EP203 Automatic Extinguisher Panel User Manual & Log Book
Contents
1. Auto Manual EARTH FAULT ENABLED Enables or disables the panel s earth fault DISABLED monitoring MANUAL RELEASE MODE DELAYED The manual release of extinguishant is delayed IMMEDIATE or immediate Extinguishant delay remains active on automatic detection ADDITIONAL INFORMATION Any additional information the user needs to be aware of is detailed below THE INFORMATION ABOVE WAS COMPLETED BY Name OF Company ON Date Page 14 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL FIRE ALARM EXTINGUISHER PANEL LOG BOOK It is recommended that this log book be maintained by a responsible person who should ensure that every entry is properly recorded In the UK this is necessary to satisfy the recommendations of BS5839 1 compliance with which may be a requirement of legislation If your premises are certificated under the Fire Precautions Act 1971 failure to keep a suitable log book may be a breach of the requirements of the certificate which is a criminal offence In order to satisfy the requirements of BS5839 1 the following must be recorded Name of the responsible person Brief details of the maintenance arrangements Dates and times of all tests including fire drills Dates and times of all fires to which the system responds Dates and ti
2. vels 1 amp 2 Menus cccceceseseeceeeeseeseceeeeeeeaeeaeeaeeaesaeeaeeaeeaseaesaeeaeseaseaeeaeteeteatias 8 2008 No responsibility can be accepted by the manufacturer or distributors of this range of extinguisher panels for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole The manufacturer s policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice E amp OE Page 2 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL A IMPORTANT SAFETY NOTES The EP203 Automatic Extinguisher Panel hereafter called the EP203 panel is safe to operate provided it has been installed in compliance with the manufacturer s instructions and used in accordance with this manual Lethal voltages are present inside the panel DO NOT operate the EP203 panel with its enclosure open There is no need to open the enclosure except to carry out commissioning engineering or maintenance work This work must only be carried out by competent service personnel who are fully conversant with the contents of the separate installation manual for this product and have the necessary skills for maintaining this equipment If the enclosure is damaged in any way expert advice should be sought regarding its repair Regular servicing of the EP203 panel
3. and extinguishing system is highly recommended preferably on a continuous maintenance contract and by a competent organisation A full itemised report of the installation should be obtained atyleast annually Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 3 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL BASIC OVERVIEW AND KEY FEATURES The EP203 panel acts as both a conventional fire alarm panel and an automatic extinguisher control panel The EP203 panel s features include the following Time stamped event log Abort and hold functions for cancelling or delaying the extinguishant release sequence Front panel mounted LCD unit displays system status and facilitates system programming Front panel mounted extinguisher release button and two keyswitches one to enter access mode and one to toggle between automatic manual modes of operation Three zone conventional detector circuits line monitored for open and short circuit faults Any zone combination can be programmed to activate an alarm and initiate the extinguishant release sequence e Three conventional alarm sounder circuits two x 1st stage one x 2nd stage line monitored for open and short circuit faults Monitored inputs for Manual Release Flow Switch Low Pressure Mode Hold and Abort Auxiliary outputs for Fire Local Fire Extract 1st Stage 2nd Stage Fault e Extinguishing output supports up to 2 solenoid
