1. Curtain 6CH Actuator All Interface and the functions Apply parameters please overview the following description of the paragraph Each channel ouput of the Shutter Blinds Actuators are independent and the same So Understand only one channel ouput is enough The following paragraph will description of the first channel output in detail 3 1 Database functions Overview The following table provide an overview of the functions and some parameters with the Cuatain actuators Shutter Blinds M W02 10 1 M W04 10 1 M W06 10 1 function General oe Ea Priority on weather alarm Y Y Y Monitoring for weather alarm Y Y Y Enable Diable manual Y Y Y operation Cycle telegram heartbeat Y Y Y Shutter mode Sue wee Move shutter Y Y Y up down Stop moving Y Y Y Limiting travel Y Y Y Move to Y Y Y position 1byte Status response Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 11 46 HDL KNX EIB BUS Shutter Blinds Actuators Status of Y Y Y moving position Status of limit Y Y Y postion Status of auto Y Y Y Status byte Y Y Y Reaction after Y Y Y voltage failure Reaction after Y Y Y voltage recovery Position eae m control Set Y Y Y position 1bit Move to Y Y Y position 1bit Safety control m Wind alarm from Y Y Y bus Rain alarm from Y Y Y bus Frost alarm from Y Y Y bus Forced Y Y Y
2. Delay 0 3600s check when leaving switching to auto2 s Delay 0 3600s check when arriving switching to auto1 s Options 0 3600s Set delay time for presence arriving leaving f a person enters the room and begin to delay when more than Delay 0 3600s check when arriving switching to auto1 s parameter configuration value the shutter blinds will switch to auto1 sun protection If a person leaves the room and begin to delay when more than check when leaving switching to auto2 s parameter configuration value the shutter blinds will switch to auto2 heating cooling control The heating cooling control is used to move to position according to temperature changing For example if have sun sun 1 and want to be heating heating 1 so that increase the quantity of heat of the room and open Shutter Blinds if have no sun sun 0 and want to be cooling cooling 1 so that keep the quantity of heat of the room and close Shutter Blinds Position for heating 1 and sun 1 Position for heating 1 and sun 0 Position for cooling 1 and sun 1 Position for cooling 1 and sun 0 Shutter Blinds move to the corresponding setting position if heat cooling auto is activated But all operation priority is highest auto control so auto control is interrupted if other operation is carried out Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hd
3. Knee Shutter Blinds Actuators Guangzhou Hedong Electronic Co Ltd HDL HDL KNX EIB BUS Shutter Blinds Actuators HDL KNX EIB BUS Product Manual Intelligent Installation Systems Contents 1 General wis sage cgeedoe ee weed ead iis eines rererere nenne 3 1 1 Product FUNCION sorosoro cessed cece Eere EEE EDET FEEFEE Kertoi 4 2 Hardware 3 isnt congue eee nireti t Tren EE ea EEE Ea NA 5 2 1 Fechnical dataseieee 5 2 2 Dimension drawings x s 5 205225 20sedon52esedesasatadanatasadasasatedesasesedess 7 2 3 Wiring diagram ocencscscsciedcieecSidesectGedep ennenen nennen ennnen nnen 8 2 4 Maintenance and Cautions cccccceeeeeeeeeeeeeeeeeeeeeeeeeees 9 3 Softwar eesse 64S y iain by EA ee ee ees 11 3 1 Database functions Overview c ceeeeeeeeeeeeeeeeeeeeeees 11 3 2 Object Association Group address define ccc 14 3 3 Function parameter General ccccccceeeeeeeeeeeeeeeeeeees 14 3 4 Function parameter Channel N eeeeeeeeeeeeeeeees 16 3 5 Channel mode blINdS 2 ccceeeeeeeeeeeeeseseeeeeeeeeeeeees 17 3 5 1Channel function 0 2 eee eee eee 20 3 5 2Channel function position 22 3 5 3Channel function safety 24 3 5 4Channel function Auto1 4 26 3 5 5Channel function Auto2 205 28 3 5 6Channel fu
4. NO Object name Function Flags Data type Ouput N Sun 0 or 1 30 Auto1 CWU DPT 1 002 1bit This communication object is used to recives Sun 0 or 1 signal Only automatic control is activated this communication object receives telegram is valid If this communication object receives a telegram value 0 the Shutter Blinds will move to the setting position Moving for sun 0 after Delay time sun 0 If this communication object receives a telegram value 1 the Shutter Blinds will move to the setting position Moving for sun 1 after Delay time sun 1 4 2 20 Objects Move to position for sun NO Object name Function Flags Data type Ouput N Position 31 Auto1 percentage CWU DPT 5 001 for sun 1byte This communication object is used to move to position when auto is activated The shutter blinds will move to position according to receiving position value 4 2 21 Objects Adjust louvre for sun NO Object name Function Flags Data type Ouput N Louvre 32 Auto1 percentage CWU DPT 5 001 for sun 1byte This communication object is used to move to position when auto is activated The shutter blinds will move to louvre position according to receiving louvre position value Guangzhou Hedong Electronic Co Ltd HDL www hdlichina com www hdichina com cn 38 46 HDL KNX EIB BUS Shutter Blinds Actu
5. store scene 64 If scene assigned 111111 NO 1 64 Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 40 46 HDL KNX EIB BUS Shutter Blinds Actuators 5 Program functions diagram Preset Enable position 1 4 Disable Auto2 for heating co Enable oling Disable Disable Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 41 46 HDL KNX EIB BUS Shutter Blinds Actuators Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 42 46 HDL KNX EIB BUS Shutter Blinds Actuators Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 43 46 HDL KNX EIB BUS Shutter Blinds Actuators Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com www hdichina com cn 44 46 HDL KNX EIB BUS Shutter Blinds Actuators Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 45 46
6. 1 Max number of communication objects 70 130 190 Max number of group addresses 254 254 254 Max number of associations 254 254 254 Note The programming requires the EIB Software Tools ETS2 V1 3 or ETS3 0 or ETS4 If use ETS2 V1 3 then import vd2 If use ETS3 0 then Import vdx If use ETS4 then import vdx or knxprod 2 2 Dimension drawings HDL amp nxiea M W02 10 1 M W04 10 1 M W06 10 1 X 72mm 144mm 216mm Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 7 46 HDL KNX EIB BUS Shutter Blinds Actuators 2 3 Wiring diagram MAW02 10 1 KNX EIB BUS MAWV04 10 1 KNX EIB BUS Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 8 46 HDL KNX EIB BUS Shutter Blinds Actuators DOGDGDOD COOH OO0O00000 MAWO6 10 1 KNX EIB BUS 1 Label area 2 Programming button amp Programming LED 3 KNX EIB Bus Connector 4 Terminal for Load Connection 5 Buttons for Up Down Stop Louvre adjustment 6 Button corresponding LED Note a Dimensions of the space to be provided for each switch b Dimensions and position of the means for supporting and fixing the switch within this space c Minimum clearance between the various parts of the switch and the surrounding parts where fitted d Minimum dimensions of ventilating
