INSTALLATION AND SETUP GUIDE CE
Contents
1. s cover and verify on the keypad that only the zones you designated for this 4209U are indicating a check or trouble condition Ionization duct detector w System Sensor 1451DH DH400 base Photoelectric direct wire System Sensor 2100 Photoelectric w heat sensor System Sensor 2100T direct wire Photoelectric W B110LP base System Sensor 2151 Photoelectric direct wire System Sensor 2400 Photoelectric w heat sensor System Sensor 2400 direct wire Photoelectric w B401B base System Sensor 2451 and B401B base DH400 base Table 3 Compatible 2 Wire Smoke Detectors Current Draw All zones shorted Input Voltage 11 14VDC oe ee EE o o From Polling From Switched Loop Power 15 5mA 110mA Table 4 Current Draw Calculations SPECIFICATIONS Sensor Loop Response Physical 400 msec all loops Sensor Loop Current switched power input of Width 6 7 167 163mm Height 4 1 4 108mm 12VDC Deve 1 1 4 32mm 7 7mA normal Electrical 25mA shorted Polling loop input 6 7 14 Sensor _ Loop Max VDC Resistance Switched Power Input 10 2 to 14VDC Current draw 15 5mA max from polling loop 110mA max from switched power source see Table 4 Up to 100 ohms of wire resistance 2k KOLR LIMITED WARRANTY Honeywell International Inc 165 Eileen Way Syosset New York 11791 warrants its product s to be in conformance with its own plans and specifications and to be free from d
2. DIP Switch Polling Loop Device DP where applicable THIS SWITCH SETTING PRESETS THE LOOPS TO THESE ZONE NUMBERS DIP Switch Position Loop Number Pe Meals oN GROUPED 2 3 4 5 6 LoopA LoopB LoopC LoopD Loop A amp B Loop C amp D ee Onin One sOrve smi see ae se sa fs a a kk On ojoj 9 0 n 12 9 J 10 Onjo 17 18 19 2 17 18 On On 2 2 2 28 235 26 On On On 33 34 35 36 33 34 e a ea JOquNnN uoz Do not select 1 4 for VISTA controls Tf 9 12 is selected for controls that have 9 hardwire zones First Loop Zone 9 will be inactive 4209U also accommodates option ONE 4208 IN USE if referred to in control programming NOTE Consult the Control Panel Instructions to determine the valid zone numbers for that control panel Table 1 4209U Zone Number Assignments For Serial Number mode DIP Switch position 6 must be on THIS SWITCH SETTING PRESETS THE LOOP TO THESE SERIAL NUMBERS a Loop Serial Number Pie Switch Roron Each serial number in the selected group can be assigned to any zone number ees 6 LOOPA LOOPB LOOPC LOOPD LOOPA amp B LOOP C amp D ON 034 9524 034 9525 034 9526 034 9527 034 9524 034 9525 O O O O Z O O O O O 090 8756 090 8757 090 8758 090 8759 090 8756 090 8757 097 8660 097 8661 097 8662 097 8663 097 8660 097 8661 104 85
3. 64 104 8565 104 8566 104 8567 104 8564 104 8565 Table 2 4209U Serial Number Assignments 2 O ON ee ON oe l ON see ONE ae eee re ON poe SON pee el ON fra ON ee ee Set the DIP switches on the 4209U as instructed below 1 Select grouped or non grouped mode using DIP Switch 1 Grouped ON Non grouped OFF 2 Select mode of operation serial number or zone assignment mode using DIP Switch 6 Serial Number mode ON Zone Assignment mode OFF 3 Select the group setting using DIP Switches 2 3 4 and 5 See Table 1 for zone assignments or Table 2 for serial number assignments If using more than one 4209U be sure to set each one to a different group setting DIP Switch 7 Not used set to OFF Select the 4209U Tamper Protection setting using DIP Switch 8 Tamper Disabled ON Tamper Enabled OFF Tamper will report for every active zone on the 4209U module PROGRAMMING All zones assigned to the 4209U must be programmed as Fire zones zone type 09 or 16 When setting the 4209U to a group of zone numbers each zone must be programmed as follows On 4140XMP and earlier controls these zones must be programmed as Left Loop Polling Loop Zones e On VISTA 40 and later controls these zones must be programmed in the 93 Menu Mode Zone Programming as INPUT TYPE 7 DP DIP Switch type polling device When setting the 4209U to a group of seri
4. Honeywell N8281V1 5 01 Rev B 4209U Universal Group Zoning Multiplex Module INSTALLATION AND SETUP GUIDE FEATURES The ADEMCO 4209U Group Zoning Multiplex Module is a 4 zone expander that allows use of available expansion zones provided by ADEMCO controls that support polling loop devices Its primary purpose is to provide additional 2 wire smoke detector loops to the control Other devices may be used but all zones must be programmed for a fire response type Characteristics of this device include e Uniquely identifies 4 supervised zones or 2 supervised zones in the grouped mode groups two supervised zones together into one zone e Supports up to 16 2 wire smoke detectors on each of its 4 loops regardless of group setting DIP Switches can be used to set zone numbers or serial numbers e When used in the serial number mode each serial number in the selected group can be assigned to any zone number e Tamper protected MOUNTING Power should be disconnected before proceeding Be sure to mount the 4209U before making any wire connections When mounted remotely tamper protection is required Holes on the back of the module s housing permit it to be mounted horizontally or vertically Wires can exit from the side or the breakout on the back of its housing To enable tamper protection set DIP Switch 8 to OFF and attach the tamper magnet provided Figure 1 to the module inside cover Be sure to e