4. menus P escape or accept options available in the panel s user menus Provides access to the Access Level 1 menu Silences the panel s internal sounder at anytime Resets the panel after the sounders have been silenced Access Level 2 only Silences or resounds the system s sounders Access Level 2 only Note This pushbutton will not silence 2nd stage alarm if the Pull down the flap and press both buttons to release the Keyswitch Controls accessed manual amp automatic S only Insert and turn the panel mounted keyswitch to the accessed position to enter Access Level 2 Authorised User level Turn and remove the keyswitch to exit Access Level 2 Insert and turn the panel mounted keyswitch to toggle the mode of the extinguishant system between Manual Only and Manual amp Automatic NOTE WHEN THE PANEL IS IN MANUAL MODE EXTINGUISHANT CANNOT BE RELEASED BY AUTOMATIC FIRE DETECTION MODE SELECT KEYSWITCHES ARE ALSO MOUNTED ON REMOTE STATUS UNITS RSU AND ECONOMY STATUS UNITS ESU AND OTHER DEVICES ANY ONE KEYSWITCH IN THE MANUAL POSITION TAKES CONTROL OF THE SYSTEM MODE Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 7 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL ACCESSING THE MENU CONTROLS Overview Two levels of menu controls are available on the EP203 panel Access Level 1 11 for General Users and Access Lev
5. sub menu if available Ur E Uwe od If applicable press the Scroll up and Scroll down W buttons to scroll the display through all active conditions faults disablements tests etc o Press the Escape 4 button to return to the previous menu 7 To exit Access Level 1 press the Escape button Note The panel will automatically exit Access Level 1 after approx 15 secs of inactivity To exit Access Level 2 turn the panel mounted keyswitch to the NOT accessed position Page 8 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL General User Controls Access Level 1 The functions that can be performed in Access Level 1 are Manually activate the extinguisher release Mute the internal sounder Also by pressing the Menu pushbutton the LCD unit displays the following menu Note All Access Level 1 menus are available to an Access Level 2 user MENU DESCRIPTION Displays all faults on the system Display Faults Displays all disablements on the system Displays all detection zones that are in test mode on system lluminates all front panel LED indicators Alarm Counter Displays the number of times fire alarm c ndition has occurred on the panel Note A Terminate Delay floating menu is also displayed for a level 1 user when there is an alarm on the system and a sounder delay is active
6. 2 select the Disp Contrast menu The panel s current LCD display contrast is displayed 2 Use the Scroll up A and Scroll down W buttons to adjust the contrast of the LCD unit 3 Press the Accept button to confirm the new setting and return to the Access Level 2 menu Disablements The Disablements menu allows the temporary disabling or enabling of the extinguishant system detection zones sounders monitored inputs relays and RSUs Typically used when there are input output faults and for system testing Any active disablements are displayed at the EP203 panelebysthe General Disablement and relevant disablement yellow LEDs lit steady Note It is recommended all disablements are immediately enabled when no longer required as they can have a major effect on how the system works Disable Exting This sub menu allows the disabling enabling of the extinguishant system 1 From the Disablements menu select the Disable Exting sub menu 2 Press the Accept button to disable enable the extinguishant system 3 Press the Escape 4 button to return to the Disablements menu Note Exting System Disabled will also be displayed at any Remote Status Units RSUs connected on the system Disable Zone This sub menu allows the disabling enabling of one or more of the panel s three detection zones Disabled zones do not report fire or fault conditions 1 From the Disablements menu select the Disable Zone sub menu 2 Sele
7. EP203 AUTOMATIC EXTINGUISHER PANEL User Manual and Log Book Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL CONTENTS IMPORTANT SAFETY NOTES i 7 iue dee E ERE NER 4E RE PERRR EE eats 3 BASIC OVERVIEW AND KEY 4 CONTROLS amp INDICATORS ERE ERE ERE 5 5 LED EL T REM 5 Pushbuttolti Controls eet eigener pentes irt e Ne 7 Keyswitch Controls ideni ade E ra MR DE e SES Y gi eR DER METRE 7 ACCESSING THE MENU 60 05 nenne 8 TOW SIV NOW e 8 Selecting the Menus and 06 8 General 9 Authorised User Controls Access Level 2 nennen nennen 10 SYSTEM SET UP DATA CHART orit E oiii ooi o trai E ERE RR AIRE Pasa TE 14 FIRE ALARM EXTINGUISHER PANEL LOG BOOK 15 INSTALLATION CERTIFICATE E REE P GE ERA 20 COMMISSIONING CERTIFICATE 3 nnnm 21 FIGURES Figure 1 Front Panel Controls and Indicators eesssssssssssseeeeeesene ennt tnnt tnnt tnnt 5 Figure 2 Overview of Access L