7. Blinds will move to up after bus voltage recovery down The Shutter Blinds will move to down after bus voltage recovery stop The Shutter Blinds will stop after bus voltage recovery set position set position or louver value is displayed gt Output position value Options 0 100 Setting to the range of position value gt Output louver value Options 0 100 or invaid Setting the range of louver value 3 5 1 Channel function The following will describe detail the functions parameter setup of the channel Show function page Options No Yes Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 20 46 HDL KNX EIB BUS Shutter Blinds Actuators If set to Yes and channel function page will be showed The function page Include Position control Safety control Auto control and Scene control Details see the following sections E 1 1 14 M W06 10 1 General A function Channel A A function 5 4 Channel B Position function control Disable Channel C n Channel D Safety function control Disable Channel E Channel F Autol function for sun Disable Scene function control Disable i Fig4 Channel function windows In normal case The each channel function is disabled If enabled and the channel function will be valid Position function control If set to Enable and Position function control will be Enable Options Disable Enable Disable disable position f
8. The following functions can be set individually for each output channel 1 Move up down 2 stop louver adjustment 3 Percentage of position control Position Percentag Louvre angle percentage 4 Limit traveling control 5 Status response status position status limit position status automatic status byte 6 Voltage failure save COPADA GAPA BW 7 voltage recovery 8 Position control Move into position preset position 1 4 Set position modification of the preset position via the EIB KNX M W06 10 1 9 Safety control wind alarm rain alarm frost alarm 10 Forced operation 11 Auto control automatic sun protection automatic heating cooling 12 Scence control scene number 1 64 The type of the Shutter Blinds Actuators Description as following M Wx y z M W04 10 1 00000000 x channel number y Current 10A channel z Application Version Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 4 46 HDL KNX EIB BUS Shutter Blinds Actuators 2 Hardware The technical properties of HDL KNX EIB Shutter Blinds Actuators as the following sections 2 1 Technical data Power supply Operating voltage supply by the bus 21 30 V DC Current consumption EIB KNX operate lt 15 mA Current consumption EIB KNX standby lt 5 mA Power consumption EIB KNX operate lt 450 mW Power consumption EIB KNX st
9. a 10 Output A Move blinds up down 1 bit ic Ww u mpe Output 4 Adjust louvre Stop moving 1 bit ol Ww u G40 Output B Move blinds up down 1 bit E w u j4 Output B Adjust louvre Stop moving 1 bit wW u G70 Output C Move blinds up down 1 bit E w u Gari Output C Adjust louvre Stop moving 1 bit w u ER 100 Output D Move blinds up down 1 bit a W u E101 Output D Adjust louvre Stop moving 1 bit gt w u E130 Output E Move blinds up down 1 bit wW u m31 Output E Adjust louvre Stop moving 1 bit E w u E60 Output F Move blinds up down 1 bit w u Eji Output F Adjust louvre Stop moving 1 bit wW u NO Object name Function Flags Data type 0 General Send cycles CRT DPT 1 003 1bit This communication object is always active and valid invert the value send telegram to bus in next frame e g last telegram value is 1 the next telegram value is 0 Weak wind 1 General alarm CWU DPT 1 005 received 1bit Slight wind 2 General alarm CWU DPT 1 005 received 1bit Strong wind 3 General alarm CWU DPT 1 005 received 1bit Rain alarm 4 General received CWU DPT 1 005 1bit Frost alarm 5 General received CWU DPT 1 005 1bit These communication objects are used to receive cyclically telegrams If the object receives a telegram value 1 or doesn t receive telegram within the monitoring Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 31 46 HDL KN
10. cn 13 46 HDL KNX EIB BUS 3 2 Object Association Group address define Shutter Blinds Actuators In following table The objects is assigned to the some function of the channel output pages If active some functions and the object will be valid One or more group addresses can be assigned to a object The association will connect group addresses to the object Name type Max number of Max number Max number communication of of grounp objects associations adress Curtain 2CH M W02 10 1 70 254 254 Actuator Curtain 4CH M W04 10 1 130 254 254 Actuator Curtain 6CH M W06 10 1 190 254 254 Actuator Table2 Overview the max number of the objects max number of associations and max number of the group addresses Note If you use ETS2V 1 3 Please import VD2 But you use the ETS3 0 Please Import VD3 to VD5 3 3 Function parameter General E 1 1 14 M W06 10 1 Channel A Channel B Channel C Channel D Channel E Channel F General Priority on receiving weather alarm from bus 1 Wind gt 2 Rain gt 3 Frost Wind operation for safety Disable Rain operation for safety Disable Frost operation for safety Disable Manual operation device itself buttons Enable Cycle send general telegram 1 65535s 0 invalid 0 OK Cancel Default Fig1 General parameter windows Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com www hdichin
11. eee eee 38 4 2 200bjects Move to position for sun 38 4 2 210bjects Adjust louvre forsun 38 4 2 220bjects Enable Disable remote control 39 4 2 230bjects Presence 2 e0e 39 4 2 240bjects heating 6 eens sence eens 39 4 2 25Objects cooling cesses cr eceseraededed 39 4 2 26Objects Call scene number 40 5 Program functions diagram 0 cee cece neces Al Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 2 46 HDL KNX EIB BUS Shutter Blinds Actuators 1 General HDL KNX EIB series Shutter Blinds Actuators output modules are developed by HDL Using KNX EIB BUS communicate with other KNX devices Database need to be downloaded to the switch actuator by using ETS2 V1 3 ETS 3 0 ETS4 The document descript how to use the products Our products use standard according to EMC electrical safety environmental conditions The curtain Shutter Blinds Actuators are used to control switched loads such as Shutter Blinds Motor Other Equipments The rights and the copyright to this manual are exclusively the property of HDL Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com www hdichina com cn 3 46 HDL KNX EIB BUS Shutter Blinds Actuators 1 1 Product Function 55555555 The Shutter Blinds Actuators can switch for 2 4 and held 6 channels independent AC loads