5. al numbers each zone must be programmed as INPUT TYPE 6 SL Serial Number Polling Loop Device Loops can be learned in any order and assigned to any legitimate zone number When prompted to learn the serial number for a particular zone you may either enter it manually through the keypad or through V Link or learn it by momentarily faulting shorting the terminals of that zone as required by the control If entering a serial number manually through the keypad enter it and press to advance to the next prompt Make sure you also enter the loop number of the device you are using for that zone see the control s instructions for more details about learning serial numbers If learning or entering a serial number and the message Duplicate of Zone XX is displayed another device with that same serial number is already in the system In that case use a different serial number group setting on the 4209U If learning a serial number by faulting its associated loop make sure that other polling loop devices are not activated as they may interfere with the device being learned VERIFICATION OF PROGRAMMING To verify proper programming the following test should be performed 1 Be sure to enable expansion zone tamper protection at the control program field 24 0 2 Set DIP Switch 8 to OFF tamper enabled 3 Replace the 4209U cover and clear the keypad of any faulted zones 4 Remove the 4209U
6. e U S Government Printing Office Washington DC 20402 The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or Users Manual Unauthorized changes or modifications could void the user s authority to operate the equipment SEE THE CONTROL PANEL S INSTALLATION INSTRUCTIONS FOR COMPLETE INFORMATION REGARDING THE LIMITATIONS OF THE ENTIRE SECURITY SYSTEM Honeywell 165 Eileen Way Syosset NY 11791 Copyright 2004 Honeywell International Inc www honeywell com security N8281V1 5 01 Rev B
7. efects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product s or for product s not having a date stamp for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period in which case the shorter period shall apply Seller s obligation shall be limited to repairing or replacing at its option free of charge for materials or labor any product s which is proved not in compliance with Seller s specifications or proves defective in materials or workmanship under normal use and service Seller shall have no obligation under this Limited Warranty or otherwise if the product s is altered or improperly repaired or serviced by anyone other than Honeywell factory service For warranty service return product s transportation prepaid to Honeywell Factory Service 165 Eileen Way Syosset New York 11791 THERE ARE NO WARRANTIES EXPRESS OR IMPLIED OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Seller does not represent that the product s it sells may not be compromised or circumvented that the p
8. moving the knockouts Use 22 gauge twisted pair wire for polling loop connections All protection loops use 2k EOL resistors included A maximum resistance of 100 ohms is allowed on protection loops excluding EOLR See Figure 2 for all connections Keep in mind that even in the grouped mode each set of terminals must have its own 2k EOLR and it must be connected across the loop wires at the last detector Power Connections must be made so that power to the smoke detectors can be momentarily interrupted to clear the alarm This can be done either via the control s auxiliary relay Gif supported or through a relay on a 4204 relay module Wire the common of the relay to 12VDC and the N C contact on the 4209U TB2 terminal 3 The relay you use must be programmed for Smoke Protector Reset see control panel s instructions When you reset an alarm at the keypad the relay arm will swing momentarily to the N O contact causing an interruption of power DIP SWITCH SETTINGS ZONE ASSIGNMENT MODE In the zone assignment mode the DIP Switches on the 4209U are used to assign the unit to a group of 4 consecutive zones in the non grouped mode or 2 consecutive zones in the grouped mode These zone numbers once designated for the 4209U cannot be used for anything else even if you don t use them all Follow the steps below using Table 1 for DIP Switch settings Serial Number Mode In the serial number mode the DIP S
