the exchange ID uniquely identify the exchange to the system 2 4 8 Exch ID 1 to 16383 The Exch ID field defines the Exchange ID for this message and must be unique for each node For produced exchanges the module IP address and the entered exchange ID uniquely define the exchange to the network Defined consumer exchanges use the IP address in the message along with this exchange ID to determine which exchange to associate with the message The parameters defined in the exchange then determine how much data is present in the message and where to place it into the module s internal database 2 4 9 CS Major CS Minor This is an optional functionality that can be used to prevent unexpected results when changes are performed to existing producer and consumer exchanges The Configuration Signature consists of two one byte integer value CS Major and CS Minor The CS Major must be equal for both Producer and Consumer exchanges The CS Minor reflects backward compatible modifications made to an exchange for example adding registers to the producer exchange count Truncating data within an exchange is not backward compatible and requires a change in the major number ProSoft Technology Inc Page 31 of 96 November 3
104. vious Page of Data 55 56 Viewing the WATTCP CFG file on the module 54 Viewing Version Information 50 W Warm Boot 9998 or Cold Boot 9999 84 Warm Booting the Module 50 What Is Covered By This Warranty 90 92 What Is Not Covered By This Warranty 90 Write PDUs 62 73 Write Register Count 26 Write Register Start 26 Y Your Feedback Please 2 Page 96 of 96 ProSoft Technology Inc November 3 2008
105. y express or implied warranty of fitness for high risk activities 6 3 4 Intellectual Property Indemnity Buyer shall indemnify and hold harmless ProSoft and its employees from and against all liabilities losses claims costs and expenses including attorney s fees and expenses related to any claim investigation litigation or proceeding whether or not ProSoft is a party which arises or is alleged to arise from Buyer s acts or omissions under these Terms or in any way with respect to the Products Without limiting the foregoing Buyer at its own expense shall indemnify and hold harmless ProSoft and defend or settle any action brought against such Companies to the extent based on a claim that any Product made to Buyer specifications infringed intellectual property rights of another party ProSoft makes no warranty that the product is or will be delivered free of any person s claiming of patent trademark or similar infringement The Buyer assumes all risks including the risk of suit that the product or any use of the product will infringe existing or subsequently issued patents trademarks or copyrights ProSoft Technology Inc Page 91 of 96 November 3 2008 MVI69 EGD CompactLogix or MicroLogix Platform Support Service amp Warranty GE Ethernet Global Data Communication Module a Any documentation included with Product purchased from ProSoft is protected by copyright and may not be duplicated or reproduced in any form with
Download Pdf Manuals
Related Search
Related Contents
Kenwood KDC-3031G Car Stereo System User Manual AT91EB40A Evaluation Board - LSR-/ ITR-Wiki 安全データシート - 林純薬 – 電子材料 Datasheet - Mouser Electronics Rosewill RUC-6181 mobile device charger CT-DBT0x 3.5" SBC manuale di istruzioni De'Longhi Cordless Kettle Builloire User's Manual Prime-Line U 9484 Instructions / Assembly Scintisol ALX-2 Copyright © All rights reserved.