12. general telegram 1 65535s 0 invalid The range of the parameter is 0 to 65535s Zero of parameter disable the function other of parameter enable this function Options 0 65535s The parameter set to nonzero Device will send a telegram data cyclically when time out Send the value alternately between 0 and 1 3 4 Function parameter Channel N Ml 1 1 14 M WO6 10 1 General Channel A Channa Channel B 5 2 n Channel C Selecting operation mode blinds Channel D oh se Channel E Total moving time from top to bottom 2 600s 30 Channel F lt Delay time when change the direction on 500 moving 50 10000ms Start up time O 255ms 0 Deceleration time 0 255ms 0 ee GD b Wb Alignment after arriving on upper or lower 2000 position 500 10000ms Limit travelling range Disable lt Total of louvre adjustment 100 2000ms 1000 Maximum number of louvre adjustment 1 50 10 Move to position via bus 0 100 Disable Status response No Status on bus voltage failure no reaction Reaction after bus voltage recovery no reaction Show the function page gt gt No OK I Cancel J Default Fig2 Channel N parameter N A B C windows Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 16 46 HDL KNX EIB BUS Shutter Blinds Actuators In the parameter windows of the Channel N can setup some common functions Through functional se
13. opening if needed and their correct arrangement e The protective devices e g fuses automatic protective devices etc to be connected to the load to avoid overloading 2 4 Maintenance and Cautions Please read this user manual carefully before any operation Don t close to the interfering devices The site should be ventilated with good cooling environment Pay attention to damp proof quakeproof and dustproof Avoid rain other liquids or caustic gas Please contact professional maintenance staff or HDL service center for repair or fix Remove the dust regularly and do not wipe the unit with the volatile liquids like alcohol gasoline etc Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 9 46 HDL KNX EIB BUS Shutter Blinds Actuators If damaged by damp or liquid turn off it immediately Regularly check the circuitry and other related circuit or cables and replace the disqualified circuitry on time For security each circuit to connect an MCB or fuse Installation location should be well ventilated pay attention to moisture shock dust proof Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 10 46 HDL KNX EIB BUS Shutter Blinds Actuators 3 Software HDL KNX EIB Shutter Blinds Actuators device types are M W02 10 1 M W04 10 1 and M W06 10 1 and the databases name are Curtain 2CH Actuator Curtain 4CH Actuator
14. status IATA Ouput N of upper pos CRT DPT 1 008 1bit This communication object is used to send status when Shutter Blinds move to upper The Shutter Actuator sends the value 1 to this communication object if the Shutter Blinds reachs the upper limit position The Shutter Actuator sends the value 0 to this communication object if the shutter blind exit the upper limit position Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 34 46 HDL KNX EIB BUS Shutter Blinds Actuators 4 2 7 Objects status of lower pos NO Object name Function Flags Data type Object status 18 Ouput N of lower pos CRT DPT 1 008 1bit This communication object is used to send status when Shutter Blinds move to lower The Shutter Actuator sends the value 1 to this communication object if the shutter blind reachs the lower limit position The Shutter Actuator sends value 0 to this communication object if the shutter blind exit the lower limit position 4 2 8 Objects status of auto NO Object name Function Flags Data type Object status 19 Ouput N of auto CRT DPT 1 011 1bit This communication object is used to send status when auto is activated or deactivated The Shutter Blinds Actuator sends the value 1 to this communication object if automatic control is activated The Shutter Actuator sends the v
15. CWU DPT 1 002 1bit This communication object is used to recive Heating signal Only automatic control is activated if This communication object receives a telegram value 1 Heating is valid 4 2 25 Objects cooling NO Object name Function Flags Data type Cooling 36 Ouput N CWU DPT 1 002 1bit This communication object is used to recive Coolling signal Only automatic Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 39 46 HDL KNX EIB BUS Shutter Blinds Actuators control is activated if This communication object receives a telegram with the value 6b 1 Coolling is valid 4 2 26 Objects Call scene number NO Object name Function Flags Data type Call scene 37 Ouput N number CWU DPT 18 001 1byte followingexplain Telegram value This communication object is used to control the scene The scene control see CIR ININ IN N IN JIN C 0 Call scene switch state R Reserved e g Hexadecimal 1 Store scene If scene assigned and the scene is the current N Scene NO bin 000000 OOh call scene 1 If scene assigned 01h call scene 2 If scene assigned 3Fh call scene 64 If scene assigned 80h store scene 1 If scene assigned 81h store scene 2 If scene assigned BFh
16. X EIB BUS Shutter Blinds Actuators period the Shutter Blinds will move to the setting Reaction on wind rain or frost alarm If the object receives a telegram value 0 within the monitoring period the Shutter Blinds will move to the setting Reaction on wind rain or frost alarm The monitoring period is restarted to count time after the object receiving each telegram Table 3 General object NO Object name Function Flags Data type Move shutter 10 Ouput N up down CWU DPT 1 008 Move blinds 1bit up down This communication object is used to move the Shutter Blinds If the object receives the value 0 the Shutter Blinds will move upwards If the object receives the value 1 the Shutter Blinds will move downwards The Shutter Blinds will stop automatically if arrives on the upper or lower end position Stop moving ag eee Ouput N Adjust CWU DPT 1 007 louvre Stop 1bit moving This communication object is used to stop moving or adjust louver lf the Shutter Blinds is moving the Shutter Blinds is stopped when a telegram is received at this communication object no matter what receives a 1 or a 0 Only in the Blinds mode if Blinds on stopping status and adjust louvre upwards after receiving value 0 or adjust louvre downwards after receiving value 1 In the Shutter mode If Shutter on stopping status and a telegram is received the shutter blinds i