8. INGUISHER PANEL Lamp Test All LED indicators can be tested at anytime by selecting using this menu 1 In Access Level 1 select the Lamp Test menu All the panel s LEDs will illuminate steady for approx 2 secs The panel s internal sounder will also sound If any LEDs fail to illuminate report the fault to the designated site engineer and make a note in the Log Book 2 On completion the display returns to the Access Level 1 menu Alarm Counter 1 In Access Level 1 select the Alarm Counter menu The total number of times the panel has been in a fire alarm condition is displayed 2 Press the Escape 4 button to return to the Access Level 1 menu Authorised User Controls Access Level 2 The functions that can be performed in Access Level 2 by turning the panel mounted keyswitch to the accessed position are e Manually activate the extinguisher release Mute the internal sounder e Silence the alarm sounders e Resound the alarm sounders Reset an alarm condition Also the LCD unit displays the following menu MENU DESCRIPTION Display Faults See Access Level 1 See Access Level 1 Displays the number of times a fire alarm condition has Adjusts the panel s date amp time settings Event Log Displays the panel s event log Disp Contrast Adjusts the contrast of the LCD unit Disables enables the extinguishant system Disable Exting Disablements Disable Zo
9. Selecting this menu activates the fire sounders immediately Display Faults 1 In Access Level 1 select the Display Faults menu The panel displays all active faults on the system e g Zone 1 O C Fault Zone 2 S C Fault etc 2 Scroll the display through all active faults using the Scroll up and Scroll down Y buttons 3 Press the Escape 4 button to return to the Access Level 1 menu Display Dis mnt The Display Disablements menu displays all active disablements on the system An Access Level 2 user sets disablements 1 In Access Level 1 select the Display Dis mnt menu The panel displays all active disablements on the system e g Zone 1 disabled etc 2 Scroll the display through all active disablements using the Scroll up A and Scroll down W buttons 3 Press thesEscape 4 button to return to the Access Level 1 menu Zones in Test This menu displays all detection zones that are currently in test mode on the system A system engineer can only put zones into test mode 1 In Access Level 1 select the Zones in Test menu The panel displays all zones currently in test on the system e g Zone 1 is on Test etc 2 Scroll the display through all active zones in test using the Scroll up A and Scroll down W buttons 3 Press the Escape 4 button to return to the Access Level 1 menu Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 9 of 21 EP203 AUTOMATIC EXT
10. TURE WHERE APPLICABLE WHERE APPL ICABLE REQUIRED Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 19 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL INSTALLATION CERTIFICATE BS5839 1 recommends that certificates be issued for all aspects of the fire alarm extinguisher system including design installation commissioning acceptance verification optional and maintenance Therefore before this user manual is handed over the following installation certificate and the commissioning certificate overleaf should be completed as appropriate by the relevant installation commissioning engineer s Please ensure that the system set up data chart and the relevant parts of the system Log Book are also completed as appropriate For countries outside the UK different certification requirements may apply Certificate of INSTALLATION for the fire alarm extinguisher system at Address I we being the competent person s responsible as indicated by my our signatures below for the installation of the fire alarm extinguisher system particulars of which are set out below CERTIFY that the said installation for which I we have been responsible complies to the best of my our knowledge and belief with the specification described below and with the recommendations of Section 4 of BS5839 1 except for the variations if a