9. nable the expansion zone tamper option at the control program field 24 0 When the installation is complete install the cover and affix the Serial Number and Zone Assignment Tables to the inside cover of the control If the modules cover is removed the magnet attached to the cover positioned near the reed switch will cause a tamper signal to be sent to the control for every active zone on the 4209U module amp es d POE v SS J 1 INSERT BOTTOM TABS FIRST ae 2 ENGAGE TOP WITH CLIP Figure 1 Tamper Magnet Installation For all fire alarm NFPA certified installations the 4209U must be tamper protected or mounted in a tamper protected cabinet When the module is to be mounted inside the control s cabinet tamper protection is not required if the cabinet is supervised Insert self tapping screws provided in two adjacent raised tabs at the back of the cabinet leaving the heads projecting 1 8 Hang the module on the screw heads via the two slotted holes on the back of the module s housing When the installation is complete install the cover and affix the Serial Number and Zone Assignment Tables to the inside cover of the control WIRING For CE installations ADEMCO N6361 EMI suppression bead is required Refer to the N6361 installation guide for wire routing instructions Polling loop and protection loop wires can be brought in either through the back or front of the unit by re
10. nd if not installed and used properly that is in strict accordance with the manufacture s instructions may cause interference to radio and television reception It has been type tested and found to comply with the limits for Class B computing device in accordance with the specifications in Part 15 of FCC Rules which are designed to provide reasonable protection against such interference in a residential installation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures If using an indoor antenna have a quality outdoor antenna installed Reorient the receiving antenna until interference is reduced or eliminated Move the radio or television receiver away from the receiver control Move the antenna leads away from any wire runs to the receiver control Plug the receiver control into a different outlet so that it and the radio or television receiver are on different branch circuits If necessary the user should consult the dealer or an experienced radio television technician for additional suggestions The user or master may find the following booklet prepared by the Federal Communications Commission helpful Interference Handbook This booklet is available from th
11. roduct s will prevent any personal injury or property loss by burglary robbery fire or otherwise or that the product s will in all cases provide adequate warning or protection Customer understands that a properly installed and maintained alarm system may only reduce the risk of a burglary robbery fire or other events occurring without providing an alarm but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property loss as a result CONSEQUENTLY SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THAT THE PRODUCT S FAILED TO GIVE WARNING HOWEVER IF SELLER IS HELD LIABLE WHETHER DIRECTLY OR INDIRECTLY FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE REGARDLESS OF CAUSE OR ORIGIN SELLER S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT S WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER This warranty replaces any previous warranties and is the only warranty made by Seller on this product s No increase or alteration written or verbal of the obligations of this Limited Warranty is authorized FEDERAL COMMUNICATIONS COMMISSION FCC Part 15 STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use The FCC requires the following statement for your information This equipment generates and uses radio frequency energy a
12. witches on the 4209U are used to assign the unit to a group of 4 serial numbers or 2 serial numbers in the grouped mode You can assign any serial number to any zone number except hardwire zone numbers on the control and you do not lose zone numbers if you don t use all 4 loops on the 4209U Follow the steps below using Table 2 for DIP Switch settings 4209U ON POSITION 1 SELECT GROUP MODE s a SHOWN OFF NON GROUPED h y POSITIONS 2 5 SELECT THE 2 GROUPED OR TB2 4 NON GROUPED SENSOR a DEVICE GROUP ADDRESS ia A SHOWN ON ON ON GND f y a OFF 2nd GROUP SELECTION abe SWITCHED n POSITION 6 Davee TYPE SHONN sabe BOWER CE Bee LON POSITION 7 NOT USED SET TO OFF VIA CONTROL POSITION 8 SELECT TAMPER PROTECTION PANEL S AUXILIARY SETTING RELAY OR 4204 SIDEVIEW SHOWN OFF TAMPER ENABLED RELAY MODULE TO REED TAMPER SWITCH POLLING A LOOP TB1 USE TWISTED PAIR FOR CE INSTALLATIONS A N6361 EMI SUPPRESSION BEAD IS REQUIRED O e O A B THE EOL RESISTOR MUST koon a i Ko BE CONNECTED ACROSS Kors i Kons O axa i Loy THE LOOP WIRES AT THE A x Sa x lt UPTO 16 2 WIRE LAST DETECTOR aoe SMOKE DETECTORS 2kEOLR 2kEOLR 2kEOLR 2kEOLR MAX OF 100 ohms WIRING RESISTANCE AND 2k EOLR 4209U SOC VO Figure 2 Summary of Connections For Zone Assignment mode DIP Switch position 6 must be off When using this mode program each zone s Input Type as
Download Pdf Manuals
Related Search
Related Contents
User manual for the EDS III basic embroidery design software V640 Series CIDRW System User`s Manual 11 Mars 2014 - OMEDIT Poitou CubeSuite+ V1.00.00 Integrated Development Environment User`s Bluestork BS-220-4USB-PBL mobile device charger Magnavox 15MF400T/37 Series Flat Panel Television User Manual UPR - TRACT - SORTIE DE L`EURO Nokia 6680 - Microsoft テルモロッシ H2O-25/COMPACT Copyright © All rights reserved.