17. a com cn 14 46 HDL KNX EIB BUS Shutter Blinds Actuators Inl the parameter of the general windows can set some common functions Priority on receiving weather alarm from bus Set priority of the weather alarm the selection of parameter configuration has six kinds of combination Options 1 Wind gt 2 Rain gt 3 Frost 1 Wind gt 2 Frost gt 3 Rain 1 Rain gt 2 Wind gt 3 Frost 1 Rain gt 2 Frost gt 3 Wind 1 Frost gt 2 Wind gt 3 Rain 1 Frost gt 2 Rain gt 3 Wind The parameter setting to the weather alarm signal is valid according to priority If the Shutter Blinds Actuator receives more than one weather alarm signal at the same time and only one the highest priority weather signal is valid Wind operation for safety If set to Enable and display Weak wind alarm received Slight wind alarm received Strong wind alarm received and Monitoring wind period 1 2000s 0 invalid Options Disable Enable Weak wind alarm received Slight wind alarm received Strong wind alarm received If set to Enable and the corresponding communication objects is displayed Options Disable Enable Disable disable weak slight strong wind alarm received communication object Enable enable weak slight strong wind alarm received communication object Rain operation for safety Frost operation for safety If set to Enable Monitoring rain period 1 2000s 0 invalid Monitoring frost period 1 2000s 0 i
18. alue 0 to this communication object if automatic control is deactivated 4 2 9 Objects status of forced operation NO Object name Function Flags Data type Object status 20 Ouput N of forced CRT DPT 1 005 alarm 1byte This communication object is used to send status when forced operation is activated or deactivated The Shutter Blinds Actuator sends the value 1 to this communication object if forced operation is activated The Shutter Actuator sends the value 0 to this communication object if forced operation has been deactivated 4 2 10 Objects Set position 1 2 NO Object name Function Flags Data type Set position 21a Ouput N 1 2 CWU DPT 1 022 1bit This communication object is used to set the preset position If this communication object receives a telegram value 0 the current position is saved as the preset Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com www hdichina com cn 35 46 HDL KNX EIB BUS Shutter Blinds Actuators value of the position If this communication object receives value 1 the current position is saved as the preset value of the position2 4 2 11 Objects Set position 3 4 NO Object name Function Flags Data type Set position 22 Ouput N 3 4 CWU DPT 1 022 1bit This communication object is used to set the preset position If
19. andby lt 150 mW Output nominal values Type of Device M W 02 10 1 04 10 1 06 10 1 Number of contacts 2 4 6 In rated current 10A 10A 10A Power loss per device at max load 27W 5 4W 8 W Un rated voltage Output switching currents 250 440V AC 50 60 Hz AC operation cos 0 8 10A 230 V Fluorescent lighting load 10 A 250 V 150 pF Minimum switching capability 0 1mA 1V DC current switching capability ohmic load 10A 12V DC Output life expectancy Mechanical Life gt 1000000 Electrical Life 240 V cos 0 8 gt 100000 Output switching delay without additional DC power Max delay time of relay per position changes charge time of the capacity 02 10 1 04 10 1 06 10 1 100ms 100ms 100ms Connections EIB KNX Bus Connection Terminal 0 8 mm single core crew terminal with Slotted head 0 2 4 mm multi core 0 4 6 mm single core cable shoe 12 mm Tightening torque Max 0 8 Nm Operating and display Red LED and EIB KNX push button all in one For assignment of the physical address Contact position indication Relay lever Load circuits S Guangzhou Hedong Electronic Co Ltd HDL www hdlchina com www hdichina com cn 5 46 HDL KNX EIB BUS Temperature range Operation Storage Transport Environment conditions humidity Appearance design Modular Type M W Dimensions H x W x D Width W unit mm Mounting width 1P 18 mm Mounting depth unit mm We
20. ators 4 2 22 Objects Enable Disable remote control NO Object name Function Flags Data type Enable Disable 33 Ouput N remote control CWU DPT 1 003 1bit This communication object is used to diable remote control If this communication receives a telegram value 1 the Shutter Blinds remote control is disable 4 2 23 Objects Presence NO Object name Function Flags Data type Presence 34 Ouput N check arrive leave C W U DPT 1 002 1bit This communication object is used to recive presence arrive signal or no presence leave signal Only automatic control is activated If the person leaves the room this communication object receive a telegram with the value 0 after Delay 0 3600s check when leaving switching auto2 automaticheating cooling is activated and the Shutter Blinds move to setting position according to the parameterised Position on heating 1 and sun 1 0 or Position on cooling 1 and sun 0 1 If the person enters into the room this communication object receive a telegram value 1 after Delay 0 3600s check when arriving switching to auto1 automaticheating cooling is deactivated automatic sun is activated and the shutter blind move to setting position Moving for sun 0 1 4 2 24 Objects heating NO Object name Function Flags Data type Ouput N 35 Auto2 Heating
21. aximum number of louver adjustment 1 50 The parameter is set only in blinds mode Options 1 50 Setting the maximum number of louver adjustment from 0 0 to 100 255 Move to position via bus 0 100 If set to Enable and move to position and move louvre to position only in Blinds mode communication objects is diplayed The Shutter Blind can be Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 18 46 HDL KNX EIB BUS Shutter Blinds Actuators moved to position and only in blinds mode the louvres also can be adjusted at any angle according to receiving communication objects value Options Disable Enable Disable disable move to position and move louver to position only in blinds mode objects Enable enable move to position and move louver to position only in blinds mode objects Status respond If set to Yes and status parameters configuration is displayed Options No Yes No status respond is not displayed Yes status respond is displayed gt Send position 0 100 The Curtain Actuator sends status value according to current position and louvre position value But only in blinds mode louvre position status communication object is displayed and send Options Disable Enable Disable disable current position louver position communication object Enable enable current position louver position communication object gt Send limit position
22. blinds move to preset position when this communication object receive a telegram with the value 1bit Options Disable Enable Disable disable move to position 1bit communication object Enable enable move to position 1bit communication object Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 23 46 HDL KNX EIB BUS Shutter Blinds Actuators 3 5 3Channel function safety E 1 1 14 M W06 10 1 General A safety Channel A amp function The weak wind alarm is used No Channel B Channel C The slight wind alarm is used No Channel D Channel E The strong wind alarm is used No Channel F Reaction on wind alarm the wind signal come from us no reaction Reaction on rain alarm the rain signal come from bus no reaction Reaction on frost alarm the frost signal come from bus no reaction Forced operation 1 2 bit Disable Forced operation 2 1 bit Disable Forced operation 3 1 bit Disable Reaction on exit forced operation no reaction OK Cancel Default Fig9 Safety function windows The weak wind alarm is used The slight wind alarm is used The strong wind alarm is used If set to Yes the corresponding communication object is valid Options No Yes No weak slight strong wind alarm signal is not used Yes weak slight strong wind alarm signal is used Reaction on wind alarm the wind signal come from bus Reaction on rain alarm the rain si