11. ablements menu Disable Relay This sub menu allows the disabling enabling of one or more of the panel s six auxiliary relay outputs Fire Local Fire Extract 1st Stage 2nd Stage and Fault Note If an Output Expansion Relay Board is fitted this sub menu also allows the disabling enabling of one or more of the card s five relay outputs Reset Mode Discharged Hold and Abort 1 From the Disablements menu select Disable Relay 2 Select the relay output s to be disabled enabled using the Scroll up and Scroll down buttons Press the Accept button to disable enable the selected relay output 4 Press the Escape 4 button to return to the Disablements menu Disable RSU This sub menu allows the disabling enabling of one or more of the panel s Remote Status Units 1 From the Disablements menu select Disable RSU 2 Select the RSU s to be disabled enabled using the Scroll up and Scroll down Y buttons Press the Accept button The panel requests confirmation Scroll down W to confirm the change Press the Accept button to disable enable the selected RSU The Disablements menu is displayed Note RSU Disabled will be displayed at the RSU that has been disabled Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 13 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL SYSTEM SET UP DATA CHART Important This chart should be completed by an authorised eng
12. ault ZONE DEVICE ACTION REQUIRED COMPLETED INITIALS Page 16 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL DATE TIME EVENT e g test fire alarm signal fault ZONE DEVICE ACTION REQUIRED COMPLETED INITIALS Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 17 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL DATE TIME EVENT e g test fire alarm signal fault ZONE DEVICE ACTION REQUIRED COMPLETED INITIALS Page 18 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 False Alarms EP203 AUTOMATIC EXTINGUISHER PANEL BRIEF CIRCUMSTANCES ON DEVICE THAT CAUSE WHERE CAUSE IS AINTENA FINDINGS OF CATEGORY FURTHER DONE DATE TIME ZONE TRIGGERED EIE C RECORD VISIT REQUIRED MAINTENANCE OF FALSE ACTION PLEASE ALARM SIGNAL IF KNOWN activities IN THE YES OR NO TECHNICIAN ALARMS REQUIRED TICK AREA Maintenance Work ZONE DEVICE DATE TIME REASONS FOR WORK WORK CARRIED FURTHER WORK SIGNA
13. ct the detection zone s to be disabled enabled using the Scroll up A and Scroll down W buttons Press the Accept gt button to disable enable a selected zone Press the Escape 4 button to return to the Disablements menu Disable Sounder This sub menu allows the disabling enabling of the fire sounders from sounding in a fire condition 1 From the Disablements menu select Disable Sounder 2 Press the Accept button to disable enable the sounder circuit 3 Press the Escape 4 button to return to the Disablements menu Page 12 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL Disable SndrDel The sounder delay sub menu allows the disabling enabling of a fire sounder delay in a fire condition 1 From the Disablements menu select Disable SndrDel 2 Press the Accept button to disable enable the delay on the sounder circuit 3 Press the Escape 4 button to return to the Disablements menu Disable Input This sub menu allows the disabling enabling of one or more of the panel s six monitored inputs Manual Release Flow Switch Low Pressure Mode Hold and Abort 1 From the Disablements menu select Disable Input 2 Select the input s to be disabled enabled using the Scroll up and Scroll down Y buttons Press the Accept button to disable enable the selected input Press the Escape 4 button to return to the Dis
14. el 2 AL2 for Authorised Users All menus are displayed at the LCD unit as detailed in Figure 2 below Note When selected menus and sub menus change from Title Case to UPPERCASE Floating menu Displayed when menu button i sounder delay is active amp alarm pr sent Display Faults Display Dismnt Zones in Test Lamp Test Alarm Counter AL1 Menu gt Floating megis Displayed at the end of floGdind prior to reset subject to Extract Option fitted accessed keyswitch St rt Extract US Loruossssesessezese b eese amp i pstOptxtract M db Display Faults Display Dismnt Zones in Test R Tet Alarm Counter amp Te Clear to todays date AL2 Menu Alarm Counter sns Set Time Date Event Log Disp Contrast Disablements Po Disable Exting i i i 1 i Show Log Log Reset Disable Zone Disable Sounder Disable SndrDel Disable Input Disable Relay Disable RSU Figure 2 Overview of Access Levels 1 amp 2 Menus Selecting the Menus and Sub Menus 1 To enter Access Level 1 menu press the Menu pushbutton or to enter Access Level 2 menu turn the panel mounted keyswitch to the accessed position Press the Scroll up A and Scroll down W buttons to highlight a menu Press the Accept lt button to select 8 menu Press the Accept lt button to select a