23. escription detailed of the Blinds mode Total moving time from top to bottom s Options 2 600s Set the total moving time when Shutter Blinds from top to buttom Delay time when chang direction on moving ms Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdlchina com cn 17 46 HDL KNX EIB BUS Shutter Blinds Actuators Options 50 10 000ms Set delay time when Shutter Blinds change in direction on moving so that up or down is not immediately changed when Shutter Blinds is moving Start up time ms Options 0 255ms Setting the start up time of the drive Deceleration time ms Options 0 255ms Setting the deceleration time of the drive Alignment after arriving on upper or lower position ms Set the time when Shutter Blinds continue to move up or down after arriving upper or lower Limit travelling range If select to Enable and set the range of shutter blinds travel Options Disable Enable Disable disable Upper Lower limit setting and limit tarvellin communication object Enable enable Upper Lower limit setting and limit tarvelling communication object Upper limit 0 100 Lower limit 0 100 Set Upper limit or Lower limit parameterized value Total of louver adjustment 100 2000ms The parameter is set only in the Blinds mode Options 100 2000ms Setting complete louver adjustment time from 0 0 to 100 255 M
24. g position and otrher operation is diable If this communication object receives a telegram value 0 binary 00 the shutter blind will move to the Position on reset of forced operation position and other operation re enabled 4 2 17 Objects Forced operation3 NO Object name Function Flags Data type Ouput N Forced 28 Safety operation3 CWU DPT 1 001 1bit This communication object is used to force operation If this communication object receives a telegram value 1 binary 01 the shutter blind will move to the setting position and otrher operation is diable If this communication object receives a telegram value 0 binary 00 the shutter blind will move to the Position on reset of forced operation position and other operation re enabled Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 37 46 HDL KNX EIB BUS Shutter Blinds Actuators 4 2 18 Objects Activation of auto control NO Object name Function Flags Data type Activation of 29 Ouput N auto control CWU DPT 1 011 1bit This communication object is used to activate weather alarm If this communication object receives the value 1 the auto control is activated If this communication object receives a telegram with the value O the weather alarm is deactivated 4 2 19 Objects Sun 0 or 1
25. gnal come from bus Reaction on frost alarm the frost signal come from bus Setting the Shutrer Blinds reaction whith this parameter Wind alarm rain alarm and frost alarm is interrupted if remote control such as up down or Stop Louver adjustment manual operation or forced operation is operated Options no reaction up down stop only set louver position only in blinds mode no reaction the Shutter Blinds is on rection when receive wind rain frost signal up the Shutter Blinds move to up when receive wind rain frost signal down the shutter blinds move to down when receive wind rain frost signal Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 24 46 HDL KNX EIB BUS Shutter Blinds Actuators stop the Shutter Blinds stop when receive wind rain frost signal only set louver position can set the shutter blinds adjustment louvre position Remote control include the following content 1 Move up down 2 Stop Louver adjustment 3 Move to position 1byte Move louver to position only in the Blinds mode 4 Limit traveling control 5 Move to position one bit preset position 1 4 6 Set position modification of the preset position via the EIB KNX 7 Scence control gt Output louver value Options 0 100 Set to the range of louver value Forced operation 1 2 bit If set to Enable the corresponding communication object can receive 2bit and control the Shutter Blinds up do
26. he telegram must 0 The scene is stored by receive a value of telegram from the bus which the value of the telegram bit 0 6 equal a scene number The scene state is the current shutter blinds position state The bit seven of value of the telegram must 1 Scene assignment scene 1 64 or no assignment Options no assignment Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 29 46 HDL KNX EIB BUS Shutter Blinds Actuators Scene NO 01 Scene NO 02 Scene NO 64 The scene number is between 1 and 64 the value is between 0 and 63 no assignment Output position value Options 0 0 100 255 The range of output position value can be set 0 0 100 255 Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 30 46 HDL KNX EIB BUS Shutter Blinds Actuators 4 Communication objects description In this section will introduce the communication objects The objects will show by setting the function enable Note In following sections the N A B C 4 1 Objects General and Output N Number Name Object Function Description Group Addresses Length C R W T U Go General Send cycles 1 bit cR T Gi General Weak wind alarm received 1 bit G W u G2 General Slight wind alarm received 1 bit wW u m mk General Strong wind alarm received 1 bit w u a4 General Rain alarm received 1 bit ret Ww u Gas General Frost alarm received 1 bit w u
27. ichina com cn 28 46 HDL KNX EIB BUS Shutter Blinds Actuators Options no reaction up down stop Position 1 to Position 4 no reaction the shutter blinds is no reaction when heating cooling and sun nosun up the shutter blinds move to up when heating cooling and sun nosun down the shutter blinds move to up when heating cooling and sun no sun stop the shutter blinds stop when heating cooling and sun nosun Position 1 to Position 4 the shutter blinds move to preset position when heating cooling and sun nosun 3 5 6 Channel function Scene E 1 1 14 M W06 10 1 General A scene Channel A amp function Scene assignment 1 No assignment Channel B Channel C gt gt Dutput position value 1 00 255 J Channel D Channel E Scene assignment 2 No assignment Channel F gt gt Output position value 100 255 Scene assignment 3 No assignment gt gt Output position value 100 255 Scene assignment 4 No assignment gt gt Output position value 100 255 Scene assignment 5 No assignment gt gt Output position value 100 255 Scene assignment 6 No assignment gt gt Dutput position value 100 255 3 OK Cancel Default Fig9 scene function windows In each channel it has 10 scenes can be stored Each scene can be set to 0 to100 The scene is called by receive a value of telegram from the bus which the value of the telegram bit 0 6 equal a scene number The bit seven of value of t