15. en sounder to silence resound sounders press w to exit from access mode zone fouitidisabie test 7 disablement C IERI tum amp remove key fault condition flashing light 7 2 x E ag irc MS ex ux EUN call the Engineer output output C TEC XS Manufactured in mowa monu lt gecesed 7 gener system delays sounder flooding low England by ony amp present fout fault zone pressure EP SERIES EN 12094 1 2003 Class A only automatic fout toutt fault Figure 1 Front Panel Controls and Indicators LCD Unit This unit provides system status information counts down the time for extinguishant release and displays Access Levels 1 amp 2 menus and sub menus LED Indicators The LED indicators on the front of the panel give a comprehensive overview of the system s current status Any fire and fault conditions are clearly displayed disablements highlighted and the status of all inputs and outputs displayed The table below summarises the various indicators and what they mean in their various states INDICATOR STATUS DESCRIPTION general fire 0 fire zones Flashing Red The panel has detected a fire alarm condition on a fire 1 2 3 A hold input has been received at the panel First stage extinguishant output has been activated Countdown timer to extinguishant release has started A flow switch input from a flow switch on the e
16. ineer prior to system handover Complete the appropriate setting box MODE DISABLED Manual Only FUNCTION SETTING DESCRIPTION ZONE SELECTION The zone Z1 Z2 Z3 combination that starts the extinguishant release sequence EXTINGUISHANT DELAY secs The countdown duration before the extinguishant is released Adjustable between 0 60 seconds EXTINGUISHANT esee secs The duration of the firing signal to the DURATION extinguishant output Adjustable between 1 300 seconds FLOODING TIME J secs The duration for release of extinguishant Adjustable between 60 1740 seconds EXTRACT OPTION FITTED eiue Selects whether a ventilation extract fan is fitted NOT FITTED or fot EXTRACT TIME jJ easeseeeee secs The duration for the ventilation extract fan operation Adjustable between 1 900 seconds FLOW OPTION FITTED Selects whether a flow switch is fitted or not NOT FITTED SOUNDER DELAY secs The time delay before the fire sounders operate Adjustable between 0 600 seconds EXT OUTPUT EOLS 1 x EOL A O The number of extinguisher System Line 2xEOL P Terminators Set at either 1 or 2 MODE EXCEPTIONS MODE FAULT Manual Only The default setting when the mode input is in Auto Manual Fault and or Disabled Set at either Manual Only or Auto Manual mode
17. ircuit fault on the low pressure switch input Extinguishant release output has been disabled Indicates all panel sounders are disabled The panel is supplied with power back up batteries accessed position and the panel is in Access Level 2 authorised user level The panel has detected a microprocessor fault Delays have been programmed into the panel A delay is currently running Faulty wiring short or open circuit has been detected on The alarm sounders have been disabled Indicates a short or open circuit on extinguishant output Page 6 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL Pushbutton Controls PUSHBUTTON DESCRIPTION scroll up A scroll down V Dependent on the status of the panel these pushbuttons scroll vertically through any fire pre alarm or fault escape 4 accept gt K extinguishant is about to be released EXTINGUISHER RELEASE CAUTION THESE PUSHBUTTONS MANUALLY RELEASE pushbuttons in yellow housing THE EXTINGUISHANT 4 EXTINGUISHER RELEASE gt i extinguishant PULL DOWN and PUSH BUTTONS i conditions that appear on the panel s LCD unit scroll vertically through the panel s user menus manipulate date time disablement settings etc i Dependent on the status of the panel these pushbuttons scroll horizontally through the panel s user
18. is displayed 2 Use the Scroll up A and Scroll down V buttons to adjust the hour the panel has a 24 hour clock 3 When the correct hour is displayed press the Accept gt button to move to the minutes field 4 Use the Scroll up A and Scroll down V buttons to adjust the minutes When the correct time is displayed press the Accept button to alter the date 6 Use the Scroll up A Scroll down and Accept gt buttons to set the day month year as appropriate 7 When correct press the Escape 4 button to return to the Access Level 2 menu Event Log 1 In Access Level 2 select the Event Log menu select Show Log sub menu The panel s last event log is displayed 2 Use the Scroll up A and Scroll down W buttons to view the previously saved events When the l g is full the newest record replaces the oldest record Events are listed in chronological order Press the Escape 4 button to return to the previous menu 4 Toreset the panel s event log in Access Level 2 select the Event Log menu then select Log Reset sub menu The panel requests confirmation to erase the event log 5 Press the Accept button to confirm and the event log is cleared from the panel s memory 6 Press the Escape 4 button to return to the previous menu Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 11 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL Disp Contrast 1 In Access Level
19. mes of all false alarms Causes circumstances surrounding and category of false alarms if known The identity of any fire detector that triggers any of the above fire alarm extinguisher signals if known Dates times and type of all faults and defects C Dates and times of all maintenance e g service visit or non routine attention USER SITE ADDRESS RESPONSIBLE PERSON S ON SITE THE SYSTEM WAS DESIGNED BY THE SYSTEM WAS INSTALLED BY THE SYSTEM WAS COMMISSIONED BY THE SYSTEM WAS ACCEPTED BY VERIFICATION WAS UNDERTAKEN BY FOR SERVICE DETAILS OF WHO YOU SHOULD CONTACT IF MAINTENANCE IS REQUIRED THE SYSTEM IS MAINTAINED UNDER CONTRACT BY Company Address Contact No Expiry Date NORMAL HOURS MON FRI TEL OUTSIDE NORMAL HOURS TEL MANNED CENTRE TEL MANNED CENTRE CODE NORMAL MAXIMUM ATTENDANCE TIME FOR A MAINTENANCE TECHNICIAN IS EXPENDABLE COMPONENT REPLACEMENT PERIODS LIST Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 15 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL Details of tests including fire drills actual fire alarms disablements enablements and faults should be recorded here False alarms and maintenance work should be recorded on page 20 DATE TIME EVENT e g test fire alarm signal f
20. n 3 of BS 5839 1 I we have not identified any obvious potential for an unacceptable rate of false alarms The documentation described in Clause 40 of BS5839 1 has been provided to the user The following work should be completed before after delete as applicable the system becomes operational The following potential cause s of false alarms should be considered at time of next service visit Before the system becomes operational it should be soak tested in accordance with the recommendations of 35 2 6 of BS5839 1 for a period of enter a period of either one week such period as required by the specification or such period as recommended by the signatory of this certificate whichever is the greatest or delete if not applicable Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 21 of 21
21. ne Disables enables detection zones Disable Sounder Disables enables fire sounders Disable Sndrdel Disables enables fire sounder delay Disables enables monitored inputs Disable Input Disables enables auxiliary relay outputs Disable Relay Disable RSU Disables enables Remote Status Units Page 10 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL Note Two floating menus Start Extract amp Stop Extract are also displayed for a level 2 user when the Extract Option is selected as fitted by an engineer These menus appear at the end of the flooding period prior to reset and start or stop the ventilation extract fan respectively Alarm Counter 1 In Access Level 2 select the Alarm Counter menu The total number of times the panel has been in a fire alarm condition since last reset is displayed Press the Escape 4 button to return to the Access Level 2 menu or to clear the alarm counter press the Accept gt button The panel requests confirmation to clear to todays date Press the Accept gt button to reset the counter The panel will start counting new fire conditions from the current date A confirmation message confirms the change has been made and the display returns to the Access Level 2 menu Set Time Date 1 In Access Level 2 select the Set Time Date menu The panel s current time setting
22. ny stated in this certificate Name in block letters Position in block letters Signature Date For and on behalf of Address amp postcode The extent of the liability of the signatory isdimited to the system described below Extent of installation work covered by this certificate Specification against which the system was installed Variations from the specification and or Section 4 of BS5839 1 see BS5839 1 Clause 7 Wiring has been tested in accordance with the recommendations of Clause 38 of BS5839 1 Test results have been recorded and provided to Unless supplied by others the as fitted drawings have been supplied to the person responsible for commissioning the system see 42 2 of BS5839 1 Page 20 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL COMMISSIONING CERTIFICATE BS5839 1 recommends that certificates be issued for all aspects of the fire alarm extinguisher system including design installation commissioning acceptance verification optional and maintenance Therefore before this user manual is handed over the following commissioning certificate and the installation certificate overleaf should be completed as appropriate by the relevant installation commissioning engineer s Please ensure that the system set up data chart and the relevant pa