28. ight unit kg Installation Mounting position Material and Colour Standard and Safety LVD Standard EMC Standard CE mark Shutter Blinds Actuators 5 C 45 C 25 C 55 C 25 C 70 C max 95 Non condensing DIN Rail Modular installation 02 10 1 04 10 1 06 10 1 90 x W x 64 72 144 216 4P 8P 12P 64 64 64 0 26 0 49 0 72 Use 35 mm mounting rail Electric switch box Plastic grey Certificated EN60669 2 1 EN60669 1 EN50090 2 2 In accordance with the EMC guideline and low voltage guideline Pollutant Note All of loads at 230 V AC Motors Lamps Incandescent lamp load Low volt halogen lamps Inductive transformer Electronic transformer Halogen lamp Mercury vapour lamp Uncompensated luminaire Parallel compensated Fluorescent lamp T5 T8 Uncompensated luminaire Parallel compensated DUO lamp Dulux lamp Uncompensated luminaire Parallel compensated Switching performance contact Max peak inrush current Ip 120 us Max peak inrush current Ip 240 us Guangzhou Hedong Electronic Co Ltd HDL Comply with RoHS 4HP 3500W 1800 W 2000 W 230 V 3500 W 2800 W 2800 W 3500 W 2000 W 2000 W 1500 W 1500 W 600 A 480 A www hdichina com www hdichina com cn 6 46 HDL KNX EIB BUS Shutter Blinds Actuators Max peak inrush current Ip 480 us 300 A Max peak inrush current Ip 1000 us 170A Application table Type M W 02 10 1 M W 04 10 1 M W 06 10
29. is interrupted if other operation is carried out Options no reaction up down stop Position 1 to Position 4 Receive percentage value 8bits no reaction the shutter blinds is no reaction when have no sun up the Shutter Blinds move to up when have no sun down the Shutter Blinds move to down when have no sun stop the Shutter Blinds stop when have no sun Position 1 to Position 4 the shutter blinds move to preset position when have no sun Receive percentage value 8bits the Shutter Blinds react according to receiving value Delay for sun 0 s Delay for sun 1 s Options 0 3600s Setting delay time sun 0 or sun 1 after reciving a telegram value and avoid shutter blinds move immediately Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 27 46 HDL KNX EIB BUS 3 5 5Channel function Auto2 E 1 1 14 M W06 10 1 General Channel A amp function amp autol Channel B Channel C Channel D Channel E Channel F Shutter Blinds Actuators A auto2 Delay 0 3600s check when leaving switching to auto2 Delay 0 3600s check when arriving switching to autol Position on heating 1 and sun 0 Position on heating 1 and sun 1 Position on cooling 1 and sun 0 Position on cooling 1 and sun 1 0 0 no reaction no reaction no reaction no reaction OK Cancel Default f Fig9 Auto2 function windows
30. lection and download the database to the device and device will work in accordance with the selected function Selecting operation mode The function of operation mode can be selected with two parameters Options Shutter Blinds Shutter selecting shutter mode Blinds selecting blinds mode The function of Shutter and Blinds mode is similar only in Blinds mode increase a few parameters and communication objects about louvre control If unstand the function of blinds and the function of shutter is naturally unstand 3 5 Channel mode blinds E 1 1 14 M WO6 10 1 General Channel A Channel Channel B Channel C Selecting operation mode Channel D Channel E Total moving time from top to bottom 2 600s 30 C Channel F Delay time when change the direction on 500 moving 50 10000ms Start up time 0 255ms 0 Deceleration time 0 255ms 0 cs Op b C Ge Alignment after arriving on upper or lower 2000 position 500 10000ms Limit travelling range Disable me Total of louvre adjustment 100 2000ms 1000 Maximum number of louvre adjustment 1 50 Move to position via bus 0 100 Status response Status on bus voltage failure Reaction after bus voltage recovery Show the function page gt gt 10 Disable No no reaction no reaction No OK Cancel Default Fig3 Cuatain Actuator windows More functions setup in this mode the following section will d
31. mote control enable Channel B Channel C Moving for sun 0 no reaction Channel D Channel E Moving for sun 1 no reaction Channel F Delay time sun 0 0 3600s 0 Delay time sun 1 0 3600s lo OK Cancel Default f Fig9 Auto1 function windows Toggling to remote control Setting to remote enable control or enable disable remote control with communication object Options enable communication object enable disable enable enable remote control communication object enable disable enable disable remote control whith communication object Moving for sun 0 no sun Moving for sun 1 sun Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 26 46 HDL KNX EIB BUS Shutter Blinds Actuators If the Sun 0 or 1 communication object receive a telegram with the value 0 the Shutter Blinds is moved to position according to setting of parameter Moving for sun 0 If the Sun 0 or 1 communication object receive a telegram with the value 1 the shutter blinds is moved to position according to setting of parameter Moving for sun 1 If set to Receive percentage value 8bits and the Shutter Blinds move to position or adjust louver position accoordinng to receipt value of 8bit objects But adjust louver position only in the Blinds mode All operation priority is highest auto control so auto control
32. moving 0 top 100 bottom gt Position3 for louvre 0 opened 100 closed Position4 for moving 0 top 100 bottom Position4 for louvre 0 opened 100 closed invali Set pasition 1 bit Disable Move to pasition 1 bit Disable OK Cancel Default Fig5 Time function windows The position function as following Preset position 1 4 If set to Enable the following parameter is displayed Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 22 46 HDL KNX EIB BUS Shutter Blinds Actuators Options Disable Enable Disable disable preset position setting Enable enable preset position setting gt Position1 for moving 0 top 100 bottom gt Position1 for louvre 0 opened 100 closed only in blinds mode Position2 for moving 0 top 100 bottom Position2 for louvre 0 opened 100 closed only in blinds mode gt Position3 for moving 0 top 100 bottom gt Position3 for louvre 0 opened 100 closed only in blinds mode Position4 for moving 0 top 100 bottom Position4 for louvre 0 opened 100 closed only in blinds mode The preset position is set with this parameter Set position 1 bit The preset position is update with a 1bit telegram Options Disable Enable Disable disable set position communication object Enable enable set position communication object Move to position 1 bit The shutter