23. rts of the Log Book are also completed as appropriate For countries outside the UK different certification requirements may apply Certificate of COMMISSIONING for the fire alarm extinguisher system at Address I we being the competent person s responsible as indicated by my our signatures below for the commissioning of the fire alarm extinguisher system particulars of which are set out below CERTIFY that the said work for which I we have been responsible complies to the best of my our knowledge and belief with the specification described below and with the recommendations of Clause 39 of BS5839 1 except for the variations if any stated in this certificate Name in block letters Position in block letters Signature Date For and on behalf of Address amp postcode The extent of the liability of the signatory is limited to the system described below Extent of system covered by this certificate Variations from the recommendations of Clause 39 of BS5839 1 see BS5839 1 Clause 7 All equipment operates correctly Installation work is as far as can reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the recommendations of 39 2c of BS5839 1 The system performs as required by the specification prepared by a copy of which I we have been given Taking into accountthe guidance contained in Sectio
24. s or multiple Metrons Adjustable extinguishant release time delay duration and flooding time Alarm counter to record the n mber of times the panel has been in an alarm state e Optional Output Expansion Relay Board providing additional relay outputs for Reset Mode Discharged Hold and Abort Connections for up to eight Remote Status Units RSU which provide remote indication of system status on an LCD unit with mode select and manual extinguisher release e Connections for up to eight Economy Status Units ESU to provide remote indication of system status with mode select e Pushbutton and keyswitch entry to two access levels displayed on the LCD unit Access Lev l 1 AL1 is for general users Access Level 2 AL2 is for authorised users Page 4 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL CONTROLS amp INDICATORS The front of the EP203 panel has various LED indicators pushbuttons keyswitches and an LCD unit as shown in Figure 1 below scroll Extinguisher Control Panel Instructions e Aam condition EVACUATE escape o accept EXTINGUISHER RELEASE 0 PULL DOWN and PUSH BUTTONS To silence the Intemal sounder press F7 To enter access mode nS zones first release extinguishant insert amp tum key accessed menu slenco niemal 1 2 3 ineo edente epe th
25. xtinguishant cylinder is received at the panel An abort input has been received at the panel Part of the system has been manually disabled and or one or more of the fire zones has a delay applied to them zone fault disable test Faulty wiring or detector removed from base detected on the zones flashing The zones lit steady have been disabled 1 2 3 The zones flashing are in test mode Approved Document No DFU0002031 Rev 3 EP203 AUTOMATIC EXTINGUISHER PANEL USER MANUAL Page 5 of 21 EP203 AUTOMATIC EXTINGUISHER PANEL INDICATOR STATUS DESCRIPTION extinguishant release disablement manual release disablement first stage output disablement second stage output disablement sounder fault flooding zone fault low pressure fault Steady Yellow Flashing Yellow Flashing Yellow Manual release facility has been disabled First stage contact has been disabled Second stage contact has been disabled Indicates the status of the extinguishant system is Manual Only mode Indicates the status of the extinguishant system is Manual 8 Automatic mode The panel has detected a fault with its power supply or The panel mounted keyswitch has been turned to the i the panel s sounder circuits Indicates there is low pressure in the extinguishant system or there is a short open c