33. nction Scene 0000585 29 4 Communication objects description 005 31 4 1 Objects General and Output N ece 31 4 2 All objects with channel N 2 eeeeeeeeeeeeeeee eee 33 4 2 1Objects limit travelling 085 33 4 2 2Objects Move to position 33 4 2 3Objects Move louver to position 34 4 2 4Objects status of position 34 4 2 5Objects status of louvre position 34 4 2 6Objects status of upper pos 34 4 2 7Objects status of lower pos 35 4 2 8Objects status of auto 00 35 4 2 9Objects status of forced operation 35 4 2 10Objects Set position 1 2 35 4 2 11Objects Set position 3 4 36 4 2 12Objects Move to position 1 2 36 4 2 130bjects Move to position 3 4 36 4 2 14Q0bjects Activation of weather alarm 36 Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 1 46 HDL KNX EIB BUS Shutter Blinds Actuators 4 2 150bjects Forced operation1 37 4 2 16Objects Forced operation1 37 4 2 17Objects Forced operation3 37 4 2 18Objects Activation of auto control 38 4 2 19Objects Sun 0 or 1 2 2
34. nvalid and the corresponding communication objects is displayed Options Disable Enable Disable disable Monitoring rain frost period setting and rain frost wind received communication object Enable enable Monitoring rain frost period setting and rain frost wind received communication object Monitoring wind period 1 2000s 0 invalid Monitoring rain period 1 2000s 0 invalid Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 15 46 HDL KNX EIB BUS Shutter Blinds Actuators Monitoring frost period 1 2000s 0 invalid The range of cyclical monitoring period is 0 to 2000s Zero of parameter is invalid Options 0 2 000s The weather sensors sends telegram which is cyclically monitored by the Shutter Blinds Actuator If the weather alarm signal is not received within the monitoring period by the Shutter Blinds Actuator the curtain move to the setting alarm position If weather sensors send a weather alarm signal and the Shutter Blinds Actuator receive the signal then the Shutter Blinds immediated move to the seting alarm position The monitoring period is restarted to time after receipt of a telegram The monitoring period of the Shutter Blinds Actuator is set that is at least two to three times as long as the cyclical sending time of the weather sensor so that do not receive the signal and Shutter Blinds immediately move to the seting alarm position Cycle send
35. o Ltd HDL www hdichina com www hdichina com cn 33 46 HDL KNX EIB BUS 4 2 3 Objects Move louver to position Shutter Blinds Actuators NO Object name Function Flags Data type Move louvre 14 Ouput N to position CWU DPT 5 001 1byte This communication object is used to move to any louvre position according to receiving value The range of telegram value is 0 0 to 255 100 the open is 0 and close is 255 Only if the Shutter Blinds stop status and adjusting louvre position is valid 4 2 4 Objects status of position NO Object name Function Flags Data type Object status 15 Ouput N of position CRT DPT 5 001 1byte This communication object is used to send position status when Shutter Blinds position is changed lf the current position of the Shutter Blinds is changed and stopped and send the current position of the Shutter Blinds to this communication object 4 2 5 Objects status of louvre position NO Object name Function Flags Data type Object status 16 Ouput N of louvre pos CRT DPT 5 001 1byte This communication object is used to send position status when Shutter Blinds louver position is changed the current position of the louvre is send to this communication object by the Shutter Blinds Actuator 4 2 6 Objects status of upper pos NO Object name Function Flags Data type Object
36. operation Auto control 2a Auto1 function Y Y Y for sun Auto2 function Y Y Y for heating cooling Scene control i te Scene NO 1 64 Y Y Y Blinds mode me Move blinds Y Y Y up down Stop moving Louvre Y Y Y adjustment Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 12 46 HDL KNX EIB BUS Shutter Blinds Actuators Limiting travel Y Y Y Move to Y Y Y position 1 byte Status response e Status of Y Y Y moving position Status of louvre Y Y Y position Status of limit Y Y Y position Status of auto Y Y Y Status byte Y Y Y Reaction after Y Y Y voltage failure Reaction after Y Y Y voltage recovery Position control Set Y Y Y position 1bit Move to Y Y Y position 1bit Safety control Wind alarm from Y Y Y bus Rain alarm from Y Y Y bus Frost alarm from Y Y Y bus Forced operation Auto control Auto1 function Y Y Y for sun Auto2 function Y Y Y for heating cooling Scene control Scene NO 1 64 Y Y Y Table1 Database application overview Note For each function and mode can only be used alone but Louvre Adjustment function can be used with blinds actuator mode Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com
37. put 4 Safety Forced operation2 1 bit Gos W u Eze Output 4 Safety Forced operation3 1 bit ce W u jz Output 4 Activation of auto control 1 bit C W u G30 Output 4 Autol Sun 0 or 1 1 bit Coe W u 31 Output 4 Autol Position percentage for sun 1Byte C Ww u sz Output 4 Autol Louvre percentage For sun 1Byte C Ww u Gass Output A Enable Disable remote control 1 bit C W u E34 Output A Presence check arrive leave 1 bit C W u Gass Output 4 Auto Heating 1 bit Cis Ww u G36 Output 4 Auto2 Cooling 1 bit C W u E37 Output 4 Call scene number 1Byte C W u 4 2 1 Objects limit travelling NO Object name Function Flags Data type Limit 12 Ouput N travelling CWU DPT 1 008 1bit This communication object is used to limit the range of Shutter Blinds travel If the object receives a telegram value 0 the Shutter Blinds will move upwards If the object receives a telegram value 1 the Shutter Blinds will move downwards The Shutter Blinds will stop automatically if receives the setting upper or lower limit position 4 2 2 Objects Move to position NO Object Function Flags Data type name Move to 13 Ouput N position 0 100 CWU DPT 5 001 1byte This communication object is used to move to any position according to receiving value The range of telegram value is 0 0 to 255 100 the top vale is O and buttom is 255 Guangzhou Hedong Electronic C
38. reached The Curtain Actuator sends status after shutter blinds arriving upper or lower Options Disable Enable Disable disable limit position status communication Enable enable limit position status communication gt Send status of automatic control If automatic control is activated or deactivated and the Curtain Actuator sends present status Options Disable Enable Disable disable automatic control status communication object Enable enable automatic control status communication object gt Send status of forced operation alarm If forced operation is activated or deactivated and the Shutter Blinds Actuator sends present status Options Disable Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 19 46 HDL KNX EIB BUS Shutter Blinds Actuators Enable Disable disable forced operation status communication object Enable enable forced operation status communication object Status on bus voltage failure Set the Shutter Blinds reaction after bus voltage failure Options no reaction up down stop up The Shutter Blinds will move to up after bus voltage failure down The Shutter Blinds will move to down after bus voltage failure stop The Shutter Blinds will stop after bus voltage failure Reaction after bus voltage recovery Setting to The Shutter Blinds react after bus voltage recovery Options no reaction up down stop set position up The Shutter
39. s no reaction Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 32 46 HDL KNX EIB BUS Shutter Blinds Actuators 4 2 All objects with channel N Number Name Object Function Description Group Addresses Length C R W T U Geo General Send cycles 1 bit CARRS Sara Eji General Weak wind alarm received 1 bit es Ws y Ez General Slight wind alarm received 1 bit G Wo sry mmk General Strong wind alarm received 1 bit C wo u j4 General Rain alarm received 1 bit Gos A IU Gas General Frost alarm received 1 bit Gos Woe Y E 10 Output A Move blinds up down 1 bit Ge We wu mi Output A Adjust louvre Stop moving 1 bit Gos Woa U G12 Output amp Limit travelling ibt C w uU E 13 Output 4 Move to position O 100 1Byte C wW u E 14 Output 4 Move louvre to position 1Byte C wo u E 15 Output 4 Object status of position 1Byte C R T Eie Output A Object status of louvre pos 1Byte C R T E7 Output A Object status of upper pos 1 bit C R T Gis Output A Object status of lower pos 1 bit GR Tt E 19 Output 4 Object status of auto 1 bit CR lt T E20 Output A Object status of forced alarm 1 bit GR oot G21 Output 4 Set position 1 2 1 bit Gos wo u E22 Output 4 Set position 3 4 1 bit wW u E23 Output Move to position 1 2 1 bit c W u E24 Output A Move to position 3 4 1 bit C W u G25 Output Activation of weather alarm 1 bit C W u Gaze Output 4 Safety Forced operation1 2 bit C W u E27 Out
40. this communication object receives a telegram value 0 the current position is saved as the preset value of the position3 If this communication object receives value 1 the current position is saved as the preset value of the position4 4 2 12 Objects Move to position 1 2 NO Object name Function Flags Data type Move to 23 Ouput N position 1 2 CWU DPT 1 022 1bit This communication object is used to move to the preset position lIf this communication object receives a telegram the shutter blind will move to the preset position If the value 0 is received the shutter blind will move to position If the value 1 is received the shutter blind will move to position2 4 2 13 Objects Move to position 3 4 NO Object name Function Flags Data type Move to 24 Ouput N position 3 4 CWU DPT 1 022 1bit This communication object is used to move to the preset position If this communication object receives a telegram the shutter blind will move to the preset position If the value O is received the shutter blind will move to position3 If the value 1 is received the shutter blind will move to position 4 4 2 14 Objects Activation of weather alarm NO Object name Function Flags Data type Activation of 25 Ouput N weather CWU DPT 1 011 alarm 1bit This communication object is used to acti
41. unction Enable enable position function Safety function control If set to Enable and Safety function control will be Enable Options Disable Enable Disable disable safety control function Enable enable safety control function Auto1 function for sun If set to Enable and Auto1 function will be Enable Auto2 function for heating cooling is displayed at the time Options Disable Enable Guangzhou Hedong Electronic Co Ltd HDL www hdlichina com www hdichina com cn 21 46 HDL KNX EIB BUS Shutter Blinds Actuators Disable disable auto control function Enable enable auto control function gt Auto2 function for heating cooling If set to Enable and Auto2 function will be Enable Options Disable Enable Disable disable auto2 control function Enable enable auto2 control function Scene function control If set to Enable and Scene function will be Enable Options Disable Enable Disable disable scene control function Enable enable scene control function 3 5 2Channel function position E 1 1 14 M W06 10 1 General A position Channel A amp function Preset position 1 4 Enable Channel B a Channel C gt Position1 for moving 0 top 100 bottom 0 0 Channel D Channel E gt Position1 for louvre 0 opened 100 closed invali Channel F Position2 for moving 0 top 100 bottom Position2 for louvre 0 opened 100 closed gt Position3 for
42. vate weather alarm If this communication object receives a telegram value 1 the weather alarm is activated If this Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 36 46 HDL KNX EIB BUS Shutter Blinds Actuators communication object receives a telegram value 0 the weather alarm is deactivated 4 2 15 Objects Forced operation1 NO Object name Function Flags Data type Ouput N Forced 26 Safety operation CWU DPT 2 008 2bit This communication object is used to force operation If this communication object receives a telegram value 2 binary 10 the shutter blind is up and other operation is diable If this communication object receives a telegram value 3 binary 11 the shutter blind is down and otrher operation is diable If this communication object receives a telegram value 0 binary 00 or value 1 binary 01 the shutter blind will move to the Position on reset of forced operation position and other operation re enabled 4 2 16 Objects Forced operation1 NO Object name Function Flags Data type Ouput N Forced 27 Safety operation2 CWU DPT 1 001 1bit This communication object is used to force operation lf this communication object receives a telegram value 1 binary 01 the shutter blind will move to the settin
43. wn All operation is interrupped if forced operaton is operated Options Disable Enable Disable disable foced operation communication object Enable enable foced operation communication object Forced operation 2 1 bit Forced operation 3 1 bit If set to Enable the corresponding communication object can receive 1 bit and control the Shutter Blinds with parameter value All operation is interrupped if forced operaton is operated Options Disable Enable Disable disable forced position setting and foced operation communication object Enable forced position setting and enable foced operation communication object Reaction on exit forced operation Seting the Shutter Blinds reaction when forced operation is exit and other operation will be able to operate Options no reaction Guangzhou Hedong Electronic Co Ltd HDL www hdichina com www hdichina com cn 25 46 HDL KNX EIB BUS Shutter Blinds Actuators up down stop Last position no reaction the Shutter Blinds is no reaction when exit forced operation up the Shutter Blinds move to up when exit forced operation down the Shutter Blinds move to down when exit forced operation stop the Shutter Blinds stop when exit forced operation Last position the Shutter Blinds move to last position when exit forced operation 3 5 4Channel function Auto1 E 1 1 14 M W06 10 1 General A autol Channel A amp function Toggling to re